Attachment J: Modifications to
Altered Facilities
1. The City will make the following modifications to Andrew Currie Recreation Center located at 1800 Norma Street, within 18 months of the effective date of this Agreement:
A. Directional Signage: There is no signage at the inaccessible entrances directing people with disabilities to the accessible entrance. Provide accessible directional signage with the International Symbol of Accessibility at the inaccessible entrances indicating the location of the nearest accessible entrance, and provide accessible signage with the International Symbol of Accessibility at all accessible entrances. Standards §§ 4.1.2(7)(d), 4.1.6(3)(e)(iii), 4.30.1, 4.30.2, 4.30.3, 4.30.5, 4.30.
B. Interior Signage: The permanent room signage provided lacks raised and Braille characters, and it is not mounted on the latch side of the doors. Provide permanent room signage with upper case, sans serif or simple serif type letters and numerals, meeting the requirements of the Standards for character height, raised characters, finish and contrast, accompanied by Grade 2 Braille; mounted on the wall adjacent to the latch side of the door or on the nearest adjacent wall at a height of 60 inches above the finished floor to the centerline of the sign; and located so that a person may approach within 3 inches of the signage without encountering protruding objects or standing within the swing of a door. Standards §§ 4.1.2(7), 4.1.6(1)(b), 4.30.1, 4.30.4, 4.30.5, 4.30.6.
C. Drinking Fountain: Although an accessible drinking fountain is provided, there is no drinking fountain provided for people who have difficulty bending or stooping. Provide a drinking fountain that is accessible to people who have difficulty bending or stooping. This can be accommodated by the use of a "hi-lo" fountain; by providing one fountain accessible to those who use wheelchairs and one fountain at a standard height convenient for those who have difficulty bending; by providing a fountain accessible to people who use wheelchairs and a cup dispenser, or by such other means as would achieve the required accessibility for each group of people. Standards §§ 4.1.3(10)(a), 4.1.6(1)(b).
D. Men's Toilet Room (Altered element; alterations standard applies)
i. The soap dispenser controls are mounted at 63 inches above the finished floor over the lavatory. Provide a soap dispenser such that the controls comply with Fig. 5 for a forward reach or with Fig. 6 for a side reach and such that it is accompanied by clear floor space of 30 by 48 inches that allows a forward or parallel approach, respectively, by a person using a wheelchair. Standards §§ 4.1.3(13), 4.1.6(1)(b), 4.27.2, 4.27.3, 4.2.4, 4.2.5, 4.2.6.
ii. There is no toilet stall for wheelchair users provided. Provide a "standard" accessible toilet stall at least 60 inches wide and at least 59 inches deep (or at least 56 inches deep with a wall-mounted toilet) such that all of the stall's elements, including stall door, stall door hardware, water closet, size and arrangement, toe clearances, grab bars, controls, and dispensers, comply with the Standards. Standards §§ 4.1.3(11), 4.1.6(1)(b), 4.22.4, 4.22.7, 4.13, 4.16, 4.17, 4.26, 4.27, Fig. 30.
E. Women's Toilet Room (Altered element; alterations standard applies)
i. There is no toilet stall provided. Provide a "standard" accessible toilet stall at least 60 inches wide and at least 59 inches deep (or at least 56 inches deep with a wall-mounted toilet) such that all of the stall's elements, including stall door, stall door hardware, water closet, size and arrangement, toe clearances, grab bars, controls, and dispensers, comply with the Standards. Standards §§ 4.1.3(11), 4.1.6(1)(b), 4.22.4, 4.22.7, 4.13, 4.16, 4.17, 4.26, 4.27, Fig. 30.
2. The City may soon determine whether it will alter or permanently close the City Hall Annex located at 1237 Murphy Street. If during the life of this Agreement the City permanently closes the Annex, this provision becomes moot upon notification to the Department. However, if the City does not permanently close the Annex and opens it to the public, the City will make the following modifications, within three years of the effective date of this Agreement:
A. Parking - East Parking Lot
i. The van accessible parking space reserved for persons with disabilities in the east parking lot lacks the required signage. At the van accessible space, provide a "Van-Accessible" sign located below the International Symbol of Accessibility such that the sign cannot be obstructed by vehicles parked in the space. Standards §§ 4.1.2(5), 4.1.6(1)(b), 4.6.4, 4.30.7(1).
ii. Although the east parking lot has a total of 167 parking spaces, an inadequate number are designated as reserved for people with disabilities. On the shortest accessible route to the accessible entrance, provide a total of six accessible spaces (one van accessible and five standard accessible spaces) designated as reserved for people with disabilities. Standard accessible spaces shall be a minimum of 96 inches wide and served by access aisles at least 60 inches wide. Van accessible spaces shall be a minimum of 96 inches wide and served by access aisles at least 96 inches wide. All spaces designated as reserved for people with disabilities shall have vertical signs with the International Symbol of Accessibility located such that they cannot be obstructed by parked vehicles. Van accessible spaces shall have an additional "Van-Accessible" sign located below the International Symbol of Accessibility. Standards §§ 4.1.2(5), 4.1.6(1)(b), 4.6, 4.30.7(1).
B. Accessible Route: The route from the designated accessible parking in the east parking lot to the main entrance and ramp is not level and lacks a curb cut. Provide at least one accessible route within the boundary of the site connecting these elements that, to the maximum extent feasible, coincides with the route for the general public. The accessible route must have a minimum clear width of 36 inches, or a minimum clear width of 42 inches if there is a turn around an obstruction less than 48 inches wide; have passing spaces at least 60 inches by 60 inches at least every 200 feet; have a minimum clear headroom of 80 inches; have a surface that is firm, stable, and slip resistant; have, in the absence of a curb ramp, ramp, elevator, or platform lift, no level changes in excess of ½ inch vertically; and have a running slope of less than 1:20 (5%) (or have been constructed as a fully accessible ramp) and a cross slope of less than 1:50 (2%). Standards §§ 4.1.3(1), 4.1.6(1)(b), 4.3, 4.5, Fig. 7.
C. Directional Signage
i. There is no signage at inaccessible entrances directing people with disabilities to the accessible entrances. Provide accessible directional signage with the International Symbol of Accessibility at the inaccessible entrances indicating the location of the nearest accessible entrance, and provide accessible signage with the International Symbol of Accessibility at all accessible entrances. Standards §§ 4.1.2(7)(d), 4.1.6(3)(e)(iii), 4.30.1, 4.30.2, 4.30.3, 4.30.5, 4.30.
ii. There is no signage directing people with disabilities to the accessible unisex single-user toilet room. Provide accessible directional signage with the International Symbol of Accessibility at inaccessible toilet rooms indicating the location of the nearest accessible toilet room, and provide accessible signage with the International Symbol of Accessibility at all accessible toilet rooms. Standards §§ 4.1.2(7)(d), 4.1.6(3)(e)(iii), 4.30.1, 4.30.2, 4.30.3, 4.30.5, 4.30.7.
D. Exterior Ramp: The front entrance ramp lacks one handrail and an extension at the top of the ramp. Provide handrails that are between 1¼ inches and 1½ inches in diameter such that the inside handrail is continuous and both handrails have a continuous gripping surface along both sides of the ramp extending at least 12 inches beyond the top and bottom of the ramp parallel with the ground surface; the handrails do not rotate within their fittings; and both handrails are mounted between 34 inches and 38 inches above the ramp surface, with ends rounded or returned smoothly to the floor, wall, or post. Standards §§ 4.1.2(1), 4.1.2(2), 4.1.6(1)(b), 4.3.8, 4.8.5.
E. Interior Signage: No accessible permanent room signage has been provided. Provide permanent room signage with upper case, sans serif or simple serif type letters and numerals, meeting the requirements of the Standards for character height, raised characters, finish and contrast, accompanied by Grade 2 Braille; mounted on the wall adjacent to the latch side of the door or on the nearest adjacent wall at a height of 60 inches above the finished floor to the centerline of the sign; and located so that a person may approach within 3 inches of the signage without encountering protruding objects or standing within the swing of a door. Standards §§ 4.1.2(7), 4.1.6(1)(b), 4.30.1, 4.30.4, 4.30.5, 4.30.6.
F. Code Enforcement Office
i. The pressure required to open the entrance door is 10 pounds. Provide a door that requires no more than 5 pounds of force to open. Standards §§ 4.1.3(7)(b), 4.1.6(1)(b), 4.13.11(2)(b).
ii. The top of the reception counter is 42 inches above the finished floor. Provide a counter on an accessible route such that a portion of the counter is at least 36 inches wide and no more than 36 inches above the finished floor, or provide an auxiliary counter with a maximum height of 36 inches in close proximity to the main counter, or provide equivalent facilitation. Equivalent facilitation may be provided in the form of a folding shelf attached to the main counter, an auxiliary table nearby, a clip board made available to the public, or other means. Standards §§ 4.1.1(2), 4.1.6(1)(b), 7.2(2), 4.1.3(1), 4.3.
G. Internal Affairs Bureau
i. The entrance door uses knob hardware and requires tight grasping and twisting of the wrist to operate. Provide a door with hardware that is easy to grasp with one hand and that does not require tight grasping, pinching, or twisting of the wrist to operate. Lever-operated mechanisms, push-type mechanisms, and U-shaped handles are acceptable designs. Standards §§ 4.1.3(7)(b), 4.1.6(1)(b), 4.13.9.
ii. The entrance door, which is accessed through a front approach, has only 8 inches of latch side maneuvering clearance on the pull side of the door. On the pull side of the door, provide maneuvering clearance at least 60 inches deep and provide a minimum of 18 inches (24 inches is preferred) of maneuvering clearance on the latch side of the door. Standards §§ 4.1.3(7)(b), 4.13.6, Fig. 25(a).
H. Elevator
i. The elevator call buttons are centered at 53 ½ inches above the finished floor and lack visual signals. Provide hall call buttons with visual signals indicating when each call is registered and when each call is answered. Provide call buttons that are centered at 42 inches above the finished floor, a minimum of ¾ inch in the smallest dimension, with the button designating the up direction on top; that the call buttons are raised or flush; and that objects mounted beneath hall call buttons do not project into the elevator lobby more than 4 inches. Standards §§ 4.1.3(5), 4.1.6(1)(b), 4.10.3, Fig. 20.
ii. No hall lanterns have been provided at the elevator. Provide hall lanterns at each hoistway entrance that emit a visible and audible signal indicating which car is answering a call. Provide audible signals that sound once for the up direction and twice for the down direction or have verbal annunciators that say "up" or "down;" and that visible signals are mounted so that their centerline is at least 72 inches above the lobby floor, they are at least 2½ inches in the smallest dimension, and they are visible from the vicinity of the hall call button. Lanterns located in cars, visible from the vicinity of hall call buttons, and conforming to the above requirements, are acceptable. Standards §§ 4.1.3(5), 4.1.6(1)(b), 4.10.4, Fig. 20.
iii. The elevator doors do not remain open for 20 seconds after they have been obstructed. Provide doors that open and close automatically with a reopening device that will stop and reopen the car door and hoistway door automatically if the door becomes obstructed by an object or person. Provide a device that is capable of completing these operations without requiring contact for obstructions passing through the opening at heights of 5 inches and 29 inches above the finished floor; that door reopening devices remain effective for at least 20 seconds, after which the doors may close; that the minimum time from notification that a car is answering a call until the doors of that car start to close is 5 seconds; and that the minimum time for elevator doors to remain fully open in response to a car call is 3 seconds. Standards §§ 4.1.3(5), 4.1.6(1)(b), 4.10.6, 4.10.7, 4.10.8, Figs. 20, 21.
iv. The elevator car control buttons are not raised or flush, they lack visual indicators, and the emergency controls are grouped at the top of the panel. Provide car control buttons that are at least ¾ inch in their smallest dimension and are raised or flush and that are designated by Braille and by raised standard alphabet characters for letters, arabic characters for numerals, or standard symbols. Provide a call button for the main entry floor is designated by a raised star at the left of the floor designation; that all raised designations for control buttons are placed immediately to the left of the buttons to which they apply; that floor buttons are provided with visual indicators to show when each call is registered and are extinguished when each call is answered; that all floor buttons are no higher than 54 inches above the finished floor for a side approach and no more than 48 inches above the finished floor for a front approach; and that emergency controls, including the emergency alarm and emergency stop, are grouped at the bottom of the panel and have their centerlines no less than 35 inches above the finished floor. Standards §§ 4.1.3(5), 4.1.6(1)(b), 4.10.12, Fig. 23.
v. The elevator car position indicators lack audible signals. Provide visual car position indicators above the car control panel or over the door to show the position of the elevator in the hoistway. Provide indicators that emit an audible and visual signal as the car passes or stops at a floor served by the elevator, with the corresponding floor designation being illuminated; and that numerals are a minimum of ½ inch high. Standards §§ 4.1.3(5), 4.1.6(1)(b), 4.10.13.
vi. Although emergency communications are provided, the elevator emergency communication controls are greater than 48 inches above the finished floor, they lack identification by a raised symbol and lettering, and the system is inoperable without voice communication. Provide a two-way communication system such that it does not require voice communication, the highest operable part is a maximum of 48 inches above the finished floor of the car, and it is identified by a raised symbol and lettering located adjacent to the device. If the system uses a handset, ensure that the length of the cord from the panel to the handset is at least 29 inches. If the system is located in a closed compartment, provide compartment door hardware that operates without tight grasping, pinching or twisting of the wrist. Standards §§ 4.1.3(5), 4.1.6(1)(b), 4.10.14.
I. Unisex Single-User Toilet Room (Altered element)
i. The toilet room sign lacks raised and Braille characters and is mounted on the door. Provide a toilet room sign with the International Symbol of Accessibility and raised and Braille characters. The sign shall be mounted on the wall adjacent to the latch side of the door with the centerline of the sign at 60 inches above the finished floor and situated such that a person can approach within 3 inches of the sign without encountering an obstruction or standing within a door swing. Standards §§ 4.1.2(7)(d), 4.1.6(1)(b), 4.30.1, 4.30.4, 4.30.5, 4.30.6, 4.30.7.
ii. The pressure required to open the entrance door is 11 pounds. Provide a door that requires no more than 5 pounds of force to open. Standards §§ 4.1.3(7)(b), 4.1.6(1)(b), 4.13.11(2)(b).
iii. No accessible mirror has been provided. Provide a mirror with the bottom edge of its reflecting surface no more than 40 inches above the finished floor. Standards §§ 4.1.3(11), 4.1.6(1)(b), 4.22.6, 4.19.6.
iv. The hot water pipes under the lavatory are not insulated or otherwise configured to protect against contact. Provide hot water and drain pipes that are insulated or otherwise configured to protect against contact. Standards §§ 4.1.3(11), 4.1.6(1)(b), 4.22.6, 4.19.4.
v. The urinal rim is 22 inches above the finished floor and its flush control is 51 inches above the finished floor. Provide a urinal with an elongated rim mounted 17 inches or less above the finished floor, a clear floor space of at least 30 inches wide and 48 inches deep centered on the urinal, and a flush control height of 44 inches or less above the finished floor. Standards §§ 4.1.3(11), 4.1.6(1)(b), 4.22.5, 4.18.2, 4.18.3, 4.18.4.
vi. The toilet paper dispenser is 45 inches from the rear wall. Provide a toilet paper dispenser that is mounted within reach, with its top at least 1½ inches under the side grab bar, and centered at least 19 inches above the finished floor. Standards §§ 4.1.3(11), 4.1.6(1)(b), 4.22.4, 4.16.6, Fig. 29(b).
vii. The top of the toilet seat is only 15 ½ inches above the finished floor. Provide a toilet with a seat that measures 17 to 19 inches above the finished floor. Standards §§ 4.1.3(11), 4.1.6(1)(b), 4.22.4, 4.16.3, Fig. 29(b).
viii. No rear grab bar has been provided. Provide a rear grab bar that is at least 36 inches in overall length, with the closer end no more than 6 inches from the side wall; mounted 33 to 36 inches above the finished floor; with a diameter between 1¼ and 1½ inches; with 1½ inches between the grab bar and the wall; and at least 1½ inches between the grab bar and any other object, such as a toilet seat cover dispenser. Standards §§ 4.1.3(11), 4.1.6(1)(b), 4.22.4, 4.16.4, 4.26.2, Fig. 29.
J. Drinking Fountains
i. The floor-mounted drinking fountain in the lobby lacks the required knee and toe clearance. Provide a drinking fountain with clear knee space between the bottom of the apron and the finished floor or ground of at least 27 inches high, 30 inches wide, and 17 to 19 inches deep; and a minimum clear floor space of 30 inches by 48 inches to allow a person in a wheelchair to approach the unit facing forward. Although an accessible drinking fountain is provided at this location, there is no drinking fountain provided for people who have difficulty bending or stooping. Provide a drinking fountain that is accessible to people who have difficulty bending or stooping. This can be accommodated by the use of a "hi-lo" fountain; by providing one fountain accessible to those who use wheelchairs and one fountain at a standard height convenient for those who have difficulty bending; by providing a fountain accessible to people who use wheelchairs and a cup dispenser, or by such other means as would achieve the required accessibility for each group of people. Standards §§ 4.1.3(10), 4.1.6(1)(b), 4.15.5(1), 4.2.4, Figs. 27(a), (b).
ii. The wall-mounted drinking fountain near the unisex single-user toilet room is inaccessible because it lacks knee and toe clearance. Provide a drinking fountain with clear knee space between the bottom of the apron and the finished floor or ground of at least 27 inches high, 30 inches wide, and 17 to 19 inches deep; and a minimum clear floor space of 30 inches by 48 inches to allow a person in a wheelchair to approach the unit facing forward. Standards §§ 4.1.3(10), 4.1.6(1)(b), 4.15.5(1), Figs. 27(a), (b).
3. The City will make the following modifications to Festival Plaza - Revel Offices located atCrockett and Commerce Streets, within six months of the effective date of this Agreement:
A. Unisex Single-User Toilet Room
i. The pressure required to open the entrance door is 15 pounds. Provide a door that requires no more than 5 pounds of force to open. Standards §§ 4.1.3(7)(b), 4.1.6(1)(b), 4.13.11(2)(b).
ii. No accessible mirror has been provided. Provide a mirror with the bottom edge of its reflecting surface no more than 40 inches above the finished floor. Standards §§ 4.1.3(11), 4.1.6(1)(b), 4.22.6, 4.19.6.
iii. The paper towel dispenser controls are mounted at 60 inches above the finished floor. Provide a paper towel dispenser with the controls a maximum height above the finished floor of 48 inches for a forward approach or 54 inches for a side approach and that is accompanied by clear floor space of 30 by 48 inches that allows a forward or parallel approach by a person using a wheelchair. Standards §§ 4.1.3(13), 4.1.6(1)(b), 4.27.2, 4.27.3, 4.2.4, 4.2.5, 4.2.6.
iv. The coat rack protrudes into the required clear floor space at the lavatory. Provide a lavatory with clear floor space at least 30 inches wide and 48 inches deep centered on the lavatory. Standards §§ 4.1.3(11), 4.1.6(1)(b), 4.22.6, 4.19.3, Fig. 32.
v. The toilet flush control is on the closed side. Provide a flush control mounted on the "open" side of the toilet's clear floor space; 44 inches or less above the finished floor; and requiring a maximum of 5 pounds of force to operate; or provide an automatic flush device. Standards §§ 4.1.3(11), 4.1.6(1)(b), 4.22.4, 4.16.5, 4.27.4.
4. The City will make the following modifications to Fire Investigation located at1700 Snow Street, within one year of the effective date of this Agreement:
A. Main Entrance
i. The main entrance door, which is accessed through a front approach, has only 10 inches of latch side maneuvering clearance on the pull side of the door. On the pull side of the door, provide maneuvering clearance at least 60 inches deep and provide a minimum of 18 inches (24 inches is preferred) of maneuvering clearance on the latch side of the door. Standards §§ 4.1.3(7)(b), 4.1.6(1)(b), 4.13.6, Fig. 25(a).
ii. The main entrance door, which is accessed through a front approach and which has both a closer and a latch, only 10 inches of latch side maneuvering clearance on the push side of the door. On the push side of the door, provide maneuvering clearance at least 48 inches deep and provide a minimum of 12 inches of maneuvering clearance on the latch side of the door, or remove the closer or the latch. Standards §§ 4.1.3(7)(b), 4.1.6(1)(b), 4.13.6, Fig. 25(a).
B. Unisex Single-User Toilet Room
i. The toilet room sign is mounted on the door. Provide a toilet room sign mounted on the wall adjacent to the latch side of the door with the centerline of the sign at 60 inches above the finished floor and situated such that a person can approach within 3 inches of the sign without encountering an obstruction or standing within a door swing. Standards §§ 4.1.2(7)(d), 4.1.6(1)(b), 4.30.1, 4.30.4, 4.30.5, 4.30.6, 4.30.7.
ii. The lavatory apron is 27 inches above the finished floor. Provide a lavatory with the top of its rim or counter 34 inches or less above the finished floor; the bottom edge of the apron at least 29 inches above the finished floor; and knee and toe clearances that comply with Fig. 31. Standards §§ 4.1.3(11), 4.1.6(1)(b), 4.22.6, 4.19.2, Fig. 31.
iii. The rear grab bar at the toilet is mounted 38 inches above the finished floor. Provide a rear grab bar that is mounted between 33 and 36 inches above the finished floor. Standards §§ 4.1.3(11), 4.1.6(1)(b), 4.22.4, 4.16.4, Fig. 29.
6. The City will make the following modifications to Fire and Police Training Academy located at 6400 Greenwood Road, within 18 months of the effective date of this Agreement:
A. Parking: Although the parking lot has a total of 27 parking spaces, none are designated as van accessible. On the shortest accessible route to the accessible entrance, provide at least one van accessible space a minimum of 96 inches wide, served by an access aisle at least 96 inches wide, with a vertical sign with the International Symbol of Accessibility located such that they cannot be obstructed by parked vehicles, and with an additional "Van-Accessible" sign located below the International Symbol of Accessibility. Standards §§ 4.1.2(5)(b), 4.1.6(1)(b), 4.6, 4.30.7(1).
B. Interior Doors: Most of the interior doors throughout the facility use knob hardware that requires tight grasping or twisting of the wrist to operate. Provide doors with hardware that is easy to grasp with one hand and that does not require tight grasping, pinching, or twisting of the wrist to operate. Lever-operated mechanisms, push-type mechanisms, and U-shaped handles are acceptable designs. Standards §§ 4.1.3(7)(b), 4.1.6(1)(b), 4.13.9.
C. Curb Ramps
i. The built-up curb ramp located on the Fire Training side of the parking lot impermissibly extends into the parking space's access aisle. Provide a curb ramp located so that it does not project into this element and all aspects of the ramp or curb cut comply with the Standards. Standards §§ 4.1.2(1), 4.1.2(2), 4.1.6(1)(b), 4.3.8, 4.7.6.
ii. The built-up curb ramp located near the main entrance lacks flared sides.Provide a curb ramp that has flared sides with the maximum slope of each flare being 1:10. Standards §§ 4.1.2(1), 4.1.2(2), 4.1.6(1)(b), 4.3.8, 4.7, Fig. 13.
D. Reception Counter: The reception counter is 42 inches above the finished floor. Provide a counter on an accessible route such that a portion of the counter is at least 36 inches wide and no more than 36 inches above the finished floor, or provide an auxiliary counter with a maximum height of 36 inches in close proximity to the main counter, or provide equivalent facilitation. Equivalent facilitation may be provided in the form of a folding shelf attached to the main counter, an auxiliary table nearby, a clip board made available to the public, or other means. Standards §§ 4.1.1(2), 4.1.6(1)(b), 7.2(2), 4.1.3(1), 4.3.
E. Drinking Fountains
i. The wall mounted drinking fountain in the center hallway has a spout that is 43 inches above the finished floor. Provide a fountain that has a spout height no higher than 36 inches, measured from the finished floor or ground surface to the spout outlet, with clear knee space between the bottom of the apron and the finished floor or ground of at least 27 inches high, 30 inches wide, and 17 to 19 inches deep; and a minimum clear floor space of 30 inches by 48 inches to allow a person in a wheelchair to approach the unit facing forward. Standards §§ 4.1.3(10), 4.1.6(1)(b), 4.15, 4.27.4, Fig. 27.
ii. Although an accessible drinking fountain is provided in the police wing, there is no drinking fountain provided for people who have difficulty bending or stooping. Provide a drinking fountain that is accessible to people who have difficulty bending or stooping. This can be accommodated by the use of a "hi-lo" fountain; by providing one fountain accessible to those who use wheelchairs and one fountain at a standard height convenient for those who have difficulty bending; by providing a fountain accessible to people who use wheelchairs and a cup dispenser, or by such other means as would achieve the required accessibility for each group of people. Standards §§ 4.1.3(10)(a), 4.1.6(1)(b).
F. Auditorium (Altered element; alterations standard applies): Although there are 50 or more fixed seats in the auditorium, there is no assistive listening system. Provide a permanently installed assistive listening system serving the fixed seating. Provide seating that is served by the system and is located within a 50 foot viewing distance of the stage or playing area and has a complete view of the stage or playing area. Provide a minimum of 8 receivers for use by the general public and signage indicating their availability. 28 C.F.R. § 35.160; Standards §§ 4.1.3(19)(b), 4.1.6(1)(b), 4.30, 4.33.
G. Women's Toilet Room - Auditorium (Altered element)
i. The toilet room sign is mounted on the door. Provide a toilet room sign mounted on the wall adjacent to the latch side of the door with the centerline of the sign at 60 inches above the finished floor and situated such that a person can approach within 3 inches of the sign without encountering an obstruction or standing within a door swing. Standards §§ 4.1.2(7)(d), 4.1.6(1)(b), 4.30.1, 4.30.4, 4.30.5, 4.30.6, 4.30.7.
ii. The pressure required to open the entrance door is 25 pounds. Provide a door that requires no more than 5 pounds of force to open. Standards §§ 4.1.3(7)(b), 4.1.6(1)(b), 4.13.11(2)(b).
iii. The paper towel dispenser controls are mounted at 56 inches above the finished floor. Provide a paper towel dispenser with the controls a maximum height above the finished floor of 48 inches for a forward approach or 54 inches for a side approach and that is accompanied by clear floor space of 30 by 48 inches that allows a forward or parallel approach by a person using a wheelchair. Standards §§ 4.1.3(13), 4.1.6(1)(b), 4.27.2, 4.27.3, 4.2.4, 4.2.5, 4.2.6.
iv. No accessible coat hook has been provided. Provide a coat hook at a maximum height above the finished floor of 48 inches for a forward approach or 54 inches for a side approach and that is accompanied by clear floor space of 30 by 48 inches that allows a forward or parallel approach by a person using a wheelchair. Standards §§ 4.1.3(12)(a), 4.1.6(1)(b), 4.25.2, 4.25.3, 4.2.4, 4.2.5, 4.2.6.
H. Men's Toilet Room - Auditorium (Altered element)
i. The toilet room sign is mounted on the door. Provide a toilet room sign mounted on the wall adjacent to the latch side of the door with the centerline of the sign at 60 inches above the finished floor and situated such that a person can approach within 3 inches of the sign without encountering an obstruction or standing within a door swing. Standards §§ 4.1.2(7)(d), 4.1.6(1)(b), 4.30.1, 4.30.4, 4.30.5, 4.30.6, 4.30.7.
ii. The required to open the entrance door is 25 pounds. Provide a door that requires no more than 5 pounds of force to open. Standards §§ 4.1.3(7)(b), 4.1.6(1)(b), 4.13.11(2)(b).
iii. The paper towel dispenser controls are mounted at 56 inches above the finished floor. Provide a paper towel dispenser with the controls a maximum height above the finished floor of 48 inches for a forward approach or 54 inches for a side approach and that is accompanied by clear floor space of 30 by 48 inches that allows a forward or parallel approach by a person using a wheelchair. Standards §§ 4.1.3(13), 4.1.6(1)(b), 4.27.2, 4.27.3, 4.2.4, 4.2.5, 4.2.6.
iv. No accessible coat hook has been provided. Provide a coat hook at a maximum height above the finished floor of 48 inches for a forward approach or 54 inches for a side approach and that is accompanied by clear floor space of 30 by 48 inches that allows a forward or parallel approach by a person using a wheelchair. Standards §§ 4.1.3(12)(a), 4.1.6(1)(b), 4.25.2, 4.25.3, 4.2.4, 4.2.5, 4.2.6.
I. Women's Toilet Room and Showers - Center Hallway (Existing element)
i. No accessible toilet room sign has been provided. Provide a toilet room sign with the International Symbol of Accessibility and raised and Braille characters mounted on the wall adjacent to the latch side of the door with the centerline of the sign 60 inches above the finished floor and situated such that a person can approach within 3 inches of the sign without encountering an obstruction or standing within a door swing. Standards §§ 4.1.2(7)(d), 4.30.1, 4.30.4, 4.30.5, 4.30.6, 4.30.7.
ii. The pressure required to open the entrance door is 17 pounds. Provide a door that requires no more than 5 pounds of force to open. Standards § 4.13.11(2)(b).
iii. The paper towel dispenser controls are mounted at 71 inches above the finished floor. Provide a paper towel dispenser with the controls a maximum height above the finished floor of 48 inches for a forward approach or 54 inches for a side approach and that is accompanied by clear floor space of 30 by 48 inches that allows a forward or parallel approach by a person using a wheelchair. Standards §§ 4.27.2, 4.27.3, 4.2.4, 4.2.5, 4.2.6.
iv. The lavatory lacks knee and toe clearance. Provide a lavatory with the top of its rim or counter 34 inches or less above the finished floor; the bottom edge of the apron at least 29 inches above the finished floor; and knee and toe clearances that comply with Fig. 31. Standards § 4.19.2, Fig. 31.
v. The lavatory hardware requires twisting of the wrist to operate. Provide a lavatory with a faucet that can be operated with 5 pounds of force or less and can be used with one hand and without tight grasping, pinching, or twisting of the wrist (lever-operated, push-type, and electronically controlled mechanisms are examples of acceptable designs). Standards §§ 4.19.5, 4.27.4.
vi. There is no toilet stall for wheelchair users provided. Provide a "standard" accessible toilet stall at least 60 inches wide and at least 59 inches deep (or at least 56 inches deep with a wall-mounted toilet) such that all of the stall's elements, including stall door, stall door hardware, water closet, size and arrangement, toe clearances, grab bars, controls, and dispensers, comply with the Standards. Standards §§ 4.13, 4.16, 4.17, 4.26, 4.27, Fig. 30.
vii. No accessible shower has been provided. Provide a shower in this room that is exactly 36 inches wide and 36 inches deep with a 48 inch long and 36 inch wide clear floor space alongside the shower opening, and an L-shaped shower seat mounted on the wall opposite the controls and extending the full depth of the stall; OR a shower that is at least 30 inches deep and 60 inches wide with no curb or threshold and with a 36 inch deep and 60 inch wide clear floor space at the shower opening. Ensure that the shower has grab bars, controls, a shower spray unit, and a seat, curb, and enclosure, if provided, that comply fully with the Standards and with Figs. 35, 36, and 37, as applicable. Standards § 4.21, Figs. 35, 36, 37.
viii. The dressing room bench is only 9 inches wide and is not fixed to the wall. Provide a 24 inch by 48 inch bench fixed to the wall along the bench's longer dimension. Ensure that the bench has sufficient structural strength and is mounted with its surface between 17 inches and 19 inches above the finished floor. Provide clear floor space alongside the bench to allow a person using a wheelchair to make a parallel transfer onto the bench. Standards §§ 4.35.4, 4.26.3.
J. Men's Toilet Room - Center Hallway
i. No accessible toilet room sign has been provided. Provide a toilet room sign with the International Symbol of Accessibility and raised and Braille characters mounted on the wall adjacent to the latch side of the door with the centerline of the sign 60 inches above the finished floor and situated such that a person can approach within 3 inches of the sign without encountering an obstruction or standing within a door swing. Standards §§ 4.1.2(7)(d), 4.30.1, 4.30.4, 4.30.5, 4.30.6, 4.30.7.
ii. The pressure required to open the entrance door is 20 pounds. Provide a door that requires no more than 5 pounds of force to open. Standards § 4.13.11(2)(b).
iii. The paper towel dispenser controls are mounted at 71 inches above the finished floor. Provide a paper towel dispenser with the controls a maximum height above the finished floor of 48 inches for a forward approach or 54 inches for a side approach and that is accompanied by clear floor space of 30 by 48 inches that allows a forward or parallel approach by a person using a wheelchair. Standards §§ 4.27.2, 4.27.3, 4.2.4, 4.2.5, 4.2.6.
iv. The lavatory lacks knee and toe clearance. Provide a lavatory with the top of its rim or counter 34 inches or less above the finished floor; the bottom edge of the apron at least 29 inches above the finished floor; and knee and toe clearances that comply with Fig. 31. Standards § 4.19.2, Fig. 31.
v. The lavatory hardware requires twisting of the wrist to operate. Provide a lavatory with a faucet that can be operated with 5 pounds of force or less and can be used with one hand and without tight grasping, pinching, or twisting of the wrist (lever-operated, push-type, and electronically controlled mechanisms are examples of acceptable designs). Standards §§ 4.19.5, 4.27.4.
vi. The urinal rim is 24 inches above the finished floor and its flush control is 53 inches above the finished floor. Provide a urinal with an elongated rim mounted 17 inches or less above the finished floor, a clear floor space of at least 30 inches wide and 48 inches deep centered on the urinal, and a flush control height of 44 inches or less above the finished floor. Standards §§ 4.18.2, 4.18.3, 4.18.4.
vii. There is no toilet stall for wheelchair users provided. Provide a "standard" accessible toilet stall at least 60 inches wide and at least 59 inches deep (or at least 56 inches deep with a wall-mounted toilet) such that all of the stall's elements, including stall door, stall door hardware, water closet, size and arrangement, toe clearances, grab bars, controls, and dispensers, comply with the Standards. Standards §§ 4.13, 4.16, 4.17, 4.26, 4.27, Fig. 30.
viii. The dressing room bench is only 9 inches wide and is not fixed to the wall. Provide a 24 inch by 48 inch bench fixed to the wall along the bench's longer dimension. Ensure that the bench has sufficient structural strength and is mounted with its surface between 17 inches and 19 inches above the finished floor. Provide clear floor space alongside the bench to allow a person using a wheelchair to make a parallel transfer onto the bench. Standards §§ 4.35.4, 4.26.3.
K. Unisex Single-User Toilet Room - Police Wing
i. The toilet room sign is mounted on the door. Provide a toilet room sign with the International Symbol of Accessibility and raised and Braille characters. The sign shall be mounted on the wall adjacent to the latch side of the door with the centerline of the sign at 60 inches above the finished floor and situated such that a person can approach within 3 inches of the sign without encountering an obstruction or standing within a door swing. Standards §§ 4.1.2(7)(d), 4.1.6(1)(b), 4.30.1, 4.30.4, 4.30.5, 4.30.6, 4.30.7.
ii. The pressure required to open the entrance door is 25 pounds. Provide a door that requires no more than 5 pounds of force to open. Standards §§ 4.1.3(7)(b), 4.1.6(1)(b), 4.13.11(2)(b).
iii. The toilet room door swings into the required clear floor space at the lavatory. Ensure that no door swings into the required clear floor space at any accessible fixture. Standards §§ 4.1.3(11), 4.1.6(1)(b), 4.22.2.
7. The City will make the following modifications to Government Plaza located at 505 Travis Street, within one year of the effective date of this Agreement:
A. Public Telephone
i. The lower telephone on the first floor is inaccessible because its highest operable part is 57 inches above the finished floor, it lacks volume control and signage, and the counter is mounted at 36 inches above the finished floor. Provide an accessible telephone with a clear floor space of at least 30 inches by 48 inches that allows either a forward or parallel approach by a person using a wheelchair such that bases, enclosures, and fixed seats do not impede approaches to the telephone; with the highest operable part of the telephone mounted no more than 48 inches above the floor for a front approach or no more than 54 inches above the floor for a side approach; that is hearing aid compatible and has a volume control mechanism; with telephone books, if provided, located between 15 and 48 inches above the finished floor for a front approach or between 9 and 54 inches above the finished floor for a side approach; with a cord of at least 29 inches long from the telephone to the handset; and with signage that complies with the Standards. Standards §§ 4.1.3(17), 4.1.6(1)(b), 4.31, 4.30.7(2).
ii. Although there are two public telephones provided, a TTY is not provided. Provide at least one accessible public TTY with the required signage. Standards §§ 4.1.3(17)(c), 4.1.6(1)(b), 4.30.7(3), 4.31.9.
B. Government Chamber: The chamber room, containing 153 seats, lacks the required number of wheelchair seating locations. Provide at least four wheelchair seating locations, with a minimum clear ground or floor space of 66 inches wide by 48 inches deep for forward or rear access, or 66 inches wide by 60 inches deep for side access. Provide a ground or floor at all wheelchair locations that is level, firm, stable, and slip resistant; that wheelchair seating areas are an integral part of the fixed seating plan and are located so as to provide people with physical disabilities a choice of lines of sight comparable to those available for members of the general public; that wheelchair seating areas adjoin an accessible route that also serves as a means of egress in case of emergency; and that at least one fixed companion seat is provided next to each wheelchair seating area. Standards §§ 4.1.3(19)(a), 4.1.6(1)(b), 4.5, 4.33.
C. Interior Signage: No accessible permanent room signage has been provided. Provide permanent room signage with upper case, sans serif or simple serif type letters and numerals, meeting the requirements of the Standards for character height, raised characters, finish and contrast, accompanied by Grade 2 Braille; mounted on the wall adjacent to the latch side of the door or on the nearest adjacent wall at a height of 60 inches above the finished floor to the centerline of the sign; and located so that a person may approach within 3 inches of the signage without encountering protruding objects or standing within the swing of a door. Standards §§ 4.1.2(7), 4.1.6(1)(b), 4.30.1, 4.30.4, 4.30.5, 4.30.6.
D. Permit Office - Suite 130
i. The pressure required to open the entrance door is 10 pounds. Provide a door that requires no more than 5 pounds of force to open. Standards §§ 4.1.3(7)(b), 4.1.6(1)(b), 4.13.11(2)(b).
ii. The entrance door has knob hardware. Provide a door with hardware that is easy to grasp with one hand and that does not require tight grasping, pinching, or twisting of the wrist to operate. Lever-operated mechanisms, push-type mechanisms, and U-shaped handles are acceptable designs. Standards §§ 4.1.3(7)(b), 4.1.6(1)(b), 4.13.9.
iii. The reception counter is 42 inches above the finished floor. Provide a counter on an accessible route such that a portion of the counter is at least 36 inches wide and no more than 36 inches above the finished floor, or provide an auxiliary counter with a maximum height of 36 inches in close proximity to the main counter, or provide equivalent facilitation. Equivalent facilitation may be provided in the form of a folding shelf attached to the main counter, an auxiliary table nearby, a clip board made available to the public, or other means. Standards §§ 4.1.1(2), 4.1.6(1)(b), 7.2(2), 4.1.3(1), 4.3.
E. Metropolitan Planning Commission/Zoning Enforcement - Suite 440: The reception counter is greater than 36 inches above the finished floor. Provide a counter on an accessible route such that a portion of the counter is at least 36 inches wide and no more than 36 inches above the finished floor, or provide an auxiliary counter with a maximum height of 36 inches in close proximity to the main counter, or provide equivalent facilitation. Equivalent facilitation may be provided in the form of a folding shelf attached to the main counter, an auxiliary table nearby, a clip board made available to the public, or other means. Standards §§ 4.1.1(2), 4.1.6(1)(b), 7.2(2), 4.1.3(1), 4.3.
F. Fire Prevention - Suite 510: The entrance door has knob hardware that requires tight grasping and twisting of the wrist to operate. Provide a door with hardware that is easy to grasp with one hand and that does not require tight grasping, pinching, or twisting of the wrist to operate. Lever-operated mechanisms, push-type mechanisms, and U-shaped handles are acceptable designs. Standards §§ 4.1.3(7)(b), 4.1.6(1)(b), 4.13.9.
G. Department of Operational Services - Suite 580: The entrance door has knob hardware that requires tight grasping and twisting of the wrist to operate. Provide a door with hardware that is easy to grasp with one hand and that does not require tight grasping, pinching, or twisting of the wrist to operate. Lever-operated mechanisms, push-type mechanisms, and U-shaped handles are acceptable designs. Standards §§ 4.1.3(7)(b), 4.1.6(1)(b), 4.13.9.
H. Drinking Fountains
i. The wall-mounted drinking fountain on the first floor has only 21 inches of knee clearance. Provide a drinking fountain with clear knee space between the bottom of the apron and the finished floor or ground of at least 27 inches high, 30 inches wide, and 17 to 19 inches deep; and a minimum clear floor space of 30 inches by 48 inches to allow a person in a wheelchair to approach the unit facing forward. Standards §§ 4.1.3(10), 4.1.6(1)(b), 4.15.5(1), Figs. 27(a), (b).
ii. Although an accessible drinking fountain is provided on the first floor, there is no drinking fountain provided for people who have difficulty bending or stooping. Provide a drinking fountain that is accessible to people who have difficulty bending or stooping. This can be accommodated by the use of a "hi-lo" fountain; by providing one fountain accessible to those who use wheelchairs and one fountain at a standard height convenient for those who have difficulty bending; by providing a fountain accessible to people who use wheelchairs and a cup dispenser, or by such other means as would achieve the required accessibility for each group of people. Standards §§ 4.1.3(10)(a), 4.1.6(1)(b).
I. Elevator
i. The elevator doors remain open for 1 second after they have been obstructed. Provide doors that open and close automatically with a reopening device that will stop and reopen the car door and hoistway door automatically if the door becomes obstructed by an object or person. Provide a device that is capable of completing these operations without requiring contact for obstructions passing through the opening at heights of 5 inches and 29 inches above the finished floor; that door reopening devices remain effective for at least 20 seconds, after which the doors may close; that the minimum time from notification that a car is answering a call until the doors of that car start to close is 5 seconds; and that the minimum time for elevator doors to remain fully open in response to a car call is 3 seconds. Standards §§ 4.1.3(5), 4.1.6(1)(b), 4.10.6, 4.10.7, 4.10.8, Figs. 20, 21.
ii. The elevator car position indicators lack audible signals. Provide visual car position indicators above the car control panel or over the door to show the position of the elevator in the hoistway. Provide indicators that emit an audible and visual signal as the car passes or stops at a floor served by the elevator, with the corresponding floor designation being illuminated; and that numerals are a minimum of ½ inch high. Standards §§ 4.1.3(5), 4.1.6(1)(b), 4.10.13.
iii. Although emergency communications are provided in the elevator, the system does not work without voice communication. Provide a two-way communication system such that it does not require voice communication, the highest operable part is a maximum of 48 inches above the finished floor of the car, and it is identified by a raised symbol and lettering located adjacent to the device. If the system uses a handset, ensure that the length of the cord from the panel to the handset is at least 29 inches. If the system is located in a closed compartment, ensure that the compartment door hardware operates without tight grasping, pinching or twisting of the wrist. Standards §§ 4.1.3(5), 4.1.6(1)(b), 4.10.14.
J. Toilet Rooms (Existing elements)
i. Both the men's and women's toilet rooms with stalls located on the first floor contain a number of inaccessible elements. Provide an accessible toilet room for each gender such that all of the room's elements, including signage, door, door hardware, clear floor space, water closet, stall size and arrangement, stall door, urinal (if provided), grab bars, lavatory, mirror, controls, and dispensers, comply with the Standards. Alternatively, provide at least one unisex, single-user toilet room such that all of the room's elements, including signage, door, door hardware, clear floor space, water closet, urinal (if provided), grab bars, lavatory, mirror, controls, and dispensers, comply with the Standards. Standards §§ 4.13, 4.16, 4.17, 4.18, 4.19, 4.26, 4.27, 4.30, Figs. 28, 29, 30. 1
ii. Provide accessible directional signage with the International Symbol of Accessibility at inaccessible toilet rooms indicating the location of the nearest accessible toilet room, and provide accessible signage with the International Symbol of Accessibility at all accessible toilet rooms. Standards §§ 4.1.2(7)(d), 4.1.6(3)(e)(iii), 4.30.1, 4.30.2, 4.30.3, 4.30.5, 4.30.7.
8. The City will make the following modifications to Independence Stadium located at 3301 Pershing Boulevard, within one year of the effective date of this Agreement:
A. Parking
i. Red Lot: Two out of the eight parking spaces reserved for persons with disabilities do not have access aisles. At each standard accessible space, provide an access aisle at least 60 inches wide. At each van accessible space, provide an access aisles at least 96 inches wide. Provide access aisles that are flat and level, with slopes and cross-slopes not exceeding 1:50 in all directions, and that their surfaces are firm, stable, and slip-resistant. Standards §§ 4.1.2(5), 4.1.6(1)(b), 4.6.3, Fig. 9.
ii. Silver Lot
(1) There are no access aisles at the spaces designated as reserved for persons with disabilities. At each standard accessible space, provide an access aisle at least 60 inches wide. At each van accessible space, provide an access aisles at least 96 inches wide. Provide access aisles that are flat and level, with slopes and cross-slopes not exceeding 1:50 in all directions, and that their surfaces are firm, stable, and slip-resistant. Standards §§ 4.1.2(5), 4.1.6(1)(b), 4.6.3, Fig. 9.
(2) Although the parking lot has a total of 270 parking spaces, none are designated as van accessible. On the shortest accessible route to the accessible entrance, provide at least three van accessible spaces a minimum of 96 inches wide, served by access aisles at least 96 inches wide, with vertical signs with the International Symbol of Accessibility located such that they cannot be obstructed by parked vehicles, and with an additional "Van-Accessible" sign located below the International Symbol of Accessibility. Standards §§ 4.1.2(5)(b), 4.1.6(1)(b), 4.6, 4.30.7(1).
B. Drinking Fountains
i. Level 1 East: Although five accessible drinking fountains are provided, there are no drinking fountains provided for people who have difficulty bending or stooping. Provide at least five drinking fountains that are accessible to people who have difficulty bending or stooping. This can be accommodated by the use of a "hi-lo" fountain; by providing one fountain accessible to those who use wheelchairs and one fountain at a standard height convenient for those who have difficulty bending; by providing a fountain accessible to people who use wheelchairs and a cup dispenser, or by such other means as would achieve the required accessibility for each group of people. Standards §§ 4.1.3(10)(a), 4.1.6(1)(b).
ii. Level 1 West: Although four accessible drinking fountains are provided, there is no drinking fountain provided for people who have difficulty bending or stooping. Provide at least four drinking fountains that are accessible to people who have difficulty bending or stooping. This can be accommodated by the use of a "hi-lo" fountain; by providing one fountain accessible to those who use wheelchairs and one fountain at a standard height convenient for those who have difficulty bending; by providing a fountain accessible to people who use wheelchairs and a cup dispenser, or by such other means as would achieve the required accessibility for each group of people. Standards §§ 4.1.3(10)(a), 4.1.6(1)(b).
iii. Level 1 South: The high fountain in the last hi-lo drinking fountain pair is not detectable to a blind person using a cane. Provide a circulation path at this location such that no objects with their bottom leading edges measuring between 27 inches and 80 inches above the finished floor protrude more than 4 inches into walks, halls, corridors, passageways, or aisles. Free-standing objects mounted on posts or pylons may overhang 12 inches maximum from 27 inches to 80 inches above the ground or finished floor. Providing a cane-detectable barrier is an acceptable solution. Standards §§ 4.1.2(3), 4.1.6(1)(b), 4.4.
iv. Level P1: Although two drinking fountains are provided, there is no accessible drinking fountain for people who use wheelchairs. Provide at least one drinking fountain with a spout height no higher than 36 inches, measured from the finished floor or ground surface to the spout outlet; and a spout located at the front of the unit that directs the water flow in a trajectory that is nearly parallel to the front of the unit and is positioned so the flow of water is within 3 inches of the front edge of the fountain and at least 4 inches high. Provide fountain controls that are operable with one hand, require 5 lbf or less to operate without tight grasping, pinching, or twisting of the wrist; and are front mounted or side mounted near the front edge. Standards §§ 4.1.3(10), 4.1.6(1)(b), 4.15, 4.27.4, Fig. 27.
v. Level 2 West: Although an accessible drinking fountain is provided, there is no drinking fountain provided for people who have difficulty bending or stooping. Provide a drinking fountain that is accessible to people who have difficulty bending or stooping. This can be accommodated by the use of a "hi-lo" fountain; by providing one fountain accessible to those who use wheelchairs and one fountain at a standard height convenient for those who have difficulty bending; by providing a fountain accessible to people who use wheelchairs and a cup dispenser, or by such other means as would achieve the required accessibility for each group of people. Standards §§ 4.1.3(10)(a), 4.1.6(1)(b).
C. Women's Toilet Room - Club Level
i. The pressure required to open the entrance door is 11 pounds. Provide a door that requires no more than 5 pounds of force to open. Standards §§ 4.1.3(7)(b), 4.1.6(1)(b), 4.13.11(2)(b).
ii. The paper towel dispenser controls are mounted at 56 inches above the finished floor. Provide a paper towel dispenser with the controls a maximum height above the finished floor of 48 inches for a forward approach or 54 inches for a side approach and that is accompanied by clear floor space of 30 by 48 inches that allows a forward or parallel approach by a person using a wheelchair. Standards §§ 4.1.3(13), 4.1.6(1)(b), 4.27.2, 4.27.3, 4.2.4, 4.2.5, 4.2.6.
D. Men's Toilet Room - Club Level
i. The pressure required to open the entrance door is 12 pounds. Provide a door that requires no more than 5 pounds of force to open. Standards §§ 4.1.3(7)(b), 4.1.6(1)(b), 4.13.11(2)(b).
ii. The paper towel dispenser controls are mounted at 56 inches above the finished floor. Provide a paper towel dispenser with the controls a maximum height above the finished floor of 48 inches for a forward approach or 54 inches for a side approach and that is accompanied by clear floor space of 30 by 48 inches that allows a forward or parallel approach by a person using a wheelchair. Standards §§ 4.1.3(13), 4.1.6(1)(b), 4.27.2, 4.27.3, 4.2.4, 4.2.5, 4.2.6.
E. Women's and Men's Toilet Rooms - Level 3 South: The paper towel dispensers controls are mounted at 56 inches above the finished floor. Provide a paper towel dispenser in each toilet room with the controls a maximum height above the finished floor of 48 inches for a forward approach or 54 inches for a side approach and that is accompanied by clear floor space of 30 by 48 inches that allows a forward or parallel approach by a person using a wheelchair. Standards §§ 4.1.3(13), 4.1.6(1)(b), 4.27.2, 4.27.3, 4.2.4, 4.2.5, 4.2.6.
F. Men's and Women's Toilet Rooms - Level 1 South: The paper towel dispensers controls are mounted at 56 inches above the finished floor. Provide a paper towel dispenser in each toilet room with the controls a maximum height above the finished floor of 48 inches for a forward approach or 54 inches for a side approach and that is accompanied by clear floor space of 30 by 48 inches that allows a forward or parallel approach by a person using a wheelchair. Standards §§ 4.1.3(13), 4.1.6(1)(b), 4.27.2, 4.27.3, 4.2.4, 4.2.5, 4.2.6.
G. East Side and West Side Locker Rooms (Altered elements)
i. No accessible locker room signs have been provided. Provide a locker room sign at locker each room with the International Symbol of Accessibility and raised and Braille characters. The sign shall be mounted on the wall adjacent to the latch side of the door with the centerline of the sign at 60 inches above the finished floor and situated such that a person can approach within 3 inches of the sign without encountering an obstruction or standing within a door swing. Standards §§ 4.1.2(7)(d), 4.1.6(1)(b), 4.30.1, 4.30.4, 4.30.5, 4.30.6, 4.30.7.
ii. The paper towel dispensers controls are mounted at 57 ½ inches above the finished floor. Provide a paper towel dispenser in each locker room with the controls a maximum height above the finished floor of 48 inches for a forward approach or 54 inches for a side approach and that is accompanied by clear floor space of 30 by 48 inches that allows a forward or parallel approach by a person using a wheelchair. Standards §§ 4.1.3(13), 4.1.6(1)(b), 4.27.2, 4.27.3, 4.2.4, 4.2.5, 4.2.6.
iii. The high fountains in the locker rooms are not detectable to a blind person using a cane. Provide a circulation path at this location such that no objects with their bottom leading edges measuring between 27 inches and 80 inches above the finished floor protrude more than 4 inches into walks, halls, corridors, passageways, or aisles. Free-standing objects mounted on posts or pylons may overhang 12 inches maximum from 27 inches to 80 inches above the ground or finished floor. Providing a cane-detectable barrier is an acceptable solution. Standards §§ 4.1.2(3), 4.1.6(1)(b), 4.4.
iv. No accessible coat/towel hooks have been provided. Provide a coat/towel hook in each locker room at a maximum height above the finished floor of 48 inches for a forward approach or 54 inches for a side approach and that is accompanied by clear floor space of 30 by 48 inches that allows a forward or parallel approach by a person using a wheelchair. Standards §§ 4.1.3(12)(a), 4.1.6(1)(b), 4.25.2, 4.25.3, 4.2.4, 4.2.5, 4.2.6.
v. The shower heads in the designated accessible showers are higher than 48 inches above the finished floor. Provide a shower in each locker room that has a shower spray unit with a hose at least 60 inches long that can be used both as a fixed shower head and as a hand-held shower. In unmonitored facilities where vandalism is a consideration, a fixed shower head mounted at 48 inches above the shower floor may be used in lieu of a hand-held shower head. Standards §§ 4.1.3(11), 4.1.6(1)(b), 4.21.6, Fig. 37.
H. East Side and West Side Coaches Locker Rooms (Altered)
i. No accessible locker room signs have been provided. Provide a locker room sign at locker each room with the International Symbol of Accessibility and raised and Braille characters. The sign shall be mounted on the wall adjacent to the latch side of the door with the centerline of the sign at 60 inches above the finished floor and situated such that a person can approach within 3 inches of the sign without encountering an obstruction or standing within a door swing. Standards §§ 4.1.2(7)(d), 4.1.6(1)(b), 4.30.1, 4.30.4, 4.30.5, 4.30.6, 4.30.7.
ii. The pressure required to open the entrance doors is 15 pounds. Provide a door at each locker room that requires no more than 5 pounds of force to open. Standards §§ 4.1.3(7)(b), 4.1.6(1)(b), 4.13.11(2)(b).
iii. The paper towel dispensers controls are mounted at 57 ½ inches above the finished floor. Provide a paper towel dispenser in each locker room with the controls a maximum height above the finished floor of 48 inches for a forward approach or 54 inches for a side approach and that is accompanied by clear floor space of 30 by 48 inches that allows a forward or parallel approach by a person using a wheelchair. Standards §§ 4.1.3(13), 4.1.6(1)(b), 4.27.2, 4.27.3, 4.2.4, 4.2.5, 4.2.6.
iv. The hot water pipes under the lavatories are not insulated or otherwise configured to protect against contact. Provide hot water and drain pipes in each locker room that are insulated or otherwise configured to protect against contact. Standards §§ 4.1.3(11), 4.1.6(1)(b), 4.22.6, 4.19.4.
v. No accessible coat/towel hooks have been provided. Provide a coat/towel hook in each locker room at a maximum height above the finished floor of 48 inches for a forward approach or 54 inches for a side approach and that is accompanied by clear floor space of 30 by 48 inches that allows a forward or parallel approach by a person using a wheelchair. Standards §§ 4.1.3(12)(a), 4.1.6(1)(b), 4.25.2, 4.25.3, 4.2.4, 4.2.5, 4.2.6.
vi. The shower heads in the designated accessible showers are higher than 48 inches above the finished floor. Provide a shower in each locker room that has a shower spray unit with a hose at least 60 inches long that can be used both as a fixed shower head and as a hand-held shower. In unmonitored facilities where vandalism is a consideration, a fixed shower head mounted at 48 inches above the shower floor may be used in lieu of a hand-held shower head. Standards §§ 4.1.3(11), 4.1.6(1)(b), 4.21.6, Fig. 37.
I. Official's Locker Room (Altered)
i. No accessible locker room sign has been provided. Provide a locker room sign with the International Symbol of Accessibility and raised and Braille characters. The sign shall be mounted on the wall adjacent to the latch side of the door with the centerline of the sign at 60 inches above the finished floor and situated such that a person can approach within 3 inches of the sign without encountering an obstruction or standing within a door swing. Standards §§ 4.1.2(7)(d), 4.1.6(1)(b), 4.30.1, 4.30.4, 4.30.5, 4.30.6, 4.30.7.
ii. The paper towel dispenser controls are mounted at 57 inches above the finished floor. Provide a paper towel dispenser with the controls a maximum height above the finished floor of 48 inches for a forward approach or 54 inches for a side approach and that is accompanied by clear floor space of 30 by 48 inches that allows a forward or parallel approach by a person using a wheelchair. Standards §§ 4.1.3(13), 4.1.6(1)(b), 4.27.2, 4.27.3, 4.2.4, 4.2.5, 4.2.6.
iii. The hot water pipes under the lavatories are not insulated or otherwise configured to protect against contact. Provide hot water and drain pipes that are insulated or otherwise configured to protect against contact. Standards §§ 4.1.3(11), 4.1.6(1)(b), 4.22.6, 4.19.4.
iv. No accessible coat hook has been provided. Provide a coat hook at a maximum height above the finished floor of 48 inches for a forward approach or 54 inches for a side approach and that is accompanied by clear floor space of 30 by 48 inches that allows a forward or parallel approach by a person using a wheelchair. Standards §§ 4.1.3(12)(a), 4.1.6(1)(b), 4.25.2, 4.25.3, 4.2.4, 4.2.5, 4.2.6.
v. The shower heads in the designated accessible showers are higher than 48 inches above the finished floor. Provide a shower that has a shower spray unit with a hose at least 60 inches long that can be used both as a fixed shower head and as a hand-held shower. In unmonitored facilities where vandalism is a consideration, a fixed shower head mounted at 48 inches above the shower floor may be used in lieu of a hand-held shower head. Standards §§ 4.1.3(11), 4.1.6(1)(b), 4.21.6, Fig. 37.
J. Women's Toilet Room - Level 1 East (Room 1)
i. The paper towel dispenser controls are mounted at 56 inches above the finished floor and over the lavatory. Provide a paper towel dispenser with the controls a maximum height above the finished floor of 48 inches for a forward approach or 54 inches for a side approach and that is accompanied by clear floor space of 30 by 48 inches that allows a forward or parallel approach by a person using a wheelchair. Standards §§ 4.1.3(13), 4.1.6(1)(b), 4.27.2, 4.27.3, 4.2.4, 4.2.5, 4.2.6.
ii. Toilet Stall for Wheelchair Users
(1) The toilet flush control is on the closed side. Provide a flush control mounted on the "open" side of the toilet's clear floor space; 44 inches or less above the finished floor; and requiring a maximum of 5 pounds of force to operate; or provide an automatic flush device. Standards §§ 4.1.3(11), 4.1.6(1)(b), 4.22.4, 4.16.5, 4.17.2, 4.27.4.
(2) No accessible coat hook has been provided. Provide a coat hook in each stall at a maximum height above the finished floor of 48 inches for a forward approach or 54 inches for a side approach and that is accompanied by clear floor space of 30 by 48 inches that allows a forward or parallel approach by a person using a wheelchair. Standards §§ 4.1.3(12)(a), 4.1.6(1)(b), 4.25.2, 4.25.3, 4.2.4, 4.2.5, 4.2.6.
K. Men's Toilet Room - Level 1 East (Room 2)
i. The paper towel dispenser controls are mounted at 56 inches above the finished floor and over the lavatory. Provide a paper towel dispenser with the controls a maximum height above the finished floor of 48 inches for a forward approach or 54 inches for a side approach and that is accompanied by clear floor space of 30 by 48 inches that allows a forward or parallel approach by a person using a wheelchair. Standards §§ 4.1.3(13), 4.1.6(1)(b), 4.27.2, 4.27.3, 4.2.4, 4.2.5, 4.2.6.
ii. Toilet Stall for Wheelchair Users
(1) No accessible coat hook has been provided. Provide a coat hook at a maximum height above the finished floor of 48 inches for a forward approach or 54 inches for a side approach and that is accompanied by clear floor space of 30 by 48 inches that allows a forward or parallel approach by a person using a wheelchair. Standards §§ 4.1.3(12)(a), 4.1.6(1)(b), 4.25.2, 4.25.3, 4.2.4, 4.2.5, 4.2.6.
(2) The rear grab bar in the designated accessible stall is inaccessible because the distance of its closer end to the side wall is 13 inches. Provide a rear grab bar that is at least 36 inches in overall length with the closer end no more than 6 inches from the side wall. Standards §§ 4.1.3(11), 4.1.6(1)(b), 4.22.4, 4.17.6, Fig. 30.
L. Women's Toilet Room - Level 1 East (Room 3)
i. The paper towel dispenser controls are mounted at 56 inches above the finished floor and over the lavatory. Provide a paper towel dispenser with the controls a maximum height above the finished floor of 48 inches for a forward approach or 54 inches for a side approach and that is accompanied by clear floor space of 30 by 48 inches that allows a forward or parallel approach by a person using a wheelchair. Standards §§ 4.1.3(13), 4.1.6(1)(b), 4.27.2, 4.27.3, 4.2.4, 4.2.5, 4.2.6.
ii. Toilet Stall for Wheelchair Users
(1) The toilet flush control is on the closed side. Provide a flush control mounted on the "open" side of the toilet's clear floor space; 44 inches or less above the finished floor; and requiring a maximum of 5 pounds of force to operate; or provide an automatic flush device. Standards §§ 4.1.3(11), 4.1.6(1)(b), 4.22.4, 4.16.5, 4.17.2, 4.27.4.
(2) No accessible coat hook has been provided. Provide a coat hook in each stall at a maximum height above the finished floor of 48 inches for a forward approach or 54 inches for a side approach and that is accompanied by clear floor space of 30 by 48 inches that allows a forward or parallel approach by a person using a wheelchair. Standards §§ 4.1.3(12)(a), 4.1.6(1)(b), 4.25.2, 4.25.3, 4.2.4, 4.2.5, 4.2.6.
(3) The rear grab bar in the designated accessible stall is inaccessible because the distance of its closer end to the side wall is 13 inches. Provide a rear grab bar that is at least 36 inches in overall length with the closer end no more than 6 inches from the side wall. Standards §§ 4.1.3(11), 4.1.6(1)(b), 4.22.4, 4.17.6, Fig. 30.
iii. Ambulatory Toilet Stall: No accessible coat hook has been provided in the ambulatory toilet stall. Provide a coat hook in each stall at a maximum height above the finished floor of 48 inches for a forward approach or 54 inches for a side approach and that is accompanied by clear floor space of 30 by 48 inches that allows a forward or parallel approach by a person using a wheelchair. Standards §§ 4.1.3(12)(a), 4.1.6(1)(b), 4.25.2, 4.25.3, 4.2.4, 4.2.5, 4.2.6.
M. Men's Toilet Room - Level 1 East (Room 4)
i. The paper towel dispenser controls are mounted at 56 inches above the finished floor and over the lavatory. Provide a paper towel dispenser with the controls a maximum height above the finished floor of 48 inches for a forward approach or 54 inches for a side approach and that is accompanied by clear floor space of 30 by 48 inches that allows a forward or parallel approach by a person using a wheelchair. Standards §§ 4.1.3(13), 4.1.6(1)(b), 4.27.2, 4.27.3, 4.2.4, 4.2.5, 4.2.6.
ii. Toilet Stall for Wheelchair Users
(1) No accessible coat hook has been provided. Provide a coat hook at a maximum height above the finished floor of 48 inches for a forward approach or 54 inches for a side approach and that is accompanied by clear floor space of 30 by 48 inches that allows a forward or parallel approach by a person using a wheelchair. Standards §§ 4.1.3(12)(a), 4.1.6(1)(b), 4.25.2, 4.25.3, 4.2.4, 4.2.5, 4.2.6.
(2) The rear grab bar in the designated accessible stall is inaccessible because the distance of its closer end to the side wall is 13 inches. Provide a rear grab bar that is at least 36 inches in overall length with the closer end no more than 6 inches from the side wall. Standards §§ 4.1.3(11), 4.1.6(1)(b), 4.22.4, 4.17.6, Fig. 30.
N. Women's Toilet Room - Level 1 East (Room 5)
i. The paper towel dispenser controls are mounted at 56 inches above the finished floor and over lavatory. Provide a paper towel dispenser with the controls a maximum height above the finished floor of 48 inches for a forward approach or 54 inches for a side approach and that is accompanied by clear floor space of 30 by 48 inches that allows a forward or parallel approach by a person using a wheelchair. Standards §§ 4.1.3(13), 4.1.6(1)(b), 4.27.2, 4.27.3, 4.2.4, 4.2.5, 4.2.6.
ii. Toilet Stall for Wheelchair Users
(1) The toilet flush control is on the closed side. Provide a flush control mounted on the "open" side of the toilet's clear floor space; 44 inches or less above the finished floor; and requiring a maximum of 5 pounds of force to operate; or provide an automatic flush device. Standards §§ 4.1.3(11), 4.1.6(1)(b), 4.22.4, 4.16.5, 4.17.2, 4.27.4.
(2) No accessible coat hook has been provided. Provide a coat hook in each stall at a maximum height above the finished floor of 48 inches for a forward approach or 54 inches for a side approach and that is accompanied by clear floor space of 30 by 48 inches that allows a forward or parallel approach by a person using a wheelchair. Standards §§ 4.1.3(12)(a), 4.1.6(1)(b), 4.25.2, 4.25.3, 4.2.4, 4.2.5, 4.2.6.
(3) The rear grab bar in the designated accessible stall is inaccessible because the distance of its closer end to the side wall is 12 inches. Provide a rear grab bar that is at least 36 inches in overall length with the closer end no more than 6 inches from the side wall. Standards §§ 4.1.3(11), 4.1.6(1)(b), 4.22.4, 4.17.6, Fig. 30.
iii. Ambulatory Toilet Stall: No accessible coat hook has been provided in the ambulatory toilet stall. Provide a coat hook in each stall at a maximum height above the finished floor of 48 inches for a forward approach or 54 inches for a side approach and that is accompanied by clear floor space of 30 by 48 inches that allows a forward or parallel approach by a person using a wheelchair. Standards §§ 4.1.3(12)(a), 4.1.6(1)(b), 4.25.2, 4.25.3, 4.2.4, 4.2.5, 4.2.6.
O. Men's Toilet Room - Level 1 East (Room 6)
i. The paper towel dispenser controls are mounted at 56 inches above the finished floor and over the lavatory. Provide a paper towel dispenser with the controls a maximum height above the finished floor of 48 inches for a forward approach or 54 inches for a side approach and that is accompanied by clear floor space of 30 by 48 inches that allows a forward or parallel approach by a person using a wheelchair. Standards §§ 4.1.3(13), 4.1.6(1)(b), 4.27.2, 4.27.3, 4.2.4, 4.2.5, 4.2.6.
ii. Toilet Stall for Wheelchair Users
(1) No accessible coat hook has been provided. Provide a coat hook at a maximum height above the finished floor of 48 inches for a forward approach or 54 inches for a side approach and that is accompanied by clear floor space of 30 by 48 inches that allows a forward or parallel approach by a person using a wheelchair. Standards §§ 4.1.3(12)(a), 4.1.6(1)(b), 4.25.2, 4.25.3, 4.2.4, 4.2.5, 4.2.6.
(2) The rear grab bar in the designated accessible stall is inaccessible because the distance of its closer end to the side wall is 12 inches. Provide a rear grab bar that is at least 36 inches in overall length with the closer end no more than 6 inches from the side wall. Standards §§ 4.1.3(11), 4.1.6(1)(b), 4.22.4, 4.17.6, Fig. 30.
P. Women's Toilet Room - Level 1 East (Room 7)
i. The paper towel dispenser controls are mounted at 56 inches above the finished floor and over the lavatory. Provide a paper towel dispenser with the controls a maximum height above the finished floor of 48 inches for a forward approach or 54 inches for a side approach and that is accompanied by clear floor space of 30 by 48 inches that allows a forward or parallel approach by a person using a wheelchair. Standards §§ 4.1.3(13), 4.1.6(1)(b), 4.27.2, 4.27.3, 4.2.4, 4.2.5, 4.2.6.
ii. Toilet Stall for Wheelchair Users
(1) The toilet flush control is on the closed side. Provide a flush control mounted on the "open" side of the toilet's clear floor space; 44 inches or less above the finished floor; and requiring a maximum of 5 pounds of force to operate; or provide an automatic flush device. Standards §§ 4.1.3(11), 4.1.6(1)(b), 4.22.4, 4.16.5, 4.17.2, 4.27.4.
(2) No accessible coat hook. Provide a coat hook in each stall at a maximum height above the finished floor of 48 inches for a forward approach or 54 inches for a side approach and that is accompanied by clear floor space of 30 by 48 inches that allows a forward or parallel approach by a person using a wheelchair. Standards §§ 4.1.3(12)(a), 4.1.6(1)(b), 4.25.2, 4.25.3, 4.2.4, 4.2.5, 4.2.6.
(3) The rear grab bar in the designated accessible stall is inaccessible because the distance of its closer end to the side wall is 12 inches. Provide a rear grab bar that is at least 36 inches in overall length with the closer end no more than 6 inches from the side wall. Standards §§ 4.1.3(11), 4.1.6(1)(b), 4.22.4, 4.17.6, Fig. 30.
iii. Ambulatory Toilet Stall: No accessible coat hook has been provided in the ambulatory toilet stall. Provide a coat hook in each stall at a maximum height above the finished floor of 48 inches for a forward approach or 54 inches for a side approach and that is accompanied by clear floor space of 30 by 48 inches that allows a forward or parallel approach by a person using a wheelchair. Standards §§ 4.1.3(12)(a), 4.1.6(1)(b), 4.25.2, 4.25.3, 4.2.4, 4.2.5, 4.2.6.
Q. Men's Toilet Room - Level 1 East (Room 8)
i. The paper towel dispenser controls are mounted at 56 inches above the finished floor and over the lavatory. Provide a paper towel dispenser with the controls a maximum height above the finished floor of 48 inches for a forward approach or 54 inches for a side approach and that is accompanied by clear floor space of 30 by 48 inches that allows a forward or parallel approach by a person using a wheelchair. Standards §§ 4.1.3(13), 4.1.6(1)(b), 4.27.2, 4.27.3, 4.2.4, 4.2.5, 4.2.6.
ii. Toilet Stall for Wheelchair Users
(1) No accessible coat hook has been provided. Provide a coat hook at a maximum height above the finished floor of 48 inches for a forward approach or 54 inches for a side approach and that is accompanied by clear floor space of 30 by 48 inches that allows a forward or parallel approach by a person using a wheelchair. Standards §§ 4.1.3(12)(a), 4.1.6(1)(b), 4.25.2, 4.25.3, 4.2.4, 4.2.5, 4.2.6.
(2) The rear grab bar in the designated accessible stall is inaccessible because the distance of its closer end to the side wall is 12 inches. Provide a rear grab bar that is at least 36 inches in overall length with the closer end no more than 6 inches from the side wall. Standards §§ 4.1.3(11), 4.1.6(1)(b), 4.22.4, 4.17.6, Fig. 30.
R. Women's Toilet Room - Level 1 East (Room 9)
i. The paper towel dispenser controls are mounted at 56 inches above the finished floor and over the lavatory. Provide a paper towel dispenser with the controls a maximum height above the finished floor of 48 inches for a forward approach or 54 inches for a side approach and that is accompanied by clear floor space of 30 by 48 inches that allows a forward or parallel approach by a person using a wheelchair. Standards §§ 4.1.3(13), 4.1.6(1)(b), 4.27.2, 4.27.3, 4.2.4, 4.2.5, 4.2.6.
ii. Toilet Stall for Wheelchair Users
(1) The toilet flush control is on the closed side. Provide a flush control mounted on the "open" side of the toilet's clear floor space; 44 inches or less above the finished floor; and requiring a maximum of 5 pounds of force to operate; or provide an automatic flush device. Standards §§ 4.1.3(11), 4.1.6(1)(b), 4.22.4, 4.16.5, 4.17.2, 4.27.4.
(2) No accessible coat hook has been provided. Provide a coat hook in each stall at a maximum height above the finished floor of 48 inches for a forward approach or 54 inches for a side approach and that is accompanied by clear floor space of 30 by 48 inches that allows a forward or parallel approach by a person using a wheelchair. Standards §§ 4.1.3(12)(a), 4.1.6(1)(b), 4.25.2, 4.25.3, 4.2.4, 4.2.5, 4.2.6.
(3) The rear grab bar in the designated accessible stall is inaccessible because the distance of its closer end to the side wall is 12 inches. Provide a rear grab bar that is at least 36 inches in overall length with the closer end no more than 6 inches from the side wall. Standards §§ 4.1.3(11), 4.1.6(1)(b), 4.22.4, 4.17.6, Fig. 30.
iii. Ambulatory Toilet Stall: No accessible coat hook has been provided in the ambulatory toilet stall. Provide a coat hook in each stall at a maximum height above the finished floor of 48 inches for a forward approach or 54 inches for a side approach and that is accompanied by clear floor space of 30 by 48 inches that allows a forward or parallel approach by a person using a wheelchair. Standards §§ 4.1.3(12)(a), 4.1.6(1)(b), 4.25.2, 4.25.3, 4.2.4, 4.2.5, 4.2.6.
S. Men's Toilet Room - Level 1 East (Room 10)
i. The paper towel dispenser controls are mounted at 56 inches above the finished floor and over the lavatory. Provide a paper towel dispenser with the controls a maximum height above the finished floor of 48 inches for a forward approach or 54 inches for a side approach and that is accompanied by clear floor space of 30 by 48 inches that allows a forward or parallel approach by a person using a wheelchair. Standards §§ 4.1.3(13), 4.1.6(1)(b), 4.27.2, 4.27.3, 4.2.4, 4.2.5, 4.2.6.
ii. Toilet Stall for Wheelchair Users
(1) No accessible coat hook has been provided. Provide a coat hook at a maximum height above the finished floor of 48 inches for a forward approach or 54 inches for a side approach and that is accompanied by clear floor space of 30 by 48 inches that allows a forward or parallel approach by a person using a wheelchair. Standards §§ 4.1.3(12)(a), 4.1.6(1)(b), 4.25.2, 4.25.3, 4.2.4, 4.2.5, 4.2.6.
(2) The rear grab bar in the designated accessible stall is inaccessible because the distance of its closer end to the side wall is 12 inches. Provide a rear grab bar that is at least 36 inches in overall length with the closer end no more than 6 inches from the side wall. Standards §§ 4.1.3(11), 4.1.6(1)(b), 4.22.4, 4.17.6, Fig. 30.
T. Unisex Toilet Room - West Ticket Booth
i. No accessible toilet room sign has been provided. Provide a toilet room sign with the International Symbol of Accessibility and raised and Braille characters. The sign shall be mounted on the wall adjacent to the latch side of the door with the centerline of the sign at 60 inches above the finished floor and situated such that a person can approach within 3 inches of the sign without encountering an obstruction or standing within a door swing. Standards §§ 4.1.2(7)(d), 4.1.6(1)(b), 4.30.1, 4.30.4, 4.30.5, 4.30.6, 4.30.7.
ii. The pressure required to open the entrance door is 12 pounds. Provide a door that requires no more than 5 pounds of force to open. Standards §§ 4.1.3(7)(b), 4.1.6(1)(b), 4.13.11(2)(b).
iii. The toilet paper dispenser in the designated accessible stall is 45 ½ inches from the rear wall. Provide a toilet paper dispenser that is mounted with its top at least 1½ inches under the side grab bar and 36 inches or less from the rear wall and is centered at least 19 inches above the finished floor. Standards §§ 4.1.3(11), 4.1.6(1)(b), 4.22.4, 4.17.3, Fig. 30(d).
U. Men's Toilet Room - Level P2
i. No accessible toilet room sign has been provided. Provide a toilet room sign with the International Symbol of Accessibility and raised and Braille characters. The sign shall be mounted on the wall adjacent to the latch side of the door with the centerline of the sign at 60 inches above the finished floor and situated such that a person can approach within 3 inches of the sign without encountering an obstruction or standing within a door swing. Standards §§ 4.1.2(7)(d), 4.1.6(1)(b), 4.30.1, 4.30.4, 4.30.5, 4.30.6, 4.30.7.
ii. The pressure required to open the entrance door is 17 pounds. Provide a door that requires no more than 5 pounds of force to open. Standards §§ 4.1.3(7)(b), 4.1.6(1)(b), 4.13.11(2)(b).
iii. Toilet Stall for Wheelchair Users
(1) The toilet flush control is on the closed side. Provide a flush control mounted on the "open" side of the toilet's clear floor space; 44 inches or less above the finished floor; and requiring a maximum of 5 pounds of force to operate; or provide an automatic flush device. Standards §§ 4.1.3(11), 4.1.6(1)(b), 4.22.4, 4.16.5, 4.17.2, 4.27.4.
(2) No accessible coat hook has been provided. Provide a coat hook at a maximum height above the finished floor of 48 inches for a forward approach or 54 inches for a side approach and that is accompanied by clear floor space of 30 by 48 inches that allows a forward or parallel approach by a person using a wheelchair. Standards §§ 4.1.3(12)(a), 4.1.6(1)(b), 4.25.2, 4.25.3, 4.2.4, 4.2.5, 4.2.6.
V. Women's Toilet Room - Level P2
i. No accessible toilet room sign has been provided. Provide a toilet room sign with the International Symbol of Accessibility and raised and Braille characters. The sign shall be mounted on the wall adjacent to the latch side of the door with the centerline of the sign at 60 inches above the finished floor and situated such that a person can approach within 3 inches of the sign without encountering an obstruction or standing within a door swing. Standards §§ 4.1.2(7)(d), 4.1.6(1)(b), 4.30.1, 4.30.4, 4.30.5, 4.30.6, 4.30.7.
ii. The pressure required to open the entrance door is 27 pounds. Provide a door that requires no more than 5 pounds of force to open. Standards §§ 4.1.3(7)(b), 4.1.6(1)(b), 4.13.11(2)(b).
iii. No accessible coat hook has been provided in the toilet stall for wheelchair users. Provide a coat hook at a maximum height above the finished floor of 48 inches for a forward approach or 54 inches for a side approach and that is accompanied by clear floor space of 30 by 48 inches that allows a forward or parallel approach by a person using a wheelchair. Standards §§ 4.1.3(12)(a), 4.1.6(1)(b), 4.25.2, 4.25.3, 4.2.4, 4.2.5, 4.2.6.
W. Women's Toilet Room - Level 2 West
i. The toilet room sign lacks raised and Braille characters. Provide a toilet room sign with the International Symbol of Accessibility and raised and Braille characters. The sign shall be mounted on the wall adjacent to the latch side of the door with the centerline of the sign at 60 inches above the finished floor and situated such that a person can approach within 3 inches of the sign without encountering an obstruction or standing within a door swing. Standards §§ 4.1.2(7)(d), 4.1.6(1)(b), 4.30.1, 4.30.4, 4.30.5, 4.30.6, 4.30.7.
ii. Although there are 28 stalls, there is no ambulatory stall provided. Provide at least one stall that is exactly 36 inches wide with an outward swinging, self-closing door and parallel grab bars complying with Fig 30(d). Standards §§ 4.1.3(11), 4.1.6(1)(b), 4.22.4, Fig. 30(d).
iii. The lavatory hot water pipes in the designated accessible stall are not insulated or otherwise configured to protect against contact. Provide hot water and drain pipes that are insulated or otherwise configured to protect against contact. Standards §§ 4.1.3(11), 4.1.6(1)(b), 4.22.6, 4.19.4.
iv. No accessible coat hook has been provided in either standard accessible stall. Provide a coat hook in each standard accessible stall at a maximum height above the finished floor of 48 inches for a forward approach or 54 inches for a side approach and that is accompanied by clear floor space of 30 by 48 inches that allows a forward or parallel approach by a person using a wheelchair. Standards §§ 4.1.3(12)(a), 4.1.6(1)(b), 4.25.2, 4.25.3, 4.2.4, 4.2.5, 4.2.6.
X. Men's Toilet Room - Level 2 West
i. The toilet room sign lacks raised and Braille characters. Provide a toilet room sign with the International Symbol of Accessibility and raised and Braille characters. The sign shall be mounted on the wall adjacent to the latch side of the door with the centerline of the sign at 60 inches above the finished floor and situated such that a person can approach within 3 inches of the sign without encountering an obstruction or standing within a door swing. Standards §§ 4.1.2(7)(d), 4.1.6(1)(b), 4.30.1, 4.30.4, 4.30.5, 4.30.6, 4.30.7.
ii. The urinal rim is 23 inches above the finished floor and its flush control is 51 ½ inches above the finished floor. Provide a urinal with an elongated rim mounted 17 inches or less above the finished floor, a clear floor space of at least 30 inches wide and 48 inches deep centered on the urinal, and a flush control height of 44 inches or less above the finished floor. Standards §§ 4.1.3(11), 4.1.6(1)(b), 4.22.5, 4.18.2, 4.18.3, 4.18.4.
iii. Although there are 13 stalls, there is no ambulatory stall provided. Provide at least one stall that is exactly 36 inches wide with an outward swinging, self-closing door and parallel grab bars complying with Fig 30(d). Standards §§ 4.1.3(11), 4.1.6(1)(b), 4.22.4, Fig. 30(d).
iv. The toilet flush control in the designated accessible stall is on the closed side. Provide a flush control mounted on the "open" side of the toilet's clear floor space; 44 inches or less above the finished floor; and requiring a maximum of 5 pounds of force to operate; or provide an automatic flush device. Standards §§ 4.1.3(11), 4.1.6(1)(b), 4.22.4, 4.16.5, 4.17.2, 4.27.4.
v. No accessible coat hook has been provided in either standard accessible stall. Provide a coat hook in each standard accessible stall at a maximum height above the finished floor of 48 inches for a forward approach or 54 inches for a side approach and that is accompanied by clear floor space of 30 by 48 inches that allows a forward or parallel approach by a person using a wheelchair. Standards §§ 4.1.3(12)(a), 4.1.6(1)(b), 4.25.2, 4.25.3, 4.2.4, 4.2.5, 4.2.6.
Y. Men's Toilet Room - Level 1 West (Room 1)
i. The wall-mounted paper towel dispenser protrudes into the main walkway and would not be detectable to a blind person using a cane. Provide a circulation path at this location such that no objects with their bottom leading edges measuring between 27 inches and 80 inches above the finished floor protrude more than 4 inches into walks, halls, corridors, passageways, or aisles. Free-standing objects mounted on posts or pylons may overhang 12 inches maximum from 27 inches to 80 inches above the ground or finished floor. Providing a cane-detectable barrier is an acceptable solution. Standards §§ 4.1.2(3), 4.1.6(1)(b), 4.4.
ii. Toilet Stall for Wheelchair Users
(1) No accessible coat hook has been provided. Provide a coat hook at a maximum height above the finished floor of 48 inches for a forward approach or 54 inches for a side approach and that is accompanied by clear floor space of 30 by 48 inches that allows a forward or parallel approach by a person using a wheelchair. Standards §§ 4.1.3(12)(a), 4.1.6(1)(b), 4.25.2, 4.25.3, 4.2.4, 4.2.5, 4.2.6.
(2) The rear grab bar in the designated accessible stall is inaccessible because the distance of its closer end to the side wall is 12 inches. Provide a rear grab bar that is at least 36 inches in overall length with the closer end no more than 6 inches from the side wall. Standards §§ 4.1.3(11), 4.1.6(1)(b), 4.22.4, 4.17.6, Fig. 30.
Z. Women's Toilet Room - Level 1 West (Room 2)
i. The wall-mounted paper towel dispenser protrudes into the main walkway and would not be detectable to a blind person using a cane. Provide a circulation path at this location such that no objects with their bottom leading edges measuring between 27 inches and 80 inches above the finished floor protrude more than 4 inches into walks, halls, corridors, passageways, or aisles. Free-standing objects mounted on posts or pylons may overhang 12 inches maximum from 27 inches to 80 inches above the ground or finished floor. Providing a cane-detectable barrier is an acceptable solution. Standards §§ 4.1.2(3), 4.1.6(1)(b), 4.4.
ii. No accessible coat hook has been provided in the standard accessible stall or in the alternate accessible stall. Provide a coat hook in each stall at a maximum height above the finished floor of 48 inches for a forward approach or 54 inches for a side approach and that is accompanied by clear floor space of 30 by 48 inches that allows a forward or parallel approach by a person using a wheelchair. Standards §§ 4.1.3(12)(a), 4.1.6(1)(b), 4.25.2, 4.25.3, 4.2.4, 4.2.5, 4.2.6.
iii. The rear grab bar in the designated accessible stall is inaccessible because the distance of its closer end to the side wall is 12 inches. Provide a rear grab bar that is at least 36 inches in overall length with the closer end no more than 6 inches from the side wall. Standards §§ 4.1.3(11), 4.1.6(1)(b), 4.22.4, 4.17.6, Fig. 30.
AA. Men's Toilet Room - Level 1 West (Room 3)
i. The wall-mounted paper towel dispenser protrudes into the main walkway and would not be detectable to a blind person using a cane. Provide a circulation path at this location such that no objects with their bottom leading edges measuring between 27 inches and 80 inches above the finished floor protrude more than 4 inches into walks, halls, corridors, passageways, or aisles. Free-standing objects mounted on posts or pylons may overhang 12 inches maximum from 27 inches to 80 inches above the ground or finished floor. Providing a cane-detectable barrier is an acceptable solution. Standards §§ 4.1.2(3), 4.1.6(1)(b), 4.4.
ii. No accessible mirror has been provided. Provide a mirror with the bottom edge of its reflecting surface no more than 40 inches above the finished floor. Standards §§ 4.1.3(11), 4.1.6(1)(b), 4.22.6, 4.19.6.
iii. No accessible coat hook has been provided. Provide a coat hook at a maximum height above the finished floor of 48 inches for a forward approach or 54 inches for a side approach and that is accompanied by clear floor space of 30 by 48 inches that allows a forward or parallel approach by a person using a wheelchair. Standards §§ 4.1.3(12)(a), 4.1.6(1)(b), 4.25.2, 4.25.3, 4.2.4, 4.2.5, 4.2.6.
iv. The rear grab bar in the designated accessible stall is inaccessible because the distance of its closer end to the side wall is 12 inches. Provide a rear grab bar that is at least 36 inches in overall length with the closer end no more than 6 inches from the side wall. Standards §§ 4.1.3(11), 4.1.6(1)(b), 4.22.4, 4.17.6, Fig. 30.
BB. Women's Toilet Room - Level 1 West (Room 4)
i. The wall-mounted paper towel dispenser protrudes into the main walkway and would not be detectable to a blind person using a cane. Provide a circulation path at this location such that no objects with their bottom leading edges measuring between 27 inches and 80 inches above the finished floor protrude more than 4 inches into walks, halls, corridors, passageways, or aisles. Free-standing objects mounted on posts or pylons may overhang 12 inches maximum from 27 inches to 80 inches above the ground or finished floor. Providing a cane-detectable barrier is an acceptable solution. Standards §§ 4.1.2(3), 4.1.6(1)(b), 4.4.
ii. No accessible coat hook has been provided in the standard accessible stall or in the alternate accessible stall. Provide a coat hook in each stall at a maximum height above the finished floor of 48 inches for a forward approach or 54 inches for a side approach and that is accompanied by clear floor space of 30 by 48 inches that allows a forward or parallel approach by a person using a wheelchair. Standards §§ 4.1.3(12)(a), 4.1.6(1)(b), 4.25.2, 4.25.3, 4.2.4, 4.2.5, 4.2.6.
iii. The rear grab bar in the designated accessible stall is inaccessible because the distance of its closer end to the side wall is 12 inches. Provide a rear grab bar that is at least 36 inches in overall length with the closer end no more than 6 inches from the side wall. Standards §§ 4.1.3(11), 4.1.6(1)(b), 4.22.4, 4.17.6, Fig. 30.
CC. Men's Toilet Room - Level 1 West (Room 5)
i. The wall-mounted paper towel dispenser protrudes into the main walkway and would not be detectable to a blind person using a cane. Provide a circulation path at this location such that no objects with their bottom leading edges measuring between 27 inches and 80 inches above the finished floor protrude more than 4 inches into walks, halls, corridors, passageways, or aisles. Free-standing objects mounted on posts or pylons may overhang 12 inches maximum from 27 inches to 80 inches above the ground or finished floor. Providing a cane-detectable barrier is an acceptable solution. Standards §§ 4.1.2(3), 4.1.6(1)(b), 4.4.
ii. No accessible coat hook has been provided. Provide a coat hook at a maximum height above the finished floor of 48 inches for a forward approach or 54 inches for a side approach and that is accompanied by clear floor space of 30 by 48 inches that allows a forward or parallel approach by a person using a wheelchair. Standards §§ 4.1.3(12)(a), 4.1.6(1)(b), 4.25.2, 4.25.3, 4.2.4, 4.2.5, 4.2.6.
iii. The rear grab bar in the designated accessible stall is inaccessible because the distance of its closer end to the side wall is 12 inches. Provide a rear grab bar that is at least 36 inches in overall length with the closer end no more than 6 inches from the side wall. Standards §§ 4.1.3(11), 4.1.6(1)(b), 4.22.4, 4.17.6, Fig. 30.
DD. Women's Toilet Room - Level 1 West (Room 6)
i. The wall-mounted paper towel dispenser protrudes into the main walkway and would not be detectable to a blind person using a cane. Provide a circulation path at this location such that no objects with their bottom leading edges measuring between 27 inches and 80 inches above the finished floor protrude more than 4 inches into walks, halls, corridors, passageways, or aisles. Free-standing objects mounted on posts or pylons may overhang 12 inches maximum from 27 inches to 80 inches above the ground or finished floor. Providing a cane-detectable barrier is an acceptable solution. Standards §§ 4.1.2(3), 4.1.6(1)(b), 4.4.
ii. No accessible coat hook has been provided in the standard accessible stall or in the alternate accessible stall. Provide a coat hook in each stall at a maximum height above the finished floor of 48 inches for a forward approach or 54 inches for a side approach and that is accompanied by clear floor space of 30 by 48 inches that allows a forward or parallel approach by a person using a wheelchair. Standards §§ 4.1.3(12)(a), 4.1.6(1)(b), 4.25.2, 4.25.3, 4.2.4, 4.2.5, 4.2.6.
iii. The rear grab bar in the designated accessible stall is inaccessible because the distance of its closer end to the side wall is 12 inches. Provide a rear grab bar that is at least 36 inches in overall length with the closer end no more than 6 inches from the side wall. Standards §§ 4.1.3(11), 4.1.6(1)(b), 4.22.4, 4.17.6, Fig. 30.
EE. Men's Toilet Room - Level 1 West (Room 7)
i. The wall-mounted paper towel dispenser protrudes into the main walkway and would not be detectable to a blind person using a cane. Provide a circulation path at this location such that no objects with their bottom leading edges measuring between 27 inches and 80 inches above the finished floor protrude more than 4 inches into walks, halls, corridors, passageways, or aisles. Free-standing objects mounted on posts or pylons may overhang 12 inches maximum from 27 inches to 80 inches above the ground or finished floor. Providing a cane-detectable barrier is an acceptable solution. Standards §§ 4.1.2(3), 4.1.6(1)(b), 4.4.
ii. No accessible coat hook has been provided. Provide a coat hook at a maximum height above the finished floor of 48 inches for a forward approach or 54 inches for a side approach and that is accompanied by clear floor space of 30 by 48 inches that allows a forward or parallel approach by a person using a wheelchair. Standards §§ 4.1.3(12)(a), 4.1.6(1)(b), 4.25.2, 4.25.3, 4.2.4, 4.2.5, 4.2.6.
iii. The rear grab bar in the designated accessible stall is inaccessible because the distance of its closer end to the side wall is 12 inches. Provide a rear grab bar that is at least 36 inches in overall length with the closer end no more than 6 inches from the side wall. Standards §§ 4.1.3(11), 4.1.6(1)(b), 4.22.4, 4.17.6, Fig. 30.
FF. Women's Toilet Room - Level 1 West (Room 8)
i. The wall-mounted paper towel dispenser protrudes into the main walkway and would not be detectable to a blind person using a cane. Provide a circulation path at this location such that no objects with their bottom leading edges measuring between 27 inches and 80 inches above the finished floor protrude more than 4 inches into walks, halls, corridors, passageways, or aisles. Free-standing objects mounted on posts or pylons may overhang 12 inches maximum from 27 inches to 80 inches above the ground or finished floor. Providing a cane-detectable barrier is an acceptable solution. Standards §§ 4.1.2(3), 4.1.6(1)(b), 4.4.
ii. No accessible coat hook has been provided in the standard accessible stall or in the alternate accessible stall. Provide a coat hook in each stall at a maximum height above the finished floor of 48 inches for a forward approach or 54 inches for a side approach and that is accompanied by clear floor space of 30 by 48 inches that allows a forward or parallel approach by a person using a wheelchair. Standards §§ 4.1.3(12)(a), 4.1.6(1)(b), 4.25.2, 4.25.3, 4.2.4, 4.2.5, 4.2.6.
iii. The rear grab bar in the designated accessible stall is inaccessible because the distance of its closer end to the side wall is 12 inches. Provide a rear grab bar that is at least 36 inches in overall length with the closer end no more than 6 inches from the side wall. Standards §§ 4.1.3(11), 4.1.6(1)(b), 4.22.4, 4.17.6, Fig. 30.
GG. Unisex Single-User Toilet Room - Security Office
i. No accessible toilet room sign has been provided. Provide a toilet room sign with the International Symbol of Accessibility and raised and Braille characters. The sign shall be mounted on the wall adjacent to the latch side of the door with the centerline of the sign at 60 inches above the finished floor and situated such that a person can approach within 3 inches of the sign without encountering an obstruction or standing within a door swing. Standards §§ 4.1.2(7)(d), 4.1.6(1)(b), 4.30.1, 4.30.4, 4.30.5, 4.30.6, 4.30.7.
ii. The paper towel dispenser controls are mounted at 58 inches above the finished floor. Provide a paper towel dispenser with the controls a maximum height above the finished floor of 48 inches for a forward approach or 54 inches for a side approach and that is accompanied by clear floor space of 30 by 48 inches that allows a forward or parallel approach by a person using a wheelchair. Standards §§ 4.1.3(13), 4.1.6(1)(b), 4.27.2, 4.27.3, 4.2.4, 4.2.5, 4.2.6.
iii. The lavatory hot water pipes are not insulated or otherwise configured to protect against contact. Provide hot water and drain pipes that are insulated or otherwise configured to protect against contact. Standards §§ 4.1.3(11), 4.1.6(1)(b), 4.22.6, 4.19.4.
9. The City will make the following modifications to Municipal Auditorium located at 705 Elvis Presley Avenue, within three years of the effective date of this Agreement:
A. Lobby Drinking Fountain: The wall-mounted drinking fountain in the lobby is inaccessible because its spout is 39 inches above the finished floor and its apron is only 15 inches above the finished floor. Provide a drinking fountain with clear knee space between the bottom of the apron and the finished floor or ground of at least 27 inches high, 30 inches wide, and 17 to 19 inches deep; and a minimum clear floor space of 30 inches by 48 inches to allow a person in a wheelchair to approach the unit facing forward. Additionally, provide a drinking fountain that is accessible to people who have difficulty bending or stooping. This can be accommodated by the use of a "hi-lo" fountain; by providing one fountain accessible to those who use wheelchairs and one fountain at a standard height convenient for those who have difficulty bending; by providing a fountain accessible to people who use wheelchairs and a cup dispenser; or by such other means as would achieve the required accessibility for each group of people. Standards §§ 4.1.3(10), 4.1.6(1)(b), 4.15.5(1), Figs. 27(a), (b).
B. Auditorium (theater): (Existing)
i. The auditorium, containing seating for 3,007, is inaccessible because the wheelchair seating locations are not dispersed throughout the theater. Provide 31 wheelchair seating areas that are an integral part of the fixed seating plan and are located so as to provide people with physical disabilities a choice of admission prices and lines of sight comparable to those available for members of the general public; that wheelchair seating areas adjoin an accessible route that also serves as a means of egress in case of emergency; and that at least one fixed companion seat is provided next to each wheelchair seating area. Standards §§ 4.1.3(19)(a), 4.1.6(1)(b), 4.5, 4.33.
ii. Although there is an audio amplification system provided in combination with fixed seating, there is no assistive listening system. Provide a permanently installed assistive listening system serving the fixed seating. Provide seating served by the system that is located within a 50 foot viewing distance of the stage or playing area and has a complete view of the stage or playing area. Provide at least 140 receivers for use by the general public and signage indicating their availability. Standards §§ 4.1.3(19)(b), 4.1.6(1)(b), 4.30, 4.33.
iii. The ramp (altered element) handrails are 33 inches high, the clear space between each handrail and the wall is 3 to 4 inches, and the handrails extend 7 inches beyond the top and bottom of the ramp. Provide handrails that are between 1¼ inches and 1½ inches in diameter with a continuous gripping surface along both sides of the ramp, extending at least 12 inches beyond the top and bottom of the ramp parallel with the ground surface. Ensure that handrails are mounted between 34 inches and 38 inches above the ramp surface and 1½ inches from the wall, with ends rounded or returned smoothly to the floor, wall, or post, and that they do not rotate within their fittings. Standards §§ 4.1.2(1), 4.1.2(2), 4.1.6(1)(b), 4.8.5.
C. Dressing/Fitting Rooms (Existing)
i. None of the dressing/fitting rooms are accessible to people with disabilities. Provide at least one accessible dressing/fitting room in this area on an accessible route with accessible signage indicating its location. Ensure that accessible dressing/fitting rooms fitted with swinging or sliding doors contain sufficient clear floor space to allow a person using a wheelchair to make a 180-degree turn inside the room and that no door swings into any part of the turning space. Ensure that private accessible dressing/fitting rooms fitted with curtained openings at least 32 inches wide contain either a clear space of 60 inches in diameter, or a "T" shaped turning space that complies with Fig. 3(b). Provide a bench 24 inches by 48 inches fixed to the wall along the longer dimension and mounted between 17 and 19 inches above the finished floor to the top of the bench. If mirrors are provided in dressing rooms of the same use, provide one full-length mirror, measuring at least 18 inches wide by 54 inches high, mounted in a position affording a view to a person on the bench as well as to a person in a standing position. Standards §§ 4.35, 4.30, 4.26.3, 4.2, 4.3, Fig. 3.
ii. The lavatories in the dressing/fitting rooms are inaccessible because the hot water pipes are not covered and twist hardware is used. Provide a lavatory in the designated accessible dressing/fitting room with the top of its rim or counter 34 inches or less above the finished floor; the bottom edge of the apron at least 29 inches above the finished floor; knee and toe clearances that comply with Fig. 31; hot water and drain pipes covered or otherwise configured to protect against contact; clear floor space at least 30 inches wide and 48 inches deep centered on the lavatory; and a faucet that can be operated with 5 pounds of force or less and can be used with one hand and without tight grasping, pinching, or twisting of the wrist (lever-operated, push-type, and electronically controlled mechanisms are examples of acceptable designs). Standards §§ 4.1.3(11), 4.1.6(1)(b), 4.22.6, 4.19.2, 4.19.3, 4.19.4, 4.19.5, 4.27.4, Figs. 31, 32.
iii. Although shower stalls are located in the dressing rooms, the City does not allow the showers to be used. But, in the event they are returned to use, the City shall provide a shower in the designated accessible dressing/fitting room that is exactly 36 inches wide and 36 inches deep with a 48 inch long and 36 inch wide clear floor space alongside the shower opening, and an L-shaped shower seat mounted on the wall opposite the controls and extending the full depth of the stall; OR a shower that is at least 30 inches deep and 60 inches wide with no curb or threshold and with a 36 inch deep and 60 inch wide clear floor space at the shower opening. Provide a shower that has grab bars, controls, a shower spray unit, and a seat, curb, and enclosure, if provided, that comply fully with the Standards and with Figs. 35, 36, and 37, as applicable. Standards §§ 4.1.3(11), 4.1.6(1)(b), 4.21, Figs. 35, 36, 37.
D. Concession Counters (Existing): The concession counters are 42 ½ inches above the finished floor. Provide a counter on an accessible route such that a portion of the counter is at least 36 inches wide and no more than 36 inches above the finished floor. Standards §§ 4.1.1(2), 4.1.6(1)(b), 7.2(1), 4.1.3(1), 4.3.
E. Elevator (Altered):
i. The elevator lacks hall lanterns. Provide hall lanterns at each hoistway entrance that emit a visible and audible signal indicating which car is answering a call. Ensure that audible signals sound once for the up direction and twice for the down direction or have verbal annunciators that say "up" or "down;" and that visible signals are mounted so that their centerline is at least 72 inches above the lobby floor, they are at least 2½ inches in the smallest dimension, and they are visible from the vicinity of the hall call button. Lanterns located in cars, visible from the vicinity of hall call buttons, and conforming to the above requirements, are acceptable. Standards §§ 4.1.3(5), 4.1.6(1)(b), 4.10.4, Fig. 20.
F. Women's Toilet Room - First Floor (Altered):
i. The toilet room sign centerline is not mounted at 60 inches above the finished floor. Provide a toilet room sign mounted on the wall adjacent to the latch side of the door with the centerline of the sign at 60 inches above the finished floor and situated such that a person can approach within 3 inches of the sign without encountering an obstruction or standing within a door swing. Standards §§ 4.1.2(7)(d), 4.1.6(1)(b), 4.30.1, 4.30.4, 4.30.5, 4.30.6, 4.30.7.
ii. The pressure required to open the entrance door is 11 pounds. Provide a door that requires no more than 5 pounds of force to open. Standards §§ 4.1.3(7)(b), 4.1.6(1)(b), 4.13.11(2)(b).
iii. The paper towel dispenser controls are mounted at 56 inches above the finished floor. Provide a paper towel dispenser with the controls a maximum height above the finished floor of 48 inches for a forward approach or 54 inches for a side approach and that is accompanied by clear floor space of 30 by 48 inches that allows a forward or parallel approach by a person using a wheelchair. Standards §§ 4.1.3(13), 4.1.6(1)(b), 4.27.2, 4.27.3, 4.2.4, 4.2.5, 4.2.6.
iv. Toilet Stall for Wheelchair Users
(1) The toilet flush control is on the closed side. Provide a flush control mounted on the "open" side of the toilet's clear floor space; 44 inches or less above the finished floor; and requiring a maximum of 5 pounds of force to operate; or provide an automatic flush device. Standards §§ 4.1.3(11), 4.1.6(1)(b), 4.22.4, 4.16.5, 4.17.2, 4.27.4.
(2) The grab bars are mounted 38 inches above the finished floor and the rear grab bar is 32 inches long. Provide a rear grab bar that is at least 36 inches in overall length, with the closer end no more than 6 inches from the side wall, and a side grab bar that is at least 40 inches in overall length, with the far end mounted at least 54 inches from the rear wall and the closer end 12 inches or less from the rear wall. Provide grab bars that are mounted 33 to 36 inches above the finished floor; with a diameter between 1¼ and 1½ inches; with 1½ inches between the grab bar and the wall; and at least 1½ inches between the grab bar and any other object, such as a toilet seat cover dispenser or a toilet paper dispenser. Standards §§ 4.1.3(11), 4.1.6(1)(b), 4.22.4, 4.17.6, 4.26.2, Fig. 30.
G. Men's Toilet Room - First Floor (Altered)
i. The toilet room sign centerline is not mounted at 60 inches above the finished floor. Provide a toilet room sign mounted on the wall adjacent to the latch side of the door with the centerline of the sign at 60 inches above the finished floor and situated such that a person can approach within 3 inches of the sign without encountering an obstruction or standing within a door swing. Standards §§ 4.1.2(7)(d), 4.1.6(1)(b), 4.30.1, 4.30.4, 4.30.5, 4.30.6, 4.30.7.
ii. The pressure required to open the entrance door is 11 pounds. Provide a door that requires no more than 5 pounds of force to open. Standards §§ 4.1.3(7)(b), 4.1.6(1)(b), 4.13.11(2)(b).
iii. The paper towel dispenser controls are mounted at 55 ½ inches above the finished floor. Provide a paper towel dispenser with the controls a maximum height above the finished floor of 48 inches for a forward approach or 54 inches for a side approach and that is accompanied by clear floor space of 30 by 48 inches that allows a forward or parallel approach by a person using a wheelchair. Standards §§ 4.1.3(13), 4.1.6(1)(b), 4.27.2, 4.27.3, 4.2.4, 4.2.5, 4.2.6.
iv. Toilet Stall for Wheelchair Users
(1) The toilet flush control is on the closed side. Provide a flush control mounted on the "open" side of the toilet's clear floor space; 44 inches or less above the finished floor; and requiring a maximum of 5 pounds of force to operate; or provide an automatic flush device. Standards §§ 4.1.3(11), 4.1.6(1)(b), 4.22.4, 4.16.5, 4.17.2, 4.27.4.
(2) The grab bars are mounted 37 ½ inches above the finished floor, the distance of the far end of the side grab bar to the rear wall is 49 ½ inches, and the rear grab bar is 32 inches long. Provide a rear grab bar that is at least 36 inches in overall length, with the closer end no more than 6 inches from the side wall, and a side grab bar that is at least 40 inches in overall length, with the far end mounted at least 54 inches from the rear wall and the closer end 12 inches or less from the rear wall. Provide grab bars that are mounted 33 to 36 inches above the finished floor; with a diameter between 1¼ and 1½ inches; with 1½ inches between the grab bar and the wall; and at least 1½ inches between the grab bar and any other object, such as a toilet seat cover dispenser or a toilet paper dispenser. Standards §§ 4.1.3(11), 4.1.6(1)(b), 4.22.4, 4.17.6, 4.26.2, Fig. 30.
H. Women's and Men's Toilet Rooms - Basement Floor (Altered)
i. The toilet room signs are not mounted on the wall adjacent to the latch side of the door. Provide a toilet room sign at each toilet room mounted on the wall adjacent to the latch side of the door with the centerline of the sign at 60 inches above the finished floor and situated such that a person can approach within 3 inches of the sign without encountering an obstruction or standing within a door swing. Standards §§ 4.1.2(7)(d), 4.1.6(1)(b), 4.30.1, 4.30.4, 4.30.5, 4.30.6, 4.30.7.
ii. The pressure required to open the entrance doors is 11 pounds. Provide a door at each toilet room that requires no more than 5 pounds of force to open. Standards §§ 4.1.3(7)(b), 4.1.6(1)(b), 4.13.11(2)(b).
iii. The doors, which are exited through a front approach, have less than 18 inches of latch side maneuvering clearance on the pull side of the doors. On the pull side of the door in each toilet room, provide maneuvering clearance at least 60 inches deep and provide a minimum of 18 inches (24 inches is preferred) of maneuvering clearance on the latch side of the door. Propping the door open during all business hours is an acceptable program access solution. Standards §§ 4.1.3(7)(b), 4.1.6(1)(b), 4.13.6, Fig. 25(a).
iv. The paper towel dispensers controls are mounted at 56 inches above the finished floor. Provide a paper towel dispenser in each toilet room with the controls a maximum height above the finished floor of 48 inches for a forward approach or 54 inches for a side approach and that is accompanied by clear floor space of 30 by 48 inches that allows a forward or parallel approach by a person using a wheelchair. Standards §§ 4.1.3(13), 4.1.6(1)(b), 4.27.2, 4.27.3, 4.2.4, 4.2.5, 4.2.6.
v. The wall-mounted paper towel dispenser protrudes into the main walkway and would not be detectable to a blind person using a cane. Provide a circulation path at this location such that no objects with their bottom leading edges measuring between 27 inches and 80 inches above the finished floor protrude more than 4 inches into walks, halls, corridors, passageways, or aisles. Free-standing objects mounted on posts or pylons may overhang 12 inches maximum from 27 inches to 80 inches above the ground or finished floor. Providing a cane-detectable barrier is an acceptable solution. Standards §§ 4.1.2(3), 4.1.6(1)(b), 4.4.
vi. Toilet Stalls for Wheelchair Users
(1) The toilets flush controls are on the closed side. Provide a flush control in each designated accessible stall mounted on the "open" side of the toilet's clear floor space; 44 inches or less above the finished floor; and requiring a maximum of 5 pounds of force to operate; or provide an automatic flush device. Standards §§ 4.1.3(11), 4.1.6(1)(b), 4.22.4, 4.16.5, 4.17.2, 4.27.4.
(2) No accessible coat hooks have been provided. Provide a coat hook in each toilet room at a maximum height above the finished floor of 48 inches for a forward approach or 54 inches for a side approach and that is accompanied by clear floor space of 30 by 48 inches that allows a forward or parallel approach by a person using a wheelchair. Standards §§ 4.1.3(12)(a), 4.1.6(1)(b), 4.25.2, 4.25.3, 4.2.4, 4.2.5, 4.2.6.
10. The City will make the following modifications to Mamie Hicks Recreation Center located at 200 Mayfair Drive, within 18 months of the effective date of this Agreement:
A. Parking (Altered element): The damaged signage designating one of the two parking spaces as reserved for persons with disabilities is too low. At this space designated as reserved for persons with disabilities, provide a vertical sign with the International Symbol of Accessibility located such that it cannot be obstructed by vehicles parked in the space. Standards §§ 4.1.2(5), 4.1.6(1)(b), 4.6.4, 4.30.7(1).
B. Directional Signage (Altered element): There is no signage at inaccessible entrances directing users to the location of the accessible entrance. Provide accessible directional signage with the International Symbol of Accessibility at inaccessible entrances directing users to the accessible entrance, and provide accessible signage with the International Symbol of Accessibility at all permanent accessible entrances. Standards §§ 4.1.3(8)(d), 4.1.3(16)(b), 4.1.6(1)(b), 4.13, 4.30.
C. Accessible Route (Existing element): There is no accessible route connecting the park's tennis courts and playground equipment. Provide at least one accessible route within the boundary of the site connecting these elements that, to the maximum extent feasible, coincides with the route for the general public. The accessible route must have a minimum clear width of 36 inches, or a minimum clear width of 42 inches if there is a turn around an obstruction less than 48 inches wide; have passing spaces at least 60 inches by 60 inches at least every 200 feet; have a minimum clear headroom of 80 inches; have a surface that is firm, stable, and slip resistant; have, in the absence of a curb ramp, ramp, elevator, or platform lift, no level changes in excess of ½ inch vertically; and have a running slope of less than 1:20 (5%) (or have been constructed as a fully accessible ramp) and a cross slope of less than 1:50 (2%). Standards §§ 4.1.3(1), 4.3, 4.5, Fig. 7.
D. Picnic Table (Altered element): No accessible picnic table has been provided. Provide at least one picnic table on an accessible route such that there is knee space at the table at least 27 inches high, 30 inches wide, and 19 inches deep, and such that the height of the top of the table is between 28 inches and 34 inches above the ground. Standards §§ 4.1.3(18), 4.1.6(1)(b), 4.32.3, 4.32.4.
E. Drinking Fountain (Altered element): Although an accessible drinking fountain is provided outside, there is no drinking fountain provided for people who have difficulty bending or stooping. Provide a drinking fountain that is accessible to people who have difficulty bending or stooping. This can be accommodated by the use of a "hi-lo" fountain; by providing one fountain accessible to those who use wheelchairs and one fountain at a standard height convenient for those who have difficulty bending; by providing a fountain accessible to people who use wheelchairs and a cup dispenser, or by such other means as would achieve the required accessibility for each group of people. Standards §§ 4.1.3(10)(a), 4.1.6(1)(b).
F. Women's Toilet Room (Altered element)
i. The pressure required to open the entrance door is 10 pounds. Provide a door that requires no more than 5 pounds of force to open. Standards §§ 4.1.3(7)(b), 4.1.6(1)(b), 4.13.11(2)(b).
ii. No accessible mirror has been provided. Provide a mirror with the bottom edge of its reflecting surface no more than 40 inches above the finished floor. Standards §§ 4.1.3(11), 4.1.6(1)(b), 4.22.6, 4.19.6.
iii. The soap dispenser controls are mounted at 56 ½ inches above the finished floor. Provide a soap dispenser with the controls a maximum height above the finished floor of 48 inches for a forward approach or 54 inches for a side approach and that is accompanied by clear floor space of 30 by 48 inches that allows a forward or parallel approach by a person using a wheelchair. Standards §§ 4.1.3(13), 4.1.6(1)(b), 4.27.2, 4.27.3, 4.2.4, 4.2.5, 4.2.6.
iv. The lavatory is inaccessible because twist hardware is used. Provide a lavatory with a faucet that can be operated with 5 pounds of force or less and can be used with one hand and without tight grasping, pinching, or twisting of the wrist (lever-operated, push-type, and electronically controlled mechanisms are examples of acceptable designs). Standards §§ 4.1.3(11), 4.1.6(1)(b), 4.22.6, 4.19.5, 4.27.4.
G. Men's Toilet Room (Altered element)
i. No accessible mirror has been provided. Provide a mirror with the bottom edge of its reflecting surface no more than 40 inches above the finished floor. Standards §§ 4.1.3(11), 4.1.6(1)(b), 4.22.6, 4.19.6.
ii. The soap dispenser controls are mounted at 56 inches above the finished floor. Provide a soap dispenser with the controls a maximum height above the finished floor of 48 inches for a forward approach or 54 inches for a side approach and that is accompanied by clear floor space of 30 by 48 inches that allows a forward or parallel approach by a person using a wheelchair. Standards §§ 4.1.3(13), 4.1.6(1)(b), 4.27.2, 4.27.3, 4.2.4, 4.2.5, 4.2.6.
iii. The lavatory has twist hardware. Provide a lavatory with a faucet that can be operated with 5 pounds of force or less and can be used with one hand and without tight grasping, pinching, or twisting of the wrist (lever-operated, push-type, and electronically controlled mechanisms are examples of acceptable designs). Standards §§ 4.1.3(11), 4.1.6(1)(b), 4.22.6, 4.19.5, 4.27.4.
iv. The urinal rim is 22 inches above the finished floor. Provide a urinal with an elongated rim mounted 17 inches or less above the finished floor, a clear floor space of at least 30 inches wide and 48 inches deep centered on the urinal, and a flush control height of 44 inches or less above the finished floor. Standards §§ 4.1.3(11), 4.1.6(1)(b), 4.22.5, 4.18.2, 4.18.3, 4.18.4.
H. Computer Room (Altered element): The latch side maneuvering clearance on the pull side of the door is obstructed by a table. On the pull side of the door, provide maneuvering clearance at least 60 inches deep and provide a minimum of 18 inches (24 inches is preferred) of maneuvering clearance on the latch side of the door. Standards §§ 4.1.3(7)(b), 4.1.6(1)(b), 4.13.6, Fig. 25(a).
11. The City will make the following modifications to Police Department located at 1234 Texas Avenue, within three years of the effective date of this Agreement:
A. Parking
i. Although the parking lot has a total of 210 parking spaces, none are designated as van accessible. On the shortest accessible route to the accessible entrance, provide at least one van accessible space a minimum of 96 inches wide, served by access aisles at least 96 inches wide, with vertical signs with the International Symbol of Accessibility located such that they cannot be obstructed by parked vehicles, and with an additional "Van-Accessible" sign located below the International Symbol of Accessibility. Standards §§ 4.1.2(5)(b), 4.1.6(1)(b), 4.6, 4.30.7(1).
ii. The signage designating three of the seven parking spaces as reserved for persons with disabilities is too low. At each space designated as reserved for persons with disabilities, provide a vertical sign with the International Symbol of Accessibility located such that it cannot be obstructed by vehicles parked in the space. Standards §§ 4.1.2(5), 4.1.6(1)(b), 4.6.4, 4.30.7(1).
B. Interior Signage: No accessible permanent room signage has been provided. Provide permanent room signage with upper case, sans serif or simple serif type letters and numerals, meeting the requirements of the Standards for character height, raised characters, finish and contrast, accompanied by Grade 2 Braille; mounted on the wall adjacent to the latch side of the door or on the nearest adjacent wall at a height of 60 inches above the finished floor to the centerline of the sign; and located so that a person may approach within 3 inches of the signage without encountering protruding objects or standing within the swing of a door. Standards §§ 4.1.2(7), 4.1.6(1)(b), 4.30.1, 4.30.4, 4.30.5, 4.30.6.
C. East and West Elevators (Existing elements)
i. The elevators hall call buttons are centered at 54 inches above the finished floor. Provide hall call buttons with visual signals indicating when each call is registered and when each call is answered. Provide call buttons that are centered at 42 inches above the finished floor, a minimum of ¾ inch in the smallest dimension, with the button designating the up direction on top; that the call buttons are raised or flush; and that objects mounted beneath hall call buttons do not project into the elevator lobby more than 4 inches. Standards §§ 4.1.3(5), 4.1.6(1)(b), 4.10.3, Fig. 20.
ii. The elevators hall lanterns do not signal once for up and twice for down. Provide hall lanterns at each hoistway entrance that emit a visible and audible signal indicating which car is answering a call. Provide audible signals that sound once for the up direction and twice for the down direction or have verbal annunciators that say "up" or "down;" and that visible signals are mounted so that their centerline is at least 72 inches above the lobby floor, they are at least 2½ inches in the smallest dimension, and they are visible from the vicinity of the hall call button. Lanterns located in cars, visible from the vicinity of hall call buttons, and conforming to the above requirements, are acceptable. Standards §§ 4.1.3(5), 4.1.6(1)(b), 4.10.4, Fig. 20.
iii. The elevators hoistway signage is not provided on both door jambs at each hoistway entrance and the signs are not centered at 60 inches above the finished floor. Provide signage at hoistway entrances with raised and Braille floor designations on both jambs such that the centerline of the characters is 60 inches above the finished floor and the characters are 2 inches high. Standards §§ 4.1.3(5), 4.1.6(1)(b), 4.10.5, Fig. 20.
iv. The elevators doors do not automatically reopen if they are obstructed by a person or object without contact. Provide doors that open and close automatically with a reopening device that will stop and reopen the car door and hoistway door automatically if the door becomes obstructed by an object or person. Provide a device that is capable of completing these operations without requiring contact for obstructions passing through the opening at heights of 5 inches and 29 inches above the finished floor; that door reopening devices remain effective for at least 20 seconds, after which the doors may close; that the minimum time from notification that a car is answering a call until the doors of that car start to close is 5 seconds; and that the minimum time for elevator doors to remain fully open in response to a car call is 3 seconds. Standards §§ 4.1.3(5), 4.1.6(1)(b), 4.10.6, 4.10.7, 4.10.8, Figs. 20, 21.
v. The elevators highest button is at 60 inches above the finished floor and the emergency controls are grouped at the top of the panel. Provide car control buttons that are no higher than 54 inches above the finished floor for a side approach and no more than 48 inches above the finished floor for a front approach; and that emergency controls, including the emergency alarm and emergency stop, are grouped at the bottom of the panel and have their centerlines no less than 35 inches above the finished floor. Standards §§ 4.1.3(5), 4.1.6(1)(b), 4.10.12, Fig. 23.
vi. Although emergency communications are provided in the elevator, the emergency communications controls are greater than 48 inches above the finished floor and the systems require voice communication. Provide a two-way communication system such that it does not require voice communication, the highest operable part is a maximum of 48 inches above the finished floor of the car, and it is identified by a raised symbol and lettering located adjacent to the device. If the system uses a handset, ensure that the length of the cord from the panel to the handset is at least 29 inches. If the system is located in a closed compartment, ensure that the compartment door hardware operates without tight grasping, pinching or twisting of the wrist. Standards §§ 4.1.3(5), 4.1.6(1)(b), 4.10.14.
D. Call Takers/Criminal History Office: The pressure required to open the entrance door is 10 pounds. Provide a door that requires no more than 5 pounds of force to open. Standards §§ 4.1.3(7)(b), 4.1.6(1)(b), 4.13.11(2)(b).
E. Investigations Violent Crimes Office: The pressure required to open the entrance door is 10 pounds. Provide a door that requires no more than 5 pounds of force to open. Standards §§ 4.1.3(7)(b), 4.1.6(1)(b), 4.13.11(2)(b).
F. Property Crimes, Financial Crimes, Auto Theft, Pawn Shop, Crime Stoppers, and Domestic Violence Unit Office: The pressure required to open the entrance door is 8 pounds. Provide a door that requires no more than 5 pounds of force to open. Standards §§ 4.1.3(7)(b), 4.1.6(1)(b), 4.13.11(2)(b).
G. Assistant Chief of Police, Uniform Services Division Office: The entrance door, which is exited through a front approach and which has both a closer and a latch, has 6 inches of latch side maneuvering clearance on the push side of the door. On the push side of the door, provide maneuvering clearance at least 48 inches deep and provide a minimum of 12 inches of maneuvering clearance on the latch side of the door, or remove the closer or the latch. Standards §§ 4.1.3(7)(b), 4.1.6(1)(b), 4.13.6, Fig. 25(a).
H. Recruiting Unit Office: The pressure required to open the entrance door is 12 pounds. Provide a door that requires no more than 5 pounds of force to open. Standards §§ 4.1.3(7)(b), 4.1.6(1)(b), 4.13.11(2)(b).
I. Sex Crimes Unit Office: The pressure required to open the entrance door is 10 pounds. Provide a door that requires no more than 5 pounds of force to open. Standards §§ 4.1.3(7)(b), 4.1.6(1)(b), 4.13.11(2)(b).
J. Public Information Office
i. The pressure required to open the entrance door is 12 pounds. Provide a door that requires no more than 5 pounds of force to open. Standards §§ 4.1.3(7)(b), 4.1.6(1)(b), 4.13.11(2)(b).
ii. The entrance door, which is accessed through a front approach, has 3 inches of latch side maneuvering clearance on the pull side of the door. On the pull side of the door, provide maneuvering clearance at least 60 inches deep and provide a minimum of 18 inches (24 inches is preferred) of maneuvering clearance on the latch side of the door. Standards §§ 4.1.3(7)(b), 4.1.6(1)(b), 4.13.6, Fig. 25(a)
K. Police Administration Office: The pressure required to open the entrance door is 15 pounds. Provide a door that requires no more than 5 pounds of force to open. Standards §§ 4.1.3(7)(b), 4.1.6(1)(b), 4.13.11(2)(b).
L. Youth Offices
i. The pressure required to open the entrance door is 9 pounds. Provide a door that requires no more than 5 pounds of force to open. Standards §§ 4.1.3(7)(b), 4.1.6(1)(b), 4.13.11(2)(b).
ii. The entrance door, which is exited through a front approach and which has both a closer and a latch, has only 3 inches of latch side maneuvering clearance on the push side of the door because of a table. On the push side of the door, provide maneuvering clearance at least 48 inches deep and provide a minimum of 12 inches of maneuvering clearance on the latch side of the door, or remove the closer or the latch. Standards §§ 4.1.3(7)(b), 4.1.6(1)(b), 4.13.6, Fig. 25(a).
M. Personnel Management Office
i. The interior office door has knob hardware that requires tight grasping and twisting of the wrist to operate. Provide a door with hardware that is easy to grasp with one hand and that does not require tight grasping, pinching, or twisting of the wrist to operate. Lever-operated mechanisms, push-type mechanisms, and U-shaped handles are acceptable designs. Standards §§ 4.1.3(7)(b), 4.1.6(1)(b), 4.13.9.
ii. The interior office door is inaccessible because the pressure required to open the door is 21 pounds. Provide a door that requires no more than 5 pounds of force to open. Standards §§ 4.1.3(7)(b), 4.1.6(1)(b), 4.13.11(2)(b).
N. Assistant Chief of Police and Investigations Division Office: The entrance door, which is exited through a front approach, has 7 inches of latch side maneuvering clearance on the pull side of the door. On the pull side of the door, provide maneuvering clearance at least 60 inches deep and provide a minimum of 18 inches (24 inches is preferred) of maneuvering clearance on the latch side of the door. Standards §§ 4.1.3(7)(b), 4.1.6(1)(b), 4.13.6, Fig. 25(a).
O. Drinking Fountains: The lower level wall-mounted drinking fountain spout is 42 inches above the finished floor and its apron is 15 inches above the finished floor. Provide a drinking fountain with clear knee space between the bottom of the apron and the finished floor or ground of at least 27 inches high, 30 inches wide, and 17 to 19 inches deep; and a minimum clear floor space of 30 inches by 48 inches to allow a person in a wheelchair to approach the unit facing forward. Additionally, provide a drinking fountain that is accessible to people who have difficulty bending or stooping. This can be accommodated by the use of a "hi-lo" fountain; by providing one fountain accessible to those who use wheelchairs and one fountain at a standard height convenient for those who have difficulty bending; by providing a fountain accessible to people who use wheelchairs and a cup dispenser; or by such other means as would achieve the required accessibility for each group of people. Standards §§ 4.1.3(10), 4.1.6(1)(b), 4.15.5(1), Figs. 27(a), (b).
P. Women's and Men's Single-User Toilet Rooms - Lower Level (Existing)
i. The pressure required to open the entrance doors is 15 pounds. Provide a door at each toilet room that requires no more than 5 pounds of force to open. Standards §§ 4.1.3(7)(b), 4.1.6(1)(b), 4.13.11(2)(b).
ii. No accessible mirrors have been provided. Provide a mirror in each toilet room with the bottom edge of its reflecting surface no more than 40 inches above the finished floor. Standards §§ 4.1.3(11), 4.1.6(1)(b), 4.22.6, 4.19.6.
iii. The lavatories aprons are 27 inches above the finished floor. Provide a lavatory in each toilet room with the top of its rim or counter 34 inches or less above the finished floor; the bottom edge of the apron at least 29 inches above the finished floor; and knee and toe clearances that comply with Fig. 31. Standards §§ 4.1.3(11), 4.1.6(1)(b), 4.22.6, 4.19.2, Fig. 31.
iv. The lavatories hot water pipes are not insulated or otherwise configured to protect against contact. Provide hot water and drain pipes in each toilet room that are insulated or otherwise configured to protect against contact. Standards §§ 4.1.3(11), 4.1.6(1)(b), 4.22.6, 4.19.4.
v. The toilets are inaccessible because there is insufficient clear floor space. Provide clear floor space at the toilets that complies with Fig. 28. Standards §§ 4.1.3(11), 4.1.6(1)(b), 4.22.4, 4.16.2, Fig. 28.
Q. Women's Single-User Toilet Room - Lower Level near the Traffic Bureau (Existing element)
i. The pressure required to open the entrance door is 15 pounds. Provide a door that requires no more than 5 pounds of force to open. Standards §§ 4.1.3(7)(b), 4.1.6(1)(b), 4.13.11(2)(b).
ii. The entrance door, which exited through a front approach, has 2 inches of latch side maneuvering clearance on the pull side of the door. On the pull side of the door, provide maneuvering clearance at least 60 inches deep and provide a minimum of 18 inches (24 inches is preferred) of maneuvering clearance on the latch side of the door. Standards §§ 4.1.3(7)(b), 4.1.6(1)(b), 4.13.6, Fig. 25(a).
iii. The toilet flush control is on the closed side. Provide a flush control mounted on the "open" side of the toilet's clear floor space; 44 inches or less above the finished floor; and requiring a maximum of 5 pounds of force to operate; or provide an automatic flush device. Standards §§ 4.1.3(11), 4.1.6(1)(b), 4.22.4, 4.16.5, 4.27.4.
R. Men's Single-User Toilet Room - Lower Level near the Traffic Bureau (Existing element)
i. The pressure required to open the entrance door is 15 pounds. Provide a door that requires no more than 5 pounds of force to open. Standards §§ 4.1.3(7)(b), 4.1.6(1)(b), 4.13.11(2)(b).
ii. The entrance door, which exited through a front approach, has 8 ½ inches of latch side maneuvering clearance on the pull side of the door. On the pull side of the door, provide maneuvering clearance at least 60 inches deep and provide a minimum of 18 inches (24 inches is preferred) of maneuvering clearance on the latch side of the door. Standards §§ 4.1.3(7)(b), 4.1.6(1)(b), 4.13.6, Fig. 25(a).
iii. The soap dispenser controls are mounted at 57 ½ inches above the finished floor. Provide a soap dispenser with the controls a maximum height above the finished floor of 48 inches for a forward approach or 54 inches for a side approach and that is accompanied by clear floor space of 30 by 48 inches that allows a forward or parallel approach by a person using a wheelchair. Standards §§ 4.1.3(13), 4.1.6(1)(b), 4.27.2, 4.27.3, 4.2.4, 4.2.5, 4.2.6.
iv. The paper towel dispenser controls are mounted at 58 inches above the finished floor. Provide a paper towel dispenser with the controls a maximum height above the finished floor of 48 inches for a forward approach or 54 inches for a side approach and that is accompanied by clear floor space of 30 by 48 inches that allows a forward or parallel approach by a person using a wheelchair. Standards §§ 4.1.3(13), 4.1.6(1)(b), 4.27.2, 4.27.3, 4.2.4, 4.2.5, 4.2.6.
v. The toilet flush control is on the closed side. Provide a flush control mounted on the "open" side of the toilet's clear floor space; 44 inches or less above the finished floor; and requiring a maximum of 5 pounds of force to operate; or provide an automatic flush device. Standards §§ 4.1.3(11), 4.1.6(1)(b), 4.22.4, 4.16.5, 4.27.4.
S. Unisex Single-User Toilet Room located on the Second Floor
i. The toilet room sign is mounted on the door. Provide a toilet room sign with the International Symbol of Accessibility and raised and Braille characters. The sign shall be mounted on the wall adjacent to the latch side of the door with the centerline of the sign at 60 inches above the finished floor and situated such that a person can approach within 3 inches of the sign without encountering an obstruction or standing within a door swing. Standards §§ 4.1.2(7)(d), 4.1.6(1)(b), 4.30.1, 4.30.4, 4.30.5, 4.30.6, 4.30.7.
ii. The lavatory has twist hardware. Provide a lavatory with a faucet that can be operated with 5 pounds of force or less and can be used with one hand and without tight grasping, pinching, or twisting of the wrist (lever-operated, push-type, and electronically controlled mechanisms are examples of acceptable designs). Standards §§ 4.1.3(11), 4.1.6(1)(b), 4.22.6, 4.19.5, 4.27.4.
iii. The rear grab bar at the toilet is 25 inches long. Provide a rear grab bar that is at least 36 inches in overall length with the closer end no more than 6 inches from the side wall. Standards §§ 4.1.3(11), 4.1.6(1)(b), 4.22.4, 4.16.4, Fig. 29.
T. Interior Directional Signage: There is no signage directing people with disabilities to the accessible toilet rooms. Provide accessible directional signage with the International Symbol of Accessibility at the inaccessible toilet rooms located on the first and second floors indicating the location of the nearest accessible toilet room, and provide accessible signage with the International Symbol of Accessibility at all accessible toilet rooms. Standards §§ 4.1.2(7)(d), 4.1.6(3)(e)(iii), 4.30.1, 4.30.2, 4.30.3, 4.30.5, 4.30.7.
12. The City will make the following modifications to Querbes Park Recreation Center located at 3500 Beverly Place, within 18 months of the effective date of this Agreement:
A. Exterior Ramp (Existing element): The route from the parking lot to the Recreation Center has a slope of 1:20 or greater, and is therefore considered a ramp. The ramp lacks handrails. Provide handrails that are between 1¼ inches and 1½ inches in diameter with a continuous gripping surface along both sides of the ramp, extending at least 12 inches beyond the top and bottom of the ramp parallel with the ground surface. Provide handrails that are mounted between 34 inches and 38 inches above the ramp surface, with ends rounded or returned smoothly to the floor, wall, or post, and that they do not rotate within their fittings. Standards §§ 4.1.2(1), 4.1.2(2), 4.1.6(1)(b), 4.3.7, 4.8.5.
B. Women's Toilet Room (Altered element)
i. The pressure required to open the entrance door is 15 pounds. Provide a door that requires no more than 5 pounds of force to open. Standards §§ 4.1.3(7)(b), 4.1.6(1)(b), 4.13.11(2)(b).
ii. No accessible coat hook has been provided. Provide a coat hook at a maximum height above the finished floor of 48 inches for a forward approach or 54 inches for a side approach and that is accompanied by clear floor space of 30 by 48 inches that allows a forward or parallel approach by a person using a wheelchair. Standards §§ 4.1.3(12)(a), 4.1.6(1)(b), 4.25.2, 4.25.3, 4.2.4, 4.2.5, 4.2.6.
iii. Although there are 6 stalls, no ambulatory stall is provided. Provide at least one stall that is exactly 36 inches wide with an outward swinging, self-closing door and parallel grab bars complying with Fig 30(d). Standards §§ 4.1.3(11), 4.1.6(1)(b), 4.22.4, Fig. 30(d).
C. Men's Toilet Room (Altered element)
i. The pressure required to open the entrance door is 12 pounds. Provide a door that requires no more than 5 pounds of force to open. Standards §§ 4.1.3(7)(b), 4.1.6(1)(b), 4.13.11(2)(b).
ii. No accessible coat hook has been provided. Provide a coat hook at a maximum height above the finished floor of 48 inches for a forward approach or 54 inches for a side approach and that is accompanied by clear floor space of 30 by 48 inches that allows a forward or parallel approach by a person using a wheelchair. Standards §§ 4.1.3(12)(a), 4.1.6(1)(b), 4.25.2, 4.25.3, 4.2.4, 4.2.5, 4.2.6.
D. Women's and Men's Locker Rooms (Altered elements)
i. The ramp to the locker rooms lacks the required edge protection. Provide edge protection at least 2 inches high at the drop off sides. Standards §§ 4.1.2(1), 4.1.2(2), 4.1.6(1)(b), 4.3.8, 4.8.7.
ii. No accessible locker room signs have been provided. Provide a locker room sign at each locker room with the International Symbol of Accessibility and raised and Braille characters. The sign shall be mounted on the wall adjacent to the latch side of the door with the centerline of the sign at 60 inches above the finished floor and situated such that a person can approach within 3 inches of the sign without encountering an obstruction or standing within a door swing. Standards §§ 4.1.2(7)(d), 4.1.6(1)(b), 4.30.1, 4.30.4, 4.30.5, 4.30.6, 4.30.7.
iii. No accessible coat hooks have been provided. Provide a coat hook in each locker room at a maximum height above the finished floor of 48 inches for a forward approach or 54 inches for a side approach and that is accompanied by clear floor space of 30 by 48 inches that allows a forward or parallel approach by a person using a wheelchair. Standards §§ 4.1.3(12)(a), 4.1.6(1)(b), 4.25.2, 4.25.3, 4.2.4, 4.2.5, 4.2.6.
E. Drinking Fountain (Altered element): The hi-lo drinking fountain near the toilet rooms is inaccessible because the high fountain is not detectable to a blind person using a cane. Provide a circulation path at this location such that no objects with their bottom leading edges measuring between 27 inches and 80 inches above the finished floor protrude more than 4 inches into walks, halls, corridors, passageways, or aisles. Free-standing objects mounted on posts or pylons may overhang 12 inches maximum from 27 inches to 80 inches above the ground or finished floor. Providing a cane-detectable barrier is an acceptable solution. Standards §§ 4.1.2(3), 4.1.6(1)(b), 4.4.
F. Women's Single-User Toilet Room - 5th Hole (Altered element)
i. The toilet flush control is on the closed side. Provide a flush control mounted on the "open" side of the toilet's clear floor space; 44 inches or less above the finished floor; and requiring a maximum of 5 pounds of force to operate; or provide an automatic flush device. Standards §§ 4.1.3(11), 4.1.6(1)(b), 4.22.4, 4.16.5, 4.27.4.
ii. The toilet paper dispenser is mounted above the side grab bar. Provide a toilet paper dispenser that is mounted within reach, with its top at least 1½ inches under the side grab bar, and centered at least 19 inches above the finished floor. Standards §§ 4.1.3(11), 4.1.6(1)(b), 4.22.4, 4.16.6, Fig. 29(b).
G. Women's Single-User Toilet Room - 14th Hole (Altered element): The toilet flush control is on the closed side. Provide a flush control mounted on the "open" side of the toilet's clear floor space; 44 inches or less above the finished floor; and requiring a maximum of 5 pounds of force to operate; or provide an automatic flush device. Standards §§ 4.1.3(11), 4.1.6(1)(b), 4.22.4, 4.16.5, 4.27.4.
H. Men's Single-User Toilet Rooms - 5th Hole and 14th Hole (Altered elements): The toilet paper dispensers are mounted above the side grab bars. Provide a toilet paper dispenser in each toilet room that is mounted within reach, with its top at least 1½ inches under the side grab bar, and centered at least 19 inches above the finished floor. Standards §§ 4.1.3(11), 4.1.6(1)(b), 4.22.4, 4.16.6, Fig. 29(b).
13. Randle T. Moore Center located at 3101 Fairfield Avenue,
has numerous barriers to
access for persons with disabilities. Within 6 months of the effective
date of this
Agreement, the City will post signs at the Randle T. Moore Center and
will otherwise
inform the public (including an informational posting on its website)
that it is providing
equivalent accessible facilities and recreation programs at Querbes
Recreation Center,
located nearby this facility.
1
The men's and women's toilet rooms on the first floor are inaccessible
because: the toilet room signs do not comply with the Standards;
the pressure required to open the entrance doors exceeds 5 pounds; the
lavatory aprons are less than 29 inches above the finished floor; the
seat cover dispensers are mounted outside of accessible reach ranges,
no accessible coat hook has been provided in the women's toilet room;
the hot water and drain pipes under the lavatory in the women's toilet
room are not covered or configured to protect against contact; and no
toilet stall is provided for wheelchair users.