ANDERSON SNACK BAR - ATTACHMENT M
I. Building Entrance Issues
Entrance Location
A. Main Entrance to Basement Snack Bar Lobby From Exterior
Remedy:
1. Install a directional sign indicating that the accessible entrance is the Secondary Access/Exit from Snack Bar at South end of building. Standards §§ 4.30.1, 4.30.2, 4.30.3, 4.30.5.
B. Secondary Access/Exit From Snack Bar at South end of building through Office
Secondary Access/Exit from Snack Bar at South end of building through Office is inaccessible.
The maneuvering space is not level.
There is a ¾" lip at threshold exterior door.
There are no directional signs.
Remedy:
1. Re-pave the current entrance to ensure that the maneuvering space is level and to ensure that the running and cross slopes are ADA compliant. Standards §§ 4.13.6, Fig. 25, 4.3.7, 4.8.
2. Install a handrail at this entrance. Standards § 4.26.
3. Bevel the ¾" lip. Standards § 4.13.8.
4. Install a directional sign indicating that this entrance is the accessible entrance to the snack bar. Standards §§ 4.30.1, 4.30.2, 4.30.3, 4.30.5.
II. Accessible Route Issues to Student Spaces
Interior Routes by Floor Level
A. Vestibule/Lobby Entrance
The door width is inaccessible. There are a pair of 27 ¾" doors.
There are no accessible room signs.
Remedy:
1. Tear down the 27 ¾" doors and install a door with a minimum clear opening of 32", or install a magnetic hold open device, or an auto-opening door. Standards §§ 4.13, 4.13.12.
2. Install accessible room signs. Standards §§ 4.30.1, 4.30.4, 4.30.5, 4.30.6.
III. Primary Student Space Issues
Student Spaces
A. Snack Bar Food Service Area
The snack bar counter is inaccessible. It is 41" in height.
Remedy:
1. Lower the counter and remove a few feet of the counter top which would allow a wheelchair user to pull up to get food and to pay for food. Standards § 7.2.
IV. Restroom Accessibility
Student Restrooms
A. Basement Men’s Restroom
Remedy:
1. Install a directional sign indicating that the accessible men’s restroom is in the Athletic Fitness Center. Standards §§ 4.30.1, 4.30.2, 4.30.3, 4.30.5.
B. Basement Women’s Restroom
Remedy:
1. Install a directional sign indicating that the accessible women’s restroom is in the Athletic Fitness Center. Standards §§ 4.30.1, 4.30.2, 4.30.3, 4.30.5.
V. Miscellaneous Accessibility Issues
There is no visual fire alarm in the lobby area.
Remedy:
1. Install a visual fire alarm in the lobby area in accordance with the requirement in paragraph 12 of the Agreement. Standards § 4.28.3.