ATTACHMENT K: Program Access in Existing Facilities

Please Note: Paragraph 57 of the Agreement requires that within 12 months of the effective date of this Agreement, the Consolidated Government will provide signage as necessary to comply with 28 C.F.R. § 35.163(b), after having surveyed all facilities that are the subject of this Agreement for the purpose of identifying those that have multiple entrances not all of which are accessible.

The technical requirements and, where appropriate, the scoping requirements of the Standards are used as a guide for determining whether a program or activity held in an existing facility is "readily accessible to and usable by" persons with disabilities and for determining what changes are necessary to make this program or activity accessible if it continues to be provided in the existing facility in question. See 28 C.F.R. §§ 35.150(b)(1), 35.151.

The chart below lists the facilities surveyed by the Department, the access issues identified during the survey, and the actions required to correct the access issues. Required actions are listed using an alphanumeric code. The key to the alphanumeric codes is provided in Attachment M to this Agreement.

In order to ensure that the programs, services, and activities housed in the Consolidated Government's facilities are accessible to persons with disabilities, when viewed in their entirety, the Consolidated Government will take the actions referenced by the alphanumeric code and described in detail in Attachment M to this Settlement Agreement within the time period specified below, which time period begins to run on the effective date of the Agreement.

Item #

Access Issue

Required Action

Completion Date

1.

Justice Complex, located at 725 Ann Avenue

   

1.1.

Parking. The parking reserved for persons with disabilities is inaccessible because the designated van accessible space has an access aisle that is 90 inches wide, the vertical signs are mounted too low, and the spaces and access aisles have slopes of 6.5%.

P3

18 months

1.2.

Ann Street Drop-Off Zone [Circle Drive]. The passenger loading zone is inaccessible because it has no access aisle and it slopes more than 2%.

P4

18 months

1.3.

Entrances

   

1.3.a.

The building does not have directional signage posted at inaccessible entrances and does not have the International Symbol of Accessibility posted at accessible entrances.

D16

18 months

1.3.b.

The Ann Street drop off entrance is inaccessible because there is a slope of 5.4% within the door's maneuvering clearance.

D13

18 months

1.3.c.

The Ann Street drop off entrance is inaccessible because the interior door requires 8 pounds of force to open.

D2

18 months

1.4.

Elevators

   

1.4.a.

The elevators are inaccessible because the hall control buttons are centered 53 inches above the finished floor.

E3

18 months

1.4.b.

The elevators are inaccessible because the hall lanterns lack audible signals.

E11

18 months

1.4.c.

The elevators are inaccessible because the highest operable car control buttons are 59 inches above the finished floor.

E4

18 months

1.4.d.

The elevators are inaccessible because the car position does not ring as the car passes or stops on floors.

E5

18 months

1.4.e.

The mailbox between the elevators on the B Level protrudes into the walkway is not detectable to blind persons using a cane.

AR8

18 months

1.5.

Assistive Listening System. Many of the assembly areas within the building are inaccessible to persons with hearing disabilities because there are no assistive listening systems available.

AA5

18 months

1.6.

Traffic Department - B Level. The counter is inaccessible because it is 42 inches above the finished floor.

C6

18 months

1.7.

Information Counter - B Level

   

1.7.a.

The counter is inaccessible because it is 43½ inches above the finished floor.

C6

18 months

1.7.b.

The counter protrudes into the walkway and is not detectable to blind persons using a cane.

AR8

18 months

1.8.

Drinking Fountain - B Level, Next to Men's Toilet Room. Although an accessible drinking fountain is provided, there is no drinking fountain provided for people who have difficulty bending or stooping.

DF3

18 months

1.9.

Men's Toilet Room with Stalls - B Level

   

1.9.a.

The toilet room sign is inaccessible because it is mounted on the door.

TR17

18 months

1.9.b.

The door is inaccessible because it requires 20 pounds of force to open.

D2

18 months

1.9.c.

Although an audible alarm is provided in this facility, there is no visual alarm appliance in the toilet room.

TR21

18 months

1.10.

Break Room - B Level. One of the vending machines is inaccessible because the highest operable part is 56 inches above the finished floor.

TR5

18 months

1.11.

Computer Room - 1st Floor. The computer tables are inaccessible because they provide only 25 inches of knee space height and the table surfaces are 26 inches above the finished floor.

C3

18 months

1.12.

Drinking Fountain - 1st Floor by Vending Machines

   

1.12.a.

Although a designated accessible drinking fountain is provided, there is no drinking fountain provided for people who have difficulty bending or stooping.

DF3

18 months

1.12.b.

The drinking fountain protrudes into the walkway and is not detectable to blind persons using a cane.

AR8

18 months

1.13.

Legislative Auditor - 1st Floor

   

1.13.a.

The counter is inaccessible because it is 42½ inches above the finished floor.

C6

18 months

1.13.b.

The door is inaccessible because it requires 10 pounds of force to open.

D2

18 months

1.14.

Domestic Court Services. The counter is inaccessible because it is 42 inches above the finished floor.

C6

18 months

1.15.

Register of Deeds. The counter is inaccessible because it is 42 inches above the finished floor.

C6

18 months

1.16.

District Court #10 - 1st Floor

   

1.16.a.

The Marriage License counter is inaccessible because it is 42 inches above the finished floor.

C6

18 months

1.16.b.

The door is inaccessible because knob hardware is used.

D1

18 months

1.16.c.

The witness stand is inaccessible because it can be accessed only by steps and the entrance is 23½ inches wide.

AA8,

AR3

18 months

1.16.d.

There is no signage informing the public of the availability of an assistive listening system.

AA3

18 months

1.17.

District Court #8

   

1.17.a.

The double doors are inaccessible because each leaf is 27 inches wide.

D24

18 months

1.17.b.

The inner door is inaccessible because it requires 10 pounds of force to open.

D2

18 months

1.17.c.

The witness stand is inaccessible because it can be accessed only by steps and the entrance is 30 inches wide.

AA8,

AR3

18 months

1.17.d.

The jury box is inaccessible because it can be accessed only by steps, the entrance is 30 inches wide, and there is no space to accommodate a wheelchair.

AA8, AA9, AR3

18 months

1.17.e.

The tables are inaccessible because they provide only 24½ inches of knee space height.

T1

18 months

1.18.

Courtroom #8 Jury Room

   

1.18.a.

The buzzer for the room is inaccessible because it is mounted 59 inches above the finished floor.

TR5

18 months

1.18.b.

The table is inaccessible because it provides only 25 inches of knee space height.

T1

18 months

1.19.

Courtroom #8 Jury Room Single-User Toilet Room

   

1.19.a.

The door is inaccessible because it requires more than 5 pounds of force to open.

D2

18 months

1.19.b.

The door is inaccessible because knob hardware is used.

D1

18 months

1.19.c.

The pull side of the door, which is accessed through a front approach, is inaccessible because it has 6½ inches of maneuvering clearance on the latch side.

D6

18 months

1.19.d.

The push side of the door, which is accessed through a front approach and which has both a closer and a latch, is inaccessible because it has 7 inches of maneuvering clearance on the latch side.

D7

18 months

1.19.e.

The toilet room is inaccessible because the toilet room door swings into the required clear floor space at the lavatory.

TR6

18 months

1.19.f.

Although an audible alarm is provided in this facility, there is no visual alarm appliance in the toilet room.

TR21

18 months

1.19.g.

No accessible mirror is provided.

TR14

18 months

1.19.h.

The soap dispenser is inaccessible because it is mounted with the control 52 inches above the finished floor and only a forward reach provided.

TR5

18 months

1.19.i.

The lavatory is inaccessible because the bottom edge of the apron is 27½ inches above the finished floor, the clear floor space is obstructed by water bottles, the pipes are not covered or configured to protect against contact, and knob hardware is used.

TR9

18 months

1.19.j.

The toilet is inaccessible because the top of the seat is 15 inches above the finished floor.

SU18

18 months

1.19.k.

The toilet is inaccessible because the centerline is 22 inches from the side wall.

SU15

18 months

1.19.l.

The toilet is inaccessible because the flush control is on the closed side.

SU1

18 months

1.19.m. 

The toilet is inaccessible because no grab bars are provided.

SU10

18 months

1.20.

District Court #2 - 1st Floor

   

1.20.a.

The double doors are inaccessible because each leaf is 27 inches wide.

D24

18 months

1.20.b.

The door is inaccessible because it requires 16 pounds of force to open.

D2

18 months

1.20.c.

The witness stand is inaccessible because it can be accessed only by steps and the entrance is 29 inches wide.

AA8,

AR3

18 months

1.20.d.

The jury box is inaccessible because it can be accessed only by steps, the entrance is 27 inches wide, and there is no space to accommodate a wheelchair.

AA8, AA9,

AR3

18 months

1.21.

Courtroom #2 Jury Room

   

1.21.a.

The door is inaccessible because knob hardware is used.

D1

18 months

1.21.b.

Both toilet rooms are inaccessible, and there is no signage directing persons with disabilities to the nearest accessible toilet rooms.

TR16

18 months

1.22.

Women's Toilet Room with Stalls - 1st Floor

   

1.22.a.

The toilet room sign is mounted 64 inches above the finished floor.

TR17

18 months

1.22.b.

Although an audible alarm is provided in this facility, there is no visual alarm appliance in the toilet room.

TR21

18 months

1.23.

District Court #18 - 2nd Floor

   

1.23.a.

The double doors are inaccessible because each leaf is 26½ inches wide.

D24

18 months

1.23.b.

The door is inaccessible because knob hardware is used.

D1

18 months

1.23.c.

The witness stand is inaccessible because it can be accessed only by steps.

AA8

18 months

1.24.

Department of Technical Services

   

1.24.a.

The double doors are inaccessible because each leaf is 27 inches wide.

D24

18 months

1.24.b.

The door is inaccessible because knob hardware is used.

D1

18 months

1.24.c.

The counter is inaccessible because it is 42 inches above the finished floor.

C6

18 months

1.25.

Delinquent Real Estate. The counter is inaccessible because it is 43 inches above the finished floor.

C6

18 months

1.26.

Men's Toilet Room with Stalls - 2nd Floor Hallway

   

1.26.a.

The toilet room sign is mounted 66 inches above the finished floor.

TR17

18 months

1.26.b.

The door is inaccessible because it requires 15 pounds of force to open.

D2

18 months

1.26.c.

Although an audible alarm is provided in this facility, there is no visual alarm appliance in the toilet room.

TR21

18 months

1.26.d.

The side grab bar at the designated accessible toilet is inaccessible because it is mounted 13 inches from the rear wall.

ST7

18 months

1.27.

Women's Toilet Room with Stalls - 2nd Floor Hallway

   

1.27.a.

The door is inaccessible because it requires 15 pounds of force to open.

D2

18 months

1.27.b.

Although an audible alarm is provided in this facility, there is no visual alarm appliance in the toilet room.

TR21

18 months

1.27.c.

The side grab bar at the designated accessible toilet is inaccessible because it is mounted 13 inches from the rear wall.

ST7

18 months

1.27.d.

The designated accessible toilet is inaccessible because the rear grab bar is obstructed by the sanitizer.

ST5

18 months

1.28.

Drinking Fountain - 2nd Floor Hallway

   

1.28.a.

Although a designated accessible drinking fountain is provided, there is no drinking fountain provided for people who have difficulty bending or stooping.

DF3

18 months

1.28.b.

The drinking fountain protrudes into the walkway and is not detectable to blind persons using a cane.

AR8

18 months

1.29.

Drinking Fountain - 3rd Floor Hallway

   

1.29.a.

Although a designated accessible drinking fountain is provided, there is no drinking fountain provided for people who have difficulty bending or stooping.

DF3

18 months

1.29.b.

The drinking fountain protrudes into the walkway and is not detectable to blind persons using a cane.

AR8

18 months

1.30.

District Court #5 - 3rd Floor

   

1.30.a.

The outer double doors are inaccessible because each leaf is 29 inches wide.

D24

18 months

1.30.b.

The inner double doors are inaccessible because each leaf is 28 inches wide.

D24

18 months

1.30.c.

The doors are inaccessible because knob hardware is used.

D1

18 months

1.30.d.

The gate to the well is inaccessible because it has an opening width of 29 inches.

D25

18 months

1.30.e.

The witness stand is inaccessible because it can be accessed only by steps.

AA8

18 months

1.30.f.

The jury box is inaccessible because it can be accessed only by steps, and there is no space to accommodate a wheelchair.

AA8,

AA9

18 months

1.31.

Courtroom #5 Jury Room

   

1.32.

The door is inaccessible because it has an opening width of 29 inches.

D25

18 months

1.33.

The door is inaccessible because knob hardware is used.

D1

18 months

1.34.

District Court #3 - 3rd Floor

   

1.34.a.

The double doors are inaccessible because each leaf is 27 inches wide.

D24

18 months

1.34.b.

The door is inaccessible because knob hardware is used.

D1

18 months

1.34.c.

The gate to the well is inaccessible because it has an opening width of 28 inches.

D25

18 months

1.34.d.

The witness stand is inaccessible because it can be accessed only by steps and the entrance is 20 inches wide.

AA8,

AR3

18 months

1.34.e.

The jury box is inaccessible because it can be accessed only by steps, the entrance is 24 inches wide, and there is no space to accommodate a wheelchair.

AA8, AA9,

AR3

18 months

1.34.f.

The jury room is inaccessible to people with mobility impairments because it can be accessed only by traversing a flight of stairs.

AR9

18 months

1.35.

District Court #6 - 3rd Floor

   

1.35.a.

The double doors are inaccessible because each leaf is 26½ inches wide.

D24

18 months

1.35.b.

The door is inaccessible because it requires more than 5 pounds of force to open.

D2

18 months

1.35.c.

The door is inaccessible because knob hardware is used.

D1

18 months

1.35.d.

The gate to the well is inaccessible because it has an opening width of 26½ inches.

D25

18 months

1.35.e.

The witness stand is inaccessible because it can be accessed only by steps and the entrance is 28 inches wide.

AA8,

AR3

18 months

1.35.f.

The jury box is inaccessible because it can be accessed only by steps, the entrance is 20 inches wide, and there is no space to accommodate a wheelchair.

AA8, AA9,

AR3

18 months

1.35.g.

The tables are inaccessible because they provide only 25 inches of knee space height.

T1

18 months

1.35.h.

The jury room is inaccessible to people with mobility impairments because it can be accessed only by traversing a flight of stairs.

AR9

18 months

1.36.

District Court #1 - 3rd Floor

   

1.36.a.

The outer double doors are inaccessible because each leaf is 27 inches wide.

D24

18 months

1.36.b.

The inner double doors are inaccessible because each leaf is 30 inches wide.

D24

18 months

1.36.c.

The doors are inaccessible because they require more than 5 pounds of force to open.

D2

18 months

1.36.d.

The doors are inaccessible because they have knob hardware.

D1

18 months

1.36.e.

The gate to the well is inaccessible because it has an opening width of 30 inches.

D25

18 months

1.36.f.

The witness stand is inaccessible because it can be accessed only by steps and the entrance is 24 inches wide.

AA8,

AR3

18 months

1.36.g.

The jury box is inaccessible because it can be accessed only by steps and there is no space to accommodate a wheelchair.

AA8,

AR3

18 months

1.36.h.

The tables are inaccessible because they provide only 25½ inches of knee space height.

T1

18 months

1.36.i.

The jury room is inaccessible to people with mobility impairments because it can be accessed only by traversing a flight of stairs.

AR9

18 months

1.37.

District Court #4 - 3rd Floor

   

1.37.a.

The double doors are inaccessible because each leaf is 27 inches wide.

D24

18 months

1.37.b.

The doors are inaccessible because they require more than 5 pounds of force to open.

D2

18 months

1.37.c.

The doors are inaccessible because they have knob hardware.

D1

18 months

1.37.d.

The witness stand is inaccessible because it can be accessed only by steps and the entrance is 28 inches wide.

AA8,

AR3

18 months

1.37.e.

The jury box is inaccessible because it can be accessed only by steps, the entrance is 20 inches wide, and there is no space to accommodate a wheelchair.

AA8, AA9,

AR3

18 months

1.37.f.

The tables are inaccessible because they provide only 25½ inches of knee space height.

T1

18 months

1.38.

Courtroom #4 Jury Room

   

1.38.a.

The door is inaccessible because it requires more than 5 pounds of force to open.

D2

18 months

1.38.b.

The door is inaccessible because knob hardware is used.

D1

18 months

1.38.c.

Both toilet rooms are inaccessible, and there is no signage directing persons with disabilities to the nearest accessible toilet rooms.

TR16

18 months

1.39.

District Court #17 - 3rd Floor

   

1.39.a.

The double doors are inaccessible because each leaf is 28 inches wide.

D24

18 months

1.39.b.

The doors are inaccessible because they require more than 5 pounds of force to open.

D2

18 months

1.39.c.

The witness stand is inaccessible because it can be accessed only by steps and the entrance is 30 inches wide.

AA8,

AR3

18 months

1.40.

Criminal Department - 3rd Floor. The counter is inaccessible because it is 42 inches above the finished floor.

C6

18 months

1.41.

Men's Toilet Room With Stalls - 3rd Floor Hallway

   

1.41.a.

The toilet room sign is mounted on the door and has no raised or Braille characters and no International Symbol of Accessibility.

TR17

18 months

1.41.b.

The door is inaccessible because it has an opening width of 28 inches.

D25

18 months

1.41.c.

The door is inaccessible because it requires more than 5 pounds of force to open.

D2

18 months

1.41.d.

The pull side of the door, which is accessed through a front approach, is inaccessible because it has 11 inches of maneuvering clearance on the latch side.

D6

18 months

1.41.e.

Although an audible alarm is provided in this facility, there is no visual alarm appliance in the toilet room.

TR21

18 months

1.41.f.

The urinal is inaccessible because the rim is 24 inches above the finished floor.

TR20

18 months

1.41.g.

There is no accessible toilet stall provided.

ST15

18 months

1.42.

Women's Toilet Room With Stalls - 3rd Floor Hallway

   

1.42.a.

The toilet room sign is mounted on the door and has no raised or Braille characters and no International Symbol of Accessibility.

TR17

18 months

1.42.b.

The pull side of the door, which is accessed through a front approach, is inaccessible because it has 11 inches of maneuvering clearance on the latch side.

D6

18 months

1.42.c.

Although an audible alarm is provided in this facility, there is no visual alarm appliance in the toilet room.

TR21

18 months

1.42.d.

There is no accessible toilet stall provided.

ST15

18 months

1.43.

Clerk of the District Court - Civil Department - 3rd Floor. The counter is inaccessible because it is 42 inches above the finished floor.

C6

18 months

1.44.

Drinking Fountain - Mezzanine Level Hallway. The drinking fountain is inaccessible because it has a spout that is 42½ inches above the finished floor.

DF6

18 months

1.45.

Court Services Signature Bonds - Mezzanine Level. The hallway form dispenser is inaccessible because it is mounted 55½ inches above the finished floor.

TR5

18 months

1.46.

District Court # 7 - Mezzanine Level

   

1.46.a.

The door is inaccessible because it requires more than 5 pounds of force to open.

D2

18 months

1.46.b.

The door is inaccessible because it has thumb latch hardware.

D1

18 months

1.46.c.

The witness stand is inaccessible because it can be accessed only by steps.

AA8

18 months

1.46.d.

The jury box is inaccessible because it can be accessed only by steps, the entrance is 26 inches wide, and there is no space to accommodate a wheelchair.

AA8, AA9, AR3

18 months

1.47.

Courtroom #7 Jury Room

   

1.47.a.

The door is inaccessible because it requires more than 5 pounds of force to open.

D2

18 months

1.47.b.

The door is inaccessible because knob hardware is used.

D1

18 months

1.47.c.

Both toilet rooms are inaccessible, and there is no signage directing persons with disabilities to the nearest accessible toilet rooms.

TR16

18 months

1.48.

Buildings and Logistics - Mezzanine Level. The counter is inaccessible because it is more than 36 inches above the finished floor.

C6

18 months

1.49.

Law Library - 5th Floor. The ramp is inaccessible because the slope is 9%, it has a handrail on only one side, the handrail is 30 inches above the finished floor, the handrail ends are not rounded or returned, and the handrail does not have a 1¼ to 1½ inch diameter gripping surface.

R3

18 months

1.50.

Men's Toilet Room with Stalls at Rear of Law Library

   

1.50.a.

The toilet room sign is mounted on the door and does not have raised or Braille characters.

TR17

18 months

1.50.b.

The door is inaccessible because it requires more than 5 pounds of force to open.

D2

18 months

1.50.c.

Although an audible alarm is provided in this facility, there is no visual alarm appliance in the toilet room.

TR21

18 months

1.50.d.

The paper towel dispenser protrudes into the walkway and is not detectable to blind persons using a cane.

AR8

18 months

1.50.e.

The lavatory is inaccessible because it has twist type hardware.

TR10

18 months

1.50.f.

The urinal is inaccessible because the rim is 23 inches above the finished floor.

TR20

18 months

1.50.g.

No accessible coat hook has been provided.

TR1

18 months

1.51.

Women's Toilet Room with Stalls at Rear of Law Library

   

1.51.a.

The toilet room sign is mounted on the door and does not have raised or Braille characters.

TR17

18 months

1.51.b.

The door is inaccessible because it requires more than 5 pounds of force to open.

D2

18 months

1.51.c.

The route within the toilet room is inaccessible because it is only 30 inches wide between the partial partition and the wall.

AR3

18 months

1.51.d.

Although an audible alarm is provided in this facility, there is no visual alarm appliance in the toilet room.

TR21

18 months

1.51.e.

The paper towel dispenser protrudes into the walkway and is not detectable to blind persons using a cane.

AR8

18 months

1.51.f.

The lavatory is inaccessible because it has twist type hardware.

TR10

18 months

1.51.g.

The toilet is inaccessible because the flush control is on the closed side.

ST2

18 months

1.52.

Court Trustee's Office - 5th Floor

   

1.52.a.

The office is inaccessible because it can only be accessed by traversing stairs.

AR2

18 months

1.52.b.

The toilet room is inaccessible, and there is no signage directing persons with disabilities to the nearest accessible toilet rooms.

TR16

18 months

1.53.

Process Service Office - 5th Floor. The office is inaccessible because it can only be accessed by traversing stairs.

AR2

18 months

2.

City Hall, located at 701 N. 7th Street

   

2.1.

Parking. The parking reserved for persons with disabilities is inaccessible because the signs near the Health Department are mounted too low.

P6

24 months

2.2.

Rear Entrance Ramp. The ramp from Anne Street to the ground floor rear entrance is inaccessible because the bottom landing has a slope of approximately 4%, the middle landing has a slope of 3.4%, and the handrails lack sufficient extensions.

R5

24 months

2.3.

Rear Elevator

   

2.3.a.

The elevator is inaccessible because there is no hoistway signage provided.

E12

24 months

2.3.b.

The elevator is inaccessible because the visual car position indicator does not go out when a call is answered.

E4

24 months

2.4.

Main Building Elevator. The elevator is inaccessible because the hoistway signage is mounted 58½ inches above the finished floor.

E12

24 months

2.5.

Interior Signage. The signage provided is inaccessible because it is mounted on or above doors and does not have raised and Braille characters.

D26

24 months

2.6.

Lobby Information Counter. The counter protrudes into the walkway and is not detectable to blind persons using a cane.

AR8

24 months

2.7.

Lobby Hotline Telephone. The telephone protrudes into the walkway and is not detectable to blind persons using a cane.

AR8

24 months

2.8.

Ground Floor Drinking Fountain. The drinking fountain is inaccessible because the spout is 39 inches above the finished floor, the water flow is 4 inches from the front of the fountain, and the knee space is 20½ inches above the finished floor.

DF1, DF5

24 months

2.9.

2nd Floor Drinking Fountain near Clerk's Office. The drinking fountain protrudes into the walkway and is not detectable to blind persons using a cane.

AR8

24 months

2.10.

3rd, 4th, 6th and 9th Floor Drinking Fountains. The drinking fountains are inaccessible because they are mounted with the spouts 41 inches above the finished floor and provide inadequate knee space.

DF1, DF5

24 months

2.11.

5th Floor Drinking Fountain near Victims Services. The drinking fountain protrudes into the walkway and is not detectable to blind persons using a cane.

AR8

24 months

2.12.

4th Floor Snack Room. The turnstile food vending machine is inaccessible because the highest operable part is 65 inches above the finished floor.

TR5

24 months

2.13.

Lobby Telephone

   

2.13.a.

The telephone is inaccessible because the cord is 28 inches long and the telephone lacks volume control.

TT1

24 months

2.13.b.

The telephone protrudes into the walkway and is not detectable to blind persons using a cane.

AR8

24 months

2.14.

County Commission Chambers. The chamber is inaccessible to persons with hearing disabilities because, although there are 280 fixed seats, there is no assistive listening system provided. This room requires 12 receivers.

AA4

24 months

2.15.

2nd and 6th Floor Single-User Toilet Rooms

   

2.15.a.

The designated accessible toilet rooms are inaccessible because they require that a key be obtained while the other toilet rooms are kept unlocked.

M2

24 months

2.15.b.

The toilet room sign is mounted on the door and has no International Symbol of Accessibility.

TR17

24 months

2.15.c.

The door is inaccessible because it requires 10 pounds of force to open.

D2

24 months

2.15.d.

The paper towel dispenser protrudes into the walkway and is not detectable to blind persons using a cane.

AR8

24 months

2.15.e.

The toilet is inaccessible because its centerline is 20 inches from the side wall.

SU15

24 months

2.15.f.

The rear grab bar at the toilet is inaccessible because it is obstructed by the feminine products dispenser.

SU4

24 months

2.16.

Courtrooms 1 and 2 on 2nd Floor

   

2.16.a.

The door is inaccessible because it requires 10 pounds of force to open.

D2

24 months

2.16.b.

The courtrooms are inaccessible to persons with hearing disabilities because, although there are approximately 105 fixed seats in each courtroom, there is no assistive listening system provided. These rooms each require 5 receivers.

AA4

24 months

2.17.

2nd Floor Telephone

   

2.17.a.

The telephone is inaccessible because it lacks volume control.

TT1

24 months

2.17.b.

The telephone protrudes into the walkway and is not detectable to blind persons using a cane.

AR8

24 months

2.18.

Prosecutor's Office - 2nd Floor. The door is inaccessible because it requires 10 pounds of force to open.

D2

24 months

2.19.

Probation Office - 2nd Floor. The door is inaccessible because it requires 13 pounds of force to open.

D2

24 months

2.20.

Meeting/Training Room - 6th Floor. The counter is inaccessible because it is 42 inches above the finished floor.

C6

24 months

2.21.

Supplier Diversity Coordinator - 6th Floor. The door is inaccessible because knob hardware is used.

D1

24 months

2.22.

Purchasing Office - 6th Floor. The counter is inaccessible because it is 42 inches above the finished floor.

C6

24 months

2.23.

Public Works - Room 712. The counter protrudes into the walkway and is not detectable to blind persons using a cane.

AR8

24 months

2.24.

Receptionist for Development Department - Room 823

   

2.25.

The counter is inaccessible because it is 42 inches above the finished floor.

C6

24 months

2.26.

The door is inaccessible because it requires more than 5 pounds of force to open.

D2

24 months

2.27.

Mayor's Commission - 9th Floor. The counter protrudes into the walkway and is not detectable to blind persons using a cane.

AR8

24 months

3.

Public Health Center, located at 619 Ann Street

   

3.1.

Entrance Ramps. The ramps from the parking lot to the entrance are inaccessible because the handrails lack extensions.

R2

24 months

3.2.

Interior Signage. Much of the signage provided is inaccessible because it is mounted on or above doors and does not have raised and Braille characters.

D26

24 months

3.3.

City Health Office Room 104. The door is inaccessible because knob hardware is used.

D1

24 months

3.4.

Telephone - Lobby

   

3.4.a.

The telephone is inaccessible because the coin slot is 67½ inches above the finished floor.

TT1

24 months

3.4.b.

The telephone protrudes into the walkway and is not detectable to blind persons using a cane.

AR8

24 months

3.5.

Survey Box. The survey box next to the telephone protrudes into the walkway and is not detectable to blind persons using a cane.

AR8

24 months

3.6.

Cashier Office

   

3.6.a.

The door is inaccessible because it requires 12 pounds of force to open.

D2

24 months

3.6.b.

The door is inaccessible because knob hardware is used.

D1

24 months

3.7.

Registration Office. The door is inaccessible because knob hardware is used.

D1

24 months

3.8.

Office of Healthy Families and KS Healthy Start Room 145. The door is inaccessible because knob hardware is used.

D1

24 months

3.9.

Interior Accessible Route. The hand sanitizer dispensers in the North and South Waiting Rooms, the drinking fountain by room 108, and the 2nd Floor drinking fountain outside Vouchers protrude into the walkway and are not detectable to blind persons using a cane.

AR8

24 months

3.10.

General Clinic Room 164. The door is inaccessible because knob hardware is used.

D1

24 months

3.11.

East Elevator

   

3.11.a.

The elevator is inaccessible because the hall lanterns do not emit an audible signal indicating when a car is answering a call.

E11

24 months

3.11.b.

The elevator is inaccessible because the hoistway signage is mounted 52 inches above the finished floor.

E12

24 months

3.12.

West Elevator

   

3.12.a.

The elevator is inaccessible because the hall lanterns' audible signals do not distinguish between up and down.

E11

24 months

3.12.b.

The elevator is inaccessible because the hoistway signage is mounted 52 inches above the finished floor.

E12

24 months

3.13.

2nd Floor WIC Unisex Single-User Toilet Room

   

3.13.a.

No accessible coat hook has been provided.

TR1

24 months

3.13.b.

The lavatory is inaccessible because the top of the rim or counter is 35 inches above the finished floor.

TR11

24 months

3.13.c.

The lavatory is inaccessible because the hot water pipes are not insulated or otherwise configured to protect against contact.

TR12

24 months

3.13.d.

The side grab bar at the toilet is inaccessible because it is obstructed by the toilet paper dispenser, it is mounted 30½ inches above the finished floor, and it is mounted with 3 inches between the grab bar and the wall.

SU5

24 months

3.13.e.

The rear grab bar at the toilet is inaccessible because it is mounted 30½ inches above the finished floor, and it is mounted with 3 inches between the grab bar and the wall.

SU2

24 months

3.14.

2nd Floor WIC Women's Toilet Room with Stalls

   

3.14.a.

The door is inaccessible because it requires more than 5 pounds of force to open.

D2

24 months

3.14.b.

The pull side of the door, which is accessed from the hinge side of the door, is inaccessible because it has inadequate clear space on the latch side.

D8

24 months

3.14.c.

No accessible mirror has been provided.

TR14

24 months

3.14.d.

The feminine products dispenser protrudes into the walkway and is not detectable to blind persons using a cane.

AR8

24 months

3.14.e.

The lavatory is inaccessible because the hot water pipes are not insulated or otherwise configured to protect against contact.

TR12

24 months

3.14.f.

There is no accessible stall provided.

ST15

24 months

3.15.

2nd Floor Men's Toilet Room with Stalls

   

3.15.a.

The pull side of the door, which is accessed from the hinge side of the door, is inaccessible because it has only 9 inches of clear space on the latch side.

D8

24 months

3.15.b.

The urinal is inaccessible because the rim is 26 inches above the finished floor.

TR20

24 months

3.16.

Child Care Licensing and Registration - Room 210. The door is inaccessible because it requires 11 pounds of force to open.

D2

24 months

3.17.

Health Center Room 215. The door is inaccessible because it requires 15 pounds of force to open.

D2

24 months

4.

K.C.K. Fire Department No. 8

   

4.1.

Parking. The parking lot, with a total of fewer than 20 parking spaces, is inaccessible because it has no accessible parking space. This lot requires 1 van accessible space.

P3

12 months

5.

George C. Meyn Community Center, located at N. 126th Street and State Avenue

   

5.1.

Parking. The parking lot, with a total of 100 parking spaces, is inaccessible because the designated accessible spaces have no vertical signage, there is no van accessible space, and all but 2 of the access aisles are less than 60 inches wide throughout. This lot requires 1 van accessible space and 3 standard accessible spaces.

P3

18 months

5.2.

Entrances. The building does not have directional signage posted at inaccessible entrances and does not have the International Symbol of Accessibility posted at accessible entrances.

D16

18 months

5.3.

Lobby Drinking Fountain

   

5.3.a.

Although a designated accessible drinking fountain is provided, there is no drinking fountain provided for people who have difficulty bending or stooping.

DF3

18 months

5.3.b.

The wall-mounted drinking fountain is inaccessible because the clear floor space is blocked by the step stool.

DF5

18 months

5.4.

Women's Lobby Toilet Room with Stalls

   

5.4.a.

The toilet room sign is mounted on the door and has no raised or Braille characters.

TR18

18 months

5.4.b.

The doors are inaccessible because they have opening widths of only 29 inches for the outer door and 30½ inches for the inner door.

D25

18 months

5.4.c.

The outer door is inaccessible because it requires 7 pounds of force to open.

D2

18 months

5.4.d.

The wall mounted light fixture protrudes into the walkway and is not detectable to blind persons using a cane.

AR8

18 months

5.4.e.

Although an audible alarm is provided in this facility, there is no visual alarm appliance in the toilet room.

TR21

18 months

5.4.f.

No accessible mirror is provided.

TR14

18 months

5.4.g.

The air dryers protrude into the walkway and are not detectable to blind persons using a cane.

AR8

18 months

5.4.h.

The lavatory is inaccessible because the hot water pipes are not insulated or otherwise configured to protect against contact.

TR12

18 months

5.4.i.

The lavatory is inaccessible because it has twist-type hardware.

TR10

18 months

5.4.j.

There is no accessible toilet stall provided.

ST15

18 months

5.5.

Men's Lobby Toilet Room with Stalls

   

5.5.a.

The toilet room sign is mounted on the door and has no raised or Braille characters.

TR18

18 months

5.5.b.

The doors are inaccessible because they have opening widths of 29½ inches for the outer door and 29 inches for the inner door.

D25

18 months

5.5.c.

The outer door is inaccessible because it requires 9 pounds of force to open.

D2

18 months

5.5.d.

The pull side of the outer door, which is accessed through a front approach, is inaccessible because it has only 8 inches of clear space on the latch side.

D6

18 months

5.5.e.

The inner door is inaccessible because it requires 7 pounds of force to open.

D2

18 months

5.5.f.

The pull side of the inner door, which is accessed through a front approach, is inaccessible because it has only 9 inches of clear space on the latch side.

D6

18 months

5.5.g.

Although an audible alarm is provided in this facility, there is no visual alarm appliance in the toilet room.

TR21

18 months

5.5.h.

No accessible mirror is provided.

TR14

18 months

5.5.i.

The air dryer protrudes into the walkway and is not detectable to blind persons using a cane.

AR8

18 months

5.5.j.

The lavatory is inaccessible because the hot water pipes are not insulated or otherwise configured to protect against contact.

TR12

18 months

5.5.k.

There is no accessible toilet stall provided.

ST15

18 months

5.6.

Auditorium

   

5.6.a.

The double doors are inaccessible because each leaf is 30 inches wide.

D24

18 months

5.6.b.

There is no accessible route connecting the wheelchair seating areas and the stage.

AA1

18 months

5.7.

Kitchen. The door is inaccessible because it requires 11 pounds of force to open.

D2

18 months

5.8.

Meeting Room. The door is inaccessible because knob hardware is used.

D1

18 months

5.9.

Information Desk. The door is inaccessible because it has an opening width of 28 inches.

D25

18 months

5.10.

Playground. The route to the playground is inaccessible because the grass is not stable, firm, and slip resistant.

AR1

18 months

6.

Armourdale Recreation Center, located at 730 Osage Avenue

   

6.1.

Parking. The parking lot, with a total of 27 parking spaces, is inaccessible because the designated accessible spaces have no access aisles, there is no van accessible space, and the signs are mounted too low. This lot requires 1 van accessible space and 1 standard accessible space.

P3

24 months

6.2.

Curb Ramp. The curb ramp from the parking lot is inaccessible because it has a slope of more than 16.5% at the bottom.

AR5

24 months

6.3.

Entry Level Men's Toilet Room with Stalls

   

6.3.a.

The toilet room sign is mounted on the door and has no raised or Braille characters.

TR17

24 months

6.3.b.

The door is inaccessible because it requires more than 5 pounds of force to open.

D2

24 months

6.3.c.

The lavatory is inaccessible because the bottom of the apron is 24 inches above the finished floor.

TR11

24 months

6.3.d.

The urinal is inaccessible because the rim is 24¼ inches above the finished floor.

TR20

24 months

6.3.e.

There is no accessible stall provided.

ST15

24 months

6.4.

Entry Level Women's Toilet Room with Stalls

   

6.4.a.

The toilet room sign is mounted on the door and has no raised or Braille characters.

TR17

24 months

6.4.b.

The door is inaccessible because it requires more than 5 pounds of force to open.

D2

24 months

6.4.c.

The lavatory is inaccessible because the bottom of the apron is 23½ inches above the finished floor.

TR11

24 months

6.4.d.

There is no accessible stall provided.

ST15

24 months

6.5.

Entry Level Drinking Fountain. The drinking fountain is inaccessible because the spout is 42 inches above the finished floor, there is inadequate clear floor space and knee clearance, and the control requires more than 5 pounds of force to operate.

DF1

24 months

6.6.

Locker Rooms. The locker rooms contain a number of inaccessible elements and are not accessible to persons with disabilities.

LR4

24 months

6.7.

Wyco Lake Park, located at Leavenworth Road and 91st Street

   

6.8.

Ramp to Korean Vietnam Veteran's Memorial. The ramp is inaccessible because it has a cross slope of up to 5.9%, and it has no handrails.

R3

12 months

6.9.

Kiddie Park Parking. The parking lot is inaccessible because there are no designated accessible parking spaces.

P3

12 months

6.10.

Kiddie Park. The routes to the playground and picnic area are inaccessible because the grass is not stable, firm and slip resistant.

AR1

12 months

6.11.

Ranger Station Parking. The parking reserved for persons with disabilities is inaccessible because it lacks appropriate vertical signage.

P6

12 months

6.12.

Ranger Station Entrance. The door is inaccessible because knob hardware is used.

D1

12 months

6.13.

Men's Toilet Room with Stalls by Ranger Station

   

6.13.a.

The toilet room sign has no raised or Braille characters.

TR17

36 months

6.13.b.

The entrance door is inaccessible because there is a 1¼ inch high threshold.

D23

36 months

6.13.c.

The toilet stall is inaccessible because it is 57 inches wide.

ST16

36 months

6.13.d.

The toilet is inaccessible because its centerline is 19½ inches from the side wall.

ST17

36 months

6.13.e.

The toilet is inaccessible because the flush control is on the closed side.

ST2

36 months

6.13.f.

The rear grab bar at the toilet is inaccessible because it is mounted 15 inches from the side wall.

ST4

36 months

6.14.

Women's Toilet Room with Stalls by Ranger Station

   

6.14.a.

The toilet room sign has no raised or Braille characters.

TR17

36 months

6.14.b.

The entrance door is inaccessible because there is a 1 inch high threshold.

D23

36 months

6.14.c.

The designated accessible toilet stall is inaccessible because it is 57 inches wide.

ST16

36 months

6.14.d.

The designated accessible toilet is inaccessible because the top of the seat is 15 inches above the finished floor.

ST20

36 months

6.14.e.

The designated accessible toilet is inaccessible because its centerline is 19 inches from the side wall.

ST17

36 months

6.14.f.

The side grab bar at the designated accessible toilet is inaccessible because it is obstructed by the toilet paper dispenser.

ST8

36 months

6.15.

Chemical Sales Building Parking. The parking lot is inaccessible because there are no designated accessible parking spaces.

P3

12 months

6.16.

Chemical Sales Building Entrance

   

6.16.a.

The path to the entrance is inaccessible because it has a slope of up to 8.7% and it has no handrails.

R5

12 months

6.16.b.

The entrance is inaccessible because knob hardware is used.

D1

12 months

6.17.

Shelters. All of the shelters contain a number of inaccessible elements and are not accessible to persons with disabilities. At least 1 fully accessible shelter, with accessible routes, parking, toilet rooms, play areas, grills, etc., is required.

ST14

AR1

PD6

P3

12 months

6.18.

Marina Boat Rental Parking

   

6.18.a.

The parking lot is inaccessible because there is no van accessible space, and the designated accessible spaces have no access aisles.

P3

12 months

6.18.b.

The route from the parking lot to the toilet rooms is inaccessible because the slope is at least 15.6% and the gravel is not firm, stable, or slip resistant.

AR1, R5

12 months

6.19.

Marina Boat Rentals Men's Toilet Rooms with Stalls

   

6.19.a.

The toilet room sign is not mounted on the latch side of the door and has no raised or Braille characters.

TR17

12 months

6.19.b.

The air dryer protrudes into the walkway and is not detectable to blind persons using a cane.

AR8

12 months

6.19.c.

The lavatory is inaccessible because it has twist-type hardware.

TR10

12 months

6.19.d.

The urinal is inaccessible because the rim is 21 inches above the finished floor.

TR20

12 months

6.19.e.

The designated accessible toilet stall is inaccessible because it is 52 inches deep.

ST16

12 months

6.19.f.

The designated accessible toilet is inaccessible because the flush control is on the closed side.

ST2

12 months

6.19.g.

The side grab bar at the designated accessible toilet is inaccessible because it is 36 inches long.

ST7

12 months

6.19.h.

The rear grab bar at the designated accessible toilet is inaccessible because it is mounted 12 inches from the side wall.

ST4

12 months

6.20.

Marina Boat Rentals Women's Toilet Rooms with Stalls

   

6.20.a.

The toilet room sign is mounted above the door and has no raised or Braille characters.

TR17

12 months

6.20.b.

The air dryer protrudes into the walkway and is not detectable to blind persons using a cane.

AR8

12 months

6.20.c.

The designated accessible toilet stall is inaccessible because it is 52 inches deep.

ST16

12 months

6.20.d.

The side grab bar at the designated accessible toilet is inaccessible because it is 36 inches long.

ST7

12 months

6.20.e.

The rear grab bar at the designated accessible toilet is inaccessible because it is mounted 11 inches from the side wall.

ST4

12 months

6.21.

Marina Sailboat Launch Parking

   

6.21.a.

The parking lot, with a total of 21 parking spaces, is inaccessible because it only has no spaces designated as accessible. This lot requires 1 van accessible space.

P3

12 months

6.21.b.

The ramp from the parking lot to the toilet rooms is inaccessible because the slope is as much as 18.6%, there is no level landing at the top, there is a handrail on only part of one side, and the handrail does not have extensions or ends that are rounded or returned.

R5

12 months

6.22.

Marina Sailboat Launch Men's Toilet Room with Stalls

   

6.22.a.

The toilet room sign is mounted above the door and has no raised or Braille characters.

TR17

12 months

6.22.b.

The lavatory is inaccessible because it has twist-type hardware.

TR10

12 months

6.22.c.

The side grab bar at the toilet is inaccessible because it is mounted with the far end 46 inches from the rear wall.

ST7

12 months

6.23.

Marina Sailboat Launch Women's Toilet Room with Stalls

   

6.23.a.

The toilet room sign is mounted above the door and has no raised or Braille characters.

TR17

12 months

6.23.b.

The door is inaccessible because there is a 1 inch high threshold.

D23

12 months

6.23.c.

The lavatory is inaccessible because it has twist-type hardware.

D23

12 months

6.23.d.

The side grab bar at the designated accessible toilet is inaccessible because it is mounted with the far end 47 inches from the rear wall.

SU6

12 months

6.24.

James P. Davis Recreation Hall Parking. The parking lot is inaccessible because there are no access aisles and no vertical signs.

P3

12 months

6.25.

Davis Hall Entrance. The entrance is inaccessible because it contains steps and the temporary ramps have slopes of up to 19.3%, have no handrails, have inadequate edge protection, and are 29 inches wide.

AR2

12 months

6.26.

Davis Hall Coat Check Counter. The counter is inaccessible because it is 40 inches above the finished floor.

C6

12 months

6.27.

Davis Hall Drinking Fountain

   

6.27.a.

The drinking fountain is inaccessible because the flow of water is 2 inches high.

DF7

12 months

6.27.b.

The wall-mounted drinking fountain is inaccessible because it provides only 25½ inches of clear knee height.

DF5

12 months

6.27.c.

Although a designated accessible drinking fountain is provided, there is no drinking fountain provided for people who have difficulty bending or stooping.

DF3

12 months

6.28.

Davis Hall Meeting Rooms

   

6.28.a.

The meeting rooms are inaccessible because the entrances contain steps.

AR2

12 months

6.28.b.

There is no accessible route connecting the seating area and the stage.

AA1

12 months

6.29.

Davis Hall Men's Toilet Room with Stalls

   

6.29.a.

The sign is mounted above the door and has no raised or Braille characters.

TR17

12 months

6.29.b.

There is no accessible mirror provided.

TR14

12 months

6.29.c.

The lavatory is inaccessible because it provides only 26 inches of knee space height.

TR11

12 months

6.29.d.

The lavatory is inaccessible because it has twist-type faucets.

TR10

12 months

6.29.e.

The urinal is inaccessible because the rim is 19 inches above the finished floor.

TR20

12 months

6.29.f.

The designated accessible toilet is inaccessible because the flush control is on the closed side.

ST2

12 months

6.30.

The side grab bar at the designated accessible toilet is inaccessible because it is 36 inches long and it is mounted 14 inches from the rear wall.

ST7

12 months

6.31.

The rear grab bar at the designated accessible toilet is inaccessible because it is mounted 7 inches from the side wall.

ST4

12 months

6.32.

Davis Hall Women's Toilet Room with Stalls

   

6.32.a.

The sign is mounted above the door and has no raised or Braille characters.

TR17

12 months

6.32.b.

There is no accessible mirror provided.

TR14

12 months

6.32.c.

The lavatory is inaccessible because it provides only 26 inches of knee space height.

TR11

12 months

6.32.d.

The lavatory is inaccessible because it has twist-type faucets.

TR10

12 months

6.32.e.

The designated accessible toilet stall is inaccessible because it is 53 inches deep.

ST16

12 months

6.32.f.

The designated accessible toilet is inaccessible because the top of the seat is 16 inches above the finished floor.

ST20

12 months

6.32.g.

The designated accessible toilet is inaccessible because the flush control is on the closed side.

ST2

12 months

6.32.h.

The side grab bar at the designated accessible toilet is inaccessible because it is 36 inches long and it is mounted 13½ inches from the rear wall.

ST7

12 months

7.

Sunflower Hill Golf Course, located at N. 126th Street and Riverview Avenue in Bonner Springs

   

7.1.

Parking. The parking lot, with a total of 181 parking spaces, is inaccessible because it has no van accessible space, the designated accessible spaces have no access aisles, the vertical signs are mounted too low, and the designated accessible spaces are not level. This lot requires 1 van accessible space and 5 standard accessible spaces.

P3

24 months

7.2.

Clubhouse. There is no access to upper and lower levels of the facility for persons with mobility impairments.

AR9

24 months

7.3.

Clubhouse – Pro Shop

   

7.3.a.

The entrance bridge is inaccessible because it has a cross slope of up to 6.2%.

AR1

24 months

7.3.b.

The double entrance doors are inaccessible because each leaf is 27 inches wide.

D24

24 months

7.3.c.

The merchandise display for golf towels and club scrubbers protrudes into the walkway and is not detectable to blind persons using a cane.

AR8

24 months

7.3.d.

The counter is inaccessible because it is 41½ inches above the finished floor.

C5

24 months

7.4.

Clubhouse – Restaurant

   

7.4.a.

The route from parking to the entrance is inaccessible because it has a cross slope of up to 5.8%.

AR1

24 months

7.4.b.

The route from parking to the entrance is inaccessible because there is a 1¼ inch change in level at the bottom of the bridge ramp.

AR1

24 months

7.4.c.

The bridge ramp is inaccessible because the handrails are 41½ inches above the finished floor, they do not have a diameter between 1¼ and 1½ inches, and the ends lack extensions and are not rounded or returned.

R4

24 months

7.4.d.

The double entrance doors are inaccessible because each leaf is 28 inches wide.

D24

24 months

7.4.e.

The food service counter is inaccessible because it is 42 inches above the finished floor.

C5

24 months

7.5.

Clubhouse Lower Level Drinking Fountain

   

7.5.a.

The drinking fountain is inaccessible because it has a spout that is 39 inches above the finished floor.

DF6

24 months

7.5.b.

The drinking fountain protrudes into the walkway and is not detectable to blind persons using a cane.

AR8

24 months

7.6.

Clubhouse Lower Level Locker Rooms. The locker rooms contain a number of inaccessible elements and are not accessible to persons with disabilities.

LR4

24 months

7.7.

6th Hole Drinking Fountain. The drinking fountain protrudes into the walkway and is not detectable to blind persons using a cane.

AR8

24 months

7.8.

6th Hole Single User Toilet Rooms. The toilet rooms contain a number of inaccessible elements and are not accessible to persons with disabilities.

SU13

24 months

7.9.

9th Hole Drinking Fountain. The drinking fountain protrudes into the walkway and is not detectable to blind persons using a cane.

AR8

24 months

7.10.

9th Hole Single User Toilet Rooms. The toilet rooms contain a number of inaccessible elements and are not accessible to persons with disabilities.

SU13

24 months

8.

Fire Headquarters, located at 815 6th Street

   

8.1.

Entrances. The building does not have directional signage posted at the inaccessible entrance.

D16

12 months

9.

Police Headquarters, located at 7th and Minnesota Avenue

   

9.1.

Main Level Women's Single-User Toilet Room

   

9.1.a.

The door is inaccessible because it requires 6 pounds of force to open.

D2

12 months

9.1.b.

No accessible coat hook has been provided.

TR1

12 months

9.1.c.

The lavatory is inaccessible because the bottom of the apron is 27¼ inches above the finished floor.

TR11

12 months

9.1.d.

The paper towel dispenser protrudes into the walkway and is not detectable to blind persons using a cane.

AR8

12 months

9.2.

Main Level Men's Single-User Toilet Room

   

9.2.a.

The door is inaccessible because it requires 10 pounds of force to open.

D2

12 months

9.2.b.

The lavatory is inaccessible because the bottom of the apron is 27½ inches above the finished floor.

TR11

12 months

9.2.c.

The toilet is inaccessible because the flush control is on the closed side.

SU1

12 months

9.2.d.

The toilet paper dispenser is inaccessible because it is mounted 44 inches from the rear wall.

SU17

12 months

9.2.e.

The side grab bar at the toilet is inaccessible because it is obstructed by the toilet paper dispenser.

SU7

12 months

9.2.f.

The paper towel dispenser protrudes into the walkway and is not detectable to blind persons using a cane.

AR8

12 months

9.3.

Lobby Drinking Fountain

   

9.3.a.

The drinking fountain protrudes into the walkway and is not detectable to blind persons using a cane.

AR8

12 months

9.3.b.

Although an accessible drinking fountain is provided, there is no drinking fountain provided for people who have difficulty bending or stooping.

DF3

12 months

10.

Bethany Recreation Center, located at 1120 Central Avenue

   

10.1.

Entrances. The building does not have directional signage posted at inaccessible entrances and does not have the International Symbol of Accessibility posted at accessible entrances.

D16

18 months

10.2.

Lower Level Unisex Single-User Toilet Room

   

10.2.a.

The toilet room does not have a sign with the International Symbol of Accessibility.

TR17

18 months

10.2.b.

The side grab bar is inaccessible because it is obstructed by the baby changing station. ST9

 18 months

10.3.

Lower Level Drinking Fountain. Although a designated accessible drinking fountain is provided, there is no drinking fountain provided for people who have difficulty bending or stooping.

DF3

18 months

10.4.

Upper Level Toilet Rooms. There is no signage directing persons with disabilities to the accessible toilet room.

TR16

18 months

10.5.

Men's Locker Room [Note: No Women's Locker Room is Provided]

   

10.5.a.

The locker room sign is mounted on the door and has no raised or Braille characters.

TR18

18 months

10.5.b.

The door is inaccessible because it requires 20 pounds of force to open.

D2

18 months

10.5.c.

The pull side of the door, which is accessed through a front approach, is inaccessible because it has only 2 inches of clear space on the latch side.

D6

18 months

10.5.d.

No accessible mirror has been provided.

TR14

18 months

10.5.e.

There is no accessible toilet stall provided.

ST15

18 months

10.5.f.

There is no accessible shower provided.

B8

18 months

10.5.g.

The bench is inaccessible because it is 11 inches deep and is not attached to the wall.

LR1

18 months

10.5.h.

No accessible towel hook has been provided.

TR1

18 months

11.

Wyandotte County Park, located at State Avenue and 126th Street

   

11.1.

Shelter L Parking. The parking lot is inaccessible because it has no designated accessible parking spaces.

P3

24 months

11.2.

Shelter L Play Equipment. There is no accessible route to the play equipment.

AR1

24 months

11.3.

Shelter L Picnic Pavilion. The picnic tables are inaccessible because none provide the required knee space.

PD6

24 months

11.4.

Shelter L Men's Toilet Room

   

11.4.a.

The toilet room sign has no raised or Braille characters.

TR17

24 months

11.4.b.

The door is inaccessible because it has an opening width of only 29 inches.

D25

24 months

11.4.c.

The lavatory is inaccessible because it has twist-type hardware.

TR10

24 months

11.4.d.

The urinal is inaccessible because the rim is 22 inches above the finished floor.

TR20

24 months

11.4.e.

The urinal is inaccessible because the flush control requires twisting of the wrist to operate.

TR3

24 months

11.4.f.

There is no accessible toilet stall provided.

ST15

24 months

11.5.

Shelter L Women's Toilet Room

   

11.5.a.

The toilet room sign has no raised or Braille characters.

TR17

24 months

11.5.b.

The door is inaccessible because it has an opening width of only 29 inches.

D25

24 months

11.5.c.

The lavatory is inaccessible because the bottom of the apron is 27 inches above the finished floor.

TR11

24 months

11.5.d.

The lavatory is inaccessible because it has twist-type hardware.

TR10

24 months

11.5.e.

There is no accessible toilet stall provided.

ST15

24 months

11.6.

Shelter C Parking. The parking lot is inaccessible because it has no designated accessible parking spaces.

P3

24 months

11.7.

Shelter C Play Equipment. There is no accessible route to the play equipment.

AR1

24 months

11.8.

Shelter C Picnic Pavilion

   

11.8.a.

The route to the pavilion is inaccessible because it slopes more than 5% but has no ramp features.

AR1

24 months

11.8.b.

The picnic tables are inaccessible because none provide the required knee space.

PD6

24 months

11.9.

Shelter C Toilet Rooms

   

11.9.a.

The doors are inaccessible because there are slopes of 12.3% (men's) and 10.5% (women's) within the doors' required maneuvering clearance.

D13

24 months

11.9.b.

Both toilet rooms were locked and could not be surveyed.

ST14

24 months

11.10.

Shelter J Parking. The parking lot is inaccessible because it has no designated accessible parking spaces.

P3

24 months

11.11.

Shelter J Play Equipment. There is no accessible route to the play equipment.

AR1

24 months

11.12.

Shelter J Picnic Pavilion

   

11.12.a.

The route to the pavilion is inaccessible because there is a 1½ inch change in level at the entrance to the pavilion.

AR1

24 months

11.12.b. 

The picnic tables are inaccessible because none provide the required knee space.

PD6

24 months

11.13.

Shelter J Men's Toilet Room

   

11.13.a. 

The toilet room sign is mounted more than 60 inches above the finished floor and has no raised or Braille characters.

TR17

24 months

11.13.b. 

The door is inaccessible because there is a 2 inch high threshold.

D23

24 months

11.13.c. 

The lavatory is inaccessible because the bottom of the apron is 27 inches above the finished floor.

TR11

24 months

11.13.d. 

The lavatory is inaccessible because it has twist-type hardware.

TR10

24 months

11.13.e. 

The urinal is inaccessible because the rim is 24 inches above the finished floor.

TR20

24 months

11.13.f. 

There is no accessible toilet stall provided.

ST15

24 months

11.14.

Shelter J Women's Toilet Room

   

11.14.a. 

The toilet room sign is mounted more than 60 inches above the finished floor and has no raised or Braille characters.

TR17

24 months

11.14.b. 

The lavatory is inaccessible because the bottom of the apron is 27 inches above the finished floor.

TR11

24 months

11.14.c. 

The lavatory is inaccessible because it has twist-type hardware.

TR10

24 months

11.14.d. 

There is no accessible toilet stall provided.

ST15

24 months

11.15.

Tennis Court Parking Near Shelter J. The parking lot is inaccessible because it has no designated accessible parking spaces.

P3

24 months

11.16.

Tennis Court Near Shelter J. The route from the parking lot to the tennis court is inaccessible because it has a slope of up to 14.2%, and it has no ramp features.

AR1, R5

24 months

11.17.

Playground Near Shelter J. The sidewalk to the playground is inaccessible because it does not contain any passing spaces, it has a 2 inch change of level where it meets the parking lot, it has cross slopes of up to 6.2%, and it has slopes of 8.8% with no ramp features.

AR1, R5

24 months

11.18.

Shelter D Parking. The parking lot is inaccessible because it has no designated accessible parking spaces.

P3

24 months

11.19.

Shelter D Play Equipment. There is no accessible route to the play equipment.

AR1

24 months

11.20.

Shelter D Men's Toilet Room

   

11.20.a. 

The toilet room sign has no raised or Braille characters.

TR17

24 months

11.20.b. 

The door is inaccessible because there is a slope of 22% within the door's required maneuvering clearance.

D13

24 months

11.20.c. 

The door is inaccessible because it has an opening width of only 29 inches.

D25

24 months

11.20.d. 

The lavatory is inaccessible because it has twist-type hardware.

TR10

24 months

11.20.e. 

The urinal is inaccessible because the rim is 23 inches above the finished floor and the flush control is 45 inches above the finished floor.

TR20

24 months

11.20.f. 

There is no accessible toilet stall provided.

ST15

24 months

11.21.

Shelter D Women's Toilet Room

   

11.21.a. 

The toilet room sign is mounted more than 60 inches above the finished floor and has no raised or Braille characters.

TR17

24 months

11.21.b. 

The door is inaccessible because there is a slope of 14.4% within the door's required maneuvering clearance.

D13

24 months

11.21.c. 

The door is inaccessible because it has an opening width of only 29 inches.

D25

24 months

11.21.d. 

The lavatory is inaccessible because it has twist-type hardware.

TR10

24 months

11.21.e. 

There is no accessible toilet stall provided.

ST15

24 months

11.22.

Museum Parking. The parking lot is inaccessible because the designated accessible spaces are less than 96 inches wide, have no access aisles, and have vertical signs that are mounted too low.

P3

24 months

11.23.

Museum Entrance. The double-leaf entrance door is inaccessible because there is a slope of 3.4%.

D13

24 months

11.24.

Museum Women's Toilet Rooms with Stalls

   

11.24.a. 

The toilet room sign is mounted on the door.

TR18

24 months

11.24.b. 

The door is inaccessible because it requires 9 pounds of force to open.

D2

24 months

11.24.c. 

The designated accessible toilet is inaccessible because the flush control is on the closed side.

ST2

24 months

11.24.d. 

The rear grab bar at the designated accessible toilet is inaccessible because it is mounted 11½ inches from the side wall.

ST4

24 months

11.25.

Museum Men's Toilet Rooms with Stalls

   

11.25.a. 

The toilet room sign is mounted on the door.

TR18

24 months

11.25.b. 

The door is inaccessible because it requires 9 pounds of force to open.

D2

24 months

11.25.c. 

The rear grab bar at the designated accessible toilet is inaccessible because it is mounted 11½ inches from the side wall.

ST4

24 months

12.

Parking Garage C, located at North 7th and Armstrong Avenue

   

12.1.

Parking. The parking is inaccessible because it there is no van accessible parking space, the vertical clearance is 84 inches high, two of the designated accessible spaces on Level G have vertical signs that are mounted too low, the designated accessible spaces on Level 1 have a cross slope of 4.5%, the designated accessible spaces on Level 2 have signs mounted too low and have cross slopes of 4%, and the designated accessible spaces on Level 3 have cross slopes of 3.8%.

P3

18 months

12.2.

Elevator

   

12.2.a.

The elevator is inaccessible because the call buttons are mounted 52 inches above the finished floor.

E3

18 months

12.2.b.

The elevator is inaccessible because the hall lanterns' audible signals do not differentiate between up and down.

E11

18 months

12.2.c.

The elevator is inaccessible because it lacks hoistway signage.

E12

18 months

12.2.d.

The elevator is inaccessible because the highest car control button is 57½ inches above the finished floor, the buttons lack raised and Braille characters, the main floor is not designated by a raised star, and the emergency controls are not grouped at the bottom of the panel.

E4

18 months

12.2.e.

The elevator is inaccessible because the car position does not ring as the car passes or stops on floors.

E5

18 months

12.3.

Bridge to Minnesota Avenue. The ramp is inaccessible because there is no handrail provided between 34 and 38 inches above the finished floor, the handrails lack extensions, and the diameter of the gripping surface is not between 1¼ and 1½ inches.

R4

18 months

12.4.

Lower Ramp to Minnesota Avenue. The ramp is inaccessible because it has a handrail on only one side.

R4

18 months

13.

Parking Lot A, located at 741 Nebraska

   

13.1.

Parking. The van accessible parking spaces are inaccessible because the route to them has a vertical clearance of 85 inches.

P9

18 months

13.2.

Elevator. The elevator was broken, providing no access to upper and lower levels of the facility for people with mobility impairments.

AR9, M1

18 months

14.

Fire Station 20, located at 7741 Kansas Avenue

   

14.1.

Parking. The parking lot, with a total of approximately 3 parking spaces, is inaccessible because there is no designated accessible parking. This lot requires 1 van accessible space.

P3

12 months

14.2.

Blood Pressure Screening Entrance

   

14.2.a.

The door is inaccessible because there is a 1¼ inch high threshold.

D23

12 months

14.2.b.

The door is inaccessible because knob hardware is used.

D1

12 months

15.

Fire Station 16, located at 1437 South 55th Street

   

15.1.

Entrance

   

15.1.a.

The door is inaccessible because there is a 1¼ inch high threshold.

D23

12 months

15.1.b.

The door is inaccessible because knob hardware is used.

D1

12 months

16.

Fire Station 17, located at 2416 South 51st Street

   

16.1.

Parking. The parking lot, with fewer than 25 parking spaces, is inaccessible because there is no designated accessible parking. This lot requires 1 van accessible space.

P3

12 months

16.2.

Route to Blood Pressure Screening Room. The route is inaccessible because the edge of the parking lot has a slope of 10.7%, the concrete slab has a cross slope of 3.7%, and the driveway has a slope of 5.7% with no ramp features.

AR1

12 months

17.

Pierson Park, located at South 55th and Douglas Avenue

   

17.1.

Shelter 1 Parking. The parking lot is inaccessible because there is no designated accessible parking.

P3

24 months

17.2.

Shelter 1 Picnic Pavilion

   

17.2.a.

The route to the pavilion is inaccessible because there are slopes of 6.6.% as the path goes down and 6.1% as the path goes up, with no ramp features.

AR1

24 months

17.2.b.

The picnic tables are inaccessible because none provide the required knee space.

PD6

24 months

17.3.

Shelter 1 Women's Toilet Rooms with Stalls

   

17.3.a.

The toilet room sign has no raised or Braille characters.

TR17

24 months

17.3.b.

The door is inaccessible because it has an opening width of only 29 inches.

D25

24 months

17.3.c.

The lavatory is inaccessible because it has twist type faucets.

TR10

24 months

17.3.d.

There is no accessible toilet stall provided.

ST15

24 months

17.4.

Shelter 1 Men's Toilet Rooms with Stalls

   

17.4.a.

The toilet room sign has no raised or Braille characters.

TR17

24 months

17.4.b.

The door is inaccessible because it has an opening width of only 29 inches.

D25

24 months

17.4.c.

The lavatory is inaccessible because it has twist type faucets.

TR10

24 months

17.4.d.

The urinal is inaccessible because the rim is 19 inches above the finished floor.

TR20

24 months

17.4.e.

There is no accessible toilet stall provided.

ST15

24 months

17.5.

Playground and Tennis Court Parking Near Shelter 1. The parking lot is inaccessible because there is no designated accessible parking.

P3

24 months

17.6.

Playground and Tennis Court Parking Near Shelter 1. The route to this area is inaccessible because insufficient passing space is provided.

AR1

24 months

17.7.

Skate Park Parking. The parking lot is inaccessible because there is no designated accessible parking.

P3

24 months

17.8.

Skate Park Toilet Rooms

   

17.8.a.

The route to the Women's toilet room is inaccessible because it has a cross slope of up to 6.5% and a slope of up to 13.7%, and the curb is 2½ inches high with no curb ramp.

AR1, R5

24 months

17.8.b.

The Men's toilet room door is inaccessible because there is a 1 inch high threshold.

D23

24 months

17.8.c.

Both toilet rooms were locked and could not be surveyed.

ST14

24 months

17.9.

Route to Skate Park. The route is inaccessible because it is only 27 inches wide past the wheel stop.

AR3

24 months

17.10.

Skate Park Picnic Tables. The picnic tables are inaccessible because none provide the required knee space.

PD6

24 months

17.11.

Shelter 2 Parking. The parking lot is inaccessible because there is no designated accessible parking.

P3

24 months

17.12.

Shelter 2. The picnic tables are inaccessible because none provide the required knee space.

PD6

24 months

17.13.

Shelter 2 Women's Toilet Room with Stalls

   

17.13.a. 

No accessible signage is provided.

TR17

24 months

17.13.b. 

The door is inaccessible because it has an opening width of only 29 inches.

D25

24 months

17.13.c. 

The lavatory is inaccessible because it has twist type faucets.

TR10

24 months

17.13.d. 

There is no accessible toilet stall provided.

ST15

24 months

17.14.

Shelter 2 Men's Toilet Room with Stalls

   

17.14.a. 

No accessible signage is provided.

TR17

24 months

17.14.b. 

The door is inaccessible because it has an opening width of only 29 inches.

D25

24 months

17.14.c. 

The lavatory is inaccessible because it has twist type faucets.

TR10

24 months

17.14.d. 

The urinal is inaccessible because the rim is more than 17 inches above the finished floor.

TR20

24 months

17.14.e. 

There is no accessible toilet stall provided.

ST15

24 months

17.15.

Pierson Community Center Parking. The parking lot, with a total of 102 parking spaces, is inaccessible because it has 2 designated accessible spaces, these spaces have no access aisles and no vertical signs, and one of them has a cross slope of 7.1%. This lot requires 1 van accessible space and 4 standard accessible spaces.

P3

24 months

17.16.

Route to Pierson Community Center. The route from the parking lot to the entrance is inaccessible because it has a slope of 15.1% near the parking lot and 10.8% further along the sidewalk.

AR1, R5

24 months

17.17.

Pierson Community Center Lobby Office. The door is inaccessible because knob hardware is used.

D1

24 months

17.18.

Pierson Community Center Lobby Drinking Fountain

   

17.18.a.

Although 2 drinking fountains are provided, neither is accessible. One fountain has a spout that is mounted more than 36 inches above the finished floor, and the other fountain has water flow that is less than 4 inches high and provides only 24½ inches of knee space height.

DF1, DF5

24 months

17.18.b.

The higher drinking fountain protrudes into the walkway and is not detectable to blind persons using a cane.

AR8

24 months

17.19.

Pierson Community Center Women's Locker Room

   

17.19.a. 

The locker room sign is mounted on the door and has no raised or Braille characters.

TR18

24 months

17.19.b. 

The door is inaccessible because it requires 10 pounds of force to open.

D2

24 months

17.19.c. 

No accessible mirror is provided.

TR14

24 months

17.19.d. 

The air dryer protrudes into the walkway and is not detectable to blind persons using a cane.

AR8

24 months

17.19.e. 

No accessible coat hook is provided.

TR1

24 months

17.19.f. 

The side grab bar at the designated accessible toilet is inaccessible because it is mounted 32 inches above the finished floor.

ST12

24 months

17.19.g. 

There is no rear grab bar provided at the designated accessible toilet.

ST3

24 months

17.20.

Pierson Community Center Men's Locker Room

   

17.20.a. 

The locker room sign is mounted on the door and has no raised or Braille characters.

TR18

24 months

17.20.b. 

The door is inaccessible because it requires 10 pounds of force to open.

D2

24 months

17.20.c. 

No accessible mirror is provided.

TR14

24 months

17.20.d. 

The air dryer protrudes into the walkway and is not detectable to blind persons using a cane.

AR8

24 months

17.20.e. 

The designated accessible toilet is inaccessible because its centerline is 16½ inches from the side wall.

ST17

24 months

17.20.f. 

No accessible coat hook is provided.

TR1

24 months

17.20.g. 

The side grab bar at the designated accessible toilet is inaccessible because it is mounted 32¼ inches above the finished floor.

ST12

24 months

17.20.h. 

There is no rear grab bar provided at the designated accessible toilet.

ST3

24 months

17.21.

Pierson Community Center Kitchen. The door is inaccessible because knob hardware is used.

D1

24 months

18.

City Park, located at City Park Drive and South Grandview Boulevard

   

18.1.

Baseball Field Parking Near Park Drive. The parking lot is inaccessible because there are no designated accessible spaces.

P3

24 months

18.2.

Routes from Baseball Field Parking. The routes from the parking lot to the closest baseball field, playground, and toilet room are inaccessible because the gravel surface is not firm, stable, and slip resistant.

AR1

24 months

18.3.

Baseball Field Drinking Fountain. There is no accessible drinking fountain provided.

DF1

24 months

18.4.

Baseball Field Toilet Rooms with Stalls. The toilet rooms contain a number of inaccessible elements and are not accessible to persons with disabilities.

ST14

24 months

18.5.

Regan Field Parking. The parking lot, with a total of 18 parking spaces, is inaccessible because there are no designated accessible parking spaces. This lot requires 1 van accessible space.

P3

24 months

18.6.

Routes from Regan Field Parking. There are no accessible routes from the parking lot to the pavilion, playground, and baseball field.

AR1

24 months

18.7.

Regan Field Drinking Fountain

   

18.7.a.

Although an accessible drinking fountain is provided, there is no drinking fountain provided for people who have difficulty bending or stooping.

DF3

24 months

18.7.b.

The drinking fountain protrudes into the walkway and is not detectable to blind persons using a cane.

AR8

24 months

18.8.

Soccer Field Parking. The parking lot is inaccessible because there are no designated accessible spaces.

P3

24 months

18.9.

Hilltop Playground Parking. The parking lot is inaccessible because there are no designated accessible spaces.

P3

24 months

18.10.

Hilltop Playground. There is no accessible route from the parking lot to the playground.

AR1

24 months

19.

Kensington Recreation Center, located at 2924 State Avenue

   

19.1.

Lower Parking Lot. The parking lot, with a total of 62 parking spaces, is inaccessible because it has only 2 designated accessible parking spaces. This lot requires 1 van accessible space and 2 standard accessible spaces.

P3

24 months

19.2.

Route from Lower Lots to Lower Park. The route is inaccessible because there is a change in level greater than ½ inch at the curb, and there is no firm, stable, and slip resistant surface along the route.

AR1

24 months

19.3.

Craft Building Parking. The parking lot, with a total of 24 parking spaces, is inaccessible because the designated accessible spaces have no access aisles and no vertical signage, and the spaces have a cross slope of 5.1%. This lot requires 1 van accessible space.

P3

24 months

19.4.

Entrances. The entrances are inaccessible because there is a slope of 2.6% within the doors' required maneuvering clearance.

D13

24 months

19.5.

Ramp From Craft Room. The ramp is inaccessible because it has a slope of 16.7%, it lacks adequate edge protection, it has a handrail on only one side, and the handrail ends lack extensions and are not rounded or returned.

R5

24 months

19.6.

Women's Toilet Rooms with Stalls

   

19.6.a.

The toilet room sign is mounted on the door and has no raised or Braille characters.

TR18

24 months

19.6.b.

The door is inaccessible because it requires more than 5 pounds of force to open.

D2

24 months

19.6.c.

The pull side of the door, which is accessed through a front approach, is inaccessible because there are 4 inches of maneuvering clearance on the latch side.

D6

24 months

19.6.d.

Although an audible alarm is provided in this facility, there is no visual alarm appliance in the toilet room.

TR21

24 months

19.6.e.

No accessible mirror has been provided.

TR14

24 months

19.6.f.

The lavatory is inaccessible because the top of the rim or counter is 37 inches above the finished floor.

TR11

24 months

19.6.g.

The lavatory is inaccessible because the hot water pipes are not insulated or otherwise configured to protect against contact.

TR12

24 months

19.6.h.

The designated accessible toilet stall is inaccessible because it is 43 inches wide.

ST16

24 months

19.6.i.

The designated accessible toilet is inaccessible because its centerline is 21½ inches from the side wall.

ST17

24 months

19.6.j.

The designated accessible toilet is inaccessible because the flush control is on the closed side.

ST2

24 months

19.6.k.

No accessible coat hook has been provided.

TR1

24 months

19.6.l.

The rear grab bar at the designated accessible toilet is inaccessible because it is 30 inches long.

ST4

24 months

19.6.m.

The rear grab bar at the designated accessible toilet is inaccessible because it is mounted 38½ inches above the finished floor.

ST12

24 months

19.7.

Men's Toilet Rooms with Stalls. The toilet room contains a number of inaccessible elements and is not accessible to persons with disabilities.

ST14

24 months

19.8.

Drinking Fountain

   

19.8.a.

The drinking fountain is inaccessible because it has a spout that is 39 inches above the finished floor.

DF6

24 months

19.8.b.

The free-standing drinking fountain is inaccessible because it does not provide clear floor space.

DF4

24 months

19.9.

Upper General Room. The mantle above the fireplace protrudes into the walkway and is not detectable to blind persons using a cane.

AR8

24 months

19.10.

Ball Court Parking. The parking lot, with a total of 46 parking spaces, is inaccessible because it has no van accessible parking space, and the designated accessible spaces have no vertical signage and have slopes of between 6% and 8.4%. This lot requires 1 van accessible space and 1 standard accessible space.

P3

24 months

19.11.

Routes from Ball Court Parking. The routes are inaccessible because the drain gutter obstructs access to the baseball spectator area, and there is no accessible route to the toilet rooms and drinking fountain are not firm, stable, and slip resistant.

AR1

24 months

20.

Parkwood Park, located at 950 Quindaro Boulevard

   

20.1.

Mid-Park Parking. The parking lot is inaccessible because there is no designated accessible parking.

P3

24 months

20.2.

Route from Mid-Park Parking. There is no accessible route from the parking lot to the toilet rooms and playground.

AR1

24 months

20.3.

Mid-Park Toilet Rooms with Stalls. The toilet rooms contain a number of inaccessible elements and are not accessible to persons with disabilities.

ST14

24 months

20.4.

Pool Parking. The parking lot is inaccessible because there is no designated accessible parking.

P3

24 months

20.5.

Pool Building. There is no access to the pool level of the facility for persons with mobility impairments.

AR9

24 months

21.

Fire Station #4 – Exterior Only, located at 3056 North 81st Street

   

21.1.

Parking. The parking lot is inaccessible because there is no designated accessible parking.

P3

12 months

22.

Fire Station #18, located at 5424 Leavenworth Road

   

22.1.

Parking. The parking lot is inaccessible because there is no designated accessible parking.

P3

12 months

23.

Fire Station #19 located at 1000 North 80th Terrace

   

23.1.

Parking. The parking lot is inaccessible because there is no designated accessible parking.

P3

12 months

24.

Argentine Recreation Center, located at 2810 Metropolitan Avenue

   

24.1.

East Parking Lot

   

24.1.a.

The parking lot, with a total of 26 parking spaces, is inaccessible because the designated accessible parking spaces have no access aisles, there is no van accessible space, and one of the signs is mounted too low. This lot requires 1 van accessible space and 1 standard accessible space.

P3

24 months

24.1.b.

The curb ramp is inaccessible because the flared sides have a slope of more than 10%.

AR5

24 months

24.2.

Entrance Ramp from North Parking Lot. The ramp is inaccessible because it has a cross-slope of 3% near the middle, it has a handrail on only one side, and none at the top, and the ends of the existing handrail lack extensions and are not rounded or returned.

R3

24 months

24.2.a.

Drinking Fountains. Although accessible drinking fountains are provided, there is no drinking fountain provided for people who have difficulty bending or stooping.

DF3

24 months

24.3.

Women's Locker Room

   

24.3.a.

The air dryer protrudes into the walkway and is not detectable to blind persons using a cane.

AR8

24 months

24.3.b.

There is no accessible stall provided.

ST15

24 months

24.3.c.

No accessible towel hook has been provided.

TR1

24 months

24.3.d.

There is no accessible locker provided.

LR3

24 months

24.4.

Men's Locker Room

   

24.4.a.

There is no accessible stall provided.

ST15

24 months

24.4.b.

No accessible towel hook has been provided.

TR1

24 months

24.4.c.

There is no accessible locker provided.

LR3

24 months

25.

Building B, located at 1300 N. 78th Street

   

25.1.

Ground Entrance Parking. The parking lot is inaccessible because the signs are mounted too low and the designated accessible parking spaces and access aisle have cross-slopes of 3.8% to 6%.

P3

24 months

25.2.

Entrances

   

25.2.a.

The building does not have directional signage posted at inaccessible entrances and does not have the International Symbol of Accessibility posted at accessible entrances.

D16

24 months

25.2.b.

The ground floor entrance ramp is inaccessible because it lacks edge protection, it lacks a level landing at the bottom, it has a handrail on only one side, and the handrail lacks extensions.

R3

24 months

25.3.

Elevator

   

25.3.a.

The elevator is inaccessible because it has no hall lanterns.

E11

24 months

25.3.b.

The elevator is inaccessible because there is no hoistway signage provided.

E12

24 months

25.3.c.

The elevator is inaccessible because the car control buttons are not raised or flush, they do not have raised and Braille characters, the button for the main entry floor is not designated by a raised star, the buttons have no visual indicators to register calls, and the highest button is more than 54 inches above the finished floor.

E4

24 months

25.3.d.

The elevator is inaccessible because it has no car position indicators.

E5

24 months

25.4.

Area Agency on Aging. The door is inaccessible because knob hardware is used.

D1

24 months

26.

Building A, located at 8200 State Avenue

   

26.1.

West Parking Lot. The parking lot is inaccessible because the van accessible parking space is 91 inches wide with a 55 inch wide access aisle, the other access aisle is 55 inches wide, and one of the designated accessible spaces has no access aisle.

P3

24 months

26.2.

Women's Lobby Toilet Room with Stalls

   

26.2.a.

The toilet room sign is mounted on the door.

TR18

24 months

26.2.b.

The designated accessible toilet is inaccessible because the flush control is on the closed side.

ST2

24 months

26.2.c.

The side grab bar at the designated accessible toilet is inaccessible because it is obstructed by the toilet paper dispenser.

ST8

24 months

26.2.d.

The side grab bar at the designated accessible toilet is inaccessible because it is mounted with the far end 48 inches from the rear wall.

ST7

24 months

26.2.e.

There is no rear grab bar provided at the designated accessible toilet.

ST3

24 months

26.3.

Men's Lobby Toilet Room with Stalls

   

26.3.a.

The toilet room sign is mounted on the door.

TR18

24 months

26.3.b.

The urinal is inaccessible because the rim is 20 inches above the finished floor.

TR20

24 months

26.3.c.

No accessible coat hook has been provided.

TR1

24 months

26.3.d.

The side grab bar at the designated accessible toilet is inaccessible because it is obstructed by the toilet paper dispenser.

ST8

24 months

26.3.e.

The side grab bar at the designated accessible toilet is inaccessible because it is mounted 13 inches from the rear wall.

ST7

24 months

26.3.f.

There is no rear grab bar provided at the designated accessible toilet.

ST3

24 months

26.4.

Elevator

   

26.4.a.

The elevator is inaccessible because the hall lanterns signal once for both up and down and there is no visual hall arrival signal.

E11

24 months

26.4.b.

The elevator is inaccessible because it lacks car position indicators.

E5

24 months

27.

Police Station, Division 3, located at 2151 South 34th Street

   

27.1.

Route to Entrance. The route from the parking area to the door is inaccessible because there are steps preventing access to the doorbell.

AR1

12 months

28.

Fire Station #2, located at 6241 State Avenue

   

28.1.

Parking. The parking lot, with a total of approximately 12 parking spaces, is inaccessible because there are no designated accessible parking spaces. This lot requires 1 van accessible space.

P3

12 months

28.2.

Route to East Entrance. The route is inaccessible because the slope of the curb cut is 15.8%.

AR5

12 months

28.3.

Entrances. The building does not have directional signage posted at inaccessible entrances and does not have the International Symbol of Accessibility posted at accessible entrances.

D16

12 months

29.

Pat Hanlon Center, located at 1101 Ridge Avenue

   

29.1.

Parking. The parking lot, with a total of 6 parking spaces, is inaccessible because there are no designated accessible parking spaces. This lot requires 1 van accessible space.

P3

24 months

29.2.

Exterior Routes

   

29.2.a.

There is no accessible route from the parking lot to the building entrance.

AR1

24 months

29.2.b.

The ramp to the entrance is inaccessible because the slope is 15.7 %, the ramp lacks level landings at the top and bottom, the handrails are mounted between 31 and 32 inches above the finished floor, and the handrail ends lack extensions and are not rounded or returned.

R5

24 months

29.3.

Men's Toilet Room with Stalls

   

29.3.a.

The toilet room sign is not mounted on the latch side of the door and has no raised or Braille characters.

TR18

24 months

29.3.b.

The door is inaccessible because it has an opening width of only 29 inches.

D25

24 months

29.3.c.

The pull side of the door, which is accessed through a front approach, is inaccessible because it has insufficient clear space on the latch side.

D6

24 months

29.3.d.

The lavatory is inaccessible because it lacks knee and toe clearance.

TR11

24 months

29.3.e.

The urinal is inaccessible because the flush control is mounted 46 inches above the finished floor.

TR20

24 months

29.3.f.

There is no accessible stall provided.

ST15

24 months

29.4.

Women's Toilet Room with Stalls

   

29.4.a.

The toilet room sign is not mounted on the latch side of the door and has no raised or Braille characters.

TR18

24 months

29.4.b.

The pull side of the door, which is accessed through a front approach, is inaccessible because it has insufficient clear space on the latch side.

D6

24 months

29.4.c.

The lavatory is inaccessible because it lacks knee and toe clearance.

TR11

24 months

29.4.d.

There is no accessible toilet stall provided.

ST15

24 months

29.5.

Drinking Fountain

   

29.5.a.

The drinking fountain is inaccessible because it has a spout that is 42 inches above the finished floor.

DF6

24 months

29.5.b.

The wall-mounted drinking fountain is inaccessible because it provides no knee clearance.

DF5

24 months

29.6.

Interior Ramp to Assembly Area

   

29.6.a.

The ramp is inaccessible because it has a slope of 28.3%, it lacks adequate edge protection, and it lacks handrails.

R5

24 months

29.6.b.

The fire extinguisher on the route to the ramp protrudes into the walkway and is not detectable to blind persons using a cane.

AR8

24 months

30.

Eisenhower Recreation Center, located at 2901 North 72nd Street

   

30.1.

Parking. The parking lot, with a total of 73 parking spaces, is inaccessible because the designated accessible spaces have no access aisles, the signs are mounted too low, and there is no van accessible space. This lot requires 1 van accessible space and 2 standard accessible spaces.

P3

24 months

30.2.

Route to Entrance. The curb cut from the parking lot to the entrance is inaccessible because the slope is 10.3%, the gutter slope is 23.5%, and the flared sides have slopes of 25.3% and 23.5%.

AR5

24 months

30.3.

Interior Main Entrance Doors

   

30.3.a.

Both sets of double doors are inaccessible because each leaf is 27½ inches wide.

D24

24 months

30.3.b.

Each door is inaccessible because it requires 14 pounds of force to open.

D2

24 months

30.4.

Interior Signage. The interior signage provided throughout the facility is inaccessible because it is often mounted on doors and lacks raised or Braille characters.

D26

24 months

30.5.

Lobby Drinking Fountain

   

30.5.a.

The drinking fountain is inaccessible because it has a spout that is 41 inches above the finished floor.

DF6

24 months

30.5.b.

The wall-mounted drinking fountain is inaccessible because it has insufficient clear floor space and knee space.

DF5

24 months

30.6.

Women's Locker Room

   

30.6.a.

No accessible mirror has been provided.

TR14

24 months

30.6.b.

The paper towel dispenser is inaccessible because it is mounted with the controls 62 inches above the finished floor.

TR5

24 months

30.6.c.

The lavatory is inaccessible because the hot water pipes are not insulated or otherwise configured to protect against contact.

TR12

24 months

30.6.d.

The lavatory is inaccessible because it has twist-type hardware.

TR10

24 months

30.6.e.

There is no accessible toilet stall provided.

ST15

24 months

30.6.f.

There is no accessible shower provided.

B8

24 months

30.6.g.

The benches in the dressing area are inaccessible because they are 13 inches deep, are mounted 16½ inches above the finished floor, and do not provide clear floor space alongside to allow a transfer.

LR1

24 months

30.7.

Men's Locker Room

   

30.7.a.

No accessible mirror has been provided.

TR14

24 months

30.7.b.

The paper towel dispenser is inaccessible because it is mounted with the controls 62 inches above the finished floor.

TR5

24 months

30.7.c.

The lavatory is inaccessible because the bottom of the apron is 27¼ inches above the finished floor.

TR11

24 months

30.7.d.

The lavatory is inaccessible because the hot water pipes are not insulated or otherwise configured to protect against contact.

TR12

24 months

30.7.e.

The lavatory is inaccessible because it has twist-type hardware.

TR10

24 months

30.7.f.

The urinal is inaccessible because the rim is 22 inches above the finished floor.

TR20

24 months

30.7.g.

There is no accessible toilet stall provided.

ST15

24 months

30.7.h.

There is no accessible shower provided.

B8

24 months

30.7.i.

The benches in the dressing area are inaccessible because they are 13 inches deep, are mounted 16½ inches above the finished floor, and do not provide clear floor space alongside to allow a transfer.

LR1

24 months

30.8.

Craft Directors Office. The door is inaccessible because it has an opening width of only 29 inches.

D25

24 months

30.9.

Drinking Fountain by IRS and Craft Office

   

30.9.a.

The drinking fountain is inaccessible because it has a spout that is 41½ inches above the finished floor.

DF6

24 months

30.10.

The wall-mounted drinking fountain is inaccessible because it has inadequate knee space.

DF5

24 months

30.11.

Men's Craft Side Toilet Room with Stalls

   

30.11.a. 

The door is inaccessible because it requires 10 pounds of force to open.

D2

24 months

30.11.b. 

The pull side of the door, which is accessed through a front approach, is inaccessible because it has only 2 inches of clear space on the latch side.

D6

24 months

30.11.c. 

No accessible mirror has been provided.

TR14

24 months

30.11.d. 

The lavatory is inaccessible because the hot water and drain pipes are not insulated or otherwise configured to protect against contact.

TR12

24 months

30.11.e. 

The lavatory is inaccessible because the faucet has twist-type hardware.

TR10

24 months

30.11.f. 

The urinal is inaccessible because the rim is 22 inches above the finished floor.

TR20

24 months

30.11.g. 

The designated accessible stall is incorrectly configured as an ambulatory stall, and there is no standard accessible stall provided.

ST15

24 months

30.12.

Women's Craft Side Toilet Room with Stalls

   

30.12.a. 

The door is inaccessible because it requires 10 pounds of force to open.

D2

24 months

30.12.b. 

The pull side of the door, which is accessed through a front approach, is inaccessible because it has only 2 inches of clear space on the latch side.

D6

24 months

30.12.c. 

No accessible mirror has been provided.

TR14

24 months

30.12.d. 

The lavatory is inaccessible because the hot water and drain pipes are not insulated or otherwise configured to protect against contact.

TR12

24 months

30.12.e. 

The lavatory is inaccessible because the faucet has twist-type hardware.

TR10

24 months

30.12.f. 

The designated accessible stall is incorrectly configured as an ambulatory stall, and there is no standard accessible stall provided.

ST15

24 months

30.13.

Ballfield Toilet Room Drinking Fountain. The drinking fountain is inaccessible because it has a spout that is 43 inches above the finished floor.

DF6

24 months

30.14.

Ballfield Toilet Rooms. The toilet rooms contain a number of inaccessible elements and are not accessible to persons with disabilities.

ST14

24 months

31.

Fire Station #3, located at Kansas Avenue

   

31.1.

Entrances. The building does not have directional signage posted at inaccessible entrances and does not have the International Symbol of Accessibility posted at accessible entrances.

D16

12 months

32.

Memorial Hall, located at 600 North 7th Street

   

32.1.

Box Office Ticket Counter. The counter is inaccessible because it is 43 inches above the finished floor.

C6

24 months

32.2.

Lobby Telephones. The two telephones are inaccessible because each booth has narrow doors and inadequate clear floor space and neither telephone has volume control.

TT1

24 months

32.3.

Main Concourse Level Concession Counters. The counters are inaccessible because they are 43 inches above the finished floor.

C4

24 months

32.4.

Drinking Fountains. The 2 drinking fountains by the unisex toilet rooms are inaccessible because they have spouts that are 37½ inches above the finished floor, the flow of water is 2½ to 3½ inches high and 4 inches from the front of the fountain, and they provide no knee space.

DF1

24 months

32.5.

Women's and Men's Lobby Toilet Rooms with Stalls

   

32.5.a.

These toilet rooms contain a number of inaccessible elements and are not accessible to people using wheelchairs, and there is no signage directing persons with disabilities to the accessible unisex toilet rooms.

TR16

24 months

32.5.b.

The toilet room signs are mounted on the door and have no raised or Braille characters.

TR18

24 months

32.5.c.

The air dryers protrude into the walkway and are not detectable to blind persons using a cane.

AR8

24 months

32.6.

Men's and Women's Toilet Rooms Downstairs off Concourse. There is no signage directing persons with disabilities to the accessible unisex toilet rooms.

TR16

24 months

32.7.

Main Level Designated Accessible Men's Single-User Toilet Room

   

32.7.a.

The toilet room sign is mounted on the door.

TR17

24 months

32.7.b.

The door is inaccessible because it requires 7 pounds of force to open.

D2

24 months

32.7.c.

The air dryer protrudes into the walkway and is not detectable to blind persons using a cane.

AR8

24 months

32.7.d.

The lavatory hot water and drain pipes are not insulated or otherwise configured to protect against contact.

TR12

24 months

32.8.

Main Level Designated Accessible Women's Single-User Toilet Room

   

32.8.a.

The toilet room sign is mounted on the door.

TR17

24 months

32.8.b.

The door is inaccessible because it requires more than 5 pounds of force to open.

D2

24 months

32.8.c.

The air dryer protrudes into the walkway and is not detectable to blind persons using a cane.

AR8

24 months

32.8.d.

The lavatory hot water and drain pipes are not insulated or otherwise configured to protect against contact.

TR12

24 months

32.9.

Stage. The stage is inaccessible because it can only be accessed by stalls.

AA1

24 months

32.10.

Ramp from Right Side of Stage to Dressing Area

   

32.10.a.

The ramp is inaccessible because it has a slope of 31.6%, and the handrails are 29½ inches above the finished floor, lack extensions, and are mounted 2½ inches from the wall.

R5

36 months

32.10.b.

The route at the bottom of the ramp is inaccessible because there are only 74 inches of head room provided in the door frame.

AR7

36 months

32.11.

Ramp from Left Side of Stage to Dressing Area

   

32.11.a.

The ramp is inaccessible because it has a slope of 26%, and the handrails are 29½ inches above the finished floor, lack extensions, and are mounted 2½ inches from the wall.

R5

36 months

32.11.b.

The route at the bottom of the ramp is inaccessible because there are only 78 inches of head room provided, and the door to the dressing area is 72 inches high.

AR7

36 months

32.12.

Telephone near Left Side Dressing Area. The telephone protrudes into the walkway and is not detectable to blind persons using a cane.

AR8

24 months

32.13.

Dressing Rooms. None of the dressing rooms on either side of the stage is accessible.

LR2

SU13

B8

24 months

32.14.

Basement Exhibition Hall

   

32.14.a. 

The doors are inaccessible because knob hardware is used.

D1

24 months

32.14.b.

The fire extinguisher and display case protrude into the walkway and are not detectable to blind persons using a cane.

AR8

24 months

32.15.

Ramp Leading to Basement Kitchen. The ramp is inaccessible because the slope is 29.1%, there is a handrail on only one side, and the handrail is 32¾ inches above the finished floor, is not continuous, and lacks extensions.

R5

36 months

32.16.

Ramp Between Main Level and Emergency Exit. The ramp is inaccessible because the slope is 24.5%, there is a handrail on only one side, and the handrail is 33½ inches above the finished floor, and lacks extensions.

R5

36 months

32.17.

Left Side Lower Level Ramp up to Assembly Area

   

32.17.a.

The ramp is inaccessible because it has a slope of 31.4%, and the handrails are 30 inches above the finished floor, lack extensions, and are mounted 2½ inches from the wall.

R5

36 months

32.17.b.

The route at the bottom of the ramp is inaccessible because there are only 77 inches of head room provided.

AR7

36 months

32.18.

Balcony Level Beer Concession Stands

   

32.18.a. 

The routes to the concession stands are inaccessible because they are 31 inches wide.

AR3

24 months

32.18.b. 

The counters are inaccessible because they are 42 inches above the finished floor.

C4

24 months

32.19.

Ramp to Upper Level/Press Box. The ramp is inaccessible because it has a slope between 24.5% and 26.3%, there is a handrail on only one side, and the handrail is 31½ inches above the finished floor and lacks extensions.

R5

36 months

32.20.

Ramp from Top of Lower Bowl to Concourse Right Side. The ramp is inaccessible because it has a slope between 26.1% and 27.5%, there is a handrail on only one side, and the handrail is between 29 and 33 inches above the finished floor, lacks extensions, and is not continuous.

R5

36 months

32.21.

Ramp from Concourse to Lower Level Seating at Bottom of Lower Bowl. The ramp is inaccessible because it has a slope of 25.8%, there is a handrail on only one side, and the handrail is 30 inches above the finished floor, is not continuous, is mounted 2½ inches from the wall, and lacks extensions.

R5

36 months

32.22.

Concert Hall. The Concert Hall, containing 3279 seats, is inaccessible because no wheelchair seating areas are provided. A total of 34 wheelchair seating areas is required.

AA7

24 months

33.

Wyandotte County Jail, located at 701 North Seventh Street

   

33.1.

Adult Booking and Intake

   

33.1.a.

The counter is inaccessible because it is more than 36 inches above the finished floor.

C6

24 months

33.1.b.

The prisoner toilet room contains a number of inaccessible elements and is not accessible to persons with disabilities.

SU13, TR7

24 months

33.2.

Telephones. The telephones throughout the facility, including those provided in visiting areas, are inaccessible because they have no volume control, they are not hearing aid compatible, and the cords are often less than 29 inches long.

TT1

24 months

33.2.a.

Visiting Areas. The visitation rooms have no accessible seating.

PJ7

24 months

33.3.

Housing Units

   

33.3.a.

Accessible housing is not dispersed among the available security levels and age levels in the facility.

PJ4

24 months

33.3.b.

There are no accessible drinking fountains provided for prisoner use.

DF1

24 months

33.4.

Medical Unit. There is no accessible medical unit available within the facility.

PJ5

24 months

33.5.

Adult Inmate Waiting Area Unisex Single-User Toilet Rooms

   

33.5.a.

The door to the toilet room on the right of the drinking fountain is inaccessible because it has an opening width of 24 inches.

D25

24 months

33.5.b.

The lavatory in the toilet room on the right of the drinking fountain is inaccessible because the hot water pipes are not insulated or otherwise configured to protect against contact.

TR12

24 months

33.5.c.

The rear grab bar at the toilet in the room on the right of the drinking fountain is inaccessible because it is 24 inches long.

SU3

24 months

33.5.d.

There is no signage at the inaccessible toilet room directing persons with disabilities to the designated accessible toilet room.

TR16

24 months

33.6.

Juvenile Holding Area Unisex Single-User Toilet Room

   

33.7.

The toilet is inaccessible because the top of the seat is 15 inches above the finished floor.

SU18

24 months

33.8.

No accessible coat hook has been provided.

TR1

24 months

33.9.

The side grab bar at the toilet is inaccessible because it is mounted with the far end less than 54 inches from the rear wall.

SU6

24 months

 