ATTACHMENT I: Modifications to Newly Constructed FacilitiesPlease Note: Paragraph 57 of the Settlement Agreement requires that within 12 months of the effective date of this Agreement, the Consolidated Government provide signage as necessary to comply with 28 C.F.R. ¤ 35.163(b), after having surveyed all facilities that are the subject of this Agreement for the purpose of identifying those that have multiple entrances not all of which are accessible. The chart below lists the facilities surveyed by the Department, the access issues identified during the survey, and the actions required to correct the access issues. Required actions are listed using an alphanumeric code. The key to the alphanumeric codes is provided in Attachment M to this Agreement. In order to ensure that the following spaces and elements in Consolidated Government facilities for which construction was commenced after January 26, 1992, are readily accessible to and usable by persons with disabilities, the Consolidated Government will take the actions referenced by the alphanumeric code and described in detail in Attachment M to this Settlement Agreement within the time periods specified below, which time periods will begin to run on the effective date of this Agreement. |
|||
Item # |
Access Issue |
Required Action |
Completion Date |
---|---|---|---|
1. |
Willa Gill Soup Kitchen, located at 645 Nebraska Avenue |
||
1.1. |
Entrances. At the main entrance, the interior door is inaccessible because it requires 22 pounds of force to open. |
D2 |
18 months |
1.2. |
Employee Unisex Single User Toilet Room in Rear |
||
1.2.a. |
The toilet room sign is mounted on the door. |
TR18 |
18 months |
1.2.b. |
The push side of the door, which is accessed through a front approach and which has both a closer and a latch, is inaccessible because it has only 2½ inches of maneuvering clearance on the latch side of the door. |
D7 |
18 months |
1.2.c. |
The toilet room is inaccessible because there is insufficient turning space provided within the room. |
TR19 |
18 months |
1.2.d. |
The toilet seat cover dispenser is inaccessible because it is mounted with the controls 50 inches above the finished floor, and it requires a front approach. |
TR5 |
18 months |
1.2.e. |
The paper towel dispenser is inaccessible because it is mounted with the automatic sensor 50 inches above the finished floor, and it requires a front approach. |
TR5 |
18 months |
1.2.f. |
The lavatory is inaccessible because the bottom of the apron is 27½ inches above the finished floor. |
TR11 |
18 months |
1.2.g. |
The side grab bar at the toilet is inaccessible because it is obstructed by the basket. |
SU8 |
18 months |
1.2.h. |
The side grab bar at the toilet is inaccessible because the far end is 50 inches from the rear wall. |
SU6 |
18 months |
1.3. |
Kitchen Foyer Coat Rack. No accessible coat hook has been provided. |
TR1 |
18 months |
1.4. |
Employee Unisex Single-User Toilet Room Near Kitchen |
||
1.4.a. |
The toilet room sign is mounted 52 inches above the finished floor. |
TR18 |
18 months |
1.4.b. |
The paper towel dispenser is inaccessible because it is mounted with the controls 63 inches above the finished floor. |
TR5 |
18 months |
1.4.c. |
The lavatory is inaccessible because the bottom of the apron is 27½ inches above the finished floor. |
TR11 |
18 months |
1.4.d. |
The rear grab bar at the toilet is inaccessible because it is 9 inches long. |
SU3 |
18 months |
1.5. |
MenÕs Toilet Room with Stalls Near Main Entrance |
||
1.5.a. |
The toilet room sign is mounted 51 inches above the finished floor. |
TR18 |
18 months |
1.5.b. |
The door is inaccessible because it requires 11 pounds of force to open. |
D2 |
18 months |
1.5.c. |
The air dryer protrudes into the walkway and is not detectable to blind persons using a cane. |
AR8 |
18 months |
1.5.d. |
The side grab bar at the designated accessible toilet is inaccessible because it is 36 inches long, and it is mounted with the far end 39 inches from the rear wall. |
ST7 |
18 months |
1.6. |
WomenÕs Toilet Room with Stalls Near Main Entrance |
||
1.6.a. |
The toilet room sign is mounted 51 inches above the finished floor. |
TR18 |
18 months |
1.6.b. |
The door is inaccessible because it requires 10 pounds of force to open. |
D2 |
18 months |
1.6.c. |
The air dryer protrudes into the walkway and is not detectable to blind persons using a cane. |
AR8 |
18 months |
1.6.d. |
The side grab bar at the designated accessible toilet is inaccessible because it is 36 inches long, and it is mounted with the far end 39 inches from the rear wall. |
ST7 |
18 months |
1.7. |
Kitchen and Lunchroom |
||
1.7.a. |
The sink is inaccessible because the hot water pipes are not insulated or otherwise configured to protect against contact. |
S2 |
18 months |
1.7.b. |
The vending machine is inaccessible because the highest operable part is 60 inches above the finished floor. |
L3 |
18 months |
1.8. |
Voice Mail Telephones. The telephones are inaccessible because their highest operable parts are all 54 inches above the finished floor, they are not hearing aid compatible, and there is no volume control signage. |
TT1 |
18 months |
1.9. |
Drinking Fountain |
||
1.9.a. |
The drinking fountain protrudes into the walkway and is not detectable to blind persons using a cane. |
AR8 |
18 months |
1.9.b. |
Although a designated accessible drinking fountain is provided, there is no drinking fountain provided for people who have difficulty bending or stooping. |
DF3 |
18 months |
2. |
Central Garage, located at 5503 State Avenue |
||
2.1. |
Parking |
||
2.1.a. |
The van accessible parking space is inaccessible because it lacks ÒVan AccessibleÓ signage. |
P6 |
24 months |
2.1.b. |
The designated accessible parking is inaccessible because one of the access aisles is 59 inches wide. |
P8 |
24 months |
2.2. |
Ramp from Parking. The ramp is inaccessible because it slopes up to 9.8%, the handrails do not have extensions at the top, and there is 2 inches between the handrail and the wall at the bottom. |
R3 |
24 months |
2.3. |
Dispatch. The pull side of the door, which is accessed through a front approach, is inaccessible because it has no maneuvering clearance on the latch side of the door. |
D6 |
24 months |
2.4. |
Transit. The pull side of the door, which is accessed through a front approach, is inaccessible because it has no maneuvering clearance on the latch side of the door. |
D6 |
24 months |
2.5. |
Park/Transit/Street/Traffic |
||
2.5.a. |
The time clock protrudes into the walkway and is not detectable to blind persons using a cane. |
AR8 |
24 months |
2.5.b. |
The counter is inaccessible because it is 42¼ inches above the finished floor. |
C6 |
24 months |
2.6. |
Kitchen Wet Bar near Parks and Rec. The sink is inaccessible because it has hardware that requires tight grasping, pinching, or twisting of the wrist to operate. |
S2 |
24 months |
2.7. |
Warehouse. The door is inaccessible because it requires 11 pounds of force to open. |
D2 |
24 months |
2.8. |
Tire Room. The door is inaccessible because it requires 10 pounds of force to open. |
D2 |
24 months |
2.9. |
Streets Warehouse |
||
2.9.a. |
The door is inaccessible because it requires 9 pounds of force to open. |
D2 |
24 months |
2.9.b. |
The door is inaccessible because it has an opening width of 9 inches due to the placement of a ladder. |
D25 |
24 months |
2.10. |
Light Maintenance Garage. The counter is inaccessible because it is 40¼ inches above the finished floor. |
C6 |
24 months |
2.11. |
Heavy Maintenance. The fire extinguisher outside the entry door protrudes into the walkway and is not detectable to blind persons using a cane. |
AR8 |
24 months |
2.12. |
Entrances |
||
2.12.a. |
The building does not have directional signage posted at inaccessible entrances and does not have the International Symbol of Accessibility posted at accessible entrances. |
D16 |
24 months |
2.12.b. |
The entrance to the Covered Garage Barn is inaccessible because there is a slope of 17.2% within the doorÕs required maneuvering clearance on the inside. |
D13 |
24 months |
2.12.c. |
The entrance to the Pole Barn is inaccessible because there is a 6¾ inch high threshold. |
D22 |
24 months |
2.12.d. |
The entrance to the Pole Barn is inaccessible because it has knob hardware. |
D1 |
24 months |
2.13. |
WomenÕs Toilet Room with Stalls near P & R Streets |
||
2.13.a. |
The toilet room sign is inaccessible because it is mounted on the door. |
TR18 |
24 months |
2.13.b. |
The door is inaccessible because it requires 15 pounds of force to open. |
D2 |
24 months |
2.13.c. |
Although the facility contains an emergency alarm system, no visual alarm is provided in the toilet room. |
TR21 |
24 months |
2.13.d. |
The toilet seat cover dispenser is inaccessible because it is mounted with the controls 57½ inches above the finished floor. |
TR5 |
24 months |
2.13.e. |
The feminine products dispenser is inaccessible because it requires tight grasping, pinching, or twisting of the wrist to operate. |
TR3 |
24 months |
2.13.f. |
The designated accessible toilet is inaccessible because its centerline is 18½ inches from the side wall. |
ST17 |
24 months |
2.13.g. |
The designated accessible toilet is inaccessible because the rear grab bar is obstructed by the flush valve. |
ST5 |
24 months |
2.14. |
MenÕs Toilet Room with Stalls near P & R Streets |
||
2.14.a. |
The toilet room sign is inaccessible because it is mounted on the door. |
TR18 |
24 months |
2.14.b. |
The door is inaccessible because it requires 17 pounds of force to open. |
D2 |
24 months |
2.14.c. |
Although the facility contains an emergency alarm system, no visual alarm is provided in the toilet room. |
TR21 |
24 months |
2.14.d. |
The toilet is inaccessible because its centerline is 19 inches from the side wall. |
ST17 |
24 months |
2.14.e. |
The toilet is inaccessible because the rear grab bar is obstructed by the flush valve. |
ST5 |
24 months |
2.15. |
Maintenance Offices Single-User Unisex Toilet Room |
||
2.15.a. |
The toilet room sign is inaccessible because it is mounted on the door. |
TR18 |
24 months |
2.15.b. |
Although the facility contains an emergency alarm system, no visual alarm is provided in the toilet room. |
TR21 |
24 months |
2.15.c. |
No accessible coat hook has been provided. |
TR1 |
24 months |
2.15.d. |
The lavatory is inaccessible because the hot water pipes are not insulated or otherwise configured to protect against contact. |
TR12 |
24 months |
2.15.e. |
The toilet is inaccessible because its centerline is 21½ inches from the side wall. |
SU15 |
24 months |
2.16. |
Heavy Maintenance Single-User Unisex Toilet Room. The toilet room contains a number of inaccessible elements and is not accessible to people with disabilities. |
SU13 |
24 months |
2.17. |
MenÕs Locker Room |
||
2.17.a. |
The locker room sign is inaccessible because it is mounted on the door. |
TR18 |
24 months |
2.17.b. |
The outer and inner doors are inaccessible because they require 10 pounds of force to open. |
D2 |
24 months |
2.17.c. |
The pull side of the outer and inner doors, which are accessed through a front approach, are inaccessible because they have 6 inches of maneuvering clearance on the latch side of the doors. |
D6 |
24 months |
2.17.d. |
Although an audible alarm is provided in this facility, there is no visual alarm appliance in the toilet room. |
TR21 |
24 months |
2.17.e. |
No accessible mirror has been provided. |
TR14 |
24 months |
2.17.f. |
The designated accessible toilet is inaccessible because its centerline is 19 inches from the side wall. |
ST17 |
24 months |
2.17.g. |
The designated accessible toilet stall door hardware is inaccessible because it has not been maintained in working order. |
M1 |
24 months |
2.17.h. |
There is no rear grab bar provided at the designated accessible toilet. |
ST3 |
24 months |
2.17.i. |
There is no accessible shower provided. |
B8 |
24 months |
2.17.j. |
The bench is inaccessible because it is 9½ inches deep and is not fixed to a wall. |
LR1 |
24 months |
2.17.k. |
There is no accessible locker provided. |
LR3 |
24 months |
2.18. |
WomenÕs Locker Room |
||
2.18.a. |
The locker room sign is inaccessible because it is mounted on the door. |
TR18 |
24 months |
2.18.b. |
The outer and inner doors are inaccessible because they require 10 pounds of force to open. |
D2 |
24 months |
2.18.c. |
The pull side of the outer and inner doors, which are accessed through a front approach, are inaccessible because they have 10 inches of maneuvering clearance on the latch side of the doors. |
D6 |
24 months |
2.18.d. |
Although an audible alarm is provided in this facility, there is no visual alarm appliance in the toilet room. |
TR21 |
24 months |
2.18.e. |
No accessible mirror has been provided. |
TR14 |
24 months |
2.18.f. |
The sanitary napkin dispenser protrudes into the walkway and is not detectable to blind persons using a cane. |
AR8 |
24 months |
2.18.g. |
The designated accessible toilet is inaccessible because its centerline is 19 inches from the side wall. |
ST17 |
24 months |
2.18.h. |
There is no accessible shower provided. |
B8 |
24 months |
2.18.i. |
The shower towel hook protrudes into the walkway and is not detectable to blind persons using a cane. |
AR8 |
24 months |
2.18.j. |
The bench is inaccessible because it is 9½ inches deep and is not fixed to a wall. |
LR1 |
24 months |
2.18.k. |
There is no accessible locker provided. |
LR3 |
24 months |
2.19. |
Door between Administration and Maintenance. The door is inaccessible because it requires 9 pounds of force to open. |
D2 |
24 months |
2.20. |
Break Room |
||
2.20.a. |
The door is inaccessible because it requires 7 pounds of force to open. |
D2 |
24 months |
2.20.b. |
The microwaves are inaccessible because their highest operable parts are 69 inches above the finished floor. |
TR5 |
24 months |
3. |
Fire Station Number 10, located at 2210 West 36th Avenue |
||
3.1. |
Parking. The parking lot, with a total of 4 parking spaces, is inaccessible because there is no designated ÒVan AccessibleÓ space. This lot requires 1 van accessible space. |
P6 |
12 months |
3.2. |
Single-User Toilet Room near Reception |
||
3.2.a. |
The paper towel dispenser is inaccessible because it requires tight grasping, pinching, or twisting of the wrist to operate. |
TR3 |
12 months |
3.2.b. |
The toilet is inaccessible because its centerline is 21 inches from the side wall. |
SU15 |
12 months |
3.3. |
WomenÕs Locker Room |
||
3.3.a. |
The feminine products dispenser protrudes into the walkway and is not detectable to blind persons using a cane. |
AR8 |
12 months |
3.3.b. |
No accessible coat hook has been provided. |
TR1 |
12 months |
3.3.c. |
The toilet paper dispenser in the designated accessible stall is inaccessible because it is mounted 38½ inches from the rear wall. |
ST19 |
12 months |
3.3.d. |
The designated accessible shower is inaccessible because the shower seat is 20¾ inches above the finished floor, and the shower unit is fixed and mounted 70 inches above the finished floor. |
B8 |
12 months |
3.3.e. |
No accessible towel hook has been provided. |
TR1 |
12 months |
3.3.f. |
There is no accessible locker provided. |
LR3 |
12 months |
3.4. |
MenÕs Locker Room |
||
3.4.a. |
No accessible coat hook has been provided. |
TR1 |
12 months |
3.4.b. |
The toilet paper dispenser in the designated accessible stall is inaccessible because it is mounted 38 inches from the rear wall. |
ST19 |
12 months |
3.4.c. |
The transfer shower is inaccessible because the transfer seat is 20¼ inches above the finished floor. |
B10 |
12 months |
3.4.d. |
No accessible towel hook has been provided. |
TR1 |
12 months |
3.4.e. |
There is no accessible locker provided. |
LR3 |
12 months |
3.5. |
Drinking Fountain in Truck Bay. Although a designated accessible drinking fountain is provided, there is no drinking fountain provided for people who have difficulty bending or stooping. |
DF3 |
12 months |