ATTACHMENT
I: Modifications to Newly Constructed Facilities
Please Note: Paragraph 33 of the Settlement Agreement requires that within three months of the effective date of this Agreement, the City provide signage as necessary to comply with 28 C.F.R. § 35.163(b), after having surveyed all facilities that are the subject of this Agreement for the purpose of identifying those that have multiple entrances not all of which are accessible. In order to ensure that the following spaces and elements in City facilities, for which construction was commenced after January 26, 1992, are readily accessible to and usable by persons with disabilities, the City will take the actions referenced by the alphanumeric code and described in detail in Attachment M to this Settlement Agreement. |
|||
item # |
Access Issue |
Required Action |
Completion Date |
---|---|---|---|
1 |
Parking Deck, located at 2nd and Market |
|
|
1.1 |
Parking Spaces |
||
1.1.a |
The designated accessible parking spaces on the north and west sides are inaccessible because they have slopes of up to 5.5%, with cross slopes of up to 7.3%, and the access aisles have slopes of up to 4.9%, with cross slopes of up to 6.4%. |
P7 |
24 months |
1.1.b |
One of the parking spaces reserved for persons with disabilities on the west side is inaccessible because the access aisle is only 52½ inches wide. |
P8 |
24 months |
1.2 |
Exterior Accessible Route - East Exit |
|
|
1.2.a |
The curb ramp on the route to the east exit is inaccessible because it has a slope of 9.7%. |
AR5 |
24 months |
1.2.b |
The ramp to the east exit is inaccessible because the handrails lack extensions at the top and bottom. |
R4 |
24 months |
1.3 |
Exterior Accessible Route - West Exit. The curb ramp on the route to the west exit is inaccessible because it has a slope of 12.5% and one side flare has a slope of 16.9%. |
AR5 |
24 months |
2 |
The Riverwalk, on the West Side of the City, Along Cape Fear River |
|
|
2.1 |
Surface of Riverwalk. Portions of the Riverwalk are inaccessible because they have slopes of more than 5% and do not have ramp features. |
R3 |
|
24 months | |||
2.2 |
Orange Street Entrance |
||
2.2.a |
The route to the entrance is inaccessible because the curb ramp has a cross slope of 3.3%. |
AR5 |
24 months |
2.2.b |
The entrance is inaccessible because there is a 1¾ inch level change between the brick surface and the wooden walkway. |
AR1 |
24 months |
2.3 |
Mueter´s Alley Entrance |
||
2.3.a |
The route to the dog station trash can is inaccessible because it contains stairs and is not firm, stable, or slip resistant. |
AR1 |
24 months |
2.3.b |
The routes onto the Riverwalk at this entrance are inaccessible because the curb ramp on one side has a slope of 12.3%, and the curb ramp on the other side has an abrupt level change of one inch at the bottom and is less than 36 inches wide. |
AR5 |
24 months |
2.4 |
Dock Street Entrance. The routes onto the Riverwalk at this entrance are inaccessible because the curb ramp on one side has a slope of 14.4% and is less than 36 inches wide and the curb ramp on the other side has a slope of 13.9%. |
AR5 |
24 months |
2.5 |
Ramp onto Riverwalk Between Docks 1 and 2. The ramp is inaccessible because it has a slope of 10.3% and the handrails have no extensions at the top or bottom. |
R5 |
24 months |
2.6 |
Ramp onto Riverwalk By Dock 2. The ramp is inaccessible because it has a slope of 14.8% and has no handrails. |
R5 |
24 months |
2.7 |
Drinking Fountain by Dock 2. Although a designated accessible drinking fountain is provided, there is no drinking fountain provided for people who have difficulty bending or stooping. |
DF3 |
24 months |
2.8 |
Ramps from Riverwalk to Parking by Docks 3 and 4 (Existing Area of Riverwalk). The ramp is inaccessible because it has a slope of 19.4%, has no handrails, and the bottom of the ramp can be blocked by legally parked cars. |
R5 |
24 months |
3 |
Greenfield Park, at Park Street south of Willard |
||
3.1 |
Drinking Fountains. The drinking fountains protrude into the walkway more than four inches at a height between 27 and 80 inches and are not detectable to blind persons using a cane. |
AR8 |
24 months |
4 |
Public Services and Storm Water Administration, at 209 Coleman Drive |
||
4.1 |
Parking. The parking is inaccessible because the parking lot has a total of 203 parking spaces, and only 3 are designated as reserved for people with disabilities. This lot requires 1 van accessible space and 6 standard accessible spaces. |
P3 |
24 months |
4.2 |
Break Room Area |
||
4.2.a |
The door is inaccessible because it requires 8 pounds of force to open. |
D2 |
24 months |
4.2.b |
The push side of the door, which is accessed through a front approach and which has both a closer and a latch, is inaccessible because it has only 10 inches of clear space on the latch side. |
D7 |
24 months |
4.2.c |
The break room is inaccessible because the drinking fountains protrude into the walkway more than four inches at a height between 27 and 80 inches and are not detectable to blind persons using a cane. |
AR8 |
24 months |
4.2.d |
The paper towel dispenser is inaccessible because it is mounted with the towels 56 inches above the finished floor and a forward approach is required. |
TR5 |
24 months |
4.3 |
Interior Accessible Route. The defibrillators and first aid stations just outside the locker room doors protrude into the walkway more than four inches at a height between 27 and 80 inches and are not detectable to blind persons using a cane. |
AR8 |
24 months |
4.4 |
Men´s Locker Room |
||
4.4.a |
The door is inaccessible because it requires 15 pounds of force to open. |
D2 |
24 months |
4.4.b |
The lavatory is inaccessible because the rim or top of the counter counter is 35 inches above the finished floor. |
TR11 |
24 months |
4.4.c |
No accessible coat hook has been provided. |
TR1 |
24 months |
4.4.d |
The seat cover dispenser is inaccessible because it is mounted 57 inches above the finished floor and a forward approach is required. |
TR5 |
24 months |
4.4.e |
The shower is inaccessible because it is 36 inches by 38 inches, the seat is 20¼ inches above the finished floor, the controls are 50 inches above the finished floor, and the controls are 21 inches from the open side of the shower. |
B8 |
24 months |
4.4.f |
The bench outside the shower is inaccessible because it is 14¾ inches deep and does not have any clear floor space alongside to allow a parallel approach. |
LR1 |
24 months |
4.4. |
The designated accessible locker is inaccessible because it requires pinching to open. |
LR3 |
24 months |
4.5 |
Women´s Locker Room |
||
4.5.a |
The door is inaccessible because it requires 15 pounds of force to open. |
D2 |
24 months |
4.5.b |
The seat cover dispenser is inaccessible because it is mounted 57 inches above the finished floor and a forward approach is required. |
TR5 |
24 months |
4.5.c |
The lavatory is inaccessible because the top of the rim or counter is 35¼ inches above the finished floor. |
TR11 |
24 months |
4.5.d |
No accessible coat hook has been provided. |
TR1 |
24 months |
4.5.e |
The side grab bar at the toilet is inaccessible because the far end is 51 inches from the rear wall. |
ST7 |
24 months |
4.5.f |
The shower is inaccessible because it is 36 inches by 38 inches, the seat is 20 inches above the finished floor, the controls are 50 inches above the finished floor, and the controls are 22 inches from the open side of the shower. |
B8 |
24 months |
4.5. |
The bench outside the shower is inaccessible because it is 14½ inches deep and 37 inches wide and does not have any clear floor space alongside to allow a parallel approach. |
LR1 |
24 months |
4.5.h |
The designated accessible locker is inaccessible because it requires pinching to open. |
LR3 |
24 months |
5 |
Storm Water and Facility Operations, at 245 Operation Center Drive |
||
5.1 |
Parking. The parking designated as reserved for persons with disabilities is inaccessible because it is not dispersed among the three buildings that share the parking lot, and none of the accessible spaces are near this facility. |
P2 |
24 months |
5.2 |
Interior Doors. The door to the first office on the right (marked "Office") is inaccessible because it requires 15 pounds of force to open. |
D2 |
24 months |
5.3 |
Interior Accessible Route. The time card machines protrude into the walkway more than four inches at a height between 27 and 80 inches and are not detectable to blind persons using a cane. |
AR8 |
24 months |
5.4 |
Break Room. The paper towel dispenser is inaccessible because the controls are mounted 53 inches above the finished floor over the counter. |
TR4 |
24 months |
5.5 |
Hallway Drinking Fountain. The drinking fountains protrude into the walkway more than four inches at a height between 27 and 80 inches and are not detectable to blind persons using a cane. |
AR8 |
24 months |
5.6 |
Women´s Locker Room |
||
5.6.a |
The door is inaccessible because it requires 13 pounds of force to open. |
D2 |
24 months |
5.6.b |
The shower is inaccessible because the seat is 21½ inches above the finished floor, the controls are 19½ inches from the open side of the shower, and the curb is more than ½ inch high. |
B8 |
24 months |
5.6.c |
The bench is inaccessible because it is 33½ inches long, is less than 24 inches deep, is 21 inches above the finished floor, and does not provide clear floor space alongside to allow a parallel approach. |
LR1 |
24 months |
5.7 |
Men´s Locker Room |
||
5.7.a |
The door is inaccessible because it requires 15 pounds of force to open. |
D2 |
24 months |
5.7.b |
No accessible mirror has been provided. |
TR14 |
24 months |
5.7.c |
The shower is inaccessible because it is 34 inches by 34 inches, the seat is 21½ inches above the finished floor, there is no clear floor space extending behind the transfer seat, the controls are 20 inches from the open side of the shower, and the curb is more than ½ inch high. |
B8 |
24 months |
5.7.d |
The benches are inaccessible because they are not fixed to the wall. |
LR1 |
24 months |
6 |
Fire Station 7 |
||
6.1 |
Parking. The parking lot, with a total of 17 parking spaces, is inaccessible because the parking space reserved for persons with disabilities is only 86 inches wide and there is no van accessible parking space. This lot requires 1 van accessible space. |
P3 |
24 months |
6.2 |
Entrances. The building does not have directional signage posted at the inaccessible rear entrance and does not have the International Symbol of Accessibility posted at the accessible front entrance. |
D16 |
24 months |
6.3 |
Interior Doors. The doors to the dorms and locker rooms are inaccessible because each door requires 10 pounds of force to open. |
D2 |
24 months |
6.4 |
Main Counter. The counter is inaccessible because its top surface is 42 inches above the finished floor and equivalent facilitation is not provided. |
C6 |
24 months |
6.5 |
Interior Accessible Route. The fire extinguisher protrudes into the walkway more than four inches at a height between 27 and 80 inches and is not detectable to blind persons using a cane. |
AR8 |
24 months |
6.6 |
Unisex Single User Toilet Room |
||
6.6.a |
The lavatory is inaccessible because the top of the rim or counter is 35 inches above the finished floor. |
TR11 |
24 months |
6.6.b |
The toilet is inaccessible because the flush control is on the closed side. |
SU1 |
24 months |
6.6.c |
The toilet is inaccessible because there are no grab bars provided. |
SU10 |
24 months |
6.7 |
Men´s Locker Room |
||
6.7.a |
The toilet room sign is inaccessible because it is mounted on the door. |
TR18 |
24 months |
6.7.b |
The lavatory is inaccessible because the top of the rim or counter is 35 inches above the finished floor. |
TR11 |
24 months |
6.7.c |
The lower urinal is inaccessible because the rim is 19 inches above the finished floor. |
TR20 |
24 months |
6.7.d |
No accessible coat hook has been provided. |
TR1 |
24 months |
6.7.e |
The toilet paper dispenser is inaccessible because it is mounted 41 inches from the rear wall. |
ST19 |
24 months |
6.7.f |
No accessible towel hook has been provided. |
TR1 |
24 months |
6.8 |
Women´s Locker Room |
||
6.8.a |
The toilet room sign is inaccessible because it is mounted on the door. |
TR18 |
24 months |
6.8.b |
No accessible coat hook has been provided. |
TR1 |
24 months |
6.8.c |
The toilet paper dispenser is inaccessible because it is mounted 41 inches from the rear wall. |
ST19 |
24 months |
6.8.d |
The side grab bar at the toilet is inaccessible because it is mounted with the far end 50½ inches from the rear wall. |
ST7 |
24 months |
6.8.e |
The shower is inaccessible because it is 39½ inches by 36 inches. |
B8 |
24 months |
7 |
Fire Station 8 |
||
7.1 |
Parking. The parking reserved for persons with disabilities is inaccessible because the access aisle has a slope of 3.1%. |
P7 |
24 months |
7.2 |
Interior Doors. The doors to the dorms, office and locker rooms are inaccessible because each door requires 10 pounds of force to open. |
D2 |
24 months |
7.3 |
Unisex Single User Toilet Room. The single user toilet room contains a number of inaccessible elements and is inaccessible to people with disabilities. |
SU13 |
24 months |
7.4 |
Men´s Locker Room |
||
7.4.a |
No accessible mirror has been provided. |
TR14 |
24 months |
7.4.b |
The lavatory is inaccessible because the top of the rim or counter is 36 inches above the finished floor. |
TR11 |
24 months |
7.4.c |
The designated accessible toilet stall is inaccessible because it is only 53 inches deep. |
ST16 |
24 months |
7.4.d |
The toilet is inaccessible because the flush control is on the closed side. |
ST2 |
24 months |
7.4.e |
No accessible coat hook has been provided. |
TR1 |
24 months |
7.4.f |
The toilet paper dispenser is inaccessible because it is mounted 39 inches from the rear wall. |
ST19 |
24 months |
7.4. |
The side grab bar at the toilet is inaccessible because it is mounted with the far end 50 inches from the rear wall. |
ST7 |
24 months |
7.4.h |
The rear grab bar at the toilet is inaccessible because it is mounted 7 inches from the side wall. |
ST4 |
24 months |
7.5 |
Women´s Locker Room |
||
7.5.a |
The lavatory is inaccessible because the top of the rim or counter is 36 inches above the finished floor. |
TR11 |
24 months |
7.5.b |
No accessible coat hook has been provided. |
TR1 |
24 months |
7.5.c |
The toilet paper dispenser is inaccessible because it is mounted 40 inches from the rear wall. |
ST19 |
24 months |
7.5.d |
The toilet is inaccessible because the flush control is on the closed side. |
ST2 |
24 months |
7.5.e |
The toilet is inaccessible because its centerline is 19 inches from the side wall. |
ST17 |
24 months |
7.5.f |
The side grab bar at the toilet is inaccessible because it is mounted with the far end 50 inches from the rear wall. |
ST7 |
24 months |
7.5. |
The rear grab bar at the toilet is inaccessible because it is mounted 7 inches from the side wall. |
ST4 |
24 months |
7.5.h |
The shower is inaccessible because it is 38 inches by 35 inches and it has no grab bars. |
B8 |
24 months |
7.5.i |
No accessible towel hook has been provided. |
TR1 |
24 months |
7.6 |
Interior Accessible Route |
||
7.6.a |
The fire extinguisher protrudes into the walkway more than four inches at a height between 27 and 80 inches and is not detectable to blind persons using a cane. |
AR8 |
24 months |
7.6.b |
The shelf outside the dorm rooms protrudes into the walkway more than four inches at a height between 27 and 80 inches and is not detectable to blind persons using a cane. |
AR8 |
24 months |
8 |
Fire Station 9 |
||
8.1 |
Parking. The parking lot, with a total of 14 parking spaces, is inaccessible because there is no designated accessible parking provided. This lot requires 1 van accessible space. |
P3 |
24 months |
8.2 |
Interior Accessible Route |
||
8.2.a |
The fire extinguisher and first aid box outside the unisex toilet room protrude into the walkway more than four inches at a height between 27 and 80 inches and are not detectable to blind persons using a cane. |
AR8 |
24 months |
8.2.b |
The shelf outside the dorm rooms protrude into the walkway more than four inches at a height between 27 and 80 inches and is not detectable to blind persons using a cane. |
AR8 |
24 months |
8.2.c |
The fire extinguisher at the women´s locker room protrudes into the walkway more than four inches at a height between 27 and 80 inches and is not detectable to blind persons using a cane. |
AR8 |
24 months |
8.3 |
Unisex Toilet Room. The single user toilet room contains a number of inaccessible elements and is inaccessible to people with disabilities. |
SU13 |
24 months |
8.4 |
Men´s Locker Room |
||
8.4.a |
The door is inaccessible because it requires 10 pounds of force to open. |
D2 |
24 months |
8.4.b |
No accessible mirror has been provided. |
TR14 |
24 months |
8.4.c |
The lavatory is inaccessible because the top of the rim or counter is 35 inches above the finished floor. |
TR11 |
24 months |
8.4.d |
The urinal is inaccessible because the rim is 19 inches above the finished floor. |
TR20 |
24 months |
8.4.e |
The designated accessible toilet is inaccessible because its centerline is 16 inches from the side wall. |
ST17 |
24 months |
8.4.f |
No accessible coat hook has been provided. |
TR1 |
24 months |
8.4. |
The toilet paper dispenser is inaccessible because it is mounted 41 inches from the rear wall. |
ST19 |
24 months |
8.4.h |
The side grab bar at the designated accessible toilet is inaccessible because it is mounted 13 inches from the rear wall. |
ST7 |
24 months |
8.4.i |
The rear grab bar at the designated accessible toilet is inaccessible because it is mounted 7 inches from the side wall. |
ST4 |
24 months |
8.4.j |
The roll-in shower is inaccessible because it has grab bars on only 2 walls. |
B8 |
24 months |
8.5 |
Women´s Locker Room |
||
8.5.a |
The door is inaccessible because it requires 10 pounds of force to open. |
D2 |
24 months |
8.5.b |
No accessible mirror has been provided. |
TR14 |
24 months |
8.5.c |
The lavatory is inaccessible because the top of the rim or counter is 35 inches above the finished floor. |
TR11 |
24 months |
8.5.d |
The soap dispenser is inaccessible because the controls are mounted 50 inches above the finished floor over the lavatory. |
TR4 |
24 months |
8.5.e |
The designated accessible toilet is inaccessible because its centerline is 16 inches from the side wall. |
ST17 |
24 months |
8.5.f |
No accessible coat hook has been provided. |
TR1 |
24 months |
8.5. |
The toilet paper dispenser is inaccessible because it is mounted 51 inches from the rear wall. |
ST19 |
24 months |
8.5.h |
The side grab bar at the designated accessible toilet is inaccessible because it is mounted 13 inches from the rear wall. |
ST7 |
24 months |
8.5.i |
The rear grab bar at the designated accessible toilet is inaccessible because it is mounted 7 inches from the side wall. |
ST4 |
24 months |
8.6 |
Dorms. The dorm doors are inaccessible because they require 10 to 15 pounds of force to open. |
D2 |
24 months |
9 |
Fire Station 11 |
||
9.1 |
Parking. The parking lot, with a total of 16 parking spaces, is inaccessible because there is no designated accessible parking provided. This lot requires 1 van accessible space. |
P3 |
24 months |
9.2 |
Men´s Locker Room |
||
9.2.a |
The door is inaccessible because it requires 10 pounds of force to open. |
D2 |
24 months |
9.2.b |
No accessible mirror has been provided. |
TR14 |
24 months |
9.2.c |
The lavatory is inaccessible because the top of the rim or counter is 36 inches above the finished floor. |
TR11 |
24 months |
9.2.d |
The designated accessible toilet stall is inaccessible because it is 53 inches deep. |
ST16 |
24 months |
9.2.e |
The toilet paper dispenser is inaccessible because it is mounted 39 inches from the rear wall. |
ST19 |
24 months |
9.2.f |
The designated accessible toilet is inaccessible because the flush control is on the closed side. |
ST2 |
24 months |
9.2. |
The side grab bar at the designated accessible toilet is inaccessible because it is mounted with the far end 51 inches from the rear wall. |
ST7 |
24 months |
9.2.h |
The rear grab bar at the designated accessible toilet is inaccessible because it is mounted 8 inches from the side wall. |
ST4 |
24 months |
9.3 |
Women´s Locker Room |
||
9.3.a |
The lavatory is inaccessible because the top of the rim or counter is 36 inches above the finished floor. |
TR11 |
24 months |
9.3.b |
The designated accessible toilet stall is inaccessible because it is 56 inches wide. |
ST16 |
24 months |
9.3.c |
The toilet paper dispenser is inaccessible because it is mounted 40 inches from the rear wall. |
ST19 |
24 months |
9.3.d |
The designated accessible toilet is inaccessible because the flush control is on the closed side. |
ST2 |
24 months |
9.3.e |
The side grab bar at the designated accessible toilet is inaccessible because it is mounted with the far end 51 inches from the rear wall. |
ST7 |
24 months |
9.3.f |
The rear grab bar at the designated accessible toilet is inaccessible because it is mounted 8 inches from the side wall. |
ST4 |
24 months |
9.3. |
The shower is inaccessible because it is 38 inches by 35 inches and the seat is mounted on the control wall with the grab bars on the opposite wall. |
B8 |
24 months |
9.4 |
Single User Unisex Toilet Room |
||
9.4.a |
The lavatory is inaccessible because the top of the rim or counter is 36 inches above the finished floor. |
TR11 |
24 months |
9.4.b |
No accessible mirror has been provided. |
TR14 |
24 months |
9.4.c |
The side grab bar at the toilet is inaccessible because it is mounted with the far end 51 inches from the rear wall. |
SU6 |
24 months |
9.4.d |
The rear grab bar at the toilet is inaccessible because it is mounted 8 inches from the side wall. |
SU3 |
24 months |
9.5 |
Interior Accessible Route |
||
9.5.a |
The fire extinguisher protrudes into the walkway more than four inches at a height between 27 and 80 inches and is not detectable to blind persons using a cane. |
AR8 |
24 months |
9.5.b |
The drinking fountains protrude into the walkway more than four inches at a height between 27 and 80 inches and are not detectable to blind persons using a cane. |
AR8 |
24 months |
10 |
Halyburton Park, at 4099 South 17th Street |
||
10.1 |
Coat Rack. The lower coat rack in the hallway is inaccessible because it requires a reach of 57 inches above the finished floor. |
TR1 |
24 months |
10.2 |
Event Center: Women´s Single User Toilet Room |
||
10.2.a |
The lavatory is inaccessible because the top of the rim or counter is 35 inches above the finished floor. |
TR11 |
24 months |
10.2.b |
The rear grab bar at the toilet is inaccessible because it is obstructed by the flush valve. |
SU4 |
24 months |
10.3 |
Event Center: Men´s Single User Toilet Room |
||
10.3.a |
The toilet is inaccessible because its centerline is 19 inches from the side wall. |
SU15 |
24 months |
10.3.b |
The toilet is inaccessible because the flush control is on the closed side. |
SU1 |
24 months |
10.3.c |
The rear grab bar at the toilet is inaccessible because it is obstructed by the flush valve. |
SU4 |
24 months |
10.4 |
Event Center: Women´s Toilet Room with Stalls |
||
10.4.a |
The door is inaccessible because it requires 17 pounds of force to open. |
D2 |
24 months |
10.4.b |
The air dryers protrude into the walkway more than four inches at a height between 27 and 80 inches and are not detectable to blind persons using a cane. |
AR8 |
24 months |
10.4.c |
The lavatory is inaccessible because the top of the rim or counter is 35 inches above the finished floor. |
TR11 |
24 months |
10.4.d |
The designated accessible toilet is inaccessible because the flush control is on the closed side. |
ST2 |
24 months |
10.4.e |
The designated accessible toilet is inaccessible because the rear grab bar is obstructed by the flush valve. |
ST5 |
24 months |
10.5 |
Event Center: Men´s Toilet Room with Stalls |
||
10.5.a |
The door is inaccessible because the pressure required to open the door is 22 pounds. |
D2 |
24 months |
10.5.b |
The lavatory is inaccessible because the top of the rim or counter is 35 inches above the finished floor. |
TR11 |
24 months |
10.5.c |
The toilet is inaccessible because the rear grab bar is obstructed by the flush valve. |
ST5 |
24 months |
10.6 |
Gazebo: The route to the gazebo is inaccessible because it is not stable firm and slip resistant and there is an 8 inch step into the gazebo. |
AR1 |
24 months |
10.7 |
Playground Equipment: The route to the playground equipment is inaccessible because it is not stable, firm, and slip resistant, and there is a 14¾ inch high barrier around the playground. |
AR1 |
24 months |
10.8 |
Barbeques: The routes to the barbeques are inaccessible because they are not stable, firm, and slip resistant. |
AR1 |
24 months |
10.9 |
Women´s Toilet Room with Stalls near Picnic Area #2. The designated accessible toilet is inaccessible because the rear grab bar is obstructed by the flush valve. |
ST5 |
24 months |
10.10 |
Men´s Toilet Room with Stalls near Picnic Area #2 |
||
10.10.a |
The designated accessible toilet is inaccessible because its centerline is 19¼ inches from the side wall. |
ST17 |
24 months |
10.10.b |
The designated accessible toilet is inaccessible because the rear grab bar is obstructed by the flush valve. |
ST5 |
24 months |
10.10.c |
The designated accessible toilet is inaccessible because the flush control is on the closed side. |
ST2 |
24 months |
11 |
Wilmington Police Headquarters |
||
11.1 |
Parking: The parking lot, with a total of 43 parking spaces, is inaccessible because the designated van accessible space is only 92 inches wide, the access aisle farthest from the van space is only 54½ inches wide, all of the designated accessible standard spaces and access aisles have slopes of more than 2%, and the designated accessible space and access aisle farthest from the van space have cross slopes of 3%. This lot requires 1 van accessible space and 1 standard accessible space. |
P3 |
24 months |
11.2 |
Exterior Ramp: The ramp to the building entrance is inaccessible because it has a slope of up to 10% and the outside handrail is mounted 2½ inches from the wall at the top of the ramp. |
R3 |
24 months |
11.3 |
The drinking fountains throughout the facility protrude into the walkway more than four inches at a height between 27 and 80 inches and are not detectable to blind persons using a cane. |
AR8 |
24 months |
11.4 |
Men´s Single User Toilet Room D204 |
||
11.4.a |
No accessible mirror has been provided. |
TR14 |
24 months |
11.4.b |
The paper towel dispenser is inaccessible because it is mounted with the controls 51 inches above the finished floor with only a front reach provided. |
TR5 |
24 months |
11.5 |
Women´s Single User Toilet Room D203 |
||
11.5.a |
No accessible mirror has been provided. |
TR14 |
24 months |
11.5.b |
The paper towel dispenser is inaccessible because it is mounted with the controls 52 inches above the finished floor with only a front reach provided. |
TR5 |
24 months |
11.6 |
Elevator: The elevator is inaccessible because, although emergency communications are provided, they require voice communication. |
E8 |
24 months |
11.7 |
Drinking Fountain between E203 and E204: The drinking fountain is inaccessible because it requires 9 pounds of force to operate. |
DF2 |
24 months |
11.8 |
Women´s Toilet Room with Stalls E203 |
||
11.8.a |
No accessible mirror has been provided. |
TR14 |
24 months |
11.8.b |
No accessible coat hook has been provided. |
TR1 |
24 months |
11.9 |
Men´s Toilet Room with Stalls E204 |
||
11.9.a |
No accessible mirror has been provided. |
TR14 |
24 months |
11.9.b |
No accessible coat hook has been provided. |
TR1 |
24 months |
11.10 |
Drinking Fountain between E231 and E232. The drinking fountain is inaccessible because it requires 8 pounds of force to operate. |
DF2 |
24 months |
11.11 |
Men´s Toilet Room with Stalls E231 |
||
11.11.a |
No accessible mirror has been provided. |
TR14 |
24 months |
11.11.b |
No accessible coat hook has been provided. |
TR1 |
24 months |
11.12 |
Women´s Toilet Room with Stalls E232: No accessible coat hook has been provided. |
TR1 |
24 months |
11.13 |
Men´s Toilet Room with Stalls F231 |
||
11.13.a |
No accessible mirror has been provided. |
TR14 |
24 months |
11.13.b |
The paper towel dispenser is inaccessible because the controls are mounted at 52 inches above the finished floor with only a forward reach provided. |
TR5 |
24 months |
11.13.c |
The seat cover dispenser is inaccessible because the controls are mounted 65 inches above the finished floor. |
TR5 |
24 months |
11.13.d |
No accessible coat hook has been provided. |
TR1 |
24 months |
11.14 |
Women´s Toilet Room with Stalls F230 |
||
11.14.a |
No accessible mirror has been provided. |
TR14 |
24 months |
11.14.b |
The seat cover dispenser is inaccessible because the controls are mounted 58 inches above the finished floor. |
TR5 |
24 months |
11.14.c |
No accessible coat hook has been provided. |
TR1 |
24 months |
11.15 |
Custody Area C103A Holding Cell Toilet |
||
11.15.a |
The toilet paper dispenser is inaccessible because it is mounted behind the toilet. |
SU17 |
24 months |
11.15.b |
The rear grab bar at the toilet is inaccessible because the space between the bar and the rear wall exceeds 1½ inches along one portion of the bar. |
SU2 |
24 months |
11.16 |
Unisex Single User Staff Toilet Room C10 |
||
11.16.a |
No accessible mirror has been provided. |
TR14 |
24 months |
11.16.b |
The toilet seat cover dispenser is inaccessible because it is mounted 57 inches above the finished floor behind the toilet. |
TR4 |
24 months |
11.17 |
Men´s Single User Toilet Room C105 |
||
11.17.a |
No accessible mirror has been provided. |
TR14 |
24 months |
11.17.b |
The seat cover dispenser is inaccessible because it is mounted with the controls 57 inches above the finished floor. |
TR5 |
24 months |
11.18 |
Women´s Single User Toilet Room C111 |
||
11.18.a |
No accessible mirror has been provided. |
TR14 |
24 months |
11.18.b |
The seat cover dispenser is inaccessible because it is mounted with the controls 58 inches above the finished floor. |
TR5 |
24 months |
11.19 |
Men´s Toilet Room with Stalls B103 |
||
11.19.a |
No accessible mirror has been provided. |
TR14 |
24 months |
11.19.b |
No accessible coat hook has been provided. |
TR1 |
24 months |
11.20 |
Women´s Toilet Room with Stalls B104 |
||
11.20.a |
No accessible mirror has been provided. |
TR14 |
24 months |
11.20.b |
No accessible coat hook has been provided. |
TR1 |
24 months |
11.21 |
Women´s Locker Room B111B / B108 |
||
11.21.a |
The seat cover dispenser is inaccessible because it is mounted with the controls 55½ inches above the finished floor. |
TR5 |
24 months |
11.21.b |
No accessible coat hook has been provided. |
TR1 |
24 months |
11.21.c |
The ambulatory stall is inaccessible because it has partitions 43 inches apart, and the toilet seat is 15¼ inches above the finished floor. |
ST1 |
24 months |
11.21.d |
The transfer shower is inaccessible because it is 47 inches deep and 38¼ inches wide, it does not provide clear floor space to allow for a transfer onto the seat, and the shower spray unit is mounted more than 18 inches from the open side. |
B8 |
24 months |
11.21.e |
The benches are inaccessible because they are 13 inches wide. |
LR1 |
24 months |
11.21.f |
There is no accessible locker provided. |
LR3 |
24 months |
11.22 |
Men´s Locker Room B120A / B120B |
||
11.22.a |
No accessible coat hook has been provided. |
TR1 |
24 months |
11.22.b |
The shower is inaccessible because it is the size of a roll-in shower with the features of a transfer shower. |
B8 |
24 months |
11.22.c |
The benches are inaccessible because they are 13 inches wide. |
LR1 |
24 months |
11.22.d |
There is no accessible locker provided. |
LR3 |
24 months |
11.23 |
Visitors Locker Room B123 |
|
|
11.23.a |
No accessible mirror has been provided. |
TR14 |
24 months |
11.23.b |
No accessible coat hook has been provided. |
TR1 |
24 months |
11.23.c |
The toilet seat cover dispenser is inaccessible because it is mounted with the controls 56 inches above the finished floor. |
TR5 |
24 months |
11.23.d |
The paper towel dispenser is inaccessible because it is mounted with the controls 50 inches above the finished floor with only a forward reach provided. |
TR5 |
24 months |
11.23.e |
The shower is inaccessible because it is 46 inches by 52 inches, it has no seat, it has grab bars on two walls, and the shower spray unit is mounted more than 18 inches from the open side. |
B8 |
24 months |
12 |
The Street Maintenance Department, at 265 Operations Center Drive |
||
12.1 |
Parking: The parking reserved for persons with disabilities is inaccessible because the middle space has a slope of 3.2% and the smaller access aisle has a slope of 3.3%. |
P7 |
24 months |
12.2 |
Exterior Accessible Route: The route from the parking lot onto the sidewalk is inaccessible because one flare of the curb ramp has a slope of 11.2%. |
AR5 |
24 months |
12.3 |
Men´s Locker Room |
||
12.3.a |
The door is inaccessible because it requires 13 pounds of force to open. |
D2 |
24 months |
12.3.b |
No accessible coat hook has been provided. |
TR1 |
24 months |
12.3.c |
The shower is inaccessible because it is 39½ inches deep and 38½ inches wide, the seat is 20 inches above the finished floor, and the controls are mounted 52½ inches above the finished floor and 24½ inches from the open side of the shower. |
B8 |
24 months |
12.3.d |
The benches are inaccessible because they are 12 inches wide and are not attached to the wall. |
LR1 |
24 months |
12.3.e |
The lockers are inaccessible because they require tight grasping to open. |
LR3 |
24 months |
12.4 |
Women´s Locker Room |
||
12.4.a |
The door is inaccessible because it requires 15 pounds of force to open. |
D2 |
24 months |
12.4.b |
The soap dispenser is inaccessible because the controls are mounted 45 inches above the finished floor over the lavatory, which is 25 inches deep. |
TR4 |
24 months |
12.4.c |
The lavatory is inaccessible because the top of the rim or counter is 35 inches above the finished floor. |
TR11 |
24 months |
12.4.d |
The designated accessible toilet is inaccessible because its centerline is 19½ inches from the side wall. |
ST17 |
24 months |
12.4.e |
No accessible coat hook has been provided. |
TR1 |
24 months |
12.4.f |
The side grab bar at the toilet is inaccessible because it is mounted with the far end 51 inches from the rear wall. |
ST7 |
24 months |
12.4. |
The shower is inaccessible because the seat is installed backwards and 20¼ inches above the finished floor, and the controls are 53 inches above the finished floor. |
B8 |
24 months |
12.4.h |
The bench is inaccessible because it is 14½ inches wide and does not have clear floor space alongside to allow for a transfer. |
LR1 |
24 months |
12.4.i |
The lockers are inaccessible because they require tight grasping to open, and the hooks are more than 54 inches above the finished floor. |
LR3 TR1 |
24 months |
12.5 |
Drinking Fountains Outside Locker Rooms: The drinking fountains protrude into the walkway more than four inches at a height between 27 and 80 inches and are not detectable to blind persons using a cane. |
AR8 |
24 months |
12.6 |
Employee Break Room. The door between the break room and the lobby is inaccessible because it requires 13 pounds of force to open. |
D2 |
24 months |
13 |
The Solid Waste Office, at 235 Operations Center Drive |
||
13.1 |
Interior Accessible Route |
||
13.1.a |
The fire extinguisher and the drinking fountain on the route to the men´s locker room protrude into the walkway more than four inches at a height between 27 and 80 inches and are not detectable to blind persons using a cane. |
AR8 |
24 months |
13.1.b |
The door from the lobby to the break room and locker rooms is inaccessible because it requires 13 pounds of force to open. |
D2 |
24 months |
13.2 |
Men´s Locker Room |
||
13.2.a |
The door is inaccessible because it requires 7 pounds of force to open. |
D2 |
24 months |
13.2.b |
No accessible mirror has been provided. |
TR14 |
24 months |
13.2.c |
The seat cover dispenser is inaccessible because the controls are mounted 57 inches above the finished floor over the toilet. |
TR4 |
24 months |
13.2.d |
The lavatory is inaccessible because the top of the rim or counter is 35 inches above the finished floor. |
TR11 |
24 months |
13.2.e |
The transfer shower is inaccessible because it has no seat, the controls are 20 inches from the open side of the shower, and the shower hose is 57½ inches long. |
B8 |
24 months |
13.2.f |
The benches are inaccessible because they are 9½ inches wide and are not attached to the wall. |
LR1 |
24 months |
13.2. |
The lockers are inaccessible because they require tight grasping to open. |
LR3 |
24 months |