Attachment F

 

 

Newly Constructed Facilities

                                                                                                           

Please Note:  Paragraph 36 of the Settlement Agreement requires that within three months of the effective date of this Agreement, the County will provide signage as necessary to comply with 28 C.F.R. § 35.163(b), after having surveyed all facilities that are the subject of this Agreement for the purpose of identifying those that have multiple entrances not all of which are accessible.

 

In order to ensure that the following spaces and elements in County facilities, for which construction was commenced after January 26, 1992, are readily accessible to and usable by persons with disabilities, the County will take the following actions:

 

1.         Within 6 months of the effective date of this Agreement, the County will complete the following modifications to the River Valley Detention Center (Juvenile) - Building B, located at 3206 West McDonough Street, Joliet:

 

a.         Single-User Toilet Room (booking area)

i. The toilet room lacks an accessible toilet paper dispenser.  Provide a toilet paper dispenser that is mounted within reach, with its top at least 1½ inches under the side grab bar, and centered at least 19 inches above the finished floor.  Standards §§ 4.1.3(11), 4.22.4, 4.16.6, Fig. 29(b).

 

b.         Shower Stall (booking area)

i. The soap dispenser is more than 48 inches above the finished floor and the continuous grab bar extends only to 2 sides of the shower.  Provide a shower in this room that is exactly 36 inches wide and 36 inches deep with a 48 inch long and 36 inch wide clear floor space alongside the shower opening, and an L-shaped shower seat mounted on the wall opposite the controls and extending the full depth of the stall; OR a shower that is at least 30 inches deep and 60 inches wide with no curb or threshold and with a 36 inch deep and 60 inch wide clear floor space at the shower opening.  Ensure that the shower has grab bars, controls, a shower spray unit, and a seat, curb, and enclosure, if provided, that comply fully with the Standards and with Figs. 35, 36, and 37, as applicable.  Standards §§ 4.1.3(11), 4.21, Figs. 35, 36, 37.           

 

2.         Within 12 months of the effective date of this Agreement, except as noted below, the County will complete the following modifications to the River Valley Justice Center Juvenile Facility - Building A, located 3200 West McDonough Street, Joliet:

 

a.         Parking

i. Although there are 118 spaces with 6 spaces designated as reserved for persons with disabilities, one space is 95 inches wide and the signage is too low and can be obstructed by parked vehicles.  On the shortest accessible route to the accessible entrance, provide one van accessible space and four standard spaces designated as reserved for people with disabilities.  Ensure that standard accessible spaces are a minimum of 96 inches wide and served by access aisles at least 60 inches wide.  Ensure that van accessible spaces are a minimum of 96 inches wide and served by access aisles at least 96 inches wide.  At all spaces designated as reserved for persons with disabilities, provide vertical signs with the International Symbol of Accessibility located such that they cannot be obstructed by parked vehicles.  At van accessible spaces, provide an additional "Van-Accessible" sign located below the International Symbol of Accessibility.  Ensure that all spaces and access aisles for persons with disabilities are flat and level, with slopes and cross-slopes not exceeding 1:50 in all directions, and that their surfaces are firm, stable, and slip-resistant.  Standards §§ 4.1.2(5), 4.6, 4.30.7(1).

 

b.         Elevators

i. There is no hoistway signage on floors one and two.  Provide signage at hoistway entrances with raised and Braille floor designations on both jambs such that the centerline of the characters is 60 inches above the finished floor and the characters are 2 inches high.  Standards §§ 4.1.3(5), 4.10.5, Fig. 20.

 

c.         Toilet Rooms with Stalls

i. Men's - 1st Floor (Lobby)

(1) The lavatory pipes are not covered or configured to protect against contact.  Provide hot water and drain pipes that are insulated or otherwise configured to protect against contact.  Standards §§ 4.1.3(11), 4.22.6, 4.19.4.

(2) No accessible coat hook has been provided.  Provide a coat hook at a maximum height above the finished floor of 48 inches for a forward approach or 54 inches for a side approach and that is accompanied by clear floor space of 30 by 48 inches that allows a forward or parallel approach by a person using a wheelchair.  Standards §§ 4.1.3(12)(a), 4.25.2, 4.25.3, 4.2.4, 4.2.5, 4.2.6.

 

ii. Women's 1st Floor (Lobby)

(1) The sanitary napkin dispenser is 57 inches above the finished floor.  Provide a sanitary napkin dispenser with the controls a maximum height above the finished floor of 48 inches for a forward approach or 54 inches for a side approach and that is accompanied by clear floor space of 30 by 48 inches that allows a forward or parallel approach by a person using a wheelchair.  Standards §§ 4.1.3(13), 4.27.2, 4.27.3, 4.2.4, 4.2.5, 4.2.6.  

(2) The lavatory pipes are not covered or configured to protect against contact.  Provide hot water and drain pipes that are insulated or otherwise configured to protect against contact.  Standards §§ 4.1.3(11), 4.22.6, 4.19.4.

(3) No accessible coat hook has been provided.  Provide a coat hook at a maximum height above the finished floor of 48 inches for a forward approach or 54 inches for a side approach and that is accompanied by clear floor space of 30 by 48 inches that allows a forward or parallel approach by a person using a wheelchair.  Standards §§ 4.1.3(12)(a), 4.25.2, 4.25.3, 4.2.4, 4.2.5, 4.2.6.

 

iii. Women's 2nd Floor

(1) The toilet room sign lacks Braille.  Provide a toilet room sign with raised and Braille characters.  The sign shall be mounted on the wall adjacent to the latch side of the door with the centerline of the sign at 60 inches above the finished floor and situated such that a person can approach within 3 inches of the sign without encountering an obstruction or standing within a door swing.  Standards §§ 4.1.2(7)(d), 4.30.1, 4.30.4, 4.30.5, 4.30.6.

(2) The pressure required to open the door is 10 pounds of force.  Provide a door that requires no more than 5 pounds of force to open.  Standards §§ 4.1.3(7)(b), 4.13.11(2)(b).

(3) The sanitary napkin dispenser is 57 inches above the finished floor.  Provide a sanitary napkin dispenser with the controls a maximum height above the finished floor of 48 inches for a forward approach or 54 inches for a side approach and that is accompanied by clear floor space of 30 by 48 inches that allows a forward or parallel approach by a person using a wheelchair.  Standards §§ 4.1.3(13), 4.27.2, 4.27.3, 4.2.4, 4.2.5, 4.2.6.  

(4) The lavatory pipes are not covered or configured to protect against contact.  Provide hot water and drain pipes that are insulated or otherwise configured to protect against contact.  Standards §§ 4.1.3(11), 4.22.6, 4.19.4.

(5) No accessible coat hook has been provided.  Provide a coat hook at a maximum height above the finished floor of 48 inches for a forward approach or 54 inches for a side approach and that is accompanied by clear floor space of 30 by 48 inches that allows a forward or parallel approach by a person using a wheelchair.  Standards §§ 4.1.3(12)(a), 4.25.2, 4.25.3, 4.2.4, 4.2.5, 4.2.6.

(6) The toilet centerline is 19 inches from the side wall.  Provide a toilet with a centerline that measures 18 inches from the near side wall.  Standards §§ 4.1.3(11), 4.22.4, 4.17.3, Fig. 30.[1]

 

iv. Men's 2nd Floor

(1) The toilet room sign lacks Braille.  Provide a toilet room sign with raised and Braille characters.  The sign shall be mounted on the wall adjacent to the latch side of the door with the centerline of the sign at 60 inches above the finished floor and situated such that a person can approach within 3 inches of the sign without encountering an obstruction or standing within a door swing.  Standards §§ 4.1.2(7)(d), 4.30.1, 4.30.4, 4.30.5, 4.30.6.

(2) The pressure required to open the door is 10 pounds of force.  Provide a door that requires no more than 5 pounds of force to open.  Standards §§ 4.1.3(7)(b), 4.13.11(2)(b).

(3) The lavatory pipes are not covered or configured to protect against contact.  Provide hot water and drain pipes that are insulated or otherwise configured to protect against contact.  Standards §§ 4.1.3(11), 4.22.6, 4.19.4.

(4) No accessible coat hook has been provided.  Provide a coat hook at a maximum height above the finished floor of 48 inches for a forward approach or 54 inches for a side approach and that is accompanied by clear floor space of 30 by 48 inches that allows a forward or parallel approach by a person using a wheelchair.  Standards §§ 4.1.3(12)(a), 4.25.2, 4.25.3, 4.2.4, 4.2.5, 4.2.6.

(5) The toilet centerline is 19 inches from the side wall.  Provide a toilet with a centerline that measures 18 inches from the near side wall.  Standards §§ 4.1.3(11), 4.22.4, 4.17.3, Fig. 30.

 

d.         Offices and Counters

i. Police Department Office

(1) The pressure required to open the door is 7 pounds of force.  Provide a door that requires no more than 5 pounds of force to open.  Standards §§ 4.1.3(7)(b), 4.13.11(2)(b).


 

(2) The top of counter is 37 ½ inches above the finished floor.  Provide a counter on an accessible route such that a portion of the counter is at least 36 inches wide and no more than 36 inches above the finished floor, or provide an auxiliary counter with a maximum height of 36 inches in close proximity to the main counter, or provide equivalent facilitation.   Equivalent facilitation may be provided in the form of a folding shelf attached to the main counter, an auxiliary table nearby, a clip board made available to the public, or other means.  Standards §§ 4.1.1(2), 7.2(2), 4.1.3(1), 4.3.

 

ii. State's Attorney's Office

(1) The pressure required to open the door is 10 pounds of force.  Provide a door that requires no more than 5 pounds of force to open.  Standards §§ 4.1.3(7)(b), 4.13.11(2)(b).

(2) The top of the counter is 37 ½ inches above the finished floor.  Provide a counter on an accessible route such that a portion of the counter is at least 36 inches wide and no more than 36 inches above the finished floor.  Standards §§ 4.1.1(2), 7.2(1), 4.1.3(1), 4.3.

 

iii. Juvenile Probation Office

(1) The pressure required to open the door is 10 pounds of force.  Provide a door that requires no more than 5 pounds of force to open.  Standards §§ 4.1.3(7)(b), 4.13.11(2)(b).

(2) The top of counter is 37½ inches above the finished floor.  Provide a counter on an accessible route such that a portion of the counter is at least 36 inches wide and no more than 36 inches above the finished floor.  Standards §§ 4.1.1(2), 7.2(1), 4.1.3(1), 4.3.

 

iv. Clerk of Circuit Court

(1) The pressure required to open the door is 10 pounds of force.  Provide a door that requires no more than 5 pounds of force to open.  Standards §§ 4.1.3(7)(b), 4.13.11(2)(b).

 

e.         Unisex, Single-User Toilet Room (Juvenile Probation, drug testing)

i. The toilet seat cover dispenser is 61 inches above the finished floor.  Provide a toilet seat cover dispenser with the controls a maximum height above the finished floor of 48 inches for a forward approach or 54 inches for a side approach and that is accompanied by clear floor space of 30 by 48 inches that allows a forward or parallel approach by a person using a wheelchair.  Standards §§ 4.1.3(13), 4.27.2, 4.27.3, 4.2.4, 4.2.5, 4.2.6.

ii. The lavatory pipes are not covered or configured to protect against contact.  Provide hot water and drain pipes that are insulated or otherwise configured to protect against contact.  Standards §§ 4.1.3(11), 4.22.6, 4.19.4.

iii. The toilet centerline is 17 inches from the side wall.  Within 24 months, provide a toilet with a centerline that measures 18 inches from the near side wall.  Standards §§ 4.1.3(11), 4.22.4, 4.16.2, Fig. 28.

iv. The flush control valve is on the closed side.  Provide a flush control mounted on the "open" side of the toilet's clear floor space; 44 inches or less above the finished floor; and requiring a maximum of 5 pounds of force to operate; or provide an automatic flush device.  Standards §§ 4.1.3(11), 4.22.4, 4.16.5, 4.27.4.

 

f.          Public Telephone

i. The top of the counter is 35 inches above the finished floor, and the highest operable part is 58 inches above the finished floor.  Provide an accessible telephone with a clear floor space of at least 30 inches by 48 inches that allows either a forward or parallel approach by a person using a wheelchair such that bases, enclosures, and fixed seats do not impede approaches to the telephone; with the highest operable part of the telephone mounted no more than 48 inches above the floor for a front approach or no more than 54 inches above the floor for a side approach; that is hearing aid compatible and has a volume control mechanism; with telephone books, if provided, located between 15 and 48 inches above the finished floor for a front approach or between 9 and 54 inches above the finished floor for a side approach; with a cord of at least 29 inches long from the telephone to the handset; and with signage that complies with the Standards.  Standards §§ 4.1.3(17), 4.31, 4.30.7(2).

ii. The telephone is not detectable to a blind person using a cane.  Provide a telephone at this location such that its bottom leading edges measure no more than 27 inches above the finished floor or protrude no more than 4 inches into the walkway.  Standards §§ 4.1.2(3), 4.4.

 

3.         Within 12 months of the effective date of this Agreement, the County will complete the following modifications to the Highway Department: Subdivision Engineering, located at 16841 West Laraway Road, Joliet:

 

a.         Unisex, Single-User Toilet Room

i. The toilet room sign is not mounted on the latch side of the door.  Provide a toilet room sign with raised and Braille characters.  The sign shall be mounted on the wall adjacent to the latch side of the door with the centerline of the sign at 60 inches above the finished floor and situated such that a person can approach within 3 inches of the sign without encountering an obstruction or standing within a door swing.  Standards §§ 4.1.2(7)(d), 4.30.1, 4.30.4, 4.30.5, 4.30.6.

ii. There is no visual alarm provided.  Provide visual alarm devices in toilet rooms and any other general usage areas (e.g., meeting rooms), hallways, lobbies, and any other area for common use.  Such devices shall be integrated into the facility alarm system and shall meet the requirements of the Standards for lamp type, color, pulse duration, intensity, and flash rate.  Visual alarm appliances shall be placed 80 inches above the highest floor level within the space or 6 inches below the ceiling, whichever is lower.  Visual alarm appliances shall be located such that no place in any room or space, including common corridors or hallways, required to have a visual alarm appliance shall be more than 50 feet from the signal.  In large rooms and spaces exceeding 100 feet across, without obstructions 6 feet above the finished floor, devices may be placed around the perimeter, spaced a maximum of 100 feet apart, in lieu of suspending appliances from the ceiling.  Standards §§ 4.1.3(14), 4.28.3.

iii. No accessible mirror has been provided.  Provide a mirror with the bottom edge of its reflecting surface no more than 40 inches above the finished floor.  Standards §§ 4.1.3(11), 4.22.6, 4.19.6.

iv. The paper towel dispenser is mounted 61 inches above the finished floor.   Provide a paper towel dispenser with mechanical controls, if any, that can be operated with 5 lbf or less and that can be used with one hand and without tight grasping, pinching, or twisting of the wrist (lever-operated, push-type, and electronically controlled mechanisms are examples of acceptable designs).  Standards §§ 4.1.3(13), 4.27.4.

v. The distance of the far end of the side grab bar to the rear wall is less than 54 inches.   Provide a side grab bar that is at least 40 inches in overall length, with the far end mounted at least 52 inches from the rear wall and the closer end 12 inches or less from the rear wall.  Standards §§ 4.1.3(11), 4.22.4, 4.16.4, Fig. 29(b).

 

4.         Within 12 months of the effective date of this Agreement, the County will complete the following modifications to the newly constructed portion of the Health Department Building, located at 501 Ella Avenue, Joliet:

 

a.         Community Room

i. Accessible Route to Exterior Entrance

(1) The route (next to the lower clinic) has a cross slope of 5.3 % and is not level.  Provide at least one accessible route within the boundary of the site connecting these elements that, to the maximum extent feasible, coincides with the route for the general public.  The accessible route must have a minimum clear width of 36 inches, or a minimum clear width of 42 inches if there is a turn around an obstruction less than 48 inches wide; have passing spaces at least 60 inches by 60 inches at least every 200 feet; have a minimum clear headroom of 80 inches; have a surface that is firm, stable, and slip resistant; have, in the absence of a curb ramp, ramp, elevator, or platform lift, no level changes in excess of ½ inch vertically; and have a running slope of less than 1:20 (5%) (or have been constructed as a fully accessible ramp) and a cross slope of less than 1:50 (2%).  Standards §§ 4.1.3(1), 4.3, 4.5, Fig. 7.

(2) Ramp

(a) The slope of the ramp is 9%, the landing at the top is 8.7%, there is a drain that is recessed ¾ inches, and the handrails are 33 inches above the finished floor.  Provide a ramp that is at least 36 inches wide and has a slope not exceeding 1:12 and a cross slope not exceeding 1:50.  Provide level landings at the top and bottom of the ramp that are at least as wide as the ramp and at least 60 inches long.  If the ramp changes direction, provide a level landing measuring at least 60 inches by 60 inches at the change in direction.  On both sides of the ramp, provide handrails between 1¼ inches and 1½ inches in diameter with a continuous gripping surface.  Ensure that the handrails extend at least 12 inches beyond the top and bottom of the ramp parallel with the ground surface, that they are mounted between 34 inches and 38 inches above the ramp surface, that they will not rotate within their fittings, and that they have ends that are rounded or return smoothly to floor, wall, or post.  Provide edge protection that is at least 2 inches high at the ramp's drop off sides.  Ensure that the ramp and its level landing at the top and bottom are designed and maintained so that water does not accumulate on walking surfaces.  Standards §§ 4.1.2(1), 4.1.2(2), 4.3.8, 4.8.

(3) There is an ash tray that is in the path of travel and is not detectable to a blind person using a cane.  Provide an accessible route such that its bottom leading edges measure no more than 27 inches above the finished floor or protrude no more than 4 inches into the walkway.  Standards §§ 4.1.2(3), 4.4.

 

ii. Toilet Rooms with Stalls

(1) Women's

(a) The pressure required to open the door is 7 pounds of force.  Provide a door that requires no more than 5 pounds of force to open.  Standards §§ 4.1.3(7)(b), 4.13.11(2)(b).

(b) There is inadequate maneuvering space on the pull side of the door to allow a person using a wheelchair to open the door.  On the pull side of the door, provide maneuvering clearance at least 60 inches deep and provide a minimum of 18 inches (24 inches is preferred) of maneuvering clearance on the latch side of the door.  Standards §§ 4.1.3(7)(b), 4.13.6, Fig. 25(a).

(c) No accessible mirror has been provided.  Provide a mirror with the bottom edge of its reflecting surface no more than 40 inches above the finished floor.  Standards §§ 4.1.3(11), 4.22.6, 4.19.6.

(d) The lavatory pipes are not covered or configured to protect against contact.  Provide hot water and drain pipes that are insulated or otherwise configured to protect against contact.  Standards §§ 4.1.3(11), 4.22.6, 4.19.4.

(e) The flush control valve is on the closed side of the toilet.  Provide a flush control mounted on the "open" side of the toilet's clear floor space; 44 inches or less above the finished floor; and requiring a maximum of 5 pounds of force to operate; or provide an automatic flush device.  Standards §§ 4.1.3(11), 4.22.4, 4.16.5, 4.17.2, 4.27.4.

(f) No accessible coat hook has been provided.  Provide a coat hook at a maximum height above the finished floor of 48 inches for a forward approach or 54 inches for a side approach and that is accompanied by clear floor space of 30 by 48 inches that allows a forward or parallel approach by a person using a wheelchair.  Standards §§ 4.1.3(12)(a), 4.25.2, 4.25.3, 4.2.4, 4.2.5, 4.2.6.

(g) The toilet paper dispenser is 18 ½ inches above the finished floor and 37 ½ inches from the rear wall.  Provide a toilet paper dispenser that is mounted with its top at least 1½ inches under the side grab bar and 36 inches or less from the rear wall and is centered at least 19 inches above the finished floor.  Standards §§ 4.1.3(11), 4.22.4, 4.17.3, Fig. 30(d).

 

(2) Men's

(a) No accessible mirror has been provided.  Provide a mirror with the bottom edge of its reflecting surface no more than 40 inches above the finished floor.  Standards §§ 4.1.3(11), 4.22.6, 4.19.6.

(b) No accessible coat hook has been provided.  Provide a coat hook at a maximum height above the finished floor of 48 inches for a forward approach or 54 inches for a side approach and that is accompanied by clear floor space of 30 by 48 inches that allows a forward or parallel approach by a person using a wheelchair.  Standards §§ 4.1.3(12)(a), 4.25.2, 4.25.3, 4.2.4, 4.2.5, 4.2.6.

(c) The toilet paper dispenser is 38 inches from the rear wall.  Provide a toilet paper dispenser that is mounted with its top at least 1½ inches under the side grab bar and 36 inches or less from the rear wall and is centered at least 19 inches above the finished floor.  Standards §§ 4.1.3(11), 4.22.4, 4.17.3, Fig. 30(d).

 

iii. Exterior Ramp (Rear Side of Building, OB-GYN side)

(1) The distance between the handrails and the wall is 2 inches and the handrail diameter is 2 inches.  Provide handrails that are between 1¼ inches and 1½ inches in diameter with a continuous gripping surface along both sides of the ramp, extending at least 12 inches beyond the top and bottom of the ramp parallel with the ground surface.  Ensure that handrails are mounted between 34 inches and 38 inches above the ramp surface, with ends rounded or returned smoothly to the floor, wall, or post, and that they do not rotate within their fittings.  Standards §§ 4.1.2(1), 4.1.2(2), 4.8.5.

 

iv. Interior Entrance Door

(1) The pressure required to open the door is 7 pounds of force.   Provide a door that requires no more than 5 pounds of force to open.  Standards §§ 4.1.3(7)(b), 4.13.11(2)(b).

 

v. Reception Area

(1) The auxiliary counters are not accessible.  Provide a counter on an accessible route such that a portion of the counter is at least 36 inches wide and no more than 36 inches above the finished floor, or provide an auxiliary counter with a maximum height of 36 inches in close proximity to the main counter, or provide equivalent facilitation.   Equivalent facilitation may be provided in the form of a folding shelf attached to the main counter, an auxiliary table nearby, a clip board made available to the public, or other means.  Standards §§ 4.1.1(2), 7.2(2), 4.1.3(1), 4.3.

vi. Sign-in Area

(1) The main counter is 41 inches above the finished floor, protrudes 7 inches into the path of travel, and would not be detectable to a blind person using a cane.  Provide a counter on an accessible route such that a portion of the counter is at least 36 inches wide and no more than 36 inches above the finished floor, or provide an auxiliary counter with a maximum height of 36 inches in close proximity to the main counter, or provide equivalent facilitation.   Equivalent facilitation may be provided in the form of a folding shelf attached to the main counter, an auxiliary table nearby, a clip board made available to the public, or other means.  Standards §§ 4.1.1(2), 7.2(2), 4.1.3(1), 4.3.  Provide an accessible route at this location such that no objects with their bottom leading edges measuring between 27 inches and 80 inches above the finished floor protrude more than 4 inches into walks, halls, corridors, passageways, or aisles.  Free-standing objects mounted on posts or pylons may overhang 12 inches maximum from 27 inches to 80 inches above the ground or finished floor.  Standards §§ 4.1.2(3), 4.4.

 

vii. Toilet Room with Stalls (Outside Waiting Rooms)

(1) Women's toilet room

(a) The pressure required to open the door is 7 pounds of force.  Provide a door that requires no more than 5 pounds of force to open.  Standards §§ 4.1.3(7)(b), 4.13.11(2)(b).

(b) There is inadequate maneuvering space on the pull side of the door to allow a person using a wheelchair to open the door.  On the pull side of the door, provide maneuvering clearance at least 60 inches deep and provide a minimum of 18 inches (24 inches is preferred) of maneuvering clearance on the latch side of the door.  Standards §§ 4.1.3(7)(b), 4.13.6, Fig. 25(a).

(c) The air dryer is more than 27 inches above the finished floor,  protrudes 9 ½ inches into the path of travel and is not detectable to a blind person using a cane.  Provide an air dryer such that its bottom leading edges measure no more than 27 inches above the finished floor or protrude no more than 4 inches into the walkway.  Standards §§ 4.1.2(3), 4.4.

(d) The baby changing station blocks the path of travel into the standard accessible toilet stall.  Provide an accessible route to the accessible toilet stall with required minimum width, passing space, head room, surface textures, slopes, and changes in level.  Standards §§ 4.1.3(11), 4.22.1, 4.3.1, 4.3.2, 4.3.3, 4.3.4, 4.3.5, 4.3.6, 4.3.7, 4.3.8.

(e) Toilet Stall

(i) The flush control valve is on the closed side of the toilet.  Provide a flush control mounted on the "open" side of the toilet's clear floor space; 44 inches or less above the finished floor; and requiring a maximum of 5 pounds of force to operate; or provide an automatic flush device.  Standards §§ 4.1.3(11), 4.22.4, 4.16.5, 4.17.2, 4.27.4.

(ii) No accessible coat hook has been provided.  Provide a coat hook at a maximum height above the finished floor of 48 inches for a forward approach or 54 inches for a side approach and that is accompanied by clear floor space of 30 by 48 inches that allows a forward or parallel approach by a person using a wheelchair.  Standards §§ 4.1.3(12)(a), 4.25.2, 4.25.3, 4.2.4, 4.2.5, 4.2.6.

(iii) The toilet paper dispenser is 38 inches from the rear wall.  Provide a toilet paper dispenser that is mounted with its top at least 1½ inches under the side grab bar and 36 inches or less from the rear wall and is centered at least 19 inches above the finished floor.  Standards §§ 4.1.3(11), 4.22.4, 4.17.3, Fig. 30(d).

(iv) The space between the side grab bar and the wall is 1¾ inches.  Provide a side grab bar that is at least 40 inches in overall length, with the far end mounted at least 52 inches from the rear wall and the closer end 12 inches or less from the rear wall; mounted 33 to 36 inches above the finished floor; with a diameter between 1¼ and 1½ inches; with 1½ inches between the grab bar and the wall; and at least 1½ inches between the grab bar and any other object, such as the toilet paper dispenser.  Standards §§ 4.1.3(11), 4.22.4, 4.17.6, 4.26.2, Figs. 30(a), (d).

 

(2) Men's toilet room

(a) The pressure required to open the door is 10 pounds of force.  Provide a door that requires no more than 5 pounds of force to open.  Standards §§ 4.1.3(7)(b), 4.13.11(2)(b).

(b) There is inadequate maneuvering space on the pull side of the door to allow a person using a wheelchair to open the door.  On the pull side of the door, provide maneuvering clearance at least 60 inches deep and provide a minimum of 18 inches (24 inches is preferred) of maneuvering clearance on the latch side of the door.  Standards §§ 4.1.3(7)(b), 4.13.6, Fig. 25(a).

(c) No accessible mirror has been provided.  Provide a mirror with the bottom edge of its reflecting surface no more than 40 inches above the finished floor.  Standards §§ 4.1.3(11), 4.22.6, 4.19.6.

 

viii. Drinking Fountain

(1) Fountain up the Ramp from the Waiting Room

(a) The spout height is more than 36 inches above the finished floor, the control requires 10 pounds of force to operate and there is inadequate knee clearances.  Provide at least one drinking fountain with a spout height no higher than 36 inches, measured from the finished floor or ground surface to the spout outlet; and a spout located at the front of the unit that directs the water flow in a trajectory that is nearly parallel to the front of the unit and is positioned so the flow of water is within 3 inches of the front edge of the fountain and at least 4 inches high.  Ensure that fountain controls are operable with one hand, require 5 lbf or less to operate without tight grasping, pinching, or twisting of the wrist; and are front mounted or side mounted near the front edge.  For each accessible drinking fountain, provide a drinking fountain that is accessible to people who have difficulty bending or stooping.  This can be accommodated by the use of a "hi-lo" fountain; by providing one fountain accessible to those who use wheelchairs and one fountain at a standard height convenient for those who have difficulty bending; by providing a fountain accessible to people who use wheelchairs and a cup dispenser; or by such other means as would achieve the required accessibility for each group of people.  Standards §§ 4.1.3(10), 4.15, 4.27.4, Fig. 27.

 

ix. Counter/Shelf - Waiting Rooms

(1) The shelf is more than 27 inches above the finished floor, extends more than 4 inches into the path of travel and is not detectable to a blind person using a cane.  Provide a shelf at this location such that its bottom leading edges measure no more than 27 inches above the finished floor or protrude no more than 4 inches into the walkway.  Standards §§ 4.1.2(3), 4.4.

                                   

 



            [1]Shifting a toilet a small distance to comply with the centerline requirement need not be expensive.  The important factor is maintaining the correct distance between the side grab bar and the toilet.  Options include moving the partition on which the grab bar is mounted or installing an offset flange to shift the toilet.  Another option is to mount the grab bar on a board attached to the side wall or partition.  The board must extend 1½ inches below the grab bar and 18 inches above the grab bar to achieve the appropriate distance between toilet and grab bar.