ATTACHMENT J: Modifications to Altered FacilitiesPlease Note: Paragraph 52 of the Settlement Agreement requires that within three months of the effective date of this Agreement, the County provide signage as necessary to comply with 28 C.F.R. § 35.163(b), after having surveyed all facilities that are the subject of this Agreement for the purpose of identifying those that have multiple entrances not all of which are accessible. The chart below lists the facilities surveyed by the Department, the access issues identified during the survey, and the actions required to correct the access issues. Required actions are listed using an alphanumeric code. The key to the alphanumeric codes is provided in Attachment M to this Agreement. In order to ensure that the following spaces and elements in the County's facilities in which alterations occurred after January 26, 1992, are readily accessible to and usable by persons with disabilities, the County will take the actions referenced by the alphanumeric code and described in detail in Attachment M to this Settlement Agreement within the time period specified below, which time period will begin to run on the effective date of this Agreement. |
|||
Item # |
Access Issue |
Required Action |
Completion Date |
---|---|---|---|
1. |
Bank Building, 19 Public Square, Belleville |
||
1.1. |
Employee Parking Lot. The parking lot, with a total of 14 parking spaces, is inaccessible because it has no spaces designated as accessible. This lot requires 1 van accessible space. |
P3 |
12 months |
1.2. |
Health Department Public Parking Lot |
||
1.2.a. |
The parking lot, with a total of 40 parking spaces, is inaccessible because it only has 1 space designated as accessible. This lot requires 1 van accessible space and 1 standard accessible space. |
P3 |
12 months |
1.2.b. |
The parking reserved for persons with disabilities is inaccessible because the space has a slope of 6.4% and the access aisle has a slope of 4.2%. |
P7 |
12 months |
1.3. |
Exterior Entrances |
||
1.3.a. |
The building does not have directional signage posted at the inaccessible entrance. |
D16 |
6 months |
1.3.b. |
The accessible entrance door is inaccessible because there is a 1 inch high threshold. |
D22 |
6 months |
1.4. |
North Side Interior Ramp. The ramp is inaccessible because the top segment slopes up to 11.3%, the level landing at the change in ramp direction is 53 inches by 54 inches, and the handrails do not have sufficient extensions at the top. |
R3 |
30 months |
1.5. |
Interior Doors. The doors throughout the facility are inaccessible because they require more than 5 pounds of force to open. |
D2 |
6 months |
1.6. |
Drinking Fountain in Health Clinic Lobby. The drinking fountain is inaccessible because the flow of water is 3½ inches from the front of the fountain, there are only 26 inches of clear knee height provided, and there is no drinking fountain provided for people who have difficulty bending or stooping. |
DF1 |
6 months |
1.7. |
Men's Toilet Room with Stalls in Health Clinic |
||
1.7.a. |
The toilet room sign is mounted on the door. |
TR17 |
6 months |
1.7.b. |
The door is inaccessible because it has an opening width of only 29½ inches. |
D25 |
24 months |
1.7.c. |
Although an audible alarm is provided in this facility, there is no visual alarm appliance in the toilet room. |
TR21 |
12 months |
1.7.d. |
The lavatory is inaccessible because the hot water pipes are not insulated or otherwise configured to protect against contact. |
TR12 |
6 months |
1.7.e. |
The designated accessible toilet is inaccessible because the top of the seat is 19½ inches high. |
ST20 |
12 months |
1.7.f. |
The designated accessible toilet is inaccessible because its centerline is 22½ inches from the side wall. |
ST17 |
12 months |
1.7.g. |
No accessible coat hook has been provided. |
TR1 |
6 months |
1.7.h. |
The side grab bar at the designated accessible toilet is inaccessible because it is mounted with the far end 48 inches from the rear wall. |
ST7 |
12 months |
1.7.i. |
The rear grab bar at the designated accessible toilet is inaccessible because it is 24 inches long and mounted more than 6 inches from the near side wall. |
ST4 |
12 months |
1.8. |
Women's Toilet Room with Stalls in Health Clinic |
||
1.8.a. |
The toilet room sign is mounted on the door. |
TR17 |
6 months |
1.8.b. |
The door is inaccessible because it has an opening width of only 29 inches. |
D25 |
24 months |
1.8.c. |
Although an audible alarm is provided in this facility, there is no visual alarm appliance in the toilet room. |
TR21 |
12 months |
1.8.d. |
The lavatory is inaccessible because the hot water pipes are not insulated or otherwise configured to protect against contact. |
TR12 |
6 months |
1.8.e. |
The designated accessible toilet is inaccessible because the top of the seat is 20½ inches high. |
ST20 |
12 months |
1.8.f. |
No accessible coat hook has been provided. |
TR1 |
6 months |
1.8.g. |
The side grab bar at the designated accessible toilet is inaccessible because it is mounted with the far end 48 inches from the rear wall. |
ST7 |
6 months |
1.8.h. |
The rear grab bar at the designated accessible toilet is inaccessible because it is 24 inches long and mounted 17 inches from the near side wall. |
ST4 |
6 months |
1.9. |
Single-User Toilet Room |
||
1.9.a. |
The toilet room sign is mounted with the centerline 63 inches high. |
TR17 |
18 months |
1.9.b. |
No accessible mirror has been provided. |
TR14 |
18 months |
1.9.c. |
The toilet room is inaccessible because there is insufficient turning space provided within the room. |
TR19 |
18 months |
1.9.d. |
The lavatory is inaccessible because it has insufficient clear floor space. |
TR8 |
18 months |
1.9.e. |
The toilet is inaccessible because its centerline is 19 inches from the side wall. |
SU15 |
18 months |
1.9.f. |
The side grab bar at the toilet is inaccessible because it is mounted with the far end less than 54 inches from the rear wall. |
SU6 |
18 months |
1.10. |
Elevator Near Lobby |
||
1.10.a. |
The elevator is inaccessible because hall lanterns are not provided that signal up or down. |
E11 |
24 months |
1.10.b. |
The elevator is inaccessible because the car position indicators do not emit a visual signal as the car passes or stops at a floor. |
E5 |
24 months |
1.10.c. |
The elevator is inaccessible because the emergency system requires voice communication to operate, it is not identified by raised symbol and lettering, and it requires tight grasping or pinching to access. |
E8 |
24 months |
1.11. |
Elevator at East End of Building |
||
1.11.a. |
The elevator is inaccessible because the car position indicators do not emit a visual signal as the car passes or stops at a floor. |
E5 |
24 months |
1.11.b. |
The elevator is inaccessible because the emergency system requires tight grasping or pinching to access. |
E8 |
24 months |
1.12. |
Basement Drinking Fountain. The drinking fountain is inaccessible because the water flow is 3½ inches from the front of the fountain, it provides only 26 inches of clear knee height, and there is no drinking fountain provided for people who have difficulty bending or stooping. |
DF1 |
12 months |
1.13. |
2nd Floor Drinking Fountain The drinking fountain is inaccessible because the water flow is 3½ inches from the front of the fountain, the controls require 7 pounds of force to operate, it provides only 26 inches of clear knee height, and there is no drinking fountain provided for people who have difficulty bending or stooping. |
DF1 |
12 months |
1.14. |
3rd Floor Drinking Fountain |
||
1.14.a. |
The drinking fountain is inaccessible because the water flow is 4 inches from the front of the fountain and there is no drinking fountain provided for people who have difficulty bending or stooping. |
DF1 |
12 months |
1.14.b. |
The drinking fountain protrudes into the walkway and is not detectable to blind persons using a cane. |
AR8 |
12 months |
1.15. |
2nd Floor East End Doors. The doors in this section of the facility are inaccessible because knob hardware is used. |
D1 |
12 months |
1.16. |
Basement Level Counter. The counter protrudes into the walkway and is not detectable to blind persons using a cane. |
AR8 |
6 months |
1.17. |
Women's Toilet Rooms with Stalls, Basement |
||
1.17.a. |
The toilet room sign is mounted on the door and has no raised or Braille characters. |
TR17 |
12 months |
1.17.b. |
The door is inaccessible because it has an opening width of only 29½ inches. |
D25 |
24 months |
1.17.c. |
Although an audible alarm is provided in this facility, there is no visual alarm appliance in the toilet room. |
TR21 |
24 months |
1.17.d. |
The feminine napkin dispenser is inaccessible because the controls require twisting of the wrist to operate. |
TR3 |
24 months |
1.17.e. |
The lavatory is inaccessible because the hot water pipes are not insulated or otherwise configured to protect against contact. |
TR12 |
24 months |
1.17.f. |
The designated accessible toilet stall is inaccessible because it is 58 inches wide. |
ST16 |
24 months |
1.17.g. |
The designated accessible toilet is inaccessible because the top of the seat is 20½ inches high. |
ST20 |
24 months |
1.17.h. |
The designated accessible toilet is inaccessible because its centerline is 28 inches from the side wall. |
ST17 |
24 months |
1.17.i. |
No accessible coat hook has been provided. |
TR1 |
24 months |
1.17.j. |
The side grab bar at the designated accessible toilet is inaccessible because it is mounted with the far end 49 inches from the rear wall. |
ST7 |
24 months |
1.17.k. |
The rear grab bar at the designated accessible toilet is inaccessible because it is 24 inches long and it is mounted more than 6 inches from the side wall. |
ST4 |
24 months |
1.18. |
Men's Toilet Room with Stalls, Basement |
||
1.18.a. |
The toilet room sign is mounted on the door and has no raised or Braille characters. |
TR17 |
24 months |
1.18.b. |
The door is inaccessible because it has an opening width of only 29 inches. |
D25 |
24 months |
1.18.c. |
Although an audible alarm is provided in this facility, there is no visual alarm appliance in the toilet room. |
TR21 |
24 months |
1.18.d. |
The lavatory is inaccessible because the hot water pipes are not insulated or otherwise configured to protect against contact. |
TR12 |
24 months |
1.18.e. |
The designated accessible toilet is inaccessible because its centerline is 19 inches from the side wall. |
ST17 |
24 months |
1.18.f. |
No accessible coat hook has been provided. |
TR1 |
24 months |
1.18.g. |
The side grab bar at the designated accessible toilet is inaccessible because it is mounted with the far end 49 inches from the rear wall. |
ST7 |
24 months |
1.18.h. |
The rear grab bar at the designated accessible toilet is inaccessible because it is 24 inches long and it is mounted more than 6 inches from the side wall. |
ST4 |
24 months |
1.19. |
Women's Toilet Room with Stalls, 2nd Floor |
||
1.19.a. |
The toilet room sign is mounted on the door and has no raised or Braille characters. |
TR17 |
24 months |
1.19.b. |
The door is inaccessible because it has an opening width of only 29 inches. |
D25 |
24 months |
1.19.c. |
Although an audible alarm is provided in this facility, there is no visual alarm appliance in the toilet room. |
TR21 |
24 months |
1.19.d. |
The toilet seat cover dispenser is inaccessible because it is mounted with the controls 58 inches high. |
TR5 |
24 months |
1.19.e. |
The lavatory is inaccessible because the hot water pipes are not insulated or otherwise configured to protect against contact. |
TR12 |
24 months |
1.19.f. |
The designated accessible toilet is inaccessible because the top of the seat is 19¾ inches high. |
ST20 |
24 months |
1.19.g. |
The designated accessible toilet is inaccessible because its centerline is 19¼ inches from the side wall. |
ST17 |
24 months |
1.19.h. |
No accessible coat hook has been provided. |
TR1 |
24 months |
1.19.i. |
The side grab bar at the designated accessible toilet is inaccessible because it is mounted with the far end 48¾ inches from the rear wall. |
ST7 |
24 months |
1.19.j. |
The rear grab bar at the designated accessible toilet is inaccessible because it is 24 inches long and it is mounted more than 6 inches from the side wall. |
ST4 |
24 months |
1.20. |
Men's Toilet Room with Stalls, 2nd Floor |
||
1.20.a. |
The toilet room sign is mounted on the door and has no raised or Braille characters. |
TR17 |
24 months |
1.20.b. |
The door is inaccessible because it has an opening width of only 29 inches. |
D25 |
24 months |
1.20.c. |
Although an audible alarm is provided in this facility, there is no visual alarm appliance in the toilet room. |
TR21 |
24 months |
1.20.d. |
The toilet seat cover dispenser is inaccessible because it is mounted with the controls 57 inches high. |
TR5 |
24 months |
1.20.e. |
The paper towel dispenser protrudes into the walkway and is not detectable to blind persons using a cane. |
AR8 |
24 months |
1.20.f. |
The lavatory is inaccessible because the hot water pipes are not insulated or otherwise configured to protect against contact. |
TR12 |
24 months |
1.20.g. |
The designated accessible toilet is inaccessible because the top of the seat is 20 inches high. |
ST20 |
24 months |
1.20.h. |
No accessible coat hook has been provided. |
TR1 |
24 months |
1.20.i. |
The side grab bar at the designated accessible toilet is inaccessible because it is mounted with the farther end 48¾ inches from the rear wall. |
ST7 |
24 months |
1.20.j. |
The rear grab bar at the designated accessible toilet is inaccessible because it is 24 inches long and it is mounted more than 6 inches from the side wall. |
ST4 |
24 months |
1.21. |
Men's Toilet Room with Stalls, 2nd FloorEast Side. The toilet room contains a number of inaccessible elements and is not accessible to people with disabilities. |
ST14 |
24 months |
1.22. |
Women's Toilet Room with Stalls, 2nd FloorEast Side |
||
1.22.a. |
The toilet room sign is mounted on the door and has no raised or Braille characters. |
TR17 |
24 months |
1.22.b. |
The pull side of the door, which is accessed from the latch side of the door, is inaccessible because it has only 1 inch of clear space on the latch side. |
D10 |
24 months |
1.22.c. |
Although an audible alarm is provided in this facility, there is no visual alarm appliance in the toilet room. |
TR21 |
24 months |
1.22.d. |
The toilet seat cover dispenser is inaccessible because it is mounted with the controls 56¼ inches high. |
TR5 |
24 months |
1.22.e. |
The feminine napkin dispenser is inaccessible because the controls require twisting of the wrist to operate. |
TR3 |
24 months |
1.22.f. |
The lavatory is inaccessible because the hot water pipes are not insulated or otherwise configured to protect against contact. |
TR12 |
24 months |
1.22.g. |
The lavatory is inaccessible because it has twist-type hardware. |
TR10 |
24 months |
1.22.h. |
The designated accessible toilet is inaccessible because the top of the seat is 19½ inches high. |
ST20 |
24 months |
1.22.i. |
The designated accessible toilet is inaccessible because its centerline is 19 inches from the side wall. |
ST17 |
24 months |
1.22.j. |
No accessible coat hook has been provided. |
TR1 |
24 months |
1.22.k. |
The side grab bar at the designated accessible toilet is inaccessible because it is mounted with the far end 48¾ inches from the rear wall. |
ST7 |
24 months |
1.22.l. |
The rear grab bar at the designated accessible toilet is inaccessible because it is 24 inches long and it is mounted more than 6 inches from the side wall. |
ST4 |
24 months |
1.23. |
2nd Floor East Side Conference Room |
||
1.23.a. |
The first aid kit is inaccessible because it is mounted with the controls too high. |
TR5 |
24 months |
1.23.b. |
The AED protrudes into the walkway and is not detectable to blind persons using a cane. |
AR8 |
24 months |
1.23.c. |
The pull side of the door, which is accessed through a front approach, is inaccessible because it has only 6 inches of clear space on the latch side. |
D6 |
24 months |
1.24. |
Interior Accessible Route |
||
1.24.a. |
The room signs and the AED sign protrude into the walkway and are not detectable to blind persons using a cane. |
AR8 |
24 months |
1.24.b. |
Parts of the 2nd, 3rd, and 4th floors are inaccessible because they require that bank personnel unlock a door, disarm an alarm, and unlock another door in order to access the elevator. |
M2 |
24 months |
1.25. |
4th Floor Doors. The doors in this area are inaccessible because knob hardware is used. |
D1 |
6 months |
2. |
Intergovernmental Grants Department Annex, 19 Public Square, Belleville |
||
2.1. |
Building Entrance |
||
2.1.a. |
The ramp is inaccessible because it is too steep, it does not have accessible handrails, and it does not have a sufficient landing at the top. |
R5 |
30 months |
2.1.b. |
The door is inaccessible because knob and thumb-latch hardware are used. |
D1 |
6 months |
3. |
Administrative Offices of the Emergency Telephone System Board, 101 South 1st Street, Belleville |
||
3.1. |
Parking Lot |
||
3.1.a. |
The parking reserved for persons with disabilities is inaccessible because it lacks van accessible signage. |
P6 |
30 months |
3.1.b. |
The parking reserved for persons with disabilities is inaccessible because the parking space has a slope of 5% and the access aisle has a slope of 3%. |
P7 |
30 months |
3.2. |
Ramp to Front Entrance. The ramp is inaccessible because the handrails are 29½ inches high and there are no handrail extensions. |
R2 |
12 months |
3.3. |
Lobby |
||
3.3.a. |
The AED machine protrudes into the walkway and is not detectable to blind persons using a cane. |
AR8 |
6 months |
3.3.b. |
The counter is inaccessible because it is 42 inches high. |
C6 |
12 months |
3.4. |
Single-User Unisex Toilet Room |
||
3.4.a. |
The toilet room sign is mounted with the centerline 52½ inches high. |
TR18 |
12 months |
3.4.b. |
No accessible mirror has been provided. |
TR14 |
12 months |
3.4.c. |
The rear grab bar at the toilet is inaccessible because it is 24 inches long. |
SU3 |
12 months |
4. |
Government Center, 10 Public Square, Belleville |
||
4.1. |
Drinking Fountain near Café |
||
4.1.a. |
The drinking fountain protrudes into the walkway and is not detectable to blind persons using a cane. |
AR8 |
6 months |
4.1.b. |
Although a designated accessible drinking fountain is provided, there is no drinking fountain provided for people who have difficulty bending or stooping. |
DF3 |
6 months |
4.2. |
5th Floor B Wing Hallway. The defibrillator protrudes into the walkway and is not detectable to blind persons using a cane. |
AR8 |
6 months |
4.3. |
County Board Meeting Room 5th Floor B Wing |
||
4.3.a. |
The meeting room is inaccessible to people with hearing disabilities because, although there are 75 fixed seats, there is no permanently installed assistive listening system provided and there is no signage information the public of the availability of the portable assistive listening system. This room requires 3 receivers. |
AA4 |
12 months |
4.3.b. |
The meeting room, containing 75 seats, is inaccessible because only 1 wheelchair seating area is provided. A total of 4 wheelchair seating areas is required. |
AA6 |
12 months |
4.3.c. |
The speakers' tables are inaccessible because they provide no knee space. |
T1 |
12 months |
4.4. |
5B Women's Toilet Room with Stalls |
||
4.4.a. |
The toilet room sign is mounted with the top 60 inches high. |
TR17 |
18 months |
4.4.b. |
The feminine napkin dispenser is inaccessible because the controls require twisting of the wrist to operate. |
TR3 |
18 months |
4.4.c. |
The air dryer protrudes into the walkway and is not detectable to blind persons using a cane. |
AR8 |
18 months |
4.4.d. |
No accessible coat hook has been provided. |
TR1 |
18 months |
4.4.e. |
The side grab bar at the designated accessible toilet is inaccessible because it is obstructed by the toilet paper dispenser. |
ST8 |
18 months |
4.4.f. |
The side grab bar at the designated accessible toilet is inaccessible because it is mounted with the far end 49½ inches from the rear wall. |
ST7 |
18 months |
4.4.g. |
The rear grab bar at the designated accessible toilet is inaccessible because it is mounted 8½ inches from the side wall. |
ST4 |
18 months |
4.4.h. |
The designated accessible toilet is inaccessible because the rear grab bar is obstructed by the flush valve and the toilet cleaner dispenser. |
ST5 |
18 months |
4.5. |
5A Men's Toilet Room with Stalls |
||
4.5.a. |
The toilet room sign is mounted with the top 60 inches high and has no raised or Braille characters. |
TR17 |
18 months |
4.5.b. |
The urinal is inaccessible because the rim is 19 inches high. |
TR20 |
18 months |
4.5.c. |
No accessible coat hook has been provided. |
TR1 |
18 months |
4.5.d. |
The side grab bar at the designated accessible toilet is inaccessible because it is obstructed by the toilet paper dispenser. |
ST8 |
18 months |
4.5.e. |
The side grab bar at the designated accessible toilet is inaccessible because it is mounted with the far end 49½ inches from the rear wall. |
ST7 |
18 months |
4.5.f. |
The rear grab bar at the designated accessible toilet is inaccessible because it is mounted 8 inches from the side wall. |
ST4 |
18 months |
4.6. |
The designated accessible toilet is inaccessible because the rear grab bar is obstructed by the flush valve and the toilet cleaner dispenser. |
ST5 |
18 months |
4.7. |
Courtrooms throughout the Facility (Existing) |
||
4.7.a. |
The doors are inaccessible because they require more than 5 pounds of force to open. |
D2 |
6 months |
4.7.b. |
The jury box and witness stand are inaccessible because they can be accessed only by steps. |
AA8 |
24 months |
4.7.c. |
The jury box has fixed seating preventing a juror using a wheelchair from sitting in the jury box. |
AA9 |
24 months |
4.7.d. |
The courtroom is inaccessible because no wheelchair seating areas are provided. |
AA6 |
24 months |
4.7.e. |
There is no signage informing the public of the availability of an assistive listening system. |
AA3 |
24 months |
4.7.f. |
No accessible coat hook has been provided. |
TR1 |
6 months |
4.8. |
4th Floor Single-User Toilet Rooms for Courtrooms 401 and 402. The toilet rooms contain a number of inaccessible elements and are not accessible to people with disabilities. |
SU13 |
6 months |
4.8.a. |
There is no signage informing the public of the availability of an assistive listening system. |
AA3 |
24 months |
4.9. |
Drinking Fountain outside Courtroom 404. The drinking fountain protrudes into the walkway and is not detectable to blind persons using a cane. |
AR8 |
12 months |
4.10. |
3rd Floor Single-User Toilet Rooms for Courtrooms 301 and 302. The toilet rooms contain a number of inaccessible elements and are not on an accessible route and do not have signage directing people with disabilities to the nearest accessible toilet rooms. |
TR16 |
12 months |
4.11. |
Women's Crisis Center Conference Room B-360. The door is inaccessible because knob hardware is used. |
D1 |
12 months |
4.12. |
Juvenile Detention Room 3rd Floor. The door is inaccessible because knob hardware is used. |
D1 |
12 months |
4.13. |
Kids Zone 3rd Floor. The door is inaccessible because knob hardware is used. |
D1 |
12 months |
4.14. |
Telephone near Women's Toilet Room 3rd Floor. The telephone is inaccessible because the knee space is 22 inches high and it is not hearing aid compatible. |
TT1 |
6 months |
4.15. |
Women's Toilet Room with Stalls, 3rd Floor |
||
4.15.a. |
The toilet room sign is mounted with the top 60 inches high and has no raised or Braille characters. |
TR17 |
12 months |
4.15.b. |
The feminine napkin dispenser is inaccessible because the controls require twisting of the wrist to operate. |
TR3 |
12 months |
4.15.c. |
No accessible coat hook has been provided. |
TR1 |
12 months |
4.15.d. |
The side grab bar at the designated accessible toilet is inaccessible because it is obstructed by the toilet paper dispenser. |
ST8 |
12 months |
4.15.e. |
The side grab bar at the designated accessible toilet is inaccessible because it is mounted with the far end 49 inches from the rear wall. |
ST7 |
12 months |
4.15.f. |
The rear grab bar at the designated accessible toilet is inaccessible because it is mounted 9 inches from the side wall. |
ST4 |
12 months |
4.15.g. |
The designated accessible toilet is inaccessible because the rear grab bar is obstructed by the flush valve and the toilet cleaner dispenser. |
ST5 |
12 months |
4.16. |
3A Men's Toilet Room with Stalls |
||
4.16.a. |
The toilet room sign is mounted with the top 60 inches high and has no raised or Braille characters. |
TR17 |
12 months |
4.16.b. |
The urinal is inaccessible because the rim is 18 inches high. |
TR20 |
12 months |
4.16.c. |
No accessible coat hook has been provided. |
TR1 |
12 months |
4.16.d. |
The side grab bar at the designated accessible toilet is inaccessible because it is obstructed by the toilet paper dispenser. |
ST19 |
12 months |
4.16.e. |
The side grab bar at the designated accessible toilet is inaccessible because it is mounted with the farther end 49 inches from the rear wall. |
ST7 |
12 months |
4.16.f. |
The rear grab bar at the designated accessible toilet is inaccessible because it is mounted 8½ inches from the side wall. |
ST4 |
12 months |
4.16.g. |
The designated accessible toilet is inaccessible because the rear grab bar is obstructed by the flush valve and the toilet cleaner dispenser. |
ST5 |
12 months |
4.17. |
2nd Floor Toilet Rooms with Stalls. The toilet rooms contain a number of inaccessible elements and are not accessible to people with disabilities, and there is no signage directing people with disabilities to the accessible toilet rooms. |
TR16 |
12 months |
4.18. |
2nd Floor Telephone. The telephone is inaccessible because it is 59½ inches high to the highest operable part. |
TT1 |
6 months |
4.19. |
Drinking Fountain near Coroner's Office. The drinking fountain protrudes into the walkway and is not detectable to blind persons using a cane. |
AR8 |
12 months |
4.20. |
Women's Toilet Room with Stalls, 1st Floor |
||
4.20.a. |
The toilet room sign is mounted with the top 60 inches high and has no raised or Braille characters. |
TR17 |
12 months |
4.20.b. |
The feminine napkin dispenser is inaccessible because the controls require twisting of the wrist to operate. |
TR3 |
12 months |
4.20.c. |
The air dryer protrudes into the walkway and is not detectable to blind persons using a cane. |
AR8 |
12 months |
4.20.d. |
The designated accessible toilet is inaccessible because its centerline is 18½ inches from the side wall. |
ST17 |
12 months |
4.20.e. |
No accessible coat hook has been provided. |
TR1 |
12 months |
4.20.f. |
The side grab bar at the designated accessible toilet is inaccessible because it is obstructed by the toilet paper dispenser. |
ST8 |
12 months |
4.20.g. |
The side grab bar at the designated accessible toilet is inaccessible because it is mounted with the far end 49 inches from the rear wall. |
ST7 |
12 months |
4.20.h. |
The rear grab bar at the designated accessible toilet is inaccessible because it is mounted 9 inches from the side wall. |
ST4 |
12 months |
4.20.i. |
The designated accessible toilet is inaccessible because the rear grab bar is obstructed by the flush valve and the toilet cleaner dispenser. |
ST5 |
12 months |
4.21. |
Men's Toilet Room with Stalls, 1st Floor |
||
4.21.a. |
The toilet room sign is mounted with the top 60 inches high and has no raised or Braille characters. |
TR17 |
12 months |
4.21.b. |
The urinal is inaccessible because the rim is 18 inches high. |
TR20 |
12 months |
4.21.c. |
No accessible coat hook has been provided. |
TR1 |
6 months |
4.21.d. |
The side grab bar at the designated accessible toilet is inaccessible because it is obstructed by the toilet paper dispenser. |
ST8 |
12 months |
4.21.e. |
The side grab bar at the designated accessible toilet is inaccessible because it is mounted with the far end 49 inches from the rear wall. |
ST7 |
12 months |
4.21.f. |
The rear grab bar at the designated accessible toilet is inaccessible because it is mounted 8 inches from the side wall. |
ST4 |
12 months |
4.21.g. |
The designated accessible toilet is inaccessible because the rear grab bar is obstructed by the flush valve and the toilet cleaner dispenser. |
ST5 |
12 months |
4.21.h. |
1st Floor Drinking Fountains. The drinking fountains protrude into the walkway and are not detectable to blind persons using a cane. |
AR8 |
12 months |
4.22. |
1A Law Library. The door is inaccessible because knob hardware is used. |
D1 |
12 months |
4.23. |
Traffic Court. The door is inaccessible because knob hardware is used. |
D1 |
12 months |
4.24. |
Payment Counter Adjacent to Courtroom 108. The counter protrudes into the walkway and is not detectable to blind persons using a cane. |
AR8 |
12 months |
4.25. |
Courtroom 109 |
||
4.25.a. |
The door is inaccessible because knob hardware is used. |
D1 |
12 months |
4.25.b. |
The pull side of the door, which is accessed through a front approach, is inaccessible because it has insufficient clear space on the latch side. |
D6 |
6 months |
4.26. |
1A Probation Office. The door is inaccessible because knob hardware is used. |
D1 |
12 months |
5. |
St. Clair County Jail, 700 North 5th Street, Belleville |
||
5.1. |
Parking Lot |
||
5.1.a. |
The parking reserved for persons with disabilities is inaccessible because it lacks appropriate vertical signage. |
P6 |
6 months |
5.1.b. |
The parking reserved for persons with disabilities is inaccessible because the parking space has a cross slope of 7.1% and the access aisle has a slope of 6%. |
P7 |
30 months |
5.1.c. |
The curb ramp is inaccessible because it has drop off sides with no flares. |
AR5 |
30 months |
5.2. |
After Hours Entrance |
||
5.2.a. |
The route to the entrance is inaccessible because there is no curb cut provided onto the sidewalk. |
AR1 |
30 months |
5.2.b. |
The intercom is inaccessible because it is mounted with the controls 60 inches high. |
TR5 |
12 months |
5.2.c. |
The door is inaccessible because there is a slope of 7.6% within the door's required maneuvering clearance. |
D13 |
30 months |
5.3. |
Drinking Fountains. Although accessible drinking fountains are provided, there is no drinking fountain provided for people who have difficulty bending or stooping. |
DF3 |
6 months |
5.4. |
LobbyVisiting Officer Attorney's Counter |
||
5.4.a. |
The counter is inaccessible because it is 42 inches high. |
C6 |
6 months |
5.4.b. |
The counter protrudes into the walkway and is not detectable to blind persons using a cane. |
AR8 |
6 months |
5.5. |
Valuables Counter (next to Visiting Officer Counter) |
||
5.5.a. |
The counter is inaccessible because it is 42 inches high. |
C6 |
6 months |
5.5.b. |
The counter protrudes into the walkway and is not detectable to blind persons using a cane. |
AR8 |
6 months |
5.6. |
Women's Toilet Room with Stalls |
||
5.6.a. |
The toilet room sign is mounted on the door and has no raised or Braille characters. |
TR17 |
6 months |
5.6.b. |
The door is inaccessible because it requires 8 pounds of force to open. |
D2 |
6 months |
5.6.c. |
No accessible mirror has been provided. |
TR14 |
6 months |
5.6.d. |
The lavatory is inaccessible because the hot water pipes are not insulated or otherwise configured to protect against contact. |
TR12 |
6 months |
5.6.e. |
No accessible coat hook has been provided. |
TR1 |
6 months |
5.6.f. |
The side grab bar at the designated accessible toilet is inaccessible because it is mounted with the far end 48 inches from the rear wall. |
ST7 |
6 months |
5.6.g. |
The designated accessible toilet is inaccessible because the rear grab bar is obstructed by the toilet cleaner dispenser. |
ST5 |
6 months |
5.7. |
Men's Toilet Room with Stalls |
||
5.7.a. |
The toilet room sign is mounted on the door and has no raised or Braille characters. |
TR17 |
6 months |
5.7.b. |
The door is inaccessible because it requires 7 pounds of force to open. |
D2 |
6 months |
5.7.c. |
No accessible mirror has been provided. |
TR14 |
6 months |
5.7.d. |
The lavatory is inaccessible because the hot water pipes are not insulated or otherwise configured to protect against contact. |
TR12 |
6 months |
5.7.e. |
No accessible coat hook has been provided. |
TR1 |
6 months |
5.7.f. |
The side grab bar at the designated accessible toilet is inaccessible because it is mounted with the far end 51½ inches from the rear wall. |
ST7 |
6 months |
5.7.g. |
The designated accessible toilet is inaccessible because the rear grab bar is obstructed by the toilet cleaner dispenser. |
ST5 |
6 months |
5.8. |
Lobby Drinking Fountain near Toilet Rooms. The drinking fountain protrudes into the walkway and is not detectable to blind persons using a cane. |
AR8 |
30 months |
5.9. |
Visitation Area. The visitation area contains fixed stools and does not have space to accommodate a wheelchair. |
T1 |
30 months |
5.10. |
Sally Port. The Sally Port is inaccessible because there is a 5 inch high step at the entrance. |
AR1 |
30 months |
5.11. |
Employee Security Entrance. The door is inaccessible because knob hardware is used. |
D1 |
30 months |
5.12. |
Cells. Throughout the facility, there is no accessible housing provided. |
PJ4 |
30 months |
5.13. |
Infirmaries. There is no accessible medical unit available within the facility. |
PJ5 |
30 months |
5.13.a. |
Pod Seating Areas. The tables are inaccessible because the fixed seats do not accommodate a wheelchair. |
T1 |
30 months |
6. |
St. Clair County Regional Office of Education, 1000 South Illinois Street, Belleville |
||
6.1. |
Parking Lot. The parking lot, with a total of 122 parking spaces, is inaccessible because it only has 4 spaces designated as accessible, and there is no space designated as van accessible. This lot requires 1 van accessible space and 4 standard accessible spaces. |
P3 |
12 months |
6.2. |
Interior Doors. The interior doors throughout the facility are inaccessible because they require more than 5 pounds of force to open. |
D2 |
6 months |
6.3. |
Main Counter. The counter is inaccessible because it is 47½ inches high. |
C6 |
12 months |
6.4. |
Single-User Unisex Toilet Room - Basement |
||
6.4.a. |
The toilet room sign is mounted with the centerline 58 inches high. |
TR18 |
6 months |
6.4.b. |
No accessible mirror has been provided. |
TR14 |
6 months |
6.4.c. |
The toilet is inaccessible because the top of the seat is 16½ inches high. |
SU18 |
6 months |
6.4.d. |
The toilet is inaccessible because its centerline is 19¼ inches from the side wall. |
SU15 |
12 months |
6.4.e. |
The toilet paper dispenser is inaccessible because it is mounted 41½ inches from the rear wall. |
SU17 |
12 months |
6.4.f. |
The side grab bar at the toilet is inaccessible because it is mounted with the far end 45½ inches from the rear wall. |
SU6 |
12 months |
6.4.g. |
There is no accessible shower provided. |
B8 |
18 months |
6.5. |
Elevator on South Side |
||
6.5.a. |
The elevator is inaccessible because the hoistway signage is centered 61¾ inches high. |
E12 |
24 months |
6.5.b. |
The elevator is inaccessible because the emergency controls are 33½ inches high. |
E9 |
24 months |
6.5.c. |
Basement Route. The fire extinguishers mounted in the basement protrude into the walkway and are not detectable to blind persons using a cane. |
AR8 |
6 months |
6.6. |
Employee Lounge, Room 140 |
||
6.6.a. |
The counter is inaccessible because it is 36 inches high. |
C8 |
24 months |
6.6.b. |
The sink is inaccessible because there is no knee space provided. |
S2 |
24 months |
6.7. |
Women's North Side Single-User Toilet Room - Main Floor |
||
6.7.a. |
The toilet room sign is mounted with the centerline 59 inches high. |
TR18 |
6 months |
6.7.b. |
No accessible mirror has been provided. |
TR14 |
6 months |
6.7.c. |
The soap dispenser is inaccessible because it is mounted with the controls 49½ inches high with a forward approach required. |
TR5 |
6 months |
6.7.d. |
The toilet is inaccessible because its centerline is 18½ inches from the side wall. |
SU15 |
24 months |
6.8. |
Men's North Side Single-User Toilet Room - Main Floor |
||
6.8.a. |
The toilet room sign is mounted with the centerline 59 inches high. |
TR18 |
6 months |
6.8.b. |
No accessible mirror has been provided. |
TR14 |
6 months |
6.8.c. |
The soap dispenser is inaccessible because it is mounted with the controls 49½ inches high with a forward approach required. |
TR5 |
6 months |
6.8.d. |
The toilet is inaccessible because its centerline is 18½ inches from the side wall. |
SU15 |
6 months |
6.9. |
Women's North Side Toilet Room with Stalls - Main Floor |
||
6.9.a. |
The toilet room sign is mounted with the centerline 59 inches high. |
TR18 |
6 months |
6.9.b. |
Although there are 6 toilet stalls, there is no ambulatory stall provided. |
ST1 |
24 months |
6.9.c. |
The designated accessible toilet is inaccessible because its centerline is 18½ inches from the side wall. |
ST17 |
24 months |
6.9.d. |
No accessible coat hook has been provided. |
TR1 |
6 months |
6.10. |
Men's North Side Toilet Room with Stalls - Main Floor |
||
6.10.a. |
The toilet room sign is mounted with the centerline 59 inches high. |
TR18 |
6 months |
6.10.b. |
No accessible mirror has been provided. |
TR14 |
6 months |
6.10.c. |
The soap dispenser is inaccessible because it is mounted with the controls 52 inches high with only a forward reach provided. |
TR5 |
6 months |
6.10.d. |
The designated accessible toilet is inaccessible because the top of the seat is 16¼ inches high. |
ST20 |
6 months |
6.10.e. |
No accessible coat hook has been provided. |
TR1 |
6 months |
6.11. |
Women's South Side Single-User Toilet Room |
||
6.11.a. |
The toilet room sign is mounted with the centerline 59 inches high. |
TR18 |
6 months |
6.11.b. |
No accessible coat hook has been provided. |
TR1 |
6 months |
6.11.c. |
No accessible mirror has been provided. |
TR14 |
6 months |
6.11.d. |
The soap dispenser is inaccessible because it is mounted with the controls 53 inches high with only a forward reach provided. |
TR5 |
6 months |
6.11.e. |
The toilet is inaccessible because its centerline is 20 inches from the side wall. |
SU15 |
24 months |
6.11.f. |
The side grab bar at the toilet is inaccessible because it is mounted with the far end 45 inches from the rear wall. |
SU6 |
24 months |
6.12. |
Men's South Side Single-User Toilet Room |
||
6.12.a. |
The toilet room sign is mounted with the centerline 59 inches high. |
TR18 |
6 months |
6.12.b. |
No accessible mirror has been provided. |
TR14 |
6 months |
6.12.c. |
The soap dispenser is inaccessible because it is mounted with the controls 50½ inches high with only a forward reach provided. |
TR5 |
6 months |
6.12.d. |
The toilet is inaccessible because its centerline is 20 inches from the side wall. |
SU15 |
24 months |
6.12.e. |
The side grab bar at the toilet is inaccessible because it is mounted with the far end 45¼ inches from the rear wall. |
SU6 |
24 months |