ATTACHMENT I: Modifications to Newly Constructed Facilities Please Note: Paragraph 36 of the Settlement Agreement requires that, within three months of the effective date of this Agreement, the City provide signage as necessary to comply with 28 C.F.R. § 35.163(b), after having surveyed all facilities that are the subject of this Agreement for the purpose of identifying those that have multiple entrances not all of which are accessible. The chart below lists the facilities surveyed by the Department, the access issues identified during the survey, and the actions required to correct the access issues. Required actions are listed using an alphanumeric code. The key to the alphanumeric codes is provided in Attachment M to this Agreement. In order to ensure that the following spaces and elements in City facilities for which construction was commenced after January 26, 1992, are readily accessible to and usable by persons with disabilities, the City will take the actions referenced by the alphanumeric code and described in detail in Attachment M to this Settlement Agreement within the time periods specified below, which time periods will begin to run on the effective date of this Agreement. |
|||
Item # |
Access Issue |
Required Action |
Completion Date |
---|---|---|---|
1 |
City Hall Building A |
||
1.1 |
Interior Doors. The interior doors throughout the building are inaccessible because they require more than 5 pounds of force to open. |
D2 |
12 months |
1.2 |
Council Chambers 129. The auditorium, containing 144 fixed seats, is inaccessible because no wheelchair seating areas are provided. A total of 4 wheelchair seating areas is required. |
AA6 |
18 months |
1.3 |
Communications Department 145. The push side of the door, which is accessed through a front approach and which has both a closer and a latch, is inaccessible because it has only 8 inches of clearance on the latch side. |
D7 |
24 months |
1.4 |
First Floor Drinking Fountains. The wall-mounted drinking fountains on the 1st floor are inaccessible because they provide only 26 inches of clear knee height, and the fountain near the west wing hallway provides only 28 inches of clear knee width. |
DF5 |
18 months |
1.5 |
Women's Toilet Room with Stalls – First Floor East |
||
1.5.a |
The entry vestibule is inaccessible because it is 26 inches deep beyond the end of the open door. |
D3 |
12 months |
1.5.b |
The paper towel dispenser by the entrance protrudes into the walkway at a height between 27 and 80 inches and is not detectable to blind persons using a cane. |
AR8 |
12 months |
1.5.c |
Although the toilet room has 6 stalls, no ambulatory stall has been provided. |
ST1 |
12 months |
1.5.d |
The designated accessible toilet is inaccessible because its centerline is 19 inches from the side wall. |
ST17 |
12 months |
1.5.e |
The toilet paper dispenser in the designated accessible stall is inaccessible because it is mounted on the rear wall. |
ST19 |
12 months |
1.6 |
Men's Toilet Room with Stalls – First Floor East |
||
1.6.a |
The urinal is inaccessible because the clear floor space is 29 inches wide. |
TR20 |
12 months |
1.6.b |
The designated accessible toilet is inaccessible because its centerline is 16½ inches from the side wall. |
ST17 |
12 months |
1.6.c |
The toilet paper dispenser in the designated accessible stall is inaccessible because it is mounted on the rear wall. |
ST19 |
12 months |
1.6.d |
The designated accessible toilet is inaccessible because the rear grab bar is obstructed by the paper towel dispenser. |
ST5 |
12 months |
1.7 |
Planning and Zoning Office. The front counter is inaccessible because it is 45 inches above the finished floor. |
C6 |
12 months |
1.8 |
Utilities Customer Services 169. The counter is inaccessible because it is 39 inches above the finished floor. |
C6 |
12 months |
1.9 |
Second Floor Drinking Fountain. Although a designated accessible drinking fountain is provided, there is no drinking fountain provided for people who have difficulty bending or stooping. |
DF3 |
12 months |
1.10 |
Women's Toilet Room with Stalls – Second Floor East Wing |
||
1.10.a |
The door is inaccessible because the vestibule is 53 inches deep. |
D3 |
18 months |
1.10.b |
The paper towel dispensers by the general use lavatories protrude into the walkway at a height between 27 and 80 inches and are not detectable to blind persons using a cane. |
AR8 |
12 months |
1.10.c |
The toilet paper dispenser in the designated accessible stall is inaccessible because it is mounted on the rear wall. |
ST19 |
12 months |
1.10.d |
The designated accessible toilet is inaccessible because the rear grab bar is obstructed by the paper towel dispenser. |
ST5 |
12 months |
1.11 |
Men's Toilet Room with Stalls – Second Floor East Wing |
||
1.11.a |
The toilet paper dispenser in the designated accessible stall is inaccessible because it is mounted on the rear wall. |
ST19 |
12 months |
1.11.b |
The designated accessible toilet is inaccessible because the rear grab bar is obstructed by the paper towel dispenser. |
ST5 |
12 months |
1.12 |
Elevators |
||
1.12.a |
Both elevators are inaccessible because the hall call buttons are centered 40½ inches above the finished floor. |
E3 |
18 months |
1.12.b |
Both elevators are inaccessible because the emergency controls are centered 31 inches above the elevator floor. |
E9 |
18 months |
1.13 |
Single User Toilet Rooms – Third Floor Mayor's Office |
||
1.13.a |
The toilet room signs are mounted on the doors and have no raised or Braille characters. |
TR18 |
12 months |
1.13.b |
The toilet paper dispensers are inaccessible because they are mounted on the rear wall. |
SU17 |
12 months |
1.13.c |
The men's toilet is inaccessible because the flush control is on the closed side. |
SU1 |
12 months |
1.13.d |
In each room, the rear grab bar at the toilet is inaccessible because it is obstructed by the toilet tank. |
SU4 |
12 months |
1.14 |
Men's Toilet Room with Stalls – Third Floor East |
||
1.14.a |
The seat cover dispenser is inaccessible because it is mounted with the controls 59 inches above the finished floor. |
TR5 |
12 months |
1.14.b |
The toilet paper dispenser in the designated accessible stall is inaccessible because it is mounted on the rear wall. |
ST19 |
12 months |
1.15 |
Women's Toilet Room with Stalls – Third Floor East |
||
1.15.a |
The designated accessible toilet is inaccessible because its centerline is 19 inches from the side wall. |
ST17 |
12 months |
1.15.b |
The toilet paper dispenser in the designated accessible stall is inaccessible because it is mounted on the rear wall. |
ST19 |
12 months |
1.15.c |
The designated accessible toilet is inaccessible because the rear grab bar is obstructed by the seat cover dispenser. |
ST5 |
12 months |
1.16 |
Third Floor Drinking Fountain |
||
1.16.a |
Although a designated accessible drinking fountain is provided, there is no drinking fountain provided for people who have difficulty bending or stooping. |
DF3 |
12 months |
1.16.b |
The drinking fountain protrudes into the walkway at a height between 27 and 80 inches and is not detectable to blind persons using a cane. |
AR8 |
12 months |
2 |
City Hall Building B |
||
2.1 |
Exterior Accessible Route. The walkway to the designated accessible entrance is inaccessible because it slopes 8.6% and has no ramp features. |
R3 |
18 months |
2.2 |
Interior Doors. The interior doors are inaccessible because they require more than 5 pounds of force to open. |
D2 |
12 months |
2.3 |
Main Lobby Permit Counter. The counter is inaccessible because it is 41½ inches above the finished floor. |
C6 |
12 months |
2.4 |
Contractor Licensing L-100. The counters are inaccessible because they are 41¾ inches above the finished floor. |
C6 |
12 months |
2.5 |
Single User Unisex Employee Toilet Room T-103 |
||
2.5.a |
No accessible mirror has been provided. |
TR14 |
12 months |
2.5.b |
The toilet paper dispenser is inaccessible because it is mounted on the rear wall. |
SU17 |
12 months |
2.5.c |
The side grab bar at the toilet is inaccessible because it is not mounted on the wall and it is 30 inches long. |
SU5 |
12 months |
2.5.d |
The roll-in shower is inaccessible because it is 29 inches deep and 58 inches wide, it has no grab bars, and there is a 1½ inch high curb. |
B8 |
12 months |
2.6 |
Building Inspections Employee Rear Entrance. The pull side of the door, which is accessed through a front approach, is inaccessible because it has less than 18 inches of clear space on the latch side. |
D6 |
12 months |
2.7 |
Men's Administration Office Toilet Room with Stalls C-105 |
||
2.7.a |
No accessible mirror has been provided. |
TR14 |
12 months |
2.7.b |
The toilet is inaccessible because its centerline is 19½ inches from the side wall. |
ST17 |
12 months |
2.8 |
Women's Administration Office Toilet Room with Stalls C-104 |
||
2.8.a |
No accessible mirror has been provided. |
TR14 |
12 months |
2.8.b |
The toilet is inaccessible because its centerline is 19½ inches from the side wall. |
ST17 |
12 months |
2.8.c |
The toilet paper dispenser is inaccessible because it is mounted 17½ inches above the finished floor. |
ST19 |
12 months |
2.9 |
Unisex Administration Office Single User Toilet Room A-104 |
||
2.9.a |
The toilet room sign is mounted 63 inches above the finished floor. |
TR18 |
12 months |
2.9.b |
No accessible mirror has been provided. |
TR14 |
12 months |
2.9.c |
The toilet paper dispenser is inaccessible because it is mounted 18 inches above the finished floor. |
SU17 |
12 months |
2.9.d |
The side grab bar at the toilet is inaccessible because it is obstructed by the seat cover dispenser. |
SU8 |
12 months |
2.10 |
Second Floor Exterior Main Entrance. The ramp to the entrance is inaccessible because the top leg slopes 10.1%, the landing at the change in direction is not level, and the ramp has no handrails. |
R3 |
12 months |
2.11 |
Engineering Room E-236. The sign is inaccessible because it is mounted on the hinge side of the door. |
D26 |
12 months |
2.12 |
Business Tax Office |
||
2.12.a |
The counter is inaccessible because it is 41½ inches above the finished floor. |
C6 |
12 months |
2.12.b |
The brochure racks are inaccessible because they are mounted with the top brochures 67 to 77 inches above the finished floor. |
TR5 |
12 months |
2.12.c |
The employee break room is inaccessible because there are only 74½ inches of head room provided underneath the television. |
AR7 |
12 months |
2.13 |
Office of Licensing Division Breakroom O-203. The television protrudes into the walkway at a height between 27 and 80 inches and is not detectable to blind persons using a cane. |
AR8 |
12 months |
2.14 |
Engineering Shower Room C-219. The roll-in shower is inaccessible because it is 29 inches deep, it has no grab bars, and the shower head is fixed more than 48 inches above the finished floor. |
B8 |
12 months |
2.15 |
Engineering Women's Toilet Room with Stalls C-217 |
||
2.15.a |
No accessible mirror has been provided. |
TR14 |
12 months |
2.15.b |
The toilet paper dispenser is inaccessible because it is mounted 39½ inches from the rear wall and 18 inches above the finished floor. |
ST19 |
12 months |
2.16 |
Engineering Men's Toilet Room with Stalls C-216 |
||
2.16.a |
No accessible mirror has been provided. |
TR14 |
12 months |
2.16.b |
The toilet paper dispenser is inaccessible because it is mounted 17½ inches above the finished floor. |
ST19 |
12 months |
2.16.c |
The rear grab bar at the toilet is inaccessible because it is mounted 8 inches from the side wall. |
ST4 |
12 months |
2.17 |
Engineering Single User Unisex Toilet Room C-213. No accessible mirror has been provided. |
TR14 |
12 months |
2.18 |
Engineering Single User Unisex Toilet Room C-214. No accessible mirror has been provided. |
TR14 |
12 months |
3 |
Prineville Water Treatment Plant |
||
3.1 |
Main Entrance |
||
3.1.a |
The ramp to the entrance is inaccessible because it slopes up to 7.6% and does not have handrails. |
R2 |
12 months |
3.1.b |
The door is inaccessible because there is a 1 inch high threshold. |
D22 |
12 months |
3.2 |
Alcove 135. Although the facility contains an emergency alarm system, the alarm system is inaccessible because there is no visual alarm in the meeting room. |
AL1 |
18 months |
3.3 |
Administrative Office 110. The door is inaccessible because it requires 6 pounds of force to open. |
D2 |
12 months |
3.4 |
Door to Utility Plant (05B). The push side of the door, which is accessed through a front approach and which has both a closer and a latch, is inaccessible because it has only 2 inches of clear space on the latch side. |
D7 |
12 months |
3.5 |
First Floor Employee Area Men's Toilet Room with Stalls 114/113 |
||
3.5.a |
The seat cover dispenser is inaccessible because it is mounted over the toilet with the controls 52½ inches above the finished floor. |
TR4 |
12 months |
3.5.b |
The soap dispenser is inaccessible because it requires 6 pounds of force to operate. |
TR3 |
12 months |
3.5.c |
The urinal is inaccessible because the clear floor space is 29½ inches wide, and the flush control is 45½ inches above the finished floor. |
TR20 |
12 months |
3.5.d |
No accessible coat hook has been provided. |
TR1 |
12 months |
3.5.e |
The transfer shower is inaccessible because the controls are not on the open side of the shower, and the shower spray unit cannot be used as a fixed shower head. |
B8 |
12 months |
3.5.f |
No accessible towel hook has been provided. |
TR1 |
12 months |
3.5.g |
The dressing area has no bench provided. |
LR1 |
18 months |
3.5.h |
There is no accessible locker provided. |
LR3 |
18 months |
3.6 |
First Floor Employee Area Women's Toilet Room with Stalls 111 |
||
3.6.a |
The door is inaccessible because it requires 6 pounds of force to open. |
D2 |
12 months |
3.6.b |
The seat cover dispenser is inaccessible because it is mounted over the toilet with the controls 51½ inches above the finished floor. |
TR4 |
12 months |
3.6.c |
The soap dispenser is inaccessible because it requires 10 pounds of force to operate. |
TR3 |
12 months |
3.6.d |
No accessible coat hook has been provided. |
TR1 |
12 months |
3.6.e |
The side grab bar at the designated accessible toilet is inaccessible because it is obstructed by the toilet paper dispenser. |
ST8 |
12 months |
3.6.f |
The transfer shower is inaccessible because the controls are not on the open side of the shower, and the shower spray unit cannot be used as a fixed shower head. |
B8 |
12 months |
3.6.g |
No accessible towel hook has been provided. |
TR1 |
12 months |
3.6.h |
The towel hooks protrude into the walkway at a height between 27 and 80 inches and are not detectable to blind persons using a cane. |
AR8 |
12 months |
3.6.i |
The dressing area has no bench provided. |
LR1 |
18 months |
3.6.j |
There is no accessible locker provided. |
LR3 |
18 months |
3.7 |
Elevator – Lobby. The elevator is inaccessible because the hall call buttons are centered 43½ inches above the finished floor. |
E3 |
18 months |
3.8 |
Defibrillator. The defibrillator is inaccessible because it is mounted with the controls 56½ inches high. |
TR5 |
12 months |
3.9 |
Training Room |
||
3.9.a |
The doors are inaccessible because they require 11 and 12 pounds of force to open. |
D2 |
12 months |
3.9.b |
The drinking fountain is inaccessible because the controls require 10 pounds of force to operate. |
DF2 |
12 months |
3.10 |
Men's Toilet Room with Stalls 213/212 |
||
3.10.a |
The door is inaccessible because it requires 6 pounds of force to open. |
D2 |
12 months |
3.10.b |
No accessible mirror has been provided. |
TR14 |
12 months |
3.10.c |
The seat cover dispenser is inaccessible because it is mounted over the toilet with the controls are mounted 53 inches above the finished floor. |
TR4 |
12 months |
3.10.d |
The soap dispenser is inaccessible because it requires 6 pounds of force to operate. |
TR3 |
12 months |
3.10.e |
The urinal is inaccessible because the rim is 18 inches high and the clear floor space is 29 inches wide. |
TR20 |
12 months |
3.10.f |
No accessible coat hook has been provided. |
TR1 |
12 months |
3.10.g |
The toilet paper dispenser is inaccessible because it is mounted more than 36 inches from the rear wall. |
ST19 |
12 months |
3.10.h |
The side grab bar at the designated accessible toilet is inaccessible because it is obstructed by the toilet paper dispenser. |
ST8 |
12 months |
3.11 |
Women's Toilet Room with Stalls 210/211 |
12 months |
|
3.11.a |
The seat cover dispenser is inaccessible because it is mounted over the toilet with the controls 52 inches above the finished floor. |
TR4 |
12 months |
3.11.b |
The soap dispenser is inaccessible because it requires 6 pounds of force to operate. |
TR3 |
12 months |
3.11.c |
The designated accessible toilet is inaccessible because its centerline is 19¼ inches from the side wall. |
ST17 |
18 months |
3.11.d |
No accessible coat hook has been provided. |
TR1 |
12 months |
3.11.e |
The side grab bar at the designated accessible toilet is inaccessible because it is obstructed by the toilet paper dispenser. |
ST8 |
12 months |
3.12 |
Gallery 204. Although the facility contains an emergency alarm system, the alarm system is inaccessible because there is no visual alarm in the Gallery conference room. |
AL1 |
18 months |
4 |
Police Athletic League Building |
||
4.1 |
Gymnasium Kitchen. The door is inaccessible because it requires 8 pounds of force to open. |
D2 |
12 months |
4.2 |
Gymnasium Drinking Fountains |
||
4.2.a |
The wall-mounted drinking fountains are inaccessible because they have 26 inches of clear knee height. |
DF5 |
12 months |
4.2.b |
Although designated accessible drinking fountains are provided, there is no drinking fountain provided for people who have difficulty bending or stooping. |
DF3 |
12 months |
4.3 |
Men's Gymnasium Toilet Room with Stalls |
||
4.3.a |
The door is inaccessible because it requires 7 pounds of force to open. |
D2 |
12 months |
4.3.b |
The toilet paper dispenser is inaccessible because it is mounted 45½ inches from the rear wall. |
ST19 |
12 months |
4.3.c |
The side grab bar at the designated accessible toilet is inaccessible because it is mounted 13 inches from the rear wall. |
ST7 |
12 months |
4.4 |
Women's Gymnasium Toilet Room with Stalls |
||
4.4.a |
The door is inaccessible because it requires 7 pounds of force to open. |
D2 |
12 months |
4.4.b |
The toilet is inaccessible because its centerline is 18¾ inches from the side wall. |
ST17 |
12 months |
4.4.c |
The toilet paper dispenser is inaccessible because it is mounted 45 inches from the rear wall. |
ST19 |
12 months |
4.4.d |
The side grab bar at the designated accessible toilet is inaccessible because it is mounted 13 inches from the rear wall. |
ST7 |
12 months |
4.5 |
Offices |
||
4.5.a |
The double doors leading to the offices are inaccessible because they require 6 pounds of force to open. |
D2 |
12 months |
4.5.b |
The office doors are inaccessible because they each have a 1 inch high threshold. |
D22 |
18 months |
5 |
Neighborhood Services Animal Control Building |
||
5.1 |
Alarms. Although the facility contains an emergency alarm system, the alarm system is inaccessible because no visual alarms are provided. |
AL1 |
12 months |
5.2 |
Lobby. The front counter protrudes into the walkway at a height between 27 and 80 inches and is not detectable to blind persons using a cane. |
AR8 |
12 months |
5.3 |
Employee Area. The door between the lobby and the employee area is inaccessible because it requires 9 pounds of force to open. |
D2 |
12 months |
5.4 |
Animal Control Officer. The door is inaccessible because it requires 10 pounds of force to open. |
D2 |
12 months |
5.5 |
Unisex Single User Toilet Room |
||
5.5.a |
The door is inaccessible because it requires 7 pounds of force to open. |
D2 |
12 months |
5.5.b |
The paper towel dispenser is inaccessible because it is mounted 52 inches high behind the toilet. |
TR4 |
12 months |
5.5.c |
The toilet is inaccessible because the top of the seat is 16 inches high. |
SU18 |
12 months |
5.5.d |
The rear grab bar at the toilet is inaccessible because it is 24 inches long. |
SU3 |
12 months |
5.6 |
Doors to Kennels |
||
5.6.a |
The doors leading to the kennels are inaccessible because the vestibule is 68 inches deep. |
D3 |
18 months |
5.6.b |
The pull side of the first door into the vestibule, which is accessed through a front approach, is inaccessible because it has only 12 inches of clearance on the latch side. |
D6 |
18 months |
5.6.c |
The second door in series is inaccessible because it requires 11 pounds of force to open. |
D2 |
18 months |
6 |
Community Center |
||
6.1 |
Interior Doors. The interior doors are inaccessible because they require more than 5 pounds of force to open. |
D2 |
12 months |
6.2 |
Assistive Listening System. The assembly areas are inaccessible to people with hearing disabilities because there is no assistive listening system available. |
AA4 |
18 months |
6.3 |
Signage. The signage provided for Rooms A, B, C, D, and the kitchen is inaccessible because it is mounted more than 60 inches high and does not have raised or Braille characters. |
D26 |
12 months |
6.4 |
South Side Women's Toilet Room with Stalls – Near Main Entrance |
||
6.4.a |
No accessible mirror has been provided. |
TR14 |
12 months |
6.4.b |
The paper towel dispenser and air dryers protrude into the walkway at a height between 27 and 80 inches and are not detectable to blind persons using a cane. |
AR8 |
12 months |
6.5 |
South Side Men's Toilet Room with Stalls – Near Main Entrance |
||
6.5.a |
No accessible mirror has been provided. |
TR14 |
12 months |
6.5.b |
The toilet seat cover dispenser is inaccessible because the controls are mounted 49 inches above the finished floor with only a forward reach provided. |
TR5 |
12 months |
6.5.c |
The paper towel dispenser and air dryers protrude into the walkway at a height between 27 and 80 inches and are not detectable to blind persons using a cane. |
AR8 |
12 months |
6.6 |
Room C. The fire alarm protrudes into the walkway at a height between 27 and 80 inches and is not detectable to blind persons using a cane. |
AR8 |
12 months |
6.7 |
Room A |
||
6.7.a |
The key for the lift to the stage is inaccessible because it requires tight grasping and twisting of the wrist to operate. |
TR3 |
12 months |
6.7.b |
The lift to the stage is inaccessible because the door requires 10 pounds of force to open. |
D2 |
12 months |
6.8 |
Kitchen. The pull side of the door, which is accessed through a front approach, is inaccessible because it has only 13 inches of clear space on the latch side. |
D6 |
18 months |
6.9 |
Administration Offices. The pull side of the door, which is accessed through a front approach, is inaccessible because it has only 13 inches of clear space on the latch side. |
D6 |
18 months |
6.10 |
Administration Office Shower Rooms |
||
6.10.a |
The men's and women's roll-in showers are inaccessible because they have grab bars on only 2 walls, and the shower hose is between 55 and 58 inches long. |
B8 |
12 months |
6.10.b |
The shelf in each room protrudes into the walkway at a height between 27 and 80 inches and is not detectable to blind persons using a cane. |
AR8 |
12 months |
6.11 |
Administration Office Single User Toilet Rooms. The paper towel dispenser and the shelf in each room protrudes into the walkway at a height between 27 and 80 inches and is not detectable to blind persons using a cane. |
AR8 |
12 months |
6.12 |
Women's Locker Room |
||
6.12.a |
The door is inaccessible because there is a ½ inch high unbeveled threshold. |
D22 |
12 months |
6.12.b |
The paper towel dispenser and the air dryer protrude into the walkway at a height between 27 and 80 inches and are not detectable to blind persons using a cane. |
AR8 |
12 months |
6.12.c |
The baby changing station is inaccessible because it is mounted with the controls 66 inches high. |
TR5 |
12 months |
6.12.d |
The lavatory is inaccessible because the top of the rim or counter is 35 inches above the finished floor. |
TR11 |
12 months |
6.12.e |
The ambulatory stall is inaccessible because it has an inward swinging door, and the top of the toilet seat is 16½ inches above the finished floor. |
ST1 |
12 months |
6.12.f |
The shower is inaccessible because the seat is 21 inches above the finished floor and the controls require tight grasping or twisting to operate. |
B8 |
18 months |
6.12.g |
No accessible towel hook has been provided. |
TR1 |
12 months |
6.12.h |
The bench is inaccessible because it is 9½ inches wide and it is not attached at the wall. |
LR1 |
18 months |
6.12.i |
There is no accessible locker provided. |
LR3 |
12 months |
6.13 |
Men's Locker Room |
||
6.13.a |
The door is inaccessible because there is a ½ inch high unbeveled threshold. |
D22 |
12 months |
6.13.b |
The paper towel dispenser and the air dryer protrude into the walkway at a height between 27 and 80 inches and are not detectable to blind persons using a cane. |
AR8 |
12 months |
6.13.c |
The baby changing station is inaccessible because it is mounted with the controls 66 inches above the finished floor. |
TR5 |
12 months |
6.13.d |
The side grab bar at the designated accessible toilet is inaccessible because it is obstructed by the toilet paper dispenser. |
ST8 |
12 months |
6.13.e |
The shower is inaccessible because the seat is 21 inches above the finished floor and the controls require tight grasping or twisting to operate. |
B8 |
18 months |
6.13.f |
No accessible towel hook has been provided. |
TR1 |
12 months |
6.13.g |
The bench is inaccessible because it is 9½ inches wide and it is not attached at the wall. |
LR1 |
18 months |
6.13.h |
There is no accessible locker provided. |
LR3 |
18 months |
6.14 |
Locker Room Drinking Fountain. Although an accessible drinking fountain is provided, there is no drinking fountain provided for people who have difficulty bending or stooping. |
DF3 |
12 months |
7 |
Deacon Street Park |
||
7.1 |
Parking. The parking lot, with a total of approximately 40 parking spaces, is inaccessible because it has no accessible parking spaces. This lot requires 1 van accessible space and 1 standard accessible space. |
P3 |
12 months |
7.2 |
Exterior Accessible Route. The route from the parking area to the pavilion is inaccessible because it is not stable, firm, and slip resistant. |
AR1 |
12 months |
8 |
Charles Ray Park |
||
8.1 |
Parking. The parking lot, with a total of 39 parking spaces, is inaccessible because it has no van accessible parking space. This lot requires 1 van accessible space and 1 standard accessible space. |
P3 |
12 months |
8.2 |
Men's Toilet Room with Stalls |
||
8.2.a |
The toilet paper dispenser is inaccessible because it is mounted 39 inches from the rear wall. |
ST19 |
12 months |
8.2.b |
The grab bars at the toilet are inaccessible because they are mounted 2 inches from the wall. |
ST13 |
12 months |
8.3 |
Women's Toilet Room with Stalls |
||
8.3.a |
The toilet is inaccessible because its centerline is 19 inches from the side wall. |
ST17 |
12 months |
8.3.b |
The toilet paper dispenser is inaccessible because it is mounted 39 inches from the rear wall. |
ST19 |
12 months |
8.3.c |
The grab bars at the toilet are inaccessible because they are mounted 2 inches from the wall. |
ST13 |
12 months |
8.4 |
Drinking Fountain at Toilet Rooms |
||
8.4.a |
Although an accessible drinking fountain is provided, there is no drinking fountain provided for people who have difficulty bending or stooping. |
DF3 |
12 months |
8.4.b |
The drinking fountain protrudes into the walkway at a height between 27 and 80 inches and is not detectable to blind persons using a cane. |
AR8 |
12 months |
8.5 |
Accessible Exterior Route. The routes to the barbeque grills are inaccessible because they are not stable, firm, and slip resistant. |
AR1 |
12 months |
9 |
Riverplace Park |
||
9.1 |
Parking. The parking lot, with a total of 31 parking spaces, is inaccessible because it has no van accessible parking space. This lot requires 1 van accessible space and 1 standard accessible space. |
P3 |
12 months |
9.2 |
Accessible Exterior Route |
||
9.2.a |
The routes to the barbeque grills and the volleyball and basketball courts are inaccessible because they are not stable, firm, and slip resistant. |
AR1 |
24 months |
9.2.b |
The route from the sidewalk to the toilet rooms is inaccessible because it slopes up to 8.8% and has no handrails, and it has a cross slope of up to 4.7% and no level landings at changes in direction. |
R3 |
24 months |
9.3 |
Playground. None of the play equipment is usable by children with disabilities. |
PG1 |
18 months |
9.4 |
Men's and Women's Toilet Rooms with Stalls. The toilet room signs are mounted 57 inches above the finished floor. |
TR18 |
12 months |
9.5 |
Drinking Fountain at Toilet Rooms |
||
9.5.a |
Although an accessible drinking fountain is provided, there is no drinking fountain provided for people who have difficulty bending or stooping. |
DF3 |
12 months |
9.5.b |
The drinking fountain protrudes into the walkway at a height between 27 and 80 inches and is not detectable to blind persons using a cane. |
AR8 |
12 months |
10 |
Girl Scout Park |
||
10.1 |
Parking. The parking lot, with a total of 24 parking spaces, is inaccessible because it has no van accessible parking space. This lot requires 1 van accessible space. |
P3 |
18 months |
10.2 |
Exterior Accessible Route. The routes to the barbeque grills are inaccessible because they are not stable, firm, and slip resistant. |
AR1 |
12 months |
10.3 |
Unisex Single User Toilet Room |
||
10.3.a |
The toilet room sign is mounted 63 inches above the finished floor. |
TR18 |
12 months |
10.3.b |
The paper towel dispenser is inaccessible because it is mounted with the controls 62 inches above the finished floor. |
TR5 |
12 months |
10.3.c |
The air dryer protrudes into the walkway at a height between 27 and 80 inches and is not detectable to blind persons using a cane. |
AR8 |
12 months |
10.3.d |
The toilet is inaccessible because its centerline is 22 inches from the side wall. |
SU15 |
12 months |
10.3.e |
The side grab bar at the toilet is inaccessible because it is obstructed by the toilet paper dispenser. |
SU7 |
12 months |
11 |
Fred Cook Park |
||
11.1 |
Picnic Pavilion |
||
11.1.a |
The picnic tables are inaccessible because none provide the required knee space |
PD6 |
18 months |
11.1.b |
The routes to the barbeque grills are inaccessible because they are not stable, firm, and slip resistant. |
AR1 |
12 months |
11.2 |
Drinking Fountain at Toilet Rooms |
||
11.2.a |
The wall-mounted drinking fountain is inaccessible because it has 26½ inches of knee space height. |
DF5 |
12 months |
11.2.b |
Although a designated accessible drinking fountain is provided, there is no drinking fountain provided for people who have difficulty bending or stooping. |
DF3 |
12 months |
11.3 |
Men's Single User Toilet Room |
||
11.3.a |
The toilet room sign is inaccessible because it does not have raised characters. |
TR18 |
12 months |
11.3.b |
No accessible mirror has been provided. |
TR14 |
12 months |
11.3.c |
The lavatory is inaccessible because it requires 9 pounds of force to operate. |
TR10 |
12 months |
11.3.d |
The side grab bar at the toilet is inaccessible because it is obstructed by the toilet paper dispenser. |
SU7 |
12 months |
11.4 |
Women's Single User Toilet Room |
||
11.4.a |
The toilet room sign is inaccessible because it does not have raised characters. |
TR18 |
12 months |
11.4.b |
No accessible mirror has been provided. |
TR14 |
12 months |
11.4.c |
The lavatory is inaccessible because it requires 7 pounds of force to operate. |
TR10 |
12 months |
11.4.d |
The side grab bar at the toilet is inaccessible because it is obstructed by the toilet paper dispenser. |
SU7 |
12 months |
12 |
Western Regional Office of the Police Department |
||
12.1 |
Parking. The parking lot, with a total of 88 parking spaces, is inaccessible because it has no van accessible parking space. This lot requires 1 van accessible space and 3 standard accessible spaces. |
P3 |
12 months |
12.2 |
Lobby. The front counter protrudes into the walkway at a height between 27 and 80 inches and is not detectable to blind persons using a cane. |
AR8 |
12 months |
12.3 |
Lobby Drinking Fountain. Although an accessible drinking fountain is provided, there is no drinking fountain provided for people who have difficulty bending or stooping. |
DF3 |
12 months |
12.4 |
Lounge. The first aid box protrudes into the walkway at a height between 27 and 80 inches and is not detectable to blind persons using a cane. |
AR8 |
12 months |
12.5 |
Booking Area Unisex Single User Toilet Room |
||
12.5.a |
The soap dispenser is inaccessible because it is mounted behind the lavatory at a height of 50 inches above the finished floor. |
TR4 |
12 months |
12.5.b |
The toilet is inaccessible because the top of the seat is 15 inches above the finished floor. |
SU18 |
12 months |
12.5.c |
The rear grab bar at the toilet is inaccessible because it is mounted 42½ inches above the finished floor. |
SU11 |
12 months |
12.5.d |
The rear grab bar at the toilet is inaccessible because it is obstructed by the toilet tank. |
SU4 |
12 months |
12.6 |
Interior Accessible Route. The message box outside the Sergeant's Office protrudes into the walkway at a height between 27 and 80 inches and is not detectable to blind persons using a cane. |
AR8 |
12 months |
12.7 |
Gymnasium. The pull side of the door, which is accessed through a front approach, is inaccessible because it has less than 18 inches of clear space on the latch side. |
D6 |
12 months |
12.8 |
Women's and Men's Locker Rooms |
||
12.8.a |
The transfer showers are inaccessible because they lack adequate clear space from which to transfer into the shower, they have no seat, and they have fixed shower heads mounted more than 48 inches above the finished floor. |
B8 |
18 months |
12.8.b |
The benches are inaccessible because they are not mounted to the wall. |
LR1 |
18 months |
12.8.c |
There is no accessible locker provided. |
LR3 |
18 months |
12.8.d |
The route to the urinal in the men's locker room is inaccessible because it is only 32 inches wide. |
AR3 |
18 months |
13 |
Whispering Pines Park |
||
13.1 |
Parking. The parking lot, with a total of 93 parking spaces, is inaccessible because it has no van accessible parking space and no vertical signage designating accessible spaces. This lot requires 1 van accessible space and 3 standard accessible spaces. |
P3 |
12 months |
13.2 |
Exterior Accessible Route. The bulletin board on the picnic pavilion across from the tennis courts protrudes into the walkway at a height between 27 and 80 inches and is not detectable to blind persons using a cane. |
AR8 |
12 months |
13.3 |
Women's Toilet Room with Stalls at Tennis Pavilion |
||
13.3.a |
No accessible coat hook has been provided. |
TR1 |
12 months |
13.3.b |
The side grab bar at the toilet is inaccessible because it is obstructed by the toilet paper dispenser. |
ST8 |
12 months |
13.4 |
Men's Toilet Room with Stalls at Tennis Pavilion |
||
13.4.a |
No accessible coat hook has been provided. |
TR1 |
12 months |
13.4.b |
The side grab bar at the toilet is inaccessible because it is obstructed by the toilet paper dispenser. |
ST8 |
12 months |
13.5 |
Baseball Field Concessions |
||
13.5.a |
The concession counter is inaccessible because it is 39 inches above the finished floor. |
C5 |
18 months |
13.5.b |
The concession counter protrudes into the walkway at a height between 27 and 80 inches and is not detectable to blind persons using a cane. |
AR8 |
18 months |
13.6 |
Baseball Field Toilet Rooms. The toilet rooms (which are not new construction) are not accessible and there is no signage directing people with disabilities to the accessible toilet rooms. |
TR16 |
12 months |
13.7 |
Women's Toilet Room with Stalls near Soccer and Football Fields |
||
13.7.a |
The air dryer protrudes into the walkway at a height between 27 and 80 inches and is not detectable to blind persons using a cane. |
AR8 |
12 months |
13.7.b |
The toilet paper dispenser is inaccessible because it is 43 inches from the rear wall. |
ST19 |
12 months |
13.7.c |
The side grab bar at the toilet is inaccessible because it is obstructed by the toilet paper dispenser. |
ST8 |
12 months |
13.8 |
Men's Toilet Room with Stalls near Soccer and Football Fields |
||
13.8.a |
The toilet room sign is not mounted 60 inches above the finished floor and does not have raised or Braille characters. |
TR18 |
12 months |
13.8.b |
The air dryer protrudes into the walkway at a height between 27 and 80 inches and is not detectable to blind persons using a cane. |
AR8 |
12 months |
13.8.c |
The toilet paper dispenser is inaccessible because it is 43 inches from the rear wall. |
ST19 |
12 months |
13.8.d |
The side grab bar at the toilet is inaccessible because it is obstructed by the toilet paper dispenser. |
ST8 |
12 months |
13.9 |
Minsky Gym Reception Counter. The counter is inaccessible because it is 41½ inches above the finished floor. |
C6 |
18 months |
13.10 |
Minsky Gym Women's Toilet Room with Stalls |
||
13.10.a |
The toilet room sign is mounted on the door. |
TR18 |
12 months |
13.10.b |
The door is inaccessible because it requires more than 5 pounds of force to open. |
D2 |
12 months |
13.10.c |
The air dryer protrudes into the walkway at a height between 27 and 80 inches and is not detectable to blind persons using a cane. |
AR8 |
12 months |
13.10.d |
The paper towel dispenser is inaccessible because the controls are mounted 62 inches above the finished floor. |
TR5 |
12 months |
13.10.e |
No accessible coat hook has been provided. |
TR1 |
12 months |
13.10.f |
The toilet paper dispenser is inaccessible because it is mounted on the rear wall. |
ST19 |
12 months |
13.10.g |
Although there are 6 toilet stalls, there is no ambulatory stall provided. |
ST1 |
18 months |
13.11 |
Minsky Gym Men's Toilet Room with Stalls |
||
13.11.a |
The toilet room sign is mounted on the door. |
TR18 |
12 months |
13.11.b |
The door is inaccessible because it requires more than 5 pounds of force to open. |
D2 |
12 months |
13.11.c |
The air dryer protrudes into the walkway at a height between 27 and 80 inches and is not detectable to blind persons using a cane. |
AR8 |
12 months |
13.11.d |
The paper towel dispenser is inaccessible because the controls are mounted 62 inches above the finished floor. |
TR5 |
12 months |
13.11.e |
No accessible coat hook has been provided. |
TR1 |
12 months |
13.11.f |
The toilet paper dispenser is inaccessible because it is mounted on the rear wall. |
ST19 |
12 months |
13.11.g |
The toilet is inaccessible because the flush control is on the closed side. |
ST2 |
12 months |
14 |
Jessica Clinton Park |
||
14.1 |
Drinking Fountains |
||
14.1.a |
The drinking fountain near the large picnic pavilion is inaccessible because the spout is not in front, the water flow is 6 inches from the front of the fountain, and the controls are not near the front edge. |
DF1 |
18 months |
14.1.b |
The drinking fountain near the toilet rooms protrudes into the walkway at a height between 27 and 80 inches and is not detectable to blind persons using a cane. |
AR8 |
18 months |
14.2 |
Men's Toilet Room with Stalls |
||
14.2.a |
The toilet room sign is inaccessible because it is mounted 63 inches above the finished floor. |
TR18 |
12 months |
14.2.b |
No accessible mirror has been provided. |
TR14 |
12 months |
14.2.c |
The paper towel dispenser protrudes into the walkway at a height between 27 and 80 inches and is not detectable to blind persons using a cane. |
AR8 |
12 months |
14.2.d |
No accessible coat hook has been provided. |
TR1 |
12 months |
14.2.e |
The side grab bar at the toilet is inaccessible because it is obstructed by the toilet paper dispenser. |
ST8 |
12 months |
14.3 |
Women's Toilet Room with Stalls |
||
14.3.a |
The toilet room sign is inaccessible because it is mounted 63 inches above the finished floor. |
TR18 |
12 months |
14.3.b |
The paper towel dispenser protrudes into the walkway at a height between 27 and 80 inches and is not detectable to blind persons using a cane. |
AR8 |
12 months |
14.3.c |
No accessible coat hook has been provided. |
TR1 |
12 months |
14.3.d |
The side grab bar at the toilet is inaccessible because it is obstructed by the toilet paper dispenser. |
ST8 |
12 months |
14.4 |
Portable Concession Stand. The concession counter is inaccessible because it is 48 inches above the finished floor. |
C5 |
12 months |
15 |
Elk Lodge Park |
||
15.1 |
Pavilion. The route to the barbeque grill is inaccessible because it is not stable, firm, and slip resistant. |
AR1 |
12 months |
15.2 |
Drinking Fountain at Toilet Rooms |
||
15.2.a |
Although an accessible is provided, there is no drinking fountain provided for people who have difficulty bending or stooping | . DF3 | 12 months |
15.2.b |
The drinking fountain protrudes into the walkway at a height between 27 and 80 inches and is not detectable to blind persons using a cane. |
AR8 |
12 months |
15.3 |
Women's and Men's Toilet Rooms with Stalls |
||
15.3.a |
The toilet room signs have no raised characters. |
TR18 |
12 months |
15.3.b |
The side grab bar at the designated accessible toilet in each room is inaccessible because it is obstructed by the toilet paper dispenser. |
ST8 |
12 months |
16 |
Sandhill Crane Park |
||
16.1 |
Parking. One of the parking spaces reserved for persons with disabilities lacks appropriate signage. |
P6 |
12 months |
16.2 |
Exterior Accessible Route. The route from the volleyball court to the small pavilion is inaccessible because it contains a ¾ inch high unbeveled change in level at the pavilion. |
AR1 |
12 months |
16.3 |
Exterior Shower. The shower is inaccessible because the controls require 15 pounds of force to operate. |
TR3 |
12 months |
16.4 |
Drinking Fountains |
||
16.4.a |
The drinking fountain near the volleyball court is inaccessible because the control requires 10 pounds of force to operate. |
DF2 |
12 months |
16.4.b |
The drinking fountain near the volleyball court is inaccessible because it does not allow a forward approach. |
DF5 |
12 months |
16.4.c |
The higher drinking fountain near the baseball fields protrudes into the walkway at a height between 27 and 80 inches and is not detectable to blind persons using a cane. |
AR8 |
12 months |
16.4.d |
Although a designated accessible drinking fountain is provided near the baseball fields, there is no drinking fountain provided for people who have difficulty bending or stooping. |
DF3 |
12 months |
16.4.e |
The drinking fountain near the playground toilet rooms is inaccessible because it has a spout that is 37 inches above the finished floor. |
DF6 |
18 months |
16.4.f |
The drinking fountain near the playground toilet rooms protrudes into the walkway at a height between 27 and 80 inches and is not detectable to blind persons using a cane. |
AR8 |
12 months |
16.5 |
Baseball Field Women's Toilet Room with Stalls |
||
16.5.a |
The toilet room sign is mounted on the door. |
TR18 |
12 months |
16.5.b |
The door is inaccessible because there is a slope of 5.7% within the door's required maneuvering clearance. |
D13 |
18 months |
16.5.c |
The door is inaccessible because it requires 9 pounds of force to open. |
D2 |
12 months |
16.5.d |
The pull side of the interior door, which is accessed through a front approach, is inaccessible because it has only 5 inches of clear space on the latch side. |
D6 |
18 months |
16.5.e |
No accessible mirror has been provided. |
TR14 |
12 months |
16.5.f |
The toilet is inaccessible because the flush control is on the closed side. |
ST2 |
12 months |
16.5.g |
No accessible coat hook has been provided. |
TR1 |
12 months |
16.5.h |
The toilet paper dispenser is inaccessible because it is mounted 52 inches from the rear wall. |
ST19 |
12 months |
16.5.i |
The side grab bar at the toilet is inaccessible because it is 24 inches long, and it is mounted 32½ inches above the finished floor and 16 inches from the rear wall. |
ST6 |
12 months |
16.5.j |
The rear grab bar at the toilet is inaccessible because it is 24 inches long and it is mounted 32 inches above the finished floor. |
ST3 |
12 months |
16.5.k |
The shower is inaccessible because it is 48 inches deep and 34 inches wide, the seat is mounted on the wall opposite the controls, the shower head is fixed 75 inches above the finished floor, and the curb is ½ inch high. |
B8 |
18 months |
16.6 |
Baseball Field Men's Toilet Room with Stalls |
||
16.6.a |
The toilet room sign is mounted on the door. |
TR18 |
12 months |
16.6.b |
The door is inaccessible because there is a slope of 8% within the door's required maneuvering clearance. |
D13 |
18 months |
16.6.c |
The air dryer protrudes into the walkway at a height between 27 and 80 inches and is not detectable to blind persons using a cane. |
AR8 |
12 months |
16.6.d |
No accessible coat hook has been provided. |
TR1 |
12 months |
16.6.e |
The toilet paper dispenser is inaccessible because it is mounted 54½ inches from the rear wall. |
ST19 |
12 months |
16.6.f |
The side grab bar at the toilet is inaccessible because it is 24 inches long, and it is mounted 32 inches above the finished floor and 20 inches from the rear wall. |
ST6 |
12 months |
16.6.g |
The rear grab bar at the toilet is inaccessible because it is 24 inches long and it is mounted 32 inches above the finished floor and 7 inches from the side wall. |
ST3 |
12 months |
16.6.h |
The shower is inaccessible because it is 37 inches deep and 42 inches wide, the seat is mounted on the wall opposite the controls, the shower head is fixed 75 inches above the finished floor, and the curb is ½ inch high. |
B8 |
18 months |
16.7 |
Playground. The route from the pavilion to the playground and the playground equipment is inaccessible because it is not stable, firm, and slip resistant. |
AR1 |
18 months |
16.8 |
Men's Toilet Room at Playground and Pavilion |
||
16.8.a |
The toilet room sign is mounted on the door. |
TR18 |
12 months |
16.8.b |
The door is inaccessible because there is a slope of 6.7% within the door's required maneuvering clearance. |
D13 |
18 months |
16.8.c |
The designated accessible toilet stall is inaccessible because it is 39¾ inches wide. |
ST16 |
18 months |
16.8.d |
The toilet is inaccessible because its centerline is 20½ inches from the side wall. |
ST17 |
18 months |
16.8.e |
No accessible coat hook has been provided. |
TR1 |
12 months |
16.8.f |
The toilet paper dispenser is inaccessible because it is mounted 49 inches from the rear wall. |
ST19 |
12 months |
16.8.g |
The side grab bar at the toilet is inaccessible because it is 24 inches long, and it is mounted 32 inches above the finished floor and 13 inches from the rear wall. |
ST6 |
12 months |
16.8.h |
The rear grab bar at the toilet is inaccessible because it is 24 inches long and it is mounted 32½ inches above the finished floor and 7¾ inches from the side wall. |
ST3 |
12 months |
16.9 |
Women's Toilet Room at Playground and Pavilion |
||
16.9.a |
The toilet room sign is mounted on the door. |
TR18 |
12 months |
16.9.b |
The door is inaccessible because there is a slope of 6.7% within the door's required maneuvering clearance. |
D13 |
18 months |
16.9.c |
The air dryer protrudes into the walkway at a height between 27 and 80 inches and is not detectable to blind persons using a cane. |
AR8 |
12 months |
16.9.d |
The toilet is inaccessible because the flush control is on the closed side. |
ST2 |
12 months |
16.9.e |
No accessible coat hook has been provided. |
TR1 |
12 months |
16.9.f |
The toilet paper dispenser is inaccessible because it is mounted 50 inches from the rear wall. |
ST19 |
12 months |
16.9.g |
The side grab bar at the toilet is inaccessible because it is 24 inches long, and it is mounted 32½ inches above the finished floor and 18½ inches from the rear wall. |
ST6 |
12 months |
16.9.h |
The rear grab bar at the toilet is inaccessible because it is 24 inches long and it is mounted 32½ inches above the finished floor. |
ST3 |
12 months |
17 |
McChesney Park |
||
17.1 |
Drinking Fountain at Playground Toilet Rooms |
||
17.1.a |
Although an accessible drinking fountain is provided, there is no drinking fountain provided for people who have difficulty bending or stooping. |
DF3 |
12 months |
17.1.b |
The drinking fountain protrudes into the walkway at a height between 27 and 80 inches and is not detectable to blind persons using a cane. |
AR8 |
12 months |
17.2 |
Playground Women's Toilet Room with Stalls |
||
17.2.a |
The air dryer protrudes into the walkway at a height between 27 and 80 inches and is not detectable to blind persons using a cane. |
AR8 |
12 months |
17.2.b |
The toilet is inaccessible because its centerline is 21 inches from the side wall. |
ST17 |
12 months |
17.2.c |
No accessible coat hook has been provided. |
TR1 |
12 months |
17.2.d |
The side grab bar at the toilet is inaccessible because it is obstructed by the toilet paper dispenser. |
ST8 |
12 months |
17.3 |
Playground Men's Toilet Room with Stalls |
||
17.3.a |
The air dryer protrudes into the walkway at a height between 27 and 80 inches and is not detectable to blind persons using a cane. |
AR8 |
12 months |
17.3.b |
The urinal is inaccessible because the clear floor space is 26¾ inches wide. |
TR20 |
18 months |
17.3.c |
The toilet is inaccessible because its centerline is 21 inches from the side wall. |
ST17 |
12 months |
17.3.d |
No accessible coat hook has been provided. |
TR1 |
12 months |
17.3.e |
The side grab bar at the toilet is inaccessible because it is obstructed by the toilet paper dispenser. |
ST8 |
12 months |
17.4 |
Exterior Accessible Route. The route to the soccer fields is inaccessible because it is not stable, firm, and slip resistant. |
AR1 |
24 months |
17.5 |
Soccer Concessions |
||
17.5.a |
The concession counter is inaccessible because it is 37½ inches above the finished floor. |
C5 |
12 months |
17.5.b |
The picnic tables are inaccessible because none provide the required knee space. |
PD6 |
18 months |
17.6 |
Drinking Fountain at Far Toilet Rooms. The high drinking fountain protrudes into the walkway at a height between 27 and 80 inches and is not detectable to blind persons using a cane. |
AR8 |
12 months |
17.7 |
Women's Toilet Room with Stalls at Far Field |
||
17.7.a |
The toilet is inaccessible because its centerline is 18¾ inches from the side wall. |
ST17 |
12 months |
17.7.b |
No accessible coat hook has been provided. |
TR1 |
12 months |
17.7.c |
The side grab bar at the toilet is inaccessible because it is obstructed by the toilet paper dispenser. |
ST8 |
12 months |
17.8 |
Men's Toilet Room with Stalls at Far Field |
||
17.8.a |
No accessible coat hook has been provided. |
TR1 |
12 months |
17.8.b |
The route to the urinal is inaccessible because it is less than 36 inches wide for more than 24 inches of depth. |
AR3 |
18 months |
17.8.c |
The side grab bar at the toilet is inaccessible because it is obstructed by the toilet paper dispenser. |
ST8 |
12 months |
18 |
Oak Hammock Park |
||
18.1 |
Exterior Accessible Route. The route from the parking area to the toilet rooms is inaccessible because it slopes up to 6.6% with no ramp features, and it has a cross slope of up to 4.4%. |
R3 |
18 months |
18.2 |
Women's Toilet Room with Stalls |
||
18.2.a |
No accessible coat hook has been provided. |
TR1 |
12 months |
18.2.b |
The air dryer protrudes into the walkway at a height between 27 and 80 inches and is not detectable to blind persons using a cane. |
AR8 |
12 months |
18.2.c |
The toilet paper dispenser is inaccessible because it is mounted 41 inches from the rear wall. |
ST19 |
12 months |
18.2.d |
The side grab bar at the toilet is inaccessible because it is obstructed by the toilet paper dispenser. |
ST8 |
12 months |
18.2.e |
The side grab bar at the toilet is inaccessible because it is 36 inches long. |
ST7 |
12 months |
18.3 |
Men's Toilet Room with Stalls |
||
18.3.a |
The urinal is inaccessible because the rim is 18½ inches above the finished floor. |
TR20 |
12 months |
18.3.b |
The toilet is inaccessible because the flush control is on the closed side. |
ST2 |
12 months |
18.3.c |
No accessible coat hook has been provided. |
TR1 |
12 months |
18.3.d |
The air dryer protrudes into the walkway at a height between 27 and 80 inches and is not detectable to blind persons using a cane. |
AR8 |
12 months |
18.3.e |
The side grab bar at the toilet is inaccessible because it is obstructed by the toilet paper dispenser. |
ST8 |
12 months |
18.3.f |
The side grab bar at the toilet is inaccessible because it is 36 inches long. |
ST7 |
12 months |
18.4 |
Drinking Fountain near Toilet Rooms |
||
18.4.a |
The drinking fountain has a spout that is 38½ inches above the finished floor. |
DF6 |
12 months |
18.4.b |
The drinking fountain protrudes into the walkway at a height between 27 and 80 inches and is not detectable to blind persons using a cane. |
AR8 |
12 months |
19 |
Turtle Run Park |
||
19.1 |
Parking. The parking reserved for persons with disabilities is inaccessible because two of the designated accessible spaces lack appropriate signage. |
P6 |
12 months |
19.2 |
Exterior Accessible Route. The route to the volleyball court is inaccessible because it is not stable, firm, and slip resistant. |
AR1 |
18 months |
19.3 |
Drinking Fountain at Toilet Rooms. Although an accessible drinking fountain is provided, there is no drinking fountain provided for people who have difficulty bending or stooping. |
DF3 |
12 months |
19.4 |
Men's and Women's Single User Toilet Rooms. The side grab bar at each toilet is inaccessible because it is obstructed by the toilet paper dispenser. |
SU7 |
12 months |