ATTACHMENT K: Program Access in Existing FacilitiesThe technical requirements and, where appropriate, the scoping requirements of the Standards are used as a guide for determining whether a program or activity held in an existing facility is “readily accessible to and usable by” persons with disabilities and for determining what changes are necessary to make this program or activity accessible if it continues to be provided in the existing facility in question. See 28 C.F.R. §§ 35.150(b)(1), 35.151. The chart below lists the facilities surveyed by the Department, the access issues identified during the survey, and the actions required to correct the access issues. Required actions are listed using an alphanumeric code. The key to the alphanumeric codes is provided in Attachment M to this Agreement. In order to ensure that the programs, services, and activities housed in Robeson County’s facilities are accessible to persons with disabilities, when viewed in their entirety, the County will take the actions referenced by the alphanumeric code and described in detail in Attachment M to this Settlement Agreement within the time period specified below, which time period begins to run on the effective date of the Agreement. |
|||
Item # |
Access Issue |
Required Action |
Completion Date |
1. |
Robeson County Administration Building |
|
|
1.1. |
Parking |
||
1.1.1. |
The parking lot, with a total of 76 parking spaces, is inaccessible because there is no van accessible space provided. This lot requires 1 van accessible space and 3 standard accessible spaces. |
P1 |
6 months |
1.1.2. |
The curb ramp is inaccessible because it has a slope of 9.6%. |
AR4 |
6 months |
1.2. |
Finance Office: The door is inaccessible because it requires 8 pounds of force to open. |
D3 |
6 months |
1.3. |
Assistant County Manager’s Office: The door is inaccessible because knob hardware is used. |
D2 |
6 months |
1.4. |
Commissioner’s Meeting Room |
||
1.4.1. |
The door is inaccessible because it requires 10 pounds of force to open. |
D3 |
6 months |
1.4.2. |
The room is inaccessible to people with hearing disabilities because there is no assistive listening system provided. |
AA4 |
6 months |
1.5. |
Drinking Fountain by Commissioner’s Meeting Room:The drinking fountains are inaccessible because neither provides sufficient clear knee height. |
DF4 |
6 months |
1.6. |
Men’s Toilet Room by Commissioner’s Meeting Room |
||
1.6.1. |
The toilet room sign is mounted on the door and has no raised or Braille characters. |
TR11 |
6 months |
1.6.2. |
The doors are inaccessible because they require 12 pounds and 10 pounds of force to open. |
D3 |
6 months |
1.6.3. |
The lavatory is inaccessible because the hot water pipes are not insulated or otherwise configured to protect against contact. |
LS2 |
6 months |
1.6.4. |
The lavatory is inaccessible because it has twist-type hardware. |
LS4 |
6 months |
1.6.5. |
The designated accessible stall is incorrectly configured as an ambulatory stall, and there is no standard accessible stall provided. |
TR2 |
6 months |
1.7. |
Women’s Toilet Room by Commissioner’s Meeting Room |
||
1.7.1. |
The toilet room sign is mounted on the door and has no raised or Braille characters. |
TR11 |
6 months |
1.7.2. |
The doors are inaccessible because they require 12 pounds and 10 pounds of force to open. |
D3 |
6 months |
1.7.3. |
The lavatory is inaccessible because the hot water pipes are not insulated or otherwise configured to protect against contact. |
LS2 |
6 months |
1.7.4. |
The lavatory is inaccessible because it has twist-type hardware. |
LS4 |
6 months |
1.7.5. |
The designated accessible stall is incorrectly configured as an ambulatory stall, and there is no standard accessible stall provided. |
TR2 |
6 months |
2. |
Robeson County Courthouse |
|
|
2.1. |
Juvenile Division Office in Basement |
||
2.1.1. |
The entrance door is inaccessible because it requires 14 pounds of force to open. |
D3 |
6 months |
2.1.2. |
Each of the office doors is inaccessible because knob hardware is used. |
D2 |
6 months |
2.1.3. |
The route past the main desk is inaccessible because it is only 30 inches wide. |
AR3 |
6 months |
2.1.4. |
The holding cell toilet rooms contain a number of inaccessible elements and are not accessible to people with disabilities. |
TR26 |
6 months |
2.1.5. |
The holding cell drinking fountain is inaccessible because the controls require 15 pounds of force to operate. |
DF2 |
6 months |
2.2. |
Magistrate’s Office in Basement: The door is inaccessible because it requires 15 pounds of force to open. |
D3 |
6 months |
2.3. |
North Side Entrance:The door is inaccessible because there is a slope of 5.5% within the door’s required maneuvering clearance. |
D1 |
6 months |
2.4. |
South Side Entrance:The door is inaccessible because there is a slope of 4.9% within the door’s required maneuvering clearance. |
D1 |
6 months |
2.5. |
Clerk of Court: The counter is inaccessible because it is 42 inches high. |
C1 |
6 months |
2.6. |
Register of Deeds: The door is inaccessible because it requires 7 pounds of force to open. |
D3 |
6 months |
2.7. |
Tax Collector |
||
2.7.1. |
The door to Room 103 is inaccessible because it requires 16 pounds of force to open. |
D3 |
6 months |
2.7.2. |
The tax office counter protrudes into the walkway and is not detectable to blind persons using a cane. |
AR7 |
6 months |
2.8. |
Child Support: The door is inaccessible because it requires 16 pounds of force to open. |
D3 |
6 months |
3. |
Offender Resource Center |
|
|
3.1. |
Front Parking Lot: The parking lot is inaccessible because there is no “van accessible” signage provided. |
P5 |
6 months |
3.2. |
Designated Accessible Entrance:The door is inaccessible because there is a slope of 5.9% within the door’s required maneuvering clearance on the interior of the building. |
D1 |
20 months |
3.3. |
Interior Doors:The doors throughout the facility are inaccessible because knob hardware is used. |
D2 |
6 months |
3.4. |
Interior Signage: The signage provided throughout the facility is inaccessible because it is mounted above the doors and does not have raised and Braille characters. |
D15 |
6 months |
3.5. |
Director’s Office: The door is inaccessible because it has an opening width of 29 1/2 inches. |
D13 |
20 months |
3.6. |
Drinking Fountain by Toilet Rooms |
||
3.6.1. |
The drinking fountain is inaccessible because it has a spout that is 38 inches high. |
DF3 |
12 months |
3.6.2. |
The wall-mounted drinking fountain is inaccessible because it does not provide sufficient knee space. |
DF4 |
12 months |
3.6.3. |
There is no drinking fountain provided for people who have difficulty bending or stooping. |
DF3 |
12 months |
3.7. |
Unisex Toilet Room by Drinking Fountain: The toilet room contains a number of inaccessible elements and is not accessible to people with disabilities. |
TR26 |
30 months |
3.8. |
Women’s Employee Toilet Room by Main Office |
||
3.8.1. |
The toilet room sign is mounted on the door and has no raised or Braille characters. |
TR11 |
6 months |
3.8.2. |
The door is inaccessible because it requires 12 pounds of force to open. |
D3 |
6 months |
3.8.3. |
No accessible coat hook has been provided. |
TR3 |
6 months |
3.8.4. |
The lavatory is inaccessible because it has twist-type hardware. |
LS4 |
12 months |
3.8.5. |
The lavatory is inaccessible because it provides no knee or toe clearance. |
LS3 |
12 months |
3.8.6. |
The designated accessible stall is incorrectly configured as an ambulatory stall, and there is no standard accessible stall provided. |
TR2 |
20 months |
3.9. |
Men’s Employee Toilet Room by Main Office |
||
3.9.1. |
The toilet room sign is mounted on the door and has no raised or Braille characters. |
TR11 |
6 months |
3.9.2. |
The door is inaccessible because it requires 10 pounds of force to open. |
D3 |
6 months |
3.9.3. |
No accessible coat hook has been provided. |
TR3 |
6 months |
3.9.4. |
No accessible mirror has been provided. |
TR5 |
12 months |
3.9.5. |
The lavatory is inaccessible because it has twist-type hardware. |
LS4 |
12 months |
3.9.6. |
The lavatory is inaccessible because the hot water pipes are not insulated or otherwise configured to protect against contact. |
LS2 |
12 months |
3.9.7. |
The designated accessible stall is incorrectly configured as an ambulatory stall, and there is no standard accessible stall provided. |
TR2 |
30 months |
4. |
Veterans Building |
||
4.1. |
Parking: The parking lot, with a total of 4 parking spaces, is inaccessible because there is no designated accessible space. This lot requires 1 van accessible space. |
P1 |
12 months |
4.2. |
Main Entrance |
||
4.2.1. |
The door is inaccessible because there is a slope of 7.3% within the door’s required maneuvering clearance. |
D1 |
30 months |
4.2.2. |
The interior door is inaccessible because knob hardware is used. |
D2 |
12 months |
4.2.3. |
The hand sanitizer inside the entrance protrudes into the walkway and is not detectable to blind persons using a cane. |
AR7 |
6 months |
4.3. |
Interior Doors:The doors throughout the facility are inaccessible because knob hardware is used. |
D2 |
12 months |
4.4. |
Unisex Single User Toilet Room |
||
4.4.1. |
The toilet room sign is mounted on the door. |
TR11 |
6 months |
4.4.2. |
No accessible mirror has been provided. |
TR5 |
12 months |
4.4.3. |
The toilet room is inaccessible because there is insufficient turning space provided within the room. |
TR21 |
30 months |
4.4.4. |
The toilet paper dispenser is inaccessible because it is mounted on the rear wall. |
TR6 |
30 months |
4.4.5. |
The lavatory is inaccessible because the hot water pipes are not insulated or otherwise configured to protect against contact. |
LS2 |
30 months |
4.4.6. |
The paper towel dispenser is inaccessible because it is mounted with the controls 56 inches high and with no clear floor space provided. |
CT3 |
30 months |
4.4.7. |
The toilet is inaccessible because there is insufficient clear floor space provided. |
TR24 |
30 months |
4.4.8. |
The toilet is inaccessible because the top of the seat is 16 1/4 inches high. |
TR9 |
30 months |
4.4.9. |
The toilet is inaccessible because its centerline is 32 inches from the side wall. |
TR7 |
30 months |
4.4.10. |
The toilet is inaccessible because there are no horizontal grab bars provided. |
TR19 |
30 months |
5. |
Bradford Pool |
||
5.1. |
Parking: The parking lots are inaccessible because there is no designated accessible parking and the grass and sand surface is not firm, stable, and slip resistant. |
P1 |
24 months |
5.2. |
Exterior Routes |
||
5.2.1. |
The routes from the parking area to the play equipment, soccer field, baseball diamonds, bleachers, concession stands, and pool building are inaccessible because the grass and sand are not firm, stable, and slip resistant. |
AR1 |
24 months |
5.2.2. |
The route from the parking lot to the pool building is inaccessible because there is a 2 1/2 inch high step onto the sidewalk to the building. |
AR1 |
12 months |
5.2.3. |
The route from the parking lot to the concession stands is inaccessible because there is a 5 inch high step onto the sidewalk around the building. |
AR1 |
12 months |
5.3. |
Playground:None of the play equipment is usable by children with disabilities. |
PG1 |
24 months |
5.4. |
Bleachers:The baseball bleachers are inaccessible because there are no wheelchair seating areas provided. |
AA6 |
12 months |
6. |
Robeson County One Stop |
||
6.1. |
Parking: The parking lot, with a total of 118 public parking spaces, is inaccessible because it has only 3 designated accessible spaces, there is no van accessible space, there are no access aisles, some of the spaces lack vertical signage, and the existing signs are mounted too low. This lot requires 1 van accessible space and 4 standard accessible spaces. |
P1 |
12 months |
6.2. |
Curb Ramp: The curb ramp is inaccessible because it has a slope of 9.6%. |
AR4 |
12 months |
6.3. |
Entrance Ramp:The ramp to the entrance is inaccessible because there are no accessible handrails provided. |
R2 |
12 months |
7. |
Public Works |
||
7.1. |
Parking |
||
7.1.1. |
The designated accessible parking is inaccessible because there is no “van accessible” signage provided. |
P5 |
12 months |
7.1.2. |
The built-up curb ramp impermissibly extends into the access aisle. |
AR4 |
12 months |
7.1.3. |
The route from the access aisle to the entrance is inaccessible because there is a 1 inch high abrupt change in the level onto the walkway. |
AR1 |
12 months |
7.2. |
Entrance |
||
7.2.1. |
The building does not have directional signage posted at inaccessible entrances and does not have the International Symbol of Accessibility posted at accessible entrances. |
D10 |
6 months |
7.2.2. |
The interior door to the receptionist at the designated accessible entrance is inaccessible because it requires 10 pounds of force to open. |
D3 |
12 months |
7.3. |
Men’s Toilet Room with Stalls |
||
7.3.1. |
The door is inaccessible because it requires 10 pounds of force to open. |
D3 |
12 months |
7.3.2. |
The lavatory is inaccessible because the top of the counter is 35 1/2 inches high. |
LS3 |
20 months |
7.3.3. |
The designated accessible toilet is inaccessible because its centerline is 20 inches from the side wall. |
TR7 |
20 months |
7.3.4. |
The designated accessible toilet is inaccessible because the flush control is on the closed side. |
TR4 |
20 months |
7.3.5. |
No accessible coat hook has been provided. |
TR3 |
6 months |
7.3.6. |
The designated accessible toilet is inaccessible because the door is not mounted on the open side of the stall. |
TR23 |
20 months |
7.4. |
Women’s Toilet Room with Stalls |
||
7.4.1. |
The door is inaccessible because it requires 11 pounds of force to open. |
D3 |
12 months |
7.4.2. |
The lavatory is inaccessible because the top of the counter is 36 inches high. |
LS3 |
20 months |
7.4.3. |
The designated accessible toilet is inaccessible because its centerline is 20 inches from the side wall. |
TR7 |
20 months |
7.4.4. |
No accessible coat hook has been provided. |
TR3 |
6 months |
7.4.5. |
The designated accessible toilet is inaccessible because the door is not mounted on the open side of the stall. |
TR23 |
20 months |
8. |
Detention Center |
||
8.1. |
Parking: The parking lot, with a total of 77 parking spaces, is inaccessible because there are only 2 designated accessible spaces, there are no access aisles, there is no designated van space, and one of the spaces has a slope of 2.7%.This lot requires 1 van accessible space and 3 standard accessible spaces. |
P1 |
6 months |
8.2. |
Designated Accessible Cell G-7 in Medical Unit |
||
8.2.1. |
No accessible mirror has been provided. |
TR5 |
6 months |
8.2.2. |
The lavatory is inaccessible because the hot water pipes are not insulated or otherwise configured to protect against contact. |
LS2 |
20 months |
8.2.3. |
The toilet is inaccessible because the side grab bar is 24 inches long. |
TR17 |
30 months |
8.2.4. |
The toilet is inaccessible because there is no rear grab bar provided. |
TR13 |
20 months |
8.2.5. |
The shower is inaccessible because it lacks a rear grab bar. |
B4 |
20 months |
8.3. |
Designated Accessible Cell A-1 in Men’s Unit |
||
8.3.1. |
The toilet is inaccessible because the side grab bar is 24 inches long. |
TR17 |
20 months |
8.3.2. |
The shower is inaccessible because it lacks a rear grab bar. |
TR13 |
20 months |
8.4. |
A-Block Activity Area: The table is inaccessible because it does not provide sufficient clear knee depth. |
T1 |
6 months |
8.5. |
Medical Records Office: The push side of the door, which is accessed through a front approach and which has both a closer and a latch, is inaccessible because it has only 2 inches of clear space on the latch side. |
D5 |
30 months |
8.6. |
Staff Break Room: The microwave is inaccessible because it is mounted with the controls 63 inches high. |
CT4 |
6 months |
9. |
O.P. Owens Agriculture Center |
||
9.1. |
Women’s Toilet Room with Stalls |
||
9.1.1. |
The toilet room sign is mounted on the door and has no raised or Braille characters. |
TR11 |
6 months |
9.1.2. |
The door is inaccessible because there is a 3 inch high threshold. |
D12 |
30 months |
9.1.3. |
No accessible mirror has been provided. |
TR5 |
6 months |
9.1.4. |
Although an audible alarm is provided in this facility, there is no visual alarm appliance in the toilet room. |
AL1 |
30 months |
9.1.5. |
The lavatory is inaccessible because the bottom of the apron is 26 inches high. |
LS3 |
25 months |
9.1.6. |
The lavatory is inaccessible because the hot water pipes are not insulated or otherwise configured to protect against contact. |
LS2 |
25 months |
9.1.7. |
The lavatory is inaccessible because it has twist-type hardware. |
LS4 |
20 months |
9.1.8. |
There is no accessible toilet stall provided. |
TR2 |
30 months |
9.2. |
Men’s Toilet Room with Stalls |
||
9.2.1. |
The toilet room sign is mounted on the door and has no raised or Braille characters. |
TR11 |
6 months |
9.2.2. |
The door is inaccessible because it requires 12 pounds of force to open. |
D3 |
10 months |
9.2.3. |
The door is inaccessible because there is a 3 inch high threshold. |
D12 |
30 months |
9.2.4. |
Although an audible alarm is provided in this facility, there is no visual alarm appliance in the toilet room. |
AL1 |
30 months |
9.2.5. |
No accessible mirror has been provided. |
TR5 |
6 months |
9.2.6. |
The lavatory is inaccessible because the bottom of the apron is 25 3/4 inches high. |
LS3 |
20 months |
9.2.7. |
The lavatory is inaccessible because it has twist-type hardware. |
LS4 |
10 months |
9.2.8. |
The urinal is inaccessible because the rim is 23 inches high and the flush control is 50 inches high. |
TR8 |
25 months |
9.2.9. |
There is no accessible toilet stall provided. |
TR2 |
20 months |
9.3. |
Drinking Fountain: The drinking fountain contains a number of inaccessible features and is not accessible to people with disabilities. |
DF1 |
25 months |
9.4. |
Auditorium |
||
9.4.1. |
The signage provided is inaccessible because it is mounted on the door and does not have raised and Braille characters. |
D15 |
6 months |
9.4.2. |
The door is inaccessible because it requires 13 pounds of force to open. |
D3 |
10 months |
9.4.3. |
The auditorium is inaccessible to people with hearing disabilities because there is no assistive listening system provided. |
AA4 |
25 months |
10. |
Robeson County Health Department |
||
10.1. |
Parking in Front of Building:The parking lot, with a total of 128 parking spaces, is inaccessible because it has only 4 spaces designated as accessible, it has no access aisles, the signs are mounted too low, and there is no designated van space. This lot requires 1 van accessible space and 4 standard accessible spaces. |
P1 |
6 months |
10.2. |
Front Entrance |
||
10.2.1. |
The building does not have directional signage posted at inaccessible entrances and does not have the International Symbol of Accessibility posted at accessible entrances. |
D10 |
6 months |
10.2.2. |
The interior door is inaccessible because it requires 9 pounds of force to open. |
D3 |
10 months |
10.3. |
Drinking Fountain |
||
10.3.1. |
The drinking fountain is inaccessible because it has a spout that is 44 inches high. |
DF3 |
15 months |
10.3.2. |
The drinking fountain is inaccessible because the controls require 7 pounds of force to operate. |
DF2 |
15 months |
10.3.3. |
The wall-mounted drinking fountain is inaccessible because there is a step obstructing the clear floor space. |
DF4 |
15 months |
10.4. |
Men’s Toilet Room with Stalls off Lobby |
||
10.4.1. |
The toilet room sign is mounted on the door. |
TR11 |
6 months |
10.4.2. |
The door is inaccessible because there is a 2 inch high threshold. |
D12 |
30 months |
10.4.3. |
Although an audible alarm is provided in this facility, there is no visual alarm appliance in the toilet room. |
AL1 |
25 months |
10.4.4. |
No accessible mirror has been provided. |
TR5 |
6 months |
10.4.5. |
The urinal is inaccessible because the rim is 22 1/2 inches high. |
TR8 |
20 months |
10.4.6. |
There is no accessible toilet stall provided. |
TR2 |
20 months |
10.5. |
Women’s Toilet Room with Stalls off Lobby |
||
10.5.1. |
The toilet room sign is mounted on the door. |
TR11 |
6 months |
10.5.2. |
The door is inaccessible because it requires 12 pounds of force to open. |
D3 |
10 months |
10.5.3. |
The door is inaccessible because there is a 2 inch high threshold. |
D12 |
30 months |
10.5.4. |
Although an audible alarm is provided in this facility, there is no visual alarm appliance in the toilet room. |
AL1 |
25 months |
10.5.5. |
No accessible mirror has been provided. |
TR5 |
6 months |
10.5.6. |
The feminine product dispenser is inaccessible because it is mounted 52 inches high behind the changing table. |
CT4 |
20 months |
10.5.7. |
There is no accessible toilet stall provided. |
TR2 |
25 months |
10.6. |
Eligibility Office: The door is inaccessible because knob hardware is used. |
D2 |
10 months |
10.7. |
Pharmacy: The counter is inaccessible because it is 42 inches high. |
C1 |
30 months |
10.8. |
WIC |
||
10.8.1. |
The counter is inaccessible because it is 44 inches high. |
C1 |
25 months |
10.8.2. |
Although a designated accessible drinking fountain is provided, there is no drinking fountain provided for people who have difficulty bending or stooping. |
DF3 |
25 months |
10.9. |
WIC Single User Toilet Room |
||
10.9.1. |
The toilet room sign is mounted on the door. |
TR11 |
6 months |
10.9.2. |
The door is inaccessible because it requires 12 pounds of force to open. |
D3 |
10 months |
10.9.3. |
Although an audible alarm is provided in this facility, there is no visual alarm appliance in the toilet room. |
AL1 |
30 months |
10.9.4. |
No accessible mirror has been provided. |
TR5 |
6 months |
10.9.5. |
The lavatory is inaccessible because the bottom of the apron is 26 inches high. |
LS3 |
25 months |
10.9.6. |
The lavatory is inaccessible because the hot water pipes are not insulated or otherwise configured to protect against contact. |
LS2 |
10 months |
10.9.7. |
The lavatory is inaccessible because it has twist-type hardware. |
LS4 |
10 months |
10.9.8. |
The toilet is inaccessible because the top of the seat is 16 inches high. |
TR7 |
20 months |
10.9.9. |
The toilet is inaccessible because the flush control is on the closed side. |
TR4 |
25 months |
10.9.10. |
The toilet is inaccessible because the side grab bar is mounted with the far end 52 inches from the rear wall. |
TR17 |
25 months |
10.9.11. |
The toilet is inaccessible because the side grab bar is obstructed by the toilet paper dispenser. |
TR16 |
10 months |
10.9.12. |
The toilet is inaccessible because there is no rear grab bar provided. |
TR13 |
15 months |
10.10. |
WIC Urine Sample Toilet Room |
||
10.10.1. |
The room contains a number of inaccessible elements and is not accessible to people with disabilities. |
TR26 |
30 months |
10.10.2. |
The fire extinguisher in the hallway protrudes into the walkway and is not detectable to blind persons using a cane. |
AR7 |
15 months |
11. |
Robeson County Parks and Recreation |
||
11.1. |
Parking: The parking lot is inaccessible because it has no van accessible parking space and no access aisle. |
P1 |
15 months |
11.2. |
Entrance: The door is inaccessible because there is a slope of 2.8% within the door's required maneuvering clearance. |
D1 |
15 months |
12. |
Board of Elections |
||
12.1. |
Parking |
||
12.1.1. |
The parking lot is inaccessible because there are no access aisles. |
P2 |
15 months |
12.1.2. |
The parking lot is inaccessible because there is no designated van accessible parking space. |
P5 |
15 months |
12.2. |
Entrance |
||
12.2.1. |
The interior door is inaccessible because it requires 12 pounds of force to open. |
D3 |
10 months |
12.2.2. |
The entrance is inaccessible because the vestibule is only 44 inches deep. |
D4 |
30 months |
12.3. |
Interior Signage:The signage provided throughout the facility is inaccessible because it is mounted on the doors and does not have raised and Braille characters. |
D15 |
6 months |
12.4. |
Lobby:The counter is inaccessible because its clear floor space is obstructed by seats. |
AR10 |
10 months |
12.5. |
Women's Toilet Room with Stalls |
||
12.5.1. |
The door is inaccessible because it requires 10 pounds of force to open. |
D3 |
10 months |
12.5.2. |
Although an audible alarm is provided in this facility, there is no visual alarm appliance in the toilet room. |
AL1 |
30 months |
12.5.3. |
No accessible mirror has been provided. |
TR5 |
6 months |
12.5.4. |
The lavatory is inaccessible because the bottom of the apron is 26 inches high. |
LS3 |
20 months |
12.5.5. |
The lavatory is inaccessible because the hot water pipes are not insulated or otherwise configured to protect against contact. |
LS2 |
15 months |
12.5.6. |
The lavatory faucet is inaccessible because the controls require twisting of the wrist to operate |
LS4 |
15 months |
12.5.7. |
The designated accessible stall is incorrectly configured as an ambulatory stall, and there is no standard accessible stall provided. |
TR2 |
20 months |
12.6. |
Men's Toilet Room with Stalls |
||
12.6.1. |
The door is inaccessible because it requires 15 pounds of force to open. |
D3 |
10 months |
12.6.2. |
The route into the toilet room is inaccessible because it is 30 inches wide past the partition. |
AR1 |
25 months |
12.6.3. |
Although an audible alarm is provided in this facility, there is no visual alarm appliance in the toilet room. |
AL1 |
25 months |
12.6.4. |
No accessible mirror has been provided. |
TR5 |
6 months |
12.6.5. |
The toilet room is inaccessible because there is insufficient turning space provided within the room. |
TR21 |
30 months |
12.6.6. |
The lavatory is inaccessible because the hot water pipes are not insulated or otherwise configured to protect against contact. |
LS2 |
15 months |
12.6.7. |
The lavatory faucet is inaccessible because the controls require twisting of the wrist to operate |
LS4 |
15 months |
12.6.8. |
The urinal is inaccessible because the rim is 20 1/2 inches high and because the clear floor space is only 28 inches wide. |
TR8 |
25 months |
12.6.9. |
The designated accessible stall is incorrectly configured as an ambulatory stall, and there is no standard accessible stall provided. |
TR2 |
30 months |
12.7. |
Drinking Fountain by Toilet Rooms |
||
12.7.1. |
The drinking fountain is inaccessible because it has a spout that is 38 inches high. |
DF3 |
15 months |
12.7.2. |
The drinking fountain protrudes into the walkway and is not detectable to blind persons using a cane. |
AR7 |
15 months |
12.8. |
Training Room |
||
12.8.1. |
The door is inaccessible because knob hardware is used. |
D2 |
15 months |
13. | Sammy Cox Park |
||
13.1. |
Parking: The parking lot is inaccessible because there are no accessible parking spaces provided. |
P1 |
30 months |
13.2. |
Routes:The routes from the parking lot to all park features are inaccessible because the grass and dirt are not firm, stable and slip resistant; the play areas are surrounded by high plastic curbs; and there is a step up to the toilet rooms. |
AR1 |
30 months |
13.3. |
Toilet Rooms: The toilet rooms contain a number of inaccessible elements and are not accessible to people with disabilities. |
TR26 |
30 months |
13.4. |
Concession Stand:The counter is inaccessible because it is 48 inches high. |
C1 |
6 months |
14. |
Rob Henderson Memorial Park |
||
14.1. |
Routes:The routes from the public right of way to all park features are inaccessible because the dirt and grass are not firm, stable and slip resistant; and the play areas are surrounded by high plastic curbs. |
AR1 |
30 months |
14.2. |
Concession Stand:The counter is inaccessible because it is 41 inches high. |
C1 |
30 months |
14.3. |
Women's Toilet Room with Stalls |
||
14.3.1. |
The toilet room is inaccessible because there is a 1 inch high abrupt change in level in front of the door. |
AR1 |
30 months |
14.3.2. |
The toilet room sign is mounted on the door and has no raised or Braille characters. |
TR11 |
30 months |
14.3.3. |
The door is inaccessible because knob hardware is used. |
D2 |
30 months |
14.3.4. |
The lavatory is inaccessible because the bottom of the apron is 26 inches high. |
LS3 |
30 months |
14.3.5. |
The lavatory is inaccessible because it has twist-type hardware. |
LS4 |
30 months |
14.3.6. |
There is no accessible toilet stall provided. |
TR2 |
30 months |
14.4. |
Men's Toilet Room with Stalls |
||
14.4.1. |
The toilet room is inaccessible because there is a 1 inch high abrupt change in level in front of the door. |
AR1 |
30 months |
14.4.2. |
The toilet room sign is mounted on the door and has no raised or Braille characters. |
TR11 |
30 months |
14.4.3. |
The door is inaccessible because knob hardware is used. |
D2 |
30 months |
14.4.4. |
The lavatory is inaccessible because the bottom of the apron is 26 inches high. |
LS3 |
30 months |
14.4.5. |
The lavatory is inaccessible because it has twist-type hardware. |
LS4 |
30 months |
14.4.6. |
There is no accessible toilet stall provided. |
TR2 |
30 months |
15. |
James Dial Park |
||
15.1. |
Parking: The parking lot is inaccessible because there are no accessible parking spaces provided. |
P1 |
30 months |
15.2. |
Routes:The routes from the parking lot to all park features are inaccessible because the dirt and grass are not firm, stable and slip resistant; there is an abrupt change in level more than 1/2 inch high onto the picnic shelter surface; and the play area is surrounded by a high plastic curb. |
AR1 |
30 months |
15.3. |
Concession Stand: The concession counter is inaccessible because it is 48 inches high. |
C1 |
30 months |
15.4. |
Men's Toilet Room with Stalls |
||
15.4.1. |
The toilet room sign is mounted on the door and has no raised or Braille characters. |
TR11 |
30 months |
15.4.2. |
The door is inaccessible because knob hardware is used. |
D2 |
30 months |
15.4.3. |
The door is inaccessible because there is a slope of 10% within the door's required maneuvering clearance. |
D1 |
30 months |
15.4.4. |
The lavatory is inaccessible because it has twist-type hardware. |
LS4 |
30 months |
15.4.5. |
The urinal is inaccessible because the rim is 27 inches high and the flush control is 49 1/2 inches high. |
TR8 |
30 months |
15.4.6. |
There is no accessible toilet stall provided. |
TR2 |
30 months |
15.5. |
Women's Toilet Room with Stalls |
||
15.5.1. |
The toilet room sign has no raised or Braille characters. |
TR11 |
30 months |
15.5.2. |
The door is inaccessible because knob hardware is used. |
D2 |
30 months |
15.5.3. |
The door is inaccessible because there is a 3 inch high threshold. |
D12 |
30 months |
15.5.4. |
There is no accessible toilet stall provided. |
TR2 |