Attachment J: Modifications to Altered Facilities

 

Please Note: Paragraph 50 of the Settlement Agreement requires that within three months of the effective date of this Agreement, the County provide signage as necessary to comply with 28 C.F.R. § 35.163(b), after having surveyed all facilities that are the subject of this Agreement for the purpose of identifying those that have multiple entrances not all of which are accessible.

 

In order to ensure that the following spaces and elements inCounty facilities, which were altered after January 26, 1992, are readily accessible to and usable by persons with disabilities, the City will take the following actions:

1. Within twelve months of the effective date of the Agreement, the County will complete the following modifications to Grapevine Park, located at 13115 Grapevine Road, Phyllis:

a. Anticipated construction or alterations: Construction of or alterations to this facility are anticipated by the County during the life of this Settlement Agreement, including construction of or alterations to the concession stand, the horseshoe area, and the performance stage. The County will submit to the Department for prior approval all construction documents including all plans and specifications, and change orders affecting accessibility for the facilities at Grapevine Park. The County will incorporate all modifications requested by the Department to ensure that the facilities comply fully with the ADA Standards for Accessible Design (Standards). These modification will be made before the facility is open for use or, if already open for use before the Department's comments are received, within three months of that date.

b. Parking (existing element): Although the parking lot has a total of 12-15 parking spaces, there are no spaces reserved for persons with disabilities. On the shortest accessible route to the accessible entrance, provide 1 van accessible space designated as reserved for people with disabilities. Ensure that the van accessible space is a minimum of 96 inches wide and served by an access aisle at least 96 inches wide. At all spaces designated as reserved for persons with disabilities, provide vertical signs with the International Symbol of Accessibility located such that they cannot be obstructed by parked vehicles. At van accessible spaces, provide an additional "Van-Accessible" sign located below the International Symbol of Accessibility. Ensure that all spaces and access aisles for persons with disabilities are flat and level, with slopes and cross-slopes not exceeding 1:50 in all directions, and that their surfaces are firm, stable, and slip-resistant. Standards §§ 4.1.2(5), 4.6, 4.30.7(1).

c. Accessible route through park (altered element): At the beginning of the accessible route from the parking lot, there is grating over a drain with spaces 1 inch apart with the long dimension parallel to the dominant direction of travel. Provide grating that has spaces no greater than ½ inch wide in one direction. If the gratings have elongated openings, they shall be placed so that the long dimension is perpendicular to the dominant direction of travel. Standards § 4.5.4.

d. Basketball court (altered element): No accessible route is provided to the basketball court from the walking track. Provide at least one accessible route within the boundary of the site connecting these elements that, to the maximum extent feasible, coincides with the route for the general public. The accessible route must have a minimum clear width of 36 inches, or a minimum clear width of 42 inches if there is a turn around an obstruction less than 48 inches wide; have passing spaces at least 60 inches by 60 inches at least every 200 feet; have a minimum clear headroom of 80 inches; have a surface that is firm, stable, and slip resistant; have, in the absence of a curb ramp, ramp, elevator, or platform lift, no level changes in excess of ½ inch vertically; and have a running slope of less than 1:20 (5%) (or have been constructed as a fully accessible ramp) and a cross slope of less than 1:50 (2%). Standards §§ 4.3, 4.5, Fig. 7.

e. Ramp from walking track to women's toilet room (altered element): No handrails or edge protection are provided at the ramp from the walking track to the women's toilet room. On both sides of the ramp, provide handrails between 1¼ inches and 1½ inches in diameter with a continuous gripping surface. Ensure that the handrails extend at least 12 inches beyond the top and bottom of the ramp parallel with the ground surface, that they are mounted between 34 inches and 38 inches above the ramp surface, that they will not rotate within their fittings, and that they have ends that are rounded or return smoothly to floor, wall, or post. Provide edge protection that is at least 2 inches high at the ramp's drop off sides. Standards §§ 4.3.8, 4.8.

f. Women's toilet room with stalls (altered element)

i. The toilet room sign lacks raised letters and Braille, and it is not mounted on the latch side of the door. Provide a toilet room sign with raised and Braille characters mounted on the wall adjacent to the latch side of the door with the centerline of the sign 60 inches above the finished floor and situated such that a person can approach within 3 inches of the sign without encountering an obstruction or standing within a door swing. Standards §§ 4.1.2(7)(d), 4.1.6(1)(b), 4.30.1, 4.30.4, 4.30.5, 4.30.6.

ii. The wall-mounted air dryer protrudes into the walkway is not detectable to a blind person or person with low vision who is using a cane. Provide a circulation path at this location such that no objects with their bottom leading edges measuring between 27 inches and 80 inches above the finished floor protrude more than 4 inches into walks, halls, corridors, passageways, or aisles. Free-standing objects mounted on posts or pylons may overhang 12 inches maximum from 27 inches to 80 inches above the ground or finished floor. Providing a cane-detectable barrier is an acceptable solution. Standards §§ 4.1.2(3), 4.1.6(1)(b), 4.4.

iii. The bottom edge of the lavatory apron is 28 ½ inches above the finished floor, there is inadequate knee and toe clearance at the lavatory, and the hot water and drain pipes under the lavatory are not covered or otherwise configured to protect against contact. Provide a lavatory with the top of its rim or counter 34 inches or less above the finished floor; the bottom edge of the apron at least 29 inches above the finished floor; knee and toe clearances that comply with Fig. 31; hot water and drain pipes covered or otherwise configured to protect against contact; clear floor space at least 30 inches wide and 48 inches deep centered on the lavatory; and a faucet that can be operated with 5 pounds of force or less and can be used with one hand and without tight grasping, pinching, or twisting of the wrist (lever-operated, push-type, and electronically controlled mechanisms are examples of acceptable designs). Standards §§ 4.1.3(11), 4.1.6(1)(b), 4.22.6, 4.19.2, 4.19.3, 4.19.4, 4.19.5, 4.27.4, Figs. 31, 32.

iv. Toilet stall for wheelchair users

(1) The toilet is inaccessible because there is insufficient clear floor space. Provide clear floor space that complies with Fig. 30 at the toilet. Standards §§ 4.1.3(11), 4.1.6(1)(b), 4.22.4, 4.17.3, Fig. 30.

(2) No accessible coat hook has been provided. Provide a coat hook at a maximum height above the finished floor of 48 inches for a forward approach or 54 inches for a side approach and that is accompanied by clear floor space of 30 by 48 inches that allows a forward or parallel approach by a person using a wheelchair. Standards §§ 4.1.3(12)(a), 4.1.6(1)(b), 4.25.2, 4.25.3, 4.2.4, 4.2.5, 4.2.6.

(3) The toilet paper dispenser is mounted 45 inches from the rear wall. Provide a toilet paper dispenser that is mounted with its top at least 1½ inches under the side grab bar and 36 inches or less from the rear wall and is centered at least 19 inches above the finished floor. Standards §§ 4.1.3(11), 4.1.6(1)(b), 4.22.4, 4.17.3, Fig. 30(d).

(4) No side or rear grab bars are provided. Provide a rear grab bar that is at least 36 inches in overall length, with the closer end no more than 6 inches from the side wall, and a side grab bar that is at least 40 inches in overall length, with the far end mounted at least 54 inches from the rear wall and the closer end 12 inches or less from the rear wall. Ensure that the grab bars are mounted 33 to 36 inches above the finished floor; with a diameter between 1¼ and 1½ inches; with 1½ inches between the grab bar and the wall; and at least 1½ inches between the grab bar and any object beside or below it and at least 18 inches between the grab bar and any object above it. Standards §§ 4.1.3(11), 4.1.6(1)(b), 4.22.4, 4.17.6, 4.26.2, Figs. 30, 39.

g. Men's toilet room with stalls (altered element)

i. The toilet room sign lacks raised letters and Braille, and it is not mounted on the latch side of the door. Provide a toilet room sign with raised and Braille characters mounted on the wall adjacent to the latch side of the door with the centerline of the sign 60 inches above the finished floor and situated such that a person can approach within 3 inches of the sign without encountering an obstruction or standing within a door swing. Standards §§ 4.1.2(7)(d), 4.1.6(1)(b), 4.30.1, 4.30.4, 4.30.5, 4.30.6.

ii. The wall-mounted air dryer protrudes into the walkway and is not detectable to a blind person or person with low vision who is using a cane. Provide a circulation path at this location such that no objects with their bottom leading edges measuring between 27 inches and 80 inches above the finished floor protrude more than 4 inches into walks, halls, corridors, passageways, or aisles. Free-standing objects mounted on posts or pylons may overhang 12 inches maximum from 27 inches to 80 inches above the ground or finished floor. Providing a cane-detectable barrier is an acceptable solution. Standards §§ 4.1.2(3), 4.1.6(1)(b), 4.4.

iii. There are inadequate knee and toe clearance at the lavatory and the hot water and drain pipes under the lavatory are not covered or otherwise configured to protect against contact. Provide a lavatory with the top of its rim or counter 34 inches or less above the finished floor; the bottom edge of the apron at least 29 inches above the finished floor; knee and toe clearances that comply with Fig. 31; hot water and drain pipes covered or otherwise configured to protect against contact; clear floor space at least 30 inches wide and 48 inches deep centered on the lavatory; and a faucet that can be operated with 5 pounds of force or less and can be used with one hand and without tight grasping, pinching, or twisting of the wrist (lever-operated, push-type, and electronically controlled mechanisms are examples of acceptable designs). Standards §§ 4.1.3(11), 4.1.6(1)(b), 4.22.6, 4.19.2, 4.19.3, 4.19.4, 4.19.5, 4.27.4, Figs. 31, 32.

iv. The urinal rim is mounted 18 ½ inches above the finished floor. Provide a urinal with an elongated rim mounted 17 inches or less above the finished floor, a clear floor space of at least 30 inches wide and 48 inches deep centered on the urinal, and a flush control height of 44 inches or less above the finished floor. Standards §§ 4.1.3(11), 4.1.6(1)(b), 4.22.5, 4.18.2, 4.18.3, 4.18.4.

v. Toilet stall for wheelchair users

(1) The toilet flush control is on the "closed" side. Provide a flush control mounted on the "open" side of the toilet's clear floor space; 44 inches or less above the finished floor; and requiring a maximum of 5 pounds of force to operate; or provide an automatic flush device. Standards §§ 4.1.3(11), 4.1.6(1)(b), 4.22.4, 4.16.5, 4.17.2, 4.27.4.

(2) No accessible coat hook has been provided. Provide a coat hook at a maximum height above the finished floor of 48 inches for a forward approach or 54 inches for a side approach and that is accompanied by clear floor space of 30 by 48 inches that allows a forward or parallel approach by a person using a wheelchair. Standards §§ 4.1.3(12)(a), 4.1.6(1)(b), 4.25.2, 4.25.3, 4.2.4, 4.2.5, 4.2.6.

(3) The toilet paper dispenser is 40 inches from the rear wall. Provide a toilet paper dispenser that is mounted with its top at least 1½ inches under the side grab bar and 36 inches or less from the rear wall and is centered at least 19 inches above the finished floor. Standards §§ 4.1.3(11), 4.1.6(1)(b), 4.22.4, 4.17.3, Fig. 30(d).

(4) No side or rear grab bars are provided. Provide a rear grab bar that is at least 36 inches in overall length, with the closer end no more than 6 inches from the side wall, and a side grab bar that is at least 40 inches in overall length, with the far end mounted at least 54 inches from the rear wall and the closer end 12 inches or less from the rear wall. Ensure that the grab bars are mounted 33 to 36 inches above the finished floor; with a diameter between 1¼ and 1½ inches; with 1½ inches between the grab bar and the wall; and at least 1½ inches between the grab bar and any object beside or below it and at least 18 inches between the grab bar and any object above it. Standards §§ 4.1.3(11), 4.1.6(1)(b), 4.22.4, 4.17.6, 4.26.2, Figs. 30, 39.

h. Drinking fountain located between the men's and women's toilet rooms (altered element)

i. Although a drinking fountain is provided, there is no accessible drinking fountain because: the spout height is 37 ½ inches above the ground; the water flow is 4 inches from the front of the fountain; and there is no option for people who have trouble bending or stooping. Provide at least one drinking fountain with a spout height no higher than 36 inches, measured from the finished floor or ground surface to the spout outlet; and a spout located at the front of the unit that directs the water flow in a trajectory that is nearly parallel to the front of the unit and is positioned so the flow of water is within 3 inches of the front edge of the fountain and at least 4 inches high. Ensure that fountain controls are operable with one hand, require 5 lbf or less to operate without tight grasping, pinching, or twisting of the wrist; and are front mounted or side mounted near the front edge. Additionally, provide a drinking fountain that is accessible to people who have difficulty bending or stooping. This can be accommodated by the use of a "hi-lo" fountain; by providing one fountain accessible to those who use wheelchairs and one fountain at a standard height convenient for those who have difficulty bending; or by such other means as would achieve the required accessibility for each group of people. Standards §§ 4.1.3(10), 4.1.6(1)(b), 4.15, 4.27.4, Fig. 27.

ii. The drinking fountain protrudes into the walkway and is not detectable to a blind person or person with low vision who is using a cane. Provide a circulation path at this location such that no objects with their bottom leading edges measuring between 27 inches and 80 inches above the finished floor protrude more than 4 inches into walks, halls, corridors, passageways, or aisles. Free-standing objects mounted on posts or pylons may overhang 12 inches maximum from 27 inches to 80 inches above the ground or finished floor. Providing a cane-detectable barrier is an acceptable solution. Standards §§ 4.1.2(3), 4.1.6(1)(b), 4.4.

2. Within twelve months of the effective date of the Agreement, the County will complete the following modifications to the Pike County Courthouse, located at 146 Main Street, Pikeville:

a. Building entrances: Building entrances that are not accessible to persons with disabilities lack signage directing people to the accessible entrance. Provide accessible directional signage with the International Symbol of Accessibility at inaccessible entrances directing users to the accessible entrance, and provide accessible signage with the International Symbol of Accessibility at all permanent accessible entrances. Standards §§ 4.1.3(8)(d), 4.1.3(16)(b), 4.1.6(1)(b), 4.13, 4.30.

b. Exterior drinking fountain: The drinking fountain located directly outside of the main entrance is undetectable to a blind person or person with low vision who uses a cane Provide a cane-detectable barrier around the fountain. Standards §§ 4.1.2(3), 4.1.6(1)(b), 4.4.

c. Picnic tables: None of the picnic tables outside of the courthouse is accessible. Provide at least one picnic table on an accessible route such that there is knee space at the table at least 27 inches high, 30 inches wide, and 19 inches deep, and such that the height of the top of the table is between 28 inches and 34 inches above the ground. Standards §§ 4.1.3(18), 4.1.6(1)(b), 4.32.3, 4.32.4.

d. Elevator

i. Although emergency communications are provided in the elevator, they are not identified by a raised symbol or lettering, and the access door to the emergency communications system requires tight grasping. Provide a two-way communication system such that it does not require voice communication, the highest operable part is a maximum of 48 inches above the finished floor of the car, and it is identified by a raised symbol and lettering located adjacent to the device. If the system uses a handset, ensure that the length of the cord from the panel to the handset is at least 29 inches. If the system is located in a closed compartment, ensure that the compartment door hardware operates without tight grasping, pinching or twisting of the wrist. Standards §§ 4.1.3(5), 4.1.6(1)(b), 4.10.14.

e. Public telephone (located in first floor hallway): The public telephone lacks volume control and signage. Provide an accessible telephone with a clear floor space of at least 30 inches by 48 inches that allows either a forward or parallel approach by a person using a wheelchair such that bases, enclosures, and fixed seats do not impede approaches to the telephone; with the highest operable part of the telephone mounted no more than 48 inches above the floor for a front approach or no more than 54 inches above the floor for a side approach; that is hearing aid compatible and has a volume control mechanism; with telephone books, if provided, located between 15 and 48 inches above the finished floor for a front approach or between 9 and 54 inches above the finished floor for a side approach; with a cord of at least 29 inches long from the telephone to the handset; and with signage that complies with the Standards. Standards §§ 4.1.3(17), 4.1.6(1)(b), 4.31, 4.30.7(2).

f. Drinking fountains

i. Although accessible drinking fountains are provided, there is no drinking fountain provided for people who have difficulty bending or stooping. Provide a drinking fountain that is accessible to people who have difficulty bending or stooping. This can be accommodated by the use of a "hi-lo" fountain; by providing one fountain accessible to those who use wheelchairs and one fountain at a standard height convenient for those who have difficulty bending; by providing a fountain accessible to people who use wheelchairs and a cup dispenser, or by such other means as would achieve the required accessibility for each group of people. Standards §§ 4.1.3(10)(a), 4.1.6(1)(b).

ii. Basement and first floor drinking fountains: The drinking fountains protrude into the hallways and are not detectable to a blind person or person with low vision using a cane. At each location, provide a circulation path such that no objects with their bottom leading edges measuring between 27 inches and 80 inches above the finished floor protrude more than 4 inches into walks, halls, corridors, passageways, or aisles. Free-standing objects mounted on posts or pylons may overhang 12 inches maximum from 27 inches to 80 inches above the ground or finished floor. Providing a cane-detectable barrier is an acceptable solution. Standards §§ 4.1.2(3), 4.1.6(1)(b), 4.4.

g. Permanent room signage: Throughout the building, permanent signs identifying rooms are mounted only on doors or above doors, and lack raised letters and Braille. Provide permanent room signage with upper case, sans serif or simple serif type letters and numerals, meeting the requirements of the Standards for character height, raised characters, finish and contrast, accompanied by Grade 2 Braille; mounted on the wall adjacent to the latch side of the door or on the nearest adjacent wall at a height of 60 inches above the finished floor to the centerline of the sign; and located so that a person may approach within 3 inches of the signage without encountering protruding objects or standing within the swing of a door. Standards §§ 4.1.2(7), 4.1.6(1)(b), 4.30.1, 4.30.4, 4.30.5, 4.30.6.

h. Door pressure: Throughout the building, the pressure required to open doors exceeds 5 pounds of force. Provide doors that require no more than 5 pounds of force to open. Standards §§ 4.1.3(7)(b), 4.1.6(1)(b), 4.13.11(2)(b).

i. Visual Alarms: Although the building contains an emergency alarm system, the visual alarm appliances are not provided in any location. Provide visual alarm devices in toilet rooms and any other general usage areas (e.g., meeting rooms), hallways, lobbies, toilet rooms, and any other area for common use. Such devices shall be integrated into the facility alarm system and shall meet the requirements of the Standards for lamp type, color, pulse duration, intensity, and flash rate. Visual alarm appliances shall be placed 80 inches above the highest floor level within the space or 6 inches below the ceiling, whichever is lower. Visual alarm appliances shall be located such that no place in any room or space, including common corridors or hallways, required to have a visual alarm appliance shall be more than 50 feet from the signal. In large rooms and spaces exceeding 100 feet across, without obstructions 6 feet above the finished floor, devices may be placed around the perimeter, spaced a maximum of 100 feet apart, in lieu of suspending appliances from the ceiling. Standards §§ 4.1.3(14), 4.1.6(1)(b), 4.28.3.

j. Parole and Probation Office: The door to the parole and probation office, which is accessed through a front approach, has 5 inches of maneuvering clearance at the latch on the pull side of the door. On the pull side of the door, provide maneuvering clearance at least 60 inches deep and provide a minimum of 18 inches (24 inches is preferred) of maneuvering clearance on the latch side of the door. Standards §§ 4.1.3(7)(b), 4.1.6(1)(b), 4.13.6, Fig. 25(a). This door, which has a closer and a latch, is also inaccessible because there is only 23 inches of clear depth on the push side of the door. On the push side of the door, provide maneuvering clearance at least 48 inches deep and provide a minimum of 12 inches of maneuvering clearance on the latch side of the door, or remove the closer or the latch. Standards §§ 4.1.3(7)(b), 4.1.6(1)(b), 4.13.6, Fig. 25(a).

k. County Clerk's Office/Marriage Records: The door to the office, which is accessed through a front approach, has 13 ½ inches of clearance at the latch on the pull side of the door. On the pull side of the door, provide maneuvering clearance at least 60 inches deep and provide a minimum of 18 inches (24 inches is preferred) of maneuvering clearance on the latch side of the door. Standards §§ 4.1.3(7)(b), 4.1.6(1)(b), 4.13.6, Fig. 25(a).

l. County Clerk's Office: The designated accessible route from the County Clerk's office to the microfiche area has a running slope that measures 6.8% without ramp features. Provide at least one accessible route within the boundary of the site connecting these elements that, to the maximum extent feasible, coincides with the route for the general public. The accessible route must have a minimum clear width of 36 inches, or a minimum clear width of 42 inches if there is a turn around an obstruction less than 48 inches wide; have passing spaces at least 60 inches by 60 inches at least every 200 feet; have a minimum clear headroom of 80 inches; have a surface that is firm, stable, and slip resistant; have, in the absence of a curb ramp, ramp, elevator, or platform lift, no level changes in excess of ½ inch vertically; and have a running slope of less than 1:20 (5%) (or have been constructed as a fully accessible ramp) and a cross slope of less than 1:50 (2%). Standards §§ 4.1.3(1), 4.1.6(1)(b), 4.3, 4.5, Fig. 7.

m. Deed Room/Hunting and Fishing Office: The designated accessible route in this room narrows to 27 inches in some locations due to the positioning of the counters. Provide an accessible route through this room with a minimum clear width of 36 inches, except at doors, where the width may decrease to 32 inches. Standards §§ 4.1.3(1), 4.1.6(1)(b), 4.3.3, 4.13.5.

n. Social Services Department Office (Existing element; program access standard applies): The door to this office, which is accessed through a front approach and has a closer and latch, has 4 inches of maneuvering clearance at the latch on the pull side of the door, and 3 inches of maneuvering clearance at the latch on the push side of the door. On the pull side of the door, provide maneuvering clearance at least 60 inches deep and provide a minimum of 18 inches (24 inches is preferred) of maneuvering clearance on the latch side of the door. Standards § 4.13.6, Fig. 25(a). On the push side of the door, provide maneuvering clearance at least 48 inches deep and provide a minimum of 12 inches of maneuvering clearance on the latch side of the door, or remove the closer or the latch. Standards § 4.13.6, Fig. 25(a).

o. County Attorney Criminal Division (Existing element): The door to this office, which is accessed through a front approach and has a closer and latch, has 12 ½ inches of maneuvering space at the latch on the pull side of the door, and 2 inches of maneuvering space at the latch on the push side of the door. On the pull side of the door, provide maneuvering clearance at least 60 inches deep and provide a minimum of 18 inches (24 inches is preferred) of maneuvering clearance on the latch side of the door. Standards § 4.13.6, Fig. 25(a). On the push side of the door, provide maneuvering clearance at least 48 inches deep and provide a minimum of 12 inches of maneuvering clearance on the latch side of the door, or remove the closer or the latch. Standards § 4.13.6, Fig. 25(a).

p. Fiscal Courtroom: Although the courtroom has fixed seats and a built-in speaker system, there are no assistive listening systems for persons who have a hearing disability. Provide a permanently installed assistive listening system (ALS) or a portable ALS with an adequate number of electrical outlets or other supplementary wiring necessary to support a portable assistive listening system. Also provide the number of receivers required by Section 4.1.3(19)(b) for use by the general public and signage indicating their availability. 28 C.F.R. § 35.160, Standards §§ 4.1.3(19)(b), 4.1.6(1)(b), 4.30, 4.33.

q. Public toilet rooms in basement, first, second, and third floors

i. No accessible toilet room signs are provided at any public toilet room. At each public toilet room, provide a toilet room sign with the International Symbol of Accessibility and raised and Braille characters. The sign shall be mounted on the wall adjacent to the latch side of the door with the centerline of the sign at 60 inches above the finished floor and situated such that a person can approach within 3 inches of the sign without encountering an obstruction or standing within a door swing. Standards §§ 4.1.2(7)(d), 4.1.6(1)(b), 4.30.1, 4.30.4, 4.30.5, 4.30.6, 4.30.7.

ii. The wall-mounted air dryer in each toilet room protrudes into the circulation route and is not detectable to a blind person or person with low vision using a cane. Provide an accessible route at this location such that no objects with their bottom leading edges measuring between 27 inches and 80 inches above the finished floor protrude more than 4 inches into walks, halls, corridors, passageways, or aisles. Free-standing objects mounted on posts or pylons may overhang 12 inches maximum from 27 inches to 80 inches above the ground or finished floor. Providing a cane detectable barrier is an acceptable solution. Standards §§ 4.1.2(3), 4.1.6(1)(b), 4.4.

iii. In each toilet room, the hot water and drain pipes under the lavatory are not insulated or otherwise configured to protect against contact. Provide hot water and drain pipes that are insulated or otherwise configured to protect against contact. Standards §§ 4.1.3(11), 4.1.6(1)(b), 4.22.6, 4.19.4.

r. Basement women's single user toilet room

i. No accessible mirror has been provided. Provide a mirror with the bottom edge of its reflecting surface no more than 40 inches above the finished floor. Standards §§ 4.1.3(11), 4.1.6(1)(b), 4.22.6, 4.19.6.

ii. The toilet centerline measures 13 inches from the side wall. Provide a toilet with a centerline that measures 18 inches from the near side wall. Standards §§ 4.1.3(11), 4.1.6(1)(b), 4.22.4, 4.16.2, Fig. 28.

iii. The grab bars at the toilet are inaccessible because they are mounted 36 ½ inches above the finished floor. Provide grab bars that are mounted between 33 and 36 inches above the finished floor. Standards §§ 4.1.3(11), 4.1.6(1)(b), 4.22.4, 4.16.4, Fig. 29.

s. Basement men's single user toilet room

i. The toilet centerline measures 19 ½ inches from the side wall. Provide a toilet with a centerline that measures 18 inches from the near side wall. Standards §§ 4.1.3(11), 4.1.6(1)(b), 4.22.4, 4.16.2, Fig. 28.

ii. The toilet paper dispenser is mounted ½ inch below the side grab bar. Provide a side grab bar that has at least 1½ inches between the grab bar and any other object, such as the toilet paper dispenser. Standards §§ 4.1.3(11), 4.1.6(1)(b), 4.22.4, 4.16.4, 4.26.2, Fig. 39.

iii. There is inadequate clear floor at the lavatory. Provide a lavatory with clear floor space at least 30 inches wide and 48 inches deep centered on the lavatory. Standards §§ 4.1.3(11), 4.1.6(1)(b), 4.22.6, 4.19.3, Fig. 32.

t. First floor women's toilet room

i. The top of the lavatory counter is mounted 35 inches above the finished floor. Provide a lavatory with the top of its rim or counter 34 inches or less above the finished floor; the bottom edge of the apron at least 29 inches above the finished floor; and knee and toe clearances that comply with Fig. 31. Standards §§ 4.1.3(11), 4.1.6(1)(b), 4.22.6, 4.19.2, Fig. 31.

ii. Toilet Stall for People with Disabilities

(1) The toilet centerline measures 21 inches from the side wall. Provide a toilet with a centerline that measures 18 inches from the near side wall. Standards §§ 4.1.3(11), 4.1.6(1)(b), 4.22.4, 4.17.3, Fig. 30.

(2) No accessible coat hook is provided. Provide a coat hook at a maximum height above the finished floor of 48 inches for a forward approach or 54 inches for a side approach and that is accompanied by clear floor space of 30 by 48 inches that allows a forward or parallel approach by a person using a wheelchair. Standards §§ 4.1.3(12)(a), 4.1.6(1)(b), 4.25.2, 4.25.3, 4.2.4, 4.2.5, 4.2.6.

u. First floor men's toilet room

i. Toilet stall for wheelchair users: The toilet centerline measures 21 inches from the side wall. Provide a toilet with a centerline that measures 18 inches from the near side wall. Standards §§ 4.1.3(11), 4.1.6(1)(b), 4.22.4, 4.17.3, Fig. 30.

v. Second floor women's toilet room

i. The toilet room door, which is accessed through a latch side approach, has 47 inches depth on the pull side of the door. On the pull side of the door, provide a path of travel at least 48 inches wide for a side approach and at least 24 inches of clear maneuvering space adjacent to the latch side of the door. Standards §§ 4.1.3(7)(b), 4.1.6(1)(b), 4.13.6, Fig. 25©.

ii. Toilet stall for wheelchair users

(1) No accessible coat hook is provided. Provide a coat hook at a maximum height above the finished floor of 48 inches for a forward approach or 54 inches for a side approach and that is accompanied by clear floor space of 30 by 48 inches that allows a forward or parallel approach by a person using a wheelchair. Standards §§ 4.1.3(12)(a), 4.1.6(1)(b), 4.25.2, 4.25.3, 4.2.4, 4.2.5, 4.2.6.

(2) The toilet paper dispenser is mounted 1 inch below the side grab bar. Provide a side grab bar that has at least 1½ inches between the grab bar and any object beside or below it and at least 18 inches between the grab bar and any object above it. Standards §§ 4.1.3(11), 4.1.6(1)(b), 4.22.4, 4.17.6, 4.26.2, Fig. 39.

(3) The overall length of the rear grab bar is 24 inches. Provide a rear grab bar that is at least 36 inches in overall length, with the closer end no more than 6 inches from the side wall; mounted 33 to 36 inches above the finished floor; with a diameter between 1¼ and 1½ inches; with 1½ inches between the grab bar and the wall; and at least 1½ inches between the grab bar and any other object, such as a toilet seat cover dispenser. Standards §§ 4.1.3(11), 4.1.6(1)(b), 4.22.4, 4.17.6, 4.26.2, Fig. 30.

w. Second floor men's toilet room

i. The toilet room door, which is accessed through a latch side approach, has 47 inches depth on the pull side of the door. On the pull side of the door, provide a path of travel at least 48 inches wide for a side approach and at least 24 inches of clear maneuvering space adjacent to the latch side of the door. Standards §§ 4.1.3(7)(b), 4.1.6(1)(b), 4.13.6, Fig. 25©.

ii. Toilet stall for wheelchair users

(1) No accessible coat hook is provided. Provide a coat hook at a maximum height above the finished floor of 48 inches for a forward approach or 54 inches for a side approach and that is accompanied by clear floor space of 30 by 48 inches that allows a forward or parallel approach by a person using a wheelchair. Standards §§ 4.1.3(12)(a), 4.1.6(1)(b), 4.25.2, 4.25.3, 4.2.4, 4.2.5, 4.2.6.

(2) The toilet paper dispenser is mounted 1 inch below the side grab bar. Provide a side grab bar that has at least 1½ inches between the grab bar and any object beside or below it and at least 18 inches between the grab bar and any object above it. Standards §§ 4.1.3(11), 4.1.6(1)(b), 4.22.4, 4.17.6, 4.26.2, Fig. 39.

x. Third floor women's toilet room

i. The lavatory has inadequate knee and toe clearances. Provide a lavatory with the top of its rim or counter 34 inches or less above the finished floor; the bottom edge of the apron at least 29 inches above the finished floor; and knee and toe clearances that comply with Fig. 31. Standards §§ 4.1.3(11), 4.1.6(1)(b), 4.22.6, 4.19.2, Fig. 31.

ii. Toilet stall for wheelchair users

(1) The top of the toilet seat is 16 inches above the finished floor. Provide a toilet with a seat that measures 17 to 19 inches above the finished floor. Standards §§ 4.1.3(11), 4.1.6(1)(b), 4.22.4, 4.16.3, 4.17.2, Fig. 30(d).

(2) The side grab bar is inaccessible because the toilet paper dispenser is mounted above it, interfering with the use of the grab bar. Provide a side grab bar that has at least 1½ inches between the grab bar and any object beside or below it and at least 18 inches between the grab bar and any object above it. Standards §§ 4.1.3(11), 4.1.6(1)(b), 4.22.4, 4.17.6, 4.26.2, Fig. 39.

(3) The far end of the side grab bar is mounted 51 inches from the rear wall and the space between the wall and the grab bar is 1 3/4 inches. Provide a side grab bar that is at least 40 inches in overall length, with the far end mounted at least 52 inches from the rear wall and the closer end 12 inches or less from the rear wall; mounted 33 to 36 inches above the finished floor; with a diameter between 1¼ and 1½ inches; with 1½ inches between the grab bar and the wall; and at least 1½ inches between the grab bar and any other object, such as the toilet paper dispenser. Standards §§ 4.1.3(11), 4.1.6(1)(b), 4.22.4, 4.17.6, 4.26.2, Figs. 30(a), (d).

y. Third floor men's toilet room

i. Toilet stall for wheelchair users

(1) No accessible coat hook has been provided. Provide a coat hook at a maximum height above the finished floor of 48 inches for a forward approach or 54 inches for a side approach and that is accompanied by clear floor space of 30 by 48 inches that allows a forward or parallel approach by a person using a wheelchair. Standards §§ 4.1.3(12)(a), 4.1.6(1)(b), 4.25.2, 4.25.3, 4.2.4, 4.2.5, 4.2.6.

(2) The toilet paper dispenser is mounted 38 inches from the rear wall. Provide a toilet paper dispenser that is mounted with its top at least 1½ inches under the side grab bar and 36 inches or less from the rear wall and is centered at least 19 inches above the finished floor. Standards §§ 4.1.3(11), 4.1.6(1)(b), 4.22.4, 4.17.3, Fig. 30(d).

z. Unisex, single user employee-only toilet rooms in the Public Works Office, the Judge Executive's Office, the Sheriff's Office, the Finance Office, and the 911 Center: Each of these toilet rooms contains a number of inaccessible elements and is not accessible to people with disabilities. When the facility is altered, provide an accessible toilet room such that all of the room's elements, including signage, door, door hardware, clear floor space, water closet, grab bars, lavatory, mirror, controls, and dispensers, comply with the Standards. Standards §§ 4.1.3(11), 4.1.6(1)(b), 4.22, 4.13, 4.16, 4.18, 4.19, 4.26, 4.27, 4.30, Figs. 28, 29.

aa. Unisex, single user toilet room in Parole Office (used for drug testing): The toilet room contains a number of inaccessible elements and is not accessible to people with disabilities. Provide an accessible toilet room such that all of the room's elements, including signage, door, door hardware, clear floor space, water closet, grab bars, lavatory, mirror, controls, and dispensers, comply with the Standards. Standards §§ 4.1.3(11), 4.1.6(1)(b), 4.22, 4.13, 4.16, 4.18, 4.19, 4.26, 4.27, 4.30, Figs. 28, 29.

 

 

 

 