Attachment I: Modifications to Newly Constructed Facilities

 

Please Note: Paragraph 50 of the Settlement Agreement requires that within three months of the effective date of this Agreement, the County will provide signage as necessary to comply with 28 C.F.R. § 35.163(b), after having surveyed all facilities that are the subject of this Agreement for the purpose of identifying those that have multiple entrances not all of which are accessible.

In order to ensure that the following spaces and elements in County facilities, for which construction was commenced after January 26, 1992, are readily accessible to and usable by persons with disabilities, the County will take the following actions:

1. Within six months of the effective date of this Agreement, Pike County will complete the following modifications to the Blackberry Creek Community Center, located next to the Blackberry Senior Citizen Center on State. Highway 1056, McCarr:

a. Parking: Although the parking lot can accommodate approximately 20 cars, there are no spaces designated for persons with disabilities. On the shortest accessible route to the accessible entrance, provide 1 van accessible space designated as reserved for people with disabilities. The van accessible space must be a minimum of 96 inches wide and served by access aisles at least 96 inches wide. At all spaces designated as reserved for persons with disabilities, provide vertical signs with the International Symbol of Accessibility located such that they cannot be obstructed by parked vehicles. At van accessible spaces, provide an additional "Van-Accessible" sign located below the International Symbol of Accessibility. All spaces and access aisles for persons with disabilities must be flat and level, with slopes and cross-slopes not exceeding 1:50 in all directions, and their surfaces must be firm, stable, and slip-resistant. Standards §§ 4.1.2(5), 4.6, 4.30.7(1).No pavement markings.

b. Main entrance (double hinged doors): The landing on the pull side (exterior) of the doors is not level, the short ramp to the landing on the pull side of the doors impedes on the maneuvering clearance depth, there is a 1 inch abrupt change in level between the ramp and the landing, and the inside of the door threshold is 1 inch in height. Provide a designated accessible entrance that has either an automatic door operator or clear and level maneuvering clearance that complies fully with Fig. 25; and with a threshold that is no greater than ¼ inch, or is no greater than ½ inch and is beveled with a slope no greater than 1:2. Provide that the accessible route has no level changes in excess of ½ inch vertically and a cross slope of less than 1:50 (2%). Standards §§ 4.1.3(1), 4.1.3(7)(a), 4.13.8 4.3, 4.5, 4.13, 4.13.6, 4.13.8, Figs. 7, 24, 25.

c. Side entrance: The side entrance door has a 1 inch change in level at the threshold to the door. Provide an accessible door with a threshold that is no greater than ¼ inch, or is no greater than ½ inch and is beveled with a slope no greater than 1:2. Standards §§ 4.1.3(7)(a), 4.13.8, 4.5.2.

d. Women's single user toilet room

i. No accessible toilet room sign is provided. Provide a toilet room sign with raised and Braille characters mounted on the wall adjacent to the latch side of the door with the centerline of the sign 60 inches above the finished floor and situated such that a person can approach within 3 inches of the sign without encountering an obstruction or standing within a door swing. Standards §§ 4.1.2(7)(d), 4.30.1, 4.30.4, 4.30.5, 4.30.6.

ii. The door to the toilet room, which is accessed through a front approach and which has both a closer and a latch, has 2½ inches of maneuvering clearance at the latch on the push side of the door (due to the position of the lavatory and lavatory supports). On the push side of the door, provide maneuvering clearance at least 48 inches deep and provide a minimum of 12 inches of maneuvering clearance on the latch side of the door, or remove the closer or the latch. Standards §§ 4.1.3(7)(b), 4.13.6, Fig. 25(a).

iii. The pressure required to open the toilet room door is 8 pounds of force. Provide a door that require no more than 5 pounds of force to open. Standards §§ 4.1.3(7)(b), 4.13.11(2)(b).

iv. No accessible mirror has been provided. Provide a mirror with the bottom edge of its reflecting surface no more than 40 inches above the finished floor. Standards §§ 4.1.3(11), 4.22.6, 4.19.6.

v. The paper towel dispenser requires tight grasping to operate. Provide a paper towel dispenser with mechanical controls, if any, that can be operated with 5 lbf or less and that can be used with one hand and without tight grasping, pinching, or twisting of the wrist (lever-operated, push-type, and electronically controlled mechanisms are examples of acceptable designs). Standards §§ 4.1.3(13), 4.27.4.

vi. The lavatory has inadequate knee and toe clearance due to the lavatory supports, and the hot water and drain pipes are not covered or otherwise configured to protect against contact. Provide a lavatory with the top of its rim or counter 34 inches or less above the finished floor; the bottom edge of the apron at least 29 inches above the finished floor; knee and toe clearances that comply with Fig. 31; hot water and drain pipes covered or otherwise configured to protect against contact; clear floor space at least 30 inches wide and 48 inches deep centered on the lavatory; and a faucet that can be operated with 5 pounds of force or less and can be used with one hand and without tight grasping, pinching, or twisting of the wrist (lever-operated, push-type, and electronically controlled mechanisms are examples of acceptable designs). Standards §§ 4.1.3(11), 4.22.6, 4.19.2, 4.19.3, 4.19.4, 4.19.5, 4.27.4, Figs. 31, 32.

vii. The toilet centerline measures 15 inches from the side wall. Provide a toilet with a centerline that measures 18 inches from the near side wall. Standards §§ 4.1.3(11), 4.22.4, 4.16.2, Fig. 28.

viii. The distance of the far end of the side grab bar to the rear wall is 46 inches. Provide a side grab bar that is at least 42 inches in overall length, with the far end mounted at least 54 inches from the rear wall and the closer end 12 inches or less from the rear wall. Standards §§ 4.1.3(11), 4.22.4, 4.16.4, Fig. 29(b).

e. Men's single user toilet room

i. No accessible toilet room sign is provided. Provide a toilet room sign with raised and Braille characters mounted on the wall adjacent to the latch side of the door with the centerline of the sign 60 inches above the finished floor and situated such that a person can approach within 3 inches of the sign without encountering an obstruction or standing within a door swing. Standards §§ 4.1.2(7)(d), 4.30.1, 4.30.4, 4.30.5, 4.30.6.

ii. The pressure required to open the toilet room door is 14 pounds of force. Provide a door that requires no more than 5 pounds of force to open. Standards §§ 4.1.3(7)(b), 4.13.11(2)(b).

iii. The urinal rim is mounted 24½ inches above the finished floor and the flush control is mounted 47 inches above the finished floor. Provide a urinal with an elongated rim mounted 17 inches or less above the finished floor, a clear floor space of at least 30 inches wide and 48 inches deep centered on the urinal, and a flush control height of 44 inches or less above the finished floor. Standards §§ 4.1.3(11), 4.22.5, 4.18.2, 4.18.3, 4.18.4.

iv. The toilet centerline is 15 inches from the side wall. Provide a toilet with a centerline that measures 18 inches from the near side wall. Standards §§ 4.1.3(11), 4.22.4, 4.16.2, Fig. 28.

v. The toilet flush control is on the "closed" side of the toilet. Provide a flush control mounted on the "open" side of the toilet's clear floor space; 44 inches or less above the finished floor; and requiring a maximum of 5 pounds of force to operate; or provide an automatic flush device. Standards §§ 4.1.3(11), 4.22.4, 4.16.5, 4.27.4.

vi. The distance of the far end of the side grab bar to the rear wall is 45 inches. Provide a side grab bar that is at least 42 inches in overall length, with the far end mounted at least 54 inches from the rear wall and the closer end 12 inches or less from the rear wall. Standards §§ 4.1.3(11), 4.22.4, 4.16.4, Fig. 29(b).

2. Within six months of the effective date of this Agreement, Pike County will complete the following modifications to the Blackberry Creek Senior Citizen Center, located at 4596 State Highway1056, McCarr:

a. Parking: Although the parking lot has a total of approximately 13 parking spaces, there are no spaces designated as reserved for persons with disabilities. On the shortest accessible route to the accessible entrance, provide 1 van accessible space designated as reserved for people with disabilities. The van accessible space must be a minimum of 96 inches wide and served by access aisles at least 96 inches wide. At all spaces designated as reserved for persons with disabilities, provide vertical signs with the International Symbol of Accessibility located such that they cannot be obstructed by parked vehicles. At van accessible space, provide an additional "Van-Accessible" sign located below the International Symbol of Accessibility. All spaces and access aisles for persons with disabilities must be flat and level, with slopes and cross-slopes not exceeding 1:50 in all directions, and their surfaces must be firm, stable, and slip-resistant. Standards §§ 4.1.2(5), 4.6, 4.30.7(1).

b. Ramp to entrance: The ramp is inaccessible because: the bottom landing of the ramp is not level (running slope measures 2.9% and cross slope measures 2.7%); the space between the bottom landing and the ramp is unstable because the cement is crumbling; the handrails are mounted 44 to 45 inches above the finished floor; the inside handrail is not continuous; the upper leg of the ramp does not have handrails on both sides; the handrails lack extensions; the handrail diameter is 5 1/4 inches; and the handrails are made of wood and not free of splinters. Provide a ramp that is at least 36 inches wide with a slope not exceeding 1:12 and a cross slope not exceeding 1:50; with level landings at least as wide as the ramp and 60 inches long at the top and bottom of the ramp; and with edge protection at least 2 inches high at the drop off sides. Provide handrails that are between 1¼ inches and 1½ inches in diameter with a continuous gripping surface along both sides of the ramp, extending at least 12 inches beyond the top and bottom of the ramp parallel with the ground surface. Ensure that handrails are mounted between 34 inches and 38 inches above the ramp surface, with ends rounded or returned smoothly to the floor, wall, or post, and that they do not rotate within their fittings. Ensure that the ramp and approaches are designed so that water will not accumulate on walking surfaces. Standards §§ 4.1.2(1), 4.1.2(2), 4.3.8, 4.8.

c. Main entrance

i. Exterior doors (2): The two exterior entrance doors, which are accessed through a front approach, are inaccessible because plant stands reduce the maneuvering space at the latch on the pull side of the door to 7 inches. On the pull side of the doors, provide maneuvering clearance at least 60 inches deep and provide a minimum of 18 inches (24 inches is preferred) of maneuvering clearance on the latch side of the door. Standards §§ 4.1.3(7)(b), 4.13.6, Fig. 25(a).

ii. Interior door (double hinged door): The pressure required to open the doors is 11 pounds. Provide doors that requires no more than 5 pounds of force to open. Standards §§ 4.1.3(7)(b), 4.13.11(2)(b).

d. Side entrance (near craft room)

i. The side entrance, which is accessed through a front approach and which has a closer and latch, has 4 inches of maneuvering clearance at the latch on the pull side of the door. On the pull side of the door, provide maneuvering clearance at least 60 inches deep and provide a minimum of 18 inches (24 inches is preferred) of maneuvering clearance on the latch side of the door. Standards §§ 4.1.3(7)(b), 4.13.6, Fig. 25(a).

ii. The side entrance threshold is 3/4 inch in height. Provide an accessible door with a threshold that is no greater than ¼ inch, or is no greater than ½ inch and is beveled with a slope no greater than 1:2. Standards §§ 4.1.3(7)(a), 4.13.8, 4.5.2.

e. Common room: The service counter to the kitchen is mounted with its top at 44 inches above the finished floor. Provide a counter on an accessible route such that a portion of the counter is at least 36 inches wide and no more than 36 inches above the finished floor, or provide an auxiliary counter with a maximum height of 36 inches in close proximity to the main counter, or provide equivalent facilitation. Equivalent facilitation may be provided in the form of a folding shelf attached to the main counter, an auxiliary table nearby, or other means. Standards §§ 4.1.1(2), 7.2(2), 4.1.3(1), 4.3.

f. Drinking fountain (located in common room): Although a lower accessible drinking fountain is provided, there is no drinking fountain provided for people who have difficulty bending or stooping. Provide a drinking fountain that is accessible to people who have difficulty bending or stooping. This can be accommodated by the use of a "hi-lo" fountain; by providing one fountain accessible to those who use wheelchairs and one fountain at a standard height convenient for those who have difficulty bending; by providing a fountain accessible to people who use wheelchairs and a cup dispenser, or by such other means as would achieve the required accessibility for each group of people. Standards § 4.1.3(10)(a).

g. Men's toilet room with stalls

i. The route to the toilet room is inaccessible because it is blocked by rocking chairs. Provide an accessible route to the toilet room with required minimum width, passing space, head room, surface textures, slopes, and changes in level. Standards §§ 4.1.3(11), 4.22.1, 4.3.1, 4.3.2, 4.3.3, 4.3.4, 4.3.5, 4.3.6, 4.3.7, 4.3.8.

ii. The toilet room sign is inaccessible. Provide a toilet room sign with raised and Braille characters. The sign shall be mounted on the wall adjacent to the latch side of the door with the centerline of the sign at 60 inches above the finished floor and situated such that a person can approach within 3 inches of the sign without encountering an obstruction or standing within a door swing. Standards §§ 4.1.2(7)(d), 4.30.1, 4.30.4, 4.30.5, 4.30.6, 4.30.7.

iii. The pressure required to open the toilet room door is 13 pounds. Provide a door that requires no more than 5 pounds of force to open. Standards §§ 4.1.3(7)(b), 4.13.11(2)(b).

iv. There is a ½ inch threshold on the interior side of the toilet room entrance door that is not beveled. Provide a door with a threshold no greater than ¼ inch, or between ¼ inch and ½ inch and beveled with a slope no greater than 1:2. Standards §§ 4.1.3(7)(b), 4.13.8, 4.5.2.

v. No accessible mirror has been provided. Provide a mirror with the bottom edge of its reflecting surface no more than 40 inches above the finished floor. Standards §§ 4.1.3(11), 4.22.6, 4.19.6.

vi. The hot water and drain pipes under the lavatory are not covered or otherwise configured against contact, and faucet operation requires twisting of the wrist. Provide a lavatory with the top of its rim or counter 34 inches or less above the finished floor; the bottom edge of the apron at least 29 inches above the finished floor; knee and toe clearances that comply with Fig. 31; hot water and drain pipes covered or otherwise configured to protect against contact; clear floor space at least 30 inches wide and 48 inches deep centered on the lavatory; and a faucet that can be operated with 5 pounds of force or less and can be used with one hand and without tight grasping, pinching, or twisting of the wrist (lever-operated, push-type, and electronically controlled mechanisms are examples of acceptable designs). Standards §§ 4.1.3(11), 4.22.6, 4.19.2, 4.19.3, 4.19.4, 4.19.5, 4.27.4, Figs. 31, 32.

vii. The urinal rim is mounted 25 inches above the finished floor and the flush control is mounted 45 ½ inches above the finished floor. Provide a urinal with an elongated rim mounted 17 inches or less above the finished floor, a clear floor space of at least 30 inches wide and 48 inches deep centered on the urinal, and a flush control height of 44 inches or less above the finished floor. Standards §§ 4.1.3(11), 4.22.5, 4.18.2, 4.18.3, 4.18.4.

viii. Toilet stall for wheelchair users

(1) The toilet flush control is on the closed side. Provide a flush control mounted on the "open" side of the toilet's clear floor space; 44 inches or less above the finished floor; and requiring a maximum of 5 pounds of force to operate; or provide an automatic flush device. Standards §§ 4.1.3(11), 4.22.4, 4.16.5, 4.17.2, 4.27.4.

(2) No accessible coat hook has been provided. Provide a coat hook at a maximum height above the finished floor of 48 inches for a forward approach or 54 inches for a side approach and that are accompanied by clear floor space of 30 by 48 inches that allows a forward or parallel approach by a person using a wheelchair. Standards §§ 4.1.3(12)(a), 4.25.2, 4.25.3, 4.2.4, 4.2.5, 4.2.6.

(3) The toilet paper dispenser is mounted 40 inches from the rear wall. Provide a toilet paper dispenser that is mounted with its top at least 1½ inches under the side grab bar and 36 inches or less from the rear wall and is centered at least 19 inches above the finished floor. Standards §§ 4.1.3(11), 4.22.4, 4.17.3, Fig. 30(d).

(4) The far end of the rear grab bar is mounted 11½ inches from the side wall. Provide a rear grab bar that is at least 36 inches in overall length, with the closer end no more than 6 inches from the side wall; mounted 33 to 36 inches above the finished floor; with a diameter between 1¼ and 1½ inches; with 1½ inches between the grab bar and the wall; and at least 1½ inches between the grab bar and any other object, such as a toilet seat cover dispenser. Standards §§ 4.1.3(11), 4.22.4, 4.17.6, 4.26.2, Fig. 30.

h. Women's toilet room with stalls

i. The route to the toilet room is inaccessible because it is blocked by rocking chairs. Provide an accessible route to the toilet room with required minimum width, passing space, head room, surface textures, slopes, and changes in level. Standards §§ 4.1.3(11), 4.22.1, 4.3.1, 4.3.2, 4.3.3, 4.3.4, 4.3.5, 4.3.6, 4.3.7, 4.3.8.

ii. The toilet room sign is inaccessible. Provide a toilet room sign with raised and Braille characters. The sign shall be mounted on the wall adjacent to the latch side of the door with the centerline of the sign at 60 inches above the finished floor and situated such that a person can approach within 3 inches of the sign without encountering an obstruction or standing within a door swing. Standards §§ 4.1.2(7)(d), 4.30.1, 4.30.4, 4.30.5, 4.30.6, 4.30.7.

iii. The pressure required to open the toilet room door is 15 pounds. Provide a door that requires no more than 5 pounds of force to open. Standards §§ 4.1.3(7)(b), 4.13.11(2)(b).

iv. There is a ½ inch threshold on the interior side of the toilet room entrance door that is not beveled. Provide a door with a threshold no greater than ¼ inch, or between ¼ inch and ½ inch and beveled with a slope no greater than 1:2. Standards §§ 4.1.3(7)(b), 4.13.8, 4.5.2.

v. The door to the toilet room, which is accessed through a front approach, has inadequate maneuvering space on the pull side of the door (40 inches deep) due to the placement of a toilet stall partition. On the pull side of the door, provide maneuvering clearance at least 60 inches deep and provide a minimum of 18 inches (24 inches is preferred) of maneuvering clearance on the latch side of the door. Standards §§ 4.1.3(7)(b), 4.13.6, Fig. 25(a).

vi. There is insufficient turning space within the toilet room. Provide an unobstructed turning space at least 60 inches in diameter or a T-shaped space complying with Fig. 3(b). Standards §§ 4.1.3(11), 4.22.3, 4.2.3, Fig. 3.

vii. No accessible mirror has been provided. Provide a mirror with the bottom edge of its reflecting surface no more than 40 inches above the finished floor. Standards §§ 4.1.3(11), 4.22.6, 4.19.6.

viii. The hot water and drain pipes under the lavatory are not covered or otherwise configured against contact, and faucet operation requires twisting of the wrist. Provide a lavatory with the top of its rim or counter 34 inches or less above the finished floor; the bottom edge of the apron at least 29 inches above the finished floor; knee and toe clearances that comply with Fig. 31; hot water and drain pipes covered or otherwise configured to protect against contact; clear floor space at least 30 inches wide and 48 inches deep centered on the lavatory; and a faucet that can be operated with 5 pounds of force or less and can be used with one hand and without tight grasping, pinching, or twisting of the wrist (lever-operated, push-type, and electronically controlled mechanisms are examples of acceptable designs). Standards §§ 4.1.3(11), 4.22.6, 4.19.2, 4.19.3, 4.19.4, 4.19.5, 4.27.4, Figs. 31, 32.

ix. Toilet stall for wheelchair users

(1) The toilet centerline measures 17 inches from the side wall. Provide a toilet with a centerline that measures 18 inches from the near side wall. Standards §§ 4.1.3(11), 4.22.4, 4.17.3, Fig. 30.

(2) No accessible coat hook has been provided. Provide a coat hook at a maximum height above the finished floor of 48 inches for a forward approach or 54 inches for a side approach and that are accompanied by clear floor space of 30 by 48 inches that allows a forward or parallel approach by a person using a wheelchair. Standards §§ 4.1.3(12)(a), 4.25.2, 4.25.3, 4.2.4, 4.2.5, 4.2.6.

(3) The toilet paper dispenser is mounted 38 inches from the rear wall. Provide a toilet paper dispenser that is mounted with its top at least 1½ inches under the side grab bar and 36 inches or less from the rear wall and is centered at least 19 inches above the finished floor. Standards §§ 4.1.3(11), 4.22.4, 4.17.3, Fig. 30(d).

(4) The near end of the rear grab bar is mounted 13 inches from the side wall. Provide a rear grab bar that is at least 36 inches in overall length, with the closer end no more than 6 inches from the side wall; mounted 33 to 36 inches above the finished floor; with a diameter between 1¼ and 1½ inches; with 1½ inches between the grab bar and the wall; and at least 1½ inches between the grab bar and any other object, such as a toilet seat cover dispenser. Standards §§ 4.1.3(11), 4.22.4, 4.17.6, 4.26.2, Fig. 30.

(5) The plant stand mounted above the rear grab bar interferes with its use. Provide a rear grab bar that has at least 1½ inches between the grab bar and any object beside or below it and at least 18 inches between the grab bar and any object above it. Standards §§ 4.1.3(11), 4.22.4, 4.17.6, 4.26.2, Fig. 39.

i. Coat hanger in exercise room: The height of the coat hanger exceeds 54 inches. Provide a coat hook at a maximum height above the finished floor of 48 inches for a forward approach or 54 inches for a side approach and that is accompanied by clear floor space of 30 by 48 inches that allows a forward or parallel approach by a person using a wheelchair. Standards §§ 4.1.3(12)(a), 4.25.2, 4.25.3, 4.2.4, 4.2.5, 4.2.6.

j. Craft room

i. At the craft room entrance, there is a ½ inch threshold which is not beveled. Provide a door with a threshold no greater than ¼ inch, or between ¼ inch and ½ inch and beveled with a slope no greater than 1:2. Standards §§ 4.1.3(7)(b), 4.13.8, 4.5.2.

ii. Although the facility contains an emergency alarm system, there is no visual alarm appliance in the toilet room. Provide a visual alarm appliance in the craft room. Standards §§ 4.1.3(14), 4.28.1, 4.28.3.

k. Director's office: The office door threshold is ½ inch in height and not beveled on the hallway side. Provide a door with a threshold no greater than ¼ inch, or between ¼ inch and ½ inch and beveled with a slope no greater than 1:2. Standards §§ 4.1.3(7)(b), 4.13.8, 4.5.2.

l. Tennis court: The route to the tennis court is not firm, stable and slip resistant due to grass overgrowth at the entrance to the tennis court. Provide at least one accessible route within the boundary of the site connecting these elements that, to the maximum extent feasible, coincides with the route for the general public. The accessible route must have a minimum clear width of 36 inches, or a minimum clear width of 42 inches if there is a turn around an obstruction less than 48 inches wide; have passing spaces at least 60 inches by 60 inches at least every 200 feet; have a minimum clear headroom of 80 inches; have a surface that is firm, stable, and slip resistant; have, in the absence of a curb ramp, ramp, elevator, or platform lift, no level changes in excess of ½ inch vertically; and have a running slope of less than 1:20 (5%) (or have been constructed as a fully accessible ramp) and a cross slope of less than 1:50 (2%). Standards §§ 4.1.3(1), 4.3, 4.5, Fig. 7.

3. Within six months of the effective date of this Agreement, Pike County will complete the following modifications to the Grants Branch Park, located at 1040 Grants Branch Road, McVeigh:

a. Parking lot adjacent to lake

i. Although the parking lot has a total of 14 parking spaces, there are no spaces provided for persons with disabilities. On the shortest accessible route to the accessible entrance, provide 1 van accessible space designated as reserved for people with disabilities. Ensure that van accessible spaces are a minimum of 96 inches wide and served by access aisles at least 96 inches wide. At all spaces designated as reserved for persons with disabilities, provide vertical signs with the International Symbol of Accessibility located such that they cannot be obstructed by parked vehicles. At van accessible spaces, provide an additional "Van-Accessible" sign located below the International Symbol of Accessibility. Ensure that all spaces and access aisles for persons with disabilities are flat and level, with slopes and cross-slopes not exceeding 1:50 in all directions, and that their surfaces are firm, stable, and slip-resistant. Standards §§ 4.1.2(5), 4.6, 4.30.7(1).

ii. The route from the parking area to the sidewalk leading to the fishing area is inaccessible because there is no curb ramp provided. Provide a curb ramp that is at least 36 inches wide, has a maximum slope of 1:12, is located so that it cannot be obstructed by parked vehicles, and has a stable, firm, and slip-resistant surface with a detectable warning extending the full width and depth of the ramp. If the curb ramp is located where pedestrians must walk across it, provide either flared sides (with a maximum slope of 1:10) or handrails or guardrails to protect against cross traffic. Standards §§ 4.1.2(1), 4.1.2(2), 4.3.8, 4.7, Fig. 12.

iii. The route from the parking area to the boat loading area is inaccessible because there is no accessible route provided (individuals must walk on the grass or in the street). Provide at least one accessible route within the boundary of the site connecting these elements that, to the maximum extent feasible, coincides with the route for the general public. The accessible route must have a minimum clear width of 36 inches, or a minimum clear width of 42 inches if there is a turn around an obstruction less than 48 inches wide; have passing spaces at least 60 inches by 60 inches at least every 200 feet; have a minimum clear headroom of 80 inches; have a surface that is firm, stable, and slip resistant; have, in the absence of a curb ramp, ramp, elevator, or platform lift, no level changes in excess of ½ inch vertically; and have a running slope of less than 1:20 (5%) (or have been constructed as a fully accessible ramp) and a cross slope of less than 1:50 (2%). Standards §§ 4.1.3(1), 4.3, 4.5, Fig. 7.

b. Parking lot between cabin and lake picnic pavilion

i. Although the parking lot has a total of 35 parking spaces, there are no spaces provided for persons with disabilities. On the shortest accessible route to the cabin, provide 1 van accessible space designated as reserved for people with disabilities. One the shortest accessible route to the picnic pavilion, provide 1 standard space designated as reserved for people with disabilities. Ensure that standard accessible spaces are a minimum of 96 inches wide and served by access aisles at least 60 inches wide. Ensure that van accessible spaces are a minimum of 96 inches wide and served by access aisles at least 96 inches wide. At all spaces designated as reserved for persons with disabilities, provide vertical signs with the International Symbol of Accessibility located such that they cannot be obstructed by parked vehicles. At van accessible spaces, provide an additional "Van-Accessible" sign located below the International Symbol of Accessibility. Ensure that all spaces and access aisles for persons with disabilities are flat and level, with slopes and cross-slopes not exceeding 1:50 in all directions, and that their surfaces are firm, stable, and slip-resistant. Standards §§ 4.1.2(5), 4.6, 4.30.7(1).

ii. The route from the parking lot to the sidewalk leading to the lake picnic pavilion is inaccessible because there is no curb ramp provided. Provide a curb ramp that is at least 36 inches wide, has a maximum slope of 1:12, is located so that it cannot be obstructed by parked vehicles, and has a stable, firm, and slip-resistant surface with a detectable warning extending the full width and depth of the ramp. If the curb ramp is located where pedestrians must walk across it, provide either flared sides (with a maximum slope of 1:10) or handrails or guardrails to protect against cross traffic. Standards §§ 4.1.2(1), 4.1.2(2), 4.3.8, 4.7, Fig. 12.

c. Cabin

i. The route from the parking lot to the ramp leading to the cabin is inaccessible because there is no accessible route provided (individuals must walk over grass or in the street). Provide at least one accessible route within the boundary of the site connecting these elements that, to the maximum extent feasible, coincides with the route for the general public. The accessible route must have a minimum clear width of 36 inches, or a minimum clear width of 42 inches if there is a turn around an obstruction less than 48 inches wide; have passing spaces at least 60 inches by 60 inches at least every 200 feet; have a minimum clear headroom of 80 inches; have a surface that is firm, stable, and slip resistant; have, in the absence of a curb ramp, ramp, elevator, or platform lift, no level changes in excess of ½ inch vertically; and have a running slope of less than 1:20 (5%) (or have been constructed as a fully accessible ramp) and a cross slope of less than 1:50 (2%). Standards §§ 4.1.3(1), 4.3, 4.5, Fig. 7.

ii. Exterior ramp: The bottom landing of the ramp is not level, firm, stable, and slip resistant (consists of dirt and grass), there is an abrupt 4 inch change in level at the bottom of the ramp; the slope of the bottom leg of the ramp measures between 9.1% and 9.7%, the slope of the top leg measures between 9.0% and 10.9%, there are no handrail extensions at the bottom or top of the ramp, the ends of the handrails do not return smoothly to the floor or post, the diameter of the handrails is 5 inches; and the handrails are not free of splinters and sharp objects. Provide a ramp that is at least 36 inches wide with a slope not exceeding 1:12 and a cross slope not exceeding 1:50; with level landings at least as wide as the ramp and 60 inches long at the top and bottom of the ramp; with level landings measuring at least 60 inches by 60 inches when the ramp changes direction; and edge protection that is at least 2 inches high at the drop off sides. Provide handrails that are between 1¼ inches and 1½ inches in diameter such that the inside handrail is continuous and both handrails have a continuous gripping surface along both sides of the ramp extending at least 12 inches beyond the top and bottom of the ramp parallel with the ground surface; the handrails do not rotate within their fittings; and both handrails are mounted between 34 inches and 38 inches above the ramp surface, with ends rounded or returned smoothly to the floor, wall, or post. Ensure that the ramp and approaches are designed so that water will not accumulate on walking surfaces. Standards §§ 4.1.2(1), 4.1.2(2), 4.3.8, 4.8.

iii. Exterior entrance doors

(1) Each entrance door has knob hardware that requires tight grasping and twisting of the wrist to operate. Provide doors with hardware that is easy to grasp with one hand and that does not require tight grasping, pinching, or twisting of the wrist to operate. Lever-operated mechanisms, push-type mechanisms, and U-shaped handles are acceptable designs. Standards §§ 4.1.3(7)(b), 4.13.9.

(2) Each entrance door has a ½ to 3/4 inch threshold on the exterior sides of the doors, and a 3/4 to 1 inch threshold on the interior sides of the doors. Provide accessible doors with thresholds that are no greater than ¼ inch, or is no greater than ½ inch and is beveled with a slope no greater than 1:2. Standards §§ 4.1.3(7)(a), 4.13.8, 4.5.2.

iv. Unisex single user toilet room

(1) No accessible toilet room sign is provided. Provide a toilet room sign with raised and Braille characters. The sign shall be mounted on the wall adjacent to the latch side of the door with the centerline of the sign at 60 inches above the finished floor and situated such that a person can approach within 3 inches of the sign without encountering an obstruction or standing within a door swing. Standards §§ 4.1.2(7)(d), 4.30.1, 4.30.4, 4.30.5, 4.30.6, 4.30.7.

(2) The toilet room door has knob hardware requiring tight grasping or twisting of the wrist to operate. Provide a door with hardware that is easy to grasp with one hand and that does not require tight grasping, pinching, or twisting of the wrist to operate. Lever-operated mechanisms, push-type mechanisms, and U-shaped handles are acceptable designs. Standards §§ 4.1.3(7)(b), 4.13.9.

(3) The door to the toilet room, which is accessed through a front approach, is inaccessible because it has only 13 inches of maneuvering clearance at the latch on the pull side of the door. On the pull side of the door, provide maneuvering clearance at least 60 inches deep and provide a minimum of 18 inches (24 inches is preferred) of maneuvering clearance on the latch side of the door. Standards §§ 4.1.3(7)(b), 4.13.6, Fig. 25(a).

(4) The toilet room door swings into the required clear floor space at the toilet. Ensure that no door swings into the required clear floor space at any accessible fixture. Standards §§ 4.1.3(11), 4.22.2.

(5) The urinal rim is mounted 23 inches above the finished floor and the flush control is mounted 45 inches above the finished floor. Provide a urinal with an elongated rim mounted 17 inches or less above the finished floor, a clear floor space of at least 30 inches wide and 48 inches deep centered on the urinal, and a flush control height of 44 inches or less above the finished floor. Standards §§ 4.1.3(11), 4.22.5, 4.18.2, 4.18.3, 4.18.4.

(6) The top of the toilet seat is 16 ½ inches above the finished floor. Provide a toilet with a seat that measures 17 to 19 inches above the finished floor. Standards §§ 4.1.3(11), 4.22.4, 4.16.3, Fig. 29(b).

(7) The toilet centerline measures 20 inches from the side wall. Provide a toilet with a centerline that measures 18 inches from the near side wall. Standards §§ 4.1.3(11), 4.22.4, 4.16.2, Fig. 28.

(8) There are no grab bars provided at the toilet. Provide a rear grab bar that is at least 36 inches in overall length, with the closer end no more than 6 inches from the side wall, and a side grab bar that is at least 42 inches in overall length, with the far end mounted at least 54 inches from the rear wall and the closer end 12 inches or less from the rear wall. Ensure that the grab bars are mounted 33 to 36 inches above the finished floor; with a diameter between 1¼ and 1½ inches; with 1½ inches between the grab bars and the wall; and at least 1½ inches between the grab bars and any other object, such as a toilet paper dispenser or a toilet seat cover dispenser. Standards §§ 4.1.3(11), 4.22.4, 4.16.4, 4.26.2, Fig. 29.

d. Parking lot at lower picnic pavilion

i. Although the parking lot has a total of 16 parking spaces, there are no spaces provided for persons with disabilities. On the shortest accessible route to picnic pavilion, provide 1 van accessible space designated as reserved for people with disabilities. Ensure that the van accessible space is a minimum of 96 inches wide and served by access aisles at least 96 inches wide. At all spaces designated as reserved for persons with disabilities, provide vertical signs with the International Symbol of Accessibility located such that they cannot be obstructed by parked vehicles. At van accessible spaces, provide an additional "Van-Accessible" sign located below the International Symbol of Accessibility. Ensure that all spaces and access aisles for persons with disabilities are flat and level, with slopes and cross-slopes not exceeding 1:50 in all directions, and that their surfaces are firm, stable, and slip-resistant. Standards §§ 4.1.2(5), 4.6, 4.30.7(1).

ii. The route from the parking lot to the sidewalk leading to the picnic pavilion is inaccessible because there is no curb ramp provided. Provide a curb ramp that is at least 36 inches wide, has a maximum slope of 1:12, is located so that it cannot be obstructed by parked vehicles, and has a stable, firm, and slip-resistant surface with a detectable warning extending the full width and depth of the ramp. If the curb ramp is located where pedestrians must walk across it, provide either flared sides (with a maximum slope of 1:10) or handrails or guardrails to protect against cross traffic. Standards §§ 4.1.2(1), 4.1.2(2), 4.3.8, 4.7, Fig. 12.

e. Portable toilets: Although three portable toilets are provided, they contain a number of inaccessible elements and are not accessible to people with disabilities. Provide an accessible portable toilet such that all of the room's elements, including signage, door, door hardware, clear floor space, water closet, grab bars, lavatory, mirror, controls, and dispensers, comply with the Standards. Standards §§ 4.1.3(11), 4.1.6(1)(b), 4.22, 4.13, 4.16, 4.18, 4.19, 4.26, 4.27, 4.30, Figs. 28, 29.

4. Within six months of the effective date of this Agreement, Pike County will complete the following modifications to the Intergenerational Center, located at 136 Park Road, Freeburn:

a. Parking: Although the parking lot has 40 parking spaces, including four designated as reserved for people with disabilities, the spaces are not demarcated, no access aisles are provided, and the vertical signs can be obstructed by parked vehicles. On the shortest accessible route to the accessible entrance, provide one van accessible space and one standard space designated as reserved for people with disabilities. The standard accessible space must be a minimum of 96 inches wide and served by access aisles at least 60 inches wide. The van accessible space must be a minimum of 96 inches wide and served by access aisles at least 96 inches wide. At all spaces designated as reserved for persons with disabilities, provide vertical signs with the International Symbol of Accessibility located such that they cannot be obstructed by parked vehicles. At van accessible spaces, provide an additional "Van-Accessible" sign located below the International Symbol of Accessibility. All spaces and access aisles for persons with disabilities must be flat and level, with slopes and cross-slopes not exceeding 1:50 in all directions, and their surfaces must be firm, stable, and slip-resistant. Standards §§ 4.1.2(5), 4.6, 4.30.7(1).

b. Day room/common room: The two kitchen counters protrude 12 inches into the circulation route and are not detectable to a blind person or person with low vision who is using a cane. Provide an accessible route at this location such that no objects with their bottom leading edges measuring between 27 inches and 80 inches above the finished floor protrude more than 4 inches into walks, halls, corridors, passageways, or aisles. Freestanding objects mounted on posts or pylons may overhang 12 inches maximum from 27 inches to 80 inches above the ground or finished floor. Providing a cane-detectable barrier is an acceptable solution. Standards §§ 4.1.2(3), 4.4.

c. Pool room: Although the facility contains an emergency alarm system, there is no visual alarm in the pool room. Provide visual alarm devices in toilet rooms and any other general usage areas (e.g., meeting rooms), hallways, lobbies, and any other area for common use. Such devices shall be integrated into the facility alarm system and shall meet the requirements of the Standards for lamp type, color, pulse duration, intensity, and flash rate. Visual alarm appliances shall be placed 80 inches above the highest floor level within the space or 6 inches below the ceiling, whichever is lower. Visual alarm appliances shall be located such that no place in any room or space, including common corridors or hallways, required to have a visual alarm appliance shall be more than 50 feet from the signal. In large rooms and spaces exceeding 100 feet across, without obstructions 6 feet above the finished floor, devices may be placed around the perimeter, spaced a maximum of 100 feet apart, in lieu of suspending appliances from the ceiling. Standards §§ 4.1.3(14), 4.28.3.

d. Dining room: The counter protrudes 12 inches from the wall and is undetectable to a blind person or person with low vision who is using a cane. Provide an accessible route at this location such that no objects with their bottom leading edges measuring between 27 inches and 80 inches above the finished floor protrude more than 4 inches into walks, halls, corridors, passageways, or aisles. Freestanding objects mounted on posts or pylons may overhang 12 inches maximum from 27 inches to 80 inches above the ground or finished floor. Providing a cane-detectable barrier is an acceptable solution. Standards §§ 4.1.2(3), 4.4.

e. Men's and women's toilet rooms (located off of the day room)

i. The toilet room signs are inaccessible. Provide toilet room signs with the International Symbol of Accessibility and raised and Braille characters. The signs shall be mounted on the wall adjacent to the latch side of the door with the centerline of the sign at 60 inches above the finished floor and situated such that a person can approach within 3 inches of the sign without encountering an obstruction or standing within a door swing. Standards §§ 4.1.2(7)(d), 4.30.1, 4.30.4, 4.30.5, 4.30.6, 4.30.7.

ii. The force required to open the toilet room entrance door is 10 pounds of force in the women's toilet room and 11 pounds of force in the men's toilet room. Provide a door that requires no more than 5 pounds of force to open. Standards §§ 4.1.3(7)(b), 4.13.11(2)(b).

iii. The urinal in the men's toilet room has a rim mounted at 23 inches above the finished floor and the flush control is mounted 45 inches above the finished floor. Provide a urinal with an elongated rim mounted 17 inches or less above the finished floor, a clear floor space of at least 30 inches wide and 48 inches deep centered on the urinal, and a flush control height of 44 inches or less above the finished floor. Standards §§ 4.1.3(11), 4.22.5, 4.18.2, 4.18.3, 4.18.4.

iv. Toilet stalls for wheelchair users

(1) The flush control of the toilet in the women's toilet room stall for wheelchair users is on the closed side. Provide a flush control mounted on the "open" side of the toilet's clear floor space; 44 inches or less above the finished floor; and requiring a maximum of 5 pounds of force to operate; or provide an automatic flush device. Standards §§ 4.1.3(11), 4.22.4, 4.16.5, 4.17.2, 4.27.4.

(2) The top of the toilet seat in the men's toilet room is 16 inches above the finished floor and its centerline measures 17 inches from the side wall. Provide a toilet with a seat that measures 17 to 19 inches above the finished floor and a centerline that measures 18 inches from the near side wall. Standards §§ 4.1.3(11), 4.22.4, 4.16.3, 4.17.2, 4.17.3, Fig. 30, Fig. 30(d).

(3) No accessible coat hook has been provided in the men's toilet room stall for wheelchair users. Provide a coat hook at a maximum height above the finished floor of 48 inches for a forward approach or 54 inches for a side approach and that is accompanied by clear floor space of 30 by 48 inches that allows a forward or parallel approach by a person using a wheelchair. Standards §§ 4.1.3(12)(a), 4.25.2, 4.25.3, 4.2.4, 4.2.5, 4.2.6.

(4) In the women's toilet room, the toilet paper dispenser is mounted 1/4 inch below the side grab bar and the far end of the side grab bar is mounted 50 inches from the rear wall. Provide a side grab bar that is at least 40 inches in overall length, with the far end mounted at least 52 inches from the rear wall and the closer end 12 inches or less from the rear wall; mounted 33 to 36 inches above the finished floor; with a diameter between 1¼ and 1½ inches; with 1½ inches between the grab bar and the wall; and at least 1½ inches between the grab bar and any other object, such as the toilet paper dispenser. Standards §§ 4.1.3(11), 4.22.4, 4.17.6, 4.26.2, Figs. 30(a), (d).

(5) In the men's toilet room, the toilet paper dispenser is mounted 1 inch below the side grab bar and the far end of the side grab bar is mounted 49 inches from the rear wall. Provide a side grab bar that is at least 40 inches in overall length, with the far end mounted at least 52 inches from the rear wall and the closer end 12 inches or less from the rear wall; mounted 33 to 36 inches above the finished floor; with a diameter between 1¼ and 1½ inches; with 1½ inches between the grab bar and the wall; and at least 1½ inches between the grab bar and any other object, such as the toilet paper dispenser. Standards §§ 4.1.3(11), 4.22.4, 4.17.6, 4.26.2, Figs. 30(a), (d).

(6) The rear grab bars at the toilet are inaccessible because the near ends are mounted 7 ½ inches (women's) and 8 inches (men's) from the side wall. At each location, provide a rear grab bar that is at least 36 inches in overall length, with the near end no more than 6 inches from the side wall; mounted 33 to 36 inches above the finished floor; with a diameter between 1¼ and 1½ inches; with 1½ inches between the grab bar and the wall; and at least 1½ inches between the grab bar and any other object, such as a toilet seat cover dispenser. Standards §§ 4.1.3(11), 4.22.4, 4.17.6, 4.26.2, Fig. 30.

f. Drinking fountains (located between the men's and women's toilet rooms): The lower drinking fountain is not accessible because the water height is less than 4 inches, the spout is not within 3 inches of the front of the fountain, and it protrudes into the walkway and would not be detectable to a low vision or blind person using a cane. Ensure that the drinking fountain spout directs the water flow in a trajectory that is nearly parallel to the front of the unit and is positioned so the flow of water is within 3 inches of the front edge of the fountain and at least 4 inches high. Standards § 4.15(3). Provide a circulation path at this location such that no objects with their bottom leading edges measuring between 27 inches and 80 inches above the finished floor protrude more than 4 inches into walks, halls, corridors, passageways, or aisles. Free-standing objects mounted on posts or pylons may overhang 12 inches maximum from 27 inches to 80 inches above the ground or finished floor. Providing a cane-detectable barrier is an acceptable solution. Standards §§ 4.1.2(3), 4.4.

g. Day care center: The pressure required to open the door between the day room and day care center is 15 pounds. Provide a door that requires no more than 5 pounds of force to open. Standards §§ 4.1.3(7)(b), 4.13.11(2)(b).

h. Single user adult toilet room in day care center

i. The toilet room sign is inaccessible. Provide a toilet room sign with the International Symbol of Accessibility and raised and Braille characters. The sign shall be mounted on the wall adjacent to the latch side of the door with the centerline of the sign at 60 inches above the finished floor and situated such that a person can approach within 3 inches of the sign without encountering an obstruction or standing within a door swing. Standards §§ 4.1.2(7)(d), 4.30.1, 4.30.4, 4.30.5, 4.30.6, 4.30.7.

ii. The pressure required to open the door to the toilet room door is 10 pounds. Provide a door that requires no more than 5 pounds of force to open. Standards §§ 4.1.3(7)(b), 4.13.11(2)(b).

iii. The door to the toilet room, which is accessed through a front approach, has 16 inches of maneuvering clearance at the latch on the pull side of the door. On the pull side of the door, provide maneuvering clearance at least 60 inches deep and provide a minimum of 18 inches (24 inches is preferred) of maneuvering clearance on the latch side of the door. Standards §§ 4.1.3(7)(b), 4.13.6, Fig. 25(a).

iv. The door to the toilet room swings into the required clear floor space at the toilet. Ensure that no door swings into the required clear floor space at any accessible fixture. Standards §§ 4.1.3(11), 4.22.2.

v. The toilet flush control is on the "closed" side of the toilet. Provide a flush control mounted on the "open" side of the toilet's clear floor space; 44 inches or less above the finished floor; and requiring a maximum of 5 pounds of force to operate; or provide an automatic flush device. Standards §§ 4.1.3(11), 4.22.4, 4.16.5, 4.27.4.

vi. There is 1 inch of space between the side grab bar and the toilet paper dispenser. Provide a side grab bar that has at least 1½ inches between the grab bar and any object beside or below it and at least 18 inches between the grab bar and any object above it. Standards §§ 4.1.3(11), 4.22.4, 4.17.6, 4.26.2, Fig. 39.

5. Within six months of the effective date of this Agreement, Pike County will complete the following modifications to the Pikeville Area Senior Citizen Center, located at 134 Bank Street, Pikeville:

a. Parking: Although the parking lot has a total of 27 parking spaces, including 2 designated as reserved for people with disabilities, the spaces reserved for people with disabilities are not accessible because the spaces are not level and the surface is not firm, stable and slip resistant. On the shortest accessible route to the accessible entrance, provide 1 van accessible space and 1 standard space designated as reserved for people with disabilities. The standard accessible space must be a minimum of 96 inches wide and served by access aisles at least 60 inches wide. The van accessible space must be a minimum of 96 inches wide and served by access aisles at least 96 inches wide. At all spaces designated as reserved for persons with disabilities, provide vertical signs with the International Symbol of Accessibility located such that they cannot be obstructed by parked vehicles. At the van accessible space, provide an additional "Van-Accessible" sign located below the International Symbol of Accessibility. All spaces and access aisles for persons with disabilities must be flat and level, with slopes and cross-slopes not exceeding 1:50 in all directions, and their surfaces must be firm, stable, and slip-resistant. Standards §§ 4.1.2(5), 4.6, 4.30.7(1).

b. Drinking fountain (located in the hallway at the entrance): Although a lower drinking fountain is provided, the water height measures 1 inch, and there is no option for people who have difficulty bending or stooping. Ensure that the drinking fountain spout directs the water flow in a trajectory that is nearly parallel to the front of the unit and is positioned so the flow of water is within 3 inches of the front edge of the fountain and at least 4 inches high. Standards § 4.15(3). Additionally, provide a drinking fountain that is accessible to people who have difficulty bending or stooping. This can be accomplished by providing a fountain accessible to people who use wheelchairs and a cup dispenser. Standards §§ 4.1.3(10), 4.15, 4.27.4, Fig. 27.

c. Recreation room (first door on left from entrance): The entrance door to the recreation room cannot be fully opened to allow for 32 inches of clear passage width because of the carpet thickness. Provide a door with a clear opening of 32 inches with the door open 90 degrees, measured between the face of the door and the opposite stop. Standards §§ 4.1.3(7)(b), 4.13.5, Fig. 24.

d. Coat rack (located outside of the door to the recreation room): Although a coat rack is provided, the hangers are more than 54 inches above the finished floor. Provide a coat hook or coat hanger at a maximum height above the finished floor of 48 inches for a forward approach or 54 inches for a side approach and that is accompanied by clear floor space of 30 by 48 inches that allows a forward or parallel approach by a person using a wheelchair. Standards §§ 4.1.3(12)(a), 4.25.2, 4.25.3, 4.2.4, 4.2.5, 4.2.6.

e. Single user toilet rooms – all

i. The toilet rooms do not have accessible signs. At each location, provide a toilet room sign with raised and Braille characters. The sign shall be mounted on the wall adjacent to the latch side of the door with the centerline of the sign at 60 inches above the finished floor and situated such that a person can approach within 3 inches of the sign without encountering an obstruction or standing within a door swing. Standards §§ 4.1.2(7)(d), 4.30.1, 4.30.4, 4.30.5, 4.30.6, 4.30.7.

ii. Although an audible alarm is provided in this facility, there are no visual alarms in the toilet rooms. Provide a visual alarm appliance in each toilet room. Standards §§ 4.1.3(14), 4.28.1, 4.28.3.

iii. The paper towel dispenser in each toilet room requires tight grasping to operate and protrudes more than 4 inches to the circulation path such that it is undetectable to a blind person or person with low vision who is using a cane. In each toilet room, provide a paper towel dispenser with mechanical controls, if any, that can be operated with 5 lbf or less and that can be used with one hand and without tight grasping, pinching, or twisting of the wrist (lever-operated, push-type, and electronically controlled mechanisms are examples of acceptable designs). At each location, provide a circulation path such that no objects with their bottom leading edges measuring between 27 inches and 80 inches above the finished floor protrude more than 4 inches into the circulation route. Free-standing objects mounted on posts or pylons may overhang 12 inches maximum from 27 inches to 80 inches above the ground or finished floor. Providing a cane-detectable barrier is an acceptable solution. Standards §§ 4.1.2(3), 4.1.3(13), 4.4, 4.27.4.

f. Women's toilet room #1 only (on right side, facing toilet room entrances)

i. No accessible mirror is provided. Provide a mirror with the bottom edge of its reflecting surface no more than 40 inches above the finished floor. Standards §§ 4.1.3(11), 4.22.6, 4.19.6.

ii. The lavatory is inaccessible because the hot water pipes are not insulated or otherwise configured to protect against contact. Provide hot water and drain pipes that are insulated or otherwise configured to protect against contact. Standards §§ 4.1.3(11), 4.22.6, 4.19.4.

iii. The grab bars at the toilet are inaccessible because the distance of the farther end of the side grab bar to the rear wall is 46 inches, the overall length of the rear grab bar is 30 inches, and the distance of the further end of the rear grab bar to the side wall is 33 to the side wall. Provide a rear grab bar that is at least 36 inches in overall length, with the closer end no more than 6 inches from the side wall, and a side grab bar that is at least 42 inches in overall length, with the far end mounted at least 54 inches from the rear wall and the closer end 12 inches or less from the rear wall. Ensure that the grab bars are mounted 33 to 36 inches above the finished floor; with a diameter between 1¼ and 1½ inches; with 1½ inches between the grab bars and the wall; and at least 1½ inches between the grab bars and any object beside or below it and at least 18 inches between the grab bar and any object above it. Standards §§ 4.1.3(11), 4.22.4, 4.16.4, 4.26.2, Figs. 29, 39.

iv. The toilet paper dispenser is inaccessible because it is mounted at 47 inches above the finished floor, above the side grab bar. Provide a toilet paper dispenser that is mounted within reach, with its top at least 1½ inches under the side grab bar, and centered at least 19 inches above the finished floor. Standards §§ 4.1.3(11), 4.22.4, 4.16.6, Fig. 29(b).

v. The rear grab bar at the toilet is obstructed by the soap dispenser mounted above it. Provide a rear grab bar that has at least 1½ inches between the grab bar and any object beside or below it and at least 18 inches between the grab bar and any object above it. Standards §§ 4.1.3(11), 4.22.4, 4.16.4, 4.26.2, Fig. 39.

vi. The toilet centerline is 15 inches from the side wall. Provide a toilet with the centerline at 18 inches from the near side wall. Standards §§ 4.1.3(11), 4.22.4, 4.16.2, Fig. 28. 1

1 Shifting a toilet a small distance to comply with the centerline requirement need not be expensive.  The important factor is maintaining the correct distance between the side grab bar and the toilet.  Options include moving the partition on which the grab bar is mounted or installing an offset flange to shift the toilet.  Another option is to mount the grab bar on a board attached to the side wall or partition.  The board must extend 1 ½" below the grab bar and 18" above the grab bar to achieve the appropriate distance between toilet and grab bar.

g. Women's toilet room #2 only (on left side, facing toilet room entrances)

i. No accessible mirror is provided. Provide a mirror with the bottom edge of its reflecting surface no more than 40 inches above the finished floor. Standards §§ 4.1.3(11), 4.22.6, 4.19.6.

ii. The door to the toilet room, which is accessed through a front approach, and which has both a closer and a latch, is inaccessible because there are 3 ½ inches of maneuvering space at the latch on the push side of the door. On the push side of the door, provide maneuvering clearance at least 48 inches deep and provide a minimum of 12 inches of maneuvering clearance on the latch side of the door, or remove the closer or the latch. Standards §§ 4.1.3(7)(b), 4.13.6, Fig. 25(a).

iii. The bottom edge of the lavatory apron is 27 ½ inches above the finished floor and the hot water and drain pipes are not covered or otherwise configured to protect against contact. Provide a lavatory with the top of its rim or counter 34 inches or less above the finished floor; the bottom edge of the apron at least 29 inches above the finished floor; knee and toe clearances that comply with Fig. 31; hot water and drain pipes covered or otherwise configured to protect against contact; clear floor space at least 30 inches wide and 48 inches deep centered on the lavatory; and a faucet that can be operated with 5 pounds of force or less and can be used with one hand and without tight grasping, pinching, or twisting of the wrist (lever-operated, push-type, and electronically controlled mechanisms are examples of acceptable designs). Standards §§ 4.1.3(11), 4.22.6, 4.19.2, 4.19.3, 4.19.4, 4.19.5, 4.27.4, Figs. 31, 32.

iv. The toilet flush control is on the "closed" side of the toilet. Provide flush controls mounted on the "open" side of the toilet clear floor space; 44 inches or less above the finished floor; and requiring a maximum of 5 pounds of force to operate; or provide an automatic flush device. Standards §§ 4.1.3(11), 4.22.4, 4.16.5, 4.27.4.

v. The grab bars at the toilet are inaccessible because the distance of the farther end of the side grab bar to the rear wall is 46 inches, and the overall length of the rear grab bar is 30 inches. Provide a rear grab bar that is at least 36 inches in overall length, with the closer end no more than 6 inches from the side wall, and a side grab bar that is at least 42 inches in overall length, with the far end mounted at least 54 inches from the rear wall and the closer end 12 inches or less from the rear wall. Ensure that the grab bars are mounted 33 to 36 inches above the finished floor; with a diameter between 1¼ and 1½ inches; with 1½ inches between the grab bars and the wall; and at least 1½ inches between the grab bars and any object beside or below it and at least 18 inches between the grab bar and any object above it. Standards §§ 4.1.3(11), 4.22.4, 4.16.4, 4.26.2, Figs. 29, 39.

vi. The toilet paper dispenser is inaccessible because it is mounted at 48 inches above the finished floor, above the side grab bar. Provide a toilet paper dispenser that is mounted within reach, with its top at least 1½ inches under the side grab bar, and centered at least 19 inches above the finished floor. Standards §§ 4.1.3(11), 4.22.4, 4.16.6, Fig. 29(b).

vii. The toilet centerline is 15 inches from the side wall. Provide a toilet with the centerline at 18 inches from the near side wall. Standards §§ 4.1.3(11), 4.22.4, 4.16.2, Fig. 28.

h. Men's toilet room #1 only (on left side, facing toilet room entrances)

i. There is insufficient turning space within the toilet room. Provide an unobstructed turning space at least 60 inches in diameter or a T-shaped space complying with Fig. 3(b). Standards §§ 4.1.3(11), 4.22.3, 4.2.3, Fig. 3.

ii. The bottom edge of the lavatory apron is 27 ½ inches above the finished floor and the hot water and drain pipes are not covered or otherwise configured to protect against contact. Provide a lavatory with the top of its rim or counter 34 inches or less above the finished floor; the bottom edge of the apron at least 29 inches above the finished floor; knee and toe clearances that comply with Fig. 31; hot water and drain pipes covered or otherwise configured to protect against contact; clear floor space at least 30 inches wide and 48 inches deep centered on the lavatory; and a faucet that can be operated with 5 pounds of force or less and can be used with one hand and without tight grasping, pinching, or twisting of the wrist (lever-operated, push-type, and electronically controlled mechanisms are examples of acceptable designs). Standards §§ 4.1.3(11), 4.22.6, 4.19.2, 4.19.3, 4.19.4, 4.19.5, 4.27.4, Figs. 31, 32.

iii. The toilet flush control is on the "closed" side of the toilet. Provide flush controls mounted on the "open" side of the toilet clear floor space; 44 inches or less above the finished floor; and requiring a maximum of 5 pounds of force to operate; or provide an automatic flush device. Standards §§ 4.1.3(11), 4.22.4, 4.16.5, 4.27.4.

iv. The grab bars at the toilet are inaccessible because the distance of the farther end of the side grab bar to the rear wall is 46 inches, and the overall length of the rear grab bar is 30 inches. Provide a rear grab bar that is at least 36 inches in overall length, with the closer end no more than 6 inches from the side wall, and a side grab bar that is at least 42 inches in overall length, with the far end mounted at least 54 inches from the rear wall and the closer end 12 inches or less from the rear wall. Ensure that the grab bars are mounted 33 to 36 inches above the finished floor; with a diameter between 1¼ and 1½ inches; with 1½ inches between the grab bars and the wall; and at least 1½ inches between the grab bars and any object beside or below it and at least 18 inches between the grab bar and any object above it. Standards §§ 4.1.3(11), 4.22.4, 4.16.4, 4.26.2, Figs. 29, 39.

v. The toilet paper dispenser is inaccessible because it is mounted at 41 inches above the finished floor, above the side grab bar. Provide a toilet paper dispenser that is mounted within reach, with its top at least 1½ inches under the side grab bar, and centered at least 19 inches above the finished floor. Standards §§ 4.1.3(11), 4.22.4, 4.16.6, Fig. 29(b).

vi. The rear grab bar at the toilet is obstructed by the soap dispenser mounted above it. Provide a rear grab bar that has at least 1½ inches between the grab bar and any object beside or below it and at least 18 inches between the grab bar and any object above it. Standards §§ 4.1.3(11), 4.22.4, 4.16.4, 4.26.2, Fig. 39.

vii. The toilet centerline is 15 inches from the side wall. Provide a toilet with the centerline at 18 inches from the near side wall. Standards §§ 4.1.3(11), 4.22.4, 4.16.2, Fig. 28.

i. Men's toilet room #2 only (on right side, facing toilet room entrances)

i. The hot water and drain pipes are not covered or otherwise configured to protect against contact. Provide hot water and drain pipes that are insulated or otherwise configured to protect against contact. Standards §§ 4.1.3(11), 4.22.6,

ii. The grab bars at the toilet are inaccessible because the distance of the farther end of the side grab bar to the rear wall is 45 ½ inches, and the overall length of the rear grab bar is 30 inches. Provide a rear grab bar that is at least 36 inches in overall length, with the closer end no more than 6 inches from the side wall, and a side grab bar that is at least 42 inches in overall length, with the far end mounted at least 54 inches from the rear wall and the closer end 12 inches or less from the rear wall. Ensure that the grab bars are mounted 33 to 36 inches above the finished floor; with a diameter between 1¼ and 1½ inches; with 1½ inches between the grab bars and the wall; and at least 1½ inches between the grab bars and any object beside or below it and at least 18 inches between the grab bar and any object above it. Standards §§ 4.1.3(11), 4.22.4, 4.16.4, 4.26.2, Figs. 29, 39.

iii. The toilet paper dispenser is inaccessible because it is mounted at 47 inches above the finished floor, above the side grab bar. Provide a toilet paper dispenser that is mounted within reach, with its top at least 1½ inches under the side grab bar, and centered at least 19 inches above the finished floor. Standards §§ 4.1.3(11), 4.22.4, 4.16.6, Fig. 29(b).

iv. The toilet centerline is 13 ½ inches from the side wall. Provide a toilet with the centerline at 18 inches from the near side wall. Standards §§ 4.1.3(11), 4.22.4, 4.16.2, Fig. 28.

j. Lounge: The counter in the kitchen is mounted with its top at 40 inches above the finished floor. Provide a counter on an accessible route such that a portion of the counter is at least 36 inches wide and no more than 36 inches above the finished floor, or provide an auxiliary counter with a maximum height of 36 inches in close proximity to the main counter, or provide equivalent facilitation. Equivalent facilitation may be provided in the form of a folding shelf attached to the main counter, an auxiliary table nearby, a clip board made available to the public, or other means. Standards §§ 4.1.1(2), 7.2(2), 4.1.3(1), 4.3.

k. Kitchen

i. The lavatory in the kitchen next to the ice machine is inaccessible because the bottom edge is mounted at 27 ½ inches above the finished floor and the hot water pipes are not insulated or otherwise configured to protect against contact. Provide a lavatory with the top of its rim or counter 34 inches or less above the finished floor; the bottom edge of the apron at least 29 inches above the finished floor; and knee and toe clearances that comply with Fig. 31. Standards §§ 4.1.3(11), 4.22.6, 4.19.2, Fig. 31. Provide hot water and drain pipes that are insulated or otherwise configured to protect against contact. Standards §§ 4.1.3(11), 4.22.6, 4.19.4.

ii. The soap dispenser and paper towel dispenser at the kitchen lavatory next to the ice machine are inaccessible because the controls are mounted more than 48 inches above the finished floor above the sink and require a forward reach. Provide a soap dispenser and a paper towel dispenser such that the controls comply with Fig. 5 for a forward reach or with Fig. 6 for a side reach and such that it is accompanied by clear floor space of 30 by 48 inches that allows a forward or parallel approach, respectively, by a person using a wheelchair. Standards §§ 4.1.3(13), 4.27.2, 4.27.3, 4.2.4, 4.2.5, 4.2.6.

6. Within six months of the effective date of this Agreement, Pike County will complete the following modifications to the Shelby Valley Senior Citizen Center, located at 111 Douglas Parkway, Pikeville:

a. Parking: Although the parking lot has a total of 23 parking spaces, the spaces designated as reserved for people with disabilities do not have access aisles, and there is no van accessible space. On the shortest accessible route to the accessible entrance, provide 1 van accessible space designated as reserved for people with disabilities. The van accessible spaces must be a minimum of 96 inches wide and served by access aisles at least 96 inches wide. At all spaces designated as reserved for persons with disabilities, provide vertical signs with the International Symbol of Accessibility located such that they cannot be obstructed by parked vehicles. At van accessible spaces, provide an additional "Van-Accessible" sign located below the International Symbol of Accessibility. Ensure that all spaces and access aisles for persons with disabilities are flat and level, with slopes and cross-slopes not exceeding 1:50 in all directions, and that their surfaces are firm, stable, and slip-resistant. Standards §§ 4.1.2(5), 4.6, 4.30.7(1).

b. Route from Parking to Entrance: The base of the curb ramp is not level, firm, stable, and slip-resistant. Provide a curb ramp that is at least 36 inches wide, has a maximum slope of 1:12, is located so that it cannot be obstructed by parked vehicles, and has a stable, firm, and slip-resistant surface with a detectable warning extending the full width and depth of the ramp. If the curb ramp is located where pedestrians must walk across it, provide either flared sides (with a maximum slope of 1:10) or handrails or guardrails to protect against cross traffic. Standards §§ 4.1.2(1), 4.1.2(2), 4.3.8, 4.7, Fig. 12.

c. Main entry door: The main entry door is inaccessible because there is a running slope of 7.8% within the door's required maneuvering clearance. Provide a door so that the floor or ground area within the required clearances is level and clear, or provide an automatic opener. Standards §§ 4.1.3(7)(a), 4.13.6, Fig. 25.

d. Exterior doors to the left of the main entry door

i. The two exterior doors to the left of the main entry door, which are accessed by a front approach and which each have both a closer and a latch, are inaccessible because there is inadequate maneuvering space at the latch on the push side of each door. On the push side of the doors, provide maneuvering clearance at least 48 inches deep and provide a minimum of 12 inches of maneuvering clearance on the latch side of the door, or remove the closer or the latch. Standards §§ 4.1.3(7)(b), 4.13.6, Fig. 25(a).

ii. The two exterior doors to the left of the main entry door have knob hardware that requires tight grasping and twisting of the wrist to operate. Provide doors with hardware that is easy to grasp with one hand and that does not require tight grasping, pinching, or twisting of the wrist to operate. Lever-operated mechanisms, push-type mechanisms, and U-shaped handles are acceptable designs. Standards §§ 4.1.3(7)(b), 4.13.9.

e. Knob hardware: Throughout the facility, interior doors have knob hardware that requires tight grasping, pinching, or twisting of the wrist to operate. Provide doors with hardware that is easy to grasp with one hand and that does not require tight grasping, pinching, or twisting of the wrist to operate. Lever-operated mechanisms, push-type mechanisms, and U-shaped handles are acceptable designs. Standards §§ 4.1.3(7)(b), 4.13.9.

f. Coat rack at building entrance: No accessible coat rack has been provided. Provide a coat hook at a maximum height above the finished floor of 48 inches for a forward approach or 54 inches for a side approach and that is accompanied by clear floor space of 30 by 48 inches that allows a forward or parallel approach by a person using a wheelchair. Standards §§ 4.1.3(12)(a), 4.25.2, 4.25.3, 4.2.4, 4.2.5, 4.2.6.

g. Kitchen

i. The window counter is mounted with its top at 39 ½ inches above the finished floor. Provide a counter on an accessible route such that a portion of the counter is at least 36 inches wide and no more than 36 inches above the finished floor, or provide an auxiliary counter with a maximum height of 36 inches in close proximity to the main counter, or provide equivalent facilitation. Equivalent facilitation may be provided in the form of a folding shelf attached to the main counter, an auxiliary table nearby, a clip board made available to the public, or other means. Standards §§ 4.1.1(2), 7.2(2), 4.1.3(1), 4.3.

ii. The pressure required to open the kitchen door exceeds 5 pounds of force. Provide a door that requires no more than 5 pounds of force to open. Standards §§ 4.1.3(7)(b), 4.13.11(2)(b).

h. Drinking fountain (located between toilet rooms)

i. The water height of the lower water fountain is 2 inches. Provide at least one drinking fountain with a spout height no higher than 36 inches, measured from the finished floor or ground surface to the spout outlet; and a spout located at the front of the unit that directs the water flow in a trajectory that is nearly parallel to the front of the unit and is positioned so the flow of water is within 3 inches of the front edge of the fountain and at least 4 inches high. Ensure that fountain controls are operable with one hand, require 5 lbf or less to operate without tight grasping, pinching, or twisting of the wrist; and are front mounted or side mounted near the front edge. Additionally, provide a drinking fountain that is accessible to people who have difficulty bending or stooping. This can be accommodated by the use of a "hi-lo" fountain; by providing one fountain accessible to those who use wheelchairs and one fountain at a standard height convenient for those who have difficulty bending; by providing a fountain accessible to people who use wheelchairs and a cup dispenser; or by such other means as would achieve the required accessibility for each group of people. Standards §§ 4.1.3(10), 4.15, 4.27.4, Fig. 27.

ii. The drinking fountain provided protrudes more than 4 inches into the circulation path, and it is undetectable to a blind person or person with low vision who is using a cane. Provide a drinking fountain at this location such that its bottom leading edges measure no more than 27 inches above the finished floor or protrude no more than 4 inches into the walkway. Providing a cane detectable barrier is an acceptable solution. Standards §§ 4.1.2(3), 4.4.

i. Single user toilet rooms (both men's and women's)

i. The toilet rooms lack accessible signs. Provide toilet room signs with raised and Braille characters. At each location, the sign shall be mounted on the wall adjacent to the latch side of the door with the centerline of the sign at 60 inches above the finished floor and situated such that a person can approach within 3 inches of the sign without encountering an obstruction or standing within a door swing. Standards §§ 4.1.2(7)(d), 4.30.1, 4.30.4, 4.30.5, 4.30.6, 4.30.7.

ii. The toilet room doors, which are accessed through a front approach and which have both a closer and a latch, are inaccessible because they have only 4 inches of maneuvering clearance at the latch on the push side of the door. At each location, on the push side of the door, provide maneuvering clearance at least 48 inches deep and provide a minimum of 12 inches of maneuvering clearance on the latch side of the door, or remove the closer or the latch. Standards §§ 4.1.3(7)(b), 4.13.6, Fig. 25(a).

iii. Although mirrors have been provided in each toilet room, they are mounted with the bottom edge of the reflecting surfaces more than 40 inches above the finished floor. At each location, provide mirrors with the bottom edge of their reflecting surface no more than 40 inches above the finished floor. Standards §§ 4.1.3(11), 4.22.6, 4.19.6.

iv. The lavatories are inaccessible because the hot water pipes are not insulated or otherwise configured to protect against contact. At each location, provide hot water and drain pipes that are insulated or otherwise configured to protect against contact. Standards §§ 4.1.3(11), 4.22.6, 4.19.4.

v. The overall length of the rear grab bars is 30 inches. At each location, provide rear grab bars that are at least 36 inches in overall length, with the closer end no more than 6 inches from the side wall; mounted 33 to 36 inches above the finished floor; with a diameter between 1¼ and 1½ inches; with 1½ inches between the grab bar and the wall; and at least 1½ inches between the grab bar and any other object, such as a toilet seat cover dispenser. Standards §§ 4.1.3(11), 4.22.4, 4.16.4, 4.26.2, Fig. 29.

vi. At each toilet room, the side grab bar at the toilet is mounted with its far end 52 inches from the rear wall. At each location, provide a side grab bar that is at least 42 inches in overall length, with the far end mounted at least 54 inches from the rear wall and the closer end 12 inches or less from the rear wall. Standards §§ 4.1.3(11), 4.22.4, 4.16.4, Fig. 29(b).

j. Women's single user toilet room only:

i. The soap dispenser controls are mounted 53 inches above the finished floor over a 14 inch obstruction. Provide a soap dispenser such that the controls comply with Fig. 5 for a forward reach or with Fig. 6 for a side reach and such that it is accompanied by clear floor space of 30 by 48 inches that allows a forward or parallel approach, respectively, by a person using a wheelchair. Standards §§ 4.1.3(13), 4.27.2, 4.27.3, 4.2.4, 4.2.5, 4.2.6.

ii. The toilet flush control is on the closed side. Provide a flush control mounted on the "open" side of the toilet's clear floor space; 44 inches or less above the finished floor; and requiring a maximum of 5 pounds of force to operate; or provide an automatic flush device. Standards §§ 4.1.3(11), 4.22.4, 4.16.5, 4.27.4.

 

 

Project Civic Access | archive.ADA.gov Home Page