ATTACHMENT K (1): Program Access in Existing FacilitiesPlease Note: Paragraph 45 of the Agreement requires that within six months of the effective date of this Agreement, the County will provide signage as necessary to comply with 28 C.F.R. § 35.163(b), after having surveyed all facilities that are the subject of this Agreement for the purpose of identifying those that have multiple entrances not all of which are accessible. The technical requirements and, where appropriate, the scoping requirements of the Standards are used as a guide for determining whether a program or activity held in an existing facility is "readily accessible to and usable by" persons with disabilities and for determining what changes are necessary to make this program or activity accessible if it continues to be provided in the existing facility in question. See 28 C.F.R. §§ 35.150(b)(1), 35.151. The chart below lists the facilities surveyed by the Department, the access issues identified during the survey, and the actions required to correct the access issues. Required actions are listed using an alphanumeric code. The key to the alphanumeric codes is provided in Attachment M to this Agreement. In order to ensure that the programs, services, and activities housed in the County's facilities are accessible to persons with disabilities, when viewed in their entirety, the County will take the actions referenced by the alphanumeric code and described in detail in Attachment M to this Settlement Agreement within the time period specified below, which time period begins to run on the effective date of the Agreement. |
|||
Item # |
Access Issue |
Required Action |
Completion Date |
---|---|---|---|
1. |
Pennington County Courthouse Complex, County Courthouse, 315 St.. Joseph Street, Pennington County, South Dakota |
||
1.1. |
Parking: |
||
1.1.1. |
The designated accessible parking spaces are inaccessible because the vertical signs are mounted less than 60 inches high. |
P3 |
30 months |
1.1.2. |
The parking lot is inaccessible because it has no van accessible parking space signage. |
P5 |
30 months |
1.2. |
Lift at South Entrance:The lift is inaccessible. because the width is 30 inches and it has a slope of 15.3% at the entrance. |
LF2 |
30 months |
1.3. |
1st Floor- Register of Deeds (Room #104): |
||
1.3.1. |
The door is inaccessible because the knob hardware requires tight grasping, pinching,or twisting of the wrist to operate. |
D2 |
30 months |
1.3.2. |
The signage provided is inaccessible because it is mounted above the door and does not have raised and Braille characters. |
D15 |
30 months |
1.3.3. |
The work counter in room 104 is inaccessible because it is 42 inches high. |
C2 |
30 months |
1.4. |
1st Floor-Commissioner's Meeting Room/Courtroom M-3: |
||
1.4.1. |
The signage provided is inaccessible because it is mounted on the door and does not have raised and Braille characters. |
D15 |
30 months |
1.4.2. |
The door is inaccessible because the knob hardware requires tight grasping,pinching, or twisting of the wrist to operate. |
D2 |
30 months |
1.4.3. |
The Commission Room/Court Room is inaccessible because there is no assistive listening system provided. |
AA4 |
30 months |
1.4.4. |
The judge's bench is inaccessible because it can be accessed only by steps. |
AA8 |
30 months |
1.4.5. |
The jury box is inaccessible because it can be accessed only by steps. |
AA8 |
30 months |
1.4.6. |
The witness stand is inaccessible because it can be accessed only by steps. |
AA8 |
30 months |
1.5. |
1st Floor-Drinking Fountain by Courtroom #3: |
||
1.5.1. |
The drinking fountain is inaccessible because the flow of water is less than 4 inches high. |
DF5 |
30 months |
1.5.2. |
The drinking fountain is inaccessible because the higher fountain protrudes into the walkway and is not detectable to blind persons using a cane. |
AR7 |
30 months |
1.6. |
1st Floor Men's Toilet Room-by Courtroom #3: |
||
1.6.1. |
The door is inaccessible because the knob hardware requires tight grasping, pinching,or twisting of the wrist to operate. |
D2 |
30 months |
1.6.2. |
The lavatory is inaccessible because the water supply and drain pipes are not insulated or otherwise configured to protect against contact. |
LS2 |
30 months |
1.6.3. |
The urinal is inaccessible because there is insufficient clear floors pace provided. |
TR24 |
30 months |
1.6.4. |
The urinal is inaccessible because the rim is 18 inches high. |
TR8 |
30 months |
1.6.5. |
The toilet compartment is inaccessible because it is 125 inches long and 45inches wide. |
TR23 |
30 months |
1.6.6. |
The toilet is inaccessible because the top of the seat is 20 inches high. |
TR9 |
30 months |
1.6.7. |
The toilet is inaccessible because the center line is 20 1/2 inches from the side wall. |
TR7 |
30 months |
1.6.8. |
The toilet is inaccessible because the side grab bar is mounted with the far end 14 inches from the rear wall. |
TR17 |
30 months |
1.7. |
1st Floor Women's Toilet Room-by Courtroom #3: |
||
1.7.1. |
The door is inaccessible because the knob hardware requires tight grasping,pinching, or twisting of the wrist to operate. |
D2 |
30 months |
1.7.2. |
The lavatory is inaccessible because the water supply and drain pipes are not insulated or otherwise configured to protect against contact. |
LS2 |
30 months |
1.7.3. |
The sanitary napkin dispenser protrudes into the clear floor space and is not detectable to blind persons using a cane. |
AR7 |
30 months |
1.7.4. |
The sanitary napkin dispenser is inaccessible because the controls require twisting of the wrist to operate. |
CT2 |
30 months |
1.7.5. |
The toilet compartment is inaccessible because it is 125 inches long and 45inches wide. |
TR23 |
30 months |
1.7.6. |
The toilet is inaccessible because the top of the seat is 20 inches high. |
TR9 |
30 months |
1.7.7. |
The toilet is inaccessible because the center line is 20 1/2 inches from the side wall. |
TR7 |
30 months |
1.7.8. |
The coat hook is inaccessible because it is mounted more than 48 inches high. |
TR3 |
30 months |
1.7.9. |
The toilet is inaccessible because the side grab bar is mounted with the near end 14 inches from the rear wall. |
TR17 |
30 months |
1.7.10. |
The toilet compartment is inaccessible because the door is located on the front partition directly in front of the toilet. |
TR25 |
30 months |
1.8. |
1st Floor Auditor's Office Voter Registration Elections: This area is inaccessible because the counter protrudes into the walkway and is not detectable to blind persons using a cane. |
AR7 |
30 months |
1.9. |
1st Floor Courtroom 103: |
||
1.9.1. |
The door is inaccessible because the knob hardware requires tight grasping, pinching,or twisting of the wrist to operate. |
D2 |
30 months |
1.9.2. |
The jury box is inaccessible because the back row can be accessed only by steps. |
AA8 |
30 months |
1.9.3. |
The judge's bench is inaccessible because it can be accessed only by steps. |
AA8 |
30 months |
1.10. |
2nd Floor Courtroom M1: |
||
1.10.1. |
The door is inaccessible because the knob hardware requires tight grasping,pinching, or twisting of the wrist to operate. |
D2 |
30 months |
1.10.2. |
Thew it ness stand is inaccessible because it can be accessed only by steps. |
AA8 |
30 months |
1.10.3. |
The route from the court room to the jury box is inaccessible because it is only 30 1/2 inches wide. |
AR3 |
30 months |
1.10.4. |
The jury box is inaccessible because it can be accessed only by steps. |
AA8 |
30 months |
1.10.5. |
The judge's bench is inaccessible because it can be accessed only by steps. |
AA8 |
30 months |
1.10.6. |
The clerk's station is inaccessible because it can be accessed only by steps. |
AA8 |
30 months |
1.11. |
2nd Floor-Drinking Fountain by Courtroom M1:The drinking fountain is inaccessible because the higher fountain protrudes into the walkway and is not detectable to blind persons using a cane. |
AR7 |
30 months |
1.12. |
2nd AED Defibrillator by Courtroom M1:This area is inaccessible because the counter protrudes into the walkway and is not detectable to blind persons using a cane. |
AR7 |
30 months |
1.13. |
2nd Floor Courtroom M2: |
||
1.13.1. |
The door is inaccessible because the knob hardware requires tight grasping, pinching,or twisting of the wrist to operate. |
D2 |
30 months |
1.13.2. |
Thew it ness stand is inaccessible because it can be accessed only by steps. |
AA8 |
30 months |
1.13.3. |
The jury box is inaccessible because the back row can be accessed only by steps. |
AA8 |
30 months |
1.13.4. |
The route from the court room to the spectator seating area is inaccessible because it is not 36 inches wide. |
AR3 |
30 months |
1.13.5. |
The judge's bench is inaccessible because it can be accessed only by steps. |
AA8 |
30 months |
1.13.6. |
The clerk's station is inaccessible because it can be accessed only by steps. |
AA8 |
30 months |
1.14. |
2nd Floor Jury Room 2B Women's Toilet Room: |
||
1.14.1. |
The door is inaccessible because the knob hardware requires tight grasping,pinching, or twisting of the wrist to operate. |
D2 |
30 months |
1.14.2. |
The pull side of the door is inaccessible because it has only 6 inches of clears pace on the latch side. |
D5 |
30 months |
1.14.3. |
The facility is inaccessible because, although the facility contains a fire alarm system, there are no visible alarm provided in toilet room. |
AL1 |
30 months |
1.14.4. |
The toilet room is inaccessible because there is insufficient turning space provided within the room. |
TR21 |
30 months |
1.14.5. |
The lavatory is inaccessible because the water supply and drain pipes are not insulated or otherwise configured to protect against contact. |
LS2 |
30 months |
1.14.6. |
The lavatory is inaccessible because the clear floor space is not adequate. |
LS5 |
30 months |
1.14.7. |
The sanitary napkin dispenser protrudes into the clear floor space and is not detectable to blind persons using a cane. |
AR7 |
30 months |
1.14.8. |
The sanitary napkin dispenser is inaccessible because the controls require twisting of the wrist to operate. |
CT2 |
30 months |
1.14.9. |
The toilet compartment is inaccessible because it is 77 inches long and 43 1/2 inches wide. |
TR23 |
30 months |
1.14.10. |
The toilet is inaccessible because the top of the seat is 20 inches high. |
TR9 |
30 months |
1.14.11. |
The toilet is inaccessible because the center line is 18 1/2 inches from the sidewall. |
TR7 |
30 months |
1.14.12. |
The coat hook is inaccessible because it is mounted 64 inches high. |
TR3 |
30 months |
1.15. |
2nd Floor Jury Room Men's Toilet Room: |
||
1.15.1. |
The door is inaccessible because the knob hardware requires tight grasping,pinching, or twisting of the wrist to operate. |
D2 |
30 months |
1.15.2. |
The pull side of the door is inaccessible because clear space on the latch side is inadequate. |
D5 |
30 months |
1.15.3. |
The facility is inaccessible because, although the facility contains a fire alarm system, there are no visible alarm provided in toilet room. |
AL1 |
30 months |
1.15.4. |
The toilet room is inaccessible because there is insufficient turning space provided within the room. |
TR21 |
30 months |
1.15.5. |
The lavatory is inaccessible because the water supply and drain pipes are not insulated or otherwise configured to protect against contact. |
LS2 |
30 months |
1.15.6. |
The lavatory is inaccessible because the clear floor space is not adequate. |
LS5 |
30 months |
1.15.7. |
The urinal is inaccessible because the rim is 20 inches high. |
TR8 |
30 months |
1.15.8. |
The coat hook is inaccessible because it is mounted 65 1/2 inches high. |
TR3 |
30 months |
1.16. |
2nd Floor Court Services Probation: |
||
1.16.1. |
The sign age provided is inaccessible because it does not have raised and Braille characters. |
D15 |
30 months |
1.16.2. |
The door is inaccessible because the knob hardware requires tight grasping,pinching, or twisting of the wrist to operate. |
D2 |
30 months |
1.16.3. |
The counter is inaccessible because it is 42 inches high. |
C1 |
30 months |
1.16.4. |
The route from the counter area to room # 7 is inaccessible because it is less than 36 inches wide. |
AR3 |
30 months |
1.17. |
2nd Floor Women's Toilet Room: |
||
1.17.1. |
The sign age provided is inaccessible because it does not have raised and Braille characters. |
D15 |
30 months |
1.17.2. |
The toilet room is inaccessible because there is insufficient turning space provided within the room. |
TR21 |
30 months |
1.17.3. |
The lavatory is inaccessible because the clear floor space is not adequate. |
LS5 |
30 months |
1.17.4. |
The urinal is inaccessible because the rim is 18 inches high. |
TR8 |
30 months |
1.17.5. |
The coat hook is inaccessible because it is mounted 61 inches high. |
TR3 |
30 months |
1.17.6. |
The toilet is inaccessible because the grab bars are mounted 2 1/2 inches from thew all on which they are mounted. |
TR20 |
30 months |
1.17.7. |
The toilet is inaccessible because the side grab bar is mounted with the far end50 inches from the rear wall. |
TR17 |
30 months |
1.17.8. |
The toilet is inaccessible because the side grab bar is obstructed by the toilet paper dispenser. |
TR15 |
30 months |
1.17.9. |
The toilet is inaccessible because the rear grab bar is 30 inches long. |
TR14 |
30 months |
1.17.10. |
The toilet compartment is inaccessible because the door is located on the front partition directly in front of the toilet. |
TR25 |
30 months |
1.18. |
2nd Floor Men's Toilet Room: |
||
1.18.1. |
The sign age provided is inaccessible because it does not have raised and Braille characters. |
D15 |
30 months |
1.18.2. |
The toilet room is inaccessible because there is insufficient turning space provided within the room. |
TR21 |
30 months |
1.18.3. |
The coat hook is inaccessible because it is mounted 61 inches high. |
TR3 |
30 months |
1.18.4. |
The toilet is inaccessible because the grab bars are mounted 2 1/2 inches from thew all on which they are mounted. |
TR20 |
30 months |
1.18.5. |
The toilet is inaccessible because the side grab bar is mounted with the far end50 inches from the rear wall. |
TR17 |
30 months |
1.18.6. |
The toilet compartment is inaccessible because the door is located on the front partition directly in front of the toilet. |
TR25 |
30 months |
1.19. |
3rd Floor Men's Toilet Room: |
||
1.19.1. |
The sign age provided is inaccessible because it is not mounted are the latch side of the door. |
D15 |
30 months |
1.19.2. |
The door is inaccessible because the knob hardware requires tight grasping,pinching, or twisting of the wrist to operate. |
D2 |
30 months |
1.19.3. |
The door is inaccessible because it requires more than 5 pounds of force to open. |
D3 |
30 months |
1.19.4. |
The lavatory is inaccessible because the water supply and drain pipes are not insulated or otherwise configured to protect against contact. |
LS2 |
30 months |
1.19.5. |
The urinal is inaccessible because the rim is 19 inches high. |
TR8 |
30 months |
1.19.6. |
The toilet compartment is inaccessible because it is 104 inches long and 43inches wide. |
TR23 |
30 months |
1.19.7. |
The toilet is inaccessible because the top of the seat is 20 inches high. |
TR9 |
30 months |
1.19.8. |
The toilet is inaccessible because the center line is 20 1/2 inches from the sidewall. |
TR7 |
30 months |
1.19.9. |
The coat hook is inaccessible because it is mounted 64 1/2 inches high. |
TR3 |
30 months |
1.19.10. |
The toilet is inaccessible because the rear grab bar is obstructed by the flush value. |
TR15 |
30 months |
1.19.11. |
The toilet is inaccessible because the rear grab bar is mounted with the far endless than 24 inches from the center of the toilet. |
TR14 |
30 months |
1.19.12. |
The toilet compartment is inaccessible because it is not 59 inches long and 60inches wide. |
TR23 |
30 months |
1.20. |
3rd Floor Women's Toilet Room: |
||
1.20.1. |
The door is inaccessible because the knob hardware requires tight grasping,pinching, or twisting of the wrist to operate. |
D2 |
30 months |
1.20.2. |
The door is inaccessible because it requires more than 5 pounds of force to open. |
D3 |
30 months |
1.20.3. |
The lavatory is inaccessible because the water supply and drain pipes are not insulated or otherwise configured to protect against contact. |
LS2 |
30 months |
1.20.4. |
The sanitary napkin dispenser protrudes into the clear floor space and is not detectable to blind persons using a cane. |
AR7 |
30 months |
1.20.5. |
The sanitary napkin dispenser is inaccessible because the controls require twisting of the wrist to operate. |
CT2 |
30 months |
1.20.6. |
The toilet compartment is inaccessible because it is 104 inches long and 43inches wide. |
TR23 |
30 months |
1.20.7. |
The toilet is inaccessible because the top of the seat is 20 inches high. |
TR9 |
30 months |
1.20.8. |
The toilet is inaccessible because the center line is 20 1/2 inches from the sidewall. |
TR7 |
30 months |
1.20.9. |
The toilet is inaccessible because the flush control is on the closed side. |
TR4 |
30 months |
1.20.10. |
The coat hook is inaccessible because it is mounted 64 1/2 inches high. |
TR3 |
30 months |
1.20.11. |
The toilet is inaccessible because the rear grab bar is obstructed by the flush value. |
TR15 |
30 months |
1.20.12. |
The toilet is inaccessible because the rear grab bar is mounted with the far endless than 24 inches from the center of the toilet. |
TR14 |
30 months |
1.21. |
3rd Floor Courtroom C4: |
||
1.21.1. |
The door is inaccessible because the knob hardware requires tight grasping,pinching, or twisting of the wrist to operate. |
D2 |
30 months |
1.21.2. |
Thew it ness stand is inaccessible because it can be accessed only by steps. |
AA8 |
30 months |
1.21.3. |
The jury box is inaccessible because it can be accessed only by steps. |
AA8 |
30 months |
1.21.4. |
The judge's bench is inaccessible because it can be accessed only by steps. |
AA8 |
30 months |
1.22. |
3rd Floor Courtroom C5: |
||
1.22.1. |
The door is inaccessible because the knob hardware requires tight grasping,pinching, or twisting of the wrist to operate. |
D2 |
30 months |
1.22.2. |
Thew it ness stand is inaccessible because it can be accessed only by steps. |
AA8 |
30 months |
1.22.3. |
The jury box is inaccessible because it can be accessed only by steps. |
AA8 |
30 months |
1.22.4. |
The clerk's station is inaccessible because it can be accessed only by steps. |
AA8 |
30 months |
1.22.5. |
The judge's bench is inaccessible because it can be accessed only by steps. |
AA8 |
30 months |
1.23. |
Elevator: |
||
1.23.1. |
The elevator is inaccessible because the car position indicators do not emit an audible signal as the car passes or stops at a floor. |
E5 |
30 months |
1.23.2. |
The elevator is inaccessible because the emergency system does not provide both audible and visible signals. |
E7 |
|
1.24. |
3rd Floor Courtroom C3: |
||
1.24.1. |
The door is inaccessible because the knob hardware requires tight grasping,pinching, or twisting of the wrist to operate. |
D2 |
30 months |
1.24.2. |
The witness stand is inaccessible because it can be accessed only by steps. |
AA8 |
30 months |
1.24.3. |
The jury box is inaccessible because it can be accessed only by steps. |
AA8 |
30 months |
1.24.4. |
The judge's bench is inaccessible because it can be accessed only by steps. |
AA8 |
30 months |
1.25. |
3rd Floor Courtroom C6: |
||
1.25.1. |
The door is inaccessible because the knob hardware requires tight grasping,pinching, or twisting of the wrist to operate. |
D2 |
30 months |
1.25.2. |
Thew it ness stand is inaccessible because it can be accessed only by steps. |
AA8 |
30 months |
1.25.3. |
The jury box is inaccessible because it can be accessed only by steps. |
AA8 |
30 months |
1.25.4. |
The judge's bench is inaccessible because it can be accessed only by steps. |
AA8 |
30 months |
1.26. |
3rd Floor Jury Rooms 3B and 3C: |
||
1.26.1. |
The door is inaccessible because the knob hardware requires tight grasping,pinching, or twisting of the wrist to operate. |
D2 |
30 months |
1.26.2. |
This area is inaccessible because the coat rack protrudes into the walkway and is not detectable to blind persons using a cane. |
AR7 |
30 months |
1.27. |
3rd Floor Jury Rooms 3B and 3C Men's Toilet Room: |
||
1.27.1. |
The door is inaccessible because the knob hardware requires tight grasping,pinching, or twisting of the wrist to operate. |
D2 |
30 months |
1.27.2. |
The lavatory is inaccessible because the water supply and drain pipes are not insulated or otherwise configured to protect against contact. |
LS2 |
30 months |
1.27.3. |
The toilet is inaccessible because the top of the seat is 20 1/2 inches high. |
TR9 |
30 months |
1.27.4. |
The coat hook is inaccessible because it is mounted 64 inches high. |
TR3 |
30 months |
1.27.5. |
The toilet is inaccessible because the rear grab bar is obstructed by the flush value. |
TR15 |
30 months |
1.28. |
3rd Floor Jury Rooms 3B and 3C Women's Toilet Room: |
||
1.28.1. |
The door is inaccessible because the knob hardware requires tight grasping,pinching, or twisting of the wrist to operate. |
D2 |
30 months |
1.28.2. |
The door is inaccessible because it requires more than 5 pounds of force to open. |
D3 |
|
1.28.3. |
The lavatory is inaccessible because the water supply and drain pipes are not insulated or otherwise configured to protect against contact. |
LS2 |
30 months |
1.28.4. |
The toilet is inaccessible because the top of the seat is 20 inches high. |
TR9 |
30 months |
1.28.5. |
The toilet is inaccessible because the center line is 21 1/2 inches from the sidewall. |
TR7 |
30 months |
1.29. |
3rd Floor Drinking Fountain Outside Jury Rooms 3B and 3C: |
||
1.29.1. |
The drinking fountain is inaccessible because it provides only 23 1/2 inches of knee clearance. |
DF4 |
30 months |
1.29.2. |
There is no drinking fountain provided for people who have difficulty bending or stooping. |
DF3 |
30 months |
1.30. |
3rd Floor Administrative Offices: |
||
1.30.1. |
The sign age provided is inaccessible because it is not mounted on the latch side of the door and does not have raised and Braille characters. |
D15 |
30 months |
1.30.2. |
The counter is inaccessible because it is greater than 36 inches high. |
C1 |
30 months |
1.30.3. |
The pull side of the door is inaccessible because the clear space on the latch side is inadequate. |
D5 |
30 months |
1.31. |
3rd Floor Courtroom C1: |
||
1.31.1. |
Thew it ness stand is inaccessible because it can be accessed only by steps. |
AA8 |
30 months |
1.31.2. |
The jury box is inaccessible because it can be accessed only by steps. |
AA8 |
30 months |
1.31.3. |
The judge's bench is inaccessible because it can be accessed only by steps. |
AA8 |
30 months |
1.31.4. |
The clerk's station is inaccessible because it can be accessed only by steps. |
AA8 |
30 months |
1.31.5. |
The route from the court room pass the bar to the area in front of the judge's bench is only 26 1/2 inches wide. |
AR3 |
30 months |
1.32. |
3rd Floor Courtroom C2: |
||
1.32.1. |
Thew it ness stand is inaccessible because it can be accessed only by steps. |
AA8 |
30 months |
1.32.2. |
The jury box is inaccessible because it can be accessed only by steps. |
AA8 |
30 months |
1.32.3. |
The judge's bench is inaccessible because it can be accessed only by steps. |
AA8 |
30 months |
1.32.4. |
The clerk's station is inaccessible because it can be accessed only by steps. |
AA8 |
30 months |
1.33. |
3rd Floor Jury Room 313 and 312: |
||
1.33.1. |
The sign age provided is inaccessible because it is mounted above the doors and does not have raised and Braille characters. |
D15 |
30 months |
1.33.2. |
The door is inaccessible because the knob hardware requires tight grasping,pinching, or twisting of the wrist to operate. |
D2 |
30 months |
1.33.3. |
This area is inaccessible because the coat rack protrudes into the walkway and is not detectable to blind persons using a cane. |
AR7 |
30 months |
1.33.4. |
The drinking fountain in room 312 contains a number of inaccessible elements and is not accessible to people with disabilities. |
DF1 |
30 months |
1.34. |
3rd Floor Jury Room 313 and 312 Women's Toilet Room:The toilet room contains a number of inaccessible elements and is not accessible to people with disabilities. |
TR1 |
30 months |
1.35. |
3rd Floor Jury Room 313 and 312 Men's Toilet Room:The toilet room contains a number of inaccessible elements and is not accessible to people with disabilities. |
TR1 |
30 months |
1.36. |
3rd Floor Women's Toilet Room:The toilet room contains a number of inaccessible elements and is not accessible to people with disabilities. |
TR1 |
30 months |
1.37. |
County Courthouse Original Building, 2nd Floor Clerk of Court Civil Division: |
||
1.37.1. |
The door is inaccessible because the knob hardware requires tight grasping,pinching, or twisting of the wrist to operate. |
D2 |
30 months |
1.37.2. |
The counter is inaccessible because it is 42 inches high. |
C1 |
30 months |
1.38. |
County Courthouse Original Building, 2nd Floor Jury Juvenile TPO: The counter is inaccessible because it is 42 inches high. |
C1 |
30 months |
1.39. |
County Courthouse Original Building, 2nd Floor Treasurer's Office:The high/low counter combination is inaccessible. |
C1 |
30 months |
1.40. |
County Courthouse Original Building, 2nd Floor Women's Toilet Room:The signage provided is inaccessible. because it is not mounted on the latch side of the door and does not have raised and Braille characters. |
D15 |
30 months |
1.41. |
County Courthouse Original Building, 2nd Floor Men's Toilet Room:The signage provided is inaccessible because it is not mounted on the latch side of the door and does not have raised and Braille characters. |
D15 |
30 months |
1.42. |
County Courthouse Original Building, 1st Floor Courtroom C-7: |
||
1.42.1. |
The sign age provided is inaccessible because it is not mounted on the latch side of the door and does not have raised and Braille characters. |
D15 |
30 months |
1.42.2. |
The jury box is inaccessible because it can be accessed only by steps. |
AA8 |
30 months |
1.43. |
County Courthouse Original Building, 1st Floor Women's Toilet Room Outside Courtroom C-7:The toilet room contains a number of inaccessible elements and is not accessible to people with disabilities. |
TR1 |
30 months |
1.44. |
County Courthouse Original Building, 1st Floor Men's Toilet Room Outside Courtroom C-7:The toilet room contains a number of inaccessible elements and is not accessible to people with disabilities. |
TR1 |
30 months |
1.45. |
County Courthouse Original Building, 1st Floor Planning and Zoning Office: The signage provided is inaccessible. because it is mounted above the counter and does not have raised and Braille characters. |
D15 |
30 months |
1.46. |
County Courthouse Original Building, Elevator:No accessible elevator is provided. |
E1 |
30 months |
1.47. |
County Courthouse Original Building, Basement Women's Toilet Room:The toilet room contains a number of inaccessible elements and is not accessible to people with disabilities. |
TR1 |
30 months |
1.48. |
County Courthouse Original Building, Basement Men's Toilet Room:The toilet room contains a number of inaccessible elements and is not accessible to people with disabilities. |
TR1 |
30 months |
1.49. |
County Courthouse Original Building, Basement, Route to Public Defender Office: |
||
1.49.1. |
The first ramp on the route to the Public Defender Office is inaccessible because it has a slope of up to 20.2%. |
R4 |
30 months |
1.49.2. |
The ramp is inaccessible because the handrails do not have 12 inch long extensions at the ends. |
R2 |
30 months |
1.49.3. |
The second ramp on the route to the Public Defender Office is inaccessible because it has a slope of up to 18.2%. |
||
1.49.4. |
The ramp is inaccessible because handrails are not provided on both sides and the handrail provided does not have 12 inch long extensions at the ends. |
R2 |
30 months |
2. |
Pennington County Jail, 307 St.. Joseph Street, Pennington County, South Dakota |
||
2.1. |
Booking Room:The table is inaccessible because it provides only 24 1/2 inches of clear knee space. |
DW1 |
30 months |
2.2. |
Unisex Rest room near Booking Area: |
||
2.2.1. |
The sign age provided is inaccessible because it is mounted on the door and does not have raised and Braille characters. |
D15 |
30 months |
2.2.2. |
The door is inaccessible because the knob hardware requires tight grasping,pinching, or twisting of the wrist to operate. |
D2 |
30 months |
2.2.3. |
No accessible mirror has been provided. |
TR5 |
30 months |
2.2.4. |
The lavatory is inaccessible because the water supply and drain pipes are not insulated or otherwise configured to protect against contact. |
LS2 |
30 months |
2.2.5. |
The toilet is inaccessible because the flush control is on the closed side. |
TR4 |
30 months |
2.2.6. |
The toilet paper dispenser is inaccessible because it is mounted 57 inches above the floor. |
TR6 |
30 months |
2.2.7. |
The toilet is inaccessible because the rear grab bar is 24 inches long. |
TR14 |
30 months |
2.3. |
Dressing Room: |
||
2.3.1. |
The dressing room contains a number of inaccessible elements and is not accessible to people with disabilities. |
LR1 |
30 months |
2.3.2. |
The shower is inaccessible because it has a 9 inch high curb at the entrance. |
B3 |
30 months |
2.4. |
Unisex Restroom near Interview Room: |
||
2.4.1. |
The sign age provided is inaccessible because it is mounted on the door and does not have raised and Braille characters. |
D15 |
30 months |
2.4.2. |
The lavatory is inaccessible because the water supply and drain pipes are not insulated or otherwise configured to protect against contact. |
LS2 |
30 months |
2.4.3. |
The toilet is inaccessible because the rear grab bar is 24 inches long. |
TR14 |
30 months |
2.5. |
1st Floor Typical Holding Cell: |
||
2.5.1. |
The door is inaccessible because it has an opening width of 27 inches. |
D14 |
30 months |
2.5.2. |
The toilet is inaccessible because there are no grab bars provided. |
TR18 |
30 months |
2.6. |
1st Floor Holding Cell #12:The toilet is inaccessible because there are no grab bars provided. |
TR18 |
30 months |
2.7. |
1st Floor Room #1 (Used for Programs): |
||
2.7.1. |
The sign age provided is inaccessible because it is mounted on the door and does not have raised and Braille characters. |
D15 |
30 months |
2.7.2. |
The door is inaccessible because the knob hardware requires tight grasping,pinching, or twisting of the wrist to operate. |
D2 |
30 months |
2.8. |
1st Floor Room #2 (Used as a Courtroom): |
||
2.8.1. |
The sign age provided is inaccessible because it is mounted on the door and does not have raised and Braille characters. |
D15 |
30 months |
2.8.2. |
The door is inaccessible because the knob hardware requires tight grasping,pinching, or twisting of the wrist to operate. |
D2 |
30 months |
2.9. |
1st Floor Library (in the process of being phased out): |
||
2.9.1. |
The sign age provided is inaccessible because it is mounted on the door and does not have raised and Braille characters. |
D15 |
30 months |
2.9.2. |
The computer desk is inaccessible because it provides only 24 1/2 inches of clear knee space. |
DW1 |
30 months |
2.9.3. |
The routes between some book stacks are inaccessible because it is only 21 inches wide. |
AR3 |
30 months |
2.10. |
2nd Floor Cell Block 1 & 2 (Female Trustees): |
||
2.10.1. |
The cell door is inaccessible because it has an opening width of less than 32inches. |
D14 |
30 months |
2.10.2. |
The toilet is inaccessible because there are no grab bars provided. |
TR18 |
30 months |
2.10.3. |
There is no accessible shower provided. |
B2 |
30 months |
2.11. |
2nd Floor Cell Block 1.5 (Work Release Females): |
||
2.11.1. |
The cell door is inaccessible because it has an opening width of less than 32inches. |
D14 |
30 months |
2.11.2. |
The toilet is inaccessible because there are no grab bars provided. |
TR18 |
30 months |
2.11.3. |
There is no accessible shower provided. |
B2 |
30 months |
2.12. |
2nd Floor Cell Blocks 3, 4 & 5 (Men Detainees): |
||
2.12.1. |
The cell door is inaccessible because it has an opening width of less than 32 inches. |
D14 |
30 months |
2.12.2. |
The toilet is inaccessible because there are no grab bars provided. |
TR18 |
30 months |
2.12.3. |
There is no accessible shower provided. |
B2 |
30 months |
2.12.4. |
The route from the lower tier to the upper tier is inaccessible because it requires traversing stairs. |
AR2 |
30 months |
2.13. |
2nd Floor Drinking Fountain (Located Outside Cell Block 5): |
||
2.13.1. |
The drinking fountain is inaccessible because the spout is 40 inches high. |
DF3 |
30 months |
2.13.2. |
This area is inaccessible because the drinking fountain protrudes into the walkway and is not detectable to blind persons using a cane. |
AR7 |
30 months |
2.14. |
2nd Cell Block #7: |
||
2.14.1. |
The toilet is inaccessible because there are no grab bars provided. |
TR18 |
30 months |
2.14.2. |
There is no accessible shower provided. |
B2 |
30 months |
2.14.3. |
The dining tables are inaccessible because they provide no area for wheelchair seating. |
DW1 |
30 months |
2.15. |
3nd Floor Cell Block 1 & 2 (The 3rd floor mirrors the 2ndfloor configuration): |
||
2.15.1. |
The cell door is inaccessible because it has an opening width of less than 32inches. |
D14 |
30 months |
2.15.2. |
The toilet is inaccessible because there are no grab bars provided. |
TR18 |
30 months |
2.15.3. |
There is no accessible shower provided. |
B2 |
30 months |
2.16. |
3rd FloorCell Block 1.5: |
||
2.16.1. |
The cell door is inaccessible because it has an opening width of less than 32inches. |
D14 |
30 months |
2.16.2. |
The toilet is inaccessible because there are no grab bars provided. |
TR18 |
30 months |
2.16.3. |
There is no accessible shower provided. |
B2 |
30 months |
2.17. |
3rd Floor Cell Blocks 3, 4 & 5: |
||
2.17.1. |
The cell door is inaccessible because it has an opening width of less than 32inches. |
D14 |
30 months |
2.17.2. |
The toilet is inaccessible because there are no grab bars provided. |
TR18 |
30 months |
2.17.3. |
There is no accessible shower provided. |
B2 |
30 months |
2.17.4. |
The route from the lower tier to the upper tier is inaccessible because it requires traversing stairs. |
AR2 |
30 months |
2.18. |
3rd Floor Drinking Fountain (Located Outside Cell Block 5): |
||
2.18.1. |
The drinking fountain is inaccessible because the spout is 40 inches high. |
DF3 |
30 months |
2.19. |
This area is inaccessible because the drinking fountain protrudes into the walkway and is not detectable to blind persons using a cane. |
AR7 |
30 months |
2.19.1. |
3rd Cell Block #7: |
||
2.19.2. |
The toilet is inaccessible because there are no grab bars provided. |
TR18 |
30 months |
2.19.3. |
There is no accessible shower provided. |
B2 |
30 months |
2.19.4. |
The dining tables are inaccessible because they provide no area for wheelchair seating. |
DW1 |
30 months |
2.20. |
4th Floor Cell Blocks 9 & 10: |
||
2.20.1. |
The toilet is inaccessible because there are no grab bars provided. |
TR18 |
30 months |
2.20.2. |
There is no accessible shower provided. |
B2 |
30 months |
2.20.3. |
The route from the lower tier to the upper tier is inaccessible because it requires traversing stairs. |
AR2 |
30 months |
3. |
Pennington County Jail Annex, 240 Kansas Street, Pennington County, South Dakota |
||
3.1. |
Medical Exam Room #1: |
||
3.1.1. |
No accessible mirror has been provided. |
TR5 |
30 months |
3.1.2. |
The toilet is inaccessible because the top of the seat is 16 inches high. |
TR9 |
30 months |
4. |
Pennington County Public Safety Building, 300 Kansas Street, Pennington County, South Dakota |
||
4.1. |
Ramp: The ramp is inaccessible because it does not have edge protection on the inside of the ramp. |
R3 |
30 months |
4.2. |
1st Floor Women's Toilet Room: |
||
4.2.1. |
The toilet compartment is inaccessible because it is 58 inches long and 47 inches wide. |
TR23 |
30 months |
4.2.2. |
The toilet is inaccessible because the top of the seat is 21 inches high. |
TR9 |
30 months |
4.2.3. |
The coat hook is inaccessible because it is mounted 62 inches high. |
TR3 |
30 months |
4.2.4. |
The toilet is inaccessible because the rear grab bar is not 36 inches long. |
TR14 |
|
4.3. |
1st Floor Men's Toilet Room: |
||
4.3.1. |
The toilet is inaccessible because the top of the seat is 21 inches high. |
TR9 |
30 months |
4.3.2. |
The coat hook is inaccessible because it is mounted 64 inches high. |
TR3 |
30 months |
4.3.3. |
The toilet is inaccessible because there is no rear grab bar provided. |
TR13 |
30 months |
4.4. |
Elevator: |
||
4.4.1. |
The elevator is inaccessible because the car position indicators do not emit an audible signal as the car passes or stops at a floor. |
E5 |
30 months |
4.4.2. |
The elevator is inaccessible because the emergency system does not provide both audible and visible signals. |
E7 |
|
4.5. |
3rd Floor Men's Toilet Room: |
||
4.5.1. |
The coat hook is inaccessible because it is mounted 62 inches high. |
TR3 |
30 months |
4.5.2. |
The toilet is inaccessible because the side grab bar is obstructed by the toilet paper dispenser. |
TR15 |
30 months |
4.6. |
3rd Floor Women's Toilet Room: |
||
4.6.1. |
The coat hook is inaccessible because it is mounted 62 inches high. |
TR3 |
30 months |
4.6.2. |
The toilet is inaccessible because the side grab bar is obstructed by the toilet paper dispenser. |
TR15 |
30 months |
4.7. |
4th Floor Men's Toilet Room (near room 401): |
||
4.7.1. |
The sign age provided is inaccessible because it is not mounted on the latch side of the door. |
D15 |
30 months |
4.7.2. |
The toilet is inaccessible because the side grab bar is obstructed by the toilet paper dispenser. |
TR15 |
30 months |
4.8. |
4th Floor Women's Toilet Room (near room 401): |
||
4.8.1. |
The sign age provided is inaccessible because it is not mounted on the latch side of the door. |
D15 |
30 months |
4.8.2. |
The coat hook is inaccessible because it is mounted 64 inches high. |
TR3 |
30 months |
4.8.3. |
The toilet is inaccessible because the side grab bar is obstructed by the toilet paper dispenser. |
TR15 |
30 months |
4.9. |
4th Floor Men's Toilet Room |
||
4.9.1. |
The sign age provided is inaccessible because it is not mounted on the latch side of the door. |
D15 |
30 months |
4.9.2. |
The coat hook is inaccessible because it is mounted 64 inches high. |
TR3 |
30 months |
4.9.3. |
The toilet is inaccessible because the side grab bar is obstructed by the toilet paper dispenser. |
TR15 |
30 months |
4.10. |
4th Floor Women's Toilet Room |
||
4.10.1. |
The toilet is inaccessible because the side grab bar is obstructed by the toilet paper dispenser. |
TR15 |
30 months |
4.10.2. |
The coat hook is inaccessible because it is mounted 64 inches high. |
TR3 |
30 months |
4.10.3. |
The toilet is inaccessible because the side grab bar is obstructed by the toilet paper dispenser. |
TR15 |
30 months |
4.10.4. |
4th Floor Route to Room 4026:This area is inaccessible because the coat rack protrudes into the walkway and is not detectable to blind persons using a cane. |
AR7 |
30 months |