ATTACHMENT I: Modifications to Newly Constructed Facilities

Please Note: Paragraph 55 of the Settlement Agreement requires that within three months of the effective date of this Agreement, the County provide signage as necessary to comply with 28 C.F.R. § 35.163(b), after having surveyed all facilities that are the subject of this Agreement for the purpose of identifying those that have multiple entrances not all of which are accessible.

The chart below lists the facilities surveyed by the Department, the access issues identified during the survey, and the actions required to correct the access issues. Required actions are listed using an alphanumeric code. The key to the alphanumeric codes is provided in Attachment M to this Agreement.

In order to ensure that the following spaces and elements in County facilities, for which construction was commenced after January 26, 1992, are readily accessible to and usable by persons with disabilities, the County will take the actions referenced by the alphanumeric code and described in detail in Attachment M to this Settlement Agreement within the time periods specified below, which time periods will begin to run on the effective date of this Agreement.

Item #

Access Issue

Required Action

Completion Date

1.

Stone Plaza, located at 7012 Highway 11 North, Carriere

   

1.1.

Parking:

   

1.1.a.

The parking lot, with a total of 48 parking spaces, is inaccessible because it has no van accessible spaces. This lot requires 1 van accessible space and 1 standard accessible space.

P3

6 months

1.1.b.

Space 1 (Far left):

   

1.1.b.(1)

The designated accessible parking space is inaccessible because the space is only 56 inches wide.

P8

6 months

1.1.b.(2)

The designated accessible parking space is inaccessible because it slopes 4.0%.

P7

6 months

1.1.c.

Space 2 (Middle): The designated accessible parking space is inaccessible because it slopes 3.5% and the access aisle shared with space 3 has a slope of 3.5%.

P7

6 months

1.1.d.

Space 3 (Right): The designated accessible parking is inaccessible because it slopes 2.9% and the access aisle shared with space 2 has a slope of 3.5%.

P7

6 months

1.2.

Adolescent Offender Program Office:

   

1.2.a.

Entrance:

   

1.2.a.(1)

The door is inaccessible because the hardware requires pinching to use.

D1

6 months

1.2.a.(2)

The entrance is inaccessible because the threshold is 1 inch high.

D22

6 months

1.2.a.(3)

The door is inaccessible because there is a slope of up to 22.7% within the door´s required maneuvering clearance.

D13

6 months

1.2.b.

Reception Area: The brochure displays are inaccessible because the reach range is over 54 inches high to the top.

TR5

6 months

1.2.c.

Single User Unisex Toilet Room: The toilet room contains a number of inaccessible elements and is not accessible to people with disabilities.

SU13

6 months

1.3.

Tax Assessor/Collector Office:

   

1.3.a.

Entrance:

   

1.3.a.(1)

The door is inaccessible because the hardware requires pinching to use.

D1

6 months

1.3.a.(2)

The door is inaccessible because there is a 1 inch high threshold.

D22

6 months

1.3.a.(3)

The door is inaccessible because there is a slope of 11.1% within the door´s required maneuvering clearance.

D13

6 months

1.3.b.

Accessible Route: The suggestion box protrudes into the walkway and is not detectable to blind persons using a cane.

AR8

6 months

1.3.c.

Single User Unisex Toilet Room: The toilet room contains a number of inaccessible elements and is not accessible to people with disabilities.

SU13

6 months

1.4.

E911 Addressing Office & Building Permits Office:

   

1.4.a.

Entrance:

   

1.4.a.(1)

The door is inaccessible because the hardware requires pinching to use.

D1

6 months

1.4.a.(2)

The door is inaccessible because the threshold is higher than ½ inch and is not beveled.

D22

6 months

1.4.a.(3)

The door is inaccessible because there is a slope of 9.4% within the door´s required maneuvering clearance.

D13

6 months

1.4.b.

Single User Unisex Toilet Room: The toilet room contains a number of inaccessible elements and is not accessible to people with disabilities.

SU13

6 months

1.5.

Mississippi Driver License Office:

   

1.5.a.

Entrance:

   

1.5.a.(1)

The door is inaccessible because the hardware requires pinching to use.

D1

6 months

1.5.a.(2)

The door is inaccessible because the threshold is higher than ½ inch and is not beveled.

D22

6 months

1.5.a.(3)

The door is inaccessible because there is a slope of 12.9% within the door´s required maneuvering clearance.

D13

6 months

1.5.b.

Testing Area:

   

1.5.b.(1)

The front counter is inaccessible because it is 44 inches high.

C6

6 months

1.5.b.(2)

The vision test machine is inaccessible because it is 48 inches high.

C3, M2

6 months

1.5.b.(3)

The route to the testing area is inaccessible because the space between partitions is only 23 inches wide.

AR3

6 months

1.5.b.(4)

The testing machine is inaccessible because it is 46 inches high.

C3, M2

6 months

1.5.c.

Single User Unisex Toilet Room: The toilet room contains a number of inaccessible elements and is not accessible to people with disabilities.

SU13

6 months

2.

Pearl River County Health Department, located at 7547 Highway 11 South, Carriere

   

2.1.

Parking:

   

2.1.a.

Space 1 (near main clinic entrance): The designated van accessible parking is inaccessible because it lacks van accessible signage.

P6

12 months

2.1.b.

Space 3 (near the environmental waiting room): The designated accessible parking space is inaccessible because it lacks vertical signage.

P6

12 months

2.1.c.

Space 5 (behind environmental): The designated accessible parking space is inaccessible because it lacks vertical signage.

P6

12 months

2.1.d.

Space 6 (behind environmental): The designated accessible parking is inaccessible because it lacks vertical signage.

P6

12 months

2.1.e.

Space 7 (behind the health clinic): The designated accessible parking is inaccessible because it lacks vertical signage.

P6

12 months

2.1.f.

Space 8 (behind the health clinic): The designated accessible parking is inaccessible because it lacks vertical signage.

P6

12 months

2.2.

Route from Parking to Main Clinic Entrance: The curb ramp is inaccessible because it has a slope of 10.2%.

AR5

12 months

2.3.

Route from Parking to Front Environmental Entrance: The route is inaccessible because there is a curb without a curb ramp.

AR1, AR5

12 months

2.4.

Route from Parking to Rear Environmental Entrance: The curb ramp is inaccessible because it has a slope of 11.7%.

AR5

12 months

2.5.

Route from Parking to Employee Entrance in Rear of Clinic: The curb ramp is inaccessible because it has a slope of 12.6%.

AR5

12 months

2.6.

Room 102 Counter: The overhanging portion of the counter protrudes into the walkway and is not detectable to blind persons using a cane.

AR8

12 months

2.7.

Room 103 Counter: The overhanging portion of the counter protrudes into the walkway and is not detectable to blind persons using a cane.

AR8

12 months

2.8.

Room 104 Counter: The overhanging portion of the counter protrudes into the walkway and is not detectable to blind persons using a cane.

AR8

12 months

2.9.

Drinking Fountain by the Lobby: Although a designated accessible drinking fountain is provided, there is no drinking fountain provided for people who have difficulty bending or stooping.

DF3

12 months

2.10.

Women´s Toilet Room by the Lobby:

   

2.10.a.

The door is inaccessible because it requires 9 pounds of force to open.

D2

12 months

2.10.b.

The door is inaccessible because the hardware is mounted 50 inches above the floor.

D1

12 months

2.10.c.

No accessible mirror has been provided.

TR14

12 months

2.10.d.

The paper towel dispenser protrudes into the walkway and is not detectable to blind persons using a cane.

AR8

12 months

2.10.e.

The rear grab bar at the designated accessible toilet is inaccessible because it is mounted 13 inches from the side wall.

ST4

12 months

2.11.

Men´s Toilet Room by the Lobby:

   

2.11.a.

The door is inaccessible because it requires 11 pounds of force to open.

D2

12 months

2.11.b.

The door is inaccessible because the hardware is mounted 50 inches above the floor.

D1

12 months

2.11.c.

No accessible mirror has been provided.

TR14

12 months

2.11.d.

The paper towel dispenser protrudes into the walkway and is not detectable to blind persons using a cane.

AR8

12 months

2.11.e.

The urinal is inaccessible because the rim is 24 inches high.

TR20

12 months

2.11.f.

The toilet paper dispenser in the designated accessible stall is inaccessible because it is mounted 40 inches from the rear wall.

ST19

12 months

2.11.g.

The rear grab bar at the designated accessible toilet is inaccessible because it is mounted 12 inches from the side wall.

ST4

12 months

2.12.

Single User Unisex Toilet Room next to Lab 113:

   

2.12.a.

No accessible mirror has been provided.

TR14

12 months

2.12.b.

The toilet is inaccessible because its centerline is 17 inches from the side wall.

SU15

12 months

2.13.

Exit Clerk Counter: The exit clerk counter protrudes into the walkway and is not detectable to blind persons using a cane.

AR8

12 months

2.14.

Women´s Toilet Room by the File Room:

   

2.14.a.

The door is inaccessible because it requires 11 pounds of force to open.

D2

12 months

2.14.b.

The designated accessible toilet is inaccessible because its centerline is 19 inches from the side wall.

ST17

12 months

2.14.c.

The rear grab bar at the designated accessible toilet is inaccessible because it is mounted 12 inches from the side wall.

ST4

12 months

2.14.d.

The designated accessible toilet is inaccessible because there is insufficient clear floor space due to the table located in the stall.

ST18, M1

12 months

2.15.

Men´s Toilet Room by the File Room:

   

2.15.a.

The door is inaccessible because it requires 10 pounds of force to open.

D2

12 months

2.15.b.

The urinal is inaccessible because the rim is 24 inches high.

TR20

12 months

2.15.c.

The designated accessible toilet is inaccessible because its centerline is 20 inches from the side wall.

ST17

12 months

2.15.d.

The rear grab bar at the designated accessible toilet is inaccessible because it is mounted 12 inches from the side wall.

ST4

12 months

2.15.e.

Drinking Fountain in the Environmental Lobby: Although a designated accessible drinking fountain is provided, there is no drinking fountain provided for people who have difficulty bending or stooping.

DF3

12 months

2.16.

Counter in Environmental Lobby: The counter protrudes into the walkway and is not detectable to blind persons using a cane.

AR8

12 months

3.

Nursing Home, located at 305 West Moody Street, Poplarville

   

3.1.

Parking:

   

3.1.a.

Space 1: The designated van accessible parking is inaccessible because it lacks vertical signage.

P6

12 months

3.1.b.

Space 2:

   

3.1.b.(1)

The designated accessible parking space is inaccessible because it lacks vertical signage.

P6

12 months

3.1.b.(2)

The designated accessible space is inaccessible because there is no access aisle.

P1

12 months

3.1.c.

Space 3:

   

3.1.c.(1)

The designated accessible parking space is inaccessible because it lacks vertical signage.

P6

12 months

3.1.c.(2)

The designated accessible space is inaccessible because there is no access aisle.

P1

12 months

3.1.d.

Space 4:

   

3.1.d.(1)

The designated accessible parking space is inaccessible because it lacks vertical signage.

P6

12 months

3.1.d.(2)

The designated accessible space is inaccessible because there is no access aisle.

P1

12 months

3.2.

Ramp to Entrance:

   

3.2.a.

The ramp is inaccessible because it has a slope of up to 11.8% and does not have level landings at the change in direction or the top.

R3

12 months

3.2.b.

The ramp is inaccessible because it does not have edge protection at the drop off sides.

R1

12 months

3.3.

Nurse Station Counter: The counter is inaccessible because it is 42 inches high.

C6

12 months

3.4.

Toilet Room and Patient Bath near the Nursing Station:

   

3.4.a.

The medical dispenser by the entrance to the Patients Bath protrudes into the walkway and is not detectable to blind persons using a cane.

AR8

12 months

3.4.b.

The toilet room sign is mounted on the door and has no raised or Braille characters.

TR18

12 months

3.4.c.

No accessible mirror has been provided.

TR14

12 months

3.4.d.

The lavatory is inaccessible because the hot water and drain pipes are not insulated or otherwise configured to protect against contact.

TR12

12 months

3.4.e.

The shower is inaccessible because the controls and shower unit are located on a side wall instead of the back wall.

B11

12 months

3.5.e.

The roll-in shower is inaccessible because no side grab bar is provided.

B8

12 months

3.5.f.

The toilet is inaccessible because its centerline is 17.5 inches from the side wall.

SU15

12 months

3.5.g.

The side grab bar at the toilet is inaccessible because the farthest end is 45.5 inches from the rear wall.

SU6

12 months

3.5.h.

The rear grab bar at the toilet is inaccessible because it is 24 inches long and the farthest end is 27 inches from the side wall.

SU3

12 months

3.5.

Women´s Toilet Room Section 2:

   

3.5.a.

The toilet room sign has a centerline of 56 inches above the finished floor.

TR18

12 months

3.5.b.

The door is inaccessible because it requires 9 pounds of force to open.

D2

12 months

3.5.c.

The coat hook is inaccessible because it is mounted 65 inches above the finished floor.

TR1

12 months

3.5.d.

The designated accessible toilet is inaccessible because the centerline is 16.25 inches from the side wall.

ST17

12 months

3.5.e.

The side grab bar at the designated accessible toilet is inaccessible because the farthest end is 44 inches from the rear wall.

ST7

12 months

3.5.f.

The rear grab bar at the designated accessible toilet is inaccessible because it is 24 inches long.

ST4

12 months

3.5.g.

The lavatory is inaccessible because the hot water pipes are not insulated or otherwise configured to protect against contact.

TR12

12 months

3.5.h.

Although the facility contains an emergency alarm system, the alarm system is inaccessible because there are no visual alarms provided in toilet room.

AL1

12 months

3.6.

Men´s Single User Toilet Room near the Dining Hall:

   

3.6.a.

The toilet room sign has a centerline of 56 inches above the finished floor and is mounted on the wall adjacent to the hinge side of the door.

TR18

12 months

3.6.b.

The toilet is inaccessible because its centerline is 17 inches from the side wall.

SU15

12 months

3.6.c.

The toilet is inaccessible because the flush control is on the closed side.

SU1

12 months

3.6.d.

The side grab bar at the toilet is inaccessible because the farthest end is 44 inches from the rear wall.

SU6

12 months

3.6.e.

The rear grab bar at the toilet is inaccessible because it is 24 inches long.

SU3

12 months

3.6.f.

The lavatory is inaccessible because the hot water pipes are not insulated or otherwise configured to protect against contact.

TR12

12 months

3.7.g.

Although the facility contains an emergency alarm system, the alarm system is inaccessible because there are no visual alarms provided in this toilet room.

AL1

12 months

3.7.

Drinking Fountain near the Dining Hall:

   

3.8.a.

Although a designated accessible drinking fountain is provided, there is no drinking fountain provided for people who have difficulty bending or stooping.

DF3

12 months

3.8.b.

The drinking fountain protrudes into the walkway and is not detectable to blind persons using a cane.

AR8

12 months

3.8.

Single User Unisex Toilet Room in Section 1 Day Room:

   

3.8.a.

The toilet room sign is mounted on the door and has no raised or Braille characters.

TR18

12 months

3.8.b.

No accessible mirror has been provided.

TR14

12 months

3.8.c.

The lavatory is inaccessible because the bottom of the apron is 27.75 inches high.

TR11

12 months

3.8.d.

The lavatory is inaccessible because the hot water pipes are not insulated or otherwise configured to protect against contact.

TR12

12 months

3.8.e.

The toilet is inaccessible because the top of the seat is 19.75 inches high.

SU18

12 months

3.8.f.

The toilet is inaccessible because its centerline is 22 inches from the side wall.

SU15

12 months

3.8.g.

The toilet is inaccessible because there are no accessible grab bars provided.

SU10

12 months

3.8.h.

Although the facility contains an emergency alarm system, the alarm system is inaccessible because there are no visual alarms provided in this toilet room.

AL1

12 months

4.

Pearl River County Justice Center, located at 171 Savannah Millard, Poplarville

   

4.1.

Parking:

   

4.1.a.

The parking lot, with a total of 88 parking spaces is inaccessible because it only has 2 spaces designated as accessible. This lot requires 1 van accessible space and 3 standard accessible spaces.

P3

12 months

4.1.b.

The designated accessible parking is inaccessible because it is not dispersed among the accessible facility entrances.

P2

12 months

4.1.c.

Left Van Accessible Space:

P6

12 months

4.1.c.(1)

The designated van accessible parking is inaccessible because the sign is mounted too low.

P6

12 months

4.1.c.(2)

The designated van accessible parking is inaccessible because the access aisle is 60 inches wide.

P8

12 months

4.1.d.

Right Accessible Space: The designated accessible parking is inaccessible because it lacks vertical signage.

P6

12 months

4.2.

Route from Parking to Prison Entrance:

   

4.2.a.

The ramp is inaccessible because the ends of the handrails do not extend at least 12 inches beyond the bottom or the inside top of the ramp, the distance between the handrail and the wall is 4 inches, and the diameter of the handrail is 2 inches.

R4

12 months

4.2.b.

The ramp is inaccessible because it does not have edge protection at the drop off sides.

R1

12 months

4.2.c.

The ramp is inaccessible because the bottom landing has a cross slope of up to 2.3%.

R5

12 months

4.2.d.

The handrail of the ramp protrudes into the walkway and is not detectable to blind persons using a cane.

AR8

12 months

4.3.

Route from Parking to Justice Court and Veterans Services:

   

4.3.a.

The ramp is inaccessible because the ends of the handrails do not extend at least 12 inches beyond the bottom or the inside top of the ramp, the distance between the handrail and the wall is 4 inches, and the diameter of the handrail is 2 inches.

R4

12 months

4.3.b.

The ramp is inaccessible because it does not have edge protection at the drop off sides.

R1

12 months

4.3.c.

The ramp is inaccessible because it has a cross slope of up to 2.7% and the bottom landing has a cross slope of 3.9%.

R5

12 months

4.3.d.

The handrail of the ramp protrudes into the walkway and is not detectable to blind persons using a cane.

AR8

12 months

4.4.

Main Prison Lobby:

   

4.4.a.

The reception counter and the record counter are inaccessible because they are 37 inches high.

C6

12 months

4.4.b.

The reception counter and the record counter protrude into the walkway and are not detectable to blind persons using a cane.

AR8

12 months

4.5.

Drinking Fountain in the Prison Lobby:

   

4.5.a.

Although a designated accessible drinking fountain is provided, there is no drinking fountain provided for people who have difficulty bending or stooping.

DF3

12 months

4.5.b.

The drinking fountain protrudes into the walkway and is not detectable to blind persons using a cane.

AR8

12 months

4.6.

Single User Women´s Toilet Room in the Prison Lobby:

   

4.6.a.

The door is inaccessible because it requires 9 pounds of force to open.

D2

12 months

4.6.b.

No accessible mirror has been provided.

TR14

12 months

4.6.c.

The lavatory is inaccessible because the top of the rim or counter is 35 inches high.

TR11

12 months

4.7.

Single User Men´s Toilet Room in Prison Lobby:

   

4.7.a.

The door is inaccessible because it requires 9 pounds of force to open.

D2

12 months

4.7.b.

The toilet is inaccessible because its centerline is 18.5 inches from the side wall.

SU15

12 months

4.7.c.

No accessible mirror has been provided.

TR14

12 months

4.8.

Lawyer Visit #2: The inmates´s side of the room is inaccessible because the fixed stool prevents a person using a wheelchair from sitting in the room.

LB4, PJ7, M2

12 months

4.9.

Reception Counter in Employee Area: The counter is inaccessible because it is 42 inches high.

C6

12 months

4.10.

Women´s Toilet Room in Employee Break Room:

   

4.10.a.

The door is inaccessible because it requires 8 pounds of force to open.

D2

12 months

4.10.b.

No accessible mirror has been provided.

TR14

12 months

4.10.c.

The designated accessible toilet stall is inaccessible because there is insufficient clear floor space.

ST18

12 months

4.10.d.

No accessible coat hook has been provided.

TR1

12 months

4.10.e.

The lavatory protrudes into the walkway and is not detectable to blind persons using a cane.

AR8

12 months

4.11.

Men´s Toilet Room in Employee Break Room:

   

4.11.a.

The door is inaccessible because it requires 9 pounds of force to open.

D2

12 months

4.11.b.

No accessible mirror has been provided.

TR14

12 months

4.11.c.

The designated accessible toilet stall is inaccessible because there is insufficient clear floor space.

ST18

12 months

4.11.d.

The designated accessible toilet is inaccessible because its centerline is 18.75 inches from the side wall.

ST17

12 months

4.11.e.

No accessible coat hook has been provided.

TR1

12 months

4.11.f.

The rear grab bar at the designated accessible toilet is inaccessible because it is mounted 36.5 inches high.

ST12

12 months

4.12.

Investigations Office: The door is inaccessible because it requires 12 pounds of force to open.

D2

12 months

4.13.

Route to Employee Locker Rooms: The door is inaccessible because it requires 13 pounds of force to open.

D2

12 months

4.14.

Women´s Employee Locker Room:

   

4.14.a.

The door is inaccessible because it requires 11 pounds of force to open.

D2

12 months

4.14.b.

No accessible mirror has been provided.

TR14

12 months

4.14.c.

No accessible coat hook has been provided.

TR1

12 months

4.14.d.

The shower is inaccessible because there is insufficient clear floor space alongside the shower opening.

B8

12 months

4.14.e.

The transfer shower is inaccessible because the hose for the shower spray unit is only 56 inches long.

B11

12 months

4.15.

Men´s Employee Locker Room:

   

4.15.a.

The door is inaccessible because it requires 13 pounds of force to open.

D2

12 months

4.15.b.

No accessible mirror has been provided.

TR14

12 months

4.15.c.

The lavatory is inaccessible because the top of the rim or counter is 34.5 inches high.

TR11

12 months

4.15.d.

No accessible coat hook has been provided.

TR1

12 months

4.15.e.

The toilet is inaccessible because the clear floor space is obstructed by a chair.

ST18, M1

12 months

4.15.f.

The transfer shower is inaccessible because there is insufficient clear floor space alongside the shower opening.

B8

12 months

4.15.g.

The transfer shower is inaccessible because the hose for the shower spray unit is only 56 inches long.

B11

12 months

4.16.

Single User Toilet Room in Main Control:

   

4.16.a.

The door is inaccessible because it requires 10 pounds of force to open.

D2

12 months

4.16.b.

No accessible mirror has been provided.

TR14

12 months

4.17.

Single User Toilet Room in Intake Holding Cell 3:

   

4.17.a.

The toilet room lacks accessible signage with the International Symbol of Accessibility.

TR16

12 months

4.17.b.

The lavatory is inaccessible because the top of the rim is 34.75 inches high.

TR11

12 months

4.17.c.

The toilet is inaccessible because its centerline is 17.5 inches from the side wall.

SU15

12 months

4.17.d.

The roll-in shower is inaccessible because no side grab bar is provided.

B8

12 months

4.18.

Single User Toilet Room in Holding Cell (outside sections): The toilet room contains a number of inaccessible elements and is not accessible to people with disabilities.

SU13

12 months

4.19.

Single User Toilet Room in Medical Holding Cell 1: The toilet room contains a number of inaccessible elements and is not accessible to people with disabilities.

SU13

12 months

4.20.

Single User Toilet Room in Medical Holding Cell 2: The side grab bar at the toilet is inaccessible it is mounted 51 inches from the rear wall.

SU6

12 months

4.21.

Route from Medical to Nurse´s Office:

   

4.21.a.

The route is inaccessible because it is only 30.5 inches wide.

AR3

12 months

4.21.b.

The push side of the door, which is accessed through a front approach, is inaccessible because the depth of the maneuvering space is less than 48 inches.

D7

12 months

4.22.

Medical Prep: The pull side of the door, which is accessed through a front approach, is inaccessible because it is less than 18 inches of clear space on the latch side.

D6

12 months

4.23.

Unisex Single User Toilet Room in Medical:

   

4.23.a.

The toilet is inaccessible because its centerline is 18.5 inches from the side wall.

SU15

12 months

4.23.b.

The side grab bar at the toilet is inaccessible because it is mounted 52.5 inches from the rear wall.

SU6

12 months

4.23.c.

The toilet room door swings into the required clear floor space at the lavatory.

TR6

12 months

4.24.

Roll-In Shower Stall in Dorm A1: The shower is inaccessible because it has a 1.75 inch curb at the entrance.

B7

12 months

4.25.

Single User Toilet Room in Lockdown A1: The side grab bar at the toilet is inaccessible because it is mounted 2.25 inches from the wall.

SU12

12 months

4.26.

Drinking Fountain in A1:

   

4.26.a.

Although a designated accessible drinking fountain is provided, there is no drinking fountain provided for people who have difficulty bending or stooping.

DF3

12 months

4.26.b.

The drinking fountain protrudes into the walkway and is not detectable to blind persons using a cane.

AR8

12 months

4.27.

Toilet Room in Dorm A2:

   

4.27.a.

The lavatory is inaccessible because the bottom of the apron is 28 inches high.

TR11

12 months

4.27.b.

The lavatory protrudes into the walkway and is not detectable to blind persons using a cane.

AR8

12 months

4.28.

Roll-In Shower Stall in Dorm A2:

   

4.28.a.

The roll-in shower is inaccessible because no side grab bar is provided.

B8

12 months

4.28.b.

The shower is inaccessible because it has a curb at the entrance.

B7

12 months

4.29.

Drinking Fountain in Dorm A2:

   

4.29.a.

The drinking fountain protrudes into the walkway and is not detectable to blind persons using a cane.

AR8

12 months

4.29.b.

Although a designated accessible drinking fountain is provided, there is no drinking fountain provided for people who have difficulty bending or stooping.

DF3

12 months

4.30.

Toilet Room in Dorm A4: The lavatory protrudes into the walkway and is not detectable to blind persons using a cane.

AR8

12 months

4.31.

Roll-In Shower Stall in Dorm A4:

   

4.31.a.

The roll-in shower is inaccessible because no side grab bar is provided.

B8

12 months

4.31.b.

The shower is inaccessible because it has a curb at the entrance.

B7

12 months

4.32.

Drinking Fountain in Dorm A4:

   

4.32.a.

The drinking fountain protrudes into the walkway and is not detectable to blind persons using a cane.

AR8

12 months

4.32.b.

Although a designated accessible drinking fountain is provided, there is no drinking fountain provided for people who have difficulty bending or stooping.

DF3

12 months

4.33.

Toilet Room in Dorm A6:

   

4.33.a.

There is no rear grab bar provided at the designated accessible toilet.

ST11

12 months

4.33.b.

The lavatory protrudes into the walkway and is not detectable to blind persons using a cane.

AR8

12 months

4.34.

Roll-In Shower Stall in Dorm A6:

   

4.34.a.

The roll-in shower is inaccessible because no side grab bar is provided.

B8

12 months

4.34.b.

The shower is inaccessible because it has a 1.75 inch curb at the entrance.

B7

12 months

4.35.

Drinking Fountain in Dorm A6:

   

4.35.a.

The drinking fountain protrudes into the walkway and is not detectable to blind persons using a cane.

AR8

12 months

4.35.b.

Although a designated accessible drinking fountain is provided, there is no drinking fountain provided for people who have difficulty bending or stooping.

DF3

12 months

4.36.

Toilet Room in Dorm B2: The lavatory protrudes into the walkway and is not detectable to blind persons using a cane.

AR8

12 months

4.37.

Roll-In Shower Stall in Dorm B2:

   

4.37.a.

The roll-in shower is inaccessible because no side grab bar is provided.

B8

12 months

4.37.b.

The shower is inaccessible because it has a curb at the entrance.

B7

12 months

4.38.

Drinking Fountain in Dorm B2:

   

4.38.a.

The drinking fountain protrudes into the walkway and is not detectable to blind persons using a cane.

AR8

12 months

4.38.b.

Although a designated accessible drinking fountain is provided, there is no drinking fountain provided for people who have difficulty bending or stooping.

DF3

12 months

4.39.

Roll-In Shower Stall in Lockdown B3:

   

4.39.a.

The roll-in shower is inaccessible because no side grab bar is provided.

B8

12 months

4.39.b.

The shower is inaccessible because it has a curb at the entrance.

B7

12 months

4.40.

Single User Toilet Room in Cell B3-12: The toilet is inaccessible because there are no grab bars provided.

SU10

12 months

4.41.

Single User Toilet Room in Cell B3-18: The toilet is inaccessible because there is no rear grab bar provided.

SU10

12 months

4.42.

Telephone in Lockdown B: The telephone is inaccessible because it is 55.5 inches high to the highest operable part.

TT1

12 months

4.43.

Drinking Fountain in Lockdown B:

   

4.43.a.

Although a designated accessible drinking fountain is provided, there is no drinking fountain provided for people who have difficulty bending or stooping.

DF3

12 months

4.43.b.

The drinking fountain protrudes into the walkway and is not detectable to blind persons using a cane.

AR8

12 months

4.44.

Unisex Single User Toilet Room by Kitchen:

   

4.44.a.

The paper towel dispenser is inaccessible because it is mounted with the controls 55 inches high.

TR5

12 months

4.44.b.

The side grab bar at the toilet is inaccessible because it is mounted 53 inches from the rear wall.

SU6

12 months

4.44.c.

The lavatory is inaccessible because the drain pipe is not insulated or otherwise configured to protect against contact.

TR12

12 months

4.44.d.

No accessible mirror has been provided.

TR14

12 months

4.45.

Ramp in Sally Port:

   

4.45.a.

The ramp is inaccessible because there are no handrails.

R4

12 months

4.45.b.

The ramp is inaccessible because it does not have edge protection at the drop off sides.

R1

12 months

4.46.

Route to the Mechanic´s Area: The route is inaccessible because it is not firm, stable, or slip-resistant.

AR1

12 months

4.47.

Women´s Toilet Room in Justice Court Lobby:

   

4.47.a.

The door is inaccessible because it requires 14 pounds of force to open.

D2

12 months

4.47.b.

No accessible mirror has been provided.

TR14

12 months

4.47.c.

The coat hook in the accessible stall is inaccessible because it is 63 inches above the finished floor.

TR1

12 months

4.47.d.

The side grab bar at the designated accessible toilet is inaccessible because it is mounted 37 inches high.

ST12

12 months

4.48.

Men´s Toilet Room in Justice Court Lobby:

   

4.48.a.

The door is inaccessible because it requires 14 pounds of force to open.

D2

12 months

4.48.b.

No accessible mirror has been provided.

TR14

12 months

4.48.c.

The lavatory is inaccessible because the top of the rim or counter is 34.5 inches high.

TR11

12 months

4.48.d.

The coat hook in the accessible stall is inaccessible because it is 63 inches above the finished floor.

TR1

12 months

4.48.e.

The side grab bar at the designated accessible toilet is inaccessible because it is mounted 37 inches high.

ST12

12 months

4.49.

Justice Court:

   

4.49.a.

The door is inaccessible because it requires 10 pounds of force to open.

D2

12 months

4.49.b.

The judge´s bench is inaccessible because it can be accessed only by steps.

AA8

12 months

4.49.c.

The Justice Court, containing 52 seats, is inaccessible because no wheelchair seating areas are provided. A total of 4 wheelchair seating areas is required.

AA6

12 months

4.50.

Single User Unisex Toilet Room behind the Justice Court:

   

4.50.a.

The door is inaccessible because it requires 10 pounds of force to open.

D2

12 months

4.50.b.

No accessible mirror has been provided.

TR14

12 months

4.50.c.

The toilet is inaccessible because its centerline is 19 inches from the side wall.

SU15

12 months

 