Attachment I: Modifications to Newly Constructed Facilities
Please Note: Paragraph 31 of the Settlement Agreement requires that within three months of the effective date of this Agreement, the City will provide signage as necessary to comply with 28 C.F.R. § 35.163(b), after having surveyed all facilities that are the subject of this Agreement for the purpose of identifying those that have multiple entrances not all of which are accessible.
In order to ensure that the following spaces and elements in City facilities, for which construction was commenced after January 26, 1992, are readily accessible to and usable by persons with disabilities, the City will take the following actions:
1. By December 31, 2010, the City will complete the following modifications to the Northeast Police Precinct, 4316 North 30th Street :
a. Parking: Although the parking lot has 24 parking spaces and two spaces are designated as reserved for people with disabilities, the designated space on the left (when facing the building) lacks a vertical sign with the International Symbol of Access and neither space is designated as "van accessible" with appropriate signage. At all spaces designated as reserved for persons with disabilities, provide vertical signs with the International Symbol of Accessibility located such that they cannot be obstructed by parked vehicles. On the shortest accessible route to the accessible entrance, provide 1 van accessible space designated as reserved for people with disabilities. Ensure that van accessible spaces are a minimum of 96 inches wide and served by access aisles at least 96 inches wide. At all spaces designated as reserved for persons with disabilities, provide vertical signs with the International Symbol of Accessibility located such that they cannot be obstructed by parked vehicles. At van accessible spaces, provide an additional "Van-Accessible" sign located below the International Symbol of Accessibility. Ensure that all spaces and access aisles for persons with disabilities are flat and level, with slopes and cross-slopes not exceeding 1:50 in all directions, and that their surfaces are firm, stable, and slip-resistant. Standards §§ 4.1.2(5), 4.6, 4.30.7(1)
b. Entrance: The interior door at the entrance to the building requires more than five pounds of force to open. Provide a door that requires no more than 5 pounds of force to open. Standards §§ 4.1.3(7)(b), 4.13.11(2)(b).
c. Permanent Room Signage: The permanent room sign for the Conference Room is not mounted on the wall on the latch side of the door and lacks characters in san serif font. Provide permanent room signage with upper case, sans serif or simple serif type letters and numerals, meeting the requirements of the Standards for character height, raised characters, finish and contrast, accompanied by Grade 2 Braille; mounted on the wall adjacent to the latch side of the door or on the nearest adjacent wall at a height of 60 inches above the finished floor to the centerline of the sign; and located so that a person may approach within 3 inches of the signage without encountering protruding objects or standing within the swing of a door. Standards §§ 4.1.2(7), 4.30.1, 4.30.4, 4.30.5, 4.30.6.
d. Alarms: While the building has audible fire alarms, it lacks visual alarms in the Conference Room, toilet rooms, and reception area. Provide visual alarm devices in toilet rooms and any other general usage areas (e.g., meeting rooms), hallways, lobbies, and any other area for common use. Such devices shall be integrated into the facility alarm system and shall meet the requirements of the Standards for lamp type, color, pulse duration, intensity, and flash rate. Visual alarm appliances shall be placed 80 inches above the highest floor level within the space or 6 inches below the ceiling, whichever is lower. Visual alarm appliances shall be located such that no place in any room or space, including common corridors or hallways, required to have a visual alarm appliance shall be more than 50 feet from the signal. In large rooms and spaces exceeding 100 feet across, without obstructions 6 feet above the finished floor, devices may be placed around the perimeter, spaced a maximum of 100 feet apart, in lieu of suspending appliances from the ceiling. Standards §§ 4.1.3(14), 4.28.3.
e. Reception Area: The bell for assistance is 56 inches above the finished floor and is placed over an obstruction. Provide a call button within accessible reach ranges at this entrance and ensure that the door will be unlocked promptly when the call button is used. Standards §§ 4.1.3(8), 4.14.1.
f. Men's and Women's Toilet Rooms with Stalls (near the Conference Room). For each:
i. The pressure required to operate the door exceeds five pounds of force. Provide a door that requires no more than 5 pounds of force to open. Standards §§ 4.1.3(7)(b), 4.13.11(2)(b).
ii. Toilet Stall for Persons with Disabilities
(1) The distance of the farther end of the side grab bar from the rear wall is 44-45 inches. Provide a side grab bar that is at least 40 inches in overall length, with the far end mounted at least 52 inches from the rear wall and the closer end 12 inches or less from the rear wall. Standards §§ 4.1.3(11), 4.22.4, 4.17.6, Figs. 30(a), (d).
(2) Men's Only: No accessible coat hook has been provided. Provide a coat hook at a maximum height above the finished floor of 48 inches for a forward approach or 54 inches for a side approach and that is accompanied by clear floor space of 30 by 48 inches that allows a forward or parallel approach by a person using a wheelchair. Standards §§ 4.1.3(12)(a), 4.25.2, 4.25.3, 4.2.4, 4.2.5, 4.2.6.
iii. Women's Only: The bottom leading edge of the sanitary napkin dispenser exceeds 27 inches above the finished floor, it extends more than four inches into the path of travel and it is, therefore, a protruding object. Provide an accessible route at this location such that no objects with their bottom leading edges measuring between 27 inches and 80 inches above the finished floor protrude more than 4 inches into walks, halls, corridors, passageways, or aisles. Free-standing objects mounted on posts or pylons may overhang 12 inches maximum from 27 inches to 80 inches above the ground or finished floor. Standards §§ 4.1.2(3), 4.4.
g. Drinking Fountain (near the Conference Room)
i. The control requires more than five pounds of force to operate. Provide a drinking fountain with controls mounted on or near the front edge that are operable with one hand, that require 5 pounds of force or less to operate, and that can be operated without tight grasping, pinching, or twisting of the wrist. Standards §§ 4.1.3(10), 4.15.4, 4.27.4.
ii. Although an accessible drinking fountain is provided, there is no drinking fountain provided for people who have difficulty bending or stooping. Provide a drinking fountain that is accessible to people who have difficulty bending or stooping. This can be accommodated by the use of a "hi-lo" fountain; by providing one fountain accessible to those who use wheelchairs and one fountain at a standard height convenient for those who have difficulty bending; by providing a fountain accessible to people who use wheelchairs and a cup dispenser, or by such other means as would achieve the required accessibility for each group of people. Standards § 4.1.3(10)(a).
2. By December 31, 2011, the City will complete the following modifications to the Southeast Police Precinct, located at 2475 Deer Park Boulevard:
a. Entrance: The interior doors at the entrance to the building require more than five pounds of force to open. Provide a door that requires no more than 5 pounds of force to open. Standards §§ 4.1.3(7)(b), 4.13.11(2)(b).
b. Alarms: While the building has audible fire alarms, it lacks visual alarms in the toilet rooms, Interview Rooms A & B, Precinct Investigations, Patrol Operations, and the secure hallways. Provide visual alarm devices in toilet rooms and any other general usage areas (e.g., meeting rooms), hallways, lobbies, and any other area for common use. Such devices shall be integrated into the facility alarm system and shall meet the requirements of the Standards for lamp type, color, pulse duration, intensity, and flash rate. Visual alarm appliances shall be placed 80 inches above the highest floor level within the space or 6 inches below the ceiling, whichever is lower. Visual alarm appliances shall be located such that no place in any room or space, including common corridors or hallways, required to have a visual alarm appliance shall be more than 50 feet from the signal. In large rooms and spaces exceeding 100 feet across, without obstructions 6 feet above the finished floor, devices may be placed around the perimeter, spaced a maximum of 100 feet apart, in lieu of suspending appliances from the ceiling. Standards §§ 4.1.3(14), 4.28.3.
c. The door to the Precinct Investigations requires 15 pounds of force to operate. Provide a door that requires no more than 5 pounds of force to open. Standards §§ 4.1.3(7)(b), 4.13.11(2)(b).
d. Drinking Fountain in Main Lobby: The spout height is 42 inches above the finished floor. Provide a fountain that has a spout height no higher than 36 inches, measured from the finished floor or ground surface to the spout outlet, and that otherwise complies with the Standards. Standards §§ 4.1.3(10), 4.15, 4.27.4, Fig. 27.
e. Men's and Women's Public Toilet Room with Stalls (off Main Lobby)
i. The pressure required to open the door exceeds five pounds of force. Provide a door that requires no more than 5 pounds of force to open. Standards §§ 4.1.3(7)(b), 4.13.11(2)(b).
ii. The Standard Accessible Stall for Wheelchair Users
(1) The flush control valve is on the closed side. Provide a flush control mounted on the "open" side of the toilet's clear floor space; 44 inches or less above the finished floor; and requiring a maximum of 5 pounds of force to operate; or provide an automatic flush device. Standards §§ 4.1.3(11), 4.22.4, 4.16.5, 4.17.2, 4.27.4.
(2) Women's Only: The toilet centerline is 19 inches from the side wall or partition. Provide a toilet with a centerline that measures 18 inches from the near side wall. Standards §§ 4.1.3(11), 4.22.4, 4.17.3, Fig. 30.
(3) Women's Only: The distance of the further end of the side grab bar to the rear wall is 49 inches. Provide a side grab bar that is at least 40 inches in overall length, with the far end mounted at least 52 inches from the rear wall and the closer end 12 inches or less from the rear wall. Standards §§ 4.1.3(11), 4.22.4, 4.17.6, Figs. 30(a), (d).
(4) Men's Only: Both the side and the rear grab bars are mounted at 37 inches above the finished floor. Provide grab bars that are mounted between 33 and 36 inches above the finished floor. Standards §§ 4.1.3(11), 4.22.4, 4.17.6, Fig. 30.
iii. Men's Only: The clear floor space centered on the urinal is 28 inches wide. Provide a urinal with an elongated rim mounted 17 inches or less above the finished floor, a clear floor space of at least 30 inches wide and 48 inches deep centered on the urinal, and a flush control height of 44 inches or less above the finished floor. Standards §§ 4.1.3(11), 4.22.5, 4.18.2, 4.18.3, 4.18.4.
f. Unisex, Single-User Toilet Room (Across from Interview Rooms A & B): This toilet room and its elements (such as door width, clear floor space, lavatory, toilet, etc.) are inaccessible to persons with disabilities. Provide an accessible toilet room such that all of the room's elements, including signage, door, door hardware, clear floor space, water closet, urinal (if provided), grab bars, lavatory, mirror, controls, and dispensers, comply with the Standards. Standards §§ 4.1.3(11), 4.22, 4.13, 4.16, 4.18, 4.19, 4.26, 4.27, 4.30, Figs. 28, 29.
3. By December 31, 2008, the City will complete the following modifications to the Benson Library, located at 60th and Binney:
a. Alarms: While the building has audible fire alarms, it lacks a visual alarm in the study room. Provide visual alarm devices in toilet rooms and any other general usage areas (e.g., meeting rooms), hallways, lobbies, and any other area for common use. Such devices shall be integrated into the facility alarm system and shall meet the requirements of the Standards for lamp type, color, pulse duration, intensity, and flash rate. Visual alarm appliances shall be placed 80 inches above the highest floor level within the space or 6 inches below the ceiling, whichever is lower. Visual alarm appliances shall be located such that no place in any room or space, including common corridors or hallways, required to have a visual alarm appliance shall be more than 50 feet from the signal. In large rooms and spaces exceeding 100 feet across, without obstructions 6 feet above the finished floor, devices may be placed around the perimeter, spaced a maximum of 100 feet apart, in lieu of suspending appliances from the ceiling. Standards §§ 4.1.3(14), 4.28.3.
b. Public Telephone (near Women's Toilet Room):
i. The counter is 40 ½ inches above the finished floor, is too close to the women's toilet room entrance so that the door obstructs callers from making a parallel approach to the telephone, and there is no lower phone. Provide an accessible telephone with a clear floor space of at least 30 inches by 48 inches that allows either a forward or parallel approach by a person using a wheelchair such that bases, enclosures, and fixed seats do not impede approaches to the telephone; with the highest operable part of the telephone mounted no more than 48 inches above the floor for a front approach or no more than 54 inches above the floor for a side approach; that is hearing aid compatible and has a volume control mechanism; with telephone books, if provided, located between 15 and 48 inches above the finished floor for a front approach or between 9 and 54 inches above the finished floor for a side approach; with a cord of at least 29 inches long from the telephone to the handset; and with signage that complies with the Standards. Standards §§ 4.1.3(17), 4.31, 4.30.7(2).
ii. There is no TTY. Provide at least one accessible public TTY with appropriate signage. Standards §§ 4.1.3(17)(c)), 4.30.7(3), 4.31.9.
iii. The telephone's bottom leading edge and that of the wooden phone book shelf are more than 27 inches above the finished floor, they extend more than four inches into the path of travel, and they are, therefore, protruding objects. Provide an accessible route at this location such that no objects with their bottom leading edges measuring between 27 inches and 80 inches above the finished floor protrude more than 4 inches into walks, halls, corridors, passageways, or aisles. Free-standing objects mounted on posts or pylons may overhang 12 inches maximum from 27 inches to 80 inches above the ground or finished floor. Standards §§ 4.1.2(3), 4.4.
c. Toilet Rooms: All of the toilet room doors require more than five pounds of force to operate. Provide a door that requires no more than 5 pounds of force to open. Standards §§ 4.1.3(7)(b), 4.13.11(2)(b).
4. By December 31, 2008,, the City will complete the following modifications to the Millard Library, located at 13214 Westwood Lane:
a. Parking: Although there are 127 parking spaces with 5 spaces designated as reserved for people with disabilities, the vertical signs designating the reserved spaces can be obstructed by parked vehicles. At each space designated as reserved for persons with disabilities, provide a vertical sign with the International Symbol of Accessibility located such that it cannot be obstructed by vehicles parked in the space. Standards §§ 4.1.2(5), 4.6.4, 4.30.7(1).
b. Public Telephone: The public telephone lacks volume control. Provide an accessible telephone with a clear floor space of at least 30 inches by 48 inches that allows either a forward or parallel approach by a person using a wheelchair such that bases, enclosures, and fixed seats do not impede approaches to the telephone; with the highest operable part of the telephone mounted no more than 48 inches above the floor for a front approach or no more than 54 inches above the floor for a side approach; that is hearing aid compatible and has a volume control mechanism; with telephone books, if provided, located between 15 and 48 inches above the finished floor for a front approach or between 9 and 54 inches above the finished floor for a side approach; with a cord of at least 29 inches long from the telephone to the handset; and with signage that complies with the Standards. Standards §§ 4.1.3(17), 4.31, 4.30.7(2).
c. Drinking Fountains: Both drinking fountains near the lobby toilet rooms are protruding objects that are not cane-detectable. Provide an accessible route at this location such that no objects with their bottom leading edges measuring between 27 inches and 80 inches above the finished floor protrude more than 4 inches into walks, halls, corridors, passageways, or aisles. Free-standing objects mounted on posts or pylons may overhang 12 inches maximum from 27 inches to 80 inches above the ground or finished floor. Standards §§ 4.1.2(3), 4.4.
d. Unisex, Single-User Toilet Room
i. Although an audible alarm is provided in this facility, there is no visual alarm appliance in the toilet room. Provide a visual alarm appliance in the toilet room. Standards §§ 4.1.3(14), 4.28.1, 4.28.3.
ii. The door swings into the required clear floor space in front of the lavatory. Ensure that no door swings into the required clear floor space at any accessible fixture. Standards §§ 4.1.3(11), 4.22.2. Standards §§ 9.6. 4.1
iii. The distance of the farther end of the side grab bar to the rear wall is 48 inches. Provide a side grab bar that is at least 42 inches in overall length, with the far end mounted at least 54 inches from the rear wall and the closer end 12 inches or less from the rear wall. Standards §§ 4.1.3(11), 4.22.4, 4.16.4, Fig. 29(b).
e. Men's and Women's Toilet Rooms with Stalls (Lobby)
i. The bottom leading edge of the air dryer is greater than 27 inches above the finished floor, it extends more than 4 inches into the path of travel, and it is, therefore, a protruding object. Provide an accessible route at this location such that no objects with their bottom leading edges measuring between 27 inches and 80 inches above the finished floor protrude more than 4 inches into walks, halls, corridors, passageways, or aisles. Free-standing objects mounted on posts or pylons may overhang 12 inches maximum from 27 inches to 80 inches above the ground or finished floor. Standards §§ 4.1.2(3), 4.4.
ii. Toilet Stall for People Who Use Wheelchairs
(1) The coat hook is inaccessible. Provide a coat hook at a maximum height above the finished floor of 48 inches for a forward approach or 54 inches for a side approach and that is accompanied by clear floor space of 30 by 48 inches that allows a forward or parallel approach by a person using a wheelchair. Standards §§ 4.1.3(12)(a), 4.25.2, 4.25.3, 4.2.4, 4.2.5, 4.2.6.
(2) The distance of the further end of the side grab bar to the rear wall is 42 inches (Women's)/ 47 inches (Men's). Provide a side grab bar that is at least 40 inches in overall length, with the far end mounted at least 52 inches from the rear wall and the closer end 12 inches or less from the rear wall. Standards §§ 4.1.3(11), 4.22.4, 4.17.6, Figs. 30(a), (d).
iii. Men's Only: The pressure required to open the door is 9 pounds of force. Provide a door that requires no more than 5 pounds of force to open. Standards §§ 4.1.3(7)(b), 4.13.11(2)(b).
5. By December 31, 2013, the City will complete the following modifications to the Household Hazardous Waste Building, located at 120 & H Street:
a. The slope of the sidewalk ramp from the parking to the entrance exceeds 1:12 in some portions and no handrails are provided. Provide a ramp that is at least 36 inches wide and has a slope not exceeding 1:12 and a cross slope not exceeding 1:50. Provide level landings at the top and bottom of the ramp that are at least as wide as the ramp and at least 60 inches long. If the ramp changes direction, provide a level landing measuring at least 60 inches by 60 inches at the change in direction. On both sides of the ramp, provide handrails between 1¼ inches and 1½ inches in diameter with a continuous gripping surface. Ensure that the handrails extend at least 12 inches beyond the top and bottom of the ramp parallel with the ground surface, that they are mounted between 34 inches and 38 inches above the ramp surface, that they will not rotate within their fittings, and that they have ends that are rounded or return smoothly to floor, wall, or post. Provide edge protection that is at least 2 inches high at the ramp's drop off sides. Ensure that the ramp and its level landing at the top and bottom are designed and maintained so that water does not accumulate on walking surfaces. Standards §§ 4.1.2(1), 4.1.2(2), 4.3.8, 4.8.
b. Permanent Rooms Signage: The permanent room signs throughout the facility are mounted on the doors, rather than on the walls to the latch side of the doors. Provide permanent room signage with upper case, sans serif or simple serif type letters and numerals, meeting the requirements of the Standards for character height, raised characters, finish and contrast, accompanied by Grade 2 Braille; mounted on the wall adjacent to the latch side of the door or on the nearest adjacent wall at a height of 60 inches above the finished floor to the centerline of the sign; and located so that a person may approach within 3 inches of the signage without encountering protruding objects or standing within the swing of a door. Standards §§ 4.1.2(7), 4.30.1, 4.30.4, 4.30.5, 4.30.6.
c. Men's, Women's, and Unisex Single-User Toilet Rooms. For each:
i. The toilet room sign is not mounted on the wall on the latch side of the door. Provide a toilet room sign with raised and Braille characters. The sign shall be mounted on the wall adjacent to the latch side of the door with the centerline of the sign at 60 inches above the finished floor and situated such that a person can approach within 3 inches of the sign without encountering an obstruction or standing within a door swing. Standards §§ 4.1.2(7)(d), 4.30.1, 4.30.4, 4.30.5, 4.30.6.
ii. Women's and Unisex Only: The toilet flush control valve is on the closed side. Provide a flush control mounted on the "open" side of the toilet's clear floor space; 44 inches or less above the finished floor; and requiring a maximum of 5 pounds of force to operate; or provide an automatic flush device. Standards §§ 4.1.3(11), 4.22.4, 4.16.5, 4.27.4.
d. Shower Room: The towel hooks are too high. Provide a towel hook at a maximum height above the finished floor of 48 inches for a forward approach or 54 inches for a side approach and that is accompanied by clear floor space of 30 by 48 inches that allows a forward or parallel approach by a person using a wheelchair. Standards §§ 4.1.3(12)(a), 4.25.2, 4.25.3, 4.2.4, 4.2.5, 4.2.6.
6. By December 31, 2013, the City will complete the following modifications to the Southwest Street Maintenance Facility, located at 4040 S. 96th Street:
a. Entrance: The pressure required to open the interior door in the main entrance vestibule is 14 pounds of force. Provide a door that requires no more than 5 pounds of force to open. Standards §§ 4.1.3(7)(b), 4.13.11(2)(b).
b. Although an accessible drinking fountain is provided, there is no drinking fountain provided for people who have difficulty bending or stooping. Provide a drinking fountain that is accessible to people who have difficulty bending or stooping. This can be accommodated by the use of a "hi-lo" fountain; by providing one fountain accessible to those who use wheelchairs and one fountain at a standard height convenient for those who have difficulty bending; by providing a fountain accessible to people who use wheelchairs and a cup dispenser, or by such other means as would achieve the required accessibility for each group of people. Standards § 4.1.3(10)(a).
c. Men's and Women's Locker Rooms. For each:
i. More than 5 pounds of force is required to operate the door. Provide a door that requires no more than 5 pounds of force to open. Standards §§ 4.1.3(7)(b), 4.13.11(2)(b).
ii. The bottom leading edge of the white paper towel dispenser by the sink is 53 inches above the finished floor, it extends 9 inches into the path of travel, and it is, therefore, a protruding object. Provide an accessible route at this location such that no objects with their bottom leading edges measuring between 27 inches and 80 inches above the finished floor protrude more than 4 inches into walks, halls, corridors, passageways, or aisles. Free-standing objects mounted on posts or pylons may overhang 12 inches maximum from 27 inches to 80 inches above the ground or finished floor. Standards §§ 4.1.2(3), 4.4.
iii. Toilet Stall for Persons with Disabilities
(1) No accessible coat hook has been provided. Provide a coat hook at a maximum height above the finished floor of 48 inches for a forward approach or 54 inches for a side approach and that is accompanied by clear floor space of 30 by 48 inches that allows a forward or parallel approach by a person using a wheelchair. Standards §§ 4.1.3(12)(a), 4.25.2, 4.25.3, 4.2.4, 4.2.5, 4.2.6.
(2) The distance of the closer end of the rear grab bar to the side wall is 11 inches and, in the women's, its height is 37 inches above the finished floor. Provide a rear grab bar that is at least 36 inches in overall length with the closer end no more than 6 inches from the side wall. Standards §§ 4.1.3(11), 4.22.4, 4.17.6, Fig. 30.
iv. Shower Stall: In the transfer shower stall, the overhang at the transfer seat is 4 only inches and the curb is 1 inch. Provide a shower in this room that is exactly 36 inches wide and 36 inches deep with a 48 inch long and 36 inch wide clear floor space alongside the shower opening, and an L-shaped shower seat mounted on the wall opposite the controls and extending the full depth of the stall; OR a shower that is at least 30 inches deep and 60 inches wide with no curb or threshold and with a 36 inch deep and 60 inch wide clear floor space at the shower opening. Ensure that the shower has grab bars, controls, a shower spray unit, and a seat, curb, and enclosure, if provided, that comply fully with the Standards and with Figs. 35, 36, and 37, as applicable. Standards §§ 4.1.3(11), 4.21, Figs. 35, 36, 37.
v. The Locker Area
(1) The bench is only 13 inches deep. Provide a 24 inch by 48 inch bench fixed to the wall along the bench's longer dimension. Ensure that the bench has sufficient structural strength and is mounted with its surface between 17 inches and 19 inches above the finished floor. Provide clear floor space alongside the bench to allow a person using a wheelchair to make a parallel transfer onto the bench. Standards §§ 4.1.3(21), 4.35.4, 4.26.3.
(2) Women's Only: The opening mechanism on the lockers is 57 inches above the finished floor and requires a person to reach over the 13 inch wide bench. Provide a locker with the controls a maximum height above the finished floor of 48 inches for a forward approach or 54 inches for a side approach and that is accompanied by clear floor space of 30 by 48 inches that allows a forward or parallel approach by a person using a wheelchair. Standards §§ 4.1.3(13), 4.27.2, 4.27.3, 4.2.4, 4.2.5, 4.2.6, Fig. 4.
d. The time punch card reader and the badge reader opposite the men's locker room are protruding objects, with the time punch card having a bottom leading edge 47 inches above the finished floor and protruding out 10 inches, and the badge reader having a bottom leading edge 50 inches above the finished floor and protruding out 8 inches. Provide an accessible route at this location such that no objects with their bottom leading edges measuring between 27 inches and 80 inches above the finished floor protrude more than 4 inches into walks, halls, corridors, passageways, or aisles. Free-standing objects mounted on posts or pylons may overhang 12 inches maximum from 27 inches to 80 inches above the ground or finished floor. Standards §§ 4.1.2(3), 4.4.
7. By December 31, 2014, the City will complete the following modifications to the Park Maintenance Building, located at Lewis and Clark Landing:
a. No parking is designated as reserved for persons with disabilities. On the shortest accessible route to the accessible entrance, provide one van accessible space designated as reserved for people with disabilities. Ensure that van accessible spaces are a minimum of 96 inches wide and served by access aisles at least 96 inches wide. At all spaces designated as reserved for persons with disabilities, provide vertical signs with the International Symbol of Accessibility located such that they cannot be obstructed by parked vehicles. At van accessible spaces, provide an additional "Van-Accessible" sign located below the International Symbol of Accessibility. Ensure that all spaces and access aisles for persons with disabilities are flat and level, with slopes and cross-slopes not exceeding 1:50 in all directions, and that their surfaces are firm, stable, and slip-resistant. Standards §§ 4.1.2(5), 4.6, 4.30.7(1).
b. Unisex, Single-User Toilet Room
i. The pressure required to open the door is 12 pounds of force. Provide a door that requires no more than 5 pounds of force to open. Standards §§ 4.1.3(7)(b), 4.13.11(2)(b).
ii. The toilet centerline is 20 inches from the side wall. Provide a toilet with a centerline that measures 18 inches from the near side wall. Standards §§ 4.1.3(11), 4.22.4, 4.16.2, Fig. 28.
c. The time punch card reader is a protruding object, with a bottom leading edge 45 inches above the finished floor and protruding out 8 inches. Provide an accessible route at this location such that no objects with their bottom leading edges measuring between 27 inches and 80 inches above the finished floor protrude more than 4 inches into walks, halls, corridors, passageways, or aisles. Free-standing objects mounted on posts or pylons may overhang 12 inches maximum from 27 inches to 80 inches above the ground or finished floor. Standards §§ 4.1.2(3), 4.4.
8. By December 31, 2011, the City will complete the following modifications to the Columbus Park Community Center, located at 1515 S. 24th Street:
a. Parking: The parking space designated as "van-accessible" is 93 inches wide with an 88 inch wide access aisle. Neither the space nor the access aisle is level. For the remaining three spaces designated as reserved for persons with disabilities, two of the spaces are narrower than 96 inches, some of the spaces and some of the access aisles are not level because they contain built-up curb ramps, and one of the spaces lacks a vertical sign with the International Symbol of Access. On the shortest accessible route to the accessible entrance, provide a van accessible space and three standard accessible spaces designated as reserved for people with disabilities. Ensure that van accessible spaces are a minimum of 96 inches wide and served by access aisles at least 96 inches wide. At all spaces designated as reserved for persons with disabilities, provide vertical signs with the International Symbol of Accessibility located such that they cannot be obstructed by parked vehicles. At van accessible spaces, provide an additional "Van-Accessible" sign located below the International Symbol of Accessibility. Ensure that all spaces and access aisles for persons with disabilities are flat and level, with slopes and cross-slopes not exceeding 1:50 in all directions, and that their surfaces are firm, stable, and slip-resistant. Standards §§ 4.1.2(5), 4.6, 4.30.7(1).
b. Entrance: The interior door requires more than 5 pounds of force to operate. Provide a door that requires no more than 5 pounds of force to open. Standards §§ 4.1.3(7)(b), 4.13.11(2)(b).
c. Drinking Fountains Near Toilet Room and Gym: Although an accessible drinking fountain is provided, there is no drinking fountain provided for people who have difficulty bending or stooping. Provide a drinking fountain that is accessible to people who have difficulty bending or stooping. This can be accommodated by the use of a "hi-lo" fountain; by providing one fountain accessible to those who use wheelchairs and one fountain at a standard height convenient for those who have difficulty bending; by providing a fountain accessible to people who use wheelchairs and a cup dispenser, or by such other means as would achieve the required accessibility for each group of people. Standards § 4.1.3(10)(a).
d. Men's and Women's Locker Rooms
i. The centerline of the sign is 68 inches above the finished floor. Provide a room sign with raised and Braille characters. The sign shall be mounted on the wall adjacent to the latch side of the door with the centerline of the sign at 60 inches above the finished floor and situated such that a person can approach within 3 inches of the sign without encountering an obstruction or standing within a door swing. Standards §§ 4.1.2(7)(d), 4.30.1, 4.30.4, 4.30.5, 4.30.6.
ii. Men's Only: The pressure required to open the door is 8 pounds of force. Provide a door that requires no more than 5 pounds of force to open. Standards §§ 4.1.3(7)(b), 4.13.11(2)(b).
iii. The air dryer and, in the women's locker room, the sanitary napkin dispensers, are protruding objects that are not cane-detectable. Provide an accessible route at this location such that no objects with their bottom leading edges measuring between 27 inches and 80 inches above the finished floor protrude more than 4 inches into walks, halls, corridors, passageways, or aisles. Free-standing objects mounted on posts or pylons may overhang 12 inches maximum from 27 inches to 80 inches above the ground or finished floor. Standards §§ 4.1.2(3), 4.4.
iv. The bottom edge of the lavatory apron is 28 inches above the finished floor. Provide a lavatory with the top of its rim or counter 34 inches or less above the finished floor; the bottom edge of the apron at least 29 inches above the finished floor; and knee and toe clearances that comply with Fig. 31. Standards §§ 4.1.3(11), 4.22.6, 4.19.2, Fig. 31.
v. Toilet Stall for Persons with Disabilities
(1) Men's Only:
(a) The toilet centerline is 17 inches from the side wall. Provide a toilet with a centerline that measures 18 inches from the near side wall. Standards §§ 4.1.3(11), 4.22.4, 4.17.3, Fig. 30.
(b) The flush control valve is on the closed side. Provide a flush control mounted on the "open" side of the toilet's clear floor space; 44 inches or less above the finished floor; and requiring a maximum of 5 pounds of force to operate; or provide an automatic flush device. Standards §§ 4.1.3(11), 4.22.4, 4.16.5, 4.17.2, 4.27.4.
(2) Women's Only:
(a) The coat hook is inaccessible. Provide a coat hook at a maximum height above the finished floor of 48 inches for a forward approach or 54 inches for a side approach and that is accompanied by clear floor space of 30 by 48 inches that allows a forward or parallel approach by a person using a wheelchair. Standards §§ 4.1.3(12)(a), 4.1.6(1)(b), 4.25.2, 4.25.3, 4.2.4, 4.2.5, 4.2.6.
(b) The far end of the side grab bar is 49 inches from the rear wall. Provide a side grab bar that is at least 40 inches in overall length, with the far end mounted at least 52 inches from the rear wall and the closer end 12 inches or less from the rear wall. Standards §§ 4.1.3(11), 4.22.4, 4.17.6, Figs. 30(a), (d).
vi. Transfer Shower Stall: The dimensions of the stall are not 36 inches by 36 inches, the grab bar is mounted at 32 inches above the finished floor and the transfer bench does not extend the full depth of the stall. Provide a shower in this room that is exactly 36 inches wide and 36 inches deep with a 48 inch long and 36 inch wide clear floor space alongside the shower opening, and an L-shaped shower seat mounted on the wall opposite the controls and extending the full depth of the stall; OR a shower that is at least 30 inches deep and 60 inches wide with no curb or threshold and with a 36 inch deep and 60 inch wide clear floor space at the shower opening. Ensure that the shower has grab bars, controls, a shower spray unit, and a seat, curb, and enclosure, if provided, that comply fully with the Standards and with Figs. 35, 36, and 37, as applicable. Standards §§ 4.1.3(11), 4.21, Figs. 35, 36, 37.
vii. No accessible towel hook has been provided. Provide a coat hook at a maximum height above the finished floor of 48 inches for a forward approach or 54 inches for a side approach and that is accompanied by clear floor space of 30 by 48 inches that allows a forward or parallel approach by a person using a wheelchair. Standards §§ 4.1.3(12)(a), 4.25.2, 4.25.3, 4.2.4, 4.2.5, 4.2.6.
viii. The bench is only 14 inches deep and 16 inches high. Provide a 24 inch by 48 inch bench fixed to the wall along the bench's longer dimension. Ensure that the bench has sufficient structural strength and is mounted with its surface between 17 inches and 19 inches above the finished floor. Provide clear floor space alongside the bench to allow a person using a wheelchair to make a parallel transfer onto the bench. Standards §§ 4.1.3(21), 4.35.4, 4.26.3.
ix. The locker hardware is inaccessible. Provide a locker with mechanical controls, if any, that can be operated with 5 pounds of force or less and that can be used with one hand and without tight grasping, pinching, or twisting of the wrist (lever-operated, push-type, and electronically controlled mechanisms are examples of acceptable designs). Standards §§ 4.1.3(13), 4.27.4.
9. By December 31, 2012, the City will complete the following modifications to Zorinsky Lake Recreation Area, located at 156th & F:
a. North Picnic Area off 156th Street
i. Parking: The parking lot has 99 spaces with 6 spaces designated as reserved for persons with disabilities, but no space is a "van accessible" space. On the shortest accessible route to the accessible entrance, provide one van accessible space and five standard spaces designated as reserved for people with disabilities. Standard accessible spaces shall be a minimum of 96 inches wide and served by access aisles at least 60 inches wide. Van accessible spaces shall be a minimum of 96 inches wide and served by access aisles at least 96 inches wide. All spaces designated as reserved for people with disabilities shall have vertical signs with the International Symbol of Accessibility located such that they cannot be obstructed by parked vehicles. Van accessible spaces shall have an additional "Van-Accessible" sign located below the International Symbol of Accessibility. Standards §§ 4.1.2(5), 4.6, 4.30.7(1).
ii. Picnic Shelters: Not all of the picnic shelters have accessible routes and signage. Provide accessible directional signage with the International Symbol of Accessibility at inaccessible picnic shelters indicating the location of the nearest accessible picnic shelter, and provide accessible signage with the International Symbol of Accessibility at all accessible picnic shelters. Standards §§ 4.1.2(7)(d), 4.1.6(3)(e)(iii), 4.30.1, 4.30.2, 4.30.3, 4.30.5, 4.30.7. To the extent that specific shelters may be reserved, institute a reservations policy that will enable parties with persons with disabilities to reserve the accessible shelters as a priority matter.
iii. Playground: There is no accessible route to the playground. Provide at least one accessible route within the boundary of the site connecting these elements that, to the maximum extent feasible, coincides with the route for the general public. The accessible route must have a minimum clear width of 36 inches, or a minimum clear width of 42 inches if there is a turn around an obstruction less than 48 inches wide; have passing spaces at least 60 inches by 60 inches at least every 200 feet; have a minimum clear headroom of 80 inches; have a surface that is firm, stable, and slip resistant; have, in the absence of a curb ramp, ramp, elevator, or platform lift, no level changes in excess of ½ inch vertically; and have a running slope of less than 1:20 (5%) (or have been constructed as a fully accessible ramp) and a cross slope of less than 1:50 (2%). Standards §§ 4.1.3(1), 4.3, 4.5, Fig. 7.
iv. Drinking Fountains
(1) Near Play Area: Although an accessible drinking fountain is provided, there is no drinking fountain provided for people who have difficulty bending or stooping. Provide a drinking fountain that is accessible to people who have difficulty bending or stooping. This can be accommodated by the use of a "hi-lo" fountain; by providing one fountain accessible to those who use wheelchairs and one fountain at a standard height convenient for those who have difficulty bending; by providing a fountain accessible to people who use wheelchairs and a cup dispenser, or by such other means as would achieve the required accessibility for each group of people. Standards § 4.1.3(10)(a).
(2) Near Rest Room
(a) The controls were missing and therefore no determination about their function could be made. Provide a drinking fountain with controls mounted on or near the front edge that are operable with one hand, that require 5 pounds of force or less to operate, and that can be operated without tight grasping, pinching, or twisting of the wrist. Standards §§ 4.1.3(10), 4.15.4, 4.27.4.
(b) No drinking fountain is provided for people with trouble bending or stooping. Provide a drinking fountain that is accessible to people who have difficulty bending or stooping. This can be accommodated by the use of a "hi-lo" fountain; by providing one fountain accessible to those who use wheelchairs and one fountain at a standard height convenient for those who have difficulty bending; by providing a fountain accessible to people who use wheelchairs and a cup dispenser, or by such other means as would achieve the required accessibility for each group of people. Standards § 4.1.3(10)(a).
(c) The bottom leading edge of the drinking fountain is 29 ½ inches from the finished floor, it extends 19 inches into the path of travel, and it is, therefore, a protruding object. Provide an accessible route at this location such that no objects with their bottom leading edges measuring between 27 inches and 80 inches above the finished floor protrude more than 4 inches into walks, halls, corridors, passageways, or aisles. Free-standing objects mounted on posts or pylons may overhang 12 inches maximum from 27 inches to 80 inches above the ground or finished floor. Standards §§ 4.1.2(3), 4.4.
v. The portable toilet provided for use during the winter when the main toilet rooms are closed is not accessible to persons with disabilities. Provide an accessible portable toilet on an accessible route such that all of its elements, including signage, door, door hardware, clear floor space, water closet, urinal (if provided), grab bars, lavatory, mirror, controls, and dispensers, comply with the Standards. Standards §§ 4.1.3(11), 4.22, 4.13, 4.16, 4.18, 4.19, 4.26, 4.27, 4.30, Figs. 28, 29.
vi. Men's and Women's Toilet Rooms with Stalls. For each:
(1) The route to the toilet room building has a 1 inch change in level where the concrete pad joins the sidewalk. Provide at least one accessible route within the boundary of the site connecting these elements that, to the maximum extent feasible, coincides with the route for the general public. The accessible route must have a minimum clear width of 36 inches, or a minimum clear width of 42 inches if there is a turn around an obstruction less than 48 inches wide; have passing spaces at least 60 inches by 60 inches at least every 200 feet; have a minimum clear headroom of 80 inches; have a surface that is firm, stable, and slip resistant; have, in the absence of a curb ramp, ramp, elevator, or platform lift, no level changes in excess of ½ inch vertically; and have a running slope of less than 1:20 (5%) (or have been constructed as a fully accessible ramp) and a cross slope of less than 1:50 (2%). Standards §§ 4.1.3(1), 4.3, 4.5, Fig. 7.
(2) The sign to the toilet room is not mounted on the latch side of the door, the centerline is not 60 inches above the finished floor, and the sign lacks raised and Braille characters. Provide a toilet room sign with raised and Braille characters. The sign shall be mounted on the wall adjacent to the latch side of the door with the centerline of the sign at 60 inches above the finished floor and situated such that a person can approach within 3 inches of the sign without encountering an obstruction or standing within a door swing. Standards §§ 4.1.2(7)(d), 4.30.1, 4.30.4, 4.30.5, 4.30.6.
(3) The air dryer is a protruding object that is not cane-detectable. Provide an accessible route at this location such that no objects with their bottom leading edges measuring between 27 inches and 80 inches above the finished floor protrude more than 4 inches into walks, halls, corridors, passageways, or aisles. Free-standing objects mounted on posts or pylons may overhang 12 inches maximum from 27 inches to 80 inches above the ground or finished floor. Standards §§ 4.1.2(3), 4.4.
(4) In the toilet stall for wheelchair users, the farthest toilet paper dispenser is centered 39 inches from the rear wall. Provide a toilet paper dispenser that is mounted with its top at least 1½ inches under the side grab bar and 36 inches or less from the rear wall and is centered at least 19 inches above the finished floor. Standards §§ 4.1.3(11), 4.22.4, 4.17.3, Fig. 30(d).
(5) Men's Only: Although there are two urinals, there is no lower urinal. Provide a urinal with an elongated rim mounted 17 inches or less above the finished floor, a clear floor space of at least 30 inches wide and 48 inches deep centered on the urinal, and a flush control height of 44 inches or less above the finished floor. Standards §§ 4.1.3(11), 4.22.5, 4.18.2, 4.18.3, 4.18.4.
b. South Picnic and Boating Area
i. Boat Area / Picnic Shelter # 5: None of the 67 parking spaces is designated with "van accessible" signage and 2 of the existing spaces designated for persons with disabilities have no access aisles. On the shortest accessible route to the accessible entrance, provide one van accessible space designated as reserved for people with disabilities. Ensure that van accessible spaces are a minimum of 96 inches wide and served by access aisles at least 96 inches wide. At all spaces designated as reserved for persons with disabilities, provide vertical signs with the International Symbol of Accessibility located such that they cannot be obstructed by parked vehicles. At van accessible spaces, provide an additional "Van-Accessible" sign located below the International Symbol of Accessibility. Ensure that all spaces and access aisles for persons with disabilities are flat and level, with slopes and cross-slopes not exceeding 1:50 in all directions, and that their surfaces are firm, stable, and slip-resistant. Standards §§ 4.1.2(5), 4.6, 4.30.7(1).
ii. Ramp from Boat and Picnic Area Parking: From the Northeastern parking spaces designated as reserved for persons with disabilities, the slope of the route is such that the route is considered a ramp. Provide a ramp that is at least 36 inches wide and has a slope not exceeding 1:12 and a cross slope not exceeding 1:50. Provide level landings at the top and bottom of the ramp that are at least as wide as the ramp and at least 60 inches long. If the ramp changes direction, provide a level landing measuring at least 60 inches by 60 inches at the change in direction. On both sides of the ramp, provide handrails between 1¼ inches and 1½ inches in diameter with a continuous gripping surface. Ensure that the handrails extend at least 12 inches beyond the top and bottom of the ramp parallel with the ground surface, that they are mounted between 34 inches and 38 inches above the ramp surface, that they will not rotate within their fittings, and that they have ends that are rounded or return smoothly to floor, wall, or post. Provide edge protection that is at least 2 inches high at the ramp's drop off sides. Ensure that the ramp and its level landing at the top and bottom are designed and maintained so that water does not accumulate on walking surfaces. Standards §§ 4.1.2(1), 4.1.2(2), 4.3.8, 4.8.
iii. Picnic Shelter No. 5 has 3 picnic tables, none of which are accessible to people who use wheelchairs. Provide at least one picnic table on an accessible route such that there is knee space at the table at least 27 inches high, 30 inches wide, and 19 inches deep, and such that the height of the top of the table is between 28 inches and 34 inches above the ground. Standards §§ 4.1.3(18), 4.32.3, 4.32.4.
iv. There are no accessible routes to the barbeques at Picnic Shelter No. 5 or on the path to the fishing pier. Provide at least one accessible route within the boundary of the site connecting these elements that, to the maximum extent feasible, coincides with the route for the general public. The accessible route must have a minimum clear width of 36 inches, or a minimum clear width of 42 inches if there is a turn around an obstruction less than 48 inches wide; have passing spaces at least 60 inches by 60 inches at least every 200 feet; have a minimum clear headroom of 80 inches; have a surface that is firm, stable, and slip resistant; have, in the absence of a curb ramp, ramp, elevator, or platform lift, no level changes in excess of ½ inch vertically; and have a running slope of less than 1:20 (5%) (or have been constructed as a fully accessible ramp) and a cross slope of less than 1:50 (2%). Standards §§ 4.1.3(1), 4.3, 4.5, Fig. 7.
v. The portable toilet provided for use during the winter when the main toilet rooms are closed is not accessible to persons with disabilities. Provide an accessible portable toilet on an accessible route such that all of its elements, including signage, door, door hardware, clear floor space, water closet, urinal (if provided), grab bars, lavatory, mirror, controls, and dispensers, comply with the Standards. Standards §§ 4.1.3(11), 4.22, 4.13, 4.16, 4.18, 4.19, 4.26, 4.27, 4.30, Figs. 28, 29.
vi. Although an accessible drinking fountain is provided, there is no drinking fountain provided for people who have difficulty bending or stooping. Provide a drinking fountain that is accessible to people who have difficulty bending or stooping. This can be accommodated by the use of a "hi-lo" fountain; by providing one fountain accessible to those who use wheelchairs and one fountain at a standard height convenient for those who have difficulty bending; by providing a fountain accessible to people who use wheelchairs and a cup dispenser, or by such other means as would achieve the required accessibility for each group of people. Standards § 4.1.3(10)(a).
vii. Men's and Women's Toilet Rooms with Stalls Near Picnic Shelter No. 5. For each:
(1) The sign to the toilet room is not mounted on the latch side of the door, the centerline is not 60 inches above the finished floor, and it lacks raised and Braille characters. Provide a toilet room sign with raised and Braille characters. The sign shall be mounted on the wall adjacent to the latch side of the door with the centerline of the sign at 60 inches above the finished floor and situated such that a person can approach within 3 inches of the sign without encountering an obstruction or standing within a door swing. Standards §§ 4.1.2(7)(d), 4.30.1, 4.30.4, 4.30.5, 4.30.6.
(2) The air dryers are protruding objects. Provide an accessible route at this location such that no objects with their bottom leading edges measuring between 27 inches and 80 inches above the finished floor protrude more than 4 inches into walks, halls, corridors, passageways, or aisles. Free-standing objects mounted on posts or pylons may overhang 12 inches maximum from 27 inches to 80 inches above the ground or finished floor. Standards §§ 4.1.2(3), 4.4.
(3) Toilet Stall for Wheelchair Users
(a) No accessible coat hook has been provided. Provide a coat hook at a maximum height above the finished floor of 48 inches for a forward approach or 54 inches for a side approach and that is accompanied by clear floor space of 30 by 48 inches that allows a forward or parallel approach by a person using a wheelchair. Standards §§ 4.1.3(12)(a), 4.25.2, 4.25.3, 4.2.4, 4.2.5, 4.2.6.
(b) The side grab bar is 37 inches above the finished floor. Provide grab bars that are mounted between 33 and 36 inches above the finished floor. Standards §§ 4.1.3(11), 4.22.4, 4.17.6, Fig. 30.
(c) The stall door hardware requires tight grasping and pinching. Provide a door with hardware usable with one hand and without tight grasping, pinching, or twisting of the wrist. Lever-operated, push-type, and U-shaped handles are acceptable designs. Standards §§ 4.1.3(11), 4.22.2, 4.13.9.
(4) Men's Only: Although there are two urinals, there is no lower urinal with an elongated rim. Provide a urinal with an elongated rim mounted 17 inches or less above the finished floor, a clear floor space of at least 30 inches wide and 48 inches deep centered on the urinal, and a flush control height of 44 inches or less above the finished floor. Standards §§ 4.1.3(11), 4.22.5, 4.18.2, 4.18.3, 4.18.4.
c. South Soccer Fields: There are three parking lots have 45, 40, and 54 spaces respectively, but no spaces are provided for persons with disabilities. On the shortest accessible route to the accessible entrance of each of these soccer fields, provide at least one van accessible space and one standard space designated as reserved for people with disabilities. Ensure that van accessible spaces are a minimum of 96 inches wide and served by access aisles at least 96 inches wide and standard accessible spaces are 96 inches wide and served by access aisles at least 60 inches wide. At all spaces designated as reserved for persons with disabilities, provide vertical signs with the International Symbol of Accessibility located such that they cannot be obstructed by parked vehicles. At van accessible spaces, provide an additional "Van-Accessible" sign located below the International Symbol of Accessibility. Ensure that all spaces and access aisles for persons with disabilities are flat and level, with slopes and cross-slopes not exceeding 1:50 in all directions, and that their surfaces are firm, stable, and slip-resistant. Standards §§ 4.1.2(5), 4.6, 4.30.7(1).
d. South Playground
i. Although there are 47 parking spaces, none are designated as reserved for persons with disabilities. On the shortest accessible route to the accessible entrance, provide one van accessible space and one standard space designated as reserved for people with disabilities. Standard accessible spaces shall be a minimum of 96 inches wide and served by access aisles at least 60 inches wide. Van accessible spaces shall be a minimum of 96 inches wide and served by access aisles at least 96 inches wide. All spaces designated as reserved for people with disabilities shall have vertical signs with the International Symbol of Accessibility located such that they cannot be obstructed by parked vehicles. Van accessible spaces shall have an additional "Van-Accessible" sign located below the International Symbol of Accessibility. Standards §§ 4.1.2(5), 4.6, 4.30.7(1).
ii. The route between the bridge and the parking spaces nearest the bridge has a 1-1/2 inch change in level at both ends of the bridge. Provide at least one accessible route within the boundary of the site connecting these elements that, to the maximum extent feasible, coincides with the route for the general public. The accessible route must have a minimum clear width of 36 inches, or a minimum clear width of 42 inches if there is a turn around an obstruction less than 48 inches wide; have passing spaces at least 60 inches by 60 inches at least every 200 feet; have a minimum clear headroom of 80 inches; have a surface that is firm, stable, and slip resistant; have, in the absence of a curb ramp, ramp, elevator, or platform lift, no level changes in excess of ½ inch vertically; and have a running slope of less than 1:20 (5%) (or have been constructed as a fully accessible ramp) and a cross slope of less than 1:50 (2%). Standards §§ 4.1.3(1), 4.3, 4.5, Fig. 7.
10. By December 31, 2008, the City will complete the following modifications to the Miller's Landing Park / River City Star:
a. There is no parking space with "van accessible" signage. At van accessible spaces, provide a "Van-Accessible" sign located below the International Symbol of Accessibility such that the sign cannot be obstructed by vehicles parked in the space. Standards §§ 4.1.2(5), 4.6.4, 4.30.7(1).
b. The ramp from the gift shop to the top of the stairs that lead to the boarding level has a slope that exceeds 1:12 at the bottom and there are no handrails. Provide a ramp that is at least 36 inches wide with a slope not exceeding 1:12 and a cross slope not exceeding 1:50; with level landings at least as wide as the ramp and 60 inches long at the top and bottom of the ramp; and with edge protection at least 2 inches high at the drop off sides. Provide handrails that are between 1¼ inches and 1½ inches in diameter with a continuous gripping surface along both sides of the ramp, extending at least 12 inches beyond the top and bottom of the ramp parallel with the ground surface. Ensure that handrails are mounted between 34 inches and 38 inches above the ramp surface, with ends rounded or returned smoothly to the floor, wall, or post, and that they do not rotate within their fittings. Ensure that the ramp and approaches are designed so that water will not accumulate on walking surfaces. Standards §§ 4.1.2(1), 4.1.2(2), 4.3.8, 4.8.
c. The handrails of the stairs from the upper landing to the boarding level are 39 inches above the finished floor. Provide handrails that are mounted between 34 inches and 38 inches above the ramp surface, with ends rounded or returned smoothly to the floor, wall, or post, and that they do not rotate within their fittings. Standards §§ 4.1.2(1), 4.1.2(2), 4.8.5.
d. The Gift Shop cash register counter is 40 inches above the finished floor. Provide a counter on an accessible route such that a portion of the counter is at least 36 inches wide and no more than 36 inches above the finished floor. Standards §§ 4.1.1(2), 7.2(1), 4.1.3(1), 4.3.
e. Drinking Fountains in Secure Courtyard and Unsecured Area. For each: The higher fountain's bottom edge is 32 inches from the finished floor, it extends 13 inches into the path of travel and is therefore a protruding object. Provide an accessible route at this location such that no objects with their bottom leading edges measuring between 27 inches and 80 inches above the finished floor protrude more than 4 inches into walks, halls, corridors, passageways, or aisles. Free-standing objects mounted on posts or pylons may overhang 12 inches maximum from 27 inches to 80 inches above the ground or finished floor. Standards §§ 4.1.2(3), 4.4.
f. Public Toilet Rooms (Secured Courtyard and Unsecure Area; Men's and Women's). For each:
i. Although an audible alarm is provided in this facility, there is no visual alarm appliance in the toilet room. Provide a visual alarm appliance in the toilet room. Standards §§ 4.1.3(14), 4.28.1, 4.28.3.
ii. In the toilet stall for wheelchair users, no accessible coat hook has been provided. Provide a coat hook at a maximum height above the finished floor of 48 inches for a forward approach or 54 inches for a side approach and that is accompanied by clear floor space of 30 by 48 inches that allows a forward or parallel approach by a person using a wheelchair. Standards §§ 4.1.3(12)(a), 4.25.2, 4.25.3, 4.2.4, 4.2.5, 4.2.6.
iii. Secure Courtyard and Unsecure Area/ Men's. For each:
(1) No accessible mirror has been provided. Provide a mirror with the bottom edge of its reflecting surface no more than 40 inches above the finished floor. Standards §§ 4.1.3(11), 4.22.6, 4.19.6.
(2) Toilet Stall for Wheelchair Users: The toilet centerline is 19-20 inches from the side wall. Provide a toilet with a centerline that measures 18 inches from the near side wall. Standards §§ 4.1.3(11), 4.22.4, 4.17.3, Fig. 30.
g. Employee Only, Unisex, Single-User Toilet Room (in Gift Shop behind cash register)
i. The toilet room lacks any signage. Provide a toilet room sign with raised and Braille characters. The sign shall be mounted on the wall adjacent to the latch side of the door with the centerline of the sign at 60 inches above the finished floor and situated such that a person can approach within 3 inches of the sign without encountering an obstruction or standing within a door swing. Standards §§ 4.1.2(7)(d), 4.30.1, 4.30.4, 4.30.5, 4.30.6.
ii. The pressure required to open the door is 21 pounds of force. Provide a door that requires no more than 5 pounds of force to open. Standards §§ 4.1.3(7)(b), 4.13.11(2)(b).
iii. The door to the toilet room swings into the required clear floor space of the lavatory. Ensure that no door swings into the required clear floor space at any accessible fixture. Standards §§ 4.1.3(11), 4.22.2. Alternatively, provide an accessible door lock.
iv. Although an audible alarm is provided in this facility, there is no visual alarm appliance in the toilet room. Provide a visual alarm appliance in the toilet room. Standards §§ 4.1.3(14), 4.28.1, 4.28.3.
v. No accessible mirror has been provided. Provide a mirror with the bottom edge of its reflecting surface no more than 40 inches above the finished floor. Standards §§ 4.1.3(11), 4.22.6, 4.19.6.
vi. No accessible coat hook has been provided. Provide a coat hook at a maximum height above the finished floor of 48 inches for a forward approach or 54 inches for a side approach and that is accompanied by clear floor space of 30 by 48 inches that allows a forward or parallel approach by a person using a wheelchair. Standards §§ 4.1.3(12)(a), 4.25.2, 4.25.3, 4.2.4, 4.2.5, 4.2.6.
11. By December 31, 2008, the City will complete the following modifications to Lewis & Clark Landing:
a. There is no accessible route from the main parking area across from Rick's Café to the waterside plaza; the route takes pedestrians down 14 steps. Provide at least one accessible route within the boundary of the site connecting these elements that, to the maximum extent feasible, coincides with the route for the general public. The accessible route must have a minimum clear width of 36 inches, or a minimum clear width of 42 inches if there is a turn around an obstruction less than 48 inches wide; have passing spaces at least 60 inches by 60 inches at least every 200 feet; have a minimum clear headroom of 80 inches; have a surface that is firm, stable, and slip resistant; have, in the absence of a curb ramp, ramp, elevator, or platform lift, no level changes in excess of ½ inch vertically; and have a running slope of less than 1:20 (5%) (or have been constructed as a fully accessible ramp) and a cross slope of less than 1:50 (2%). Standards §§ 4.1.3(1), 4.3, 4.5, Fig. 7.
b. The sidewalk between the accessible parking opposite the front of Rick's Café has no curb cut where it crosses the street. Provide a curb ramp that is at least 36 inches wide, has a maximum slope of 1:12, is located so that it cannot be obstructed by parked vehicles, and has a stable, firm, and slip-resistant surface with a detectable warning extending the full width and depth of the ramp. If the curb ramp is located where pedestrians must walk across it, provide either flared sides (with a maximum slope of 1:10) or handrails or guardrails to protect against cross traffic. Standards §§ 4.1.2(1), 4.1.2(2), 4.3.8, 4.7, Fig. 12.
c. The following ramps have the barriers listed below. For each, provide a ramp that is at least 36 inches wide and has a slope not exceeding 1:12 and a cross slope not exceeding 1:50. Provide level landings at the top and bottom of the ramp that are at least as wide as the ramp and at least 60 inches long. If the ramp changes direction, provide a level landing measuring at least 60 inches by 60 inches at the change in direction. On both sides of the ramp, provide handrails between 1¼ inches and 1½ inches in diameter with a continuous gripping surface. Ensure that the handrails extend at least 12 inches beyond the top and bottom of the ramp parallel with the ground surface, that they are mounted between 34 inches and 38 inches above the ramp surface, that they will not rotate within their fittings, and that they have ends that are rounded or return smoothly to floor, wall, or post. Provide edge protection that is at least 2 inches high at the ramp's drop off sides. Ensure that the ramp and its level landing at the top and bottom are designed and maintained so that water does not accumulate on walking surfaces. Standards §§ 4.1.2(1), 4.1.2(2), 4.3.8, 4.8.
i. Ramp Between Parking and Public Restrooms: The slope of the path at most points exceeds 1:12, it lacks handrails, the rise of the ramp exceeds 30 inches and there is no level landing to rest.
ii. Ramp to the Labor Monument (near river): The slope of the path at points exceeds 1:12, there is inadequate edge protection, the ramp lacks handrails on both sides for its entire span, and the handrails that are provided are 2 inches in diameter and 35 inches above the finished ramp surface.
iii. Ramp Opposite the Front Of Rick's Café Boatyard (non-river-side): The slope of the path at points exceeds 1:12 at points, it has inadequate edge protection and handrail extensions at its top and bottom, and the handrails are 2 inches in diameter.
d. Drinking fountains near public toilet rooms: The higher fountain is 33 inches above the finished floor and extends 12 inches into the path of travel and is therefore a protruding object. The lower fountain has a bottom leading edge that is higher than 27 inches above the finished floor and it extends 14 inches into the circulation path. Both are protruding objects that are not cane-detectable. Provide an accessible route at this location such that no objects with their bottom leading edges measuring between 27 inches and 80 inches above the finished floor protrude more than 4 inches into walks, halls, corridors, passageways, or aisles. Free-standing objects mounted on posts or pylons may overhang 12 inches maximum from 27 inches to 80 inches above the ground or finished floor. Standards §§ 4.1.2(3), 4.4.
e. Men's and Women's Public Toilet Rooms with Stalls for Park Patrons. For each:
i. The accessible sign to the toilet room is not mounted on the latch side of the door. Provide a toilet room sign with raised and Braille characters. The sign shall be mounted on the wall adjacent to the latch side of the door with the centerline of the sign at 60 inches above the finished floor and situated such that a person can approach within 3 inches of the sign without encountering an obstruction or standing within a door swing. Standards §§ 4.1.2(7)(d), 4.30.1, 4.30.4, 4.30.5, 4.30.6.
ii. The bottom leading edge of the paper towel dispenser is 48 inches above the finished floor, it extends 9 inches into the path of travel, and it is, therefore, a protruding object. Provide an accessible route at this location such that no objects with their bottom leading edges measuring between 27 inches and 80 inches above the finished floor protrude more than 4 inches into walks, halls, corridors, passageways, or aisles. Free-standing objects mounted on posts or pylons may overhang 12 inches maximum from 27 inches to 80 inches above the ground or finished floor. Standards §§ 4.1.2(3), 4.4.
iii. The paper towel dispenser is a vertical round roll which requires tight grasping, pinching or turning of the wrist to operate. Provide a paper towel dispenser with mechanical controls, if any, that can be operated with 5 pounds of force or less and that can be used with one hand and without tight grasping, pinching, or twisting of the wrist (lever-operated, push-type, and electronically controlled mechanisms are examples of acceptable designs). Standards §§ 4.1.3(13), 4.27.4.
iv. Toilet Stall for Persons with Disabilities
(1) The toilet centerline is 19-19 ½ inches from the side wall. Provide a toilet with a centerline that measures 18 inches from the near side wall. Standards §§ 4.1.3(11), 4.22.4, 4.17.3, Fig. 30.
(2) The distance of the toilet paper dispenser to the rear wall exceeds 36 inches. Provide a toilet paper dispenser that is mounted with its top at least 1½ inches under the side grab bar and 36 inches or less from the rear wall and is centered at least 19 inches above the finished floor. Standards §§ 4.1.3(11), 4.22.4, 4.17.3, Fig. 30(d).
(3) The distance of the farther end of the side grab bar to the rear wall is 47-50 inches. Provide a side grab bar that is at least 40 inches in overall length, with the far end mounted at least 52 inches from the rear wall and the closer end 12 inches or less from the rear wall. Standards §§ 4.1.3(11), 4.22.4, 4.17.6, Figs. 30(a), (d).
(4) Men's Only: The distance closer end of the rear grab bar to the side wall is 9 inches. Provide a rear grab bar that is at least 36 inches in overall length with the closer end no more than 6 inches from the side wall. Standards §§ 4.1.3(11), 4.22.4, 4.17.6, Fig. 30.
v. Women's Only: No accessible mirror has been provided. Provide a mirror with the bottom edge of its reflecting surface no more than 40 inches above the finished floor. Standards §§ 4.1.3(11), 4.22.6, 4.19.6.
12. By December 31, 2011, the City will complete the following modifications to Fire Station #3, located at 3126 S. 16th Street:
a. Upper Building
i. Although there are 12 parking spaces, the one space designated as reserved for persons with disabilities is 94 inches wide, it is not level, it lacks "van accessible" signage, and the access aisle is not level. On the shortest accessible route to the accessible entrance, provide one van accessible space designated as reserved for people with disabilities. Ensure that van accessible spaces are a minimum of 96 inches wide and served by access aisles at least 96 inches wide. At all spaces designated as reserved for persons with disabilities, provide vertical signs with the International Symbol of Accessibility located such that they cannot be obstructed by parked vehicles. At van accessible spaces, provide an additional "Van-Accessible" sign located below the International Symbol of Accessibility. Ensure that all spaces and access aisles for persons with disabilities are flat and level, with slopes and cross-slopes not exceeding 1:50 in all directions, and that their surfaces are firm, stable, and slip-resistant. Standards §§ 4.1.2(5), 4.6, 4.30.7(1).
ii. The interior entrance door requires 11 pounds of force to operate. Provide a door that requires no more than 5 pounds of force to open. Standards §§ 4.1.3(7)(b), 4.13.11(2)(b).
iii. Men's and Women's Single-User Toilet Rooms in Lobby. For each:
(1) No accessible coat hook has been provided. Provide a coat hook at a maximum height above the finished floor of 48 inches for a forward approach or 54 inches for a side approach and that is accompanied by clear floor space of 30 by 48 inches that allows a forward or parallel approach by a person using a wheelchair. Standards §§ 4.1.3(12)(a), 4.25.2, 4.25.3, 4.2.4, 4.2.5, 4.2.6.
(2) No accessible mirror has been provided. Provide a mirror with the bottom edge of its reflecting surface no more than 40 inches above the finished floor. Standards §§ 4.1.3(11), 4.22.6, 4.19.6.
(3) The bottom edge of the lavatory apron is 28 inches above the finished floor. Provide a lavatory with the top of its rim or counter 34 inches or less above the finished floor; the bottom edge of the apron at least 29 inches above the finished floor; and knee and toe clearances that comply with Fig. 31. Standards §§ 4.1.3(11), 4.22.6, 4.19.2, Fig. 31.
(4) The toilet flush control valve is on the closed side. Provide a flush control mounted on the "open" side of the toilet's clear floor space; 44 inches or less above the finished floor; and requiring a maximum of 5 pounds of force to operate; or provide an automatic flush device. Standards §§ 4.1.3(11), 4.22.4, 4.16.5, 4.27.4.
(5) Men's Only:
(a) The height of the side grab bar is 32 inches above the finished floor. Provide grab bars that are mounted between 33 and 36 inches above the finished floor. Standards §§ 4.1.3(11), 4.22.4, 4.16.4, Fig. 29.
(b) The distance of the farther end of the rear grab bar to the side wall is 38 inches. Provide a rear grab bar that is at least 36 inches in overall length with the closer end no more than 6 inches from the side wall. Standards §§ 4.1.3(11), 4.22.4, 4.16.4, Fig. 29.
b. Lower Building (Fire Investigations)
i. The van accessible parking reserved for persons with disabilities lacks the appropriate signage. At van accessible spaces, provide a "Van-Accessible" sign located below the International Symbol of Accessibility such that the sign cannot be obstructed by vehicles parked in the space. Standards §§ 4.1.2(5), 4.6.4, 4.30.7(1).
ii. The interior entrance door requires 14 pounds of force to operate. Provide a door that requires no more than 5 pounds of force to open. Standards §§ 4.1.3(7)(b), 4.13.11(2)(b).
iii. The permanent room signs lack raised and Braille characters and are not mounted on the wall to the latch side of the doors. Provide permanent room signage with upper case, sans serif or simple serif type letters and numerals, meeting the requirements of the Standards for character height, raised characters, finish and contrast, accompanied by Grade 2 Braille; mounted on the wall adjacent to the latch side of the door or on the nearest adjacent wall at a height of 60 inches above the finished floor to the centerline of the sign; and located so that a person may approach within 3 inches of the signage without encountering protruding objects or standing within the swing of a door. Standards §§ 4.1.2(7), 4.30.1, 4.30.4, 4.30.5, 4.30.6.
iv. Reception Area (Fire Investigation): The counter is 42 inches above the finished floor. Provide a counter on an accessible route such that a portion of the counter is at least 36 inches wide and no more than 36 inches above the finished floor, or provide an auxiliary counter with a maximum height of 36 inches in close proximity to the main counter, or provide equivalent facilitation. Equivalent facilitation may be provided in the form of a folding shelf attached to the main counter, an auxiliary table nearby, a clip board made available to the public, or other means. Standards §§ 4.1.1(2), 7.2(2), 4.1.3(1), 4.3.
c. Men's and Women's Single-User Toilet Rooms. For each:
i. The door swings into the required clear floor space at the lavatory. Ensure that no door swings into the required clear floor space at any accessible fixture. Standards §§ 4.1.3(11), 4.22.2.
ii. No accessible coat hook has been provided. Provide a coat hook at a maximum height above the finished floor of 48 inches for a forward approach or 54 inches for a side approach and that is accompanied by clear floor space of 30 by 48 inches that allows a forward or parallel approach by a person using a wheelchair. Standards §§ 4.1.3(12)(a), 4.25.2, 4.25.3, 4.2.4, 4.2.5, 4.2.6.
iii. No accessible mirror has been provided. Provide a mirror with the bottom edge of its reflecting surface no more than 40 inches above the finished floor. Standards §§ 4.1.3(11), 4.22.6, 4.19.6.
iv. The bottom edge of the lavatory apron is 27 ½-28 inches above the finished floor. Provide a lavatory with the top of its rim or counter 34 inches or less above the finished floor; the bottom edge of the apron at least 29 inches above the finished floor; and knee and toe clearances that comply with Fig. 31. Standards §§ 4.1.3(11), 4.22.6, 4.19.2, Fig. 31.
v. The toilet centerline is 19-19 ½ inches from the side wall. Provide a toilet with a centerline that measures 18 inches from the near side wall. Standards §§ 4.1.3(11), 4.22.4, 4.16.2, Fig. 28.
vi. Women's Only: The toilet flush control is on the closed side. Provide a flush control mounted on the "open" side of the toilet's clear floor space; 44 inches or less above the finished floor; and requiring a maximum of 5 pounds of force to operate; or provide an automatic flush device. Standards §§ 4.1.3(11), 4.22.4, 4.16.5, 4.27.4.
13. By December 31, 2011, the City will complete the following modifications to Fire Station #63, located at 16736 S. 16th Street:
a. Although there are 18 parking spaces with 2 designated as reserved for persons with disabilities, the space designated as van accessible has signage that can be obstructed by parked vehicles. At the van accessible space, provide a "Van-Accessible" sign located below the International Symbol of Accessibility such that the sign cannot be obstructed by vehicles parked in the space. Standards §§ 4.1.2(5), 4.6.4, 4.30.7(1).
b. Men's and Women's Single-User Toilet Rooms. For each:
i. The pressure required to open the door is 16 pounds of force. Provide a door that requires no more than 5 pounds of force to open. Standards §§ 4.1.3(7)(b), 4.13.11(2)(b).
ii. The distance of the farther end of the toilet's rear grab bar from the side wall is 40 inches. Provide a rear grab bar that is at least 36 inches in overall length with the closer end no more than 6 inches from the side wall. Standards §§ 4.1.3(11), 4.22.4, 4.16.4, Fig. 29.
iii. Women's Only: The distance end of the further end of the toilet's side grab bar to the rear wall is 49 inches from the side wall. Provide a side grab bar that is at least 42 inches in overall length, with the far end mounted at least 54 inches from the rear wall and the closer end 12 inches or less from the rear wall. Standards §§ 4.1.3(11), 4.22.4, 4.16.4, Fig. 29(b).
14. By December 31, 2011, the City will complete the following modifications to Fire Station #65, located at 7010 S. 142 Street:
a. Parking: Although there are 38 parking spaces with two spaces designated as reserved for persons with disabilities, the space designated as "van accessible" is 81 inches wide and the second designated space is 90 inches wide. On the shortest accessible route to the accessible entrance, provide one van accessible space and one standard space designated as reserved for people with disabilities. Ensure that standard accessible spaces are a minimum of 96 inches wide and served by access aisles at least 60 inches wide. Ensure that van accessible spaces are a minimum of 96 inches wide and served by access aisles at least 96 inches wide. At all spaces designated as reserved for persons with disabilities, provide vertical signs with the International Symbol of Accessibility located such that they cannot be obstructed by parked vehicles. At van accessible spaces, provide an additional "Van-Accessible" sign located below the International Symbol of Accessibility. Ensure that all spaces and access aisles for persons with disabilities are flat and level, with slopes and cross-slopes not exceeding 1:50 in all directions, and that their surfaces are firm, stable, and slip-resistant. Standards §§ 4.1.2(5), 4.6, 4.30.7(1).
b. The pressure required to open the interior door is 11 pounds of force. Provide a door that requires no more than 5 pounds of force to open. Standards §§ 4.1.3(7)(b), 4.13.11(2)(b).
c. Drinking Fountain (Main Hallway by Locker Rooms)
i. The spout height is 37 ½ inches above the finished floor. Provide a fountain that has a spout height no higher than 36 inches, measured from the finished floor or ground surface to the spout outlet, and that otherwise complies with the Standards. Standards §§ 4.1.3(10), 4.15, 4.27.4, Fig. 27.
ii. No drinking fountain is provided for people with trouble bending or stooping. Provide a drinking fountain that is accessible to people who have difficulty bending or stooping. This can be accommodated by the use of a "hi-lo" fountain; by providing one fountain accessible to those who use wheelchairs and one fountain at a standard height convenient for those who have difficulty bending; by providing a fountain accessible to people who use wheelchairs and a cup dispenser, or by such other means as would achieve the required accessibility for each group of people. Standards § 4.1.3(10)(a).
d. Men's and Women's Public Toilet Rooms with Stalls. For each:
i. The pressure required to open the door is 8-10 pounds of force. Provide a door that requires no more than 5 pounds of force to open. Standards §§ 4.1.3(7)(b), 4.13.11(2)(b).
ii. The Standard Accessible Stall for Wheelchair Users
(1) No accessible coat hook has been provided. Provide a coat hook at a maximum height above the finished floor of 48 inches for a forward approach or 54 inches for a side approach and that is accompanied by clear floor space of 30 by 48 inches that allows a forward or parallel approach by a person using a wheelchair. Standards §§ 4.1.3(12)(a), 4.25.2, 4.25.3, 4.2.4, 4.2.5, 4.2.6.
(2) Men's Only: The flush control valve is on the closed side. Provide a flush control mounted on the "open" side of the toilet's clear floor space; 44 inches or less above the finished floor; and requiring a maximum of 5 pounds of force to operate; or provide an automatic flush device. Standards §§ 4.1.3(11), 4.22.4, 4.16.5, 4.17.2, 4.27.4.
15. By December 31, 2008, the City will complete the following modifications to OmahaPark Four, located at 1011 Jackson Street:
a. Parking: Although there are 434 parking spaces in this garage, only 7 are designated as reserved for persons with disabilities; none of the designated spaces is among the 220 monthly parking spaces; most are less than 96 inches wide; none is designated as "van-accessible;" none is a covered space (though many of the inaccessible spaces are covered); and the vertical signage at each is very faded. On the shortest accessible route to the accessible entrance, provide 2 van accessible spaces and 7 standard spaces designated as reserved for people with disabilities. Ensure that standard accessible spaces are a minimum of 96 inches wide and served by access aisles at least 60 inches wide. Ensure that van accessible spaces are a minimum of 96 inches wide and served by access aisles at least 96 inches wide. At all spaces designated as reserved for persons with disabilities, provide vertical signs with the International Symbol of Accessibility located such that they cannot be obstructed by parked vehicles. At van accessible spaces, provide an additional "Van-Accessible" sign located below the International Symbol of Accessibility. Ensure that all spaces and access aisles for persons with disabilities are flat and level, with slopes and cross-slopes not exceeding 1:50 in all directions, and that their surfaces are firm, stable, and slip-resistant. Standards §§ 4.1.2(5), 4.6, 4.30.7(1).
16. By December 31, 2008, the City will complete the following modifications to the OmahaPark Five, located at 301 N. 19th Street:
a. Although 9 of the 454 parking spaces in this garage are designated as reserved for persons with disabilities, some of them are less than 96 inches wide and all have vertical signage that is easily obstructed by parked vehicles. On the shortest accessible route to the accessible entrance, provide 2 van accessible spaces and 7 standard spaces designated as reserved for people with disabilities. Ensure that standard accessible spaces are a minimum of 96 inches wide and served by access aisles at least 60 inches wide. Ensure that van accessible spaces are a minimum of 96 inches wide and served by access aisles at least 96 inches wide. At all spaces designated as reserved for persons with disabilities, provide vertical signs with the International Symbol of Accessibility located such that they cannot be obstructed by parked vehicles. At van accessible spaces, provide an additional "Van-Accessible" sign located below the International Symbol of Accessibility. Ensure that all spaces and access aisles for persons with disabilities are flat and level, with slopes and cross-slopes not exceeding 1:50 in all directions, and that their surfaces are firm, stable, and slip-resistant. Standards §§ 4.1.2(5), 4.6, 4.30.7(1).
b. Ramp to Door: Many areas of the ramp have a cross-slope exceeding the maximum allowable cross-slope for a ramp and there are no handrail extensions at the bottom of the ramp. Provide a ramp that is at least 36 inches wide with a slope not exceeding 1:12 and a cross slope not exceeding 1:50; with level landings at least as wide as the ramp and 60 inches long at the top and bottom of the ramp; and with edge protection at least 2 inches high at the drop off sides. Provide handrails that are between 1¼ inches and 1½ inches in diameter with a continuous gripping surface along both sides of the ramp, extending at least 12 inches beyond the top and bottom of the ramp parallel with the ground surface. Ensure that handrails are mounted between 34 inches and 38 inches above the ramp surface, with ends rounded or returned smoothly to the floor, wall, or post, and that they do not rotate within their fittings. Ensure that the ramp and approaches are designed so that water will not accumulate on walking surfaces. Standards §§ 4.1.2(1), 4.1.2(2), 4.3.8, 4.8.
17. By December 31, 2008, the City will complete the following modifications to the OmahaPark Six, located at 320 N. 17th Street:
a. Although 20 of the 955 parking spaces in this garage are designated as reserved for persons with disabilities, many designated spaces are narrower than 96 inches and all of the vertical signs designating accessible spaces are easily obstructed by parked vehicles. On the shortest accessible route(s), provide 3 van accessible spaces and 16 standard spaces designated as reserved for people with disabilities. Ensure that standard accessible spaces are a minimum of 96 inches wide and served by access aisles at least 60 inches wide. Ensure that van accessible spaces are a minimum of 96 inches wide and served by access aisles at least 96 inches wide. At all spaces designated as reserved for persons with disabilities, provide vertical signs with the International Symbol of Accessibility located such that they cannot be obstructed by parked vehicles. At van accessible spaces, provide an additional "Van-Accessible" sign located below the International Symbol of Accessibility. Ensure that all spaces and access aisles for persons with disabilities are flat and level, with slopes and cross-slopes not exceeding 1:50 in all directions, and that their surfaces are firm, stable, and slip-resistant. Standards §§ 4.1.2(5), 4.6, 4.30.7(1).
b. Elevators: The door protective and reopening devices are not working properly in either the West or East elevators. Provide doors that open and close automatically with a reopening device that will stop and reopen the car door and hoistway door automatically if the door becomes obstructed by an object or person. Ensure that the device is capable of completing these operations without requiring contact for obstructions passing through the opening at heights of 5 inches and 29 inches above the finished floor; that door reopening devices remain effective for at least 20 seconds, after which the doors may close; that the minimum time from notification that a car is answering a call until the doors of that car start to close is 5 seconds; and that the minimum time for elevator doors to remain fully open in response to a car call is 3 seconds. Standards §§ 4.1.3(5), 4.10.6, 4.10.7, 4.10.8, Figs. 20, 21.
c. Ramp on L-2: Near the middle of the ramp, the cross-slope exceeds the maximum allowable cross-slope for a ramp and there is 4 inches between the inside of one of the handrails and the side wall. Provide a ramp that is at least 36 inches wide with a slope not exceeding 1:12 and a cross slope not exceeding 1:50; with level landings at least as wide as the ramp and 60 inches long at the top and bottom of the ramp; and with edge protection at least 2 inches high at the drop off sides. Provide handrails that are between 1¼ inches and 1½ inches in diameter, exactly 1-1/2 inches from the side wall, with a continuous gripping surface along both sides of the ramp, extending at least 12 inches beyond the top and bottom of the ramp parallel with the ground surface. Ensure that handrails are mounted between 34 inches and 38 inches above the ramp surface, with ends rounded or returned smoothly to the floor, wall, or post, and that they do not rotate within their fittings. Ensure that the ramp and approaches are designed so that water will not accumulate on walking surfaces. Standards §§ 4.1.2(1), 4.1.2(2), 4.3.8, 4.8.
d. L-1 West Ramp: For portions of the ramp, the slope exceeds the maximum allowable slope of 1:12 and the handrail extensions at the top and bottom of the ramp are inadequate. Provide a ramp that is at least 36 inches wide with a slope not exceeding 1:12 and a cross slope not exceeding 1:50; with level landings at least as wide as the ramp and 60 inches long at the top and bottom of the ramp; and with edge protection at least 2 inches high at the drop off sides. Provide handrails that are between 1¼ inches and 1½ inches in diameter with a continuous gripping surface along both sides of the ramp, extending at least 12 inches beyond the top and bottom of the ramp parallel with the ground surface. Ensure that handrails are mounted between 34 inches and 38 inches above the ramp surface, with ends rounded or returned smoothly to the floor, wall, or post, and that they do not rotate within their fittings. Ensure that the ramp and approaches are designed so that water will not accumulate on walking surfaces. Standards §§ 4.1.2(1), 4.1.2(2), 4.3.8, 4.8.
18. By December 31, 2008, the City will complete the following modifications to the OmahaPark Seven, located at 100 N. 15th Street:
a. Although 14 of the 700 parking spaces in this garage are designated as reserved for persons with disabilities, many designated spaces are narrower than 96 inches and all of the vertical signs designating accessible spaces are easily obstructed by parked vehicles. On the shortest accessible route(s), provide 2 van accessible spaces and 12 standard spaces designated as reserved for people with disabilities. Ensure that standard accessible spaces are a minimum of 96 inches wide and served by access aisles at least 60 inches wide. Ensure that van accessible spaces are a minimum of 96 inches wide and served by access aisles at least 96 inches wide. At all spaces designated as reserved for persons with disabilities, provide vertical signs with the International Symbol of Accessibility located such that they cannot be obstructed by parked vehicles. At van accessible spaces, provide an additional "Van-Accessible" sign located below the International Symbol of Accessibility. Ensure that all spaces and access aisles for persons with disabilities are flat and level, with slopes and cross-slopes not exceeding 1:50 in all directions, and that their surfaces are firm, stable, and slip-resistant. Standards §§ 4.1.2(5), 4.6, 4.30.7(1).
b. The fire extinguishers throughout the facility are mounted at 67 inches above the finished floor. Provide fire extinguishers mounted at a maximum height above the finished floor of 48 inches for a forward approach or 54 inches for a side approach and that is accompanied by clear floor space of 30 by 48 inches that allows a forward or parallel approach by a person using a wheelchair. Standards §§ 4.1.3(13), 4.27.2, 4.27.3, 4.2.4, 4.2.5, 4.2.6, Fig. 4.
c. On level L-8, the right-hand parking space designated for persons with disabilities encroaches upon the accessible route, so that if a car is parked in the space, there is not enough maneuvering clearance to get to the door to the elevator lobby. Provide an accessible route at this location with a minimum clear width of 36 inches, except at doors, where the width may decrease to 32 inches. Standards §§ 4.1.3(1), 4.3.3, 4.13.5.
d. East Elevator at South Tower: The audio component of the emergency communication system had too much interference and the recipient's instructions could not be understood; there was no way to determine if the emergency communications worked without voice communication. Provide a two-way communication system such that it does not require voice communication, the highest operable part is a maximum of 48 inches above the finished floor of the car, and it is identified by a raised symbol and lettering located adjacent to the device. If the system uses a handset, ensure that the length of the cord from the panel to the handset is at least 29 inches. If the system is located in a closed compartment, ensure that the compartment door hardware operates without tight grasping, pinching or twisting of the wrist. Standards §§ 4.1.3(5), 4.10.14.
e. Ramp at East Exit Level 1: The slope of the ramp exceeds the maximum allowable slope of 1:12, there are no handrails, and there is no level landing at the bottom of the ramp at the door. Provide a ramp that is at least 36 inches wide with a slope not exceeding 1:12 and a cross slope not exceeding 1:50; with level landings at least as wide as the ramp and 60 inches long at the top and bottom of the ramp; and with edge protection at least 2 inches high at the drop off sides. Provide handrails that are between 1¼ inches and 1½ inches in diameter with a continuous gripping surface along both sides of the ramp, extending at least 12 inches beyond the top and bottom of the ramp parallel with the ground surface. Ensure that handrails are mounted between 34 inches and 38 inches above the ramp surface, with ends rounded or returned smoothly to the floor, wall, or post, and that they do not rotate within their fittings. Ensure that the ramp and approaches are designed so that water will not accumulate on walking surfaces. Standards §§ 4.1.2(1), 4.1.2(2), 4.3.8, 4.8.
19. By December 31, 2008, the City will complete the following modifications to the OmahaPark Eight, located at 1215 Capital Entrance:
a. Although 26 of the 1270 parking spaces in this garage are designated as reserved for persons with disabilities, many designated spaces are narrower than 96 inches and all of the vertical signs designating accessible spaces are easily obstructed by parked vehicles. On the shortest accessible route(s), provide 3 van accessible spaces and 19 standard spaces designated as reserved for people with disabilities. Ensure that standard accessible spaces are a minimum of 96 inches wide and served by access aisles at least 60 inches wide. Ensure that van accessible spaces are a minimum of 96 inches wide and served by access aisles at least 96 inches wide. At all spaces designated as reserved for persons with disabilities, provide vertical signs with the International Symbol of Accessibility located such that they cannot be obstructed by parked vehicles. At van accessible spaces, provide an additional "Van-Accessible" sign located below the International Symbol of Accessibility. Ensure that all spaces and access aisles for persons with disabilities are flat and level, with slopes and cross-slopes not exceeding 1:50 in all directions, and that their surfaces are firm, stable, and slip-resistant. Standards §§ 4.1.2(5), 4.6, 4.30.7(1).
b. Vehicles parked in spaces 449, 539, or 629 will block the accessible routes between the parking spaces reserved for persons with disabilities and the doors to the elevator vestibules. At each of these locations, provide at least one accessible route that has a minimum clear width of 36 inches. Standards §§ 4.1.3(1), 4.3, 4.5, Fig. 7.
c. Elevators: East and West. For each: The emergency communication systems do not work without voice communication, as a test call revealed that the operator did not know what to do in response to a silent call. Provide a two-way communication system such that it does not require voice communication, the highest operable part is a maximum of 48 inches above the finished floor of the car, and it is identified by a raised symbol and lettering located adjacent to the device. If the system uses a handset, ensure that the length of the cord from the panel to the handset is at least 29 inches. If the system is located in a closed compartment, ensure that the compartment door hardware operates without tight grasping, pinching or twisting of the wrist. Standards §§ 4.1.3(5), 4.10.14.
20. By December 31, 2014, the City will complete the following modifications to the Harry and Gail Koch Family Tennis Center, located at 12440 West Maple Road:
a. Parking - Lower: Although 130 parking spaces are provided in both lots, only one space is reserved for persons with disabilities and the paved surface is covered with loose dirt and gravel, so the surface is not firm, stable, and slip-resistant. On the shortest accessible route to the accessible entrance, provide 1 van accessible space and 4 standard spaces designated as reserved for people with disabilities. Ensure that standard accessible spaces are a minimum of 96 inches wide and served by access aisles at least 60 inches wide. Ensure that van accessible spaces are a minimum of 96 inches wide and served by access aisles at least 96 inches wide. At all spaces designated as reserved for persons with disabilities, provide vertical signs with the International Symbol of Accessibility located such that they cannot be obstructed by parked vehicles. At van accessible spaces, provide an additional "Van-Accessible" sign located below the International Symbol of Accessibility. Ensure that all spaces and access aisles for persons with disabilities are flat and level, with slopes and cross-slopes not exceeding 1:50 in all directions, and that their surfaces are firm, stable, and slip-resistant. Standards §§ 4.1.2(5), 4.6, 4.30.7(1).
b. Telephones: Although a telephone is provided for public use, it is not hearing aid compatible. Provide an accessible telephone with a clear floor space of at least 30 inches by 48 inches that allows either a forward or parallel approach by a person using a wheelchair such that bases, enclosures, and fixed seats do not impede approaches to the telephone; with the highest operable part of the telephone mounted no more than 48 inches above the floor for a front approach or no more than 54 inches above the floor for a side approach; that is hearing aid compatible and has a volume control mechanism; with telephone books, if provided, located between 15 and 48 inches above the finished floor for a front approach or between 9 and 54 inches above the finished floor for a side approach; with a cord of at least 29 inches long from the telephone to the handset; and with signage that complies with the Standards. Make available a TTY and provide signage indicating its availability. Standards §§ 4.1.3(17), 4.31, 4.30.7(2).
c. Men's and Women's Locker Rooms: For each:
i. The benches are too narrow. Provide a 24 inch by 48 inch bench fixed to the wall along the bench's longer dimension. Ensure that the bench has sufficient structural strength and is mounted with its surface between 17 inches and 19 inches above the finished floor. Provide clear floor space alongside the bench to allow a person using a wheelchair to make a parallel transfer onto the bench. Standards §§ 4.1.3(21), 4.35.4, 4.26.3.
ii. Men's Only: No accessible coat hook has been provided. Provide a coat hook at a maximum height above the finished floor of 48 inches for a forward approach or 54 inches for a side approach and that is accompanied by clear floor space of 30 by 48 inches that allows a forward or parallel approach by a person using a wheelchair. Standards §§ 4.1.3(12)(a), 4.25.2, 4.25.3, 4.2.4, 4.2.5, 4.2.6.