ATTACHMENT J: Modifications to Altered FacilitiesPlease Note: Paragraph 55 of the Settlement Agreement requires that within three months of the effective date of this Agreement, the City provide signage as necessary to comply with 28 C.F.R. § 35.163(b), after having surveyed all facilities that are the subject of this Agreement for the purpose of identifying those that have multiple entrances not all of which are accessible. The chart below lists the facilities surveyed by the Department, the access issues identified during the survey, and the actions required to correct the access issues. Required actions are listed using an alphanumeric code. The key to the alphanumeric codes is provided in Attachment M to this Agreement. In order to ensure that the following spaces and elements in the City´s facilities in which alterations occurred after January 26, 1992, are readily accessible to and usable by persons with disabilities, the City will take the actions referenced by the alphanumeric code and described in detail in Attachment M to this Settlement Agreement within the time period specified below, which time period will begin to run on the effective date of this Agreement. |
|||
Item # | Access Issue | Required Action | Completion Date |
---|---|---|---|
1. | Van Zandt Pier, located at Washington Street and Van Zandt Avenue | ||
1.1. | Ramp: The ramp is inaccessible because no accessible handrails have been provided. | R4 | 12 months |
2. | Elm Street Pier, located at Elm Street and Washington Street | ||
2.1. | Ramp to Floating Dock | ||
2.1.a. | The ramp is inaccessible because there is a 4½ inch wide gap at the top. | AR1 | 12 months |
2.1.b. | The ramp is inaccessible because the handrails are 42 inches above the finished floor/ground and lack adequate extensions. | R4 | 12 months |
3. | Newport Gateway Center, located at 23 America´s Cup Avenue | ||
3.1. | Parking | ||
3.1.a. | The covered van parking space is inaccessible because it has 75 inches of vertical clearance. | P9 | 24 months |
3.1.b. | The parking areas, with a total of 495 parking spaces, are inaccessible because the covered van parking space and several other spaces lack vertical signage, the access aisle for the outdoor designated accessible space has a slope of 4.8% along one side, one of the designated accessible spaces is 91 inches wide, and the standard accessible parking spaces have access aisles ranging from 51 to 52 inches wide. | P6 | 24 months |
3.1.c. | The designated accessible parking is inaccessible because it is not dispersed among the accessible facility entrances as there is no accessible parking by the west end of the building. | P2 | 24 months |
3.2. | Garage Routes | ||
3.2.a. | The underside of the stairs in the East side of the parking garage is an overhead hazard that is not detectable to blind persons using a cane. | AR7 | 24 months |
3.2.b. | The fire alarm in the East side of the parking garage protrudes into the walkway and is not detectable to blind persons using a cane. | AR8 | 24 months |
3.3. | Parking Canopies | ||
3.3.a. | The route from the visitor´s center to the tour bus area is inaccessible because the curb ramp on the side closest to the visitor center has an abrupt 1 inch high step at the bottom and a slope of 10%. | AR5 | 24 months |
3.3.b. | The route from the visitor´s center to the tour bus area is inaccessible because the curb ramp on the side closest to the tour buses has flared sides with slopes of 20.1% and 13.7%. | AR5 | 24 months |
3.4. | Entrances | ||
3.4.a. | The building does not have directional signage posted at inaccessible entrances and does not have the International Symbol of Accessibility posted at accessible entrances. | D16 | 24 months |
3.4.b. | The West side entrance door by the bus loading area is inaccessible because there is a ¾ inch high step onto the carpet in front of the door. | AR1 | 24 months |
3.5. | Interior Doors: The doors to the Dunkin Donuts and the Toilet Rooms are inaccessible because they require 10 to 15 pounds of force to open. | D2 | 24 months |
3.6. | Main Lobby: The end of the visitor´s brochure counter protrudes into the walkway and is not detectable to blind persons using a cane. | AR8 | 24 months |
3.7. | Drinking Fountains by Dunkin Donuts: Although a designated accessible drinking fountain is provided, there is no drinking fountain provided for people who have difficulty bending or stooping. | DF3 | 24 months |
3.8. | Courtesy Telephone for Tours/Hotels: The telephone is inaccessible because it is not hearing aid compatible, it does not have volume control signage, and it provides inadequate knee space. | TT1 | 24 months |
3.9. | Pay Telephone by Dunkin Donuts: The telephone is inaccessible because its highest operable part is 55½ inches above the finished floor. | TT1 | 24 months |
3.10. | Women´s Toilet Room with Stalls near Dunkin Donuts | ||
3.10.a. | The toilet room sign is mounted 65 inches above the finished floor on the hinge side of the door and has no raised or Braille characters. | TR18 | 24 months |
3.10.b. | Although there are 13 toilet stalls, no ambulatory stall has been provided. | ST1 | 24 months |
3.11. | Men´s Toilet Room with Stalls near Dunkin Donuts | ||
3.11.a. | The toilet room sign is mounted 64 inches above the finished floor and has no raised or Braille characters. | D26 | 24 months |
3.11.b. | The urinal is inaccessible because the rim is 18 inches above the finished floor. | TR20 | 24 months |
3.12. | Elevator: The elevator is inaccessible because the car control buttons do not have Braille characters, and the call button for the main entry floor is not designated by a raised star. | E4 | 24 months |
4. | Parks and Recreation Cottage Office | ||
4.1. | Entrance | ||
4.1.a. | The door is inaccessible because there is a 1½ inch high threshold. | D22 | 12 months |
4.1.b. | The push side of the door, which is accessed through a front approach and which has both a closer and a latch, is inaccessible because it has only 3½ inches of clear space on the latch side. | D7 | 12 months |
5. | Easton´s Beach, located at 175 Memorial Boulevard | ||
5.1. | Men´s Off-Season Toilet Room with Stalls | ||
5.1.a. | The toilet room sign is mounted on the door and has no raised or Braille characters. | TR18 | 30 months |
5.1.b. | The lavatory is inaccessible because the hot water pipes are not insulated or otherwise configured to protect against contact. | TR12 | 30 months |
5.1.c. | The urinal is inaccessible because the rim is 24 inches above the finished floor. | TR20 | 30 months |
5.1.d. | The side grab bar at the designated accessible toilet is inaccessible because it is obstructed by the toilet paper dispenser. | ST8 | 30 months |
5.2. | Women´s Off-Season Toilet Room with Stalls | ||
5.2.a. | The toilet room sign is mounted on the door and has no raised or Braille characters. | TR18 | 30 months |
5.2.b. | The lavatory is inaccessible because the hot water pipes are not insulated or otherwise configured to protect against contact. | TR12 | 30 months |
5.2.c. | The designated accessible stall is incorrectly configured as an ambulatory stall, and there is no standard accessible stall provided. | ST15 | 30 months |
5.3. | Rosie´s Beach Store: The counter is inaccessible because it is 42 inches above the finished floor. | C5 | 30 months |
5.4. | Men´s Club Locker Room | ||
5.4.a. | The locker room sign has no raised or Braille characters. | TR18 | 30 months |
5.4.b. | Although an audible alarm is provided in this facility, there is no visual alarm appliance in the toilet room. | TR21 | 30 months |
5.4.c. | The paper towel dispenser and air dryer protrude into the walkway and are not detectable to blind persons using a cane. | AR8 | 30 months |
5.4.d. | The urinal is inaccessible because the rim is 18 inches above the finished floor, the clear floor space is 27½ inches wide, and the flush control is 46 inches above the finished floor. | TR20 | 30 months |
5.4.e. | The designated accessible toilet is inaccessible because the flush control is on the closed side. | ST2 | 30 months |
5.4.f. | The side grab bar at the designated accessible toilet is inaccessible because it is obstructed by the toilet paper dispenser. | ST8 | 30 months |
5.4.g. | The side grab bar at the designated accessible toilet is inaccessible because it is mounted with the far end 50 inches from the rear wall. | ST7 | 30 months |
5.4.h. | The shower is inaccessible because it is 34½ inches deep, the grab bars are 1 inch in diameter and mounted 2 inches from the wall, and the curb is 3½ inches high. | B8 | 30 months |
5.5. | Women´s Club Locker Room | ||
5.5.a. | The locker room sign is mounted more than 60 inches above the finished floor and has no raised or Braille characters. | TR18 | 30 months |
5.5.b. | Although an audible alarm is provided in this facility, there is no visual alarm appliance in the toilet room. | TR21 | 30 months |
5.5.c. | The wall-mounted shelf, paper towel dispenser, and air dryer protrude into the walkway and are not detectable to blind persons using a cane. | AR8 | 30 months |
5.5.d. | The side grab bar at the designated accessible toilet is inaccessible because it is obstructed by the toilet paper dispenser. | ST8 | 30 months |
5.5.e. | The shower is inaccessible because the grab bars are 1 inch in diameter and mounted 2 inches from the wall, and the curb is 4 inches high. | B8 | 30 months |
5.6. | Ground Level Men´s Toilet Room with Stalls | ||
5.6.a. | The toilet room sign has no raised or Braille characters. | TR18 | 30 months |
5.6.b. | The lavatory is inaccessible because the hot water pipes are not insulated or otherwise configured to protect against contact. | TR12 | 30 months |
5.6.c. | The lavatory is inaccessible because it has twist-type hardware. | TR10 | 30 months |
5.6.d. | The air dryers and corner shelf protrude into the walkway and are not detectable to blind persons using a cane. | AR8 | 30 months |
5.6.e. | The designated accessible stall is incorrectly configured as an ambulatory stall, and no standard accessible stall has been provided. | ST15 | 30 months |
5.6.f. | The shower is inaccessible because no shower spray unit is provided and the shower head is mounted 65 inches above the finished floor. | B11 | 30 months |
5.6.g. | The shower is inaccessible because there is insufficient clear floor space alongside the transfer seat. | B8 | 30 months |
5.7. | Ground Level Women´s Toilet Room with Stalls | ||
5.7.a. | The toilet room sign is mounted on the door and has no Braille characters. | TR18 | 30 months |
5.7.b. | The lavatory is inaccessible because the hot water pipes are not insulated or otherwise configured to protect against contact. | TR12 | 30 months |
5.7.c. | The lavatory is inaccessible because it has twist-type hardware. | TR10 | 30 months |
5.7.d. | The air dryers and corner shelf protrude into the walkway and are not detectable to blind persons using a cane. | AR8 | 30 months |
5.7.e. | The designated accessible stall is incorrectly configured as an ambulatory stall, and there is no standard accessible stall provided. | ST15 | 30 months |
5.7.f. | The shower is inaccessible because no shower spray unit is provided and the shower head is mounted 65 inches above the finished floor. | B11 | 30 months |
5.7.g. | The shower is inaccessible because there is insufficient clear floor space alongside the transfer seat. | B8 | 30 months |
5.8. | Parking: The parking lots are inaccessible because the west side parking has no vertical signage, and the east side parking has no access aisles and no van accessible spaces, and many of the spaces are missing vertical signs. These lots require a total of 3 van accessible spaces and 14 standard accessible spaces, appropriately dispersed amongst the various lots. | P3P3 | 30 months |
6. | King Park, located at 100 Wellington Avenue | ||
6.1. | Bleachers: The route to the bleachers is inaccessible because grass is not firm, stable and slip resistant. | AR1 | 24 months |
6.2. | Concessions: The concession counters are inaccessible because they are 42 and 39½ inches above the finished floor. | C5 | 24 months |
6.3. | Playground: There is no accessible route to the playground equipment or to the swings because the sand and the grass are not firm, stable, and slip resistant. | AR1 | 24 months |
6.4. | Toilet Rooms - General: Many of the toilet rooms were locked and could not be surveyed. | ST14 | 24 months |
6.5. | Ramp to Picnic Pavilion Toilet Rooms: The ramp is inaccessible because it does not have edge protection at the drop off sides. | R1 | 24 months |
6.6. | Picnic Pavilion Women´s Toilet Room with Stalls | ||
6.6.a. | The sign is mounted above the door and has no raised or Braille characters. | TR18 | 24 months |
6.6.b. | The lavatory is inaccessible because the hot water pipes are not insulated or otherwise configured to protect against contact. | TR12 | 24 months |
6.6.c. | The side grab bar at the designated accessible toilet is inaccessible because it is obstructed by the toilet paper dispenser. | ST8 | 24 months |
6.6.d. | The rear grab bar at the designated accessible toilet is inaccessible because it is mounted 11 inches from the side wall. | ST4 | 24 months |
6.7. | Picnic Pavilion Men´s Toilet Room with Stalls | ||
6.7.a. | The toilet room sign is mounted above the door and has no raised or Braille characters. | TR18 | 24 months |
6.7.b. | The urinal is inaccessible because the rim is 21 inches above the finished floor and the flush control is 48 inches above the finished floor. | TR20 | 24 months |
6.7.c. | The side grab bar at the designated accessible toilet is inaccessible because it is obstructed by the toilet paper dispenser. | ST8 | 24 months |
6.7.d. | The rear grab bar at the designated accessible toilet is inaccessible because it is mounted 11 inches from the side wall. | ST4 | 24 months |
6.8. | Fieldhouse Men´s Single User Toilet Room | ||
6.8.a. | The toilet room sign is mounted on the door and has no raised or Braille characters. | TR18 | 24 months |
6.8.b. | The paper towel dispenser protrudes into the walkway and is not detectable to blind persons using a cane. | AR8 | 24 months |
6.8.c. | The lavatory is inaccessible because the hot water pipes are not insulated or otherwise configured to protect against contact. | TR12 | 24 months |
6.8.d. | The toilet is inaccessible because the top of the seat is 16 inches above the finished floor. | SU18 | 24 months |
6.8.e. | The toilet is inaccessible because its centerline is 22 inches from the side wall. | SU15 | 24 months |
6.8.f. | The toilet is inaccessible because there are no grab bars provided. | SU10 | 24 months |
6.9. | Fieldhouse Women´s Single User Toilet Room | ||
6.9.a. | The toilet room sign is mounted on the door and has no raised or Braille characters. | TR18 | 24 months |
6.9.b. | The lavatory is inaccessible because the hot water pipes are not insulated or otherwise configured to protect against contact. | TR12 | 24 months |
6.9.c. | The toilet paper dispenser is inaccessible because it is mounted 38 inches from the rear wall. | SU17 | 24 months |
6.9.d. | The toilet is inaccessible because the flush control is on the closed side. | SU1 | 24 months |
6.9.e. | The toilet is inaccessible because there are no grab bars provided. | SU10 | 24 months |