Attachment K: Program Access in Existing Facilities

Please Note: Paragraph 50 of the Agreement requires that within three months of the effective date of this Agreement, the City will provide signage as necessary to comply with 28 C.F.R. § 35.163(b), after having surveyed all facilities that are the subject of this Agreement for the purpose of identifying those that have multiple entrances not all of which are accessible.

1.    The technical requirements and, where appropriate, the scoping requirements of the Standards are used as a guide for determining whether a program or activity held in an existing facility is “readily accessible to and usable by” persons with disabilities and for determining what changes are necessary to make this program or activity accessible if it continues to be provided in the existing facility in question. See 28 C.F.R. §§ 35.150(b)(1), 35.151.

2.     In order to ensure that each of the City’s programs, services, and activities operating at a facility that is the subject of this Agreement, when viewed in its entirety, are readily accessible to and usable by persons with disabilities, the City will take the following actions:

3.     Within 30 months of the effective date of this Agreement, the City will make the following modifications to the Branchbrook Branch Library, located at 235 Clifton Avenue.

a.     Accessible Route. The route from the sidewalk into and through the facility contains numerous steps, both outside and inside. Provide at least one accessible route into and through the library that, to the maximum extent feasible, coincides with the route for the general public. The accessible route must have a minimum clear width of 36 inches, or a minimum clear width of 42 inches if there is a turn around an obstruction less than 48 inches wide; have passing spaces at least 60 inches by 60 inches at least every 200 feet; have a minimum clear headroom of 80 inches; have a surface that is firm, stable, and slip resistant; have, in the absence of a curb ramp, ramp, elevator, or platform lift, no level changes in excess of ½ inch vertically; and have a running slope of less than 1:20 (5%) (or have been constructed as a fully accessible ramp) and a cross slope of less than 1:50 (2%). Standards §§ 4.3, 4.5, Fig. 7.

4.     Within 30 months of the effective date of this Agreement, the City will make the following modifications to the City Hall, located at 920 Broad Street.

a.     Signage

i.    The building does not have directional signage at all inaccessible entrances. Provide accessible directional signage with the International Symbol of Accessibility at inaccessible entrances directing users to the accessible entrance, and provide accessible signage with the International Symbol of Accessibility at all permanent accessible entrances. Standards §§ 4.1.3(8)(d), 4.13, 4.30.

ii.    The signage posted throughout the building is not accessible. Provide permanent room signage with upper case, sans serif or simple serif type letters and numerals, meeting the requirements of the Standards for character height, raised characters, finish and contrast, accompanied by Grade 2 Braille; mounted on the wall adjacent to the latch side of the door or on the nearest adjacent wall at a height of 60 inches above the finished floor to the centerline of the sign; and located so that a person may approach within 3 inches of the signage without encountering protruding objects or standing within the swing of a door. Standards §§ 4.30.1, 4.30.4, 4.30.5, 4.30.6.

b.     Platform Lift. Although a lift is provided in the basement, the lift is not operational. Provide an operating lift that is on an accessible route; has interior dimensions of at least 30 inches by 48 inches; facilitates unassisted entry, operation, and exit; has a floor surface that is firm, stable, and slip-resistant, or, if carpeted, has a carpet with a pile that is no more than ½ inch deep; has a change of level at the entrance that is no more than ½ inch and beveled. Ensure that the lift has operating controls that are located between 15 and 48 inches above the floor for a front approach or between 9 and 54 inches above the floor for a side approach; that are usable with one hand and do not require tight grasping, pinching, or twisting of the wrist to operate; and that require a force no greater than 5 lbf to operate. Standards § 4.11.

c.     Office Doors

i.    The doors throughout the building have knob hardware. Provide doors with hardware that is easy to grasp with one hand and that does not require tight grasping, pinching, or twisting of the wrist to operate. Lever-operated mechanisms, push-type mechanisms, and U-shaped handles are acceptable designs. Standards § 4.13.9.

ii.    In Room B-13, the pressure required to open the door is 15 pounds. Provide a door that requires no more than 5 pounds of force to open. Standards § 4.13.11(2)(b).

iii.    In Room B-23, each of the double entrance doors is 29½ inches wide. Provide a door at this location that has at least one active leaf with a clear opening at least 32 inches wide when measured from the face of the door to the middle edge of the other door when one door is opened 90 degrees and that has hardware usable with one hand and without tight grasping, pinching, or twisting of the wrist OR provide an automatic door opener that opens both doors simultaneously. Standards § 4.13, Figs. 24, 25.

iv.    In Room B-25, the Manager's office door is 31 inches wide. Provide a door with a clear opening of 32 inches with the door open 90 degrees, measured between the face of the door and the opposite stop. Standards § 4.13.5, Fig. 24.

v.    In Room B-26, each of the double entrance doors is 29½ inches wide. Provide a door at this location that has at least one active leaf with a clear opening at least 32 inches wide when measured from the face of the door to the middle edge of the other door when one door is opened 90 degrees and that has hardware usable with one hand and without tight grasping, pinching, or twisting of the wrist OR provide an automatic door opener that opens both doors simultaneously. Standards § 4.13, Figs. 24, 25.

vi.    In Room 104, each of the double entrance doors is 28½ inches wide. Provide a door at this location that has at least one active leaf with a clear opening at least 32 inches wide when measured from the face of the door to the middle edge of the other door when one door is opened 90 degrees and that has hardware usable with one hand and without tight grasping, pinching, or twisting of the wrist OR provide an automatic door opener that opens both doors simultaneously. Standards § 4.13, Figs. 24, 25.

vii.    In Room 218, the pressure required to open the door is 13 pounds. Provide a door that requires no more than 5 pounds of force to open. Standards § 4.13.11(2)(b).

viii.    In Room 205, the pressure required to open the door is 14 pounds. Provide a door that requires no more than 5 pounds of force to open. Standards § 4.13.11(2)(b).

ix.    In Room 207, each of the double entrance doors is 23 inches wide. Provide a door at this location that has at least one active leaf with a clear opening at least 32 inches wide when measured from the face of the door to the middle edge of the other door when one door is opened 90 degrees and that has hardware usable with one hand and without tight grasping, pinching, or twisting of the wrist OR provide an automatic door opener that opens both doors simultaneously. Standards § 4.13, Figs. 24, 25.

x.    In Room 207, the entrance to the Aide's Space is 25 inches wide. Provide an accessible route to the Aide’s Space with a minimum clear width of 36 inches, except at doors, where the width may decrease to 32 inches. Standards §§ 4.3.3, 4.13.5.

xi.    In Room 220, each of the double entrance doors is 29 inches wide. Provide a door at this location that has at least one active leaf with a clear opening at least 32 inches wide when measured from the face of the door to the middle edge of the other door when one door is opened 90 degrees and that has hardware usable with one hand and without tight grasping, pinching, or twisting of the wrist OR provide an automatic door opener that opens both doors simultaneously. Standards § 4.13, Figs. 24, 25.

xii.    In Room 220, the pressure required to open the door is 9 pounds. Provide a door that requires no more than 5 pounds of force to open. Standards § 4.13.11(2)(b).

xiii.    In Room 406, each of the double entrance doors to the rear offices and conference room is 30½ inches wide. Provide a door at this location that has at least one active leaf with a clear opening at least 32 inches wide when measured from the face of the door to the middle edge of the other door when one door is opened 90 degrees and that has hardware usable with one hand and without tight grasping, pinching, or twisting of the wrist OR provide an automatic door opener that opens both doors simultaneously. Standards § 4.13, Figs. 24, 25.

xiv.    In Room 421, the pressure required to open the door is 9 pounds. Provide a door that requires no more than 5 pounds of force to open. Standards § 4.13.11(2)(b).

xv.    In Room 421, each of the double entrance doors is 26½ inches wide. Provide a door at this location that has at least one active leaf with a clear opening at least 32 inches wide when measured from the face of the door to the middle edge of the other door when one door is opened 90 degrees and that has hardware usable with one hand and without tight grasping, pinching, or twisting of the wrist OR provide an automatic door opener that opens both doors simultaneously. Standards § 4.13, Figs. 24, 25.

xvi.    In Room 420, the entrance door is 30 inches wide. Provide a door with a clear opening of 32 inches with the door open 90 degrees, measured between the face of the door and the opposite stop. Standards § 4.13.5, Fig. 24.

d.     Counters

i.    In Room B-9, the counter is 41½ inches high. Provide a counter on an accessible route such that a portion of the counter is at least 36 inches wide and no more than 36 inches above the finished floor, or provide an auxiliary counter with a maximum height of 36 inches in close proximity to the main counter, or provide equivalent facilitation. Equivalent facilitation may be provided in the form of a folding shelf attached to the main counter, an auxiliary table nearby, a clip board made available to the public, or other means. Standards §§ 7.2(2), 4.3.

ii.    The counter surface in Room B-12 protrudes into the main walkway and would not be detectable to a blind person using a cane. Provide an accessible route at this location such that no objects with their bottom leading edges measuring between 27 inches and 80 inches above the finished floor protrude more than 4 inches into walks, halls, corridors, passageways, or aisles. Free-standing objects mounted on posts or pylons may overhang 12 inches maximum from 27 inches to 80 inches above the ground or finished floor. Standards § 4.4.

iii.    In Room B-13, the counter is 40 inches high. Provide a counter on an accessible route such that a portion of the counter is at least 36 inches wide and no more than 36 inches above the finished floor, or provide an auxiliary counter with a maximum height of 36 inches in close proximity to the main counter, or provide equivalent facilitation. Equivalent facilitation may be provided in the form of a folding shelf attached to the main counter, an auxiliary table nearby, a clip board made available to the public, or other means. Standards §§ 7.2(2), 4.3.

iv.    In Room B-26, the counter is 43 inches high. Provide a counter on an accessible route such that a portion of the counter is at least 36 inches wide and no more than 36 inches above the finished floor, or provide an auxiliary counter with a maximum height of 36 inches in close proximity to the main counter, or provide equivalent facilitation. Equivalent facilitation may be provided in the form of a folding shelf attached to the main counter, an auxiliary table nearby, a clip board made available to the public, or other means. Standards §§ 7.2(2), 4.3.

v.    The counter surface in Room B-26 protrudes into the main walkway and would not be detectable to a blind person using a cane. Provide an accessible route at this location such that no objects with their bottom leading edges measuring between 27 inches and 80 inches above the finished floor protrude more than 4 inches into walks, halls, corridors, passageways, or aisles. Free-standing objects mounted on posts or pylons may overhang 12 inches maximum from 27 inches to 80 inches above the ground or finished floor. Standards § 4.4.

vi.    In Room 117, the counter is 43 inches high. Provide a counter on an accessible route such that a portion of the counter is at least 36 inches wide and no more than 36 inches above the finished floor, or provide an auxiliary counter with a maximum height of 36 inches in close proximity to the main counter, or provide equivalent facilitation. Equivalent facilitation may be provided in the form of a folding shelf attached to the main counter, an auxiliary table nearby, a clip board made available to the public, or other means. Standards §§ 7.2(2), 4.3.

vii.    In Room 112, the counters are 38 and 44 inches high. Provide a counter on an accessible route such that a portion of the counter is at least 36 inches wide and no more than 36 inches above the finished floor, or provide an auxiliary counter with a maximum height of 36 inches in close proximity to the main counter, or provide equivalent facilitation. Equivalent facilitation may be provided in the form of a folding shelf attached to the main counter, an auxiliary table nearby, a clip board made available to the public, or other means. Standards §§ 7.2(2), 4.3.

viii.    In Room 111, the counters are 43, 45 and 44 inches high. Provide a counter on an accessible route such that a portion of the counter is at least 36 inches wide and no more than 36 inches above the finished floor, or provide an auxiliary counter with a maximum height of 36 inches in close proximity to the main counter, or provide equivalent facilitation. Equivalent facilitation may be provided in the form of a folding shelf attached to the main counter, an auxiliary table nearby, a clip board made available to the public, or other means. Standards §§ 7.2(2), 4.3.

ix.    In Room 104, the counters are 40½ and 40 inches high. Provide a counter on an accessible route such that a portion of the counter is at least 36 inches wide and no more than 36 inches above the finished floor, or provide an auxiliary counter with a maximum height of 36 inches in close proximity to the main counter, or provide equivalent facilitation. Equivalent facilitation may be provided in the form of a folding shelf attached to the main counter, an auxiliary table nearby, a clip board made available to the public, or other means. Standards §§ 7.2(2), 4.3.

x.    The counter surface in Room 218 protrudes into the main walkway and would not be detectable to a blind person using a cane. Provide an accessible route at this location such that no objects with their bottom leading edges measuring between 27 inches and 80 inches above the finished floor protrude more than 4 inches into walks, halls, corridors, passageways, or aisles. Free-standing objects mounted on posts or pylons may overhang 12 inches maximum from 27 inches to 80 inches above the ground or finished floor. Standards § 4.4.

xi.    In Room 101, the counter in the outer office is 40½ inches high, and the counter in the inner office is 43½ inches high. In each area, provide a counter on an accessible route such that a portion of the counter is at least 36 inches wide and no more than 36 inches above the finished floor, or provide an auxiliary counter with a maximum height of 36 inches in close proximity to the main counter, or provide equivalent facilitation. Equivalent facilitation may be provided in the form of a folding shelf attached to the main counter, an auxiliary table nearby, a clip board made available to the public, or other means. Standards §§ 7.2(2), 4.3.

xii.    The counter surfaces in Room 304 protrude into the main walkway and would not be detectable to a blind person using a cane. Provide an accessible route at this location such that no objects with their bottom leading edges measuring between 27 inches and 80 inches above the finished floor protrude more than 4 inches into walks, halls, corridors, passageways, or aisles. Free-standing objects mounted on posts or pylons may overhang 12 inches maximum from 27 inches to 80 inches above the ground or finished floor. Standards § 4.4.

xiii. In Room 306, the counter is 40 inches high. Provide a counter on an accessible route such that a portion of the counter is at least 36 inches wide and no more than 36 inches above the finished floor, or provide an auxiliary counter with a maximum height of 36 inches in close proximity to the main counter, or provide equivalent facilitation. Equivalent facilitation may be provided in the form of a folding shelf attached to the main counter, an auxiliary table nearby, a clip board made available to the public, or other means. Standards §§ 7.2(2), 4.3.

xiv.     In Room 406, the counter is 43½ inches high. Provide a counter on an accessible route such that a portion of the counter is at least 36 inches wide and no more than 36 inches above the finished floor, or provide an auxiliary counter with a maximum height of 36 inches in close proximity to the main counter, or provide equivalent facilitation. Equivalent facilitation may be provided in the form of a folding shelf attached to the main counter, an auxiliary table nearby, a clip board made available to the public, or other means. Standards §§ 7.2(2), 4.3.

xv.     Room 420, the county is 42 inches high. Provide a counter on an accessible route such that a portion of the counter is at least 36 inches wide and no more than 36 inches above the finished floor, or provide an auxiliary counter with a maximum height of 36 inches in close proximity to the main counter, or provide equivalent facilitation. Equivalent facilitation may be provided in the form of a folding shelf attached to the main counter, an auxiliary table nearby, a clip board made available to the public, or other means. Standards §§ 7.2(2), 4.3.

e.     Offices – General

i.    In Room B-23, the path of travel is 24 inches wide. Provide an accessible route in this room with a minimum clear width of 36 inches, except at doors, where the width may decrease to 32 inches. Standards §§ 4.3.3, 4.13.5.

ii.    Room 115 contains steps with no accessible alternate route. Provide at least one accessible route within this office that, to the maximum extent feasible, coincides with the route for the general public. The accessible route must have a minimum clear width of 36 inches, or a minimum clear width of 42 inches if there is a turn around an obstruction less than 48 inches wide; have passing spaces at least 60 inches by 60 inches at least every 200 feet; have a minimum clear headroom of 80 inches; have a surface that is firm, stable, and slip resistant; have, in the absence of a curb ramp, ramp, elevator, or platform lift, no level changes in excess of ½ inch vertically; and have a running slope of less than 1:20 (5%) (or have been constructed as a fully accessible ramp) and a cross slope of less than 1:50 (2%). Standards §§ 4.3, 4.5, Fig. 7.

iii.    In Room 113, the path of travel is 27½ inches wide. Provide an accessible route in this room with a minimum clear width of 36 inches, except at doors, where the width may decrease to 32 inches. Standards §§ 4.3.3, 4.13.5.

iv.    In Room 112, the plat table is 53 inches high to the top. Provide at least one table on an accessible route such that there is knee space at the table at least 27 inches high, 30 inches wide, and 19 inches deep, and such that the height of the top of the table is between 28 inches and 34 inches above the ground. Standards §§ 4.32.3, 4.32.4.

v.    In Room 209, the computer keyboards are 26 inches high to the bottom. Provide a computer on a table or counter that has clear floor space that is 30 inches wide and 48 inches deep, knee clearance at least 27 inches high, 30 inches wide, and 19 inches deep, and a writing surface between 28 and 34 inches above the finished floor. Standards §§ 4.2.4.1, 4.32.

vi.    In Room 421, the path of travel is 33½ inches wide. Provide an accessible route in this room with a minimum clear width of 36 inches, except at doors, where the width may decrease to 32 inches. Standards §§ 4.3.3, 4.13.5.

vii.    In Room 402, the path of travel is 25 inches wide. Provide an accessible route in this room with a minimum clear width of 36 inches, except at doors, where the width may decrease to 32 inches. Standards §§ 4.3.3, 4.13.5.

f.     Municipal Council Chambers (Room 215)

i.    In Room 215, each of the double entrance doors is 30 inches wide. Provide a door at this location that has at least one active leaf with a clear opening at least 32 inches wide when measured from the face of the door to the middle edge of the other door when one door is opened 90 degrees and that has hardware usable with one hand and without tight grasping, pinching, or twisting of the wrist OR provide an automatic door opener that opens both doors simultaneously. Standards § 4.13, Figs. 24, 25.

ii.    Room 215 has no wheelchair seating provided. Provide at least 4 wheelchair seating areas, each with a minimum clear ground or floor space of 66 inches wide by 48 inches deep for forward or rear access, or 66 inches wide by 60 inches deep for side access. Ensure that the ground or floor at all wheelchair locations is level, firm, stable, and slip resistant; that wheelchair seating areas are an integral part of the fixed seating plan and are located so as to provide people with physical disabilities a choice of lines of sight comparable to those available for members of the general public; that wheelchair seating areas adjoin an accessible route that also serves as a means of egress in case of emergency; and that at least one fixed companion seat is provided next to each wheelchair seating area. Standards §§ 4.1.3(19)(a), 4.5, 4.33.

g.     Elevator. The elevator is 61½ inches wide. Provide an elevator with a cab that is a minimum of 51 inches deep from the back wall of the cab to the control panel and 54 inches deep from the back wall of the cab to the face of the door; that, if the doors are centered on the wall, is at least 80 inches wide and, if the doors are located to one side of the wall, is at least 68 inches wide. Ensure that the door opening is at least 36 inches wide, and that floor surfaces are firm, stable, and slip-resistant. Standards §§ 4.10.9, 4.10.10, Fig. 22.

h.     Drinking Fountains

i.    The drinking fountains throughout the facility have a spout that is 38 inches above the finished floor. On each floor, provide a fountain that has a spout height no higher than 36 inches, measured from the finished floor or ground surface to the spout outlet, and that otherwise complies with the Standards. Standards §§ 4.15, 4.27.4, Fig. 27.

ii.    The drinking fountains throughout the facility protrude into the main walkway and would not be detectable to a blind person using a cane. Provide an accessible route at these locations such that no objects with their bottom leading edges measuring between 27 inches and 80 inches above the finished floor protrude more than 4 inches into walks, halls, corridors, passageways, or aisles. Free-standing objects mounted on posts or pylons may overhang 12 inches maximum from 27 inches to 80 inches above the ground or finished floor. Standards § 4.4.

i.    Toilet Rooms with Stalls

i.    Although an audible alarm is provided in this facility, there is no visual alarm appliance provided in the toilet rooms. In each toilet room, provide a visual alarm appliance that complies with the Standards. Standards §§ 4.28.1, 4.28.3.

ii.    The toilet room signs are incorrectly mounted and do not have raised characters or Braille, and there is no directional signage at inaccessible toilet rooms indicating the location of the nearest accessible toilet rooms. For each toilet room, provide a toilet room sign with raised and Braille characters mounted on the wall adjacent to the latch side of the door with the centerline of the sign at 60 inches above the finished floor and situated such that a person can approach within 3 inches of the sign without encountering an obstruction or standing within a door swing. For each accessible toilet room, provide the International Symbol of Accessibility on the sign. For each inaccessible toilet room, provide directional signage with the International Symbol of Accessibility indicating the location of the nearest accessible toilet room. Standards §§ 4.1.2(7)(d), 4.1.6(3)(e)(iii), 4.30.1, 4.30.2, 4.30.3, 4.30.4, 4.30.5, 4.30.6, 4.30.7.

iii.    In the 4th floor toilet room, the paper towel dispenser protrudes into the main walkway and would not be detectable to a blind person using a cane. Provide an accessible route at this location such that no objects with their bottom leading edges measuring between 27 inches and 80 inches above the finished floor protrude more than 4 inches into walks, halls, corridors, passageways, or aisles. Free-standing objects mounted on posts or pylons may overhang 12 inches maximum from 27 inches to 80 inches above the ground or finished floor. Standards § 4.4.

iv.    In the 4th floor women’s toilet room, the flush in the designated accessible stall is mounted on the closed side. Provide a flush control mounted on the “open” side of the toilet’s clear floor space; 44 inches or less above the finished floor; and requiring a maximum of 5 pounds of force to operate; or provide an automatic flush device. Standards §§ 4.16.5, 4.17.2, 4.27.4.

v.    The third floor men's and women's toilet rooms have signage identifying them as being accessible when they are inaccessible. Remove the accessible signage at each toilet room, and provide accessible directional signage with the International Symbol of Accessibility at each of these inaccessible toilet rooms indicating the location of the nearest accessible toilet rooms, and provide accessible signage with the International Symbol of Accessibility at all accessible toilet rooms. Standards §§ 4.1.2(7)(d), 4.1.6(3)(e)(iii), 4.30.1, 4.30.2, 4.30.3, 4.30.5, 4.30.7.

vi.    The wall-mounted paper towel dispenser, located near the lavatory in the fourth floor women's toilet room, protrudes into the path of travel and would not be detectable to a blind person using a cane. Provide an accessible route at this location such that no objects with their bottom leading edges measuring between 27 inches and 80 inches above the finished floor protrude more than 4 inches into walks, halls, corridors, passageways, or aisles. Free-standing objects mounted on posts or pylons may overhang 12 inches maximum from 27 inches to 80 inches above the ground or finished floor. Standards § 4.4.

vii.    The side grab bar at the toilet is inaccessible because toilet paper dispenser is located less than 1 ½ inches from the bar. Provide a side grab bar that has at least 1½ inches between the grab bar and any other object, such as the toilet paper dispenser. Standards §§ 4.17.6, 4.26.2, Fig. 39.

5.     Within 30 months of the effective date of this Agreement, the City will make the following modifications to the City Museum, located at 49 Washington Place.

a.     Small Parking Lot. One of the parking spaces reserved for persons with disabilities lacks appropriate signage, and there is no van accessible signage. At all spaces designated as reserved for persons with disabilities, provide vertical signs with the International Symbol of Accessibility located such that they cannot be obstructed by parked vehicles. At van accessible spaces, provide an additional “Van-Accessible” sign located below the International Symbol of Accessibility. Standards §§ 4.6.4, 4.30.7(1).

b.     Large Parking Lot. Although the parking lot has a total of more than 300 parking spaces, there are no spaces designated as reserved for people with disabilities. On the shortest accessible route to the accessible entrance, provide at least 1 van accessible space and 7 standard spaces designated as reserved for people with disabilities. Standard accessible spaces shall be a minimum of 96 inches wide and served by access aisles at least 60 inches wide. Van accessible spaces shall be a minimum of 96 inches wide and served by access aisles at least 96 inches wide. All spaces designated as reserved for people with disabilities shall have vertical signs with the International Symbol of Accessibility located such that they cannot be obstructed by parked vehicles. Van accessible spaces shall have an additional “Van-Accessible” sign located below the International Symbol of Accessibility. Standards §§ 4.1.2(5), 4.6, 4.30.7(1).

c.     South Wing. The ramp has no handrail extensions at the top and bottom, and the distance between the handrails and the wall is more than 1½ inches. Provide handrails that are between 1¼ inches and 1½ inches in diameter with a continuous gripping surface along both sides of the ramp, extending at least 12 inches beyond the top and bottom of the ramp parallel with the ground surface. Ensure that handrails are mounted between 34 inches and 38 inches above the ramp surface and between 1¼ and 1½ inches from the wall, with ends rounded or returned smoothly to the floor, wall, or post, and that they do not rotate within their fittings. Standards § 4.8.5.

d.     Program Hall. There are no accessible eating surfaces provided. Provide at least one table on an accessible route such that there is knee space at least 27 inches high, 30 inches wide, and 19 inches deep, and such that the height of the top of the table is between 28 inches and 34 inches above the ground. Standards §§ 4.32.3, 4.32.4.

e.     Telephone Near Gardens. The telephone is not hearing aid compatible. Provide an accessible telephone with a clear floor space of at least 30 inches by 48 inches that allows either a forward or parallel approach by a person using a wheelchair such that bases, enclosures, and fixed seats do not impede approaches to the telephone; with the highest operable part of the telephone mounted no more than 48 inches above the floor for a front approach or no more than 54 inches above the floor for a side approach; that is hearing aid compatible and has a volume control mechanism; with a cord of at least 29 inches long from the telephone to the handset; and with signage that complies with the Standards. Standards §§ 4.31, 4.30.7(2).

f.     North Wing. The ramp has no handrail extensions and the ends of the handrails are not rounded or returned smoothly to the floor, wall, or post. Provide handrails that are between 1¼ inches and 1½ inches in diameter with a continuous gripping surface along both sides of the ramp, extending at least 12 inches beyond the top and bottom of the ramp parallel with the ground surface. Ensure that handrails are mounted between 34 inches and 38 inches above the ramp surface and between 1¼ and 1½ inches from the wall, with ends rounded or returned smoothly to the floor, wall, or post, and that they do not rotate within their fittings. Standards § 4.8.5.

g.     Auditorium South Basement

i.    The auditorium lacks fixed aisle seating without armrests. Provide at least 3 aisle seats with no armrests on the aisle side, or with removable or folding armrests on the aisle side, identified by a sign or marker. Provide signage in the ticket office notifying patrons that such seating is available. Standards § 4.1.3(19)(a).

ii.    Although there are more than 50 seats provided in the auditorium, there is no assistive listening system. Provide a permanently installed assistive listening system serving the fixed seating. Ensure that the seating served by the system is located within a 50 foot viewing distance of the stage or playing area and has a complete view of the stage or playing area. Provide at least 12 receivers for use by the general public and signage indicating their availability. Standards §§ 4.30, 4.33.

h.     Mezzanine Drinking Fountain. The drinking fountain protrudes into the main walkway and would not be detectable to a blind person using a cane. Provide an accessible route at this location such that no objects with their bottom leading edges measuring between 27 inches and 80 inches above the finished floor protrude more than 4 inches into walks, halls, corridors, passageways, or aisles. Free-standing objects mounted on posts or pylons may overhang 12 inches maximum from 27 inches to 80 inches above the ground or finished floor. Standards § 4.4.

i.    South Wing Counters

i.    The Information Center counter is 42 inches high. Provide a counter on an accessible route such that a portion of the counter is at least 36 inches wide and no more than 36 inches above the finished floor, or provide an auxiliary counter with a maximum height of 36 inches in close proximity to the main counter, or provide equivalent facilitation. Equivalent facilitation may be provided in the form of a folding shelf attached to the main counter, an auxiliary table nearby, a clip board made available to the public, or other means. Standards §§ 7.2(2), 4.3.

ii.    The Museum Gift Shop counter is 38½ inches high. Provide a counter on an accessible route such that a portion of the counter is at least 36 inches wide and no more than 36 inches above the finished floor. Standards §§ 7.2(1), 4.3.

j.     South Wing Telephone. The telephone is not hearing aid compatible and does not have volume control. Provide an accessible telephone with a clear floor space of at least 30 inches by 48 inches that allows either a forward or parallel approach by a person using a wheelchair such that bases, enclosures, and fixed seats do not impede approaches to the telephone; with the highest operable part of the telephone mounted no more than 48 inches above the floor for a front approach or no more than 54 inches above the floor for a side approach; that is hearing aid compatible and has a volume control mechanism; with telephone books, if provided, located between 15 and 48 inches above the finished floor for a front approach or between 9 and 54 inches above the finished floor for a side approach; with a cord of at least 29 inches long from the telephone to the handset; and with signage that complies with the Standards. Standards §§ 4.31, 4.30.7(2).

k.     South Wing Men’s Toilet Room. The lavatory’s hot water pipes are not insulated or otherwise configured to protect against contact. Provide hot water and drain pipes that are insulated or otherwise configured to protect against contact. Standards § 4.19.4.

l.     Mezzanine Men’s Toilet Room

i.    The toilet in the designated accessible stall has its flush control on the closed side. Provide a flush control mounted on the “open” side of the toilet’s clear floor space; 44 inches or less above the finished floor; and requiring a maximum of 5 pounds of force to operate; or provide an automatic flush device. Standards §§ 4.16.5, 4.17.2, 4.27.4.

ii.    The toilet paper dispenser in the designated accessible stall is mounted above the grab bar. Provide a toilet paper dispenser that is mounted with its top at least 1½ inches under the side grab bar and 36 inches or less from the rear wall and is centered at least 19 inches above the finished floor. Standards § 4.17.3, Fig. 30(d).

m.     Mezzanine Women’s Toilet Room. The toilet paper dispenser in the designated accessible stall is mounted above the grab bar. Provide a toilet paper dispenser that is mounted with its top at least 1½ inches under the side grab bar and 36 inches or less from the rear wall and is centered at least 19 inches above the finished floor. Standards § 4.17.3, Fig. 30(d).

n.     Unisex Toilet Room Junior Museum Second Level

i.    The toilet room is kept locked. Provide a fully accessible, unlocked toilet room or make the inaccessible men’s and women’s 2nd floor toilet rooms accessible.

ii.    The toilet’s centerline measures 22 inches from the side wall. Provide a toilet with a centerline that measures 18 inches from the near side wall. Standards § 4.17.3, Fig. 30.

iii.    The paper towel dispenser protrudes into the main walkway and would not be detectable to a blind person using a cane. Provide an accessible route at this location such that no objects with their bottom leading edges measuring between 27 inches and 80 inches above the finished floor protrude more than 4 inches into walks, halls, corridors, passageways, or aisles. Free-standing objects mounted on posts or pylons may overhang 12 inches maximum from 27 inches to 80 inches above the ground or finished floor. Standards § 4.4.

o.     Second Floor Men’s Toilet Room

i.    The toilet in the designated accessible stall has its flush control on the closed side. Provide a flush control mounted on the “open” side of the toilet’s clear floor space; 44 inches or less above the finished floor; and requiring a maximum of 5 pounds of force to operate; or provide an automatic flush device. Standards §§ 4.16.5, 4.17.2, 4.27.4.

ii.    The paper towel dispenser protrudes into the main walkway and would not be detectable to a blind person using a cane. Provide an accessible route at this location such that no objects with their bottom leading edges measuring between 27 inches and 80 inches above the finished floor protrude more than 4 inches into walks, halls, corridors, passageways, or aisles. Free-standing objects mounted on posts or pylons may overhang 12 inches maximum from 27 inches to 80 inches above the ground or finished floor. Standards § 4.4.

p.     Second Floor Women’s Toilet Room. The paper towel dispenser protrudes into the main walkway and would not be detectable to a blind person using a cane. Provide an accessible route at this location such that no objects with their bottom leading edges measuring between 27 inches and 80 inches above the finished floor protrude more than 4 inches into walks, halls, corridors, passageways, or aisles. Free-standing objects mounted on posts or pylons may overhang 12 inches maximum from 27 inches to 80 inches above the ground or finished floor. Standards § 4.4.

q.     Third Floor Men’s Toilet Room

i.    The toilet in the designated accessible stall has its flush control on the closed side. Provide a flush control mounted on the “open” side of the toilet’s clear floor space; 44 inches or less above the finished floor; and requiring a maximum of 5 pounds of force to operate; or provide an automatic flush device. Standards §§ 4.16.5, 4.17.2, 4.27.4.

ii.    The paper towel dispenser protrudes into the main walkway and would not be detectable to a blind person using a cane. Provide an accessible route at this location such that no objects with their bottom leading edges measuring between 27 inches and 80 inches above the finished floor protrude more than 4 inches into walks, halls, corridors, passageways, or aisles. Free-standing objects mounted on posts or pylons may overhang 12 inches maximum from 27 inches to 80 inches above the ground or finished floor. Standards § 4.4.

r.     Third Floor Women’s Toilet Room. The paper towel dispenser protrudes into the main walkway and would not be detectable to a blind person using a cane. Provide an accessible route at this location such that no objects with their bottom leading edges measuring between 27 inches and 80 inches above the finished floor protrude more than 4 inches into walks, halls, corridors, passageways, or aisles. Free-standing objects mounted on posts or pylons may overhang 12 inches maximum from 27 inches to 80 inches above the ground or finished floor. Standards § 4.4.

s.     The path of travel to the first floor Sunken Court (the Main Court) includes 5 steps. Provide at least one accessible route within the boundary of the site connecting the Sunken Court with other elements that, to the maximum extent feasible, coincides with the route for the general public. The accessible route must have a minimum clear width of 36 inches, or a minimum clear width of 42 inches if there is a turn around an obstruction less than 48 inches wide; have passing spaces at least 60 inches by 60 inches at least every 200 feet; have a minimum clear headroom of 80 inches; have a surface that is firm, stable, and slip resistant; have, in the absence of a ramp, elevator, or platform lift, no level changes in excess of ½ inch vertically; and have a running slope of less than 1:20 (5%) (or have been constructed as a fully accessible ramp) and a cross slope of less than 1:50 (2%). Standards §§ 4.3, 4.5, Fig. 7.

6.     Within 30 months of the effective date of this Agreement, the City will make the following modifications to the Department of Neighborhood and Recreational Services, Division of Inspections and Enforcement, located at 159 Hansberry Avenue.

a.     Accessible Route. The route into the facility is not level. Provide at least one accessible route to the facility that, to the maximum extent feasible, coincides with the route for the general public. The accessible route must have a minimum clear width of 36 inches, or a minimum clear width of 42 inches if there is a turn around an obstruction less than 48 inches wide; have passing spaces at least 60 inches by 60 inches at least every 200 feet; have a minimum clear headroom of 80 inches; have a surface that is firm, stable, and slip resistant; have, in the absence of a curb ramp, ramp, elevator, or platform lift, no level changes in excess of ½ inch vertically; and have a running slope of less than 1:20 (5%) (or have been constructed as a fully accessible ramp) and a cross slope of less than 1:50 (2%). Standards §§ 4.3, 4.5, Fig. 7.

b.     Unisex Toilet Room

i.    There is a 6 inch step into the toilet room. Provide at least one accessible route into the toilet room that, to the maximum extent feasible, coincides with the route for the general public. The accessible route must have a minimum clear width of 36 inches, or a minimum clear width of 42 inches if there is a turn around an obstruction less than 48 inches wide; have passing spaces at least 60 inches by 60 inches at least every 200 feet; have a minimum clear headroom of 80 inches; have a surface that is firm, stable, and slip resistant; have, in the absence of a curb ramp, ramp, elevator, or platform lift, no level changes in excess of ½ inch vertically; and have a running slope of less than 1:20 (5%) (or have been constructed as a fully accessible ramp) and a cross slope of less than 1:50 (2%). Standards §§ 4.3, 4.5, Fig. 7.

ii.    The toilet room sign is incorrectly mounted and does not have raised characters or Braille. Provide a toilet room sign with raised and Braille characters mounted on the wall adjacent to the latch side of the door with the centerline of the sign at 60 inches above the finished floor and situated such that a person can approach within 3 inches of the sign without encountering an obstruction or standing within a door swing. Standards §§ 4.1.2(7)(d), 4.30.1, 4.30.4, 4.30.5, 4.30.6.

iii.    The door has knob hardware. Provide a door with hardware usable with one hand and without tight grasping, pinching, or twisting of the wrist. Lever-operated, push-type, and U-shaped handles are acceptable designs. Standards § 4.13.9.

iv.    No accessible mirror has been provided. Provide a mirror with the bottom edge of its reflecting surface no more than 40 inches above the finished floor. Standards § 4.19.6.

v.    The toilet room door swings into the required clear floor space at the lavatory and toilet. Ensure that no door swings into the required clear floor space at any accessible fixtures. Standards § 4.22.2.

vi.    There is 51½ inches by 68 inches of turning space in the room. Provide an unobstructed turning space at least 60 inches in diameter or a T-shaped space complying with Fig. 3(b). Standards §§ 4.22.3, 4.2.3, Fig. 3.

vii.    The soap dispenser is mounted 60 inches above the finished floor. Provide a soap dispenser with the controls a maximum height above the finished floor of 48 inches for a forward approach or 54 inches for a side approach and that is accompanied by clear floor space of 30 by 48 inches that allows a forward or parallel approach by a person using a wheelchair. Standards §§ 4.27.2, 4.27.3, 4.2.4, 4.2.5, 4.2.6.

viii.    The lavatory’s hot water pipes are not insulated or otherwise configured to protect against contact. Provide hot water and drain pipes that are insulated or otherwise configured to protect against contact. Standards § 4.19.4.

ix.    The top of the toilet seat is 15½ inches above the finished floor. Provide a toilet with a seat that measures 17 to 19 inches above the finished floor. Standards § 4.16.3, Fig. 29(b).

x.    The toilet’s centerline measures 15 inches from the side wall. Provide a toilet with a centerline that measures 18 inches from the near side wall. Standards § 4.16.2, Fig. 28.

xi.    There are no grab bars provided at the toilet. Provide a rear grab bar that is at least 36 inches in overall length, with the closer end no more than 6 inches from the side wall, and a side grab bar that is at least 42 inches in overall length, with the far end mounted at least 54 inches from the rear wall and the closer end 12 inches or less from the rear wall. Ensure that the grab bars are mounted 33 to 36 inches above the finished floor; with a diameter between 1¼ and 1½ inches; with 1½ inches between the grab bars and the wall; and at least 1½ inches between the grab bars and any other object, such as a toilet paper dispenser or a toilet seat cover dispenser. Standards §§ 4.16.4, 4.26.2, Fig. 29.

xii.    The lavatory is inaccessible because it has twist faucet hardware. Provide a lavatory with a faucet that can be operated with 5 pounds of force or less and can be used with one hand and without tight grasping, pinching, or twisting of the wrist (lever-operated, push-type, and electronically controlled mechanisms are examples of acceptable designs). Standards §§ 4.19.5, 4.27.4.

7.     Within 30 months of the effective date of this Agreement, the City will make the following modifications to the Department of Neighborhood Services, Division of Inspections and Enforcement, located at 44 Mt. Prospect Avenue.

a.     Unisex Toilet Room

i.    The toilet room sign is incorrectly mounted and does not have raised characters or Braille. Provide a toilet room sign with raised and Braille characters mounted on the wall adjacent to the latch side of the door with the centerline of the sign at 60 inches above the finished floor and situated such that a person can approach within 3 inches of the sign without encountering an obstruction or standing within a door swing. Standards §§ 4.1.2(7)(d), 4.30.1, 4.30.4, 4.30.5, 4.30.6.

ii.    The door has knob hardware. Provide a door with hardware usable with one hand and without tight grasping, pinching, or twisting of the wrist. Lever-operated, push-type, and U-shaped handles are acceptable designs. Standards § 4.13.9.

iii.    The paper towel dispenser is mounted 65 inches above the finished floor. Provide a paper towel dispenser with the controls a maximum height above the finished floor of 48 inches for a forward approach or 54 inches for a side approach and that is accompanied by clear floor space of 30 by 48 inches that allows a forward or parallel approach by a person using a wheelchair. Standards §§ 4.27.2, 4.27.3, 4.2.4, 4.2.5, 4.2.6.

iv.    The lavatory does not provide adequate knee and toe clearance. Provide a lavatory with the top of its rim or counter 34 inches or less above the finished floor; the bottom edge of the apron at least 29 inches above the finished floor; and knee and toe clearances that comply with Fig. 31. Standards § 4.19.2, Fig. 31.

v.    The lavatory has twist-type hardware. Provide a lavatory with a faucet that can be operated with 5 pounds of force or less and can be used with one hand and without tight grasping, pinching, or twisting of the wrist (lever-operated, push-type, and electronically controlled mechanisms are examples of acceptable designs). Standards §§ 4.19.5, 4.27.4.

vi.    The stall is only 32 inches wide. Provide a “standard” accessible toilet stall at least 60 inches wide and at least 59 inches deep (or at least 56 inches deep with a wall-mounted toilet). Standards § 4.17, Fig. 30.

vii.    The top of the toilet seat is 16 inches above the finished floor. Provide a toilet with a seat that measures 17 to 19 inches above the finished floor. Standards §§ 4.16.3, 4.17.2, Fig. 30(d).

viii.    The toilet’s centerline measures 15 inches from the side wall. Provide a toilet with a centerline that measures 18 inches from the near side wall. Standards § 4.17.3, Fig. 30.

ix.    The toilet paper dispenser is mounted behind the toilet. Provide a toilet paper dispenser that is mounted with its top at least 1½ inches under the side grab bar and 36 inches or less from the rear wall and is centered at least 19 inches above the finished floor. Standards § 4.17.3, Fig. 30(d).

x.    There are no grab bars provided at the toilet. Provide a rear grab bar that is at least 36 inches in overall length, with the closer end no more than 6 inches from the side wall, and a side grab bar that is at least 42 inches in overall length, with the far end mounted at least 54 inches from the rear wall and the closer end 12 inches or less from the rear wall. Ensure that the grab bars are mounted 33 to 36 inches above the finished floor; with a diameter between 1¼ and 1½ inches; with 1½ inches between the grab bars and the wall; and at least 1½ inches between the grab bars and any other object, such as a toilet paper dispenser or a toilet seat cover dispenser. Standards §§ 4.16.4, 4.26.2, Fig. 29.

8.     Within 30 months of the effective date of this Agreement, the City will make the following modifications to the East District Police, located at 649 Market Street.

a.     Entrance

i.    There are stairs at the entrance. Provide at least one accessible route into the building that, to the maximum extent feasible, coincides with the route for the general public. The accessible route must have a minimum clear width of 36 inches, or a minimum clear width of 42 inches if there is a turn around an obstruction less than 48 inches wide; have passing spaces at least 60 inches by 60 inches at least every 200 feet; have a minimum clear headroom of 80 inches; have a surface that is firm, stable, and slip resistant; have, in the absence of a curb ramp, ramp, elevator, or platform lift, no level changes in excess of ½ inch vertically; and have a running slope of less than 1:20 (5%) (or have been constructed as a fully accessible ramp) and a cross slope of less than 1:50 (2%). Standards §§ 4.3, 4.5, Fig. 7.

ii.    The entrance door has an opening width of only 27 inches. Provide a designated accessible entrance with a clear opening of 32 inches with the door open 90 degrees, measured between the face of the door and the opposite stop. Standards § 4.13.5, Fig. 24.

b.     Unisex Toilet Room with Stalls

i.    The toilet room sign is incorrectly mounted and does not have raised characters or Braille. Provide a toilet room sign with raised and Braille characters mounted on the wall adjacent to the latch side of the door with the centerline of the sign at 60 inches above the finished floor and situated such that a person can approach within 3 inches of the sign without encountering an obstruction or standing within a door swing. Standards §§ 4.1.2(7)(d), 4.30.1, 4.30.4, 4.30.5, 4.30.6.

ii.    The pressure required to open the door is greater than 5 pounds. Provide a door that requires no more than 5 pounds of force to open. Standards § 4.13.11(2)(b).

iii.    The door has knob hardware. Provide a door with hardware usable with one hand and without tight grasping, pinching, or twisting of the wrist. Lever-operated, push-type, and U-shaped handles are acceptable designs. Standards § 4.13.9.

iv.    There is a 6 inch step into the toilet room. Provide at least one accessible route into the toilet room that, to the maximum extent feasible, coincides with the route for the general public. The accessible route must have a minimum clear width of 36 inches, or a minimum clear width of 42 inches if there is a turn around an obstruction less than 48 inches wide; have passing spaces at least 60 inches by 60 inches at least every 200 feet; have a minimum clear headroom of 80 inches; have a surface that is firm, stable, and slip resistant; have, in the absence of a curb ramp, ramp, elevator, or platform lift, no level changes in excess of ½ inch vertically; and have a running slope of less than 1:20 (5%) (or have been constructed as a fully accessible ramp) and a cross slope of less than 1:50 (2%). Standards §§ 4.3, 4.5, Fig. 7.

v.    The lavatory apron is 27 inches above the finished floor and there is insufficient knee and toe clearances. Provide a lavatory with the top of its rim or counter 34 inches or less above the finished floor; the bottom edge of the apron at least 29 inches above the finished floor; and knee and toe clearances that comply with Fig. 31. Standards § 4.19.2, Fig. 31.

vi.    The lavatory’s hot water pipes are not insulated or otherwise configured to protect against contact. Provide hot water and drain pipes that are insulated or otherwise configured to protect against contact. Standards § 4.19.4.

vii.    The urinal does have an elongated rim, and the rim is 24 inches above the finished floor. Provide a urinal with an elongated rim mounted 17 inches or less above the finished floor, a clear floor space of at least 30 inches wide and 48 inches deep centered on the urinal, and a flush control height of 44 inches or less above the finished floor. Standards §§ 4.18.2, 4.18.3, 4.18.4.

viii.    There is no accessible stall provided. Provide a “standard” accessible toilet stall at least 60 inches wide and at least 59 inches deep (or at least 56 inches deep with a wall-mounted toilet) such that all of the stall’s elements, including stall door, stall door hardware, water closet, size and arrangement, toe clearances, grab bars, controls, and dispensers, comply with the Standards. Standards §§ 4.13, 4.16, 4.17, 4.26, 4.27, Fig. 30.

9.     Within 30 months of the effective date of this Agreement, the City will make the following modifications to the Fire Department Headquarters, located at 1010 18th Avenue.

a.     Entrance. There are steps at the voting entrance door and the Norwood Street public entrance. Provide at least one accessible route into the building that, to the maximum extent feasible, coincides with the route for the general public. The accessible route must have a minimum clear width of 36 inches, or a minimum clear width of 42 inches if there is a turn around an obstruction less than 48 inches wide; have passing spaces at least 60 inches by 60 inches at least every 200 feet; have a minimum clear headroom of 80 inches; have a surface that is firm, stable, and slip resistant; have, in the absence of a curb ramp, ramp, elevator, or platform lift, no level changes in excess of ½ inch vertically; and have a running slope of less than 1:20 (5%) (or have been constructed as a fully accessible ramp) and a cross slope of less than 1:50 (2%). Standards §§ 4.3, 4.5, Fig. 7.

b.     Counter. The counter at the Norwood Street public entrance is 43 inches high. Provide a counter on an accessible route such that a portion of the counter is at least 36 inches wide and no more than 36 inches above the finished floor, or provide an auxiliary counter with a maximum height of 36 inches in close proximity to the main counter, or provide equivalent facilitation. Equivalent facilitation may be provided in the form of a folding shelf attached to the main counter, an auxiliary table nearby, a clip board made available to the public, or other means. Standards §§ 7.2(2), 4.3.

10.     Within 30 months of the effective date of this Agreement, the City will make the following modifications to Fire Station Engine 5, located at 65 Congress Street.

a.     Entrance. There is a 6.2 % slope at the bay doors. Provide at least one accessible route into the facility that, to the maximum extent feasible, coincides with the route for the general public. The accessible route must have a minimum clear width of 36 inches, or a minimum clear width of 42 inches if there is a turn around an obstruction less than 48 inches wide; have passing spaces at least 60 inches by 60 inches at least every 200 feet; have a minimum clear headroom of 80 inches; have a surface that is firm, stable, and slip resistant; have, in the absence of a curb ramp, ramp, elevator, or platform lift, no level changes in excess of ½ inch vertically; and have a running slope of less than 1:20 (5%) (or have been constructed as a fully accessible ramp) and a cross slope of less than 1:50 (2%). Standards §§ 4.3, 4.5, Fig. 7.

11.     Within 30 months of the effective date of this Agreement, the City will make the following modifications to Fire Station Engine 9, located at 197 to 199 Summer Avenue.

a.     Entrance. The call button on the side of the building is 61 inches high. Provide a call button on an accessible route with the controls a maximum height above the finished floor of 48 inches for a forward approach or 54 inches for a side approach and that is accompanied by clear floor space of 30 by 48 inches that allows a forward or parallel approach by a person using a wheelchair. Standards §§ 4.27.2, 4.27.3, 4.2.4, 4.2.5, 4.2.6.

12.     Within 30 months of the effective date of this Agreement, the City will make the following modifications to Fire Station Engine 13, located at 714 to 718 Mt. Prospect Avenue.

a.     Entrance. There is a 5 inch step at the entrance door. Provide at least one accessible route into the building that, to the maximum extent feasible, coincides with the route for the general public. The accessible route must have a minimum clear width of 36 inches, or a minimum clear width of 42 inches if there is a turn around an obstruction less than 48 inches wide; have passing spaces at least 60 inches by 60 inches at least every 200 feet; have a minimum clear headroom of 80 inches; have a surface that is firm, stable, and slip resistant; have, in the absence of a curb ramp, ramp, elevator, or platform lift, no level changes in excess of ½ inch vertically; and have a running slope of less than 1:20 (5%) (or have been constructed as a fully accessible ramp) and a cross slope of less than 1:50 (2%). Standards §§ 4.3, 4.5, Fig. 7.

13.     Within 30 months of the effective date of this Agreement, the City will make the following modifications to Fire Station Engine 15, located at 269 to 271 Park Avenue.

a.     Entrance

i.    There is a 6 inch step at the entrance door. Provide at least one accessible route into the building that, to the maximum extent feasible, coincides with the route for the general public. The accessible route must have a minimum clear width of 36 inches, or a minimum clear width of 42 inches if there is a turn around an obstruction less than 48 inches wide; have passing spaces at least 60 inches by 60 inches at least every 200 feet; have a minimum clear headroom of 80 inches; have a surface that is firm, stable, and slip resistant; have, in the absence of a curb ramp, ramp, elevator, or platform lift, no level changes in excess of ½ inch vertically; and have a running slope of less than 1:20 (5%) (or have been constructed as a fully accessible ramp) and a cross slope of less than 1:50 (2%). Standards §§ 4.3, 4.5, Fig. 7.

ii.    The call button is 62 inches high. Provide a call button on an accessible route with the controls a maximum height above the finished floor of 48 inches for a forward approach or 54 inches for a side approach and that is accompanied by clear floor space of 30 by 48 inches that allows a forward or parallel approach by a person using a wheelchair. Standards §§ 4.27.2, 4.27.3, 4.2.4, 4.2.5, 4.2.6.

14.     Within 30 months of the effective date of this Agreement, the City will make the following modifications to Fire Station Engine 19, located at 526 to 528 Frelinghuysen Avenue.

a.     Entrance. There is a 2½ inch step at the bay doors. Provide at least one accessible route into the building that, to the maximum extent feasible, coincides with the route for the general public. The accessible route must have a minimum clear width of 36 inches, or a minimum clear width of 42 inches if there is a turn around an obstruction less than 48 inches wide; have passing spaces at least 60 inches by 60 inches at least every 200 feet; have a minimum clear headroom of 80 inches; have a surface that is firm, stable, and slip resistant; have, in the absence of a curb ramp, ramp, elevator, or platform lift, no level changes in excess of ½ inch vertically; and have a running slope of less than 1:20 (5%) (or have been constructed as a fully accessible ramp) and a cross slope of less than 1:50 (2%). Standards §§ 4.3, 4.5, Fig. 7.

15.     Within 30 months of the effective date of this Agreement, the City will make the following modifications to Fire Station Engine 21 & 26, located at 420 to 428 Sanford Avenue.

a.     Entrance. The ramp to the present polling entrance has a slope of 10.5 %, and the proposed entrance has a slope of 5.8%. Provide at least one accessible route into the building that, to the maximum extent feasible, coincides with the route for the general public. The accessible route must have a minimum clear width of 36 inches, or a minimum clear width of 42 inches if there is a turn around an obstruction less than 48 inches wide; have passing spaces at least 60 inches by 60 inches at least every 200 feet; have a minimum clear headroom of 80 inches; have a surface that is firm, stable, and slip resistant; have, in the absence of a curb ramp, ramp, elevator, or platform lift, no level changes in excess of ½ inch vertically; and have a running slope of less than 1:20 (5%) (or have been constructed as a fully accessible ramp) and a cross slope of less than 1:50 (2%). Standards §§ 4.3, 4.5, Fig. 7.

16.     Within 30 months of the effective date of this Agreement, the City will make the following modifications to Fire Station Engine 28, located at 691 North 6th Street.

a.     Entrance

i.    There is a 7 inch step at the entrance door. Provide at least one accessible route into the building that, to the maximum extent feasible, coincides with the route for the general public. The accessible route must have a minimum clear width of 36 inches, or a minimum clear width of 42 inches if there is a turn around an obstruction less than 48 inches wide; have passing spaces at least 60 inches by 60 inches at least every 200 feet; have a minimum clear headroom of 80 inches; have a surface that is firm, stable, and slip resistant; have, in the absence of a curb ramp, ramp, elevator, or platform lift, no level changes in excess of ½ inch vertically; and have a running slope of less than 1:20 (5%) (or have been constructed as a fully accessible ramp) and a cross slope of less than 1:50 (2%). Standards §§ 4.3, 4.5, Fig. 7.

ii.    The call button is 56½ inches high. Provide a call button on an accessible route with the controls a maximum height above the finished floor of 48 inches for a forward approach or 54 inches for a side approach and that is accompanied by clear floor space of 30 by 48 inches that allows a forward or parallel approach by a person using a wheelchair. Standards §§ 4.27.2, 4.27.3, 4.2.4, 4.2.5, 4.2.6.

17.     Within 30 months of the effective date of this Agreement, the City will make the following modifications to the First Avenue Branch Library, located at 282 First Avenue.

a.     Entrance

i.    There is a step at the entrance door. Provide at least one accessible route into the building that, to the maximum extent feasible, coincides with the route for the general public. The accessible route must have a minimum clear width of 36 inches, or a minimum clear width of 42 inches if there is a turn around an obstruction less than 48 inches wide; have passing spaces at least 60 inches by 60 inches at least every 200 feet; have a minimum clear headroom of 80 inches; have a surface that is firm, stable, and slip resistant; have, in the absence of a curb ramp, ramp, elevator, or platform lift, no level changes in excess of ½ inch vertically; and have a running slope of less than 1:20 (5%) (or have been constructed as a fully accessible ramp) and a cross slope of less than 1:50 (2%). Standards §§ 4.3, 4.5, Fig. 7.

ii.    The entrance door has knob hardware. Provide a door with hardware that is easy to grasp with one hand and that does not require tight grasping, pinching, or twisting of the wrist to operate. Lever-operated mechanisms, push-type mechanisms, and U-shaped handles are acceptable designs. Standards § 4.13.9.

b.     Accessible Route. The route from the entrance past the reception desk is 25 inches wide. Provide an accessible route at the location with a minimum clear width of 36 inches, except at doors, where the width may decrease to 32 inches. Standards §§ 4.3.3, 4.13.5.

c.     Unisex Toilet Room. The entrance door to the toilet room is 24 inches wide and the toilet room contains numerous inaccessible elements and is not accessible to people with disabilities. Provide an accessible toilet room such that all of the room’s elements, including signage, door, door hardware, clear floor space, water closet, urinal (if provided), grab bars, lavatory, mirror, controls, and dispensers, comply with the Standards. Standards §§ 4.13, 4.16, 4.18, 4.19, 4.26, 4.27, 4.30, Figs. 28, 29.

d.     Seating. There is no accessible seating provided in the library. Provide accessible tables on an accessible route at least 36 inches wide. Ensure that the tables have clear floor space of 30 inches wide by 48 inches deep, knee clearance of at least 27 inches high by 30 inches wide by 19 inches deep, and a writing surface between 28 and 34 inches above the finished floor. Standards §§ 8.2, 4.2.4.1, 4.32.

e.     Card Catalogs and Magazine Displays. The card catalogs and magazine displays have inaccessible reach ranges and insufficient width between catalogs. Provide card catalogs and magazine displays with a minimum of 36 inches of clear width between units and with reach ranges of between 18 inches and 54 inches (maximum height of 48 inches is preferred) above the finished floor. Standards § 8.4, Fig. 55.

f.     Stacks. There is insufficient width between the stacks. Provide at least 36 inches of clear width between all stacks and provide a clear width of 42 inches between stacks where possible. Standards § 8.5, Fig. 56.

18.     Within 30 months of the effective date of this Agreement, the City will make the following modifications to the Hayes Park West Pool, located at 179 Boyd Street.

a.     Entrance Ramp. The ramp lacks a handrail on the inside, and the handrail lacks extensions on the top and bottom. Provide handrails that are between 1¼ inches and 1½ inches in diameter such that the inside handrail is continuous and both handrails have a continuous gripping surface along both sides of the ramp extending at least 12 inches beyond the top and bottom of the ramp parallel with the ground surface; the handrails do not rotate within their fittings; and both handrails are mounted between 34 inches and 38 inches above the ramp surface, with ends rounded or returned smoothly to the floor, wall, or post. Standards § 4.8.5.

b.     Telephone. The telephone is mounted with its highest operable part 60 inches above the finished floor. Provide an accessible telephone with a clear floor space of at least 30 inches by 48 inches that allows either a forward or parallel approach by a person using a wheelchair such that bases, enclosures, and fixed seats do not impede approaches to the telephone; with the highest operable part of the telephone mounted no more than 48 inches above the floor for a front approach or no more than 54 inches above the floor for a side approach; that is hearing aid compatible and has a volume control mechanism; with a cord of at least 29 inches long from the telephone to the handset; and with signage that complies with the Standards. Standards §§ 4.31, 4.30.7(2).

c.     Entrance to Rec Center / Access to Pool. There is a 1¾ inch step at the entrance. Provide at least one accessible route to the Rec Center / Pool that, to the maximum extent feasible, coincides with the route for the general public. The accessible route must have a minimum clear width of 36 inches, or a minimum clear width of 42 inches if there is a turn around an obstruction less than 48 inches wide; have passing spaces at least 60 inches by 60 inches at least every 200 feet; have a minimum clear headroom of 80 inches; have a surface that is firm, stable, and slip resistant; have, in the absence of a curb ramp, ramp, elevator, or platform lift, no level changes in excess of ½ inch vertically; and have a running slope of less than 1:20 (5%) (or have been constructed as a fully accessible ramp) and a cross slope of less than 1:50 (2%). Standards §§ 4.3, 4.5, Fig. 7.

d.     Entrance Door to Pool Shower Rooms. The pressure required to open the door is 12 pounds. Provide a door that requires no more than 5 pounds of force to open. Standards § 4.13.11(2)(b).

e.     Women’s and Men’s Toilet Room with Stalls

i.    The toilet room signs are mounted on the door. For each room, provide a toilet room sign with raised and Braille characters mounted on the wall adjacent to the latch side of the door with the centerline of the sign at 60 inches above the finished floor and situated such that a person can approach within 3 inches of the sign without encountering an obstruction or standing within a door swing. Standards §§ 4.1.2(7)(d), 4.30.1, 4.30.4, 4.30.5, 4.30.6.

ii.    The seat cover dispenser in the women’s toilet room is mounted 65 inches high. Provide a seat cover dispenser with the controls a maximum height above the finished floor of 48 inches for a forward approach or 54 inches for a side approach and that is accompanied by clear floor space of 30 by 48 inches that allows a forward or parallel approach by a person using a wheelchair. Standards §§ 4.27.2, 4.27.3, 4.2.4, 4.2.5, 4.2.6.

iii.    The soap dispenser in each room is mounted 54 inches high with a forward reach required. In each room, provide a soap dispenser with the controls a maximum height above the finished floor of 48 inches for a forward approach or 54 inches for a side approach and that is accompanied by clear floor space of 30 by 48 inches that allows a forward or parallel approach by a person using a wheelchair. Standards §§ 4.27.2, 4.27.3, 4.2.4, 4.2.5, 4.2.6.

iv.    In each room, the lavatory’s hot water pipes are not insulated or otherwise configured to protect against contact. In each room, provide hot water and drain pipes that are insulated or otherwise configured to protect against contact. Standards § 4.19.4.

v.    In the women’s toilet room, the lavatories have twist-type hardware. Provide a lavatory with a faucet that can be operated with 5 pounds of force or less and can be used with one hand and without tight grasping, pinching, or twisting of the wrist (lever-operated, push-type, and electronically controlled mechanisms are examples of acceptable designs). Standards §§ 4.19.5, 4.27.4.

vi.    The urinals in the men’s toilet room do not have elongated rims, the rims are 21 inches high, and the flush controls are 46 inches high. Provide a urinal with an elongated rim mounted 17 inches or less above the finished floor, a clear floor space of at least 30 inches wide and 48 inches deep centered on the urinal, and a flush control height of 44 inches or less above the finished floor. Standards §§ 4.18.2, 4.18.3, 4.18.4.

vii.    There is no accessible stall provided in either toilet room. In each room, provide a “standard” accessible toilet stall at least 60 inches wide and at least 59 inches deep (or at least 56 inches deep with a wall-mounted toilet) such that all of the stall’s elements, including stall door, stall door hardware, water closet, size and arrangement, toe clearances, grab bars, controls, and dispensers, comply with the Standards. Standards §§ 4.13, 4.16, 4.17, 4.26, 4.27, Fig. 30.

f.     Drinking Fountain

i.    The drinking fountain’s controls require more than 5 pounds to operate. Provide a drinking fountain with controls mounted on or near the front edge that are operable with one hand, that require 5 lbf or less to operate, and that can be operated without tight grasping, pinching, or twisting of the wrist. Standards §§ 4.15.4, 4.27.4.

ii.    Although an accessible drinking fountain is provided, there is no drinking fountain provided for people who have difficulty bending or stooping. Provide a drinking fountain that is accessible to people who have difficulty bending or stooping. This can be accommodated by the use of a “hi-lo” fountain; by providing one fountain accessible to those who use wheelchairs and one fountain at a standard height convenient for those who have difficulty bending; by providing a fountain accessible to people who use wheelchairs and a cup dispenser, or by such other means as would achieve the required accessibility for each group of people. Standards § 4.1.3(10)(a).

19.     Within 30 months of the effective date of this Agreement, the City will make the following modifications to Health and Human Services, located at 110 William Street.

a.     Exterior Main Entrance Ramp. The ramp has no level landing at the top and the handrails are 28 inches high, do not have extensions at the top or bottom, and do not have a diameter of 1¼ to 1½ inches. Provide a ramp that is at least 36 inches wide with a slope not exceeding 1:12 and a cross slope not exceeding 1:50; with level landings at least as wide as the ramp and 60 inches long at the top and bottom of the ramp; and with edge protection at least 2 inches high at the drop off sides. Provide handrails that are between 1¼ inches and 1½ inches in diameter with a continuous gripping surface along both sides of the ramp, extending at least 12 inches beyond the top and bottom of the ramp parallel with the ground surface. Ensure that handrails are mounted between 34 inches and 38 inches above the ramp surface, with ends rounded or returned smoothly to the floor, wall, or post, and that they do not rotate within their fittings. Ensure that the ramp and approaches are designed so that water will not accumulate on walking surfaces. Standards §§ 4.3.8, 4.8.

b.     Interior Doors

i.    There is no accessible signage provided. Provide permanent room signage with upper case, sans serif or simple serif type letters and numerals, meeting the requirements of the Standards for character height, raised characters, finish and contrast, accompanied by Grade 2 Braille; mounted on the wall adjacent to the latch side of the door or on the nearest adjacent wall at a height of 60 inches above the finished floor to the centerline of the sign; and located so that a person may approach within 3 inches of the signage without encountering protruding objects or standing within the swing of a door. Standards §§ 4.30.1, 4.30.4, 4.30.5, 4.30.6.

ii.    Knob hardware is used throughout the facility. Provide doors with hardware that is easy to grasp with one hand and that does not require tight grasping, pinching, or twisting of the wrist to operate. Lever-operated mechanisms, push-type mechanisms, and U-shaped handles are acceptable designs. Standards § 4.13.9.

c.     Counters

i.    The lobby counter is 42½ inches high. Provide a counter on an accessible route such that a portion of the counter is at least 36 inches wide and no more than 36 inches above the finished floor, or provide an auxiliary counter with a maximum height of 36 inches in close proximity to the main counter, or provide equivalent facilitation. Equivalent facilitation may be provided in the form of a folding shelf attached to the main counter, an auxiliary table nearby, a clip board made available to the public, or other means. Standards §§ 7.2(2), 4.3.

ii.    The security desk counter is 43 inches high. Provide a counter on an accessible route such that a portion of the counter is at least 36 inches wide and no more than 36 inches above the finished floor, or provide an auxiliary counter with a maximum height of 36 inches in close proximity to the main counter, or provide equivalent facilitation. Equivalent facilitation may be provided in the form of a folding shelf attached to the main counter, an auxiliary table nearby, a clip board made available to the public, or other means. Standards §§ 7.2(2), 4.3.

iii.    The cashier’s counter is 40 inches high. Provide a counter on an accessible route such that a portion of the counter is at least 36 inches wide and no more than 36 inches above the finished floor. Standards §§ 7.2(1), 4.3.

d.     Lower Level Telephone. The telephone is not hearing aid compatible, does not have volume control, and does not have signage as required. Provide an accessible telephone with a clear floor space of at least 30 inches by 48 inches that allows either a forward or parallel approach by a person using a wheelchair such that bases, enclosures, and fixed seats do not impede approaches to the telephone; with the highest operable part of the telephone mounted no more than 48 inches above the floor for a front approach or no more than 54 inches above the floor for a side approach; that is hearing aid compatible and has a volume control mechanism; with telephone books, if provided, located between 15 and 48 inches above the finished floor for a front approach or between 9 and 54 inches above the finished floor for a side approach; with a cord of at least 29 inches long from the telephone to the handset; and with signage that complies with the Standards. Standards §§ 4.31, 4.30.7(2).

e.     Toilet Rooms with Stalls

i.    The toilet room sign for each room is incorrectly mounted and does not have raised characters or Braille. For each toilet room, provide a toilet room sign with raised and Braille characters mounted on the wall adjacent to the latch side of the door with the centerline of the sign at 60 inches above the finished floor and situated such that a person can approach within 3 inches of the sign without encountering an obstruction or standing within a door swing. Standards §§ 4.1.2(7)(d), 4.30.1, 4.30.4, 4.30.5, 4.30.6.

ii.    The pressure required to open the men’s lobby toilet room door is 9 pounds, the women’s lobby toilet room door is 10 pounds, the men’s lower level toilet room door is 10 pounds, and the women’s lower level toilet room door is 10 pounds. For each room, provide a door that requires no more than 5 pounds of force to open. Standards § 4.13.11(2)(b).

iii.    The lavatory in each toilet room has hot water pipes that are not insulated or otherwise configured to protect against contact. In each room, provide hot water and drain pipes that are insulated or otherwise configured to protect against contact. Standards § 4.19.4.

iv.    The urinal in each men’s toilet room does not have an elongated rim. In each men’s toilet room, provide a urinal with an elongated rim mounted 17 inches or less above the finished floor, a clear floor space of at least 30 inches wide and 48 inches deep centered on the urinal, and a flush control height of 44 inches or less above the finished floor. Standards §§ 4.18.2, 4.18.3, 4.18.4.

v.    In each toilet room, the toilet paper dispenser is mounted 39 inches from the wall and above the side grab bar. Provide a toilet paper dispenser that is mounted with its top at least 1½ inches under the side grab bar and 36 inches or less from the rear wall and is centered at least 19 inches above the finished floor. Standards § 4.17.3, Fig. 30(d).

vi.    None of the toilet rooms has a rear grab. Provide a rear grab bar that is at least 36 inches in overall length, with the closer end no more than 6 inches from the side wall; mounted 33 to 36 inches above the finished floor; with a diameter between 1¼ and 1½ inches; with 1½ inches between the grab bar and the wall; and at least 1½ inches between the grab bar and any other object, such as a toilet seat cover dispenser. Standards §§ 4.17.6, 4.26.2, Fig. 30.

f.     Single-User Toilet Rooms

i.    The toilet room sign for each room is incorrectly mounted and does not have raised characters or Braille. For each toilet room, provide a toilet room sign with raised and Braille characters mounted on the wall adjacent to the latch side of the door with the centerline of the sign at 60 inches above the finished floor and situated such that a person can approach within 3 inches of the sign without encountering an obstruction or standing within a door swing. Standards §§ 4.1.2(7)(d), 4.30.1, 4.30.4, 4.30.5, 4.30.6.

ii.    In each toilet room, the lavatories have twist-type hardware. In each room, provide a lavatory with a faucet that can be operated with 5 pounds of force or less and can be used with one hand and without tight grasping, pinching, or twisting of the wrist (lever-operated, push-type, and electronically controlled mechanisms are examples of acceptable designs). Standards §§ 4.19.5, 4.27.4.

iii.    In each toilet room, the paper towel dispenser protrudes into the main walkway and would not be detectable to a blind person using a cane. Provide an accessible route at this location such that no objects with their bottom leading edges measuring between 27 inches and 80 inches above the finished floor protrude more than 4 inches into walks, halls, corridors, passageways, or aisles. Free-standing objects mounted on posts or pylons may overhang 12 inches maximum from 27 inches to 80 inches above the ground or finished floor. Standards § 4.4.

iv.    In each toilet room, the paper towel dispenser is inaccessible because the operation requires tight grasping. Provide a paper towel dispenser in each toilet room with mechanical controls, if any, that can be operated with 5 lbf or less and that can be used with one hand and without tight grasping, pinching, or twisting of the wrist (lever-operated, push-type, and electronically controlled mechanisms are examples of acceptable designs). Ensure that the controls are a maximum height above the finished floor of 48 inches for a forward approach or 54 inches for a side approach and that it is accompanied by clear floor space of 30 by 48 inches that allows a forward or parallel approach by a person using a wheelchair. Standards §§ 4.27.2, 4.27.3, 4.27.4, 4.2.4, 4.2.5, 4.2.6.

v.    In each toilet room, the rear grab bar is 26 inches long. In each room, provide a rear grab bar that is at least 36 inches in overall length with the closer end no more than 6 inches from the side wall. Standards § 4.16.4, Fig. 29.

g.     Drinking Fountains. The fountains in the lobby and on the lower level each have spouts that are 39 inches above the finished floor. On each floor, provide a fountain that has a spout height no higher than 36 inches, measured from the finished floor or ground surface to the spout outlet, and that otherwise complies with the Standards. Standards §§ 4.15, 4.27.4, Fig. 27.

20.     Within 30 months of the effective date of this Agreement, the City will make the following modifications to the James and Gibson Recreation and Aquatic Center, located at St. Charles and Rome Streets.

a.     Entrance to Ice Rink. Each of the double-leaf entrance doors has 30 inches of clearance. Provide an entrance that has at least one active leaf with a minimum 32 inch clear opening width with the door open 90 degrees, measured between the face of the door and the opposite stop; that has either an automatic door operator or clear and level maneuvering clearance that complies fully with Fig. 25; and that has a threshold not exceeding ½ inch in height and beveled with a slope no greater than 1:2. Standards § 4.13, Figs. 24, 25.

b.     Assembly Area Seating. There are no accessible seats in the bleachers. Provide accessible wheelchair seats in conformance with Standards § 4.1.3(19)(a), each with a minimum clear ground or floor space of 66 inches wide by 48 inches deep for forward or rear access, or 66 inches wide by 60 inches deep for side access. Ensure that the ground or floor at all wheelchair locations is level, firm, stable, and slip resistant; that wheelchair seating areas are an integral part of the fixed seating plan and are located so as to provide people with physical disabilities a choice of admission prices and lines of sight comparable to those available for members of the general public; that wheelchair seating areas adjoin an accessible route that also serves as a means of egress in case of emergency; and that at least one fixed companion seat is provided next to each wheelchair seating area. Standards §§ 4.1.3(19)(a), 4.5, 4.33.

c.     Drinking Fountains. Each of 5 the drinking fountains in the facility has a spout between 41 and 42 inches high and has insufficient knee space. Provide at least 3 drinking fountain with a spout height no higher than 36 inches, measured from the finished floor or ground surface to the spout outlet; and a spout located at the front of the unit that directs the water flow in a trajectory that is nearly parallel to the front of the unit and is positioned so the flow of water is within 3 inches of the front edge of the fountain and at least 4 inches high. Ensure that fountain controls are operable with one hand, require 5 lbf or less to operate without tight grasping, pinching, or twisting of the wrist; and are front mounted or side mounted near the front edge. Additionally, provide a drinking fountain that is accessible to people who have difficulty bending or stooping. This can be accommodated by the use of a “hi-lo” fountain; by providing one fountain accessible to those who use wheelchairs and one fountain at a standard height convenient for those who have difficulty bending; by providing a fountain accessible to people who use wheelchairs and a cup dispenser; or by such other means as would achieve the required accessibility for each group of people. Standards §§ 4.15, 4.27.4, Fig. 27.

d.     Two of the Drinking Fountains, located in the Ice Rink Area, protrude into the main walkway and would not be detectable to a blind person using a cane. Provide an accessible route at these two locations such that no objects with their bottom leading edges measuring between 27 inches and 80 inches above the finished floor protrude more than 4 inches into walks, halls, corridors, passageways, or aisles. Free-standing objects mounted on posts or pylons may overhang 12 inches maximum from 27 inches to 80 inches above the ground or finished floor. Standards § 4.4.

e.     Toilet Rooms with Stalls

i.    The toilet room sign for each room is incorrectly mounted and does not have raised characters or Braille. For each toilet room, provide a toilet room sign with raised and Braille characters mounted on the wall adjacent to the latch side of the door with the centerline of the sign at 60 inches above the finished floor and situated such that a person can approach within 3 inches of the sign without encountering an obstruction or standing within a door swing. Standards §§ 4.1.2(7)(d), 4.30.1, 4.30.4, 4.30.5, 4.30.6.

ii.    Each toilet room door has knob hardware. For each room, provide doors with hardware that is easy to grasp with one hand and that does not require tight grasping, pinching, or twisting of the wrist to operate. Lever-operated mechanisms, push-type mechanisms, and U-shaped handles are acceptable designs. Standards § 4.13.9.

iii.    The entry door to the women’s toilet room requires 11 pounds of force to open. Provide a door that requires no more than 5 pounds of force to open. Standards § 4.13.11(2)(b).

iv.    The entry door to the women's toilet room, which is accessed through a front approach and which has both a closer and a latch, is inaccessible because the push side of the door has less than 12 inches of maneuvering clearance on the latch side. On the push side of the door, provide maneuvering clearance at least 48 inches deep and provide a minimum of 12 inches of maneuvering clearance on the latch side of the door, or remove the closer or the latch. Standards § 4.13.6, Fig. 25(a).

v.    The entry door to the men's toilet room, which is accessed through a front approach, is inaccessible because the pull side has less than 18 inches of maneuvering clearance on the latch side of the door. On the pull side of the door, provide maneuvering clearance at least 60 inches deep and provide a minimum of 18 inches (24 inches is preferred) of maneuvering clearance on the latch side of the door. Standards § 4.13.6, Fig. 25(a).

vi.    The soap dispenser in the men’s toilet room is 51 inches high with a forward reach required. Provide a soap dispenser with the controls a maximum height above the finished floor of 48 inches for a forward approach or 54 inches for a side approach and that is accompanied by clear floor space of 30 by 48 inches that allows a forward or parallel approach by a person using a wheelchair. Standards §§ 4.27.2, 4.27.3, 4.2.4, 4.2.5, 4.2.6.

vii.    The paper towel dispenser in the men’s toilet room is 60 inches high with a forward reach required, and the paper towel dispenser in the women’s toilet room is 57 inches high. In each room, provide a paper towel dispenser with the controls a maximum height above the finished floor of 48 inches for a forward approach or 54 inches for a side approach and that is accompanied by clear floor space of 30 by 48 inches that allows a forward or parallel approach by a person using a wheelchair. Standards §§ 4.27.2, 4.27.3, 4.2.4, 4.2.5, 4.2.6.

viii.    The paper towel dispenser in each toilet room protrudes into the main walkway and would not be detectable to a blind person using a cane. Provide an accessible route at these locations such that no objects with their bottom leading edges measuring between 27 inches and 80 inches above the finished floor protrude more than 4 inches into walks, halls, corridors, passageways, or aisles. Free-standing objects mounted on posts or pylons may overhang 12 inches maximum from 27 inches to 80 inches above the ground or finished floor. Standards § 4.4.

ix.    The lavatory in each toilet room does not have hot water pipes that are insulated or otherwise configured to protect against contact. In each room, provide hot water and drain pipes that are insulated or otherwise configured to protect against contact. Standards § 4.19.4.

x.    The rim of the urinal in the men’s toilet room is not elongated and is mounted 22 inches high. Provide a urinal with an elongated rim mounted 17 inches or less above the finished floor, a clear floor space of at least 30 inches wide and 48 inches deep centered on the urinal, and a flush control height of 44 inches or less above the finished floor. Standards §§ 4.18.2, 4.18.3, 4.18.4.

xi.    There is no accessible stall provided in either toilet room. In each room, provide a “standard” accessible toilet stall at least 60 inches wide and at least 59 inches deep (or at least 56 inches deep with a wall-mounted toilet) such that all of the stall’s elements, including stall door, stall door hardware, water closet, size and arrangement, toe clearances, grab bars, controls, and dispensers, comply with the Standards. Standards §§ 4.13, 4.16, 4.17, 4.26, 4.27, Fig. 30.

f.     Unisex Team Locker Rooms 3 and 4

i.    The locker room sign for each room is incorrectly mounted and does not have raised characters or Braille. For each locker room, provide a toilet room sign with raised and Braille characters mounted on the wall adjacent to the latch side of the door with the centerline of the sign at 60 inches above the finished floor and situated such that a person can approach within 3 inches of the sign without encountering an obstruction or standing within a door swing. Standards §§ 4.1.2(7)(d), 4.30.1, 4.30.4, 4.30.5, 4.30.6.

ii.    Each locker room door has knob hardware. For each room, provide doors with hardware that is easy to grasp with one hand and that does not require tight grasping, pinching, or twisting of the wrist to operate. Lever-operated mechanisms, push-type mechanisms, and U-shaped handles are acceptable designs. Standards § 4.13.9.

iii.    The entry door to each locker room requires 9 pounds of force to open. For each room, provide a door that requires no more than 5 pounds of force to open. Standards § 4.13.11(2)(b).

iv.    The entry door to each locker room, which is accessed through a front approach, is inaccessible because the pull side has less than 18 inches of maneuvering clearance on the latch side of the door. On the pull side of the door, for each room, provide maneuvering clearance at least 60 inches deep and provide a minimum of 18 inches (24 inches is preferred) of maneuvering clearance on the latch side of the door. Standards § 4.13.6, Fig. 25(a).

v.    The lavatories in each locker room do not have hot water pipes that are insulated or otherwise configured to protect against contact. In each room, provide hot water and drain pipes that are insulated or otherwise configured to protect against contact. Standards § 4.19.4.

vi.    The lavatories in each locker room have twist-type hardware. Provide a lavatory with a faucet that can be operated with 5 pounds of force or less and can be used with one hand and without tight grasping, pinching, or twisting of the wrist (lever-operated, push-type, and electronically controlled mechanisms are examples of acceptable designs). Standards §§ 4.19.5, 4.27.4.

vii.    The shelf in each locker room protrudes into the main walkway and would not be detectable to a blind person using a cane. Provide an accessible route at this location such that no objects with their bottom leading edges measuring between 27 inches and 80 inches above the finished floor protrude more than 4 inches into walks, halls, corridors, passageways, or aisles. Free-standing objects mounted on posts or pylons may overhang 12 inches maximum from 27 inches to 80 inches above the ground or finished floor. Standards § 4.4.

viii.    There is no accessible stall provided in either locker room. In each locker room, provide a “standard” accessible toilet stall at least 60 inches wide and at least 59 inches deep (or at least 56 inches deep with a wall-mounted toilet) such that all of the stall’s elements, including stall door, stall door hardware, water closet, size and arrangement, toe clearances, grab bars, controls, and dispensers, comply with the Standards. Standards §§ 4.13, 4.16, 4.17, 4.26, 4.27, Fig. 30.

ix.    There is no accessible shower provided in either locker room. In each room, provide a shower that is exactly 36 inches wide and 36 inches deep with a 48 inch long and 36 inch wide clear floor space alongside the shower opening, and an L-shaped shower seat mounted on the wall opposite the controls and extending the full depth of the stall; OR a shower that is at least 30 inches deep and 60 inches wide with no curb or threshold and with a 36 inch deep and 60 inch wide clear floor space at the shower opening. Ensure that the shower has grab bars, controls, a shower spray unit, and a seat, curb, and enclosure, if provided, that comply fully with the Standards and with Figs. 35, 36, and 37, as applicable. Standards § 4.21, Figs. 35, 36, 37.

g.     Unisex Team Locker Rooms 5/6 and 1/2

i.    The locker room sign for each room is incorrectly mounted and does not have raised characters or Braille. For each locker room, provide a toilet room sign with raised and Braille characters mounted on the wall adjacent to the latch side of the door with the centerline of the sign at 60 inches above the finished floor and situated such that a person can approach within 3 inches of the sign without encountering an obstruction or standing within a door swing. Standards §§ 4.1.2(7)(d), 4.30.1, 4.30.4, 4.30.5, 4.30.6.

ii.    Each locker room door has knob hardware. For each room, provide doors with hardware that is easy to grasp with one hand and that does not require tight grasping, pinching, or twisting of the wrist to operate. Lever-operated mechanisms, push-type mechanisms, and U-shaped handles are acceptable designs. Standards § 4.13.9.

iii.    The entry door to each locker room, which is accessed through a front approach, is inaccessible because the pull side has less than 18 inches of maneuvering clearance on the latch side of the door. On the pull side of the door, for each room, provide maneuvering clearance at least 60 inches deep and provide a minimum of 18 inches (24 inches is preferred) of maneuvering clearance on the latch side of the door. Standards § 4.13.6, Fig. 25(a).

iv.    The lavatories in each locker room do not have hot water pipes that are insulated or otherwise configured to protect against contact. In each room, provide hot water and drain pipes that are insulated or otherwise configured to protect against contact. Standards § 4.19.4.

v.    The lavatories in each locker room have twist-type hardware. In each room, provide a lavatory with a faucet that can be operated with 5 pounds of force or less and can be used with one hand and without tight grasping, pinching, or twisting of the wrist (lever-operated, push-type, and electronically controlled mechanisms are examples of acceptable designs). Standards §§ 4.19.5, 4.27.4.

vi.    There is no accessible stall provided in either locker room. In each locker room, provide a “standard” accessible toilet stall at least 60 inches wide and at least 59 inches deep (or at least 56 inches deep with a wall-mounted toilet) such that all of the stall’s elements, including stall door, stall door hardware, water closet, size and arrangement, toe clearances, grab bars, controls, and dispensers, comply with the Standards. Standards §§ 4.13, 4.16, 4.17, 4.26, 4.27, Fig. 30.

vii.    There is no accessible shower provided in either locker room. In each room, provide a shower that is exactly 36 inches wide and 36 inches deep with a 48 inch long and 36 inch wide clear floor space alongside the shower opening, and an L-shaped shower seat mounted on the wall opposite the controls and extending the full depth of the stall; OR a shower that is at least 30 inches deep and 60 inches wide with no curb or threshold and with a 36 inch deep and 60 inch wide clear floor space at the shower opening. Ensure that the shower has grab bars, controls, a shower spray unit, and a seat, curb, and enclosure, if provided, that comply fully with the Standards and with Figs. 35, 36, and 37, as applicable. Standards § 4.21, Figs. 35, 36, 37.

21.     Within 30 months of the effective date of this Agreement, the City will make the following modifications to the John F. Kennedy Recreation Center, located at 211 West Kinney Street.

a.     Accessible Route. The double-leaf doors into the gym from the men’s and women’s toilet rooms are each 24 inches wide. Provide a designated accessible entrance that has at least one active leaf with a minimum 32 inch clear opening width with the door open 90 degrees, measured between the face of the door and the opposite stop; that has either an automatic door operator or clear and level maneuvering clearance that complies fully with Fig. 25; and that has a threshold not exceeding ½ inch in height and beveled with a slope no greater than 1:2. Standards § 4.13, Figs. 24, 25.

b.     Gym

i.    There is no accessible seating provided in the stands Provide accessible wheelchair seats in conformance with Standards § 4.1.3(19)(a), each with a minimum clear ground or floor space of 66 inches wide by 48 inches deep for forward or rear access, or 66 inches wide by 60 inches deep for side access. Ensure that the ground or floor at all wheelchair locations is level, firm, stable, and slip resistant; that wheelchair seating areas are an integral part of the fixed seating plan and are located so as to provide people with physical disabilities a choice of admission prices and lines of sight comparable to those available for members of the general public; that wheelchair seating areas adjoin an accessible route that also serves as a means of egress in case of emergency; and that at least one fixed companion seat is provided next to each wheelchair seating area. Standards §§ 4.1.3(19)(a), 4.5, 4.33.

ii.    No accessible coat hook has been provided in the gym. Provide a coat hook at a maximum height above the finished floor of 48 inches for a forward approach or 54 inches for a side approach and that is accompanied by clear floor space of 30 by 48 inches that allows a forward or parallel approach by a person using a wheelchair. Standards §§ 4.25.2, 4.25.3, 4.2.4, 4.2.5, 4.2.6.

c.     Toilet Room with Stalls

i.    The toilet room sign for each room is incorrectly mounted and does not have raised characters or Braille. For each toilet room, provide a toilet room sign with raised and Braille characters mounted on the wall adjacent to the latch side of the door with the centerline of the sign at 60 inches above the finished floor and situated such that a person can approach within 3 inches of the sign without encountering an obstruction or standing within a door swing. Standards §§ 4.1.2(7)(d), 4.30.1, 4.30.4, 4.30.5, 4.30.6.

ii.    Each toilet room door has knob hardware. For each room, provide doors with hardware that is easy to grasp with one hand and that does not require tight grasping, pinching, or twisting of the wrist to operate. Lever-operated mechanisms, push-type mechanisms, and U-shaped handles are acceptable designs. Standards § 4.13.9.

iii.    The paper towel dispenser in each toilet room protrudes into the main walkway and would not be detectable to a blind person using a cane. Provide an accessible route at these locations such that no objects with their bottom leading edges measuring between 27 inches and 80 inches above the finished floor protrude more than 4 inches into walks, halls, corridors, passageways, or aisles. Free-standing objects mounted on posts or pylons may overhang 12 inches maximum from 27 inches to 80 inches above the ground or finished floor. Standards § 4.4.

iv.    The lavatories in each toilet room do not have hot water pipes that are insulated or otherwise configured to protect against contact. In each room, provide hot water and drain pipes that are insulated or otherwise configured to protect against contact. Standards § 4.19.4.

v.    The lavatories in each toilet room have twist-type hardware. In each room, provide a lavatory with a faucet that can be operated with 5 pounds of force or less and can be used with one hand and without tight grasping, pinching, or twisting of the wrist (lever-operated, push-type, and electronically controlled mechanisms are examples of acceptable designs). Standards §§ 4.19.5, 4.27.4.

vi.    There is no accessible stall provided in either toilet room. In each toilet room, provide a “standard” accessible toilet stall at least 60 inches wide and at least 59 inches deep (or at least 56 inches deep with a wall-mounted toilet) such that all of the stall’s elements, including stall door, stall door hardware, water closet, size and arrangement, toe clearances, grab bars, controls, and dispensers, comply with the Standards. Standards §§ 4.13, 4.16, 4.17, 4.26, 4.27, Fig. 30.

22.     Within 30 months of the effective date of this Agreement, the City will make the following modifications to the Mother Nellie Grier Senior Citizens Center, located at 104 Maple Avenue.

a.     Entrance

i.    There is no International Symbol of Accessibility at the accessible entrance and no directional signage at the inaccessible entrance. Provide accessible directional signage with the International Symbol of Accessibility at inaccessible entrances directing users to the accessible entrance, and provide accessible signage with the International Symbol of Accessibility at all permanent accessible entrances. Standards §§ 4.1.3(8)(d), 4.13, 4.30.

ii.    The route to the ramp on the Hansbury Avenue side of the building is in disrepair and contains several changes in level great than ½ inch. Provide at least one accessible route to the accessible entrance that, to the maximum extent feasible, coincides with the route for the general public. The accessible route must have a minimum clear width of 36 inches, or a minimum clear width of 42 inches if there is a turn around an obstruction less than 48 inches wide; have passing spaces at least 60 inches by 60 inches at least every 200 feet; have a minimum clear headroom of 80 inches; have a surface that is firm, stable, and slip resistant; have, in the absence of a curb ramp, ramp, elevator, or platform lift, no level changes in excess of ½ inch vertically; and have a running slope of less than 1:20 (5%) (or have been constructed as a fully accessible ramp) and a cross slope of less than 1:50 (2%). Standards §§ 4.3, 4.5, Fig. 7.

iii.    The entrance ramp on the Hansbury Avenue side of the building does not have a level landing at the bottom, does not have a handrail on the inside of the ramp, has no handrail extensions on the top or bottom of the ramp, and does not have edge protection. Provide a ramp that is at least 36 inches wide with a slope not exceeding 1:12 and a cross slope not exceeding 1:50; with level landings at least as wide as the ramp and 60 inches long at the top and bottom of the ramp; and with edge protection at least 2 inches high at the drop off sides. Provide handrails that are between 1¼ inches and 1½ inches in diameter with a continuous gripping surface along both sides of the ramp, extending at least 12 inches beyond the top and bottom of the ramp parallel with the ground surface. Ensure that handrails are mounted between 34 inches and 38 inches above the ramp surface, with ends rounded or returned smoothly to the floor, wall, or post, and that they do not rotate within their fittings. Ensure that the ramp and approaches are designed so that water will not accumulate on walking surfaces. Standards §§ 4.3.8, 4.8.

b.     Doors. The doors throughout the facility have knob hardware. Provide doors with hardware that is easy to grasp with one hand and that does not require tight grasping, pinching, or twisting of the wrist to operate. Lever-operated mechanisms, push-type mechanisms, and U-shaped handles are acceptable designs. Standards § 4.13.9.

c.     Men’s Toilet Room with Stalls

i.    The toilet room sign is incorrectly mounted and does not have raised characters or Braille. Provide a toilet room sign with raised and Braille characters mounted on the wall adjacent to the latch side of the door with the centerline of the sign at 60 inches above the finished floor and situated such that a person can approach within 3 inches of the sign without encountering an obstruction or standing within a door swing. Standards §§ 4.1.2(7)(d), 4.30.1, 4.30.4, 4.30.5, 4.30.6.

ii.    The entrance door is 29 inches wide. Provide a door with a clear opening of 32 inches with the door open 90 degrees, measured between the face of the door and the opposite stop. Standards § 4.13.5, Fig. 24.

iii.    The pressure required to open the entrance door is 10 pounds. Provide a door that requires no more than 5 pounds of force to open. Standards § 4.13.11(2)(b).10 lbs

iv.    The lavatory’s hot water pipes are not insulated or otherwise configured to protect against contact. Provide hot water and drain pipes that are insulated or otherwise configured to protect against contact. Standards § 4.19.4.No wrap

v.    There is no accessible stall provided. Provide a “standard” accessible toilet stall at least 60 inches wide and at least 59 inches deep (or at least 56 inches deep with a wall-mounted toilet) such that all of the stall’s elements, including stall door, stall door hardware, water closet, size and arrangement, toe clearances, grab bars, controls, and dispensers, comply with the Standards. Standards §§ 4.13, 4.16, 4.17, 4.26, 4.27, Fig. 30.

d.     Women’s Toilet Room with Stalls

i.    The toilet room sign is incorrectly mounted and does not have raised characters or Braille. Provide a toilet room sign with raised and Braille characters mounted on the wall adjacent to the latch side of the door with the centerline of the sign at 60 inches above the finished floor and situated such that a person can approach within 3 inches of the sign without encountering an obstruction or standing within a door swing. Standards §§ 4.1.2(7)(d), 4.30.1, 4.30.4, 4.30.5, 4.30.6.

ii.    The entrance door is 29½ inches wide. Provide a door with a clear opening of 32 inches with the door open 90 degrees, measured between the face of the door and the opposite stop. Standards § 4.13.5, Fig. 24.

iii.    The pressure required to open the entrance door is 10 pounds. Provide a door that requires no more than 5 pounds of force to open. Standards § 4.13.11(2)(b).10 lbs

iv.    The tampon dispenser is mounted with its controls 62½ inches high. Provide a tampon dispenser with the controls a maximum height above the finished floor of 48 inches for a forward approach or 54 inches for a side approach and that is accompanied by clear floor space of 30 by 48 inches that allows a forward or parallel approach by a person using a wheelchair. Standards §§ 4.27.2, 4.27.3, 4.2.4, 4.2.5, 4.2.6.

v.    The lavatory’s hot water pipes are not insulated or otherwise configured to protect against contact. Provide hot water and drain pipes that are insulated or otherwise configured to protect against contact. Standards § 4.19.4.No wrap

vi.    There is no accessible stall provided. Provide a “standard” accessible toilet stall at least 60 inches wide and at least 59 inches deep (or at least 56 inches deep with a wall-mounted toilet) such that all of the stall’s elements, including stall door, stall door hardware, water closet, size and arrangement, toe clearances, grab bars, controls, and dispensers, comply with the Standards. Standards §§ 4.13, 4.16, 4.17, 4.26, 4.27, Fig. 30.

e.     Main Room Drinking Fountain

i.    The drinking fountain’s spout is too high. Provide a fountain that has a spout height no higher than 36 inches, measured from the finished floor or ground surface to the spout outlet, and that otherwise complies with the Standards. Standards §§ 4.15, 4.27.4, Fig. 27.Spout too high

ii.    The drinking fountain has hardware that requires tight grasping, pinching, or twisting of the wrist to operate. Provide a drinking fountain with controls mounted on or near the front edge that are operable with one hand, that require 5 lbf or less to operate, and that can be operated without tight grasping, pinching, or twisting of the wrist. Standards §§ 4.15.4, 4.27.4.

f.     Head Start Program. The Head Start Program can only be accessed through the rear entrance, which has a 6 inch step. Provide at least one accessible route to the Head Start Program that, to the maximum extent feasible, coincides with the route for the general public. The accessible route must have a minimum clear width of 36 inches, or a minimum clear width of 42 inches if there is a turn around an obstruction less than 48 inches wide; have passing spaces at least 60 inches by 60 inches at least every 200 feet; have a minimum clear headroom of 80 inches; have a surface that is firm, stable, and slip resistant; have, in the absence of a curb ramp, ramp, elevator, or platform lift, no level changes in excess of ½ inch vertically; and have a running slope of less than 1:20 (5%) (or have been constructed as a fully accessible ramp) and a cross slope of less than 1:50 (2%). Standards §§ 4.3, 4.5, Fig. 7.

23.     Within 30 months of the effective date of this Agreement, the City will make the following modifications to the Municipal Court Annex Building, located at 31 Green Street.

a.     Entrance

i.    The path of travel to the facility is 27 inches wide at the entry point between two buildings. Provide an accessible route to the facility with a minimum clear width of 36 inches, except at doors, where the width may decrease to 32 inches. Standards §§ 4.3.3, 4.13.5.

ii.    There is no International Symbol of Accessibility at the accessible entrance and no directional signage at the inaccessible entrance. Provide accessible directional signage with the International Symbol of Accessibility at inaccessible entrances directing users to the accessible entrance, and provide accessible signage with the International Symbol of Accessibility at all permanent accessible entrances. Standards §§ 4.1.3(8)(d), 4.13, 4.30.

iii.    The exterior entrance ramp has a 2 inch step onto the ramp and there is more than 1½ inches between the handrail and the wall. Provide a ramp that is at least 36 inches wide with a slope not exceeding 1:12 and a cross slope not exceeding 1:50; with level landings at least as wide as the ramp and 60 inches long at the top and bottom of the ramp; and with edge protection at least 2 inches high at the drop off sides. Provide handrails that are between 1¼ inches and 1½ inches in diameter with a continuous gripping surface along both sides of the ramp, extending at least 12 inches beyond the top and bottom of the ramp parallel with the ground surface. Ensure that handrails are mounted between 34 inches and 38 inches above the ramp surface and 1½ inches from the wall, with ends rounded or returned smoothly to the floor, wall, or post, and that they do not rotate within their fittings. Ensure that the ramp and approaches are designed so that water will not accumulate on walking surfaces. Standards §§ 4.3.8, 4.8.

b.     Interior Doors

i.    There is no accessible signage throughout the facility. Provide permanent room signage with upper case, sans serif or simple serif type letters and numerals, meeting the requirements of the Standards for character height, raised characters, finish and contrast, accompanied by Grade 2 Braille; mounted on the wall adjacent to the latch side of the door or on the nearest adjacent wall at a height of 60 inches above the finished floor to the centerline of the sign; and located so that a person may approach within 3 inches of the signage without encountering protruding objects or standing within the swing of a door. Standards §§ 4.30.1, 4.30.4, 4.30.5, 4.30.6.

ii.    There is knob hardware on doors throughout the facility. Provide doors with hardware that is easy to grasp with one hand and that does not require tight grasping, pinching, or twisting of the wrist to operate. Lever-operated mechanisms, push-type mechanisms, and U-shaped handles are acceptable designs. Standards § 4.13.9.

c.     Telephones

i.    The phones on the 1st floor are not hearing aid compatible and do not have the required signage. Provide an accessible telephone with a clear floor space of at least 30 inches by 48 inches that allows either a forward or parallel approach by a person using a wheelchair such that bases, enclosures, and fixed seats do not impede approaches to the telephone; with the highest operable part of the telephone mounted no more than 48 inches above the floor for a front approach or no more than 54 inches above the floor for a side approach; that is hearing aid compatible and has a volume control mechanism; with telephone books, if provided, located between 15 and 48 inches above the finished floor for a front approach or between 9 and 54 inches above the finished floor for a side approach; with a cord of at least 29 inches long from the telephone to the handset; and with signage that complies with the Standards. Standards §§ 4.1.3(17)(a), 4.31, 4.30.7(2).

ii.    The telephones not in phone booths protrude into the main walkway and would not be detectable to a blind person using a cane. Provide an accessible route at this location such that no objects with their bottom leading edges measuring between 27 inches and 80 inches above the finished floor protrude more than 4 inches into walks, halls, corridors, passageways, or aisles. Free-standing objects mounted on posts or pylons may overhang 12 inches maximum from 27 inches to 80 inches above the ground or finished floor. Standards § 4.4.

d.     Offices and Counters

i.    The Violations Payment window is 45 inches high. Provide a counter on an accessible route such that a portion of the counter is at least 36 inches wide and no more than 36 inches above the finished floor, or provide an auxiliary counter with a maximum height of 36 inches in close proximity to the main counter, or provide equivalent facilitation. Equivalent facilitation may be provided in the form of a folding shelf attached to the main counter, an auxiliary table nearby, a clip board made available to the public, or other means. Standards §§ 7.2(2), 4.3.

ii.    Each of the double-leaf entrance doors to Room 105 is 27 inches wide. Provide an entrance that has at least one active leaf with a minimum 32 inch clear opening width with the door open 90 degrees, measured between the face of the door and the opposite stop; that has either an automatic door operator or clear and level maneuvering clearance that complies fully with Fig. 25; and that has a threshold not exceeding ½ inch in height and beveled with a slope no greater than 1:2. Ensure that all hardware and operating devices have shapes that are easy to grasp with one hand and do not require tight grasping, pinching, or twisting of the wrist to operate, and that they are mounted no higher than 48 inches above the finished floor. Standards § 4.13, Figs. 24, 25.

iii.    The path of travel around the chair in Room 105 is 26 inches wide. Provide an accessible route in this area with a minimum clear width of 36 inches, except at doors, where the width may decrease to 32 inches. Standards §§ 4.3.3, 4.13.5.

iv.    The information counter in Room 105 is 40 inches high. Provide a counter on an accessible route such that a portion of the counter is at least 36 inches wide and no more than 36 inches above the finished floor, or provide an auxiliary counter with a maximum height of 36 inches in close proximity to the main counter, or provide equivalent facilitation. Equivalent facilitation may be provided in the form of a folding shelf attached to the main counter, an auxiliary table nearby, a clip board made available to the public, or other means. Standards §§ 7.2(2), 4.3.

v.    The entry door to Room 203, which is accessed through a front approach and which has both a closer and a latch, is inaccessible because on the push side of the door it has less than 12 inches of maneuvering clearance on the latch side. On the push side of the door, provide maneuvering clearance at least 48 inches deep and provide a minimum of 12 inches of maneuvering clearance on the latch side of the door, or remove the closer or the latch. Standards § 4.13.6, Fig. 25(a).

vi.    The information counter in Room 203 is 40 inches high. Provide a counter on an accessible route such that a portion of the counter is at least 36 inches wide and no more than 36 inches above the finished floor, or provide an auxiliary counter with a maximum height of 36 inches in close proximity to the main counter, or provide equivalent facilitation. Equivalent facilitation may be provided in the form of a folding shelf attached to the main counter, an auxiliary table nearby, a clip board made available to the public, or other means. Standards §§ 7.2(2), 4.3.

e.     Elevators

i.    The elevators do not have hall lanterns. Provide hall lanterns at each hoistway entrance that emit a visible and audible signal indicating which car is answering a call. Ensure that audible signals sound once for the up direction and twice for the down direction or have verbal annunciators that say “up” or “down;” and that visible signals are mounted so that their centerline is at least 72 inches above the lobby floor, they are at least 2½ inches in the smallest dimension, and they are visible from the vicinity of the hall call button. Lanterns located in cars, visible from the vicinity of hall call buttons, and conforming to the above requirements, are acceptable. Standards § 4.10.4, Fig. 20.

ii.    The elevators do not have hoistway signage,. Provide signage at hoistway entrances with raised and Braille floor designations on both jambs such that the centerline of the characters is 60 inches above the finished floor and the characters are 2 inches high. Standards § 4.10.5, Fig. 20.

iii.    The elevators do not have door protective and reopening devices, and the elevator doors close too quickly. Provide doors that open and close automatically with a reopening device that will stop and reopen the car door and hoistway door automatically if the door becomes obstructed by an object or person. Ensure that the device is capable of completing these operations without requiring contact for obstructions passing through the opening at heights of 5 inches and 29 inches above the finished floor; that door reopening devices remain effective for at least 20 seconds, after which the doors may close; that the minimum time from notification that a car is answering a call until the doors of that car start to close is 5 seconds; and that the minimum time for elevator doors to remain fully open in response to a car call is 3 seconds. Standards §§ 4.10.6, 4.10.7, 4.10.8, Figs. 20, 21.

f.     1st Floor Drinking Fountain

i.    Although an accessible drinking fountain is provided, there is no drinking fountain provided for people who have difficulty bending or stooping. Provide a drinking fountain that is accessible to people who have difficulty bending or stooping. This can be accommodated by the use of a “hi-lo” fountain; by providing one fountain accessible to those who use wheelchairs and one fountain at a standard height convenient for those who have difficulty bending; by providing a fountain accessible to people who use wheelchairs and a cup dispenser, or by such other means as would achieve the required accessibility for each group of people. Standards § 4.1.3(10)(a).

ii.    The drinking fountain protrudes into the main walkway and would not be detectable to a blind person using a cane. Provide an accessible route at this location such that no objects with their bottom leading edges measuring between 27 inches and 80 inches above the finished floor protrude more than 4 inches into walks, halls, corridors, passageways, or aisles. Free-standing objects mounted on posts or pylons may overhang 12 inches maximum from 27 inches to 80 inches above the ground or finished floor. Standards § 4.4.

g.     Courtrooms

i.    Each of the double-leaf entrance doors to Courtroom Part 1 is 28 inches wide, and each leaf to Courtroom Part 7 is 29 inches wide. At each courtroom, provide an entrance that has at least one active leaf with a minimum 32 inch clear opening width with the door open 90 degrees, measured between the face of the door and the opposite stop; that has either an automatic door operator or clear and level maneuvering clearance that complies fully with Fig. 25; and that has a threshold not exceeding ½ inch in height and beveled with a slope no greater than 1:2. Ensure that all hardware and operating devices have shapes that are easy to grasp with one hand and do not require tight grasping, pinching, or twisting of the wrist to operate, and that they are mounted no higher than 48 inches above the finished floor. Standards § 4.13, Figs. 24, 25.

ii.    Although there are more than 50 fixed seats in each courtroom, there is no assistive listening system. In each courtroom, provide a permanently installed assistive listening system serving the fixed seating. Ensure that the seating served by the system is located within a 50 foot viewing distance of the stage or playing area and has a complete view of the stage or playing area. Provide receivers as required by Standards § 4.1.3(19)(b) for use by the general public and provide signage indicating their availability. Standards §§ 4.30, 4.33.

iii.    There are no accessible wheelchair seating locations provided in any of the courtrooms. In each courtroom, provide seats as required by Standards § 4.1.3(19)(a), each with a minimum clear ground or floor space of 66 inches wide by 48 inches deep for forward or rear access, or 66 inches wide by 60 inches deep for side access. Ensure that the ground or floor at all wheelchair locations is level, firm, stable, and slip resistant; that wheelchair seating areas are an integral part of the fixed seating plan and are located so as to provide people with physical disabilities a choice of lines of sight comparable to those available for members of the general public; that wheelchair seating areas adjoin an accessible route that also serves as a means of egress in case of emergency; and that at least one fixed companion seat is provided next to each wheelchair seating area. Standards §§ 4.1.3(19)(a), 4.5, 4.33.

h.     Toilet Rooms

i.    The toilet room signs are mounted incorrectly and do not raised characters or Braille. At each accessible toilet room, provide a toilet room sign with the International Symbol of Accessibility and raised and Braille characters mounted on the wall adjacent to the latch side of the door with the centerline of the sign at 60 inches above the finished floor and situated such that a person can approach within 3 inches of the sign without encountering an obstruction or standing within a door swing. Standards §§ 4.1.2(7)(d), 4.30.1, 4.30.4, 4.30.5, 4.30.6, 4.30.7.

ii.    There is no signage at the inaccessible toilet rooms directing people with disabilities to the accessible toilet rooms. Provide accessible directional signage with the International Symbol of Accessibility at inaccessible toilet rooms indicating the location of the nearest accessible toilet room, and provide accessible signage with the International Symbol of Accessibility at all accessible toilet rooms. Standards §§ 4.1.2(7)(d), 4.1.6(3)(e)(iii), 4.30.1, 4.30.2, 4.30.3, 4.30.5, 4.30.7.

iii.    No accessible mirror has been provided in either 1st floor toilet room. In each room, provide a mirror with the bottom edge of its reflecting surface no more than 40 inches above the finished floor. Standards § 4.19.6.

iv.    The lavatory in each 1st floor toilet room has hot water pipes that are not insulated or otherwise configured to protect against contact. In each room, provide hot water and drain pipes that are insulated or otherwise configured to protect against contact. Standards § 4.19.4.

v.    No accessible coat hook has been provided in either 1st floor toilet room. In each room, provide a coat hook at a maximum height above the finished floor of 48 inches for a forward approach or 54 inches for a side approach and that is accompanied by clear floor space of 30 by 48 inches that allows a forward or parallel approach by a person using a wheelchair. Standards §§ 4.25.2, 4.25.3, 4.2.4, 4.2.5, 4.2.6.

vi.    There are no grab bars provided at the designated accessible toilet in the 1st floor men’s toilet room. In the 1st floor women’s toilet room, there is no rear grab bar, and the side grab is mounted too far from the rear wall and has a receptacle mounted on top of it. In the designated accessible toilet stall in each toilet room, provide a rear grab bar that is at least 36 inches in overall length, with the closer end no more than 6 inches from the side wall, and a side grab bar that is at least 40 inches in overall length, with the far end mounted at least 54 inches from the rear wall and the closer end 12 inches or less from the rear wall. Ensure that the grab bars are mounted 33 to 36 inches above the finished floor; with a diameter between 1¼ and 1½ inches; with 1½ inches between the grab bar and the wall; and at least 1½ inches between the grab bar and any other object, such as a toilet seat cover dispenser or a toilet paper dispenser. Standards §§ 4.17.6, 4.26.2, Fig. 30.

vii.    The toilet paper dispenser in the 1st floor women's toilet room is inaccessible because it is located above the side grab bar. Provide a toilet paper dispenser that is mounted with its top at least 1½ inches under the side grab bar and 36 inches or less from the rear wall and is centered at least 19 inches above the finished floor. Standards § 4.17.3, Fig. 30(d).

viii.    The hand dryers in both 1st floor toilet rooms protrude into the main walkway and would not be detectable to a blind person using a cane. Provide an accessible route at these locations such that no objects with their bottom leading edges measuring between 27 inches and 80 inches above the finished floor protrude more than 4 inches into walks, halls, corridors, passageways, or aisles. Free-standing objects mounted on posts or pylons may overhang 12 inches maximum from 27 inches to 80 inches above the ground or finished floor. Standards § 4.4.

24.     Within 30 months of the effective date of this Agreement, the City will make the following modifications to the North District Police Department, located at 1 Lincoln Avenue.

a.     Interior Entrance Ramp. The ramp has no level landing at the top, no handrail on the inside, and no handrail extensions at the top or bottom. Provide a ramp that is at least 36 inches wide with a slope not exceeding 1:12 and a cross slope not exceeding 1:50; with level landings at least as wide as the ramp and 60 inches long at the top and bottom of the ramp; and with edge protection at least 2 inches high at the drop off sides. Provide handrails that are between 1¼ inches and 1½ inches in diameter with a continuous gripping surface along both sides of the ramp, extending at least 12 inches beyond the top and bottom of the ramp parallel with the ground surface. Ensure that handrails are mounted between 34 inches and 38 inches above the ramp surface, with ends rounded or returned smoothly to the floor, wall, or post, and that they do not rotate within their fittings. Ensure that the ramp and approaches are designed so that water will not accumulate on walking surfaces. Standards §§ 4.3.8, 4.8.

25.     Within 30 months of the effective date of this Agreement, the City will make the following modifications to the North District Community Service Substation, located at 928 Summer Avenue.

a.     Entrance. There is a 4 inch step at the entrance. Provide at least one accessible route into the facility that, to the maximum extent feasible, coincides with the route for the general public. The accessible route must have a minimum clear width of 36 inches, or a minimum clear width of 42 inches if there is a turn around an obstruction less than 48 inches wide; have passing spaces at least 60 inches by 60 inches at least every 200 feet; have a minimum clear headroom of 80 inches; have a surface that is firm, stable, and slip resistant; have, in the absence of a curb ramp, ramp, elevator, or platform lift, no level changes in excess of ½ inch vertically; and have a running slope of less than 1:20 (5%) (or have been constructed as a fully accessible ramp) and a cross slope of less than 1:50 (2%). Standards §§ 4.3, 4.5, Fig. 7.

26.     Within 30 months of the effective date of this Agreement, the City will make the following modifications to the Police Emergency Bureau, located at 472 Orange Street.

a.     Exterior Entrance Ramp. The ramp is too steep and has no edge protection, no handrails, and no level landing at the top. Provide a ramp that is at least 36 inches wide with a slope not exceeding 1:12 and a cross slope not exceeding 1:50; with level landings at least as wide as the ramp and 60 inches long at the top and bottom of the ramp; and with edge protection at least 2 inches high at the drop off sides. Provide handrails that are between 1¼ inches and 1½ inches in diameter with a continuous gripping surface along both sides of the ramp, extending at least 12 inches beyond the top and bottom of the ramp parallel with the ground surface. Ensure that handrails are mounted between 34 inches and 38 inches above the ramp surface, with ends rounded or returned smoothly to the floor, wall, or post, and that they do not rotate within their fittings. Ensure that the ramp and approaches are designed so that water will not accumulate on walking surfaces. Standards §§ 4.3.8, 4.8.

b.     Entrance Door. The entrance door has no level approach on the outside and no automatic opener. Provide a door so that the floor or ground area within the required clearances is level and clear, or provide an automatic door opener. Standards § 4.13.6, Fig. 25.

27.     Within 30 months of the effective date of this Agreement, the City will make the following modifications to the Police Headquarters, located at 22 Franklin Street.

a.     Sidewalk. The sidewalks are in disrepair and are not firm, stable, or slip-resistant. Provide at least one accessible route within the boundary of the site connecting these elements that, to the maximum extent feasible, coincides with the route for the general public. The accessible route must have a minimum clear width of 36 inches, or a minimum clear width of 42 inches if there is a turn around an obstruction less than 48 inches wide; have passing spaces at least 60 inches by 60 inches at least every 200 feet; have a minimum clear headroom of 80 inches; have a surface that is firm, stable, and slip resistant; have, in the absence of a curb ramp, ramp, elevator, or platform lift, no level changes in excess of ½ inch vertically; and have a running slope of less than 1:20 (5%) (or have been constructed as a fully accessible ramp) and a cross slope of less than 1:50 (2%). Standards §§ 4.3, 4.5, Fig. 7.

b.     Entrance. There is a 4 inch step at the entrance. Provide at least one accessible route into the facility that, to the maximum extent feasible, coincides with the route for the general public. The accessible route must have a minimum clear width of 36 inches, or a minimum clear width of 42 inches if there is a turn around an obstruction less than 48 inches wide; have passing spaces at least 60 inches by 60 inches at least every 200 feet; have a minimum clear headroom of 80 inches; have a surface that is firm, stable, and slip resistant; have, in the absence of a curb ramp, ramp, elevator, or platform lift, no level changes in excess of ½ inch vertically; and have a running slope of less than 1:20 (5%) (or have been constructed as a fully accessible ramp) and a cross slope of less than 1:50 (2%). Standards §§ 4.3, 4.5, Fig. 7.

c.     Interior Signage. There is no accessible signage provided in the facility. Provide permanent room signage with upper case, sans serif or simple serif type letters and numerals, meeting the requirements of the Standards for character height, raised characters, finish and contrast, accompanied by Grade 2 Braille; mounted on the wall adjacent to the latch side of the door or on the nearest adjacent wall at a height of 60 inches above the finished floor to the centerline of the sign; and located so that a person may approach within 3 inches of the signage without encountering protruding objects or standing within the swing of a door. Standards §§ 4.30.1, 4.30.4, 4.30.5, 4.30.6.

d.     Ramp to Internal Affairs. The ramp has a slope of 11.9 degrees, chairs protrude into the level landing at the top, there is no edge protection, there is a handrail on only one side, and the existing handrail does not have extensions at the top or bottom, does not have a diameter between 1¼ and 1½ inches and does not have ends that are rounded or returned smoothly to the wall, floor, or post. Provide a ramp that is at least 36 inches wide with a slope not exceeding 1:12 and a cross slope not exceeding 1:50; with level landings at least as wide as the ramp and 60 inches long at the top and bottom of the ramp; and with edge protection at least 2 inches high at the drop off sides. Provide handrails that are between 1¼ inches and 1½ inches in diameter with a continuous gripping surface along both sides of the ramp, extending at least 12 inches beyond the top and bottom of the ramp parallel with the ground surface. Ensure that handrails are mounted between 34 inches and 38 inches above the ramp surface, with ends rounded or returned smoothly to the floor, wall, or post, and that they do not rotate within their fittings. Ensure that the ramp and approaches are designed so that water will not accumulate on walking surfaces. Standards §§ 4.3.8, 4.8.

e.     Elevator

i.    The elevator has no hall lanterns. Provide hall lanterns at each hoistway entrance that emit a visible and audible signal indicating which car is answering a call. Ensure that audible signals sound once for the up direction and twice for the down direction or have verbal annunciators that say “up” or “down;” and that visible signals are mounted so that their centerline is at least 72 inches above the lobby floor, they are at least 2½ inches in the smallest dimension, and they are visible from the vicinity of the hall call button. Lanterns located in cars, visible from the vicinity of hall call buttons, and conforming to the above requirements, are acceptable. Standards § 4.10.4, Fig. 20.

ii.    The elevator door is only 34 inches wide. Provide an elevator with a door opening at least 36 inches wide. Standards § 4.10.9, Fig. 22.

f.     Counters

i.    The 1st floor reception counter is 40½ inches high. Provide a counter on an accessible route such that a portion of the counter is at least 36 inches wide and no more than 36 inches above the finished floor, or provide an auxiliary counter with a maximum height of 36 inches in close proximity to the main counter, or provide equivalent facilitation. Equivalent facilitation may be provided in the form of a folding shelf attached to the main counter, an auxiliary table nearby, a clip board made available to the public, or other means. Standards §§ 7.2(2), 4.3.

ii.    The 1st floor Records counter 42½ inches high. Provide a counter on an accessible route such that a portion of the counter is at least 36 inches wide and no more than 36 inches above the finished floor, or provide an auxiliary counter with a maximum height of 36 inches in close proximity to the main counter, or provide equivalent facilitation. Equivalent facilitation may be provided in the form of a folding shelf attached to the main counter, an auxiliary table nearby, a clip board made available to the public, or other means. Standards §§ 7.2(2), 4.3.

iii.    The 2nd floor Internal Affairs counter is 43 inches high. Provide a counter on an accessible route such that a portion of the counter is at least 36 inches wide and no more than 36 inches above the finished floor, or provide an auxiliary counter with a maximum height of 36 inches in close proximity to the main counter, or provide equivalent facilitation. Equivalent facilitation may be provided in the form of a folding shelf attached to the main counter, an auxiliary table nearby, a clip board made available to the public, or other means. Standards §§ 7.2(2), 4.3.

iv.    The 3rd floor Release and Auto Unit counters are 42 inches high. Provide a counter in this area on an accessible route such that a portion of the counter is at least 36 inches wide and no more than 36 inches above the finished floor, or provide an auxiliary counter with a maximum height of 36 inches in close proximity to the main counter, or provide equivalent facilitation. Equivalent facilitation may be provided in the form of a folding shelf attached to the main counter, an auxiliary table nearby, a clip board made available to the public, or other means. Standards §§ 7.2(2), 4.3.

v.    The 3rd floor Criminal Investigations counter is 40½ inches high. Provide a counter on an accessible route such that a portion of the counter is at least 36 inches wide and no more than 36 inches above the finished floor, or provide an auxiliary counter with a maximum height of 36 inches in close proximity to the main counter, or provide equivalent facilitation. Equivalent facilitation may be provided in the form of a folding shelf attached to the main counter, an auxiliary table nearby, a clip board made available to the public, or other means. Standards §§ 7.2(2), 4.3.

g.     Accessible Routes

i.    The sofa in the 1st floor Records office narrows the path of travel to 29 inches. Provide an accessible route through the office with a minimum clear width of 36 inches, except at doors, where the width may decrease to 32 inches. Standards §§ 4.3.3, 4.13.5.

ii.    The 1st floor Records office door has knob hardware. Provide a door with hardware that is easy to grasp with one hand and that does not require tight grasping, pinching, or twisting of the wrist to operate. Lever-operated mechanisms, push-type mechanisms, and U-shaped handles are acceptable designs. Standards § 4.13.9.

h.     Records Office Fingerprint Table. The table is 40½ inches high to the top. Provide a fingerprinting area on an accessible route such that there is knee space at least 27 inches high, 30 inches wide, and 19 inches deep, and such that the height of the top of the table or counter surface is between 28 inches and 34 inches above the ground. Standards §§ 4.32.3, 4.32.4.

28.     Within 30 months of the effective date of this Agreement, the City will make the following modifications to the Newark Public Library's Main Branch, located at 5 Washington Street.

a.     Entrance

i.    There are stairs up to the entrance. Provide at least one accessible route into the facility that, to the maximum extent feasible, coincides with the route for the general public. The accessible route must have a minimum clear width of 36 inches, or a minimum clear width of 42 inches if there is a turn around an obstruction less than 48 inches wide; have passing spaces at least 60 inches by 60 inches at least every 200 feet; have a minimum clear headroom of 80 inches; have a surface that is firm, stable, and slip resistant; have, in the absence of a curb ramp, ramp, elevator, or platform lift, no level changes in excess of ½ inch vertically; and have a running slope of less than 1:20 (5%) (or have been constructed as a fully accessible ramp) and a cross slope of less than 1:50 (2%). Standards §§ 4.3, 4.5, Fig. 7.

ii.    The interior entrance door requires 9 pounds of force to open. Provide a door that requires no more than 5 pounds of force to open. Standards § 4.13.11(2)(b).

b.     2nd Floor Toilet Rooms

i.    The signage for each room is incorrectly mounted and does not have raised characters or Braille. Provide a toilet room sign with raised and Braille characters mounted on the wall adjacent to the latch side of the door with the centerline of the sign at 60 inches above the finished floor and situated such that a person can approach within 3 inches of the sign without encountering an obstruction or standing within a door swing. Standards §§ 4.1.2(7)(d), 4.30.1, 4.30.4, 4.30.5, 4.30.6.

ii.    The women’s toilet room door requires 15 pounds of force to open. Provide a door that requires no more than 5 pounds of force to open. Standards § 4.13.11(2)(b).

iii.    Both toilet rooms have knob hardware. For each room, provide a door with hardware that is easy to grasp with one hand and that does not require tight grasping, pinching, or twisting of the wrist to operate. Lever-operated mechanisms, push-type mechanisms, and U-shaped handles are acceptable designs. Standards § 4.13.9.

iv.    A partition in the women’s toilet room narrows the path of travel to 31 inches; a partition in the men’s toilet room narrows the path of travel to 30 inches. In each room, provide an accessible route with a minimum clear width of 36 inches, except at doors, where the width may decrease to 32 inches. Standards §§ 4.3.3, 4.13.5.

v.    Although the facility contains an emergency alarm system, there is no visual alarm in either toilet room. Provide visual alarm devices in toilet rooms and any other general usage areas (e.g., meeting rooms), hallways, lobbies, and any other area for common use. Such devices shall be integrated into the facility alarm system and shall meet the requirements of the Standards for lamp type, color, pulse duration, intensity, and flash rate. Visual alarm appliances shall be placed 80 inches above the highest floor level within the space or 6 inches below the ceiling, whichever is lower. Visual alarm appliances shall be located such that no place in any room or space, including common corridors or hallways, required to have a visual alarm appliance shall be more than 50 feet from the signal. In large rooms and spaces exceeding 100 feet across, without obstructions 6 feet above the finished floor, devices may be placed around the perimeter, spaced a maximum of 100 feet apart, in lieu of suspending appliances from the ceiling. Standards § 4.28.3.

vi.    No accessible mirror has been provided in either toilet room. In each room, provide a mirror with the bottom edge of its reflecting surface no more than 40 inches above the finished floor. Standards § 4.19.6.

vii.    The paper towel dispenser in the women’s toilet room is mounted 60 inches high, and the paper towel dispenser in the men’s toilet room is mounted 58 inches high over the lavatory. In each room, provide a paper towel dispenser with the controls a maximum height above the finished floor of 48 inches for a forward approach or 54 inches for a side approach and that is accompanied by clear floor space of 30 by 48 inches that allows a forward or parallel approach by a person using a wheelchair. Standards §§ 4.27.2, 4.27.3, 4.2.4, 4.2.5, 4.2.6.

viii.    The paper towel dispenser in the women’s toilet room protrudes into the main walkway and would not be detectable to a blind person using a cane. Provide an accessible route at this location such that no objects with their bottom leading edges measuring between 27 inches and 80 inches above the finished floor protrude more than 4 inches into walks, halls, corridors, passageways, or aisles. Free-standing objects mounted on posts or pylons may overhang 12 inches maximum from 27 inches to 80 inches above the ground or finished floor. Standards § 4.4.

ix.    In each toilet room, the lavatory does not have sufficient knee and toe clearance. In each room, provide a lavatory with the top of its rim or counter 34 inches or less above the finished floor; the bottom edge of the apron at least 29 inches above the finished floor; and knee and toe clearances that comply with Fig. 31. Standards § 4.19.2, Fig. 31.

x.    The lavatory in each toilet room does not have hot water pipes that are insulated or otherwise configured to protect against contact. In each room, provide hot water and drain pipes that are insulated or otherwise configured to protect against contact. Standards § 4.19.4.

xi.    The lavatory in each toilet room has twist type hardware. In each room, provide a lavatory with a faucet that can be operated with 5 pounds of force or less and can be used with one hand and without tight grasping, pinching, or twisting of the wrist (lever-operated, push-type, and electronically controlled mechanisms are examples of acceptable designs). Standards §§ 4.19.5, 4.27.4.

xii.    The urinal in the men’s toilet room has a rim mounted 19 inches above the finished floor. Provide a urinal with an elongated rim mounted 17 inches or less above the finished floor, a clear floor space of at least 30 inches wide and 48 inches deep centered on the urinal, and a flush control height of 44 inches or less above the finished floor. Standards §§ 4.18.2, 4.18.3, 4.18.4.

xiii. There is no accessible stall provided in either toilet room. In each toilet room, provide a “standard” accessible toilet stall at least 60 inches wide and at least 59 inches deep (or at least 56 inches deep with a wall-mounted toilet) such that all of the stall’s elements, including stall door, stall door hardware, water closet, size and arrangement, toe clearances, grab bars, controls, and dispensers, comply with the Standards. Standards §§ 4.13, 4.16, 4.17, 4.26, 4.27, Fig. 30.

c.     Circulation Desk. The counter is 39 inches high. Provide a counter on an accessible route such that a portion of the counter is at least 36 inches wide and no more than 36 inches above the finished floor, or provide an auxiliary counter with a maximum height of 36 inches in close proximity to the main counter, or provide equivalent facilitation. Equivalent facilitation may be provided in the form of a folding shelf attached to the main counter, an auxiliary table nearby, a clip board made available to the public, or other means. Standards §§ 7.2(2), 4.3.

d.     Interior Doors

i.    The door to the English as a Second Language area is 30½ inches wide. Provide a door with a clear opening of 32 inches with the door open 90 degrees, measured between the face of the door and the opposite stop. Standards § 4.13.5, Fig. 24.

ii.    Each leaf of the doors to the African American Room is 27 inches wide, and has twist hardware. Provide a door to this room that has at least one active leaf with a clear opening at least 32 inches wide when measured from the face of the door to the middle edge of the other door when one door is opened 90 degrees and that has hardware usable with one hand and without tight grasping, pinching, or twisting of the wrist OR provide an automatic door opener that opens both doors simultaneously. Standards § 4.13, Figs. 24, 25.

iii.    Each leaf of the doors to the Sala Hispanoamericana is 27 inches wide. Provide a door to this room that has at least one active leaf with a clear opening at least 32 inches wide when measured from the face of the door to the middle edge of the other door when one door is opened 90 degrees and that has hardware usable with one hand and without tight grasping, pinching, or twisting of the wrist OR provide an automatic door opener that opens both doors simultaneously. Standards § 4.13, Figs. 24, 25.

iv.    The door to the Internet Computer Room requires 9 pounds of force to open. Provide a door that requires no more than 5 pounds of force to open. Standards § 4.13.11(2)(b).

v.    Each leaf of the doors to the New Jersey Division is 30 inches wide. Provide a door to this room that has at least one active leaf with a clear opening at least 32 inches wide when measured from the face of the door to the middle edge of the other door when one door is opened 90 degrees and that has hardware usable with one hand and without tight grasping, pinching, or twisting of the wrist OR provide an automatic door opener that opens both doors simultaneously. Standards § 4.13, Figs. 24, 25.

vi.    Each leaf of the doors to the Victoria Technology Center is 31 inches wide. Provide a door to this room that has at least one active leaf with a clear opening at least 32 inches wide when measured from the face of the door to the middle edge of the other door when one door is opened 90 degrees and that has hardware usable with one hand and without tight grasping, pinching, or twisting of the wrist OR provide an automatic door opener that opens both doors simultaneously. Standards § 4.13, Figs. 24, 25.

e.     Stacks. The shelves in the African American Room and the Sala Hispanoamericana are 33½ inches apart, and the shelves in the Stack Room on all floors are 34½ inches apart. Provide at least 36 inches of clear width between all stacks and provide a clear width of 42 inches between stacks where possible. Standards § 8.5, Fig. 56.

f.     Elevator

i.    The hall call buttons are centered 56 inches above the finished floor. Provide hall (lobby) call buttons centered at 42 inches above the finished floor, a minimum of ¾ inch in the smallest dimension, with the button designating the up direction on top. Standards § 4.10.3, Fig. 20.

ii.    The hall lanterns do not have audible signals. Provide hall lanterns at each hoistway entrance that emit a visible and audible signal. Ensure that audible signals sound once for the up direction and twice for the down direction or have verbal annunciators that say “up” or “down;” and that visible signals are mounted so that their centerline is at least 72 inches above the lobby floor, they are at least 2½ inches in the smallest dimension, and they are visible from the vicinity of the hall call button. Lanterns located in cars, visible from the vicinity of hall call buttons, and conforming to the above requirements, are acceptable. Standards § 4.10.4, Fig. 20.

iii.    The elevator has no hoistway signage. Provide signage at hoistway entrances with raised and Braille floor designations on both jambs such that the centerline of the characters is 60 inches above the finished floor and the characters are 2 inches high. Standards § 4.10.5, Fig. 20.

iv.    The elevator door is 32 inches wide, and the elevator measures 76 inches by 46 inches. Provide an elevator with a cab that is a minimum of 51 inches deep from the back wall of the cab to the control panel and 54 inches deep from the back wall of the cab to the face of the door; that, if the doors are centered on the wall, is at least 80 inches wide and, if the doors are located to one side of the wall, is at least 68 inches wide. Ensure that the door opening is at least 36 inches wide, and that floor surfaces are firm, stable, and slip-resistant. Standards §§ 4.10.9, 4.10.10, Fig. 22.

v.    The elevator’s car control buttons do not have raised or Braille characters, do not have the main entry floor designated by a star, and do not have the emergency controls grouped at the bottom of the panel no less than 35 inches high. Provide car control buttons that are at least ¾ inch in their smallest dimension and are raised or flush and that are designated by Braille and by raised standard alphabet characters for letters, arabic characters for numerals, or standard symbols. Ensure that the call button for the main entry floor is designated by a raised star at the left of the floor designation; that all raised designations for control buttons are placed immediately to the left of the buttons to which they apply; that floor buttons are provided with visual indicators to show when each call is registered and are extinguished when each call is answered; that all floor buttons are no higher than 54 inches above the finished floor for a side approach and no more than 48 inches above the finished floor for a front approach; and that emergency controls, including the emergency alarm and emergency stop, are grouped at the bottom of the panel and have their centerlines no less than 35 inches above the finished floor. Standards § 4.10.12, Fig. 23.

29.     Within 30 months of the effective date of this Agreement, the City will make the following modifications to the Roseville Branch Library, located at 99 Fifth Street.

a.     Accessible Route. The sidewalk is in disrepair and does not have a level surface and is not stable, firm, and slip-resistant; and there are 2 steps up to the entrance. Provide at least one accessible route to the facility that, to the maximum extent feasible, coincides with the route for the general public. The accessible route must have a minimum clear width of 36 inches, or a minimum clear width of 42 inches if there is a turn around an obstruction less than 48 inches wide; have passing spaces at least 60 inches by 60 inches at least every 200 feet; have a minimum clear headroom of 80 inches; have a surface that is firm, stable, and slip resistant; have, in the absence of a curb ramp, ramp, elevator, or platform lift, no level changes in excess of ½ inch vertically; and have a running slope of less than 1:20 (5%) (or have been constructed as a fully accessible ramp) and a cross slope of less than 1:50 (2%). Standards §§ 4.3, 4.5, Fig. 7.

b.     Entrance

i.    Each leaf of the double-leaf entrance door is 27 inches wide. Provide a designated accessible entrance that has at least one active leaf with a minimum 32 inch clear opening width with the door open 90 degrees, measured between the face of the door and the opposite stop; that has either an automatic door operator or clear and level maneuvering clearance that complies fully with Fig. 25; and that has a threshold not exceeding ½ inch in height and beveled with a slope no greater than 1:2. Ensure that all hardware and operating devices have shapes that are easy to grasp with one hand and do not require tight grasping, pinching, or twisting of the wrist to operate, and that they are mounted no higher than 48 inches above the finished floor. Standards § 4.13, Figs. 24, 25.

ii.    The entrance doors have knob hardware. Provide doors with hardware that is easy to grasp with one hand and that does not require tight grasping, pinching, or twisting of the wrist to operate. Lever-operated mechanisms, push-type mechanisms, and U-shaped handles are acceptable designs. Standards § 4.13.9.

c.     Card Catalog and Magazine Display. The card catalog and magazine display are mounted outside of accessible reach ranges and do not have sufficient width between them. Provide card catalogs and magazine displays with a minimum of 36 inches of clear width between units and with reach ranges of between 18 inches and 54 inches (maximum height of 48 inches is preferred) above the finished floor. Standards § 8.4, Fig. 55.

d.     Unisex Toilet Room. The entrance door is 29 inches wide, and the room contains a number of inaccessible elements and is not accessible to people with disabilities. Provide an accessible toilet room such that all of the room’s elements, including signage, door, door hardware, clear floor space, water closet, urinal (if provided), grab bars, lavatory, mirror, controls, and dispensers, comply with the Standards. Standards §§ 4.13, 4.16, 4.18, 4.19, 4.26, 4.27, 4.30, Figs. 28, 29.

30.     Within 30 months of the effective date of this Agreement, the City will make the following modifications to the Rotunda Pool, located at Clinton Avenue.

a.     Accessible Route

i.    The route to the pool gate entry has a built-up ramp that is too steep. Provide at least one accessible route to the pool that, to the maximum extent feasible, coincides with the route for the general public. The accessible route must have a minimum clear width of 36 inches, or a minimum clear width of 42 inches if there is a turn around an obstruction less than 48 inches wide; have passing spaces at least 60 inches by 60 inches at least every 200 feet; have a minimum clear headroom of 80 inches; have a surface that is firm, stable, and slip resistant; have, in the absence of a curb ramp, ramp, elevator, or platform lift, no level changes in excess of ½ inch vertically; and have a running slope of less than 1:20 (5%) (or have been constructed as a fully accessible ramp) and a cross slope of less than 1:50 (2%). Standards §§ 4.3, 4.5, Fig. 7.

ii.    The route to the toilet rooms from the rec room has double leaf doors, each of which is 25½ inches wide. Provide a door at this location that has at least one active leaf with a clear opening at least 32 inches wide when measured from the face of the door to the middle edge of the other door when one door is opened 90 degrees and that has hardware usable with one hand and without tight grasping, pinching, or twisting of the wrist OR provide an automatic door opener that opens both doors simultaneously.. Standards § 4.13, Figs. 24, 25.

iii.    The stairs to the 2nd level do not have handrail extensions at the top or bottom and the ends of the handrails are not rounded or returned smoothly to the wall, floor, or post. Provide stairs with handrails on both sides of the stairs such that the inside handrail on switchbacks or doglegs is continuous; handrails that are not continuous beyond the top and bottom of the stairs extend at least 12 inches beyond the top riser and at least 12 inches plus the width of one tread beyond the bottom riser; there is a clear space between the handrails and the wall of 1½ inches; gripping surfaces are uninterrupted by newel posts, other construction elements, or obstructions; the handrails are mounted between 34 and 38 inches above stair nosings; the ends of the handrails are either rounded or returned smoothly to the floor, wall, or post; and the handrails do not rotate within their fittings. Standards § 4.9.

b.     Toilet Rooms

i.    The signs for each toilet room are incorrectly mounted and do not have raised characters or Braille. For each room, provide a toilet room sign with raised and Braille characters mounted on the wall adjacent to the latch side of the door with the centerline of the sign at 60 inches above the finished floor and situated such that a person can approach within 3 inches of the sign without encountering an obstruction or standing within a door swing. Standards §§ 4.1.2(7)(d), 4.30.1, 4.30.4, 4.30.5, 4.30.6.

ii.    The hand dryers in each toilet room protrude into the main walkway and would not be detectable to a blind person using a cane. Provide an accessible route at each location such that no objects with their bottom leading edges measuring between 27 inches and 80 inches above the finished floor protrude more than 4 inches into walks, halls, corridors, passageways, or aisles. Free-standing objects mounted on posts or pylons may overhang 12 inches maximum from 27 inches to 80 inches above the ground or finished floor. Standards § 4.4.

iii.    Although there are 6 stalls in the women’s toilet room, there is no ambulatory stall provided. Provide at least one stall that is exactly 36 inches wide with an outward swinging, self-closing door and parallel grab bars complying with Fig 30(d). Standards §§ 4.22.4, Fig. 30(d).

iv.    The toilet in the women’s designated accessible stall is mounted 20½ inches from the side wall. Provide a toilet with a centerline that measures 18 inches from the near side wall. Standards § 4.17.3, Fig. 30.

v.    The flush controls on the toilets in both toilet rooms’ designated accessible stalls are mounted on the closed side. In each designated accessible stall, provide a flush control mounted on the “open” side of the toilet’s clear floor space; 44 inches or less above the finished floor; and requiring a maximum of 5 pounds of force to operate; or provide an automatic flush device. Standards §§ 4.16.5, 4.17.2, 4.27.4.

vi.    No accessible coat hook has been provided in either toilet room. In each room, provide a coat hook at a maximum height above the finished floor of 48 inches for a forward approach or 54 inches for a side approach and that is accompanied by clear floor space of 30 by 48 inches that allows a forward or parallel approach by a person using a wheelchair. Standards §§ 4.25.2, 4.25.3, 4.2.4, 4.2.5, 4.2.6.

vii.    In the designated accessible stall in each toilet room, the grab bars are mounted in the wrong place, and the rear grab bars are too short. In each accessible stall, provide a rear grab bar that is at least 36 inches in overall length, with the closer end no more than 6 inches from the side wall nearer the toilet, and a side grab bar that is at least 40 inches in overall length, with the far end mounted at least 54 inches from the rear wall and the closer end 12 inches or less from the rear wall, and that is mounted on the side wall closer to the toilet. Ensure that the grab bars are mounted 33 to 36 inches above the finished floor; with a diameter between 1¼ and 1½ inches; with 1½ inches between the grab bar and the wall; and at least 1½ inches between the grab bar and any other object, such as a toilet seat cover dispenser or a toilet paper dispenser. Standards §§ 4.17.6, 4.26.2, Fig. 30.

c.     Drinking Fountains

i.    Although an accessible drinking fountain is provided, there is no drinking fountain provided for people who have difficulty bending or stooping. Provide a drinking fountain that is accessible to people who have difficulty bending or stooping. This can be accommodated by the use of a “hi-lo” fountain; by providing one fountain accessible to those who use wheelchairs and one fountain at a standard height convenient for those who have difficulty bending; by providing a fountain accessible to people who use wheelchairs and a cup dispenser, or by such other means as would achieve the required accessibility for each group of people. Standards § 4.1.3(10)(a).

ii.    The wall-mounted drinking fountains have insufficient knee space. Provide a drinking fountain with clear knee space between the bottom of the apron and the finished floor or ground of at least 27 inches high, 30 inches wide, and 17 to 19 inches deep; and a minimum clear floor space of 30 inches by 48 inches to allow a person in a wheelchair to approach the unit facing forward. Standards § 4.15.5(1), Figs. 27(a), (b).

iii.    The wall-mounted drinking fountains protrude into the main walkway and would not be detectable to a blind person using a cane. Provide an accessible route at this location such that no objects with their bottom leading edges measuring between 27 inches and 80 inches above the finished floor protrude more than 4 inches into walks, halls, corridors, passageways, or aisles. Free-standing objects mounted on posts or pylons may overhang 12 inches maximum from 27 inches to 80 inches above the ground or finished floor. Standards § 4.4.

31.     Within 30 months of the effective date of this Agreement, the City will make the following modifications to the South District Police Department, located at 254 West Bigelow Street.

a.     Entrance

i.    There are stairs to the entrance and just inside the entrance. Provide at least one accessible route into the facility that, to the maximum extent feasible, coincides with the route for the general public. The accessible route must have a minimum clear width of 36 inches, or a minimum clear width of 42 inches if there is a turn around an obstruction less than 48 inches wide; have passing spaces at least 60 inches by 60 inches at least every 200 feet; have a minimum clear headroom of 80 inches; have a surface that is firm, stable, and slip resistant; have, in the absence of a curb ramp, ramp, elevator, or platform lift, no level changes in excess of ½ inch vertically; and have a running slope of less than 1:20 (5%) (or have been constructed as a fully accessible ramp) and a cross slope of less than 1:50 (2%). Standards §§ 4.3, 4.5, Fig. 7.

ii.    The interior door at the top of the steps requires 12 pounds of force to open. Provide a door that requires no more than 5 pounds of force to open. Standards § 4.13.11(2)(b).

b.     Stairs. The exterior stairs lack handrails, and the handrails on the interior stairs lack handrail extensions and have ends that are not rounded or returned smoothly to the floor, wall, or post. On both sets of stairs, provide handrails on both sides of the stairs such that handrails that are not continuous beyond the top and bottom of the stairs extend at least 12 inches beyond the top riser and at least 12 inches plus the width of one tread beyond the bottom riser; there is a clear space between the handrails and the wall of 1½ inches; gripping surfaces are uninterrupted by newel posts, other construction elements, or obstructions; the handrails are mounted between 34 and 38 inches above stair nosings; the ends of the handrails are either rounded or returned smoothly to the floor, wall, or post; and the handrails do not rotate within their fittings. Standards § 4.9.

32.     Within 30 months of the effective date of this Agreement, the City will make the following modifications to the South District Police Sub-Station, located at 1049 Bergen Street.

a.     Entrance

i.    The entrance door has a slope greater than 1:50 within the door’s required maneuvering clearance. Provide a door so that the floor or ground area within the required clearances is level and clear. Standards § 4.13.6, Fig. 25.

ii.    The entrance door, which is accessed through a front approach, has insufficient maneuvering clearance on the pull side. On the pull side of the door, provide maneuvering clearance at least 60 inches deep and provide a minimum of 18 inches (24 inches is preferred) of maneuvering clearance on the latch side of the door. Standards § 4.13.6, Fig. 25(a).

iii.    The entrance door has a 1 inch threshold. Provide a door with a threshold no greater than ¼ inch, or between ¼ inch and ½ inch and beveled with a slope no greater than 1:2. Standards §§ 4.13.8, 4.5.2.

b.     Interior Door

i.    The interior door to the substation offices, which is accessed through a front approach, has insufficient maneuvering clearance on the pull side. On the pull side of the door, provide maneuvering clearance at least 60 inches deep and provide a minimum of 18 inches (24 inches is preferred) of maneuvering clearance on the latch side of the door. Standards § 4.13.6, Fig. 25(a).

ii.    The interior door to the substation offices has know hardware. Provide a door with hardware that is easy to grasp with one hand and that does not require tight grasping, pinching, or twisting of the wrist to operate. Lever-operated mechanisms, push-type mechanisms, and U-shaped handles are acceptable designs. Standards § 4.13.9.

33.     Within 30 months of the effective date of this Agreement, the City will make the following modifications to St. Peter’s Recreation Center, located at 378 Lyons Avenue.

a.     Exterior Ramp. The exterior ramp to the pool is excessively sloped and the handrail on one side is too high. Provide a ramp that is at least 36 inches wide with a slope not exceeding 1:12 and a cross slope not exceeding 1:50; with level landings at least as wide as the ramp and 60 inches long at the top and bottom of the ramp; and with edge protection at least 2 inches high at the drop off sides. Provide handrails that are between 1¼ inches and 1½ inches in diameter with a continuous gripping surface along both sides of the ramp, extending at least 12 inches beyond the top and bottom of the ramp parallel with the ground surface. Ensure that handrails are mounted between 34 inches and 38 inches above the ramp surface, with ends rounded or returned smoothly to the floor, wall, or post, and that they do not rotate within their fittings. Ensure that the ramp and approaches are designed so that water will not accumulate on walking surfaces. Standards §§ 4.3.8, 4.8.

b.     Entrance. There is a 1½ inches threshold at the entrance door. Provide a door with a threshold no greater than ¼ inch, or between ¼ inch and ½ inch and beveled with a slope no greater than 1:2. Standards §§ 4.13.8, 4.5.2.

c.     Fixed Seating. The exterior chess tables are 23 inches high to the bottom and have less than 30 inches between the fixed seats. Provide at least one table on an accessible route such that there is knee space at the table at least 27 inches high, 30 inches wide, and 19 inches deep, and such that the height of the top of the table is between 28 inches and 34 inches above the ground. Standards §§ 4.32.3, 4.32.4.

d.     Interior Accessible Route.

i.    The ramp to the interior lower level is too steep and there are no handrails. Provide a ramp that is at least 36 inches wide with a slope not exceeding 1:12 and a cross slope not exceeding 1:50; with level landings at least as wide as the ramp and 60 inches long at the top and bottom of the ramp; with level landings measuring at least 60 inches by 60 inches when the ramp changes direction; and edge protection that is at least 2 inches high at the drop off sides. Provide handrails that are between 1¼ inches and 1½ inches in diameter such that the inside handrail is continuous and both handrails have a continuous gripping surface along both sides of the ramp extending at least 12 inches beyond the top and bottom of the ramp parallel with the ground surface; the handrails do not rotate within their fittings; and both handrails are mounted between 34 inches and 38 inches above the ramp surface, with ends rounded or returned smoothly to the floor, wall, or post. Ensure that the ramp and approaches are designed so that water will not accumulate on walking surfaces. Standards §§ 4.3.8, 4.8.

ii.    The only route to the 2nd level requires traversing stairs. Provide at least one accessible route to this level that, to the maximum extent feasible, coincides with the route for the general public. The accessible route must have a minimum clear width of 36 inches, or a minimum clear width of 42 inches if there is a turn around an obstruction less than 48 inches wide; have passing spaces at least 60 inches by 60 inches at least every 200 feet; have a minimum clear headroom of 80 inches; have a surface that is firm, stable, and slip resistant; have, in the absence of a curb ramp, ramp, elevator, or platform lift, no level changes in excess of ½ inch vertically; and have a running slope of less than 1:20 (5%) (or have been constructed as a fully accessible ramp) and a cross slope of less than 1:50 (2%). Standards §§ 4.3, 4.5, Fig. 7.

e.     Toilet Rooms

i.    The signs are mounted on the door and do not have raised characters or Braille. For each toilet room, provide a toilet room sign with raised and Braille characters. The sign shall be mounted on the wall adjacent to the latch side of the door with the centerline of the sign at 60 inches above the finished floor and situated such that a person can approach within 3 inches of the sign without encountering an obstruction or standing within a door swing. Standards §§ 4.1.2(7)(d), 4.30.1, 4.30.4, 4.30.5, 4.30.6.

ii.    The door to each toilet room is 28½ inches wide. For each room, provide a door with a clear opening of 32 inches with the door open 90 degrees, measured between the face of the door and the opposite stop. Standards § 4.13.5, Fig. 24.

iii.    The door to the men’s toilet room requires 9 pounds of force to open, and the door to the women’s toilet room requires 8½ pounds of force to open. For each room, provide a door that requires no more than 5 pounds of force to open. Standards § 4.13.11(2)(b).

iv.    The lavatories in each toilet room do not provide sufficient knee clearance. In each room, provide a lavatory with the top of its rim or counter 34 inches or less above the finished floor; the bottom edge of the apron at least 29 inches above the finished floor; and knee and toe clearances that comply with Fig. 31. Standards § 4.19.2, Fig. 31.

v.    The toilet flush in the designated accessible stall in each toilet room is mounted on the closed side of the toilet. In each designated accessible stall, provide a flush control mounted on the “open” side of the toilet’s clear floor space; 44 inches or less above the finished floor; and requiring a maximum of 5 pounds of force to operate; or provide an automatic flush device. Standards §§ 4.16.5, 4.17.2, 4.27.4.

vi.    The toilet paper dispenser in the men’s designated accessible stall is mounted above the side grab bar. Provide a toilet paper dispenser that is mounted with its top at least 1½ inches under the side grab bar and 36 inches or less from the rear wall and is centered at least 19 inches above the finished floor. Standards § 4.17.3, Fig. 30(d).

vii.    There is no rear grab bar provided in the men’s designated accessible stall. Provide a rear grab bar that is at least 36 inches in overall length, with the closer end no more than 6 inches from the side wall; mounted 33 to 36 inches above the finished floor; with a diameter between 1¼ and 1½ inches; with 1½ inches between the grab bar and the wall; and at least 1½ inches between the grab bar and any other object, such as a toilet seat cover dispenser. Standards §§ 4.17.6, 4.26.2, Fig. 30.

viii.    The designated accessible stall in the men's toilet room is incorrectly configured, and there is no standard accessible stall provided. Provide a "standard" accessible toilet stall at least 60 inches wide and at least 59 inches deep (or at least 56 inches deep with a wall-mounted toilet) such that all of the stall's elements, including stall door, stall door hardware, water closet, size and arrangement, toe clearances, grab bars, controls, and dispensers, comply with the Standards. Standards §§ 4.13, 4.16, 4.17, 4.26, 4.27, Fig. 30.

ix.    There are no grab bars provided in the women’s designated accessible stall. Provide a rear grab bar that is at least 36 inches in overall length, with the closer end no more than 6 inches from the side wall, and a side grab bar that is at least 40 inches in overall length, with the far end mounted at least 54 inches from the rear wall and the closer end 12 inches or less from the rear wall. Ensure that the grab bars are mounted 33 to 36 inches above the finished floor; with a diameter between 1¼ and 1½ inches; with 1½ inches between the grab bar and the wall; and at least 1½ inches between the grab bar and any other object, such as a toilet seat cover dispenser or a toilet paper dispenser. Standards §§ 4.17.6, 4.26.2, Fig. 30.

f.     Locker Rooms

i.    The door has knob hardware. Provide a door with hardware that is easy to grasp with one hand and that does not require tight grasping, pinching, or twisting of the wrist to operate. Lever-operated mechanisms, push-type mechanisms, and U-shaped handles are acceptable designs. Standards § 4.13.9.

ii.    The locker rooms contain numerous inaccessible elements and are not accessible to people using wheelchairs. Provide accessible locker rooms such that all of the room’s elements, including signage, door, door hardware, clear floor space, locker, bench, dressing area, shower, water closet, urinal (if provided), grab bars, lavatory, mirror, controls, and dispensers, comply with the Standards. Standards §§ 4.13, 4.16, 4.18, 4.19, 4.21, 4.26, 4.27, 4.30, 4.35, Figs. 28, 29.

iii.    The drinking fountains in the locker rooms have spouts 40 inches above the finished floor. Provide a fountain that has a spout height no higher than 36 inches, measured from the finished floor or ground surface to the spout outlet, and that otherwise complies with the Standards. Standards §§ 4.15, 4.27.4, Fig. 27.

iv.    The wall-mounted drinking fountains in the locker rooms have insufficient knee clearance. Provide a drinking fountain with clear knee space between the bottom of the apron and the finished floor or ground of at least 27 inches high, 30 inches wide, and 17 to 19 inches deep; and a minimum clear floor space of 30 inches by 48 inches to allow a person in a wheelchair to approach the unit facing forward. Standards § 4.15.5(1), Figs. 27(a), (b).

34.     Within 30 months of the effective date of this Agreement, the City will make the following modifications to Symphony Hall, located at 1020 Broad Street.

a.     Accessible Route

i.    The curb cut at the entrance to the Sarah Vaughan Concert Hall has an awning pole impeding access. Provide a curb ramp that has at least 36 inches of unimpeded width, has a maximum slope of 1:12, is located so that it cannot be obstructed by parked vehicles, and has a stable, firm, and slip-resistant surface with a detectable warning extending the full width and depth of the ramp. If the curb ramp is located where pedestrians must walk across it, provide either flared sides (with a maximum slope of 1:10) or handrails or guardrails to protect against cross traffic. Standards § 4.3.8, 4.7, Fig. 12.

ii.    The interior entrance ramp to the front entry doors to the Sarah Vaughan Concert Hall has a rise of greater than 30 inches with no level landing, and the handrails are not continuous. Provide a ramp with a maximum rise of 30 inches for any run, and provide level landings at the top and bottom of each run that are at least as wide as the ramp and at least 60 inches long. Provide handrails that are between 1¼ inches and 1½ inches in diameter with a continuous gripping surface along both sides of the ramp, extending at least 12 inches beyond the top and bottom of the ramp parallel with the ground surface. Ensure that handrails are mounted between 34 inches and 38 inches above the ramp surface, with ends rounded or returned smoothly to the floor, wall, or post, and that they do not rotate within their fittings. Standards § 4.8.5. Standards §§ 4.3.8, 4.8, Fig. 16.

iii.    The interior ramp along the side of the Sarah Vaughan Concert Hall, leading from the seating area to the rear entry door, is inaccessible because it has no handrails. Provide handrails that are between 1¼ inches and 1½ inches in diameter such that the inside handrail is continuous and both handrails have a continuous gripping surface along both sides of the ramp extending at least 12 inches beyond the top and bottom of the ramp parallel with the ground surface; the handrails do not rotate within their fittings; and both handrails are mounted between 34 inches and 38 inches above the ramp surface and 1½ inches from the wall, with ends rounded or returned smoothly to the floor, wall, or post. Standards § 4.8.5.

b.     Entrances

i.    The building does not have the International Symbol of Accessibility posted at accessible entrances and does not have directional signage posted at the inaccessible entrance. Provide accessible directional signage with the International Symbol of Accessibility at inaccessible entrances directing users to the accessible entrance, and provide accessible signage with the International Symbol of Accessibility at all permanent accessible entrances. Standards §§ 4.1.3(8)(d), 4.13, 4.30.

ii.    The entrance doors to the Sarah Vaughan Concert Hall and the Terrace Room require twisting to operate. Provide doors with hardware that is easy to grasp with one hand and that does not require tight grasping, pinching, or twisting of the wrist to operate. Lever-operated mechanisms, push-type mechanisms, and U-shaped handles are acceptable designs. Standards § 4.13.9.

iii.    There is a step up to the box office entrance. Provide at least one accessible route to the box office that, to the maximum extent feasible, coincides with the route for the general public. The accessible route must have a minimum clear width of 36 inches, or a minimum clear width of 42 inches if there is a turn around an obstruction less than 48 inches wide; have passing spaces at least 60 inches by 60 inches at least every 200 feet; have a minimum clear headroom of 80 inches; have a surface that is firm, stable, and slip resistant; have, in the absence of a curb ramp, ramp, elevator, or platform lift, no level changes in excess of ½ inch vertically; and have a running slope of less than 1:20 (5%) (or have been constructed as a fully accessible ramp) and a cross slope of less than 1:50 (2%). Standards §§ 4.3, 4.5, Fig. 7.

iv.    Each leaf of the doors to the box office entrance is 30½ inches wide. Provide a door at this location that has at least one active leaf with a clear opening at least 32 inches wide when measured from the face of the door to the middle edge of the other door when one door is opened 90 degrees and that has hardware usable with one hand and without tight grasping, pinching, or twisting of the wrist OR provide an automatic door opener that opens both doors simultaneously. Standards § 4.13, Figs. 24, 25.

v.    The vestibule at the box office entrance is 21 inches deep from the end of one open door to the other set of doors. Provide an accessible entrance to the box office such that the space between any two doors in series is at least 48 inches plus the width of any door swinging into the space. Ensure that doors in series swing either in the same direction or away from the space between the doors. Standards § 4.13.7, Fig. 26.

c.     Signage. There is no accessible signage provided inside the facility. Provide permanent room signage with upper case, sans serif or simple serif type letters and numerals, meeting the requirements of the Standards for character height, raised characters, finish and contrast, accompanied by Grade 2 Braille; mounted on the wall adjacent to the latch side of the door or on the nearest adjacent wall at a height of 60 inches above the finished floor to the centerline of the sign; and located so that a person may approach within 3 inches of the signage without encountering protruding objects or standing within the swing of a door. Standards §§ 4.30.1, 4.30.4, 4.30.5, 4.30.6.

d.     Telephone. There is no accessible telephone provided. Provide an accessible telephone with a clear floor space of at least 30 inches by 48 inches that allows either a forward or parallel approach by a person using a wheelchair such that bases, enclosures, and fixed seats do not impede approaches to the telephone; with the highest operable part of the telephone mounted no more than 48 inches above the floor for a front approach or no more than 54 inches above the floor for a side approach; that is hearing aid compatible and has a volume control mechanism; with telephone books, if provided, located between 15 and 48 inches above the finished floor for a front approach or between 9 and 54 inches above the finished floor for a side approach; with a cord of at least 29 inches long from the telephone to the handset; and with signage that complies with the Standards. Standards §§ 4.31, 4.30.7(2).

e.     Sarah Vaughan Concert Hall

i.    The concert hall, containing 2800 seats has only 4 wheelchair seating locations. Provide at least from table 4.1.3(19)(a)) wheelchair seating areas, each with a minimum clear ground or floor space of 66 inches wide by 48 inches deep for forward or rear access, or 66 inches wide by 60 inches deep for side access. Ensure that the ground or floor at all wheelchair locations is level, firm, stable, and slip resistant; that wheelchair seating areas are an integral part of the fixed seating plan and are located so as to provide people with physical disabilities a choice of admission prices and lines of sight comparable to those available for members of the general public; that wheelchair seating areas adjoin an accessible route that also serves as a means of egress in case of emergency; and that at least one fixed companion seat is provided next to each wheelchair seating area. Standards §§ 4.1.3(19)(a), 4.5, 4.33.

ii.    The path of travel to the lift to the stage from inside the theater contains obstacles. Provide at least one accessible route within the boundary of the site connecting these elements that, to the maximum extent feasible, coincides with the route for the general public. The accessible route must have a minimum clear width of 36 inches, or a minimum clear width of 42 inches if there is a turn around an obstruction less than 48 inches wide; have passing spaces at least 60 inches by 60 inches at least every 200 feet; have a minimum clear headroom of 80 inches; have a surface that is firm, stable, and slip resistant; have, in the absence of a curb ramp, ramp, elevator, or platform lift, no level changes in excess of ½ inch vertically; and have a running slope of less than 1:20 (5%) (or have been constructed as a fully accessible ramp) and a cross slope of less than 1:50 (2%). Standards §§ 4.3, 4.5, Fig. 7.

f.     Terrace Ballroom. There is no access to the stage for people who use wheelchairs. Provide an accessible route connecting all spaces used by performers. Standards §§ 4.3, 4.33.5.

g.     Studio Theater

i.    Although there are more than 50 fixed seats, there is no assistive listening system. Provide a permanently installed assistive listening system serving the fixed seating. Ensure that the seating served by the system is located within a 50 foot viewing distance of the stage or playing area and has a complete view of the stage or playing area. Provide at least 9 receivers for use by the general public and signage indicating their availability. Standards §§ 4.30, 4.33.

ii.    None of the dessing rooms behind Studio Theater is accessible. Provide at least one accessible dressing room in this area on an accessible route with accessible signage indicating its location. Ensure that accessible dressing rooms fitted with swinging or sliding doors contain sufficient clear floor space to allow a person using a wheelchair to make a 180-degree turn inside the room and that no door swings into any part of the turning space. Ensure that private accessible dressing rooms fitted with curtained openings at least 32 inches wide contain either a clear space of 60 inches in diameter, or a “T” shaped turning space that complies with Fig. 3(b). Provide a bench 24 inches by 48 inches fixed to the wall along the longer dimension and mounted between 17 and 19 inches above the finished floor to the top of the bench. If mirrors are provided in dressing rooms of the same use, provide one full-length mirror, measuring at least 18 inches wide by 54 inches high, mounted in a position affording a view to a person on the bench as well as to a person in a standing position. Standards §§ 4.35, 4.30, 4.26.3, 4.2, 4.3, Fig. 3.

h.     Box Office

i.    The ticket counter is 44 inches high. Provide a counter on an accessible route such that a portion of the counter is at least 36 inches wide and no more than 36 inches above the finished floor, or provide an auxiliary counter with a maximum height of 36 inches in close proximity to the main counter, or provide equivalent facilitation. Equivalent facilitation may be provided in the form of a folding shelf attached to the main counter, an auxiliary table nearby, a clip board made available to the public, or other means. Standards §§ 7.2(2), 4.3.

ii.    The customer counter is 41 inches high. Provide a counter on an accessible route such that a portion of the counter is at least 36 inches wide and no more than 36 inches above the finished floor, or provide an auxiliary counter with a maximum height of 36 inches in close proximity to the main counter, or provide equivalent facilitation. Equivalent facilitation may be provided in the form of a folding shelf attached to the main counter, an auxiliary table nearby, a clip board made available to the public, or other means. Standards §§ 7.2(2), 4.3.

i.    1st Floor Toilet Rooms

i.    The toilet room signs are mounted on the doors, and there are no raised characters or Braille. For each room, provide a toilet room sign with raised and Braille characters. The sign shall be mounted on the wall adjacent to the latch side of the door with the centerline of the sign at 60 inches above the finished floor and situated such that a person can approach within 3 inches of the sign without encountering an obstruction or standing within a door swing. Standards §§ 4.1.2(7)(d), 4.30.1, 4.30.4, 4.30.5, 4.30.6.

ii.    There is no accessible toilet stall provided in either room. In each room, provide a “standard” accessible toilet stall at least 60 inches wide and at least 59 inches deep (or at least 56 inches deep with a wall-mounted toilet) such that all of the stall’s elements, including stall door, stall door hardware, water closet, size and arrangement, toe clearances, grab bars, controls, and dispensers, comply with the Standards. Standards §§ 4.13, 4.16, 4.17, 4.26, 4.27, Fig. 30.

j.     Elevator. There are no hall lanterns provided. Provide hall lanterns at each hoistway entrance that emit a visible and audible signal indicating which car is answering a call. Ensure that audible signals sound once for the up direction and twice for the down direction or have verbal annunciators that say “up” or “down;” and that visible signals are mounted so that their centerline is at least 72 inches above the lobby floor, they are at least 2½ inches in the smallest dimension, and they are visible from the vicinity of the hall call button. Lanterns located in cars, visible from the vicinity of hall call buttons, and conforming to the above requirements, are acceptable. Standards § 4.10.4, Fig. 20.

35.     Within 30 months of the effective date of this Agreement, the City will make the following modifications to the Water and Sewer Department, located at 239 Central Avenue.

a.     Entrance. The building does not have the International Symbol of Accessibility posted at the accessible entrance and does not have directional signage posted at the inaccessible entrance. Provide accessible directional signage with the International Symbol of Accessibility at inaccessible entrances directing users to the accessible entrance, and provide accessible signage with the International Symbol of Accessibility at all permanent accessible entrances. Standards §§ 4.1.3(8)(d), 4.13, 4.30.

36.     Within 30 months of the effective date of this Agreement, the City will make the following modifications to the Weequahic Branch Library, located at 355 Osborne Terrace.

a.     Check-Out Counter. The counter is 44½ inches high. Provide a counter on an accessible route such that a portion of the counter is at least 36 inches wide and no more than 36 inches above the finished floor, or provide an auxiliary counter with a maximum height of 36 inches in close proximity to the main counter, or provide equivalent facilitation. Equivalent facilitation may be provided in the form of a folding shelf attached to the main counter, an auxiliary table nearby, a clip board made available to the public, or other means. Standards §§ 7.2(2), 4.3.

b.     Interior Ramp. The handrail on one side does not have extensions and is not continuous. Provide handrails that are between 1¼ inches and 1½ inches in diameter with a continuous gripping surface along both sides of the ramp, extending at least 12 inches beyond the top and bottom of the ramp parallel with the ground surface. Ensure that handrails are mounted between 34 inches and 38 inches above the ramp surface, with ends rounded or returned smoothly to the floor, wall, or post, and that they do not rotate within their fittings. Standards § 4.8.5.

c.     Toilet Rooms with Stalls

i.    The toilet room signs are mounted on the doors and do not have raised characters or Braille. For each room, provide a toilet room sign with raised and Braille characters. The sign shall be mounted on the wall adjacent to the latch side of the door with the centerline of the sign at 60 inches above the finished floor and situated such that a person can approach within 3 inches of the sign without encountering an obstruction or standing within a door swing. Standards §§ 4.1.2(7)(d), 4.30.1, 4.30.4, 4.30.5, 4.30.6.

ii.    The door to the men’s toilet room requires 11 pounds of force to open, and the door to the women’s toilet room requires 12 pounds of force to open. For each room, provide a door that requires no more than 5 pounds of force to open. Standards § 4.13.11(2)(b).

iii.    No accessible mirror has been provided in the men’s toilet room. Provide a mirror with the bottom edge of its reflecting surface no more than 40 inches above the finished floor. Standards § 4.19.6.

iv.    There is insufficient clear floor space provided at the lavatory in the men’s toilet room. Provide a lavatory with clear floor space at least 30 inches wide and 48 inches deep centered on the lavatory. Standards § 4.19.3, Fig. 32.

v.    The lavatories in each toilet room have hot water pipes that are not insulated or otherwise configured to protect against contact. In each room, provide hot water and drain pipes that are insulated or otherwise configured to protect against contact. Standards § 4.19.4.

vi.    The hand dryers in both toilet rooms protrudes into the main walkway and would not be detectable to a blind person using a cane. Provide an accessible route at these locations such that no objects with their bottom leading edges measuring between 27 inches and 80 inches above the finished floor protrude more than 4 inches into walks, halls, corridors, passageways, or aisles. Free-standing objects mounted on posts or pylons may overhang 12 inches maximum from 27 inches to 80 inches above the ground or finished floor. Standards § 4.4.

vii.    The urinal in the men’s toilet room has 24 inches of clear floor width. Provide a urinal with an elongated rim mounted 17 inches or less above the finished floor, a clear floor space of at least 30 inches wide and 48 inches deep centered on the urinal, and a flush control height of 44 inches or less above the finished floor. Standards §§ 4.18.2, 4.18.3, 4.18.4.

viii.    The flush control on the toilet in the men’s toilet room is on the closed side of the toilet. Provide a flush control mounted on the “open” side of the toilet’s clear floor space; 44 inches or less above the finished floor; and requiring a maximum of 5 pounds of force to operate; or provide an automatic flush device. Standards §§ 4.16.5, 4.17.2, 4.27.4.

ix.    The stall door on the designated accessible stall in the women’s toilet room swings into the toilet’s clear floor space. Ensure that no door swings into the required clear floor space at any accessible fixture. Standards § 4.22.2.

d.     Drinking Fountain. The wall-mounted fountain has insufficient knee space. Provide a drinking fountain with clear knee space between the bottom of the apron and the finished floor or ground of at least 27 inches high, 30 inches wide, and 17 to 19 inches deep; and a minimum clear floor space of 30 inches by 48 inches to allow a person in a wheelchair to approach the unit facing forward. Standards § 4.15.5(1), Figs. 27(a), (b).

37.     Within 30 months of the effective date of this Agreement, the City will make the following modifications to the Welfare Building, located at 394 University Avenue.

a.     Signage. There is no accessible interior signage provided. Provide permanent room signage with upper case, sans serif or simple serif type letters and numerals, meeting the requirements of the Standards for character height, raised characters, finish and contrast, accompanied by Grade 2 Braille; mounted on the wall adjacent to the latch side of the door or on the nearest adjacent wall at a height of 60 inches above the finished floor to the centerline of the sign; and located so that a person may approach within 3 inches of the signage without encountering protruding objects or standing within the swing of a door. Standards §§ 4.30.1, 4.30.4, 4.30.5, 4.30.6.

b.     Counters

i.    The lobby information counter is 43 inches high. Provide a counter on an accessible route such that a portion of the counter is at least 36 inches wide and no more than 36 inches above the finished floor, or provide an auxiliary counter with a maximum height of 36 inches in close proximity to the main counter, or provide equivalent facilitation. Equivalent facilitation may be provided in the form of a folding shelf attached to the main counter, an auxiliary table nearby, a clip board made available to the public, or other means. Standards §§ 7.2(2), 4.3.

ii.    The SRS waiting area counter is 48 inches high at the windows. Provide a counter on an accessible route such that a portion of the counter is at least 36 inches wide and no more than 36 inches above the finished floor, or provide an auxiliary counter with a maximum height of 36 inches in close proximity to the main counter, or provide equivalent facilitation. Equivalent facilitation may be provided in the form of a folding shelf attached to the main counter, an auxiliary table nearby, a clip board made available to the public, or other means. Standards §§ 7.2(2), 4.3.

c.     Drinking Fountain. The fountain’s spout is 43 inches high. Provide a fountain that has a spout height no higher than 36 inches, measured from the finished floor or ground surface to the spout outlet, and that otherwise complies with the Standards. Standards §§ 4.15, 4.27.4, Fig. 27.

d.     Toilet Rooms with Stalls

i.    The toilet room signs are mounted on the doors. For each room, provide a toilet room sign with raised and Braille characters. The sign shall be mounted on the wall adjacent to the latch side of the door with the centerline of the sign at 60 inches above the finished floor and situated such that a person can approach within 3 inches of the sign without encountering an obstruction or standing within a door swing. Standards §§ 4.1.2(7)(d), 4.30.1, 4.30.4, 4.30.5, 4.30.6.

ii.    The paper towel dispenser in each toilet room is inaccessible because twisting of the wrist is required to operate them. Provide a paper towel dispenser in each room with mechanical controls, if any, that can be operated with 5 lbf or less and that can be used with one hand and without tight grasping, pinching, or twisting of the wrist (lever-operated, push-type, and electronically controlled mechanisms are examples of acceptable designs). Standards § 4.27.4.

iii.    The paper towel dispenser in each toilet room protrudes into the main walkway and would not be detectable to a blind person using a cane. Provide an accessible route at these locations such that no objects with their bottom leading edges measuring between 27 inches and 80 inches above the finished floor protrude more than 4 inches into walks, halls, corridors, passageways, or aisles. Free-standing objects mounted on posts or pylons may overhang 12 inches maximum from 27 inches to 80 inches above the ground or finished floor. Standards § 4.4.

iv.    There is no accessible lavatory provided in either toilet room. In each room provide a lavatory with the top of its rim or counter 34 inches or less above the finished floor; the bottom edge of the apron at least 29 inches above the finished floor; knee and toe clearances that comply with Fig. 31; hot water and drain pipes covered or otherwise configured to protect against contact; clear floor space at least 30 inches wide and 48 inches deep centered on the lavatory; and a faucet that can be operated with 5 pounds of force or less and can be used with one hand and without tight grasping, pinching, or twisting of the wrist (lever-operated, push-type, and electronically controlled mechanisms are examples of acceptable designs). Standards §§ 4.19.2, 4.19.3, 4.19.4, 4.19.5, 4.27.4, Figs. 31, 32.

v.    The urinal in the men’s toilet room has a rim mounted 24 inches above the finished floor and a flush control 51 inches above the finished floor. Provide a urinal with an elongated rim mounted 17 inches or less above the finished floor, a clear floor space of at least 30 inches wide and 48 inches deep centered on the urinal, and a flush control height of 44 inches or less above the finished floor. Standards §§ 4.18.2, 4.18.3, 4.18.4.

vi.    There is no rear grab bar provided at the toilet in the designated accessible stall in either toilet room. In each accessible stall, provide a rear grab bar that is at least 36 inches in overall length, with the closer end no more than 6 inches from the side wall; mounted 33 to 36 inches above the finished floor; with a diameter between 1¼ and 1½ inches; with 1½ inches between the grab bar and the wall; and at least 1½ inches between the grab bar and any other object, such as a toilet seat cover dispenser. Standards §§ 4.17.6, 4.26.2, Fig. 30.

vii.    The toilet paper dispenser in each toilet room’s designated accessible stall is mounted above the side grab bar. Provide a toilet paper dispenser in each designated accessible stall that is mounted with its top at least 1½ inches under the side grab bar and 36 inches or less from the rear wall and is centered at least 19 inches above the finished floor. Standards § 4.17.3, Fig. 30(d).

38.     Within 30 months of the effective date of this Agreement, the City will make the following modifications to the West District Precinct, located at 10 17th Avenue.

a.     Entrance

i.    There are steps to the entrance. Provide at least one accessible route into the facility that, to the maximum extent feasible, coincides with the route for the general public. The accessible route must have a minimum clear width of 36 inches, or a minimum clear width of 42 inches if there is a turn around an obstruction less than 48 inches wide; have passing spaces at least 60 inches by 60 inches at least every 200 feet; have a minimum clear headroom of 80 inches; have a surface that is firm, stable, and slip resistant; have, in the absence of a curb ramp, ramp, elevator, or platform lift, no level changes in excess of ½ inch vertically; and have a running slope of less than 1:20 (5%) (or have been constructed as a fully accessible ramp) and a cross slope of less than 1:50 (2%). Standards §§ 4.3, 4.5, Fig. 7.

ii.    The exterior entrance stairs do not have handrails. Provide handrails on both sides of the stairs such that the inside handrail on switchbacks or doglegs is continuous; handrails that are not continuous beyond the top and bottom of the stairs extend at least 12 inches beyond the top riser and at least 12 inches plus the width of one tread beyond the bottom riser; there is a clear space between the handrails and the wall of 1½ inches; gripping surfaces are uninterrupted by newel posts, other construction elements, or obstructions; the handrails are mounted between 34 and 38 inches above stair nosings; the ends of the handrails are either rounded or returned smoothly to the floor, wall, or post; and the handrails do not rotate within their fittings. Standards § 4.9.

b.     Interior Doors. The doors throughout the facility use knob hardware. Provide doors with hardware that is easy to grasp with one hand and that does not require tight grasping, pinching, or twisting of the wrist to operate. Lever-operated mechanisms, push-type mechanisms, and U-shaped handles are acceptable designs. Standards § 4.13.9.

c.     Unisex Toilet Room in Conference Room

i.    The sign is incorrectly mounted and does not have raised characters or Braille. Provide a toilet room sign with raised and Braille characters. The sign shall be mounted on the wall adjacent to the latch side of the door with the centerline of the sign at 60 inches above the finished floor and situated such that a person can approach within 3 inches of the sign without encountering an obstruction or standing within a door swing. Standards §§ 4.1.2(7)(d), 4.30.1, 4.30.4, 4.30.5, 4.30.6.

ii.    The toilet room contains a number of noncompliant elements and is not accessible to people using wheelchairs. Provide an accessible toilet room such that all of the room’s elements, including signage, door, door hardware, clear floor space, water closet, urinal (if provided), grab bars, lavatory, mirror, controls, and dispensers, comply with the Standards. Standards §§ 4.13, 4.16, 4.18, 4.19, 4.26, 4.27, 4.30, Figs. 28, 29.

39.     Within 30 months of the effective date of this Agreement, the City will make the following modifications to the West District Neighborhood Substation, located at 763 South Orange Avenue.

a.     Entrance

i.    There are steps to the entrance. Provide at least one accessible route into the facility that, to the maximum extent feasible, coincides with the route for the general public. The accessible route must have a minimum clear width of 36 inches, or a minimum clear width of 42 inches if there is a turn around an obstruction less than 48 inches wide; have passing spaces at least 60 inches by 60 inches at least every 200 feet; have a minimum clear headroom of 80 inches; have a surface that is firm, stable, and slip resistant; have, in the absence of a curb ramp, ramp, elevator, or platform lift, no level changes in excess of ½ inch vertically; and have a running slope of less than 1:20 (5%) (or have been constructed as a fully accessible ramp) and a cross slope of less than 1:50 (2%). Standards §§ 4.3, 4.5, Fig. 7.

ii.    The handrails on the exterior stairs are not stable, do not have extensions on the top or bottom, and do not have ends that are rounded or returned smoothly to the wall, floor, or post. Provide handrails on both sides of the stairs such that the inside handrail on switchbacks or doglegs is continuous; handrails that are not continuous beyond the top and bottom of the stairs extend at least 12 inches beyond the top riser and at least 12 inches plus the width of one tread beyond the bottom riser; there is a clear space between the handrails and the wall of 1½ inches; gripping surfaces are uninterrupted by newel posts, other construction elements, or obstructions; the handrails are mounted between 34 and 38 inches above stair nosings; the ends of the handrails are either rounded or returned smoothly to the floor, wall, or post; and the handrails do not rotate within their fittings. Standards § 4.9.