ATTACHMENT K: Program Access in Existing Facilities

Please Note: Paragraph 65 of the Agreement requires that within twelve months of the effective date of this Agreement, the County will provide signage as necessary to comply with 28 C.F.R. § 35.163(b), after having surveyed all facilities that are the subject of this Agreement for the purpose of identifying those that have multiple entrances not all of which are accessible.

The technical requirements and, where appropriate, the scoping requirements of the Standards are used as a guide for determining whether a program or activity held in an existing facility is "readily accessible to and usable by" persons with disabilities and for determining what changes are necessary to make this program or activity accessible if it continues to be provided in the existing facility in question. See 28 C.F.R. §§ 35.150(b)(1), 35.151.

The chart below lists the facilities surveyed by the Department, the access issues identified during the survey, and the actions required to correct the access issues. Required actions are listed using an alphanumeric code. The key to the alphanumeric codes is provided in Attachment M to this Agreement.

In order to ensure that the programs, services, and activities housed in the County's facilities are accessible to persons with disabilities, when viewed in their entirety, the County will take the actions referenced by the alphanumeric code and described in detail in Attachment M to this Settlement Agreement within the time period specified below, which time period begins to run on the effective date of the Agreement.

Item # Access Issue Required Action Completion Date
1 Children's Resource Center, 332 W. Edmonston Drive, Rockville, MD 20850
1.1 Parking - Space #1 (van accessible - near front of entrance, right-most accessible space)
1.1.a The parking space reserved for persons with disabilities is inaccessible because the parking space is 91 inches wide. P8 60 months
1.1.b The parking space reserved for persons with disabilities is inaccessible because the slope of the space measures 8.7 %, the cross slope measures 3.4%, the slope of the adjacent access aisle measures 8.0%, and the cross slope measures 3.3%. P7 60 months
1.2 Parking - Space #2 (near front of entrance, left-most accessible space)
1.2.a The parking space reserved for persons with disabilities is inaccessible because the parking space is 92 inches wide. P8 60 months
1.2.b The parking space reserved for persons with disabilities is inaccessible because the slope of the parking space measures 8.4%, the slope of the adjacent access aisle measures 8.0% and the cross slope of the access aisle measures 3.3%. P7 60 months
1.3 Parking - Space #3 (at middle of building next to wooden ramp)
1.3.a The parking space reserved for persons with disabilities is inaccessible because the parking space is 93 inches wide. P8 60 months
1.4 Parking - Space #4 (at middle of building, at left of space #3)
1.4.a The parking space reserved for persons with disabilities is inaccessible because the parking space is 91 inches wide. P8 60 months
1.5 Parking - Space #5 (at far end of building - right-most accessible parking space)
1.5.a The parking space is inaccessible because there is no access aisle adjacent to it. P1 60 months
1.6 Parking - Space #6 (at far end of building - middle accessible parking space)
1.6.a The parking space reserved for persons with disabilities is inaccessible because the parking space is 92½ inches wide. P8 60 months
1.7 Parking - Space #7 (at far end of building - left-most accessible space)
1.7.a The parking space reserved for persons with disabilities is inaccessible because the parking space is 93 inches wide. P8 60 months
1.8 Wooden Exterior Ramp Leading to Front Entrance (next to Parking Space #3)
1.8.a The ramp is inaccessible because the slope of the topmost ramp segment measures 8.8%, the ramp lacks adequate edge protection, there are no compliant handrails, and one of the level landings in between ramp segments measures 45 inches wide and 52 inches deep. R2, R3 60 months
1.9 Exterior Front Entrance
1.9.a The door is inaccessible because the automatic door activator requires 7 pounds of force to operate. D2 60 months
1.10 Permanent Room Signage throughout Facility
1.10.a The signage provided next to doorways open to the public throughout the facility is inaccessible because they lack raised and Braille characters, are not mounted 60 inches above the finished floor and are not mounted on the latch side of the door. D26 60 months
1.11 Doors / Offices throughout Facility
1.11.a Numerous doors used by the public throughout the facility are inaccessible because knob hardware is used. D1 60 months
1.12 Pay Telephone Near Front Entrance
1.12.a The telephone is inaccessible because the clear floor space measures 24 inches wide, the highest operable part is 65 inches above the finished floor, the telephone lacks volume control, and the bench along the wall obstructs the clear floor space of the phone. TT1 60 months
1.13 Resource & Referral Center
1.13.a The registration counter at the Resource and Referral Center is inaccessible because it lacks a lower counter or clipboard. C6 60 months
1.14 Unisex Single User Toilet Room Near Front Entrance - 1st Floor
1.14.a There is no signage directing people with disabilities to the accessible toilet rooms. TR16 60 months
1.15 Designated Accessible Unisex Single User Toilet Room - 1st Floor
1.15.a No accessible coat hook has been provided. TR1 60 months
1.15.b No accessible mirror has been provided. TR14 60 months
1.15.c There is insufficient turning space within the toilet room. TR19 60 months
1.15.d The seat cover dispenser is inaccessible because the controls are mounted 60 inches above the finished floor. TR4 60 months
1.15.e The soap dispenser is inaccessible because the controls are mounted 50 inches above the finished floor, and front approach is required. TR5 60 months
1.15.f The baby changing table is inaccessible because the controls are mounted 58 inches above the finished floor. TR5 60 months
1.15.g The toilet is inaccessible because its centerline measures 16 inches from the side wall. SU15 60 months
1.15.h The toilet is inaccessible because the flush control is on the closed side. SU1 60 months
1.15.i The side grab bar at the toilet is inaccessible because it measures 24 inches in length, the far end is 29 inches from the rear wall, it is mounted 37 inches above the finished floor, and it is obstructed by the toilet paper dispenser. SU5 60 months
1.15.j The rear grab bar at the toilet is inaccessible because the length measures 37 inches. SU3 60 months
1.16 Drinking Fountain- near designated accessible toilet room on 1st Floor
1.16.a The drinking fountain near the designated accessible toilet room is inaccessible because the fountain lacks knee space height. DF4 60 months
1.17 Elevator to D and C Wings
1.17.a The elevator is inaccessible because there is no audio or visual hall arrival signal provided. E11 60 months
1.17.b The elevator is inaccessible because it lacks hall lanterns. E11 60 months
1.17.c The elevator is inaccessible because the hoistway signage is mounted 62 inches above the finished floor. E12 60 months
1.18 Room D-5
1.18.a The door to Rom D-5 is inaccessible because the pressure required to open the door is 13 pounds. D2 60 months
1.18.b The coat rack protrudes into the walkway and would not be detectable to a blind person using a cane. AR8 60 months
1.19 Room D-2
1.19.a The pull side of the door, which is accessed through a front approach, is inaccessible because it has only 2 inches of space on the latch side. D6, AR9 60 months
1.19.b The route between the wall and the chairs is inaccessible because it is only 22 inches wide. AR3 60 months
1.19.c The route to the tables is inaccessible because it is only 11 3/4 inches wide. AR3 60 months
1.20 Room D-3
1.20.a The pull side of the door, which is accessed through a front approach, is inaccessible because it has only 2 inches of space on the latch side. D6, AR9 60 months
1.21 Child Care Health Consultation- Room C-1
1.21.a The door to room C-1 is inaccessible because it has an opening width of only 29 inches. D25, AR9 60 months
1.21.b The door to room C-1 is inaccessible because the pressure required to open the door is 16 pounds. D2 60 months
1.22 Waddles/Toddler Room, Room C-2
1.22.a The door to room C-2 is inaccessible because the pressure required to open the door is 12 pounds. D2 60 months
1.22.b The gate to the kids area is inaccessible because it has an opening width of only 29 inches. D25, AR9 60 months
1.22.c The door to the changing room without toilet is inaccessible because it has an opening width of only 29 ½ inches. D25, AR9 60 months
1.23 Unisex Toilet Room with Stalls in C-2
1.23.a The toilet room sign is inaccessible. TR16, TR18 60 months
1.23.b The soap dispenser at the adult lavatory is inaccessible because the controls are mounted 58 inches above the finished floor. TR5 60 months
1.23.c The adult lavatory is inaccessible because the top of the lavatory is mounted 37 inches above the finished floor. TR11, TR16 60 months
1.23.d The adult lavatory is inaccessible because it lacks knee and toe clearances. TR11, TR16 60 months
1.23.e The adult lavatory is inaccessible because the knee space is blocked by a trash bin under the sink. TR11 60 months
1.23.f The adult lavatory is inaccessible because the hot water pipes are not insulated or otherwise configured to protect against contact. TR12 60 months
1.23.g There is no accessible stall provided. ST15, TR16 60 months
1.24 A.P. Room - The door to the A.P. room is inaccessible because each leaf has an opening width of only 30 inches. D25, AR9 60 months
1.25 Room C-8 - The pull side of the door, which is accessed through a front approach, is inaccessible because it has only 2 inches of space on the latch side. D6, AR9 60 months
1.26 Room C-7 - The pull side of the door, which is accessed through a front approach, is inaccessible because it has only 2 inches of space on the latch side. D6, AR9 60 months
1.27 Room C-4 - The pull side of the door, which is accessed through a front approach, is inaccessible because it has only 2 inches of space on the latch side. D6, AR9 60 months
1.28 Room C-6 - The pull side of the door, which is accessed through a front approach, is inaccessible because it has only 2 inches of space on the latch side. D6, AR9 60 months
1.29 Room C-5 - The pull side of the door, which is accessed through a front approach, is inaccessible because it has only 2 inches of space on the latch side. D6, AR9 60 months
1.30 Exterior Ramp to C Wing - The ramp is inaccessible because there is a handrail on only one side and it is 44 inches high, the slope measures between 12.4% and 20.6%, the higher landing in between segments measures 54 inches wide by 64 inches deep, and the lower landing in between segments measures 54 inches wide and 49 inches deep. R4, R5 60 months
1.31 Training Department, Room A-4 - The pull side of the door, which is accessed through a front approach, is inaccessible because it has insufficiently deep maneuvering clearance. D6 60 months
1.32 Boys Toilet Room with Stalls near B Wing Entrance
1.32.a The toilet room sign is inaccessible. TR16, TR18 60 months
1.32.b The door to the toilet room is inaccessible because it has an opening width of only 29 inches. D25, TR16 60 months
1.32.c The lavatory is inaccessible because it lacks toe and knee clearances. TR11, TR16 60 months
1.32.d The lavatory is inaccessible because it requires use of a foot pedal to operate. TR10, TR16 60 months
1.32.e The urinal is inaccessible because the urinal rim is mounted 18 inches above the finished floor. TR20, TR16 60 months
1.32.f The designated accessible stall is incorrectly configured as an ambulatory stall, and there is no standard accessible stall provided. ST15, TR16 60 months
1.32.g Girls Toilet Room with Stalls near B Wing
1.32.h The toilet room sign is inaccessible. TR16, TR18 60 months
1.32.i The door to the toilet room is inaccessible because it has an opening width of only 29 inches. D25, TR16 60 months
1.32.j There is insufficient turning space within the toilet room. TR19, TR16 60 months
1.32.k The lavatory is inaccessible because it requires use of a foot pedal to operate. TR10, TR16 60 months
1.32.l The designated accessible stall is incorrectly configured as an ambulatory stall, and there is no standard accessible stall provided. ST15, TR16 60 months
1.32.m The route from through the toilet room is inaccessible because the drain on the floor presents a change in level above grade. AR2, TR16 60 months
1.33 Drinking Fountain near Entrance to B Wing
1.33.a The drinking fountain is inaccessible because it lacks knee space height, width, and depth. DF4 60 months
1.33.b Although a designated accessible drinking fountain is provided, there is no drinking fountain provided for people who have difficulty bending or stooping. DF3 60 months
1.34 Room B-3
1.34.a The door to room B-3 is inaccessible because it has an opening width of only 30 inches. D25, AR9 60 months
1.34.b The door to room B-3 is inaccessible because the pressure required to open the door exceeds 5 pounds. D2 60 months
1.35 Exterior Ramp to B Wing Near Entrance
1.35.a The ramp is inaccessible because the handrail on the right side is not continuous and the handrails lack sufficient extensions. R4 60 months
1.36 Unisex Adult Toilet Room B-Wing
1.36.a There is no signage directing people with disabilities to the accessible toilet rooms. TR16 60 months
1.37 Exterior Door to Portable Classroom
1.37.a The exterior door is inaccessible because it has an opening width of only 22 inches. D25, AR9 60 months
1.38 Ramp to Portable Classroom
1.38.a The ramp is inaccessible because there is a handrail on only one side, the distance between the handrail and the wall is 2¼ inches, and the handrail is 2¼ inches wide. R4 60 months
2 Juror Lot, Jefferson and Monroe Avenues, Rockville, MD 20850
2.1 Parking - Although the parking lot has a total of 141 parking spaces with three parking spaces designated as being accessible for persons with disabilities, an inadequate number are designated as reserved for people with disabilities. In addition, two of the accessible spaces lack appropriate signage. P3 36 months
3 Silver Spring Health and Human Services - Regional Center, 8818 Georgia Avenue, Silver Spring, Maryland 20910
3.1 Entrance - The railing for the power door opener protrudes into the walkway and would not be detectable to a blind person using a cane. AR8 60 months
3.2 Ramp near Entrance
3.2.a The ramp is inaccessible because the slope at the top measures 10%, and the slope at the bottom landing measures 5.3%, the ramp lacks edge protection on one side, the handrails are mounted 31 inches above the finished floor, there are no handrail extensions on the left or the bottom, the bottom left handrail is not returned, there is a 2 inch gap between the handrail and the wall, and the handrail measures 2 ½ inches in diameter. R1, R4 60 months
3.2.b The bottom left handrail protrudes into the walkway and would not be detectable to a blind person using a cane. AR8 60 months
3.3 Sidewalk at bottom of ramp - The sidewalk at the bottom of the ramp is inaccessible because the slope measures 7.5% and the cross slope measures 6.1%. AR1, R5 60 months
3.4 Parking
3.4.a The parking reserved for persons with disabilities is inaccessible because none of the parking spaces are level with slopes measuring 5.5% and the access aisles have slopes measuring 6% and cross slopes measuring 4.6%. P7 60 months
3.4.b The parking reserved for persons with disabilities is not located on the shortest accessible route to the accessible facility entrance. P5 60 months
3.5 Route from Parking to Main Entrance - Ramp - The route from the parking area to the main entrance is inaccessible because the slope measures 2.4%, the cross slope measures 5.9% and the left side of the ramp is flared. AR1, AR5 60 months
3.6 Interior doors throughout the facility - The doors leading to various offices, toilet rooms, hallways, and other areas used by the public are inaccessible because knob hardware is used. D1 60 months
3.7 Women's Toilet Room (stalls) - Lobby
3.7.a The toilet room door is inaccessible because the pressure required to open the door is 10 pounds. D2 60 months
3.7.b The pull side of the door to the toilet room, which is accessed through a front approach, is inaccessible because it has only 2 inches of maneuvering clearance. D6 60 months
3.7.c The sanitary napkin dispenser is inaccessible because the controls are mounted 51 inches above the finished floor over an obstruction. TR4 60 months
3.7.d The lavatory is inaccessible because there is insufficient knee space. TR11 60 months
3.7.e The toilet is inaccessible because there is insufficient clear floor space. ST18 60 months
3.7.f The toilet is inaccessible because the top of the seat is 15 ½ inches above the finished floor. ST20 60 months
3.7.g The toilet is inaccessible because its centerline measures 20 inches from the side wall. ST17 60 months
3.7.h No accessible coat hook has been provided. TR1 60 months
3.7.i The side grab bar at the toilet is inaccessible because the toilet paper dispenser and the seat cover dispenser interfere with its use. ST9 60 months
3.8 Men's Toilet Room (stalls) - Lobby
3.8.a The toilet room door is inaccessible because the pressure required to open the door is 10 pounds. D2 60 months
3.8.b The pull side of the door to the toilet room, which is accessed through a front approach, is inaccessible because it has only 2 inches of maneuvering clearance. D6 60 months
3.8.c The toilet is inaccessible because there is insufficient clear floor space. ST18 60 months
3.8.d The toilet is inaccessible because its centerline measures 19 ½ inches from the side wall. ST17 60 months
3.8.e The toilet is inaccessible because the flush control is on the closed side. ST2 60 months
3.8.f No accessible coat hook has been provided. TR1 60 months
3.8.g The side grab bar at the toilet is inaccessible because the toilet paper dispenser and the seat cover dispenser interfere with its use. ST8 60 months
3.9 Lobby Drinking Fountain
3.9.a The drinking fountain protrudes into the walkway and would not be detectable to a blind person using a cane. AR8 60 months
3.9.b Although an accessible drinking fountain is provided, there is no drinking fountain provided for people who have difficulty bending or stooping. DF3 60 months
3.10 Room 353 - The pull side of the door to Room 353, which is accessed through a front approach, is inaccessible because it has only 4½ inches of maneuvering clearance. D6, AR9 60 months
3.11 Child and Adult Mental Health Office - The registration counter is inaccessible because it is mounted 42 inches above the finished floor. C6 60 months
3.12 Unisex Single-User Toilet Room
3.12.a The toilet room sign is inaccessible. TR16, TR18 60 months
3.12.b The door to the toilet room is inaccessible because it has an opening width of only 27 inches. D25, TR16 60 months
3.12.c No accessible mirror has been provided. TR14 60 months
3.12.d The seat dispenser is inaccessible because the controls are mounted 53 inches above the finished floor over an obstruction. TR4 60 months
3.12.e The toilet is inaccessible because its centerline measures 16 inches from the side wall. SU15, TR16 60 months
3.12.f The toilet paper dispenser is inaccessible because it is mounted 1 inch under the grab bar and interferes with the use of the grab bar. SU8 60 months
3.12.g The rear grab bar at the toilet is inaccessible because the overall length measures 24 inches and it is mounted 36 ½ inches above the finished floor. SU3, TR16 60 months
3.13 Room 512 - The door to Room 512, which is accessed from the latch side of the door, is inaccessible because it lacks maneuvering space and depth. D10, AR9 60 months
3.14 Room 517 - The route through the office is inaccessible because it is only 24 inches wide. D25, AR9 60 months
3.15 Interior Door to Back Hallway, Therapist Office - The double doors to the back hallway are inaccessible because each leaf measures 27 inches wide. D25, AR9 60 months
3.16 Women's Toilet Room (stalls) - 2nd Floor
3.16.a The toilet room sign is inaccessible. TR16, TR18 60 months
3.16.b The toilet room door is inaccessible because the pressure required to open the door is 11 pounds. D2 60 months
3.16.c The pull side of the door to the toilet room, which is accessed from the front, is inaccessible because it has only 2 inches of maneuvering clearance on the latch side. D6, TR16 60 months
3.16.d The push side of the door to the toilet room, which is accessed through a front approach and which has both a closer and a latch, is inaccessible because it has no latch-side maneuvering clearance. D7, TR16 60 months
3.16.e There is an air dryer that protrudes into the walkway and would not be detectable to a blind person using a cane. AR8 60 months
3.16.f The soap dispenser is inaccessible because the controls are mounted 52 inches above the finished floor over an obstruction. TR4 60 months
3.16.g The lavatory is inaccessible because the knee and toes clearances measure 6 inches. TR11, TR16 60 months
3.16.h The lavatory is inaccessible because the hot water pipes are not insulated or otherwise configured to protect against contact. TR12 60 months
3.16.i There is no accessible stall provided. ST15, TR16 60 months
3.17 Men's Toilet Room (stalls) - 2nd Floor
3.17.a The toilet room sign is inaccessible. TR16, TR18 60 months
3.17.b The toilet room door is inaccessible because the pressure required to open the door is 9 pounds. D2 60 months
3.17.c The pull side of the door to the toilet room, which is accessed through a front approach, is inaccessible because it has no latch-side maneuvering clearance. D6, TR16 60 months
3.17.d The push side of the door to the toilet room, which is accessed through a front approach and which has both a closer and a latch, is inaccessible because it has no latch-side maneuvering clearance. D7, TR16 60 months
3.17.e The toilet room door is inaccessible because there is a 1 inch threshold. D23, TR16 60 months
3.17.f The lavatory is inaccessible because the lavatory knee and toe clearances measure 7 inches. TR11, TR16 60 months
3.17.g The lavatory is inaccessible because the hot water pipes are not insulated or otherwise configured to protect against contact. TR12 60 months
3.17.h The faucet is inaccessible because it requires twisting of the wrist to operate. TR10 60 months
3.17.i The urinal is inaccessible because the urinal is centered at 27 ½ inches. TR20, TR16 60 months
3.17.j There is no accessible stall provided. ST15, TR16 60 months
3.18 Drinking Fountain - 2nd Floor - Although a drinking fountain is provided, there is no accessible drinking fountain because it lacks knee space width and there is no approach to the drinking fountain due to a chair and trash can. DF1 60 months
3.19 Entry door leading to hallway toward offices - 2nd Floor - The office door is inaccessible because the lock requires tight grasping and twisting. D1, AR9 60 months
3.20 Room 203 - The pull side of the door to room 203, which is accessed through a front approach, is inaccessible because it has only 3 inches of maneuvering clearance. D6, AR9 60 months
3.21 Elevator - The elevator is inaccessible because, although emergency communications are provided, the emergency phone cord measures 21 inches. E8 60 months
3.22 Single User Toilet Room at Community Action Partnership
3.22.a The toilet room sign is inaccessible. TR16, TR18 60 months
3.22.b The door to the toilet room is inaccessible because it has an opening width of only 28 inches. D25, TR16 60 months
3.22.c No accessible coat hook has been provided. TR1 60 months
3.22.d No accessible mirror has been provided. TR14 60 months
3.22.e The seat cover dispenser is inaccessible because the controls are mounted 52 inches above the finished floor over an obstruction. TR4 60 months
3.22.f The lavatory is inaccessible because the clear floor space is obstructed by the trash receptacle. TR8 60 months
3.22.g The toilet is inaccessible because its centerline measures 15 ½ inches from the side wall. SU15, TR16 60 months
3.22.h The toilet is inaccessible because the flush control is on the closed side. SU1, TR16 60 months
3.22.i The toilet paper dispenser is inaccessible because it is mounted 15 ½ inches above the finished floor and obstructs the side grab bar. SU8 60 months
3.22.j The side grab bar at the toilet is inaccessible because the far end is mounted 60 inches from the rear wall. SU6, TR16 60 months
3.22.k The rear grab bar at the toilet is inaccessible because the overall length measures 24 inches, the far end of the rear grab is mounted 26 inches from the side wall, and the distance between the grab bar and the wall is 1 3/4 inches. SU2, TR16 60 months
4 Noyes Library for Children, 10237 Carroll Place, Kensington, Maryland 20895
4.1 Single User Toilet Room - The unisex single user toilet room contains a number of inaccessible elements and is not accessible to people with disabilities. SU13 48 months
4.2 Exterior Entrance and Doors
4.2.a There are only stairs leading to the doors. AR2 48 months
4.2.b The exterior entrance is inaccessible because the vestibule measures 43 inches between doors. D3 48 months
4.2.c The exterior entrance is inaccessible because it lacks maneuvering clearance on both the push and pull sides of the door. D6, D7 48 months
4.2.d The threshold at both exterior doors is inaccessible because there is a 1 inch change in level at the threshold to the door. D23 48 months
4.2.e The interior door is inaccessible because knob hardware is used. D1 48 months
4.3 Stairs - The stairs at the entrance are inaccessible because they are 9¾ inches wide, the top step is 8 ½ inches wide, and there are no handrail extensions. AR10 48 months
4.4 Stairs - The stairs at the courtyard are inaccessible because they lack handrails. AR10 48 months
5 Mid-County Regional Services Center, 2424 Reedie Drive, Wheaton, MD 20902
5.1 Route - to crosswalk, across Reedie, up curb ramp, along sidewalk to entrance
5.1.a The route from Reedie to the entrance is inaccessible because the curb ramp lacks detectable warnings. AR5 36 months
5.1.b The route from Reedie to the entrance is inaccessible because there is a 1 ½ inch change in level at the gutter at the sidewalk near the crosswalk. AR1 36 months
5.2 Drinking Fountain - main lobby
5.2.a Although a drinking fountain is provided, there is no accessible drinking fountain because the water height measures 3 inches at the lower fountain. DF7 36 months
5.2.b The higher drinking fountain protrudes into the walkway and would not be detectable to a blind person using a cane. AR8 36 months
5.3 Men's Toilet Room - 1st floor
5.3.a The toilet room sign is mounted on the door. TR17 36 months
5.3.b The toilet room door is inaccessible because the pressure required to open the door is 17 pounds. D2 36 months
5.3.c The pull side of the door to the toilet room, which is accessed through a front approach, is inaccessible because it has only 13 ½ inches maneuvering space on the latch side. D6 36 months
5.3.d The seat cover dispenser is inaccessible because the controls are mounted 59 inches above the finished floor. TR4 36 months
5.3.e The toilet is inaccessible because its centerline measures 16 ½ inches from the side wall. ST17 36 months
5.3.f The side grab bar at the toilet is inaccessible because the closer end is mounted 13 inches to the rear wall ad the grab bar is mounted 31 ½ inches above the finished floor. ST6 36 months
5.3.g The rear grab bar at the toilet is inaccessible because it is mounted 38 inches above the finished floor. ST12 36 months
5.4 Women's Toilet Room - 1st Floor
5.4.a The toilet room door is inaccessible because the pressure required to open the door is 18 pounds. D2 36 months
5.4.b The seat cover dispenser is inaccessible because the controls are mounted 61 inches above the finished floor. TR4 36 months
5.4.c The lavatory is inaccessible because the top of the counter is mounted 34 ½ inches above the finished floor. TR11 36 months
5.4.d The toilet is inaccessible because its centerline measures 20 inches from the side wall. ST17 36 months
5.4.e The toilet is inaccessible because the flush control is on the closed side. ST2 36 months
5.4.f The side grab bar at the toilet is inaccessible because it is obstructed by the toilet paper dispenser. ST9 36 months
5.4.g The side grab bar at the toilet is inaccessible because the far end is mounted 45 inches from the rear wall. ST13 36 months
5.5 Meeting Room - 1st floor
5.5.a The meeting room door is inaccessible because the pressure required to open the door is 16 pounds. D2 36 months
5.5.b The meeting room is inaccessible to people with hearing impairments because there is no signage indicating the availability of an assistive listening system. AA3 36 months
5.6 Men's Single User Toilet Room - Project Health Clinic
5.6.a The toilet room signage is inaccessible. TR18, MC4 36 months
5.6.b The door to the toilet room is inaccessible because it has an opening width of only 23 inches. D25, MC4 36 months
5.6.c The toilet room door is inaccessible because the pressure required to open the door is 11 pounds. D2, MC4 36 months
5.6.d The door to the toilet room, which is accessed from the front, is inaccessible because it has only 4 ½ inches of maneuvering space due to a table. D6, D7, MC4 36 months
5.6.e No accessible coat hook has been provided. TR1, MC4 36 months
5.6.f There is insufficient turning space within the toilet room. TR19, MC4 36 months
5.6.g The seat cover dispenser is inaccessible because the controls are mounted 45 inches above the finished floor over the toilet. TR4, MC4 36 months
5.6.h The lavatory is inaccessible because the hot water pipes are not insulated or otherwise configured to protect against contact. TR12, MC4 36 months
5.6.i The toilet is inaccessible because its centerline measures 14 ½ inches from the side wall. SU15, MC4 36 months
5.6.j The toilet is inaccessible because the flush control is on the closed side. SU1, MC4 36 months
5.6.k The toilet paper dispenser is inaccessible because it is mounted 40 inches from the rear wall. SU17, MC4 36 months
5.6.l There are no grab bars provided. Provide a rear grab bar that is at least 36 inches in overall length, with the closer end no more than 6 inches from the side wall, and a side grab bar that is at least 42 inches in overall length, with the far end mounted at least 54 inches from the rear wall and the closer end 12 inches or less from the rear wall. SU10, MC4 36 months
5.7 Women's Single User Toilet Room - Project Health Clinic
5.7.a The toilet room signage is mounted 61 inches above the finished floor. MC4 36 months
5.7.b The door to the toilet room is inaccessible because it has an opening width of only 30 inches. D25, MC4 36 months
5.7.c The toilet room door is inaccessible because the pressure required to open the door is 12 pounds. D2, MC4 36 months
5.7.d The door to the toilet room, which is accessed from the front, is inaccessible because it has only 8 inches of maneuvering space due to a trash can. D6, D7, MC4 36 months
5.7.e The route to the toilet room is inaccessible because a table blocks the path of travel in the room. AR2, AR3, MC4 36 months
5.7.f There is insufficient turning space within the toilet room. TR19, MC4 36 months
5.7.g The seat cover dispenser is inaccessible because the controls are mounted 45 inches above the finished floor over the toilet. TR4, MC4 36 months
5.7.h The toilet is inaccessible because its centerline measures 16 ½ inches from the side wall. SU15, MC4 36 months
5.7.i There are no grab bars provided. SU10, MC4 36 months
5.8 Elevators
5.8.a The door is inaccessible because it has an opening width of only 31 inches. D25 36 months
5.8.b The elevator is inaccessible because, although emergency communications are provided, they require voice communication to operate. E8 36 months
5.9 Drinking Fountains - 2nd Floor - The higher drinking fountain protrudes into the walkway and would not be detectable to a blind person using a cane. AR8 36 months
5.10 HHS Women's Cancer Control Program - 2nd Floor
5.10.a The HHS door is inaccessible because the pressure required to open the door is 10 pounds. D2 36 months
5.10.b The conference room door is inaccessible because the pressure required to open the door is 12 pounds. D2 36 months
5.10.c The conference room is inaccessible to people with hearing impairments because there is no signage indicating the availability of an assistive listening system. AA3 36 months
5.11 United Ministries Food Pantry - 2nd Floor
5.11.a The pull side of the door to food pantry, which is accessed through a front approach, is inaccessible because it has only 4 inches of maneuvering clearance. D6, AR9 36 months
5.11.b Although the facility contains an emergency alarm system, the alarm system is inaccessible because no visual alarm is provided at this location. TR21 36 months
5.12 Men's Toilet Room - stalls
5.12.a The toilet room sign is not mounted on the latch side of the door. TR17 36 months
5.12.b The toilet room door is inaccessible because the pressure required to open the door is 10 pounds. D2 36 months
5.12.c The seat cover dispenser is inaccessible because the controls are mounted 60 inches above the finished floor. TR4 36 months
5.12.d There is no accessible stall provided.

ST15

TR16

36 months
5.13 Women's Toilet Room - stalls
5.13.a The toilet room sign is not mounted on the latch side of the door. TR17 36 months
5.13.b The toilet room door is inaccessible because the pressure required to open the door is 14 pounds. D2 36 months
5.13.c The seat cover dispenser is inaccessible because the controls are mounted 60 inches above the finished floor. TR4 36 months
5.13.d There is no accessible stall provided.

ST15

TR16

36 months
5.14 Clean and Safe Team Office - 3rd Floor - The office door is inaccessible because the pressure required to open the door is 8 pounds. D2 36 months
5.15 Montgomery County Police Department - 3rd Floor - The main counter is inaccessible because the hole through which people communicate is 55 inches above the finished floor, and there is no alternate means to communicate. C7 36 months
5.16 Drinking Fountain - The drinking fountain in the 3rd floor hallway is inaccessible because the knee space height measures 21 inches high. DF4 36 months
5.17 Men's Toilet Room - Stalls, 3rd Floor
5.17.a The toilet room sign is not mounted on the latch side of the door.

TR17

TR16

36 months
5.17.b The toilet room door is inaccessible because the pressure required to open the door is 14 pounds. D2 36 months
5.17.c There is no accessible stall provided.

ST15

TR16

36 months
5.18 Women's Toilet Room - Stalls, 3rd Floor
5.18.a The toilet room sign is not mounted on the latch side of the door.

TR17

TR16

36 months
5.18.b The toilet room door is inaccessible because the pressure required to open the door is 10 pounds. D2 36 months
5.18.c The pull side of the door to the toilet room, which is accessed through a front approach, is inaccessible because it has only 12 inches maneuvering clearance on the latch side.

D6

TR16

36 months
5.18.d The seat cover dispenser is inaccessible because the controls are mounted 60 inches above the finished floor. TR4 36 months
5.18.e The air dryer protrudes into the walkway and would not be detectable to a blind person using a cane. AR8 36 months
5.18.f There is no accessible stall provided.

ST15

TR16

36 months
5.18.g The side grab bar at the toilet is inaccessible because it is obstructed by the sanitary napkin dispenser. ST9 36 months
5.18.h The lavatory is inaccessible because the hot water pipes are not insulated or otherwise configured to protect against contact. TR12 36 months
5.19 Adult Behavioral Health Program - 3rd Floor, door into lobby - The pull side of the door to the Health program, which is accessed through a front approach, is inaccessible because it has only 5 inches maneuvering clearance on the latch side. D6, AR9 36 months
5.20 Adult Behavioral Health Program - 3rd Floor, door from lobby to offices
5.20.a The door to the lobby is inaccessible because it has an opening width of only 30 inches. D25 36 months
5.20.b The door is inaccessible because the pressure required to open the door is 7 pounds. D2 36 months
5.20.c The lobby door is inaccessible because knob hardware is used. D1 36 months
5.21 Conference Room #307
5.21.a The pull side of the door, which is accessed through a front approach, is inaccessible because it has only 11 inches maneuvering clearance on the latch side. D6, AR9 36 months
5.21.b The conference room is inaccessible to people with hearing impairments because there is no signage indicating the availability of an assistive listening system. AA3 36 months
6 5th District Police Station - Germantown, Department of Police, 20000 Aircraft Drive, Germantown, Maryland 20874
6.1 Parking - The parking lot, with a total of approximately 46 parking spaces, is inaccessible because there is no adequate van accessible access aisle, no van accessible signage, and the 3 designated standard accessible spaces do not comply with the standards because of inadequate size, slope and ground surface. This lot requires 1 van accessible space and one standard accessible space. P3 60 months
6.2 Route from parking to Front Entrance - The route from the parking area to the front entrance is inaccessible because the routes from the parking spaces have slopes of 6.2% and 10%. In addition, the route in between the parking spaces has an adequate slope but has a cross-slope of 3.1%. AR1 60 months
6.3 Drinking Fountain in Lobby - Although a lower drinking fountain is provided, there is no drinking fountain provided for people who have difficulty bending or stooping. DF3 60 months
6.4 Men's Single-User Toilet Room in Lobby - The single user toilet room contains a number of inaccessible elements and is not accessible to people with disabilities. SU14 60 months
6.5 Women's Toilet Room in Lobby - The single user toilet room contains a number of inaccessible elements and is not accessible to people with disabilities. SU14 60 months
6.6 Counter in Lobby - The lobby counter is inaccessible because it is 43 inches above the finished floor with no equivalent facilitation provided. C6 60 months
6.7 Rear/Prisoner Entrance - sally port - There is a 5 ½ inch change in level at the threshold at the door. D23 60 months
6.8 Holding Cells
6.8.a The holding cell toilet room has a standard toilet and lavatory that is not accessible to persons with disabilities. TR7, SU14 60 months
6.8.b Although an audible alarm is provided in this facility, there is no visual alarm appliance in the holding cells. TR21 60 months
6.9 Juvenile Holding Cells
6.9.a The holding cell toilet room has a standard toilet and lavatory that is not accessible to persons with disabilities. TR7, SU14 60 months
7 Damascus Childcare Center, 9625 Main Street, Damascus, Maryland 20872
7.1 Parking - The route through and around the parking area is not firm, stable and slip-resistant, and there are several large cracks along the route. AR1 12 months
7.2 Accessible Route
7.2.a The route from the parking area to the front entrance is inaccessible because it has a slope of 6% (with no ramp features) and a cross slope of 2.3%. AR1 12 months
7.2.b There is no detectable warning at the curb ramp, and it slopes 13.1%. AR5 12 months
7.3 Unisex Toilet Room - SUTR
7.3.a The toilet room lacks accessible signage. TR17 12 months
7.3.b Although an audible alarm is provided in this facility, there is no visual alarm appliance in the toilet room. TR21 12 months
7.3.c No accessible mirror has been provided. TR14 12 months
7.3.d The lavatory is inaccessible because the hot water pipes are not insulated or otherwise configured to protect against contact. TR12 12 months
7.3.e The lavatory is inaccessible because the bottom edge of the apron measures 28 inches above the finished floor. TR11 12 months
7.3.f There is insufficient turning space within the toilet room because the room measures 69 inches by 31 inches. TR19 12 months
7.3.g The toilet is inaccessible because its centerline measures 19 inches from the side wall, and the flush control is mounted on the "closed" side of the toilet. SU15 12 months
7.3.h The toilet paper dispenser is inaccessible because it is 15 inches from the finished floor and 45 inches from the rear wall. SU17 12 months
7.3.i The distance from the rear wall to the far end of the side grab bar is 45 inches. SU6 12 months
7.3.j The rear grab bar is 30 inches long, and the distance from the side wall to the far end of the rear grab bar is 34 inches. SU3 12 months
7.3.k The rear grab bar at the toilet is inaccessible because it is obstructed by the flush valve. SU4 12 months
7.3.l The table in front of the toilet obstructs maneuvering space and, therefore, the toilet is inaccessible because there is insufficient clear floor space. SU16 12 months
8 Damascus Senior Center, 9701 Main Street, Damascus, Maryland 20872
8.1 Accessible Route - The route from the parking area to the entrance is inaccessible because it has slope of more than 6% and a cross slope as much as 2.8%. AR1 12 months
8.2 Small Meeting Room
8.2.a No accessible coat hook has been provided. TR1 12 months
8.2.b The faucet is inaccessible because the hardware requires twisting of the wrist to operate. TR10 12 months
8.3 Assembly Area
8.3.a The route from the main auditorium area up to the stage is inaccessible because it requires using steps. AR2, AR9 12 months
8.3.b The auditorium is inaccessible because the pressure required to open the door is 7 pounds. D2 12 months
8.3.c The coat rack requires a reach of 63 inches above the finished floor to use it. TR1, TR5 12 months
8.3.d There is no signage informing the public of the availability of an assistive listening system. AA3 12 months
8.4 Health Room - The door is inaccessible because the magazine rack only allows an opening width of 29 inches. D25 12 months
8.5 Craft Room - Although an audible alarm is provided in this facility, there is no visual alarm appliance in the craft room. TR21 12 months
8.6 Men's Toilet Room - Stalls
8.6.a The toilet room lacks accessible signage because it is not on the latch side of the door, its centerline is 63 inches above the finish floor, and there are no Braille characters. TR17, TR16, TR22 12 months
8.6.b The toilet room is inaccessible because the pressure required to open the door is 8 pounds. D2 12 months
8.6.c The toilet room door swings into the required clear floor space at the lavatory. TR8, TR16, TR22 12 months
8.6.d Although an audible alarm is provided in this facility, there is no visual alarm appliance in the toilet room. TR21 12 months
8.6.e There is insufficient turning space within the toilet room. TR19, TR16, TR22 12 months
8.6.f The lavatory is inaccessible because the bottom edge of the apron is 28 inches above the finished floor. TR11, TR16, TR22 12 months
8.6.g The urinal is inaccessible because the rim is 25 inches above the finished floor, it allows only 27 inches by 48 inches of clear floor space, and the flush control is 45 inches above the finished floor. TR20, TR16, TR22 12 months
8.6.h The route to the stalls is inaccessible because a large metal table makes the path only 34 inches wide. AR3 12 months
8.6.i There is no accessible stall provided. ST15, TR16, TR22 12 months
8.7 Women's Toilet Room - Stalls
8.7.a The toilet room lacks accessible signage because it is not on the latch side of the door, its centerline is 63 inches above the finish floor, and there is no braille. TR17 12 months
8.7.b The toilet room is inaccessible because the pressure required to open the door is 7 pounds. D2 12 months
8.7.c The toilet room door swings into the required clear floor space and leaves only 23 inches. SU16, TR16, TR22 12 months
8.7.d Although an audible alarm is provided in this facility, there is no visual alarm appliance in the toilet room. TR21 12 months
8.7.e There is insufficient turning space within the toilet room. TR19, TR16, TR22 12 months
8.7.f The lavatory is inaccessible because the bottom edge of the apron is 28 inches above the finished floor. TR11, TR16, TR22 12 months
8.7.g The route to the stalls is inaccessible because a large metal table makes the path only 34 inches wide. AR3 12 months
8.7.h There is no accessible stall provided. ST15, TR16, TR22 12 months
8.7.i No accessible coat hook has been provided. TR1 12 months
9 Montgomery Aquatic Center, 5900 Executive Boulevard, North Bethesda, MD 20852
9.1 Entrance - The building is inaccessible because it does not display signage for persons with a disability. D16 48 months
9.2 Lower Level Stairs - The route near the lower level stairs is inaccessible because it presents an overhead hazard. AR7 48 months
9.3 Upper Level Front Counter - The front counter is inaccessible because it is 42 inches above the finished floor. C6 48 months
9.4 Men's Toilet Room Upper Level - Stalls
9.4.a The toilet room lacks accessible signage because the sign is not on the latch side of the door. TR17 48 months
9.4.b The toilet room is inaccessible because the pressure required to open the door is 17 pounds. D2 48 months
9.4.c The pull side of the door to the toilet room, which is accessed through a front approach, is inaccessible because it has a maneuvering clearance that is only 44 ½ inches deep due to a partition. D6 48 months
9.4.d The air dryer protrudes into the walkway and would not be detectable to a blind person using a cane. AR8 48 months
9.4.e The lavatory is inaccessible because the bottom edge of the apron is 28 inches from the finished floor. TR11 48 months
9.4.f The urinal is inaccessible because the rim is 23 inches above the finished floor, it allows only 27 inches by 48 inches of clear floor space, and the flush control is 44 ½ inches above the finished floor. TR20 48 months
9.4.g The toilet is inaccessible because the top of the seat is 22 inches above the finished floor. ST20 48 months
9.4.h The toilet is inaccessible because the flush control is on the closed side. ST2 48 months
9.4.i No accessible coat hook has been provided. TR1 48 months
9.4.j The toilet paper dispenser is inaccessible because it is mounted 43 inches from the rear wall. ST19 48 months
9.4.k The rear grab bar at the toilet is inaccessible because it is mounted with its end 8 ½ inches from the side wall. ST4 48 months
9.4.l The rear grab bar at the toilet is inaccessible because the flush control interferes with its usage. ST5 48 months
9.5 Women's Toilet Room Upper Level - Stalls
9.5.a The toilet room lacks accessible signage because it is not on the latch side of the door. TR17 48 months
9.5.b The toilet room is inaccessible because the pressure required to open the door is 15 pounds. D2 48 months
9.5.c The air dryer protrudes into the walkway and would not be detectable to a blind person using a cane. AR8 48 months
9.5.d The lavatory is inaccessible because the bottom edge of the apron is mounted 27 ½ inches above the finished floor. TR11 48 months
9.5.e The toilet is inaccessible because the top of the seat is 22 inches above the finished floor. ST20 48 months
9.5.f The toilet is inaccessible because the flush control is on the closed side. ST2 48 months
9.5.g No accessible coat hook has been provided. TR1 48 months
9.5.h The toilet paper dispenser is inaccessible because it is 37 ½ inches from the rear wall. ST19 48 months
9.5.i The side grab bar at the toilet is inaccessible because a trash receptacle interferes with its usage. ST9 48 months
9.5.j The side grab bar at the toilet is inaccessible because it is mounted 32 and ½ inches above the finished floor. ST12 48 months
9.5.k The rear grab bar at the toilet is inaccessible because the flush control interferes with its usage. ST5 48 months
9.6 Drinking Fountain Upper Level - The drinking fountain has a spout that is 37 inches above the finished floor. DF6 48 months
9.7 Telephone - The telephone is inaccessible because there is no signage to indicate its accessibility. TT1 48 months
9.8 Special Needs Changing Room - Lower Level
9.8.a The signage provided is inaccessible because it is mounted incorrectly. TR17 48 months
9.8.b The special needs changing room is inaccessible because the pressure required to open the door is 12 pounds. D2 48 months
9.8.c The pull side of the entrance door is inaccessible because the hardware requires tight grasping. D1 48 months
9.8.d The lavatory is inaccessible because the bottom edge of the apron is mounted 28 inches above the finished floor. TR11 48 months
9.8.e The toilet is inaccessible because the seat is 22 inches above the finished floor and its centerline is 20 inches from the side wall. SU14 48 months
9.8.f The side grab bar is inaccessible because the toilet paper dispenser is mounted 9 ½ inches above the grab bar, the side grab bar is 24 inches long, and the total length from the rear wall to the far end of the grab bar is 34 ½ inches. SU5 48 months
9.8.g The rear grab bar is inaccessible because its closer end is mounted 6 ½ inches from the side wall, and the flush control interferes with its usage. SU2 48 months
9.8.h The shower is inaccessible because the seat is not opposite of the controls, the shower does not have an L-shaped grab bar, and the grab bars are 41 ½ inches above the finished floor. B9 48 months
9.8.i The hardware for the locker doors are inaccessible. D1 48 months
9.8.j No accessible mirror has been provided. TR14 48 months
9.8.k The bench provided is inaccessible because it is 24 inches above the finished floor, and it is not fixed or attached to the wall. L1 48 months
9.9 Drinking Fountain at Upper Pool Area at top of Ramp
9.9.a The drinking fountain has a spout that is 37 inches above the finished floor. DF6 48 months
9.9.b The drinking fountain protrudes into the walkway and would not be detectable to a blind person using a cane. AR8 48 months
9.10 Drinking Fountain near Men's Locker
9.10.a The drinking fountain has a spout that is 37 ½ inches above the finished floor. DF6 48 months
9.10.b The drinking fountain protrudes into the walkway and would not be detectable to a blind person using a cane. AR8 48 months
9.11 Elevator at Lobby
9.11.a The elevator is inaccessible because the emergency controls are at 27 ½ inches above the elevator floor. E9 48 months
9.11.b The elevator is inaccessible because there is no raised lettering or symbols for the emergency system. E4 48 months
9.11.c The elevator is inaccessible because, although emergency communications are provided, the door to the emergency controls requires tight pinching to operate, the telephone cord is only 27 inches long, and the system does not operate without voice communication. E8 48 months
9.12 Lower Level Pool Entry - not through locker rooms
9.12.a The door from the lobby is inaccessible because the pressure required to open the door is 12 pounds. D2 48 months
9.12.b The door into the pool area is inaccessible because the pressure required to open the door is 10 pounds. D2 48 months
9.13 Ramp - in pool area - The route from the locker rooms up to the Jacuzzi and small pool is inaccessible because the ramp is slippery and does not have 12 inch handrail extensions at the top of the ramp. AR1, R4 48 months
9.14 Women's Locker Room - Lower Level
9.14.a The toilet room lacks accessible signage because its centerline is mounted 59 ½ inches from the finish floor and there is not Brailled. TR17, TR16 48 months
9.14.b The women's locker room is inaccessible because the pressure required to open the door is 14 pounds. D2, TR16 48 months
9.14.c The door hardware is inaccessible. D1, TR16 48 months
9.14.d The lockers are inaccessible because pinching is required to operate the doors. D1 48 months
9.14.e The benches provided are inaccessible because they are 17 inches wide.

L1

TR16

48 months
9.14.f The air dryer protrudes into the walkway and would not be detectable to a blind person using a cane. AR8 48 months
9.14.g The lavatory is inaccessible because the bottom edge of the apron is mounted 27 inches above the finished floor. TR11, TR16 48 months
9.14.h The lavatory is inaccessible because the hot water pipes are not insulated or otherwise configured to protect against contact. TR12 48 months
9.14.i The faucet is inaccessible because the hardware requires twisting of the wrist to operate. TR10 48 months
9.14.j Although there are 5 total toilet stalls, there is no accessible stall provided. ST15, TR16 48 months
9.14.k The showers have a number of inaccessible features. B8 48 months
9.15 Men's Locker Room - Lower Level
9.15.a There is no room signage. TR17, TR16 48 months
9.15.b The men's locker room is inaccessible because the pressure required to open the door is 9 pounds. D2 48 months
9.15.c The door hardware is inaccessible. D1, TR16 48 months
9.15.d The lockers are inaccessible because pinching is required to operate the doors. D1, TR16 48 months
9.15.e The benches provided are inaccessible because they are 17 inches wide. L1, TR16 48 months
9.15.f The soap dispenser protrudes into the walkway and would not be detectable to a blind person using a cane. AR8 48 months
9.15.g The air dryer protrudes into the walkway and would not be detectable to a blind person using a cane. AR8 48 months
9.15.h The lavatory is inaccessible because the bottom edge of the apron is 28 ¼ inches above the finished floor. TR11, TR16 48 months
9.15.i The lavatory is inaccessible because the hot water pipes are not insulated or otherwise configured to protect against contact. TR12 48 months
9.15.j The faucet is inaccessible because the hardware requires twisting of the wrist to operate. TR10 48 months
9.15.k The urinal is inaccessible because the rim is 18 ½ inches above the finished floor. TR20, TR16 48 months
9.15.l No accessible clothes hook has been provided. TR1 48 months
9.15.m Although there are 5 total toilet stalls, there is no accessible stall provided. ST15, TR16 48 months
9.15.n There is no accessible shower provided. B8, TR16 48 months
9.16 Fountains outside locker rooms, and inside men's and women's locker rooms
9.16.a The drinking fountains each have a spout that is 37 inches above the finished floor. DF6 48 months
9.16.b Each drinking fountain protrudes 28 inches into the walkway and would not be detectable to a blind person using a cane. AR8 48 months
10 Mental Health – 751 Twinbrook Parkway Building, 751 Twinbrook Parkway, Rockville, MD 20851
10.1 Mental Health Center - Entrance
10.1.a There is a 1 inch threshold at the exterior door. D23 60 months
10.1.b The automatic door opener railing protrudes into the walkway and would not be detectable to a blind person using a cane. AR8 60 months
10.2 Telephone at Mental Health Entrance - The telephone is inaccessible because the coin slot is 55 inches from the finished floor. TT1 60 months
10.3 Outpatient Mental Health Center
10.3.a The outpatient Mental Health Center is inaccessible because the pressure required to open the door is 8 pounds. D2 60 months
10.3.b There is a 3/4 inch threshold at the door. D23 60 months
10.4 Elevator - Near Substance Abuse Entrance and Mental Health - The elevator car does not automatically level itself within ½ inch. AR2, E1, E2 60 months
10.5 Counter - 2nd Floor Lobby - The counter protrudes 10 ¾ inches, its leading edge 32 inches above the finished floor, into the walkway and would not be detectable to a blind person using a cane. AR8 60 months
10.6 Substance Abuse - Room 238 Computer Lab
10.6.a The substance abuse room is inaccessible because the pressure required to open the door is 10 pounds. D2 60 months
10.6.b The door is inaccessible because knob hardware is used. D1 60 months
10.6.c The pull side of the door to the lab, which is accessed through a front approach, is inaccessible because it has inadequate maneuvering clearance. D6 60 months
10.6.d The push side of the door to the lab, which is accessed through a front approach and which has both a closer and a latch, is inaccessible because it has inadequate maneuvering clearance. D7 60 months
10.6.e The computer counter is inaccessible because the bottom edge of the counter is 25 ¼ inches above the finished floor, and the clear floor space is only 24 ½ inches wide. C6 60 months
10.7 Methadone Area - The door is inaccessible because knob hardware is used. D1 60 months
10.8 Rooms 294 and 292 (and all other offices open to the public under these programs) - The doors are inaccessible because knob hardware is used. D1 60 months
10.9 Room 206 (typical of the 15 group rooms)
10.9.a This room is inaccessible because the pressure required to open the door is greater than 7 pounds. D2 60 months
10.9.b The door is inaccessible because knob hardware is used. D1 60 months
10.9.c The pull side of the door to the lab, which is accessed through a front approach, is inaccessible because it has 2 ½ maneuvering clearance on the latch side. D6 60 months
10.10 Men's Lounge - 2nd Floor Main Hall
10.10.a The men's lounge is inaccessible because the pressure required to open the door is 21 pounds. D2 60 months
10.10.b The door is inaccessible because knob hardware is used. D1 60 months
10.10.c The pull side of the door to the lab, which is accessed through a front approach, is inaccessible because it has 2 ½ maneuvering clearance on the latch side. D6 60 months
10.11 Kitchen - 2nd Floor Main Hall
10.11.a The door is inaccessible because knob hardware is used. D1 60 months
10.11.b The pull side of the door to the lab, which is accessed through a front approach, is inaccessible because it has 2 ½ maneuvering clearance on the latch side. D6 60 months
10.11.c The serving counter is inaccessible because it is 43 inches above the finished floor. C6 60 months
10.11.d The route to the serving counter is inaccessible because the route narrows to 30 inches wide at the "island." AR3 60 months
10.11.e The towel dispenser is inaccessible because the controls are mounted 55 inches above the finished floor. TR5 60 months
10.12 Lunch Room - 2nd Floor Main Hall
10.12.a The lunch room is inaccessible because the pressure required to open the door is 7 pounds. D2 60 months
10.12.b The door is inaccessible because knob hardware is used. D1 60 months
10.12.c The pull side of the door to the lab, which is accessed through a front approach, is inaccessible because it has 2 ½ maneuvering clearance on the latch side. D6 60 months
10.13 Accessible Route from Security Desk to Main Reception
10.13.a The security mirror protrudes into the walkway at 72 inches above the finished floor and would not be detectable to a blind person using a cane. AR8 60 months
10.13.b The main counter is inaccessible because it is higher than 36 inches above the finished floor. C6 60 months
10.13.c The main desk protrudes 5 ½ inches with its leading edge 40 ½ above the finished floor into the walkway and would not be detectable to a blind person using a cane. AR8 60 months
10.14 Women's Toilet - 2nd Floor Near Elevator - Stalls
10.14.a There is no accessible room sign. TR17 60 months
10.14.b The door is inaccessible because it has an opening width of only 29 inches. D25 60 months
10.14.c The women's toilet room is inaccessible because the pressure required to open the door is 11 pounds. D2 60 months
10.14.d The door is inaccessible because knob hardware is used. D1 60 months
10.14.e The toilet room contains a number of inaccessible elements and is not accessible to people with disabilities. ST14 60 months
10.15 Men's Toilet Room - 2nd Floor Near Elevator - Stalls
10.15.a There is no toilet room sign. TR17 60 months
10.15.b The door is inaccessible because it has an opening width of only 29 inches. D25 60 months
10.15.c The men's toilet room is inaccessible because the pressure required to open the door is 12 pounds. D2 60 months
10.15.d The door is inaccessible because knob hardware is used. D1 60 months
10.15.e The toilet room contains a number of inaccessible elements and is not accessible to people with disabilities. ST14 60 months
10.16 Telephone - 2nd Floor Across from Toilet Rooms - The telephone protrudes into the walkway and would not be detectable to a blind person using a cane. AR8 60 months
10.17 Drinking Fountain - 2nd Floor Across from Toilet Rooms - Although an accessible drinking fountain is provided, there is no drinking fountain provided for people who have difficulty bending or stooping. DF3 60 months
10.18 Accessible Route from Substance Abuse to CORE - The route from Substance Abuse to CORE is inaccessible because there is a cross slope up to 3 %. AR1, AR2 60 months
10.19 Room Signage throughout CORE facility - There is no compliant permanent room signage for permanent room information (e.g., room numbers). D26 60 months
10.20 Accessible Route to CORE Toilet Rooms - The route to the CORE toilet rooms is not accessible because the hallway narrows to 35 ½ inches wide. AR3 60 months
10.21 Women's Toilet Rooms - 1st Floor - Stalls
10.21.a The toilet room lacks accessible signage because the sign is mounted on the door. TR17 60 months
10.21.b The women's toilet room is inaccessible because the pressure required to open the door is 10 pounds. D2 60 months
10.21.c No accessible mirror has been provided. TR14 60 months
10.21.d The towel dispenser is inaccessible because the controls are mounted 58 inches above the finished floor. TR5 60 months
10.21.e The lavatory is inaccessible because the hot water pipes are not insulated or otherwise configured to protect against contact. TR12 60 months
10.21.f The lavatory is inaccessible because twist-type hardware used to operate the faucet. TR10 60 months
10.21.g The stall door is inaccessible because the hardware requires tight grasping to operate. ST14 60 months
10.21.h The toilet is inaccessible because its centerline measures 24 inches from the side wall. ST17 60 months
10.21.i No accessible coat hook has been provided. TR1 60 months
10.21.j The toilet paper dispenser is inaccessible because it is 17 inches above the finished floor. ST19 60 months
10.21.k The side grab bar at the toilet is inaccessible because it is mounted 32 inches above the finished floor. ST12 60 months
10.21.l The rear grab bar is inaccessible because it is 30 inches long, its end is 10 inches from the side wall, and the flush control interferes with its usage. ST3 60 months
10.21.m The rear grab bar does not have the structural strength to support 250 pounds. Provide a rear grab bar that provides adequate structural strength. Standards § 4.26.3. ST11 60 months
10.22 Men's Toilet Room - 1st Floor - Stalls
10.22.a The toilet room lacks accessible signage because the sign is on the door. TR17 60 months
10.22.b The men's toilet room is inaccessible because the pressure required to open the door is 12 pounds. D2 60 months
10.22.c No accessible mirror has been provided. TR14 60 months
10.22.d The towel dispenser is inaccessible because the controls are mounted 58 inches above the finished floor. TR5 60 months
10.22.e The lavatory is inaccessible because it does not allow adequate knee or toe clearances. TR11 60 months
10.22.f The lavatory is inaccessible because twist-type hardware used to operate the faucet. TR10 60 months
10.22.g The urinal is inaccessible because the rim is 22 ½ inches above the finished floor, it allows only 27 inches by 48 inches of clear floor space, and the flush control is 50 inches above the finished floor. TR20 60 months
10.22.h The stall door is inaccessible because the hardware requires tight grasping to operate. ST14 60 months
10.22.i The toilet is inaccessible because its centerline measures 24 inches from the side wall. ST17 60 months
10.22.j The toilet is inaccessible because the flush control is on the closed side. ST2 60 months
10.22.k No accessible coat hook has been provided. TR1 60 months
10.22.l The side grab bar at the toilet is inaccessible because it is 32 inches above the finished floor. ST12 60 months
10.22.m The rear grab bar at the toilet is inaccessible because it is 30 inches long and its end is 10 ½ inches from the side wall. ST11 60 months
10.22.n The rear grab bar at the toilet is inaccessible because the flush control interferes with its usage. ST5 60 months
10.23 Interior Door at CORE - hallway adjacent to toilet room
10.23.a The door is inaccessible because it has only 6 ½ inches of maneuvering space on the latch side. D6 60 months
10.23.b The push side of the door is inaccessible because it has only 6 inches of maneuvering space. D7 60 months
10.23.c The door is inaccessible because knob hardware is used. D1 60 months
10.24 Overflow Room - The computers are inaccessible because the table on which they are placed has a knee clearance that is 26 ½ inches from the finished floor and is 28 inches wide. T1 60 months
10.25 CORE exterior entrance
10.25.a There is a 1 ¼ inch threshold at the door. D23 60 months
10.25.b The entrance door is locked, and visitors are required to operate a doorbell in order to gain admittance. The doorbell is located at 56 inches above the finished floor and requires a forward reach. D14 60 months
11 2nd District Police Station – Bethesda, 7359 Wisconsin Avenue, Bethesda, Maryland 20814
11.1 East West Highway Main Entrance
11.1.a The route from the street to the main entrance is inaccessible because the slope of the first corner curb ramp is 9.1% and the slope of the second corner curb ramp is 14.2%. AR5 60 months
11.1.b The ramp next to the main entrance is inaccessible because no edge protection is provided. R1 60 months
11.1.c The route to the main entrance is inaccessible because the top landing at the ramp slopes 5%, there is only a handrail on one side, and the existing handrail is only 32 inches from the finished floor of the ramp and does not have 12 inch extensions at the bottom. R3 60 months
11.2 Lobby - The finger printing counter is inaccessible because it is 43 ½ inches above the finished floor. C6 60 months
11.3 Telephone - The telephone is inaccessible because there is no volume control. TT1 60 months
11.4 Men's Lobby Toilet Room with Stalls
11.4.a The toilet room lacks accessible signage because the sign is mounted on the door and has no Braille or raised lettering. TR17 60 months
11.4.b The pressure required to open the doors is 9 pounds. D2 60 months
11.4.c The push side of the door, which is accessed from the latch side of the door, is inaccessible because it has only 3 inches of maneuvering space. D11 60 months
11.4.d The seat cover dispenser is inaccessible because the seat covers are 60 inches above the finished floor. TR4 60 months
11.4.e The towel dispenser is inaccessible because the controls are mounted 55 inches above the finished floor. TR5 60 months
11.4.f The lavatory is inaccessible because the hot water pipes are not insulated or otherwise configured to protect against contact. TR12 60 months
11.4.g The urinal is inaccessible because the rim is 25 inches above the finished floor. TR20 60 months
11.4.h The toilet is inaccessible because the flush control is on the closed side. ST2 60 months
11.4.i No accessible coat hook has been provided. TR1 60 months
11.4.j The stall door is inaccessible because the hardware requires twisting to operate. ST14 60 months
11.5 Women's Lobby Toilet Room with Stalls
11.5.a The toilet room lacks accessible signage because the sign is mounted on the door and has no Braille or raised characters. TR17 60 months
11.5.b The pressure required to open the doors is 8 pounds. D2 60 months
11.5.c The seat cover dispenser is inaccessible because the seat covers are 56 inches above the finished floor. TR4 60 months
11.5.d The sanitary napkin dispenser is inaccessible because the controls are mounted at 67 ½ inches above the finished floor. TR5 60 months
11.5.e The lavatory is inaccessible because the hot water pipes are not insulated or otherwise configured to protect against contact. TR12 60 months
11.5.f The toilet is inaccessible because the flush control is on the closed side. ST2 60 months
11.5.g No accessible coat hook has been provided. TR1 60 months
11.5.h The stall door is inaccessible because the hardware requires twisting to operate. ST14 60 months
12 Leland Community Center, 4301 Willow Lane, Chevy Chase, Maryland 20815
12.1 Parking - The parking lot is inaccessible because, although there are three parking spaces designated as accessible, four parking spaces are required to be accessible (with at least one being van-accessible), one space has only a 33 inch wide access aisle, and none of the spaces have vertical signage designated the space as accessible none are designated as being accessible for persons with disabilities. P3 24 months
12.2 Parking Lot Entrance - The route from the parking area to the entrance is inaccessible because the curb ramp has a 16.5% slope and a 3.5% cross slope. AR5 24 months
12.3 Exterior Bench - There is no accessible route to the fixed bench outside the Community Center. AR1 24 months
12.4 Men's Locker Room
12.4.a The toilet room lacks accessible signage because it is not mounted on the latch side of the door, its centerline is higher than 60 inches above the finish floor and it has no braille or raised characters. TR17 24 months
12.4.b The pressure required to open the doors is 14 pounds. D2 24 months
12.4.c The air dryer is inaccessible because the controls are 65 inches above the finished floor. TR5 24 months
12.4.d The air dryer protrudes into the walkway and would not be detectable to a blind person using a cane. AR8 24 months
12.4.e The soap dispenser is inaccessible because the controls are mounted at 53 inches above the finished floor over the lavatory, and a front reach is required. TR4 24 months
12.4.f The lavatory is inaccessible because the bottom edge of the apron measures 28 inches above the finished floor. TR11 24 months
12.4.g The lavatory is inaccessible because the hot water pipes are not insulated or otherwise configured to protect against contact. TR12 24 months
12.4.h The urinal is inaccessible because the rim is 25 inches above the finished floor, it allows only 27 inches by 48 inches of clear floor space, and the flush control is 49 inches above the finished floor. TR20 24 months
12.4.i The toilet is inaccessible because the flush control is on the closed side. ST2 24 months
12.4.j The side grab bar is inaccessible because the toilet paper dispenser is mounted less than 18 inches above it. ST9 24 months
12.4.k The rear grab bar is inaccessible because it is not a continuous grab bar that is 36 inches long, but two shorter grab bars with a gap in the middle. ST3 24 months
12.4.l The shower is inaccessible because the seat does not extend to the full depth of the stall, the shower spray unit is fixed at 73 inches above the shower floor, and the curb to the shower stall is 3 inches high. B8 24 months
12.4.m The shower hook is inaccessible because it is mounted 71 inches above the finished floor. TR1 24 months
12.4.n The bench is 10 ½ inches deep. L1 24 months
12.5 Women's Locker Room
12.5.a The toilet room lacks accessible signage because it is not mounted on the latch side of the door, its centerline is higher than 60 inches above the finish floor and it has no braille or raised characters. TR17 24 months
12.5.b The pressure required to open the doors is 12 pounds. D2 24 months
12.5.c The air dryer is inaccessible because the controls are mounted 63 inches above the finished floor. TR5 24 months
12.5.d The air dryer protrudes into the walkway and would not be detectable to a blind person using a cane. AR8 24 months
12.5.e The lavatory is inaccessible because the bottom edge of the apron is mounted 28 inches above the finished floor. TR11 24 months
12.5.f The lavatory is inaccessible because the hot water pipes are not insulated or otherwise configured to protect against contact. TR12 24 months
12.5.g The toilet is inaccessible because the top of the seat is 20 inches above the finished floor. ST20 24 months
12.5.h The toilet is inaccessible because its centerline measures 16 inches from the side wall. ST17 24 months
12.5.i The side grab bar is inaccessible because the toilet paper dispenser is mounted less than 18 inches above it. ST9 24 months
12.5.j The rear grab bar is inaccessible because it is not a continuous grab bar that is 36 inches long, but two shorter grab bars with a gap in the middle. ST3 24 months
12.5.k The shower is inaccessible because the seat does not extend to the full depth of the stall, the shower spray unit is fixed 73 inches above the shower floor, and the curb to the shower is 3 inches high. B8 24 months
12.5.l The shower hook is inaccessible because it is mounted 71 inches above the finished floor. TR1 24 months
12.5.m The bench is 10 ½ inches deep. L1 24 months
12.6 Women's Lobby Toilet Room with Stalls
12.6.a The toilet room lacks accessible signage because it is mounted on the door. TR17 24 months
12.6.b The pressure required to open the doors is 15 pounds. D2 24 months
12.6.c The lavatory is inaccessible because the bottom edge of the apron is mounted 28 inches above the finished floor. TR11 24 months
12.6.d The lavatory is inaccessible because the hot water pipes are not insulated or otherwise configured to protect against contact. TR12 24 months
12.6.e The toilet is inaccessible because the flush control is on the closed side. ST2 24 months
12.6.f No accessible coat hook has been provided. TR1 24 months
12.6.g The side grab bar is inaccessible because the toilet paper dispenser is mounted less than 18 inches above it. ST9 24 months
12.6.h The rear grab bar is inaccessible because it is not a continuous grab bar that is 36 inches long, but two shorter grab bars with a gap in the middle. ST3 24 months
12.7 Men's Lobby Toilet Room with Stalls
12.7.a The toilet room lacks accessible signage because it is mounted on the door. TR17 24 months
12.7.b The pressure required to open the doors is 19 pounds. D2 24 months
12.7.c The lavatory is inaccessible because the bottom edge of the apron is mounted 28 inches above the finished floor. TR11 24 months
12.7.d The lavatory is inaccessible because the hot water pipes are not insulated or otherwise configured to protect against contact. TR12 24 months
12.7.e The urinal is inaccessible because the rim is 25 inches above the finished floor, and the flush control is 51 inches above the finished floor. TR20 24 months
12.7.f The stall door is inaccessible because the hardware requires twisting to operate. ST14 24 months
12.7.g The side grab bar is inaccessible because the toilet paper dispenser is mounted less than 18 inches above it. ST9 24 months
12.7.h The rear grab bar is inaccessible because it is not a continuous grab bar that is 36 inches long, but two shorter grab bars with a gap in the middle. ST3 24 months
13 Chevy Chase Library, 8005 Connecticut Avenue, Chevy Chase, Maryland 20815
13.1 Parking - The parking lot, with a total of approximately 103 parking spaces, is inaccessible because only 2 are designated as being accessible for persons with disabilities, there is no designated van-accessible space, and the access aisles are only 53 inches wide. This lot requires 1 van accessible space and a total of 4 standard accessible spaces. P3 48 months
13.2 Route to Entrance
13.2.a The route from the street to the sidewalk leading to a ramp is inaccessible because the curb ramp has a slope of 13.1% and a cross slope of 3.8%. AR5 48 months
13.2.b The route to the entrance is inaccessible because the ramp has a slope of 10% at the top and 12.8% at the bottom, and the handrails have no extensions at the bottom. AR1, R4 48 months
13.3 Telephone
13.3.a The telephone is inaccessible because there is no volume control. TT1 48 months
13.3.b The route to the telephone is obstructed by the display/brochure racks. AR2, AR3 48 months
13.4 Elevator Near Ramp Entrance
13.4.a The elevator is inaccessible because, after notification, the doors start to close in 4 seconds. E6 48 months
13.4.b The elevator is inaccessible because, although emergency communications are provided, the door to access the system requires tight pinching to operate. E8 48 months
13.5 Men's Lower Level Toilet Room with Stalls
13.5.a The toilet room lacks accessible signage because it is not mounted on the latch side of the door, its centerline is higher than 60 inches above the finish floor and it has no Braille or raised characters. TR17, TR16, TR22 48 months
13.5.b The pressure required to open the doors is 11 pounds. D2 48 months
13.5.c The light switch is inaccessible because it is 55 inches above the finished floor. TR5, TR16, TR22 48 months
13.5.d The lavatory is inaccessible because the bottom edge of the apron is mounted 27 inches above the finished floor. TR11, TR16, TR22 48 months
13.5.e The urinal is inaccessible because the flush control is 54 inches above the finished floor. TR20, TR16, TR22 48 months
13.5.f There is no standard accessible stall provided. ST15, TR16, TR22 48 months
13.6 Women's Lower Level Toilet Room with Stalls
13.6.a The toilet room sign is inaccessible because it is mounted on the door and has no raised characters or Braille. TR17, TR16 48 months
13.6.b The door is inaccessible because it has an opening width of only 31 inches. D25, TR16, TR22 48 months
13.6.c The pressure required to open the doors is 11 pounds. D2 48 months
13.6.d The light switch is inaccessible because it is 55 inches above the finished floor. TR5, TR16, TR22 48 months
13.6.e The lavatory is inaccessible because the bottom edge of the apron is mounted 27 inches above the finished floor. TR11, TR16, TR22 48 months
13.6.f There is no standard accessible stall provided. ST15, TR16, TR22 48 months
13.7 Lower Level Drinking Fountain
13.7.a The drinking fountain has a spout that is 38 inches above the finished floor. DF6 48 months
13.7.b Although drinking fountains are provided, there is no accessible drinking fountain because the water flow is four inches from the front of the fountain. DF7 48 months
13.8 Check-Out Counter - The route to the check-out counter is not accessible because it is blocked by the book cart. AR2 48 months
14 Silver Spring Library, 8901 Colesville Road, Silver Spring, Maryland 20910
14.1 Parking - The parking lot is inaccessible because there is no designated van-accessible space and the existing spaces and access aisles slope 5.3% to 7.8%. This lot requires 1 van accessible space. P3 60 months
14.2 Main Entrance - The route from the parking area to the main entrance is inaccessible because it has a cross slope of 3.1%. AR1 60 months
14.3 Basement Entrance
14.3.a The route on the sidewalk to the basement entrance is inaccessible because it has slope of 7.9% near the entrance and 9.8% at the parking area, with no ramp features at either. AR1 60 months
14.3.b The curb ramp at the basement entrance slopes 10.6% and has an abrupt ½ inch edge. AR5 60 months
14.4 Magazine Displays - The magazine displays are inaccessible because their reach ranges are between 10 and 65 ½ inches. L1 60 months
14.5 Stacks - The book stacks are inaccessible because the space between stacks is between 34 ½ to 35 inches wide. L5 60 months
14.6 Drinking Fountains
14.6.a The upstairs drinking fountain is inaccessible because it provides only a 26-inch high knee clearance. DF5 60 months
14.6.b The drinking fountain in the basement has a spout that is 41 inches above the finished floor. DF6 60 months
14.6.c Although two drinking fountains are provided, there is no higher fountain on the main floor and no lower fountain in the basement. DF1 60 months
14.7 Main Floor Single-User Unisex Toilet Room
14.7.a The toilet room sign is inaccessible because it is mounted on the door and has no raised or Braille characters. TR17 60 months
14.7.b The pressure required to open the doors is 12 pounds. D2 60 months
14.7.c The door is inaccessible because knob hardware is used. D1 60 months
14.7.d The toilet is inaccessible because its centerline measures 24 inches from the side wall. SU15 60 months
14.7.e The toilet is inaccessible because the flush control is on the closed side. SU1 60 months
14.7.f The side grab bar at the toilet is inaccessible because it is 36 inches long and the far end is 40 inches from the rear wall. SU5 60 months
14.7.g The rear grab bar at the toilet is inaccessible because it is 24 inches long and the toilet pipes interfere with its usage. SU2 60 months
14.8 Elevator in Reference Section
14.8.a The elevator is inaccessible because a rack projects 12 inches below the hall call buttons. AR8, E3 60 months
14.8.b The elevator is inaccessible because after notification, the doors start to close within 4 seconds. E6 60 months
14.8.c The elevator is inaccessible because the emergency communications system is not identified by a raised symbol and lettering and the door to the emergency communications controls requires tight grasping to open. E4, E8 60 months
14.9 Women's Basement Toilet Room with Stalls
14.9.a The toilet room sign is inaccessible because it is mounted on the door and has no raised characters or braille. TR17 60 months
14.9.b The pressure required to open the doors is 14 pounds. D2 60 months
14.9.c The door is inaccessible because knob hardware is used. D1 60 months
14.9.d The soap dispenser is inaccessible because the controls are mounted 49 inches above the finished floor and 11 inches over an obstruction. TR4 60 months
14.9.e The sanitary napkin dispenser is inaccessible because it has knob hardware. TR3 60 months
14.9.f The lavatory is inaccessible because it has insufficient knee clearance. TR11 60 months
14.9.g The lavatory is inaccessible because the hot water pipes are not insulated or otherwise configured to protect against contact. TR12 60 months
14.9.h The lavatory is inaccessible because the clear floor space is 29 ½ inches wide. TR8 60 months
14.9.i The toilet is inaccessible because its centerline measures 17 inches from the side wall. ST17 60 months
14.9.j The toilet is inaccessible because the flush control is on the closed side. ST2 60 months
14.9.k No accessible coat hook has been provided. TR1 60 months
14.9.l The side grab bar is inaccessible because the toilet paper dispenser is mounted less than 18 inches above it. ST9 60 months
14.9.m The side grab bar at the toilet is inaccessible because it is 36 inches long and its far end is 40 inches from the rear wall. ST6 60 months
14.9.n The rear grab bar at the toilet is inaccessible because the toilet flush control obstructs its use. ST5 60 months
14.10 Men's Basement Toilet Room with Stalls
14.10.a The toilet room sign is inaccessible because it is mounted on the door and has no raised characters or braille. TR17 60 months
14.10.b The pressure required to open the doors is 11 pounds. D2 60 months
14.10.c The door is inaccessible because knob hardware is used. D1 60 months
14.10.d The lavatory is inaccessible because it has insufficient knee clearance. TR11 60 months
14.10.e The lavatory is inaccessible because the hot water pipes are not insulated or otherwise configured to protect against contact. TR12 60 months
14.10.f The urinal is inaccessible because the rim is 24 inches above the finished floor, and the flush control is 50 inches above the finished floor. TR20 60 months
14.10.g The designated accessible toilet stall is inaccessible because the clear floor space at the toilet is 58 inches deep. ST18 60 months
14.10.h The toilet is inaccessible because the top of the seat is 20 inches above the finished floor. ST20 60 months
14.10.i The toilet is inaccessible because its centerline measures 17 inches from the side wall. ST17 60 months
14.10.j No accessible coat hook has been provided. TR1 60 months
14.10.k The side grab bar at the toilet is inaccessible because it is 36 inches long and its far end is 40 inches from the rear wall. ST6 60 months
14.10.l The rear grab bar at the toilet is inaccessible because the toilet flush control obstructs its use. ST5 60 months
15 Plum Gar Community Center, 19561 Scenery Drive, Germantown, Maryland 20874
15.1 Parking
15.1.a The parking lot is inaccessible because there is no van accessible space. This lot requires 1 van accessible space. P3 60 months
15.1.b The route from the parking area to the main building is inaccessible because there are no detectable warnings on the curb ramp. AR5 60 months
15.2 Main Building Telephone - The telephone is inaccessible because the clear floor space is blocked by trash and recycling cans, the highest operable part (coin slot) is 57 inches above the finished floor, and there is no volume control. TT1 60 months
15.3 Main Building Men's Single-User Toilet Room
15.3.a The toilet room sign is inaccessible because it is mounted on the door. TR17 60 months
15.3.b The pressure required to open the doors is 13 pounds. D2 60 months
15.3.c The pull side of the door to the toilet room, which is accessed through a front approach, is inaccessible because it has only 3 inches maneuvering clearance on the latch side. D6 60 months
15.3.d No accessible coat hook has been provided. TR1 60 months
15.3.e No accessible mirror has been provided. TR14 60 months
15.3.f The air dryer protrudes into the walkway and would not be detectable to a blind person using a cane. AR8 60 months
15.3.g The urinal is inaccessible because the rim is 18 inches above the finished floor. TR20 60 months
15.3.h The toilet is inaccessible because there is insufficient clear floor space due to the urinal screen. SU16 60 months
15.3.i The toilet is inaccessible because its centerline measures 17 ½ inches from the side wall. SU15 60 months
15.3.j The toilet is inaccessible because the flush control is on the closed side. SU1 60 months
15.3.k The side grab bar at the toilet is inaccessible because its far end is mounted 48 inches from the side wall. SU6 60 months
15.4 Main Building Women's Single-User Toilet Room
15.4.a The toilet room sign is inaccessible because it is mounted on the door. TR17 60 months
15.4.b The pressure required to open the doors is 20 pounds. D2 60 months
15.4.c No accessible coat hook has been provided. TR1 60 months
15.4.d No accessible mirror has been provided. TR14 60 months
15.4.e The soap dispenser is inaccessible because the controls are mounted 49 ¾ inches above the finished floor and a forward reach is required. TR4 60 months
15.4.f The air dryer protrudes 7½ inches with its leading edge 39 ¼ inches above the finished floor into the walkway and would not be detectable to a blind person using a cane. AR8 60 months
15.4.g The toilet is inaccessible because its centerline measures 18 ½ inches from the side wall. SU15 60 months
15.4.h The side grab bar at the toilet is inaccessible because its far end is 48 inches from the rear wall. SU6 60 months
15.5 Main Building Lobby
15.5.a Although an accessible drinking fountain is provided, there is no drinking fountain provided for people who have difficulty bending or stooping. DF3 60 months
15.5.b The counter is inaccessible because it is 42 inches above the finished floor. C6 60 months
15.6 Main Building Meeting Room Kitchen
15.6.a The door is inaccessible because knob hardware is used. D1 60 months
15.6.b The microwave is inaccessible because the highest operable part is 56 ½ inches high. TR5 60 months
15.7 Main Building Gym - There is a 1 inch threshold at the door. D23 60 months
15.8 Trailer Entrance
15.8.a The route to the trailer entrance is inaccessible because the ramp has no handrails or handrail extensions at the very bottom of the ramp, and the slope near the top of the ramp is 9%. R3, R4 60 months
15.8.b The building is inaccessible because there is no signage at the accessible entrance. D16 60 months
15.8.c There is a 3/4 inch threshold at the door. D23 60 months
15.9 Trailer Conference Room - The trailer conference room is inaccessible to people with hearing impairments because there is no signage indicating the availability of an assistive listening system. AA3 60 months
15.10 Trailer Unisex Single-User Toilet Room
15.10.a The door is inaccessible because knob hardware is used. D1 60 months
15.10.b No accessible coat hook has been provided. TR1 60 months
15.10.c The side grab bar at the toilet is inaccessible because it is 38 inches long and the far end is 50 inches from the rear wall. SU10 60 months
15.10.d The rear grab bar at the toilet is inaccessible because it is 33 inches long. SU3 60 months
15.11 Exterior routes of travel
15.11.a The route from the parking area to the basketball court slopes up to 16.8%. AR1 60 months
15.11.b The routes to the front and rear playgrounds are inaccessible because, at each, the route is not firm, stable and slip-resistant, and, at each, the route to one piece of equipment is obstructed by a 4 inch by 4 inch board. AR1 60 months
15.11.c The route from the parking area to the baseball field is inaccessible because it is down a steep, grassy hill. AR1 60 months
16 Pre-Release Center, 11651 Nebel Street, Rockville, Maryland 20852
16.1 Parking
16.1.a The parking reserved for persons with disabilities is inaccessible because at least one accessible parking space slopes 2.8%. P7 48 months
16.1.b The route at the curb ramp is inaccessible because there are no detectable warnings. AR5 48 months
16.2 Courtyard
16.2.a The route from each of the four living units to the courtyard is inaccessible because of a step at each of these living units.

AR1, AR9

48 months
16.2.b There are no accessible tables in the courtyard. T1 48 months
16.3 Exterior Accessible Route
16.3.a The route from the accessible parking spaces to the entrance slopes 8.7% over a 5 foot length, and a 15 foot length has cross-slope of 3.4%. AR1 48 months
16.3.b The main sidewalk from the designated accessible parking spaces to the main entrance is inaccessible because it slopes 6.6% and does not include ramp features. AR1, R3 48 months
16.3.c The curb ramp next to the accessible parking spaces slopes 10.9%. AR5 48 months
16.3.d The sidewalk to the classroom trailer slopes more than 5% for 15 foot length and has no ramp features. AR1 48 months
16.4 Entrance - There is a 11/4 inch threshold at the door. D23 48 months
16.5 Interior Signs - Throughout the facility, signage is mounted on doors and has no raised characters or Braille. D26 48 months
16.6 Alarms
16.6.a Although an audible alarm is provided in this facility, there are no visual alarms. TR21 48 months
16.7 Front Lobby Telephone - The telephone is inaccessible because the clear floor space is only 28 inches wide, the highest operable part (coin slot) is 54½ inches above the finished floor - forward reach required, and it has no volume control. TT1 48 months
16.8 Interior Accessible Route
16.8.a Nearly all collection boxes and counters throughout the facility protrude into the walkway and would not be detectable to a blind person using a cane. AR8 48 months
16.8.b The main lobby mailbox protrudes 6½ inches, with its leading edge 49 inches above the finished floor, into the walkway and would not be detectable to a blind person using a cane. AR8 48 months
16.8.c The Unit 2 mirror protrudes into the walkway and would not be detectable to a blind person using a cane. AR8 48 months
16.8.d The route leading near the underside of the stairway in Unit 2 is inaccessible because there is decreased headroom. AR7 48 months
16.9 Doors - The doors throughout the facility are inaccessible because knob hardware is used. D1 48 months
16.10 Front Lobby Counter - The counter is inaccessible because it is 42 ½ inches above the finished floor. C6 48 months
16.11 Ramp - Front Lobby
16.11.a The front lobby ramp is inaccessible because it slopes 12%. In addition, the handrails are not stable, are not of the correct diameter or distance from the wall, the ends of the handrails are not rounded or return to the floor, and there are no 12 inch extensions at the top of bottom of the handrails. R3 48 months
16.11.b The ramp is inaccessible because it does not have edge protection along the entire length of the ramp. R1 48 months
16.12 Ramp -The ramp from the dining room to the lobby is inaccessible because it has no handrails and slopes 8.6%. R4, R5 48 months
16.13 Ramp - The ramp to unit 4 is inaccessible because it is only 32 inches wide, and the handrail is not continuous at the fire extinguisher. R3, R4 48 months
16.14 Ramp - The exit ramp from the main building to the classroom trailer is inaccessible because it has no handrails. R4 48 months
16.15 Ramp - The ramp to the classroom trailer is inaccessible because it has a sudden rise at the bottom, and the handrails have no level extensions at the bottom. R3, R4 48 months
16.16 Lobby Drinking Fountain - The drinking fountain in the lobby protrudes 19 inches, with its leading edge 28 inches above the finished floor, into the walkway and would not be detectable to a blind person using a cane. AR8 48 months
16.17 Main lobby toilet rooms - There is no signage directing people with disabilities to the accessible toilet rooms. TR16 48 months
16.18 Bedrooms - Although there are a total of 90 bedrooms, only one bedroom is designated as accessible. Provide a total of 4 bedrooms accessible to people with mobility disabilities. AR2, H6 48 months
16.19 Bedroom 104
16.19.a The bedroom sign is inaccessible because it is mounted on the door. D26 48 months
16.19.b The desk is inaccessible because it has 23 inches of knee space width. T1 48 months
16.20 Bedroom 104 Toilet Room
16.20.a The door is inaccessible because knob hardware is used. D1 48 months
16.20.b The door to the toilet room, which is accessed from the front, is inaccessible because it has only 10 inches of maneuvering space on the latch side, with 32 ½ inches of maneuvering depth. D7 48 months
16.20.c No accessible mirror has been provided. TR14 48 months
16.20.d There is insufficient turning space within the toilet room. TR19 48 months
16.20.e The toilet is inaccessible because its centerline measures 15 inches from the side wall. SU15 48 months
16.20.f The side grab bar at the toilet is inaccessible because it is 25 inches long the far end is 25 inches from the rear wall, and the space between the grab bar and the wall is 3 inches. SU5 48 months
16.20.g The rear grab bar at the toilet is inaccessible because it is 24 inches long and the space between the grab bar and the wall is 5 ½ inches. SU5 48 months
16.20.h The shower in is inaccessible because the transfer shower is 44 inches wide by 33 inches deep; there is inadequate clear floor space outside the shower; the seat provided is 21 inches high; there is a grab bar only on one wall; and there is a ¾ inch curb. B8 48 months
17 Avery Road Facility, 703 Avery Road
17.1 Interior doors used by the public throughout the facility
17.1.a The doors used by the public throughout the facility (i.e., cafeteria entrance / exit doors; fire exit doors; doors leading to Rooms 22, 35, and 37; and other doors) are inaccessible because knob hardware is used. D1 60 months
17.1.b Some offices have permanent room signage that are inaccessible – e.g., room number signage do not have raised or Braille characters. D26 60 months
17.2 Cafeteria Entrance and Exit Doors - The cafeteria is inaccessible because the pressure required to open both sets of doors are 12 and 15 pounds. D2 60 months
17.3 Cafeteria Food Line - The food service line is inaccessible because the tray counter is 48 inches above the finished floor, and there is a 12 inch reach over to the food. PD2 60 months
17.4 Cafeteria Telephone
17.4.a The telephone is inaccessible because a table obstructs the clear floor space, the knee space is 24 inches wide, and the coin slot is 58 inches above the finished floor. AR2, T1, TT1 60 months
17.4.b The telephone protrudes into the walkway and would not be detectable to a blind person using a cane. AR8 60 months
17.5 Telephone Outside of Cafeteria
17.5.a The telephone is inaccessible because the knee clearance is 15 ½ inches wide, and the coin slot is 55 inches above the finished floor. TT1 60 months
17.5.b The telephone protrudes 10 inches into the walkway and would not be detectable to a blind person using a cane. AR8 60 months
17.6 Drinking Fountain near Staff Toilet Room - The drinking fountain is inaccessible because the water does not flow at least four inches above the drinking fountain surface, and the knee clearance is 29 ½ inches wide and 9 inches deep. In addition, although a lower fountain is provided, there is no drinking fountain provided for people who have difficulty bending or stooping. DF7 60 months
17.7 Nurses Station - The counter is inaccessible because it is 42 ½ inches above the finished floor. C6 60 months
17.8 Room 48 - The pull side of the door to the room, which is accessed via a front approach, is inaccessible because it has only 9 inches of clear floor space on the latch side. D6 60 months
17.9 Medicine Counter - Room 76
17.9.a The counter is inaccessible because its top surface is 43 inches above the finished floor. C6 60 months
17.9.b The counter protrudes into the walkway and would not be detectable to a blind person using a cane. AR8 60 months
17.9.c The route to the medicine counter is inaccessible because it is only 30 inches wide where the counter obstructs it. AR3 60 months
17.10 Laundry Room - Female - The laundry room is inaccessible because the pressure required to open the door is 10 pounds. D2 60 months
17.11 Laundry Room - Male - The laundry room is inaccessible because the pressure required to open the door is 10 pounds. D2 60 months
17.12 Accessible transient rooms for both genders - The rooms used for temporary lodging / shelter by both genders are inaccessible because there is no telephone notification provided for persons with hearing impairments. H11 60 months
17.13 Room 44 - Accessible Room for Women
17.13.a The route within this room is inaccessible because there is only 25 ½ inches of space between the beds and, therefore, the route does not accessibly connect all accessible elements. AR3 60 months
17.13.b The temperature controls (thermostat) is inaccessible because the controls require twisting. MC1, GC1 60 months
17.13.c Although an audible alarm is provided in this facility, there is no visual alarm appliance in this room. TR21 60 months
17.13.d The shower hose is inaccessible because the shower hose is 57 inches long. B11 60 months
17.13.e The bathtub is inaccessible because the single grab bar above the controls is only 19 inches long. B4, B5 60 months
17.13.f The push side of a door leading from the toilet room and which is accessed through a front approach, is inaccessible because it has only 8 inches of maneuvering space on the latch side. D7 60 months
17.13.g Although an audible alarm is provided in this facility, there is no visual alarm appliance in the toilet room. TR21 60 months
17.13.h The lavatory is inaccessible because the hot water pipes are not insulated or otherwise configured to protect against contact. TR12 60 months
17.13.i The toilet is inaccessible because the top of the seat is 19 ½ inches above the finished floor. SU18 60 months
17.13.j The side grab bar at the toilet is inaccessible because the towel holder is mounted 14½ inches above the grab bar and interferes with its usage. SU8 60 months
17.13.k The rear grab bar at the toilet is inaccessible because it is 30 inches long. SU3 60 months
17.13.l The rear grab bar at the toilet is inaccessible because the toilet flush control interferes with its usage. SU4 60 months
17.14 Room 51 - Men's Accessible Room
17.14.a The desk is inaccessible because it has 23 ½ inches of knee space width and the bottom edge of the desk is 24 inches from the finished floor. T1 60 months
17.14.b The shower is inaccessible because the shower spray unit is broken and the hose is 57 inches long. B8 60 months
17.14.c The temperature controls (thermostat) are inaccessible because the controls require twisting. MC1, GC1 60 months
17.14.d Although an audible alarm is provided in this facility, there is no visual alarm appliance in this room. TR21 60 months
17.14.e The bathtub is inaccessible because the single grab bar over the controls is only 20 inches long. B4, B5 60 months
17.14.f The push side of a door leading from the toilet room and which is accessed through a front approach, is inaccessible because it has only 8 inches of maneuvering space on the latch side. D7 60 months
17.14.g The light switch is inaccessible because it is 55 inches above the finished floor. TR5 60 months
17.14.h Although an audible alarm is provided in this facility, there is no visual alarm appliance in the toilet room. TR21 60 months
17.14.i No accessible mirror has been provided. TR14 60 months
17.14.j The toilet is inaccessible because the flush control is on the closed side. SU1 60 months
17.14.k The side grab bar at the toilet is inaccessible because the towel holder is mounted 14 ½ inches above the grab bar and interferes with its usage. SU4 60 months
17.14.l The rear grab bar at the toilet is inaccessible because it is 30 inches long. SU3 60 months
17.14.m The rear grab bar at the toilet is inaccessible because the toilet flush control interferes with its usage. SU4 60 months
17.15 Telephone Near Lounge
17.15.a The telephone is inaccessible because the coin slot is 54 ½ inches above the finished floor. TT1 60 months
17.15.b The telephone protrudes into the walkway and would not be detectable to a blind person using a cane. AR8 60 months
17.15.c The route through the lounge to the telephones is inaccessible because immovable chairs prevent adequate clear width. AR3 60 months
17.16 Smoke Deck
17.16.a There is a 1¼ inch threshold at the door. D23 60 months
17.16.b There is no accessible seating at the picnic table. PD6 60 months
17.17 Telephone near Smoke Deck
17.17.a The telephone is inaccessible because there is no lower phone and the knee clearance is only 16 ½ inches wide and 10 inches deep. TT1 60 months
17.17.b The route to the telephone is inaccessible because the chairs prevent adequate clear width. AR3 60 months
17.18 Room 96 - Accessible Detox Room - The room is inaccessible because there is no telephone notification provided for persons with hearing impairments. H11 60 months
17.19 Room 96 - Single User Toilet Room
17.19.a The route to the toilet room is inaccessible because the path of travel into the toilet room is too narrow. AR3 60 months
17.19.b No accessible mirror has been provided. TR14 60 months
17.19.c There is insufficient turning space within the toilet room. TR19 60 months
17.19.d The toilet is inaccessible because the flush control is on the closed side. SU1 60 months
17.19.e The side grab bar is 36 inches long, the end closest to the rear wall is 17 ½ inches from the rear wall, the space between side grab and wall is more than 1 ½ inches wide, and there is a towel bar 13 inches above the bar which interferes with the usage of the grab bar. SU5, SU8 60 months
17.19.f The rear grab bar at the toilet is inaccessible because it is 29 inches long, the space between the grab bar and the wall is not 1 ½ inches, and the flush control obstructs its usage. SU3, SU4 60 months
17.19.g The shower is inaccessible because it is 34 inches by 56 ½ inches, there is no seat provided, and the grab bar on the rear wall does not extend the length of the wall. B8 60 months
17.20 Detox Area laundry - The door is inaccessible because it has only 6 inches of latch-side maneuvering space on the pull side of the door. D6 60 months
17.21 Lobby Area Women's Single User Toilet Room
17.21.a The toilet room sign is inaccessible because its centerline is not mounted 60 inches above the finished floor, it does not have Braille characters, and there is no International symbol of accessibility. TR17 60 months
17.21.b The toilet room is inaccessible because the pressure required to open the door is 15 pounds. D2 60 months
17.21.c The push side of the door to the toilet room, which is accessed through a front approach and which has both a closer and a latch, is inaccessible because the lavatory is obstructing maneuvering space. D7 60 months
17.21.d Although an audible alarm is provided in this facility, there is no visual alarm appliance in the toilet room. TR21 60 months
17.21.e No accessible mirror has been provided. TR14 60 months
17.21.f There is insufficient turning space within the toilet room. TR19 60 months
17.21.g The soap dispenser is inaccessible because the controls are mounted 55 inches above the finished floor. TR5 60 months
17.21.h The rear grab bar at the toilet is inaccessible because the flush control obstructs its usage. SU4 60 months
17.22 Lobby Area Men's Single User Toilet Room
17.22.a The toilet room sign is inaccessible because it has no International symbol of accessibility, its centerline is not mounted 60 inches above the finished floor, and there are no Braille characters. TR17 60 months
17.22.b The toilet room is inaccessible because the pressure required to open the door is 11 pounds. D2 60 months
17.22.c The push side of the door to the toilet room, which is accessed through a front approach and which has both a closer and a latch, is inaccessible because the lavatory is obstructing maneuvering space. D7 60 months
17.22.d Although an audible alarm is provided in this facility, there is no visual alarm appliance in the toilet room. TR21 60 months
17.22.e No accessible mirror has been provided. TR14 60 months
17.22.f There is insufficient turning space within the toilet room. TR19 60 months
17.22.g The soap dispenser is inaccessible because the controls are mounted 53½ inches above the finished floor and a forward reach is required. TR4 60 months
17.22.h The toilet is inaccessible because the flush control is on the closed side. SU1 60 months
17.22.i The rear grab bar at the toilet is inaccessible because the flush control obstructs its usage. SU4 60 months
17.23 Main Entrance - There is a 2 inch threshold at the door. D23 60 months
17.24 Parking to Front Entrance - There is no detectable warning at the curb ramp, it slopes 9.9%, and the flared sides slope 17.6% on the left and 22.3% on the right. AR5 60 months
18 Martin Luther King, Jr., Swim Center, 1201 Jackson Road, Silver Spring, Maryland 20901
18.1 Route from parking to Main Entrance - The route from the parking area to the front entrance is inaccessible because the curb ramp slopes 12% and the slope of the flared sides is 18% on the left and 15.8% on the right. AR5 36 months
18.2 Single User Toilet Room - Special Changing Room, Pool Level
18.2.a The pull side of the door to the toilet room is inaccessible because it has only 11 inches of maneuvering space on the latch side. D10, TR16 36 months
18.2.b No accessible coat hook has been provided. TR1 36 months
18.2.c No accessible mirror has been provided. TR14 36 months
18.2.d The baby changing table is inaccessible because the handle is mounted 58 inches above the finished floor. TR5 36 months
18.2.e The lavatory is inaccessible because the hot water pipes are not completely insulated or otherwise configured to protect against contact. TR12 36 months
18.2.f The toilet paper dispenser is inaccessible because it is mounted on the far wall. SU17 36 months
18.2.g There are no accessible grab bars provided. SU10, TR16 36 months
18.2.h The bench is 18 inches deep and 43 ½ inches long.

L1, TR16

36 months
18.2.i The roll-in shower is inaccessible because the seat is not mounted adjacent to the controls, there are not grab bars extending across all three walls, there is 2½ inches between the existing grab bars and the wall, and the shower head is inaccessible. B8, TR16 36 months
18.3 Bleachers along the length of Pool
18.3.a The door from large assembly area is inaccessible because the pressure required to open the door is 15 pounds. D2 36 months
18.3.b The push side of the door, which is accessed through a front approach and which has both a closer and a latch, is inaccessible because it has only 12 inches of maneuvering clearance on the latch side with only 34 inches of depth. D7 36 months
18.3.c The bleachers have no designated wheelchair locations. AA6 36 months
18.4 Main Level Toilet Room with Stalls - Men's
18.4.a The toilet room sign is inaccessible because its centerline is mounted 61 inches above the finished floor. TR17 36 months
18.4.b The toilet room is inaccessible because the pressure required to open the door is 10 pounds. D2 36 months
18.4.c The urinal is inaccessible because the rim is 18 ½ inches above the finished floor, the flush control is 46 inches above the finished floor, and it allows only a 22-inch wide clear floor space. TR20 36 months
18.4.d The toilet is inaccessible because the flush control is on the closed side and is 46 inches above the finished floor. ST2 36 months
18.4.e The side grab bar at the toilet is inaccessible because it is obstructed by the toilet paper dispenser. ST9 36 months
18.5 Main Level Toilet Room with Stalls - Women's
18.5.a The toilet room sign is inaccessible because its centerline is mounted 61 inches above the finished floor. TR17 36 months
18.5.b The toilet room is inaccessible because the pressure required to open the door is 12 pounds. D2 36 months
18.5.c No accessible mirror has been provided. TR14 36 months
18.5.d The lavatory is inaccessible because the hot water pipes are not insulated or otherwise configured to protect against contact. TR12 36 months
18.5.e No accessible coat hook has been provided. TR1 36 months
18.5.f The side grab bar at the toilet is inaccessible because it is obstructed by the toilet paper dispenser. ST9 36 months
18.6 Spa - The door is inaccessible because it has an opening width of only 30 inches. D25 36 months
18.7 Teaching Pool - The door is inaccessible because it has an opening width of only 30 inches. D25 36 months
18.8 Telephone at main entrance vestibule - The telephone is inaccessible because the coin clot is 60 inches above the finished floor. TT1 36 months
18.9 Elevator at Entrance
18.9.a The elevator is inaccessible because the hall call buttons are centered 41 inches above the finished floor. E3 36 months
18.9.b The elevator is inaccessible because the doors do not automatically reopen without requiring contact for objects passing through the opening at heights between 5 and 29 inches above the finished floor. E6 36 months
18.9.c The elevator is inaccessible because the Braille character floor designations are mounted to the right of the buttons. E4 36 months
18.9.d The elevator is inaccessible because the door to the emergency communications controls requires tight grasping to open. E8 36 months
18.10 Route to Pool Area from Elevator - The route from the elevator to the pool area is inaccessible because there is inadequate head room under the stairs, and the stairs are also a protruding object. AR7 36 months
18.11 Drinking fountain at Pool Level Exercise Room - The drinking fountain has a spout that is 43 inches above the finished floor. DF6 36 months
18.12 Drinking fountain at main Pool - The drinking fountain has a spout that is 39 inches above the finished floor. DF6 36 months
18.13 Locker Room - both Men and Women
18.13.a The locker room signage is inaccessible because it is mounted on the door. TR17 36 months
18.13.b The door to the locker room is inaccessible because the pressure required to open the door is 8 pounds. D2 36 months
18.13.c The lavatory is inaccessible because the bottom of the apron is 28 inches high. TR11 36 months
18.13.d The lavatory is inaccessible because the hot water pipes are not insulated or otherwise configured to protect against contact. TR12 36 months
18.13.e The lavatory is inaccessible because there is inadequate clear floor space. TR8 36 months
18.13.f The toilet is inaccessible because the flush control is on the closed side. ST2 36 months
18.13.g No accessible coat hook has been provided. TR1 36 months
18.13.h The side grab bar is inaccessible because the toilet paper dispenser is mounted less than 18 inches above it. ST9 36 months
18.13.i The side grab bar at the toilet is inaccessible because the distance of the closer end is 2 inches from the rear wall, and there is 2 ½ inches between the grab bar and the wall. ST6, ST7 36 months
18.13.j There is no rear grab bar provided at the accessible toilet. ST3 36 months
19 Lawrence Court House, 1 Lawrence Court, Rockville, Maryland
19.1 Ramp leading to rear accessible entrance - The ramp leading to the rear accessible entrance is inaccessible because the slope of the middle segment is 8.5%, the slope of the upper segment is 9%, and there are no 12 inch handrail extensions at the bottom of ramp. R3 60 months
19.2 Exterior Entrances - The building is inaccessible because there is no signage or directional signage provided at each entrance. D16 60 months
19.3 Single User Toilet Room - In Accessible Room
19.3.a The toilet room lacks accessible signage. TR17 60 months
19.3.b The pull side of the door to the toilet room is inaccessible because it has only 8 inches of maneuvering space on the latch side. D6 60 months
19.3.c No accessible mirror has been provided. TR14 60 months
19.3.d The lavatory is inaccessible because the hot water pipes are not insulated or otherwise configured to protect against contact. TR12 60 months
19.3.e The end of the side grab bar that is closest to the rear wall is13 ½ from the rear wall. ST7 60 months
19.3.f There is no rear grab bar. ST3 60 months
19.4 Shower - The shower is inaccessible because there is not a continuous L-shaped grab bar, the shower spray hose is 57 inches long, and the curb at the shower stall is 1 ½ inches high. B8 60 months
19.5 Sleeping Area - Back of Living Room, near Accessible Entrance
19.5.a The route along the bed is inaccessible because it is only 16 inches wide along the radiator. AR3 60 months
19.5.b The temperature controls (thermostat) are inaccessible because the controls require twisting. MC1, GC1 60 months
19.6 Living Room - The computer desk is inaccessible because there is not adequate knee space. T1 60 months
19.7 Telephone at Main Foyer - The telephone is inaccessible because the coin slot is 58 ½ inches above the finished floor. TT1 60 months
19.8 Dining Room - The tables in the dining room are inaccessible because there is only 24 ½ inches of knee clearance height at the apron. TR11 60 months
19.9 Single User Toilet Room - Staff and Visitors
19.9.a The toilet room lacks accessible signage. TR17 60 months
19.9.b The toilet room is inaccessible because the pressure required to open the door is 14 pounds. D2 60 months
19.9.c The door to the toilet room is inaccessible because it has only 11 ½ inches of maneuvering space. D7 60 months
19.9.d The route into the toilet room is inaccessible. AR3 60 months
19.9.e No accessible mirror has been provided. TR14 60 months
19.9.f There is insufficient turning space within the toilet room. TR19 60 months
19.9.g The lavatory is inaccessible because the bottom edge of the apron is 27 inches above the finished floor and it does not allow adequate knee or toe clearances, and the hardware requires twisting of the wrist to operate. TR10, TR11 60 months
19.9.h The lavatory is inaccessible because the hot water pipes are not insulated or otherwise configured to protect against contact. TR12 60 months
19.9.i The toilet is inaccessible because the radiator obstructs the clear floor space. SU16 60 months
19.9.j The toilet is inaccessible because the top of the seat is 15 ½ inches above the finished floor. SU18 60 months
19.9.k The toilet is inaccessible because its centerline measures 15 ½ inches from the side wall. SU15 60 months
19.9.l There are no grab bars provided. SU10 60 months
19.10 Main Office
19.10.a The door is inaccessible because it has an opening width of only 31 inches. D25, AR9 60 months
19.10.b The door is inaccessible because knob hardware is used. D1 60 months
19.11 Back Office
19.11.a The door is inaccessible because it has an opening width of only 28 inches. D25, AR9 60 months
19.11.b The route to the 2nd door is inaccessible because it is only 20 ½ inches wide. AR3, AR9 60 months
19.12 Counselor's Office - The door is inaccessible because it has an opening width of only 30 inches. D25, AR9 60 months
19.13 Front Porch
19.13.a The route to the front porch is inaccessible because there is a step at the door. AR1 60 months
19.13.b The door is inaccessible because knob hardware is used. D1 60 months
19.14 Parking
19.14.a The parking lot is inaccessible because there is no marked parking and, therefore, no designated accessible parking or access aisles. This lot requires 1 van accessible space. P3 60 months
20 Piccard Drive Department of Health and Human Services, 1301 Piccard Drive, Rockville, Maryland
20.1 Accessible Route from East Parking Lot
20.1.a There is no detectable warning at the curb ramp. AR5 36 months
20.2 Accessible Route from North Parking Lot
20.2.a The route from the North parking area to the entrance is inaccessible because it has a slope of up to 5.5%. MC2 36 months
20.3 Triage and Evaluation Unit - Women's Locker Room
20.3.a The room sign is inaccessible because its centerline is mounted 56 inches above the finished floor. D26 36 months
20.3.b The triage and evaluation unit is inaccessible because the pressure required to open the door is 7 pounds. D2 36 months
20.3.c The lavatory is inaccessible because the top of the rim or counter is 35 inches above the finished floor. TR11 36 months
20.3.d The toilet is inaccessible because the flush control is on the closed side. ST2 36 months
20.3.e The side grab bar is inaccessible because it is obstructed by the upper toilet paper dispenser, and there is not consistently 1 ½ inches between the grab bar and the wall. ST9, ST6 36 months
20.3.f The rear grab bar at the toilet is inaccessible because it is 24 ½ inches long. ST4 36 months
20.4 Triage and Evaluation Unit - Women's Tub - The shower is inaccessible because no shower spray unit is provided and the shower head is higher than 48 inches above the finished floor. B11 36 months
20.5 Triage and Evaluation Unit - Men's Locker Room
20.5.a The room sign is inaccessible because its centerline is mounted 56 inches above the finished floor. D26 36 months
20.5.b The triage and evaluation unit is inaccessible because the pressure required to open the door is 10 pounds. D2 36 months
20.5.c The lavatory is inaccessible because the top of the rim or counter is 35 inches above the finished floor. TR11 36 months
20.5.d The side grab bar is inaccessible because it is obstructed by the upper toilet paper dispenser, and there is not consistently 1 ½ inches between the grab bar and the wall. ST6, ST9 36 months
20.6 Drinking Fountains - The drinking fountain protrudes into the walkway and would not be detectable to a blind person using a cane. AR8 36 months
20.7 1st Floor Women's Toilet Room - Stalls
20.7.a The toilet room sign is inaccessible because its centerline is mounted 56 ½ inches above the finished floor. TR17 36 months
20.7.b The toilet room is inaccessible because the pressure required to open the door is 12 pounds. D2 36 months
20.7.c The air dryer protrudes into the walkway and would not be detectable to a blind person using a cane. AR8 36 months
20.7.d The lavatory is inaccessible because the hot water pipes are not insulated or otherwise configured to protect against contact. TR12 36 months
20.7.e The side grab bar is inaccessible because the toilet paper dispenser is mounted less than 18 inches above it. ST9 36 months
20.8 1st Floor Men's Toilet Room - Stalls
20.8.a The toilet room sign is inaccessible because its centerline is mounted 56 inches above the finished floor. TR17 36 months
20.8.b The toilet room is inaccessible because the pressure required to open the door is 12 pounds. D2 36 months
20.8.c The seat cover dispenser is inaccessible because the seat covers are 61 ½ inches above the finished floor. TR4 36 months
20.8.d The air dryer protrudes into the walkway and would not be detectable to a blind person using a cane. AR8 36 months
20.8.e The toilet is inaccessible because its centerline measures 19 ½ inches from the side wall. ST17 36 months
20.8.f The toilet is inaccessible because the flush control is on the closed side. ST2 36 months
20.8.g No accessible coat hook has been provided. TR1 36 months
20.8.h The side grab bar is inaccessible because the toilet paper dispenser is mounted less than 18 inches above it. ST9 36 months
20.8.i The rear grab bar at the toilet is inaccessible because it is 39 inches above the finished floor. ST3 36 months
20.9 Women's Toilet Room at Emergency Services Income Support - Stalls
20.9.a The door is inaccessible because the pressure required to open the door is 18 pounds. D2 36 months
20.9.b The seat cover dispenser is inaccessible because the seat covers are 64 inches above the finished floor. TR4 36 months
20.9.c The air dryer protrudes 6 inches, with its leading edge 35 inches above the finished floor, into the walkway and would not be detectable to a blind person using a cane. AR8 36 months
20.9.d The side grab bar at the toilet is inaccessible because it is obstructed by the toilet paper dispenser. ST9 36 months
20.10 Men's Toilet Room at Emergency Services Income Support - Stalls
20.10.a The seat cover dispenser is inaccessible because the seat covers are 64 inches above the finished floor. TR4 36 months
20.10.b The air dryer protrudes 6 inches, with its leading edge 35 inches above the finished floor, into the walkway and would not be detectable to a blind person using a cane. AR8 36 months
20.10.c The door to the stall is inaccessible because there is a twist-type handle. ST14 36 months
20.10.d The toilet is inaccessible because its centerline measures 21 inches from the side wall. ST17 36 months
20.10.e No accessible coat hook has been provided. TR1 36 months
20.10.f The side grab bar at the toilet is inaccessible because it is obstructed by the toilet paper dispenser. ST9 36 months
20.10.g The side grab bar at the toilet is inaccessible because its diameter is only 1 inch and the space between the grab bar and the wall is 2 inches. ST6 36 months
20.11 2nd floor drinking fountain - The drinking fountain protrudes into the walkway and would not be detectable to a blind person using a cane. AR8 36 months
20.12 Women's Toilet Room at Rental Assistance/Home Energy Program - Stalls
20.12.a The toilet room is inaccessible because the pressure required to open the door is 12 pounds. D2 36 months
20.12.b The seat cover dispenser is inaccessible because the seat covers are 64 inches above the finished floor. TR4 36 months
20.12.c The air dryer protrudes 6 inches, with its leading edge 35 inches above the finished floor, into the walkway and would not be detectable to a blind person using a cane. AR8 36 months
20.12.d The side grab bar at the toilet is inaccessible because it is obstructed by the toilet paper dispenser. ST9 36 months
20.13 Men's Toilet Room at Rental Assistance/Home Energy Program - Stalls
20.13.a The seat cover dispenser is inaccessible because the seat covers are 64 inches above the finished floor. TR4 36 months
20.13.b The air dryer protrudes 6 inches, with its leading edge 35 inches above the finished floor, into the walkway and would not be detectable to a blind person using a cane. AR8 36 months
20.13.c The door to the stall is inaccessible because there is a twist-type handle. ST14 36 months
20.13.d The toilet is inaccessible because its centerline measures 21 inches from the side wall. ST17 36 months
20.13.e No accessible coat hook has been provided. TR1 36 months
20.13.f The side grab bar at the toilet is inaccessible because it is obstructed by the toilet paper dispenser. ST9 36 months
20.13.g The side grab bar at the toilet is inaccessible because its diameter is only 1 inch and the space between the grab bar and the wall is 2 inches. ST6 36 months
20.14 Drinking Fountain - 4th Floor
20.14.a The drinking fountain has a spout that is 37 ½ inches above the finished floor. DF6 36 months
20.14.b The drinking fountain protrudes into the walkway and would not be detectable to a blind person using a cane. AR8 36 months
21 3rd District Police Station - Silver Spring, 801 Sligo Avenue, Silver Spring, Maryland 20910
21.1 Parking - The parking lot, with a total of approximately 90 parking spaces, is inaccessible because only two spaces are designated as accessible, there is no designated van-accessible space, the designated spaces and access aisles are too narrow at 88 inches and 40 inches respectively, and they have a cross slope as high as 5.4%. This lot requires 1 van accessible space and 3 standard accessible spaces. P3 60 months
21.2 Main Entrance
21.2.a The ramp at the main entrance is inaccessible because it slopes 10.4% near top of lower leg; the level landing where it changes direction is 48 inches wide; and there are no handrail extensions at the bottom. R3 60 months
21.2.b The pressure required to open the interior entrance door is 7 pounds. D2 60 months
21.3 Telephone - The telephone is inaccessible because a chair blocks clear floor space and the highest operable part is 54½ inches above the finished floor. TT1 60 months
21.4 Women's Single-User Toilet Room
21.4.a The toilet room sign is inaccessible because it is mounted on the door and has no raised or Braille characters. TR17 60 months
21.4.b The pressure required to open the toilet room door is 6 pounds. D2 60 months
21.4.c No accessible coat hook has been provided. TR1 60 months
21.4.d The soap dispenser is inaccessible because the controls are mounted 49 inches above the finished floor and a forward reach is required. TR4 60 months
21.4.e The towel dispenser is inaccessible because the controls are mounted 52 inches above the finished floor and require a forward reach. TR4 60 months
21.4.f The lavatory is inaccessible because the bottom edge of the apron is mounted 28 inches above the finished floor. TR11 60 months
21.4.g The side grab bar at the toilet is inaccessible because its far end is 53 inches from the rear wall. ST6, ST7 60 months
21.5 Men's Single-User Toilet Room
21.5.a The toilet room sign is inaccessible because it is mounted on the door and has no raised or Braille characters. TR17 60 months
21.5.b The pressure required to open the toilet room entrance door is 7 pounds. D2 60 months
21.5.c No accessible coat hook has been provided. TR1 60 months
21.5.d No accessible mirror has been provided. TR14 60 months
21.5.e The soap dispenser is inaccessible because the controls are mounted 50 inches above the finished floor and a forward reach is required. TR4 60 months
21.5.f The side grab bar at the toilet is inaccessible because it is 26 inches long and its far end is 28 inches from the rear wall. ST7 60 months
21.6 Drinking Fountain - Although an accessible drinking fountain is provided, there is no drinking fountain provided for people who have difficulty bending or stooping. DF3 60 months
21.7 Holding Cells - There are no accessible toilet facilities in each type of the holding cells. PJ1 60 months
22 Kensington Park Library, 4201 Knowles Avenue, Kensington, Maryland 20895
22.1 Parking - The parking lot is inaccessible because there is no designated van accessible space. Additionally, 3 out of the 5 spaces designated as accessible are less than 96 inches wide, 4 of the spaces slope between 3.8% and 5.5% with cross-slopes 3.1% to 6.3%, 3 of the 4 access aisles slope 4.9% to 5.2% and 3 have cross slopes of 3.45 to 5.6%, and the gutter in one of the access aisles has a cross slope of 18.3% and a change in level higher than ½ inch. This lot requires 1 van accessible space and 4 standard accessible spaces. P3 48 months
22.2 Exterior Route
22.2.a The route from the parking area to the entrance is inaccessible because the curb ramp in front of the parking area has a slope of 24.7%. AR5 48 months
22.2.b The ramp from the bus stop at Knowles Avenue to the sidewalk leading to the library has a running slope of 9% on the 3rd leg from the bottom and a cross-slope of 3.7% to 8.1% on the top leg; the top landing is 41 inches long with a slope of 6.2%; the bottom landing has a slope of between 14.3% and 20.1% due to the curb ramp from the crosswalk; the middle landings slope between 2.9% and 4.9%; handrails have 11 inch extensions and chipping paint that could cause splinters. R3 48 months
22.3 Entrance by Parking Lot - There is a 1 ¼ inch threshold at the door. D23 48 months
22.4 Seating
22.4.a The accessible computer (#12) is inaccessible because the computer table has 15½ inches of knee depth. T1 48 months
22.4.b The carrels in the library are inaccessible because they provide only 26 ¼ inches of knee height. L4 48 months
22.5 Check-Out Counter - The check-out area is inaccessible because the main counter is 38 inches above the finished floor and the lower portion of the counter is covered in papers. L2 48 months
22.6 Stacks - The book stacks are inaccessible because the space between the audio books stacks is only 30 inches, the width between the mysteries stacks is 18 inches, and the width between the taped books is 33 inches. L5 48 months
22.7 Magazine displays - The magazine display is inaccessible because the top shelf is 68 inches above the finished floor. L1 48 months
22.8 Study Room
22.8.a The pressure required to open the study room entrance door is 15 pounds. D2 48 months
22.8.b The door to the study room, which is accessed from the front, is inaccessible because a trash can impedes maneuvering space clearance. D7 48 months
22.8.c The study table is inaccessible because it only has 26 inches of knee height. T1 48 months
22.9 Elevator Lift
22.9.a The door is inaccessible because it has an opening width of only 31 inches. D25, AR9 48 months
22.9.b The pressure required to open the door on the first level is 16 pounds. D2 48 months
22.10 Lower Level Meeting Room
22.10.a The pressure required to open the lower level meeting room door is 12 pounds. D2 48 months
22.10.b The meeting room, which has a capacity of at least 205 seats, is inaccessible to people with hearing impairments because there is no signage indicating the availability of an assistive listening system. AA3 48 months
22.11 Lower Level Accessible Route - The underside of the stairway provides limited headroom and would not be detectable to a blind person using a cane. AR7 48 months
22.12 Lower Level Men's Toilet Room with Stalls
22.12.a The toilet room sign is inaccessible because it is mounted on the door and has no raised or Braille characters. TR17 48 months
22.12.b The pressure required to open the toilet room entrance door is 11 pounds. D2 48 months
22.12.c The lavatory is inaccessible because the bottom edge of the apron is mounted 28 inches above the finished floor and has inadequate knee clearance. TR11 48 months
22.12.d The lavatory is inaccessible because the clear floor space 28 inches wide and 15½ inches deep. TR8 48 months
22.12.e The urinal is inaccessible because the rim is 20 inches above the finished floor, it allows only a 36 inch wide clear floor space for greater than 24 inches deep, and the flush control is 47 inches above the finished floor. TR20 48 months
22.12.f The designated accessible toilet stall is inaccessible because the stall is only 58 inches deep with a floor-mounted toilet. ST16 48 months
22.12.g The toilet is inaccessible because its centerline measures 16 inches from the side wall. ST17 48 months
22.12.h No accessible coat hook has been provided. TR1 48 months
22.12.i The grab bars at the toilet are inaccessible because they are 37 inches above the finished floor. ST13 48 months
22.13 Lower Level Women's Toilet Room with Stalls
22.13.a The toilet room sign is inaccessible because it is mounted on the door and has no raised or Braille characters. TR17 48 months
22.13.b The pressure required to open the toilet room entrance door is 14 pounds. D2 48 months
22.13.c The baby changing table is inaccessible because the handle is mounted 59 inches above the finished floor. TR5 48 months
22.13.d The lavatory is inaccessible because the bottom edge of the apron is mounted 28 ½ inches above the finished floor and has inadequate knee clearance. TR11 48 months
22.13.e The lavatory is inaccessible because the hot water pipes are not insulated or otherwise configured to protect against contact. TR12 48 months
22.13.f The toilet is inaccessible because there is insufficient clear floor space. ST18 48 months
22.13.g The toilet is inaccessible because its centerline measures 17 inches from the side wall. ST17 48 months
22.13.h The toilet is inaccessible because the flush control is on the closed side. ST2 48 months
22.13.i No accessible coat hook has been provided. TR1 48 months
22.13.j The grab bars at the toilet are inaccessible because they are 37 inches above the finished floor. ST12 48 months
22.14 Drinking Fountains
22.14.a The lower level fountain is inaccessible because it requires 17 pounds of force to operate. DF2 48 months
22.14.b The lower level fountain protrudes into the walkway and would not be detectable to a blind person using a cane. AR8 48 months
22.14.c For the upper and lower levels, although an accessible drinking fountain is provided on both levels, there is no drinking fountain provided for people who have difficulty bending or stooping. DF3 48 months
22.15 Telephone at Main Entrance - The telephone is inaccessible because the telephone book obstructs the clear floor space and the highest operable part is 54½ inches above the finished floor. TT1 48 months
23 Holiday Park Senior Center, 3950 Ferrara Drive, Wheaton, Maryland 20906
23.1 Drinking Fountains - The three drinking fountains all have a spout that is higher than 36 inches above the finished floor. DF6 12 months
23.2 Elevators
23.2.a The elevators are inaccessible because the main entry floor call buttons in both elevators are not designated by a raised star. E4 12 months
23.2.b The elevator is inaccessible because, although emergency communications are provided, the emergency communications in both elevators are not identified by raised symbols or lettering, and the telephone cord is only 23 inches long. E4, E8 12 months
23.3 1st Floor Senior Travel Office
23.3.a The counter is inaccessible because it is 37 ½ inches above the finished floor and equivalent facilitation is not provided. C6 12 months
23.3.b The counter protrudes into the walkway and would not be detectable to a blind person using a cane. AR8 12 months
23.4 2nd Floor Interages, Inc., Office - The door is inaccessible because knob hardware is used. D1 12 months
23.5 Dining Hall - The coffee dispenser is inaccessible because the dispensing device is 53 inches above the finished floor and 13 inches back over an obstacle. TR4 12 months
23.6 Senior Programs - The interior door is inaccessible because the hardware requires pinching to operate. D1 12 months
23.7 2nd Floor Conference Room - The counter is inaccessible because it is 37 ¼ inches above the finished floor and equivalent facilitation is not provided. C6 12 months
23.8 1st Floor Conference Room - The door is inaccessible because knob hardware is used. D1 12 months
23.9 1st Floor Meeting / Multipurpose Room - There is no accessible route connecting the seating areas and the stage. AR3, AR9 12 months
23.10 1st Floor Designated Accessible Men's Toilet Room with Stalls
23.10.a The toilet room sign is inaccessible because it is mounted on the door and has no raised or Braille characters. TR17 12 months
23.10.b The pressure required to open the toilet room entrance door is 12 pounds. D2 12 months
23.10.c The light switch is inaccessible because it is 55 inches above the finished floor. TR5 12 months
23.10.d No accessible mirror has been provided. TR14 12 months
23.10.e The towel dispenser is inaccessible because the controls are mounted 60 ½ inches above the finished floor. TR5 12 months
23.10.f The towel dispenser protrudes into the walkway and would not be detectable to a blind person using a cane. AR8 12 months
23.10.g The lavatory is inaccessible because the rim or counter is 35 inches above the finished floor. TR11 12 months
23.10.h The toilet is inaccessible because its centerline measures 16 inches from the side wall. ST17 12 months
23.10.i The toilet is inaccessible because the flush control is on the closed side. ST2 12 months
23.10.j No accessible coat hook has been provided. TR1 12 months
23.10.k The side grab bar at the toilet is inaccessible because it is 36 inches long with its far end 43 inches from the rear wall, it is 30 inches above the finished floor, and it leaves 2 ½ inches between it and the wall. ST6, ST7 12 months
23.10.l The rear grab bar at the toilet is inaccessible because its closer end is mounted 19 ½ inches from the side wall, it is 30 inches above the finished floor, and it leaves 2 ¼ inches between it and the wall. ST4 12 months
23.11 1st Floor Designated Accessible Women's Toilet Room with Stalls
23.11.a The toilet room sign is inaccessible because it is mounted on the door and has no raised or Braille characters. TR17 12 months
23.11.b The pressure required to open the toilet room entrance door is 12 pounds. D2 12 months
23.11.c The light switch is inaccessible because it is 55 inches above the finished floor. TR5 12 months
23.11.d The seat cover dispenser is inaccessible because the seat covers are 58 inches above the finished floor. TR4 12 months
23.11.e The towel dispenser is inaccessible because the controls are mounted 58 ½ inches above the finished floor. TR5 12 months
23.11.f The paper towel dispenser protrudes into the walkway and would not be detectable to a blind person using a cane. AR8 12 months
23.11.g The lavatory is inaccessible because the rim or counter is 34 ½ inches above the finished floor. TR11 12 months
23.11.h The toilet is inaccessible because the top of the seat is 20 inches above the finished floor. ST20 12 months
23.11.i The toilet is inaccessible because its centerline measures 15 inches from the side wall. ST17 12 months
23.11.j No accessible coat hook has been provided. TR1 12 months
23.11.k The side grab bar is inaccessible because the toilet paper dispenser is mounted less than 18 inches above it. ST9 12 months
23.11.l The side grab bar at the toilet is inaccessible because it is 36 inches long with its far end 43 inches from the rear wall, it is 30 inches above the finished floor, and it leaves 2 ½ inches between it and the wall. ST6, ST7 12 months
23.11.m The rear grab bar at the toilet is inaccessible because its closer end is mounted 7 inches from the side wall, it is 30 inches above the finished floor, and it leaves 2 ½ inches between it and the wall. ST7 12 months
24 Bauer Drive Community Center, 14625 Bauer Drive, Rockville, Maryland 20852
24.1 Parking
24.1.a The 2 designated accessible spaces by the playground do not have vertical signs, and they have a slope of 2.7%. P6, P7 48 months
24.1.b The 3 designated accessible spaces by the main entrance do not have access aisles. P1 48 months
24.1.c The curb ramp at the access aisle has side flares that slope 23.1% and 22.9%. AR5 48 months
24.2 Exterior Ramp to Social Hall -The exterior ramp to the social hall is inaccessible because the landing at the top slopes 2.5%, the ramp slopes 9.1%, and the handrails are not smooth and free of splinters and sharp objects. R3 48 months
24.3 Social Hall Toilet Rooms
24.3.a There is no signage to the accessible toilet rooms in the lobby area. TR16 48 months
24.3.b The door signs are mounted on the doors and have no raised or Braille characters. D26 48 months
24.4 Women's Lobby Toilet Room with Stalls
24.4.a The toilet room sign is inaccessible because it is mounted on the door and has no raised or Braille characters. TR17 48 months
24.4.b There is a 3/4 inch threshold at the door. D23 48 months
24.4.c The lavatory is inaccessible because the hot water pipes are not insulated or otherwise configured to protect against contact. TR12 48 months
24.4.d The designated accessible stall is 54 inches deep with a floor-mounted toilet, and the trash can obstructs the toilet's clear floor space. ST14 48 months
24.4.e The toilet is inaccessible because its centerline measures 19 inches from the side wall. ST17 48 months
24.4.f The toilet is inaccessible because the flush control is on the closed side. ST2 48 months
24.4.g No accessible coat hook has been provided. TR1 48 months
24.4.h The toilet paper dispenser is inaccessible because it is mounted on the far side wall. SU17 48 months
24.4.i The rear grab bar at the toilet is inaccessible because it is obstructed by the toilet flush. ST5 48 months
24.5 Men's Lobby Toilet Room with Stalls
24.5.a The toilet room sign is inaccessible because it is mounted on the door. TR17 48 months
24.5.b There is a 3/4 inch threshold at the door. D23 48 months
24.5.c No accessible mirror has been provided. TR14 48 months
24.5.d The soap dispenser is inaccessible because the controls are mounted 52 inches above the finished floor and 13 inches back over an obstruction. TR4 48 months
24.5.e The lavatory is inaccessible because the rim or counter is 36 inches above the finished floor. TR11 48 months
24.5.f The lavatory is inaccessible because the hot water pipes are not insulated or otherwise configured to protect against contact. TR12 48 months
24.5.g The urinal is inaccessible because the flush control is 48 inches above the finished floor. TR20 48 months
24.5.h The designated accessible stall is 54 inches wide. ST16 48 months
24.5.i The toilet is inaccessible because its centerline measures 17 ½ inches from the side wall. ST17 48 months
24.5.j The toilet paper dispenser is inaccessible because it is mounted on the far side wall. ST17 48 months
24.5.k The side grab bar at the toilet is inaccessible because it leaves 3 inches between it and the wall. ST6 48 months
24.5.l The rear grab bar at the toilet is inaccessible because it is obstructed by the toilet flush. ST5 48 months
24.6 Art Room -The counter is inaccessible because the counter at the sink area is 37 inches above the finished floor. TR11 48 months
24.7 Gymnasium
24.7.a The hand controls on the foosball table protrude into the walkway and would not be detectable to a blind person using a cane. AR8 48 months
24.7.b There is an exercise bar apparatus attached to the wall that protrudes into the walkway and would not be detectable to a blind person using a cane. AR8 48 months
24.8 Exercise Room -The drinking fountain has a spout that is 40 inches above the finished floor. DF6 48 months
24.9 Conference Room -The door is inaccessible because knob hardware is used. D1 48 months
24.10 Community Room -The pressure required to open the community room entrance door is 15 pounds. D2 48 months
24.11 Lobby Telephone -The telephone is inaccessible because the highest operable part is 54 inches above the finished floor, and front reach is required. TT1 48 months
25 Red Brick Courthouse, 50 Courthouse Square, Rockville, Maryland 20850
25.1 Designated Accessible Rear Entrance
25.1.a The curb ramp has no flared side, handrail, nor guardrail on one side. AR5 60 months
25.1.b The building is inaccessible because it has no signage to indicate accessibility. D16 60 months
25.1.c There is a ¾ inch threshold at the rear entrance door. D23 60 months
25.1.d The push button used to open the door is inaccessible because it requires 20 pounds of pressure to operate. D2 60 months
25.1.e The interior ramp just inside the metal detector is inaccessible because it slopes 10.9%; the handrails are 32 inches high, there are no handrail extensions, there is 2¼ inches between a handrail and the wall, and the handrails are 1¾ inch in diameter. R3 60 months
25.2 Grand Courtroom -Although the courtroom has an assistive listening system, there is no signage indicating its availability. AA3 60 months
25.3 Drinking Fountain -The 2nd floor drinking fountain is inaccessible because the water height is only 2 inches high, and the operating control requires 7 pounds of force. In addition, there is no drinking fountain provided for people who have difficulty bending or stooping. DF7 60 months
25.4 Drinking Fountain -Ground Floor
25.4.a The drinking fountain is inaccessible because the operating control requires 10 pounds of force. DF2 60 months
25.4.b Although an accessible drinking fountain is provided, there is no drinking fountain provided for people who have difficulty bending or stooping. DF3 60 months
25.5 Men's Ground Floor Toilet Room with Stalls
25.5.a The ramp at the toilet room entrance does not have flared sides or edge protection at the drop off sides. R1 60 months
25.5.b The toilet room sign is inaccessible because it is mounted on the door. TR17 60 months
25.5.c The seat cover dispenser is inaccessible because the seat covers are 55 inches above the finished floor. TR4 60 months
25.5.d The lavatory is inaccessible because the bottom edge of the apron is mounted 28 ½ inches above the finished floor. TR11 60 months
25.5.e The toilet is inaccessible because its centerline measures 20 inches from the side wall. ST17 60 months
25.5.f The toilet is inaccessible because the flush control is on the closed side. ST2 60 months
25.5.g No accessible coat hook has been provided. TR1 60 months
25.5.h The side grab bar at the toilet is inaccessible because the far end of the side grab bar is 50 inches from rear wall. ST7 60 months
25.6 Women's Ground Floor Toilet Room with Stalls
25.6.a The ramp leading to the entrance has a slope of 12.8%. R5 60 months
25.6.b The toilet room sign is inaccessible because it is mounted on the door. TR17 60 months
25.6.c The seat cover dispenser is inaccessible because the seat covers are 58 inches above the finished floor. TR4 60 months
25.6.d The sanitary napkin dispenser protrudes into the walkway and would not be detectable to a blind person using a cane. AR8 60 months
25.6.e The lavatory is inaccessible because the bottom edge of the apron is mounted 28 inches above the finished floor. TR11 60 months
25.6.f The toilet is inaccessible because its centerline measures 19 inches from the side wall. ST17 60 months
25.6.g No accessible coat hook has been provided. TR1 60 months
25.6.h The toilet paper dispenser is inaccessible because it is mounted 43 inches from the rear wall. ST19 60 months
25.6.i The side grab bar at the toilet is inaccessible because its far end is 49 inches from the rear wall. ST7 60 months
26 Long Branch Pool, 8700 Piney Branch Road, Silver Spring, Maryland 20901
26.1 Parking
26.1.a Although the parking lot has designated accessible parking spaces, an inadequate number are van accessible. This lot requires at least 1 van accessible space in addition to at least one standard accessible space. P3 48 months
26.1.b The curb ramp provided is inaccessible because it has a 1 inch lip at the bottom. AR5 48 months
26.2 Men's Locker Room
26.2.a The locker room sign is inaccessible because it is not mounted 60 inches above the finished floor and has no raised characters or Braille.

D26,

TR16

48 months
26.2.b No accessible mirror has been provided. TR14 48 months
26.2.c The air dryers protrude into the walkway and would not be detectable to a blind person using a cane. AR8 48 months
26.2.d The lavatory is inaccessible because the hot water pipes are not insulated or otherwise configured to protect against contact. TR12 48 months
26.2.e The urinal is inaccessible because the rim is 17 ½ inches above the finished floor. TR20, LR4,TR16 48 months
26.2.f There is no accessible stall provided. ST15, LR4,TR16 48 months
26.2.g There is no accessible shower provided. B8, LR4,TR16 48 months
26.2.h The bench is 15 ½ inches deep. L1,TR16 48 months
26.3 Women's Locker Room
26.3.a The locker room sign is inaccessible because it is not mounted 60 inches above the finished floor and has no raised characters or Braille. D26, TR16 48 months
26.3.b No accessible mirror has been provided. TR14 48 months
26.3.c The air dryers protrude into the walkway and would not be detectable to a blind person using a cane. AR8 48 months
26.3.d The soap dispenser is inaccessible because the controls are mounted 51 inches above the finished floor over a 13 inch obstruction). TR4 48 months
26.3.e The lavatory is inaccessible because the hot water pipes are not insulated or otherwise configured to protect against contact. TR12 48 months
26.3.f There is no accessible stall provided. ST15, LR4, TR16 48 months
26.3.g There is no accessible shower provided. B8, LR4, TR16 48 months
26.3.h The bench is 15 ½ inches deep. L1, TR16 48 months
26.4 Telephone -The telephone by the men's locker room is inaccessible because it has no volume control. TT1 48 months
26.5 Outdoor Pool Single-User Locker Room
26.5.a The locker room sign is inaccessible because it is not mounted 60 inches above the finished floor and has no raised characters or Braille. D26 48 months
26.5.b No accessible mirror has been provided. TR14 48 months
26.5.c The toilet is inaccessible because the top of the seat is 19 ½ inches above the finished floor. ST20 48 months
26.5.d The toilet is inaccessible because the flush control is on the closed side. ST2 48 months
26.5.e The side grab bar at the toilet is inaccessible because the far end is 51 inches from the rear wall. ST7 48 months
26.5.f The rear grab bar at the toilet is inaccessible because it is 25 inches long and its near end is mounted 8 ½ inches from the side wall. ST4 48 months
26.5.g The shower is inaccessible because it has no grab bars and the hose is 58 inches long. B8, B9, B11 48 months
26.5.h The bench is between 14 and 20 inches deep, 16 inches high, and 33 inches long. LR1 48 months
27 Executive Office Building, 101 Monroe Street, Rockville, Maryland 20850
27.1 Cafeteria
27.1.a The route through the cafeteria narrows to 31 inches between the salad bar and soda refrigerators. AR3 24 months
27.1.b The suggestion box by a door leading to outdoor seating protrudes 7 inches into the walkway with its leading edge 43 inches above the finished and would not be detectable to a blind person using a cane. AR8 24 months
27.1.c There is no accessible seating at the outdoor picnic tables. PD6 24 months
27.1.d The underside of the stairs to the cafeteria level has no barrier to block off the area of limited head room. AR7 24 months
27.2 Terrace Level Computer Kiosk -There is no knee or toe clearance at the computer kiosk due to a printer and a foot rest under the desk. T1 24 months
27.3 Security Counter -The counter is inaccessible because it is 42 inches above the finished floor. C6 24 months
27.4 2nd Floor Office of the County Executive -The pressure required to open the doors leading to the three conference rooms range from 15 to 17 pounds. D2, AR9 24 months
27.5 3rd Floor Office of County Attorney -The three conference rooms are inaccessible because each room has a door with knob hardware. D1 24 months
27.6 6th Floor Division of Solid Waste -The mailboxes protrude 12 inches into the walkway with its leading edge 40 ½ inches above the finished and would not be detectable to a blind person using a cane. AR8 24 months
27.7 10th Floor Department of Public Works and Transportation
27.7.a The conference room sign is inaccessible because it has no raised or Braille characters. D26 24 months
27.7.b The door is inaccessible because knob hardware is used. D1 24 months
27.8 12th Floor Fire and Rescue Services -The AED protrudes 7 inches into the walkway with its leading edge 48 inches above the finished and would not be detectable to a blind person using a cane. AR8 24 months
27.9 14th Floor OMB -The large conference room door is inaccessible because knob hardware is used. D1 24 months
27.10 Terrace Level Drinking Fountains
27.10.a Although several drinking fountains are provided in this facility, there are no accessible drinking fountains. The terrace level drinking fountain by elevator is inaccessible because the spout is not in front, the water height is less than 4 inches, the water flow is not within 3 inches of the front of the fountain, the controls are not mounted near the front of the fountain and they require twisting to operate. Provide at least 7 drinking fountains in this facility with a spout height no higher than 36 inches, measured from the finished floor or ground surface to the spout outlet; DF1 24 months
27.11 Drinking Fountains throughout facility – Terrace, Lobby, and 2nd through 15th floors
27.11.a Although several drinking fountains are provided in this facility, there are no accessible drinking fountains. DF1 24 months
27.11.b The drinking fountain on the 2nd floor protrudes into the walkway and would not be detectable to a blind person using a cane. AR8 24 months
27.12 Terrace Level Men's Toilet Room with Stalls
27.12.a The toilet room sign is inaccessible because it is mounted 63 inches above the finished floor and has no raised or Braille characters. TR17 24 months
27.12.b The pressure required to open the toilet room entrance door is 10 pounds. D2 24 months
27.12.c The pull side of the door, which is accessed through a front approach, is inaccessible because it has only 17 inches on the latch side. D6 24 months
27.12.d The lavatory is inaccessible because the bottom edge of the apron is mounted 28 ½ inches above the finished floor and does not provide adequate knee clearance. TR11 24 months
27.12.e The toilet is inaccessible because the flush control is on the closed side. ST2 24 months
27.12.f No accessible coat hook has been provided. TR1 24 months
27.12.g The side grab bar is inaccessible because the toilet paper dispenser is mounted less than 18 inches above it. ST9 24 months
27.12.h The rear grab bar at the toilet is inaccessible because it is 24 ½ inches long and its closer end is mounted 9 ½ inches from the side wall. ST7 24 months
27.13 Terrace Level Women's Toilet Room with Stalls
27.13.a The toilet room sign is inaccessible because it is mounted 63 inches above the finished floor and has no raised or Braille characters. TR17 24 months
27.13.b The pressure required to open the toilet room entrance door is 11 pounds. D2 24 months
27.13.c The lavatory is inaccessible because the bottom edge of the apron is mounted 28 ½ inches above the finished floor and provides inadequate knee clearance. TR11 24 months
27.13.d There is no accessible stall provided. ST15 24 months
27.14 Lobby Women's Toilet Room with Stalls
27.14.a The toilet room sign is inaccessible because it is mounted 61 inches above the finished floor. TR17 24 months
27.14.b The lavatory is inaccessible because it has insufficient knee clearance. TR11 24 months
27.14.c The lavatory is inaccessible because the hot water pipes are not insulated or otherwise configured to protect against contact. TR12 24 months
27.14.d The toilet is inaccessible because its centerline measures 19 ½ inches from the side wall. ST17 24 months
27.14.e No accessible coat hook has been provided. TR1 24 months
27.14.f The side grab bar is inaccessible because the toilet paper dispenser is mounted less than 18 inches above it. ST9 24 months
27.14.g The rear grab bar at the toilet is inaccessible because its closer end is mounted 8 inches from side wall. ST4 24 months
27.15 Lobby Men's Toilet Room with Stalls
27.15.a The toilet room sign is inaccessible because it is mounted on the door with its centerline 61 ½ inches above the finished floor. TR17 24 months
27.15.b No accessible mirror has been provided. TR14 24 months
27.15.c The lavatory is inaccessible because the bottom edge of the apron is mounted 28 inches above the finished floor and provides inadequate knee clearance. TR11 24 months
27.15.d The lavatory is inaccessible because the hot water pipes are not insulated or otherwise configured to protect against contact. TR12 24 months
27.15.e The toilet is inaccessible because its centerline measures 18 ½ inches from the side wall. ST17 24 months
27.15.f The toilet is inaccessible because the flush control is on the closed side. ST2 24 months
27.15.g No accessible coat hook has been provided. TR1 24 months
27.15.h The side grab bar is inaccessible because the toilet paper dispenser is mounted less than 18 inches above it. ST9 24 months
27.15.i The rear grab bar at the toilet is inaccessible because its closer end is mounted 8½ inches from side wall. ST4 24 months
27.16 Elevator -The elevator is inaccessible because the car control buttons are too high. E4 24 months
27.17 3rd Floor Office of the County Attorney -The counter at is inaccessible because it is 41 inches above the finished floor and no equivalent facilitation is provided. C6 24 months
27.18 Telephones
27.18.a Although the telephone on the lobby level is designated as accessible, it is not accessible because it does not have volume control. TT1 24 months
27.18.b Although there are 4 pay telephones provided on the lobby level, a TTY is not provided. TT2 24 months
27.19 2nd Floor Men's Toilet Room with Stalls
27.19.a The toilet room sign is inaccessible because it is mounted on the door. TR17, TR16 24 months
27.19.b The pressure required to open the toilet room entrance door is 13 pounds. D2 24 months
27.19.c There is no standard accessible stall provided. ST15, TR16 24 months
27.20 2nd Floor Women's Toilet Room with Stalls
27.20.a The toilet room sign is inaccessible because it is mounted on the door. TR17, TR16 24 months
27.20.b The pressure required to open the toilet room entrance door is 15 pounds. D2 24 months
27.20.c The route to the toilet room is inaccessible because the path into the room narrows to less than 32 inches by the mirror. AR3, TR16 24 months
27.20.d The lavatory is inaccessible because the clear floor space is blocked by an armchair. TR8 24 months
27.20.e There is no standard accessible stall provided. ST15, TR16 24 months
27.21 3rd Floor Men's Toilet Room with Stalls
27.21.a The toilet room sign is inaccessible because it is mounted on the door. TR17, TR16 24 months
27.21.b The pressure required to open the toilet room entrance door is 15 pounds. D2 24 months
27.21.c The lavatory is inaccessible because it does not provide sufficient knee space. TR11, TR16 24 months
27.21.d There is no standard accessible stall provided. ST15, TR16 24 months
27.22 3rd Floor Women's Toilet Room with Stalls
27.22.a The toilet room sign is inaccessible because it is mounted on the door. TR17, TR16 24 months
27.22.b The pressure required to open the toilet room entrance door is 13 pounds. D2 24 months
27.22.c The pull side of the door, which is accessed through a front approach, is inaccessible because it has only 12 inches of maneuvering space on the latch side. D6, TR16 24 months
27.22.d The lavatory is inaccessible because it does not allow adequate knee or toe clearances. TR11, TR16 24 months
27.22.e There is no standard accessible stall provided. ST15, TR16 24 months
27.23 4th Floor Women's Toilet Room with Stalls
27.23.a The toilet room sign is inaccessible because it is mounted on the door. TR17, TR16 24 months
27.23.b The pressure required to open the toilet room entrance door is 14 pounds. D2 24 months
27.23.c The pull side of the door, which is accessed through a front approach, is inaccessible because it has only 12 inches of maneuvering space on the latch side. D6, TR16 24 months
27.23.d The lavatory is inaccessible because the clear floor space is blocked by a desk. TR8 24 months
27.23.e There is no standard accessible stall provided. ST15, TR16 24 months
27.24 4th Floor Men's Toilet Room with Stalls
27.24.a The toilet room sign is inaccessible because it is mounted on the door. TR17, TR16 24 months
27.24.b The pressure required to open the toilet room entrance door is 12 pounds. D2 24 months
27.24.c The lavatory is inaccessible because it does not allow adequate knee or toe clearances. TR11, TR16 24 months
27.24.d There is no standard accessible stall provided. ST15, TR16 24 months
27.25 5th Floor Women's Toilet Room with Stalls
27.25.a The toilet room sign is inaccessible because it is mounted on the door. TR17, TR16 24 months
27.25.b The pressure required to open the toilet room entrance door is 12 pounds. D2 24 months
27.25.c The pull side of the door, which is accessed through a front approach, is inaccessible because it has only 12 inches of maneuvering space on the latch side. D6, TR16 24 months
27.25.d The lavatory is inaccessible because the clear floor space is blocked by a desk. TR8 24 months
27.25.e There is no standard accessible stall provided. ST15, TR16 24 months
27.26 5th Floor Men's Toilet Room with Stalls
27.26.a The toilet room sign is inaccessible because it is mounted on the door. TR17, TR16 24 months
27.26.b The pressure required to open the toilet room entrance door is 10 pounds. D2 24 months
27.26.c The lavatory is inaccessible because it does not allow adequate knee or toe clearances. TR11, TR16 24 months
27.26.d There is no standard accessible stall provided. ST15, TR16 24 months
27.27 7th Floor Human Resources Counter -The counter is inaccessible because it is 42 ½ inches above the finished floor. C6 24 months
27.28 10th Floor Reception Counter -The counter is inaccessible because it is 44 inches above the finished floor. C6 24 months
27.29 6th Floor Men's Toilet Room with Stalls
27.29.a The toilet room sign is inaccessible because it is mounted on the door. TR17, TR16 24 months
27.29.b The pressure required to open the toilet room entrance door is 11 pounds. D2 24 months
27.29.c The lavatory is inaccessible because it does not allow adequate knee or toe clearances. TR11, TR16 24 months
27.29.d There is no standard accessible stall provided. ST15, TR16 24 months
27.30 6th Floor Women's Toilet Room with Stalls
27.30.a The toilet room sign is inaccessible because it is mounted on the door. TR17, TR16 24 months
27.30.b The pressure required to open the toilet room entrance door is 15 pounds. D2 24 months
27.30.c The lavatory is inaccessible because it does not allow adequate knee or toe clearances. TR11, TR16 24 months
27.30.d There is no standard accessible stall provided. ST15, TR16 24 months
27.31 7th Floor Women's Toilet Room with Stalls
27.31.a The toilet room sign is inaccessible because it is mounted on the door. TR17, TR16 24 months
27.31.b The pressure required to open the toilet room entrance door is 15 pounds. D2 24 months
27.31.c The lavatory is inaccessible because it does not allow adequate knee or toe clearances. TR12, TR16 24 months
27.31.d The lavatory is inaccessible because the hot water drain pipes are not covered. TR12 24 months
27.31.e There is no standard accessible stall provided. ST15, TR16 24 months
27.32 7th Floor Men's Toilet Room with Stalls
27.32.a The toilet room sign is inaccessible because it is mounted on the door. TR17, TR16 24 months
27.32.b The pressure required to open the toilet room entrance door is 15 pounds. D2 24 months
27.32.c The lavatory is inaccessible because it does not allow adequate knee or toe clearances. TR11, TR16 24 months
27.32.d The lavatory is inaccessible because the hot water pipes are not insulated or otherwise configured to protect against contact. TR12 24 months
27.32.e There is no standard accessible stall provided. ST15, TR16 24 months
27.33 8th Floor Women's Toilet Room with Stalls
27.33.a The toilet room sign is inaccessible because it is mounted on the door. TR17, TR16 24 months
27.33.b The pressure required to open the toilet room entrance door is 13 pounds. D2 24 months
27.33.c The lavatory is inaccessible because it does not allow adequate knee or toe clearances. TR11, TR16 24 months
27.33.d There is no standard accessible stall provided. ST15, TR16 24 months
27.34 8th Floor Men's Toilet Room with Stalls
27.34.a The toilet room sign is inaccessible because it is mounted on the door. TR17, TR16 24 months
27.34.b The pressure required to open the toilet room entrance door is 11 pounds. D2 24 months
27.34.c The lavatory is inaccessible because it does not allow adequate knee or toe clearances. TR11, TR16 24 months
27.34.d There is no standard accessible stall provided. ST15, TR16 24 months
27.35 9th Floor Women's Toilet Room with Stalls
27.35.a The toilet room sign is inaccessible because it is mounted on the door. TR17, TR16 24 months
27.35.b The pressure required to open the toilet room entrance door is 12 pounds. D2 24 months
27.35.c The lavatory is inaccessible because it does not allow adequate knee or toe clearances. TR11, TR16 24 months
27.35.d There is no standard accessible stall provided. ST15, TR16 24 months
27.36 9th Floor Men's Toilet Room with Stalls
27.36.a The toilet room sign is inaccessible because it is mounted on the door. TR17, TR16 24 months
27.36.b The pressure required to open the toilet room entrance door is 12 pounds. D2 24 months
27.36.c There is no standard accessible stall provided. ST15, TR16 24 months
27.37 10th Floor Men's Toilet Room with Stalls
27.37.a The toilet room sign is inaccessible because it is mounted on the door. TR17, TR16 24 months
27.37.b The pressure required to open the toilet room entrance door is 13 pounds. D2 24 months
27.37.c There is no standard accessible stall provided. ST15, TR16 24 months
27.38 10th Floor Women's Toilet Room with Stalls
27.38.a The toilet room sign is inaccessible because it is mounted on the door. TR17, TR16 24 months
27.38.b The pressure required to open the toilet room entrance door is 15 pounds. D2 24 months
27.38.c There is no standard accessible stall provided. ST15, TR16 24 months
27.39 11th Floor Men's Toilet Room with Stalls
27.39.a The toilet room sign is inaccessible because it is mounted on the door. TR17, TR16 24 months
27.39.b The pressure required to open the toilet room entrance door is 14 pounds. D2 24 months
27.39.c There is no standard accessible stall provided. ST15, TR16 24 months
27.40 11th Floor Women's Toilet Room with Stalls
27.40.a The toilet room sign is inaccessible because it is mounted on the door. TR17, TR16 24 months
27.40.b The pressure required to open the toilet room entrance door is 13 pounds. D2 24 months
27.40.c The pull side of the door, which is accessed through a front approach, is inaccessible because it has only 12 inches of maneuvering space on the latch side. D6, TR16 24 months
27.40.d There is no standard accessible stall provided. ST15, TR16 24 months
27.41 14th Floor OMB Counter -The counter is inaccessible because it is 47 inches above the finished floor. C6 24 months
27.42 12th Floor Men's Toilet Room with Stalls
27.42.a The toilet room sign is inaccessible because it is mounted on the door. TR17, TR16 24 months
27.42.b The pressure required to open the toilet room entrance door is 13 pounds. D2 24 months
27.42.c There is no standard accessible stall provided. ST15, TR16 24 months
27.43 12th Floor Women's Toilet Room with Stalls
27.43.a The toilet room sign is inaccessible because it is mounted on the door. TR17, TR16 24 months
27.43.b The pressure required to open the toilet room entrance door is 14 pounds. D2 24 months
27.43.c The lavatory is inaccessible because the clear floor space is blocked by a desk. TR8 24 months
27.43.d There is no standard accessible stall provided. ST15, TR16 24 months
27.44 13th Floor Men's Toilet Room with Stalls
27.44.a The toilet room sign is inaccessible because it is mounted on the door. TR17, TR16 24 months
27.44.b The pressure required to open the toilet room entrance door is 15 pounds. D2 24 months
27.44.c There is no standard accessible stall provided. ST15, TR16 24 months
27.45 13th Floor Women's Toilet Room with Stalls
27.45.a The toilet room sign is inaccessible because it is mounted on the door. TR17, TR16 24 months
27.45.b The pressure required to open the toilet room entrance door is 13 pounds. D2 24 months
27.45.c The door to the toilet room, which is accessed from a front approach, is inaccessible because it has only12 inches of maneuvering space on the latch side. D10, TR16 24 months
27.45.d There is no standard accessible stall provided. ST15, TR16 24 months
27.46 14th Floor Men's Toilet Room with Stalls
27.46.a The toilet room sign is inaccessible because it is mounted on the door. TR17, TR16 24 months
27.46.b The pressure required to open the toilet room entrance door is greater than 5 pounds. D2 24 months
27.46.c There is no standard accessible stall provided. ST15, TR16 24 months
27.47 14th Floor Women's Toilet Room with Stalls
27.47.a The toilet room sign is inaccessible because it is mounted on the door. TR17, TR16 24 months
27.47.b The pressure required to open the toilet room entrance door is 14 pounds. D2 24 months
27.47.c The door to the toilet room, which is accessed from a front approach, is inaccessible because it has only12 inches of maneuvering space on the latch side. D10, TR16 24 months
27.47.d There is no standard accessible stall provided. ST15, TR16 24 months
27.48 15th Floor Men's Toilet Room with Stalls
27.48.a The toilet room sign is inaccessible because it is mounted on the door. TR17, TR16 24 months
27.48.b The pressure required to open the toilet room entrance door is 15 pounds. D2 24 months
27.48.c There is no standard accessible stall provided. ST15, TR16 24 months
27.49 15th Floor Women's Toilet Room with Stalls
27.49.a The toilet room sign is inaccessible because it is mounted on the door. TR17, TR16 24 months
27.49.b The pressure required to open the toilet room entrance door is 13 pounds. D2 24 months
27.49.c The door to the toilet room, which is accessed from a front approach, is inaccessible because it has only 12 inches of maneuvering space on the latch side. D10, TR16 24 months
27.49.d The lavatory is inaccessible because the clear floor space is blocked by a desk. TR8 24 months
27.49.e There is no standard accessible stall provided. ST15, TR16 24 months
28 Strathmore Mansion, 5301 Tuckerman Lane, North Bethesda, Maryland 20852
28.1 Rear Parking Lot -The parking spaces reserved for persons with disabilities are inaccessible because the spaces are 92 inches wide or less, and cross slopes exceed 2%. P7, P8 36 months
28.2 Front Parking Lot near Entrance -The parking lot, with a total of approximately 80 parking spaces, is inaccessible because only 2 designated accessible spaces are provided, the spaces have cross slopes up to 4.8%, and the access aisles have cross slopes of up to 2.8%. This lot requires 1 van accessible space and a total of 4 standard accessible spaces. P3 36 months
28.3 Mansion Parking
28.3.a The parking reserved for persons with disabilities is inaccessible because the spaces have a cross slope of up to 5.8% and the access aisles have a cross slope of up to 5.2%. P7 36 months
28.3.b The van accessible parking reserved for persons with disabilities lacks the appropriate signage. P6 36 months
28.4 Ramp from parking to Mansion's accessible entrance -The ramp is not accessible because handrails are not on both sides, the end of one handrail is not rounded or returned, and the diameter of the handrail is 2 ¼ inches. R4 36 months
28.5 Entrance -The building is inaccessible because it has no signage to indicate accessibility. D16 36 months
28.6 Elevators near Accessible Entrance
28.6.a The elevator is inaccessible because there are no audible and visual signals provided. E5 36 months
28.6.b The elevator is inaccessible because the hoistway signage is centered 40 inches above the finished floor. E12 36 months
28.6.c The elevator is inaccessible because there is no raised star to indicate the main floor. E4 36 months
28.6.d The elevator is inaccessible because, although emergency communications are provided, no one answered the call when tested. E8 36 months
28.7 1st Floor Toilet Room near Gift Shop (right side) -Single User Toilet Room
28.7.a The toilet room lacks accessible signage. TR17 36 months
28.7.b The toilet room is inaccessible because the pressure required to open the door is 10 pounds. D2 36 months
28.7.c No accessible coat hook has been provided. TR1 36 months
28.7.d No accessible mirror has been provided. TR14 36 months
28.7.e The toilet is inaccessible because its centerline measures 17 inches from the side wall. SU15 36 months
28.7.f The toilet paper dispenser is inaccessible because it is mounted 42 inches from the rear wall. SU17 36 months
28.7.g The far end of the side grab bar is 49 inches from the rear wall. SU6 36 months
28.8 1st Floor Toilet Room near Gift Shop (left side) -Single User Toilet Room
28.8.a The toilet room lacks accessible signage. TR17 36 months
28.8.b The toilet room is inaccessible because the pressure required to open the door is 10 pounds. D2 36 months
28.8.c No accessible coat hook has been provided. TR1 36 months
28.8.d No accessible mirror has been provided. TR14 36 months
28.8.e The toilet is inaccessible because its centerline measures 17 inches from the side wall. SU15 36 months
28.8.f The toilet paper dispenser is inaccessible because it is mounted 42 inches from the rear wall. SU17 36 months
28.8.g The far end of the side grab bar is 49 inches from the rear wall. SU6 36 months
28.9 2nd Floor Toilet Room (right side) -Single User Toilet Room
28.9.a The toilet room lacks accessible signage. TR17 36 months
28.9.b The toilet room is inaccessible because the pressure required to open the door is 10 pounds. D2 36 months
28.9.c No accessible coat hook has been provided. TR1 36 months
28.9.d No accessible mirror has been provided. TR14 36 months
28.9.e The toilet is inaccessible because its centerline measures 17 inches from the side wall. SU15 36 months
28.9.f The toilet paper dispenser is inaccessible because it is mounted 42 inches from the rear wall. SU17 36 months
28.9.g The far end of the side grab bar is 49 inches from the rear wall. SU6 36 months
28.10 2nd Floor Toilet Room (left side) -Single User Toilet Room
28.10.a The toilet room lacks accessible signage. TR17 36 months
28.10.b The toilet room is inaccessible because the pressure required to open the door is 10 pounds. D2 36 months
28.10.c No accessible coat hook has been provided. TR1 36 months
28.10.d No accessible mirror has been provided. TR14 36 months
28.10.e The toilet is inaccessible because its centerline measures 17 inches from the side wall. SU15 36 months
28.10.f The toilet paper dispenser is inaccessible because it is mounted 42 inches from the rear wall. SU17 36 months
28.10.g The far end of the side grab bar is 49 inches from the rear wall. SU6 36 months
28.11 Drinking Fountain near Gift Shop
28.11.a The drinking fountain is inaccessible because the operating control requires 7 pounds of force. DF2 36 months
28.11.b The drinking fountain protrudes 17 inches into the walkway with its leading edge greater than 27 inches above the finished floor and would not be detectable to a blind person using a cane. AR8 36 months
29 Potomac Community Center, 11315 Falls Road, Potomac, Maryland
29.1 General Facility
29.1.a Throughout the facility, there are no permanent room signs having Braille or raised lettering. D26 48 months
29.1.b Although an audible alarm is provided in this facility, there are not visual alarm appliances in all toilet rooms. TR21 48 months
29.2 Parking
29.2.a The parking lot, with a total of approximately 332 parking spaces, is inaccessible because only 6 accessible spaces are provided, none of which are van accessible. This lot requires 1 van accessible space and 7 standard accessible spaces. P3 48 months
29.2.b One of the current parking spaces reserved for persons with disabilities is inaccessible because the parking space near the play area is served by an access aisle that is too narrow. P8 48 months
29.3 Route to Entrance Door -The route from the parking area to the entrance is inaccessible because the curb ramp slopes 15.8%. AR5 48 months
29.4 Route to Play Area -There is no accessible route to the play area because a high curb surrounds the area. AR1 48 months
29.5 Route to Tennis Courts -The route to the tennis courts is inaccessible because there is no level surface and the slope is as high as 16.2%, and the width between wheel stops is 35 inches. AR1 48 months
29.6 Route to Basketball Courts -The route to the basketball courts is inaccessible because it is over grass and there is no level surface. AR1 48 months
29.7 Route to Hockey Rink and Baseball Area
29.7.a The route to the hockey rink and baseball area is inaccessible because there is a 7 inch gap along the route and 1 ½ inch change in level at the base of the ramp to the hockey rink. AR1 48 months
29.7.b There is no accessible route to Baseball Field #2. AR1 48 months
29.8 Ramp at Hockey Rink -The ramp is inaccessible because there is no continuous inside rail, no extensions at the top and bottom of the ramp, and the cross slope at the 3rd leg of ramp is 2.7%. R3 48 months
29.9 Gymnasium -The door hardware is inaccessible. D1 48 months
29.10 Classroom -The door is inaccessible because knob hardware is used. D1 48 months
29.11 Meeting Room #1 -The door is inaccessible because knob hardware is used. D1 48 months
29.12 Arts and Crafts Room -The door is inaccessible because knob hardware is used. D1 48 months
29.13 Weight Room
29.13.a The weight room is inaccessible because the pressure required to open the door is 12 pounds. D2 48 months
29.13.b There is no accessible path of travel inside the room. AR3 48 months
29.14 Social Hall
29.14.a There is no access to stage area within the social hall. AR3, AR9 48 months
29.14.b The door is inaccessible because the thumb latch hardware requires pinching to operate. D1 48 months
29.15 Drinking Fountain at Social Hall Lobby -he drinking fountain is inaccessible because the knee clearance provided is 25 inches from the floor. DF5 48 months
29.16 Community Room
29.16.a The door is inaccessible because the hardware requires twisting to operate. TR10 48 months
29.16.b The community room is inaccessible because the pressure required to open the door is 15 pounds. D2 48 months
29.17 Exterior Route to Daycare Center and Western Area Office
29.17.a The route to the Daycare Center and the Western Area Office is inaccessible because there is a ¾ inch lip inside the ramp. AR1 48 months
29.17.b The slope of the curb ramp is 10.8% and the flared side is 36.1%, and is inaccessible. AR5 48 months
29.18 Entrance at Daycare Center and Western Area Office -The interior vestibule door is inaccessible because the pressure required to open the door is 11 pounds. D2 48 months
29.19 Daycare Center and Western Area Office
29.19.a The door is inaccessible because the opener hardware requires twisting. TR10 48 months
29.19.b The pull side of the door, which is accessed from the latch side of the door, is inaccessible because it does not provide adequate clearance. D6 48 months
29.20 Western Area Office Meeting Room -The door is inaccessible because it requires twisting to open it. D1 48 months
29.21 Route to Toilet Rooms -The route to the toilet rooms is inaccessible because it is only 33 inches wide at the Good Humor machine. AR3 48 months
29.22 Women's Toilet Room at Gym -Stalls
29.22.a The toilet room sign is inaccessible because its centerline is mounted 57 inches above the finished floor. TR16, TR22 48 months
29.22.b The toilet room is inaccessible because the pressure required to open the door is 15 pounds. D2 48 months
29.22.c There is a 3/4 inch threshold at the door. D23, TR22 48 months
29.22.d Although an audible alarm is provided in this facility, there is no visual alarm appliance in the toilet room. TR21 48 months
29.22.e The lavatory is inaccessible because the hot water pipes are not insulated or otherwise configured to protect against contact. TR12 48 months
29.22.f The toilet is inaccessible because its centerline measures 16 ½ inches from the side wall. ST17, TR22 48 months
29.22.g The toilet is inaccessible because the flush control is on the closed side. ST2, TR22 48 months
29.22.h No accessible coat hook has been provided. TR1 48 months
29.22.i The side grab bar at the toilet is inaccessible because it is obstructed by the toilet paper dispenser. ST9 48 months
29.22.j The rear grab bar at the toilet is inaccessible because it is only 24 inches long. ST4, TR22 48 months
29.23 Men's Toilet Room at Gym -Stalls
29.23.a The toilet room sign is inaccessible because its centerline is 57 inches above the finished floor. TR16, TR22 48 months
29.23.b The toilet room is inaccessible because the pressure required to open the door is 10 pounds. D2 48 months
29.23.c There is a 3/4 inch threshold at the door. D23, TR22 48 months
29.23.d Although an audible alarm is provided in this facility, there is no visual alarm appliance in the toilet room. TR21 48 months
29.23.e The lavatory is inaccessible because the bottom edge of the apron is mounted 28 inches above the finished floor. TR11, TR22 48 months
29.23.f The lavatory is inaccessible because the hot water pipes are not insulated or otherwise configured to protect against contact. TR12 48 months
29.23.g There is no standard accessible stall provided. ST15, TR22 48 months
29.24 Women's Toilet Room at Social Hall -Stalls
29.24.a The toilet room sign is inaccessible because it is mounted 57 inches above the finished floor. TR16 48 months
29.24.b Although an audible alarm is provided in this facility, there is no visual alarm appliance in the toilet room. TR21 48 months
29.24.c The lavatory is inaccessible because the hot water pipes are not insulated or otherwise configured to protect against contact. TR12 48 months
29.24.d There is no standard accessible stall provided. ST15, TR22 48 months
29.25 Men's Toilet Room at Social Hall -Stalls
29.25.a The toilet room sign is inaccessible because it mounted 57 inches above the finished floor. TR16, TR22 48 months
29.25.b Although an audible alarm is provided in this facility, there is no visual alarm appliance in the toilet room. TR21 48 months
29.25.c The lavatory is inaccessible because the hot water pipes are not insulated or otherwise configured to protect against contact. TR12 48 months
29.25.d There is no standard accessible stall provided. ST15, TR22 48 months
30 Judicial Center, 50 Maryland Avenue, Rockville, Maryland
30.1 Assignment Office -The main counter is inaccessible because it is 42 inches above the finished floor. C6 60 months
30.2 Licensing Department -The licensing department is inaccessible because the pressure required to open the door is 14 pounds. D2 60 months
30.3 Cubicle Area in Licensing Department -used by the public -The desks in the cubicle area are inaccessible because they provide only 25 inches of knee space height. T1 60 months
30.4 Telephone Bank -1st Floor -The telephone(s) is inaccessible because there is no volume control and the coin slot is 56 inches above the finished floor. TT1 60 months
30.5 Men's Toilet Room on 1st floor -stalls
30.5.a The toilet room sign is inaccessible because its centerline is mounted 68 inches above the finished floor. TR17 60 months
30.5.b The entrance door to the toilet room is inaccessible because the door opening is only 31 inches wide. D25 60 months
30.5.c The lavatory and towel dispenser are inaccessible because the trash can obstructs them. TR8 60 months
30.5.d The lavatory is inaccessible because the bottom edge of the apron is mounted 28 inches above the finished floor. TR11 60 months
30.5.e The designated accessible toilet stall is inaccessible because the stall measures 55 inches by 59 inches. ST16 60 months
30.5.f The toilet is inaccessible because the flush control is on the closed side. ST2 60 months
30.5.g No accessible coat hook has been provided. TR1 60 months
30.5.h The toilet paper dispenser is inaccessible because it is mounted 38 inches from the rear wall. ST19 60 months
30.5.i The side grab bar at the toilet is inaccessible because it is mounted at 32 ½ inches above the finished floor. ST6, ST12 60 months
30.5.j The rear grab bar at the toilet is inaccessible because it is only 32 inches long and it is mounted 32 inches above the finished floor. ST3 60 months
30.6 Women's Toilet Room on 1st floor -stalls
30.6.a The entrance door to the toilet room is inaccessible because the door opening is only 31 inches wide. D25 60 months
30.6.b The lavatory is inaccessible because the bottom edge of the apron is mounted 28 inches above the finished floor. TR11 60 months
30.6.c The feminine products dispenser is inaccessible because the controls are mounted at 59 inches above the finished floor. TR5 60 months
30.6.d The designated accessible toilet stall is inaccessible because the stall measures 55 inches by 59 inches. ST16 60 months
30.6.e No accessible coat hook has been provided. TR1 60 months
30.6.f The toilet paper dispenser is inaccessible because it is mounted 41 inches above the finished floor, and is mounted 41 inches from the rear wall. ST19 60 months
30.6.g The side grab bar at the toilet is inaccessible because it is mounted at 32 ½ inches above the finished floor. ST6, ST12 60 months
30.6.h There is no rear grab bar provided. ST3 60 months
30.7 Criminal Office -The criminal office is inaccessible because the pressure required to open the door is 14 pounds. D2 60 months
30.8 Central Files -The table in the central files area is inaccessible because the bottom edge of the table apron is 26 ½ inches above the finished floor. TR11 60 months
30.9 Drinking Fountain -1st floor (lower fountain)
30.9.a The drinking fountain is inaccessible because the water flows 4 inches from the front of the fountain. DF7 60 months
30.9.b The drinking fountain protrudes into the walkway and would not be detectable to a blind person using a cane. AR8 60 months
30.10 Drinking Fountain -1st Floor (higher fountain) -The drinking fountain protrudes into the walkway and would not be detectable to a blind person using a cane. AR8 60 months
30.11 Elevators at Lobby -The clearance between the car platform sill and the edge of the hoistway landing is 1 ½ inches. E10 60 months
30.12 Drinking Fountain on 4th Floor -near Jury Room -The drinking fountain is not accessible because the spout is not in the front of the fountain, it is mounted 43 inches from the finished floor, the water flows only 2 inches high, the controls require twisting and require a force greater than 5 pounds to operate. DF1 60 months
30.13 Men's Toilet Room at 4th Floor near Jury Room -Stalls
30.13.a The urinal is inaccessible because the rim is 19 inches above the finished floor. TR20 60 months
30.13.b The designated accessible toilet stall is inaccessible because it measures 54 inches by 59 inches. ST16 60 months
30.13.c The toilet is inaccessible because the flush control is on the closed side. ST2 60 months
30.13.d No accessible coat hook has been provided. TR1 60 months
30.13.e The rear grab bar is mounted at 32 inches above the finished floor. ST12 60 months
30.14 Women's Toilet Room at 4th Floor near Jury Room -Stalls
30.14.a The lavatory is inaccessible because the hot water pipes are not insulated or otherwise configured to protect against contact. TR12 60 months
30.14.b The designated accessible toilet stall is inaccessible because it measures 53 ½ inches by 60 inches. ST16 60 months
30.14.c No accessible coat hook has been provided. TR1 60 months
30.14.d The rear grab bar at the toilet is inaccessible because its closer end is mounted 7 inches from the side wall, and there is 1¾ inches between the bar and the wall. ST3, ST4 60 months
30.15 Courtroom 16
30.15.a Courtroom 16 is inaccessible because the pressure required to open the door is 13 pounds. D2 60 months
30.15.b Although courtroom 16 has an assistive listening system, there is no signage to indicate its availability. AA3 60 months
30.16 Women's Toilet Room in Jury Room in Courtroom 16 -Single User Toilet Room
30.16.a The toilet room sign is inaccessible because its centerline is not mounted 60 inches above the finished floor and there is no symbol of accessibility. TR17 60 months
30.16.b No accessible coat hook has been provided. TR1 60 months
30.16.c The lavatory is inaccessible because the clear floor space is 30 inches by 43 inches, and the turning space is obstructed by a table. TR8, TR19 60 months
30.16.d The toilet is inaccessible because the flush control is on the closed side. SU1 60 months
30.16.e The far end of the side grab bar is 46 ½ inches from the rear wall. SU6 60 months
30.16.f The rear grab bar at the toilet is inaccessible because it is 24 ½ inches long and its far end is only 29 inches from the side wall. ST3, ST4 60 months
30.17 Men's Toilet in Jury Room in Courtroom 16 -Single User Toilet Room
30.17.a The toilet room sign is inaccessible because it is not mounted 60 inches above the finished floor and there is no symbol of accessibility. TR17 60 months
30.17.b No accessible coat hook has been provided. TR1 60 months
30.17.c The lavatory is inaccessible because the clear floor space is 30 inches by 43 inches, and the turning space is obstructed. TR8, TR19 60 months
30.17.d The toilet is inaccessible because the top of the seat is 20 inches above the finished floor. SU18 60 months
30.17.e The far end of the side grab bar is only 48 inches from the rear wall. SU6 60 months
30.17.f The rear grab bar at the toilet is inaccessible because it is 24 ½ inches long and its far end is only 30 inches from the side wall. SU6 60 months
30.18 Courtroom 17 -Designated Accessible -The signage at the women's toilet room in the jury room is inaccessible because it is not mounted on the latch side of the door. TR17 60 months
30.19 Jury Assembly Area -Although the jury assembly area has an assistive listening system, there is no signage to indicate its availability. AA3 60 months
31 Hungerford Office Building, 401 Hungerford Drive, Rockville, MD 20850
31.1 Parking - Although the parking lot provides a designated accessible parking area, the area slopes greater than 2%. P7 12 months
31.2 Front Entrance at Parking Lot
31.2.a There is a greater than 1 inch threshold at the door. D23 12 months
31.2.b The railing next to the Front Entrance protrudes into the walkway and would not be detectable to a blind person using a cane. AR8 12 months
31.3 Volunteer and Community Service Center -Counselor Area -The door is inaccessible because knob hardware is used. D1 60 months
31.4 Volunteer and Community Service Center – Interior Entrance to hallway
31.4.a The pressure required to open the door is 7 pounds. D2 60 months
31.4.b The pull side of the door to the room, which is accessed through a front approach, is inaccessible because it has only 11 3/4 inches of maneuvering space adjacent to the latch side of the door. D6 60 months
31.4.c The push side of the door, which is accessed through a front approach and which has both a closer and a latch, is inaccessible because it has only 11 ½ inches of maneuvering space adjacent to the latch side of the door. D7 60 months
31.5 Visitors Sign-In Desk -The edge of the counter protrudes into the walkway and would not be detectable to a blind person using a cane. AR8 60 months
31.6 Drinking Fountain -Lobby -The drinking fountain is inaccessible because the knee width is 27 inches. DF5 60 months
31.7 Women's Toilet Room -Lobby (1st Floor)
31.7.a There is no accessible signage. TR17 60 months
31.7.b There is no accessible stall provided. ST15 60 months
31.8 Men's Toilet Room - Lobby
31.8.a There is no accessible signage. TR17 60 months
31.8.b The urinal is inaccessible because the rim is 22 inches above the finished floor. TR20 60 months
31.8.c There is no accessible stall provided. ST15 60 months
31.9 Meeting Room - 5th Floor -The pressure required to open the door is 15 pounds. D2 60 months
31.10 Small conference room - 5th Floor -The door is inaccessible because knob hardware is used. D1 60 months
31.11 Drinking Fountain - 5th Floor - The drinking fountain is inaccessible because the knee clearance is 28 inches. DF5 60 months
31.12 Women's Toilet Room - 5th Floor
31.12.a There is no accessible signage. TR17, TR16 60 months
31.12.b The door to the toilet room, which is accessed from a front approach, is inaccessible because it has only13 inches of maneuvering space. D7, TR16 60 months
31.12.c There is no accessible stall provided. ST15, TR16 60 months
31.13 Men's Toilet Room - 5th Floor
31.13.a There is no accessible signage. TR17, TR16 60 months
31.13.b The door to the toilet room, which is accessed from a front approach, is inaccessible because it has only10 ¾ inches of maneuvering space. D7, TR16 60 months
31.13.c The seat cover dispenser is inaccessible because the seat covers are 55 ½ inches above the finished floor. TR4 60 months
31.13.d The lavatory is inaccessible because the bottom edge of the apron is mounted 28 inches above the finished floor. TR11, TR16 60 months
31.13.e The urinal is inaccessible because the rim is 22 ½ inches above the finished floor and it allows only a 29 inch wide clear floor space. TR20, TR16 60 months
31.13.f There is no accessible stall provided. ST15, TR16 60 months
31.14 Elevator - Lobby - The elevator is inaccessible because, after notification, the door starts to close in 3 seconds. E6 60 months
31.15 Small Conference Room - Aging and Disability Services - 4th Floor
31.15.a The door is inaccessible because knob hardware is used. D1 60 months
31.15.b No accessible coat hook has been provided. TR1 60 months
31.16 Drinking Fountain - 4th Floor hallway
31.16.a The drinking fountain is inaccessible because the operating control requires greater than 5 pounds of force. DF2 60 months
31.16.b The drinking fountain is inaccessible because the knee clearance is 27 ¾ inches wide. DF5 60 months
31.17 Women's Toilet Room - 4th Floor (stalls)
31.17.a The toilet room sign is inaccessible because it is mounted on the door and its centerline is mounted 63 ½ inches above the finished floor. TR17 60 months
31.17.b The lavatory is inaccessible because the bottom edge of the apron is mounted 28 ½ inches above the finished floor. TR11 60 months
31.17.c The toilet is inaccessible because the flush control is on the closed side. ST2 60 months
31.18 Men's Toilet Room - 4th floor
31.18.a The toilet room sign is inaccessible because it is mounted on the door and its centerline is mounted at 63 ½ inches above the finished floor. TR17 60 months
31.18.b The lavatory is inaccessible because the bottom edge of the apron is mounted 28 inches above the finished floor. TR11 60 months
31.18.c The toilet is inaccessible because its centerline measures 21 ½ inches from the side wall. ST17 60 months
31.19 Main Counter – Aging and Disability Services 3rd Floor Lobby - The counter protrudes into the walkway and would not be detectable to a blind person using a cane. AR8 60 months
31.20 Conference Room - 301
31.20.a The pressure required to open the door is 13 pounds. D2 60 months
31.20.b The conference room is inaccessible to people with hearing impairments because there is no signage indicating the availability of an assistive listening system. AA3 60 months
31.20.c The coat rack requires a reach of 56 inches above the finished floor to use it. TR1 60 months
31.21 Interview Room #1 - The door is inaccessible because knob hardware is used. D1 60 months
31.22 Interview Room #2 - The door is inaccessible because knob hardware is used. D1 60 months
31.23 Drinking Fountain - 3rd Floor Hallway - The drinking fountain is inaccessible because the knee clearance is 28 inches wide. DF5 60 months
31.24 Women's Toilet Room - 3rd Floor
31.24.a There is no accessible signage. TR17, TR16 60 months
31.24.b The lavatory is inaccessible because the bottom edge of the apron is 28 ½ inches above the finished floor. TR11, TR16 60 months
31.24.c There is no accessible stall provided. ST15, TR16 60 months
31.25 Men's Toilet Room - 3rd Floor
31.25.a There is no accessible signage. TR17, TR16 60 months
31.25.b The pressure required to open the toilet room entrance door is 13 pounds. D2 60 months
31.25.c The pull side of the door to the toilet room, which is accessed through a front approach, is inaccessible because it has only 10 ½ inches maneuvering space on the latch side of the door. D6, TR16 60 months
31.25.d The lavatory is inaccessible because the bottom edge of the apron is 27 ½ inches above the finished floor. TR11, TR16 60 months
31.25.e There is no accessible stall provided. ST15, TR16 60 months
31.26 Drinking Fountain - 2nd Floor - The drinking fountain is inaccessible because the knee clearance is 28 inches wide. DF5 60 months
31.27 Women's Toilet Room - 2nd Floor Hallway
31.27.a The toilet room sign is inaccessible. TR17, TR16 60 months
31.27.b The pressure required to open the toilet room entrance door is 14 pounds. D2 60 months
31.27.c The pull side of the door to the toilet room, which is accessed through a front approach, is inaccessible because it has only 14 ½ inches maneuvering space on the latch side of the door. D6, TR16 60 months
31.27.d There is a 3/4 inch threshold at the door, and there is no bevel at this location. D23 60 months
31.27.e The lavatory is inaccessible because the bottom edge of the apron is 28 ¼ inches above the finished floor. TR11, TR16 60 months
31.27.f There is no accessible stall provided. ST15, TR16 60 months
31.28 Men's Toilet Room - 2nd Floor Hallway
31.28.a The toilet room sign is inaccessible. TR17, TR16 60 months
31.28.b The pressure required to open the toilet room entrance door is 12 pounds. D2 60 months
31.28.c The pull side of the door to the toilet room, which is accessed through a front approach, is inaccessible because it has only 10 1/4 inches maneuvering space on the latch side of the door. D6, TR16 60 months
31.28.d There is a 3/4 inch threshold at the door, and there is no bevel at this location. D23 60 months
31.28.e The seat cover dispenser is inaccessible because the seat covers are 58 inches above the finished floor. TR4 60 months
31.28.f The lavatory is inaccessible because the bottom edge of the apron is 28 inches above the finished floor. TR11, TR16 60 months
31.28.g The urinal is inaccessible because the rim is 22 ½ inches above the finished floor and it allows only a 29 inch wide clear floor space. TR20, TR16 60 months
31.28.h There is no accessible stall provided. ST15, TR16 60 months
31.29 Conference Room - 1st Floor - The pressure required to open the entrance door is 16 pounds. D2 60 months
32 Avery Road 701
32.1 Main Entrance
32.1.a The pressure required to open the interior entrance door is 10 pounds. D2 36 months
32.1.b The entrance vestibule is 24 inches wide between both doors when open. D3 36 months
32.2 Women's Lobby Single-User Toilet Room
32.2.a The toilet room sign is mounted on the door and has no raised or Braille characters. TR17 36 months
32.2.b The feminine products dispenser requires twisting to operate. TR10 36 months
32.2.c The soap dispenser is inaccessible because the controls are mounted at 49½ inches above the finished floor over the lavatory. TR4 36 months
32.2.d The toilet has insufficient clear floor space due to the placement of the drawer unit. SU16 36 months
32.2.e The rear grab bar at the toilet is 24 inches long and is mounted 7 inches from the near side wall. SU3, TR16 36 months
32.3 Men's Lobby Single-User Toilet Room
32.3.a The toilet room sign is mounted on the door and has no raised characters or Braille. TR17 36 months
32.3.b The pressure required to open the door is 12 pounds. D2 36 months
32.3.c There is a 1 inch threshold at the door. D23, TR16 36 months
32.3.d No accessible mirror has been provided. TR14 36 months
32.3.e The lavatory hot water pipes are not insulated or otherwise configured to protect against contact. TR12 36 months
32.3.f The lavatory has twist faucets. TR10 36 months
32.3.g The urinal rim is 22 inches high and the flush control is 51 inches high. TR20, TR16 36 months
32.3.h The toilet stall has no accessible features. ST14, TR16 36 months
32.4 Lobby Drinking Fountain
32.4.a The wall-mounted drinking fountain is inaccessible because it has 29 inches of clear knee width. DF5 36 months
32.4.b Although a designated accessible drinking fountain is provided, there is no drinking fountain provided for people who have difficulty bending or stooping. DF3 36 months
32.5 Offices throughout the facility - The office doors throughout the facility have knob hardware. D1 36 months
32.6 Dining Area - The coat hooks are mounted 60 inches high. TR1 36 months
32.7 Laundry - The dryers have twist hardware. MC1, GC1 36 months
32.8 Typical Accessible Room #1
32.8.a The door has knob hardware. D1 36 months
32.8.b The pressure required to open the door is 10 pounds. D2 36 months
32.8.c The room temperature controls have twist hardware. MC1, GC1 36 months
32.8.d The rooms do not have visual alarms connected to the building emergency alarm system or have an acceptable alternative alarm. TR21 36 months
32.8.e The highest washer/dryer controls are 57 inches high. MC1, GC1 36 months
32.9 Typical Accessible Room #2
32.9.a The door has knob hardware. D1 36 months
32.9.b The room temperature controls have twist hardware. MC1, GC1 36 months
32.9.c The light switch is 55½ inches high. TR5 36 months
32.9.d The clothes rod in the closet is 66 inches high. TR5 36 months
32.10 Rear Patio
32.10.a The patio door has a 1 inch threshold. D23 36 months
32.10.b The 5 inch high ramp to the patio has no edge protection, the slope is 11.2%, and the top landing is 45 inches deep. R3 36 months
33 Avery House 705
33.1 Parking -The parking reserved for persons with disabilities slopes 5.8% and the access aisle slopes 4.8%. P7 36 months
33.2 Exterior Accessible Route
33.2.a The curb ramp from the parking lot onto the sidewalk has flared sides that slope 39.2% on one side and 39.8% on the other side. AR1, AR5 36 months
33.2.b The sidewalk portion immediately after the curb ramp slopes 8.2% and has no ramp features. Where the route slopes more than 5%, provide a ramp that is at least 36 inches wide and has a slope not exceeding 8.33% and a cross slope not exceeding 2%. AR1 36 months
33.3 Entrance -The fire extinguisher and child's coat rack inside the main entrance protrude into the walkway and would not be detectable to a blind person using a cane. AR8 36 months
33.4 Bedroom #3
33.4.a The bedroom entrance door has knob hardware. D1 36 months
33.4.b The clothes rod in the closet is 76 inches high. TR5 36 months
33.4.c The desk is 25¼ inches high to the bottom. T1 36 months
33.4.d The shower is 35 by 34½ inches, the transfer seat is 21½ inches high, there is no grab bar on the control wall, the existing grab bar is mounted 37½ inches high, there is only a fixed shower head mounted higher than 48 inches, and the curb is higher than ½ inch. B8 36 months
33.4.e The bathtub is inaccessible because the higher grab bars are mounted 32 inches high, the lower grab bar is mounted 7 inches above the rim of the tub, and there is no seat. B6 36 months
33.5 Single-User Toilet Room in Room 3
33.5.a Although the facility contains an emergency alarm system, there is no visual alarm in this toilet room. TR21 36 months
33.5.b The lavatory is 36 inches high to the top of the rim. TR11 36 months
33.5.c The lavatory is inaccessible because the hot water pipes are not insulated or otherwise configured to protect against contact. TR12 36 months
33.5.d The toilet flush control is on the closed side. SU1 36 months
33.5.e The rear grab bar at the toilet is 24 inches long. SU3 36 months
33.6 Interior Accessible Route from Bedroom #3 to Living Room
33.6.a The fire extinguisher in the hallway protrudes into the walkway and would not be detectable to a blind person using a cane. AR8 36 months
33.6.b The route through the fire door narrows to 27 inches wide where the lectern is placed in the hallway. AR3 36 months
33.6.c The door from the hallway to the living room requires 12 pounds of force to open. D2 36 months
33.6.d The push side of the exit door, which is accessed through a front approach and which has both a closer and a latch, is inaccessible because it has only 1 or 2 inches of clearance on the latch side. D7 36 months
33.7 Rear Patio - The route to the rear patio door narrows to 26½ inches wide at the couches in the living room. AR3 36 months
33.8 Dining Room - The microwave is located with its highest controls 51 inches high over a 6 inch deep obstruction. TR4 36 months
33.9 Kitchen - The door has a clear opening width of only 31 inches. D25 36 months
33.10 Telephone - The pay telephone near the offices has insufficient clear floor space. TT1 36 months
33.11 Offices - The pull side of the door to Office 2, which is accessed through a front approach, is inaccessible because it has inadequate maneuvering space on the latch side. D6, AR9 36 months
34 Longwood Community Center, 19300 Georgia Avenue, Brookeville, Maryland 20833
34.1 Parking
34.1.a The parking lot, with a total of approximately 98 parking spaces, is inaccessible because there is no van accessible parking space, the designated accessible parking spaces are all between 91 and 93 inches wide, 3 of the spaces have no vertical signage, and 2 of the spaces have cross slopes of 2.1% to 2.7% and share an access aisle with a cross slope of 3.2%. This lot requires 1 van accessible space and 3 standard accessible spaces. P3 48 months
34.1.b Three of the four curb ramps have slopes of 9.6%, 10.6%, and 14.7%, respectively, and the flared sides of all four slope 10.4%, 10.6%, 12.2.%, and 13.9%, respectively. In addition, no detectable warnings / contrast is provided. AR5 48 months
34.2 Accessible Exterior Route - The route from the sidewalk to the entrance has a slope of 8.3% and a cross slope of 5.4%, and it does not have any ramp features. AR1 48 months
34.3 Telephone - The pay phone in the lobby has clear floor space 13½ inches wide and 32 inches deep, the highest operable part is 56½ inches high, and there is no volume control. TT1 48 months
34.4 Platform Lift - The interior of the lift is 33½ inches wide by 42 inches deep. LF2 48 months
34.5 Men's Toilet Room with Stalls
34.5.a The toilet room sign is mounted on the door. TR16, TR17 48 months
34.5.b The pressure required to open the door is 15 pounds. D2 48 months
34.5.c The lavatory is 26½ inches high to the bottom of the apron. TR11, TR16 48 months
34.5.d The lavatory has twist faucets. TR10 48 months
34.5.e There is no accessible stall provided. ST15, TR16 48 months
34.6 Women's Toilet Room with Stalls
34.6.a The toilet room sign is mounted on the door. TR17, TR16 48 months
34.6.b The pressure required to open the door is 10 pounds. D2 48 months
34.6.c The lavatory is 27 inches high to the bottom of the apron. TR11, TR16 48 months
34.6.d The lavatory has twist faucets. TR10 48 months
34.6.e There is no accessible stall provided. ST15, TR16 48 months
34.7 Drinking Fountains
34.7.a The drinking fountain near the weight room has a spout that is 37 inches above the finished floor. DF6 48 months
34.7.b Although accessible drinking fountains are provided, there is no drinking fountain provided for people who have difficulty bending or stooping. DF3 48 months
34.8 Multi-Purpose Room -The counter is 42 inches high. C6 48 months
34.9 Women's Single-User Toilet Room in Multi-Purpose Room
34.9.a The toilet room sign is mounted on the door. TR17, TR16, TR22 48 months
34.9.b The pressure required to open the door is 14 pounds. D2 48 months
34.9.c The pull side of the door, which is accessed through a front approach, has only one or two inches of maneuvering space on the latch side. D6,TR16, TR22 48 months
34.9.d Although the facility contains an emergency alarm system, there is no visual alarm appliance in the toilet room. TR21 48 months
34.9.e There is insufficient turning space within the toilet room. TR19,TR16, TR22 48 months
34.9.f The air dryer protrudes into the walkway and would not be detectable to a blind person using a cane. AR8 48 months
34.9.g The lavatory is 26½ inches high to the bottom of the apron. TR11,TR16, TR22 48 months
34.9.h The toilet flush control is on the closed side. SU1 48 months
34.9.i The side grab bar is inaccessible because the toilet paper dispenser is mounted less than 18 inches above it. SU8 48 months
34.9.j The far end of the side grab bar at the toilet is 52 inches from the rear wall. SU6 48 months
34.10 Men's Single-User Toilet Room in the Multi-Purpose Room
34.10.a The toilet room sign is mounted on the door. TR17,TR16, TR22 48 months
34.10.b The pressure required to open the door is 13 pounds. D2 48 months
34.10.c The pull side of the door, which is accessed through a front approach, has only one or two inches of maneuvering space on the latch side. D6,TR16, TR22 48 months
34.10.d Although the facility contains an emergency alarm system, there is no visual alarm appliance in the toilet room. TR21 48 months
34.10.e There is insufficient turning space within the toilet room. TR19,TR16, TR22 48 months
34.10.f The air dryer protrudes into the walkway and would not be detectable to a blind person using a cane. AR8 48 months
34.10.g The lavatory is 27 inches high to the bottom of the apron. TR11,TR16, TR22 48 months
34.10.h The side grab bar is inaccessible because the toilet paper dispenser is mounted less than 18 inches above it. SU8 48 months
34.10.i The far end of the side grab bar at the toilet is 52 inches from the rear wall. SU6 48 months
35 Olney Swim Center, 16601 Georgia Avenue, Olney, Maryland 20832
35.1 Parking -The parking lot, with a total of approximately 208 parking spaces, is inaccessible because there are only 6 spaces designated as accessible, these spaces are between 88 and 94 inches wide, and there is no van accessible sign posted at the van accessible space. This lot requires 1 van accessible space and 6 standard accessible spaces. P3 36 months
35.2 Exterior Accessible Route -The route from the designated accessible parking spaces to the entrance has a slope of 10.5% and a cross slope of 4.9%. AR1 36 months
35.3 Interior Accessible Route
35.3.a The pay telephone protrudes into the walkway and would not be detectable to a blind person using a cane. AR8 36 months
35.3.b On the route to the locker rooms, the key boxes protrude into the walkway and would not be detectable to a blind person using a cane. AR8 36 months
35.4 Women's Toilet Room with Stalls near Lobby
35.4.a The toilet room sign is mounted 57 inches above the finished floor. TR17 36 months
35.4.b The pressure required to open the entrance door is 10 pounds. D2 36 months
35.4.c The lavatory is 28 inches high to the bottom of the apron. TR11 36 months
35.4.d No accessible coat hook has been provided. TR1 36 months
35.4.e The side grab bar is inaccessible because the toilet paper dispenser is mounted less than 18 inches above it. ST9 36 months
35.4.f The side grab bar at the toilet is mounted with the near end 14 inches from the rear wall. ST7 36 months
35.4.g The rear grab bar at the toilet is mounted ¾ inch above the toilet pipes. ST5 36 months
35.5 Men's Toilet Room with Stalls near Lobby
35.5.a The toilet room sign is mounted 61½ inches high and is mounted on the hinge side of the door. TR17 36 months
35.5.b The pressure required to open the door is 10 pounds. D2 36 months
35.5.c The soap dispenser is mounted over the sink 49 inches high with only a forward reach. TR4 36 months
35.5.d The urinal rim is 25 inches high and the flush is 52 inches high. TR20 36 months
35.5.e No accessible coat hook has been provided. TR1 36 months
35.5.f The side grab bar is inaccessible because the toilet paper dispenser is mounted less than 18 inches above it. ST9 36 months
35.5.g The rear grab bar at the toilet is mounted with the near end 7½ inches from the side wall. ST4 36 months
35.5.h The rear grab bar at the toilet is mounted ¾ inch above the toilet pipes. ST5 36 months
35.6 Men's Locker Room
35.6.a The toilet room sign is mounted 56 inches above the finished floor. TR17 36 months
35.6.b The pressure required to open the door is 12 pounds. D2 36 months
35.6.c The soap dispenser is mounted over the sink at 49 inches high. TR4 36 months
35.6.d The urinal rim is 19 inches high. TR20 36 months
35.6.e No accessible coat hook has been provided, either in the designated accessible stall or by the drinking fountain. TR1 36 months
35.6.f The side grab bar is inaccessible because the toilet paper dispenser is mounted less than 18 inches above it, and it is mounted with its near end 13 inches from the rear wall. ST9, ST7 36 months
35.6.g The rear grab bar at the toilet is mounted ¾ inch above the flush. ST5 36 months
35.6.h The roll-in shower has a grab bar mounted behind the seat, the shower spray unit must be hand held, and the shower spray unit hose is 34 inches long. B8 36 months
35.6.i The benches are 9½ inches wide. L1 36 months
35.6.j Although an accessible drinking fountain is provided in the locker room, there is no drinking fountain provided for people who have difficulty bending or stooping. DF3 36 months
35.6.k The drinking fountain protrudes into the walkway and would not be detectable to a blind person using a cane. AR8 36 months
35.7 Women's Locker Room
35.7.a The toilet room sign is mounted 56 inches high and is mounted on the hinge side of the door. TR17 36 months
35.7.b The pressure required to open the door is 10 pounds. D2 36 months
35.7.c Although the facility contains an emergency alarm system, there is no visual alarm in this locker room. TR21 36 months
35.7.d The soap dispenser is mounted over the sink at 49½ inches high. TR5 36 months
35.7.e The lavatory is 28 inches high to the bottom of the apron, and there is insufficient knee clearance. TR11 36 months
35.7.f No accessible coat hook has been provided. TR1 36 months
35.7.g The toilet is inaccessible because the top of the seat is 20 inches above the finished floor. ST20 36 months
35.7.h The side grab bar is inaccessible because the toilet paper dispenser is mounted less than 18 inches above it. ST9 36 months
35.7.i The rear grab bar at the toilet is mounted ¾ inch above the toilet pipes, and the near end is mounted 7 inches from the side wall. ST4, ST5 36 months
35.7.j The transfer shower has a seat that is 16 inches high and 32½ inches long, the shower spray unit must be hand held, and the shower spray unit hose is 34 inches long. B8 36 months
35.7.k The benches are 9½ inches wide. L1 36 months
35.7.l Although an accessible drinking fountain is provided in the locker room, there is no drinking fountain provided for people who have difficulty bending or stooping. DF3 36 months
35.8 "Special Changing Room"
35.8.a The toilet room sign is mounted 56 inches above the finished floor. TR17, TR16 36 months
35.8.b The pressure required to open the door is 12 pounds. D2 36 months
35.8.c Although the facility contains an emergency alarm system, there is no visual alarm in this locker room. TR21 36 months
35.8.d The toilet is inaccessible because its centerline measures 19 inches from the side wall. ST17, TR16 36 months
35.8.e The toilet flush control is on the closed side. ST2, TR16 36 months
35.8.f The rear grab bar at the toilet is 24 inches long, it is mounted 7 inches from the near side wall, and there is ¾ inch between the bar and the toilet pipes. ST4, ST5, TR16 36 months
35.8.g The transfer shower has a seat that is 16½ inches high and 34 inches long, and the shower spray unit is fixed at 64 inches high. B8, TR16 36 months
35.8.h The bench is 23 inches high. L1, TR16 36 months
35.9 Pool Drinking Fountains
35.9.a Although there are 4 drinking fountains in the pool room, two of the fountains have spouts 37 and 38½ inches high, two have water that flows 1 and 3 inches high, all have controls that require 7, 10, 12, or 30 pounds to operate, and none is accessible to people who have difficulty bending or stooping. Provide 2 drinking fountains DF1 36 months
35.9.b All of the drinking fountains protrude into the walkway and would not be detectable to a blind person using a cane. AR8 36 months
35.10 Weight Room
35.10.a The pressure required to open the door is 8 pounds. D2 36 months
35.10.b Although an accessible drinking fountain is provided, there is no drinking fountain provided for people who have difficulty bending or stooping. DF3 36 months
35.11 Drinking Fountain near Snack Machines -Although there is a drinking fountain provided, the spout is 38 inches high, the controls require 7 pounds of force to operate, and there is no fountain accessible to people who have difficulty bending or stooping. DF1 36 months
35.12 Multi-Purpose Room
35.12.a The pressure required to open the door is 10 pounds. D2 36 months
35.12.b The television is mounted with less than 80 inches of head room below it. AR7 36 months
36 District Courthouse, 27 Courthouse Square, Rockville, Maryland
36.1 Accessible Route from Parking Area (parking lot shared with Red Brick Courthouse)
36.1.a The curb ramp at Maryland Avenue slopes 13.3%. MC3, AR5 60 months
36.1.b The curb ramp at E. Montgomery Avenue slopes 10.5%. MC3, AR5 60 months
36.1.c The route from the parking area to the entrance is inaccessible because the sidewalk has a slope of 5.8%. MC3, AR1 60 months
36.2 Accessible Route / Curb Ramp at S. Washington and E. Montgomery
36.2.a The flared side of the curb ramp at S. Washington slopes 13.4%. MC3, AR5 60 months
36.2.b The curb ramp at Montgomery Avenue slopes 9.1% and has a flared side that slopes 10.8%. MC3, AR5 60 months
36.2.c The route to the building via S. Washington is inaccessible because the bricks are damaged and have changes in level up to 1 inch AR1 60 months
36.3 Accessible Route using W. Jefferson Street
36.3.a The curb ramp at W. Jefferson is inaccessible because it slopes 11% and has a cross slope of 6.3%, there is a 1 ¼ change in level at the ramp transition, and the gutter at the curb cut slopes 8.4%. MC3, AR5 60 months
36.3.b The slope at the top of the curb ramp slopes 9.4% and has a cross slope of 2.6%. MC3, AR5 60 months
36.4 Jefferson Street Entrance - The route to enter this building is inaccessible because the route through the security scanner is only 31 inches wide, and the route around the security scanner is only 28 ½ inches wide. AR3 60 months
36.5 VOP (Violation of Probation) Office - First Floor - The suggestion lock box protrudes 9 ½ inches into the walkway with its leading edge 47 ¼ inches above the finished and would not be detectable to a blind person using a cane. AR8 60 months
36.6 Parole and Probation Intake Office 1
36.6.a The parole and intake office (one) is inaccessible because the pressure required to open the door is 17 pounds. D2 60 months
36.6.b The door is inaccessible because knob hardware is used. D1 60 months
36.7 Parole and Probation Intake Office 2
36.7.a The parole and probation intake office (two) is inaccessible because the pressure required to open the door is 10 pounds. D2 60 months
36.7.b The door is inaccessible because knob hardware is used. D1 60 months
36.8 Drinking Fountain Near VOP - The water at the drinking fountain only flows 3 inches high. DF7 60 months
36.9 Men's Toilet Room Near VOP - Stalls
36.9.a The toilet room sign is inaccessible because it is not mounted on the latch side of the door. TR17 60 months
36.9.b The toilet room is inaccessible because the pressure required to open the door is 10 pounds. D2 60 months
36.9.c The towel dispenser is inaccessible because the controls are mounted 63 inches above the finished floor over the trash can. TR4 60 months
36.9.d The lavatory is inaccessible because the bottom edge of the apron is mounted 28 ½ inches above the finished floor. TR11 60 months
36.9.e The toilet is inaccessible because the flush control is on the closed side. ST2 60 months
36.9.f No accessible coat hook has been provided. TR1 60 months
36.9.g The side grab bar at the toilet is inaccessible because it is obstructed by the toilet paper dispenser. ST9 60 months
36.9.h The rear grab bar at the toilet is inaccessible because there is only ¾ inch between it and the flush fixture. ST5 60 months
36.10 Women's Toilet Room Near VOP - Stalls
36.10.a The toilet room sign is inaccessible because it is not mounted on the latch side of the door. TR17 60 months
36.10.b The toilet room is inaccessible because the pressure required to open the door is 10 pounds. D2 60 months
36.10.c The seat cover dispenser is inaccessible because the seat covers are 61 inches above the finished floor. TR4 60 months
36.10.d The towel dispenser is inaccessible because the controls are mounted 63 inches above the finished floor. TR5 60 months
36.10.e The sanitary napkin dispenser is inaccessible because the controls are mounted 60 inches above the finished floor. TR5 60 months
36.10.f The toilet is inaccessible because its centerline measures 17 inches from the side wall. ST17 60 months
36.10.g No accessible coat hook has been provided. TR1 60 months
36.10.h The side grab bar at the toilet is inaccessible because the toilet paper dispenser interferes with its usage. ST9 60 months
36.10.i The side grab bar at the toilet is inaccessible because it is 36 inches long. ST7 60 months
36.10.j The rear grab bar at the toilet is inaccessible because its closer end is 7 inches from the side wall. ST7 60 months
36.10.k The rear grab bar at the toilet is inaccessible because there is only ¾ inch between it and the rear wall. ST6 60 months
36.11 Elevators at First Floor
36.11.a The elevator is inaccessible because, although the car control buttons are designated with raised characters, the is no Braille provided. E4 60 months
36.11.b The elevator is inaccessible because, although emergency communications are provided, tight grasping or pinching is required to open the emergency compartment door. E8 60 months
36.12 TTY's - Although there are more than 4 public telephones provided in the building, a TTY is not provided. TT2 60 months
36.13 Telephone on 1st floor - Courtroom Waiting Area
36.13.a The telephone is inaccessible because there is no volume control. TT1 60 months
36.13.b The telephone protrudes 7 inches into the walkway and would not be detectable to a blind person using a cane. AR8 60 months
36.14 Telephone on 3rd floor - Courtroom Waiting Area at 303 and 304 -The telephone is inaccessible because there is no volume control. TT1 60 months
36.15 Drinking Fountain - near courtroom 303 and 304 -The water at the drinking fountain only flows 3 inches high. DF7 60 months
36.16 Men's Toilet Room near Courtroom 303 and 304 - Stalls
36.16.a The toilet room lacks accessible signage. TR17 60 months
36.16.b The toilet room is inaccessible because the pressure required to open the door is 10 pounds. D2 60 months
36.16.c The door is inaccessible because knob hardware is used. D1 60 months
36.16.d The towel dispenser is inaccessible because the controls are mounted 56 inches above the finished floor. TR5 60 months
36.16.e The lavatory is inaccessible because the hot water pipes are not insulated or otherwise configured to protect against contact. TR12 60 months
36.16.f There is no accessible stall provided. ST15 60 months
36.17 Women's Toilet Room near Courtroom 303 and 304 - Stalls
36.17.a The toilet room lacks accessible signage. TR17 60 months
36.17.b The toilet room is inaccessible because the pressure required to open the door is 10 pounds. D2 60 months
36.17.c The door is inaccessible because knob hardware is used. D1 60 months
36.17.d The towel dispenser is inaccessible because the controls are mounted 57 inches above the finished floor. TR5 60 months
36.17.e The lavatory is inaccessible because the bottom edge of the apron is mounted 28 ½ inches above the finished floor. TR11 60 months
36.17.f The lavatory is inaccessible because the hot water pipes are not insulated or otherwise configured to protect against contact. TR12 60 months
36.17.g The toilet is inaccessible because its centerline measures 18 ½ inches from the side wall. ST17 60 months
36.17.h No accessible coat hook has been provided. TR1 60 months
36.17.i The side grab bar at the toilet is inaccessible because it is not mounted 33 to 36 above the finished floor, the farther end is 50 inches from the rear wall, and there are items that interfere with its usage. ST6 60 months
36.17.j The rear grab bar at the toilet is inaccessible because it is angled. ST3 60 months
36.18 Telephone - 2nd Floor Courtroom Waiting Area
36.18.a The telephone is inaccessible because the coin slot is 56 inches above the finished floor and there is no volume control. TT1 60 months
36.18.b The telephone protrudes 11 inches into the walkway with its leading edge 29 inches above the finished and would not be detectable to a blind person using a cane. AR8 60 months
36.19 Drinking Fountain by Landlord Tenant Office
36.19.a The water at the drinking fountain only flows 2 inches high. DF7 60 months
36.19.b The drinking fountain is inaccessible because the trash can below the drinking fountain obstructs the knee clearance. DF5 60 months
36.20 Men's Toilet Room by Landlord Tenant Office - Stalls
36.20.a The toilet room is inaccessible because the pressure required to open the door is 12 pounds. D2 60 months
36.20.b The toilet is inaccessible because the flush control is on the closed side. ST2 60 months
36.20.c The side grab bar at the toilet is inaccessible because the farther end is 50 inches from the rear wall, and the toilet paper dispenser obstructs its usage. ST7, ST9 60 months
36.20.d The rear grab bar at the toilet is inaccessible because its closer end is 12 inches from the side wall. ST4 60 months
36.21 Women's Toilet Room by Landlord Tenant Office -Stalls
36.21.a The toilet room sign is inaccessible because it is mounted on the door and its centerline is 62 inches from the finished floor. TR17 60 months
36.21.b The toilet room is inaccessible because the pressure required to open the door is 10 pounds. D2 60 months
36.21.c No accessible mirror has been provided. TR14 60 months
36.21.d The lavatory is inaccessible because the hot water pipes at the lower mirror are not insulated or otherwise configured to protect against contact. TR12 60 months
36.21.e The lavatory is inaccessible because the bottom edge of the apron is mounted 28 inches above the finished floor. TR11 60 months
36.21.f The toilet is inaccessible because its centerline measures 20 inches from the side wall. ST17 60 months
36.21.g The side grab bar is inaccessible because the toilet paper dispenser is mounted too close. ST9 60 months
36.21.h The rear grab bar at the toilet is inaccessible because it is mounted at an angle. ST3 60 months
36.22 Telephone on 2nd Floor across from elevators - The telephone is inaccessible because there is no volume control. TT1 60 months
36.23 Drinking Fountain - 2nd Floor
36.23.a The drinking fountain has a spout that is 39 inches above the finished floor. DF6 60 months
36.23.b The drinking fountain protrudes 19 inches into the walkway with its leading edge 30 inches above the finished and would not be detectable to a blind person using a cane. AR8 60 months
36.24 Alternative Dispute Resolution Office
36.24.a The door is inaccessible because knob hardware is used and it is mounted higher than 48 inches above the finished floor. D1 60 months
36.24.b The push side of the door, which is accessed from the latch side of the door, is inaccessible because it has inadequate maneuvering space. D11 60 months
36.24.c There is an inaccessible threshold at the door. D23 60 months
36.25 District Court Commissioners Office
36.25.a The door is inaccessible because the pressure required to open the door is greater than 5 pounds. D2 60 months
36.26 Civil Office
36.26.a The door is inaccessible because it has an opening width of only 27 inches per leaf. D24 60 months
36.26.b The civil office is inaccessible because the pressure required to open the door is 6 pounds. D2 60 months
36.26.c The door is inaccessible because knob hardware is used. D1 60 months
36.26.d The counter is inaccessible because it is 43 inches above the finished floor. C6 60 months
36.27 Adult Courtroom 2 (Room 302)
36.27.a The Adult Courtroom # 2 is inaccessible because the pressure required to open the door is 12 pounds. D2 60 months
36.27.b The door hardware is inaccessible. D1 60 months
36.27.c Although an audible alarm is provided in this facility, there is no visual alarm appliance in the court room. TR21 60 months
36.27.d There is no designated accessible seating in the spectator section of the courtroom. AA6 60 months
36.27.e The witness stand is inaccessible because there is a step up to the stand. AA8 60 months
36.28 Adult Courtroom # 4 (Room 202)
36.28.a The Adult Courtroom # 4 is inaccessible because the pressure required to open the door is 14 pounds. D2 60 months
36.28.b The door hardware is inaccessible. D1 60 months
36.28.c The Adult Courtroom # 4 is inaccessible to people with hearing impairments because there is no assistive listening system. AA5 60 months
36.28.d Although an audible alarm is provided in this facility, there is no visual alarm appliance in the court room. TR21 60 months
36.28.e There is no designated accessible seating in the spectator section of the courtroom. AA6 60 months
36.28.f The witness stand is inaccessible because there are steps up to the stand. AA8 60 months
36.29 Adult Courtroom # 6 (Room 101)
36.29.a The Adult Courtroom # 6 is inaccessible because the pressure required to open the door is 10 pounds. D2 60 months
36.29.b The door is inaccessible because knob hardware is used. D1 60 months
36.29.c Although the Adult Courtroom # 6 has an assistive listening system, there is no signage indicating its availability. AA3 60 months
36.29.d Although an audible alarm is provided in this facility, there is no visual alarm appliance in the courtroom. TR21 60 months
36.29.e There is no designated accessible seating in the spectator section of the courtroom. AA6 60 months
36.29.f The witness stand is inaccessible because there are steps up to the stand. AA8 60 months
36.30 Courtroom # 18 -Although Courtroom # 18 has an assistive listening system, there is no signage indicating its availability. AA3 60 months
36.31 Sally Port Ramp -The sally port ramp is inaccessible because it slopes 21%, the landing is 50 inches by 50 inches, there is no handrail, and there are drop off sides without edge protection. R3 60 months
36.32 Female Juvenile Cell
36.32.a The bench is 14 inches deep. L1 60 months
36.32.b The side grab bar at the toilet is inaccessible because it is 36 inches long and 32 inches above the finished floor. SU5 60 months
36.32.c There is no rear grab bar provided. SU2 60 months
36.33 Male Juvenile Cell
36.33.a The bench is 14 inches deep. L1 60 months
36.33.b The side grab bar at the toilet is inaccessible because it is 36 inches long and 32 inches above the finished floor. SU5 60 months
36.33.c There is no rear grab bar provided. SU2 60 months
36.34 Adult Holding Cells -The door immediately off the elevator leading to all adult holding cells is inaccessible because it has an opening width of only 30 inches. D25 60 months
36.35 Male Adult Holding Cell
36.35.a The second door is inaccessible because it has an opening width of only 30 inches. D25 60 months
36.35.b The toilet is inaccessible because the top of the seat is 15 inches above the finished floor. SU18 60 months
36.35.c No grab bars are provided. SU10 60 months
36.35.d The lavatory is inaccessible because there is no knee clearance. TR11 60 months
36.36 Female Adult Holding Cell
36.36.a The door to the cell is inaccessible because it has an opening width of only 17 inches. D25 60 months
36.36.b The toilet is inaccessible. SU13 60 months
36.36.c No grab bars are provided. SU10 60 months
36.36.d There is insufficient turning space within the toilet room. TR19 60 months
37 Council Office Building - GARAGE, 100 Maryland Avenue, Rockville MD 20850
37.1 Parking - Level 1 (PUBLIC PARKING)(A/B) -The parking reserved for persons with disabilities lacks appropriate signage at space #4 (to the right of the entrance). Built-up curb ramps - Several built-up curb ramps on the entrance level along the routes between the accessible parking spaces and the street exceed the maximum allowable ramp slope. The 2nd ramp slopes 9.5%, the 3rd ramp slopes 10.7%, and the 4th ramp slopes 11.8%, and are inaccessible. P6, AR5 18 months
38 Parking Garage #7, Cameron and Fenwick Streets, Silver Spring, Maryland
38.1 Parking Spaces
38.1.a This garage has approximately 1280 parking spaces. There are 24 designated standard accessible parking spaces having various inaccessible features. There are no van accessible spaces, some of the access aisles are less than 60 inches wide, the cross slope for the existing spaces and access aisles are as much as 5.9%, some of the signs are mounted too low, and the vertical clearance is 87 inches high. This lot requires at least 3 van accessible spaces and 21 standard accessible spaces. MC2 36 months
38.1.b The valves next to the garage entrance / exit stairway doors protrude into the walkway and would not be detectable to a blind person using a cane. AR8 36 months
38.2 Elevator - Car 3
38.2.a The elevator is inaccessible because the hall call buttons are centered 44 inches above the finished floor. E3 36 months
38.2.b The elevator is inaccessible because the hoistway signage does not include Braille characters. E12 36 months
38.2.c The clearance between the car platform sill and the edge of the hoistway landing is 1 ½ inches. E10 36 months
38.2.d The elevator is inaccessible because there are no Braille characters provided adjacent to the car control buttons. E4 36 months
38.2.e The elevator is inaccessible because, although emergency communications are provided, the centerline of the emergency control buttons is 24 inches above the elevator floor. E9 36 months
38.2.f The elevator is inaccessible because there is no audible floor indication. E5 36 months
38.3 Ramp at Exit to Cameron Street - The ramp at the exit to Cameron Street is inaccessible because there is no level landing at the top, the handrails are 31 inches high and not continuous on both sides, there are no 12 inch extensions, and there are 2 inches between handrail and wall. R3 36 months
39 Kensington Volunteer Fire Department, Station 25, 14401 Connecticut Avenue, Kensington, Maryland
39.1 Parking
39.1.a The parking lot, with a total of approximately 28 parking spaces, is inaccessible because there is no van accessible space provided and no signage to indicate the accessible spaces. This lot requires 1 van accessible space and 1 standard accessible space. P3 60 months
39.1.b The built-up curb ramp impermissibly extends into the accessible parking spaces' shared access aisle. AR5 60 months
39.1.c The curb ramp is inaccessible because it has a cross slope of 2.2%. AR5 60 months
39.2 Route from Parking to Entrance - The route from the parking area to the entrance is inaccessible because it slopes 6.2% with no ramp features. AR1 60 months
39.3 Entrance near Garages
39.3.a The entrance is inaccessible because there is a slope of 7.2% within the door's required maneuvering clearance. D13 60 months
39.3.b There is a change in level greater than ½ " high without a bevel at the threshold to the door. D23 60 months
39.4 Toilet Room near Front Lobby - Single User
39.4.a The signage is inaccessible because there are no Braille characters or symbol of accessibility. TR17 60 months
39.4.b The pressure required to open the toilet room entrance door is 11 pounds. D2 60 months
39.4.c The door is inaccessible because knob hardware is used. D1 60 months
39.4.d No accessible mirror has been provided. TR14 60 months
39.4.e The lavatory is inaccessible because the bottom edge of the apron is mounted 27 ½ inches above the finished floor. TR11 60 months
39.4.f The lavatory is inaccessible because the hot water pipes are not insulated or otherwise configured to protect against contact. TR12 60 months
39.4.g The toilet is inaccessible because its centerline measures 19 inches from the side wall. SU15 60 months
39.4.h The toilet is inaccessible because the flush control is on the closed side. SU1 60 months
39.4.i The toilet paper dispenser is inaccessible because it is mounted 37 inches from the rear wall. SU17 60 months
39.4.j The end of the side grab bar is 13 inches from the rear wall. SU6 60 months
39.4.k The rear grab bar at the toilet is inaccessible because it is 24 inches long, the closer end is 7 inches from the side wall, and the flush control interferes with its usage. ST5 60 months
39.5 Television Room Drinking Fountain
39.5.a The water at the drinking fountain flows 4 ½ inches away from the front of the fountain. DF7 60 months
39.5.b The drinking fountain is inaccessible because the knee clearance is 26 ¾ inches wide and was obstructed by a grille and a trash can at the time of our survey. DF5 60 months
40 Wheaton Regional Library, 11701 Georgia Avenue, Wheaton, Maryland 20902
40.1 Lower Rightmost Entrance by Parking Level (when facing facility) - The pressure required to open the interior vestibule entrance door is 15 pounds. D2 60 months
40.2 Telephone on Lower/Parking level -The telephone at the lower level parking area is inaccessible because the coin slot is 55 inches above the finished ground. TT1 60 months
40.3 Route from Entrances to meeting rooms, elevator, toilets, etc - The two wall mounted fire extinguishers each protrude 5 ½ inches into the walkway with their leading edges 47 and 48 inches above the finished floor and would not be detectable to a blind person using a cane. AR8 60 months
40.4 Drinking Fountains
40.4.a Although a low drinking fountain is provided both on the upper and lower levels, there is no drinking fountain provided on either level for people who have difficulty bending or stooping. DF3 60 months
40.4.b The upper level drinking fountain is inaccessible because it has 26 inches of knee height. DF5 60 months
40.5 Women's Toilet Room on Lower Level - Stalls
40.5.a The pressure required to open the toilet room entrance door is 14 pounds. D2 60 months
40.5.b Although an audible alarm is provided in this facility, there is no visual alarm appliance in the toilet room. TR21 60 months
40.5.c The seat cover dispenser is inaccessible because the seat covers are 60 inches above the finished floor. TR4 60 months
40.5.d The toilet is inaccessible because the top of the seat is 20 inches above the finished floor. ST20 60 months
40.5.e The toilet is inaccessible because its centerline measures 28 inches from the side wall. ST17 60 months
40.5.f The toilet is inaccessible because the flush control is on the closed side. ST2 60 months
40.5.g The side grab bar at the toilet is inaccessible because it is obstructed by the toilet paper dispenser. ST9 60 months
40.5.h The rear grab bar at the toilet is inaccessible because its closer end is 6 ½ inches from the side wall. ST4 60 months
40.6 Men's Toilet Room on Lower Level - Stalls
40.6.a The pressure required to open the toilet room entrance door is 11 pounds. D2 60 months
40.6.b Although an audible alarm is provided in this facility, there is no visual alarm appliance in the toilet room. TR21 60 months
40.6.c The seat cover dispenser is inaccessible because the seat covers are 60 inches above the finished floor. TR4 60 months
40.6.d The lavatory is inaccessible because the hot water pipes are not insulated or otherwise configured to protect against contact. TR12 60 months
40.6.e The toilet is inaccessible because the top of the seat is 19 ½ inches above the finished floor. ST20 60 months
40.6.f The toilet is inaccessible because its centerline measures 28 inches from the side wall. ST17 60 months
40.6.g The coat hook is mounted 66 inches above the finished floor. TR1 60 months
40.6.h The side grab bar at the toilet is inaccessible because it is obstructed by the toilet paper dispenser. ST9 60 months
40.6.i The rear grab bar at the toilet is inaccessible because its closer end is 7 inches from the side wall. ST4 60 months
40.7 Women's Toilet Room on Upper Level - Stalls
40.7.a The room sign is inaccessible because it is on the door and its centerline is mounted 64 inches above the finished floor. TR16, TR18 60 months
40.7.b The pressure required to open the toilet room entrance door is 12 pounds. D2 60 months
40.7.c The door to the toilet room is inaccessible because the pull side has only 6 ½ inches of maneuvering space on the latch side. D6, TR16 60 months
40.7.d The light switch is inaccessible because it is 55 inches above the finished floor. TR5 60 months
40.7.e Although an audible alarm is provided in this facility, there is no visual alarm appliance in the toilet room. TR21 60 months
40.7.f The seat cover dispenser is inaccessible because the seat covers are 60 inches above the finished floor. TR4 60 months
40.7.g The baby changing counter is inaccessible because the controls are mounted 55 inches above the finished floor. TR5 60 months
40.7.h The lavatory is inaccessible because the top of its rim is 35 inches above the finished floor. TR11, TR16 60 months
40.7.i The lavatory is inaccessible because the hot water pipes are not insulated or otherwise configured to protect against contact. TR12 60 months
40.7.j The designated accessible toilet stall is inaccessible because the stall measures 54 inches by 58 inches. ST16, TR16 60 months
40.7.k The toilet is inaccessible because the top of the seat is 19 ½ inches above the finished floor. ST20, TR16 60 months
40.7.l The toilet is inaccessible because its centerline measures 21 inches from the side wall. ST17, TR16 60 months
40.7.m The side grab bar is inaccessible because it is obstructed by the toilet paper dispenser. ST9 60 months
40.7.n The side grab bar at the toilet is inaccessible because its farther end is 47 inches from the rear wall. ST7, TR16 60 months
40.7.o The rear grab bar at the toilet is inaccessible because its closer end is 11 inches from the side wall. ST4, TR16 60 months
40.8 Men's Toilet Room on Upper Level - Stalls
40.8.a The room sign is inaccessible because it is mounted on the door and its centerline is mounted 64 inches above the finished floor. D26 60 months
40.8.b The pressure required to open the toilet room entrance door is greater than 5 pounds. D2 60 months
40.8.c The door to the toilet room is inaccessible because the pull side has only 7 inches of maneuvering space on the latch side. D6, TR16 60 months
40.8.d The light switch is inaccessible because it is 55 inches above the finished floor. TR5, TR16 60 months
40.8.e Although an audible alarm is provided in this facility, there is no visual alarm appliance in the toilet room. TR21 60 months
40.8.f The seat cover dispenser is inaccessible because the seat covers are 66 inches above the finished floor. TR4 60 months
40.8.g The baby changing counter is inaccessible because the controls are mounted 55 inches above the finished floor. TR5 60 months
40.8.h The lavatory is inaccessible because the top of its rim is 36 inches above the finished floor. TR11, TR16 60 months
40.8.i The designated accessible toilet stall is inaccessible because the stall measures 54 inches by 55 inches. ST16, TR16 60 months
40.8.j The toilet is inaccessible because the top of the seat is 20 inches above the finished floor. ST20, TR16 60 months
40.8.k The toilet is inaccessible because its centerline measures 20 ½ inches from the side wall. ST17, TR16 60 months
40.8.l The side grab bar is inaccessible because the toilet paper dispenser is not mounted at least 1 ½ inches below it, and it obstructs its use. ST9 60 months
40.8.m The side grab bar at the toilet is inaccessible because its farther end is 46 inches from the rear wall. ST7, TR16 60 months
40.9 Elevator
40.9.a The elevator is inaccessible because there is no main entry floor designation. E4 60 months
40.9.b The elevator is inaccessible because, although emergency communications are provided, they require tight pinching or grasping to operate. E8 60 months
40.10 Check-Out Counter - The check-out counter is inaccessible because it is 38 ½ inches above the finished floor. C6 60 months
40.11 Magazine Display - The top shelf of the magazine display is inaccessible because it is 63 inches above the finished floor. L1 60 months
40.12 Parking - The parking reserved for persons with disabilities is inaccessible because each of the 6 designated accessible parking spaces is less than 96 inches wide, and the van accessible access aisle is only 64 inches wide. P8 60 months
40.13 Route from Parking to Lower Level Entrances - The curb ramp leading to the right-most lower level entrance is inaccessible because the "gutter" slope slopes 14.6%. AR1 60 months
40.14 Outdoor Telephone at right-most Lower Level Entrance - The outdoor telephone at the right-most lower level entrance is inaccessible because the coin slot is 55 inches from the ground. TT1 60 months
40.15 Exterior Ramp leading to Upper-Level Entrance - The ramp leading to the upper-level entrance is inaccessible because the landing has a slope of 2.3%, and there are no handrail extensions. R3 60 months
41 Clara Barton Community Center, 7425 MacArthur Boulevard, Cabin John, Maryland 20818
41.1 Parking - The parking lot is inaccessible because none are designated as being van accessible for persons with disabilities. This lot requires 1 van accessible space. P3 48 months
41.2 Women's Toilet Room with Stalls near Lobby
41.2.a The toilet room sign is mounted on the door and has no Braille or raised characters. TR17 48 months
41.2.b The pressure required to open the door is 15 pounds. D2 48 months
41.2.c No accessible mirror has been provided. TR14 48 months
41.2.d The lavatory hot water pipes are not insulated or otherwise configured to protect against contact. TR12 48 months
41.2.e Although there are 7 stalls, there is no ambulatory stall provided. ST1 48 months
41.2.f In the standard accessible stall, the toilet flush control is on the closed side. ST2 48 months
41.2.g No accessible coat hook has been provided. TR1 48 months
41.2.h The side grab bar at the toilet is obstructed by the toilet paper dispenser. ST9 48 months
41.3 Men's Toilet Room with Stalls near Lobby
41.3.a The toilet room sign is mounted on the door and has no Braille or raised characters. TR17 48 months
41.3.b No accessible mirror has been provided. TR14 48 months
41.3.c The lavatory hot water pipes are not insulated or otherwise configured to protect against contact. TR12 48 months
41.3.d The lower urinal's rim is 21 inches high. TR20 48 months
41.3.e The accessible stall's toilet centerline measures 17 inches from the side wall. ST17 48 months
41.3.f No accessible coat hook has been provided. TR1 48 months
41.3.g The side grab bar at the toilet is obstructed by the toilet paper dispenser. ST9 48 months
41.4 Spanish Room
41.4.a The pressure required to open the door is 6 pounds. D2 48 months
41.4.b The door has knob hardware. D1 48 months
41.5 Weight Room
41.5.a The pressure required to open the door is 10 pounds. D2 48 months
41.5.b The door has knob hardware. D1 48 months
42 Council Office Building, 100 Maryland Avenue, Rockville, Maryland 20850
42.1 2nd Floor Unisex Toilet Room with Stalls next to the Code Enforcement office
42.1.a The toilet room sign is mounted on the door. TR16, TR18 60 months
42.1.b The pressure required to open the door is 7 pounds. D2 60 months
42.1.c The pull side of the door, which is accessed through a front approach, has only 4½ inches of clearance on the latch side. D6, TR16 60 months
42.1.d The seat cover dispenser is mounted at 63 inches above the finished floor. TR4 60 months
42.1.e The door lock is mounted at 53 inches above the finished floor with only a forward reach provided. TR5, TR16 60 months
42.1.f The top of the toilet seat is 20 inches above the finished floor. SU18, TR16 60 months
42.1.g The toilet centerline measures 20 inches from the side wall. SU15, TR16 60 months
42.1.h The toilet flush control is on the closed side. ST2, TR16 60 months
42.1.i No accessible coat hook has been provided. TR1 60 months
42.2 2nd Floor Men's and Women's Toilet Rooms Near Elevators
42.2.a There is no signage directing people with disabilities to the accessible toilet rooms. TR16 60 months
42.2.b The toilet room signs are mounted on the doors and have no Braille, and some do not have raised characters. TR17 60 months
42.3 2nd Floor Women's Toilet Room with Stalls
42.3.a The toilet room contains a number of inaccessible elements and is not accessible to people with disabilities. TR16, TR22 60 months
42.4 2nd Floor Drinking Fountains (two)
42.4.a Although accessible drinking fountains are provided, there is no drinking fountain provided for people who have difficulty bending or stooping. DF3 60 months
42.4.b Both drinking fountains protrude into the walkway and would not be detectable to a blind person using a cane. AR8 60 months
42.5 Conference Room 225
42.5.a The door has knob hardware. D1 60 months
42.6 Ethics Commission Office 204 - The door has knob hardware. D1 60 months
42.7 Fire and Rescue Office - The door has knob hardware. D1 60 months
42.8 Office of the People's Counsel 226
42.8.a The pressure required to open the door is 12 pounds. D2 60 months
42.8.b The door has knob hardware. D1 60 months
42.9 Office of Cable and Communication Services 250
42.9.a The pressure required to open the door is 10 pounds. D2 60 months
42.9.b The door has knob hardware. D1 60 months
42.9.c The counter is 42 inches high. C6 60 months
42.10 Code Enforcement and Licensing 260
42.10.a The pressure required to open the door is 8 pounds. D2 60 months
42.10.b The counter is 42 inches high. C6 60 months
42.11 3rd Floor Mailboxes - The mailboxes next to the elevator protrude into the walkway and would not be detectable to a blind person using a cane. AR8 60 months
42.12 3rd Floor Drinking Fountains
42.12.a Both 3rd floor drinking fountains have a spout that is 42 inches above the finished floor. DF6 60 months
42.12.b The drinking fountain near the elevator has controls that require 7 pounds of force to operate. DF2 60 months
42.13 3rd Floor Large Council Meeting Room
42.13.a The closed leaf of the double door from the elevators does not have a level approach on one side, has knob hardware, and requires 12 pounds of force to open. D1, D2, D13 60 months
42.13.b The internal ramp between the elevator and the Council Meeting Room does not have a level landing at the top and has a handrail on only part of one side, and the existing handrail is 32½ inches high, does not have extensions at the top and bottom, and is 2 inches in diameter. AR2, R3 60 months
42.13.c The double doors to the meeting room are 29¼ inches wide per leaf, require 12 pounds of force to open, and have thumb latch hardware. D1, D2, D5 60 months
42.13.d There is no accessible route to the council dias seating area because of three steps leading to this area. AR3 60 months
42.13.e The wheelchair seating areas do not have a fixed companion seat next to each wheelchair area. A total of 5 wheelchair seating areas is required. AA6 60 months
42.13.f Although there are more than 50 fixed seats, there is either no assistive listening system or signage indicating its availability. AA3, AA5 60 months
42.13.g The ramp leading to the base of the dias does not have edge protection on the sides. R1 60 months
42.14 3rd Floor Small Council Conference Room 320
42.14.a The entry doors both have knob hardware. D1 60 months
42.14.b The pressure required to open both entry doors is 10 pounds. D2 60 months
42.15 3rd Floor Council Conference Room Toilet Rooms
42.15.a The toilet room signs are mounted on the doors and have no Braille. TR16, TR18 60 months
42.15.b There is no signage directing people with disabilities to the accessible toilet rooms. TR16 60 months
42.16 3rd Floor Women's Toilet Room with Stalls near Elevators
42.16.a The toilet room sign is mounted 56 inches high and is not on the latch side of the door. TR16, TR18 60 months
42.16.b The door is 28½ inches wide. D25, TR16 60 months
42.16.c Although an audible alarm is provided in this facility, there is no visual alarm appliance in the toilet room. TR21 60 months
42.16.d The seat cover dispenser is mounted 61 inches high and a forward reach is required. TR4 60 months
42.16.e The designated accessible stall is incorrectly configured as an ambulatory stall, and there is no standard accessible stall provided. ST15, TR16 60 months
42.17 3rd Floor Men's Toilet Room with Stalls near Elevators
42.17.a The toilet room sign is mounted 55½ inches high and is not on the latch side of the door. TR16, TR18 60 months
42.17.b The door is 29 inches wide. D25, TR16 60 months
42.17.c Although an audible alarm is provided in this facility, there is no visual alarm appliance in the toilet room. TR21 60 months
42.17.d The seat cover dispenser is mounted 58 inches high. TR4 60 months
42.17.e The urinal is inaccessible because the rim measures 21 inches above the finished floor, and the flush control is 48 inches above the finished floor. TR20, TR16 60 months
42.17.f The designated accessible stall is incorrectly configured as an ambulatory stall, and there is no standard accessible stall provided. ST15, TR16 60 months
42.18 4th Floor Drinking Fountain near Elevators
42.18.a Although an accessible drinking fountain is provided, there is no drinking fountain provided for people who have difficulty bending or stooping. DF3 60 months
42.18.b The drinking fountain protrudes into the walkway and would not be detectable to a blind person using a cane. AR8 60 months
42.19 4th Floor Women's Toilet Room near Elevators
42.19.a The toilet room sign is mounted 55 inches high and is not on the latch side of the door. TR16, TR18 60 months
42.19.b The pressure required to open the door is 10 pounds. D2 60 months
42.19.c The pull side of the door, which is accessed through a front approach, has only 1 inch of clearance on the latch side. D6, TR16 60 months
42.19.d The path of travel into the room is 33 inches wide at the toilet stall. TR15, SU16, TR16 60 months
42.19.e The seat cover dispenser is mounted 53 inches high with a forward reach required. TR4 60 months
42.19.f The lavatory is 35 inches high to the top of the rim. TR11, TR16 60 months
42.19.g The toilet centerline measures 16 inches from the side wall. SU15, TR16 60 months
42.19.h The toilet flush control is on the closed side. SU1, TR16 60 months
42.19.i No accessible coat hook has been provided. TR1 60 months
42.19.j The toilet paper dispenser is mounted 40 inches from the rear wall. SU17 60 months
42.19.k The side grab bar at the toilet is obstructed by the toilet paper dispenser. SU8 60 months
42.19.l The rear grab bar at the toilet is mounted 18 inches from the side wall. SU3, TR16 60 months
42.20 4th Floor Men's Toilet Room near Elevators
42.20.a The toilet room sign is mounted 58 inches high. TR16, TR18 60 months
42.20.b The pressure required to open the door is 10 pounds. D2 60 months
42.20.c The pull side of the door, which is accessed through a front approach, has only 1 inch of clearance on the latch side. D6, TR16 60 months
42.20.d The toilet centerline measures 15½ inches from the side wall. SU15, TR16 60 months
42.20.e No accessible coat hook has been provided. TR1 60 months
42.20.f The toilet paper dispenser is mounted 43 inches from the rear wall. SU17 60 months
42.20.g The side grab bar at the toilet is obstructed by the toilet paper dispenser. SU8 60 months
42.20.h The rear grab bar at the toilet is mounted 17 ½ inches from the side wall. SU3, TR16 60 months
42.21 Exterior Route - The route from the parking garage to the rear entrance has a slope of 7.6% and a cross-slope of 2.6% near the garage entrance, has a slope of 6.5% and a cross-slope of 2.4% near the door, is steeper than 5% at several other points and has no ramp features; and the sidewalk near the rear entrance is cracked and broken. AR1 60 months
42.22 Entrance Lobby - The coat rack protrudes into the walkway and would not be detectable to a blind person using a cane. AR8 60 months
42.23 Cafeteria - The ends of the tray slides protrude into the walkway and would not be detectable to a blind person using a cane. AR8 60 months
42.24 1st Floor Drinking Fountain -The drinking fountain protrudes into the walkway and would not be detectable to a blind person using a cane. AR8 60 months
42.25 1st Floor Women's Single-User Toilet Room near Auditorium
42.25.a The toilet room sign is mounted on the door and has no Braille characters. TR16, TR18 60 months
42.25.b Although an audible alarm is provided in this facility, there is no visual alarm appliance in the toilet room. TR21 60 months
42.25.c The seat cover dispenser is mounted 56 inches high. TR4 60 months
42.25.d The toilet centerline measures 14¼ inches from the side wall. SU15, TR16 60 months
42.25.e The toilet flush control is on the closed side. SU1, TR16 60 months
42.25.f The toilet paper dispenser is mounted 42 inches from the rear wall. SU17 60 months
42.25.g The side grab bar at the toilet is 36 inches long, with its far end 41 inches from the rear wall. SU6, TR16 60 months
42.25.h The rear grab bar at the toilet is 25 inches long. SU3, TR16 60 months
42.25.i The door lock requires tight grasping to operate. TR3 60 months
42.26 1st Floor Unisex Single-User Toilet Room near Auditorium
42.26.a The toilet room sign is mounted on the door and has no Braille characters. TR16, TR18 60 months
42.26.b The pull side of the door, which is accessed through a front approach, has only 3¾ inches of clearance on the latch side. D6, TR16 60 months
42.26.c Although an audible alarm is provided in this facility, there is no visual alarm appliance in the toilet room. TR21 60 months
42.26.d The paper towel dispenser is mounted 57 inches high. TR5 60 months
42.26.e The lavatory hot water pipes are not completely insulated or otherwise configured to protect against contact. TR12 60 months
42.26.f There is no accessible urinal provided. TR20, TR16 60 months
42.26.g The toilet has insufficient clear floor space. SU16, TR16 60 months
42.26.h The top of the toilet seat is 20 inches above the finished floor. SU18, TR16 60 months
42.26.i The toilet centerline measures 16½ inches from the side wall. SU15, TR16 60 months
42.26.j The toilet flush control is on the closed side. SU1, TR16 60 months
42.26.k The toilet paper dispenser is mounted 41 inches from the rear wall. SU17 60 months
42.26.l The side grab bar at the toilet is 36 inches long, with its far end 42½ inches from the rear wall. SU6, TR16 60 months
42.26.m The rear grab bar at the toilet is 25 inches long. SU3, TR16 60 months
42.26.n The rear grab bar at the toilet is mounted 1¼ inches above the flush control. SU4 60 months
42.26.o The door lock requires tight grasping to operate. TR3 60 months
42.26.p The door handle is 50 inches high. TR5 60 months
42.27 1st Floor Auditorium
42.27.a The pressure required to open the doors is 15 pounds. D2 60 months
42.27.b The door hardware is inaccessible because door lock requires pinching to operate. D1 60 months
42.27.c There are no accessible seating areas provided. Provide 4 wheelchair seating areas,

AA6, AR9

60 months
42.27.d Although there are more than 50 fixed seats, the auditorium is inaccessible there is no signage indicating the availability of an assistive listening system. AA3, AA5 60 months
42.27.e The ramp up to the stage has a slope of 15.2%, there are insufficient landings at the top and bottom, the handrails are 32 inches and 33 inches high and are not stable, the handrail diameter is 2 inches, and there are no handrail extensions at the ends of the handrails. Prove a ramp that is at least 36 inches wide with a slope not exceeding 8.33% and a cross slope not exceeding 2%; with level landings at least as wide as the ramp and 60 inches long at the top and bottom of the ramp; and with edge protection at least 2 inches high at the drop off sides. R3, AR9 60 months
42.28 1st Floor Drinking Fountains
42.28.a Although accessible drinking fountains are provided, there is no drinking fountain provided for people who have difficulty bending or stooping. DF3 60 months
42.28.b The fountains protrude into the walkway and would not be detectable to a blind person using a cane. AR8 60 months
42.29 Interior Route from Auditorium to Elevators - There are light fixtures that protrude into the walkway at 72 inches high that would not be detectable to a blind person using a cane. AR8 60 months
42.30 1st Floor Toilet Rooms with Stalls near Elevator
42.30.a The toilet room signs are mounted on the door. TR18 60 months
42.30.b There is no signage directing people with disabilities to the accessible toilet rooms. TR16 60 months
42.31 2nd Floor Hearing Room - Judge Davidson
42.31.a The attorney tables are 23½ inches high to the bottom. T1 60 months
42.31.b The door has knob hardware. D1 60 months
42.31.c The hearing room is inaccessible because there is no signage indicating the availability of an assistive listening system. AA3 60 months
42.32 2nd Floor Law Library - The route around the table is 21 inches wide at the corner, and 30 inches wide along the side. AR2, AR3 60 months
43 Upcounty Regional Services Center, 12900 Middlebrook Road, Germantown, Maryland
43.1 Route from Front Parking Area to Main Entrance - The route from the parking area to the main entrance is inaccessible because there is a 1 inch change in level at one point along the sidewalk. AR1 24 months
43.2 Route from Side Parking Area to Main Entrance - Along the route from the side parking area to the main entrance, the path narrows to only 30 inches width because of a trash can. AR1 24 months
43.3 Front Lobby Counter - The counter is 42 inches above the finished floor. C6 24 months
43.4 Doorways used by the public throughout the facility - The permanent room signage provided for most of the offices and rooms used by the public are inaccessible because there is no Braille characters or raised lettering. D26 24 months
43.5 Tourist Information Office/Gilchrist Center/Meeting Rooms - The pressure required to open the entry door into the area is 12 pounds. D2 24 months
43.6 Maryland National Capital Park and Planning Commission - The pressure required to open the door is 8 pounds. D2 24 months
43.6.a 1st Floor Drinking Fountain - The flow of water at the drinking fountain is not within 3 inches of the front of the fountain. DF7 24 months
43.7 Regional Services Office -The pressure required to open the door is 15 pounds. D2 24 months
43.8 Public Telephones - First Floor - The telephones on the first floor are inaccessible because there is no volume control. TT1 24 months
43.9 Elevators - The elevator is inaccessible because, although emergency communications are provided, they are not identified by raised lettering, the door requires pinching to open, and the system requires voice communication. E4, E8 24 months
43.10 Men's 2nd Floor Toilet Rooms - Stalls
43.10.a The centerline of the toilet room sign is mounted 62 inches above the finished floor. TR17 24 months
43.10.b The pull side of the door, which is accessed through a front approach, is inaccessible because it has only 10 ½ inches of maneuvering clearance. D6, TR16 24 months
43.10.c No accessible mirror has been provided. TR14 24 months
43.10.d The corner of the lavatory counter protrudes 21 inches into the walkway, 28 inches above the finished floor, and would not be detectable to a blind person using a cane. AR8 24 months
43.10.e The urinal is inaccessible because the rim is mounted 17 ½ inches above the finished floor and the flush control is 47 inches above the finished floor. TR20, TR16 24 months
43.10.f The side grab bar at the toilet is inaccessible because it is obstructed by the toilet paper dispenser. ST9 24 months
43.10.g The toilet is inaccessible because the top of the seat is 19 ½ inches above the finished floor. ST20, TR16 24 months
43.11 Women's 2nd Floor Toilet Room - Stalls
43.11.a The centerline of the toilet room sign is mounted 62 inches above the finished floor. TR16, TR18 24 months
43.11.b The pull side of the door, which is accessed through a front approach, is inaccessible because it has only 11 inches of maneuvering clearance. D6, TR16 24 months
43.11.c No accessible mirror has been provided. TR14 24 months
43.11.d The baby changing table is inaccessible because its handle is 56 ½ inches above the finished floor, and, once it is opened, the table top is 38 ½ inches above the finished floor. TR5, T1 24 months
43.11.e The corner of the lavatory counter protrudes 21 inches into the walkway, 28 inches above the finished floor, and would not be detectable to a blind person using a cane. AR8 24 months
43.11.f The lavatory is inaccessible because the hot water pipes are not insulated or otherwise configured to protect against contact. TR12 24 months
43.11.g The toilet is inaccessible because the top of the seat is 20 inches above the finished floor. ST20, TR16 24 months
43.11.h The toilet is inaccessible because the flush control is on the closed side. ST2, TR16 24 months
43.12 Drinking Fountains between the 2nd floor toilet rooms
43.12.a Although drinking fountains are provided, the water flows 6 ½ inches from the front of the fountain. DF7 24 months
43.12.b The drinking fountains protrude into the walkway and would not be detectable to a blind person using a cane. AR8 24 months
43.13 HHS Cashier Counter - 2nd Floor
43.13.a The counter is inaccessible because its top surface is 38 ½ inches above the finished floor. C5 24 months
43.13.b The counter protrudes into the walkway and would not be detectable to a blind person using a cane. AR8 24 months
43.14 WATS/GUIDE Youth Services - The push side of the door, which is accessed through a front approach and which has both a closer and a latch, is inaccessible because it has only 7 inches of maneuvering clearance. D7 24 months
43.15 3rd Floor Toilet Room - stalls - The toilet rooms on the 3rd floor are inaccessible and there is no signage directing people with disabilities to the accessible toilet rooms. TR16, TR18 24 months
44 Garage 49, 7601 Woodmont Avenue, Bethesda, Maryland 20814
44.1 Parking
44.1.a The parking lot, with a total of 937 parking spaces, is inaccessible because all of the designated accessible spaces are less than 96 inches wide and no van accessible spaces have been provided. This lot requires 3 van accessible spaces and 15 standard spaces. P3 24 months
45        Merrimac Neighborhood Park, 6415 Winston Drive, Bethesda, MD 20817 (MNCPPC)
45.1    Parking
45.1.a The parking lot, with a total of approximately 21 parking spaces, is inaccessible because none are designated as being accessible for persons with disabilities.  This lot requires 1 van accessible space. P3 24 months
45.1.b Accessible Route from Parking to Tennis Courts and Basketball Courts
45.2    The route from the parking area to the tennis and basketball courts is inaccessible because the slope of the route measures 16.1% and the cross slope of the route measures 7.7%. AR1 24 months
45.2.a The built up curb ramp to the tennis courts is inaccessible because the cross slope measures 2.6% and the slope of the flared sides measures 21.8%. AR5 24 months
46        Capitol View - Homewood Local Park, 2929 Edgewood Road, Kensington, MD 20895 (MNCPPC)
46.1    Parking
46.1.a The parking lot, with a total of approximately 17 parking spaces, is inaccessible because none are designated as being van accessible for persons with disabilities.  This lot requires 1 van accessible space.  In addition, the current parking spaces reserved for persons with disabilities are inaccessible because the slope of parking space #1 measures 5.7%, the slope of the adjacent access aisle measures 4.9%, the slope of parking space # 2 measures 4.2%, and the slope of the adjacent access aisle measures 3.7% P3 6 months
46.2    Accessible Route
46.2.a There is no accessible route between the playground and the ballfield and no accessible route to the pay telephone. AR1 6 months
46.3    Pay Telephone
46.3.a The telephone is inaccessible because the highest operable part is 56 inches high. TT1 6 months
46.4    Outdoors accessible portable toilet room
46.4.a The toilet room lacks accessible signage. TR17 6 months
46.4.b The side grab bar at the toilet is inaccessible because it is obstructed by the toilet paper dispenser. SU7 6 months
46.4.c The side grab bar at the toilet is inaccessible because the far end is less than 54 inches from the rear wall. SU6 6 months
47        Stratton Local Park, 9925 Harrogate Road, Bethesda, MD 20817 (MNCPPC)
47.1    Parking
47.1.a Although the parking lot has a total of 25 parking spaces, none is van accessible.  In addition, the current parking space designated as being reserved for persons with disabilities is inaccessible because the cross slope of the parking space measures 5.1% and the cross slope of the access aisle measures 4.6%. P7 60 months
47.2    Accessible Route
47.2.a The routes throughout the park are inaccessible because the slope of the route to the tennis court measures 14.4%, the bottom of the route into the park slopes 6.3% and is not constructed as a ramp, the route to the picnic area slopes 10.7%, the route to the playground slopes between 7.5% and 10.7% and is not constructed as a ramp, and the routes to the barbeque grill and ballfield are not firm, stable, or slip resistant. AR1 60 months
47.3    Picnic Tables
47.3.a The picnic tables are inaccessible because none provide the required knee space. PD6 60 months
48        Ken-Gar Palisades Park, 4140 Wexford & Beach Drive, Kensington, Maryland 20895 (MNCPPC)
48.1    Parking
48.1.a The parking lot, with a total of approximately 30 parking spaces, is inaccessible because only 1 is designated as reserved for people with disabilities, and the sign for that space is mounted too low.  This lot requires 1 van accessible space and 1 standard accessible space. P3 60 months
48.1.b Telephone - There is not an accessible route to the telephone. AR1  60 months
48.2    Two Portable Single User Toilet Rooms
48.2.a The side grab bar at each toilet is inaccessible because it is obstructed by the toilet paper dispenser. SU7 60 months
48.2.b The side grab bar at each toilet is inaccessible because the far end is less than 54 inches from the rear wall. SU6 60 months
48.3    Route to Playground area and Exercise Center
48.3.a The route to the playground area and the exercise center is inaccessible because the surface is not firm, stable or slip resistant and is covered in grass and wood chips. AR1 60 months
48.4    Route from Parking to Tennis Court
48.4.a The route from the parking lot to the tennis court is inaccessible because there is a 16.6% slope before the court gate. AR1 60 months
48.5    Drinking Fountain
48.5.a The route to the drinking fountain is inaccessible because the slope measures 11.8%. AR1 60 months
49        Rock Creek Hills Local Park, 3701 Saul Road, Kensington, Maryland 20895 (MNCPPC)
49.1    Parking
49.1.a Although the parking lot has a total of 63 parking spaces, only 1 is designated as reserved for people with disabilities, and there is no vertical signage.  In addition, the parking space reserved for persons with disabilities is inaccessible because the slope measures 3.3%.  This lot requires a total of 1 van accessible space and 2 standard spaces designated as reserved for people with disabilities on the shortest accessible route to the accessible entrance. P3, P7 6 months
49.2    Accessible Route - designated accessible parking to portable toilet area
49.2.a The route from the designated accessible parking space to the portable toilet area is inaccessible because there is a 1 inch change in level at the curb ramp, and the slope of the curb ramp measures 9.6%. AR1, AR5 6 months
49.3    Dispenser for "Mutt Mitt"
49.3.a The route to the "Mutt Mitt" dispenser is inaccessible because the surface is grass and is not firm, stable or slip resistant. AR1 6 months
49.4    Drinking Fountain - near toilet area
49.4.a Although a drinking fountain is provided, there is no accessible drinking fountain because the spout is not located in the front of the water fountain. DF1 6 months
49.5    Unisex Portable Toilet
49.5.a The side grab bar at the toilet is inaccessible because it is obstructed by the toilet paper dispenser. SU7 6 months
49.5.b The side grab bar at the toilet is inaccessible because the far end is less than 54 inches from the rear wall. SU12 6 months
49.6    Route to Basketball, Playground, Tennis Court 6 months
49.6.a The route to the tennis court is inaccessible because it is not firm, stable and slip resistant and the slope measures 11.6% at the tennis courts. AR1 6 months
50        Kensington Cabin Local Park, 1000 Kensington Parkway, Kensington, MD 20895 (MNCPPC)
50.1    Accessible Route from Street Parking
50.1.a There is no accessible route that connects the main points of the parks programs such as the phone, playground, basketball court, picnic table and tennis court, the route that is provided has a 2 ¾ inch change in level, the slope measures 6.8% although it is not constructed as a ramp, and the cross slope measures 2.4%. AR1, R4 24 months
51        Newport Mill Park, 11201 Newport Mill Road, Kensington, Maryland 20895 (MNCPPC)
51.1    Parking
51.1.a The parking lot, with a total of approximately 25 parking spaces, is inaccessible because none are designated as being accessible for persons with disabilities.  This lot requires 1 van accessible space. P3 6 months
51.2    Accessible Route from Parking to Ball Fields
51.2.a The route from the parking area to the ball fields is inaccessible because the slope measures 12.7%. AR1 6 months
51.3    Spectator Seating by the baseball diamond
51.3.a There is no accessible route to the spectator seating by the baseball diamond. AR1 6 months
51.3.b The spectator seating at the baseball field is inaccessible because there is no clear floor space for wheelchair seating by the diamonds. AA6 6 months
52        Pleasant View Park, 11321 Norris Drive, Kensington, Maryland 20895 (MNCPPC)
52.1    Accessible Route - from on-street parking at Norris to soccer field - The route from the on-street parking to Norris soccer field is inaccessible because there is a 7.8% slope on the route and a 1 inch abrupt level change near the pillar. AR1 48 months
52.2    Curb Ramp - The route from the on street parking to the soccer field is inaccessible because there is an abrupt edge at the beginning of the ramp and the slope of the ramp measures 13.2%. AR5 48 months
53        Burning Tree Park, 7904 Beechtree Road, Bethesda, Maryland 20817 (MNCPPC)
53.1    Parking - The parking lot, with a total of approximately 30 parking spaces, is inaccessible because none are designated as being accessible for persons with disabilities.  This lot requires 1 van accessible space and one standard accessible space. P3 36 months
53.2    Accessible Routes
53.2.a There is no accessible route from the parking area to the playing field. AR1 36 months
53.2.b There is no accessible route to the tennis courts because the existing route goes down a steep hill and is not a firm, stable or slip resistant path. AR1 36 months
54        Dewey Park, 11720 Dewey Road, Veirs Mill, Maryland 20906 (MNCPPC)
54.1    Parking
54.1.a The parking lot, with a total of approximately 25 parking spaces, is inaccessible because none are designated as being accessible for persons with disabilities.  This lot requires 1 van accessible space. P3 6 months
54.1.b The parking lot by the playground, with a total of approximately 24 parking spaces, is inaccessible because none are designated as being accessible for persons with disabilities.  This lot requires 1 van accessible space. P3 6 months
54.2    Drinking Fountain by Soccer Field
54.2.a The drinking fountain is inaccessible because is provides only 26 ½ inches of knee height. DF5 6 months
54.2.b Although an accessible drinking fountain is provided, there is no drinking fountain provided for people who have difficulty bending or stooping. DF6 6 months
54.2.c The two routes to the drinking fountain both contain steps. AR1 6 months
54.3    Accessible Route
54.3.a The route from the parking area to the playground area and picnic tables is inaccessible because the surface is not firm, stable or slip resistant and none of the play equipment is usable by children with disabilities. AR1 6 months
54.3.b The route to the tennis courts has a 1 ½ inch step. AR1 6 months
54.4    Picnic Tables
54.4.a The picnic tables are inaccessible because none provide the required knee space. PD6 6 months
55        Cabin John Local Park, 7401 MacArthur Blvd. , Cabin John, Maryland 20818 (MNCPPC)
55.1    Parking - The parking lot, with a total of approximately 18 parking spaces, is inaccessible because none are designated as being accessible for persons with disabilities.  This lot requires 1 van accessible space. P3 24 months
55.2    Accessible Route - The route to the tennis courts, picnic tables, and swings is inaccessible because it requires the use of steps, and there is no curb ramp. AR1, AR5 24 months
56        Takoma - Piney Branch Local Park, 2 Darwin Avenue, Takoma Park, Maryland 20910 (MNCPPC)
56.1    Parking - The parking lot, with a total of approximately 52 parking spaces, is inaccessible because none are designated as being accessible for persons with disabilities.  This lot requires 1 van accessible space and 2 standard accessible spaces. P3 18 months
56.2    Accessible Route - The route to the park and lower level basketball courts and ball fields are inaccessible because they require the use of stairs and are not usable for a person using a wheelchair for mobility. AR1 18 months
57        Ayrlawn Local Park, 5652 Oakmont Avenue, Bethesda, MD 20817 (MNCPPC)
57.1    Accessible Route - Parking Lot to Park - The route from the parking area to the park is inaccessible because there is a 5 inch curb and no designated path over the grass.  AR1 48 months
57.2    Parking - The parking lot, with a total of approximately 9 parking spaces, is inaccessible because none are designated as being accessible for persons with disabilities.  This lot requires 1 van accessible space. P3 48 months
58        Seven Locks Local Park, 6922 Seven Locks Road, Rockville, MD 20818 (MNCPPC)
58.1    Parking - The parking lot, with a total of approximately 29 parking spaces, is inaccessible because none are designated as being accessible for persons with disabilities.  This lot requires 1 van accessible space and one standard accessible space. P3 36 months
58.2    Accessible Route - The route to the play area, tennis and basketball courts, and picnic area is inaccessible because of steps. AR1 36 months
59        Argyle Recreation Center & Local Park, 1030 Forest Glen Road, Silver Spring, MD 20901 (MNCPPC)
59.1    Parking
59.1.a The parking lot, with a total of approximately 31 parking spaces, is inaccessible because only 1 accessible space is provided.  This lot requires 1 van accessible space and 1 standard accessible space. P3 36 months
59.1.b The parking currently reserved for persons with disabilities is inaccessible because the space and the access aisle slope 7.6%. P7 36 months
59.2    Accessible Route from Parking to Tennis - The route from the parking area to the tennis courts is inaccessible because there is no level surface and it slopes up to 13.2%. AR1 36 months
59.3    Accessible Route from Parking to Playground and Ballfield - The route from the parking area to the playground and ballfield is inaccessible because there is no level surface and it is not firm, stable and slip resistant. AR1 36 months
59.4    Men's Interior Toilet Room - Stalls
59.4.a The toilet room sign is inaccessible because it is not mounted on the latch side of the door, its centerline is not mounted 60 inches above the finished floor, and there is no Braille. TR17 36 months
59.4.b The pull side of the entry door, which is accessed through a front approach, is inaccessible because the drinking fountain blocks the latch-side clearance. D6 6 months
59.4.c The light switch is inaccessible because it is on a dial and requires tight grasping. TR10 36 months
59.4.d The air dryer protrudes into the walkway and would not be detectable to a blind person using a cane. AR8 6 months
59.4.e No accessible mirror has been provided. TR14 6 months
59.4.f  The urinal is inaccessible because the rim is 24 inches above the finished floor and the flush control is 51 inches above the finished floor. TR20 6 months
59.4.g No accessible coat hook has been provided. TR1 36 months
59.4.h The side grab bar at the toilet is inaccessible because its farther end is 48 inches from the rear wall. ST7 6 months
59.4.i  The rear grab bar at the toilet is inaccessible because its closer end is 6 ½ inches from the side wall. ST4 6 months
59.5    Women's Interior Toilet Room - Stalls
59.5.a The toilet room sign is inaccessible because its centerline is mounted 65 inches above the finished floor. TR17 36 months
59.5.b The pull side of the door, which is accessed from the latch side of the door, is inaccessible because it provides only 42 ½ inches for the path of travel. D6, AR2 36 months
59.5.c The light switch is inaccessible because it requires twisting to operate. TR10 36 months
59.5.d The air dryer protrudes into the walkway and would not be detectable to a blind person using a cane. AR8 6 months
59.5.e The toilet is inaccessible because its centerline measures 16 ¾ inches from the side wall. ST17 6 months
59.5.f  No accessible coat hook has been provided. TR1 36 months
59.5.g The side grab bar at the toilet is inaccessible because its farther end is 48 inches from the rear wall. ST7 6 months
59.5.h The rear grab bar at the toilet is inaccessible because its closer end is 6 ½ inches from the side wall. ST4 6 months
59.6    Interior Drinking Fountain - Near Toilet Rooms
59.6.a The drinking fountain protrudes into the walkway with its leading edge 28 inches above the finished and would not be detectable to a blind person using a cane. AR8 6 months
59.6.b Although an accessible drinking fountain is provided, there is no drinking fountain provided for people who have difficulty bending or stooping. DF3 6 months
59.7    Exterior Drinking Fountain - near entrance door
59.7.a The drinking fountain is inaccessible because the operating control requires twisting and greater than 5 pounds of force. DF2 6 months
59.7.b The drinking fountain protrudes 10 inches into the walkway with its leading edge 30 inches above the finished and would not be detectable to a blind person using a cane. AR8 6 months
59.8    Portable Toilet near Accessible Parking Space
59.8.a The toilet room sign is not accessible because the sign is not mounted 60 inches above the ground and there is no Braille. TR17 6 months
59.8.b The rear grab bar at the toilet is inaccessible because it is 32 inches long. SU3 6 months

 