ATTACHMENT I: Modifications to Newly Constructed Facilities

Please Note: Paragraph 65 of the Settlement Agreement requires that within twelve months of the effective date of this Agreement, the County provide signage as necessary to comply with 28 C.F.R. § 35.163(b), after having surveyed all facilities that are the subject of this Agreement for the purpose of identifying those that have multiple entrances not all of which are accessible.

The chart below lists the facilities surveyed by the Department, the access issues identified during the survey, and the actions required to correct the access issues. Required actions are listed using an alphanumeric code. The key to the alphanumeric codes is provided in Attachment M to this Agreement.

In order to ensure that the following spaces and elements in County facilities for which construction was commenced after January 26, 1992, are readily accessible to and usable by persons with disabilities, the County will take the actions referenced by the alphanumeric code and described in detail in Attachment M to this Settlement Agreement within the time periods specified below, which time periods will begin to run on the effective date of this Agreement.

Item # Access Issue Remedial Action Completion Date
1 Burtonsville Volunteer Fire Department - Station 15, 13900 Old Columbia Pike, Burtonsville, Maryland 20866
1.1 Route from Parking to Entrance - The route is inaccessible because the slope at the bottom of the curb ramp measures 15.3%. AR1 12 months
1.2 Interior Hallway - The trophy display protrudes into the walkway and is not detectable to blind persons using a cane. AR8 12 months
1.3 Exercise Room - The television shelf protrudes into the walkway and is not detectable to blind persons using a cane. AR8 12 months
1.4 Designated Accessible Single-User Unisex Toilet Room
1.4.a The toilet room sign is not mounted on the latch side of the door. TR18 12 months
1.4.b The toilet room door is inaccessible because it requires 11 pounds of force to open. D2 12 months
1.4.c The pull side of the door, which is accessed through a front approach, is inaccessible because it has only 16 inches of clear space on the latch side. D6 12 months
1.4.d No accessible coat hook has been provided. TR1 12 months
1.5 Drinking Fountain near Single-User Toilet Room - Although a designated accessible drinking fountain is provided, there is no drinking fountain provided for people who have difficulty bending or stooping. DF3 12 months
2 East County Community Center, 3310 Gateshead Manor Way, Silver Spring, Maryland 20904
2.1 Parking - The parking lot is inaccessible because, although there are three accessible parking spaces, none are van accessible. In addition, one of the accessible parking spaces does not have vertical signage. This lot requires 1 van accessible space and 2 standard spaces. P3 12 months
2.2 Accessible route to entrance - The curb ramp is inaccessible because it has a slope of 15.9%. AR5 12 months
2.3 Community Room 1
2.3.a The community room door is inaccessible because it requires 7 pounds of force to open. D2 12 months
2.3.b The service counter is inaccessible because it is mounted 42 inches above the finished floor. C6 12 months
2.4 Gymnasium - The gymnasium is inaccessible to people who are deaf or hard of hearing because although there are 100+ fixed seats, there is no signage informing the public of the availability of an assistive listening system. AA4

AA3

12 months
2.5 Lobby Drinking Fountains - The drinking fountains protrude into the walkway and are not detectable to blind persons using a cane. AR8 12 months
2.6 Men's Toilet Room with Stalls
2.6.a The toilet room door is inaccessible because it requires 9 pounds of force to open. D2 12 months
2.6.b The hand dryers protrude into the walkway and are not detectable to blind persons using a cane. AR8 12 months
2.6.c The designated accessible toilet is inaccessible because its centerline is 19 inches from the side wall. ST17 12 months
2.6.d No accessible coat hook has been provided. TR1 12 months
2.6.e The toilet paper dispenser is inaccessible because it is mounted less than 18 inches above the side grab bar. ST19 12 months
2.7 Women's Toilet Room with Stalls
2.7.a The toilet room door is inaccessible because it requires 9 pounds of force to open. D2 12 months
2.7.b The hand dryer protrudes into the walkway and is not detectable to blind persons using a cane. AR8 12 months
2.7.c The designated accessible toilet is inaccessible because the flush control is on the closed side. ST2 12 months
2.7.d No accessible coat hook has been provided. TR1 12 months
2.7.e The toilet paper dispenser is inaccessible because it is mounted less than 18 inches above the side grab bar. ST19 12 months
2.8 Art Studio - The art studio door is inaccessible because it requires 11 pounds of force to open. D2 12 months
2.9 Game Room - The game room door is inaccessible because it requires 10 pounds of force to open. D2 12 months
2.10 Exercise Room
2.10.a The television protrudes into the walkway and is not detectable to blind persons using a cane. AR8 12 months
2.10.b The coat rack is inaccessible because it requires a reach of 63 inches above the finished floor. TR2 12 months
2.11 Drinking Fountain near Locker Rooms - The wall-mounted drinking fountain is inaccessible because the clear knee space is 26 inches. DF5 12 months
2.12 Women's Locker Room
2.12.a The locker room door is inaccessible because it requires 10 pounds of force to open. D2 12 months
2.12.b The hand dryer protrudes into the walkway and is not detectable to blind persons using a cane. AR8 12 months
2.12.c The toilet paper dispenser is inaccessible because it is mounted less than 18 inches above the grab bar and 39 inches from the rear wall. ST19 12 months
2.12.d The bench in the locker room is inaccessible because it is 39 inches long and 9 ½ inches wide and not attached to the wall. LR1 12 months
2.13 Men's Locker Room
2.13.a The locker room door is inaccessible because it requires 9 pounds of force to open. D2 12 months
2.13.b The hand dryer protrudes into the walkway and is not detectable to blind persons using a cane. AR8 12 months
2.13.c The designated accessible toilet is inaccessible because the flush control is on the closed side. ST2 12 months
2.13.d The toilet paper dispenser is inaccessible because it is mounted less than 18 inches above the side grab bar. ST19 12 months
2.13.e The bench in the locker room is inaccessible because it is 36 inches long and 9 ½ inches wide and not attached to the wall. LR1 12 months
2.14 Route from Side Entrance to Playground - This route is inaccessible because the running slope is 10.1% in the middle and 10.7% at the bottom of the path. AR1 12 months
3 Eastern Montgomery Regional Center, 3300 Briggs Chaney Road, Silver Spring, Maryland 20904
3.1 Parking - The parking lot, with a total of 168 parking spaces, is inaccessible because only 5 are designated as being accessible, the access aisle in the space designated as "van accessible" is 80 inches wide, and one standard space has an access aisle that is 44 inches wide. This lot requires 1 van accessible space and 5 standard spaces. P3 12 months
3.2 Curb ramp - The route from the parking to the entrance is inaccessible because it has a slope of 15.4. AR5 12 months
3.3 Department of Health and Human Services Reception Office - The door is inaccessible because it requires 10 pounds of force to open. D2 12 months
3.4 Department of Health and Human Services Single-User Unisex Public Toilet Room
3.4.a The toilet room sign is mounted on the door and has no raised or Braille characters. TR18 12 months
3.4.b The toilet room door is inaccessible because it requires 7 pounds of force to open. D2 12 months
3.4.c No accessible coat hook has been provided. TR1 12 months
3.4.d The lavatory is inaccessible because the hot water pipes are not insulated or otherwise configured to protect against contact. TR12 12 months
3.4.e The toilet paper dispenser is inaccessible because it is mounted 39 inches from the rear wall. SU17 12 months
3.5 Department of Health and Human Services Single-User Unisex Staff Toilet Room
3.5.a The toilet room sign is mounted on the door and has no raised or Braille characters. TR18 12 months
3.5.b The toilet room door is inaccessible because it requires more than 5 pounds of force to open. D2 12 months
3.5.c The seat cover dispenser is inaccessible because a forward reach of 53 ½ inches above the finished floor is required to use it. TR5 12 months
3.5.d The lavatory is inaccessible because the hot water pipes are not insulated or otherwise configured to protect against contact. TR12 12 months
3.5.e The toilet paper dispenser is inaccessible because it is mounted 39 inches from the rear wall. SU17 12 months
3.6 Drinking Fountain in Department of Health and Human Services Lobby
3.6.a Although a drinking fountain is provided, there is no accessible drinking fountain because the spout is located 6 inches from the front of the fountain. DF1 12 months
3.6.b The drinking fountain protrudes into the walkway and is not detectable to blind persons using a cane. AR8 12 months
3.7 Department of Health and Human Services Entry Lobby - Accessible Route
3.7.a The fire extinguisher case and the mailboxes near the drinking fountain protrude into the walkway and would not be detectable to a blind person using a cane. AR8 12 months
3.8 Administrative Offices - Kitchen
3.8.a The paper towel dispenser is inaccessible because the controls are mounted 56 inches above the finished floor. TR5 12 months
3.8.b The microwave is inaccessible because the controls are mounted 54 ½ inches above the finished floor over an 11 ½ inch obstruction. TR4 12 months
3.9 Administrative Offices - Single-User Unisex Staff Toilet Room
3.9.a The toilet room door is inaccessible because it requires 11 pounds of force to open. D2 12 months
3.9.b The lavatory is inaccessible because there is no knee space due to the vanity. TR11 12 months
3.9.c The lavatory is inaccessible because the door swings into the required clear floor space. TR6 12 months
3.9.d The designated accessible toilet is inaccessible because the flush control is on the closed side. SU1 12 months
3.9.e The toilet paper dispenser is inaccessible because it is mounted 40 inches from the rear wall. SU17 12 months
3.9.f The toilet is inaccessible because there are no grab bars provided at the toilet. SU10 12 months
3.10 Administrative Offices - Single-User Men's Toilet Room
3.10.a The toilet room door is inaccessible because it requires 10 pounds of force to open. D2 12 months
3.10.b The lavatory is inaccessible because the door swings into the required clear floor space. TR6 12 months
3.10.c No accessible coat hook has been provided. TR1 12 months
3.10.d The lavatory is inaccessible because the hot water pipes are not insulated or otherwise configured to protect against contact. TR12 12 months
3.10.e The toilet paper dispenser is inaccessible because it is mounted 40 inches from the rear wall SU17 12 months
3.11 Administrative Offices - Single-User Women's Toilet Room
3.11.a The toilet room door is inaccessible because it requires 9 pounds of force to open. D2 12 months
3.11.b The lavatory is inaccessible because the door swings into the required clear floor space. TR6 12 months
3.11.c No accessible coat hook has been provided. TR1 12 months
3.11.d The lavatory is inaccessible because the hot water pipes are not insulated or otherwise configured to protect against contact. TR12 12 months
3.11.e The toilet paper dispenser is inaccessible because it is mounted 39 ½ inches from the rear wall. SU17 12 months
3.12 Administrative Offices - Single-User Women's Lobby Toilet Room
3.12.a The toilet room door is inaccessible because it requires 7 pounds of force to open. D2 12 months
3.12.b The lavatory is inaccessible because the door swings into the required clear floor space. TR6 12 months
3.12.c No accessible coat hook has been provided. TR1 12 months
3.12.d The lavatory is inaccessible because the hot water pipes are not insulated or otherwise configured to protect against contact. TR12 12 months
3.12.e The toilet paper dispenser is inaccessible because it is mounted 40 inches from the rear wall. SU17 12 months
3.12.f The side grab bar at the toilet is inaccessible because it is 36 inches long and the far end is mounted 48 inches from the rear wall. SU5 12 months
3.13 Administrative Offices - Single-User Men's Lobby Toilet Room
3.13.a The toilet room door is inaccessible because it requires 9 pounds of force to open. D2 12 months
3.13.b The lavatory is inaccessible because the hot water pipes are not insulated or otherwise configured to protect against contact. TR12 12 months
3.13.c The toilet paper dispenser is inaccessible because it is mounted 39 ½ inches from the rear wall. SU17 12 months
4 Parking Garage # 60, 921 Wayne Avenue, Silver Spring, MD
4.1 Level 2
4.1.a The parking reserved for persons with disabilities is inaccessible because the slope of four of the spaces is not level, ranging up to 2.9%. P7 24 months
4.1.b The parking is inaccessible because there are parking bollards in the access aisle of the designated accessible parking spaces P1 24 months
4.2 Level 3
4.2.a The parking reserved for persons with disabilities is inaccessible because two of the four access aisles are not level, having cross slopes ranging up to 2.4%. P7 24 months
4.2.b The parking is inaccessible because parking bollards are located in the access aisles of designated accessible parking spaces. P1 24 months
4.3 Parking Level 1.5 - near Round House Educational Center
4.3.a The parking reserved for persons with disabilities is inaccessible because the van accessible space near the pay by foot station has a cross slope of 3.2%. P7 24 months
4.3.b The parking reserved for persons with disabilities is inaccessible because parking space #5 has a cross slope of 3.3%. P7 24 months
4.3.c The parking reserved for persons with disabilities is inaccessible because the access aisles serving the van accessible space and space #5 are not level with cross slopes of 2.6%. P7 24 months
4.4 Ramp near Round House Education Center - The ramp is inaccessible because the slope is 13.4% at the bottom and 10.8% at the top. R3 24 months
4.5 Ramp at Round House Education Center Back Door - The ramp is inaccessible because it lacks edge protection and handrails. R1, R2 24 months
5 Round House Theater Education Center, 925 Wayne Ave, Silver Spring, Maryland 20910
5.1 Entrance
5.1.a The building is inaccessible because there is no directional signage at the inaccessible entrance directing people with disabilities to the accessible entrance. D16 24 months
5.1.b The interior vestibule door is inaccessible because it requires 10 pounds of force to open. D2 24 months
5.2 Unisex Toilet Room - Single-User
5.2.a No accessible mirror has been provided. TR14 24 months
5.2.b The toilet is inaccessible because the top of the seat is 16 inches above the finished floor. SU18 24 months
5.2.c The toilet is inaccessible because its centerline is 19 ½ inches from the side wall. SU15 24 months
5.2.d The designated accessible toilet is inaccessible because the flush control is on the closed side. SU1 24 months
5.3 Route between main entrance and classrooms
5.3.a The route from the main entrance to the classrooms is inaccessible because the slope to the yellow room is 7.3%, and no ramp features are provided. AR1 24 months
5.4 Drinking Fountains
5.4.a Although a drinking fountain is provided, there is no accessible drinking fountain because the water height is 2 inches. DF7 24 months
5.5 Women's Toilet Room in Main Hall - Stalls
5.5.a The toilet room sign is mounted 73 inches above the finished floor. The toilet room sign is mounted on the door and has no raised or Braille characters. TR18 24 months
5.5.b The door is inaccessible because there is a ½ inch threshold with an insufficient bevel. D22 24 months
5.5.c The baby changing table is inaccessible because the control (handle) is mounted 56 ½ inches above the finished floor. TR5 24 months
5.5.d The lavatory is inaccessible because the apron is mounted 27 ½ inches above the finished floor and the knee and toe clearance is 6 inches. TR11 24 months
5.5.e The bench in the toilet room is inaccessible because it is 16 inches deep and 42 inches long. LR1 24 months
5.6 Men's Toilet Room in Main Hall - Stalls
5.6.a The toilet room sign is mounted 69 inches above the finished floor. TR18 24 months
5.6.b The toilet room door is inaccessible because there is a ¾ inch threshold. D22 24 months
5.6.c The lavatory is inaccessible because the apron is mounted 27 inches above the finished floor and the knee clearance is 6 inches. TR11 24 months
5.6.d The urinal is inaccessible because the flush control is mounted 46 inches above the finished floor. TR20 24 months
5.7 Ramp next to Yellow Room - The ramp is inaccessible because the slope is 10.1% at the top. R5 24 months
5.8 Other Ramp Leading to Exit - The ramp is inaccessible because the slope is 9.2%. R5 24 months
6 Strathmore Hall, 5301 Tuckerman Lane, North Bethesda, Maryland 20852
6.1 Assistive Listening System
6.1.a The main hall is inaccessible to people who are deaf or hard of hearing because, although there are 25 assistive listening system devices, this is an inadequate amount for a total of 1,976 seats. AA4 36 months
6.2 Accessible Seating
6.2.a The auditorium provides a sufficient number of wheelchair seating locations; however, there is an inadequate amount of companion seating, and the lines of sight for wheelchair seating areas can be obstructed by people standing in the row in front of them (while the fixed seats have a less obstructed view than wheelchair seats). AA6 36 months
6.2.b The auditorium lacks fixed aisle seating for people with disabilities. AA2 36 months
6.3 Doors - The pressure to open doors used by the public throughout the facility (including doors to enter and exit all wheelchair seating areas and the doors en route to and into the toilet rooms) is greater than 5 pounds throughout the facility. Provide all doors with no more than 5 pounds of force to open. D2 36 months
6.4 Ramp from Main Level to Orchestra - The ramp is inaccessible because the bottom of the ramp slopes 8.7% and the handrails have no extensions. R4, R5 36 months
6.5 Lift to Family Viewing Area in Auditorium - The operating controls of the lift are inaccessible because they require 8 pounds of force to operate. LF2 36 months
6.6 Orchestra Level 0-1 Women's Toilet Room with Stalls
6.6.a The toilet room sign is mounted on the hinge side of the door, 57 inches above the finished floor. TR18 36 months
6.6.b The rear grab bar at the toilet is inaccessible because it is mounted 36 ½ inches above the finished floor. ST3 36 months
6.7 Orchestra Level 0-2 Women's Toilet Room with Stalls
6.7.a The toilet room sign is mounted on the hinge side of the door, 57 ½ inches above the finished floor. TR18 36 months
6.7.b The designated accessible toilet is inaccessible because the top of the seat is 19 ¾ inches above the finished floor. ST20 36 months
6.7.c The designated accessible toilet is inaccessible because its centerline is 17 inches from the side wall. ST17 36 months
6.7.d The side grab bar at the toilet is inaccessible because the toilet paper is mounted 1¼ inches below the side grab bar and interferes with its use. ST8 36 months
6.7.e The rear grab bar at the toilet is inaccessible because the closer end is mounted 7 inches from the side wall. ST4 36 months
6.7.f Because there are 6 or more stalls (17 total stalls), an ambulatory stall is required. The ambulatory stall provided is inaccessible because the toilet is not centered within the stall, the toilet paper is only 1¼ inches below the grab bar and interferes with its use, a shelf is mounted 6 inches above the grab bar and interferes with its use, and the closer end of the grab bar on the right (facing the toilet) is mounted 13 inches from the rear wall ST1 36 months
6.8 Orchestra Level 0-3 Men's Toilet Room with Stalls
6.8.a The toilet room sign is mounted 57 ½ inches above the finished floor. TR18 36 months
6.8.b The toilet paper dispenser is inaccessible because it is mounted 40 inches from the rear wall. ST19 36 months
6.8.c The rear grab bar at the toilet is inaccessible because its closer end is 7 inches from the side wall. ST4 36 months
6.9 Orchestra Level 0-4 Men's Toilet Room with Stalls
6.9.a The toilet room sign is mounted 57 ½ inches above the finished floor. TR18 36 months
6.9.b The urinal is inaccessible because the rim is mounted 17 ½ inches above the finished floor. TR20 36 months
6.9.c The side grab bar at the toilet is inaccessible because its closer end is mounted 13 inches from the rear wall. ST7 36 months
6.9.d The rear grab bar at the toilet is inaccessible because its closer end is mounted 7 inches from the side wall. ST4 36 months
6.10 Orchestra Level 0-5 Women's Toilet Room with Stalls
6.10.a The side grab bar at the toilet is inaccessible because its closer end is mounted 13 inches from the rear wall. ST7 36 months
6.10.b The rear grab bar at the toilet is inaccessible because its closer end is mounted 7 inches from the side wall. ST4 36 months
6.10.c Because there are 6 or more stalls (10 total stalls), an ambulatory stall is required. The ambulatory stall provided is inaccessible because the stall is 36 ½ inches wide and both grab bars are mounted with their closer end 13 inches from the rear wall. ST1 36 months
6.11 Elevator E-1 near Toilet Room 0-3
6.11.a The elevator is inaccessible because the hall arrival signal sounds once for both "up" and "down." E11 36 months
6.11.b The clearance between the car platform sill and the edge of the hoistway landing is 1 ½ inches. E10 36 months
6.12 Circles Lounge - The bar has neither a lower portion nor accessible tables within the area. PD3 36 months
6.13 Circles Lounge Toilet Rooms Route
6.13.a The pull side of the door, which is accessed through a front approach, is inaccessible because it has only 9 ½ inches of clear space on the latch side. D6 36 months
6.14 Circles Lounge Men's Toilet Room with Stalls
6.14.a The designated accessible toilet is inaccessible because the flush control is on the closed side. ST2 36 months
6.14.b The toilet paper dispenser is inaccessible because it is mounted 41 inches from the rear wall. ST19 36 months
6.15 Circles Lounge Women's Toilet Room with Stalls - The route into the toilet room is impeded by a trash can. AR3 36 months
6.16 Green Room Dressing Room 132 - Soloist
6.16.a The closet is inaccessible because the bar is 64 inches above the finished floor. TR2 36 months
6.16.b The designated accessible toilet is inaccessible because the top of the seat is 19 ½ inches above the finished floor. ST20 36 months
6.17 Green Room Dressing Room 136 - Conductor
6.17.a The closet is inaccessible because the bar is 64 inches above the finished floor. TR2 36 months
6.17.b The designated accessible toilet is inaccessible because the top of the seat is 19 ½ inches above the finished floor. ST20 36 months
6.17.c The transfer shower is inaccessible because the shower seat is installed backwards. B10 36 months
6.18 Green Room Dressing Room 134
6.18.a The closet is inaccessible because the bar is 64 inches above the finished floor. TR2 36 months
6.18.b The transfer shower is inaccessible because the shower seat is installed backwards. B10 36 months
6.19 Green Room Drinking Fountain near Rooms 119 - 123
6.19.a The wall-mounted drinking fountain is inaccessible because it provides only 26¼ inches of knee space height. DF5 36 months
6.20 2nd Floor Drinking Fountain
6.20.a The wall-mounted drinking fountain is inaccessible because it only provides 26¼ inches of knee space height. DF5 36 months
6.21 Green Room Dressing Rooms 119 - 123
6.21.a The bench provided is only 12 inches wide and not attached to the wall. LR1 36 months
6.22 Shower near Room 123
6.22.a

The clear floor space at the shower is inaccessible because it does not overlap the transfer seat by 12 inches. B8 36 months
6.23 Toilet Room with Stalls near Room 123
6.23.a The side grab bar at the toilet is inaccessible because the closer end is 13 inches from the rear wall. ST7 36 months
6.23.b The rear grab bar at the toilet is inaccessible because the closer end is 7 inches from the side wall ST4 36 months
6.23.c The transfer shower is inaccessible because the shower seat is installed backwards. B10 36 months
6.24 Toilet Room with Stalls near Room 119
6.24.a The side grab bar at the toilet is inaccessible because the closer end is 13 inches from the rear wall. ST7 36 months
6.24.b The rear grab bar at the toilet is inaccessible because the closer end is 7 inches from the side wall ST4 36 months
6.25 Promenade Women's Toilet Room with Stalls P-2
6.25.a The side grab bar at the toilet is inaccessible because the closer end is 13 inches from the rear wall and the grab bar is mounted 36 ½ inches above the finished floor. ST11 36 months
6.25.b The rear grab bar at the toilet is inaccessible because the closer end is 7 inches from the side wall. ST4 36 months
6.26 Promenade Women's Toilet Room with Stalls P-3
6.26.a The designated accessible toilet is inaccessible because the flush control is on the closed side. ST2 36 months
6.26.b The side grab bar at the toilet is inaccessible because the closer end is 12 ½ inches from the rear wall and it is mounted 36 ½ inches above the finished floor. ST6 36 months
6.26.c The rear grab bar at the toilet is inaccessible because the closer end is 6 ½ inches from the side wall ST4 36 months
6.26.d Because there are 6 or more stalls (10 total stalls), an ambulatory stall is required. The ambulatory stall provided is inaccessible because the stall is 36 ½ inches wide. ST1 36 months
6.27 Promenade Men's Toilet Room with Stalls P-4
6.27.a The urinal is inaccessible because the flush control is mounted 44 ½ inches above the finished floor. TR20 36 months
6.27.b The side grab bar at the toilet is inaccessible because the closer end is 12 ½ inches from the rear wall and it is mounted 36 ½ inches above the finished floor. ST6 36 months
6.28 Drinking Fountains between P-1 and P-2, P-3 and P-4, G-1 and G-2, G-6 and G-7
6.28.a The wall-mounted drinking fountains at each location are inaccessible because they only provide 25 ½ inches of knee space height. DF5 36 months
6.29 Grand Tier Men's Toilet Room with Stalls G-1
6.29.a The side grab bar at the toilet is inaccessible because the toilet paper is 1¼ inches under the bar and interferes with its use. ST8 36 months
6.29.b The rear grab bar at the toilet is inaccessible because the closer end is 6 ½ inches from the side wall ST4 36 months
6.30 Grand Tier Women's Toilet Room with Stalls G-2
6.30.a The side grab bar at the toilet is inaccessible because the closer end is 13 inches from the rear wall and the grab bar is mounted 36 ½ inches above the finished floor. ST6 36 months
6.30.b The rear grab bar at the toilet is inaccessible because the closer end is 7 ½ inches from the side wall and the grab bar is mounted 36 ½ inches above the finished floor. ST3 36 months
6.30.c Although there are 8 total stalls and an ambulatory stall is provided, it is not accessible because it is 36 ½ inches wide, the toilet paper is 41 inches from the rear wall, and the left grab bar (facing toilet) is mounted with its closer end 13 inches from the rear wall. ST1 36 months
6.31 Grand Tier Men's Toilet Room with Stalls G-4 - The closer end of the rear grab bar at the toilet is mounted 7 inches from side wall. ST4 36 months
6.32 Grand Tier Women's Toilet Room with Stalls G-5
6.32.a The side grab bar at the toilet is inaccessible because the toilet paper is mounted 1¼ inches under the bar and interferes with its use. ST8 36 months
6.33 Grand Tier Single-User Unisex Toilet Room G-6
6.33.a The designated accessible toilet is inaccessible because its centerline is 17 inches from the side wall. SU15 36 months
6.33.b The rear grab bar at the toilet is inaccessible because its closer end is mounted 7 inches from the side wall. ST4 36 months
6.34 Grand Tier Single-User Unisex Toilet Room G-7
6.34.a The designated accessible toilet is inaccessible because its centerline is 17 inches from the side wall. SU15 36 months
6.34.b The rear grab bar at the toilet is inaccessible because its closer end is mounted 7 inches from the side wall. ST4 36 months
6.35 Box Office Corridor Men's Toilet Room with Stalls
6.35.a The grab bars are inaccessible for a variety of reasons. The side grab bar at the toilet is inaccessible because the toilet paper is mounted 1¼ inches under the bar and interferes with its use, the side grab bar is mounted with its closer end mounted 13 inches from the rear wall, and the rear grab bar is mounted with its closer end 7 ½ inches from the side wall. ST11 36 months
6.36 Box Office Corridor Women's Toilet Room with Stalls
6.36.a The grab bars at the toilet are inaccessible for a variety of reasons. The toilet paper is mounted 1¼ inches under the bar and interferes with its use; the side grab bar is mounted so its closer end is 13 inches from the rear wall, the rear grab bar is mounted so its closer end is 7 inches from the wall, and both grab bars are mounted more than 36 inches above the finished floor. ST11 36 months
6.36.b Although there are 6 stalls, and an ambulatory stall is provided, the grab bars in the ambulatory stall are mounted with their closer ends 13 inches from the rear wall, and the shelf above and toilet paper dispenser below the left grab bar interfere with the use of the bar. ST1 36 months
6.37 Box Office Corridor Drinking Fountain - The drinking fountain is inaccessible because the knee clearance is 25 ½ inches above the finished floor. DF5 36 months
6.38 Education Center 1st Floor Men's Toilet Room with Stalls - The grab bars at the toilet are inaccessible for a variety of reasons. The side grab bar is inaccessible because the toilet seat paper dispenser interferes with its use and because its closer end is mounted 13 inches from the rear wall. The rear grab bar at the toilet is inaccessible because its closer end is mounted 7 inches from the side wall. ST11 36 months
6.39 Education Center 1st Floor Women's Toilet Room with Stalls - The rear grab bar at the toilet is inaccessible because its closer end is mounted 7 inches from the side wall. ST4 36 months
6.40 Education Center 4th Floor Men's Toilet Room with Stalls - The grab bars at the toilet are inaccessible for a variety of reasons. The side grab bar at the toilet is inaccessible because the toilet seat dispenser interferes with its use and because its closer end is mounted 13 inches from the rear wall. The closer end of the rear grab bar is mounted 7 inches from the side wall. ST11 36 months
6.41 Education Center 4th Floor Women's Toilet Room with Stalls - The grab bars at the toilet are inaccessible for a variety of reasons. The side grab bar at the toilet is inaccessible because the toilet seat dispenser interferes with its use and because its closer end is mounted 13 inches from the rear wall. The closer end of the rear grab bar is mounted 7 inches from the side wall. ST11 36 months
7 Martin Luther King, Jr., Outdoor Pool / Swim Center, 1201 Jackson Road , Silver Spring, Maryland 20901
7.1 Parking - The parking lot, with a total of 22 parking spaces, is inaccessible because although 4 spaces are designated as being accessible, there is no van accessible space. This lot requires 1 van accessible space. P3 36 months
7.2 Staff Area Single-User Unisex Toilet Room
7.2.a The door is inaccessible because it requires 12 pounds of force to open. D2 36 months
7.2.b The lavatory is inaccessible because the door swings into the required clear floor space. TR6 36 months
7.2.c No accessible mirror has been provided. TR14 36 months
7.2.d The lavatory is inaccessible because the bottom edge of the lavatory apron is 28 inches above the finished floor. TR11 36 months
7.2.e The hand dryer protrudes into the walkway and is not detectable to blind persons using a cane. AR8 36 months
7.2.f The toilet is inaccessible because the top of the seat is 20 ½ inches above the finished floor. SU18 36 months
7.2.g The grab bars at the toilet are inaccessible for a variety of reasons. The side grab bar is 34 inches long, its farther end is 36 inches from the rear wall, and it is mounted 37 inches above the finished floor. The rear grab bar is 22 inches long and is mounted 37 inches above the finished floor. ST11 36 months
7.3 Men's Outdoor Pool Locker Room
7.3.a The locker room sign is not mounted with its centerline 60 inches above the finished floor, and it has no raised or Braille characters. D16 36 months
7.3.b No accessible mirror has been provided. TR14 36 months
7.3.c The hand dryers protrude into the walkway and would not be detectable to a blind person using a cane. AR8 36 months
7.3.d The urinal is inaccessible because its rim is 18 ½ inches above the finished floor. TR20 36 months
7.3.e Although there are 6 stalls, there is no ambulatory stall provided. ST1 36 months
7.3.f No accessible coat hook has been provided. TR1 36 months
7.3.g The side grab bar at the toilet is inaccessible because it is 34 inches long, the farther end is 36 inches from the rear wall, and it is mounted 37 inches above the finished floor. ST6 36 months
7.3.h The rear grab bar at the toilet is inaccessible because it is 22 inches long and is mounted 37 inches above the finished floor. SU2 36 months
7.3.i The shower does not provide sufficient clear floor space, the shower transfer seat is 19 ½ inches above the floor, there are no grab bars, the shower hose is 57 inches long, and the shower for people with disabilities does not offer the same privacy that the other showers do. B8 36 months
7.3.j The bench in the locker room is inaccessible because it is only 15 ¼ inches wide. LR1 36 months
7.4 Women's Outdoor Pool Locker Room
7.4.a The locker room sign has no raised or Braille characters, and it is not mounted with its centerline 60 inches above the finished floor. D16 36 months
7.4.b No accessible mirror has been provided. TR14 36 months
7.4.c The hand dryers protrude into the walkway and are not detectable to blind persons using a cane. AR8 36 months
7.4.d Although there are 9 stalls in the toilet room, there is no ambulatory stall provided. ST1 36 months
7.4.e The toilet paper dispenser is inaccessible because it is mounted 37 inches from the rear wall. ST19 36 months
7.4.f The side grab bar at the toilet is inaccessible because it is 34 inches long, the farther end is 36 inches from the rear wall, and it is mounted 37 inches above the finished floor. ST6 36 months
7.4.g The rear grab bar at the toilet is inaccessible because it is 22 inches long and is mounted 37 inches above the finished floor. SU2 36 months
7.4.h Grab bars are not provided at the shower, and the shower hose is 57 inches long. In addition, because it does not have a curtain or private changing area, the accessible shower does not afford its users the same level of privacy as the other showers do. B8 36 months
7.4.i The bench in the locker room is inaccessible because it is only 15 ¼ inches wide. LR1 36 months
7.5 Outdoor Pool Single-User Unisex Roll-In Shower
7.5.a Grab bars and not provided at the shower, and the shower hose is 57 inches long. B8 36 months
7.6 Outdoor Pool Unisex Changing Room
7.6.a The changing room sign has no raised or Braille characters, and the sign is not mounted with its centerline 60 inches above the finished floor. D16 36 months
7.6.b The door is inaccessible because it requires 15 pounds of force to open. D2 36 months
7.6.c The hand dryer protrudes into the walkway and is not detectable to blind persons using a cane. AR8 36 months
7.6.d No accessible mirror has been provided. TR14 36 months
7.6.e The toilet is inaccessible because its centerline is 19 inches from the side wall. SU15 36 months
7.6.f The clear floor space at the toilet is impeded by a pull-down side grab bar. SU16 36 months
7.6.g The side grab bar at the toilet is inaccessible because it is on the "open" side of the toilet, it is 28 ½ inches long, the far end is 28 ½ inches from the rear wall, and it is mounted 37 inches above the finished floor. SU5 36 months
7.6.h There is no rear grab bar provided. SU2 36 months
7.6.i Grab bars are not provided at the shower, and the seat provided is not adjacent to the shower controls. B8 36 months
7.7 Pool Picnic Tables
7.7.a There are no accessible picnic tables provided for use by people with mobility disabilities. PD6 36 months
8 Bethesda Chevy Chase Regional Services Center, 4805 Edgemoor Lane, Bethesda, Maryland 20814
8.1 Administrative Office / Lobby
8.1.a The counter is inaccessible because it is 43 inches above the finished floor. C6 12 months
8.2 Signs
8.2.a The signs for rooms and offices throughout the building are not mounted with their centerlines 60 inches above the finished floor, and these signs have no raised or Braille characters. D16 12 months
8.3 Administrative Office Single-User Unisex Toilet Room
8.3.a The toilet room sign is inaccessible. TR18 12 months
8.3.b The lavatory is inaccessible because the hot water pipes are not insulated or otherwise configured to protect against contact. TR12 12 months
8.3.c The toilet is inaccessible because the top of the seat is 15 inches above the finished floor. SU18 12 months
8.3.d The designated accessible toilet is inaccessible because the flush control is on the closed side. SU1 12 months
8.4 Men's 2nd Floor Toilet Room with Stalls
8.4.a The door is inaccessible because it requires 8 pounds of force to open. D2 12 months
8.4.b The side grab bar at the toilet is obstructed because the toilet paper dispenser is mounted with its top ¼ inch below the bar. SU4 12 months
8.5 Women's 2nd Floor Toilet Room with Stalls
8.5.a The feminine products dispenser is inaccessible because it has twist-type hardware. TR3 12 months
8.6 Senior Services Main Entrance
8.6.a The entrance is inaccessible because the newspaper stand blocks the pull side clearance at the door, which is required for a front approach. D6 12 months
8.7 Day Care Single-User Toilet Room near Kitchen
8.7.a The toilet is inaccessible because the top of the seat is 15 inches above the finished floor. SU18 12 months
8.7.b The toilet is inaccessible because its centerline is 19 inches from the side wall. SU15 12 months
8.7.c The designated accessible toilet is inaccessible because the flush control is on the closed side. SU1 12 months
9 Long Branch Senior Center, 8700 Piney Branch Road, Silver Spring, Maryland 20901
9.1 Parking
9.1.a The parking lot is inaccessible because although it has designated accessible parking spaces, there are no van accessible spaces provided, two of the access aisles serving the standard accessible spaces are 52 and 49 inches wide, and the spaces have slopes exceeding 2 %. This lot requires 1 van accessible space and 1 standard accessible space. P3 36 months
9.2 Ramp at Front Center of Community Center
9.2.a The ramp is inaccessible because the bottom leg of the ramp has a slope of 9.6%, and the handrails do not have extensions at the top and bottom of the ramp. R3 36 months
9.3 Entrance Ramps, Left and Right side
9.3.a The ramp on the left is inaccessible because the middle legs of the ramp have slopes ranging between 8.9% and 9.2%; there are insufficient landings at the top, bottom, and middle of the ramp (i.e., landings are too small and they have excessive slopes ranging between 2.4% and 3.9%); there are no handrail extensions at the tops and bottoms of the ramp; the ends of the handrails are not rounded or returned to the floor/ground; and the handrail diameter is 2¼ inches. The ramp on the right is inaccessible because the middle legs have excessive slopes ranging between 9.3% and 9.4%; there are insufficient landings at the top, bottom, and middle (too small, and they have slopes ranging between 4.6% and 5.7%); and there are insufficient handrail extensions. AR1, D16, MC5 36 months
9.4 Route from Accessible Parking to Front Entrance
9.4.a The slope of the route is 5.8% with no ramp features, and the cross-slope is 5.8%. AR1 36 months
9.4.b The curb ramp is inaccessible the slopes of the primary curb ramps are as follows: 11% running slope with a flared side having a slope of 10.7%; 9.5% running slope; 9.2% running slope with a flared side having a slope of 12%; and 8.4% running slope. AR5 36 months
9.5 Entrances
9.5.a There is no directional signage at the inaccessible entrances to direct people to the accessible entrance. D16 36 months
9.5.b At one of the entrances, the control button that operates the interior vestibule door requires 14 pounds of force. D2 36 months
9.6 Gym / Workout Room
9.6.a The coat rack is inaccessible because the clothing bar is 65 inches above the finished floor. TR2 36 months
9.7 Social Hall, Community Lounge, Arts and Crafts Room, Conference Room, Game Room
9.7.a Each of these rooms is inaccessible to people who are deaf or hard of hearing because there is no signage informing the public of the availability of an assistive listening system. AA4

AA3

36 months
9.7.b The game room door is inaccessible because it requires 15 pounds of force to open. D2 36 months
9.8 Women's 1st Floor Locker Room
9.8.a The door is inaccessible because it requires 10 pounds of force to open. D2 36 months
9.8.b The door is inaccessible because it has a ½ inch threshold. D22 36 months
9.8.c The air dryers protrude into the walkway and are not detectable to blind persons using a cane. AR8 36 months
9.8.d The seat cover dispenser is inaccessible because the controls are mounted 58 inches above the finished floor. TR5 36 months
9.8.e No accessible coat hook has been provided. TR1 36 months
9.8.f The side grab bar at the toilet is inaccessible because the toilet paper is mounted above the bar and interferes with its use, and the farther end of the side grab bar is 51 ½ inches from the rear wall. ST8 36 months
9.8.g The rear grab bar at the toilet is inaccessible because its closer end is 8 ½ inches from the side wall. ST4 36 months
9.8.h The shower is inaccessible because it does not provide a fixed shower head, the seat does not extend the full length of the shower, and the shower hose is 57 inches long. B8 36 months
9.8.i The bench provided is inaccessible because it is 11 ½ inches wide and 15 ½ inches high. LR1 36 months
9.9 Men's 1st Floor Lobby Locker Room
9.9.a The door is inaccessible because there is a ½ inch threshold. D22 36 months
9.9.b The air dryers protrude into the walkway and are not detectable to blind persons using a cane. AR8 36 months
9.9.c The lavatory is inaccessible because the hot water pipes are not insulated or otherwise configured to protect against contact. TR12 36 months
9.9.d The designated accessible toilet is inaccessible because the flush control is on the closed side. ST2 36 months
9.9.e No accessible coat hook has been provided. TR1 36 months
9.9.f The seat cover dispenser is inaccessible because the controls are mounted 59 inches above the finished floor. TR5 36 months
9.9.g The side grab bar at the toilet is inaccessible because the toilet paper is mounted above the bar and interferes with its use, and the farther end of the grab bar is 50 ½ inches from the rear wall. ST8 36 months
9.9.h The rear grab bar at the toilet is inaccessible because its closer end is 7 ½ inches from the side wall. ST4 36 months
9.9.i The shower is inaccessible because it does not provide a fixed shower head, the seat is 16 ½ inches from the shower floor, and the shower hose is 58 inches long. B8 36 months
9.9.j The bench provided is inaccessible because it is 11 ½ inches wide and 15 ½ inches high. LR1 36 months
9.10 Telephone
9.10.a The telephone is inaccessible because chairs impede the approach, and there is no volume control or signage. AR2 36 months
9.11 Elevator
9.11.a The elevator is inaccessible because the doors begin to close only 3 or 4 seconds after notification of elevator arrival. E6 36 months
9.12 Drinking Fountains
9.12.a The drinking fountains on the 1st and 2nd floor are protruding objects and are not be detectable to a blind person using a cane. AR8 36 months
9.13 Women's 2nd Floor Toilet Room with Stalls
9.13.a The seat cover dispenser is inaccessible because the controls are mounted 61 inches above the finished floor. TR5 36 months
9.13.b The diaper changing table is inaccessible because the handle is mounted 55 inches above the finished floor. TR5 36 months
9.13.c The designated accessible toilet is inaccessible because the top of the seat is 19 ½ inches above the finished floor. ST20 36 months
9.13.d No accessible coat hook has been provided. TR1 36 months
9.13.e The side grab bar at the toilet is inaccessible because the toilet paper dispenser is mounted above the bar and interferes with its use, and the farther end is 48 ½ inches from the rear wall. ST8 36 months
9.13.f The rear grab bar at the toilet is inaccessible because the closer end is 8 inches from the side wall. ST4 36 months
9.14 Men's 2nd Floor Toilet Room with Stalls
9.14.a The seat cover dispenser is inaccessible because the controls are mounted 62 inches above the finished floor. TR5 36 months
9.14.b The hand dryer protrudes into the walkway and is not detectable to blind persons using a cane. AR8 36 months
9.14.c The urinal is inaccessible because only 28 inches of clear floor space width are provided at the urinal. TR20 36 months
9.14.d The designated accessible toilet is inaccessible because its centerline is 17 inches from the side wall. ST17 36 months
9.14.e The designated accessible toilet is inaccessible because the flush control is on the closed side. ST2 36 months
9.14.f No accessible coat hook has been provided. TR1 36 months
9.14.g The side grab bar at the toilet is inaccessible because the toilet paper dispenser is mounted above the bar and interferes with its use, and the farther end is 51 inches from the rear wall. ST8 36 months
9.14.h The rear grab bar at the toilet is inaccessible because the closer end is 8 ½ inches from the side wall. ST4 36 months
10 Conference Center, 5701 Marinelli Drive, North Bethesda, Maryland 20852
10.1

Parking
10.1.a The van accessible parking reserved for persons with disabilities lacks the appropriate signage. P6 36 months
10.1.b One of the parking spaces reserved for persons with disabilities is inaccessible because the space has a slope of 2.8% and a cross slope of 4.1%. P7 36 months
10.2 Accessible Route
10.2.a The route from the parking area to the entrance is inaccessible because it has a steep cross slope of 3.5%. AR1 36 months
10.2.b The route from the parking area to the entrance is inaccessible because the slope of the curb ramp in front is 11.9%; the slope of the curb ramp next to the parking is 15.8%; the slope of the curb ramp next to the building is 21.8%; the gutter from the sidewalk heading south has a slope of 13.4% with a ¾ inch change in level at the top; and the middle curb ramps in front between the drives have slopes of 8.9% with a gutter slope of 13.1%. AR5 36 months
10.2.c The route from the sidewalk to the lower level entrance has a slope of 10.3%. AR1 36 months
10.3 Entrances
10.3.a The building is inaccessible because there is no signage identifying the accessible entrance and no directional signage at the inaccessible entrances. D16 36 months
10.3.b The building is inaccessible because fewer than 50% of its entrances are accessible. D12 36 months
10.4 Assistive Listening System
10.4.a There is no signage informing the public of the availability of an assistive listening system. AA3 36 months
10.5 Brookside A, Oakley, and Event Room (staff only)
10.5.a The doors to the following rooms is excessive: Brookside A (7 pounds), Oakley (9 pounds), and Event Room (8 pounds) D2 36 months
10.6 Women's Employee Locker Room
10.6.a The room sign is mounted on the door and has no raised characters or Braille. TR18 36 months
10.6.b The door is inaccessible because it requires 11 pounds of force to open. D2 36 months
10.6.c The lotion dispenser is inaccessible because the controls are mounted 56 inches above the finished floor with a forward reach required. TR5 36 months
10.6.d The designated accessible toilet is inaccessible because the top of the seat is 19 ½ inches above the finished floor. ST20 36 months
10.6.e No accessible coat hook has been provided. TR1 36 months
10.6.f The toilet paper dispenser is inaccessible because it is mounted on the rear wall. ST19 36 months
10.6.g The door to the accessible stall does not have a door latch and, therefore, does not provide people with disabilities the same level of privacy that is afforded to people without disabilities. D1 36 months
10.6.h The bench provided is inaccessible because it is 9 ½ inches wide. LR1 36 months
10.7 Men's Employee Locker Room
10.7.a The room sign is mounted on the door and has no raised characters or Braille. TR18 36 months
10.7.b The door is inaccessible because it requires 12 pounds of force to open. D2 36 months
10.7.c The lotion dispenser is inaccessible because the controls are mounted 57 inches above the finished floor with a forward reach required. TR5 36 months
10.7.d The designated accessible toilet is inaccessible because the top of the seat is 20 inches above the finished floor. ST20 36 months
10.7.e No accessible coat hook has been provided. TR1 36 months
10.7.f The toilet paper dispenser is inaccessible because it is mounted 171/2 inches above the finished floor. ST19 36 months
10.7.g The bench provided is 9 ½ inches wide. LR1 36 months
10.8 Business Center and Staff Office
10.8.a The doors to the Business Center and the Staff Office is inaccessible because they each require 8 pounds of force to open. D2 36 months
10.9 Front Reception Office
10.9.a The counter is inaccessible because it is more than 36 inches above the finished floor. C6 36 months
10.10 Amphitheater
10.10.a The door at the top of the amphitheater is inaccessible because it requires 8 pounds of force to open. D2 36 months
10.10.b The ramp to the floor of the amphitheater has a handrail mounted with 2½ inches between the ramp handrails and wall, and the top landing is only 50 inches deep. R5 36 months
10.10.c The corner of the ramp handrail protrudes into the walkway and is not detectable to a blind person using a cane. AR8 36 months
10.10.d There is no signage informing the public of the availability of an assistive listening system. AA3 36 months
10.11 Telephones
10.11.a The telephone provided at the employee locker room is inaccessible because the highest operable part is 57 inches above the finished floor. TT1 36 months
10.12 Upper Level Unisex Single-User Toilet Room
10.12.a The door is inaccessible because it requires 13 pounds of force to open. D2 36 months
10.12.b No accessible mirror has been provided. TR14 36 months
10.12.c The designated accessible toilet stall is inaccessible because it has insufficient clear floor space. ST16 36 months
10.12.d The rear grab bar at the toilet is inaccessible because it is 24 inches long. ST4 36 months
10.13 Upper Level Women's Toilet Room with Stalls
10.13.a The door is inaccessible because it requires 14 pounds of force to open. D2 36 months
10.13.b No accessible mirror has been provided. TR14 36 months
10.13.c Although there are 6 stalls, no ambulatory stall has been provided. ST1 36 months
10.13.d No accessible coat hook has been provided. TR1 36 months
10.14 Upper Level Men's Toilet Room with Stalls
10.14.a The door is inaccessible because it requires 8 pounds of force to open. D2 36 months
10.14.b No accessible mirror has been provided. TR14 36 months
10.14.c No accessible coat hook has been provided. TR1 36 months
10.14.d The toilet paper dispenser is inaccessible because it is mounted 18 inches above the finished floor. ST19 36 months
10.15 Starbucks' Women's Toilet Room with Stalls
10.15.a The door is inaccessible because it requires 10 pounds of force to open. D2 36 months
10.15.b The lavatory is inaccessible because there is insufficient knee clearance. TR11 36 months
10.15.c No accessible coat hook has been provided. TR1 36 months
10.15.d The toilet paper dispenser is inaccessible because it is mounted 43 inches from the rear wall. ST19 36 months
10.15.e Although there is an ambulatory stall provided, it is 38 inches wide, and the grab bars are mounted 37 inches above the finished floor. ST1 36 months
10.16 Starbucks' Men's Toilet Room with Stalls
10.16.a The door is inaccessible because it requires 14 pounds of force to open. D2 36 months
10.16.b No accessible mirror has been provided. TR14 36 months
10.16.c The lavatory is inaccessible because it has insufficient knee clearance. TR11 36 months
10.16.d The designated accessible toilet is inaccessible because its centerline is 19 inches from the side wall. ST17 36 months
10.16.e No accessible coat hook has been provided. TR1 36 months
10.17 Lower Level Women's Toilet Room with Stalls
10.17.a The room sign is mounted on the door and has no raised characters or Braille. TR18 36 months
10.17.b The door is inaccessible because it requires 8 pounds of force to open. D2 36 months
10.17.c The pull side of the door, which is accessed through a front approach, is inaccessible because it has only 9 inches of clear space on the latch side. D6 36 months
10.17.d The lavatory is inaccessible because it has insufficient knee clearance. TR11 36 months
10.17.e The toilet paper dispenser in the standard accessible stall is inaccessible because it is mounted 43 inches from the rear wall. ST19 36 months
10.17.f The toilet paper dispenser in the ambulatory stall is inaccessible because it is mounted 41 inches from the rear wall. ST19 36 months
10.18 Lower Level Men's Toilet Room with Stalls
10.18.a The room sign is inaccessible because it has no raised characters. TR18 36 months
10.18.b The door is inaccessible because it requires 9 pounds of force to open. D2 36 months
10.18.c No accessible mirror has been provided. TR14 36 months
10.18.d The designated accessible toilet is inaccessible because its centerline is 19 inches from the side wall. ST17 36 months
10.18.e No accessible coat hook has been provided. TR1 36 months
10.18.f The toilet paper dispenser is inaccessible because it is mounted 18 inches above the finished floor. ST19 36 months
10.18.g Although an ambulatory stall is provided, it is 36 ½ inches wide and the centerline of the toilet is 17 inches from the side wall. ST1 36 months
11 Black Rock Center for the Arts, 12901 Town Commons Drive, Germantown, Maryland 20874
11.1 Rear Parking
11.1.a The parking lot, with a total of 76 parking spaces, is inaccessible because only 3 spaces reserved for people with disabilities. This lot requires 1 van accessible space and 3 standard accessible spaces. P3 36 months
11.2 Street-Side Entrance Exterior Ramp
11.2.a The ramp is inaccessible because the bottom landing has a slope of 14% and a cross slope of 7%. R5 36 months
11.3 Dance Studio
11.3.a The door between the dance studio and dressing area is inaccessible because it requires 10 pounds of force to open. D2 36 months
11.3.b The route to the control booth is inaccessible because it requires using a steep flight of stairs / ladder. AR1 36 months
11.4 Dance Studio Dressing Area Toilet Rooms (left and right)
11.4.a The two toilet rooms have no accessible features. SU13 36 months
11.5 Dance Studio Dressing Area Accessible Unisex Toilet and Shower Room (middle)
11.5.a Although an audible alarm is provided in this facility, there is no visual alarm appliance in the toilet room. AL1 36 months
11.5.b No accessible mirror has been provided. TR14 36 months
11.5.c The toilet is inaccessible because its centerline is 19 ½ inches from the side wall. SU15 36 months
11.5.d No accessible coat hook has been provided. TR1 36 months
11.5.e The shower is inaccessible because there is a ¾ inch curb at the entrance to the shower. B7 36 months
11.5.f The shower is inaccessible because the seat does not extend the full width of the shower stall. B10 36 months
11.6 Auditorium
11.6.a The accessible seating locations have no fixed companion seats AA6 36 months
11.7 Auditorium Dressing Area Toilet Rooms (left and right)
11.7.a The two single user toilet rooms behind the auditorium have no accessible features. SU13 36 months
11.8 Auditorium Unisex Toilet and Shower Room (middle)
11.8.a No accessible mirror has been provided. TR14 36 months
11.8.b The toilet is inaccessible because the top of the seat is 19 ½ inches above the finished floor. SU18 36 months
11.8.c No accessible coat hook has been provided. TR1 36 months
11.8.d The side grab bar at the toilet is inaccessible because its farther end is 48 inches from the rear wall. ST7 36 months
11.8.e The rear grab bar at the toilet is inaccessible because it is 24 inches long. ST4 36 months
11.8.f The shower is inaccessible because the clear floor space required for transfer overhangs the wrong wall of the shower (the one opposite the seat) and there is a ¾ inch curb. B8 36 months
11.9 1st Floor Women's Toilet Room with Stalls
11.9.a The door is inaccessible because it requires 10 pounds of force to open. D2 36 months
11.9.b The baby changing table is inaccessible because the handle is 53 inches above the finished floor and a forward reach is required. TR5 36 months
11.9.c The designated accessible toilet stall is inaccessible because it is 58 inches wide. ST16 36 months
11.9.d The designated accessible toilet is inaccessible because the top of the seat is 19 ½ inches above the finished floor. ST20 36 months
11.9.e The designated accessible toilet is inaccessible because its centerline is 19 inches from the side wall. ST17 36 months
11.10 1st Floor Men's Toilet Room with Stalls
11.10.a The door is inaccessible because it requires 10 pounds of force to open. D2 36 months
11.10.b The baby changing table is inaccessible because the controls (handle) are mounted 53 inches above the finished floor and a forward reach is required. TR5 36 months
11.10.c The designated accessible toilet is inaccessible because the top of the seat is 20 inches above the finished floor. ST20 36 months
11.11 1st Floor Lobby Drinking Fountains
11.11.a The drinking fountains protrude into the walkway and are not detectable to a blind person using a cane. AR8 36 months
11.12 Studio 1, 2, and 3
11.12.a The studio is inaccessible to people who are deaf or hard of hearing because there is no signage informing the public of the availability of an assistive listening system. AA4

AA3

36 months
11.13 Conference Room #217
11.13.a The studio is inaccessible to people who are deaf or hard of hearing because there is no signage informing the public of the availability of an assistive listening system. AA4

AA3

36 months
11.14 2nd Floor Drinking Fountains
11.14.a The drinking fountains protrude into the walkway and are not detectable to a blind person using a cane. AR8 36 months
11.15 2nd Floor Women's Toilet Room with Stalls
11.15.a The door is inaccessible because it requires 11 pounds of force to open. D2 36 months
11.15.b The side grab bar at the toilet is inaccessible because its closer end is 13 inches from the rear wall. ST7 36 months
11.16 2nd Floor Men's Toilet Room with Stalls
11.16.a The door is inaccessible because it requires 11 pounds of force to open. D2 36 months
11.16.b The lavatory is inaccessible because the trash can obstructs the clear floor space. TR6 36 months
12 Rockville Public Library, 21 Maryland Avenue, Rockville, MD
12.1 Exterior Entrances and Doors - Maryland Avenue Entrance
12.1.a The building is inaccessible because directional signage is not provided at the inaccessible entrance. D16 24 months
12.1.b The door is inaccessible because it requires 11 pounds of force to open. D2 24 months
12.2 Women's Toilet Room with Stalls - 3rd Floor
12.2.a The building is inaccessible because the number of accessible entrances is not equivalent to the number of exits required by the applicable building/fire codes. Provide at least 2 accessible entrances to the building and provide signage at all inaccessible entrances directing users to the accessible entrance(s). D12 24 months
12.2.b The route from the entrance into the library is inaccessible because it requires the use of stairs. AR1 24 months
12.3 Women's Toilet Room with Stalls - Front Entrance
12.3.a The door is inaccessible because it requires 15 pounds of force to open. D2 24 months
12.3.b No accessible coat hook has been provided. TR1 24 months
12.3.c The side grab bar at the toilet is inaccessible because it is mounted 37 inches above the finished floor. ST12 24 months
12.4 Men's Toilet Room with Stalls - Front Entrance
12.4.a The door is inaccessible because it requires 18 pounds of force to open. D2 24 months
12.4.b The urinal is inaccessible because the flush control is mounted 45 inches above the finished floor and the rim is 17 3/8 inches above the finished floor. TR20 24 months
12.4.c No accessible coat hook has been provided. TR1 24 months
12.4.d The side grab bar at the toilet is inaccessible because it is mounted 36 ½ inches above the finished floor. ST12 24 months
12.5 Drinking Fountain- 1st Floor
12.5.a The drinking fountain is inaccessible because it has only 26 inches of knee space height. DF5 24 months
12.6 Children's Area
12.6.a The tables are inaccessible because none provide adequate knee clearance. L4 24 months
12.7 Meeting Room 1- 1st Floor
12.7.a The door is inaccessible because it requires 12 pounds of force to open. D2 24 months
12.8 Staff Office- 1st Floor
12.8.a The door is inaccessible because it requires 14 pounds of force to open. D2 24 months
12.8.b The cabinet protrudes 28 inches into the walkway is not detectable to blind persons using a cane. AR8 24 months
12.9 Single User Family Restroom in Children's Area- 1st Floor
12.9.a The toilet room door swings into the required clear floor space at the toilet. SU16 24 months
12.10 Single User Staff Only Toilet Room - 1st Floor
12.10.a The door is inaccessible because it requires 14 pounds of force to open. D2 24 months
12.10.b The toilet is inaccessible because its centerline is 19 inches from the side wall. SU15 24 months
12.10.c The side grab bar at the toilet is inaccessible because its closer end is 13 ½ inches from the rear wall. SU6 24 months
12.10.d The side grab bar at the toilet is inaccessible because it is mounted at 36 3/4 inches above the finished floor. SU11 24 months
12.11 Drinking Fountain- 2nd Floor
12.11.a The drinking fountain is inaccessible because it only provides 26 inches of knee space height. DF5 24 months
12.12 Women's Toilet Room with Stalls - 2nd Floor
12.12.a The door is inaccessible because it requires 14 pounds of force to open. D2 24 months
12.12.b The designated accessible toilet is inaccessible because its centerline is 17 3/4 inches from the side wall. ST17 24 months
12.13 Mens's Toilet Room with Stalls - 2nd Floor
12.13.a The door is inaccessible because it requires 15 pounds of force to open. D2 24 months
12.13.b The urinal is inaccessible because the flush control is mounted 45 inches above the finished floor. TR20 24 months
12.14 Library Area - 2nd Floor
12.14.a The map catalog is inaccessible because the bottom of it is 11 inches above the floor. L2 24 months
12.14.b A column near one of the stacks reduces the width between them to 31 inches. L5 24 months
12.14.c The study room door is inaccessible because it requires 15 pounds of force to open. D2 24 months
12.15 Meeting Room 2 and Staff Only Office - 2nd Floor
12.15.a The door to the Meeting Room is 11 pounds, and the Staff Only Office is 9 pounds. D2 24 months
12.16 Kitchen Area - 2nd Floor
12.16.a The coat rack area requires a reach 75 inches above the finished floor. 24 months
12.17 Computer Lab - 2nd Floor
12.17.a The door is inaccessible because it requires 10 pounds of force to open. D2 24 months
12.17.b The back row of tables provide only 26 inches of knee space height. L4 24 months
12.18 Staff-Only Single User Toilet Room - 2nd Floor
12.18.a The door is inaccessible because it requires 15 pounds of force to open. D2 24 months
12.18.b The toilet is inaccessible because its centerline is 16 ½ inches from the side wall. SU15 24 months
12.19 Drinking Fountain - 3rd Floor
12.19.a The drinking fountain is inaccessible because it only provides 26 inches of knee space height. DF5 24 months
12.20 Beal Street Entrance
12.20.a The toilet room sign is mounted with its centerline 62 inches above the finished floor. TR18 24 months
12.20.b The door is inaccessible because it requires 18 pounds of force to open. D2 24 months
12.20.c The designated accessible toilet is inaccessible because its centerline is 18 ½ inches from the side wall. ST17 24 months
12.20.d The side grab bar at the toilet is inaccessible because its overall length is 36 inches. ST7 24 months
12.21 Men's Toilet Room with Stalls - 3rd Floor
12.21.a The toilet room sign is mounted with its centerline 62 inches above the finished floor. TR18 24 months
12.21.b The door is inaccessible because it requires 16 pounds of force to open. D2 24 months
12.21.c The urinal is inaccessible because the flush control is mounted 48 ½ inches above the finished floor. TR20 24 months
12.22 Library Admin Office Entrance - Suite 310
12.22.a The double doors are inaccessible because each leaf only provides a clear opening of 31 inches. D25 24 months
12.22.b The door is inaccessible because it requires 19 pounds of force to open. D2 24 months
12.23 GIS Training Lab - 3rd Floor
12.23.a The tables in the lab are inaccessible because their bottom edges are only 25 ½ inches above the finished floor and they do not provide adequate knee clearance. T1 24 months
12.24 GIS Lunch Area - 3rd Floor
12.24.a The route between the table and refrigerator is inaccessible because it is only 30 ½ inches wide. AR3 24 months
12.25 Literary/Council (Suite 320) and (Office of Human Rights (Suite 330)
12.25.a The door to the Literacy Council is 10 pounds, and the door to the Office of Human Rights is 9 pounds. D2 24 months
12.26 Library 233
12.26.a The route between the table and the bookcase is inaccessible because only 26 inches of clear space is provided. AR3 24 months
13 Silver Spring Volunteer Fire Department - Station 1, 8131 Georgia Avenue, Silver Spring, MD 20910
13.1 Exterior Entrances
13.1.a The building is inaccessible because fewer than 50% of its entrances are accessible. D12 36 months
13.2 Counter
13.2.a The main counter is inaccessible because it is 41 inches above the finished floor. C6 36 months
13.2.b The fire extinguisher protrudes 7 inches into the walkway at a height of 32 inches above the finished floor and is not detectable to blind persons using a cane. AR8 36 months
13.3 Men's Accessible Locker Room
13.3.a The door is inaccessible because it requires 9 pounds of force to open. D2 36 months
13.3.b No accessible mirror has been provided. TR14 36 months
13.3.c The seat cover dispenser is inaccessible because it is mounted 57 inches above the finished floor. TR5 36 months
13.3.d The clear floor space at the toilet is too narrow. ST16 36 months
13.3.e The toilet paper dispenser is inaccessible because it is mounted too far from the rear wall. ST19 36 months
13.3.f A side grab bar is not provided at the toilet. ST6 36 months
13.3.g The shower is inaccessible because it is 38 inches wide and 36 ½ inches deep. B8 36 months
13.3.h The bench provided is 15 inches wide and 16 ½ inches high, and it is not attached or fixed to the wall. LR1 36 months
13.4 Lounge Area
13.4.a The route within the area provides only 28 inches between the chair and the couch. AR3 36 months
13.5 Truck Bay and nearby routes
13.5.a The door is inaccessible because it requires 12 pounds of force to open. D2 36 months
13.5.b The routes into the bay area and the workout room are inaccessible because of the presence of a step. AR1 36 months
13.6 Community Room
13.6.a The community room does not have an assistive listening system. AA4 36 months
13.6.b The telephone is inaccessible because its highest operable part is mounted beyond the reach ranges of a person using a wheelchair. TT1 36 months
13.6.c The television protrudes into the walkway and is not detectable to blind persons using a cane. AR8 36 months
13.7 Women's Single User Toilet Room - Near Community Room
13.7.a The door is inaccessible because it requires 7 pounds of force to open. D2 36 months
13.7.b The pull side of the door, which is accessed through a front approach, is inaccessible because it has only 16 inches of maneuvering clearance on the latch side of the door. D6 36 months
13.7.c The seat cover dispenser is inaccessible because it requires a reach of 61 inches above the finished floor. TR5 36 months
13.7.d The grab bars at the toilet are inaccessible because 1 ¾ inches of space is provided between the wall and each of the grab bars. SU10 36 months
13.8 Men's Single User Toilet Room - Near Community Room
13.8.a The door is inaccessible because it requires 10 pounds of force to open. D2 36 months
13.8.b The seat cover dispenser is inaccessible because it requires a reach of 57 inches above the finished floor. TR5 36 months
13.9 Women's Locker Room - 2nd Floor
13.9.a The door is inaccessible because it requires 11 pounds of force to open. D2 36 months
13.9.b No accessible mirror has been provided. TR14 36 months
13.9.c The seat cover dispenser is inaccessible because it requires a reach 55 inches above the finished floor. TR5 36 months
13.9.d The designated accessible toilet stall is inaccessible because it is 57 inches wide by 60 inches deep with a floor mounted toilet. ST16 36 months
13.9.e The designated accessible toilet is inaccessible because its centerline is 17 inches from the side wall. ST17 36 months
13.9.f The bench is inaccessible because it is 36 inches long and 9 inches wide, it is not attached at the wall, and it provides only 20 inches of clear floor space. LR1 36 months
13.10 Men's Locker Room - 2nd Floor
13.10.a The door is inaccessible because it requires 9 pounds of force to open. D2 36 months
13.10.b No accessible mirror has been provided. TR14 36 months
13.10.c The side grab bar at the toilet is inaccessible because it is mounted 36 ½ inches above the finished floor and its farther end is 48 inches from the rear wall. ST6 36 months
13.10.d The designated accessible toilet stall is inaccessible because it is 57 inches wide by 60 inches deep. ST16 36 months
13.10.e The bench is inaccessible because it is 36 inches long and 9 inches wide, it is not attached at the wall, and it provides only 27 inches of clear floor space. LR1 36 months
13.10.f The fire extinguisher cabinet protrudes into the walkway and is not detectable to blind persons using a cane. AR8 36 months
13.11 Women's Single User Toilet Room - 2nd floor
13.11.a The door is inaccessible because it requires 12 pounds of force to open. D2 36 months
13.11.b The seat cover dispenser is inaccessible because it requires a reach 61 inches above the finished floor. TR5 36 months
13.12 Men's Single User Toilet Room - 2nd floor
13.12.a The door is inaccessible because it requires 11 pounds of force to open. D2 36 months
13.12.b The seat cover dispenser is inaccessible because it requires a reach 61 inches above the finished floor. TR5 36 months
13.13 Drinking Fountains - 2nd Floor
13.13.a The drinking fountain is inaccessible because the water height is 3 ½ inches above the drain bowl. DF1 36 months
13.14 Urban District Office Counter - 3rd Floor
13.14.a The main counter is inaccessible because it is 40 inches above the finished floor. C6 36 months
13.15 Women's Single User Toilet Room - 3rd Floor
13.15.a The door is inaccessible because it requires 10 pounds of force to open. D2 36 months
13.15.b The seat cover dispenser is inaccessible because it requires a reach 61 inches above the finished floor. TR5 36 months
13.15.c The toilet is inaccessible because its centerline is 19 inches from the side wall. SU15 36 months
13.16 Men's Single User Toilet Room - 3rd Floor
13.16.a The door is inaccessible because it requires 10 pounds of force to open. D2 36 months
13.16.b The seat cover dispenser is inaccessible because it requires a reach 61 inches above the finished floor. TR5 36 months
13.16.c The toilet is inaccessible because its centerline is 19 inches from the side wall. SU15 36 months
13.17 Women's Locker Room - 3rd Floor
13.17.a The door is inaccessible because it requires 10 pounds of force to open. D2 36 months
13.17.b No accessible mirror has been provided. TR14 36 months
13.17.c The paper towel dispenser is inaccessible because the controls are mounted at 61 inches above the finished floor. TR5 36 months
13.17.d The toilet paper dispenser is inaccessible because it is mounted 37 inches from the rear wall. ST19 36 months
13.18 Men's Locker Room - 3rd Floor
13.18.a The door is inaccessible because it requires 9 pounds of force to open. D2 36 months
13.18.b No accessible mirror has been provided. TR14 36 months
13.18.c The side grab bar at the toilet is inaccessible because it is mounted 36 ½ inches above the finished floor. ST12 36 months
13.19 Urban District Kitchen
13.19.a The sink is inaccessible because the faucet is beyond the reach range of people who use wheelchairs. TR4 36 months
13.20 Entrance - South Tower, Urban Entrance
13.20.a The entrance is inaccessible because there is a slope of 2.2% within the door's required maneuvering clearance. D13 36 months
13.20.b The door is inaccessible because it has a 1 ½ inch threshold. D22 36 months
14 Gwendolyn E. Coffield Community Center, 2450 Layttonsville Road, Silver Spring, Maryland 20910
14.1 Route from Parking to Sidewalk
14.1.a The route from the parking area to the sidewalk is inaccessible because there is no detectable warning at the curb ramp, and the slope of the primary curb ramp is 10.9%. AR5 36 months
14.1.b The parking reserved for persons with disabilities is inaccessible because the designated spaces and access aisles have slopes ranging from 3.5% to 5.3%. P7 36 months
14.1.c The access aisles for two designated standard accessible parking spaces are too narrow. P8 36 months
14.2 Conference Room - 103
14.2.a The room is inaccessible to people who are deaf or hard of hearing because it does not provide an assistive listening system. AA4 36 months
14.3 Accessible Route - weight room
14.3.a The route between the treadmill and the weight machine is 27 ½ inches. AR1 36 months
14.4 Gym
14.4.a The door is inaccessible because it requires 7 pounds of force to open. D2 36 months
14.5 Women's Locker Room
14.5.a The door is inaccessible because it requires 7 pounds of force to open. D2 36 months
14.5.b The hand dryer protrudes 7 inches into the walkway and is not detectable to blind persons using a cane. AR8 36 months
14.5.c No accessible coat hook has been provided. TR1 36 months
14.5.d The toilet paper dispenser is inaccessible because it is mounted 38 inches from the rear wall. ST19 36 months
14.5.e The bench is inaccessible because it is 16 inches wide. LR1 36 months
14.6 Men's Locker Room
14.6.a The door is inaccessible because it requires 12 pounds of force to open. D2 36 months
14.6.b The hand dryer protrudes 7 inches into the walkway and is not detectable to blind persons using a cane. AR8 36 months
14.6.c The urinal is inaccessible because the rim is 19 inches above the finished floor. TR20 36 months
14.6.d The shower is inaccessible because the shower unit hose is 55 inches long. B11 36 months
14.6.e The bench is inaccessible because it is 16 inches wide. LR1 36 months
14.6.f The hardware on the door to the stall requires tight grasping and twisting. D1 36 months
14.7 Elevator - Lobby
14.7.a The elevator is inaccessible because, although emergency communications are provided, the handle to the box requires pinching to open. E8 36 months
14.8 Lounge - 2nd Floor
14.8.a The door is inaccessible because it requires 14 pounds of force to open. D2 36 months
14.9 Art Room - 205
14.9.a The door is inaccessible because it requires 9 pounds of force to open. D2 36 months
14.9.b The sink is inaccessible because it is 35 inches above the finished floor and the faucet is beyond the reach ranges of people who use wheelchairs. TR4 36 months
14.10 Route between 2nd Floor Lobby and Silver Spring Regional Office
14.10.a The door is inaccessible because it requires 11 pounds of force to open. D2 36 months
14.11 Women's Toilet Room - stalls
14.11.a The door is inaccessible because it requires 10 pounds of force to open. D2 36 months
14.11.b The toilet room sign is mounted with its centerline 62 inches above the finished floor. TR18 36 months
14.11.c The air dryer protrudes 7 inches into the walkway at a height of 39 ½ inches above the finished floor and is not detectable to blind persons using a cane. AR8 36 months
14.11.d No accessible coat hook has been provided. TR1 36 months
14.11.e The stall door hardware requires tight grasping or twisting. D1 36 months
14.12 Men's Toilet Room - stalls
14.12.a The toilet room sign is mounted with its centerline 61 ½ inches above the finished floor. TR18 36 months
14.12.b The door is inaccessible because it requires 12 pounds of force to open. D2 36 months
14.12.c The air dryer protrudes 7 inches into the walkway, 38 inches above the finished floor, and is not detectable to blind persons using a cane. AR8 36 months
14.12.d The urinal is inaccessible because the rim is 18 ½ inches above the finished floor. TR20 36 months
14.12.e No accessible coat hook has been provided. TR1 36 months
14.12.f The toilet paper dispenser is inaccessible because it is mounted 38 inches from the rear wall. ST19 36 months
14.12.g The stall door hardware requires tight grasping or twisting. D1 36 months
14.13 Social Hall - 202
14.13.a The door is inaccessible because it requires 11 pounds of force to open. D2 36 months
14.13.b

The door is inaccessible because it requires 13 pounds of force to open. D2 36 months
14.13.c The sink is inaccessible because the faucet is beyond the reach ranges of people who use wheelchairs. TR4 36 months
14.14 Playground
14.14.a The route from the back parking area to the building has a slope of 10.6%, and there is no accessible route to the play ground equipment or basketball courts. AR1 36 months
15 Shelter - Protected Address
15.1 Single-User Toilet Rooms for Room 167 and 169
15.1.a The toilet is inaccessible because its centerline is 17 inches from the side wall. SU15 6 months
15.1.b The toilet paper dispenser is inaccessible because it is mounted 15 inches above the finished floor. SU17 6 months
15.1.c No grab bars are provided in the transfer shower. B9 6 months
15.1.d The shower is inaccessible because the transfer seat is broken and the controls are mounted on the back wall. B8 6 months
15.2 Women's Toilet at Main Entrance - Stalls
15.2.a The lavatory is inaccessible because it does not provide adequate clear floor space. TR6 6 months
15.2.b The side grab bar at the toilet is inaccessible because the toilet paper dispenser is mounted less than 18 inches above the grab bar and interferes with its use. ST8 6 months
15.2.c The bathtub is inaccessible because there is no tub seat provided and the grab bars do not comply with the requirements of the Standards. B6 6 months
15.3 Women's Toilet Room on back hall near smoking deck - Stalls
15.3.a The lavatory is inaccessible because the hot water pipes are not insulated or otherwise configured to protect against contact. TR12 6 months
15.3.b The side grab bar at the toilet is inaccessible because the toilet paper dispenser mounted 40 inches above the finished floor, less than 18 inches above the grab bar. ST8 6 months
15.3.c The bathtub is inaccessible because there is no tub seat provided, and the grab bars do not comply with the Standards. B6 6 months
15.4 Resident Telephone in Hallway near Smoking Deck (not pay telephone)
15.4.a The telephone is inaccessible because its highest operable part is 61 inches above the finished floor, it is not hearing aid compatible, and there is no volume control. TT1 6 months
15.5 Women's Toilet Room near larger dining/living area - Stalls
15.5.a The lavatory is inaccessible because the hot water pipes are not insulated or otherwise configured to protect against contact. TR12 6 months
15.5.b The side grab bar at the toilet is inaccessible because the toilet paper dispenser is mounted less than 18 inches above the grab bar. ST8 6 months
15.5.c The bathtub is inaccessible because there is no tub seat provided and the grab bars do not comply with the Standards. B6 6 months
15.6 Single-User Toilet Room in Lobby
15.6.a Although an audible alarm is provided in this facility, there is no visual alarm appliance in the toilet room. Provide a visual alarm appliance in the toilet room. Standards §§ 4.1.3(14), 4.28.1, 4.28.3. 6 months
15.6.b The lavatory is inaccessible because the top of the counter is 35 inches above the finished floor. TR11 6 months
15.6.c The toilet paper dispenser is inaccessible because it is mounted 37 inches from the rear wall. ST19 6 months
15.6.d The side grab bar at the toilet is inaccessible because the toilet paper dispenser are mounted 38 inches above the finished floor, above the grab bar. ST8
15.7 Exterior Entrance
15.7.a The call button is mounted at 55 inches above the finished floor. D14 6 months
15.8 Parking
15.8.a The parking lot, with a total of 33 parking spaces, is inaccessible because although two are designated as being accessible for persons with disabilities, the parking lot does not provide a van accessible space or signage at any of the designated accessible spaces. In addition, the accessible parking spaces have a slope of up to 4.8%. This lot requires 1 van accessible space and 1 standard accessible space. P3 6 months
15.9 Accessible Route from Parking
15.9.a The route from the parking area to the shelter is inaccessible because the trailer obstructs the path and parked cars reduce the width of the route to less than 36 inches. AR1 6 months
16 Quince Orchard Library, 15831 Quince Orchard Road, Gaithersburg
16.1 Accessible Route
16.1.a The routes from the parking area to the main entrance are inaccessible because there is no detectable warning at the curb ramps and the slopes of the curb portion are 19% and 26.3%. AR5 24 months
16.2 General Room Signage
16.2.a Not all signs have raised letters and Braille, nor are all mounted with their centerlines at 60" high to the latch side of the door. D26

24 months
16.3 Meeting Room #1 and #2 - near entrance
16.3.a The pull sides of both doors, which are accessed through a front approach, are inaccessible because the latch sides are blocked by flyer racks. D6 24 months
16.3.b The sink is inaccessible because the faucet is beyond the reach of persons using wheelchairs. TR4 24 months
16.4 Men's Toilet Room - Stalls
16.4.a The toilet room sign is mounted in the wrong area and its centerline is not 60 inches above the finished floor. TR18 24 months
16.4.b The designated accessible toilet is inaccessible because the flush control is on the closed side. ST2 24 months
16.4.c The side grab bar at the toilet is inaccessible because its closer end is 13 inches from the rear wall, and the toilet paper dispenser interferes with its use. ST8 24 months
16.4.d The rear grab bar at the toilet is inaccessible because its closer end is mounted 7 inches from the side wall. ST4 24 months
16.4.e The urinal is inaccessible because the clear floor space provided is less than 30 inches wide. TR20 24 months
16.5 Women's Toilet Room - Stalls
16.5.a The toilet room sign is mounted in the wrong area and its centerline is not 60 inches above the finished floor. TR18 24 months
16.5.b The designated accessible toilet is inaccessible because the flush control is on the closed side. ST2 24 months
16.5.c The side grab bar at the toilet is inaccessible because its closer end is 13 ½ inches from the rear wall, and the toilet paper dispenser interferes with its use. ST8 24 months
16.5.d The rear grab bar at the toilet is inaccessible because its closer end is mounted 7 inches from the side wall. ST4 24 months
17 Sandy Spring Fire Department, 17921 Brooke Road
17.1 Parking
17.1.a The parking lot, with a total of 149 parking spaces, is inaccessible because there is no van accessible space, the spaces are too narrow, the signage provided can be obstructed, and there is no signage to designate two of the designated accessible spaces as accessible. This lot requires 1 van accessible space and 4 standard accessible spaces. P3 24 months
17.2 Men's Toilet Room near ballroom - Stalls
17.2.a The door is inaccessible because it requires 17 pounds of force to open. D2 24 months
17.2.b No accessible mirror has been provided. TR14 24 months
17.2.c No accessible coat hook has been provided. TR1 24 months
17.2.d The toilet paper dispenser is inaccessible because it is mounted 39 inches from the rear wall and 18 ½ inches above the finished floor. ST19 24 months
17.2.e The side of the lavatory protrudes into the walkway and is not detectable to blind persons using a cane. AR8 24 months
17.3 Women's Toilet Room near ballroom - Stalls
17.3.a The door is inaccessible because it requires 15 pounds of force to open. D2 24 months
17.3.b No accessible mirror has been provided. TR14 24 months
17.3.c The lavatory is inaccessible because the hot water pipes are not insulated or otherwise configured to protect against contact. TR12 24 months
17.3.d No accessible coat hook has been provided. TR1 24 months
17.3.e The toilet paper dispenser is inaccessible because it is mounted 40 inches from the rear wall and 18 ½ inches above the finished floor. ST19 24 months
17.3.f The side of the lavatory protrudes into the walkway and is not detectable to blind persons using a cane. AR8 24 months
17.4 Drinking Fountain in Ballroom (lower Fountain)
17.4.a The drinking fountain is inaccessible because it provides inadequate knee space. DF5 24 months
17.5 Elevator
17.5.a The elevator is inaccessible because, although emergency communications are provided, they are not identified by raised lettering or a symbol. E7 24 months
17.6 Entrance and Fire Department Main Desk - Office
17.6.a The door is inaccessible because it requires 23 pounds of force to open. D2 24 months
17.7 Single-User Toilet Room - lower level
17.7.a No accessible mirror has been provided. TR14 24 months
17.7.b The toilet paper dispenser is inaccessible because it is mounted 40 inches from the rear wall. SU17 24 months
17.7.c The rear grab bar at the toilet is inaccessible because it is 24 inches long. ST4 24 months
18 Damascus Community Center, 25520 Oak Drive, Damascus, Maryland 20872
18.1 Parking
18.1.a The parking lot, with a total of 145 parking spaces, is inaccessible because there is no van accessible space, and some of the designated accessible spaces and access aisles have cross-slopes between 2.5% and 3.5%. This lot requires 1 van accessible space and 4 standard accessible spaces. P3 12 months
18.2 Accessible Route
18.2.a The accessible route from the parking to the playground has a cross-slope of 4% on the sidewalk. AR1 12 months
18.3 Music Classroom 119
18.3.a The coat rack is inaccessible because it requires a reach of 66 inches above the finished floor. TR4 12 months
18.4 Lounge
18.4.a The service counter is 41 inches high. C6 12 months
18.5 Social Hall / Gymnasium 122
18.5.a The service counter is 41 inches high. C6 12 months
18.6 Assistive Listening System
18.6.a The facility is inaccessible to people who are deaf or hard of hearing because there is no signage informing the public of the availability of an assistive listening system. AA4 AA3 12 months
18.7 Accessible Route
18.7.a The route between the weight room and the exercise room is 26 wide near the trash can. AR3 12 months
18.7.b The table in the weight room protrudes into the walkway and is not detectable to blind persons using a cane. AR8 12 months
18.8 Men's Locker Room near Weight Room
18.8.a The lower urinal's rim is 18 inches high. TR20 12 months
18.8.b The changing area does not have adequate clear floor space, and the benches are 36 inches long, 9½ inches wide, and not attached to the wall. SU16
18.8.c The locker controls require pinching to operate. D1 12 months
18.9 Women's Locker Room near Weight Room
18.9.a The changing area does not have adequate clear floor space, and the benches are 36 inches long, 9½ inches wide, and not attached to the wall. TR20 12 months
18.9.b The locker controls require pinching to operate. D1 12 months
18.10 Computer Lab
18.10.a The desks are 26 ½ inches high, and 25 inches high with the keyboard in place. T1 12 months
19 Germantown Indoor Swim Center, 18000 Central Park Circle, Boyds, Maryland 20841
19.1 Special Needs Changing Rooms (two)
19.1.a The entrance has a ¾ inch threshold. D22 6 months
19.2 Administrative Office near Front Entrance
19.2.a The door is inaccessible because it requires 14 pounds of force to open. D2 6 months
19.3 Party / Classroom Kitchenette
19.3.a The storage cabinets are 58 inches high to the latch. TR5 6 months
19.4 Lobby Drinking Fountain
19.4.a The drinking fountain protrudes into the walkway and is not detectable to blind persons using a cane. AR8 6 months
19.5 Men's Lobby Toilet Room with Stalls
19.5.a The toilet room sign is mounted on the door. TR18 6 months
19.5.b The baby changing station handle is 66 ¾ inches above the finished floor. TR5 6 months
19.5.c The designated accessible toilet is inaccessible because its centerline is 19 inches from the side wall. ST17 6 months
19.5.d The rear grab bar at the toilet is mounted with its closer end 8 inches from the side wall. ST4 6 months
19.6 Women's Lobby Toilet Room with Stalls
19.6.a The toilet room sign is mounted on the door. TR18 6 months
19.6.b The baby changing station handle is 66 ¾ inches above the finished floor. TR5 6 months
19.6.c The rear grab bar at the toilet is mounted with its closer end 8 inches from the side wall. ST4 6 months
19.7 Exercise Room
19.7.a The door is inaccessible because it requires 20 pounds of force to open. D2 6 months
19.7.b The routes providing access to the exercise machines narrows to 28 inches at various points. AR3 6 months
19.8 Women's Locker Room
19.8.a The door is inaccessible because it requires 14 pounds of force to open. D2 6 months
19.8.b The paper towel dispenser is mounted with its controls 62½ inches above the finished floor. TR5 6 months
19.8.c The hair dryers protrude into the walkway and are not detectable to blind persons using a cane. AR8 6 months
19.8.d The lavatory apron is 28 inches above the finished floor. TR11 6 months
19.8.e The designated accessible toilet is inaccessible because its centerline is 19 inches from the side wall. ST17 6 months
19.8.f The rear grab bar is mounted with its closer end 8 inches from the side wall. ST4 6 months
19.8.g The ambulatory stall's partitions are 38 inches apart, the door is not self-closing, the toilet centerline is 19 inches from the side wall, and the far end of both grab bars is 48 inches from rear wall. ST1 6 months
19.8.h The roll-in shower has no grab bars, and the shower spray units are fixed at 46 and 78 inches high. B8 6 months
19.8.i The shower soap dispenser protrudes into the walkway and is not detectable to blind persons using a cane. AR8 6 months
19.8.j The bench affixed to the wall is 11½ inches deep. LR1 6 months
19.9 Men's Locker Room
19.9.a The door is inaccessible because it requires 15 pounds of force to open. D2 6 months
19.9.b The paper towel dispenser is mounted with its controls 67 inches above the finished floor. TR5 6 months
19.9.c The hair dryer protrudes into the walkway and is not detectable to blind persons using a cane. AR8 6 months
19.9.d The lavatory apron is 28 inches above the finished floor. TR11 6 months
19.9.e The designated accessible toilet is inaccessible because its centerline is 19 inches from the side wall. ST17 6 months
19.9.f The rear grab bar at the toilet is mounted with its closer end 7 inches from the side wall. ST4 6 months
19.9.g The bench affixed to the wall is 11½ inches deep. LR1 6 months
19.10 Entrance
19.10.a The room signs are mounted on the door. TR18 6 months
19.10.b The baby changing station handles are 66 inches above the finished floor. TR5 6 months
19.10.c The side grab bar in one room is 36 inches long, and the far end of the side grab bar in each room is less than 52 inches from the rear wall. ST7
19.10.d In one room, the bench is inaccessible because it is 11½ inches deep. LR1 6 months
19.11 Aquatic Office / First Aid Single-User Toilet Room
19.11.a The door is inaccessible because it requires 12 pounds of force to open. D2 6 months
19.11.b The designated accessible toilet is inaccessible because its centerline is 20 inches from the side wall. SU15 6 months
19.11.c No grab bars are provided at the toilet. SU10 6 months
19.12 Aquatic Office / Staff Locker Room
19.12.a The benches are less than 24 inches deep. LR1 6 months
20 Montgomery County Correctional Facility, 22880 Whelan Lane, Boyds, Maryland 20841
20.1 Parking
20.1.a The curb ramp from visitor parking to the entrance has a ½ inch step at the bottom where water pools. AR5 36 months
20.2 Entrances
20.2.a There is no International Symbol of Access at the accessible entrance and no directional signage at the inaccessible entrance. D16 36 months
20.2.b The designated accessible entrance has knob hardware. D1 36 months
20.2.c The interior door at the designated accessible entrance is inaccessible because it requires 12 pounds of force to open. D2 36 months
20.3 Request Boxes throughout the Facility
20.3.a The medical request boxes located throughout the facility are mounted 70 to 73½ inches high, and many of the inmate request boxes are mounted 55 inches high, all of which are beyond the reach ranges of people who use wheelchairs. TR5 36 months
20.4 Interior Doors
20.4.a The interior doors throughout the facility have knob hardware. D1 36 months
20.5 Interior Signage
20.5.a The signage throughout the facility is mounted on the doors and lacks raised and Braille characters. D16 36 months
20.6 Lobby
20.6.a The high drinking fountain protrudes into the walkway and is not detectable to blind persons using a cane. AR8 36 months
20.7 Women's Lobby Toilet Room with Stalls
20.7.a No accessible coat hook has been provided. TR1 36 months
20.8 Men's Lobby Toilet Room with Stalls
20.8.a The route to the urinal is less than 32 inches wide. TR20 36 months
20.9 Women's 2nd Floor Toilet Room with Stalls
20.9.a The door is inaccessible because it requires 20 pounds of force to open. D2 36 months
20.9.b The designated accessible toilet is inaccessible because the top of the seat is 20 inches above the finished floor. ST20 36 months
20.9.c The designated accessible toilet is inaccessible because its centerline is 17 inches from the side wall. ST17 36 months
20.9.d The grab bars at the toilet are mounted 2 ½ inches from the wall. ST13 36 months
20.10 Men's 2nd Floor Toilet Room with Stalls
20.10.a The door is inaccessible because it requires 18 pounds of force to open. D2 36 months
20.10.b The designated accessible toilet is inaccessible because the top of the seat is 20 inches above the finished floor. ST20 36 months
20.10.c The grab bars at the toilet are mounted 2 ½ inches from the wall. ST13 36 months
20.11 Ramp to 1st Floor, North Side
20.11.a There are no extensions at the ends of the handrails, and there is a 2 inch gap between the handrail and the wall. R4 36 months
20.12 Men's Single-User Staff Toilet Room N1.013
20.12.a The door is inaccessible because it requires 20 pounds of force to open. D2 36 months
20.12.b No accessible coat hook has been provided. TR1 36 months
20.12.c The toilet centerline is 16 ½ inches from the side wall. SU15 36 months
20.12.d The designated accessible toilet is inaccessible because the flush control is on the closed side. SU1 36 months
20.12.e The side grab bar at the toilet is 32 inches long. SU6 36 months
20.12.f The rear grab bar at the toilet is 17 inches long. ST4 36 months
20.13 Women's Single-User Staff Toilet Room N1.012
20.13.a The door is inaccessible because it requires 20 pounds of force to open. D2 36 months
20.13.b The top of the toilet seat is 20 inches above the finished floor. SU18 36 months
20.13.c The rear grab bar at the toilet is obstructed by the soap dispenser. ST5 36 months
20.14 North 1 Pod 2 Crisis Intervention Unit - Men's Roll-In Shower
20.14.a Although the facility is monitored, the shower spray unit cannot be hand-held. B11 36 months
20.15 North 1 Pod 1 Segregation Men's Shower
20.15.a The shower spray unit is fixed at 60 inches above the finished floor. B11 36 months
20.16 North 2 Men's Staff Single-User Toilet Room
20.16.a The men's single-user toilet room contains a number of inaccessible elements and is not accessible to people with disabilities. SU13 36 months
20.16.b North 2 Women's Staff Single-User Toilet Room
20.16.c The rear grab bar at the toilet is obstructed by the soap dispenser. ST5 36 months
20.17 North 2 Pod 2 Men's Roll-In Shower
20.17.a Although the facility is monitored, the shower spray unit cannot be hand-held. B11 36 months
20.18 North 2 Pod 1 Women's Roll-In Shower
20.18.a Although the facility is monitored, the shower spray unit cannot be hand-held. B11 36 months
20.19 Classrooms / Library - Single-User Inmate Toilet Room C1.454
20.19.a The far end of the side grab bar at the toilet is 51 inches from the rear wall. SU6 36 months
20.20 Infirmary
20.20.a In single-user toilet room C1.250, the far end of the side grab bar at the toilet is 50½ inches from the rear wall. SU6 36 months
20.20.b The telephone cord is 17 inches long. TT1 36 months
20.20.c The transfer shower is 36 by 38 inches, and the shower spray unit is fixed at more than 48 inches above the finished floor. B8 36 months
20.20.d

The fire extinguisher in the hallway outside the male ward protrudes into the walkway and is not detectable to blind persons using a cane. AR8 36 months
20.20.e The shower spray unit in the Male Negative Airflow Room (C1.265) cannot be hand-held. B11 36 months
20.21 Infirmary - Staff Men's Single-User Toilet Room with Lockers
20.21.a No accessible mirror has been provided. TR14 36 months
20.21.b The side grab bar at the toilet is obstructed by the seat cover dispenser. SU7 36 months
20.22 Infirmary - Staff Women's Single-User Toilet Room with Lockers
20.22.a The side grab bar at the toilet is obstructed by the seat cover dispenser. SU7 36 months
20.23 Administrative Area - Women's Staff Locker Room
20.23.a The hair dryer is mounted with the controls 70 ½ inches above the finished floor. TR5 36 months
20.23.b No accessible coat hook has been provided in the designated accessible toilet stall or in the dressing area. TR1 36 months
20.24 Administrative Area - Men's Staff Locker Room
20.24.a The hair dryer is mounted with the controls 76 inches above the finished floor. TR5 36 months
20.24.b No accessible coat hook has been provided in the designated accessible toilet stall or in the dressing area. TR1 36 months
20.25 West Housing Women's Staff Single-User Toilet Room W1.006
20.25.a No accessible coat hook has been provided. TR1 36 months
20.25.b The designated accessible toilet is inaccessible because the flush control is on the closed side. SU1 36 months
20.26 West Housing Men's Staff Single-User Toilet Room W1.024
20.26.a No accessible coat hook has been provided. TR1 36 months
20.26.b The side grab bar at the toilet is 30 inches long, with the far end mounted 33 inches from the rear wall. SU6 36 months
20.26.c The rear grab bar at the toilet is 15 ½ inches long and there is 2 inches of space between the grab bar and the wall. SU2 36 months
20.27 West 1 Pod 1 and Pod 2 Men's Roll-In Showers
20.27.a The shower spray units cannot be hand-held and are not mounted at the appropriate height. B11 36 months
20.28 West Staff Unisex Single-User Toilet Room W1.238
20.28.a The side grab bar at the toilet is less than 42 inches long. SU6 36 months
20.28.b The rear grab bar at the toilet is less than 36 inches long. ST4 36 months
20.29 Women's Staff Toilet Room with Stalls C1.503
20.29.a No accessible coat hook has been provided. TR1 36 months
20.30 Men's Staff Toilet Room with Stalls C1.502
20.30.a No accessible coat hook has been provided. TR1 36 months
20.30.b The designated accessible toilet is inaccessible because the flush control is on the closed side. ST2 36 months
21 Men's Emergency Shelter, 600 East Gude Drive, Rockville, Maryland
21.1 Parking
21.1.a The parking lot, with a total of 10 parking spaces, is inaccessible because it does not have a van accessible space. This lot requires 1 van accessible space. P3 6 months
21.2 Curb Ramp at Parking Area
21.2.a The curb ramp on the route from the parking area to the main entrance is inaccessible because it has a slope of 11 % and a cross slope of 2.3 %. AR5
21.3 Entrance
21.3.a The building is inaccessible because it has 2 entrances and does not have informational signage regarding the accessible entrance. D16 6 months
21.4 Case Management Office
21.4.a The route from the main door through the office interior is inaccessible because it narrows to 26 inches near the furniture. AR1 6 months
21.4.b The door is inaccessible because it requires 13 pounds of force to open. D2 6 months
21.5 Staff Single User Toilet Room - (also used by residents who require an accessible toilet room)
21.5.a There is no accessible toilet room sign. TR18 6 months
21.5.b The designated accessible toilet is inaccessible because the flush control is on the closed side. SU1 6 months
21.5.c The toilet is inaccessible because its centerline is 17 inches from the side wall. SU15 6 months
21.6 Resident Men and Women's Toilet Rooms with Stalls
21.6.a There is no accessible toilet room sign. TR18 6 months
21.6.b The door is inaccessible because it requires more than 5 pounds of force to open. D2 6 months
21.6.c The lavatory is inaccessible because the top of the counter is 35 ½ inches above the finished floor. TR11 6 months
21.6.d The lavatory is inaccessible because the faucet requires twisting of a knob to operate. TR10 6 months
21.7 Men's Showers
21.7.a Although 3 showers are provided, there is no accessible shower. B8 6 months
21.8 Drinking Fountain
21.8.a The drinking fountain is inaccessible because it requires 20 pounds of force to operate. DF2 6 months

 