Attachment L

 

Facilities Owned by Others

 

Please Note: Paragraph 49 of the Settlement Agreement requires that, within one year of the effective date of this Agreement, the County provide signage as necessary to comply with 28 C.F.R. § 35.163(b), after having surveyed all facilities that are the subject of this Agreement for the purpose of identifying those that have multiple entrances not all of which are accessible.

 

Access to County Programs Housed in Others' Facilities:  In order to ensure that the County's programs, services, and activities that are operated at facilities owned or controlled by other entities as listed below are, when viewed in their entirety, readily accessible to and usable by persons with mobility impairments, within 36 months of the effective date of this Agreement, the County will ensure that the actions listed below have been accomplished.  Alternatively, for any barrier listed below that has not been timely addressed, within 39 months of the effective date of this Agreement, the County and the Department will work cooperatively to develop, and the County will implement, a written plan regarding how the County program, activity, or service at issue will be made accessible to persons with disabilities, when viewed in its entirety.

A.        It is agreed that in matters pertaining to accessible parking and the signage for same, the County may follow the New York State code requirements of providing all accessible spaces with a 96" access aisle, including the standard "Permit only - Handicapped Parking" sign with symbol, in lieu of providing the ADA prescribed 'Van Accessible' signage".

 

B.         Within 36 months of the effective date of this Agreement, the County will complete the following modifications to the Appellate Court, located at 50 East Avenue, Rochester, NY:  [New Construction]

 

1.         Accessible Route

a. The main interior door requires 10 pounds of force to open.  Provide a door that requires no more than 5 pounds of force to open.  Standards §§ 4.1.3(7)(b), 4.13.11(2)(b).

b. The main entrance ramp lacks a level landing at the bottom.  Provide a ramp that is at least 36 inches wide with a slope not exceeding 1:12 and a cross slope not exceeding 1:50; with level landings at least as wide as the ramp and 60 inches long at the top and bottom of the ramp; with level landings measuring at least 60 inches by 60 inches when the ramp changes direction; and edge protection that is at least 2 inches high at the drop off sides.  Provide handrails that are between 1¼ inches and 1½ inches in diameter such that the inside handrail is continuous and both handrails have a continuous gripping surface along both sides of the ramp extending at least 12 inches beyond the top and bottom of the ramp parallel with the ground surface; the handrails do not rotate within their fittings; and both handrails are mounted between 34 inches and 38 inches above the ramp surface, with ends rounded or returned smoothly to the floor, wall, or post.  Ensure that the ramp and approaches are designed so that water will not accumulate on walking surfaces.  Standards §§ 4.1.2(1), 4.1.2(2), 4.3.8, 4.8.

 

2.         Signage

a. The courtrooms' permanent room signage does not have raised characters or Braille, and the signs are mounted incorrectly.  For each, provide permanent room signage with upper case, sans serif or simple serif type letters and numerals, meeting the requirements of the Standards for character height, raised characters, finish and contrast, accompanied by Grade 2 Braille; mounted on the wall adjacent to the latch side of the door or on the nearest adjacent wall at a height of 60 inches above the finished floor to the centerline of the sign; and located so that a person may approach within 3 inches of the signage without encountering protruding objects or standing within the swing of a door.  Standards §§ 4.1.2(7), 4.30.1, 4.30.4, 4.30.5, 4.30.6.

b. There is no signage in the lobby directing people to the TTY.  Provide at least one accessible public TTY with appropriate signage.  Standards §§ 4.1.3(17)(c), 4.30.7(3), 4.31.9.

 

3.         Library                       

a. The interior door to the Library requires 6 pounds of force to open.  Provide a door that requires no more than 5 pounds of force to open.  Standards §§ 4.1.3(7)(b), 4.13.11(2)(b).

 

4.         Clerk's Office                                               

a. The interior door to the Clerk's Office requires 10 pounds of force to open.  Provide a door that requires no more than 5 pounds of force to open.  Standards §§ 4.1.3(7)(b), 4.13.11(2)(b).

 

5.         1st Floor Men's Toilet Room with Stalls

a. The door requires 10 pounds of force to open.  Provide a door that requires no more than 5 pounds of force to open.  Standards §§ 4.1.3(7)(b), 4.13.11(2)(b).

b. The toilet flush control in the designated accessible stall is on the closed side of the stall.  Provide a flush control mounted on the "open" side of the toilet's clear floor space; 44 inches or less above the finished floor; and requiring a maximum of 5 pounds of force to operate; or provide an automatic flush device.  Standards §§ 4.1.3(11), 4.22.4, 4.16.5, 4.17.2, 4.27.4.

c. The overall length of the rear grab bar is 30 inches.  Provide a rear grab bar that is at least 36 inches in overall length with the closer end no more than 6 inches from the side wall.  Standards §§ 4.1.3(11), 4.22.4, 4.17.6, Fig. 30.

 

6.         1st Floor Women's Toilet Room with Stalls

a. The door requires 10 pounds of force to open.  Provide a door that requires no more than 5 pounds of force to open.  Standards §§ 4.1.3(7)(b), 4.13.11(2)(b).

b. The overall length of the rear grab bar is 30 inches.  Provide a rear grab bar that is at least 36 inches in overall length with the closer end no more than 6 inches from the side wall.  Standards §§ 4.1.3(11), 4.22.4, 4.17.6, Fig. 30.

 

7.         2nd Floor Men's Toilet Room with Stalls

a. The door requires 11 pounds of force to open.  Provide a door that requires no more than 5 pounds of force to open.  Standards §§ 4.1.3(7)(b), 4.13.11(2)(b).

b. The overall length of the rear grab bar is 30 inches.  Provide a rear grab bar that is at least 36 inches in overall length with the closer end no more than 6 inches from the side wall.  Standards §§ 4.1.3(11), 4.22.4, 4.17.6, Fig. 30.

 

8.         2nd Floor Women's Toilet Room with Stalls

a. The door requires 14 pounds of force to open.  Provide a door that requires no more than 5 pounds of force to open.  Standards §§ 4.1.3(7)(b), 4.13.11(2)(b).

b. The toilet flush control in the designated accessible stall is on the closed side of the stall.  Provide a flush control mounted on the "open" side of the toilet's clear floor space; 44 inches or less above the finished floor; and requiring a maximum of 5 pounds of force to operate; or provide an automatic flush device.  Standards §§ 4.1.3(11), 4.22.4, 4.16.5, 4.17.2, 4.27.4.

c. The centerline of the toilet in the designated accessible stall is 19 inches from the near side wall.  Provide a toilet with a centerline that measures 18 inches from the near side wall.  Standards §§ 4.1.3(11), 4.22.4, 4.17.3, Fig. 30.

d. The overall length of the rear grab bar is 30 inches.  Provide a rear grab bar that is at least 36 inches in overall length with the closer end no more than 6 inches from the side wall.  Standards §§ 4.1.3(11), 4.22.4, 4.17.6, Fig. 30.

 

9.         2nd Floor Courtroom II

a. The entry doors require 11 pounds of force and 7 pounds of force to open.  Provide doors that requires no more than 5 pounds of force to open.  Standards §§ 4.1.3(7)(b), 4.13.11(2)(b).

b. There are no companion seats provided next to wheelchair seating locations.  Provide wheelchair seating areas, each with a minimum clear ground or floor space of 66 inches wide by 48 inches deep for forward or rear access, or 66 inches wide by 60 inches deep for side access.  Ensure that the ground or floor at all wheelchair locations is level, firm, stable, and slip resistant; that wheelchair seating areas are an integral part of the fixed seating plan and are located so as to provide people with physical disabilities a choice of lines of sight comparable to those available for members of the general public; that wheelchair seating areas adjoin an accessible route that also serves as a means of egress in case of emergency; and that at least one fixed companion seat is provided next to each wheelchair seating area.  Standards §§ 4.1.3(19)(a), 4.5, 4.33.

c. There is no signage informing the public of the availability of an assistive listening system.  Provide accessible signage indicating the availability of the assistive listening system.  Standards §§ 4.1.3(19)(b), 4.30.

 

C.        Within 36 months of the effective date of this Agreement, the County will complete the following modifications to the City Place, located at 50 West Main Street, Rochester, NY:  [Altered Facility]

 

1.         Accessible Route

a. The head room under the stairway on the first floor is only 48 inches high, posing a hazard to people who are blind or have low vision.  Provide an accessible route at this location such that no objects with their bottom leading edges measuring between 27 inches and 80 inches above the finished floor protrude more than 4 inches into walks, halls, corridors, passageways, or aisles.  Free-standing objects mounted on posts or pylons may overhang 12 inches maximum from 27 inches to 80 inches above the ground or finished floor.  Standards § 4.4.

b. The drinking fountains on the first and second floors, and the water valve on the second, third, and fourth floors, are protruding objects and are not cane detectable.  Provide accessible routes at these locations such that no objects with their bottom leading edges measuring between 27 inches and 80 inches above the finished floor protrude more than 4 inches into walks, halls, corridors, passageways, or aisles.  Free-standing objects mounted on posts or pylons may overhang 12 inches maximum from 27 inches to 80 inches above the ground or finished floor.  Standards §§ 4.1.2(3), 4.1.6(1)(b), 4.4.

c. The interior door at the main west entrance requires 12 pounds of force to open.  Provide a door that requires no more than 5 pounds of force to open.  Standards §§ 4.1.3(7)(b), 4.1.6(1)(b), 4.13.11(2)(b).

d. Permanent room signs do not have raised and Braille characters, are not mounted 60 inches high to the center of the signs, are not mounted on the wall on the latch side of the door, and do not have character height between 5/8 and 2 inches.  Provide permanent room signage with upper case, sans serif or simple serif type letters and numerals, meeting the requirements of the Standards for character height, raised characters, finish and contrast, accompanied by Grade 2 Braille; mounted on the wall adjacent to the latch side of the door or on the nearest adjacent wall at a height of 60 inches above the finished floor to the centerline of the sign; and located so that a person may approach within 3 inches of the signage without encountering protruding objects or standing within the swing of a door.  Standards §§ 4.1.2(7), 4.1.6(1)(b), 4.30.1, 4.30.4, 4.30.5, 4.30.6.

 

2.         Telephones

a. There are no lowered telephones provided at the North Entrance or Center "C" and the telephone provided allows only 25 inches of knee space.  Provide an accessible telephone with a clear floor space of at least 30 inches by 48 inches that allows either a forward or parallel approach by a person using a wheelchair such that bases, enclosures, and fixed seats do not impede approaches to the telephone; with the highest operable part of the telephone mounted no more than 48 inches above the floor for a front approach or no more than 54 inches above the floor for a side approach; that is hearing aid compatible and has a volume control mechanism; with telephone books, if provided, located between 15 and 48 inches above the finished floor for a front approach or between 9 and 54 inches above the finished floor for a side approach; with a cord of at least 29 inches long from the telephone to the handset; and with signage that complies with the Standards.  Standards §§ 4.1.3(17), 4.1.6(1)(b), 4.31, 4.30.7(2).

b. The highest operable part of the North Entrance telephones is above the reach range of a person using a wheelchair, the cord is 22 inches long and there is no signage provided at the North Entrance telephones.  Provide an accessible telephone with a clear floor space of at least 30 inches by 48 inches that allows either a forward or parallel approach by a person using a wheelchair such that bases, enclosures, and fixed seats do not impede approaches to the telephone; with the highest operable part of the telephone mounted no more than 48 inches above the floor for a front approach or no more than 54 inches above the floor for a side approach; that is hearing aid compatible and has a volume control mechanism; with telephone books, if provided, located between 15 and 48 inches above the finished floor for a front approach or between 9 and 54 inches above the finished floor for a side approach; with a cord of at least 29 inches long from the telephone to the handset; and with signage that complies with the Standards.  Standards §§ 4.1.3(17), 4.1.6(1)(b), 4.31, 4.30.7(2).

c. The North Entrance telephones protrudes 10 inches into the path of travel and is not detectable to a blind person using a cane.  Provide a telephone at this location such that its bottom leading edges measure no more than 27 inches above the finished floor or protrude no more than 4 inches into the walkway.  Standards §§ 4.1.2(3), 4.1.6(1)(b), 4.4.

d. The house phones do not provide access for people who are deaf.  Provide at least one accessible public TTY with appropriate signage.  Standards §§ 4.1.3(17)(c), 4.1.6(1)(b), 4.30.7(3), 4.31.9.  Alternatively, the County will provide a program access solution to enable persons who cannot use the telephone an alternate method to summon assistance.

 

3.         Ramp at Main Entrance

a. The main entrance ramp has a slope of 11.1 percent and lacks handrails.  Provide a ramp that is at least 36 inches wide with a slope not exceeding 1:12 and a cross slope not exceeding 1:50; with level landings at least as wide as the ramp and 60 inches long at the top and bottom of the ramp; and with edge protection at least 2 inches high at the drop off sides.  Provide handrails that are between 1¼ inches and 1½ inches in diameter with a continuous gripping surface along both sides of the ramp, extending at least 12 inches beyond the top and bottom of the ramp parallel with the ground surface.  Ensure that handrails are mounted between 34 inches and 38 inches above the ramp surface, with ends rounded or returned smoothly to the floor, wall, or post, and that they do not rotate within their fittings.  Ensure that the ramp and approaches are designed so that water will not accumulate on walking surfaces.  Standards §§ 4.1.2(1), 4.1.2(2), 4.1.6(1)(b), 4.3.8, 4.8.  Alternatively, the County will provide directional signage inside and outside of the building directing patrons with disabilities to the Main Street entrance and exit.

 

4.         Elevators

a. The Center "C" elevator doors remain open only 3 seconds after reopening.  Provide doors that open and close automatically with a reopening device that will stop and reopen the car door and hoistway door automatically if the door becomes obstructed by an object or person.  Ensure that the device is capable of completing these operations without requiring contact for obstructions passing through the opening at heights of 5 inches and 29 inches above the finished floor; that door reopening devices remain effective for at least 20 seconds, after which the doors may close; that the minimum time from notification that a car is answering a call until the doors of that car start to close is 5 seconds; and that the minimum time for elevator doors to remain fully open in response to a car call is 3 seconds.  Standards §§ 4.1.3(5), 4.1.6(1)(b), 4.10.6, 4.10.7, 4.10.8, Figs. 20, 21.

 

5.         Room 3129 Children's Services

a. The entrance door requires 15 pounds of force to open.  Provide a door that requires no more than 5 pounds of force to open.  Standards §§ 4.1.3(7)(b), 4.1.6(1)(b), 4.13.11(2)(b).

b. The counter is 45 inches above the finished floor.  Provide a counter on an accessible route such that a portion of the counter is at least 36 inches wide and no more than 36 inches above the finished floor, or provide an auxiliary counter with a maximum height of 36 inches in close proximity to the main counter, or provide equivalent facilitation.  Equivalent facilitation may be provided in the form of a folding shelf attached to the main counter, an auxiliary table nearby, a clip board made available to the public, or other means.  Standards §§ 7.2(2), 4.3.

 

6.         Room 4105 Public Safety

a. The entrance door requires 15 pounds of force to open.  Provide a door that requires no more than 5 pounds of force to open.  Standards §§ 4.1.3(7)(b), 4.1.6(1)(b), 4.13.11(2)(b).

 

7.         6th Floor DOT Permits

a. The entrance door requires 15 pounds of force to open.  Provide a door that requires no more than 5 pounds of force to open.  Standards §§ 4.1.3(7)(b), 4.1.6(1)(b), 4.13.11(2)(b).

 

8.         7th Floor Environmental Services

a. The entrance door requires 12 pounds of force to open.  Provide a door that requires no more than 5 pounds of force to open.  Standards §§ 4.1.3(7)(b), 4.1.6(1)(b), 4.13.11(2)(b).

 

9.         8th Floor Planning

a. The counter is 45 inches above the finished floor. Provide a counter on an accessible route such that a portion of the counter is at least 36 inches wide and no more than 36 inches above the finished floor, or provide an auxiliary counter with a maximum height of 36 inches in close proximity to the main counter, or provide equivalent facilitation.   Equivalent facilitation may be provided in the form of a folding shelf attached to the main counter, an auxiliary table nearby, a clip board made available to the public, or other means.  Standards §§ 7.2(2), 4.3.

 

10.       2nd Floor Training Area

a. There is no signage informing the public of the availability of an assistive listening system.  Provide accessible signage indicating the availability of the assistive listening system.  Standards §§ 4.1.3(19)(b), 4.1.6(1)(b), 4.30.

 

11.       3rd Floor Auditorium A

a. The entrance door requires 15 pounds of force to open.  Provide a door that requires no more than 5 pounds of force to open.  Standards §§ 4.1.3(7)(b), 4.1.6(1)(b), 4.13.11(2)(b).

b. There is no assistive listening system provided.  Provide a permanently installed assistive listening system (ALS) or a portable ALS with an adequate number of electrical outlets or other supplementary wiring necessary to support a portable assistive listening system.  Also provide a minimum of 2 receivers for use by the general public and signage indicating their availability.  Standards §§ 4.1.3(19)(b), 4.1.6(1)(b), 4.30, 4.33.

 

12.       3rd Floor Auditorium B

a. The entrance door requires 15 pounds of force to open.  Provide a door that requires no more than 5 pounds of force to open.  Standards §§ 4.1.3(7)(b), 4.1.6(1)(b), 4.13.11(2)(b).

b. There is no assistive listening system provided.  Provide a permanently installed assistive listening system (ALS) or a portable ALS with an adequate number of electrical outlets or other supplementary wiring necessary to support a portable assistive listening system.  Also provide a minimum of 2 receivers for use by the general public and signage indicating their availability.  Standards §§ 4.1.3(19)(b), 4.1.6(1)(b), 4.30, 4.33.

 

13.       1-A Men's Toilet Room with Stalls

a. The entrance door requires 13 pounds of force to open.  Provide a door that requires no more than 5 pounds of force to open.  Standards §§ 4.1.3(7)(b), 4.1.6(1)(b), 4.13.11(2)(b).

b. The toilet paper dispenser is mounted above the side grab bar.  Provide a toilet paper dispenser that is mounted with its top at least 1½ inches under the side grab bar and 36 inches or less from the rear wall and is centered at least 19 inches above the finished floor.  Standards §§ 4.1.3(11), 4.1.6(1)(b), 4.22.4, 4.17.3, Fig. 30(d).

 

14.       1-A Women's Toilet Room with Stalls

a. The entrance door requires 14 pounds of force to open.  Provide a door that requires no more than 5 pounds of force to open.  Standards §§ 4.1.3(7)(b), 4.1.6(1)(b), 4.13.11(2)(b).

b. The toilet flush control in the designated accessible stall is on the closed side of the stall.  Provide a flush control mounted on the "open" side of the toilet's clear floor space; 44 inches or less above the finished floor; and requiring a maximum of 5 pounds of force to operate; or provide an automatic flush device.  Standards §§ 4.1.3(11), 4.1.6(1)(b), 4.22.4, 4.16.5, 4.17.2, 4.27.4.

c. The toilet paper dispenser in the designated accessible stall is mounted above the side grab bar.  Provide a toilet paper dispenser that is mounted with its top at least 1½ inches under the side grab bar and 36 inches or less from the rear wall and is centered at least 19 inches above the finished floor.  Standards §§ 4.1.3(11), 4.1.6(1)(b), 4.22.4, 4.17.3, Fig. 30(d).

 

15.       1-B Men's Toilet Room with Stalls

a. The entrance door requires 14 pounds of force to open.  Provide a door that requires no more than 5 pounds of force to open.  Standards §§ 4.1.3(7)(b), 4.1.6(1)(b), 4.13.11(2)(b).

b. No accessible coat hook has been provided.  Provide a coat hook at a maximum height above the finished floor of 48 inches for a forward approach or 54 inches for a side approach and that is accompanied by clear floor space of 30 by 48 inches that allows a forward or parallel approach by a person using a wheelchair.  Standards §§ 4.1.3(12)(a), 4.1.6(1)(b), 4.25.2, 4.25.3, 4.2.4, 4.2.5, 4.2.6.

c. The toilet paper dispenser is mounted above the side grab bar.  Provide a toilet paper dispenser that is mounted with its top at least 1½ inches under the side grab bar and 36 inches or less from the rear wall and is centered at least 19 inches above the finished floor.  Standards §§ 4.1.3(11), 4.1.6(1)(b), 4.22.4, 4.17.3, Fig. 30(d).

 

16.       3-A Women's Toilet Room with Stalls

a. The entrance door requires 15 pounds of force to open.  Provide a door that requires no more than 5 pounds of force to open.  Standards §§ 4.1.3(7)(b), 4.1.6(1)(b), 4.13.11(2)(b).

b. The toilet paper dispenser in the designated accessible stall is mounted above the side grab bar.  Provide a toilet paper dispenser that is mounted with its top at least 1½ inches under the side grab bar and 36 inches or less from the rear wall and is centered at least 19 inches above the finished floor.  Standards §§ 4.1.3(11), 4.1.6(1)(b), 4.22.4, 4.17.3, Fig. 30(d).

 

17.       3-A Men's Toilet Room with Stalls

a. The entrance door requires 15 pounds of force to open.  Provide a door that requires no more than 5 pounds of force to open.  Standards §§ 4.1.3(7)(b), 4.1.6(1)(b), 4.13.11(2)(b).

b. The paper towel dispenser is mounted with the highest operable part 56 inches above the finished floor.  Provide a paper towel dispenser with the controls a maximum height above the finished floor of 48 inches for a forward approach or 54 inches for a side approach and that is accompanied by clear floor space of 30 by 48 inches that allows a forward or parallel approach by a person using a wheelchair.  Standards §§ 4.1.3(13), 4.1.6(1)(b), 4.27.2, 4.27.3, 4.2.4, 4.2.5, 4.2.6.

c. The toilet flush control in the designated accessible stall is on the closed side of the stall.  Provide a flush control mounted on the "open" side of the toilet's clear floor space; 44 inches or less above the finished floor; and requiring a maximum of 5 pounds of force to operate; or provide an automatic flush device.  Standards §§ 4.1.3(11), 4.1.6(1)(b), 4.22.4, 4.16.5, 4.17.2, 4.27.4.

d. The toilet paper dispenser in the designated accessible stall is mounted above the side grab bar.  Provide a toilet with a seat that measures 17 to 19 inches above the finished floor.  Standards §§ 4.1.3(11), 4.1.6(1)(b), 4.22.4, 4.16.3, 4.17.2, Fig. 30(d).

 

18.       1st Floor Women's Single-User Toilet Room

a. The entrance door requires 15 pounds of force to open.  Provide a door that requires no more than 5 pounds of force to open.  Standards §§ 4.1.3(7)(b), 4.1.6(1)(b), 4.13.11(2)(b).

b. The toilet flush control is on the closed side.  Provide a flush control mounted on the "open" side of the toilet's clear floor space; 44 inches or less above the finished floor; and requiring a maximum of 5 pounds of force to operate; or provide an automatic flush device.  Standards §§ 4.1.3(11), 4.1.6(1)(b), 4.22.4, 4.16.5, 4.27.4.

c. The toilet paper dispenser is mounted above the side grab bar.  Provide a toilet paper dispenser that is mounted within reach, with its top at least 1½ inches under the side grab bar, and centered at least 19 inches above the finished floor.  Standards §§ 4.1.3(11), 4.1.6(1)(b), 4.22.4, 4.16.6, Fig. 29(b).

 

19.       2-A 2nd Floor Women's Toilet Room with Stalls

a. The toilet room sign is mounted 65 inches above the finished floor to the sign's centerline.  Provide a toilet room sign with raised and Braille characters.  The sign shall be mounted on the wall adjacent to the latch side of the door with the centerline of the sign at 60 inches above the finished floor and situated such that a person can approach within 3 inches of the sign without encountering an obstruction or standing within a door swing.  Standards §§ 4.1.2(7)(d), 4.1.6(1)(b), 4.30.1, 4.30.4, 4.30.5, 4.30.6.

b. The entrance door requires 14 pounds of force to open.  Provide a door that requires no more than 5 pounds of force to open.  Standards §§ 4.1.3(7)(b), 4.1.6(1)(b), 4.13.11(2)(b).

c. The overhead heater is mounted 76½ inches above the finished floor and is not detectable to a blind person using a cane.  Provide a path of travel such that no objects with their bottom leading edges measuring between 27 inches and 80 inches above the finished floor protrude more than 4 inches into walks, halls, corridors, passageways, or aisles.  Free-standing objects mounted on posts or pylons may overhang 12 inches maximum from 27 inches to 80 inches above the ground or finished floor.  Standards §§ 4.1.2(3), 4.1.6(1)(b), 4.4.

d. The toilet flush control is on the closed side of the room.  Provide a flush control mounted on the "open" side of the toilet's clear floor space; 44 inches or less above the finished floor; and requiring a maximum of 5 pounds of force to operate; or provide an automatic flush device.  Standards §§ 4.1.3(11), 4.1.6(1)(b), 4.22.4, 4.16.5, 4.17.2, 4.27.4.

e. The toilet paper dispenser is mounted above the side grab bar and 37 inches from the rear wall.  Provide a toilet paper dispenser that is mounted with its top at least 1½ inches under the side grab bar and 36 inches or less from the rear wall and is centered at least 19 inches above the finished floor.  Standards §§ 4.1.3(11), 4.1.6(1)(b), 4.22.4, 4.17.3, Fig. 30(d).

f. The rear grab bar is mounted 10 inches from the near side wall.  Provide a rear grab bar that is at least 36 inches in overall length with the closer end no more than 6 inches from the side wall.  Standards §§ 4.1.3(11), 4.1.6(1)(b), 4.22.4, 4.17.6, Fig. 30.

 

20.       2-A 2nd Floor Men's Toilet Room with Stalls

a. The entrance door requires 15 pounds of force to open.  Provide a door that requires no more than 5 pounds of force to open.  Standards §§ 4.1.3(7)(b), 4.1.6(1)(b), 4.13.11(2)(b).

b. The overhead heater is mounted 76 inches above the finished floor and is not detectable to a blind person using a cane.  Provide a path of travel such that no objects with their bottom leading edges measuring between 27 inches and 80 inches above the finished floor protrude more than 4 inches into walks, halls, corridors, passageways, or aisles.  Free-standing objects mounted on posts or pylons may overhang 12 inches maximum from 27 inches to 80 inches above the ground or finished floor.  Standards §§ 4.1.2(3), 4.1.6(1)(b), 4.4.

c. The toilet paper dispenser is mounted above the side grab bar.  Provide a toilet paper dispenser that is mounted with its top at least 1½ inches under the side grab bar and 36 inches or less from the rear wall and is centered at least 19 inches above the finished floor.  Standards §§ 4.1.3(11), 4.1.6(1)(b), 4.22.4, 4.17.3, Fig. 30(d).

 

21.       2-B 2nd Floor Men's Single-User Toilet Room

a. The entrance door requires 15 pounds of force to open.  Provide a door that requires no more than 5 pounds of force to open.  Standards §§ 4.1.3(7)(b), 4.1.6(1)(b), 4.13.11(2)(b).

b. The toilet paper dispenser is mounted above the side grab bar.  Provide a toilet paper dispenser that is mounted with its top at least 1½ inches under the side grab bar and 36 inches or less from the rear wall and is centered at least 19 inches above the finished floor.  Standards §§ 4.1.3(11), 4.1.6(1)(b), 4.22.4, 4.17.3, Fig. 30(d).

 

22.       2-B 2nd Floor Women's Single-User Toilet Room

a. The entrance door requires 13 pounds of force to open.  Provide a door that requires no more than 5 pounds of force to open.  Standards §§ 4.1.3(7)(b), 4.1.6(1)(b), 4.13.11(2)(b).

b. The paper towel dispenser is mounted with the highest operable part 52 inches above the finished floor and a forward reach required.  Provide a paper towel dispenser with the controls a maximum height above the finished floor of 48 inches for a forward approach or 54 inches for a side approach and that is accompanied by clear floor space of 30 by 48 inches that allows a forward or parallel approach by a person using a wheelchair.  Standards §§ 4.1.3(13), 4.1.6(1)(b), 4.27.2, 4.27.3, 4.2.4, 4.2.5, 4.2.6.

 

c. The toilet flush control is on the closed side.  Provide a flush control mounted on the "open" side of the toilet's clear floor space; 44 inches or less above the finished floor; and requiring a maximum of 5 pounds of force to operate; or provide an automatic flush device.  Standards §§ 4.1.3(11), 4.1.6(1)(b), 4.22.4, 4.16.5, 4.27.4.

d. The toilet paper dispenser is mounted above the side grab bar.  Provide a toilet paper dispenser that is mounted within reach, with its top at least 1½ inches under the side grab bar, and centered at least 19 inches above the finished floor.  Standards §§ 4.1.3(11), 4.1.6(1)(b), 4.22.4, 4.16.6, Fig. 29(b).

 

23.       North Entrance 1st Floor Drinking Fountain

a. The height of the spout is 42 inches above the finished floor and the water arcs only 3 inches high, the controls require 14 pounds of force to operate.   Provide a fountain that has a spout height no higher than 36 inches, measured from the finished floor or ground surface to the spout outlet, and that otherwise complies with the Standards.  Standards §§ 4.1.3(10), 4.1.6(1)(b), 4.15, 4.27.4, Fig. 27.  The County will provide a cup dispenser to provide access to persons who use wheelchairs.

 

24.       Main Entrance 1st Floor Drinking Fountain

a. The drinking fountain is a protruding object and is not detectable to blind people using canes.  Provide a drinking fountain at this location such that its bottom leading edges measure no more than 27 inches above the finished floor or protrude no more than 4 inches into the walkway.  Standards §§ 4.1.2(3), 4.1.6(1)(b), 4.4.

 

25.       2-W 2nd Floor Drinking Fountain

a. Although an accessible drinking fountain is provided, there is no drinking fountain provided for people who have difficulty bending or stooping.  For each accessible drinking fountain, provide a drinking fountain that is accessible to people who have difficulty bending or stooping.  This can be accommodated by the use of a "hi-lo" fountain; by providing one fountain accessible to those who use wheelchairs and one fountain at a standard height convenient for those who have difficulty bending; by providing a fountain accessible to people who use wheelchairs and a cup dispenser, or by such other means as would achieve the required accessibility for each group of people.  Standards §§ 4.1.3(10)(a), 4.1.6(1)(b).

b. The drinking fountain is a protruding object and is not detectable to blind people using canes.  Provide a high drinking fountain at this location such that its bottom leading edges measure no more than 27 inches above the finished floor or protrude no more than 4 inches into the walkway.  Standards §§ 4.1.2(3), 4.1.6(1)(b), 4.4.

 

D.        Within 36 months of the effective date of this Agreement, the County will complete the following modifications to the Bullshead Health Department, located at 855 West Main Street, Rochester, NY. [Altered]

 

1.         Accessible Route

 

a. There is no signage indicating which entrance is accessible and no signage at the inaccessible entrance directing people with disabilities to the accessible entrance.  Provide accessible directional signage with the International Symbol of Accessibility at inaccessible entrances directing users to the accessible entrance, and provide accessible signage with the International Symbol of Accessibility at all permanent accessible entrances.  Standards §§ 4.1.3(8)(d), 4.1.3(16)(b), 4.1.6(1)(b), 4.13, 4.30.

 

b. Permanent room signs do not have raised and Braille characters and are not mounted on the wall on the latch side of the door.  Provide permanent room signage with upper case, sans serif or simple serif type letters and numerals, meeting the requirements of the Standards for character height, raised characters, finish and contrast, accompanied by Grade 2 Braille; mounted on the wall adjacent to the latch side of the door or on the nearest adjacent wall at a height of 60 inches above the finished floor to the centerline of the sign; and located so that a person may approach within 3 inches of the signage without encountering protruding objects or standing within the swing of a door.  Standards §§ 4.1.2(7), 4.1.6(1)(b), 4.30.1, 4.30.4, 4.30.5, 4.30.6.

 

2.         Alarms

 

a. Although audible alarms are provided in the facility, there is no visual alarm in the toilet room.  Provide visual alarm devices in toilet rooms and any other general usage areas (e.g., meeting rooms), hallways, lobbies, and any other area for common use.  Such devices shall be integrated into the facility alarm system and shall meet the requirements of the Standards for lamp type, color, pulse duration, intensity, and flash rate.  Visual alarm appliances shall be placed 80 inches above the highest floor level within the space or 6 inches below the ceiling, whichever is lower.  Visual alarm appliances shall be located such that no place in any room or space, including common corridors or hallways, required to have a visual alarm appliance shall be more than 50 feet from the signal.  In large rooms and spaces exceeding 100 feet across, without obstructions 6 feet above the finished floor, devices may be placed around the perimeter, spaced a maximum of 100 feet apart, in lieu of suspending appliances from the ceiling.  Standards §§ 4.1.3(14), 4.1.6(1)(b), 4.28.3.

 

3.         Telephones

a. The telephone lacks appropriate signage.  Provide an accessible telephone with a clear floor space of at least 30 inches by 48 inches that allows either a forward or parallel approach by a person using a wheelchair such that bases, enclosures, and fixed seats do not impede approaches to the telephone; with the highest operable part of the telephone mounted no more than 48 inches above the floor for a front approach or no more than 54 inches above the floor for a side approach; that is hearing aid compatible and has a volume control mechanism; with telephone books, if provided, located between 15 and 48 inches above the finished floor for a front approach or between 9 and 54 inches above the finished floor for a side approach; with a cord of at least 29 inches long from the telephone to the handset; and with signage that complies with the Standards.  Standards §§ 4.1.3(17), 4.1.6(1)(b), 4.31, 4.30.7(2).

 

4.         Main Entrance Ramp

a. Adequate edge protection is not provided.  Provide edge protection at least 2 inches high at the drop off sides.  Standards §§ 4.1.2(1), 4.1.2(2), 4.1.6(1)(b), 4.3.8, 4.8.7.

b. There are no handrails provided.  Provide handrails that are between 1¼ inches and 1½ inches in diameter with a continuous gripping surface along both sides of the ramp, extending at least 12 inches beyond the top and bottom of the ramp parallel with the ground surface.  Ensure that handrails are mounted between 34 inches and 38 inches above the ramp surface, with ends rounded or returned smoothly to the floor, wall, or post, and that they do not rotate within their fittings.  Standards §§ 4.1.2(1), 4.1.2(2), 4.1.6(1)(b), 4.8.5.

 

5.         Treatment Room Area Unisex, Single-User Toilet Room

a. There is no appropriate signage provided.  Provide a toilet room sign with raised and Braille characters.  The sign shall be mounted on the wall adjacent to the latch side of the door with the centerline of the sign at 60 inches above the finished floor and situated such that a person can approach within 3 inches of the sign without encountering an obstruction or standing within a door swing.  Standards §§ 4.1.2(7)(d), 4.1.6(1)(b), 4.30.1, 4.30.4, 4.30.5, 4.30.6.

b. The toilet centerline is 16 inches from the near side wall.  Provide a toilet with a centerline that measures 18 inches from the near side wall.  Standards §§ 4.1.3(11), 4.1.6(1)(b), 4.22.4, 4.16.2, Fig. 28.

 

6.         Front Waiting Room Unisex, Single-User Toilet Room

a. There is no appropriate signage provided.   Provide a toilet room sign with raised and Braille characters.  The sign shall be mounted on the wall adjacent to the latch side of the door with the centerline of the sign at 60 inches above the finished floor and situated such that a person can approach within 3 inches of the sign without encountering an obstruction or standing within a door swing.  Standards §§ 4.1.2(7)(d), 4.1.6(1)(b), 4.30.1, 4.30.4, 4.30.5, 4.30.6.

b. The overall length of the rear grab bar is  25 inches long.  Provide a rear grab bar that is at least 36 inches in overall length with the closer end no more than 6 inches from the side wall.  Standards §§ 4.1.3(11), 4.1.6(1)(b), 4.22.4, 4.16.4, Fig. 29.

 

E.         Within 36 months of the effective date of this Agreement, the County will complete the following modifications to the Health and Social Services, Bausch Building, located at 691 St. Paul Street, Rochester, NY. [Existing]

 

1.         5th Floor

a. The door requires more than 10 pounds of force to open.  Provide a door that requires no more than 5 pounds of force to open.  Standards § 4.13.11(2)(b).

b. The secure access area can only be accessed by telephone, which does not allow access for people who are deaf or hard of hearing.  Provide a call button within accessible reach ranges at this entrance and ensure that the door will be unlocked promptly when the call button is used.  Standards § 4.1.3(8).  The County will provide a way for persons who are deaf or hard of hearing to summon assistance without delay.

 

2.         4th Floor

a. The door requires more than 10 pounds of force to open.  Provide a door that requires no more than 5 pounds of force to open.  Standards § 4.13.11(2)(b).

b. The secure access area can only be accessed by telephone, which does not allow access for people who are deaf or hard of hearing.  Provide a call button within accessible reach ranges at this entrance and ensure that the door will be unlocked promptly when the call button is used.  Standards § 4.1.3(8).  The County will provide a way for persons who are deaf or hard of hearing to summon assistance without delay.

 

3.         3rd Floor

a. The door requires more than 10 pounds of force to open.  Provide a door that requires no more than 5 pounds of force to open.  Standards § 4.13.11(2)(b).

b. The secure access area can only be accessed by telephone, which does not allow access for people who are deaf or hard of hearing.  Provide a call button within accessible reach ranges at this entrance and ensure that the door will be unlocked promptly when the call button is used.  Standards § 4.1.3(8).  The County will provide a way for persons who are deaf or hard of hearing to summon assistance without delay.

 

4.         Main Reception Area

a. The door requires 9 pounds of force to open.  Provide a door that requires no more than 5 pounds of force to open.  Standards § 4.13.11(2)(b).

 

5.         Room 524 Women's Toilet Room with Stalls

a. The toilet room sign is mounted on the door.  Provide a toilet room sign with raised and Braille characters.  The sign shall be mounted on the wall adjacent to the latch side of the door with the centerline of the sign at 60 inches above the finished floor and situated such that a person can approach within 3 inches of the sign without encountering an obstruction or standing within a door swing.  Standards §§ 4.1.2(7)(d), 4.30.1, 4.30.4, 4.30.5, 4.30.6.

b. The entrance door requires 13 pounds of force to open.  Provide a door that requires no more than 5 pounds of force to open.  Standards § 4.13.11(2)(b).

c. No accessible coat hook has been provided.  Provide a coat hook at a maximum height above the finished floor of 48 inches for a forward approach or 54 inches for a side approach and that is accompanied by clear floor space of 30 by 48 inches that allows a forward or parallel approach by a person using a wheelchair.  Standards §§ 4.25.2, 4.25.3, 4.2.4, 4.2.5, 4.2.6.

d. The pipes under the lavatory are not covered or otherwise configured to protect against contact.  Provide hot water and drain pipes that are insulated or otherwise configured to protect against contact.  Standards § 4.19.4.

e. The centerline of the toilet in the designated accessible stall is 19¾ inches from the near side wall.  Provide a toilet with a centerline that measures 18 inches from the near side wall.  Standards § 4.17.3, Fig. 30.

f. The toilet paper dispenser in the designated accessible stall is mounted 42½ inches from the rear wall.  Provide a toilet paper dispenser that is mounted with its top at least 1½ inches under the side grab bar and 36 inches or less from the rear wall and is centered at least 19 inches above the finished floor.  Standards § 4.17.3, Fig. 30(d).

 

6.         Room 524 Men's Toilet Room with Stalls

a. The toilet room sign is mounted on the door.  Provide a toilet room sign with raised and Braille characters.  The sign shall be mounted on the wall adjacent to the latch side of the door with the centerline of the sign at 60 inches above the finished floor and situated such that a person can approach within 3 inches of the sign without encountering an obstruction or standing within a door swing.  Standards §§ 4.1.2(7)(d), 4.30.1, 4.30.4, 4.30.5, 4.30.6.

b. The entrance door requires 10 pounds of force to open.  Provide a door that requires no more than 5 pounds of force to open.  Standards § 4.13.11(2)(b).

c. No accessible coat hook has been provided.  Provide a coat hook at a maximum height above the finished floor of 48 inches for a forward approach or 54 inches for a side approach and that is accompanied by clear floor space of 30 by 48 inches that allows a forward or parallel approach by a person using a wheelchair.  Standards §§ 4.25.2, 4.25.3, 4.2.4, 4.2.5, 4.2.6.

d. The pipes under the lavatory are not covered or otherwise configured to protect against contact.  Provide hot water and drain pipes that are insulated or otherwise configured to protect against contact.  Standards § 4.19.4.

e. The centerline of the toilet in the designated accessible stall is 20½ inches from the near side wall.  Provide a toilet with a centerline that measures 18 inches from the near side wall.  Standards § 4.17.3, Fig. 30.

f. The toilet paper dispenser in the designated accessible stall is mounted 44½ inches from the rear wall.  Provide a toilet paper dispenser that is mounted with its top at least 1½ inches under the side grab bar and 36 inches or less from the rear wall and is centered at least 19 inches above the finished floor.  Standards § 4.17.3, Fig. 30(d).

g. The side grab bar is only 36 inches long and the farther end is mounted only 42 inches from the rear wall.  Provide a side grab bar that is at least 40 inches in overall length, with the far end mounted at least 52 inches from the rear wall and the closer end 12 inches or less from the rear wall.  Standards § 4.17.6, Figs. 30(a), (d).

 

7.         Room 424 Women's Toilet Room with Stalls

a. The toilet room sign is mounted on the door.  Provide a toilet room sign with raised and Braille characters.  The sign shall be mounted on the wall adjacent to the latch side of the door with the centerline of the sign at 60 inches above the finished floor and situated such that a person can approach within 3 inches of the sign without encountering an obstruction or standing within a door swing.  Standards §§ 4.1.2(7)(d), 4.30.1, 4.30.4, 4.30.5, 4.30.6.

b. The entrance door requires 10 pounds of force to open.    Provide a door that requires no more than 5 pounds of force to open.  Standards § 4.13.11(2)(b).

c. The top rim of the lavatory county is 35 inches above the finished floor.  Provide a lavatory with the top of its rim or counter 34 inches or less above the finished floor; the bottom edge of the apron at least 29 inches above the finished floor; and knee and toe clearances that comply with Fig. 31.  Standards § 4.19.2, Fig. 31.

d. The pipes under the lavatory are not covered or otherwise configured to protect against contact.  Provide hot water and drain pipes that are insulated or otherwise configured to protect against contact.  Standards § 4.19.4.

e. No accessible coat hook has been provided.  Provide a coat hook at a maximum height above the finished floor of 48 inches for a forward approach or 54 inches for a side approach and that is accompanied by clear floor space of 30 by 48 inches that allows a forward or parallel approach by a person using a wheelchair.  Standards §§ 4.25.2, 4.25.3, 4.2.4, 4.2.5, 4.2.6.

f. The toilet paper dispenser in the designated accessible stall is mounted 45 inches from the rear wall.  Provide a toilet paper dispenser that is mounted with its top at least 1½ inches under the side grab bar and 36 inches or less from the rear wall and is centered at least 19 inches above the finished floor.  Standards § 4.17.3, Fig. 30(d).

 

8.         Room 424 Men's Toilet Room with Stalls

a. The toilet room sign is mounted on the door.  Provide a toilet room sign with raised and Braille characters.  The sign shall be mounted on the wall adjacent to the latch side of the door with the centerline of the sign at 60 inches above the finished floor and situated such that a person can approach within 3 inches of the sign without encountering an obstruction or standing within a door swing.  Standards §§ 4.1.2(7)(d), 4.30.1, 4.30.4, 4.30.5, 4.30.6.

b. The entrance door requires 10 pounds of force to open.    Provide a door that requires no more than 5 pounds of force to open.  Standards § 4.13.11(2)(b).

c. The highest operable part of the baby changing station is mounted at 58½ inches above the finished floor when the station is closed.  Provide a baby changing table  with a maximum height above the finished floor of 48 inches for a forward approach or 54 inches for a side approach and that is accompanied by clear floor space of 30 by 48 inches that allows a forward or parallel approach by a person using a wheelchair.  Standards §§ 4.27.2, 4.27.3, 4.2.4, 4.2.5, 4.2.6.

d. The pipes under the lavatory are not covered or otherwise configured to protect against contact.  Provide hot water and drain pipes that are insulated or otherwise configured to protect against contact.  Standards § 4.19.4.

e. The urinal is mounted with the rim 25 inches and the flush control 52½ inches above the finished floor.  Provide a urinal with an elongated rim mounted 17 inches or less above the finished floor, a clear floor space of at least 30 inches wide and 48 inches deep centered on the urinal, and a flush control height of 44 inches or less above the finished floor.  Standards §§ 4.18.2, 4.18.3, 4.18.4.

f. No accessible coat hook has been provided.  Provide a coat hook at a maximum height above the finished floor of 48 inches for a forward approach or 54 inches for a side approach and that is accompanied by clear floor space of 30 by 48 inches that allows a forward or parallel approach by a person using a wheelchair.  Standards §§ 4.25.2, 4.25.3, 4.2.4, 4.2.5, 4.2.6.

g. The toilet paper dispenser in the designated accessible stall is mounted 45 inches from the rear wall.  Provide a toilet paper dispenser that is mounted with its top at least 1½ inches under the side grab bar and 36 inches or less from the rear wall and is centered at least 19 inches above the finished floor.  Standards § 4.17.3, Fig. 30(d).

 

9.         Room 325 Women's Toilet Room

a. The room does not have appropriate signage. Provide a toilet room sign with raised and Braille characters.  The sign shall be mounted on the wall adjacent to the latch side of the door with the centerline of the sign at 60 inches above the finished floor and situated such that a person can approach within 3 inches of the sign without encountering an obstruction or standing within a door swing.  Standards §§ 4.1.2(7)(d), 4.30.1, 4.30.4, 4.30.5, 4.30.6.

b. The entrance door requires 8 pounds of force to open.    Provide a door that requires no more than 5 pounds of force to open.  Standards § 4.13.11(2)(b).

c. The door threshold is a barrier to wheelchair access.  Provide a door with a threshold no greater than ¼ inch, or between ¼ inch and ½ inch and beveled with a slope no greater than 1:2.  Standards §§ 4.13.8, 4.5.2.

d. The pipes under the lavatory are not covered or otherwise configured to protect against contact.  Provide hot water and drain pipes that are insulated or otherwise configured to protect against contact.  Standards § 4.19.4.

e. The toilet paper dispenser in the designated accessible stall is mounted 45 inches from the rear wall.  Provide a toilet paper dispenser that is mounted with its top at least 1½ inches under the side grab bar and 36 inches or less from the rear wall and is centered at least 19 inches above the finished floor.  Standards § 4.17.3, Fig. 30(d).

 

10.       Room 325 Men's Toilet Room with Stalls

a. The toilet room sign is mounted on the door.  Provide a toilet room sign with raised and Braille characters.  The sign shall be mounted on the wall adjacent to the latch side of the door with the centerline of the sign at 60 inches above the finished floor and situated such that a person can approach within 3 inches of the sign without encountering an obstruction or standing within a door swing.  Standards §§ 4.1.2(7)(d), 4.30.1, 4.30.4, 4.30.5, 4.30.6.

b. The entrance door requires 10 pounds of force to open.    Provide a door that requires no more than 5 pounds of force to open.  Standards § 4.13.11(2)(b).

c. The door threshold is a barrier to persons using wheelchairs.  Provide a door with a threshold no greater than ¼ inch, or between ¼ inch and ½ inch and beveled with a slope no greater than 1:2.  Standards §§ 4.13.8, 4.5.2.

d. The urinal is mounted with the rim 25 inches above the finished floor.  Provide a urinal with an elongated rim mounted 17 inches or less above the finished floor, a clear floor space of at least 30 inches wide and 48 inches deep centered on the urinal, and a flush control height of 44 inches or less above the finished floor.  Standards §§ 4.18.2, 4.18.3, 4.18.4.

e. No accessible coat hook has been provided.  Provide a coat hook at a maximum height above the finished floor of 48 inches for a forward approach or 54 inches for a side approach and that is accompanied by clear floor space of 30 by 48 inches that allows a forward or parallel approach by a person using a wheelchair.  Standards §§ 4.25.2, 4.25.3, 4.2.4, 4.2.5, 4.2.6.

f. The toilet paper dispenser in the designated accessible stall is mounted 45 inches from the rear wall.  Provide a toilet paper dispenser that is mounted with its top at least 1½ inches under the side grab bar and 36 inches or less from the rear wall and is centered at least 19 inches above the finished floor.  Standards § 4.17.3, Fig. 30(d).

 

11.       Room 224 Women's Toilet Room with Stalls

a. The toilet room sign is mounted on the door.  Provide a toilet room sign with raised and Braille characters.  The sign shall be mounted on the wall adjacent to the latch side of the door with the centerline of the sign at 60 inches above the finished floor and situated such that a person can approach within 3 inches of the sign without encountering an obstruction or standing within a door swing.  Standards §§ 4.1.2(7)(d), 4.30.1, 4.30.4, 4.30.5, 4.30.6.

b. The entrance door requires more than 5 pounds of force to open.  Provide a door that requires no more than 5 pounds of force to open.  Standards § 4.13.11(2)(b).

c. The door threshold is a barrier to people who use wheelchairs.  Provide a door with a threshold no greater than ¼ inch, or between ¼ inch and ½ inch and beveled with a slope no greater than 1:2.  Standards §§ 4.13.8, 4.5.2.

d. The highest operable part of the baby changing station is mounted at 58 inches above the finished floor when the station is closed.  Provide a baby changing station with a maximum height above the finished floor of 48 inches for a forward approach or 54 inches for a side approach and that is accompanied by clear floor space of 30 by 48 inches that allows a forward or parallel approach by a person using a wheelchair.  Standards §§ 4.27.2, 4.27.3, 4.2.4, 4.2.5, 4.2.6.

e. The pipes under the lavatory are not covered or otherwise configured to protect against contact.  Provide hot water and drain pipes that are insulated or otherwise configured to protect against contact.  Standards § 4.19.4.

f. No accessible coat hook has been provided.  Provide a coat hook at a maximum height above the finished floor of 48 inches for a forward approach or 54 inches for a side approach and that is accompanied by clear floor space of 30 by 48 inches that allows a forward or parallel approach by a person using a wheelchair.  Standards §§ 4.25.2, 4.25.3, 4.2.4, 4.2.5, 4.2.6.

g. The toilet paper dispenser in the designated accessible stall is mounted 45 inches from the rear wall.  Provide a toilet paper dispenser that is mounted with its top at least 1½ inches under the side grab bar and 36 inches or less from the rear wall and is centered at least 19 inches above the finished floor.  Standards § 4.17.3, Fig. 30(d).

 

12.       Room 224 Men's Toilet Room with Stalls

a. The toilet room sign is mounted on the door.  Provide a toilet room sign with raised and Braille characters.  The sign shall be mounted on the wall adjacent to the latch side of the door with the centerline of the sign at 60 inches above the finished floor and situated such that a person can approach within 3 inches of the sign without encountering an obstruction or standing within a door swing.  Standards §§ 4.1.2(7)(d), 4.30.1, 4.30.4, 4.30.5, 4.30.6.

b. The entrance door requires more than 5 pounds of force to open.  Provide a door that requires no more than 5 pounds of force to open.  Standards § 4.13.11(2)(b).

c. The door threshold is a barrier to people who use wheelchairs.  Provide a door with a threshold no greater than ¼ inch, or between ¼ inch and ½ inch and beveled with a slope no greater than 1:2.  Standards §§ 4.13.8, 4.5.2.

d. The highest operable part of the baby changing station is mounted at 58 inches above the finished floor when the station is closed.  Provide a baby changing station with a maximum height above the finished floor of 48 inches for a forward approach or 54 inches for a side approach and that is accompanied by clear floor space of 30 by 48 inches that allows a forward or parallel approach by a person using a wheelchair.  Standards §§ 4.27.2, 4.27.3, 4.2.4, 4.2.5, 4.2.6.

e. The pipes under the lavatory are not covered or otherwise configured to protect against contact.  Provide hot water and drain pipes that are insulated or otherwise configured to protect against contact.  Standards § 4.19.4.

f. The urinal is mounted with the rim 25 inches and the flush control 50 inches above the finished floor.  Provide a urinal with an elongated rim mounted 17 inches or less above the finished floor, a clear floor space of at least 30 inches wide and 48 inches deep centered on the urinal, and a flush control height of 44 inches or less above the finished floor.  Standards §§ 4.18.2, 4.18.3, 4.18.4.

g. No accessible coat hook has been provided.  Provide a coat hook at a maximum height above the finished floor of 48 inches for a forward approach or 54 inches for a side approach and that is accompanied by clear floor space of 30 by 48 inches that allows a forward or parallel approach by a person using a wheelchair.  Standards §§ 4.25.2, 4.25.3, 4.2.4, 4.2.5, 4.2.6.

h. The toilet paper dispenser in the designated accessible stall is mounted 45 inches from the rear wall.  Provide a toilet paper dispenser that is mounted with its top at least 1½ inches under the side grab bar and 36 inches or less from the rear wall and is centered at least 19 inches above the finished floor.  Standards § 4.17.3, Fig. 30(d).

 

13.       Elevators

a. After reopening, the doors of the main elevator stay open for only 2 seconds.  Provide doors that open and close automatically with a reopening device that will stop and reopen the car door and hoistway door automatically if the door becomes obstructed by an object or person.  Ensure that the device is capable of completing these operations without requiring contact for obstructions passing through the opening at heights of 5 inches and 29 inches above the finished floor; that door reopening devices remain effective for at least 20 seconds, after which the doors may close; that the minimum time from notification that a car is answering a call until the doors of that car start to close is 5 seconds; and that the minimum time for elevator doors to remain fully open in response to a car call is 3 seconds.  Standards §§ 4.10.6, 4.10.7, 4.10.8, Figs. 20, 21.

b. The door to the emergency communications in the main elevator sticks.  Provide a two-way communication system such that it does not require voice communication, the highest operable part is a maximum of 48 inches above the finished floor of the car, and it is identified by a raised symbol and lettering located adjacent to the device.  If the system uses a handset, ensure that the length of the cord from the panel to the handset is at least 29 inches.  If the system is located in a closed compartment, ensure that the compartment door hardware operates without tight grasping, pinching or twisting of the wrist.  Standards § 4.10.14.

c. After reopening, the doors of the elevator facing Child and Family Services remain open for only 2 seconds.  Ensure that the device is capable of completing these operations without requiring contact for obstructions passing through the opening at heights of 5 inches and 29 inches above the finished floor; that door reopening devices remain effective for at least 20 seconds, after which the doors may close; that the minimum time from notification that a car is answering a call until the doors of that car start to close is 5 seconds; and that the minimum time for elevator doors to remain fully open in response to a car call is 3 seconds.  Standards §§ 4.10.6, 4.10.7, 4.10.8, Figs. 20, 21.

d. The door to the emergency communications in the elevator facing Child and Family Services sticks.  Provide a two-way communication system such that it does not require voice communication, the highest operable part is a maximum of 48 inches above the finished floor of the car, and it is identified by a raised symbol and lettering located adjacent to the device.  If the system uses a handset, ensure that the length of the cord from the panel to the handset is at least 29 inches.  If the system is located in a closed compartment, ensure that the compartment door hardware operates without tight grasping, pinching or twisting of the wrist.  Standards § 4.10.14.

e. After reopening, the doors of the left elevator remain open for only 2 seconds.  Ensure that the device is capable of completing these operations without requiring contact for obstructions passing through the opening at heights of 5 inches and 29 inches above the finished floor; that door reopening devices remain effective for at least 20 seconds, after which the doors may close; that the minimum time from notification that a car is answering a call until the doors of that car start to close is 5 seconds; and that the minimum time for elevator doors to remain fully open in response to a car call is 3 seconds.  Standards §§ 4.10.6, 4.10.7, 4.10.8, Figs. 20, 21.

 

14.       Room 120 Men's Toilet Room with Stalls

a. The toilet room sign is mounted on the door.  Provide a toilet room sign with raised and Braille characters.  The sign shall be mounted on the wall adjacent to the latch side of the door with the centerline of the sign at 60 inches above the finished floor and situated such that a person can approach within 3 inches of the sign without encountering an obstruction or standing within a door swing.  Standards §§ 4.1.2(7)(d), 4.30.1, 4.30.4, 4.30.5, 4.30.6.

b. The entrance door requires more than 5 pounds of force to open.  Provide a door that requires no more than 5 pounds of force to open.  Standards § 4.13.11(2)(b).

c. The door threshold is greater than ½ inch.  Provide a door with a threshold no greater than ¼ inch, or between ¼ inch and ½ inch and beveled with a slope no greater than 1:2.  Standards §§ 4.13.8, 4.5.2.

d. The pipes under the lavatory are not covered or otherwise configured to protect against contact.  Provide hot water and drain pipes that are insulated or otherwise configured to protect against contact.  Standards § 4.19.4.

e. The urinal is mounted with the rim 25 inches and the flush control 52 inches above the finished floor.  Provide a urinal with an elongated rim mounted 17 inches or less above the finished floor, a clear floor space of at least 30 inches wide and 48 inches deep centered on the urinal, and a flush control height of 44 inches or less above the finished floor.  Standards §§ 4.18.2, 4.18.3, 4.18.4.

f. No accessible coat hook has been provided.  Provide a coat hook at a maximum height above the finished floor of 48 inches for a forward approach or 54 inches for a side approach and that is accompanied by clear floor space of 30 by 48 inches that allows a forward or parallel approach by a person using a wheelchair.  Standards §§ 4.25.2, 4.25.3, 4.2.4, 4.2.5, 4.2.6.

g. The toilet paper dispenser in the designated accessible stall is mounted 43 inches from the rear wall.  Provide a toilet paper dispenser that is mounted with its top at least 1½ inches under the side grab bar and 36 inches or less from the rear wall and is centered at least 19 inches above the finished floor.  Standards § 4.17.3, Fig. 30(d).

 

15.       Room 144 Women's Toilet Room with Stalls

a. The toilet room sign is mounted on the door.  Provide a toilet room sign with raised and Braille characters.  The sign shall be mounted on the wall adjacent to the latch side of the door with the centerline of the sign at 60 inches above the finished floor and situated such that a person can approach within 3 inches of the sign without encountering an obstruction or standing within a door swing.  Standards §§ 4.1.2(7)(d), 4.30.1, 4.30.4, 4.30.5, 4.30.6.

b. The entrance door requires more than 5 pounds of force to open.  Provide a door that requires no more than 5 pounds of force to open.  Standards § 4.13.11(2)(b).

c. The door threshold poses a barrier to people who use wheelchairs.  Provide a door with a threshold no greater than ¼ inch, or between ¼ inch and ½ inch and beveled with a slope no greater than 1:2.  Standards §§ 4.13.8, 4.5.2.

d. The highest operable part of the baby changing station is mounted at 58 inches above the finished floor when the station is closed.  Provide a baby changing station with a maximum height above the finished floor of 48 inches for a forward approach or 54 inches for a side approach and that is accompanied by clear floor space of 30 by 48 inches that allows a forward or parallel approach by a person using a wheelchair.  Standards §§ 4.27.2, 4.27.3, 4.2.4, 4.2.5, 4.2.6.

e. The pipes under the lavatory are not covered or otherwise configured to protect against contact.  Provide hot water and drain pipes that are insulated or otherwise configured to protect against contact.  Standards § 4.19.4.

f. No accessible coat hook has been provided.  Provide a coat hook at a maximum height above the finished floor of 48 inches for a forward approach or 54 inches for a side approach and that is accompanied by clear floor space of 30 by 48 inches that allows a forward or parallel approach by a person using a wheelchair.  Standards §§ 4.25.2, 4.25.3, 4.2.4, 4.2.5, 4.2.6.

g. The toilet paper dispenser in the designated accessible stall is mounted 45 inches from the rear wall.  Provide a toilet paper dispenser that is mounted with its top at least 1½ inches under the side grab bar and 36 inches or less from the rear wall and is centered at least 19 inches above the finished floor.  Standards § 4.17.3, Fig. 30(d).

h. The shelf is mounted 55¼ inches above the finished floor to the lowest edge.  Provide a shelf with a maximum height above the finished floor of 48 inches for a forward approach or 54 inches for a side approach and that is accompanied by clear floor space of 30 by 48 inches that allows a forward or parallel approach by a person using a wheelchair.  Standards §§ 4.27.2, 4.27.3, 4.2.4, 4.2.5, 4.2.6.

 

16.       Women's Toilet Room Main Reception Area 

a. The toilet room sign is mounted on the door.  Provide a toilet room sign with raised and Braille characters.  The sign shall be mounted on the wall adjacent to the latch side of the door with the centerline of the sign at 60 inches above the finished floor and situated such that a person can approach within 3 inches of the sign without encountering an obstruction or standing within a door swing.  Standards §§ 4.1.2(7)(d), 4.30.1, 4.30.4, 4.30.5, 4.30.6.

b. The entrance door requires more than 5 pounds of force to open.  Provide a door that requires no more than 5 pounds of force to open.  Standards § 4.13.11(2)(b).

c. The door threshold is a barrier to people who use wheelchairs.  Provide a door with a threshold no greater than ¼ inch, or between ¼ inch and ½ inch and beveled with a slope no greater than 1:2.  Standards §§ 4.13.8, 4.5.2.

d. The pipes under the lavatory are not covered or otherwise configured to protect against contact.  Provide hot water and drain pipes that are insulated or otherwise configured to protect against contact.  Standards § 4.19.4.

 

17.       Men's Toilet Room Main Reception Area

a. The toilet room sign is mounted on the door.  Provide a toilet room sign with raised and Braille characters.  The sign shall be mounted on the wall adjacent to the latch side of the door with the centerline of the sign at 60 inches above the finished floor and situated such that a person can approach within 3 inches of the sign without encountering an obstruction or standing within a door swing.  Standards §§ 4.1.2(7)(d), 4.30.1, 4.30.4, 4.30.5, 4.30.6.

b. The entrance door requires more than 5 pounds of force to open.  Provide a door that requires no more than 5 pounds of force to open.  Standards § 4.13.11(2)(b).

c. The door threshold is a barrier to people who use wheelchairs.  Provide a door with a threshold no greater than ¼ inch, or between ¼ inch and ½ inch and beveled with a slope no greater than 1:2.  Standards §§ 4.13.8, 4.5.2.

d. The pipes under the lavatory are not covered or otherwise configured to protect against contact.  Provide hot water and drain pipes that are insulated or otherwise configured to protect against contact.  Standards § 4.19.4.

e. No accessible coat hook has been provided.  Provide a coat hook at a maximum height above the finished floor of 48 inches for a forward approach or 54 inches for a side approach and that is accompanied by clear floor space of 30 by 48 inches that allows a forward or parallel approach by a person using a wheelchair.  Standards §§ 4.25.2, 4.25.3, 4.2.4, 4.2.5, 4.2.6.

f. The toilet paper dispenser in the designated accessible stall is mounted 45 inches from the rear wall.  Provide a toilet paper dispenser that is mounted with its top at least 1½ inches under the side grab bar and 36 inches or less from the rear wall and is centered at least 19 inches above the finished floor.  Standards § 4.17.3, Fig. 30(d).

g. The urinal is inaccessible because its rim is too high and the flush control 52 inches above the finished floor.  Provide a urinal with an elongated rim mounted 17 inches or less above the finished floor, a clear floor space of at least 30 inches wide and 48 inches deep centered on the urinal, and a flush control height of 44 inches or less above the finished floor.  Standards §§ 4.18.2, 4.18.3, 4.18.4.

 

18.       Drinking Fountains

a. There are no drinking fountains provided for people who have difficulty bending and stooping.  Provide a drinking fountain that is accessible to people who have difficulty bending or stooping.  This can be accommodated by the use of a "hi-lo" fountain; by providing one fountain accessible to those who use wheelchairs and one fountain at a standard height convenient for those who have difficulty bending; by providing a fountain accessible to people who use wheelchairs and a cup dispenser, or by such other means as would achieve the required accessibility for each group of people.  Standards § 4.1.3(10)(a).

b. The controls of the drinking fountain by room 247 require 8 pounds of force to operate.  Provide a drinking fountain with controls mounted on or near the front edge that are operable with one hand, that require 5 lbf or less to operate, and that can be operated without tight grasping, pinching, or twisting of the wrist.  Standards §§ 4.15.4, 4.27.4.

c. The controls of the drinking fountain by room 120 require 8 pounds of force to operate.  Provide a drinking fountain with controls mounted on or near the front edge that are operable with one hand, that require 5 lbf or less to operate, and that can be operated without tight grasping, pinching, or twisting of the wrist.  Standards §§ 4.15.4, 4.27.4.

d. The controls of the drinking fountain by Main Reception require 10 pounds of force to operate.  Provide a drinking fountain with controls mounted on or near the front edge that are operable with one hand, that require 5 lbf or less to operate, and that can be operated without tight grasping, pinching, or twisting of the wrist.  Standards §§ 4.15.4, 4.27.4.

 

F.         Within 36 months of the effective date of this Agreement, the County will complete the following modifications to the Public Defender's Office, located at 36 West Main Street, Rochester, NY: [Altered]

 

1.         Accessible Route

a. There is no signage indicating which entrance is accessible and no signage at the inaccessible entrance directing people with disabilities to the accessible entrance.  Provide accessible directional signage with the International Symbol of Accessibility at inaccessible entrances directing users to the accessible entrance, and provide accessible signage with the International Symbol of Accessibility at all permanent accessible entrances.  Standards §§ 4.1.3(8)(d), 4.1.3(16)(b), 4.1.6(1)(b), 4.13, 4.30.

 

2.         There is no accessible signage designating permanent rooms and spaces.  Provide permanent room signage with upper case, sans serif or simple serif type letters and numerals, meeting the requirements of the Standards for character height, raised characters, finish and contrast, accompanied by Grade 2 Braille; mounted on the wall adjacent to the latch side of the door or on the nearest adjacent wall at a height of 60 inches above the finished floor to the centerline of the sign; and located so that a person may approach within 3 inches of the signage without encountering protruding objects or standing within the swing of a door.  Standards §§ 4.1.2(7), 4.1.6(1)(b), 4.30.1, 4.30.4, 4.30.5, 4.30.6.

 

3.         Alarms

a. Although the facility contains an emergency alarm system, the alarm system is inaccessible because there are no visual alarms.  Provide visual alarm devices in toilet rooms and any other general usage areas (e.g., meeting rooms), hallways, lobbies, and any other area for common use.  Such devices shall be integrated into the facility alarm system and shall meet the requirements of the Standards for lamp type, color, pulse duration, intensity, and flash rate.  Visual alarm appliances shall be placed 80 inches above the highest floor level within the space or 6 inches below the ceiling, whichever is lower.  Visual alarm appliances shall be located such that no place in any room or space, including common corridors or hallways, required to have a visual alarm appliance shall be more than 50 feet from the signal.  In large rooms and spaces exceeding 100 feet across, without obstructions 6 feet above the finished floor, devices may be placed around the perimeter, spaced a maximum of 100 feet apart, in lieu of suspending appliances from the ceiling.  Standards §§ 4.1.3(14), 4.1.6(1)(b), 4.28.3.

 

4.         2nd Floor Reception Area           

a. The entrance door requires 12 pounds of force to open.  Provide a door that requires no more than 5 pounds of force to open.  Standards §§ 4.1.3(7)(b), 4.1.6(1)(b), 4.13.11(2)(b).

b. The double door to the main office requires 14 pounds of force to open.  Provide a door that requires no more than 5 pounds of force to open.  Standards §§ 4.1.3(7)(b), 4.1.6(1)(b), 4.13.11(2)(b).

 

5.         Drinking Fountain

a. The spout height it 43 inches above the finished floor.  Provide a fountain that has a spout height no higher than 36 inches, measured from the finished floor or ground surface to the spout outlet, and that otherwise complies with the Standards.  Standards §§ 4.1.3(10), 4.1.6(1)(b), 4.15, 4.27.4, Fig. 27.

b. The fountain controls are not operable with one hand and require tight grasping, pinching, or twisting of the wrist to operate.  Provide a drinking fountain with controls mounted on or near the front edge that are operable with one hand, that require 5 lbf or less to operate, and that can be operated without tight grasping, pinching, or twisting of the wrist.  Standards §§ 4.1.3(10), 4.1.6(1)(b), 4.15.4, 4.27.4.

 

6.         Elevators

a. The main elevator hall call buttons do not provide visual signals to indicate the call is registered or answered, the buttons are not raised or flush, the "up" button is not on top, and objects below the call buttons project more than 4 inches.  Provide hall (lobby) call buttons with visual signals indicating when each call is registered and when each call is answered.  Ensure that the call buttons are centered at 42 inches above the finished floor, a minimum of ¾ inch in the smallest dimension, with the button designating the up direction on top; that the call buttons are raised or flush; and that objects mounted beneath hall call buttons do not project into the elevator lobby more than 4 inches.  Standards §§ 4.1.3(5), 4.1.6(1)(b), 4.10.3, Fig. 20.

b. The main elevator hall lanterns do not provide audible and visual arrival signals, are not centered at least 72 inches above the finished floor, and are not visible from the area of the hall call buttons.  Provide hall lanterns at each hoistway entrance that emit a visible and audible signal indicating which car is answering a call.  Ensure that audible signals sound once for the up direction and twice for the down direction or have verbal annunciators that say "up" or "down;" and that visible signals are mounted so that their centerline is at least 72 inches above the lobby floor, they are at least 2½ inches in the smallest dimension, and they are visible from the vicinity of the hall call button.  Lanterns located in cars, visible from the vicinity of hall call buttons, and conforming to the above requirements, are acceptable.  Standards §§ 4.1.3(5), 4.1.6(1)(b), 4.10.4, Fig. 20.

c. The main elevator does not have hoistway signage provided.  Provide signage at hoistway entrances with raised and Braille floor designations on both jambs such that the centerline of the characters is 60 inches above the finished floor and the characters are 2 inches high.  Standards §§ 4.1.3(5), 4.1.6(1)(b), 4.10.5, Fig. 20.

d. The centerline of the emergency controls in the main elevator is 38 inches above the finished floor.  Provide emergency controls, including the emergency alarm and emergency stop, grouped at the bottom of the panel with their centerlines no less than 35 inches above the finished floor.  Standards §§ 4.1.3(5), 4.1.6(1)(b), 4.10.12, Fig. 23.

e. The main elevator does not provide audible or visual car position signals.  Provide visual car position indicators above the car control panel or over the door to show the position of the elevator in the hoistway.  Ensure that indicators emit an audible and visual signal as the car passes or stops at a floor served by the elevator, with the corresponding floor designation being illuminated; and that numerals are a minimum of ½ inch high.  Standards §§ 4.1.3(5), 4.1.6(1)(b), 4.10.13.

f. The elevator which requires a key to operate, and is not generally available to the public, does not have hoistway signage in raised characters and Braille.  Provide signage at hoistway entrances with raised and Braille floor designations on both jambs such that the centerline of the characters is 60 inches above the finished floor and the characters are 2 inches high.  Standards §§ 4.1.3(5), 4.1.6(1)(b), 4.10.5, Fig. 20.

 

7.         Designated Accessible Unisex, Single-User  Toilet Room

a. The room sign is mounted on the door, there is no International Symbol of Accessibility, and the sign does not have raised and Braille characters.   Provide a toilet room sign with raised and Braille characters.  The sign shall be mounted on the wall adjacent to the latch side of the door with the centerline of the sign at 60 inches above the finished floor and situated such that a person can approach within 3 inches of the sign without encountering an obstruction or standing within a door swing.  Standards §§ 4.1.2(7)(d), 4.1.6(1)(b), 4.30.1, 4.30.4, 4.30.5, 4.30.6.

b. The entry door requires 12 pounds of force to open.  Provide a door that requires no more than 5 pounds of force to open.  Standards §§ 4.1.3(7)(b), 4.1.6(1)(b), 4.13.11(2)(b).

c. No accessible mirror has been provided.  Provide a mirror with the bottom edge of its reflecting surface no more than 40 inches above the finished floor.  Standards §§ 4.1.3(11), 4.1.6(1)(b), 4.22.6, 4.19.6.

d. The toilet paper dispenser is mounted less than 19 inches above the finished floor.  Provide a toilet paper dispenser that is mounted within reach, with its top at least 1½ inches under the side grab bar, and centered at least 19 inches above the finished floor.  Standards §§ 4.1.3(11), 4.1.6(1)(b), 4.22.4, 4.16.6, Fig. 29(b).

 

G.        Within 36 months of the effective date of this Agreement, the County will complete the following modifications to the Public Safety, Wegman Building, located at 80 West Main Street, Rochester, NY: [Existing]

 

1.         There is no signage at inaccessible entrances directing people with disabilities to accessible entrances.  Provide accessible directional signage with the International Symbol of Accessibility at inaccessible entrances directing users to the accessible entrance, and provide accessible signage with the International Symbol of Accessibility at all permanent accessible entrances.  Standards §§ 4.1.3(8)(d), 4.1.3(16)(b), 4.1.6(1)(b), 4.13, 4.30.

 

2.         Elevator

a. The hall call buttons do not have visual signals indicating when a call is answered.   Provide hall (lobby) call buttons with visual signals indicating when each call is registered and when each call is answered.  Ensure that the call buttons are centered at 42 inches above the finished floor, a minimum of ¾ inch in the smallest dimension, with the button designating the up direction on top; that the call buttons are raised or flush; and that objects mounted beneath hall call buttons do not project into the elevator lobby more than 4 inches.  Standards §§ 4.1.3(5), 4.1.6(1)(b), 4.10.3, Fig. 20.

b. There are no hall lanterns provided.  Provide hall lanterns at each hoistway entrance that emit a visible and audible signal indicating which car is answering a call.  Ensure that audible signals sound once for the up direction and twice for the down direction or have verbal annunciators that say "up" or "down;" and that visible signals are mounted so that their centerline is at least 72 inches above the lobby floor, they are at least 2½ inches in the smallest dimension, and they are visible from the vicinity of the hall call button.  Lanterns located in cars, visible from the vicinity of hall call buttons, and conforming to the above requirements, are acceptable.  Standards §§ 4.1.3(5), 4.1.6(1)(b), 4.10.4, Fig. 20.

c. When the doors reopen, they remain open for only 11 seconds and after notification, the doors start to close after only 3 seconds..  Provide doors that open and close automatically with a reopening device that will stop and reopen the car door and hoistway door automatically if the door becomes obstructed by an object or person.  Ensure that the device is capable of completing these operations without requiring contact for obstructions passing through the opening at heights of 5 inches and 29 inches above the finished floor; that door reopening devices remain effective for at least 20 seconds, after which the doors may close; that the minimum time from notification that a car is answering a call until the doors of that car start to close is 5 seconds; and that the minimum time for elevator doors to remain fully open in response to a car call is 3 seconds.  Standards §§ 4.1.3(5), 4.1.6(1)(b), 4.10.6, 4.10.7, 4.10.8, Figs. 20, 21.

 

3.         Pre-Sentence Investigation Office Unisex, Single-User Toilet Room

a. The signage is mounted on the door.  Provide a toilet room sign with raised and Braille characters.  The sign shall be mounted on the wall adjacent to the latch side of the door with the centerline of the sign at 60 inches above the finished floor and situated such that a person can approach within 3 inches of the sign without encountering an obstruction or standing within a door swing.  Standards §§ 4.1.2(7)(d), 4.1.6(1)(b), 4.30.1, 4.30.4, 4.30.5, 4.30.6.

b. The clear floor space at the lavatory is obstructed by furniture and equipment.  Provide a lavatory with clear floor space at least 30 inches wide and 48 inches deep centered on the lavatory.  Standards § 4.19.3, Fig. 32.

 

4.         Socio-Legal Unisex, Single-User Toilet Room

a. The signage is mounted on the door.  Provide a toilet room sign with raised and Braille characters.  The sign shall be mounted on the wall adjacent to the latch side of the door with the centerline of the sign at 60 inches above the finished floor and situated such that a person can approach within 3 inches of the sign without encountering an obstruction or standing within a door swing.  Standards §§ 4.1.2(7)(d), 4.1.6(1)(b), 4.30.1, 4.30.4, 4.30.5, 4.30.6.

b. The toilet seat cover dispenser is inaccessible.  Provide a toilet seat cover dispenser with the controls a maximum height above the finished floor of 48 inches for a forward approach or 54 inches for a side approach and that is accompanied by clear floor space of 30 by 48 inches that allows a forward or parallel approach by a person using a wheelchair.  Standards §§ 4.27.2, 4.27.3, 4.2.4, 4.2.5, 4.2.6.

 

H.        Within 36 months of the effective date of this Agreement, the County will complete the following modifications to the Department of Motor Vehicles - Ridge Crest, located at 1940 West Ridge Road, Rochester, NY.

 

1.         Parking

a. The access aisle serving the van accessible parking space measures 60 inches.  At van accessible spaces, provide a "Van-Accessible" sign located below the International Symbol of Accessibility such that the sign cannot be obstructed by vehicles parked in the space and a designated van accessible parking spaces that are a minimum of 96 inches wide and served by access aisles at least 96 inches wide.  Standards §§ 4.6.4, 4.30.7(1), 4.1.2(5)(b), 4.6.3, Fig.9.

b. The designated accessible parking spaces serving the Department of Motor Vehicles are not level and do not have level access aisles.  Provide four designated accessible parking spaces and access aisles that are flat and level, with slopes and cross-slopes not exceeding 1:50 in all directions, with surfaces that are firm, stable, and slip-resistant.  Standards §§ 4.3.6, 4.5.1, 4.6.3.

 

2.         Exterior Entrances and Doors

a. The interior door at the entrance requires 10 pounds of force to operate.  Provide a door that requires no more than 5 pounds of force to open.  Standards § 4.13.11(2)(b).

 

3.         Telephones

a. The counter that serves the telephone does not have adequate knee space and the telephone lacks accessible signage.   Provide an accessible telephone with a clear floor space of at least 30 inches by 48 inches that allows either a forward or parallel approach by a person using a wheelchair such that bases, enclosures, and fixed seats do not impede approaches to the telephone; with the highest operable part of the telephone mounted no more than 48 inches above the floor for a front approach or no more than 54 inches above the floor for a side approach; that is hearing aid compatible and has a volume control mechanism; with telephone books, if provided, located between 15 and 48 inches above the finished floor for a front approach or between 9 and 54 inches above the finished floor for a side approach; with a cord of at least 29 inches long from the telephone to the handset; and with signage that complies with the Standards.  Standards §§ 4.31, 4.30.7(2).

 

4.         Writing Counters

a. The shelf/writing area is a protruding object.  Provide a shelf/writing area at this location such that its bottom leading edges measure no more than 27 inches above the finished floor or protrude no more than 4 inches into the walkway.  Standards § 4.4.

b. The shelf/writing area is mounted 38 inches above the finished floor and measures 12 inches deep.  Provide a shelf /writing area on an accessible route such that a portion of the counter is at least 36 inches wide and no more than 36 inches above the finished floor.  Alternatively, provide equivalent facilitation in the form of a clipboard.  Standards §§ 7.2(1), 4.3.

 

5.         Unisex, Single-User Toilet Room

a. The toilet room signage is mounted on the door.  Provide a toilet room sign with raised and Braille characters.  The sign shall be mounted on the wall adjacent to the latch side of the door with the centerline of the sign at 60 inches above the finished floor and situated such that a person can approach within 3 inches of the sign without encountering an obstruction or standing within a door swing.  Standards §§ 4.1.2(7)(d), 4.30.1, 4.30.4, 4.30.5, 4.30.6.

b. The toilet room door requires 10 pounds of force to operate.   Provide a door that requires no more than 5 pounds of force to open.  Standards § 4.13.11(2)(b).

c. The mirror is inaccessible.  Provide a mirror with the bottom edge of its reflecting surface no more than 40 inches above the finished floor.  Standards § 4.19.6.

d. The flush control valve is on the closed side.  Provide a flush control mounted on the "open" side of the toilet's clear floor space; 44 inches or less above the finished floor; and requiring a maximum of 5 pounds of force to operate; or provide an automatic flush device.  Standards §§ 4.16.5, 4.27.4.

 

I.          Within 36 months of the effective date of the Agreement, the County will make the following modifications to the License Bureau - Suburban Plaza,  located at 2199 Henrietta Road, Rochester, NY:

 

1.         Unisex, Single-User Toiler Room (In Public Area)

i. The toilet room sign is not mounted on the latch side and lacks raised and Braille letters.  Provide a toilet room sign with raised and Braille characters.  The sign shall be mounted on the wall adjacent to the latch side of the door with the centerline of the sign at 60 inches above the finished floor and situated such that a person can approach within 3 inches of the sign without encountering an obstruction or standing within a door swing.  Standards §§ 4.1.2(7)(d), 4.30.1, 4.30.4, 4.30.5, 4.30.6.

ii. The pressure required to open the door is 8 pounds of force.  Provide a door that requires no more than 5 pounds of force to open.  Standards § 4.13.11(2)(b).

iii. The distance of the farther end of the side grab bar to the rear wall is 49 inches.  Provide a side grab bar that is at least 40 inches in overall length, with the far end mounted at least 52 inches from the rear wall and the closer end 12 inches or less from the rear wall.  Standards § 4.16.4, Fig. 29(b).

iv. The distance of the farther end of the rear grab bar to the side wall is 29 inches.  Provide a rear grab bar that is at least 36 inches in

v. overall length with the closer end no more than 6 inches from the side wall.  Standards § 4.16.4, Fig. 29.

 

J.          Within 36  months of the effective date of the Agreement, the County will make the following modifications to the Sheriff's Office - Zone B, located at 245 Summit Road, Rochester, NY:

 

1.         Parking

a. Although there are 85 parking spaces with 4 designated as reserved for persons with disabilities, the signage designating the spaces as reserved for persons with disabilities is low and can be obstructed by parked vehicles.  At each space designated as reserved for persons with disabilities, provide a vertical sign with the International Symbol of Accessibility located such that it cannot be obstructed by vehicles parked in the space.  Standards §§ 4.6.4, 4.30.7(1).

 

2.         Exterior Entrance

a. The threshold at the exterior door is 1 ¾ inches.  Provide a door with a threshold no greater than ¼ inch, or between ¼ inch and ½ inch and beveled with a slope no greater than 1:2.  Standards §§ 4.13.8, 4.5.2.

 

3.         Unisex, Single-User Toilet Room

a. The toilet room sign is mounted on the door.  Provide a toilet room sign with raised and Braille characters.  The sign shall be mounted on the wall adjacent to the latch side of the door with the centerline of the sign at 60 inches above the finished floor and situated such that a person can approach within 3 inches of the sign without encountering an obstruction or standing within a door swing.  Standards §§ 4.1.2(7)(d), 4.30.1, 4.30.4, 4.30.5, 4.30.6.

b. No accessible coat hook has been provided.  Provide a coat hook at a maximum height above the finished floor of 48 inches for a forward approach or 54 inches for a side approach and that is accompanied by clear floor space of 30 by 48 inches that allows a forward or parallel approach by a person using a wheelchair.  Standards §§ 4.25.2, 4.25.3, 4.2.4, 4.2.5, 4.2.6.

c. The lavatory hot water pipes are not insulated or otherwise configured to protect against contact.  Provide hot water and drain pipes that are insulated or otherwise configured to protect against contact.  Standards § 4.19.4.

d. The toilet centerline is 20 inches from the side wall.  Provide a toilet with a centerline that measures 18 inches from the near side wall.  Standards § 4.16.2, Fig. 28.

e. The toilet flush control valve is on the closed side.  Provide a flush control mounted on the "open" side of the toilet's clear floor space; 44 inches or less above the finished floor; and requiring a maximum of 5 pounds of force to operate; or provide an automatic flush device.  Standards §§ 4.16.5, 4.27.4.

f. The overall length of the rear grab bar and the distance of its farther end to the side wall is less than 48 inches.  Provide a rear grab bar that is at least 36 inches in overall length with the closer end no more than 6 inches from the side wall.  Standards § 4.16.4, Fig. 29. 

 

4.         The Drinking Fountain

a. Although an accessible drinking fountain is provided, there is no drinking fountain provided for people who have difficulty bending or stooping.  For each accessible drinking fountain, provide a drinking fountain that is accessible to people who have difficulty bending or stooping.  This can be accommodated by the use of a "hi-lo" fountain; by providing one fountain accessible to those who use wheelchairs and one fountain at a standard height convenient for those who have difficulty bending; by providing a fountain accessible to people who use wheelchairs and a cup dispenser, or by such other means as would achieve the required accessibility for each group of people.  Standards § 4.1.3(10)(a).

 

5.         Holding Cells

a. Left (As Looking at Door)

i. This holding cell is accessible with one addition:  Provide a rear grab bar that is at least 36 inches in overall length, with the closer end no more than 6 inches from the side wall, and a side grab bar that is at least 40 inches in overall length, with the far end mounted at least 52 inches from the rear wall and the closer end 12 inches or less from the rear wall.  Ensure that the grab bars are mounted 33 to 36 inches above the finished floor; with a diameter between 1¼ and 1½ inches; with 1½ inches between the grab bars and the wall; and at least 1½ inches between the grab bars and any other object, such as a toilet paper dispenser or a toilet seat cover dispenser.  Standards §§ 4.16.4, 4.26.2, Fig. 29.

 

K.        Within 36 months of the effective date of the Agreement, the County will make the following modifications to the Sheriff's Office - Zone C, located at 2401 Buffalo Road, Rochester, NY:

 

1.         Although there are 85 parking spaces, none are designated as reserved for persons with disabilities.  On the shortest accessible route to the accessible entrance, provide 1 van accessible space and 3 standard spaces designated as reserved for people with disabilities.  Standard accessible spaces shall be a minimum of 96 inches wide and served by access aisles at least 60 inches wide.  Van accessible spaces shall be a minimum of 96 inches wide and served by access aisles at least 96 inches wide.  All spaces designated as reserved for people with disabilities shall have vertical signs with the International Symbol of Accessibility located such that they cannot be obstructed by parked vehicles.  Van accessible spaces shall have an additional "Van-Accessible" sign located below the International Symbol of Accessibility.  Standards §§ 4.1.2(5), 4.6, 4.30.7(1).

 

2.         Accessible Route

a. The route from the parking lot to the exterior entrance lacks curb cuts.  Provide a curb ramp that is at least 36 inches wide, has a maximum slope of 1:12, is located so that it cannot be obstructed by parked vehicles, and has a stable, firm, and slip-resistant surface with a detectable warning extending the full width and depth of the ramp.  If the curb ramp is located where pedestrians must walk across it, provide either flared sides (with a maximum slope of 1:10) or handrails or guardrails to protect against cross traffic.  Standards § 4.3.8, 4.7, Fig. 12.

 

3.         Exterior Entrance

a. The entrance lacks a level landing.  Provide a door so that the floor or ground area within the required clearances is level and clear.  Standards § 4.13.6, Fig. 25.

b. The telephone used as a "call button" during nights is inaccessible to people with hearing and speech impairments.  Establish a means by which persons who are deaf or hard of hearing can access the facility after hours.

 

4.         Drinking Fountain

a. The spout height is 40 inches above the finished floor and the water is 3 inches from the front of the fountain.  Provide a fountain that has a spout height no higher than 36 inches, measured from the finished floor or ground surface to the spout outlet, and that otherwise complies with the Standards, or provide a cup dispenser. Standards §§ 4.15, 4.27.4, Fig. 27.

 

5.         Unisex, Single-User Toilet Room

a. The toilet room lacks an accessible sign.  Provide a toilet room sign with raised and Braille characters.  The sign shall be mounted on the wall adjacent to the latch side of the door with the centerline of the sign at 60 inches above the finished floor and situated such that a person can approach within 3 inches of the sign without encountering an obstruction or standing within a door swing.  Standards §§ 4.1.2(7)(d), 4.30.1, 4.30.4, 4.30.5, 4.30.6.

b. The toilet room door has knob hardware that requires tight grasping, pinching or turning of the wrist to operate.  Provide a door with hardware that is easy to grasp with one hand and that does not require tight grasping, pinching, or twisting of the wrist to operate.  Lever-operated mechanisms, push-type mechanisms, and U-shaped handles are acceptable designs.  Standards § 4.13.9.

c. Although the toilet room provides an audible alarm, no visual alarm is provided.  Provide visual alarm devices in toilet rooms and any other general usage areas (e.g., meeting rooms), hallways, lobbies, and any other area for common use.  Such devices shall be integrated into the facility alarm system and shall meet the requirements of the Standards for lamp type, color, pulse duration, intensity, and flash rate.  Visual alarm appliances shall be placed 80 inches above the highest floor level within the space or 6 inches below the ceiling, whichever is lower.  Visual alarm appliances shall be located such that no place in any room or space, including common corridors or hallways, required to have a visual alarm appliance shall be more than 50 feet from the signal.  In large rooms and spaces exceeding 100 feet across, without obstructions 6 feet above the finished floor, devices may be placed around the perimeter, spaced a maximum of 100 feet apart, in lieu of suspending appliances from the ceiling.  Standards § 4.28.3.

d. The top of the lavatory counter is 36 inches above the finished floor.  Provide a lavatory with the top of its rim or counter 34 inches or less above the finished floor; the bottom edge of the apron at least 29 inches above the finished floor; and knee and toe clearances that comply with Fig. 31.  Standards § 4.19.2, Fig. 31.

e. The lavatory hot water pipes are not insulated or otherwise configured to protect against contact.  Provide hot water and drain pipes that are insulated or otherwise configured to protect against contact.  Standards § 4.19.4.

f. The clear floor space at the lavatory is obstructed by moveable objects.  Provide a lavatory with clear floor space at least 30 inches wide and 48 inches deep centered on the lavatory.  Standards § 4.19.3, Fig. 32.

g. The toilet seat is 20 inches above the finished floor.  Provide a toilet with a seat that measures 17 to 19 inches above the finished floor.  Standards § 4.16.3, Fig. 29(b).

h. The toilet centerline is 24 inches from the side wall.  Provide a toilet with a centerline that measures 18 inches from the near side wall.  Standards § 4.16.2, Fig. 28.

i. The toilet the flush control is on the closed side.  Provide a flush control mounted on the "open" side of the toilet's clear floor space; 44 inches or less above the finished floor; and requiring a maximum of 5 pounds of force to operate; or provide an automatic flush device.  Standards §§ 4.16.5, 4.27.4.

j. The overall length of the side grab bar is 36 inches and the distance of its farther end to the rear wall is 45 inches.  Provide a side grab bar that is at least 40 inches in overall length, with the far end mounted at least 52 inches from the rear wall and the closer end 12 inches or less from the rear wall.  Standards § 4.16.4, Fig. 29(b).

k. The overall length of the rear grab bar is 24 inches and the distance of its closer end to the side wall is 13 inches.  Provide a rear grab bar that is at least 36 inches in overall length with the closer end no more than 6 inches from the side wall.  Standards § 4.16.4, Fig. 29.

 

6.         Holding Cells

a. There are 2 holding cells, each of which lack accessible toilets and grab bars.  Provide at least one that has an accessible toilet that complies with the Standards or provide a program access solution.  Standards §§ 4.13, 4.16, 4.18, 4.19, 4.26, 4.27, 4.30, Figs. 28, 29.