ATTACHMENT K: Program Access in Existing Facilities
Please Note: Paragraph 58 of the Agreement requires that within one (1) year of the effective date of this Agreement, the City of Milwaukee will provide signage as necessary to comply with 28 C.F.R. § 35.163(b), after having surveyed all facilities that are the subject of this Agreement for the purpose of identifying those that have multiple entrances not all of which are accessible.
The technical requirements and, where appropriate, the scoping requirements of the Standards are used as a guide for determining whether a program or activity held in an existing facility is €śreadily accessible to and usable by€ť persons with disabilities and for determining what changes are necessary to make this program or activity accessible if it continues to be provided in the existing facility in question. See 28 C.F.R. §§ 35.150(b)(1), 35.151.
The chart below lists the facilities surveyed by the Department, the access issues identified during the survey, and the actions required to correct the access issues. Required actions are listed using an alphanumeric code. The key to the alphanumeric codes is provided in Attachment M to this Agreement.
In order to ensure that the programs, services, and activities housed in the City€™s facilities are accessible to persons with disabilities, when viewed in their entirety, the City of Milwaukee will take the actions referenced by the alphanumeric code and described in detail in Attachment M to this Settlement Agreement within the time period specified below, which time period begins to run on the effective date of the Agreement.
|
|||
Item # |
Access Issue |
Required Action |
Completion Date |
1. |
Center Street Library, 2727 Fon Du Lac Av. |
|
|
1.1. |
Parking lot: The designated accessible parking is inaccessible because it slopes up to 3.8%, and the shared access aisle slopes 3.5% and has a cross-slope of 2.9%. |
P4 |
30 months |
1.2. |
Meeting room (near front entrance): The entry doors are inaccessible because they require 10 pounds of force to open. |
D3 |
12 months |
1.3. |
Drinking fountain (near front entrance): Although a designated accessible drinking fountain is provided, there is no drinking fountain provided for people who have difficulty bending or stooping. |
DF3 |
30 months |
1.4. |
Women€™s single-user toilet room (near front entrance): |
|
|
1.4.1. |
The toilet room sign has no raised or Braille characters. |
TR11 |
12 months |
1.4.2. |
The pull side of the door, which is accessed from the latch side of the door, is inaccessible because it has less than 48 inches of clear space on the latch side. |
D5 |
30 months |
1.4.3. |
The door is inaccessible because it has an opening width of 29˝ inches. |
D14 |
30 months |
1.4.4. |
The door is inaccessible because knob hardware is used. |
D2 |
24 months |
1.4.5. |
Although an audible alarm is provided in this facility, there is no visual alarm appliance in the toilet room. |
AL1 |
30 months |
1.4.6. |
No accessible mirror has been provided. |
TR5 |
24 months |
1.4.7. |
The hand dryer protrudes into the walkway and is not detectable to blind persons using a cane. |
AR7 |
12 months |
1.4.8. |
The lavatory is inaccessible because the hot water and drain pipes are not insulated or otherwise configured to protect against contact. |
LS2 |
24 months |
1.4.9. |
The toilet nearest to the lavatory is inaccessible because its centerline is 15 inches from the side wall. |
TR7 |
30 months |
1.4.10. |
The toilet nearest to the lavatory is inaccessible because the flush control is on the closed side. |
TR4 |
30 months |
1.4.11. |
The toilet nearest to the lavatory is inaccessible because there is no rear grab bar provided. |
TR13 |
24 months |
1.5. |
Men€™s single-user toilet room (near front entrance): |
|
|
1.5.1. |
The toilet room sign is not mounted with tactile characters between 48 and 60 inches high, and has no raised or Braille characters. |
TR11 |
12 months |
1.5.2. |
The pull side of the door, which is accessed from the latch side of the door, is inaccessible because it has less than 48 inches of clear space on the latch side. |
D5 |
30 months |
1.5.3. |
The door is inaccessible because it has an opening width of 29˝ inches. |
D14 |
30 months |
1.5.4. |
The door is inaccessible because knob hardware is used. |
D2 |
24 months |
1.5.5. |
Although an audible alarm is provided in this facility, there is no visual alarm appliance in the toilet room. |
AL1 |
30 months |
1.5.6. |
No accessible mirror has been provided. |
TR5 |
24 months |
1.5.7. |
The lavatory is inaccessible because the hot water and drain pipes are not insulated or otherwise configured to protect against contact. |
LS2 |
24 months |
1.5.8. |
The toilet paper dispenser is inaccessible because it is mounted 42˝ inches from the rear wall. |
TR6 |
12 months |
1.5.9. |
The toilet is inaccessible because the side grab bar is mounted with its farther end 46 inches from the rear wall. |
TR17 |
12 months |
1.5.10. |
The toilet is inaccessible because there is no rear grab bar provided. |
TR13 |
24 months |
1.6. |
Stacks: The book stacks are inaccessible because the space between stacks narrows to only 30˝ inches wide. |
AR3 |
30 months |
1.7. |
Computer tables: The computer tables are inaccessible because they provide 25˝ inches of clear knee height. |
DW1 |
12 months |
1.8. |
Group study office: |
|
|
1.8.1. |
The door is inaccessible because it has an opening width of 30˝ inches. |
D14 |
24 months |
1.8.2. |
The door is inaccessible because knob hardware is used. |
D2 |
24 months |
1.8.3. |
The door is inaccessible because it requires 13 pounds of force to open. |
D3 |
12 months |
1.9. |
Project Open Door office: |
|
|
1.9.1. |
The door is inaccessible because it has an opening width of 30˝ inches. |
D14 |
30 months |
1.9.2. |
The door is inaccessible because knob hardware is used. |
D2 |
24 months |
1.9.3. |
The door is inaccessible because it requires 13 pounds of force to open. |
D3 |
12 months |
2. |
East Library, 1910 E. North Av. (Newly constructed since DOJ survey; the newly constructed East Library will be surveyed by ILA within 18 months per agreement paragraph ___) |
|
|
2.1. |
Exterior entrances: The building does not have directional signage posted at inaccessible entrances and does not have the international Symbol of Accessibility posted at accessible entrances. |
D10 |
|
2.2. |
Exterior ramp: The ramp is inaccessible because no handrails are provided. |
R2 |
|
2.3. |
Check-out area: The check-out area is inaccessible because the counter is more than 36 inches high. |
C1 |
|
2.4. |
Men and women€™s toilet rooms by the check-out counter: The toilet rooms contain a number of inaccessible elements and are not accessible to people with disabilities. |
TR1 |
|
2.5. |
Drinking fountains: |
|
|
2.5.a. |
The wall-mounted drinking fountain on the north side is inaccessible because it provides only 24 inches of clear knee height. |
DF4 |
|
2.5.b. |
Although a designated accessible drinking fountain is provided on the north side, there is no drinking fountain provided for people who have difficulty bending or stooping. |
DF3 |
|
2.5.c. |
The drinking fountain on the south side protrudes into the walkway and is not detectable to blind persons using a cane. |
AR7 |
|
2.5.d. |
Although a designated accessible drinking fountain is provided on the south side, there is no drinking fountain provided for people who have difficulty bending or stooping. |
DF3 |
|
3. |
Fire Engine House #22, 8814 W. Lisbon Av. (Polling conducted here) |
|
|
3.1. |
Parking lot: The parking lot, with a total of approximately 6 parking spaces, is inaccessible because the pavement is unmarked and no designated accessible parking space is provided. This lot requires 1 van accessible space. |
P1 |
30 months |
3.2. |
Exterior entrances (general): The building does not have directional signage posted at inaccessible entrances and does not have the International Symbol of Accessibility posted at accessible entrances. |
D10 |
24 months |
3.3. |
Exterior entrance (side entrance from parking lot): |
|
|
3.3.1. |
The door is inaccessible because there is a 1˝ inch high threshold. |
D12 |
30 months |
3.3.2. |
The door is inaccessible because knob hardware is used. |
D2 |
24 months |
3.3.3. |
The door is inaccessible because there is a slope of 7.7% within the door€™s required maneuvering clearance. |
D7 |
30 months |
4. |
Fire Engine House #38, 8463 N. Granville Rd. (Polling conducted here) |
|
|
4.1. |
Parking lot: The parking lot is inaccessible because the pavement is unmarked and no designated accessible parking space is provided. This lot requires 1 van accessible space. |
P1 |
30 months |
4.2. |
Exterior route from parking to polling entrance (rear bay door, open during polling): |
|
|
4.2.1. |
The walking surface is inaccessible because a grate has openings of more than 1 inch wide each. |
AR5 |
30 months |
4.2.2. |
The route where the rear bay door meets the concrete is inaccessible because there is a 1 inch change in level. |
AR1 |
30 months |
4.3. |
Unisex single-user toilet room (open to the public): |
|
|
4.3.1. |
The toilet room sign is mounted on the door and has no raised or Braille characters. |
TR11 |
24 months |
4.3.2. |
The door is inaccessible because knob hardware is used. |
D2 |
24 months |
4.3.3. |
No accessible mirror has been provided. |
TR5 |
24 months |
4.3.4. |
The lavatory is inaccessible because the hot water and drain pipes are not insulated or otherwise configured to protect against contact. |
LS2 |
24 months |
4.3.5. |
The toilet is inaccessible because its centerline is 19 inches from the side wall. |
TR7 |
30 months |
4.3.6. |
The toilet is inaccessible because the flush control is on the closed side. |
TR4 |
30 months |
5. |
Mill Road Library, 6431 N. 76th St. |
|
|
5.1. |
Parking lot: The designated accessible parking is inaccessible because the signs are mounted too low. |
P1 |
30 months |
5.2. |
Main exterior entrance: The door is inaccessible because there is a slope of 2.6% within the door€™s required maneuvering clearance, and the auto door opener is not working. |
D7, M1 |
30 months |
5.3. |
Women€™s single-user toilet room: |
|
|
5.3.1. |
The toilet room sign is mounted on the door and has no raised or Braille characters. |
TR11 |
30 months |
5.3.2. |
The door is inaccessible because it has an opening width of 29 inches. |
D14 |
30 months |
5.3.3. |
The door is inaccessible because knob hardware is used. |
D2 |
30 months |
5.3.4. |
The pull side of the door, which is accessed through a front approach, is inaccessible because it has only 4 inches of clear space on the latch side. |
D5 |
30 months |
5.3.5. |
The push side of the door, which is accessed through a front approach and which has both a closer and a latch, is inaccessible because it has only 4 inches of clear space on the latch side. |
D5 |
30 months |
5.3.6. |
No accessible mirror has been provided. |
TR5 |
30 months |
5.3.7. |
No accessible coat hook has been provided. |
TR3 |
30 months |
5.3.8. |
The lavatory is inaccessible because there is inadequate clear floor space in front of the lavatory, it has twist-type hardware, the bottom of the apron is 27˝ inches high and there is inadequate knee and toe clearance, and the hot water and drain pipes are not insulated or otherwise configured to protect against contact. |
LS1 |
30 months |
5.3.9. |
The baby changing station is inaccessible because the surface, when open, is higher than 34 inches high. |
DW1 |
30 months |
5.3.10. |
The toilet is inaccessible because the top of the seat is 16˝ inches high. |
TR9 |
30 months |
5.3.11. |
The toilet is inaccessible because there are no accessible grab bars provided. |
TR18 |
30 months |
5.4. |
Men€™s single-user toilet room: |
|
|
5.4.1. |
The toilet room sign is mounted on the door and has no raised or Braille characters. |
TR11 |
30 months |
5.4.2. |
The door is inaccessible because it has an opening width of 29 inches. |
D14 |
30 months |
5.4.3. |
The door is inaccessible because knob hardware is used. |
D2 |
30 months |
5.4.4. |
The pull side of the door, which is accessed through a front approach, is inaccessible because it has only 4 inches of clear space on the latch side. |
D5 |
30 months |
5.4.5. |
The push side of the door, which is accessed through a front approach and which has both a closer and a latch, is inaccessible because it has inadequate clear space on the latch side. |
D5 |
30 months |
5.4.6. |
No accessible mirror has been provided. |
TR5 |
30 months |
5.4.7. |
The toilet is inaccessible because the top of the seat is 15˝ inches high. |
TR9 |
30 months |
5.4.8. |
The toilet is inaccessible because the flush control is on the closed side. |
TR4 |
30 months |
5.4.9. |
The toilet paper dispenser is inaccessible because it is mounted 44 inches from the rear wall. |
TR6 |
30 months |
5.4.10. |
The toilet is inaccessible because there are no accessible grab bars provided. |
TR18 |
30 months |
5.5. |
Drinking fountain near toilet rooms: |
|
|
5.5.1. |
The drinking fountain is inaccessible because the flow of water is 5 inches from the front of the fountain. |
DF5 |
30 months |
5.5.2. |
The wall-mounted drinking fountain is inaccessible because it provides only 25 inches of clear knee height. |
DF4 |
30 months |
5.5.3. |
Although a designated accessible drinking fountain is provided, there is no drinking fountain provided for people who have difficulty bending or stooping. |
DF3 |
30 months |
6. |
Northwest Health Center, 6431 N. 76th St. |
|
|
6.1. |
Parking lot: |
|
|
6.1.1. |
The parking lot, with a total of 84 parking spaces, is inaccessible because only 2 designated accessible parking spaces are provided, the designated van-accessible parking space has a 61 inch access aisle, the designated accessible spaces and access aisles have slopes and cross-slopes exceeding 2%, and the signage provided is too low. This lot requires 1 van accessible space and 3 standard accessible spaces. |
P1 |
30 months |
6.2. |
Exterior ramp near rear entrance: |
|
|
6.2.1. |
The ramp is inaccessible because it does not have edge protection at the drop off sides. |
R3 |
30 months |
6.2.2. |
The ramp is inaccessible because one side lacks handrails, the diameter of the provided handrail is 2˝ inches, and the handrail lacks 12 inch extensions at the top and bottom of the ramp. |
R2 |
30 months |
6.3. |
Exterior entrance (rear): |
|
|
6.3.1. |
The designated accessible entrance is inaccessible because it is locked at all times. |
D8 |
30 months |
6.3.2. |
The double-leaf door is inaccessible because each leaf is only 29 inches wide. Opening the other leaf requires reaching latches at the top and bottom of that leaf. |
D13 |
30 months |
6.4. |
Interior elevator: |
|
|
6.4.1. |
The elevator is inaccessible because the hall call buttons are mounted with the centerline at 51 inches high. |
E3 |
30 months |
6.4.2. |
There are no hall lanterns provided. |
E10 |
30 months |
6.4.3. |
The elevator is inaccessible because the car control buttons do not have raised and Braille characters to the left of the buttons, the button for the main entry floor is not designated by a raised star, the buttons do not have visual indicators to register calls or to go out when a call is answered, and the highest car control button is mounted higher than 54 inches high. |
E4 |
30 months |
6.4.4. |
The elevator is inaccessible because the car position indicators do not emit an audible and visual signal as the car passes or stops at a floor. |
E5 |
30 months |
6.4.5. |
The elevator is inaccessible because the emergency system is not identified by raised symbols and lettering, and it requires tight grasping or pinching to access. |
E7 |
30 months |
6.5. |
Interior doorways throughout building: |
|
|
6.5.1. |
Interior doors throughout the building are inaccessible because knob hardware is used. |
D2 |
24 months |
6.5.2. |
The signage provided throughout the facility is inaccessible because it does not have raised and Braille characters. |
D15 |
24 months |
6.6. |
Women€™s toilet room with stalls - basement: |
|
|
6.6.1. |
The toilet room sign has no raised or Braille characters. |
TR11 |
24 months |
6.6.2. |
The pull side of the door, which is accessed through a front approach, is inaccessible because it has only 2 inches of clear space on the latch side. |
D5 |
30 months |
6.6.3. |
No accessible mirror has been provided. |
TR5 |
24 months |
6.6.4. |
The paper towel dispenser is inaccessible because it is mounted with the controls 56 inches high. |
CT4 |
24 months |
6.6.5. |
The lavatory is inaccessible because the hot water and drain pipes are not insulated or otherwise configured to protect against contact. |
LS2 |
24 months |
6.6.6. |
The lavatory is inaccessible because it has twist-type hardware. |
LS4 |
24 months |
6.6.7. |
The sanitary napkin dispenser is inaccessible because the controls require twisting of the wrist to operate. |
CT2 |
24 months |
6.6.8. |
There is no accessible toilet stall provided. |
TR2 |
30 months |
6.7. |
Men€™s toilet room with stalls - basement: |
|
|
6.7.1. |
The toilet room sign has no raised or Braille characters. |
TR11 |
24 months |
6.7.2. |
The entry doors are inaccessible because the vestibule is not sufficiently deep. |
D4 |
30 months |
6.7.3. |
The innermost vestibule door is inaccessible because it has an opening width of 31 inches. |
D14 |
30 months |
6.7.4. |
No accessible mirror has been provided. |
TR5 |
24 months |
6.7.5. |
The paper towel dispenser is inaccessible because it is mounted with the controls too high. |
CT4 |
24 months |
6.7.6. |
The soap dispenser is inaccessible because it is mounted with the controls too high. |
CT4 |
24 months |
6.7.7. |
The lavatory is inaccessible because the hot water and drain pipes are not insulated or otherwise configured to protect against contact. |
LS2 |
24 months |
6.7.8. |
The lavatory is inaccessible because it has twist-type hardware. |
LS4 |
24 months |
6.7.9. |
There is no accessible toilet stall provided. |
TR2 |
30 months |
6.8. |
Drinking fountain - basement: |
|
|
6.8.1. |
The drinking fountain is inaccessible because it has a spout that is more than 36 inches high. |
DF3 |
30 months |
6.8.2. |
The drinking fountain is inaccessible because it does not provide adequate clear knee depth. |
DF4 |
30 months |
6.8.3. |
The drinking fountain protrudes into the walkway and is not detectable to blind persons using a cane. |
AR7 |
24 months |
6.9. |
Women€™s toilet room with stalls near room 134: |
|
|
6.9.1. |
The toilet room sign has no raised or Braille characters. |
TR11 |
24 months |
6.9.2. |
No accessible mirror has been provided. |
TR5 |
24 months |
6.9.3. |
The toilet stall door swings into the required clear floor space at the lavatory. |
TR12 |
30 months |
6.9.4. |
The lavatory is inaccessible because the hot water and drain pipes are not insulated or otherwise configured to protect against contact. |
LS2 |
24 months |
6.9.5. |
The lavatory is inaccessible because it has twist-type hardware. |
LS4 |
24 months |
6.9.6. |
The paper towel dispenser is inaccessible because it is mounted beyond reach ranges behind the lavatory. |
CT3 |
24 months |
6.9.7. |
There is no accessible toilet stall provided. |
TR2 |
30 months |
6.10. |
Men€™s toilet room with stalls near room 127: |
|
|
6.10.1. |
The toilet room sign has no raised or Braille characters. |
TR11 |
24 months |
6.10.2. |
The pull side of the door, which is accessed through a front approach, is inaccessible because it has only 2 inches of clear space on the latch side. |
D5 |
30 months |
6.10.3. |
The toilet stall door swings into the required clear floor space at the urinal. |
TR12 |
30 months |
6.10.4. |
No accessible mirror has been provided. |
TR5 |
24 months |
6.10.5. |
The lavatory is inaccessible because the hot water and drain pipes are not insulated or otherwise configured to protect against contact. |
LS2 |
24 months |
6.10.6. |
The lavatory is inaccessible because it has twist-type hardware. |
LS4 |
24 months |
6.10.7. |
There is no accessible toilet stall provided. |
TR2 |
30 months |
6.11. |
Women€™s toilet room with stalls near room 127: |
|
|
6.11.1. |
The toilet room sign has no raised or Braille characters. |
TR11 |
24 months |
6.11.2. |
The pull side of the first door in a series, which is accessed through a front approach, is inaccessible because it has only 2 inches of clear space on the latch side. |
D5 |
30 months |
6.11.3. |
The entry doors are inaccessible because the vestibule is not sufficiently deep. |
D4 |
30 months |
6.11.4. |
The second (inside) vestibule door is inaccessible because it has an opening width of 30˝ inches. |
D14 |
30 months |
6.11.5. |
No accessible mirror has been provided. |
TR5 |
24 months |
6.11.6. |
The sanitary napkin dispenser protrudes into the walkway and is not detectable to blind persons using a cane. |
AR7 |
24 months |
6.11.7. |
The sanitary napkin dispenser is inaccessible because the controls require twisting of the wrist to operate. |
CT2 |
24 months |
6.11.8. |
The lavatory is inaccessible because the hot water and drain pipes are not insulated or otherwise configured to protect against contact. |
LS2 |
24 months |
6.11.9. |
The lavatory is inaccessible because it has twist-type hardware. |
LS4 |
24 months |
6.11.10. |
There is no accessible toilet stall provided. |
TR2 |
30 months |
6.12. |
Men€™s toilet room with stalls near room 134: |
|
|
6.12.1. |
The toilet room sign has no raised or Braille characters. |
TR11 |
24 months |
6.12.2. |
The pull side of the door, which is accessed through a front approach, is inaccessible because it has only 2 inches of clear space on the latch side. |
D5 |
30 months |
6.12.3. |
No accessible mirror has been provided. |
TR5 |
24 months |
6.12.4. |
The lavatory is inaccessible because the hot water and drain pipes are not insulated or otherwise configured to protect against contact. |
LS2 |
24 months |
6.12.5. |
The lavatory is inaccessible because it has twist-type hardware. |
LS4 |
24 months |
6.12.6. |
There is no accessible toilet stall provided. |
TR2 |
30 months |
6.13. |
Drinking fountain near room 134: The drinking fountain is inaccessible because it has a spout that is 38 inches high. |
DF3 |
30 months |
6.14. |
Exterior route - 2nd floor: The clear plastic cover for a manual fire alarm station in a corridor protrudes into the walkway and is not detectable to blind persons using a cane. |
AR7 |
30 months |
7. |
Parking Structure at 724 N. 2nd St. |
|
|
7.1. |
The parking lot, with a total of 495 parking spaces, is inaccessible because it only has 6 spaces designated as accessible. This lot requires 2 van accessible spaces and 7 standard accessible spaces. |
P1 |
24 months |
7.2. |
The designated accessible parking on the 2nd level is inaccessible because it has a cross-slope of up to 4.3% and its sign is mounted too low. |
P4, P3 |
30 months |
7.3. |
The designated accessible parking on the 3rd level is inaccessible because it has a cross-slope of up to 3.8% and its sign is mounted too low. |
P4, P3 |
30 months |
7.4. |
The designated accessible parking on the 4th level is inaccessible because it has a cross-slope of up to 7.3% and its sign is mounted too low. |
P4, P3 |
30 months |
7.5. |
The designated accessible parking on the 5th level is inaccessible because it has a cross-slope of up to 5% and its sign is mounted too low. |
P4, P3 |
30 months |
7.6. |
The designated accessible parking on the 6th level is inaccessible because its access aisle measures 56 inches across, it has a cross-slope of up to 3%, and its sign is mounted too low. |
P1 |
30 months |
7.7. |
The designated accessible parking on the 7th level is inaccessible because it has a cross-slope of up to 3.1% and its sign is mounted too low. |
P4, P3 |
30 months |
7.8. |
The elevator is inaccessible because the emergency system requires voice communication to operate. |
E7 |
30 months |
8. |
Parking Structure at MacArthur Square, 841 N. James Lovell St. |
|
|
8.1. |
The parking lot, with a total of 1445 parking spaces of which 26 are designated as being accessible, is inaccessible because none are designated as being van-accessible. This lot requires 5 van accessible spaces and 20 standard accessible spaces. |
P1 |
30 months |
8.2. |
The parking lot is inaccessible because several designated accessible parking spaces have access aisles with slopes and/or cross-slopes that exceed 2%. |
P4 |
30 months |
9. |
Parking Structure at N. 4th and Highland, 324 W. Highland St. |
|
|
9.1. |
The parking lot, with a total of 993 parking spaces, is inaccessible because it has only 19 spaces designated as accessible. This lot requires 4 van accessible spaces and 16 standard accessible spaces. |
P1 |
30 months |
9.2. |
The parking lot is inaccessible because all of the designated accessible parking signage are mounted too low. |
P3 |
24 months |
9.3. |
The designated accessible parking on the Roof Level is inaccessible because it is only 82 inches wide. |
P6 |
30 months |
9.4. |
The designated accessible parking on Level 5 is inaccessible because its access is only 55 inches wide. |
P6 |
30 months |
9.5. |
The designated accessible parking on Level 6 is inaccessible because its access is only 55 inches wide. |
P6 |
30 months |
10. |
Police - 2nd District Station, 245 W. Lincoln Av. |
|
|
10.1. |
Exterior route: The route between the ramp with handrails and the sidewalk is inaccessible because it has a slope of 5.7% and cross-slopes of 2.7% with no ramp features. |
AR1 |
30 months |
10.2. |
Unisex single-user toilet room in the reception / front area: |
|
|
10.2.1. |
The toilet is inaccessible because the side grab bar is mounted with its closer end 16 inches from the rear wall. |
TR17 |
24 months |
10.3. |
Reception counter: The counter is inaccessible because it is 42˝ inches high. |
C1 |
30 months |
11. |
Police - 4th District Station, 6929 W. Silver Spring Dr. |
|
|
11.1. |
Parking lot: The parking lot, with a total of 8 non-parallel parking spaces, is inaccessible because no van-accessible parking is provided and the sole designated accessible parking space lacks an access aisle. This lot requires 1 van accessible space. |
P5 |
30 months |
11.2. |
Curb ramp next to parking lot: The curb ramp is inaccessible because it has a slope of 10.6%. |
AR4 |
30 months |
11.3. |
Exterior route: |
|
|
11.3.1. |
The route between the curb ramp and the main entrance is inaccessible because it has a cross-slope of 2.8% at one point, a slope of 6.7% with no ramp features at another point, and a ľ inch change of level along the sidewalk. |
AR1 |
30 months |
11.4. |
Main entrance doorway: The door is inaccessible because there is a ľ inch high threshold. |
D12 |
30 months |
11.5. |
Counter at main entrance: The counter is inaccessible because it is 42 inches high. |
C1 |
30 months |
11.6. |
Single-user toilet room near entrance: |
|
|
11.6.1. |
The toilet room sign is mounted on the door and has no raised or Braille characters. |
TR11 |
24 months |
11.6.2. |
The entry door is inaccessible because it has an opening width of 29 inches. |
D14 |
30 months |
11.6.3. |
The pull side of the door, which is accessed through a front approach, is inaccessible because it has less than 60 inches of clear space depth in front of the door. |
D5 |
24 months |
11.6.4. |
No accessible mirror has been provided. |
TR5 |
24 months |
11.6.5. |
The sanitary napkin dispenser is inaccessible because the controls require twisting of the wrist to operate. |
CT2 |
24 months |
11.6.6. |
The lavatory is inaccessible because the hot water and drain pipes are not insulated or otherwise configured to protect against contact. |
LS2 |
24 months |
11.6.7. |
The lavatory is inaccessible because it has twist-type hardware. |
LS4 |
24 months |
11.6.8. |
The toilet room is inaccessible because there is insufficient turning space provided within the room. |
TR21 |
30 months |
11.6.9. |
The toilet stall door swings into the required clear floor space at the toilet. |
TR12 |
30 months |
11.6.10. |
The toilet is inaccessible because the flush control is on the closed side. |
TR4 |
30 months |
11.6.11. |
The toilet is inaccessible because there are no grab bars provided. |
TR18 |
24 months |
11.7. |
Drinking fountain between toilet rooms near entrance: |
|
|
11.7.1. |
The drinking fountain is inaccessible because the spout height is 43 inches high, the water flow height is neither at least 4 inches high nor within 3 inches from the front of the unit, the controls are not operable with one hand without tight grasping and/or twisting, the alcove is not wide enough to accommodate a wheelchair clear space for a forward approach, and knee space depth is only 11 inches. |
DF1 |
30 months |
11.7.2. |
Although a designated accessible drinking fountain is provided, there is no drinking fountain provided for people who have difficulty bending or stooping. |
DF3 |
30 months |
11.8. |
Holding cells: There is no accessible cell provided. |
PJ1 |
30 months |
12. |
Police - 5th District Station, 2920 N. 4th St. |
|
|
12.1. |
Front exterior main entrance: The switch to operate the powered door is inaccessible because the controls require 15 pounds of pressure to operate. |
CT2 |
24 months |
12.2. |
Drinking fountain near main entrance: Although a designated accessible drinking fountain is provided, there is no drinking fountain provided for people who have difficulty bending or stooping. |
DF3 |
30 months |
12.3. |
Unisex single-user toilet room near main entrance: |
|
|
12.3.1. |
The toilet room sign has no Braille characters. |
TR11 |
30 months |
12.3.2. |
The door is inaccessible because it requires 15 pounds of force to open. |
D3 |
24 months |
12.3.3. |
Although an audible alarm is provided in this facility, there is no visual alarm appliance in the toilet room. |
AL1 |
30 months |
12.3.4. |
No accessible mirror has been provided. |
TR5 |
24 months |
12.3.5. |
The toilet paper dispenser is inaccessible because it is mounted 42 inches from the rear wall. |
TR6 |
24 months |
12.4. |
Unisex single-user toilet room near sally port / holding area: The toilet room contains a number of inaccessible elements and is not accessible to people with disabilities. |
TR1 |
30 months |
12.5. |
Ramp at sally port: |
|
|
12.5.1. |
The ramp is inaccessible because it has a slope of up to 9.6%. |
R4 |
30 months |
12.5.2. |
The ramp is inaccessible because the level landing at the top of the ramp has a depth of only 37˝ inches. |
R5 |
30 months |
12.5.3. |
The ramp is inaccessible because handrails is provided on one side of the ramp only. |
R2 |
30 months |
12.6. |
Unisex single-user toilet room near booking area / cells: The toilet room contains a number of inaccessible elements and is not accessible to people with disabilities. |
TR1 |
30 months |
12.7. |
Interview room: The interview room contains a number of inaccessible elements and is not accessible to people with disabilities. |
PJ4 |
30 months |
12.8. |
Holding cells: There is no accessible cell provided. |
PJ1 |
30 months |
13. |
Police - 6th District Station, 3006 S. 27th St. |
|
|
13.1. |
Exterior routes and ramps: |
|
|
13.1.1. |
The ramps between the sidewalk and the main entrances are inaccessible because they have slopes of up to 15.6% and cross-slopes of up to 4.1%. |
R4 |
30 months |
13.1.2. |
The ramps between the sidewalk and the main entrances are inaccessible because they lack handrails on one side along some of the ramp segments. |
R2 |
30 months |
13.1.3. |
The ramps between the sidewalk and the main entrances are inaccessible because they lack edge protection. |
R3 |
30 months |
13.1.4. |
The route to the designated accessible entrance is inaccessible because there is a change in level ranging from 1 inch to 2 inches where the ramps meet the surface immediately in front of the accessible entrance. |
AR1 |
30 months |
13.2. |
Exterior entrances: The building does not have directional signage posted at inaccessible entrances and does not have the International Symbol of Accessibility posted at accessible entrances. |
D10 |
24 months |
13.3. |
Men€™s single-user toilet room in lobby / reception area: |
|
|
13.3.1. |
The toilet room sign is mounted on the door and has no raised or Braille characters. |
TR11 |
24 months |
13.3.2. |
The door is inaccessible because knob hardware is used. |
D2 |
24 months |
13.3.3. |
Although an audible alarm is provided in this facility, there is no visual alarm appliance in the toilet room. |
AL1 |
30 months |
13.3.4. |
No accessible mirror has been provided. |
TR5 |
24 months |
13.3.5. |
The lavatory is inaccessible because the hot water and drain pipes are not insulated or otherwise configured to protect against contact. |
LS2 |
24 months |
13.3.6. |
The toilet is inaccessible because its centerline is 27 inches from the side wall. |
TR7 |
30 months |
13.3.7. |
The toilet is inaccessible because the side grab bar is mounted with its farther end 52 inches from the rear wall. |
TR17 |
24 months |
13.4. |
Women€™s single-user toilet room in lobby / reception area: |
|
|
13.4.1. |
The toilet room sign is mounted on the door and has no raised or Braille characters. |
TR11 |
24 months |
13.4.2. |
The door is inaccessible because knob hardware is used. |
D2 |
24 months |
13.4.3. |
Although an audible alarm is provided in this facility, there is no visual alarm appliance in the toilet room. |
AL1 |
30 months |
13.4.4. |
No accessible mirror has been provided. |
TR5 |
24 months |
13.4.5. |
The lavatory is inaccessible because the hot water and drain pipes are not insulated or otherwise configured to protect against contact. |
LS2 |
24 months |
13.4.6. |
The toilet is inaccessible because its centerline is 27 inches from the side wall. |
TR7 |
30 months |
13.4.7. |
The toilet is inaccessible because the side grab bar is mounted with its farther end 52 inches from the rear wall. |
TR17 |
24 months |
13.5. |
Drinking fountains near public toilet rooms: |
|
|
13.5.1. |
The drinking fountain protrudes into the walkway and is not detectable to blind persons using a cane. |
AR7 |
24 months |
13.5.2. |
Although a designated accessible drinking fountain is provided, there is no drinking fountain provided for people who have difficulty bending or stooping. |
DF3 |
30 months |
14. |
Police - 7th District Station, 3626 W. Fond Du Lac Av. |
|
|
14.1. |
Main entrance: |
|
|
14.1.1. |
The door is inaccessible because there is a slope of 4.1% within the door€™s required maneuvering clearance. |
D7 |
30 months |
14.1.2. |
The interior vestibule entrance door is inaccessible because it requires 11 pounds of force to open. |
D3 |
24 months |
14.2. |
Route from sally port to booking area: The route is inaccessible because there is a slope of 7.8% at one point with no ramp features. |
AR1 |
30 months |
14.3. |
Front counter / customer service area: The counter is inaccessible because it is 42 inches high. |
C1 |
30 months |
14.4. |
Women€™s single-user toilet room - near main entrance: |
|
|
14.4.1. |
The toilet room sign has no raised or Braille characters. |
TR11 |
24 months |
14.4.2. |
The door is inaccessible because it has an opening width of 29 inches. |
D14 |
30 months |
14.4.3. |
The door is inaccessible because it requires 11 pounds of force to open. |
D3 |
24 months |
14.4.4. |
The door is inaccessible because knob hardware is used. |
D2 |
24 months |
14.4.5. |
The toilet room door swings into the required clear floor space at the lavatory. |
TR12 |
30 months |
14.4.6. |
Although an audible alarm is provided in this facility, there is no visual alarm appliance in the toilet room. |
AL1 |
30 months |
14.4.7. |
The lavatory is inaccessible because the hot water and drain pipes are not insulated or otherwise configured to protect against contact. |
LS2 |
30 months |
14.4.8. |
The toilet is inaccessible because the top of the seat is 15 inches high. |
TR9 |
30 months |
14.4.9. |
The toilet is inaccessible because the flush control is on the closed side. |
TR4 |
30 months |
14.4.10. |
The toilet is inaccessible because the side grab bar is 30 inches long and it is mounted with its farther end 36 inches from the rear wall. |
TR17 |
24 months |
14.4.11. |
The toilet is inaccessible because the rear grab bar is 30 inches long. |
TR14 |
24 months |
14.5. |
Men€™s toilet room with stalls - near main entrance: |
|
|
14.5.1. |
The toilet room sign has no raised or Braille characters. |
TR11 |
24 months |
14.5.2. |
The pull side of the door, which is accessed through a front approach, is inaccessible because its clear space is obstructed by a wall-mounted box next to the latch side jamb. |
D5 |
30 months |
14.5.3. |
The door is inaccessible because it has an opening width of 29 inches. |
D14 |
30 months |
14.5.4. |
The door is inaccessible because it requires 12 pounds of force to open. |
D3 |
24 months |
14.5.5. |
The door is inaccessible because knob hardware is used. |
D2 |
24 months |
14.5.6. |
The toilet stall door swings into the required clear floor space at the urinal. |
TR12 |
30 months |
14.5.7. |
Although an audible alarm is provided in this facility, there is no visual alarm appliance in the toilet room. |
AL1 |
30 months |
14.5.8. |
No accessible mirror has been provided. |
TR5 |
24 months |
14.5.9. |
The lavatory is inaccessible because the hot water and drain pipes are not insulated or otherwise configured to protect against contact. |
LS2 |
24 months |
14.5.10. |
The designated accessible toilet is inaccessible because the top of the seat is 15 inches high. |
TR9 |
30 months |
14.5.11. |
The designated accessible toilet is inaccessible because the flush control is on the closed side. |
TR4 |
30 months |
14.5.12. |
No accessible coat hook has been provided. |
TR3 |
24 months |
14.5.13. |
The designated accessible toilet is inaccessible because the side grab bar is 30 inches long and it is mounted with the farther end 42 inches from the rear wall. |
TR17 |
24 months |
14.5.14. |
The designated accessible toilet is inaccessible because the rear grab bar is 30 inches long. |
TR14 |
24 months |
14.6. |
Interview room: The interview room contains a number of inaccessible elements and is not accessible to people with disabilities. |
PJ4 |
30 months |
14.7. |
Holding cells: There is no accessible cell provided. |
PJ1 |
30 months |
15. |
Southside Health Center, 1639 S. 23rd St. |
|
|
15.1. |
Parking lot: The parking lot, with a total of 110 parking spaces of which 5 are designated as being accessible, is inaccessible because none are designated as being van-accessible. This lot requires 1 van accessible space and 4 standard accessible spaces. |
P1 |
24 months |
15.2. |
Elevator (lobby): |
|
|
15.2.1. |
The elevator is inaccessible because the hall call buttons are mounted with their centerline 52 inches high. |
E3 |
24 months |
15.2.2. |
The elevator is inaccessible because the hall lanterns are not visible from the hall call buttons area. |
E10 |
30 months |
15.2.3. |
The elevator is inaccessible because there is no hoistway signage provided. |
E11 |
24 months |
15.2.4. |
The elevator is inaccessible because the car control buttons do not have raised and Braille characters to the left of the buttons, the button for the main entry floor is not designated by a raised star, and the highest button is 56 inches high. |
E4 |
24 months |
15.2.5. |
The elevator is inaccessible because the car position indicators do not emit an audible and visual signal as the car passes or stops at a floor. |
E5 |
30 months |
15.2.6. |
The elevator is inaccessible because the emergency system requires voice communication to operate, and it is not identified by raised symbol or lettering. |
E7 |
30 months |
15.3. |
Unisex single-user toilet room - waiting room 2, south: |
|
|
15.3.1. |
The toilet room sign has no raised or Braille characters, and its clear floor space is obstructed by a chair. |
TR11 |
24 months |
15.3.2. |
The toilet room door swings into the required clear floor space at the lavatory. |
TR12 |
30 months |
15.3.3. |
No accessible mirror has been provided. |
TR5 |
24 months |
15.3.4. |
The lavatory is inaccessible because the hot water and drain pipes are not insulated or otherwise configured to protect against contact. |
LS2 |
24 months |
15.3.5. |
The toilet is inaccessible because the flush control is on the closed side. |
TR4 |
30 months |
15.3.6. |
The toilet is inaccessible because the side grab bar is mounted with its farther end 50 inches from the rear wall. |
TR17 |
24 months |
15.3.7. |
The toilet is inaccessible because the rear grab bar is 33 inches long and mounted with its closer end 9 inches from the side wall. |
TR14 |
24 months |
15.4. |
Unisex single-user toilet room - waiting room 2, north: |
|
|
15.4.1. |
The toilet room sign has no raised or Braille characters. |
TR11 |
24 months |
15.4.2. |
No accessible mirror has been provided. |
TR5 |
24 months |
15.4.3. |
The lavatory is inaccessible because the hot water and drain pipes are not insulated or otherwise configured to protect against contact. |
LS2 |
24 months |
15.4.4. |
The toilet is inaccessible because the flush control is on the closed side. |
TR4 |
30 months |
15.4.5. |
The toilet paper dispenser is inaccessible because it is mounted 38 inches from the rear wall. |
TR6 |
24 months |
15.4.6. |
The toilet is inaccessible because the rear grab bar is mounted with its farthest end 40˝ inches from the side wall. |
TR14 |
24 months |
15.5. |
Interior route / doorway: The hallway doorway leading to the south wing is inaccessible because it has an opening width of 30 inches. |
D14 |
30 months |
15.6. |
Unisex single-user toilet room - waiting room 1, east: There is no signage directing people with disabilities to the accessible toilet rooms. |
TR10 |
24 months |
15.7. |
Unisex single-user toilet room - waiting room 1, west: |
|
|
15.7.1. |
The toilet room sign has no raised or Braille characters, and is not mounted at the required height. |
TR11 |
24 months |
15.7.2. |
No accessible mirror has been provided. |
TR5 |
24 months |
15.7.3. |
The baby changing station is inaccessible because it is mounted with the handle 59 inches high, and the surface, when open, is 41 inches high. |
DW1 |
24 months |
15.7.4. |
The toilet is inaccessible because the side grab bar is mounted with its farther end 50 inches from the rear wall. |
TR17 |
24 months |
15.7.5. |
The toilet is inaccessible because the flush control is on the closed side. |
TR4 |
30 months |
16. |
Port of Milwaukee, 2323 S. Lincoln Memorial Dr. |
|
|
16.1. |
Parking lot: |
|
|
16.1.1. |
The parking lot, with a total of 31 parking spaces, is inaccessible because it only has 1 space designated as accessible. This lot requires 1 van accessible space and 1 standard accessible space. |
P1 |
30 months |
16.1.2. |
The designated accessible parking is inaccessible because the sign is mounted too low. |
P3 |
24 months |
16.1.3. |
The built-up curb ramp impermissibly extends into the required parking space€™s access aisle. |
AR4, P2 |
30 months |
16.2. |
Exterior ramp to front entrance: |
|
|
16.2.1. |
The ramp is inaccessible because the ends of the handrails are not rounded or returned, there are no handrail extensions at the top nor bottom of the ramp, and the handrails are 33 inches from the floor. |
R2 |
24 months |
16.2.2. |
First floor office doors: Numerous office doors throughout the first floor are inaccessible because knob hardware is used. |
D2 |
24 months |
16.3. |
Women€™s toilet room with stalls / locker room - 1st floor next to kitchen: |
|
|
16.3.1. |
The locker room door is inaccessible because it requires 7 pounds of force to open. |
D3 |
12 months |
16.3.2. |
Although an audible alarm is provided in this facility, there is no visual alarm appliance in the toilet room. |
AL1 |
30 months |
16.3.3. |
The stall door swings into the required clear floor space at the lavatory. |
TR12 |
30 months |
16.3.4. |
The designated accessible stall is incorrectly configured as an ambulatory stall, and there is no standard accessible stall provided. |
TR2 |
30 months |
16.3.5. |
There is no accessible shower provided. |
B2 |
30 months |
16.3.6. |
The bench is inaccessible because it is only 9 inches wide, and it is not attached at a wall or provides a back support. |
LR2 |
30 months |
16.3.7. |
There is no accessible locker provided. |
LR3 |
30 months |
16.4. |
Men€™s toilet room with stalls / locker room - 1st floor next to kitchen: |
|
|
16.4.1. |
The locker room door is inaccessible because it requires 7 pounds of force to open. |
D3 |
12 months |
16.4.2. |
Although an audible alarm is provided in this facility, there is no visual alarm appliance in the toilet room. |
AL1 |
30 months |
16.4.3. |
The hair dryer is inaccessible because it is mounted with the controls 73 inches high. |
CT4 |
12 months |
16.4.4. |
The urinal is inaccessible because the flush control height is 52 inches high. |
TR8 |
30 months |
16.4.5. |
The designated accessible stall is incorrectly configured as an ambulatory stall, and there is no standard accessible stall provided. |
TR2 |
30 months |
16.4.6. |
There is no accessible shower provided. |
B2 |
30 months |
16.4.7. |
The bench is inaccessible because it is only 9˝ inches wide, and it is not attached at a wall or provides a back support. |
LR2 |
30 months |
16.4.8. |
There is no accessible locker provided. |
LR3 |
30 months |
16.5. |
Women€™s toilet room with stalls 2nd floor: |
|
|
16.5.1. |
The door is inaccessible because it requires 7 pounds of force to open. |
D3 |
12 months |
16.5.2. |
The sanitary napkin dispenser protrudes into the walkway and is not detectable to blind persons using a cane. |
AR7 |
12 months |
16.5.3. |
The lavatory is inaccessible because the hot water and drain pipes are not insulated or otherwise configured to protect against contact. |
LS2 |
24 months |
16.5.4. |
No accessible coat hook has been provided. |
TR3 |
24 months |
16.5.5. |
The designated accessible stall is incorrectly configured as an ambulatory stall, and there is no standard accessible stall provided. |
TR2 |
30 months |
16.6. |
Men€™s toilet room with stalls 2nd floor: |
|
|
16.6.1. |
The door is inaccessible because it requires 7 pounds of force to open. |
D3 |
12 months |
16.6.2. |
The lavatory is inaccessible because the hot water and drain pipes are not insulated or otherwise configured to protect against contact. |
LS2 |
24 months |
16.6.3. |
The urinal is inaccessible because the rim is 24 inches high and the flush control height is 53˝ inches high. |
TR8 |
30 months |
16.6.4. |
No accessible coat hook has been provided. |
TR3 |
24 months |
16.6.5. |
The designated accessible stall is incorrectly configured as an ambulatory stall, and there is no standard accessible stall provided. |
TR2 |
30 months |
17. |
Tippecanoe Library, 3912 S. Howell Av. |
|
|
17.1. |
Parking lot: The parking lot, with a total of 47 parking spaces of which 2 are designated as being accessible, is inaccessible because none are designated as being van-accessible and one of the designated accessible parking spaces lacks vertical signage. This lot requires 1 van accessible space and 1 standard accessible space. |
P1 |
24 months |
17.2. |
Exterior main entrance: The door is inaccessible because there is a slope of 4.2% within the door€™s required maneuvering clearance. |
D7 |
24 months |
17.3. |
Drinking fountains near toilet rooms: |
|
|
17.3.1. |
The drinking fountains are inaccessible because the flow of water is more than 5 inches away from the front of the fountains. |
DF5 |
24 months |
17.3.2. |
The drinking fountains are inaccessible because they provide less than 17 inches of clear knee depth. |
DF4 |
24 months |
17.3.3. |
Although a designated accessible drinking fountain is provided, there is no drinking fountain provided for people who have difficulty bending or stooping. |
DF3 |
24 months |
17.4. |
Women€™s single-user toilet room near the check-out counter: |
|
|
17.4.1. |
The toilet room sign has no raised or Braille characters. |
TR11 |
24 months |
17.4.2. |
The door is inaccessible because it requires 14 pounds of force to open. |
D3 |
24 months |
17.4.3. |
The door is inaccessible because knob hardware is used. |
D2 |
24 months |
17.4.4. |
The pull side of the door, which is accessed through a front approach, is inaccessible because it has inadequate clear space on the latch side. |
D5 |
24 months |
17.4.5. |
The toilet room is inaccessible because there is insufficient turning space provided within the room. |
TR21 |
24 months |
17.4.6. |
The lavatory is inaccessible because the hot water and drain pipes are not insulated or otherwise configured to protect against contact. |
LS2 |
24 months |
17.4.7. |
The lavatory is inaccessible because it has twist-type hardware. |
LS4 |
24 months |
17.4.8. |
The toilet is inaccessible because there is no rear grab bar provided. |
TR13 |
24 months |
17.5. |
Men€™s single-user toilet room near the check-out counter: |
|
|
17.5.1. |
The toilet room sign has no raised or Braille characters. |
TR11 |
24 months |
17.5.2. |
The door is inaccessible because it requires 14 pounds of force to open. |
D3 |
24 months |
17.5.3. |
The door is inaccessible because knob hardware is used. |
D2 |
24 months |
17.5.4. |
The lavatory is inaccessible because the hot water and drain pipes are not insulated or otherwise configured to protect against contact. |
LS2 |
24 months |
17.5.5. |
The lavatory is inaccessible because it has twist-type hardware. |
LS4 |
24 months |
17.5.6. |
The urinal is inaccessible because the flush control is 80 inches high. |
TR8 |
24 months |
17.5.7. |
The toilet is inaccessible because the flush control is on the closed side. |
TR4 |
24 months |
17.5.8. |
The toilet is inaccessible because the top of the seat is 16 inches high. |
TR9 |
24 months |
17.5.9. |
The toilet is inaccessible because no side grab bar is provided, and the two €śgrab handles€ť interfere with the rear grab bar. |
TR18 |
24 months |
17.5.10. |
The toilet is inaccessible because the rear grab bar is 24 inches long and mounted 3 inches from the side wall. |
TR14 |
24 months
|