No. |
Building |
General Location |
Specific Location |
DOJ Report Item |
Photo |
1991 Standards
Section |
2010 Standards
requirement where different from 1991 |
2010 Standards Section |
Date Completed |
Notes |
20 |
Trefethen
Aquatic Center |
Exterior |
Pool
Deck |
No
shower grab bars are provided. An accessible shower with grab bars along the
control wall and side wall is required. |
TAC
5 |
4.1.3(11),
4.23.8, 4.21.4, 4.26 and Fig. 37(b) |
|
|
|
|
21 |
Trefethen
Aquatic Center |
Exterior |
Pool
Deck |
A
shower spray unit is not provided. A shower spray unit with a hose at least
60 inches long that can be used as a fixed shower head and as a hand held
shower is required |
TAC
6 |
4.1.3(11),
4.23.8 and 4.21.6 |
A
shower spray unit with a hose 59 inches long minimum that can be used both as
a fixed-position shower head an as a handheld shower shall be provided. The
shower spray unit shall have an on/off control with a non-positive shut-off. |
213.3.6
and 608.6 |
|
|
22 |
Trefethen
Aquatic Center |
Pool
Building |
Men's
and Women's Locker Room |
The
force required to open the vestibule door is 15 lbf. The maximum allowable
force for opening an interior door is 5 lbf. |
none |
4.1.3(7)(b)
and 4.13.11(2)(b) |
|
|
|
|
23 |
Trefethen
Aquatic Center |
Pool
Building |
Men's
and Women's Locker Room |
The
typical towel hook is 69 inches above the finish floor. A hook no higher than
54 inches above the finish floor for a side reach is required. (Men's Locker
Room) |
TAC
6 |
4.1.3(12)(a),
4.25.3, 4.2.6 and Fig. 6 |
A
hook no higher than 48 inches above the finish floor for an unobstructed
reach is required. (Men's Locker Room) |
222.2,
803.5 and 308 |
|
|
27 |
Trefethen
Aquatic Center |
Pool
Building |
Men's
and Women's Locker Room |
The
paper towel dispenser control is located 58 inches above the finish floor. A
paper towel dispenser with a control that is located no higher than 54 inches
above the finish floor for a side reach is required. |
TAC
9 and TAC10 |
4.1.3(11),
4.23.7, 4.27.3, 4.2.6 and Fig. 6 |
A
dispenser with a control no higher than 48 inches above the finish floor for
an unobstructed reach is required. |
205.1,
309.3 and 308 |
|
|
31 |
Trefethen
Aquatic Center |
Pool
Building |
Men's
and Women's Locker Room Shower Area |
The
space between the control wall and the shower seat is 3¼ inches. The space
between the wall and shower seat shall be no more than 1½ inches. |
TAC
13 and TAC 14 |
4.1.3(11),
4.23.4, 4.17.6, 4.26.2 and Fig. 39(e) |
|
|
|
|
32 |
Trefethen
Aquatic Center |
Pool
Building |
Men's
and Women's Locker Room Shower Area |
The
towel hooks are more than 54 inches above the finish floor. A hook no higher
than 54 inches above the finish floor for a side reach is required. (Women's
Locker Room) |
TAC
15 and TAC 16 |
4.1.3(12)(a),
4.25.3, 4.2.6 and Fig. 6 |
A
hook no higher than 48 inches above the finish floor for an unobstructed
reach is required. (Women Locker Room) |
222.2,
803.5 and 308 |
|
|
33 |
Trefethen
Aquatic Center |
Pool
Building |
Men's
and Women's Locker Room Shower Area |
A
12-inch deep bench is provided. A 24-inch by 48-inch bench fixed to the wall
along the longer dimension is required. (Women's Locker Room) |
TAC
16 |
4.1.3(21)
and 4.35.4 |
Benches
shall have seats that are 42 inches long minimum and 20 inches deep minimum
to 24 inches deep maximum. The bench shall provide back support or shall be
affixed to a wall. |
222.1,
803.4 and 903 |
|
|
37 |
Natural
Science Building |
Addition
- First Floor |
Physics
Laboratory - Room 105 |
The
utility hooks are 77 inches above the finish floor. A hook no higher than 54
inches above the finish floor for a side reach is required. |
NSB2 |
4.1.5,
4.1.3(12)(a), 4.25.3, 4.2.6 and Fig. 6 |
A
hook no higher than 48 inches above the finish floor for an unobstructed
reach is required. |
225.2,
811.3 and 308 |
|
|
43 |
Natural
Science Building |
Addition
- First Floor |
Chemistry
Research Laboratory - Room 106 |
The
utility hooks are 71 inches above the finish floor. A hook no higher than 54
inches above the finish floor for a side reach is required. |
NSB5 |
4.1.5,
4.1.3(12)(a), 4.25.3, 4.2.6 and Fig. 6 |
A
hook no higher than 48 inches above the finish floor for an unobstructed
reach is required. |
225.2,
811.3 and 308 |
|
|
44 |
Natural
Science Building |
Addition
- First Floor |
Chemistry
Research Laboratory - Room 106 |
The
lowest peg on the drying rack is located 52 inches above the finish floor. A
peg that is located no higher than 46 inches above the finish floor for a
side reach over an obstruction is required. |
NSB6 |
4.1.5,
4.1.3(12)(a), 4.25.3, 4.2.6 and Fig. 6 |
|
|
|
|
45 |
Natural
Science Building |
Addition
- First Floor |
Chemistry
Research Laboratory - Room 106 |
The
paper towel dispenser control is located 59 inches above the finish floor. A
paper towel dispenser with a control that is located no higher than 46 inches
above the finish floor for a side reach over an obstruction is required. |
NSB6 |
4.1.5,
4.1.3(13), 4.27.3, 4.2.6 and Fig. 6 |
A
dispenser with a control no higher than 48 inches above the finish floor for
an unobstructed reach is required. |
205.1,
309.3 and 308 |
|
|
50 |
Natural
Science Building |
Addition
- First Floor |
Advanced
Chemistry Laboratory - Room 101 |
The
paper towel dispenser control is located 60 inches above the finish floor. A
paper towel dispenser with a control that is located no higher than 54 inches
above the finish floor for a side reach is required. |
NSB9 |
4.1.5,
4.1.3(13), 4.27.3, 4.2.6 and Fig. 6 |
A
dispenser with a control no higher than 48 inches above the finish floor for
an unobstructed reach is required. |
205.1,
309.3 and 308 |
|
|
51 |
Natural
Science Building |
Addition
- First Floor |
Advanced
Chemistry Laboratory - Room 101 |
A
29-inch deep reach is provided to the typical lab station electrical outlets.
An electrical outlet with a 24-inch maximum side reach is required at an
accessible lab station. |
NSB10 |
4.1.5,
4.1.3(18), 4.2.6 and Fig. 6(c) |
|
|
|
|
55 |
Natural
Science Building |
Addition
- First Floor |
Corridor |
An
exit sign is not mounted on the wall adjacent to the latch side of the door.
A sign mounted on the wall adjacent to the latch side of the door identifying
the exit in raised characters and Braille is required. |
NSB12 |
4.1.5,
4.1.3(16)(a), 4.30.1, 4.30.4, 4.30.5 and 4.30.6 |
Tactile
characters on signs shall be located between 48 inches minimum and 60 inches
maximum above the finish floor, measured to the baseline of the tactile
character. |
216.2,
703.1-5 |
|
|
58 |
Natural
Science Building |
Addition
- Second Floor |
Chemistry
Laboratory - Room 206 |
The
utility hooks are 72 inches above the finish floor. A hook no higher than 54
inches above the finish floor for a side reach is required. |
NSB14 |
4.1.5,
4.1.3(12)(a), 4.25.3, 4.2.6 and Fig. 6 |
A
hook no higher than 48 inches above the finish floor for an unobstructed
reach is required. |
225.2,
811.3 and 308 |
|
|
59 |
Natural
Science Building |
Addition
- Second Floor |
Chemistry
Laboratory - Room 206 |
The
paper towel dispenser control is located 52 inches above the finish floor. A
paper towel dispenser with a control that is located no higher than 46 inches
above the finish floor for a side reach over an obstruction is required. |
NSB15 |
4.1.5,
4.1.3(13), 4.27.3, 4.2.6 and Fig. 6(c) |
A
dispenser with a control no higher than 48 inches above the finish floor for
an unobstructed reach is required. |
205.1,
309.3 and 308 |
|
|
64 |
Natural
Science Building |
Addition
- Second Floor |
Organic
Chemistry Laboratory - Room 201 |
A
29-inch deep reach is provided to the typical lab station electrical outlets.
An electrical outlet with a 24-inch maximum side reach is required at an
accessible lab station. |
NSB16 |
4.1.5,
4.1.3(18), 4.2.6 and Fig. 6(c) |
|
|
|
|
68 |
Natural
Science Building |
Addition
- First and Second Floors |
Men's
Toilet Room |
The
force required to open the toilet room door is 15 lbf. The maximum allowable
force for opening an interior door is 5 lbf. |
none |
4.1.5,
4.1.3(7)(b) and 4.13.11(2)(b) |
|
|
|
|
70 |
Natural
Science Building |
Addition
- First and Second Floors |
Men's
Toilet Room Designated Accessible Toilet Stall |
The
rear grab bar is mounted 38 inches above the finish floor to the centerline
of the bar. The rear grab bar shall be mounted 33 to 36 inches above the
finish floor to the centerline. |
NSB18 |
4.1.5,
4.1.3(11), 4.22.4, 4.17.6 and Fig. 30(c). |
Grab
bars shall be installed 33 inches minimum and 36 inches maximum above the
finish floor to the top of the gripping surface. |
213.3.1,
604.8.1.5 and 609.4 |
|
|
73 |
Natural
Science Building |
Addition
- First and Second Floors |
Women's
Toilet Room |
The
force required to open the toilet room door is 12 lbf. The maximum allowable
force for opening an interior door is 5 lbf. |
none |
4.1.5,
4.1.3(7)(b) and 4.13.11(2)(b) |
|
|
|
|
74 |
Natural
Science Building |
Addition
- First and Second Floors |
Women's
Toilet Room Designated Accessible Toilet Stall |
The
toilet flush control is mounted on top of the toilet tank. Flush controls are
required to be mounted on the wide side of the toilet area. |
NSB20 |
4.1.5,
4.1.3(11), 4.22.4, 4.17.2 and 4.16.5 |
|
|
|
|
75 |
Natural
Science Building |
Addition
- First and Second Floors |
Women's
Toilet Room Designated Accessible Toilet Stall |
The
rear grab bar is mounted 38 inches above the finish floor to the centerline
of the bar. The rear grab bar shall be mounted 33 to 36 inches above the
finish floor to the centerline. |
NSB21 |
4.1.5,
4.1.3(11), 4.22.4, 4.17.6 and Fig. 30(c) |
Grab
bars shall be installed 33 inches minimum and 36 inches maximum above the
finish floor to the top of the gripping surface. |
213.3.1,
604.8.1.5 and 609.4 |
|
|
84 |
Natural
Science Building |
Existing
Building - First and Second Floors |
Zoology
Laboratory - Room 171 (typical laboratory) |
The
emergency shower handle is 67 inches above the finish floor. An emergency
shower handle that is mounted no higher than 54 inches above the finish floor
for a side reach is required. |
NSB27 |
4.1.3(13),
4.27.3, 4.2.6 and Fig. 6 |
An
emergency shower with a control no higher than 48 inches above the finish
floor for an unobstructed reach is required. |
205.1,
309.3 and 308 |
|
|
86 |
Natural
Science Building |
Existing
Building - First and Second Floors |
Zoology
Laboratory - Room 171 (typical laboratory) |
A
26-inch deep reach is provided to the typical lab station outlets and
controls. An electrical outlet with a 24-inch maximum side reach is required
at an accessible lab station. |
NSB28 |
4.1.3(18),
4.2.6 and Fig. 6(c) |
|
|
|
|
90 |
Natural
Science Building |
Existing
Building - First and Second Floors |
Women's
Toilet Room |
A
toilet room sign is not mounted on the wall adjacent to the latch side of the
door. A sign mounted on the wall adjacent to the latch side of the door
identifying the toilet room in raised characters and Braille is required. |
NSB33 |
4.1.3(16)(a),
4.30.1, 4.30.4, 4.30.5 and 4.30.6 |
Tactile
characters on signs shall be located between 48 inches minimum and 60 inches
maximum above the finish floor, measured to the baseline of the tactile
character. |
216.2,
703.1-5 |
|
|
91 |
Natural
Science Building |
Existing
Building - First and Second Floors |
Women's
Toilet Room |
The
women's toilet room is not accessible, and a directional sign to the
designated accessible women's toilet room is not provided. A sign indicating
the location of the designated accessible women's toilet room is required. |
NSB33 |
4.1.2(7)(d)
and 4.1.6(3)(e)(iii) |
|
|
|
|
92 |
Alderwood
Hall |
Entrance |
Side
Entrance |
The
sign indicating the route to the designated accessible entrance is obscured
by foliage. A directional sign indicating the route to the designated
accessible entrance is required. |
AH1 |
Title
III Regulations 36.211 and 4.1.2(7)(c) and 4.1.6(1)(h) |
|
|
|
|
93 |
Alderwood
Hall |
Entrance |
Designated
Accessible Entrance Ramp |
A
level ramp landing is not provided at the bottom of the ramp run. Ramps are
required to have level landings at the top and bottom of each ramp run. |
AH2
and AH3 |
4.1.2(1),
4.3.7 and 4.8.4 |
|
|
|
|
94 |
Alderwood
Hall |
Entrance |
Designated
Accessible Entrance Ramp |
The
intermediate ramp landing is 53½ inches long. The minimum landing length
shall be 60 inches clear. |
AH4 |
4.1.2(1),
4.3.7 and 4.8.4(2) |
|
|
|
|
95 |
Alderwood
Hall |
Entrance |
Designated
Accessible Entrance Ramp |
The
slope of the upper ramp segment is approximately 1:10. The maximum allowable
ramp slope is 1:12. |
AH2 |
4.1.2(1),
4.3.7 and 4.8.2 |
|
|
|
|
96 |
Alderwood
Hall |
Entrance |
Designated
Accessible Entrance Ramp |
The
top ramp landing is 49 inches long. The minimum landing length shall be 60
inches clear. |
AH2 |
4.1.2(1),
4.3.7 and 4.8.4(2) |
|
|
|
|
97 |
Alderwood
Hall |
Entrance |
Designated
Accessible Entrance Ramp |
No
handrail is provided on the wall side of the ramp. Handrails are required on
both sides of the ramp. |
AH2
through AH5 |
4.1.2(1),
4.3.7 and 4.8.6 |
|
|
|
|
98 |
Alderwood
Hall |
Entrance |
Designated
Accessible Entrance Ramp |
The
top of the ramp handrail is 32 inches above the ramp surface. The top of
handrail gripping surfaces shall be between 34 and 38 inches above the ramp
surface. |
AH2 |
4.1.2(1),
4.3.7 and 4.8.5(5) |
|
|
|
|
99 |
Alderwood
Hall |
Entrance |
Designated
Accessible Entrance Ramp |
The
handrail does not extend beyond the bottom of the ramp segment. The handrail
shall extend at least 12 inches beyond the bottom of the ramp segment, and
the extension shall be parallel with the ground surface. |
AH2
and AH3 |
4.1.2(1),
4.3.7, 4.8.5(2) and Fig. 17 |
|
|
|
|
100 |
Alderwood
Hall |
First
Floor |
Unisex
Toilet Room |
A
toilet room sign is not mounted on the wall adjacent to the latch side of the
door. A sign mounted on the wall adjacent to the latch side of the door
identifying the toilet room in raised characters and Braille is required. |
AH5
and AH6 |
4.1.3(16)(a),
4.30.1, 4.30.4, 4.30.5 and 4.30.6 |
Tactile
characters on signs shall be located between 48 inches minimum and 60 inches
maximum above the finish floor, measured to the baseline of the tactile
character. |
216.2,
703.1-5 |
|
|
101 |
Alderwood
Hall |
First
Floor |
Unisex
Toilet Room |
The
60-inch diameter turning space is obstructed by furniture. An unobstructed
60‑inch diameter or t-shaped turning space is required. |
AH7
and AH8 |
4.1.3(11),
4.22.3, 4.2.3 and Fig. 3 |
|
|
|
|
102 |
Alderwood
Hall |
First
Floor |
Unisex
Toilet Room |
The
toilet clear floor space is obstructed by furniture. Clear floor space that
is a minimum of 48 inches wide and 56 inches deep is required. |
AH9
and AH10 |
4.1.3(11),
4.22.4, 4.16.2 and Fig. 28 |
|
|
|
|
106 |
Alderwood
Hall |
First
Floor |
Unisex
Toilet Room |
The
toilet flush control is mounted on the narrow side of the toilet area. Flush
controls are required to be mounted on the wide side of the toilet area.
(Right Hand Toilet Room) |
AH7 |
4.1.3(11),
4.22.4 and 4.16.5 |
|
|
|
|
107 |
Alderwood
Hall |
Second
Floor |
Typical
Classrooms |
A
room number sign is not mounted on the wall adjacent to the latch side of the
door. A sign mounted on the wall adjacent to the latch side of the door
identifying the room number in raised characters and Braille is required. |
AH11 |
4.1.3(16)(a),
4.30.1, 4.30.4, 4.30.5 and 4.30.6 |
Tactile
characters on signs shall be located between 48 inches minimum and 60 inches
maximum above the finish floor, measured to the baseline of the tactile
character. |
216.2,
703.1-5 |
|
|
108 |
Alderwood
Hall |
Second
Floor |
Storage
Closet |
The
door has knob hardware which requires twisting of the wrist to operate. Door
hardware that does not require tight grasping, pinching or twisting of the
wrist to operate is required. |
AH12 |
4.1.3(7)(b)
and 4.13.9 |
|
|
|
|
109 |
Alderwood
Hall |
Second
Floor |
Men's
and Women's Toilet Rooms |
The
toilet room sign is mounted 56 inches above the finish floor to the
centerline of the sign. A sign mounted on the wall adjacent to the latch side
of the door at 60 inches above the finish floor to the centerline of the sign
is required. |
AH13
and AH14 |
4.1.3(16)(a)
and 4.30.6 |
Tactile
characters on signs shall be located between 48 inches minimum and 60 inches
maximum above the finish floor, measured to the baseline of the tactile
character. |
216.2,
703.1-5 |
|
|
110 |
Alderwood
Hall |
Second
Floor |
Men's
and Women's Toilet Rooms |
The
force required to open the toilet room door is greater than 5 lbf. The
maximum allowable force for opening an interior door is 5 lbf. |
none |
4.1.3(7)(b)
and 4.13.11(2)(b) |
|
|
|
|
112 |
Alderwood
Hall |
Second
Floor |
Men's
and Women's Toilet Rooms |
The
60-inch diameter turning space is obstructed by furniture. An unobstructed
60‑inch diameter or t-shaped turning space is required. (Women's Toilet
Room) |
AH15
and AH16 |
4.1.3(11),
4.22.3, 4.2.3 and Fig. 3 |
|
|
|
|
113 |
Alderwood
Hall |
Second
Floor |
Men's
and Women's Toilet Rooms |
The
lavatory clear floor space is obstructed by furniture. Clear floor space that
is a minimum of 30 inches wide and 48 inches deep is required. (Women's
Toilet Room) |
AH17 |
4.1.3(11),
4.22.6, 4.19.3 and Fig. 32 |
|
|
|
|
115 |
Alderwood
Hall |
Second
Floor |
Girl's
Toilet Rooms |
The
toilet room sign is mounted 56 inches above the finish floor to the
centerline of the sign. A sign mounted on the wall adjacent to the latch side
of the door at 60 inches above the finish floor to the centerline of the sign
is required. |
AH18 |
4.1.3(16)(a)
and 4.30.6 |
Tactile
characters on signs shall be located between 48 inches minimum and 60 inches
maximum above the finish floor, measured to the baseline of the tactile
character. |
216.2,
703.1-5 |
|
|
118 |
Haas
Pavilion |
Exterior |
Parking
Lot A-3 |
No
"van accessible" sign is provided. One van accessible parking space with a
96-inch wide access aisle identified by an additional "van accessible" sign
mounted below the symbol of accessibility is required. |
HP1 |
4.1.2(5)(a)(b),
4.6.3, 4.6.4 and 4.30.7 |
|
|
|
|
119 |
Haas
Pavilion |
Exterior |
Parking
Lot A-3 |
The
cross slope of the accessible parking space and the adjacent access aisle
varies between 1:30 and 1:37. Accessible parking spaces and access aisle are
required to be level with surface slopes not exceeding 1:50 (2%) in all
directions. |
HP1 |
4.1.2(5)(a)(b)
and 4.6.3 |
|
|
|
|
120 |
Haas
Pavilion |
Exterior |
Entrance |
The
main entrance is up eleven risers, and directional signage is not provided
indicating the route to the designated accessible entrance. A directional
sign indicating the route to the designated accessible entrance is required. |
HP2 |
4.1.2(5)(a)(b)
and 4.6.3 |
|
|
|
|
128 |
Haas
Pavilion |
First
Floor |
Gymnasium |
Signage
notifying patrons of the availability of an assistive listening system is not
provided. A permanently installed assistive listening, 28 receivers and
signage notifying patrons of the availability of a listening system is
required. |
none |
4.1.3(19)(b),
4.33.6, 4.33.7 and 4.30.7(4) |
An
assistive listening system with 26 receivers, including 7 hearing-aid
compatible receivers shall be provided. A sign informing patrons of the
availability of the assistive listening system shall be provided. |
216.10,
219, 703.5, 703.7.2.4 and 706 |
|
|
130 |
Haas
Pavilion |
First
Floor |
Corridor |
The
water flow is 3 inches high. The spout shall provide a flow of water at least
4 inches high so as to allow the insertion of a cup or glass under the flow
of water. |
HP11 |
4.1.3(10)(a)
and 4.15.3 |
|
|
|
|
132 |
Haas
Pavilion |
First
Floor |
Offices
(typical) |
The
room number sign is mounted higher than 60 inches above the finish floor to
the centerline of the sign. A permanent room sign mounted at 60 inches above
the finish floor to the centerline of the sign is required. |
HP12
and HP13 |
4.1.3(16)(a)
and 4.30.6 |
Tactile
characters on signs shall be located between 48 inches minimum and 60 inches
maximum above the finish floor, measured to the baseline of the tactile
character. |
216.2,
703.1-5 |
|
|
133 |
Haas
Pavilion |
First
Floor |
Offices
(typical) |
The
clear opening width of the door is 29 inches. The clear opening width of the
door is required to be 32 inches minimum measured between the face of the
door and the opposite stop when the door is open 90 degrees. |
HP12
and HP13 |
4.1.3(7)(b),
4.13.5 and Fig. 24(a) |
|
|
|
|
134 |
Haas
Pavilion |
First
Floor |
Offices
(typical) |
The
doors have knob hardware which requires twisting of the wrist to operate.
Door hardware that does not require tight grasping, pinching or twisting of
the wrist to operate is required. |
HP12
and HP13 |
4.1.3(7)(b)
and 4.13.9 |
|
|
|
|
135 |
Haas
Pavilion |
First
Floor |
Men's
Toilet Room |
The
toilet room sign is mounted 63 inches above the finish floor to the
centerline of the sign. A toilet room sign mounted at 60 inches above the
finish floor to the centerline of the sign is required. |
HP14 |
4.1.3(16)(a)
and 4.30.6 |
Tactile
characters on signs shall be located between 48 inches minimum and 60 inches
maximum above the finish floor, measured to the baseline of the tactile
character. |
216.2,
703.1-5 |
|
|
140 |
Haas
Pavilion |
First
Floor |
Men's
Toilet Room |
The
typical urinal rim is located 25 inches above the finish floor. A urinal with
a rim that is a maximum of 17 inches above the finish floor is required. |
HP17 |
4.1.3(11),
4.22.5 and 4.18.2 |
|
|
|
|
141 |
Haas
Pavilion |
First
Floor |
Men's
Toilet Room |
The
typical urinal flush control is located 53 inches above the finish floor. A
urinal with a flush control that is a maximum of 44 inches above the finish
floor is required. |
HP17 |
4.1.3(11),
4.22.5 and 4.18.4 |
|
|
|
|
142 |
Haas
Pavilion |
First
Floor |
Men's
Toilet Room |
Knee
clearance at the typical lavatory is 24 inches above the finish floor. A
lavatory with knee clearance at least 27 inches above the finish floor is
required. |
HP18 |
4.1.3(11),
4.22.6 and 4.19.2 |
|
|
|
|
143 |
Haas
Pavilion |
First
Floor |
Men's
Toilet Room |
The
typical lavatory faucet has a knob controls. Controls which do not require
tight grasping, tight pinching or twisting of the wrist to operate are
required. |
HP18 |
4.1.3(11),
4.22.6, 4.19.5 and 4.27.4 |
|
|
|
|
144 |
Haas
Pavilion |
First
Floor |
Women's
Toilet Room |
The
toilet room sign is mounted 63 inches above the finish floor to the
centerline of the sign. A toilet room sign mounted at 60 inches above the
finish floor to the centerline of the sign is required. |
HP19 |
4.1.3(16)(a)
and 4.30.6 |
Tactile
characters on signs shall be located between 48 inches minimum and 60 inches
maximum above the finish floor, measured to the baseline of the tactile
character. |
216.2,
703.1-5 |
|
|
146 |
Haas
Pavilion |
First
Floor |
Women's
Toilet Room |
The
force required to open the vestibule door is 10 lbf. The maximum allowable
force for opening an interior door is 5 lbf. |
HP21 |
4.1.3(7)(b)
and 4.13.11(2)(b) |
|
|
|
|
148 |
Haas
Pavilion |
First
Floor |
Women's
Toilet Room Designated Accessible Toilet Stall |
The
toilet seat is 16½ inches high. The toilet seat is required to be between 17
and 19 inches high. |
HP21 |
4.1.3(11),
4.22.4, 4.17.2, 4.16.3 and Fig. 29(b) |
|
|
|
|
149 |
Haas
Pavilion |
First
Floor |
Women's
Toilet Room Designated Accessible Toilet Stall |
The
toilet centerline is 24 inches from the side partition. The toilet centerline
is required to be exactly 18 inches from the side wall. |
HP21 |
4.1.3(11),
4.22.4, 4.17.3 and Fig. 30(a-1) |
The
centerline of the toilet shall be 16 inches minimum to 18 inches maximum from
the side wall or partition. |
213.3.2
and 604.2 |
|
|
150 |
Haas
Pavilion |
First
Floor |
Women's
Toilet Room |
The
toilet paper dispenser is mounted 39 inches from the rear wall to the far end
of the dispenser. The far end of the dispenser is required to be mounted no
more than 36 inches from the rear wall. |
HP21 |
4.1.3(11),
4.22.4, 4.17.6 and Fig. 30(d) |
The
toilet paper dispenser shall be 7 inches minimum and 9 inches maximum in
front of the toilet measured to the centerline of the dispenser. The outlet
of the dispenser shall be 15 inches minimum and 48 inches maximum above the
finish floor and shall not be located behind grab bars. |
213.3.2
and 604.7 |
|
|
150 |
Haas
Pavilion |
First
Floor |
Women's
Toilet Room Designated Accessible Toilet Stall |
The
toilet paper dispenser is mounted 39 inches from the rear wall to the far end
of the dispenser. The far end of the dispenser is required to be mounted no
more than 36 inches from the rear wall. |
HP21 |
4.1.3(11),
4.22.4, 4.17.6 and Fig. 30(d) |
The
toilet paper dispenser shall be 7 inches minimum and 9 inches maximum in
front of the toilet measured to the centerline of the dispenser. The outlet
of the dispenser shall be 15 inches minimum and 48 inches maximum above the
finish floor and shall not be located behind grab bars. |
213.3.2
and 604.7 |
|
|
151 |
Haas
Pavilion |
First
Floor |
Women's
Toilet Room |
Knee
clearance at the typical lavatory is 24 inches above the finish floor. A
lavatory with knee clearance at least 27 inches above the finish floor is
required. |
HP22 |
4.1.3(11),
4.22.6 and 4.19.2 |
|
|
|
|
152 |
Haas
Pavilion |
First
Floor |
Women's
Toilet Room |
The
typical lavatory faucet has knob controls. Controls which do not require
tight grasping, tight pinching or twisting of the wrist to operate are
required. |
HP22 |
4.1.3(11),
4.22.6, 4.19.5 and 4.27.4 |
|
|
|
|
153 |
Haas
Pavilion |
Lower
Level |
Corridor |
The
drinking fountain protrudes 12½ inches from the wall and the leading edge is
33 inches above the finish floor. Objects mounted to walls with their leading
edges between 27 inches and 80 inches above the finish floor shall protrude
no more than 4 inches into the circulation path. |
HP23 |
4.1.3(2)
and 4.4.1 |
|
|
|
|
154 |
Haas
Pavilion |
Lower
Level |
Corridor |
One
inaccessible drinking fountain is provided. One drinking fountain accessible
to individuals who use wheelchairs and one drinking fountain accessible to
individuals who have trouble bending or stooping are required. |
HP23 |
4.1.3(10)(a)
and 4.15 |
|
|
|
|
155 |
Haas
Pavilion |
Lower
Level |
Corridor |
The
typical equipment counter is 41½ inches above the finish floor. A portion of
the main counter which is a minimum of 36 inches long and a maximum of 36
inches high, an auxiliary counter with a maximum height of 36 inches in close
proximity to the main counter or equivalent facilitation is required. |
HP24 |
7.2(2) |
A
portion of the counter that is 36 inches high maximum shall be provided. |
227.3
and 904.4 |
|
|
156 |
Haas
Pavilion |
Lower
Level |
Dance
Studios and Offices (typical) |
A
room number sign is not mounted on the wall adjacent to the latch side of the
door. A sign mounted on the wall adjacent to the latch side of the door
identifying the room number in raised characters and Braille is required. |
HP25
and HP26 |
4.1.3(16)(a),
4.30.1, 4.30.4, 4.30.5 and 4.30.6 |
Tactile
characters on signs shall be located between 48 inches minimum and 60 inches
maximum above the finish floor, measured to the baseline of the tactile
character. |
216.2,
703.1-5 |
|
|
158 |
Haas
Pavilion |
Lower
Level |
Dance
Studios and Offices (typical) |
The
doors have knob hardware which requires twisting of the wrist to operate.
Door hardware that does not require tight grasping, pinching or twisting of
the wrist to operate is required. |
HP25
and HP26 |
4.1.3(7)(b)
and 4.13.9 |
|
|
|
|
159 |
Haas
Pavilion |
Lower
Level |
Men's
Locker Room |
A
toilet room sign is not mounted on the wall adjacent to the latch side of the
door. A sign mounted on the wall adjacent to the latch side of the door
identifying the toilet room in raised characters and Braille is required. |
HP27 |
4.1.3(16)(a),
4.30.1, 4.30.4, 4.30.5 and 4.30.6 |
Tactile
characters on signs shall be located between 48 inches minimum and 60 inches
maximum above the finish floor, measured to the baseline of the tactile
character. |
216.2,
703.1-5 |
|
|
160 |
Haas
Pavilion |
Lower
Level |
Men's
Locker Room |
The
clear opening width of the door is 29 inches. The clear opening width of the
door is required to be 32 inches minimum measured between the face of the
door and the opposite stop when the door is open 90 degrees. |
HP27 |
4.1.3(7)(b),
4.13.5 and Fig. 24(a) |
|
|
|
|
161 |
Haas
Pavilion |
Lower
Level |
Men's
Locker Room |
The
force required to open the door is 10 lbf. The maximum allowable force for
opening an interior door is 5 lbf. |
none |
4.1.3(7)(b)
and 4.13.11(2)(b) |
|
|
|
|
164 |
Haas
Pavilion |
Lower
Level |
Men's
Locker Room Toilet Area |
The
typical urinal rim is located 24 inches above the finish floor. A urinal with
a rim that is a maximum of 17 inches above the finish floor is required. |
HP30 |
4.1.3(11),
4.23.5 and 4.18.2 |
|
|
|
|
165 |
Haas
Pavilion |
Lower
Level |
Men's
Locker Room Toilet Area |
The
typical urinal flush control is located 52 inches above the finish floor. A
urinal with a flush control that is a maximum of 44 inches above the finish
floor is required. |
HP30 |
4.1.3(11),
4.23.5 and 4.18.4 |
|
|
|
|
167 |
Haas
Pavilion |
Lower
Level |
Men's
Locker Room Toilet Area |
Knee
clearance at the typical lavatory is 26 inches above the finish floor. A
lavatory with knee clearance at least 27 inches above the finish floor is
required. |
HP31 |
4.1.3(11),
4.23.6 and 4.19.2 |
|
|
|
|
168 |
Haas
Pavilion |
Lower
Level |
Men's
Locker Room Toilet Area |
The
drain pipe and hot water pipe underneath the typical lavatory are not
insulated or configured against contact. Drain and hot water pipes shall be
insulated or otherwise configured against contact. |
HP31 |
4.1.3(11),
4.23.6 and 4.19.4 |
Water
supply and drain pipes under lavatories shall be insulated or otherwise
configured against. |
213.3.4
and 606.5 |
|
|
169 |
Haas
Pavilion |
Lower
Level |
Men's
Locker Room Toilet Area |
The
typical lavatory faucet has knob controls. Controls which do not require
tight grasping, tight pinching or twisting of the wrist to operate are
required. |
HP31 |
4.1.3(11),
4.23.6, 4.19.5 and 4.27.4 |
|
|
|
|
170 |
Haas
Pavilion |
Lower
Level |
Men's
Locker Room Toilet Area |
The
typical soap dispenser control is located 46 inches above the finish floor. A
soap dispenser with a control that is located no higher than 44 inches above
the finish floor for a forward reach over an obstruction is required. |
HP31 |
4.1.3(11),
4.23.7, 4.27.3, 4.2.5 and Fig. 5(b) |
|
|
|
|
171 |
Haas
Pavilion |
Lower
Level |
Men's
Locker Room Toilet Area |
The
paper towel dispenser control is located 58 inches above the finish floor. A
paper towel dispenser with a control that is located no higher than 54 inches
above the finish floor for a side reach is required. |
HP31 |
4.1.3(11),
4.23.7, 4.27.3, 4.2.6 and Fig. 6 |
A
dispenser with a control no higher than 48 inches above the finish floor for
an unobstructed reach is required. |
205.1,
309.3 and 308 |
|
|
172 |
Haas
Pavilion |
Lower
Level |
Men's
Locker Room |
One
inaccessible drinking fountain is provided. One drinking fountain accessible
to individuals who use wheelchairs and one drinking fountain accessible to
individuals who have trouble bending or stooping are required. |
HP32 |
4.1.3(10)(a)
and 4.15 |
|
|
|
|
173 |
Haas
Pavilion |
Lower
Level |
Men's
Locker Room |
The
typical locker has a control which requires pinching and twisting of the
wrist to operate. A locker with a control which does not require tight
grasping, tight pinching or twisting of the wrist to operate is required. |
HP33
and HP34 |
4.1.3(12),
4.25.4 and 4.27.4 |
|
|
|
|
175 |
Haas
Pavilion |
Lower
Level |
Men's
Locker Room Shower Area |
No
shower grab bars are provided. An accessible shower with grab bars along the
control wall and side wall is required. |
HP35 |
4.1.3(11),
4.23.8, 4.21.4, 4.26 and Fig. 37(b) |
|
|
|
|
176 |
Haas
Pavilion |
Lower
Level |
Men's
Locker Room Shower Area |
The
typical shower faucet has knob controls. Controls which do not require tight
grasping, tight pinching or twisting of the wrist to operate are
required. |
HP35 |
4.1.3(11),
4.23.8, 4.21.5 and 4.27.4 |
|
|
|
|
177 |
Haas
Pavilion |
Lower
Level |
Men's
Locker Room Shower Area |
A
shower spray unit is not provided. A shower spray unit with a hose at least
60 inches long that can be used as a fixed shower head and as a hand held
shower is required. |
HP35 |
4.1.3(11),
4.23.8 and 4.21.6 |
A
shower spray unit with a hose 59 inches long minimum that can be used both as
a fixed-position shower head an as a handheld shower shall be provided. The
shower spray unit shall have an on/off control with a non-positive shut-off. |
213.3.6
and 608.6 |
|
|
178 |
Haas
Pavilion |
Lower
Level |
Women's
Locker Room |
A
toilet room sign is not mounted on the wall adjacent to the latch side of the
door. A sign mounted on the wall adjacent to the latch side of the door
identifying the toilet room in raised characters and Braille is required. |
HP36 |
4.1.3(16)(a),
4.30.1, 4.30.4, 4.30.5 and 4.30.6 |
Tactile
characters on signs shall be located between 48 inches minimum and 60 inches
maximum above the finish floor, measured to the baseline of the tactile
character. |
216.2,
703.1-5 |
|
|
181 |
Haas
Pavilion |
Lower
Level |
Women's
Locker Room |
The
force required to open the corridor door and the vestibule door is 10 lbf.
The maximum allowable force for opening an interior door is 5 lbf. |
none |
4.1.3(7)(b)
and 4.13.11(2)(b) |
|
|
|
|
194 |
Haas
Pavilion |
Lower
Level |
Women's
Locker Room |
The
typical locker has a control which requires pinching and twisting of the
wrist to operate. A locker with a control which does not require tight
grasping, tight pinching or twisting of the wrist to operate is required. |
HP42 |
4.1.3(12),
4.25.4 and 4.27.4 |
|
|
|
|
195 |
Haas
Pavilion |
Lower
Level |
Women's
Locker Room |
A
bench fixed to the wall is not provided. A 24-inch by 48-inch bench fixed to
the wall along the longer dimension is required. |
HP43 |
4.1.3(21)
and 4.35.4 |
Benches
shall have seats that are 42 inches long minimum and 20 inches deep minimum
to 24 inches deep maximum. The bench shall provide back support or shall be
affixed to a wall. |
222.1,
803.4 and 903 |
|
|
197 |
Haas
Pavilion |
Lower
Level |
Women's
Locker Room |
The
typical hair dryer control is located 62 inches above the finish floor. A
hair dryer with a control that is located no higher than 54 inches above the
finish floor for a side reach is required. |
HP44 |
4.1.3(11),
4.23.7, 4.27.3, 4.2.6 and Fig. 6 |
A
hair dryer with a control no higher than 48 inches above the finish floor for
an unobstructed reach is required. |
205.1,
309.3 and 308 |
|
|
198 |
Haas
Pavilion |
Lower
Level |
Women's
Locker Room Shower |
The
typical shower compartment is 31 inches wide by 35 inches deep. Either an
accessible transfer shower that is exactly 36 inches wide by 36 inches deep
or an accessible roll-in shower that is a minimum of 60 inches wide by 30
inches deep shall be provided. |
HP45 |
4.1.3(11),
4.23.8, 4.21.2, and Fig. 35(a)(b) |
|
|
|
|
199 |
Haas
Pavilion |
Lower
Level |
Women's
Locker Room Shower Area |
No
shower seat is provided. A seat shall be provided in shower stalls 36 inches
wide by 36 inches deep |
HP45 |
4.1.3(11),
4.23.8, 4.21.3, 4.26 and Fig. 36 |
|
|
|
|
200 |
Haas
Pavilion |
Lower
Level |
Women's
Locker Room Shower Area |
No
shower grab bars are provided. An accessible shower with grab bars along the
control wall and side wall is required. |
HP45 |
4.1.3(11),
4.23.8, 4.21.4, 4.26 and Fig. 37(a)(b) |
|
|
|
|
201 |
Haas
Pavilion |
Lower
Level |
Women's
Locker Room Shower Area |
The
typical shower faucet has knob controls. Controls which do not require tight
grasping, tight pinching or twisting of the wrist to operate are
required. |
HP45 |
4.1.3(11),
4.23.8, 4.21.5 and 4.27.4 |
|
|
|
|
202 |
Haas
Pavilion |
Lower
Level |
Women's
Locker Room Shower Area |
A
shower spray unit is not provided. A shower spray unit with a hose at least
60 inches long that can be used as a fixed shower head and as a hand held
shower is required. |
HP45 |
4.1.3(11),
4.23.8 and 4.21.6 |
A
shower spray unit with a hose 59 inches long minimum that can be used both as
a fixed-position shower head an as a handheld shower shall be provided. The
shower spray unit shall have an on/off control with a non-positive shut-off. |
213.3.6
and 608.6 |
|
|
203 |
Haas
Pavilion |
Lower
Level |
Women's
Locker Room Dressing Area |
The
clear opening width of the typical dressing compartment door is 23 inches.
The clear opening width of the door is required to be 32 inches minimum
measured between the face of the door and the opposite stop when the door is
open 90 degrees. |
HP46 |
4.1.3(7)(b),
4.13.5 and Fig. 24(a) |
|
|
|
|
204 |
Haas
Pavilion |
Lower
Level |
Women's
Locker Room Dressing Area |
An
unobstructed turning space is not provided in the typical dressing
compartment. A 60-inch diameter or t-shaped turning space is required. |
HP46 |
4.1.3(21),
4.35.2, 4.2.3 and Fig. 3 |
|
|
|
|
205 |
Haas
Pavilion |
Lower
Level |
Women's
Locker Room Dressing Area |
A
bench fixed to the wall is not provided. A 24-inch by 48-inch bench fixed to
the wall along the longer dimension is required. |
none |
4.1.3(21)
and 4.35.4 |
Benches
shall have seats that are 42 inches long minimum and 20 inches deep minimum
to 24 inches deep maximum. The bench shall provide back support or shall be
affixed to a wall. |
222.1,
803.4 and 903 |
|
|
208 |
Music
Building |
First
Floor |
CCM
Women's Toilet Room |
The
women's toilet room is not accessible, and a directional sign to the
designated accessible toilet is not provided. A sign indicating the location
of the designated accessible toilet rooms on the second floor is required. |
MB3
and MB4 |
4.1.6(3)(e)(iii) |
|
|
|
|
209 |
Music
Building |
First
Floor |
Concert
Hall Lobby |
No
signage is provided indicating the route to the designated accessible concert
hall entrance. A directional sign indicating the route to the designated
accessible second floor concert hall entrance is required. |
MB5 |
4.1.2(7)(c)
and 4.1.6(1)(h) |
|
|
|
|
210 |
Music
Building |
Second
Floor |
Women's
Toilet Room |
The
force required to open the toilet room door is 20 lbf. The maximum allowable
force for opening an interior door is 5 lbf. |
none |
4.1.3(7)(b)
and 4.13.11(2)(b) |
|
|
|
|
212 |
Music
Building |
Second
Floor |
Women's
Toilet Room Ambulatory Toilet Stall |
The
toilet seat is 16 inches high. The toilet seat is required to be between 17
and 19 inches high. |
MB6 |
4.1.3(11),
4.22.4, 4.16.3 and Fig. 29(b) |
|
|
|
|
216 |
Music
Building |
Second
Floor |
Unisex
Toilet Room |
The
force required to open the toilet room door is 16 lbf. The maximum allowable
force for opening an interior door is 5 lbf. |
none |
4.1.3(7)(b)
and 4.13.11(2)(b) |
|
|
|
|
217 |
Music
Building |
Second
Floor |
Unisex
Toilet Room |
The
lavatory protrudes 23½ inches from the wall and the leading edge is 30 inches
above the finish floor. Objects mounted to walls with their leading edges
between 27 inches and 80 inches above the finish floor shall protrude no more
than 4 inches into the circulation path. |
MB9 |
4.1.3(2)
and 4.4.1 |
|
|
|
|
219 |
Music
Building |
Second
Floor |
Men's
Toilet Room |
The
force required to open the toilet room door is 16 lbf. The maximum allowable
force for opening an interior door is 5 lbf. |
none |
4.1.3(7)(b)
and 4.13.11(2)(b) |
|
|
|
|
220 |
Music
Building |
Second
Floor |
Men's
Toilet Room |
The
lavatory protrudes 23½ inches from the wall and the leading edge is 30 inches
above the finish floor. Objects mounted to walls with their leading edges
between 27 inches and 80 inches above the finish floor shall protrude no more
than 4 inches into the circulation path. |
MB11 |
4.1.3(2)
and 4.4.1 |
|
|
|
|
226 |
Music
Building |
Second
Floor |
Practice
Studio Corridor |
The
high drinking fountain protrudes 18 inches from the wall and the leading edge
is more than 27 inches above the finish floor. Objects mounted to walls with
their leading edges between 27 inches and 80 inches above the finish floor
shall protrude no more than 4 inches into the circulation path. |
MB17 |
4.1.3(2)
and 4.4.1 |
|
|
|
|
228 |
Music
Building |
Littlefield
Concert Hall |
Entrance |
Signage
identifying the designated accessible concert hall entrance is not provided.
The accessible concert hall entrance shall be identified by the International
Symbol of Accessibility. |
MB19 |
4.1.2(7)(c),
4.30.7(1) and Fig. 43(a)(b) |
|
|
|
|
229 |
Music
Building |
Littlefield
Concert Hall |
Auditorium |
Two
aisle seats with movable armrests are provided. Five aisle seats with no
armrests on the aisle side, or removable or folding armrests on the aisle
side are required. |
MB20 |
4.1.3(19)(a) |
At
least 5 percent of the total number of aisle seats provided shall have
folding or retractable armrests on the aisle side. |
221.4
and 802.4 |
|
|
230 |
Music
Building |
Littlefield
Concert Hall |
Auditorium |
The
stage is located six risers above the auditorium floor, and directional
signage is not provided indicating the route to the designated accessible
stage entrance. A directional sign indicating the route to the designated
accessible stage entrance is required. |
MB21 |
4.1.2(7)(c),
4.1.6(1)(h), 4.1.3(19)(a) and 4.33.5 |
|
|
|
|
235 |
Music
Building |
Littlefield
Concert Hall |
Stage |
Signage
identifying the designated accessible stage entrance is not provided. The
designated accessible stage entrance shall be identified by the International
Symbol of Accessibility. |
MB25 |
4.1.2(7)(c),
4.30.7(1) and Fig. 43(a)(b) |
|
|
|
|
248 |
Aaron
Art Center |
Exterior |
Route
to Entrance |
The
entrance to the Aaron Art Center is up four risers, and directional signage
is not provided indicating the route to the designated accessible entrance
ramp. A directional sign indicating the route to the designated accessible
entrance ramp is required. |
AC7 |
4.1.2(7)(c)
and 4.1.6(1)(h) |
|
|
|
|
251 |
Aaron
Art Center |
Exterior |
Route
to Entrance |
The
main entrance to the art museum is up seven risers, and directional signage
is not provided indicating the route to the designated accessible art museum
entrance. A directional sign indicating the route to the designated
accessible entrance is required. |
AC10 |
4.1.2(7)(c)
and 4.1.6(1)(h) |
|
|
|
|
257 |
Aaron
Art Center |
Aaron
Art Center |
Vestibule |
The
drinking fountain protrudes 20½ inches from the wall and the leading edge is
28 inches above the finish floor. Objects mounted to walls with their leading
edges between 27 inches and 80 inches above the finish floor shall protrude
no more than 4 inches into the circulation path. |
AC19
and AC20 |
4.1.3(2)
and 4.4.1 |
|
|
|
|
258 |
Aaron
Art Center |
Aaron
Art Center |
Vestibule |
A
standard height drinking fountain is not provided. One drinking fountain
accessible to individuals who use wheelchairs and one drinking fountain
accessible to individuals who have trouble bending or stooping are required. |
AC19
and AC20 |
4.1.3(10)(a)
and 4.15 |
|
|
|
|
259 |
Aaron
Art Center |
Aaron
Art Center |
Vestibule |
The
spout outlet is 37 inches high. The spout outlet shall be no higher than 36
inches above the finish floor. |
AC19 |
4.1.3(10)(a)
and 4.15.2 |
|
|
|
|
260 |
Aaron
Art Center |
Aaron
Art Center |
Vestibule |
The
water flow is 3 inches high. The spout shall provide a flow of water at least
4 inches high so as to allow the insertion of a cup or glass under the flow
of water. |
AC19 |
4.1.3(10)(a)
and 4.15.3 |
|
|
|
|
261 |
Aaron
Art Center |
Aaron
Art Center |
Danforth
Lecture Hall |
The
sign does not identify the room number in raised characters and Braille. A
sign mounted on the wall adjacent to the latch side of the door identifying
the room number in raised characters and Braille is required. |
AC21 |
4.1.3(16)(a)
and 4.30.4 |
Tactile
characters on signs shall be located between 48 inches minimum and 60 inches
maximum above the finish floor, measured to the baseline of the tactile
character. |
216.2,
703.1-5 |
|
|
262 |
Aaron
Art Center |
Aaron
Art Center |
Danforth
Lecture Hall |
The
force required to open the door is 10 lbf. The maximum allowable force for
opening an interior door is 5 lbf. |
none |
4.1.3(7)(b)
and 4.13.11(2)(b) |
|
|
|
|
264 |
Aaron
Art Center |
Aaron
Art Center |
Danforth
Lecture Hall |
The
lecture hall contains 84 fixed seats, and no aisle seats with movable
armrests are provided. One aisle seat with no armrests on the aisle side, or
removable or folding armrests on the aisle side are required. |
AC23 |
4.1.3(19)(a) |
At
least 5 percent of the total number of aisle seats provided shall have
folding or retractable armrests on the aisle side. |
221.4
and 802.4 |
|
|
266 |
Aaron
Art Center |
Aaron
Art Center |
Danforth
Lecture Hall |
Signage
notifying patrons of the availability of an assistive listening system is not
provided. A permanently installed assistive listening, four receivers and
signage notifying patrons of the availability of a listening system is
required. |
none |
4.1.3(19)(b),
4.33.6, 4.33.7 and 4.30.7(4) |
An
assistive listening system with 4 receivers, including 2 hearing-aid
compatible receivers shall be provided. A sign informing patrons of the
availability of the assistive listening system shall be provided. |
216.10,
219, 703.5, 703.7.2.4 and 706 |
|
|
267 |
Aaron
Art Center |
Aaron
Art Center |
Women's
Toilet Room |
A
toilet room sign is not mounted on the wall adjacent to the latch side of the
door. A sign mounted on the wall adjacent to the latch side of the door
identifying the toilet room in raised characters and Braille is required. |
AC33 |
4.1.3(16)(a),
4.30.1, 4.30.4, 4.30.5 and 4.30.6 |
Tactile
characters on signs shall be located between 48 inches minimum and 60 inches
maximum above the finish floor, measured to the baseline of the tactile
character. |
216.2,
703.1-5 |
|
|
268 |
Aaron
Art Center |
Aaron
Art Center |
Women's
Toilet Room |
The
maneuvering clearance on the latch side of the door is 4½ inches. A minimum
of 12 inches is required on the latch side of the door for a forward push
approach when the door has both a closer and a latch. |
AC34 |
4.1.3(7)(b),
4.13.6 and Fig. 25(a) |
|
|
|
|
269 |
Aaron
Art Center |
Aaron
Art Center |
Women's
Toilet Room |
The
force required to open the toilet room door is 9 lbf. The maximum allowable
force for opening a fire door is the minimum opening force allowable by the
appropriate administrative authority. |
none |
4.1.3(7)(b)
and 4.13.11(1) |
|
|
|
|
272 |
Aaron
Art Center |
Aaron
Art Center |
Men's
Toilet Room |
A
toilet room sign is not mounted on the wall adjacent to the latch side of the
door. A sign mounted on the wall adjacent to the latch side of the door
identifying the toilet room in raised characters and Braille is required. |
AC36 |
4.1.3(16)(a),
4.30.1, 4.30.4, 4.30.5 and 4.30.6 |
Tactile
characters on signs shall be located between 48 inches minimum and 60 inches
maximum above the finish floor, measured to the baseline of the tactile
character. |
216.2,
703.1-5 |
|
|
273 |
Aaron
Art Center |
Aaron
Art Center |
Men's
Toilet Room |
The
maneuvering clearance on the latch side of the door is 4½ inches. A minimum
of 12 inches is required on the latch side of the door for a forward push
approach when the door has both a closer and a latch. |
AC37 |
4.1.3(7)(b),
4.13.6 and Fig. 25(a) |
|
|
|
|
275 |
Aaron
Art Center |
Aaron
Art Center |
Men's
Toilet Room |
The
force required to open the toilet room door is 10 lbf. The maximum allowable
force for opening a fire door is the minimum opening force allowable by the
appropriate administrative authority. |
none |
4.1.3(7)(b)
and 4.13.11(1) |
|
|
|
|
276 |
Aaron
Art Center |
Aaron
Art Center |
Men's
Toilet Room Designated Accessible Toilet Stall |
The
toilet flush control is mounted on the narrow side of the toilet area. Flush
controls are required to be mounted on the wide side of the toilet area. |
AC39 |
4.1.3(11),
4.22.4, 4.17.2 and 4.16.5 |
|
|
|
|
280 |
Aaron
Art Center |
Aaron
Art Center |
Men's
Toilet Room Designated Accessible Toilet Stall |
The
coat hook is 66½ inches above the finish floor. A hook no higher than 54
inches above the finish floor for a side reach is required. |
AC40 |
4.1.3(12)(a),
4.25.3, 4.2.6 and Fig. 6 |
A
hook no higher than 48 inches above the finish floor for an unobstructed
reach is required. |
222.2,
803.5 and 308 |
|
|
283 |
Carnegie
Hall |
Exterior |
Entrance |
The
entrance door hardware is mounted 50 inches above the finish floor. Hardware
shall be mounted no higher than 48 inches above the finish floor. |
CH-3 |
4.1.3(8),
4.1.3(7)(a) and 4.13.9 |
|
|
|
|
284 |
Carnegie
Hall |
Level
One |
Elevator |
Floor
designations are not provided on the first and second floor hoistway entrance
jambs. Raised and Braille floor designations are required on both hoistway
entrance jambs at 60 inches above the finish floor to the centerline of the
character. |
CH4
through CH7 |
4.1.3(5),
4.10.5 and Figure 20 |
Tactile
characters on signs shall be located between 48 inches minimum and 60 inches
maximum above the finish floor, measured to the baseline of the tactile
character. |
206.6,
407.2.3, 703.2 and 703.4.1 |
|
|
286 |
Carnegie
Hall |
Level
One |
M
Center |
The
display case protrudes 9 inches from the wall and the leading edge is 35½
inches above the finish floor. Objects mounted to walls with their leading
edges between 27 inches and 80 inches above the finish floor shall protrude
no more than 4 inches into the circulation path. |
CH9 |
4.1.3(2)
and 4.4.1 |
|
|
|
|
288 |
Carnegie
Hall |
Level
One |
Offices
(typical) |
The
doors have knob hardware which requires twisting of the wrist to operate.
Door hardware that does not require tight grasping, pinching or twisting of
the wrist to operate is required. |
CH11
through CH13 |
4.1.3(7)(b)
and 4.13.9 |
|
|
|
|
291 |
Carnegie
Hall |
Level
Two |
Mills
College Annual Fund Room 229 |
The
door has knob hardware which requires twisting of the wrist to operate. Door
hardware that does not require tight grasping, pinching or twisting of the
wrist to operate is required. |
none |
4.1.3(7)(b)
and 4.13.9 |
|
|
|
|
292 |
Carnegie
Hall |
Level
Two |
Offices
(typical) |
A
room number sign is not mounted on the wall adjacent to the latch side of the
door. A sign mounted on the wall adjacent to the latch side of the door
identifying the room number in raised characters and Braille is required. |
CH16
and CH17 |
4.1.3(16)(a),
4.30.1, 4.30.4, 4.30.5 and 4.30.6 |
Tactile
characters on signs shall be located between 48 inches minimum and 60 inches
maximum above the finish floor, measured to the baseline of the tactile
character. |
216.2,
703.1-5 |
|
|
293 |
Lisser
Hall |
Exterior |
Parking
Lot E-2 |
The
curb ramp projects into the access aisle of the designated accessible parking
space in front of the annex. Accessible parking spaces and access aisle are
required to be level with surface slopes not exceeding 1:50 (2%) in all
directions. |
LH1
and LH2 |
4.1.2(5)(a)
and 4.6.3 |
|
|
|
|
304 |
Lisser
Hall |
First
Floor |
Lobby |
The
typical coffee bar counter is 42 inches above the finish floor. At least one
coffee bar with a portion of the main counter which is a minimum of 36 inches
long and a maximum of 36 inches high is required. |
LH13 |
7.2(1) |
|
|
|
|
305 |
Lisser
Hall |
First
Floor |
Auditorium |
No
wheelchair locations are provided. Four wheelchair locations are required. |
LH14
through LH16 |
4.1.3(19)(a),
4.33.2, 4.33.3 and 4.33.4 |
Five
wheelchair locations are required. |
221.2.1
and 802 |
|
|
306 |
Lisser
Hall |
First
Floor |
Auditorium |
No
aisle seats with movable armrest are provided. Three aisle seats with no
armrests on the aisle side, or removable or folding armrests on the aisle
side are required. |
LH17 |
4.1.3(19)(a) |
At
least 5 percent of the total number of aisle seats provided shall have
folding or retractable armrests on the aisle side. |
221.4
and 802.4 |
|
|
307 |
Lisser
Hall |
First
Floor |
Auditorium |
Signage
notifying patrons of the availability of an assistive listening system is not
provided. A permanently installed assistive listening, eight receivers and
signage notifying patrons of the availability of a listening system is
required |
none |
4.1.3(19)(b),
4.33.6, 4.33.7 and 4.30.7(4) |
An
assistive listening system with 9 receivers, including 2 hearing-aid
compatible receivers shall be provided. A sign informing patrons of the
availability of the assistive listening system shall be provided. |
216.10,
219, 703.5, 703.7.2.4 and 706 |
|
|
308 |
Lisser
Hall |
First
Floor |
Vestibule |
The
clear opening width of a single leaf of the double leaf door is 27 inches.
The clear opening width of at least one leaf of the door is required to be 32
inches minimum measured between the face of the door and the opposite stop
when the door is open 90 degrees. |
LH18 |
4.1.3(7)(b),
4.13.4, 4.13.5 and Fig. 24(a) |
|
|
|
|
309 |
Lisser
Hall |
First
Floor |
Vestibule |
One
standard height drinking fountain is provided. A drinking fountain accessible
to individuals who use wheelchairs is required. |
LH19 |
4.1.3(10)(a)
and 4.15 |
|
|
|
|
310 |
Lisser
Hall |
First
Floor |
Vestibule |
The
ticket counter is 42½ inches above the finish floor. A ticket counter with a
portion of the main counter which is a minimum of 36 inches long and a
maximum of 36 inches high is required. |
LH20 |
7.2(1) |
|
|
|
|
311 |
Lisser
Hall |
First
Floor |
Men's
and Women's Toilet Rooms |
The
men's and women's toilet rooms are not accessible, and a directional sign to
the designated accessible toilet room is not provided. A sign indicating the
location of the designated accessible toilet room is required. |
LH21
and LH22 |
4.1.6(3)(e)(iii) |
|
|
|
|
312 |
Lisser
Hall |
First
Floor |
Route
to Unisex Toilet Room on Portico |
The
clear opening width of a single leaf of the double leaf entrance door is 27
inches. The clear opening width of at least one leaf of the door is required
to be 32 inches minimum measured between the face of the door and the
opposite stop when the door is open 90 degrees. |
LH23 |
4.1.3(8),
4.1.3(7)(b), 4.13.4, 4.13.5 and Fig. 24(a) |
|
|
|
|
315 |
Lisser
Hall |
First
Floor |
Unisex
Toilet Room |
The
toilet centerline is 20½ inches from the side wall. The toilet centerline is
required to be exactly 18 inches from the side wall. |
LH25 |
4.1.3(11),
4.22.4, 4.16.2 and Fig. 28 |
The
centerline of the toilet shall be 16 inches minimum to 18 inches maximum from
the side wall or partition. |
213.3.2
and 604.2 |
|
|
325 |
Mills
Hall |
First
Floor |
Women's
Toilet Room - Room 131 Designated Accessible Toilet Stall |
The
toilet seat is 16½ inches high. The toilet seat is required to be between 17
and 19 inches high. |
MH8 |
4.1.3(11),
4.22.4, 4.17.2, 4.16.3 and Fig. 29(b) |
|
|
|
|
328 |
Mills
Hall |
First
Floor |
Women's
Toilet Room - Room 131 |
The
clearance at the lavatory apron is 27½ inches above the finish floor.
Clearance at least 29 inches above the finish floor to the bottom of the
apron is required. |
MH9 |
4.1.3(11),
4.22.6 and 4.19.2 |
Lavatory
knee clearance shall be 8 inches deep minimum at 27 inches minimum above the
finish floor |
213.3.4,
606.2 and 306.3 |
|
|
330 |
Mills
Hall |
First
Floor |
Men's
Toilet Room - Room 125 Designated Accessible Toilet Stall |
The
toilet stall is 57 inches wide and 52 inches deep to the in‑swinging
stall door. An accessible toilet stall with an in‑swinging door and a
wall mounted toilet is required to provide a clear floor space that is a
minimum of 60 inches wide and 56 inches deep. |
MH11 |
4.1.3(11),
4.22.4, 4.17.3 and Fig. 30(a-1) |
|
|
|
|
333 |
Mills
Hall |
First
Floor |
Men's
Toilet Room - Room 125 |
The
clearance at the lavatory apron is 27½ inches above the finish floor.
Clearance at least 29 inches above the finish floor to the bottom of the
apron is required. |
MH13 |
4.1.3(11),
4.22.6 and 4.19.2 |
Lavatory
knee clearance shall be 8 inches deep minimum at 27 inches minimum above the
finish floor |
213.3.4,
606.2 and 306.3 |
|
|
334 |
Mills
Hall |
Second
and Third Floors |
Corridor |
The
clear opening width of the typical office and meeting room door is 29 inches.
The clear opening width of a door is required to be 32 inches minimum
measured between the face of the door and the opposite stop when the door is
open 90 degrees. |
MH14
and MH15 |
4.1.3(7)(b),
4.13.5 and Fig. 24(a) |
|
|
|
Relocate
classes and meetings to accessible rooms as required |
335 |
Mills
Hall |
Second
and Third Floors |
Men's
and Women's Toilet Rooms |
The
men's and women's toilet room are not accessible, and a directional sign to
the designated accessible men's and women's toilet rooms is not provided. A
sign indicating the location of the designated accessible toilet rooms is
required. |
MH17
through MH19 |
4.1.6(3)(e)(iii) |
|
|
|
|
336 |
Mills
Hall |
Second
and Third Floors |
Men's
and Women's Toilet Rooms |
The
force required to open the doors is 8 lbf. The maximum allowable force for
opening an interior door is 5 lbf. |
none |
4.1.3(7)(b)
and 4.13.11(2)(b) |
|
|
|
|
337 |
Mills
Hall |
Second
and Third Floors |
Men's
and Women's Toilet Rooms |
The
shelf in the designated accessible toilet stall protrudes 14½ inches from the
wall and the leading edge is 41 inches above the finish floor. Objects
mounted to walls with their leading edges between 27 inches and 80 inches
above the finish floor shall protrude no more than 4 inches into the
circulation path. |
MH20
and MH21 |
4.1.3(2)
and 4.4.1 |
|
|
|
|
339 |
Mills
Hall |
Fourth
Floor Guest Suite 413 |
Entrance |
The
door has a chain security lock, which requires tight pinching to operate.
Door hardware that does not require tight grasping, pinching or twisting of
the wrist to operate is required. |
MH22 |
9.1.2,
9.2.2(3) and 4.13.9 |
|
|
|
|
340 |
Mills
Hall |
Fourth
Floor Guest Suite 413 |
Entrance |
The
force required to open the door is 8 lbf. The maximum allowable force for
opening an interior door is 5 lbf. |
none |
9.1.2,
9.2.2(3) and 4.13.11(2)(b) |
|
|
|
|
343 |
Mills
Hall |
Fourth
Floor Guest Suite 413 |
Kitchen |
The
microwave control is higher than 54 inches above the finish floor. A
microwave control that is no higher than 54 inches above the finish floor for
a side reach is required. |
MH25
and MH26 |
9.1.2,
9.2.2(7), 4.27.3, 4.2.6 and Fig. 6 |
A
microwave with a control no higher than 48 inches above the finish floor for
an unobstructed reach is required. |
224.2,
806.2.5, 804.6, 309.3 and 308 |
|
|
344 |
Mills
Hall |
Fourth
Floor Guest Suite 413 |
Kitchen |
The
oven controls require tight grasping and twisting of the wrist to operate.
Controls which do not require tight grasping, tight pinching or twisting of
the wrist to operate are required. |
MH25
and MH26 |
9.1.2,
9.2.2(7) and 4.27.4 |
|
|
|
|
345 |
Mills
Hall |
Fourth
Floor Guest Suite 413 |
Bedroom |
The
clear opening width of the walk-in closet door is 25½ inches. The clear
opening width of the door is required to be 32 inches minimum measured
between the face of the door and the opposite stop when the door is open 90
degrees. |
MH27 |
9.1.2,
9.2.2(3) and 4.13.5 |
|
|
|
|
346 |
Mills
Hall |
Fourth
Floor Guest Suite 413 |
Bedroom |
The
closet rod is 69 inches above the finish floor. A closet rod that is a
maximum of 54 inches above the finish floor for a side reach is
required. |
MH27 |
9.1.2,
9.2.2(4), 4.25.3, 4.2.6 and Fig. 6 |
A
rod no higher than 46 inches above the finish floor for an obstructed side
reach is required. |
222.2,
803.5 and 308 |
|
|
347 |
Mills
Hall |
Fourth
Floor Guest Suite 413 |
Bedroom |
The
closet shelf is 71 inches above the finish floor. A closet shelf that is a
maximum of 54 inches above the finish floor for a side reach is
required. |
MH27 |
9.1.2,
9.2.2(4), 4.25.3, 4.2.6 and Fig. 6 |
A
shelf no higher than 46 inches above the finish floor for an obstructed side
reach is required. |
222.2,
803.5 and 308 |
|
|
348 |
Mills
Hall |
Fourth
Floor Guest Suite 413 |
Bathroom |
The
pocket door hardware requires tight pinching and twisting of the wrist to
operate. Door hardware that does not require tight grasping, pinching or
twisting of the wrist to operate is required. |
MH28
and MH29 |
9.1.2,
9.2.2(3) and 4.13.9 |
|
|
|
|
350 |
Mills
Hall |
Fourth
Floor Guest Suite 413 |
Bathroom |
A
bathtub seat is not provided. A securely mounted bathtub seat is
required. |
MH31 |
9.1.2,
9.2.2(6)(e), 4.23.8, 4.20.3 and Fig. 33 |
|
|
|
|
351 |
Mills
Hall |
Fourth
Floor Guest Suite 413 |
Bathroom |
The
bathtub faucet has knob controls. Controls which do not require tight
grasping, tight pinching or twisting of the wrist to operate are
required. |
MH32 |
9.1.2,
9.2.2(6)(e), 4.23.8, 4.20.5 and 4.27.4 |
|
|
|
|
352 |
Mills
Hall |
Fourth
Floor Guest Suite 413 |
Bathroom |
The
bathtub controls are located in the center of the control wall. Offset
bathtub controls, which are located between the open edge and the midpoint of
the tub are required. |
MH32 |
9.1.2,
9.2.2(6)(e), 4.23.8 and 4.20.5 |
|
|
|
|
358 |
Reinhardt
Alumnae House |
Entrance |
Door |
A
½-inch vertical change in level is located at the threshold. A change in
level that is no higher than ¼ inch vertical or ½ inch beveled with a slope
no greater than 1:2 is required. |
RAH4 |
4.1.2(1),
4.1.3(8), 4.3.8 and 4.5.2 |
|
|
|
|
361 |
Reinhardt
Alumnae House |
Interior |
Toilet
Room Corridor |
The
clear opening width of the door is 31½ inches. The clear opening width of the
door is required to be 32 inches minimum measured between the face of the
door and the opposite stop when the door is open 90 degrees. |
RAH6 |
4.1.3(7)(b),
4.13.5 and Fig. 24(a) |
|
|
|
|
362 |
Reinhardt
Alumnae House |
Interior |
Women's
Toilet Room |
The
women's toilet room is not accessible, and a directional sign to the
designated accessible toilet room is not provided. A sign indicating the
location of the designated accessible toilet room is required. |
RAH7 |
4.1.6(3)(e)(iii) |
|
|
|
|
363 |
Reinhardt
Alumnae House |
Interior |
Unisex
Toilet Room |
The
toilet room sign is mounted more than 60 inches above the finish floor to the
centerline of the sign. A permanent room sign mounted at 60 inches above the
finish floor to the centerline of the sign is required. |
RAH7 |
4.1.3(16)(a)
and 4.30.6 |
Tactile
characters on signs shall be located between 48 inches minimum and 60 inches
maximum above the finish floor, measured to the baseline of the tactile
character. |
216.2,
703.1-5 |
|
|
364 |
Reinhardt
Alumnae House |
Interior |
Unisex
Toilet Room |
The
toilet room sign is mounted more than 60 inches above the finish floor to the
centerline of the sign. A permanent room sign mounted at 60 inches above the
finish floor to the centerline of the sign is required. |
RAH8 |
4.1.3(16)(a)
and 4.30.6 |
Tactile
characters on signs shall be located between 48 inches minimum and 60 inches
maximum above the finish floor, measured to the baseline of the tactile
character. |
216.2,
703.1-5 |
|
|
365 |
Reinhardt
Alumnae House |
Interior |
Unisex
Toilet Room |
The
force required to open the toilet room door is 10 lbf. The maximum allowable
force for opening an interior door is 5 lbf. |
none |
4.1.3(7)(b)
and 4.13.11(2)(b) |
|
|
|
|
367 |
Reinhardt
Alumnae House |
Interior |
Unisex
Toilet Room |
The
rear toilet grab bar is 24 inches long. A 36-inch long rear grab bar is
required. |
RAH10 |
4.1.3(11),
4.22.4, 4.16.4 and Fig. 29(a) |
|
|
|
|
368 |
Reinhardt
Alumnae House |
Interior |
Unisex
Toilet Room |
The space
between the wall and the rear grab bar is 2 inches. The space between the
wall and the grab bar shall be exactly 1½ inches. |
RAH10 |
4.1.3(11),
4.22.4, 4.16.4, 4.26.2 and Fig. 39(e) |
|
|
|
|