ATTACHMENT K: Program Access in Existing Facilities

 

Please Note: Paragraph 35 of the Agreement requires that within twelve months of the effective date of this Agreement, the Village will provide signage as necessary to comply with 28 C.F.R. § 35.163(b), after having surveyed all facilities that are the subject of this Agreement for the purpose of identifying those that have multiple entrances not all of which are accessible.

The technical requirements and, where appropriate, the scoping requirements of the Standards are used as a guide for determining whether a program or activity held in an existing facility is "readily accessible to and usable by" persons with disabilities and for determining what changes are necessary to make this program or activity accessible if it continues to be provided in the existing facility in question. See 28 C.F.R. §§ 35.150(b)(1), 35.151. Actions are to be completed within 24 months of the effective date of this Agreement.

The chart below lists the facilities surveyed and gives an alphanumeric code for the required remedial action. The key to these codes is found in Attachment M to this agreement.

Item #

Access Issue

Required Action

1

Village of Midlothian Town Hall Building - 14801 S. Pulaski Road

1.1

Parking - near Police Entrance and Main Entrance

1.1.a

The parking lot, which has at least 20 spaces, is inaccessible because there are no designated van accessible spaces. This lot requires at least 1 van accessible parking space.

P3

1.1.b

The designated accessible parking space on the left (facing the building) is inaccessible because it slopes 2.7%.

P7

1.1.c

The access aisle is inaccessible because it slopes 2.5% and has a cross slope of 2.2%.

P7

2

Village of Midlothian Town Hall Building - Community Room - 14801 S. Pulaski Road

2.1

Community Room

2.1.a

The community room does not have directional signage posted at its inaccessible entrance, and does not have the International Symbol of Accessibility posted at the accessible entrance.

D16

2.1.b

Although the facility contains an emergency alarm system, the alarm system is inaccessible because there are no visual alarms provided in the Community Room.

AL1

2.2

Unisex Single User Toilet Room - at Community Room

2.2.a

The toilet room sign has no symbol of access, it is not on the wall adjacent to the latch side of the door and its centerline is 56 inches above the finished floor.

TR17

2.2.b

The door is inaccessible because it requires 10 pounds of force to open.

D2

2.2.c

The pull side of the door, which is accessed through a front approach and which has both a closer and a latch, is inaccessible because it has inadequate clear space on the latch side.

D6

2.2.d

The push side of the door, which is accessed from the latch side of the door, is inaccessible because it has inadequate clear space on the latch side.

D11

2.2.e

No accessible coat hook has been provided.

TR1

2.2.f

No accessible mirror has been provided.

TR14

2.2.g

The toilet is inaccessible because the flush control is on the closed side.

SU1

2.2.h

The side and rear grab bars at the toilet are inaccessible because they are mounted 38 inches above the finished floor.

SU11

3

Village of Midlothian Town Hall Building - 14801 S. Pulaski Road

3.1

Main Entrance

3.1.a

The main entrance does not have the International Symbol of Accessibility posted at the accessible entrance.

D16

3.1.b

The route at the main entrance is inaccessible because there are 78 ½ inches of head-room provided under the hanging lamp.

AR7

 

3.2

Front Office

3.2.a

The counter at the front office is inaccessible because it protrudes into the walkway, at a height of between 27 and 80 inches, and is not detectable to blind persons using a cane.

AR8

3.3

Drinking Fountain

3.3.a

Although an accessible drinking fountain is provided, there is no drinking fountain provided for people who have difficulty bending or stooping.

DF3

4

Fire Station #2 - 14700 Homan

4.1

Entrance

4.1.a

The main entrance does not have the International Symbol of Accessibility posted at the accessible entrance.

D16

5

Raday Lodge - 3220 W. 145th Street

5.1

Parking

5.1.a

The parking lot, with a total of 110 total spaces, is inaccessible because there are only 4 designated accessible parking spaces and there are no designated van accessible spaces. This lot requires at least 5 accessible spaces, of which, at least 1 is required to be van accessible.

P3

5.2

Entrance

5.2.a

The lodge does not have directional signage posted at its inaccessible entrance, and does not have the International Symbol of Accessibility posted at the accessible entrance.

D16

5.3

Assembly/Party Area

5.3.a

The assembly area is inaccessible because a portable or permanently installed assistive listening system (ALS) is not available.

AA5

 

5.4

Women's Room with stalls

5.4.a

The women's toilet room is inaccessible because the sign is not mounted on the wall adjacent to the latch side of the door.

TR17

5.4.b

The door is inaccessible because it requires more than 5 pounds of force to open.

D2

5.4.c

The counter is inaccessible because it protrudes 13 ½ inches into the walkway at 32 inches above the finished floor and is not detectable to blind persons using a cane.

AR8

5.4.d

The side grab bar at the designated accessible toilet is inaccessible because the farther end is 48 inches from the rear wall.

ST6

5.4.e

The designated accessible toilet is inaccessible because the flush control is on the closed side.

ST2

5.4.f

The toilet paper dispenser in the designated accessible stall is inaccessible because it is mounted 44 inches from the rear wall.

ST19

5.4.g

The designated accessible toilet is inaccessible because its centerline is 14 ½ inches from the side wall.

ST17

5.4.h

The lavatory is inaccessible because the hot water pipes and drain are not insulated or otherwise configured to protect against contact.

TR12

5.5

Men's Room with stalls

5.5.a

The men's toilet room is inaccessible because the sign is on the latch side of the door with its centerline 60 inches above the finished floor.

TR17

5.5.b

The door is inaccessible because it requires more than 5 pounds of force to open.

D2

5.5.c

The towel dispenser is inaccessible because it is mounted 53 inches above the finished floor and requires an 18 inch reach over an object.

TR4

5.5.d

The side grab bar at the designated accessible toilet is inaccessible because the farther end is 48 inches from the rear wall.

ST6

5.5.e

The lavatory is inaccessible because the hot water pipes and drain are not insulated or otherwise configured to protect against contact.

TR12

5.5.f

No accessible coat hook has been provided.

TR1

6

Midlothian Historical Society - 14609 Springfield Avenue

6.1

Parking

6.1.a

The parking reserved for persons with disabilities is inaccessible because the sign is mounted too low and does not indicate that it is van accessible.

P6

6.2

Drinking Fountain

6.2.a

The fountain is inaccessible because it protrudes 13 inches into the walkway at 32 ½ inches above the finished floor and is not detectable to blind persons using a cane.

AR8

6.2.b

There is no drinking fountain provided for people who have difficulty bending or stooping.

DF3

6.3

Women's single user toilet room

6.3.a

The women's toilet room is inaccessible because the sign is mounted with its centerline 68 inches above the finished floor.

TR17

6.3.b

The door is inaccessible because it requires more than 5 pounds of force to open.

D2

6.3.c

Although the facility contains an emergency alarm system, the alarm system is inaccessible because there are no visual alarms provided in this room.

AL1

6.3.d

The towel dispenser is inaccessible because its highest operable part is mounted 56 ½ inches above the finished floor.

TR5

6.3.e

The lavatory is inaccessible because the hot water and drain pipes are not insulated or otherwise configured to protect against contact.

TR12

6.3.f

The side grab bar at the toilet is inaccessible because the farther end is 49 inches from the rear wall.

SU6

6.4

Men's single user toilet room

6.4.a

The men's toilet room is inaccessible because the sign is mounted with its centerline 65 inches above the finished floor.

TR17

6.4.b

Although the facility contains an emergency alarm system, the alarm system is inaccessible because there are no visual alarms provided in this room.

AL1

6.4.c

The lavatory is inaccessible because the hot water pipes are not insulated or otherwise configured to protect against contact.

TR12

6.4.d

The side grab bar at the toilet is inaccessible because there is an obstruction ½ inch above it.

SU8

6.5

Art Room

6.5.a

The tables in the art room are inaccessible because the top of all tables is 36 inches above the finished floor.

T1

7

Village of Midlothian Council Chambers - 14801 S. Pulaski Road

7.1

Council Chambers Room

7.1.a

Although the facility contains an emergency alarm system, the alarm system is inaccessible because there are no visual alarms provided in the Council Chambers.

AL1

7.1.b

The Council Chambers is inaccessible to persons who are deaf or hard of hearing because, although there are 80 fixed seats, there is no assistive listening system provided.

AA5

7.2

Women's single user toilet room

7.2.a

The women's toilet room is inaccessible because the sign is mounted with its centerline 54 ½ inches above the finished floor.

TR17

 

7.2.b

The door is inaccessible because it requires 8 pounds of force to open.

D2

7.2.c

No accessible coat hook has been provided.

TR1

7.2.d

No accessible mirror has been provided.

TR14

7.2.e

The soap dispenser is inaccessible because it is mounted with the controls 51 inches above the finished floor and a forward reach is required.

TR5

7.2.f

The toilet is inaccessible because the flush control is on the closed side.

SU1

7.2.g

The toilet paper dispenser is inaccessible because it is mounted 43 ½ inches from the rear wall.

SU17

7.2.i

The shelf above the side grab bar is inaccessible because it protrudes 8 inches at 57 3/4 inches above the finished floor and is not detectable to blind persons using a cane.

AR8

7.2.k

The rear grab bar at the toilet is inaccessible because it is obstructed by the paper towel holder.

SU8

7.3

Men's single user toilet room

7.3.a

The men's toilet room is inaccessible because the sign does not have the International Symbol of Accessibility.

TR17

7.3.b

The men's toilet room is inaccessible because the sign is mounted with its centerline 54 ½ inches above the finished floor.

TR17

7.3.c

The door is inaccessible because it requires 7 pounds of force to open.

D2

7.3.d

No accessible coat hook has been provided.

TR1

7.3.e

No accessible mirror has been provided.

TR14

7.3.f

The toilet is inaccessible because the flush control is on the closed side.

SU1

7.3.g

The toilet paper dispenser is inaccessible because it is mounted 44 inches from the rear wall.

SU17

7.3.h

The side grab bar is inaccessible because it is 38 inches above the finished floor.

SU11

7.3.i

The rear grab bar is inaccessible because it is 38 inches above the finished floor.

SU11

7.3.j

The rear grab bar at the toilet is inaccessible because it is obstructed by the paper towel holder.

SU8

8

Midlothian Public Works - 14801 S. Pulaski Road

8.1

Parking

8.1.a

The parking lot is inaccessible because it has no designated accessible spaces. This lot requires one van accessible space.

P3

9

Village of Midlothian Police Entrance - 14801 S. Pulaski Road

9.1

Entrance

9.1.a

The "Police" signage is not detectable to a blind person using a cane.

AR8

9.1.b

The ashtray protrudes 8 inches into the walkway at 37 inches above the finished floor and is not detectable to blind persons using a cane.

AR8

9.1.c

The exterior route is inaccessible because there is a 1 inch wide crack in the sidewalk at the threshold.

AR1

9.2

Drinking Fountain

9.2.a

Although a cup dispenser is provided, it is mounted too high above the finished floor to be within the reach range of a person using a wheelchair.

TR5, DF3

9.3

Information Counter

9.3.a

The counter is inaccessible because its top is 37 inches above the finished floor.

C6

9.4

Auxiliary Counter

9.4.a

The counter is inaccessible because its top is 39 inches above the finished floor.

C6

 

 