ATTACHMENT K: Program Access in Existing FacilitiesThe technical requirements and, where appropriate, the scoping requirements of the Standards are used as a guide for determining whether a program or activity held in an existing facility is “readily accessible to and usable by” persons with disabilities and for determining what changes are necessary to make this program or activity accessible if it continues to be provided in the existing facility in question. See 28 C.F.R. §§ 35.150(b)(1), 35.151. The chart below lists the facilities surveyed by the Department, the access issues identified during the survey, and the actions required to correct the access issues. Required actions are listed using an alphanumeric code. The key to the alphanumeric codes is provided in Attachment M to this Agreement. In order to ensure that the programs, services, and activities housed in the County’s facilities are accessible to persons with disabilities, when viewed in their entirety, the County will take the actions referenced by the alphanumeric code and described in detail in Attachment M to this Settlement Agreement within the time period specified below, which time period begins to run on the effective date of the Agreement. |
|||
Item # | Access Issue | Required Action | Completion Date |
---|---|---|---|
1. |
Courthouse, 513 Washington Ave |
|
|
1.1. |
Entrance: The building does not have directional signage posted at inaccessible entrances and does not have the International Symbol of Accessibility posted at accessible entrances. |
D10 |
12 months |
1.2. |
Women's 1st Floor Toilet Room with Stalls: |
||
1.2.1. |
The door is inaccessible because it requires 11 pounds of force to open. |
D3 |
12 months |
1.2.2. |
No accessible mirror has been provided. |
TR5 |
12 months |
1.3. |
Men's 1st Floor Toilet Room with Stalls: |
||
1.3.1. |
The door is inaccessible because it requires 10 pounds of force to open. |
D3 |
12 months |
1.3.2. |
No accessible mirror has been provided. |
TR5 |
12 months |
1.3.3. |
No accessible coat hook has been provided. |
TR3 |
12 months |
1.4. |
Drinking Fountain 1st Floor: The drinking fountain is inaccessible because it has a spout that is 41 inches high and provides 12 inches of clear knee height. |
DF1 |
18 months |
1.5. |
Constable Pct. 1/Notary (Room 101): The door is inaccessible because knob hardware is used. |
D2 |
18 months |
1.6. |
Highway Patrol (Room 103): The counter is inaccessible because it is 45 inches high. |
C1 |
12 months |
1.7. |
Justice of the Peace (Room 108): The counter is inaccessible because it is 48 inches high. |
C1 |
12 months |
1.8. |
Justice of the Peace (Room 104-D): The counter is inaccessible because it is 48 inches high. |
C1 |
12 months |
1.9. |
Sheriff's Office (Room 109A): The door is inaccessible because knob hardware is used. |
D2 |
18 months |
1.10. |
Justice of the Peace Court (Room 104-A): |
||
1.10.1. |
The door is inaccessible because it requires 17 pounds of force to open. |
D3 |
12 months |
1.11. |
Commissioners Court (Room 114): |
||
1.11.1. |
The door is inaccessible because it requires 10 pounds of force to open. |
D3 |
12 months |
1.11.2. |
The courtroom gallery, containing 50 seats, is inaccessible because there are no designated wheelchair seating areas provided. A total of two wheelchair seating areas is required. |
AA6 |
12 months |
1.11.3. |
The courtroom is inaccessible to people with hearing disabilities because, although there are 50 fixed seats, there is no assistive listening system provided.This courtroom requires two receivers. |
AA4 |
6 months |
1.12. |
Toilet Rooms Floors 2, 3, and 4: There is no signage directing people with disabilities to the accessible toilet rooms. |
TR10 |
6 months |
1.13. |
Suite 214: |
||
1.13.1. |
The route from the entrance to the judge's office is inaccessible because the entry door narrows the passage to 26 inches wide. |
AR3 |
24 months |
1.13.2. |
The doors throughout the suite are inaccessible because knob hardware is used. |
D2 |
18 months |
1.14. |
Room 207: The doors within the office are inaccessible because knob hardware is used. |
D2 |
18 months |
1.15. |
Break Room, 2nd Floor: The door is inaccessible because knob hardware is used. |
D2 |
18 months |
1.16. |
Administrator County Court at Law (Room 210): |
||
1.16.1. |
The door is inaccessible because it requires 7 pounds of force to open. |
D3 |
6 months |
1.16.2. |
The pull side of the door, which is accessed through a front approach, is inaccessible because it has no clear space on the latch side. |
D5 |
30 months |
1.17. |
170th District Court (Room 211): |
||
1.17.1. |
The courtroom is inaccessible to people with hearing disabilities because, although there is fixed seating and an audio amplification system, there is no assistive listening system provided.This courtroom requires one receiver. |
AA4 |
6 months |
1.18. |
Bailiff's Office: The door is inaccessible because knob hardware is used. |
D2 |
18 months |
1.19. |
Jury Room (213): |
||
1.19.1. |
The door is inaccessible because knob hardware is used. |
D2 |
18 months |
1.19.2. |
The door is inaccessible because it requires 6 pounds of force to open. |
D3 |
6 months |
1.20. |
Elevator: The elevator is inaccessible because the emergency system requires voice communication to operate. |
E7 |
24 months |
1.21. |
54th District Court (3rd Floor): |
||
1.21.1. |
There is no signage informing the public of the availability of an assistive listening system. |
AA3 |
6 months |
1.22. |
Jury Room (Room 304): |
||
1.22.1. |
The door is inaccessible because knob hardware is used. |
D2 |
18 months |
1.22.2. |
The table is inaccessible because it provides 26 inches of clear knee height. |
DW1 |
6 months |
1.23. |
19th Court Administrator (3rd Floor): |
||
1.23.1. |
The door is inaccessible because knob hardware is used. |
D2 |
18 months |
1.23.2. |
The door is inaccessible because it requires 9 pounds of force to open. |
D3 |
6 months |
1.23.3. |
The counter is inaccessible because it is 41 1/2 inches high. |
C1 |
12 months |
1.24. |
19th District Court (3rd Floor): |
||
1.24.1. |
The courtroom is inaccessible to people with hearing disabilities because there is no assistive listening system provided. |
AA4 |
6 months |
1.25. |
414 District Court (3rd Floor): |
||
1.25.1. |
The courtroom is inaccessible to people with hearing disabilities because there is no assistive listening system provided. |
AA4 |
6 months |
1.26. |
414 District Court Jury Room (3rd Floor): |
||
1.26.1. |
The door is inaccessible because it requires 6 pounds of force to open. |
D3 |
6 months |
1.26.2. |
The door is inaccessible because knob hardware is used. |
D2 |
18 months |
1.26.3. |
The jury room is inaccessible to people with hearing disabilities because there is no assistive listening system provided. |
AA4 |
6 months |
1.27. |
Tenth Court of Appeals (4th Floor): The microphone and timer on the podium are inaccessible because they aremounted greater than 54 inches high. |
CT4 |
12 months |
1.28. |
Grand Jury and Conference Room (4th Floor): |
||
1.28.1. |
The route is inaccessible because the room is accessed by steps. |
AR2; LF1 |
24 months |
1.28.2. |
The grand jury room is inaccessible to people with hearing disabilities because there is no assistive listening system provided. |
AA4 |
6 months |
1.28.3. |
The drinking fountain is inaccessible because the spout is mounted greater than 36 inches high and no other means of providing water is available. |
DF1 |
24 months |
1.29. |
Law Library (4th Floor): |
||
1.29.1. |
The route into the room is inaccessible because it is accessed by steps. |
AR2 |
24 months |
1.29.2. |
The computer desk is inaccessible because it provides 25 1/2 inches of clear knee height. |
DW1 |
6 months |
2. |
Courthouse Annex, 219 N 6th Street |
||
2.1. |
Accessible Route Annex Catwalk (3rd Floor): |
||
2.1.1. |
The first door from the courthouse to the annex via the catwalk is inaccessible because it has an opening width of 31 inches. |
D14 |
24 months |
2.1.2. |
The second door from the courthouse to the annex via the catwalk is inaccessible because it has an opening width of 30 inches. |
D14 |
24 months |
2.1.3. |
The third door from the courthouse to the annex via the catwalk is inaccessible because it has an opening width of 29 inches. |
D14 |
24 months |
2.1.4. |
The double doors between the courthouse and the annex are inaccessible because each leaf is 27 inches wide. |
D13 |
24 months |
2.1.5. |
The double doors between the courthouse and the annex are inaccessible because a single leaf requires 8 pounds of force to open. |
D3 |
24 months |
2.2. |
District Clerk, Criminal Division: The counter is inaccessible because it is 30 inches wide. |
C1 |
18 months |
2.3. |
District Clerk, Civil Division: The counter is inaccessible because it is 30 inches wide. |
C1 |
18 months |
2.4. |
Elevator: The elevator is inaccessible because the emergency system requires voice communication to operate. |
E7 |
24 months |
2.5. |
Drinking Fountain, 2nd Floor: |
||
2.5.1. |
The wall-mounted drinking fountain is inaccessible because it provides only 24 inches of clear knee height. |
DF4 |
18 months |
2.5.2. |
Although a designated accessible drinking fountain is provided, there is no drinking fountain provided for people who have difficulty bending or stooping. |
DF3 |
18 months |
2.6. |
2nd Floor, Women's Toilet Room with Stalls: |
||
2.6.1. |
The paper towel dispenser protrudes into the walkway and is not detectable to blind persons using a cane. |
AR7 |
12 months |
2.6.2. |
The toilet room does not have an accessible toilet and there is no directional signage to the closest accessible toilet room on the first floor. |
TR10 |
12 months |
2.7. |
2nd Floor, Men's Toilet Room with Stalls: |
||
2.7.1. |
The paper towel dispenser protrudes into the walkway and is not detectable to blind persons using a cane. |
AR7 |
12 months |
2.7.2. | The stall door swings into the clear floor space at the urinal and there is no directional signage to the closest accessible toilet room on the first floor. |
TR10 |
12 months |
3. |
Parking for County IV-D Court and County Welfare Parking, 619 Washington Ave |
||
3.1. |
The parking lot, with a total of 73 parking spaces, is inaccessible because there are no accessible parking spaces provided. This lot requires one van accessible space and two standard accessible spaces. |
P1 |
24 months |
4. |
Fairgrounds - Coliseum, 4613 Bosque Road |
||
4.1. |
Men's Toilet Room with Stalls (C155): |
||
4.1.1. |
The door is inaccessible because it requires 11 pounds of force to open. |
D3 |
12 months |
4.1.2. |
The paper towel dispenser protrudes into the walkway and is not detectable to blind persons using a cane. |
AR7 |
12 months |
4.2. |
Women's Toilet Room with Stalls (C180): The door is inaccessible because it requires 11 pounds of force to open. |
D3 |
12 months |
4.3. |
Men's Toilet Room with Stalls (C188): |
||
4.3.1. |
The door is inaccessible because it requires 11 pounds of force to open. |
D3 |
12 months |
4.3.2. |
The soap dispenser protrudes into the walkway and is not detectable to blind persons using a cane. |
AR7 |
12 months |
4.3.3. |
The designated accessible toilet is inaccessible because the side grab bar is mounted 13 inches from the rear wall. |
STR17 |
12 months |
4.4. |
Unisex Single User Toilet Room (C165): |
||
4.4.1. |
The door is inaccessible because it requires 8 pounds of force to open. |
D3 |
12 months |
4.4.2. |
The toilet is inaccessible because its centerline is 19 inches from the side wall. |
TR7 |
18 months |
4.5. |
Arena: The arena, containing 5605 seats, is inaccessible because approximately 25 wheelchair seating areas are provided. A total of 40 wheelchair seating areas is required. |
AA6 |
30 months |
4.6. |
Back Porch Club Ticket Counter: The counter protrudes into the walkway and is not detectable to blind persons using a cane. |
AR7 |
18 months |
4.7. |
Back Porch Club - Women's Toilet Room with Stalls: The door is inaccessible because it requires 10 pounds of force to open. |
D3 |
12 months |
4.8. |
Back Porch Club - Men's Toilet Room with Stalls: |
||
4.8.1. |
The door is inaccessible because it requires 10 pounds of force to open. |
D3 |
12 months |
4.8.2. |
The paper towel dispenser protrudes into the walkway and is not detectable to blind persons using a cane. |
AR7 |
12 months |
4.8.3. |
The lavatory is inaccessible because it has twist-type hardware. |
LS4 |
12 months |
4.8.4. |
The urinal is inaccessible because the rim is 18 inches high. |
TR8 |
24 months |
4.8.5. |
The designated accessible toilet is inaccessible because its centerline is 19 inches from the side wall. |
TR7 |
18 months |
5. |
Fairgrounds -Creative Arts Building, 4613 Bosque |
||
5.1. |
Ramp: The ramp to the stage is inaccessible because it has a slope of up to 25.3% and has no handrails. |
R4; R2 |
24 months |
5.2. |
Women's Toilet Room with Stalls: |
||
5.2.1. |
The toilet room sign is mounted with the baseline of the highest tactile characters 62 inches above the finish floor. |
TR11 |
24 months |
5.2.2. |
The door is inaccessible because it requires 10 pounds of force to open. |
D3 |
24 months |
5.2.3. |
No accessible mirror has been provided. |
TR5 |
24 months |
5.2.4. |
The hand dryer protrudes into the walkway and is not detectable to blind persons using a cane. |
AR7 |
24 months |
5.2.5. |
The lavatory is inaccessible because the hot water pipes are not insulated or otherwise configured to protect against contact. |
LS2 |
24 months |
5.2.6. |
No accessible coat hook has been provided. |
TR3 |
24 months |
5.2.7. |
The designated accessible toilet is inaccessible because the flush control is on the closed side. |
TR4 |
24 months |
5.2.8. |
The designated accessible toilet is inaccessible because the side grab bar is obstructed by the toilet paper dispenser. |
TR15 |
24 months |
5.2.9. |
The ambulatory stall is inaccessible because it is 38 inches wide, the top of the toilet seat is 20 inches high, and the coat hook is 58 inches high. |
TR22 |
24 months |
5.3. |
Men's Toilet Room with Stalls: |
||
5.3.1. |
The door is inaccessible because it requires 14 pounds of force to open. |
D3 |
24 months |
5.3.2. |
No accessible mirror has been provided. |
TR5 |
24 months |
5.3.3. |
The lavatory is inaccessible because the hot water pipes are not insulated or otherwise configured to protect against contact. |
LS2 |
24 months |
5.3.4. |
The designated accessible toilet is inaccessible because its centerline is 19 inches from the side wall. |
TR7 |
24 months |
5.3.5. |
The designated accessible toilet is inaccessible because the flush control is on the closed side. |
TR4 |
24 months |
5.3.6. |
No accessible coat hook has been provided. |
TR3 |
24 months |
5.3.7. |
The designated accessible toilet is inaccessible because the side grab bar is obstructed by the toilet paper dispenser. |
TR15 |
24 months |
5.4. |
Drinking Fountain between Exhibit and Creative Arts Building: |
||
5.4.1. |
The drinking fountain protrudes into the walkway and is not detectable to blind persons using a cane. |
AR7 |
24 months |
5.4.2. |
Although a designated accessible drinking fountain is provided, there is no drinking fountain provided for people who have difficulty bending or stooping. |
DF3 |
24 months |
5.5. |
Women's Toilet Room with Stalls (between Exhibit and Creative Arts): |
||
5.5.1. |
The toilet room sign is mounted on the door and has no raised or Braille characters. |
TR11 |
24 months |
5.5.2. |
The door is inaccessible because it requires 7 pounds of force to open. |
D3 |
24 months |
5.5.3. |
The paper towel dispenser protrudes into the walkway and is not detectable to blind persons using a cane. |
AR7 |
24 months |
5.5.4. |
The lavatory is inaccessible because the hot water pipes are not insulated or otherwise configured to protect against contact. |
LS2 |
24 months |
5.5.5. |
The designated accessible toilet is inaccessible because its centerline is 21 inches from the side wall. |
TR7 |
24 months |
5.5.6. |
The designated accessible toilet is inaccessible because the flush control is on the closed side. |
TR4 |
24 months |
5.5.7. |
The designated accessible toilet is inaccessible because the side grab bar is obstructed by the toilet paper dispenser. |
TR15 |
24 months |
5.5.8. |
The designated accessible toilet is inaccessible because the side grab bar is mounted 37 inches high. |
TR19 |
24 months |
5.5.9. |
The ambulatory stall is inaccessible because it is 38 inches wide, the toilet is not centered within the stall, and no accessible coat hook is provided. |
TR22 |
24 months |
5.6. |
Men's Toilet Room with Stalls: |
||
5.6.1. |
The door is inaccessible because it requires 8 pounds of force to open. |
D3 |
24 months |
5.6.2. |
The paper towel dispenser protrudes into the walkway and is not detectable to blind persons using a cane. |
AR7 |
24 months |
5.6.3. |
The lavatory is inaccessible because the hot water pipes are not insulated or otherwise configured to protect against contact. |
LS2 |
24 months |
5.6.4. |
The urinal is inaccessible because the flush control is 46 inches high. |
TR8 |
24 months |
5.6.5. |
The designated accessible toilet is inaccessible because the flush control is on the closed side. |
TR4 |
24 months |
5.6.6. |
No accessible coat hook has been provided. |
TR3 |
24 months |
5.6.7. |
The designated accessible toilet is inaccessible because the side grab bar is obstructed by the toilet paper dispenser. |
TR15 |
24 months |
6. |
Fairgrounds -Exhibits Hall, 4613 Bosque |
||
6.1. |
GE Office: |
||
6.1.1. |
The door is inaccessible because knob hardware is used. |
D2 |
12 months |
6.1.2. |
The door is inaccessible because there is a 1 1/2 inch high threshold. |
D12 |
12 months |
6.1.3. |
The counter is inaccessible because it is 42 inches high. |
C1 |
12 months |
6.2. |
Concession Counter: The counter is inaccessible because it is 42 inches high. |
C1 |
12 months |
7. |
Fairgrounds- Show Pavilion, 4613 Bosque |
||
7.1. |
Women's Toilet Room with Stalls (5.111): |
||
7.1.1. |
The door is inaccessible because it requires 15 pounds of force to open. |
D3 |
24 months |
7.1.2. |
The paper towel dispenser protrudes into the walkway and is not detectable to blind persons using a cane. |
AR7 |
24 months |
7.1.3. |
The toilet paper dispenser in the designated accessible stall is more than 7 to 9 inches in front of the front of the toilet. |
TR6 |
24 months |
7.2. |
Men's Toilet Room with Stalls (5.110): |
||
7.2.1. |
The door is inaccessible because it requires 12 pounds of force to open. |
D3 |
24 months |
7.2.2. |
The paper towel dispenser protrudes into the walkway and is not detectable to blind persons using a cane. |
AR7 |
24 months |
7.2.3. |
The urinal is inaccessible because the rim is 20 inches high. |
TR8 |
24 months |
7.2.4. |
The designated accessible toilet is inaccessible because the side grab bar is obstructed by the toilet paper dispenser. |
TR15 |
24 months |
7.3. |
Women's Locker Room, Show Pavilion: |
||
7.3.1. |
The toilet room sign is mounted on the door and has no raised or Braille characters. |
TR11 |
24 months |
7.3.2. |
The door is inaccessible because it requires 12 pounds of force to open. |
D3 |
24 months |
7.3.3. |
The toilet paper dispenser in the designated accessible stall is mounted more than 7 to 9 inches in front of the toilet. |
TR6 |
24 months |
7.3.4. |
The door into the shower room is inaccessible because it requires 16 pounds of force to open. |
D3 |
24 months |
7.3.5. |
The shower is inaccessible because no shower spray unit is provided and the shower head is higher than 48 inches above the finished floor. |
B7 |
24 months |
7.3.6. |
The bench is inaccessible because it is 11 inches deep and it does not provide clear floor space alongside to allow a transfer. |
LR2 |
24 months |
7.4. |
Men's Locker Room, Show Pavilion: |
||
7.4.1. |
The door is inaccessible because it requires 15 pounds of force to open. |
D3 |
24 months |
7.4.2. |
The lavatory is inaccessible because the hot water pipes are not insulated or otherwise configured to protect against contact. |
LS2 |
24 months |
7.4.3. |
The lavatory is inaccessible because it has twist-type hardware. |
LS4 |
24 months |
7.4.4. |
The urinal is inaccessible because the rim is 18 inches high. |
TR8 |
24 months |
7.5. |
Women's Toilet Room with Stalls (2.137): |
||
7.5.1. |
The door is inaccessible because it requires 14 pounds of force to open. |
D3 |
24 months |
7.5.2. |
The paper towel dispenser protrudes into the walkway and is not detectable to blind persons using a cane. |
AR7 |
24 months |
7.5.3. |
The toilet paper dispenser in the designated accessible stall is mounted more than 7 to 9 inches in front of the toilet. |
TR6 |
24 months |
7.5.4. |
The designated accessible toilet is inaccessible because the side grab bar is obstructed by the toilet paper dispenser. |
TR15 |
24 months |
7.6. |
Men's Toilet Room with Stalls (2.138): |
||
7.6.1. |
The toilet room sign does not have Braille or raised characters. |
TR11 |
24 months |
7.6.2. |
The door is inaccessible because it requires 14 pounds of force to open. |
D3 |
24 months |
7.6.3. |
The paper towel dispenser protrudes into the walkway and is not detectable to blind persons using a cane. |
AR7 |
24 months |
7.6.4. |
The urinal is inaccessible because the rim is 18 inches high. |
TR8 |
24 months |
7.7. |
Drinking Fountain: The wall-mounted drinking fountain is inaccessible because it provides only 26 inches of clear knee height. |
DF4 |
24 months |
7.8. |
Men's Dressing Room 2.144: |
||
7.8.1. |
The shower is inaccessible because no shower spray unit is provided and the shower head is higher than 48 inches above the finished floor. |
B7 |
24 months |
7.8.2. |
The bench is inaccessible because it is 22 inches deep and it does not provide clear floor space alongside to allow a transfer. |
LR2 |
24 months |
8. |
Fairgrounds - Stand Alone Toilet Rooms, 4613 Bosque |
||
8.1. |
Women’s Toilet Room |
||
8.1.1. |
The toilet room sign is mounted above the door and has no raised or Braille characters. |
TR11 |
24 months |
8.1.2. |
The door is inaccessible because it requires 10 pounds of force to open. |
D3 |
24 months |
8.1.3. |
The paper towel dispenser protrudes into the walkway and is not detectable to blind persons using a cane. |
AR7 |
24 months |
8.1.4. |
The lavatory is inaccessible because the hot water pipes are not insulated or otherwise configured to protect against contact. |
LS4 |
24 months |
8.2. |
Men’s Toilet Room: |
||
8.2.1. |
There is no signage directing people with disabilities to the accessible toilet rooms. |
TR10 |
24 months |
8.2.2. |
The paper towel dispenser protrudes into the walkway and is not detectable to blind persons using a cane. |
AR7 |
24 months |
8.2.3. |
The lavatory is inaccessible because the bottom of the apron is 27 1/2 inches high. |
LS3 |
24 months |
8.2.4. |
The lavatory is inaccessible because it has twist-type hardware. |
LS4 |
24 months |
8.2.5. |
The urinal is inaccessible because the rim is 20 inches high. |
TR8 |
24 months |
8.2.6. |
The designated accessible stall is incorrectly configured as an ambulatory stall, and there is no standard accessible stall provided. |
TR1 |
24 months |
9. |
Fairgrounds- Parking, 4613 Bosque |
||
9.1. |
South Parking: The designated accessible parking is inaccessible because it lacks vertical signage. |
P3 |
24 months |
9.2. |
East Parking (unpaved): The parking lot is inaccessible because there is no designated accessible parking. |
P1 |
24 months |
9.3. |
West Parking (near West A): The parking lot is inaccessible because there are no van accessible spaces provided and not all the designated accessible spaces have vertical signs. |
P3; P5 |
24 months |
9.4. |
West Parking (near West B): The parking lot is inaccessible because there are no van accessible spaces provided and not all the designated accessible spaces have vertical signs. |
P3; P5 |
24 months |
9.5. |
West Parking (near Coliseum): The parking lot is inaccessible because there are no van accessible spaces provided and not all the designated accessible spaces have vertical signs. |
P3; P5 |
24 months |
9.6. |
West Parking (near ticket booth across from Coliseum): The parking lot is inaccessible because there are no van accessible spaces provided and not all the designated accessible spaces have vertical signs. |
P3; P5 |
24 months |
9.7. |
Ticket booth: |
||
9.7.1. |
The counter is inaccessible because it is 32 inches wide. |
C1 |
30 months |
9.7.2. |
The route directly in front of the ticket window is inaccessible because it has a slope of 8.9% and a cross slope of 3.3%. |
AR2 |
30 months |
10. |
Justice of the Peace Precinct 7, 929 Elm Street, Waco |
||
10.1. |
Parking:The parking lot, with a total of 48 parking spaces, is inaccessible because it has no van accessible parking space, and two of the designated accessible spaces have cross slopes between 3.3% and 5.1%. This lot requires 1 van accessible space and 1 standard accessible space. |
P5; P4 |
24 months |
10.2. |
Interior Doors with Closers: The doors throughout the facility are inaccessible because they require more than 5 pounds of force to open. |
D3 |
18 months |
10.3. |
Reception Counter |
||
10.3.1. |
The counter is inaccessible because it is 41 inches high. |
C1 |
18 months |
10.3.2. |
The counter protrudes into the walkway and is not detectable to blind persons using a cane. |
AR7 |
18 months |
11. |
Tradinghouse Reservoir Park |
||
11.1. |
There is no designated accessible parking provided. |
P1 |
30 months |
11.2. |
There is no accessible route to the covered pavilion. |
AR1 |
30 months |
12. |
Justice of the Peace Precinct 5, 307 S Madison, McGregor |
||
12.1. |
Entrance: |
||
12.1.1. |
The inner vestibule door is inaccessible because it requires 9 pounds of force to open. |
D3 |
24 months |
12.1.2. |
The door is inaccessible because the vestibule is not sufficiently deep. |
D4 |
24 months |
12.2. |
Route to courtroom: The route to the courtroom is inaccessible because the path narrows to 31 inches wide. |
AR3 |
24 months |
12.3. |
Women’s Single User Toilet Room: |
||
12.3.1. |
The toilet room sign is mounted on the door and has no raised or Braille characters. |
TR11 |
24 months |
12.3.2. |
The door is inaccessible because it has an opening width of 28 inches. |
D14 |
24 months |
12.3.3. |
The door is inaccessible because knob hardware is used. |
D2 |
24 months |
12.3.4. |
The push side of the door, which is accessed from the hinge side of the door, is inaccessible because it has only 16 inches of clear depth. |
D5 |
24 months |
12.3.5. |
No accessible coat hook has been provided. |
TR3 |
24 months |
12.3.6. |
No accessible mirror has been provided. |
TR5 |
24 months |
12.3.7. |
The lavatory is inaccessible because there is no knee space clearance. |
LS3 |
24 months |
12.3.8. |
The lavatory is inaccessible because it has twist-type hardware. |
LS4 |
24 months |
12.3.9. |
The toilet is inaccessible because there is no clear floor space around the toilet to allow a transfer, the seat is 16 inches high, the centerline of the toilet is 21 1/2 from the side wall, and the flush control is mounted on the “closed” side of the toilet. |
TR2 |
24 months |
12.3.10. |
The toilet paper dispenser is inaccessible because it is mounted on the rear wall. |
TR6 |
24 months |
12.3.11. |
The toilet is inaccessible because there are no grab bars provided. |
TR18 |
24 months |
12.4. |
Men’s Single User Toilet Room: |
||
12.4.1. |
The toilet room sign is mounted on the door and has no raised or Braille characters. |
TR11 |
24 months |
12.4.2. |
The door is inaccessible because it has an opening width of 28 inches. |
D14 |
24 months |
12.4.3. |
The door is inaccessible because knob hardware is used. |
D2 |
24 months |
12.4.4. |
The toilet room door swings into the required clear floor space at the lavatory. |
TR12 |
24 months |
12.4.5. |
No accessible mirror has been provided. |
TR5 |
24 months |
12.4.6. |
The lavatory is inaccessible because the hot water pipes are not insulated or otherwise configured to protect against contact. |
LS2 |
24 months |
12.4.7. |
The lavatory is inaccessible because it has twist-type hardware. |
LS4 |
24 months |
12.4.8. |
The toilet is inaccessible because the top of the seat is 16 inches high. |
TR9 |
24 months |
12.4.9. |
The toilet is inaccessible because its centerline is 22 inches from the side wall. |
TR7 |
24 months |
12.4.10. |
The toilet paper dispenser is inaccessible because it is mounted on the rear wall. |
TR6 |
24 months |
12.4.11. |
The toilet is inaccessible because there are no grab bars provided. |
TR18 |
24 months |
12.5. |
Courtroom: |
||
12.5.1. |
The door is inaccessible because knob hardware is used. |
D2 |
24 months |
12.5.2. |
The judge’s bench and witness chair are inaccessible because they can be accessed only by steps. |
AA8 |
24 months |
12.6. |
Drinking Fountain: |
||
12.6.1. |
The drinking fountain is inaccessible because it has a spout that is 49 inches high. |
DF3 |
24 months |
12.6.2. |
The wall-mounted drinking fountain is inaccessible because it provides no clear knee space height. |
DF4 |
24 months |
13. |
Justice of the Peace Precinct 3, 201 N Reagan Street, West |
||
13.1. |
Parking: The parking lot, with a total of 5 parking spaces is inaccessible because there is no accessible parking.This lot requires one van accessible space. |
P1 |
24 months |
13.2. |
Exterior Route: The route from the parking lot to the entrance is inaccessible because it slopes up to 7.9%. |
AR1 |
24 months |
13.3. |
Interior Route - Lobby: The route between the chairs and mail shelf is inaccessible because there is 27 inches of clear width space. |
AR3 |
3 months |
13.4. |
Drinking Fountain: The free standing drinking fountain is inaccessible because it does not provide sufficient clear floor space. |
AR10 |
3 months |
13.5. |
Courtroom: |
||
13.5.1. |
The witness stand and jury box are inaccessible because they can be accessed only by steps. |
AA8 |
24 months |
13.5.2. |
The route to the witness stand is inaccessible because it is only 28 1/2 inches wide. |
AR3 |
24 months |
13.5.3. |
The courtroom, containing 24 seats, is inaccessible because there are no wheelchair seating areas provided. A total of one wheelchair seating area is required. |
AA6 |
24 months |
13.5.4. |
The courtroom is inaccessible to people with hearing disabilities because, although there is fixed seating and an audio amplification system, there is no assistive listening system provided.This courtroom requires one receiver. |
AA4 |
6 months |
13.6. |
Unisex Single User Toilet Room: |
||
13.6.1. |
The lavatory is inaccessible because the bottom of the apron is 27 1/4 inches high. |
LS3 |
24 months |
13.6.2. |
The lavatory is inaccessible because the hot water pipes are not insulated or otherwise configured to protect against contact. |
LS2 |
24 months |
13.6.3. |
The toilet is inaccessible because its centerline is 19 inches from the side wall. |
TR7 |
24 months |
13.6.4. |
The toilet is inaccessible because the flush control is on the closed side. |
TR4 |
24 months |
13.6.5. |
The toilet is inaccessible because the far end of the side grab bar is mounted 49 1/2 inches from the rear wall. |
TR17 |
24 months |
13.6.6. |
The toilet is inaccessible because the side grab bar is mounted 1 inch from the wall. |
TR20 |
24 months |
13.6.7. |
The toilet is inaccessible because the rear grab bar is 24 inches long and mounted 6 1/2 inches from the side wall. |
TR14 |
24 months |
13.6.8. |
The toilet is inaccessible because the rear grab bar is obstructed by the toilet tank. |
TR15 |
24 months |
13.7. |
Route from courtroom to constable's office: |
||
13.7.1. |
The route is inaccessible because the clear floor space width is 27 inches. |
AR3 |
24months |
13.7.2. |
The door is inaccessible because knob hardware is used. |
D2 |
24 months |
14. |
Probation Department, 504 N 6th Street |
||
14.1. |
Parking: |
||
14.1.1. |
The designated accessible parking is inaccessible because it slopes up to 8.6%. |
P4 |
30 months |
14.1.2. |
The designated accessible parking is inaccessible because it lacks vertical signage. |
P3 |
30 months |
14.2. |
Conference Room (117A): |
||
14.2.1. |
The door is inaccessible because it requires 10 pounds of force to open. |
D3 |
24 months |
14.2.2. |
The table is inaccessible because it provides 25 1/2 inches of clear knee height. |
DW1 |
24 months |
14.3. |
Women's Toilet Room with Stalls (UA Testing Area): |
||
14.3.1. |
The toilet room sign is mounted on the door and has no raised or Braille characters. |
TR11 |
24 months |
14.3.2. |
No accessible mirror has been provided. |
TR5 |
24 months |
14.3.3. |
The designated accessible toilet stall is inaccessible because it is 60 inches long and 40 inches wide. |
TR2 |
24 months |
14.3.4. |
The designated accessible toilet is inaccessible because its centerline is 20 inches from the side wall. |
TR7 |
24 months |
14.3.5. |
No accessible coat hook has been provided. |
TR3 |
24 months |
14.3.6. |
The designated accessible toilet is inaccessible because the side grab bar is 24 inches long and it is mounted 20 inches from the rear wall with the far end mounted 44 inches from the rear wall. |
TR17 |
24 months |
14.4. |
Men's Toilet Room with Stalls (UA Testing Area): |
||
14.4.1. |
The toilet room sign is mounted on the door and has no raised or Braille characters. |
TR11 |
24 months |
14.4.2. |
No accessible mirror has been provided. |
TR5 |
24 months |
14.4.3. |
The urinal is inaccessible because the rim is 18 inches high. |
TR8 |
24 months |
14.4.4. |
The designated accessible toilet is inaccessible because its centerline is 20 inches from the side wall. |
TR7 |
24 months |
14.4.5. |
The designated accessible toilet is inaccessible because the far end of the side grab bar is mounted 44 inches from the rear wall. |
TR17 |
24 months |
14.5. |
Drinking Fountain: Although a designated accessible drinking fountain is provided, there is no drinking fountain provided for people who have difficulty bending or stooping. |
DF3 |
24 months |
14.6. |
Kitchen/Conference/ Training Room: |
||
14.6.1. |
The door is inaccessible because it requires 7 pounds of force to open. |
D3 |
24 months |
14.6.2. |
The kitchen sink is inaccessible because the controls require twisting of the wrist to operate. |
LS4 |
24 months |
14.7. |
Women's Toilet Room with Stalls (Altered): |
||
14.7.1. |
The door is inaccessible because it requires 14 pounds of force to open. |
D3 |
24 months |
14.7.2. |
No accessible mirror has been provided. |
TR5 |
24 months |
14.7.3. |
The lavatory is inaccessible because the hot water pipes are not insulated or otherwise configured to protect against contact. |
LS2 |
24 months |
14.7.4. |
The designated accessible toilet is inaccessible because its centerline is 19 inches from the side wall. |
TR7 |
24 months |
14.7.5. |
The designated accessible toilet is inaccessible because the side grab bar is 36 inches long and the far end is mounted 40 inches from the rear wall. |
TR17 |
24 months |
14.7.6. |
There is no rear grab bar provided at the designated accessible toilet. |
TR13 |
24 months |
14.8. |
Men's Toilet Room with Stalls (Altered): |
||
14.8.1. |
The door is inaccessible because it requires 14 pounds of force to open. |
D3 |
24 months |
14.8.2. |
The lavatory is inaccessible because it has twist-type hardware. |
LS4 |
24 months |
14.8.3. |
The designated accessible stall is incorrectly configured as an ambulatory stall, and there is no standard accessible stall provided. |
TR1 |
24 months |
14.8.4. |
No accessible coat hook has been provided. |
TR3 |
24 months |
14.9. |
Drinking Fountain: Although a designated accessible drinking fountain is provided, there is no drinking fountain provided for people who have difficulty bending or stooping. |
DF3 |
24 months |
14.10. |
Classroom 101A: |
||
14.10.1. |
The door is inaccessible because it requires 10 pounds of force to open. |
D3 |
24 months |
14.10.2. |
The table is inaccessible because it provides 25 1/2 inches of clear knee height. |
DW1 |
6 months |
14.11. |
Drinking Fountain - Lobby: The drinking fountain protrudes into the walkway and is not detectable to blind persons using a cane. |
AR7 |
24 months |
14.12. |
Women's Toilet Rooms with Stalls - Lobby: |
||
14.12.1. |
The toilet room sign is mounted on the door and has no raised or Braille characters. |
TR11 |
24 months |
14.12.2. |
The lavatory is inaccessible because there is no knee or toe space clearance. |
LS3 |
24 months |
14.12.3. |
The lavatory is inaccessible because it has twist-type hardware. |
LS4 |
24 months |
14.12.4. |
The designated accessible stall is incorrectly configured as an ambulatory stall, and there is no standard accessible stall provided. |
TR1 |
24 months |
14.13. |
Men's Toilet Room with Stalls - Lobby: |
||
14.13.1. |
The toilet room sign is mounted on the door and has no raised or Braille characters. |
TR11 |
24 months |
14.13.2. |
The lavatory is inaccessible because there is no knee or toe space clearance. |
LS3 |
24 months |
14.13.3. |
The urinal is inaccessible because the rim is 18 inches high. |
TR8 |
24 months |
14.13.4. |
The designated accessible stall is incorrectly configured as an ambulatory stall, and there is no standard accessible stall provided. |
TR1 |
24 months |
14.14. |
Entrance: The interior vestibule door is inaccessible because it requires 10 pounds of force to open. |
D3 |
24 months |
15. |
County Extension Office, 420 N 6th Street |
||
15.1. |
Unisex Single User Toilet Room: |
||
15.1.1. |
The toilet room sign has no raised or Braille characters. |
TR11 |
24 months |
15.1.2. |
The door is inaccessible because knob hardware is used. |
D2 |
24 months |
15.1.3. |
The light switch is inaccessible because it is mounted 77 inches high above the lavatory. |
CT3 |
24 months |
15.1.4. |
No accessible mirror has been provided. |
TR5 |
24 months |
15.1.5. |
The lavatory is inaccessible because the hot water pipes are not insulated or otherwise configured to protect against contact. |
LS2 |
24 months |
15.1.6. |
The toilet is inaccessible because there is insufficient clear floor space provided. |
TR24 |
24 months |
15.1.7. |
The toilet is inaccessible because the top of the seat is 16 inches high. |
TR9 |
24 months |
15.1.8. |
The toilet is inaccessible because its centerline is 13 1/2 inches from the side wall. |
TR7 |
24 months |
15.1.9. |
The toilet is inaccessible because the flush control is on the closed side. |
TR4 |
24 months |
15.1.10. |
The toilet is inaccessible because the side grab bar is 24 inches long and its far end mounted 27 inches from the rear wall. |
TR17 |
24 months |
15.1.11. |
The toilet is inaccessible because there is no rear grab bar provided. |
TR13 |
24 months |
15.1.12. |
The shelf protrudes into the walkway and is not detectable to blind persons using a cane. |
AR7 |
24 months |
15.2. |
Doors: The doors throughout the building is inaccessible because knob hardware is used. |
D2 |
24 months |
15.3. |
Ag Life Extension Meeting Room: |
||
15.3.1. |
The door is inaccessible because it requires 10 pounds of force to open. |
D3 |
24 months |
15.3.2. |
The wall mounted telephone is inaccessible because it is mounted with the controls 65 inches high. |
CT4 |
24 months |
15.4. |
Reception Area Counter: The counter is inaccessible because it is 42 inches high. |
C1 |
24 months |
15.5. |
Parking: The designated accessible parking is inaccessible because it lacks vertical signage. |
P3 |
24 months |
16. |
MHMR Crisis Center, 1200 Clifton Street |
||
16.1. |
Parking: |
||
16.1.1. |
The parking closest to the main entrance is inaccessible because there are no van accessible access aisles. |
P6 |
30 months |
16.1.2. |
The curb ramp at the parking closest to the main entrance is inaccessible because it has a slope of 9.6% and has no flared sides. |
AR4 |
30 months |
16.2. |
Main Entrance: The door is inaccessible because the door hardware requires tight grasping, pinching, or twisting of the wrist. |
D2 |
12 months |
16.3. |
Unisex Single User Toilet Room (Lobby): |
||
16.3.1. |
The toilet room sign is mounted on the door and has no raised or Braille characters. |
TR11 |
12 months |
16.3.2. |
The door is inaccessible because knob hardware is used. |
D2 |
12 months |
16.3.3. |
The lavatory is inaccessible because the hot water pipes are not insulated or otherwise configured to protect against contact. |
LS2 |
12 months |
16.3.4. |
The toilet paper dispenser is inaccessible because it is mounted 43 inches from the rear wall. |
TR6 |
12 months |
16.3.5. |
The toilet is inaccessible because there is no side grab bar provided. |
TR16 |
12 months |
16.3.6. |
The toilet is inaccessible because the rear grab bar is obstructed by the toilet seat cover dispenser. |
TR15 |
12 months |
16.4. |
MCOT (Mobile Crisis Outreach Team): The doors in this area are inaccessible because knob hardware is used. |
D2 |
12 months |
16.4.1. |
Men's Single User Toilet Room (Room 136): |
||
16.4.1(1) |
The toilet room sign is mounted on the door and has no raised or Braille characters. |
TR11 |
12 months |
16.4.1(2) |
The door is inaccessible because knob hardware is used. |
D2 |
12 months |
16.4.1(3) |
The lavatory is inaccessible because the hot water pipes are not insulated or otherwise configured to protect against contact. |
LS2 |
12 months |
16.4.1(4) |
The toilet paper dispenser is inaccessible because it is mounted 41 inches from the rear wall. |
TR6 |
12 months |
16.4.1(5) |
The toilet is inaccessible because the side grab bar is obstructed by the toilet paper dispenser. |
TR15 |
12 months |
16.4.2. |
Drinking Fountain (Admissions Area): The lower drinking fountain protrudes into the walkway and is not detectable to blind persons using a cane. |
AR7 |
12 months |
16.4.3. |
Drinking Fountain (Admissions Area between Rooms 105 and 107): The drinking fountain protrudes into the walkway and is not detectable to blind persons using a cane. |
AR7 |
12 months |
16.4.4. |
Overflow Waiting Area: The door is inaccessible because knob hardware is used. |
D2 |
12 months |
16.5. |
Crisis Assessment and Triage: The doors to the Nursing Room and Medical Telecare Offices are inaccessible because knob hardware is used. |
D2 |
12 months |
16.6. |
Shower Stalls Crisis Respite and Transitional Housing (Women's): There is no accessible shower provided. |
B2 |
30 months |
16.7. |
Shower Stalls Crisis Respite and Transitional Housing (Men's): There is no accessible shower provided. |
B2 |
30 months |
16.8. |
Transient Lodging Rooms: The doors are inaccessible because they have an opening width of 28 inches. |
D14 |
30 months |
16.9. |
Single User Toilet Room (Crisis Respite and Transitional Housing - Women's): |
||
16.9.1. |
The toilet room sign is mounted on the door and has no raised or Braille characters. |
TR11 |
12 months |
16.9.2. |
The lavatory is inaccessible because the hot water pipes are not insulated or otherwise configured to protect against contact. |
LS2 |
12 months |
16.10. |
Single User Toilet Room (Crisis Respite and Transitional Housing - Men's): |
||
16.10.1. |
The toilet room sign is mounted on the door and has no raised or Braille characters. |
TR11 |
12 months |
16.10.2. |
The lavatory is inaccessible because the hot water pipes are not insulated or otherwise configured to protect against contact. |
LS2 |
12 months |
17. |
Detention Center and Annex, 520 Columbus Avenue |
||
17.1. |
Women's Single User Toilet Room (Lobby): |
||
17.1.1. |
The toilet room sign is mounted on the door and has no raised or Braille characters. |
TR11 |
30 months |
17.1.2. |
The door is inaccessible because knob hardware is used. |
D2 |
30 months |
17.1.3. |
The lavatory is inaccessible because it has twist-type hardware. |
LS4 |
30 months |
17.1.4. |
The lavatory is inaccessible because the hot water pipes are not insulated or otherwise configured to protect against contact. |
LS2 |
30 months |
17.1.5. |
The toilet is inaccessible because there is insufficient clear floor space provided. |
TR24 |
30 months |
17.1.6. |
The toilet is inaccessible because its centerline is 20 1/2 inches from the side wall. |
TR7 |
30 months |
17.1.7. |
The toilet is inaccessible because the side grab bar is obstructed by the toilet paper dispenser. |
TR15 |
30 months |
17.1.8. |
The toilet is inaccessible because there is no rear grab bar provided. |
TR13 |
30 months |
17.2. |
Men's Single User Toilet Room (Lobby): |
||
17.2.1. |
The toilet room sign is mounted on the door and has no raised or Braille characters. |
TR11 |
30 months |
17.2.2. |
The door is inaccessible because knob hardware is used. |
D2 |
30 months |
17.2.3. |
The lavatory is inaccessible because it has twist-type hardware. |
LS4 |
30 months |
17.2.4. |
The lavatory is inaccessible because the hot water pipes are not insulated or otherwise configured to protect against contact. |
LS2 |
30 months |
17.2.5. |
The toilet is inaccessible because there is insufficient clear floor space provided. |
TR24 |
30 months |
17.2.6. |
The toilet is inaccessible because its centerline is 19 inches from the side wall. |
TR7 |
30 months |
17.2.7. |
The toilet is inaccessible because the flush control is on the closed side. |
TR4 |
30 months |
17.2.8. |
The toilet is inaccessible because there is no rear grab bar provided. |
TR13 |
30 months |
18. |
Highway 6 Jail, 3201 E State Highway 6 |
||
18.1. |
Parking: The designated accessible parking is inaccessible because not all the designated parking spaces have vertical signage. |
P3 |
24 months |
18.2. |
Main Entrance Lobby: |
||
18.2.1. |
Men's Single User Toilet Room: |
||
18.2.1(1) |
The toilet is inaccessible because the flush control is on the closed side. |
TR4 |
18 months |
18.2.1(2) |
The soap dispenser is inaccessible because it is mounted with the controls higher than 48 inches high for a forward approach. |
CT4 |
18 months |
18.2.2. |
Women's Single User Toilet Room: |
||
18.2.2(1) |
The lavatory is inaccessible because the hot water pipes are not insulated or otherwise configured to protect against contact. |
LS2 |
18 months |
18.2.2(2) |
The soap dispenser is inaccessible because it is mounted with the controls higher than 48 inches high for a forward approach. |
CT4 |
18 months |