Barrier Number Floor Location Number Description Condition Barrier notes Standards
2 Ext. E-102 Curb Ramp 10 - 10.4% slope Slope of existing Curb Ramp in the direction of travel exceeds 1:12 (8.3%). 4.7.2; Fig. 11
3 Ext. E-102 Curb Ramp 2.3 - 3% cross slope Cross slope of existing Curb Ramp (perpendicular to the direction of travel) exceeds 1:50 (2%). 4.7.2
4 Ext. E-102 Curb Ramp 19.3% flared side Existing Curb Ramp flared sides exceed 10%. 4.7.5; Fig. 12
5 Ext. E-103 Curb Ramp 2.5% cross slope Cross slope of existing Curb Ramp (perpendicular to the direction of travel) exceeds 1:50 (2%). 4.7.2
6 Ext. E-103 Curb Ramp 15.8% flared side Existing Curb Ramp flared sides exceed 10%. 4.7.5; Fig. 12
12 Ext. E-106 Curb Ramp 17.1% flared side Existing Curb Ramp flared sides exceed 10%. 4.7.5; Fig. 12
13 Ext. E-107 Curb Ramp 19% flared side Existing Curb Ramp flared sides exceed 10%. 4.7.5; Fig. 12
15 Ext. E-109 Curb Ramp 9% slope Slope of existing Curb Ramp in the direction of travel exceeds 1:12 (8.3%). 4.7.2; Fig. 11
16 Ext. E-109 Curb Ramp Less than 24" straight curb Existing diagonal, or corner-type, Curb Ramp has flared sides, but does not have at least 24" length of straight curb also within marked crossing. Defendants will address by contacting New York City agencies/entities with authority to re-paint crosswalk. 4.7.10; Fig. 15
19 Ext. E-111 Curb Ramp 9.1 - 9.9% slope Slope of existing Curb Ramp in the direction of travel exceeds 1:12 (8.3%). 4.7.2; Fig. 11
22 Ext. E-114 Curb Ramp Less than 24" straight curb Existing diagonal, or corner-type, Curb Ramp has flared sides, but does not have at least 24" length of straight curb also within marked crossing. Defendants will address by contacting New York City agencies/entities with authority to re-paint crosswalk. 4.7.10; Fig. 15
267 01 C-121 Lobby Visual alarm on ceiling Visual Signal(s) mounted at incorrect height. Visual signal is to be mounted at 80" AFF or 6" below ceiling (whichever is lower). 4.28.3(6)
283 02 A-104 Concourse Ramp No handrail Ramp > 6" high, or > 72" long with no handrail. 4.8.5
372 02 A-125 Ticket Counter Inconspicuous signs regarding assistive listening device No signage is provided at the ticket office or other apparent location notifying patrons of the availability of an Assistive Listening System. 4.1.3(19)(b)
373 02 A-125 Ticket Counter 42" AFF Sales, Service or Information Counter(s) or Teller Window(s) higher than 36" AFF or at Cash Register(s) for sales or distribution of goods or services to the public. Twenty-three counters, none accessible. 7.2
377 02 A-129 Madison Square Garden Bridge Lobby Visual alarm on ceiling Visual Signal(s) mounted at incorrect height. Visual signal is to be mounted at 80" AFF or 6" below ceiling (whichever is lower). 4.28.3(6)
378 02 A-130 Madison Square Garden Bridge Lobby Visual alarm on ceiling Visual Signal(s) mounted at incorrect height. Visual signal is to be mounted at 80" AFF or 6" below ceiling (whichever is lower). 4.28.3(6)
382 02 A-132 Madison Square Garden Lobby Visual alarm on ceiling Visual Signal(s) mounted at incorrect height. Visual signal is to be mounted at 80" AFF or 6" below ceiling (whichever is lower). 4.28.3(6)
383 02 A-133 Visual Alarm in Concourse by Escalator Visual alarm on ceiling Visual Signal(s) mounted at incorrect height. Visual signal is to be mounted at 80" AFF or 6" below ceiling (whichever is lower). 4.28.3(6)
384 02 A-134 Visual Alarm in Concourse by Escalator Column 22 Visual alarm on ceiling Visual Signal(s) mounted at incorrect height. Visual signal is to be mounted at 80" AFF or 6" below ceiling (whichever is lower). 4.28.3(6)
726 02 B-125 Visual Alarm in Concourse by Escalator Column 30 Visual alarm on ceiling Visual Signal(s) mounted at incorrect height. Visual signal is to be mounted at 80" AFF or 6" below ceiling (whichever is lower). 4.28.3(6)
727 02 B-126 Visual Alarm in Concourse by Escalator Column 26 Visual alarm on ceiling Visual Signal(s) mounted at incorrect height. Visual signal is to be mounted at 80" AFF or 6" below ceiling (whichever is lower). 4.28.3(6)
824 02 C-114 Visual Alarm in Concourse by Column 43 Visual alarm on ceiling Visual Signal(s) mounted at incorrect height. Visual signal is to be mounted at 80" AFF or 6" below ceiling (whichever is lower). 4.28.3(6)
825 02 C-115 Visual Alarm in Concourse by Column 45 Visual alarm on ceiling Visual Signal(s) mounted at incorrect height. Visual signal is to be mounted at 80" AFF or 6" below ceiling (whichever is lower). 4.28.3(6)
826 02 C-116 Visual Alarm in Concourse by Column 1 Visual alarm on ceiling Visual Signal(s) mounted at incorrect height. Visual signal is to be mounted at 80" AFF or 6" below ceiling (whichever is lower). 4.28.3(6)
833 02 D-103 Concourse Ramp No handrail Ramp > 6" high, or > 72" long with no handrail. 4.8.5
853 02 D-114 Madison Square Garden Bridge Lobby Visual alarm on ceiling Visual Signal(s) mounted at incorrect height. Visual signal is to be mounted at 80" AFF or 6" below ceiling (whichever is lower). 4.28.3(6)
854 02 D-115 Visual Alarm in Concourse by Escalator Column 9 Visual alarm on ceiling Visual Signal(s) mounted at incorrect height. Visual signal is to be mounted at 80" AFF or 6" below ceiling (whichever is lower). 4.28.3(6)
855 02 D-116 Visual Alarm in Concourse by Escalator Column 5 Visual alarm on ceiling Visual Signal(s) mounted at incorrect height. Visual signal is to be mounted at 80" AFF or 6" below ceiling (whichever is lower). 4.28.3(6)
1814 06 000 Public Pay Telephone No forward approach phone Two or more banks of public pay telephones on this floor. None meet the requirements for a forward reach telephone, where a minimum of 1 per floor is required. 4.1.3(17)(a)
1815 06 A-101 Lighted Signs 5.5" projection, 34.5" AFF Protruding object with bottom between 27" and 80" AFF projects more than 4" from wall or 12" from post. 4.4.1; Fig. 8a-d
1816 06 A-102 Public Pay Telephone No outlet Bank of 3 or more phones: None have shelf or outlet for portable TTY. 4.1.3(17)(d)
1817 06 A-102 Public Pay Telephone 65" AFF Operable parts of phone outside reach range; five public pay telephones, none accessible 4.1.3(17), 4.31.3; Fig. 5, 6, 44a-b
1818 06 A-102 Public Pay Telephone No volume control Accessible telephone does not have volume control. 4.1.3(17)(b)
1819 06 A-102 Public Pay Telephone Grasping and twisting Push button controls are required: Operable part of telephone requires grasping or twisting to operate 4.31.6
1820 06 A-103 Gift and Souvenir Counter 42" AFF Sales, Service or Information Counter(s) or Teller Window(s) higher than 36" AFF or at Cash Register(s) for sales or distribution of goods or services to the public. 7.2
1821 06 A-104 ATM All Instructions on ATM screen Instructions and/or Information for use not accessible to and independently usable by persons with visual impairments. 4.34.5
1822 06 A-105 Concession Counter 41.75" AFF Sales, Service or Information Counter(s) or Teller Window(s) higher than 36" AFF: At Cash Register(s) for sales or distribution of goods or services to the public. 7.2
1824 06 A-107 Women's Toilet Room Visual alarm on ceiling Visual Signal(s) mounted at incorrect height. Visual signal is to be mounted at 80" AFF or 6" below ceiling (whichever is lower). 4.28.3(6)
1825 06 A-107 Women's Toilet Room No raised lettering and Braille Existing room and/or gender identification signage is noncompliant. 4.1.3(16)(a), 4.30.4
1826 06 A-107 Women's Toilet Room Sign above arch Existing room and/or identification sign is incorrectly located. 4.30.6
1827 06 A-107 Women's Toilet Room 12 stalls, 0 ambulatory If greater than or equal to 6, and if standard accessible stall provided, 36" wide ambulatory accessible stall also required. 4.1.3(11), 4.22.4; Fig. 30d
1830 06 A-107 Women's Toilet Room 66.5" AFF Coat hook > 48" above finish floor front reach, or > 54"; side reach. 4.22.7, 4.27.3; Fig. 5, 6
1831 06 A-107 Women's Toilet Room 9.5" corner Rear Wall grab bar > 6" from side wall or (partition) nearest water closet. 4.1.3(11), 4.22.4, 4.16.4, 4.17.6; Fig. 29, 30
1832 06 A-107 Women's Toilet Room 27" centerline Centerline of water closet is < or > 18" from sidewall or partition. 4.1.3(11), 4.22.4, 4.16.2, 4.17.3; Fig. 28, 30
1834 06 A-107 Women's Toilet Room 27# Manual flush control at water closet requires > 5 lbs. of force to activate. 4.1.3(11), 4.22.4, 4.16.5, 4.17.2, 4.27.4
1835 06 A-107 Women's Toilet Room Toilet tissue on far wall Toilet paper dispenser located other than side wall nearest water closet. 4.1.3(11), 4.22.4, 4.16.6, 4.17.2; Fig. 29b, 30(d)
1836 06 A-107 Women's Toilet Room Large roll toilet paper Large roll toilet paper dispenser requires pinching and does not allow continuous delivery. 4.1.3(11), 4.22.4, 4.16.6, 4.17.2; Fig. 29b, 30(d)
1837 06 A-107 Women's Toilet Room 26.5" wide Clearance < 30" x 48" at lavatory. 4.1.3(11), 4.22.6, 4.19.3; Fig. 32
1838 06 A-107 Women's Toilet Room No insulation Hot water pipes not insulated or covered. 4.1.3(11), 4.22.6, 4.19.4
1839 06 A-107 Women's Toilet Room 67" AFF Towel dispenser or blower outside reach range. 4.1.3(11), 4.22.7, 4.27.3; Fig. 4, 5, 6
1840 06 A-107 Women's Toilet Room 5.5" projection, 31" AFF Protruding object with bottom between 27" and 80" above finish floor projects > 4" from wall into circulation path. 4.4.1, 4.4.2; Fig. 8
1841 06 A-107 Women's Toilet Room 16# Control or operating mechanism takes > 5 lbs. force to operate or requires tight gripping, grasping or twisting of wrist. Soap dispenser. 4.1.3(11), 4.22.7, 4.27.4
1842 06 A-108 Public Pay Telephone No volume control Accessible telephone does not have volume control. 4.1.3(17)(b)
1843 06 A-108 Public Pay Telephone Grasping and twisting Push button controls are required: Operable part of telephone requires grasping or twisting to operate 4.31.6
1845 06 A-110 Condiment Counter 14" projection, 35" AFF Protruding object with bottom between 27" and 80" AFF projects more than 4" from wall or 12" from post. 4.4.1; Fig. 8a-d
1846 06 A-110 Condiment Counter 42.25" AFF Table or counter top < 28" AFF, or > 34" AFF. 4.1.3(18), 4.32.4, 5.2
1848 06 A-111 Lobby Doors 2 seconds Existing Closer causes Door to travel from 70 degrees open to 3" from latch in less than 3 sec. 4.13.10
1849 06 A-112 Drinking Fountain 41" AFF Spout outlet higher than 36" AFF. 4.15.2
1850 06 A-112 Drinking Fountain 11# Controls require more than 5# force to operate. 4.15.4, 4.27.4
1851 06 A-113 Bar/Pub: Counter Around Wall 5.75" projection, 41.75" AFF Protruding object with bottom between 27" and 80" AFF projects more than 4" from wall or 12" from post. 4.4.1; Fig. 8a-d
1852 06 A-113 Bar/Pub: Counter Around Column 7" projection, 40.75" AFF Protruding object with bottom between 27" and 80" AFF projects more than 4" from wall or 12" from post. 4.4.1; Fig. 8a-d
1853 06 A-113 Bar/Pub: Display Television 8.25" projection, 57.25" AFF Protruding object with bottom between 27" and 80" AFF projects more than 4" from wall or 12" from post. 4.4.1; Fig. 8a-d
1854 06 A-113 (near D-106) First Aid Room: Door from Concourse 30" clear Clearance width < 32" at single doorway. (Deduct 5/8" from width criteria for Alt. Tech. Infeas.) 4.13.5; Fig. 24
1856 06 A-113 (near D-106) First Aid Room: Door from Concourse Knob Existing door hardware requires tight grasping, pinching, or twisting of the wrist to operate. 4.13.9
1858 06 A-113 (near D-106) First Aid Room: Door from Concourse 12# Force to operate interior non-fire-rated door exceeds 5#. 4.13.11(2)(b)
1859 06 A-113 (near D-106) First Aid Room: Door from Concourse Sign on door, no raised lettering and Braille Existing room identification signage is noncompliant. 4.1.3(16)(a)
1860 06 A-113 (near D-106) First Aid Room No visual alarm An audible alarm system is provided within this building. A visual signal is not provided in this common use area. 4.1.3(14), 4.28.1
1861 06 A-113 Bar/Pub Visual alarm on ceiling Visual Signal(s) mounted at incorrect height. Visual signal is to be mounted at 80" AFF or 6" below ceiling (whichever is lower). 4.28.3(6)
1862.1 06 A-113 (near D-106) First Aid Room: Toilet Room Inaccessible; no directional signage No directional signage to nearest accessible toilet room at inaccessible toilet room. 4.1.6(3)(e)(iii)
1873 06 A-113 Bar/Pub: Drink Counter 42.5" AFF Food or Drink served to customers at Counter or Bar on stools or standing, but no section meets accessibility requirements. 5.2
1874 06 A-113 Bar/Pub: Concession Counter 43.5" AFF Sales, Service or Information Counter(s) or Teller Window(s) higher than 36" AFF or at Cash Register(s) for sales or distribution of goods or services to the public. 7.2
1875 06 A-114 Team Store Visual alarm on ceiling Visual Signal(s) mounted at incorrect height. Visual signal is to be mounted at 80" AFF or 6" below ceiling (whichever is lower). 4.28.3(6)
1876 06 A-114 Team Store: Sales Counter 42" AFF Sales, Service or Information Counter(s) or Teller Window(s) higher than 36" AFF or at Cash Register(s) for sales or distribution of goods or services to the public. 7.2
1877 06 A-115 Visual Alarm in Concourse by Column 15 Visual alarm on ceiling Visual Signal(s) mounted at incorrect height. Visual signal is to be mounted at 80" AFF or 6" below ceiling (whichever is lower). 4.28.3(6)
1878 06 A-116 Visual Alarm in Concourse by Column 18 Visual alarm on ceiling Visual Signal(s) mounted at incorrect height. Visual signal is to be mounted at 80" AFF or 6" below ceiling (whichever is lower). 4.28.3(6)
1879 06 A-117 Visual Alarm in Concourse by Column 20 Visual alarm on ceiling Visual Signal(s) mounted at incorrect height. Visual signal is to be mounted at 80" AFF or 6" below ceiling (whichever is lower). 4.28.3(6)
1880 06 A-118 Fire Pull at Column 18 63" AFF Control outside reach range. 4.1.3(13), 4.27.3; Fig. 5, 6
1881 06 B-101 Public Pay Telephone No shelf or outlet Bank of 3 or more phones: None have shelf or outlet for portable TTY. 4.1.3(17)(d)
1882 06 B-101 Public Pay Telephone 55.5" AFF Operable parts of phone outside reach range.n Four public pay telephones, none accessible. 4.1.3(17), 4.31.3; Fig. 5, 6, 44a-b
1883 06 B-101 Public Pay Telephone Grasping and twisting Push button controls are required: Operable part of telephone requires grasping or twisting to operate 4.31.6
1884 06 B-101 Public Pay Telephone No TTY 4 or more Public Pay Phones, interior and exterior, at this site, and no interior TTY. 4.1.3(17)(c)(i) and (ii)
1885 06 B-102 Lighted Sign 5.5" projection, 38.5" AFF Protruding object with bottom between 27" and 80" AFF projects more than 4" from wall or 12" from post. 4.4.1; Fig. 8a-d
1886 06 B-103 Women's Toilet Room Visual alarm on ceiling Visual Signal(s) mounted at incorrect height. Visual signal is to be mounted at 80" AFF or 6" below ceiling (whichever is lower). 4.28.3(6)
1887 06 B-103 Women's Toilet Room No raised lettering and Braille Existing room and/or gender identification signage is noncompliant. 4.1.3(16)(a), 4.30.4
1888 06 B-103 Women's Toilet Room Sign above arch Existing room and/or identification sign is incorrectly located. 4.30.6
1889.1 06 B-103 Women's Toilet Room Inaccessible; no directional signage No directional signage to nearest accessible toilet room at inaccessible toilet room. 4.1.6(3)(e)(iii)
1900 06 B-104 Men's Toilet Room Visual alarm on ceiling Visual Signal(s) mounted at incorrect height. Visual signal is to be mounted at 80" AFF or 6" below ceiling (whichever is lower). 4.28.3(6)
1901 06 B-104 Men's Toilet Room No raised lettering and Braille Existing room and/or gender identification signage is noncompliant. 4.1.3(16)(a), 4.30.4
1902 06 B-104 Men's Toilet Room Sign above arch Existing room and/or identification sign is incorrectly located. 4.30.6
1903.1 06 B-104 Men's Toilet Room Inaccessible; no directional signage No directional signage to nearest accessible toilet room at inaccessible toilet room. 4.1.6(3)(e)(iii)
1917 06 B-105 Eating Counter 16" projection, 38.5" AFF Protruding object with bottom between 27" and 80" AFF projects more than 4" from wall or 12" from post. 4.4.1; Fig. 8a-d
1918 06 B-105 Eating Counter 42.5" AFF Table or counter top < 28" AFF, or > 34" AFF. 4.1.3(18), 4.32.4, 5.2
1919 06 B-106 Moveable Eating Tables 39" AFF Table or counter top < 28" AFF, or > 34" AFF. 4.1.3(18), 4.32.4, 5.2
1924 06 B-107 Men's Toilet Room Visual alarm on ceiling Visual Signal(s) mounted at incorrect height. Visual signal is to be mounted at 80" AFF or 6" below ceiling (whichever is lower). 4.28.3(6)
1925 06 B-107 Men's Toilet Room No raised lettering and Braille Existing room and/or gender identification signage is noncompliant. 4.1.3(16)(a), 4.30.4
1926 06 B-107 Men's Toilet Room Sign above arch Existing room and/or identification sign is incorrectly located. 4.30.6
1927 06 B-107 Men's Toilet Room 6 stalls, 0 ambulatory If greater than or equal to 6, and if standard accessible stall provided, 36" wide ambulatory accessible stall also required. 4.1.3(11), 4.22.4; Fig. 30d
1928 06 B-107 Men's Toilet Room 38.5" wide Accessible stall width < 60". 4.1.3(11), 4.22.4, 4.17.3; Fig. 30d
1930 06 B-107 Men's Toilet Room 66.5" AFF Coat hook > 48" above finish floor front reach, or > 54"; side reach. 4.22.7, 4.27.3; Fig. 5, 6
1931 06 B-107 Men's Toilet Room No rear grab bar No rear grab bar (except at 36" alternate accessible stall). 4.1.3(11), 4.22.4, 4.16.4, 4.17.6; Fig. 29, 30
1932 06 B-107 Men's Toilet Room 13# Manual flush control at water closet requires > 5 lbs. of force to activate. 4.1.3(11), 4.22.4, 4.16.5, 4.17.2, 4.27.4
1933 06 B-107 Men's Toilet Room Large roll toilet paper Large roll toilet paper dispenser requires pinching and does not allow continuous delivery. 4.1.3(11), 4.22.4, 4.16.6, 4.17.2; Fig. 29b, 30(d)
1934 06 B-107 Men's Toilet Room 46.5" AFF Manual flush control at urinal > 44" above finished floor. 4.1.3(11), 4.22.5, 4.18.4
1935 06 B-107 Men's Toilet Room 12# Manual flush control at urinal requires > five pounds force to activate. 4.1.3(11), 4.22.5, 4.18.4, 4.27.4
1937 06 B-107 Men's Toilet Room 27" wide Clearance < 30" x 48" at lavatory. 4.1.3(11), 4.22.6, 4.19.3; Fig. 32
1938 06 B-107 Men's Toilet Room No insulation Hot water pipes not insulated or covered. 4.1.3(11), 4.22.6, 4.19.4
1939 06 B-107 Men's Toilet Room 66" AFF Towel dispenser or blower outside reach range. 4.1.3(11), 4.22.7, 4.27.3; Fig. 4, 5, 6
1940 06 B-107 Men's Toilet Room 5.25" projection, 31.5" AFF Protruding object with bottom between 27" and 80" above finish floor projects > 4" from wall into circulation path. 4.4.1, 4.4.2; Fig. 8
1941 06 B-107 Men's Toilet Room 16# Control or operating mechanism takes > 5 lbs. force to operate or requires tight gripping, grasping or twisting of wrist. Soap dispenser. 4.1.3(11), 4.22.7, 4.27.4
1942 06 B-108 Lighted Sign 5.5" projection, 30.5" AFF Protruding object with bottom between 27" and 80" AFF projects more than 4" from wall or 12" from post. 4.4.1; Fig. 8a-d
1943 06 B-109 Concession Counter 41.25" AFF Sales, Service or Information Counter(s) or Teller Window(s) higher than 36" AFF or at Cash Register(s) for sales or distribution of goods or services to the public. 7.2
1944 06 B-110 Guest Services Counter 42" AFF Sales, Service or Information Counter(s) or Teller Window(s) higher than 36" AFF or at Cash Register(s) for sales or distribution of goods or services to the public. 7.2
1963 06 B-117 Public Pay Telephone Grasping and twisting Push button controls are required: Operable part of telephone requires grasping or twisting to operate 4.31.6
1965 06 B-118 Condiment Counter 14" projection, 34.5" AFF Protruding object with bottom between 27" and 80" AFF projects more than 4" from wall or 12" from post. 4.4.1; Fig. 8a-d
1966 06 B-118 Public Pay Telephone No volume control Accessible telephone does not have volume control. 4.1.3(17)(b)
1967 06 B-118 Public Pay Telephone Grasping and twisting Push button controls are required: Operable part of telephone requires grasping or twisting to operate 4.31.6
1968 06 B-118 Condiment Counter 42.5" AFF Table or counter top < 28" AFF, or > 34" AFF. 4.1.3(18), 4.32.4, 5.2
1970 06 B-119 Elevator Lobby Jamb identification, 1 side only Floor Designations at Elevator Hoistway are not located on both jambs of Hoistway openings. 4.10.5; Fig. 20
1972 06 B-120 Lobby Doors 2 seconds Existing Closer causes Door to travel from 70 degrees open to 3" from latch in less than 3 sec. 4.13.10
1973 06 B-121 Condiment Counter 14" projection, 34.25" AFF Protruding object with bottom between 27" and 80" AFF projects more than 4" from wall or 12" from post. 4.4.1; Fig. 8a-d
1974 06 B-121 Condiment Counter 41.75" AFF Table or counter top < 28" AFF, or > 34" AFF. 4.1.3(18), 4.32.4, 5.2
2037 06 B-130 Two Elevators No signal Existing Car Position Indicator does not give an Audible Signal. 4.10.4
2039 06 B-135 Visual Alarm in Corridor by Column 31 Visual alarm on ceiling Visual Signal(s) mounted at incorrect height. Visual signal is to be mounted at 80" AFF or 6" below ceiling (whichever is lower). 4.28.3(6)
2040 06 B-136 Visual Alarm in Corridor by Column 28 Visual alarm on ceiling Visual Signal(s) mounted at incorrect height. Visual signal is to be mounted at 80" AFF or 6" below ceiling (whichever is lower). 4.28.3(6)
2041 06 B-137 Visual Alarm in Corridor by Column 24 Visual alarm on ceiling Visual Signal(s) mounted at incorrect height. Visual signal is to be mounted at 80" AFF or 6" below ceiling (whichever is lower). 4.28.3(6)
2046 06 B-139 Fire Pull at Column 30 62.5" AFF Control outside reach range. 4.1.3(13), 4.27.3; Fig. 5, 6
2049 06 B-140 Fire Pull at Column 25 63" AFF Control outside reach range. 4.1.3(13), 4.27.3; Fig. 5, 6
2052 06 C-101 Women's Toilet Room Visual alarm on ceiling Visual Signal(s) mounted at incorrect height. Visual signal is to be mounted at 80" AFF or 6" below ceiling (whichever is lower). 4.28.3(6)
2053 06 C-101 Women's Toilet Room No raised lettering and Braille Existing room and/or gender identification signage is noncompliant. 4.1.3(16)(a), 4.30.4
2054 06 C-101 Women's Toilet Room Sign above arch Existing room and/or identification sign is incorrectly located. 4.30.6
2055.1 06 C-101 Women's Toilet Room Inaccessible; no directional signage No directional signage to nearest accessible toilet room at inaccessible toilet room. 4.1.6(3)(e)(iii)
2067 06 C-102 Eating Counter 16" projection, 37.75" AFF Protruding object with bottom between 27" and 80" AFF projects more than 4" from wall or 12" from post. 4.4.1; Fig. 8a-d
2068 06 C-102 Eating Counter 41.75" AFF Table or counter top < 28" AFF, or > 34" AFF. 4.1.3(18), 4.32.4, 5.2
2069 06 C-103 Moveable Eating Tables 39" AFF Table or counter top < 28" AFF, or > 34" AFF. 4.1.3(18), 4.32.4, 5.2
2075 06 C-105 Public Pay Telephone No outlet Bank of 3 or more phones: None have shelf or outlet for portable TTY. 4.1.3(17)(d)
2076 06 C-105 Public Pay Telephone 65" AFF Operable parts of phone outside reach range. Five public pay telephones, none accessible. 4.1.3(17), 4.31.3; Fig. 5, 6, 44a-b
2077 06 C-105 Public Pay Telephone No volume control Accessible telephone does not have volume control. 4.1.3(17)(b)
2078 06 C-105 Public Pay Telephone Grasping and twisting Push button controls are required: Operable part of telephone requires grasping or twisting to operate 4.31.6
2079 06 C-106 Gift and Souvenir Counter 42" AFF Sales, Service or Information Counter(s) or Teller Window(s) higher than 36" AFF or at Cash Register(s) for sales or distribution of goods or services to the public. 7.2
2150 06 C-110 Lighted Sign 5.5" projection, 38.5" AFF Protruding object with bottom between 27" and 80" AFF projects more than 4" from wall or 12" from post. 4.4.1; Fig. 8a-d
2151 06 C-111 Concession Counter 41.5" AFF Sales, Service or Information Counter(s) or Teller Window(s) higher than 36" AFF or at Cash Register(s) for sales or distribution of goods or services to the public. 7.2
2152 06 C-112 Lighted Sign 5.5" projection, 30" AFF Protruding object with bottom between 27" and 80" AFF projects more than 4" from wall or 12" from post. 4.4.1; Fig. 8a-d
2153 06 C-113 Women's Toilet Room Visual alarm on ceiling Visual Signal(s) mounted at incorrect height. Visual signal is to be mounted at 80" AFF or 6" below ceiling (whichever is lower). 4.28.3(6)
2154 06 C-113 Women's Toilet Room No raised lettering and Braille Existing room and/or gender identification signage is noncompliant. 4.1.3(16)(a), 4.30.4
2155 06 C-113 Women's Toilet Room Sign above arch Existing room and/or identification sign is incorrectly located. 4.30.6
2156 06 C-113 Women's Toilet Room 12 stalls, 0 ambulatory If greater than or equal to 6, and if standard accessible stall provided, 36" wide ambulatory accessible stall also required. 4.1.3(11), 4.22.4; Fig. 30d
2158 06 C-113 Women's Toilet Room 66.5" AFF Coat hook > 48" above finish floor front reach, or > 54"; side reach. 4.22.7, 4.27.3; Fig. 5, 6
2160 06 C-113 Women's Toilet Room 19.5" centerline Centerline of water closet is < or > 18" from sidewall or partition. 4.1.3(11), 4.22.4, 4.16.2, 4.17.3; Fig. 28, 30
2161 06 C-113 Women's Toilet Room Narrow side Manual flush control is not located on open side of water closet. 4.1.3(11), 4.22.4, 4.16.5, 4.17.2
2162 06 C-113 Women's Toilet Room 13# Manual flush control at water closet requires > 5 lbs. of force to activate. 4.1.3(11), 4.22.4, 4.16.5, 4.17.2, 4.27.4
2163 06 C-113 Women's Toilet Room Large roll toilet paper Large roll toilet paper dispenser requires pinching and does not allow continuous delivery. 4.1.3(11), 4.22.4, 4.16.6, 4.17.2; Fig. 29b, 30(d)
2164 06 C-113 Women's Toilet Room No insulation Hot water pipes not insulated or covered. 4.1.3(11), 4.22.6, 4.19.4
2165 06 C-113 Women's Toilet Room 67" AFF Towel dispenser or blower outside reach range. 4.1.3(11), 4.22.7, 4.27.3; Fig. 4, 5, 6
2166 06 C-113 Women's Toilet Room 5.25" AFF, 31" AFF Protruding object with bottom between 27" and 80" above finish floor projects > 4" from wall into circulation path. 4.4.1, 4.4.2; Fig. 8
2167 06 C-113 Women's Toilet Room 12# Control or operating mechanism takes > 5 lbs. force to operate or requires tight gripping, grasping or twisting of wrist. Soap dispenser. 4.1.3(11), 4.22.7, 4.27.4
2180 06 C-116 Condiment Counter 14" projection, 34.75" AFF Protruding object with bottom between 27" and 80" AFF projects more than 4" from wall or 12" from post. 4.4.1; Fig. 8a-d
2181 06 C-116 Condiment Counter 42.25" AFF Table or counter top < 28" AFF, or > 34" AFF. 4.1.3(18), 4.32.4, 5.2
2184 06 C-118 Lobby Doors 2 seconds Existing Closer causes Door to travel from 70 degrees open to 3" from latch in less than 3 sec. 4.13.10
2186 06 C-120 Drinking Fountain 41" AFF Spout outlet higher than 36" AFF. 4.15.2
2187 06 C-120 Drinking Fountain 3" waterflow Stream height less than 4". 4.15.3
2188 06 C-120 Drinking Fountain 10# Controls require more than 5# force to operate. 4.15.4, 4.27.4
2189 06 C-121 Condiment Counters 14" projection, 34.5" AFF Protruding object with bottom between 27" and 80" AFF projects more than 4" from wall or 12" from post. 4.4.1; Fig. 8a-d
2190 06 C-121 Public Pay Telephones No volume control Accessible telephone does not have volume control. 4.1.3(17)(b)
2191 06 C-121 Public Pay Telephones Grasping and twisting Push button controls are required: Operable part of telephone requires grasping or twisting to operate 4.31.6
2192 06 C-121 Condiment Counters 42" AFF Table or counter top < 28" AFF, or > 34" AFF. 4.1.3(18), 4.32.4, 5.2
2193 06 C-122 Public Pay Telephone No volume control Accessible telephone does not have volume control. 4.1.3(17)(b)
2194 06 C-122 Public Pay Telephone Grasping and twisting Push button controls are required: Operable part of telephone requires grasping or twisting to operate 4.31.6
2195 06 C-122 Public Pay Telephone 27.75" AFF, 12" projection Telephone mounted with bottom between 27" and 80" AFF projects > 4" from the wall or > 12" from a post. 4.31.4, 4.4.1; Fig. 8a-e
2243 06 C-124 Men's Toilet Room Visual alarm on ceiling Visual Signal(s) mounted at incorrect height. Visual signal is to be mounted at 80" AFF or 6" below ceiling (whichever is lower). 4.28.3(6)
2244 06 C-124 Men's Toilet Room No raised lettering and Braille Existing room and/or gender identification signage is noncompliant. 4.1.3(16)(a), 4.30.4
2245 06 C-124 Men's Toilet Room Sign above arch Existing room and/or identification sign is incorrectly located. 4.30.6
2246.1 06 C-124 Men's Toilet Room Inaccessible; no directional signage No directional signage to nearest accessible toilet room at inaccessible toilet room. 4.1.6(3)(e)(iii)
2259 06 C-125 Team Store: Wall Mounted Television by Cash Register 21.25" projection, 63" AFF Protruding object with bottom between 27" and 80" AFF projects more than 4" from wall or 12" from post. 4.4.1; Fig. 8a-d
2260 06 C-125 Team Store: Ceiling Suspended Exit Sign 77" AFF Head Room < 80" AFF clearance at Interior Accessible Route. 4.4.2; Fig. 8a-d
2261 06 C-125 Team Store: Visual alarm 78.5" AFF Visual Signal(s) mounted at incorrect height. Visual signal is to be mounted at 80" AFF or 6" below ceiling (whichever is lower). 4.28.3(6)
2262 06 C-125 Team Store: Sales Counter 42" AFF Sales, Service or Information Counter(s) or Teller Window(s) higher than 36" AFF or at Cash Register(s) for sales or distribution of goods or services to the public. Five cash registers, none accessible. 7.2
2263 06 C-125 Team Store: Collectors Cash Register Counter 40" AFF Sales, Service or Information Counter(s) or Teller Window(s) higher than 36" AFF or at Cash Register(s) for sales or distribution of goods or services to the public. 7.2
2264 06 C-126 Visual Alarm in Concourse by Column 38 Visual alarm on ceiling Visual Signal(s) mounted at incorrect height. Visual signal is to be mounted at 80" AFF or 6" below ceiling (whichever is lower). 4.28.3(6)
2265 06 C-127 Visual Alarm in Concourse by Column 42 Visual alarm on ceiling Visual Signal(s) mounted at incorrect height. Visual signal is to be mounted at 80" AFF or 6" below ceiling (whichever is lower). 4.28.3(6)
2266 06 C-128 Visual Alarm in Concourse by Column 44 Visual alarm on ceiling Visual Signal(s) mounted at incorrect height. Visual signal is to be mounted at 80" AFF or 6" below ceiling (whichever is lower). 4.28.3(6)
2267 06 C-129 Visual Alarm in Concourse by Column 46 Visual alarm on ceiling Visual Signal(s) mounted at incorrect height. Visual signal is to be mounted at 80" AFF or 6" below ceiling (whichever is lower). 4.28.3(6)
2268 06 C-130 Visual Alarm in Concourse by Column 2 Visual alarm on ceiling Visual Signal(s) mounted at incorrect height. Visual signal is to be mounted at 80" AFF or 6" below ceiling (whichever is lower). 4.28.3(6)
2272 06 C-132 Fire Pull at Column 43 62.5" AFF Control outside reach range. 4.1.3(13), 4.27.3; Fig. 5, 6
2273 06 C-133 Fire Pull at Column 1 64" AFF Control outside reach range. 4.1.3(13), 4.27.3; Fig. 5, 6
2274 06 C-134 Bar: Eating Counter 41.5" AFF, 8" projection Protruding object with bottom between 27" and 80" AFF projects more than 4" from wall or 12" from post. 4.4.1; Fig. 8a-d
2277 06 C-134 Bar: Tables 42" AFF Less than 5% of Seating, Tables or Dining Counters accessible overall, or in Smoking or Non-Smoking area. 4.32, 5.1,
2278 06 C-134 Bar: Bar Counter 43" AFF Sales, Service or Information Counter(s) or Teller Window(s) higher than 36" AFF or at Cash Register(s) for sales or distribution of goods or services to the public. 7.2
2279 06 D-101 Men's Toilet Room Visual alarm on ceiling Visual Signal(s) mounted at incorrect height. Visual signal is to be mounted at 80" AFF or 6" below ceiling (whichever is lower). 4.28.3(6)
2280 06 D-101 Men's Toilet Room No raised lettering and Braille Existing room and/or gender identification signage is noncompliant. 4.1.3(16)(a), 4.30.4
2281 06 D-101 Men's Toilet Room Sign above arch Existing room and/or identification sign is incorrectly located. 4.30.6
2282 06 D-101 Men's Toilet Room 6 stalls, 0 ambulatory If greater than or equal to 6, and if standard accessible stall provided, 36" wide ambulatory accessible stall also required. 4.1.3(11), 4.22.4; Fig. 30d
2283 06 D-101 Men's Toilet Room 41" wide Accessible stall width < 60". 4.1.3(11), 4.22.4, 4.17.3; Fig. 30a
2285 06 D-101 Men's Toilet Room 67" AFF Coat hook > 48" above finish floor front reach, or > 54"; side reach. 4.22.7, 4.27.3; Fig. 5, 6
2287 06 D-101 Men's Toilet Room No rear wall grab bar No rear grab bar (except at 36" alternate accessible stall). 4.1.3(11), 4.22.4, 4.16.4, 4.17.6; Fig. 29, 30
2288 06 D-101 Men's Toilet Room 16.5" AFF Top of water closet seat <17" or > 19" above finish floor. 4.1.3(11), 4.22.4, 4.16.3, 4.17.2; Fig. 29b, 30(d)
2289 06 D-101 Men's Toilet Room 13# Manual flush control at water closet requires > 5 lbs. of force to activate. 4.1.3(11), 4.22.4, 4.16.5, 4.17.2, 4.27.4
2290 06 D-101 Men's Toilet Room Large roll toilet paper Large roll toilet paper dispenser requires pinching and does not allow continuous delivery. 4.1.3(11), 4.22.4, 4.16.6, 4.17.2; Fig. 29b, 30(d)
2292 06 D-101 Men's Toilet Room 15# Manual flush control at urinal requires > five pounds force to activate. 4.1.3(11), 4.22.5, 4.18.4, 4.27.4
2293 06 D-101 Men's Toilet Room No insulation Hot water pipes not insulated or covered. 4.1.3(11), 4.22.6, 4.19.4
2294 06 D-101 Men's Toilet Room 67" AFF Towel dispenser or blower outside reach range. 4.1.3(11), 4.22.7, 4.27.3; Fig. 4, 5, 6
2295 06 D-101 Men's Toilet Room 5.5" projection, 31" AFF Protruding object with bottom between 27" and 80" above finish floor projects > 4" from wall into circulation path. 4.4.1, 4.4.2; Fig. 8
2296 06 D-101 Men's Toilet Room 16# Control or operating mechanism takes > 5 lbs. force to operate or requires tight gripping, grasping or twisting of wrist. Soap dispenser. 4.1.3(11), 4.22.7, 4.27.4
2297 06 D-102 Lighted Sign 5.5" projection, 30.25" AFF Protruding object with bottom between 27" and 80" AFF projects more than 4" from wall or 12" from post. 4.4.1; Fig. 8a-d
2298 06 D-103 Concession Counter 42" AFF Sales, Service or Information Counter(s) or Teller Window(s) higher than 36" AFF or at Cash Register(s) for sales or distribution of goods or services to the public. 7.2
2300 06 D-105 Public Pay Telephone 65" AFF Operable parts of phone outside reach range. Three public pay telephone, none accessible. 4.1.3(17), 4.31.3; Fig. 5, 6, 44a-b
2301 06 D-105 Public Pay Telephone No volume control Accessible telephone does not have volume control. 4.1.3(17)(b)
2302 06 D-105 Public Pay Telephone Grasping and twisting Push button controls are required: Operable part of telephone requires grasping or twisting to operate 4.31.6
2303 06 D-106 Public Pay Telephone No volume control Accessible telephone does not have volume control. 4.1.3(17)(b)
2304 06 D-106 Public Pay Telephone Grasping and twisting Push button controls are required: Operable part of telephone requires grasping or twisting to operate 4.31.6
2305 06 D-106 Public Pay Telephone 12" projection, 28" AFF Telephone mounted with bottom between 27" and 80" AFF projects > 4" from the wall or > 12" from a post. 4.31.4, 4.4.1; Fig. 8a-e
2306 06 D-107 Public Pay Telephone No volume control Accessible telephone does not have volume control. 4.1.3(17)(b)
2307 06 D-107 Public Pay Telephone Grasping and twisting Push button controls are required: Operable part of telephone requires grasping or twisting to operate 4.31.6
2308 06 D-107 Public Pay Telephone 12" projection, 28" AFF Telephone mounted with bottom between 27" and 80" AFF projects > 4" from the wall or > 12" from a post. 4.31.4, 4.4.1; Fig. 8a-e
2310 06 D-108 Lobby Doors 2 seconds Existing Closer causes Door to travel from 70 degrees open to 3" from latch in less than 3 sec. 4.13.10
2311 06 D-109 Condiment Counter 14" projection, 35" AFF Protruding object with bottom between 27" and 80" AFF projects more than 4" from wall or 12" from post. 4.4.1; Fig. 8a-d
2312 06 D-110 Condiment Counter 14" projection, 34.25" AFF Protruding object with bottom between 27" and 80" AFF projects more than 4" from wall or 12" from post. 4.4.1; Fig. 8a-d
2313 06 D-110 Condiment Counter 42.25" AFF Table or counter top < 28" AFF, or > 34" AFF. 4.1.3(18), 4.32.4, 5.2
2314 06 D-110 Condiment Counter 41.75" AFF Table or counter top < 28" AFF, or > 34" AFF. 4.1.3(18), 4.32.4, 5.2
2315 06 D-111 Public Pay Telephone No volume control Accessible telephone does not have volume control. 4.1.3(17)(b)
2316 06 D-111 Public Pay Telephone Grasping and twisting Push button controls are required: Operable part of telephone requires grasping or twisting to operate 4.31.6
2317 06 D-111 Public Pay Telephone 12" projection, 28" AFF Telephone mounted with bottom between 27" and 80" AFF projects > 4" from the wall or > 12" from a post. 4.31.4, 4.4.1; Fig. 8a-e
2318 06 D-112 Collectors Gallery: Wall Mounted Television 77" AFF, 24" projection Protruding object with bottom between 27" and 80" AFF projects more than 4" from wall or 12" from post. 4.4.1; Fig. 8a-d
2319 06 D-112 Collectors Gallery: Counter 42" AFF Sales, Service or Information Counter(s) or Teller Window(s) higher than 36" AFF or at Cash Register(s) for sales or distribution of goods or services to the public. 7.2
2320 06 D-113 Visual Alarm in Concourse by Column 12 Visual alarm on ceiling Visual Signal(s) mounted at incorrect height. Visual signal is to be mounted at 80" AFF or 6" below ceiling (whichever is lower). 4.28.3(6)
2321 06 D-114 Visual Alarm in Concourse by Column 9 Visual alarm on ceiling Visual Signal(s) mounted at incorrect height. Visual signal is to be mounted at 80" AFF or 6" below ceiling (whichever is lower). 4.28.3(6)
2322 06 D-115 Visual Alarm in Concourse by Column 5 Visual alarm on ceiling Visual Signal(s) mounted at incorrect height. Visual signal is to be mounted at 80" AFF or 6" below ceiling (whichever is lower). 4.28.3(6)
2323 06 D-116 Fire Pull at Column 12 60" AFF Control outside reach range. 4.1.3(13), 4.27.3; Fig. 5, 6
2324 06 D-117 Fire Pull at Column 6 63" AFF Control outside reach range. 4.1.3(13), 4.27.3; Fig. 5, 6
2356 07 A-118 Men's Toilet Room Visual alarm on ceiling Visual Signal(s) mounted at incorrect height. Visual signal is to be mounted at 80" AFF or 6" below ceiling (whichever is lower). 4.28.3(6)
2375 07 A-119 Men's Toilet Room Visual alarm on ceiling Visual Signal(s) mounted at incorrect height. Visual signal is to be mounted at 80" AFF or 6" below ceiling (whichever is lower). 4.28.3(6)
2393 07 A-120 Visual Alarm in Concourse by Column 21 Visual alarm on ceiling Visual Signal(s) mounted at incorrect height. Visual signal is to be mounted at 80" AFF or 6" below ceiling (whichever is lower). 4.28.3(6)
2394 07 A-121 Visual Alarm in Concourse by Column 15 Visual alarm on ceiling Visual Signal(s) mounted at incorrect height. Visual signal is to be mounted at 80" AFF or 6" below ceiling (whichever is lower). 4.28.3(6)
2445 07 B-120 Visual Alarm in Concourse by Column 34 Visual alarm on ceiling Visual Signal(s) mounted at incorrect height. Visual signal is to be mounted at 80" AFF or 6" below ceiling (whichever is lower). 4.28.3(6)
2446 07 B-121 Visual Alarm in Concourse by Column 29 Visual alarm on ceiling Visual Signal(s) mounted at incorrect height. Visual signal is to be mounted at 80" AFF or 6" below ceiling (whichever is lower). 4.28.3(6)
2447 07 B-122 Visual Alarm in Concourse by Column 25 Visual alarm on ceiling Visual Signal(s) mounted at incorrect height. Visual signal is to be mounted at 80" AFF or 6" below ceiling (whichever is lower). 4.28.3(6)
2480 07 C-116 Men's Toilet Room Visual alarm on ceiling Visual Signal(s) mounted at incorrect height. Visual signal is to be mounted at 80" AFF or 6" below ceiling (whichever is lower). 4.28.3(6)
2496 07 C-117 Men's Toilet Room Visual alarm on ceiling Visual Signal(s) mounted at incorrect height. Visual signal is to be mounted at 80" AFF or 6" below ceiling (whichever is lower). 4.28.3(6)
2511 07 C-118 Visual Alarm in Concourse by Column 47 Visual alarm on ceiling Visual Signal(s) mounted at incorrect height. Visual signal is to be mounted at 80" AFF or 6" below ceiling (whichever is lower). 4.28.3(6)
2512 07 C-119 Visual Alarm in Concourse by Column 43 Visual alarm on ceiling Visual Signal(s) mounted at incorrect height. Visual signal is to be mounted at 80" AFF or 6" below ceiling (whichever is lower). 4.28.3(6)
2513 07 C-120 Visual Alarm in Concourse by Column 40 Visual alarm on ceiling Visual Signal(s) mounted at incorrect height. Visual signal is to be mounted at 80" AFF or 6" below ceiling (whichever is lower). 4.28.3(6)
2514 07 C-121 Visual Alarm in Concourse by Column 37 Visual alarm on ceiling Visual Signal(s) mounted at incorrect height. Visual signal is to be mounted at 80" AFF or 6" below ceiling (whichever is lower). 4.28.3(6)
2529 07 D-108 Women's Toilet Room Visual alarm on ceiling Visual Signal(s) mounted at incorrect height. Visual signal is to be mounted at 80" AFF or 6" below ceiling (whichever is lower). 4.28.3(6)
2571 07 D-120 Visual Alarm in Concourse by Column 11 Visual alarm on ceiling Visual Signal(s) mounted at incorrect height. Visual signal is to be mounted at 80" AFF or 6" below ceiling (whichever is lower). 4.28.3(6)
2574 07 D-123 Visual Alarm in Concourse by Column 8 Visual alarm on ceiling Visual Signal(s) mounted at incorrect height. Visual signal is to be mounted at 80" AFF or 6" below ceiling (whichever is lower). 4.28.3(6)
2575 08 000 Public Pay Telephone No forward approach phone Two or more banks of public pay telephones on this floor. None meet the requirements for a forward reach telephone, where a minimum of 1 per floor is required. 4.1.3(17)(a)
2577 08 A-101 Lobby Doors 2 seconds Existing Closer causes Door to travel from 70 degrees open to 3" from latch in less than 3 sec. 4.13.10
2580 08 A-102 Corridor Ramp No handrail Ramp > 6" high, or > 72" long with no handrail or with handrail on one side only. 4.8.5
2581 08 A-103 Public Pay Telephone No volume control Accessible telephone does not have volume control. 4.1.3(17)(b)
2582 08 A-103 Public Pay Telephone Grasping and twisting Push button controls are required: Operable part of telephone requires grasping or twisting to operate 4.31.6
2584 08 A-104 Men's Toilet Room 27.5" clear Clear width of active leaf of double door < 32". (Deduct 5/8" from width criteria for Alt. Tech. Infeas.) 4.13.5; Fig. 24
2585 08 A-104 Men's Toilet Room 2.5 seconds Existing Closer causes Door to travel from 70 degrees open to 3" from latch in less than 3 sec. 4.13.10
2586 08 A-104 Men's Toilet Room 15# Force to operate interior non-fire-rated door exceeds 5#. 4.13.11(2)(b)
2587 08 A-104 Men's Toilet Room Visual alarm on ceiling Visual Signal(s) mounted at incorrect height. Visual signal is to be mounted at 80" AFF or 6" below ceiling (whichever is lower). 4.28.3(6)
2588 08 A-104 Men's Toilet Room No raised lettering and Braille Existing room and/or gender identification signage is noncompliant. 4.1.3(16)(a), 4.30.4
2589 08 A-104 Men's Toilet Room Sign above door Existing room and/or identification sign is incorrectly located. 4.30.6
2591 08 A-104 Men's Toilet Room 2" rise Change in level > .5". 4.3.8; Fig. 7c, 7d
2592 08 A-104 Men's Toilet Room 4 stalls, 0 accessible No standard accessible toilet stall. If > one but < six, one standard accessible stall required. 4.1.3(11), 4.22.4, 4.17.3; Fig. 30a
2593 08 A-104 Men's Toilet Room 24" clear Stall door width < 32" clear width. 4.1.3(11), 4.22.4, 4.17.5; Fig. 30
2594 08 A-104 Men's Toilet Room No grab bars No grab bars. 4.1.3(11), 4.22.4, 4.16.4, 4.17.6; Fig. 28, 29, 30
2595 08 A-104 Men's Toilet Room 16" AFF Top of water closet seat <17" or > 19" above finish floor. 4.1.3(11), 4.22.4, 4.16.3, 4.17.2; Fig. 29b, 30(d)
2596 08 A-104 Men's Toilet Room 9# Manual flush control at water closet requires > 5 lbs. of force to activate. 4.1.3(11), 4.22.4, 4.16.5, 4.17.2, 4.27.4
2597 08 A-104 Men's Toilet Room Large roll toilet paper Large roll toilet paper dispenser requires pinching and does not allow continuous delivery. 4.1.3(11), 4.22.4, 4.16.6, 4.17.2; Fig. 29b, 30(d)
2599 08 A-104 Men's Toilet Room 11# Manual flush control at urinal requires > five pounds force to activate. 4.1.3(11), 4.22.5, 4.18.4, 4.27.4
2600 08 A-104 Men's Toilet Room 26.5" knee clearance Lavatory with < required knee clearance and/or toe clearance. 4.1.3(11), 4.22.6, 4.19.2; Fig. 31
2601 08 A-104 Men's Toilet Room 11# Faucet controls requires > 5 pounds of force to operate. 4.1.3(11), 4.22.6, 4.19.5, 4.27.4
2602 08 A-104 Men's Toilet Room 46.5" AFF Bottom of mirror reflecting surface > 40" above finish floor. 4.1.3(11), 4.22.6, 4.19.6; Fig. 31
2603 08 A-104 Men's Toilet Room 67" AFF Towel dispenser or blower outside reach range. 4.1.3(11), 4.22.7, 4.27.3; Fig. 4, 5, 6
2604 08 A-104 Men's Toilet Room 7# Control or operating mechanism takes > 5 lbs. force to operate or requires tight gripping, grasping or twisting of wrist. Towel dispenser. 4.1.3(11), 4.22.7, 4.27.4
2605 08 A-104 Men's Toilet Room 14# Control or operating mechanism takes > 5 lbs. force to operate or requires tight gripping, grasping or twisting of wrist. Soap dispenser. 4.1.3(11), 4.22.7, 4.27.4
2606 08 A-105 Public Pay Telephone 64.25" AFF Operable parts of phone outside reach range. 4.1.3(17), 4.31.3; Fig. 5, 6, 44a-b
2607 08 A-105 Public Pay Telephone No volume control Accessible telephone does not have volume control. 4.1.3(17)(b)
2608 08 A-105 Public Pay Telephone Grasping and twisting Push button controls are required: Operable part of telephone requires grasping or twisting to operate 4.31.6
2609 08 A-106 Door between Concourse and Seating Knob Existing door hardware requires tight grasping, pinching, or twisting of the wrist to operate. 4.13.9
2610 08 A-107 Visual Alarm in Concourse by Column 21 Visual alarm on ceiling Visual Signal(s) mounted at incorrect height. Visual signal is to be mounted at 80" AFF or 6" below ceiling (whichever is lower). 4.28.3(6)
2611 08 A-108 Visual Alarm in Concourse by Column 19 Visual alarm on ceiling Visual Signal(s) mounted at incorrect height. Visual signal is to be mounted at 80" AFF or 6" below ceiling (whichever is lower). 4.28.3(6)
2612 08 A-109 Fire Pull at Column 21 63" AFF Control outside reach range. 4.1.3(13), 4.27.3; Fig. 5, 6
2613 08 B-101 Public Pay Telephone Grasping and twisting Push button controls are required: Operable part of telephone requires grasping or twisting to operate 4.31.6
2614 08 B-101 Public Pay Telephone 27.75" AFF, 12" projection Telephone mounted with bottom between 27" and 80" AFF projects > 4" from the wall or > 12" from a post. 4.31.4, 4.4.1; Fig. 8a-e
2617 08 B-102 Corridor Ramp No handrail Ramp > 6" high, or > 72" long with no handrail or with handrail on one side only. 4.8.5
2619 08 B-103 Elevator Lobby Jamb identification, 1 side only Floor Designations at Elevator Hoistway are not located on both jambs of Hoistway openings. 4.10.5; Fig. 20
2621 08 B-104 Lobby Doors 2 seconds Existing Closer causes Door to travel from 70 degrees open to 3" from latch in less than 3 sec. 4.13.10
2622 08 B-105 Door between Concourse and Seating at Column 30 Knob Existing door hardware requires tight grasping, pinching, or twisting of the wrist to operate. 4.13.9
2623 08 B-106 Public Pay Telephones 64.25" AFF Operable parts of phone outside reach range. Two public pay telephones, none accessible. 4.1.3(17), 4.31.3; Fig. 5, 6, 44a-b
2624 08 B-106 Public Pay Telephones No volume control Accessible telephone does not have volume control. 4.1.3(17)(b)
2625 08 B-106 Public Pay Telephones Grasping and twisting Push button controls are required: Operable part of telephone requires grasping or twisting to operate 4.31.6
2626 08 B-107 Women's Toilet Room 27.5" clear Clear width of active leaf of double door < 32". (Deduct 5/8" from width criteria for Alt. Tech. Infeas.) 4.13.5; Fig. 24
2627 08 B-107 Women's Toilet Room 21# Force to operate interior non-fire-rated door exceeds 5#. 4.13.11(2)(b)
2628 08 B-107 Women's Toilet Room Visual alarm on ceiling Visual Signal(s) mounted at incorrect height. Visual signal is to be mounted at 80" AFF or 6" below ceiling (whichever is lower). 4.28.3(6)
2629 08 B-107 Women's Toilet Room No raised lettering and Braille Existing room and/or gender identification signage is noncompliant. 4.1.3(16)(a), 4.30.4
2630 08 B-107 Women's Toilet Room Above door Existing room and/or identification sign is incorrectly located. 4.30.6
2632 08 B-107 Women's Toilet Room 10 stalls, 0 ambulatory If greater than or equal to 6, and if standard accessible stall provided, 36" wide ambulatory accessible stall also required. 4.1.3(11), 4.22.4; Fig. 30d
2633 08 B-107 Women's Toilet Room 10 stalls, 0 accessible No standard accessible toilet stall. If > one but < six, one standard accessible stall required. 4.1.3(11), 4.22.4, 4.17.3; Fig. 30a
2634 08 B-107 Women's Toilet Room 23.5" clear Stall door width < 32" clear width. 4.1.3(11), 4.22.4, 4.17.5; Fig. 30
2635 08 B-107 Women's Toilet Room 15.25" AFF Top of water closet seat <17" or > 19" above finish floor. 4.1.3(11), 4.22.4, 4.16.3, 4.17.2; Fig. 29b, 30(d)
2636 08 B-107 Women's Toilet Room 15.5" centerline Centerline of water closet is < or > 18" from sidewall or partition. 4.1.3(11), 4.22.4, 4.16.2, 4.17.3; Fig. 28, 30
2637 08 B-107 Women's Toilet Room 12# Manual flush control at water closet requires > 5 lbs. of force to activate. 4.1.3(11), 4.22.4, 4.16.5, 4.17.2, 4.27.4
2638 08 B-107 Women's Toilet Room Large roll toilet paper Large roll toilet paper dispenser requires pinching and does not allow continuous delivery. 4.1.3(11), 4.22.4, 4.16.6, 4.17.2; Fig. 29b, 30(d)
2640 08 B-107 Women's Toilet Room No insulation Hot water pipes not insulated or covered. 4.1.3(11), 4.22.6, 4.19.4
2641 08 B-107 Women's Toilet Room 7 seconds Self-closing faucet < 10 seconds open. 4.1.3(11), 4.22.6, 4.19.5
2642 08 B-107 Women's Toilet Room 7# Faucet controls requires > 5 pounds of force to operate. 4.1.3(11), 4.22.6, 4.19.5, 4.27.4
2643 08 B-107 Women's Toilet Room 46" AFF Bottom of mirror reflecting surface > 40" above finish floor. 4.1.3(11), 4.22.6, 4.19.6; Fig. 31
2644 08 B-107 Women's Toilet Room 66.75" AFF Towel dispenser or blower outside reach range. 4.1.3(11), 4.22.7, 4.27.3; Fig. 4, 5, 6
2645 08 B-107 Women's Toilet Room 15# Control or operating mechanism takes > 5 lbs. force to operate or requires tight gripping, grasping or twisting of wrist. Soap dispenser. 4.1.3(11), 4.22.7, 4.27.4
2650 08 B-109 Visual Alarm in Concourse by Column 30 Visual alarm on ceiling Visual Signal(s) mounted at incorrect height. Visual signal is to be mounted at 80" AFF or 6" below ceiling (whichever is lower). 4.28.3(6)
2651 08 B-110 Visual Alarm in Concourse by Column 26 Visual alarm on ceiling Visual Signal(s) mounted at incorrect height. Visual signal is to be mounted at 80" AFF or 6" below ceiling (whichever is lower). 4.28.3(6)
2652 08 B-111 Visual Alarm in Concourse by Column 25 Visual alarm on ceiling Visual Signal(s) mounted at incorrect height. Visual signal is to be mounted at 80" AFF or 6" below ceiling (whichever is lower). 4.28.3(6)
2653 08 B-112 Fire Pull at Column 25 63" AFF Control outside reach range. 4.1.3(13), 4.27.3; Fig. 5, 6
2654 08 B-113 Fire Pull at Column 30 63" AFF Control outside reach range. 4.1.3(13), 4.27.3; Fig. 5, 6
2655 08 C-101 Men's Toilet Room 27.5" clear Clear width of active leaf of double door < 32". (Deduct 5/8" from width criteria for Alt. Tech. Infeas.) 4.13.5; Fig. 24
2656 08 C-101 Men's Toilet Room 2 seconds Existing Closer causes Door to travel from 70 degrees open to 3" from latch in less than 3 sec. 4.13.10
2657 08 C-101 Men's Toilet Room 12# Force to operate interior non-fire-rated door exceeds 5#. 4.13.11(2)(b)
2658 08 C-101 Men's Toilet Room Visual alarm on ceiling Visual Signal(s) mounted at incorrect height. Visual signal is to be mounted at 80" AFF or 6" below ceiling (whichever is lower). 4.28.3(6)
2659 08 C-101 Men's Toilet Room No raised lettering and Braille Existing room and/or gender identification signage is noncompliant. 4.1.3(16)(a), 4.30.4
2660 08 C-101 Men's Toilet Room Sign above door Existing room and/or identification sign is incorrectly located. 4.30.6
2662 08 C-101 Men's Toilet Room .75" AFF Change in level > .5". Marble threshold. 4.3.8; Fig. 7c, 7d
2663 08 C-101 Men's Toilet Room 4 stalls, 0 accessible No standard accessible toilet stall. If > one but < six, one standard accessible stall required. 4.1.3(11), 4.22.4, 4.17.3; Fig. 30a
2664 08 C-101 Men's Toilet Room 24" clear Stall door width < 32" clear width. 4.1.3(11), 4.22.4, 4.17.5; Fig. 30
2665 08 C-101 Men's Toilet Room 65.5" AFF Coat hook > 48" above finish floor front reach, or > 54"; side reach. 4.22.7, 4.27.3; Fig. 5, 6
2666 08 C-101 Men's Toilet Room 16" AFF Top of water closet seat <17" or > 19" above finish floor. 4.1.3(11), 4.22.4, 4.16.3, 4.17.2; Fig. 29b, 30(d)
2667 08 C-101 Men's Toilet Room 15" centerline Centerline of water closet is < or > 18" from sidewall or partition. 4.1.3(11), 4.22.4, 4.16.2, 4.17.3; Fig. 28, 30
2669 08 C-101 Men's Toilet Room 8# Manual flush control at water closet requires > 5 lbs. of force to activate. 4.1.3(11), 4.22.4, 4.16.5, 4.17.2, 4.27.4
2670 08 C-101 Men's Toilet Room 9# Manual flush control at water closet requires > 5 lbs. of force to activate. 4.1.3(11), 4.22.4, 4.16.5, 4.17.2, 4.27.4
2672 08 C-101 Men's Toilet Room Not insulated Hot water pipes not insulated or covered. 4.1.3(11), 4.22.6, 4.19.4
2673 08 C-101 Men's Toilet Room 10# Faucet controls requires > 5 pounds of force to operate. 4.1.3(11), 4.22.6, 4.19.5, 4.27.4
2674 08 C-101 Men's Toilet Room 46.25" AFF Bottom of mirror reflecting surface > 40" above finish floor. 4.1.3(11), 4.22.6, 4.19.6; Fig. 31
2675 08 C-101 Men's Toilet Room 67.25" AFF Towel dispenser or blower outside reach range. 4.1.3(11), 4.22.7, 4.27.3; Fig. 4, 5, 6
2676 08 C-101 Men's Toilet Room 14# Control or operating mechanism takes > 5 lbs. force to operate or requires tight gripping, grasping or twisting of wrist. Soap dispenser. 4.1.3(11), 4.22.7, 4.27.4
2679 08 C-102 Corridor Ramp No handrail Ramp > 6" high, or > 72" long with no handrail or with handrail on one side only. 4.8.5
2680 08 C-103 Public Pay Telephone 64" AFF Operable parts of phone outside reach range. Two pay telephones, none accessible. 4.1.3(17), 4.31.3; Fig. 5, 6, 44a-b
2681 08 C-103 Public Pay Telephone No volume control Accessible telephone does not have volume control. 4.1.3(17)(b)
2682 08 C-103 Public Pay Telephone Grasping and twisting Push button controls are required: Operable part of telephone requires grasping or twisting to operate 4.31.6
2686 08 C-106 Public Pay Telephone No volume control Accessible telephone does not have volume control. 4.1.3(17)(b)
2687 08 C-106 Public Pay Telephone Grasping and twisting Push button controls are required: Operable part of telephone requires grasping or twisting to operate 4.31.6
2692 08 C-108 Visual Alarm in Concourse by Column 1 Visual alarm on ceiling Visual Signal(s) mounted at incorrect height. Visual signal is to be mounted at 80" AFF or 6" below ceiling (whichever is lower). 4.28.3(6)
2693 08 C-109 Visual Alarm in Concourse by Column 47 Visual alarm on ceiling Visual Signal(s) mounted at incorrect height. Visual signal is to be mounted at 80" AFF or 6" below ceiling (whichever is lower). 4.28.3(6)
2694 08 C-110 Visual Alarm in Concourse by Column 44 Visual alarm on ceiling Visual Signal(s) mounted at incorrect height. Visual signal is to be mounted at 80" AFF or 6" below ceiling (whichever is lower). 4.28.3(6)
2695 08 C-111 Fire Pull at Column 43 62.5" AFF Control outside reach range. 4.1.3(13), 4.27.3; Fig. 5, 6
2696 08 C-112 Fire Pull at Column 1 64" AFF Control outside reach range. 4.1.3(13), 4.27.3; Fig. 5, 6
2698 08 D-102 Public Pay Telephone 64" AFF Operable parts of phone outside reach range. Two pay phones, none accessible. 4.1.3(17), 4.31.3; Fig. 5, 6, 44a-b
2699 08 D-102 Public Pay Telephone No volume control Accessible telephone does not have volume control. 4.1.3(17)(b)
2700 08 D-102 Public Pay Telephone Grasping and twisting Push button controls are required: Operable part of telephone requires grasping or twisting to operate 4.31.6
2703 08 D-103 Corridor Ramp No handrail Ramp > 6" high, or > 72" long with no handrail or with handrail on one side only. 4.8.5
2704 08 D-104 Women's Toilet Room 27.5" clear Clear width of active leaf of double door < 32". (Deduct 5/8" from width criteria for Alt. Tech. Infeas.) 4.13.5; Fig. 24
2705 08 D-104 Women's Toilet Room .75" abrupt Existing beveled threshold is greater than 3/4" high, or greater than 3/4" high at Exterior Sliding Door. Threshold at entrance to toilet room. 4.1.6(3)(d)(ii), 4.13.8; Fig. 7c, 7d
2706 08 D-104 Women's Toilet Room 12# Force to operate interior non-fire-rated door exceeds 5#. 4.13.11(2)(b)
2707 08 D-104 Women's Toilet Room Visual alarm on ceiling Visual Signal(s) mounted at incorrect height. Visual signal is to be mounted at 80" AFF or 6" below ceiling (whichever is lower). 4.28.3(6)
2708 08 D-104 Women's Toilet Room No raised lettering and Braille Existing room and/or gender identification signage is noncompliant. 4.1.3(16)(a), 4.30.4
2709 08 D-104 Women's Toilet Room Sign above door. Existing room and/or identification sign is incorrectly located. 4.30.6
2711 08 D-104 Women's Toilet Room 10 stalls, 0 ambulatory If greater than or equal to 6, and if standard accessible stall provided, 36" wide ambulatory accessible stall also required. 4.1.3(11), 4.22.4; Fig. 30d
2712 08 D-104 Women's Toilet Room 10 stalls, 0 accessible No standard accessible toilet stall. If > one but < six, one standard accessible stall required. 4.1.3(11), 4.22.4, 4.17.3; Fig. 30a
2713 08 D-104 Women's Toilet Room 23.25" clear Stall door width < 32" clear width. 4.1.3(11), 4.22.4, 4.17.5; Fig. 30
2714 08 D-104 Women's Toilet Room 67" AFF Coat hook > 48" above finish floor front reach, or > 54"; side reach. 4.22.7, 4.27.3; Fig. 5, 6
2715 08 D-104 Women's Toilet Room No grab bars No grab bars. 4.1.3(11), 4.22.4, 4.16.4, 4.17.6; Fig. 28, 29, 30
2716 08 D-104 Women's Toilet Room 16" AFF Top of water closet seat <17" or > 19" above finish floor. 4.1.3(11), 4.22.4, 4.16.3, 4.17.2; Fig. 29b, 30(d)
2717 08 D-104 Women's Toilet Room 14.25" centerline Centerline of water closet is < or > 18" from sidewall or partition. 4.1.3(11), 4.22.4, 4.16.2, 4.17.3; Fig. 28, 30
2718 08 D-104 Women's Toilet Room 9# Manual flush control at water closet requires > 5 lbs. of force to activate. 4.1.3(11), 4.22.4, 4.16.5, 4.17.2, 4.27.4
2719 08 D-104 Women's Toilet Room Large roll toilet paper Large roll toilet paper dispenser requires pinching and does not allow continuous delivery. 4.1.3(11), 4.22.4, 4.16.6, 4.17.2; Fig. 29b, 30(d)
2721 08 D-104 Women's Toilet Room No insulation Hot water pipes not insulated or covered. 4.1.3(11), 4.22.6, 4.19.4
2722 08 D-104 Women's Toilet Room 5 seconds Self-closing faucet < 10 seconds open. 4.1.3(11), 4.22.6, 4.19.5
2723 08 D-104 Women's Toilet Room 46.5" AFF Bottom of mirror reflecting surface > 40" above finish floor. 4.1.3(11), 4.22.6, 4.19.6; Fig. 31
2724 08 D-104 Women's Toilet Room 67.5" AFF Towel dispenser or blower outside reach range. 4.1.3(11), 4.22.7, 4.27.3; Fig. 4, 5, 6
2725 08 D-104 Women's Toilet Room 15# Control or operating mechanism takes > 5 lbs. force to operate or requires tight gripping, grasping or twisting of wrist. Soap dispenser. 4.1.3(11), 4.22.7, 4.27.4
2726 08 D-105 Public Pay Telephone No volume control Accessible telephone does not have volume control. 4.1.3(17)(b)
2727 08 D-105 Public Pay Telephone Grasping and twisting Push button controls are required: Operable part of telephone requires grasping or twisting to operate 4.31.6
2728 08 D-106 Visual Alarm in Concourse by Column 6 Visual alarm on ceiling Visual Signal(s) mounted at incorrect height. Visual signal is to be mounted at 80" AFF or 6" below ceiling (whichever is lower). 4.28.3(6)
2729 08 D-107 Visual Alarm in Concourse by Column 3 Visual alarm on ceiling Visual Signal(s) mounted at incorrect height. Visual signal is to be mounted at 80" AFF or 6" below ceiling (whichever is lower). 4.28.3(6)
2730 08 D-108 Fire Pull at Column 6 64.5" AFF Control outside reach range. 4.1.3(13), 4.27.3; Fig. 5, 6
2731 09 000 Public Pay Telephone No forward approach phone Two or more banks of public pay telephones on this floor. None meet the requirements for a forward reach telephone, where a minimum of 1 per floor is required. 4.1.3(17)(a)
2753 09 A-110 Visual Alarm in Corridor by Column 16 76" AFF, 9.75" from ceiling Visual Signal(s) mounted at incorrect height. Visual signal is to be mounted at 80" AFF or 6" below ceiling (whichever is lower). 4.28.3(6)
2757 09 B-102 Men's Toilet Room Visual alarm on ceiling Visual Signal(s) mounted at incorrect height. Visual signal is to be mounted at 80" AFF or 6" below ceiling (whichever is lower). 4.28.3(6)
2758 09 B-102 Men's Toilet Room No raised lettering and Braille Existing room and/or gender identification signage is noncompliant. 4.1.3(16)(a), 4.30.4
2759 09 B-102 Men's Toilet Room Not on latch side Existing room and/or identification sign is incorrectly located. 4.30.6
2760 09 B-102 Men's Toilet Room Inaccessible; no directional signage No directional signage to nearest accessible toilet room at inaccessible toilet room. 4.1.6(3)(e)(iii)
2779 09 B-103 Women's Toilet Room Visual alarm on ceiling Visual Signal(s) mounted at incorrect height. Visual signal is to be mounted at 80" AFF or 6" below ceiling (whichever is lower). 4.28.3(6)
2780 09 B-103 Women's Toilet Room No raised lettering and Braille Existing room and/or gender identification signage is noncompliant. 4.1.3(16)(a), 4.30.4
2781 09 B-103 Women's Toilet Room Not on latch side Existing room and/or identification sign is incorrectly located. 4.30.6
2782 09 B-103 Women's Toilet Room Inaccessible; no directional signage No directional signage to nearest accessible toilet room at inaccessible toilet room. 4.1.6(3)(e)(iii)
2844 09 C-106 Men's Toilet Room Visual alarm on ceiling Visual Signal(s) mounted at incorrect height. Visual signal is to be mounted at 80" AFF or 6" below ceiling (whichever is lower). 4.28.3(6)
2845 09 C-106 Men's Toilet Room No raised lettering and Braille Existing room and/or gender identification signage is noncompliant. 4.1.3(16)(a), 4.30.4
2846 09 C-106 Men's Toilet Room Not on latch side Existing room and/or identification sign is incorrectly located. 4.30.6
2847 09 C-106 Men's Toilet Room Inaccessible; no directional signage No directional signage to nearest accessible toilet room at inaccessible toilet room. 4.1.6(3)(e)(iii)
2868 09 C-107 Concession Counter; Slope Along Accessible Route 14.60% Excessive slope without handrails along accessible route 4.3.7, 4.5.2
2869 09 C-107 Condiment Counter 32" AFF, 15" projection Protruding object with bottom between 27" and 80" AFF projects more than 4" from wall or 12" from post. 4.4.1; Fig. 8a-d
2871 09 C-107 Concession Counter 40.75" AFF Sales, Service or Information Counter(s) or Teller Window(s) higher than 36" AFF or at Cash Register(s) for sales or distribution of goods or services to the public. 7.2
2872 09 C-108 Women's Toilet Room Visual alarm on ceiling Visual Signal(s) mounted at incorrect height. Visual signal is to be mounted at 80" AFF or 6" below ceiling (whichever is lower). 4.28.3(6)
2873 09 C-108 Women's Toilet Room No raised lettering and Braille Existing room and/or gender identification signage is noncompliant. 4.1.3(16)(a), 4.30.4
2874 09 C-108 Women's Toilet Room Not on latch side Existing room and/or identification sign is incorrectly located. 4.30.6
2875 09 C-108 Women's Toilet Room No directional signage No directional signage to nearest accessible toilet room at inaccessible toilet room. 4.1.6(3)(e)(iii)
2934 09 D-111 Visual Alarm in Concourse by Column 10 75.75" AFF, 10.5" from ceiling Visual Signal(s) mounted at incorrect height. Visual signal is to be mounted at 80" AFF or 6" below ceiling (whichever is lower). 4.28.3(6)
2982 10 A-110 Visual Alarm in Concourse by Column 18 Visual alarm on ceiling Visual Signal(s) mounted at incorrect height. Visual signal is to be mounted at 80" AFF or 6" below ceiling (whichever is lower). 4.28.3(6)
2983 10 A-111 Visual Alarm in Concourse by Column Visual alarm on ceiling Visual Signal(s) mounted at incorrect height. Visual signal is to be mounted at 80" AFF or 6" below ceiling (whichever is lower). 4.28.3(6)
2984 10 A-112 Visual Alarm in Concourse by Column Visual alarm on ceiling Visual Signal(s) mounted at incorrect height. Visual signal is to be mounted at 80" AFF or 6" below ceiling (whichever is lower).4.28.3(6)