Barrier Number | Floor | Location Number | Description | Condition | Barrier notes | Standards |
---|---|---|---|---|---|---|
177 | 01 | C-108 | Time Clock in Elevator Lobby | 8" projection, 39.5" AFF | Protruding object with bottom between 27" and 80" AFF projects more than 4" from wall or 12" from post. | 4.4.1; Fig. 8a-d |
273 | 01 | C-125 | Counter in Security Lobby by Time Clock | 8.5" projection, 39.25" AFF | Protruding object with bottom between 27" and 80" AFF projects more than 4" from wall or 12" from post. | 4.4.1; Fig. 8a-d |
1087 | 05 | 000- Phone | Public Pay Telephone | No forward approach phone | Two or more banks of public pay telephones on this floor. None meet the requirements for a forward reach telephone, where a minimum of 1 per floor is required. | 4.1.3(17)(a) |
1098 | 05 | A-106 | Concession Counter | 41.5" AFF | Sales, Service or Information Counter(s) or Teller Window(s) higher than 36" AFF or at Cash Register(s) for sales or distribution of goods or services | 7.2 |
1099 | 05 | A-107 | Condiment Counter | 14" projection, 34.75" AFF | Protruding object with bottom between 27" and 80" AFF projects more than 4" from wall or 12" from post. Object is located along route of travel. | 4.4.1; Fig. 8a-d |
1100 | 05 | A-107 | Condiment Counter | 42.25" AFF | Sales, Service or Information Counter(s) or Teller Window(s) higher than 36" AFF or at Cash Register(s) for sales or distribution of goods or services to the public. | 7.2 |
1109 | 05 | B-106 | Drinking Fountain | 41" AFF | Spout outlet higher than 36" AFF. | 4.15.2 |
1110 | 05 | B-106 | Drinking Fountain | 14# | Controls require more than 5# force to operate. | 4.15.4, 4.27.4 |
1111 | 05 | B-107 | Women's Toilet Room | Visual alarm on ceiling | Visual Signal(s) mounted at incorrect height. Visual signal is to be mounted at 80" AFF or 6" below ceiling (whichever is lower). | 4.28.3(6) |
1112 | 05 | B-107 | Women's Toilet Room | No raised lettering and Braille, sign in arch greater than 60" centerline | Existing room and/or gender identification signage is noncompliant. | 4.1.3(16)(a), 4.30.4, 4.30.6 |
1113 | 05 | B-107 | Women's Toilet Room | 10 stalls, 0 ambulatory | If greater than or equal to 6, and if standard accessible stall provided, 36" wide ambulatory accessible stall also required. | 4.1.3(11), 4.22.4; Fig. 30d |
1114 | 05 | B-107 | Women's Toilet Room | 40.5" wide | Accessible stall width < 60" | 4.1.3(11), 4.22.4, 4.17.3; Fig. 30a |
1115 | 05 | B-107 | Women's Toilet Room | 67.5" AFF | Coat hook > 48" above finish floor front reach, or > 54"; side reach. | 4.22.7, 4.27.3; Fig. 5, 6 |
1116 | 05 | B-107 | Women's Toilet Room | 1.75" clear | Grab bar-to-wall clearance < or > 1-1/2". | 4.1.3(11), 4.22.4, 4.16.4, 4.17.6, 4.26.2; Fig. 39 |
1117 | 05 | B-107 | Women's Toilet Room | No rear grab bars | No rear grab bar (except at 36" alternate accessible stall). | 4.1.3(11), 4.22.4, 4.16.4, 4.17.6; Fig. 29, 30 |
1118 | 05 | B-107 | Women's Toilet Room | 19.5" AFF | Top of water closet seat <17" or > 19" above finish floor. | 4.1.3(11), 4.22.4, 4.16.3, 4.17.2; Fig. 29b, 30(d) |
1119 | 05 | B-107 | Women's Toilet Room | 20" centerline | Centerline of water closet is < or > 18" from sidewall or partition. | 4.1.3(11), 4.22.4, 4.17.3; Fig. 28, 30 |
1119.1 | 05 | B-107 | Women's Toilet Room | door opposite toilet fixture | Stall door is immediately opposite the water closet instead of diagonally opposite and within 4" from corner of stall. | 4.1.3(11), 4.17.3, 4.22.4, Fig. 30 |
1120 | 05 | B-107 | Women's Toilet Room | 13# | Manual flush control at water closet requires > 5 lbs. of force to activate. | 4.1.3(11), 4.22.4, 4.16.5, 4.17.2, 4.27.4 |
1121 | 05 | B-107 | Women's Toilet Room | Large roll toilet paper | Large roll toilet paper dispenser requires pinching and does not allow continuous delivery. | 4.1.3(11), 4.22.4, 4.16.6, 4.17.2; Fig. 29b, 30(d) |
1122 | 05 | B-107 | Women's Toilet Room | No insulation | Hot water pipes not insulated or covered. | 4.1.3(11), 4.22.6, 4.19.4 |
1123 | 05 | B-107 | Women's Toilet Room | 66.75" AFF | Towel dispenser or blower outside reach range. | 4.1.3(11), 4.22.7, 4.27.3; Fig. 4, 5, 6 |
1124 | 05 | B-107 | Women's Toilet Room | 5" projection, 30" AFF | Control or operating mechanism takes > 5 lbs. force to operate or requires tight gripping, grasping or twisting of wrist. Soap dispenser. | 4.1.3(11), 4.22.7, 4.27.4 |
1125 | 05 | B-107 | Women's Toilet Room | 13# | Visual Signal(s) mounted at incorrect height. Visual signal is to be mounted at 80" AFF or 6" below ceiling (whichever is lower). | 4.28.3(6) |
1126 | 05 | B-108 | Men's Toilet Room | Visual alarm on ceiling | Visual Signal(s) mounted at incorrect height. Visual signal is to be mounted at 80" AFF or 6" below ceiling (whichever is lower). | 4.28.3(6) |
1127 | 05 | B-108 | Men's Toilet Room | Sign in arch greater than 60" centerline, no raised lettering and Braille | Existing room and/or gender identification signage is noncompliant. | 4.1.3(16)(a), 4.30.4, 4.30.6 |
1128 | 05 | B-108 | Men's Toilet Room | 41.5" wide | Accessible stall width < 60". | 4.1.3(11), 4.22.4, 4.17.3; Fig. 30a |
1129 | 05 | B-108 | Men's Toilet Room | No rear grab bar | No rear grab bar (except at 36" alternate accessible stall). | 4.1.3(11), 4.22.4, 4.16.4, 4.17.6; Fig. 29, 30 |
1130 | 05 | B-108 | Men's Toilet Room | 20" centerline | Centerline of water closet is < or > 18" from sidewall or partition. | 4.1.3(11), 4.22.4, 4.16.2, 4.17.3; Fig. 28, 30 |
1130.1 | 05 | B-108 | Men's Toilet Room | door opposite toilet fixture | Stall door is immediately opposite the water closet instead of diagonally opposite and within 4" from corner of stall. | 4.1.3(11), 4.17.3, 4.22.4, Fig. 30 |
1131 | 05 | B-108 | Men's Toilet Room | 12# | Manual flush control at water closet requires > 5 lbs. of force to activate | 4.1.3(11), 4.22.4, 4.16.5, 4.17.2, 4.27.4 |
1132 | 05 | B-108 | Men's Toilet Room | Large roll toilet paper | Large roll toilet paper dispenser requires pinching and does not allow continuous delivery. | 4.1.3(11), 4.22.4, 4.16.6, 4.17.2; Fig. 29b, 30(d) |
1133 | 05 | B-108 | Men's Toilet Room | 15# | Manual flush control at urinal requires > five pounds force to activate. | 4.1.3(11), 4.22.5, 4.18.4, 4.27.4 |
1134 | 05 | B-108 | Men's Toilet Room | No insulation | Hot water pipes not insulated or covered. | 4.1.3(11), 4.22.6, 4.19.4 |
1135 | 05 | B-108 | Men's Toilet Room | 67.5" AFF | Towel dispenser or blower outside reach range. | 4.1.3(11), 4.22.7, 4.27.3; Fig. 4, 5, 6 |
1136 | 05 | B-108 | Men's Toilet Room | 5" projection, 30.75" AFF | Protruding object with bottom between 27" and 80" above finish floor projects > 4" from wall into circulation path. Baby changing station. | 4.4.1, 4.4.2; Fig. 8 |
1137 | 05 | B-108 | Men's Toilet Room | 16# | Control or operating mechanism takes > 5 lbs. force to operate or requires tight gripping, grasping or twisting of wrist. Soap dispenser. | 4.1.3(11), 4.22.7, 4.27.4 |
1138 | 05 | B-109 | Corridor Doors | 1.5 seconds | Existing Closer causes Door to travel from 70 degrees open to 3" from latch in less than 3 sec. | 4.13.10 |
1140 | 05 | B-111 | Box in Corridor | 12.5" projection, 65" AFF | Protruding object with bottom between 27" and 80" AFF projects more than 4" from wall or 12" from post. | 4.4.1; Fig. 8a-d |
1146 | 05 | B-117 | Fire Pull at Column 29 | 63" AFF | Control outside reach range. | 4.1.3(13), 4.27.3; Fig. 5, 6 |
1644 | 05 | D-116 | Lighted Sign | 5.5" projection, 34.5" AFF | Protruding object with bottom between 27" and 80" AFF projects more than 4" from wall or 12" from post. | 4.4.1; Fig. 8a-d |
1645 | 05 | D-117 | Public Pay Telephone | No outlet | Bank of 3 or more phones: None have shelf or outlet for portable TTY. | 4.1.3(17)(d) |
1646 | 05 | D-117 | Public Pay Telephone | 65" AFF | Operable parts of phone outside reach range. Three public pay telephones, none accessible. | 4.1.3(17), 4.31.3; Fig. 5, 6, 44a-b |
1647 | 05 | D-117 | Public Pay Telephone | No volume control | Accessible telephone does not have volume control. | 4.1.3(17)(b) |
1648 | 05 | D-117 | Public Pay Telephone | Grasping and twisting | Push button controls are required: Operable part of telephone requires grasping or twisting to operate | 4.31.6 |
1650 | 05 | D-118 | Lobby Doors | 2 seconds | Existing Closer causes Door to travel from 70 degrees open to 3" from latch in less than 3 sec. | 4.13.10 |
1661.1 | 05 | D-125 | Women's Toilet Room | No directional signage | No directional signage to nearest accessible toilet room at inaccessible toilet room. | 4.1.6(3)(e)(iii) |
1665 | 05 | D-125 | Women's Toilet Room | Visual alarm on ceiling | Visual Signal(s) mounted at incorrect height. Visual signal is to be mounted at 80" AFF or 6" below ceiling (whichever is lower). | 4.28.3(6) |
1666 | 05 | D-125 | Women's Toilet Room | No raised lettering and Braille, sign suspended from ceiling | Existing room and/or gender identification signage is noncompliant. MSG will provide directional signage to the nearest accessible restroom. | 4.1.3(16)(a), 4.30.4, 4.30.6 |
1681.1 | 05 | D-126 | Men's Toilet Room | Inaccessible; no directional signage | No directional signage to nearest accessible toilet room at inaccessible toilet room. | .1.6(3)(e)(iii) |
1683 | 05 | D-126 | Men's Toilet Room | Visual alarm on ceiling | Visual Signal(s) mounted at incorrect height. Visual signal is to be mounted at 80" AFF or 6" below ceiling (whichever is lower). | 4.28.3(6) |
1684 | 05 | D-126 | Men's Toilet Room | Sign on door, no raised lettering and Braille | Existing room and/or gender identification signage is noncompliant. MSG will provide directional signage to the nearest accessible restroom. | 4.1.3(16)(a), 4.30.4, 4.30.6 |
1702.1 | 05 | D-127 | Men's Toilet Room | Inaccessible; no directional signage | No directional signage to nearest accessible toilet room at inaccessible toilet room. | 4.1.6(3)(e)(iii) |
1705 | 05 | D-127 | Men's Toilet Room | Visual alarm on ceiling | Visual Signal(s) mounted at incorrect height. Visual signal is to be mounted at 80" AFF or 6" below ceiling (whichever is lower). | 4.28.3(6) |
1706 | 05 | D-127 | Men's Toilet Room | No raised lettering and Braille, sign suspended from ceiling | Existing room and/or gender identification signage is noncompliant. MSG will provide directional signage to the nearest accessible restroom. | 4.1.3(16)(a), 4.30.4, 4.30.6 |
1723.1 | 05 | D-128 | Women's Toilet Room | Inaccessible; no directional signage | No directional signage to nearest accessible toilet room at inaccessible toilet room. | 4.1.6(3)(e)(iii) |
1726 | 05 | D-128 | Women's Toilet Room | Visual alarm on ceiling | Visual Signal(s) mounted at incorrect height. Visual signal is to be mounted at 80" AFF or 6" below ceiling (whichever is lower). MSG will provide directional signage to the nearest accessible restroom. | 4.28.3(6) |
1727 | 05 | D-128 | Women's Toilet Room | Sign on door, no raised lettering and Braille | Existing room and/or gender identification signage is noncompliant. MSG will provide directional signage to the nearest accessible restroom. | 4.1.3(16)(a), 4.30.4, 4.30.6 |
1746 | 05 | D-132 | Gift and Souvenir Counter | 41.5" AFF | Sales, Service or Information Counter(s) or Teller Window(s) higher than 36" AFF or at Cash Register(s) for sales or distribution of goods or services to the public. | 7.2 |
1747 | 05 | D-133 | Concession Counter | 42" AFF | Sales, Service or Information Counter(s) or Teller Window(s) higher than 36" AFF or at Cash Register(s) for sales or distribution of goods or services to the public. | 7.2 |
1748 | 05 | D-134 | Condiment Counter | 14" projection, 35" AFF | Protruding object with bottom between 27" and 80" AFF projects more than 4" from wall or 12" from post. | 4.4.1; Fig. 8a-d |
1749 | 05 | D-134 | Condiment Counter | 42.25" AFF | Sales, Service or Information Counter(s) or Teller Window(s) higher than 36" AFF or at Cash Register(s) for sales or distribution of goods or services to the public. | 7.2 |
1750 | 05 | D-135 | Lighted Sign | 5.5" projection, 33.25" AFF | Protruding object with bottom between 27" and 80" AFF projects more than 4" from wall or 12" from post. | 4.4.1; Fig. 8a-d |
1808 | 05 | D-145 | Visual Alarm in Corridor | Visual alarm on ceiling | Visual Signal(s) mounted at incorrect height. Visual signal is to be mounted at 80" AFF or 6" below ceiling (whichever is lower). | 4.28.3(6) |
1809 | 05 | D-146 | Visual Alarm in Corridor | Visual alarm on ceiling | Visual Signal(s) mounted at incorrect height. Visual signal is to be mounted at 80" AFF or 6" below ceiling (whichever is lower). | 4.28.3(6) |
1810 | 05 | D-147 | Visual Alarm in Corridor (by Gate #52) | Visual alarm on ceiling | Visual Signal(s) mounted at incorrect height. Visual signal is to be mounted at 80" AFF or 6" below ceiling (whichever is lower). | 4.28.3(6) |
1812 | 05 | D-149 | Fire Pull at Column 7 (located across from elevator) | 63" AFF | Control outside reach range. | 4.1.3(13), 4.27.3; Fig. 5, 6 |
3117 | 05 | B-107 | Women's Toilet Room | 32.5" AFF | The height from the centerline of grab bar(s) to finish floor is < 33" or > 36". | 4.1.3(11), 4.22.4, 4.16.4, 4.17.6; Fig. 29, 30 |
3118 | 05 | B-108 | Men's Toilet Room | 32.75" AFF | The height from the centerline of grab bar(s) to finish floor is < 33" or > 36". | 4.1.3(11), 4.22.4, 4.16.4, 4.17.6; Fig. 29, 30 |