ATTACHMENT K: Program Access in Existing FacilitiesPlease Note: Paragraph 54 of the Agreement requires that within nine months of the effective date of this Agreement, the City of Jacksonville will provide signage as necessary to comply with 28 C.F.R. § 35.163(b), after having surveyed all facilities that are the subject of this Agreement for the purpose of identifying those that have multiple entrances not all of which are accessible. The technical requirements and, where appropriate, the scoping requirements of the Standards are used as a guide for determining whether a program or activity held in an existing facility is “readily accessible to and usable by” persons with disabilities and for determining what changes are necessary to make this program or activity accessible if it continues to be provided in the existing facility in question. See 28 C.F.R. §§ 35.150(b)(1), 35.151. The chart below lists the facilities surveyed by the Department, the access issues identified during the survey, and the actions required to correct the access issues. Required actions are listed using an alphanumeric code. The key to the alphanumeric codes is provided in Attachment M to this Agreement. In order to ensure that the programs, services, and activities housed in the City of Jacksonville facilities are accessible to persons with disabilities, when viewed in their entirety, the City of Jacksonville will take the actions referenced by the alphanumeric code and described in detail in Attachment M to this Settlement Agreement within the time period specified below, which time period begins to run on the effective date of the Agreement. |
|||
Item # | Access Issue | Required Action | Completion Date |
---|---|---|---|
1. | IM Sulzbacher Shelter, 611 Adams Street | ||
1.1 | Entrance ramp: The ramp is inaccessible because it has a slope between 8.9% and 10.2% and the handrails lack extensions. | R3 | 36 months |
1.2 | Dorms: | ||
1.2.a | The facility is inaccessible because no accessible sleeping rooms are provided. A total of 2 accessible rooms is required. | L1 | 12 months |
1.2.b | The lift to the 2nd floor is inaccessible because it requires that a key be obtained from an employee before the lift can be operated. | LF2 | 12 months |
1.3 | Single-user unisex toilet room in lobby: | ||
1.3.a | The toilet room sign is mounted on the door and has no raised or Braille characters. | TR11 | 12 months |
1.3.b | The door is inaccessible because it requires 12 pounds of force to open. | D12 | 12 months |
1.3.c | The push side of the door, which is accessed through a front approach and which has both a closer and a latch, is inaccessible because it has only 2 inches of clear space on the latch side. | D5 | 24 months |
1.3.d | The toilet room is inaccessible because there is insufficient turning space provided within the room. | TR21 | 24 months |
1.3.e | Main Women / Family area: The telephones and a box on the wall in the main area protrude into the walkway and are not detectable to blind persons using a cane. | AR7 | 24 months |
1.4 | Single-user unisex toilet rooms in main Women / Family area: | ||
1.4.a | The toilet room signs are mounted on the door and have no raised or Braille characters. | LS3 | 12 months |
1.4.b | The doors are inaccessible because they require 9 pounds of force to open. | D12 | 24 months |
1.4.c | The push side of each door, which is accessed through a front approach and which has both a closer and a latch, is inaccessible because it has only 6 inches of clear space on the latch side. | D5 | 24 months |
1.4.d | Although an audible alarm is provided in this facility, there is no visual alarm appliance in either toilet room. | AL1 | 36 months |
1.4.e | No accessible coat hook has been provided in either room. | TR3 | 12 months |
1.4.f | The soap dispensers are inaccessible because they are mounted 53 inches high above the lavatory. | CT3 | 12 months |
1.4.g | The paper towel dispensers are inaccessible because they are mounted with the controls 51 inches high. | CT4 | 12 months |
1.4.h | One of the toilets is inaccessible because the flush control is on the closed side. | TR4 | 24 months |
1.4.i | The toilets are inaccessible because the side grab bars are obstructed by the toilet paper dispensers. | TR15 | 12 months |
1.4.j | The rear grab bars at the toilets are inaccessible because they are obstructed by the toilet flush valve. | TR15 | 12 months |
1.5 | Drinking fountain in main Women / Family area: | ||
1.5.a | The drinking fountain is inaccessible because it has a spout that is 39 1/2 inches high. | DF3 | 24 months |
1.5.b | The drinking fountain is inaccessible because its control requires 10 pounds of force to operate. | DF2 | 24 months |
1.6 | Women’s locker room in Women / Family area: | ||
1.6.a | The toilet room sign is mounted on the door and has no raised or Braille characters. | LS3 | 12 months |
1.6.b | The door is inaccessible because it requires 8 pounds of force to open. | D3 | 12 months |
1.6.c | No accessible coat hook has been provided. | TR3 | 12 months |
1.6.d | The side grab bar at the designated accessible toilet is inaccessible because it is obstructed by the toilet paper dispenser. | TR15 | 12 months |
1.6.e | There is no accessible shower provided. | B2 | 24 months |
1.6.f | The shelf in the shower protrudes into the walkway and is not detectable to blind persons using a cane. | AR7 | 24 months |
1.7 | Men’s locker room in Women / Family area: | ||
1.7.a | The toilet room sign is mounted on the door and has no raised or Braille characters. | LS3 | 12 months |
1.7.b | The door is inaccessible because it requires 14 pounds of force to open. | D3 | 12 months |
1.7.c | No accessible coat hook has been provided. | TR3 | 12 months |
1.7.d | There is no accessible shower provided. | B2 | 24 months |
1.7.e | The shelf in the shower protrudes into the walkway and is not detectable to blind persons using a cane. | AR7 | 24 months |
1.8 | Women / Family area side patio: | ||
1.8.a | The exterior stairway creates an overhead hazard that is not detectable to blind persons using a cane. | AR6 | 36 months |
1.8.b | The picnic tables are inaccessible because none provide the required knee space. | DW1 | 24 months |
1.8.c | The route to the playground is inaccessible because the dirt is not firm, stable, and slip-resistant and there is a step up onto the playground surface. | AR1 | 36 months |
1.8.d | The cement ramp along the wall to the patio is inaccessible because it lacks edge protection, one handrail does not extend the entire length of the ramp, the handrails lack extensions, and the diameter of the handrails is 1 3/4 inches. | R1 | 36 months |
1.8.e | The wooden ramp to the patio is inaccessible because it lacks handrails. | R3 | 24 months |
1.9 | North side Women / Singles entrance: The door is inaccessible because it requires 8 pounds of force to open. | D3 | 12 months |
1.10 | North Women / Singles / Families Common Room: | ||
1.10.a | The door is inaccessible because knob hardware is used. | D2 | 12 months |
1.10.b | The telephone is inaccessible because it lacks volume control. | TT1 | 24 months |
1.11 | Locker room for north Women / Singles / Families bedrooms: | ||
1.11.a | The door is inaccessible because it requires 14 pounds of force to open. | D3 | 12 months |
1.11.b | The baby changing table is inaccessible because it is mounted with the controls 63 inches high. | CT4 | 12 months |
1.11.c | No accessible coat hook has been provided. | TR3 | 12 months |
1.11.d | The roll-in shower is not accessible because there are grab bars on only 2 walls, and the controls are 55 inches high. | B2 | 24 months |
1.11.e | The shelf in the shower protrudes into the walkway and is not detectable to blind persons using a cane. | AR7 | 24 months |
1.12 | South side Women / Singles entrance: | ||
1.12.a | The doors are inaccessible because they require 11 pounds and 15 pounds of force to open. | D3 | 12 months |
1.12.b | The exterior door is inaccessible because knob hardware is used. | D2 | 12 months |
1.12.c | The push side of the exterior door, which is accessed through a front approach and which has both a closer and a latch, is inaccessible because it has only 9 inches of clear space on the latch side. | D5 | 24 months |
1.13 | South Women / Singles common area: The telephone is inaccessible because it lacks volume control. | TT1 | 24 months |
1.14 | South Women / Singles side patio: The push side of the door, which is accessed through a front approach and which has both a closer and a latch, is inaccessible because it has only 11 inches of clear space on the latch side. | D5 | 24 months |
1.15 | South Women / Singles / Families locker room: | ||
1.15.a | The toilet room sign is inaccessible. | TR11 | 12 months |
1.15.b | The entrance door is inaccessible because it requires 6 pounds of force to open. | D3 | 12 months |
1.15.c | The pull side of the door, which is accessed through a front approach, is inaccessible because it has only 14 inches of clear space on the latch side. | D5 | 24 months |
1.15.d | The designated accessible toilet is inaccessible because the flush control is on the closed side. | TR4 | 24 months |
1.15.e | No accessible coat hook has been provided. | TR3 | 12 months |
1.15.f | The roll-in shower is inaccessible because the controls are 56 inches high. | B2 | 24 months |
1.16 | Case manager’s office: The door is inaccessible because knob hardware is used. | D3 | 12 months |
1.17 | Dining hall: | ||
1.17.a | The pull side of the door, which is accessed through a front approach, is inaccessible because it has only 9 inches of clear space on the latch side. | D5 | 24 months |
1.17.b | The food distribution counter is inaccessible because it is 41 1/2 inches high. | DW1 | 24 months |
1.18 | Single user toilet rooms with baths on second floor (rooms 212 and 210/211): | ||
1.18.a | The toilet room signs are mounted on the doors. | TR11 | 12 months |
1.18.b | The doors are inaccessible because they require 12 pounds of force to open. | D3 | 12 months |
1.18.c | Although an audible alarm is provided in this facility, there is no visual alarm appliance in either toilet room. | AL1 | 36 months |
1.18.d | The lavatories are inaccessible because the hot water pipes are not insulated or otherwise configured to protect against contact. | LS2 | 12 months |
1.18.e | The toilets are inaccessible because the top of the seat is 16 inches high. | TR9 | 36 months |
1.18.f | The toilet in room 210/211 is inaccessible because the flush control is on the closed side. | TR4 | 24 months |
1.18.g | The bathtubs are inaccessible because no seat is provided, the showerhead cannot be handheld, the clear floor space is 25 inches wide, and the grab bars at the heads of each bathtub are 12 inches long. | B1 | 24 months |
1.19 | Men’s pavilion: | ||
1.19.a | The drinking fountain protrudes into the walkway and is not detectable to blind persons using a cane. | AR7 | 24 months |
1.19.b | Although a designated accessible drinking fountain is provided, there is no drinking fountain provided for people who have difficult bending or stooping. | DF3 | 12 months |
1.19.c | The picnic tables are inaccessible because none provide the required knee space. | DW1 | 24 months |
1.20 | Men’s common area: | ||
1.20.a | The entry door is inaccessible because it requires 15 pounds of force to open. | D3 | 12 months |
1.20.b | The drinking fountain is inaccessible because the controls require 10 pounds of force to operate. | DF2 | 24 months |
1.21 | Men’s locker room: | ||
1.21.a | The toilet room sign is inaccessible. | TR11 | 12 months |
1.21.b | The entry door is inaccessible because it requires 15 pounds of force to open. | D3 | 12 months |
1.21.c | No accessible mirror has been provided. | TR5 | 12 months |
1.21.d | The lavatory is inaccessible because the hot water pipes are not insulated or otherwise configured to protect against contact. | LS2 | 12 months |
1.21.e | There is no accessible toilet stall provided. | TR2 | 24 months |
1.21.f | The roll-in shower is not accessible because there are no grab bars, and the controls are 55 inches high. | B2 | 24 months |
2. | Oceanway Park, 12215 Sago Avenue | ||
2.1 | Route from pool to playground: The route is inaccessible because it has a cross-slope of 6.3%. | AR1 | 36 months |
2.2 | Exterior playground drinking fountain: | ||
2.2.a | The drinking fountain is inaccessible because the controls require 12 pounds of force to operate. | DF2 | 24 months |
2.2.b | Although a designated accessible drinking fountain is provided, there is no drinking fountain provided for people who have difficulty bending or stooping. | DF3 | 12 months |
2.3 | Ramp to the dock: The ramp is inaccessible because there are no handrails provided. | R3 | 24 months |
2.4 | Route from parking to tennis courts: The route is inaccessible because the surface is not firm, stable, and slip-resistant due to sand. | AR1 | 36 months |
2.5 | Tennis court: | ||
2.5.a | The entryway onto the tennis court is inaccessible because it has an opening width of 34 inches for a length of more than 24 inches, and there is a portion that is 27 inches wide. | AR3 | 12 months |
2.5.b | The entrance door is inaccessible because it has an opening width of 29 inches. | D14 | 24 months |
2.6 | Route to ballfield: The route is inaccessible because the sand and grass are not firm, stable, and slip-resistant. | AR1 | 36 months |
2.7 | Ballfield bleachers: The bleachers are inaccessible because there is no wheelchair seating area provided. | AA6 | 36 months |
2.8 | Drinking fountain near toilet room by ballfield: | ||
2.8.a | The drinking fountain is inaccessible because the controls require 15 pounds of force to operate. | DF2 | 24 months |
2.8.b | Although a designated accessible drinking fountain is provided, there is no drinking fountain provided for people who have difficulty bending or stooping. | DF3 | 12 months |
2.9 | Route to basketball court and swings: The route is inaccessible because the sand and grass are not firm, stable, and slip-resistant. | AR1 | 36 months |
2.10 | Men’s toilet room by picnic pavilion: | ||
2.10.a | The toilet room sign is mounted on the door and has no raised or Braille characters. | TR11 | 12 months |
2.10.b | The urinal is inaccessible because the rim is 22 inches high. | TR8 | 36 months |
2.10.c | The designated accessible toilet is inaccessible because the flush control is on the closed side. | TR4 | 24 months |
2.10.d | No accessible coat hook has been provided. | TR3 | 12 months |
2.10.e | The side grab bar at the designated accessible toilet is inaccessible because it is mounted with the far end 48 inches from the rear wall. | TR16 | 12 months |
2.10.f | The rear grab bar at the designated accessible toilet is inaccessible because it is 24 inches long. | TR14 | 12 months |
2.11 | Women’s toilet room by picnic pavilion: | ||
2.11.a | The toilet room sign is mounted on the door and has no raised or Braille characters. | TR11 | 12 months |
2.11.b | The lavatory is inaccessible because it has twist-type hardware. | LS4 | 24 months |
2.11.c | The lavatory is inaccessible because the hot water pipes are not insulated or otherwise configured to protect against contact. | LS2 | 12 months |
2.11.d | No accessible coat hook has been provided. | TR3 | 12 months |
2.11.e | The side grab bar at the designated accessible toilet is inaccessible because it is mounted with the far end 48 inches from the rear wall. | TR16 | 12 months |
2.11.f | The rear grab bar at the designated accessible toilet is inaccessible because it is 24 inches long. | TR14 | 12 months |
3. | Oceanway Community Center, 12215 Sago Avenue | ||
3.1 | Route past office 3: The fire extinguisher outside Office 3 protrudes into the walkway and is not detectable to blind persons using a cane. | AR7 | 24 months |
3.2 | Main area: The doors in the main area are inaccessible because knob hardware is used. | D2 | 12 months |
3.3 | Women’s toilet room with stalls: | ||
3.3.a | The toilet room sign is mounted on the door. | TR11 | 12 months |
3.3.b | The doors are inaccessible because they require 10 and 11 pounds of force to open. | D3 | 12 months |
3.3.c | The entrance to the toilet room is inaccessible because the vestibule is not sufficiently deep. | D4 | 12 months |
3.3.d | Although an audible alarm is provided in this facility, there is no visual alarm appliance in the toilet room. | AL1 | 36 months |
3.3.e | No accessible mirror has been provided. | TR5 | 12 months |
3.3.f | The soap dispenser is inaccessible because it is mounted with the controls 56 inches high. | CT4 | 12 months |
3.3.g | The lavatory is inaccessible because the top of the rim or counter is 35 1/2 inches high. | LS3 | 36 months |
3.3.h | The toilet paper dispenser in the designated accessible stall is inaccessible because it is mounted on the far wall. | TR6 | 12 months |
3.3.i | The side grab bar at the designated accessible toilet is inaccessible because it is mounted with the far end 44 inches from the rear wall. | TR17 | 12 months |
3.3.j | The rear grab bar at the designated accessible toilet is inaccessible because it is 18 inches long and it is mounted 9 inches from the side wall. | TR14 | 12 months |
3.4 | Men’s toilet room: | ||
3.4.a | The toilet room sign is mounted on the door. | TR11 | 12 months |
3.4.b | The doors are inaccessible because they each require 11 pounds of force to open. | D3 | 12 months |
3.4.c | The entrance to the toilet room is inaccessible because the vestibule is not sufficiently deep. | D4 | 12 months |
3.4.d | Although an audible alarm is provided in this facility, there is no visual alarm appliance in the toilet room. | AL1 | 36 months |
3.4.e | No accessible mirror has been provided. | TR5 | 12 months |
3.4.f | The soap dispenser is inaccessible because it is mounted with the controls 58 inches high. | CT4 | 12 months |
3.4.g | The lavatory is inaccessible because the top of the rim or counter is 36 inches high. | LS3 | 36 months |
3.4.h | The urinal is inaccessible because the rim is 23 inches high and the flush control is 51 inches high. | TR8 | 36 months |
3.4.i | The designated accessible toilet is inaccessible because the top of the seat is not between 17 and 19 inches high. | TR9 | 24 months |
3.4.j | The designated accessible toilet is inaccessible because the flush control is on the closed side. | TR4 | 24 months |
3.4.k | The toilet paper dispenser in the designated accessible stall is inaccessible because it is mounted more than 9 inches from the front of the toilet. | TR6 | 12 months |
3.4.l | The side grab bar at the designated accessible toilet is inaccessible because it is mounted with the far end 44 inches from the rear wall. | TR17 | 12 months |
3.4.m | The rear grab bar at the designated accessible toilet is inaccessible because it is 18 inches long and it is mounted 9 1/2 inches from the side wall. | TR14 | 12 months |
3.4.n | The designated accessible toilet is inaccessible because the rear grab bar is obstructed by the toilet tank. | TR15 | 24 months |
3.4.o | There is no accessible shower provided. | B2 | 12 months |
3.5 | Drinking fountain near toilet rooms: The drinking fountain is inaccessible because the spout is 41 1/2 inches high. | DF3 | 24 months |
4. | Pre-Trial Detention Facility, 501 E. Adams Street | ||
4.1 | General: The counters and several other objects at the control stations throughout the facility protrude into the walkways and are not detectable to blind persons using a cane. | AR7 | 24 months |
4.2 | Ramp to entrance: The ramp is inaccessible because the top landing has a cross-slope of up to 4.5%, there are handrails on only one side of the ramp, the handrail lacks extensions, and the diameter of the handrail is 2 3/4 inches. | R1 | 36 months |
4.3 | Entrance: The interior vestibule entrance door is inaccessible because it requires 13 pounds of force to open. | D3 | 12 months |
4.4 | Telephones at front entrance: The telephones are inaccessible because they are 55 1/2 inches high to the highest operable part. | TT1 | 24 months |
4.5 | Women’s toilet room with stalls at front entrance: | ||
4.5.a | The toilet room sign is mounted on the door. | TR11 | 12 months |
4.5.b | The entrance door is inaccessible because it requires 12 pounds of force to open. | D3 | 12 months |
4.5.c | Although an audible alarm is provided in this facility, there is no visual alarm appliance in the toilet room. | AL1 | 36 months |
4.5.d | No accessible mirror has been provided. | TR5 | 12 months |
4.5.e | The soap dispenser is inaccessible because it is mounted 56 inches high above the lavatories. | CT3 | 12 months |
4.5.f | The designated accessible stall is incorrectly configured as an ambulatory stall, and there is no standard accessible stall provided. | TR2 | 36 months |
4.6 | Men’s toilet room with stalls at the front entrance: | ||
4.6.a | The toilet room sign is mounted on the door. | TR11 | 12 months |
4.6.b | The entrance door is inaccessible because it requires more than 5 pounds of force to open. | D3 | 12 months |
4.6.c | Although an audible alarm is provided in this facility, there is no visual alarm appliance in the toilet room. | AL1 | 36 months |
4.6.d | No accessible mirror has been provided. | TR5 | 12 months |
4.6.e | The soap dispenser is inaccessible because it is mounted 56 inches high above the lavatories. | CT3 | 12 months |
4.6.f | The designated accessible stall is incorrectly configured as an ambulatory stall, and there is no standard accessible stall provided. | TR2 | 36 months |
4.7 | Drinking fountain at front entrance: The drinking fountain is inaccessible because it has a spout that is 43 inches high. | DF3 | 24 months |
4.8 | First floor visitation area: The door is inaccessible because knob hardware is used. | D2 | 12 months |
4.9 | Staff toilet room by intake area (used by prisoners with disabilities): | ||
4.9.a | The toilet room sign is mounted on the door. | TR11 | 12 months |
4.9.b | Although an audible alarm is provided in this facility, there is no visual alarm appliance in the toilet room. | AL1 | 36 months |
4.9.c | No accessible mirror has been provided. | TR5 | 12 months |
4.9.d | The toilet is inaccessible because the flush control is on the closed side. | TR4 | 24 months |
4.9.e | The toilet is inaccessible because the side grab bar is obstructed by the toilet seat cover dispenser. | TR15 | 12 months |
4.10 | Cells: Accessible housing is not dispersed among the available security levels and housing options within the facility, including isolation cells, etc., and designated accessible cells contain a number of inaccessible features and are not accessible to people with disabilities. | PJ1 | 36 months |
4.11 | M-2 Clinic staff single user toilet room (used by prisoners with disabilities): | ||
4.11.a | The toilet is inaccessible because there are no grab bars provided. | TR18 | 12 months |
4.11.b | No accessible mirror has been provided. | TR5 | 12 months |
4.11.c | The paper towel dispenser is inaccessible because it is mounted with the controls 62 inches high. | CT4 | 12 months |
4.11.d | The toilet is inaccessible because the top of the seat is 14 1/2 inches high. | TR9 | 36 months |
4.11.e | The lavatory is inaccessible because the hot water pipes are not insulated or otherwise configured to protect against contact. | LS2 | 12 months |
4.11.f | The lavatory is inaccessible because it has twist-type hardware. | LS4 | 24 months |
4.12 | Paths of travel: There are several objects located at control stations throughout the facility that protrude into the walkway and are not detectable to blind persons using a cane. | AR7 | 24 months |
4.13 | Gym - metal ramp at doorway: | ||
4.13.a | The door to the gym is inaccessible because there is a slope of 10% within the door’s required maneuvering clearance due to the metal ramp. | D7 | 36 months |
4.13.b | The pull side of the door to the gym, which is accessed through a front approach, is inaccessible because it has less than 18 inches of clear space on the latch side. | D5 | 12 months |
4.13.c | The ramp is inaccessible because it does not have edge protection at the drop off sides. | R3 | 36 months |
5. | Forsyth Pocket Park / Jesse B. Smith Park, 123 E. Forsyth Street | ||
5.1 | Route from street parking: | ||
5.1.a | The curb ramp at the street corner is inaccessible because it has a slope of 10.9% and one flared side has a slope of 16.3%. | AR4 | 36 months |
5.1.b | The route throughout the park is inaccessible because uneven pavers cause changes in level as high as 1 inch. | AR1 | 36 months |
5.2 | Drinking fountain: The drinking fountain is inaccessible because the controls require 10 pounds of force to operate. | DF2 | 24 months |
6. | Florida Theater, 128 E. Forsyth Street | ||
6.1 | Exterior route: The curb ramp at the street corner is inaccessible because it has a slope of 9.7% and one flared side has a slope of 28.6%. | AR4 | 36 months |
6.2 | Main Entrance: | ||
6.2.a | The double doors are inaccessible because each leaf is 28 1/2 inches wide. | D13 | 12 months |
6.2.b | The doors are inaccessible because the thresholds are between 3/4 inch and 1 inch high and are only partially beveled. | D12 | 24 months |
6.3 | Box office: | ||
6.3.a | The box office entry door is inaccessible because there is a slope of 9.6% within the door’s required maneuvering clearance. | D7 | 36 months |
6.3.b | The pull side of the door, which is accessed through a front approach, is inaccessible because it has less than 18 inches of clear space on the latch side. | D5 | 24 months |
6.3.c | The counter is inaccessible because it is 41 inches high. | C1 | 24 months |
6.3.d | The door between the box office and theater is inaccessible because knob hardware is used. | D2 | 12 months |
6.3.e | The door between the box office and theater is inaccessible because the threshold is 3/4 inch high and only partially beveled. | D12 | 24 months |
6.4 | Designated accessible toilet room with stall in lobby: | ||
6.4.a | The door leading to the toilet room and accessible seating is inaccessible because the threshold is 3/4 inch high and only partially beveled. | D12 | 12 months |
6.4.b | The door leading to the toilet room and accessible seating is inaccessible because it has knob hardware. | D2 | 12 months |
6.4.c | The toilet room sign is mounted on the door and has no raised characters. | TR11 | 12 months |
6.4.d | The second door is inaccessible because it requires 10 pounds of force to open and the door must be lifted slightly. | D3 | 12 months |
6.4.e | The ashtray protrudes into the walkway and is not detectable to blind persons using a cane. | AR7 | 24 months |
6.4.f | The stall door is inaccessible because it has an opening width of 30 inches. | D14 | 12 months |
6.4.g | The side grab bar at the toilet is inaccessible because it is mounted with the far end 48 inches from the rear wall. | TR17 | 12 months |
6.5 | Lobby refreshment counter: The counter is inaccessible because it is 41 inches high. | C1 | 24 months |
6.6 | Ramp to accessible theater seating: The ramp is inaccessible because it has a slope of up to 10% near the bottom, there is a handrail on only one side, and the handrail’s ends are not rounded or returned. | R4 | months |
6.7 | Drinking fountain on route to accessible seating: | ||
6.7.a | The drinking fountain is inaccessible because the flow of water is 1 inch high. | DF5 | 12 months |
6.7.b | The wall-mounted drinking fountain is inaccessible because it provides only 24 1/2 inches of clear knee height. | DF4 | 24 months |
6.8 | Theater: | ||
6.8.a | The entry doors are inaccessible because knob hardware is used. | D2 | 12 months |
6.8.b | There is no accessible route directly connecting the wheelchair seating areas and the performing areas. | AA1 | 12 months |
6.8.c | The ramp leading from the street to the stage is inaccessible because it has a slope of 12.3% and it has no handrails. | R4 | 36 months |
6.9 | Orchestra lobby: | ||
6.9.a | The telephones contain no accessible features and are located in booths too small to accommodate a wheelchair. | TT1 | 24 months |
6.9.b | The drinking fountains contain a number of inaccessible elements and are inaccessible to people with disabilities. | DF1 | 24 months |
6.10 | Dressing / green room: The door is inaccessible because it has an opening width of 28 inches. | D14 | 24 months |
6.11 | Single user toilet room near dressing room: | ||
6.11.a | The toilet room sign is mounted on the door and has no raised characters. | TR11 | 12 months |
6.11.b | The lavatory is inaccessible because the hot water pipes are not insulated or otherwise configured to protect against contact. | LS2 | 12 months |
6.11.c | The toilet is inaccessible because there is no side grab bar. | TR16 | 12 months |
6.11.d | The rear grab bar at the designated accessible toilet is inaccessible because it is 18 inches long and it is mounted 32 inches high. | TR14 | 12 months |
7. | Police Memorial Building, 501 E. Bay Street | ||
7.1 | Parking: The parking reserved for persons with disabilities is inaccessible because the designated accessible parking spaces and access aisles have slopes ranging from 3.4% to 6.1%. | P4 | 36 months |
7.2 | Toilet rooms in front lobby: The toilet rooms contain a number of inaccessible elements and are not accessible to people with disabilities. | TR1 | 36 months |
8. | Jacksonville Central Health Plaza, 515 W. 6th Street | ||
8.1 | Parking lot: | ||
8.1.a | The parking lot, with a total of 221 parking spaces, is inaccessible because it has only 6 spaces designated as accessible. This lot requires 2 van accessible spaces and 5 standard accessible spaces. In addition, the designated van-accessible parking space has an access aisle 72 inches wide. | P1 | 36 months |
8.1.b | The curb ramp is inaccessible because it has a slope of 9.6%. | AR1 | 36 months |
8.2 | Route from north parking lot to main entrance: The route is inaccessible because it has a slope of 7.7% with no ramp features. | AR1 | 36 months |
8.3 | South side parking: | ||
8.3.a | The access aisle is inaccessible because is has a slope of 3.2%. | P4 | 36 months |
8.3.b | The curb ramp is inaccessible because it has a slope of 9.9%. | AR4 | 36 months |
8.3.c | The built-up curb ramp impermissibly extends into the required parking space’s access aisle. | AR4 | 36 months |
8.4 | Exterior entrances: The building does not have directional signage posted at inaccessible entrances and does not have the International Symbol of Accessibility posted at accessible entrances. | D10 | 12 months |
8.5 | Birth and Death Certificates, Room 106: The door is inaccessible because it requires 17 pounds of force to open. | D3 | 12 months |
8.6 | Mental Health Services: The door is inaccessible because it requires 14 pounds of force to open. | D3 | 12 months |
8.7 | Drinking fountain by women’s toilet room: | ||
8.7.a | The drinking fountain is inaccessible because the spout is 44 inches high. | DF3 | 24 months |
8.7.b | The drinking fountain is inaccessible because the flow of water is less than 4 inches high. | DF5 | 12 months |
8.7.c | The drinking fountain is inaccessible because the controls require 15 pounds of force to operate. | DF2 | 24 months |
8.7.d | The wall-mounted drinking fountain is inaccessible because it provides insufficient clear knee height. | DF4 | 24 months |
8.8 | Drinking fountain by men’s toilet room: | ||
8.8.a | The drinking fountain is inaccessible because the spout is 44 inches high. | DF3 | 24 months |
8.8.b | The drinking fountain is inaccessible because the flow of water is less than 4 inches high. | DF5 | 12 months |
8.8.c | The drinking fountain is inaccessible because the controls require 12 pounds of force to operate. | DF2 | 24 months |
8.8.d | The wall-mounted drinking fountain is inaccessible because it provides insufficient clear knee height. | DF4 | 24 months |
8.9 | Women’s toilet room on south side: | ||
8.9.a | The toilet room sign is mounted 55 inches high. | TR11 | 12 months |
8.9.b | The door is inaccessible because it requires 15 pounds of force to open. | D3 | 12 months |
8.9.c | The pull side of the door, which is accessed through a front approach, is inaccessible because it has approximately 2 inches of clear space on the latch side. | D5 | 24 months |
8.9.d | Although an audible alarm is provided in this facility, there is no visual alarm appliance in the toilet room. | AL1 | 36 months |
8.9.e | No accessible mirror has been provided. | TR5 | 12 months |
8.9.f | The seat cover dispenser is inaccessible because it is mounted with the controls 61 1/2 inches high. | CT4 | 12 months |
8.9.g | The soap dispenser is inaccessible because it is mounted with the controls 54 inches high above the lavatories. | CT3 | 12 months |
8.9.h | The paper towel dispenser is inaccessible because it is mounted with the controls 61 inches high. | CT4 | 12 months |
8.9.i | The lavatory is inaccessible because it has twist-type hardware. | LS4 | 24 months |
8.9.j | The designated accessible stall is incorrectly configured as an ambulatory stall, and there is no standard accessible stall provided. | TR2 | 36 months |
8.9.k | The paper towel dispenser protrudes into the walkway and is not detectable to blind persons using a cane. | AR7 | 24 months |
8.10 | Men’s toilet room on south side: | ||
8.10.a | The toilet room sign does not have raised characters. | TR11 | 12 months |
8.10.b | The door is inaccessible because it requires 17 pounds of force to open. | D3 | 12 months |
8.10.c | The pull side of the door, which is accessed through a front approach, is inaccessible because it has inadequate clear space on the latch side. | D5 | 24 months |
8.10.d | No accessible mirror has been provided. | TR5 | 12 months |
8.10.e | The soap dispenser is inaccessible because it is mounted with the controls 50 inches high above the lavatories. | CT3 | 12 months |
8.10.f | The paper towel dispenser is inaccessible because it is mounted with the controls 61 inches high. | CT4 | 12 months |
8.10.g | The designated accessible stall is incorrectly configured as an ambulatory stall, and there is no standard accessible stall provided. | TR2 | 36 months |
8.10.h | The paper towel dispenser protrudes into the walkway and is not detectable to blind persons using a cane. | AR7 | 24 months |
8.11 | Smith Auditorium: | ||
8.11.a | The auditorium is inaccessible to people with hearing disabilities because there is no assistive listening system provided. | AA4 | 12 months |
8.11.b | The interior ramp is inaccessible because it has a slope of up to 9.2%. | R4 | 12 months |
8.11.c | The accessible exterior entrance door is kept locked, and persons with disabilities must go to the main entrance to get someone to unlock the door. | D8 | 12 months |
8.11.d | The exterior ramp to the auditorium is inaccessible because it has a slope of up to 10.1%. | R4 | 12 months |
8.11.e | The ramp is inaccessible because no handrails are provided. | R3 | 12 months |
8.12 | Health Center Clinic check-in counter: | ||
8.12.a | The counter is inaccessible because it is 45 1/2 inches high. | C1 | 24 months |
8.12.b | The counter protrudes into the walkway and is not detectable to blind persons using a cane. | AR7 | 24 months |
8.13 | Health Center Clinic examination rooms: The examination tables are inaccessible. | EB1 | 36 months |
8.14 | Single-user toilet room #39 in Women’s Health area: | ||
8.14.a | The toilet is inaccessible because the flush control is on the closed side. | TR4 | 24 months |
8.14.b | The toilet paper dispenser is inaccessible because it is mounted more than 9 inches from the front of the toilet. | TR6 | 12 months |
8.14.c | The toilet is inaccessible because the side grab bar is mounted with the far end 50 inches from the rear wall. | TR17 | 12 months |
8.15 | Single-user toilet room #38 in Women’s Health area: | ||
8.15.a | The toilet paper dispenser is inaccessible because it is mounted more than 9 inches from the front of the toilet. | TR6 | 12 months |
8.15.b | The toilet is inaccessible because the farther end of the side grab bar is mounted 50 inches from the rear wall. | TR17 | 12 months |
8.16 | Men’s toilet room with stalls near Dental Clinic: | ||
8.16.a | The paper towel dispenser protrudes into the walkway and is not detectable to blind persons using a cane. | AR7 | 24 months |
8.16.b | The designated accessible stall is incorrectly configured as an ambulatory stall, and there is no standard accessible stall provided. | TR2 | 36 months |
8.17 | Women’s toilet room near the dental clinic: | ||
8.17.a | The door is inaccessible because it requires 15 pounds of force to open. | D3 | 12 months |
8.17.b | The designated accessible stall is incorrectly configured as an ambulatory stall, and there is no standard accessible stall provided. | TR2 | 12 months |
8.17.c | The paper towel dispenser protrudes into the walkway and is not detectable to blind persons using a cane. | AR7 | 24 months |
8.17.d | The baby changing table is inaccessible because it is mounted with the controls 57 inches high. | CT4 | 12 months |
9. | Office of the Sheriff, Community Corrections Division, 451 Catherine Street | ||
9.1 | Ramp from parking to entrance: The ramp is inaccessible because it has a slope of up to 9.2%, handrails are not provided on both sides of the ramp, and handrail extensions are not provided. | R4 | 36 months |
9.2 | Drinking fountain in front lobby: Although a designated accessible drinking fountain is provided, there is no drinking fountain provided for people who have difficulty bending or stooping. | DF3 | 12 months |
9.3 | Women’s toilet room in front lobby: | ||
9.3.a | The toilet room lacks accessible signage. | TR11 | 12 months |
9.3.b | The door is inaccessible because it requires 10 pounds of force to open. | D3 | 12 months |
9.3.c | The lavatory is inaccessible because the hot water pipes are not insulated or otherwise configured to protect against contact. | LS2 | 12 months |
9.3.d | The lavatory is inaccessible because it has twist-type hardware. | LS4 | 24 months |
9.3.e | The designated accessible stall is incorrectly configured as an ambulatory stall, and there is no standard accessible stall provided. | TR2 | 36 months |
9.4 | Men’s toilet room in front lobby: | ||
9.4.a | The toilet room lacks accessible signage. | TR11 | 12 months |
9.4.b | The lavatory is inaccessible because the hot water pipes are not insulated or otherwise configured to protect against contact. | LS2 | 12 months |
9.4.c | The lavatory is inaccessible because it has twist-type hardware. | LS4 | 24 months |
9.4.d | The urinal is inaccessible because the rim is 19 1/2 inches high. | TR8 | 36 months |
9.4.e | The designated accessible stall is incorrectly configured as an ambulatory stall, and there is no standard accessible stall provided. | TR2 | 36 months |
9.5 | Ramp to CCD - A: The ramp is inaccessible because it has a slope of 29.1%, it lacks edge protection, and the handrails lack extensions and are not continuous on one side. | R4 | 36 months |
9.6 | Entrance to CCD - A (A101): The entrance is inaccessible because it contains an 8 inch high step. | AR1 | 36 months |
9.7 | Entrance to CCD - B: The entrance is inaccessible because it contains a set of steps. | AR1 | 36 months |
9.8 | CCD - A and B Dorms: | ||
9.8.a | There is no accessible housing cell provided. | PJ1 | 24 months |
9.8.b | The toilet rooms contain a number of inaccessible elements and are not accessible to people with disabilities. | TR1 | 36 months |
9.8.c | There are no accessible showers provided. | B2 | 24 months |
9.8.d | There is no accessible drinking fountain provided. | DF1 | 24 months |
10. | Mary Singleton Community Center, 150 E 1st Street | ||
10.1 | Curb ramp at bus drop-off: The curb ramp is inaccessible because it has a slope of 18.9%, and the flared sides have slopes of 26.8% and 30.2%. | AR4 | 36 months |
10.2 | Drinking fountain near auditorium: | ||
10.2.a | The drinking fountain is inaccessible because it has a spout that is 39 inches high. | DF3 | 24 months |
10.2.b | The drinking fountain protrudes into the walkway and is not detectable to blind persons using a cane. | AR7 | 24 months |
10.3 | Women’s toilet room across from the auditorium: | ||
10.3.a | The toilet room sign is mounted on the door. | TR11 | 12 months |
10.3.b | The door is inaccessible because it requires 16 pounds of force to open. | D3 | 12 months |
10.3.c | No accessible mirror has been provided. | TR5 | 12 months |
10.3.d | The lavatory is inaccessible because it has twist-type hardware. | LS4 | 24 months |
10.3.e | There is no accessible toilet stall provided. | TR2 | 36 months |
10.3.f | No accessible coat hook has been provided. | TR3 | 12 months |
10.4 | Men’s toilet room across from auditorium: | ||
10.4.a | The toilet room sign is mounted on the door. | TR11 | 12 months |
10.4.b | The toilet room could not be accessed during the Department’s survey. | TR1 | 36 months |
10.5 | Center front hall: The wooden box attached to a beam protrudes into the walkway and is not detectable to blind persons using a cane. | AR7 | 24 months |
10.6 | Drinking fountain by game room: | ||
10.6.a | The drinking fountain is inaccessible because it has a spout that is 38 1/2 inches high. | DF3 | 24 months |
10.6.b | The drinking fountain protrudes into the walkway and is not detectable to blind persons using a cane. | AR7 | 24 months |
10.7 | Women’s toilet room by TV lounge: | ||
10.7.a | The toilet room sign had fallen down. | TR11, M1 | 12 months |
10.7.b | The door is inaccessible because it requires 15 pounds of force to open. | D3 | 12 months |
10.7.c | The paper towel dispenser protrudes into the walkway and is not detectable to blind persons using a cane. | AR7 | 24 months |
10.7.d | No accessible mirror has been provided. | TR5 | 12 months |
10.7.e | The lavatory is inaccessible because it has twist-type hardware. | LS4 | 24 months |
10.7.f | The designated accessible stall is incorrectly configured as an ambulatory stall, and there is no standard accessible stall provided. | TR2 | 36 months |
10.8 | Men’s toilet room by TV lounge: | ||
10.8.a | The toilet room sign is mounted on the door. | TR11 | 12 months |
10.8.b | The door is inaccessible because it requires 15 pounds of force to open. | D3 | 12 months |
10.8.c | The paper towel dispenser protrudes into the walkway and is not detectable to blind persons using a cane. | AR7 | 24 months |
10.8.d | No accessible mirror has been provided. | TR5 | 12 months |
10.8.e | The lavatory is inaccessible because it has twist-type hardware. | LS4 | 24 months |
10.8.f | The urinal is inaccessible because the rim is 19 inches high. | TR8 | 36 months |
10.8.g | The designated accessible stall is incorrectly configured as an ambulatory stall, and there is no standard accessible stall provided. | TR2 | 36 months |
11. | Hanna Park, 500 Wonderwood Drive | ||
11.1 | Drinking fountain near main entrance parking lot: The fountain is inaccessible because the spout is 37 1/2 inches high, the control requires 8 pounds of force to operate, the unit does not allow a front approach, and there is no access for people who have difficulty bending or stooping. | DF1 | 24 months |
11.2 | Public telephone by main entrance: The route to the public telephone is inaccessible because the grass surface is not firm, stable, or slip-resistant, and there is a 2 to 3 inch high step from the parking lot. | AR1 | 36 months |
11.3 | Main office building: Although a designated accessible drinking fountain is provided, there is no drinking fountain provided for people who have difficulty bending or stooping. | DF3 | 12 months |
11.4 | Women’s single-user toilet room in main office building: | ||
11.4.a | The door is inaccessible because it requires 11 pounds of force to open. | D3 | 12 months |
11.4.b | The door is inaccessible because it is obstructed by the carpet and cannot be opened 90 degrees. | D14 | 12 months |
11.4.c | The lavatory is inaccessible because it has twist-type hardware. | LS4 | 24 months |
11.4.d | The toilet is inaccessible because its centerline is 20 inches from the side wall. | TR7 | 36 months |
11.4.e | The toilet paper dispenser in the designated accessible stall is inaccessible because it is mounted more than 9 inches from the front of the toilet. | TR6 | 12 months |
11.5 | Men’s single-user toilet room in main office building: | ||
11.5.a | The door is inaccessible because it is obstructed by the carpet and cannot be opened 90 degrees. | D14 | 12 months |
11.5.b | The lavatory is inaccessible because it has twist-type hardware. | LS4 | 24 months |
11.5.c | The toilet paper dispenser in the designated accessible stall is inaccessible because it is mounted more than 9 inches from the front of the toilet. | TR6 | 12 months |
11.6 | Ramp from parking lot #11 to beach: The ramp is inaccessible because it does not have a level landing at the bottom of the ramp and the handrails lack extensions. | R5 | 24 months |
11.7 | Ramp from parking lot #8 to beach: The ramp is inaccessible because the handrails are not continuous, and they lack extensions. | R2 | 24 months |
11.8 | Parking lot #8, Shelter #1: The picnic tables are inaccessible because none provide the required knee space. | DW1 | 12 months |
11.9 | Parking lot #8, Shelter #2: | ||
11.9.a | The route to the shelter and to the bleachers is inaccessible because the sand is not firm, stable, and slip-resistant. | AR1 | 36 months |
11.9.b | The picnic tables are inaccessible because none provide the required knee space. | DW1 | 24 months |
11.10 | Parking lot #8, Shelter #3: The picnic tables are inaccessible because none provide the required knee space. | DW1 | 24 months |
11.11 | Parking lot #8 toilet rooms: | ||
11.11.a | The drinking fountain is inaccessible because it has a spout that is 37 1/2 inches high. | DF3 | 24 months |
11.11.b | The toilet room signs are mounted above the doors and have no raised or Braille characters. | TR11 | 12 months |
11.11.c | No accessible mirror has been provided in either toilet room. | TR5 | 12 months |
11.11.d | The air dryers protrude into the walkway and are not detectable to blind persons using a cane. | AR7 | 12 months |
11.11.e | The lavatory in the men’s toilet room is inaccessible because it has twist-type hardware. | LS4 | 24 months |
11.11.f | The urinal in the men’s toilet room is inaccessible because the rim is 20 inches high and the flush control is 54 inches high. | TR8 | 36 months |
11.11.g | The designated accessible stalls are incorrectly configured as ambulatory stalls, and there is no standard accessible stall provided in either room. | TR2 | 36 months |
11.12 | Parking lot #7: The parking lot is inaccessible because one space reserved for persons with disabilities has a slope of 6.1% and the access aisle has a slope of 3.4%. | P4 | 36 months |
11.13 | Parking lot #5: The parking lot is inaccessible because there is no designated accessible parking. | P1 | 36 months |
11.14 | Parking lot #5, Shelters #7, #6, #5: | ||
11.14.a | There is no accessible route to the shelters, or to the volleyball court at Shelter #6, because the grass and sand are not firm, stable, and slip resistant. | AR1 | 36 months |
11.14.b | The picnic tables are inaccessible because none provide the required knee space. | DW1 | 24 months |
11.15 | Hanna Park lake and playground: | ||
11.15.a | The parking lot is inaccessible because there is no designated accessible parking. | P1 | 36 months |
11.15.b | There is no accessible route to the picnic tables or BBQ pit because the grass and sand are not firm, stable, and slip resistant. | AR1 | 36 months |
11.15.c | The picnic tables are inaccessible because none provide the required knee space. | DW1 | 24 months |
11.16 | Water Park: The picnic tables are inaccessible because none provide the required knee space. | DW1 | 24 months |
11.17 | Boat rentals: There is no accessible route to the boat rentals because the grass and sand are not firm, stable, and slip resistant. | AR1 | 36 months |
11.18 | Parking lot #1: | ||
11.18.a | The parking lot, with a total of 117 parking spaces, is inaccessible because it only has 3 spaces designated as accessible. This lot requires 1 van accessible space and 4 standard accessible spaces. | P1 | 36 months |
11.18.b | The parking reserved for persons with disabilities is inaccessible because the signs are mounted too low. | P3 | 12 months |
11.19 | Ramp from parking lot #1 to beach: The ramp is inaccessible because it has a slope of up to 12.9% leading up from the parking lot and a slope of up to 17.3% leading down to the beach, it lacks edge protection, and it does not have compliant handrails. | R1 | 36 months |
11.20 | Parking lot #2: The parking lot, with a total of 76 parking spaces, is inaccessible because it has no spaces designated as accessible. This lot requires 1 van accessible space and 3 standard accessible spaces. | P1 | 36 months |
11.21 | Parking lot #3: The parking lot, with a total of 69 parking spaces, is inaccessible because it only has 1 space designated as accessible. This lot requires 1 van accessible space and 2 standard accessible spaces. | P1 | 36 months |
11.22 | Parking lot #4: The parking lot, with a total of 62 parking spaces, is inaccessible because it only has 2 spaces designated as accessible. This lot requires 1 van accessible space and 2 standard accessible spaces. | P1 | 36 months |
11.23 | Ramp near parking lot #5 to beach: The ramp is inaccessible because it has slopes in excess of 8.33%, it lacks edge protection, and it lacks compliant handrails. | R1 | 36 months |
11.24 | Shelter #4: | ||
11.24.a | There is no accessible route to the shelter because the grass and sand are not firm, stable, and slip resistant. | AR1 | 36 months |
11.24.b | The picnic tables are inaccessible because none provide the required knee space. | DW1 | 24 months |
11.25 | Shelters #12, 13, 14, 35: | ||
11.25.a | There is no accessible route to these shelters because the grass and sand are not firm, stable, and slip resistant. | AR1 | 36 months |
11.25.b | The picnic tables are inaccessible because none provide the required knee space. | DW1 | 24 months |
11.26 | Men’s toilet room with stalls in building #27 near lake: | ||
11.26.a | The toilet room sign is mounted above the door and has no raised or Braille characters. | TR11 | 12 months |
11.26.b | No accessible mirror has been provided. | TR5 | 12 months |
11.26.c | The air dryers protrude into the walkway and are not detectable to blind persons using a cane. | AR7 | 12 months |
11.26.d | The lavatory is inaccessible because the top of the rim or counter is 35 1/2 inches high. | LS3 | 36 months |
11.26.e | The urinal is inaccessible because the rim is 20 inches high and the flush control is 48 inches high. | TR8 | 36 months |
11.26.f | The designated accessible stall is incorrectly configured as an ambulatory stall, and there is no standard accessible stall provided. | TR2 | 36 months |
11.27 | Women’s, Toilet room with stalls in building #27 near lake: | ||
11.27.a | The toilet room sign is mounted above the door and has no raised or Braille characters. | TR11 | 12 months |
11.27.b | No accessible mirror has been provided. | TR5 | 12 months |
11.27.c | The air dryer protrudes into the walkway and is not detectable to blind persons using a cane. | AR7 | 12 months |
11.27.d | The designated accessible stall is incorrectly configured as an ambulatory stall, and there is no standard accessible stall provided. | TR2 | 36 months |
11.28 | Exterior drinking fountain at building #27: | ||
11.28.a | The drinking fountain is inaccessible because it has a spout that is 39 inches high. | DF3 | 24 months |
11.28.b | The drinking fountain is inaccessible because the controls require 12 pounds of force to operate. | DF2 | 24 months |
11.28.c | The drinking fountain is inaccessible because the flow of water is 2 inches high. | DF5 | 12 months |
11.28.d | The drinking fountain protrudes into the walkway and is not detectable to blind persons using a cane. | AR7 | 24 months |
11.28.e | The route to from drinking fountain is inaccessible because it has a cross slope of 4.2%. | AR1 | 36 months |
11.29 | “Mutt Mitt” dispenser at building #27: | ||
11.29.a | The “Mutt Mitt” dispenser protrudes into the walkway and is not detectable to blind persons using a cane. | AR7 | 12 months |
11.29.b | The “Mutt Mitt” dispenser is inaccessible because it is mounted with the controls 64 1/2 inches high. | CT4 | 12 months |
11.30 | Ramp to building #27: The ramp is inaccessible because the handrails are mounted 32 inches above the ramp surface and lack extensions. | R1 | 24 months |
11.31 | Picnic Pavilion #8: | ||
11.31.a | There is no accessible route to the shelter because the grass and sand are not firm, stable, and slip resistant. | AR1 | 36 months |
11.31.b | The picnic tables are inaccessible because none provide the required knee space. | DW1 | 24 months |
11.32 | Dolphin Plaza: | ||
11.32.a | The parking space and access aisle reserved for persons with disabilities are inaccessible because they have slopes of 6.5% and cross slopes between 2.8% and 3.9%. | P4 | 36 months |
11.32.b | The route to the picnic areas is inaccessible because each picnic area has several steps leading to it. | AR1 | 36 months |
11.33 | Dolphin Plaza building #30 women’s toilet room with stalls: | ||
11.33.a | The toilet room sign is mounted above the door and has no raised or Braille characters. | TR11 | 12 months |
11.33.b | No accessible mirror has been provided. | TR5 | 12 months |
11.33.c | The air dryer protrudes into the walkway and is not detectable to blind persons using a cane. | AR7 | 12 months |
11.33.d | The designated accessible stall is incorrectly configured as an ambulatory stall, and there is no standard accessible stall provided. | TR2 | 12 months |
11.34 | Dolphin Plaza building #30 men’s toilet room with stalls: | ||
11.34.a | The toilet room sign is mounted above the doors and has no raised or Braille characters. | TR11 | 12 months |
11.34.b | No accessible mirror has been provided. | TR5 | 12 months |
11.34.c | The air dryer protrudes into the walkway and is not detectable to blind persons using a cane. | AR7 | 12 months |
11.34.d | The urinal is inaccessible because the rim is 25 inches high and the flush control is 51 inches high. | TR8 | 36 months |
11.34.e | The designated accessible stall is incorrectly configured as an ambulatory stall, and there is no standard accessible stall provided. | TR2 | 36 months |
11.35 | Dolphin Plaza building #23 men’s toilet room with stalls: | ||
11.35.a | No accessible mirror has been provided. | TR5 | 12 months |
11.35.b | The toilet room is inaccessible because there is insufficient turning space provided within the room. | TR21 | 12 months |
11.35.c | The air dryer and paper towel dispenser protrude into the walkway and are not detectable to blind persons using a cane. | AR7 | 12 months |
11.35.d | The urinal is inaccessible because the rim is 29 1/2 inches high. | TR8 | 36 months |
11.35.e | The toilet paper dispenser in the designated accessible stall is inaccessible because it is mounted more than 9 inches from the front of the toilet. | TR6 | 12 months |
11.36 | Dolphin Plaza building #23 women’s toilet room with stalls: | ||
11.36.a | The door is inaccessible because it requires 8 pounds of force to open. | D3 | 12 months |
11.36.b | No accessible mirror has been provided. | TR5 | 12 months |
11.36.c | The air dryer and paper towel dispenser protrude into the walkway and are not detectable to blind persons using a cane. | AR7 | 12 months |
11.36.d | The toilet paper dispenser in the designated accessible stall is inaccessible because it is mounted more than 9 inches from the front of the toilet. | TR6 | 12 months |
11.37 | Dolphin Plaza building #23 banquet room: The banquet room is inaccessible because the arched wooden columns provide an overhead hazard that is not detectable to blind persons using a cane. | AR6 | 24 months |
11.38 | Pelican Plaza: | ||
11.38.a | The upper ramp closer to building #29 is inaccessible because it has a slope of up to 21%, it lacks a handrail on one side, it lacks handrail extensions, and the ramp lacks edge protection. | R1 | 36 months |
11.38.b | The ramp between buildings #29 and #31, closer to building #31, is inaccessible because it has a slope of up to 12%, it has no handrails, and there is a two inch depression in the concrete pavement at the top of the ramp. | R4 | 36 months |
11.39 | Pelican Plaza building #29 women’s toilet room with stalls: | ||
11.39.a | The toilet room sign is mounted above the door and has no raised or Braille characters. | TR11 | 12 months |
11.39.b | No accessible mirror has been provided. | TR5 | 12 months |
11.39.c | The air dryer protrudes into the walkway and is not detectable to blind persons using a cane. | AR7 | 12 months |
11.39.d | The designated accessible stall is incorrectly configured as an ambulatory stall, and there is no standard accessible stall provided. | TR2 | 36 months |
11.40 | Pelican Plaza building #29 men’s toilet room with stalls: | ||
11.40.a | The toilet room sign is mounted above the door and has no raised or Braille characters. | TR11 | 12 months |
11.40.b | No accessible mirror has been provided. | TR5 | 12 months |
11.40.c | The air dryer protrudes into the walkway and is not detectable to blind persons using a cane. | AR7 | 12 months |
11.40.d | The urinal is inaccessible because the rim is 25 inches high and the flush control is 51 inches high. | TR8 | 36 months |
11.40.e | The designated accessible stall is incorrectly configured as an ambulatory stall, and there is no standard accessible stall provided. | TR2 | 36 months |
12. | Times Union Center, 300 W. Water Street | ||
12.1 | Main entrance: The door is inaccessible because there is a slope of 5.4% within the door’s required maneuvering clearance. | D7 | 36 months |
12.2 | Drinking Fountains: The drinking fountains throughout the facility protrude into the walkway and are not detectable to blind persons using a cane. | AR7 | 24 months |
12.3 | Ramp to SMG offices: The ramp is inaccessible because the handrails are mounted 33 inches high on one side and 33 1/2 inches high on the other side. | R3 | 24 months |
12.4 | Elevator near main lobby: The elevator is inaccessible because the emergency system requires voice communication to operate. | E7 | 24 months |
12.5 | Women’s single-user toilet room 1245: | ||
12.5.a | The toilet room sign is mounted on the door. | TR11 | 12 months |
12.5.b | The toilet seat cover dispenser is inaccessible because it is mounted 48 inches high behind the toilet. | CT3 | 12 months |
12.5.c | The toilet is inaccessible because the rear grab bar is obstructed by the soap dispenser and the seat cover dispenser. | TR15 | 12 months |
12.5.d | The toilet is inaccessible because the side grab bar is obstructed by the toilet seat cover dispenser. | TR15 | 12 months |
12.5.e | The toilet is inaccessible because the flush control is on the closed side. | TR4 | 24 months |
12.5.f | The feminine products dispenser protrudes into the walkway and is not detectable to blind persons using a cane. | AR7 | 24 months |
12.6 | Men’s single-user toilet room 1248/1250: | ||
12.6.a | The pull side of the exterior door, which is accessed through a front approach, is inaccessible because it has only 5 1/2 inches of clear space on the latch side. | D5 | 24 months |
12.6.b | The entry doors are inaccessible because they require 7 pounds and 11 pounds of force to open. | D3 | 12 months |
12.6.c | The toilet seat cover dispenser is inaccessible because it is mounted 47 inches high behind the toilet. | CT3 | 12 months |
12.6.d | No accessible coat hook has been provided. | TR3 | 12 months |
12.6.e | The toilet is inaccessible because the side grab bar is obstructed by the toilet seat cover dispenser. | TR15 | 12 months |
12.6.f | The toilet is inaccessible because its centerline is 21 inches from the side wall. | TR7 | 36 months |
12.6.g | The toilet is inaccessible because the flush control is on the closed side. | TR4 | 24 months |
12.7 | Telephone 1198: The telephone and shelf protrude into the walkway and are not detectable to blind persons using a cane. | AR7 | 24 months |
12.8 | Women’s single-user toilet room 1215: | ||
12.8.a | The toilet seat cover dispenser is inaccessible because it is mounted 48 inches high behind the toilet. | CT3 | 12 months |
12.8.b | The toilet is inaccessible because the side grab bar is obstructed by the toilet paper dispenser. | TR15 | 12 months |
12.8.c | The toilet is inaccessible because the rear grab bar is obstructed by the toilet seat cover dispenser. | TR15 | 12 months |
12.9 | Women’s toilet room with stalls 1220A: | ||
12.9.a | The designated accessible toilet is inaccessible because the side grab bar is obstructed by the toilet paper dispenser. | TR15 | 12 months |
12.9.b | The designated accessible toilet is inaccessible because the rear grab bar is obstructed by the toilet seat cover dispenser. | TR15 | 12 months |
12.9.c | The ambulatory toilet stall is inaccessible because the door swings inward, and the toilet seat is 16 1/2 inches high. | TR22 | 24 months |
12.10 | Women’s toilet room with stalls 3146: | ||
12.10.a | The designated accessible toilet is inaccessible because the flush control is on the closed side. | TR4 | 24 months |
12.10.b | The designated accessible toilet is inaccessible because the side grab bar is obstructed by the toilet paper dispenser. | TR6 | 12 months |
12.10.c | The designated accessible toilet is inaccessible because the rear grab bar is obstructed by the toilet seat cover dispenser. | TR15 | 12 months |
12.10.d | Although there are 9 toilet stalls, there is no ambulatory stall provided. | TR22 | 24 months |
12.11 | Women’s toilet room with stalls 3150: | ||
12.11.a | The designated accessible toilet is inaccessible because its centerline is 20 inches from the side wall. | TR7 | 24 months |
12.11.b | The designated accessible toilet is inaccessible because the side grab bar is obstructed by the toilet paper dispenser. | TR6 | 12 months |
12.11.c | The designated accessible toilet is inaccessible because the rear grab bar is obstructed by the toilet seat cover dispenser. | TR15 | 12 months |
12.11.d | Although there are 15 toilet stalls, there is no ambulatory stall provided. | TR22 | 24 months |
12.12 | Men’s toilet room with stalls 1180A: | ||
12.12.a | No accessible mirror has been provided. | TR5 | 12 months |
12.12.b | No accessible urinal has been provided. | TR8 | 36 months |
12.12.c | No accessible coat hook has been provided. | TR3 | 12 months |
12.12.d | The designated accessible toilet is inaccessible because the flush control is on the closed side. | TR4 | 24 months |
12.12.e | The side grab bar at the designated accessible toilet is inaccessible because it is obstructed by the toilet paper dispenser. | TR15 | 12 months |
12.12.f | The designated accessible toilet is inaccessible because the side grab bar is obstructed by the toilet paper dispenser | TR6 | 12 months |
12.12.g | Although there are 6 toilet stalls, there is no ambulatory stall provided. | TR22 | 24 months |
12.13 | Austin Lobby (1st floor): The counter is inaccessible because it is 42 1/2 inches high. | C1 | 24 months |
12.14 | Men’s toilet room with stalls 3140: | ||
12.14.a | No accessible mirror has been provided. | TR5 | 12 months |
12.14.b | No accessible urinal has been provided. | TR8 | 36 months |
12.14.c | No accessible coat hook has been provided. | TR3 | 12 months |
12.14.d | The designated accessible toilet is inaccessible because the flush control is on the closed side. | TR4 | 24 months |
12.14.e | The designated accessible toilet is inaccessible because its centerline is 20 1/2 inches from the side wall. | TR7 | 24 months |
12.14.f | The designated accessible toilet is inaccessible because the side grab bar is obstructed by the toilet paper dispenser | TR6 | 12 months |
12.14.g | The designated accessible toilet is inaccessible because the rear grab bar is obstructed by the toilet seat cover dispenser. | TR15 | 12 months |
12.14.h | The toilet seat cover dispenser is inaccessible because it is mounted 50 inches high with only a forward reach provided. | CT4 | 12 months |
12.14.i | The designated accessible toilet stall is inaccessible because its privacy latch is missing while other stalls do have privacy latches. | EB1 | 12 months |
12.14.j | Although there are 7 toilet stalls, there is no ambulatory stall provided. | TR22 | 24 months |
12.15 | Men’s toilet room with stalls 3147: | ||
12.15.a | No accessible urinal has been provided. | TR8 | 36 months |
12.15.b | No accessible coat hook has been provided. | TR3 | 12 months |
12.15.c | The designated accessible toilet is inaccessible because the side grab bar is obstructed by the toilet paper dispenser | TR6 | 12 months |
12.15.d | The designated accessible toilet is inaccessible because the rear grab bar is obstructed by the toilet seat cover dispenser. | TR15 | 12 months |
12.15.e | The toilet seat cover dispenser is inaccessible because it is mounted 50 inches high with only a forward reach provided. | CT4 | 12 months |
13. | Eastside Park / Flossie Brunson Park, 1050 Franklin Street | ||
13.1 | Parking: The parking lot is inaccessible because, although there are 3 designated accessible spaces, there are no access aisles and no vertical signage. | P1 | 36 months |
13.2 | Entrance: The entrance door is inaccessible because knob hardware is used. | D2 | 12 months |
13.3 | Women’s toilet room with stalls: | ||
13.3.a | The toilet room sign is mounted on the door and has no raised or Braille characters. | TR11 | 12 months |
13.3.b | The door is inaccessible because it requires more than 5 pounds of force to open. | D3 | 12 months |
13.3.c | The sanitary napkin and paper towel dispensers protrude into the walkway and are not detectable to blind persons using a cane. | AR7 | 12 months |
13.3.d | The lavatory is inaccessible because the hot water pipes are not insulated or otherwise configured to protect against contact. | LS2 | 12 months |
13.3.e | No accessible coat hook has been provided. | TR3 | 12 months |
13.3.f | The designated accessible stall is inaccessible because it is 40 1/2 inches wide. | TR23 | 12 months |
13.3.g | The rear grab bar at the toilet is inaccessible because it is 30 inches long. | TR13 | 12 months |
13.3.h | The side grab bar at the toilet is inaccessible because it is 36 inches long. | TR16 | 12 months |
13.4 | Men’s toilet room with stalls: | ||
13.4.a | The toilet room sign is mounted on the door and has no raised or Braille characters. | TR11 | 12 months |
13.4.b | The door is inaccessible because it requires more than 5 pounds of force to open. | D3 | 12 months |
13.4.c | No accessible mirror has been provided. | TR5 | 12 months |
13.4.d | The lavatory is inaccessible because the hot water pipes are not insulated or otherwise configured to protect against contact. | LS2 | 12 months |
13.4.e | The urinal is inaccessible because the rim is 24 inches high and the flush control is 49 1/2 inches high. | TR8 | 36 months |
13.4.f | No accessible coat hook has been provided. | TR3 | 12 months |
13.4.g | The designated accessible stall is inaccessible because it is 40 inches wide. | TR23 | 12 months |
13.4.h | The rear grab bar at the toilet is inaccessible because it is 30 inches long. | TR13 | 12 months |
13.4.i | The side grab bar at the toilet is inaccessible because it is 36 inches long. | TR16 | 12 months |
13.5 | Drinking fountain: The floor-mounted drinking fountain is inaccessible because it has a spout that is 43 inches high. | DF3 | 24 months |
13.6 | Ramp to water play area: The ramp is inaccessible because there is no level landing at the top or bottom of the ramp, it has a slope of 10.1%, and the handrails lack extensions. | R4 | 36 months |
13.7 | Playground: There is no accessible route to the play equipment because the wood chips are not firm, stable and slip resistant. | AR1 | 36 months |
13.8 | Tennis courts: The entrance is inaccessible because, where there is a 180̊ turn around an obstruction less than 48 inches deep, the path is less than 42 inches wide. | AR1 | 12 months |
14. | Emmett Reed Center, 1093 West 6th Street | ||
14.1 | Parking lot: The parking lot, with a total of 95 parking spaces, is inaccessible because it has no van accessible parking space. This lot requires 1 van accessible space and 3 standard accessible spaces. | P1 | 36 months |
14.2 | Route from pool to main entrance: The route between the pool and main entrance is inaccessible because there are two significant gaps in the concrete where the surface is not firm, stable, and slip-resistant. | AR1 | 36 months |
14.3 | Ramp by pool: The ramp is inaccessible because it lacks edge protection at the drop off sides. | R3 | 36 months |
14.4 | Ramps to locker rooms: The ramps are inaccessible because they lack handrails. | R3 | 24 months |
14.5 | Drinking fountains: Although designated accessible drinking fountains are provided throughout the facility, there are no drinking fountains provided for people who have difficulty bending or stooping. | DF3 | 12 months |
14.6 | Women’s single user toilet room near main entrance: | ||
14.6.a | The lavatory is inaccessible because the hot water pipes are not insulated or otherwise configured to protect against contact. | LS2 | 12 months |
14.6.b | The toilet is inaccessible because its centerline is 19 1/2 inches from the side wall. | TR7 | 36 months |
14.6.c | The toilet paper dispenser in the designated accessible stall is inaccessible because it is mounted more than 9 inches from the front of the toilet. | TR6 | 12 months |
14.6.d | The toilet is inaccessible because the side grab bar is obstructed by the toilet paper dispenser. | TR15 | 12 months |
14.7 | Men’s single user toilet room near main entrance: | ||
14.7.a | The lavatory is inaccessible because the hot water pipes are not insulated or otherwise configured to protect against contact. | LS2 | 12 months |
14.7.b | The toilet is inaccessible because its centerline is 19 1/2 inches from the side wall. | TR7 | 36 months |
14.7.c | The toilet paper dispenser in the designated accessible stall is inaccessible because it is mounted more than 9 inches from the front of the toilet. | TR6 | 12 months |
14.7.d | The toilet is inaccessible because the side grab bar is obstructed by the toilet paper dispenser. | TR15 | 12 months |
14.8 | Check-in counter outside gym: The counter is inaccessible because it is 41 inches high. | C1 | 24 months |
14.9 | Men’s locker room: | ||
14.9.a | The toilet room sign is mounted on the door and has no raised or Braille characters. | TR11 | 12 months |
14.9.b | The door is inaccessible because it requires 22 pounds of force to open. | D3 | 12 months |
14.9.c | The pull side of the door, which is accessed through a front approach, is inaccessible because it lacks clear floor space on the latch side. | D5 | 24 months |
14.9.d | The lavatory is inaccessible because the bottom of the apron is 26 inches high. | LS3 | 36 months |
14.9.e | The lavatory is inaccessible because it has twist-type hardware. | LS4 | 24 months |
14.9.f | The urinal is inaccessible because the rim is 24 inches high. | TR8 | 36 months |
14.9.g | No accessible shower is provided. | B2 | 24 months |
14.9.h | The bench is inaccessible because it is 12 inches wide and 13 inches high. | LR2 | 24 months |
14.10 | Women’s locker room: | ||
14.10.a | The toilet room sign is mounted on the door and has no raised or Braille characters. | TR11 | 12 months |
14.10.b | The door is inaccessible because it requires 22 pounds of force to open. | D3 | 12 months |
14.10.c | The pull side of the door, which is accessed through a front approach, is inaccessible because it lacks clear floor space on the latch side. | D5 | 12 months |
14.10.d | The lavatory is inaccessible because it has twist-type hardware. | LS4 | 24 months |
14.10.e | No accessible shower is provided. | B2 | 24 months |
14.10.f | The bench is inaccessible because it is 14 inches high, and it is not attached to the wall. | LR2 | 24 months |
14.11 | 1st floor exercise room: The fire extinguisher is a protruding object and is not detectable to blind persons using a cane. | AR7 | 24 months |
14.12 | Women’s rear lobby toilet room with stalls: | ||
14.12.a | The toilet is inaccessible because its centerline is 20 1/2 inches from the side wall. | TR7 | 24 months |
14.12.b | No accessible coat hook has been provided. | TR3 | 12 months |
14.12.c | The designated accessible toilet is inaccessible because the side grab bar is obstructed by the toilet paper dispenser. | TR15 | 12 months |
14.13 | Men’s rear lobby toilet room with stalls: | ||
14.13.a | The urinal is inaccessible because the rim is 24 inches high. | TR8 | 36 months |
14.13.b | The toilet is inaccessible because the flush control is on the closed side. | TR4 | 24 months |
14.13.c | No accessible coat hook has been provided. | TR3 | 12 months |
14.13.d | The designated accessible toilet is inaccessible because the side grab bar is obstructed by the toilet paper dispenser. | TR15 | 12 months |
14.14 | Elevator, rear lobby: | ||
14.14.a | The elevator is inaccessible because, after reopening due to an obstruction, the doors stay open less than 20 seconds. | E6 | 24 months |
14.14.b | The elevator is inaccessible because the emergency controls are not grouped together at the bottom of the panel. | E8 | 24 months |
14.14.c | The elevator is inaccessible because the car position indicators do not ring or illuminate as the car passes or stops on floors. | E5 | 24 months |
14.14.d | The elevator is inaccessible because the emergency system requires voice communication to operate. | E7 | 24 months |
14.15 | 2nd floor offices: | ||
14.15.a | The doors are inaccessible because knob hardware is used. | D2 | 12 months |
14.15.b | The signage provided is inaccessible because it is mounted above the doors and does not have raised and Braille characters. | D15 | 12 months |
14.16 | Men’s 2nd floor toilet room with stalls: | ||
14.16.a | The lavatory is inaccessible because it has twist-type hardware. | LS4 | 24 months |
14.16.b | The urinal is inaccessible because the rim is more than 17 inches high. | TR8 | 36 months |
14.16.c | No accessible coat hook has been provided. | TR3 | 12 months |
14.16.d | The toilet is inaccessible because the flush control is on the closed side. | TR4 | 24 months |
14.16.e | The designated accessible toilet is inaccessible because the side grab bar is obstructed by the toilet paper dispenser. | TR15 | 12 months |
14.17 | Women’s 2nd floor toilet room with stalls: The toilet room contains a number of inaccessible elements and is not accessible to people with disabilities. | TR1 | 24 months |
14.18 | Telephone: The telephone protrudes into the walkway and is not detectable to blind persons using a cane. | AR7 | 24 months |
15. | Head Start, 515 Victoria Street | ||
15.1 | Entrances: The building does not have directional signage posted at inaccessible entrances and does not have the International Symbol of Accessibility posted at accessible entrances. | D10 | 12 months |
15.2 | Parking: The parking lot, with a total of 18 parking spaces, is inaccessible because there are no accessible parking spaces. This lot requires 1 van accessible space. | P1 | 36 months |
15.3 | Rear entrance: | ||
15.3.a | The entrance ramp is inaccessible because it has a slope of up to 13.4% and it has no compliant handrails. | R4 | 36 months |
15.3.b | The door is inaccessible because there is a 1 1/2 inch high threshold. | D12 | 24 months |
15.4 | Fire extinguishers: The fire extinguishers by the door and the drinking fountain protrude into the walkway and are not detectable to blind persons using a cane. | AR7 | 24 months |
15.5 | Interior doors: The doors throughout the facility are inaccessible because knob hardware is used. | D2 | 12 months |
15.6 | Intake room: | ||
15.6.a | There is no accessible route to the room because furniture narrows the path of travel to less than 32 inches wide. | AR1 | 12 months |
15.6.b | The door is inaccessible because it has an opening width of 30 inches. | D14 | 24 months |
15.7 | Single user unisex toilet room: | ||
15.7.a | The toilet room sign is mounted on the door and has no raised or Braille characters. | TR11 | 12 months |
15.7.b | Although an audible alarm is provided in this facility, there is no visual alarm appliance in the toilet room. | AL1 | 36 months |
15.7.c | The toilet is inaccessible because its centerline is 25 inches from the side wall. | TR7 | 36 months |
15.7.d | The toilet is inaccessible because the flush control is on the closed side. | TR4 | 24 months |
15.7.e | The side grab bar at the toilet is inaccessible because it is 30 inches long. | TR16 | 12 months |
15.7.f | The toilet is inaccessible because no rear grab bar is provided. | TR13 | 12 months |
15.8 | Exterior playground: There is no accessible route to the play area because the grass is not firm, stable, and slip resistant. | AR1 | 36 months |
16. | Julius Guinyard Park (Jefferson Street Park), 1358 N Jefferson Street | ||
16.1 | Playground: There is no accessible route to the playground because the grass is not firm, stable, and slip resistant. | AR1 | 36 months |
16.2 | Picnic area: The route to the picnic area is inaccessible because the grass is not firm, stable, and slip resistant. | AR1 | 36 months |
16.3 | Baseball field: The route to the baseball field picnic area is inaccessible because the grass is not firm, stable, and slip resistant. | AR1 | 36 months |
17. | Durkee Field - James Small Stadium, 1701 Myrtle Avenue North / 1200 West 8th Street | ||
17.1 | Seating area: | ||
17.1.a | The ramp to the seating area is inaccessible because there is no handrail on one side at the bottom of the ramp, and the ramp has a slope of up to 9.5%. | R2 | 36 months |
17.1.b | The stadium is inaccessible because no wheelchair seating areas are provided. | AA6 | 36 months |
17.2 | Unisex single user toilet rooms near ticket counter and museum: Although an audible alarm is provided in this facility, there are no visual alarm appliances in these toilet rooms. | AL1 | 36 months |
17.3 | Men’s and women’s toilet rooms with stalls near ticket counter: There is no signage directing people with disabilities to the accessible toilet rooms, and the inaccessible toilet rooms have signage indicating that they are accessible. | TR16 | 12 months |
17.4 | Concession Counters: | ||
17.4.a | The counters are all inaccessible because they are between 40 inches and 43 inches high. | C1 | 12 months |
17.4.b | The counters protrude into the walkway and are not detectable to blind persons using a cane. | AR7 | 12 months |
17.5 | Dugouts: There is no accessible route to the dugouts because the dirt is not firm, stable, and slip resistant. | AR1 | 36 months |
17.6 | Picnic tables: The picnic areas are inaccessible because none of the picnic tables provide accessible knee space. | DW1 | 24 months |
17.7 | Playground: There playground is inaccessible because there is a step to get onto the playground surface and the sand surface is not firm, stable, and slip resistant. | AR1 | 36 months |
18. | Clanzel T. Brown Community Center, 4575 Moncrief Road | ||
18.1 | Parking: | ||
18.1.a | The parking lot, with a total of 163 parking spaces, is inaccessible because there are only 5 accessible spaces provided and none are designated van-accessible. This lot requires 1 van accessible space and 5 standard accessible spaces. | P1 | 36 months |
18.1.b | The designated accessible parking spaces by the tennis couts are inaccessible because the access aisle is only 34 inches wide. | P2 | 36 months |
18.2 | Interior signage: The signage provided throughout the facility is inaccessible because it does not have raised and Braille characters. | D15 | 12 months |
18.3 | Sign-in counter: The counter is inaccessible because it is 41 1/2 inches high. | C1 | 24 months |
18.4 | Drinking fountain near toilet rooms: The drinking fountain is inaccessible because it has a spout that is 39 inches high. | DF3 | 24 months |
18.5 | Men’s toilet room with stalls: | ||
18.5.a | The toilet room sign is mounted on the door and has no raised or Braille characters. | TR11 | 12 months |
18.5.b | The door is inaccessible because it requires 20 pounds of force to open. | D3 | 12 months |
18.5.c | The entrance is inaccessible because the vestibule is 41 1/2 inches deep from the end of the open door. | D4 | 12 months |
18.5.d | No accessible mirror has been provided. | TR5 | 12 months |
18.5.e | The paper towel dispenser by the inaccessible lavatory protrudes into the walkway and is not detectable to blind persons using a cane. | AR7 | 12 months |
18.5.f | The urinal is inaccessible because the rim is 25 inches high and the flush control is 51 1/2 inches high. | TR8 | 36 months |
18.5.g | The designated accessible toilet is inaccessible because the flush control is on the closed side. | TR4 | 24 months |
18.5.h | No accessible coat hook has been provided. | TR3 | 12 months |
18.5.i | The side grab bar at the toilet is inaccessible because it is 36 inches long. | TR13 | 12 months |
18.5.j | The rear grab bar at the toilet is inaccessible because it is 18 inches long and it is mounted 7 1/2 inches from the side wall. | TR16 | 12 months |
18.6 | Women’s toilet room with stalls: | ||
18.6.a | The toilet room sign is mounted on the door and has no raised or Braille characters. | TR11 | 12 months |
18.6.b | The entrance is inaccessible because the vestibule is 42 1/2 inches deep from the end of the open door. | D4 | 12 months |
18.6.c | No accessible mirror has been provided. | TR5 | 12 months |
18.6.d | The soap dispenser is inaccessible because it is mounted with the controls 50 1/2 inches high between the lavatories. | CT3 | 12 months |
18.6.e | The lavatory is inaccessible because the top of the rim or counter is 35 inches high. | LS3 | 36 months |
18.6.f | The lavatory is inaccessible because it has twist-type hardware. | LS4 | 12 months |
18.6.g | No accessible coat hook has been provided. | TR3 | 12 months |
18.6.h | The designated accessible toilet is inaccessible because the side grab bar is obstructed by the toilet paper dispenser. | TR15 | 12 months |
18.6.i | The side grab bar at the toilet is inaccessible because it is 36 inches long. | TR13 | 12 months |
18.6.j | The rear grab bar at the toilet is inaccessible because it is 18 inches long and it is mounted 8 1/2 inches from the side wall. | TR16 | 12 months |
18.7 | Patio: The picnic tables are inaccessible because none provide the required knee space. | DW1 | 24 months |
19. | Clanzel T. Brown Pool, 4515 Moncrief Road | ||
19.1 | Route from parking lot to pool: The route is inaccessible because adequate passing space is not provided along its length, the pavement is cracked and has gaps of greater than 1/2 inch, and it has slopes and cross slopes of up to 12.4%. | AR1 | 36 months |
19.2 | Drinking fountain: The floor-mounted drinking fountain is inaccessible because its spout is 38 inches high, and there is no knee space provided. | DF1 | 24 months |
19.3 | Women’s locker room: | ||
19.3.a | The locker room sign is high on the wall and has no raised or Braille characters. | TR11 | 12 months |
19.3.b | The lavatory is inaccessible because it has twist-type hardware. | LS4 | 12 months |
19.3.c | The designated accessible stall is incorrectly configured as an ambulatory stall, and there is no standard accessible stall provided. | TR2 | 36 months |
19.3.d | There is no accessible shower provided. | B2 | 24 months |
19.3.e | There is no bench provided. | LR2 | 24 months |
19.4 | Men’s locker room: | ||
19.4.a | The locker room sign is too high on the wall and has no raised or Braille characters. | TR11 | 12 months |
19.4.b | The lavatory is inaccessible because it has twist-type hardware. | LS4 | 12 months |
19.4.c | The urinal is inaccessible because the rim is 21 1/2 inches high and the flush control is 49 inches high. | TR8 | 36 months |
19.4.d | The designated accessible stall is incorrectly configured as an ambulatory stall, and there is no standard accessible stall provided. | TR2 | 36 months |
19.4.e | There is no accessible shower provided. | B2 | 24 months |
19.4.f | There is no bench provided. | LR2 | 24 months |
20. | Clanzel T. Brown Sports Complex, 4575 Moncrief Road | ||
20.1 | Routes: The routes to the basketball court, baseball fields, picnic areas, and benches are inaccessible because the grass is not firm, stable, and slip resistant. | AR1 | 36 months |
20.2 | Picnic tables: The picnic tables are inaccessible because none provide the required knee space. | DW1 | 24 months |
20.3 | Women’s locker room at tennis pavilion: | ||
20.3.a | The toilet room sign is mounted on the door and has no raised or Braille characters. | TR11 | 12 months |
20.3.b | Although an audible alarm is provided in this facility, there is no visual alarm appliance in the toilet room. | AL1 | 36 months |
20.3.c | The lavatory is inaccessible because the hot water pipes are not insulated or otherwise configured to protect against contact. | LS2 | 12 months |
20.3.d | The designated accessible stall is incorrectly configured as an ambulatory stall, and there is no standard accessible stall provided. | TR2 | 36 months |
20.3.e | No accessible shower is provided. | B2 | 12 months |
20.3.f | The bench is inaccessible because it is 13 1/4 inches wide and 19 1/2 inches high. | LR2 | 12 months |
20.3.g | There is no accessible locker provided. | LR3 | 24 months |
20.4 | Men’s locker room at tennis pavilion: | ||
20.4.a | The toilet room sign is mounted on the door and has no raised or Braille characters. | TR11 | 12 months |
20.4.b | Although an audible alarm is provided in this facility, there is no visual alarm appliance in the toilet room. | AL1 | 36 months |
20.4.c | No accessible mirror has been provided. | TR5 | 12 months |
20.4.d | The urinal is inaccessible because the rim is 19 1/2 inches high. | TR8 | 36 months |
20.4.e | The designated accessible stall is incorrectly configured as an ambulatory stall, and there is no standard accessible stall provided. | TR2 | 36 months |
20.4.f | No accessible shower is provided. | B2 | 12 months |
20.4.g | The bench is inaccessible because it is 13 1/4 inches wide and 19 1/2 inches high. | LR2 | 24 months |
20.4.h | There is no accessible locker provided. | LR3 | 12 months |
20.5 | Drinking fountain at tennis pavilion: | ||
20.5.a | The drinking fountain is inaccessible because it has a spout that is 41 1/2 inches high. | DF3 | 24 months |
20.5.b | The drinking fountain is inaccessible because the controls require 8 pounds of force to operate. | DF2 | 24 months |
21. | Supervisor of Elections, 231 East Forsyth Street | ||
21.1 | Curb ramp: The curb ramp is inaccessible because it has a slope of 13.5%. | AR4 | 36 months |
21.2 | Route to entrance: The route from the parking area to the entrance is inaccessible because it has a cross slope of 3.8% in at least one location. | AR1 | 36 months |
22. | Claude Yates City Hall Annex, 231 East Forsyth Street | ||
22.1 | Entrances: The building does not have the International Symbol of Accessibility posted at accessible entrances. | D10 | 12 months |
22.2 | Interior room signage: The room signage throughout the facility is inaccessible because it is not mounted 48-60 inches high and it lacks raised and Braille characters. | D15 | 12 months |
22.3 | Counters throughout facility, including rooms 230, 260, 270, 330, 350, 360, and 470: The counters protrude into the walkway and are not detectable to blind persons using a cane. | AR7 | 24 months |
22.4 | Drinking fountains: Although designated accessible drinking fountains are provided, there is no drinking fountain provided in the facility for people who have difficulty bending or stooping. | DF3 | 12 months |
22.5 | Elevators 1 & 2: The elevators are inaccessible because the emergency communications require tight grasping and pinching to access. | E7 | 24 months |
22.6 | Drinking fountain near room 163: The drinking fountain protrudes into the walkway and is not detectable to blind persons using a cane. | AR7 | 24 months |
22.7 | Men’s toilet room with stalls near room 163: | ||
22.7.a | The toilet room sign is mounted on the door and has no raised or Braille characters. | TR11 | 12 months |
22.7.b | The door is inaccessible because it requires 11 pounds of force to open. | D3 | 12 months |
22.7.c | The air dryer protrudes into the walkway and is not detectable to blind persons using a cane. | AR7 | 12 months |
22.7.d | The toilet seat cover dispenser is inaccessible because it is mounted 64 inches high. | CT4 | 12 months |
22.7.e | The lavatory is inaccessible because the hot water pipes are not insulated or otherwise configured to protect against contact. | LS2 | 12 months |
22.7.f | The designated accessible stall is incorrectly configured as an ambulatory stall, and there is no standard accessible stall provided. | TR2 | 36 months |
22.8 | Women’s toilet room with stalls near room 165: | ||
22.8.a | The toilet room sign is mounted on the door and has no raised or Braille characters. | TR11 | 12 months |
22.8.b | The door is inaccessible because it requires 11 pounds of force to open. | D3 | 12 months |
22.8.c | The toilet seat cover dispenser is inaccessible because it is mounted 58 inches high. | CT3 | 12 months |
22.8.d | The air dryer protrudes into the walkway and is not detectable to blind persons using a cane. | AR7 | 12 months |
22.8.e | The lavatory is inaccessible because the hot water pipes are not insulated or otherwise configured to protect against contact. | LS2 | 12 months |
22.8.f | The designated accessible stall is incorrectly configured as an ambulatory stall, and there is no standard accessible stall provided. | TR2 | 36 months |
22.9 | Drinking fountain near room 109: The drinking fountain protrudes into the walkway and is not detectable to blind persons using a cane. | AR7 | 12 months |
22.10 | Men’s toilet room with stalls near room 263: | ||
22.10.a | The toilet room sign is mounted on the door and has no raised or Braille characters. | TR11 | 12 months |
22.10.b | The door is inaccessible because it requires 9 pounds of force to open. | D3 | 12 months |
22.10.c | The toilet seat cover dispenser is inaccessible because it is mounted 61 inches high. | CT3 | 12 months |
22.10.d | The air dryer protrudes into the walkway and is not detectable to blind persons using a cane. | AR7 | 12 months |
22.10.e | The lavatory is inaccessible because the hot water pipes are not insulated or otherwise configured to protect against contact. | LS2 | 12 months |
22.10.f | The designated accessible stall is incorrectly configured as an ambulatory stall, and there is no standard accessible stall provided. | TR2 | 36 months |
22.11 | Women’s toilet room with stalls near room 263: | ||
22.11.a | The toilet room sign is mounted on the door and has no raised or Braille characters. | TR11 | 12 months |
22.11.b | The door is inaccessible because it requires 11 pounds of force to open. | D3 | 12 months |
22.11.c | The toilet seat cover dispenser is inaccessible because it is mounted 60 inches high. | CT3 | 12 months |
22.11.d | The air dryer protrudes into the walkway and is not detectable to blind persons using a cane. | AR7 | 12 months |
22.11.e | The lavatory is inaccessible because the hot water pipes are not insulated or otherwise configured to protect against contact. | LS2 | 12 months |
22.11.f | The designated accessible stall is incorrectly configured as an ambulatory stall, and there is no standard accessible stall provided. | TR2 | 12 months |
22.12 | Men’s toilet room with stalls 3rd floor: | ||
22.12.a | The toilet room sign is mounted on the door and has no raised or Braille characters. | TR11 | 12 months |
22.12.b | The door is inaccessible because it requires 10 pounds of force to open. | D3 | 12 months |
22.12.c | The toilet seat cover dispenser is inaccessible because it is mounted 61 inches high. | CT3 | 12 months |
22.12.d | The air dryer protrudes into the walkway and is not detectable to blind persons using a cane. | AR7 | 12 months |
22.12.e | The lavatory is inaccessible because the hot water pipes are not insulated or otherwise configured to protect against contact. | LS2 | 12 months |
22.12.f | The designated accessible stall is incorrectly configured as an ambulatory stall, and there is no standard accessible stall provided. | TR2 | 36 months |
22.13 | Women’s toilet room with stalls 3rd floor: | ||
22.13.a | The toilet room sign is mounted on the door and has no raised or Braille characters. | TR11 | 12 months |
22.13.b | The door is inaccessible because it requires 10 pounds of force to open. | D3 | 12 months |
22.13.c | The air dryer and paper towel dispenser protrude into the walkway and are not detectable to blind persons using a cane. | AR7 | 12 months |
22.13.d | The lavatory is inaccessible because the hot water pipes are not insulated or otherwise configured to protect against contact. | LS2 | 12 months |
22.13.e | The designated accessible stall is incorrectly configured as an ambulatory stall, and there is no standard accessible stall provided. | TR2 | 36 months |
22.14 | Room 450: The door is inaccessible because it requires 15 pounds of force to open. | D3 | 12 months |
22.15 | Room 470: The door is inaccessible because it requires 16 pounds of force to open. | D3 | 12 months |
22.16 | Drinking fountain near room 463: The drinking fountain is inaccessible because the water flow is 3 inches high. | DF5 | 12 months |
23. | Bethesda Park, 10790 Key Haven Boulevard | ||
23.1 | Community room: | ||
23.1.a | The office counter protrudes into the walkway and is not detectable to blind persons using a cane. | AR7 | 24 months |
23.1.b | The community room is inaccessible because no assistive listening system is provided. | AA4 | 36 months |
23.2 | Kitchen: The paper towel dispenser is inaccessible because it is mounted 53 inches high over the sink. | CT3 | 12 months |
23.3 | Men’s toilet room with stalls near main entrance: | ||
23.3.a | The toilet room sign is mounted on the door and has no raised or Braille characters. | TR11 | 12 months |
23.3.b | No accessible coat hook has been provided. | TR3 | 12 months |
23.4 | Women’s toilet room with stalls near main entrance: The toilet room sign is mounted on the door and has no raised or Braille characters. | TR11 | 12 months |
23.5 | Route to Cabins 3 & 4: The route is inaccessible because there is a 1 1/2 inch high change in level on the sidewalk. | AR1 | 36 months |
23.6 | Cabin 3 single user toilet room: | ||
23.6.a | The toilet is inaccessible because the flush control is on the closed side. | TR4 | 24 months |
23.6.b | The toilet paper dispenser in the designated accessible stall is inaccessible because it is mounted more than 9 inches from the front of the toilet. | TR6 | 12 months |
23.6.c | The toilet is inaccessible because the side grab bar is 36 inches long. | TR17 | 12 months |
23.6.d | The toilet is inaccessible because there is no rear grab bar provided. | TR13 | 12 months |
23.6.e | The roll-in shower is inaccessible because there are insufficient grab bars provided. | B2 | 12 months |
23.7 | Cabin 4 single user toilet room: | ||
23.7.a | The toilet is inaccessible because its centerline is 15 1/2 inches from the side wall. | TR7 | 36 months |
23.7.b | The toilet is inaccessible because the side grab bar is 36 inches long. | TR17 | 12 months |
23.7.c | The toilet is inaccessible because there is no rear grab bar provided. | TR13 | 12 months |
23.7.d | The roll-in shower is inaccessible because there are insufficient grab bars provided. | B2 | 12 months |
24. | Yates Parking Garage, 200 East Adams Street | ||
24.1 | Parking: The garage, with a total of 660 parking spaces, is inaccessible because it only has 1 space designated as van-accessible, one of the Ground level designated accessible spaces and access aisles has a slope of 7.9% and the other is not on the shortest accessible route to an accessible entrance, and many of the other designated accessible spaces have access aisles 47 inches wide and/or obstructed by columns, and the signage on the 6th floor is mounted too low. This lot requires 3 van accessible spaces and 11 standard accessible spaces. | P1 | 36 months |
24.2 | Elevators: | ||
24.2.a | The elevators are inaccessible because hall lanterns are only provided on the first floor. | E10 | 24 months |
24.2.b | The elevators are inaccessible because the emergency communications require tight grasping or pinching to access. | E7 | 24 months |
25. | Wallace Small Senior Center 1083 Line St. | ||
25.1 | Parking: The designated accessible parking space is inaccessible because it has no access aisle and there is no van accessible space provided. | P1 | 36 months |
25.2 | Entrance ramp: The ramp is inaccessible because it has a slope of up to 10.3% and it has a handrail on only one side. | R4 | 36 months |
25.3 | Drinking fountain near sign in counter: | ||
25.3.a | The drinking fountain is inaccessible because the controls require 10 pounds of force to operate. | DF2 | 24 months |
25.3.b | The wall-mounted drinking fountain is inaccessible because it provides only 22 1/2 inches of knee space. | DF4 | 24 months |
25.3.c | Although a designated accessible drinking fountain is provided, there is no drinking fountain provided for people who have difficulty bending or stooping. | DF3 | 24 months |
25.4 | Kitchen: | ||
25.4.a | The door is inaccessible because knob hardware is used. | D2 | 12 months |
25.4.b | The sink is inaccessible because there is no knee space provided. | LS3 | 12 months |
25.5 | Women’s single user toilet room: | ||
25.5.a | The toilet room sign is mounted on the door and has no raised or Braille characters. | TR11 | 12 months |
25.5.b | Although an audible alarm is provided in this facility, there is no visual alarm appliance in the toilet room. | AL1 | 36 months |
25.5.c | The toilet is inaccessible because its centerline is 16 inches from the side wall. | TR7 | 12 months |
25.5.d | The toilet is inaccessible because the flush control is on the closed side. | TR4 | 24 months |
25.5.e | The rear grab bar at the toilet is inaccessible because it is 24 inches long. | TR13 | 12 months |
25.6 | Men’s single user toilet room: | ||
25.6.a | The toilet room sign is mounted on the door and has no raised or Braille characters. | TR11 | 12 months |
25.6.b | Although an audible alarm is provided in this facility, there is no visual alarm appliance in the toilet room. | AL1 | 36 months |
25.6.c | The urinal is inaccessible because the rim is 20 inches high. | TR8 | 36 months |
25.6.d | The toilet is inaccessible because its centerline is 16 inches from the side wall. | TR7 | 12 months |
25.6.e | The rear grab bar at the toilet is inaccessible because it is 24 inches long. | TR13 | 12 months |
25.7 | Picnic shelter: The picnic tables are inaccessible because none provide the required knee space. | DW1 | 24 months |
26. | Fire Station #1, 611 North Liberty Street | ||
26.1 | Men’s toilet room: | ||
26.1.a | The toilet room sign is mounted on the door. | TR11 | 12 months |
26.1.b | Although an audible alarm is provided in this facility, there is no visual alarm appliance in the toilet room. | AL1 | 36 months |
26.1.c | No accessible mirror has been provided. | TR5 | 12 months |
26.1.d | The paper towel dispenser is inaccessible because it is mounted 51 inches high over the lavatories. | CT3 | 12 months |
26.1.e | The lavatory is inaccessible because the hot water pipes are not insulated or otherwise configured to protect against contact. | LS2 | 12 months |
26.1.f | The designated accessible stall is incorrectly configured as an ambulatory stall, and there is no standard accessible stall provided. | TR2 | 36 months |
26.1.g | No accessible shower is provided. | B2 | 12 months |
27. | Park Admin Offices, 851 North Market Street | ||
27.1 | Parking: The designated accessible parking space is inaccessible because it has a slope of 5.9% and the access aisle has a slope of 6.5%. | P4 | 36 months |
27.2 | Designated accessible entrance: | ||
27.2.a | The route to the entrance is inaccessible because there is a slope of 10.4% leading to the door. | AR1 | 36 months |
27.2.b | The door is inaccessible because there is a slope of 11.4% within the door’s required maneuvering clearance. | D7 | 36 months |
27.2.c | The door is inaccessible because there is a 1 inch high threshold. | D12 | 12 months |
27.3 | Interior doors: Many of the doors throughout the facility are inaccessible because knob hardware is used. | D2 | 12 months |
27.4 | Visitor’s office: The counter protrudes into the walkway and is not detectable to blind persons using a cane. | AR7 | 12 months |
27.5 | Elevator: The elevator is inaccessible because the emergency system requires voice communication to operate. | E7 | 24 months |
27.6 | Men’s toilet room with stalls in basement: | ||
27.6.a | The door is inaccessible because it requires 7 pounds of force to open. | D3 | 12 months |
27.6.b | The soap dispenser is inaccessible because it is mounted with the controls 56 inches high. | CT4 | 12 months |
27.6.c | The urinal is inaccessible because the rim is 24 inches high. | TR8 | 12 months |
27.6.d | No accessible coat hook has been provided. | TR3 | 12 months |
27.7 | Women’s toilet room with stalls in basement: | ||
27.7.a | The door is inaccessible because it requires 7 pounds of force to open. | D3 | 12 months |
27.7.b | No accessible coat hook has been provided. | TR3 | 12 months |
27.8 | 2nd Floor drinking fountain: Although a designated accessible drinking fountain is provided, there is no drinking fountain provided for people who have difficulty bending or stooping. | DF3 | 12 months |
27.9 | Single user toilet rooms on 1st and 2nd floor: These toilet rooms are inaccessible and there is no signage directing people with disabilities to the designated accessible basement toilet rooms. | TR16 | 12 months |
28. | Adams Street Parking Garage, 231 East Adams Street | ||
28.1 | Parking: | ||
28.1.a | The designated accessible spaces and access aisles on level 2 are inaccessible because they have slopes between 3.9% and 5.8%. | P4 | 36 months |
28.1.b | There are no accessible van parking spaces because the garage has a vertical clearance of 88 inches. | P8 | 36 months |
28.1.c | One of the designated accessible parking spaces on level 3 is inaccessible because it does not have vertical signage. | P3 | 12 months |
28.2 | Route to elevator on level 2: The route from the parking area to the elevator is inaccessible because it has a slope of up to 7.2%. | AR1 | 36 months |
28.3 | Elevator: | ||
28.3.a | The elevator is inaccessible because there is no hoistway signage provided. | E12 | 24 months |
28.3.b | The elevator is inaccessible because there are no hall lantern signals. | E10 | 24 months |
28.3.c | The elevator is inaccessible because the time from notification that a car is answering a call until the doors of that car start to close is 4 seconds. | E6 | 24 months |
28.3.d | The elevator is inaccessible because the emergency system requires voice communication to operate. | E7 | 24 months |
29. | J.S. Johnson Community Center, 1112 Jackson Street | ||
29.1 | Exterior route: The route is inaccessible because there are changes in level 1 inch high at the end of the parking access aisle and at the entrance to the tennis court. | AR1 | 36 months |
29.2 | Interior doors: The doors throughout the facility are inaccessible because knob hardware is used. | D2 | 12 months |
29.3 | Kitchen: | ||
29.3.a | The sink is inaccessible because it has twist type knobs and does not provide knee space. | LS1 | 12 months |
29.3.b | The paper towel dispenser is inaccessible because it is mounted 67 inches high. | CT3 | 12 months |
29.4 | Social room: The computer table is inaccessible because it is 26 1/4 inches high to the bottom edge. | T1 | 24 months |
29.5 | Drinking fountain in main hallway: | ||
29.5.a | The drinking fountain is inaccessible because it has a spout that is 42 inches high. | DF3 | 12 months |
29.5.b | The drinking fountain protrudes into the walkway and is not detectable to blind persons using a cane. | AR7 | 12 months |
29.6 | Ceramic room: The sink is inaccessible because it has twist type knobs. | LS4 | 24 months |
29.7 | Inaccessible toilet rooms: There is no signage directing people with disabilities to the accessible toilet rooms. | TR16 | 12 months |
29.8 | Men’s single user toilet room in pool room: | ||
29.8.a | The toilet room sign does not have the International Symbol of Accessibility. | TR11 | 12 months |
29.8.b | No accessible mirror has been provided. | TR5 | 12 months |
29.8.c | The toilet is inaccessible because the seat is 15 3/4 inches high. | SU14 | 36 months |
29.8.d | The side grab bar at the toilet is inaccessible because it is mounted with the far end 47 inches from the rear wall. | TR16 | 12 months |
29.8.e | The rear grab bar at the toilet is inaccessible because it is 30 inches long and it is mounted 7 inches from the side wall. | TR13 | 12 months |
29.9 | Women’s single user toilet room in pool room: | ||
29.9.a | The toilet room sign does not have the International Symbol of Accessibility. | TR11 | 12 months |
29.9.b | No accessible mirror has been provided. | TR5 | 12 months |
29.9.c | The toilet is inaccessible because the flush control is on the closed side. | TR4 | 12 months |
29.9.d | The side grab bar at the toilet is inaccessible because it is mounted with the far end 47 inches from the rear wall. | TR16 | 12 months |
29.9.e | The rear grab bar at the toilet is inaccessible because it is 30 inches long and it is mounted 7 inches from the side wall. | TR13 | 12 months |
29.9.f | The rear grab bar at the toilet is inaccessible because it is obstructed by the toilet tank. | TR15 | 12 months |
29.9.g | The toilet room door swings into the required clear floor space at the lavatory. | TR6 | 12 months |
29.10 | Drinking fountain in pool room: | ||
29.10.a | The drinking fountain is inaccessible because the flow of water is less than 4 inches high. | DF5 | 12 months |
29.10.b | The drinking fountain is inaccessible because the controls require 7 pounds of force to operate. | DF2 | 12 months |
29.10.c | The drinking fountain protrudes into the walkway and is not detectable to blind persons using a cane. | AR7 | 12 months |
29.10.d | Although a designated accessible drinking fountain is provided, there is no drinking fountain provided for people who have difficulty bending or stooping. | DF3 | 12 months |
30. | Beaches Senior Center, 281 19th Avenue South | ||
30.1 | Front entrance: | ||
30.1.a | The front entrance is inaccessible because there is a slope of 9% near the door. | AR1 | 36 months |
30.1.b | There is no accessible route to the picnic tables in front of the facility because there is a step up onto the curb. | AR1 | 36 months |
30.2 | Interior doors: The doors throughout the facility are inaccessible because knob hardware is used. | D2 | 12 months |
30.3 | Classroom: The defibrillator protrudes into the walkway and is not detectable to blind persons using a cane. | AR7 | 24 months |
30.4 | Drinking fountain by toilet rooms: Although a designated accessible drinking fountain is provided, there is no drinking fountain provided for people who have difficulty bending or stooping. | DF3 | 12 months |
30.5 | Women’s toilet room: | ||
30.5.a | The toilet room sign is mounted on the door and has no raised or Braille characters. | TR11 | 12 months |
30.5.b | Although an audible alarm is provided in this facility, there is no visual alarm appliance in the toilet room. | AL1 | 36 months |
30.5.c | The lavatory is inaccessible because the top of the rim or counter is 36 inches high. | LS3 | 36 months |
30.5.d | The designated accessible stall is incorrectly configured as an ambulatory stall, and there is no standard accessible stall provided. | TR2 | 36 months |
30.6 | Men’s toilet room: | ||
30.6.a | The toilet room sign is mounted on the door and has no raised or Braille characters. | TR11 | 12 months |
30.6.b | The door is inaccessible because it requires 9 pounds of force to open. | D3 | 12 months |
30.6.c | Although an audible alarm is provided in this facility, there is no visual alarm appliance in the toilet room. | AL1 | 36 months |
30.6.d | The lavatory is inaccessible because the top of the rim or counter is 35 3/4 inches high. | LS3 | 36 months |
30.6.e | The urinal is inaccessible because the rim is 23 1/2 inches high and the flush control is 50 inches high. | TR8 | 36 months |
30.6.f | The designated accessible stall is incorrectly configured as an ambulatory stall, and there is no standard accessible stall provided. | TR2 | 36 months |
31. | Baldwin Fire Station #46, 610 Oliver Street (exterior only) | ||
31.1 | Parking: There is no designated accessible parking provided. | P1 | 36 months |
31.2 | Entrances: | ||
31.2.a | The doors are inaccessible because there are thresholds more than 3/4 inches high. | D12 | 24 months |
31.2.b | The doors are inaccessible because knob hardware is used. | D2 | 12 months |
31.2.c | The mailbox next to one entrance protrudes into the walkway and is not detectable to blind persons using a cane. | AR7 | 24 months |
32. | Mandarin Senior Center, 3848 Hartley Road | ||
32.1 | Curb ramp: The curb ramp leading to the entrance ramp is inaccessible because the side flares have slopes of 25.1% and 17.9%. | AR4 | 36 months |
32.2 | Entrance ramp: The ramp is inaccessible because it has a slope of up to 10.2%. | R4 | 36 months |
32.3 | Interior doors: The doors throughout the facility are inaccessible because knob hardware is used. | D2 | 12 months |
32.4 | Computer room: The pull side of the door, which is accessed through a front approach, is inaccessible because it has only 15 inches of clear space on the latch side. | D5 | 24 months |
32.5 | Drinking fountain by toilet rooms: | ||
32.5.a | The drinking fountain is inaccessible because the controls require 10 pounds of force to operate. | DF2 | 24 months |
32.5.b | Although a designated accessible drinking fountain is provided, there is no drinking fountain provided for people who have difficulty bending or stooping. | DF3 | 12 months |
32.6 | Women’s toilet room with stalls: | ||
32.6.a | The toilet room sign is mounted on the door and has no raised or Braille characters. | TR11 | 12 months |
32.6.b | The door is inaccessible because it requires 11 pounds of force to open. | D3 | 12 months |
32.6.c | The paper towel dispenser is inaccessible because it is mounted with the controls 55 inches high. | CT4 | 12 months |
32.6.d | The lavatory is inaccessible because the hot water pipes are not insulated or otherwise configured to protect against contact. | LS2 | 12 months |
32.6.e | The designated accessible stall is incorrectly configured as an ambulatory stall, and there is no standard accessible stall provided. | TR2 | 36 months |
32.7 | Men’s toilet room with stalls: | ||
32.7.a | The toilet room sign is mounted on the door and has no raised or Braille characters. | TR11 | 12 months |
32.7.b | The door is inaccessible because it requires 13 pounds of force to open. | D3 | 12 months |
32.7.c | The lavatory is inaccessible because the hot water pipes are not insulated or otherwise configured to protect against contact. | LS2 | 12 months |
32.7.d | The urinal is inaccessible because the rim is 24 1/2 inches high and the flush control is 51 1/2 inches high. | TR8 | 36 months |
32.7.e | The designated accessible stall is incorrectly configured as an ambulatory stall, and there is no standard accessible stall provided. | TR2 | 36 months |
32.8 | Rear door: The door is inaccessible because there is a slope of 9.7% within the door’s required maneuvering clearance. | D7 | 36 months |
32.9 | Entrance to billiard building: The door is inaccessible because there is a slope of 6.9% within the door’s required maneuvering clearance. | D7 | 36 months |
32.10 | Card / game building: | ||
32.10.a | The entrance door is inaccessible because knob hardware is used. | D2 | 12 months |
32.10.b | The route through the building is inaccessible because the halls are only 34 1/2 inches wide. | AR2 | 12 months |
32.10.c | The drinking fountain is inaccessible because the controls require 7 pounds of force to operate. | DF2 | 24 months |
32.10.d | Although a designated accessible drinking fountain is provided, there is no drinking fountain provided for people who have difficulty bending or stooping. | DF3 | 12 months |
32.11 | Card / game building single-user toilet room: | ||
32.11.a | The lavatory is inaccessible because the hot water pipes are not insulated or otherwise configured to protect against contact. | LS2 | 12 months |
32.11.b | The toilet paper dispenser in the designated accessible stall is inaccessible because it is mounted more than 9 inches from the front of the toilet. | TR6 | 12 months |
32.11.c | The side grab bar at the toilet is inaccessible because it is mounted 37 inches high with the closer end 12 1/2 inches from the rear wall, and the space between the grab bar and the wall is 2¼ inches. | TR16 | 12 months |
32.11.d | The rear grab bar at the toilet is inaccessible because it is mounted 36 3/4 inches high and the space between rear grab bar and wall is 2 1/4 inches. | TR13 | 12 months |
33. | Mandarin Library, 3330 Kori Street | ||
33.1 | Parking: | ||
33.1.a | The built-up curb ramps impermissibly extend into the required parking spaces. | AR4 | 36 months |
33.1.b | The parking lot, with a total of 77 parking spaces, is inaccessible because there are only 2 designated accessible spaces, and one of the signs is mounted too low. This lot requires 1 van accessible space and 3 standard accessible spaces. | P1 | 36 months |
33.2 | Library: | ||
33.2.a | The book depository is inaccessible because it is 55 inches high. | CT4 | 12 months |
33.2.b | The magazine displays are inaccessible because the maximum reach ranges are 55 3/4 inches high. | CT4 | 12 months |
33.3 | Drinking fountain by community room: | ||
33.3.a | The drinking fountain is inaccessible because the controls require 7 pounds of force to operate. | DF2 | 24 months |
33.3.b | Although a designated accessible drinking fountain is provided, there is no drinking fountain provided for people who have difficulty bending or stooping. | DF3 | 12 months |
33.4 | Large community room: | ||
33.4.a | The door is inaccessible because it requires 12 pounds of force to open. | D3 | 12 months |
33.4.b | The stage is inaccessible because there is a step to access it. | AR2 | 24 months |
33.4.c | The room is inaccessible to people with hearing disabilities because there is no assistive listening system provided. This room requires 7 receivers. | AA4 | 36 months |
33.5 | Small office: The door is inaccessible because knob hardware is used. | D2 | 12 months |
33.6 | Women’s toilet room with stalls: | ||
33.6.a | The toilet room sign is mounted on the door and has no raised or Braille characters. | TR11 | 12 months |
33.6.b | The door is inaccessible because it requires 15 pounds of force to open. | D3 | 12 months |
33.6.c | No accessible mirror has been provided. | TR5 | 12 months |
33.6.d | The lavatory is inaccessible because it has twist-type hardware. | LS4 | 12 months |
33.6.e | The designated accessible stall is incorrectly configured as an ambulatory stall, and there is no standard accessible stall provided. | TR2 | 24 months |
33.7 | Men’s toilet room with stalls: | ||
33.7.a | The toilet room sign is mounted on the door and has no raised or Braille characters. | TR11 | 12 months |
33.7.b | The door is inaccessible because it requires 17 pounds of force to open. | D3 | 12 months |
33.7.c | The urinal is inaccessible because the rim is 23 inches high. | TR8 | 36 months |
33.7.d | The designated accessible stall is incorrectly configured as an ambulatory stall, and there is no standard accessible stall provided. | TR2 | 24 months |
34. | Maxville Community Center, 18065 Pennsylvania Avenue | ||
34.1 | Entrance ramp: The ramp is inaccessible because it lacks handrails. | R3 | 24 months |
34.2 | Interior doors: The doors throughout the facility are inaccessible because knob hardware is used. | D2 | 12 months |
34.3 | Women’s toilet room with stalls: | ||
34.3.a | The toilet room sign is mounted on the door and has no raised or Braille characters. | TR11 | 12 months |
34.3.b | The toilet room entrance doors are inaccessible because they require 7 and 9 pounds of force to open. | D3 | 12 months |
34.3.c | The pull side of the interior door, which is accessed through a front approach, is inaccessible because it lacks adequate maneuvering clearance. | D5 | 12 months |
34.3.d | The door is inaccessible because the vestibule is not sufficiently deep. | D4 | 12 months |
34.3.e | No accessible mirror has been provided. | TR5 | 12 months |
34.3.f | The toilet is inaccessible because the seat is 20 inches high. | TR9 | 24 months |
34.3.g | The side grab bar at the designated accessible toilet is inaccessible because it is 36 inches long. | TR16 | 12 months |
34.3.h | The designated accessible toilet is inaccessible because the side grab bar is mounted 32 inches high. | ST12 | 12 months |
34.3.i | The rear grab bar at the toilet is inaccessible because it is 18 inches long and it is mounted 10 inches from the side wall. | TR13 | 12 months |
34.4 | Men’s toilet room with stalls: | ||
34.4.a | The toilet room sign is mounted on the door and has no raised or Braille characters. | TR11 | 12 months |
34.4.b | The toilet room entrance doors are inaccessible because they each require 7 pounds of force to open. | D3 | 12 months |
34.4.c | The pull side of the exterior door, which is accessed through a front approach, is inaccessible because it lacks adequate maneuvering clearance. | D5 | 12 months |
34.4.d | The door is inaccessible because the vestibule is not sufficiently deep. | D4 | 12 months |
34.4.e | No accessible mirror has been provided. | TR5 | 12 months |
34.4.f | The urinal is inaccessible because the rim is 25 inches high. | TR8 | 36 months |
34.4.g | The designated accessible stall is inaccessible because the flush control is on the closed side. | TR4 | 24 months |
34.4.h | The side grab bar at the toilet is inaccessible because it is 36 inches long. | TR13 | 12 months |
34.4.i | The rear grab bar at the toilet is inaccessible because it is 18 inches long and it is mounted 9 inches from the side wall. | TR13 | 12 months |
34.5 | Drinking fountain outside kitchen: | ||
34.5.a | The wall-mounted drinking fountain is inaccessible because it provides only 23 inches of clear knee height. | DF4 | 24 months |
34.5.b | Although a designated accessible drinking fountain is provided, there is no drinking fountain provided for people who have difficulty bending or stooping. | DF3 | 12 months |
34.6 | Picnic Shelters: | ||
34.6.a | There is no accessible route to the grills because the grass is not firm, stable, and slip resistant. | AR1 | 36 months |
34.6.b | The picnic tables are inaccessible because none provide the required knee space. | DW1 | 24 months |
35. | Burnett Park, 3740 Burnett Park Road | ||
35.1 | Drinking fountain near concession stand: The drinking fountain is inaccessible because the spout is 41 inches high, and the controls require 10 pounds of force to operate. | DF1 | 24 months |
35.2 | Concession stand: | ||
35.2.a | The concession stand counter is inaccessible because it is 41 inches high. | C1 | 24 months |
35.2.b | The counter protrudes into the walkway and is not detectable to blind persons using a cane. | AR7 | 24 months |
35.2.c | The picnic table is inaccessible because it does not provide the required knee space. | DW1 | 24 months |
35.3 | Ballfield by concession stand: | ||
35.3.a | The door to the home team dugout is inaccessible because the opening is only 28 inches wide. | D14 | 24 months |
35.3.b | The pull side of the door to the batting cages, which is accessed through a front approach, is inaccessible because it has only no clear space on the latch side. | D5 | 24 months |
35.4 | Drinking fountain by toilet rooms: | ||
35.4.a | The drinking fountain is inaccessible because the water flow is less than 4 inches high. | DF5 | 12 months |
35.4.b | The drinking fountain is inaccessible because the controls require 8 pounds of force to operate. | DF2 | 24 months |
35.4.c | Although a designated accessible drinking fountain is provided, there is no drinking fountain provided for people who have difficulty bending or stooping. | DF3 | 12 months |
35.5 | Women’s toilet room with stalls by ballfields | ||
35.5.a | The toilet room sign is mounted on the door and has no raised or Braille characters. | TR11 | 12 months |
35.5.b | The door is inaccessible because it requires 10 pounds of force to open. | D3 | 12 months |
35.5.c | Although an audible alarm is provided in this facility, there is no visual alarm appliance in the toilet room. | AL1 | 36 months |
35.5.d | The lavatory is inaccessible because it has twist-type hardware. | LS4 | 24 months |
35.5.e | No accessible coat hook has been provided. | TR3 | 12 months |
35.5.f | The side grab bar at the toilet is inaccessible because it is mounted 17 inches from the rear wall. | TR16 | 12 months |
35.6 | Men’s toilet room by ballfields: | ||
35.6.a | The toilet room sign is mounted on the door and has no raised or Braille characters. | TR11 | 12 months |
35.6.b | The toilet room was locked and could not be surveyed. | TR1 | 36 months |
35.7 | Picnic pavilion: | ||
35.7.a | The routes to the grills are inaccessible because the grass is not firm, stable, and slip resistant. | AR1 | 36 months |
35.7.b | The picnic tables are inaccessible because none provide the required knee space. | DW1 | 24 months |
35.8 | Drinking fountain by picnic area: | ||
35.8.a | The drinking fountain is inaccessible because the controls require 13 pounds of force to operate. | DF2 | 24 months |
35.8.b | The drinking fountains protrude into the walkway and are not detectable to blind persons using a cane. | AR7 | 24 months |
36. | Burnett Park Community Center, 3740 Burnett Park Road | ||
36.1 | Interior doors: The doors throughout the facility are inaccessible because knob hardware is used. | D2 | 12 months |
36.2 | Drinking fountain by toilet room: | ||
36.2.a | The drinking fountain is inaccessible because the controls require 16 pounds of force to operate. | DF2 | 24 months |
36.2.b | Although a designated accessible drinking fountain is provided, there is no drinking fountain provided for people who have difficulty bending or stooping. | DF3 | 12 months |
36.2.c | The drinking fountain unit protrudes into the walkway and is not detectable to blind persons using a cane. | AR7 | 24 months |
36.3 | Men’s toilet room with stalls: | ||
36.3.a | The door is inaccessible because it requires 15 pounds of force to open. | D3 | 12 months |
36.3.b | No accessible mirror has been provided. | TR5 | 12 months |
36.3.c | The lavatory is inaccessible because the hot water pipes are not insulated or otherwise configured to protect against contact. | LS2 | 12 months |
36.3.d | The toilet room door swings into the required clear floor space at the lavatory. | TR6 | 24 months |
36.3.e | The route to the urinal is inaccessible because it is only 29 inches wide. | AR3 | 12 months |
36.3.f | The designated accessible toilet stall is inaccessible because it is 53 inches long and 53 inches wide. | TR23 | 12 months |
36.3.g | The toilet paper dispenser in the designated accessible stall is inaccessible because it is mounted more than 9 inches from the front of the toilet, and is on the wall opposite the side grab bar. | TR6 | 12 months |
36.3.h | The side grab bar at the toilet is inaccessible because it is mounted 32 3/4 inches high with its far end 49 1/2 inches from the rear wall, and the space between the grab bar and the wall is 2 1/2 inches. | TR16 | 12 months |
36.4 | Women’s toilet room with stalls: | ||
36.4.a | The toilet room sign is mounted on the hinge side of the door. | TR11 | 12 months |
36.4.b | The door is inaccessible because it requires 14 pounds of force to open. | D3 | 12 months |
36.4.c | No accessible mirror has been provided. | TR5 | 12 months |
36.4.d | The lavatory is inaccessible because the hot water pipes are not insulated or otherwise configured to protect against contact. | LS2 | 12 months |
36.4.e | The lavatory is inaccessible because it has insufficient clear floor space. | LS5 | 36 months |
36.4.f | The route to the lavatory is inaccessible because it is only 29 inches wide. | AR3 | 12 months |
36.4.g | The designated accessible stall is incorrectly configured as an ambulatory stall, and there is no standard accessible stall provided. | TR2 | 12 months |
37. | Westbrook Library, 2809 Commonwealth Avenue. (Also used for polling) | ||
37.1 | Parking: | ||
37.1.a | The parking lot is inaccessible because there are no access aisles. | P2 | 36 months |
37.1.b | The parking signage is inaccessible because it is obstructed by trees. | M1 | 12 months |
37.1.c | The designated accessible parking is inaccessible because it lacks van accessible signage. | P3 | 12 months |
37.2 | Route from the parking lot to the main entrance: The route is inaccessible because it is not firm, stable or slip resistant and has not been maintained. | AR1, M1 | 36 months |
37.3 | Exterior exit door: | ||
37.3.a | The door is inaccessible because there is a .75 inch high threshold that is not beveled. | D12 | 24 months |
37.3.b | The door is inaccessible because knob hardware is used. | D2 | 12 months |
37.4 | Computer stations tables: The computer and card catalog are inaccessible because the bottom edge of their table is 25 inches high. | C1 | 12 months |
37.5 | Route from the main library area to the toilet rooms: The route is inaccessible because it is obstructed by a book cart and the path is 27 inches wide. | AR1 | 12 months |
37.6 | Men’s single user toilet room: | ||
37.6.a | The door is inaccessible because it requires 11 pounds of force to open. | D3 | 12 months |
37.6.b | The pull side of the door, which is accessed from the latch side of the door, is inaccessible because it is obstructed by a book cart and the path is 27 inches wide. | D5 | 12 months |
37.6.c | The toilet room is inaccessible because the clear floor space is obstructed by a trash can. | SU16 | 12 months |
37.6.d | The toilet is inaccessible because the rear grab bar is obstructed by the soap dispenser. | TR15 | 12 months |
37.6.e | The toilet is inaccessible because the rear grab bar is 31 inches long. | TR14 | 12 months |
37.6.f | The toilet is inaccessible because the flush control is on the closed side. | TR4 | 24 months |
37.6.g | The toilet paper dispenser in the designated accessible stall is inaccessible because it is mounted more than 9 inches from the front of the toilet. | TR6 | 12 months |
37.7 | Women’s single user toilet room: | ||
37.7.a | The door is inaccessible because it requires 11 pounds of force to open. | D3 | 12 months |
37.7.b | The pull side of the door, which is accessed from the latch side of the door, is inaccessible because it is obstructed by a book cart and the path is 27 inches wide | D5 | 12 months |
37.7.c | The toilet is inaccessible because the rear grab bar is obstructed by the soap dispenser. | TR15 | 12 months |
37.8 | Computer and conference room: | ||
37.8.a | The door is inaccessible because the pull side is obstructed by a book truck. | D18 | 12 months |
37.8.b | The door is inaccessible because it requires 12 pounds of force to open. | D3 | 12 months |
37.8.c | The door is inaccessible because knob hardware is used. | D2 | 12 months |