ATTACHMENT I: Modifications to Newly Constructed Facilities

Please Note: Paragraph 54 of the Settlement Agreement requires that within nine months of the effective date of this Agreement, the City of Jacksonville provide signage as necessary to comply with 28 C.F.R. § 35.163(b), after having surveyed all facilities that are the subject of this Agreement for the purpose of identifying those that have multiple entrances not all of which are accessible.

The chart below lists the facilities surveyed by the Department, the access issues identified during the survey, and the actions required to correct the access issues. Required actions are listed using an alphanumeric code. The key to the alphanumeric codes is provided in Attachment M to this Agreement.

In order to ensure that the following spaces and elements in City of Jacksonville facilities for which construction was commenced after January 26, 1992, are readily accessible to and usable by persons with disabilities, the City of Jacksonville will take the actions referenced by the alphanumeric code and described in detail in Attachment M to this Settlement Agreement within the time periods specified below, which time periods will begin to run on the effective date of this Agreement.

Item # Access Issue Required Action Completion Date
1. Baseball Grounds of Jacksonville, 301 A. Philip Randolph Boulevard    
1.1. Parking lot P:    
1.1.a. The parking reserved for persons with disabilities is inaccessible because it lacks appropriate vertical signage. P3 12 months
1.1.b. The parking lot is inaccessible because there are no access aisles. P2 36 months
1.2. Route from home plate gate to elevator located behind the stairs: The route around the stairs to the right is inaccessible because it has a slope of 6.6% with no ramp features. AR1 36 months
1.3. Toilet rooms: The metal shelves mounted in the toilet rooms throughout the facility protrude into the walkway and are not detectable to blind persons using a cane. AR7 24 months
1.4. Men’s toilet room with stalls - lower concourse, 3rd base side:    
1.4.a. The toilet room sign is mounted on the door. TR11 12 months
1.4.b. The toilet seat cover dispenser is inaccessible because it is mounted too high behind the toilet. CT3 12 months
1.4.c. The paper towel dispenser in the toilet stall protrudes 9 1/2 inches into the walkway and is not detectable to blind persons using a cane. AR7 12 months
1.4.d. The baby changing station is inaccessible because the surface, when open, is 43 inches high. DW1 12 months
1.4.e. No accessible coat hook has been provided. TR3 12 months
1.4.f. The side grab bar at the designated accessible toilet is inaccessible because it is obstructed by the toilet paper dispenser. TR6 12 months
1.4.g. The designated accessible toilet is inaccessible because the rear grab bar is obstructed by the toilet seat cover dispenser. TR15 12 months
1.4.h. The urinal is inaccessible because the flush control is mounted 45 inches high. TR8 36 months
1.5. Women’s toilet room with stalls - lower concourse, 3rd base side:    
1.5.a. The toilet room sign is mounted on the door. TR11 12 months
1.5.b. The baby changing station is inaccessible because the surface, when open, is 43 inches high. DW1 12 months
1.5.c. No accessible coat hook has been provided. TR3 12 months
1.5.d. The side grab bar at the designated accessible toilet is inaccessible because it is obstructed by the toilet paper dispenser. TR6 12 months
1.5.e. The designated accessible toilet is inaccessible because the rear grab bar is obstructed by the toilet seat cover dispenser and the paper towel dispenser. TR15 12 months
1.5.f. Ambulatory stall:    
1.5.f(1) The toilet seat cover dispenser is inaccessible because it is mounted too high behind the toilet. CT3 12 months
1.5.f(2) The designated ambulatory stall is inaccessible because it is 38 inches wide, one side grab bar is obstructed by the toilet paper dispenser, and the door is not self-closing. TR22,TR6 24 months
1.5.f(3) No accessible coat hook has been provided. TR3 12 months
1.6. Single user toilet room - lower concourse, 3rd base side:    
1.6.a. The baby changing station is inaccessible because the surface, when open, is 44 inches high and, when closed, the controls are 55 inches high. DW1,CT3 12 months
1.6.b. The toilet is inaccessible because its centerline is 18 1/2 inches from the side wall. TR7 36 months
1.6.c. The toilet seat cover dispenser is inaccessible because it is mounted too high behind the toilet. CT3 12 months
1.6.d. The toilet is inaccessible because the rear grab bar is obstructed by the toilet seat cover dispenser. TR15 12 months
1.6.e. The side grab bar at the toilet is inaccessible because it is obstructed by the toilet paper dispenser. TR6 12 months
1.7. Picnic tables - lower concourse: The picnic tables are inaccessible because none provide the required knee space. DW1 24 months
1.8. Palm tree pavilion - 3rd base gate near ramp A: The picnic tables are inaccessible because none provide the required knee space. DW1 24 months
1.9. Women’s toilet room with stalls - near playground in centerfield:    
1.9.a. The baby changing station is inaccessible because, when closed, the handle is 55 inches high, and, when open, the surface is 44 inches high. DW1,CT3 12 months
1.9.b. No accessible coat hook has been provided. TR3 12 months
1.9.c. The designated accessible toilet is inaccessible because the rear grab bar is obstructed by the paper towel dispenser and the seat cover dispenser. TR15 12 months
1.9.d. The toilet seat cover dispenser is inaccessible because it is mounted too high behind the toilet. CT3 12 months
1.9.e. Ambulatory stall: The ambulatory stall is inaccessible because the stall door is not self closing and the side grab bar is obstructed by the toilet paper dispenser. TR22,TR6 12 months
1.10. Men’s toilet room with stalls - near playground in centerfield:    
1.10.a. The baby changing station is inaccessible because, when closed, the handle is 55 inches high, and, when open, the surface is 44 inches high. DW1,CT3 12 months
1.10.b. No accessible coat hook has been provided. TR3 12 months
1.10.c. The toilet seat cover dispenser is inaccessible because it is mounted too high behind the toilet. CT3 12 months
1.10.d. The designated accessible toilet is inaccessible because the rear grab bar is obstructed by the toilet seat cover dispenser and the paper towel dispenser. TR15 12 months
1.10.e. Ambulatory stall: The ambulatory stall is inaccessible because the stall door is not self closing and the side grab bar is obstructed by the toilet paper dispenser. TR22,TR6 12 months
1.11. Single user toilet room - near playground in centerfield:    
1.11.a. The paper towel dispenser protrudes into the walkway and is not detectable to blind persons using a cane. AR7 24 months
1.11.b. The baby changing station is inaccessible because, when closed, the handle is 56 inches high, and, when open, the surface is 43 inches high. DW1,CT3 12 months
1.11.c. The side grab bar at the toilet is inaccessible because it is obstructed by the toilet paper dispenser. TR6 12 months
1.11.d. The rear grab bar at the toilet is inaccessible because it is obstructed by the seat cover dispenser. TR15 12 months
1.11.e. The toilet seat cover dispenser is inaccessible because it is mounted too high behind the toilet. CT3 12 months
1.11.f. The designated accessible toilet is inaccessible because the rear grab bar is obstructed by the seat cover dispenser. TR15 12 months
1.12. Drinking fountain - playground in centerfield:    
1.12.a. The drinking fountain is inaccessible because it provides only 26 inches of clear knee height. DF4 24 months
1.12.b. The higher drinking fountain protrudes into the walkway and is not detectable to blind persons using a cane. AR7 24 months
1.13. Men’s toilet room with stalls - main concourse, 1st base side near sections 117/116:    
1.13.a. The paper towel dispenser protrudes into the walkway and is not detectable to blind persons using a cane. AR7 24 months
1.13.b. The baby changing station is inaccessible because, when closed, the handle is 55 inches high, and, when open, the surface is 43 inches high. DW1,CT3 12 months
1.13.c. No accessible coat hook has been provided. TR3 12 months
1.13.d. The side grab bar at the designated accessible toilet is inaccessible because it is obstructed by the toilet paper dispenser. TR6 12 months
1.13.e. The toilet seat cover dispenser is inaccessible because it is mounted too high behind the toilet. CT3 12 months
1.13.f. The designated accessible toilet is inaccessible because the rear grab bar is obstructed by the toilet seat cover dispenser. TR15 12 months
1.14. Women’s toilet room with stalls - main concourse, 1st base side near sections 117/116:    
1.14.a. The paper towel dispenser protrudes into the walkway and is not detectable to blind persons using a cane. AR7 24 months
1.14.b. The baby changing station is inaccessible because, when closed, the handle is 55 inches high, and, when open, the surface is 43 inches high. DW1,CT3 12 months
1.14.c. The toilet is inaccessible because its centerline is 19 inches from the side wall. TR7 24 months
1.14.d. No accessible coat hook has been provided. TR3 12 months
1.14.e. The side grab bar at the designated accessible toilet is inaccessible because it is obstructed by the toilet paper dispenser. TR6 12 months
1.14.f. The toilet seat cover dispenser is inaccessible because it is mounted too high behind the toilet. CT3 12 months
1.14.g. Ambulatory stall:    
1.14.g(1) The toilet seat cover dispenser is inaccessible because it is mounted behind the toilet. CT3 12 months
1.14.g(2) The ambulatory stall is inaccessible because one side grab bar is obstructed by the toilet paper dispenser. TR6 12 months
1.14.g(3) No accessible coat hook has been provided. TR3 12 months
1.15. Men’s toilet room with stalls - main concourse, 1st base side near sections 113/112/111:    
1.15.a. The baby changing station is inaccessible because, when closed, the handle is 55 inches high, and, when open, the surface is 43 inches high. DW1,CT3 12 months
1.15.b. The paper towel dispenser protrudes into the walkway and is not detectable to blind persons using a cane. AR7 24 months
1.15.c. No accessible coat hook has been provided. TR3 12 months
1.15.d. The side grab bar at the designated accessible toilet is inaccessible because it is obstructed by the toilet paper dispenser. TR15 12 months
1.15.e. The toilet seat cover dispenser is inaccessible because it is mounted too high behind the toilet. CT3 12 months
1.15.f. The designated accessible toilet is inaccessible because the rear grab bar is obstructed by the toilet seat cover dispenser and the paper towel dispenser. TR15 12 months
1.16. Women’s toilet room with stalls - main concourse, 1st base side, near sections 113/112/111:    
1.16.a. The baby changing station is inaccessible because, when closed, the handle is 55 inches high, and, when open, the surface is 43 inches high. DW1,CT3 12 months
1.16.b. No accessible coat hook has been provided. TR3 12 months
1.16.c. The side grab bar at the designated accessible toilet is inaccessible because it is obstructed by the toilet paper dispenser. TR15 12 months
1.16.d. The designated accessible toilet is inaccessible because the rear grab bar is obstructed by the toilet seat cover dispenser. TR15 12 months
1.16.e. Ambulatory stall:    
1.16.e(1) The toilet seat cover dispenser is inaccessible because it is mounted too high behind the toilet. CT3 12 months
1.16.e(2) The ambulatory stall is inaccessible because one side grab bar is obstructed by the toilet paper dispenser. TR15 12 months
1.17. Single user toilet room - main concourse, 1st base side, near sections 113/112/111:    
1.17.a. The paper towel dispenser protrudes into the walkway and is not detectable to blind persons using a cane. AR7 24 months
1.17.b. The baby changing station is inaccessible because, when closed, the handle is 55 inches high, and, when open, the surface is 43 inches high. DW1,CT3 12 months
1.17.c. The side grab bar at the toilet is inaccessible because it is obstructed by the toilet paper dispenser. TR6 12 months
1.17.d. The toilet seat cover dispenser is inaccessible because it is mounted too high behind the toilet. CT3 12 months
1.17.e. The toilet seat cover dispenser is inaccessible because it is mounted too high behind the toilet. TR15 12 months
1.18. Women’s toilet room with stalls - main concourse, 3rd base side, near sections 106/105/104/103:    
1.18.a. The baby changing station is inaccessible because, when closed, the handle is 55 inches high, and, when open, the surface is 43 inches high. DW1,CT3 12 months
1.18.b. The paper towel dispenser at the entrance protrudes into the walkway and is not detectable to blind persons using a cane. AR7 12 months
1.18.c. The designated accessible toilet is inaccessible because its centerline is 19 inches from the side wall. TR7 24 months
1.18.d. No accessible coat hook has been provided. TR3 12 months
1.18.e. The side grab bar at the designated accessible toilet is inaccessible because it is obstructed by the toilet paper dispenser. TR6 12 months
1.18.f. The toilet seat cover dispenser is inaccessible because it is mounted too high behind the toilet. CT3 12 months
1.18.g. The designated accessible toilet is inaccessible because the rear grab bar is obstructed by the toilet seat cover dispenser and the paper towel dispenser. TR15 12 months
1.18.h. Ambulatory stall: The ambulatory stall is inaccessible because the door is not self-closing, and one side grab bar is obstructed by the toilet paper dispenser. TR22,TR6 12 months
1.19. Men’s toilet room with stalls - main concourse, 3rd base side, near sections 106/105/104/103:    
1.19.a. The baby changing station is inaccessible because, when closed, the handle is 55 inches high, and, when open, the surface is 43 inches high. DW1,CT3 12 months
1.19.b. The paper towel dispensers protrude into the walkway and are not detectable to blind persons using a cane. AR7 24 months
1.19.c. No accessible coat hook has been provided. TR3 12 months
1.19.d. The side grab bar at the designated accessible toilet is inaccessible because it is obstructed by the toilet paper dispenser. TR6 12 months
1.19.e. The toilet seat cover dispenser is inaccessible because it is mounted too high behind the toilet. CT3 12 months
1.19.f. The designated accessible toilet is inaccessible because the rear grab bar is obstructed by the toilet seat cover dispenser and the paper towel dispenser. TR15 12 months
1.20. Condiment counter - main concourse, near section 103-106 toilet rooms: The condiment counter protrudes into the walkway and is not detectable to blind persons using a cane. AR7 12 months
1.21. Wheelchair seating - main concourse: The wheelchair seating area in section 115 that contains one wheelchair space is inaccessible because the wheelchair space is only 30 1/2 inches wide. AA6 12 months
1.22. Party Deck C / Sky Deck #1 - upper level: Sky Deck #1 is inaccessible because no wheelchair seating is provided. AA6 12 months
1.23. Single user family toilet room - upper level near Party Deck D:    
1.23.a. The baby changing station is inaccessible because, when closed, the handle is 55 inches high, and, when open, the surface is 43 inches high. DW1,CT3 12 months
1.23.b. The paper towel dispenser protrudes into the walkway and is not detectable to blind persons using a cane. AR7 12 months
1.23.c. The side grab bar at the toilet is inaccessible because it is obstructed by the toilet paper dispenser. TR6 12 months
1.23.d. The rear grab bar at the toilet is inaccessible because it is obstructed by the seat cover dispenser. TR15 12 months
1.23.e. The toilet seat cover dispenser is inaccessible because it is mounted too high behind the toilet. CT3 12 months
1.24. Men’s toilet room with stalls - upper level near sundowners lounge:    
1.24.a. The toilet room sign is not mounted on the latch side of the door. TR11 12 months
1.24.b. The baby changing station is inaccessible because, when closed, the handle is 56 inches high, and, when open, the surface is 44 inches high. DW1,CT3 12 months
1.24.c. The paper towel dispenser protrudes into the walkway and is not detectable to blind persons using a cane. AR7 12 months
1.24.d. No accessible coat hook has been provided. TR3 12 months
1.24.e. The side grab bar at the designated accessible toilet is inaccessible because it is obstructed by the toilet paper dispenser. TR6 12 months
1.24.f. The toilet seat cover dispenser is inaccessible because it is mounted too high behind the toilet. CT3 12 months
1.24.g. The designated accessible toilet is inaccessible because the rear grab bar is obstructed by the toilet seat cover dispenser and the paper towel dispenser. TR15 12 months
1.25. Women’s toilet room with stalls - upper level near sundowners lounge:    
1.25.a. The baby changing station is inaccessible because, when closed, the handle is 55 inches high, and, when open, the surface is 43 inches high. DW1,CT3 12 months
1.25.b. The paper towel dispensers protrude into the walkway and are not detectable to blind persons using a cane. AR7 12 months
1.25.c. No accessible coat hook has been provided. TR3 12 months
1.25.d. The side grab bar at the designated accessible toilet is inaccessible because it is obstructed by the toilet paper dispenser. TR6 12 months
1.25.e. The toilet seat cover dispenser is inaccessible because it is mounted too high behind the toilet. CT3 12 months
1.25.f. The designated accessible toilet is inaccessible because the rear grab bar is obstructed by the toilet seat cover dispenser. TR15 12 months
1.26. Drinking fountain - upper level, near sundowners lounge:    
1.26.a. The drinking fountain is inaccessible because the flow of water is 1/2 inch high. DF5 12 months
1.26.b. The drinking fountain is inaccessible because it provides only 26 1/4 inches of clear knee height. DF4 12 months
1.27. Single user toilet rooms - upper level at media boxes:    
1.27.a. The baby changing stations are inaccessible because, when closed, the handles are 56 inches high, and, when open, the surfaces are 44 inches high. DW1,CT3 12 months
1.27.b. The paper towel dispensers protrude into the walkway and are not detectable to blind persons using a cane. AR7 12 months
1.27.c. The side grab bar at each toilet is inaccessible because it is obstructed by the toilet paper dispenser. TR6 12 months
1.27.d. The rear grab bar at each toilet is inaccessible because it is obstructed by the seat cover dispenser. TR15 12 months
1.27.e. Each toilet seat cover dispenser is inaccessible because it is mounted too high behind the toilet. CT3 12 months
1.28. Single user toilet room - first aid room on main concourse:    
1.28.a. The paper towel dispenser protrudes into the walkway and is not detectable to blind persons using a cane. AR7 12 months
1.28.b. The rear grab bar at the toilet is inaccessible because it is obstructed by the seat cover dispenser. TR15 12 months
1.28.c. The toilet seat cover dispenser is inaccessible because it is mounted too high behind the toilet. CT3 12 months
1.29. Single user toilet room - home team dugout, 3rd base side:    
1.29.a. The toilet is inaccessible because its centerline is 20 inches from the side wall. TR7 12 months
1.29.b. The side grab bar at the toilet is inaccessible because it is obstructed by the toilet paper dispenser. TR6 12 months
1.29.c. The side grab bar at the toilet is inaccessible because it is mounted 3 1/2 inches from the wall. TR20 12 months
1.29.d. The rear grab bar at the toilet is inaccessible because it is obstructed by the seat cover dispenser and the paper towel dispenser. TR15 12 months
1.29.e. The toilet seat cover dispenser is inaccessible because it is mounted too high behind the toilet. CT3 12 months
1.30. Home Team Locker Room:    
1.30.a. No accessible coat hook has been provided. TR3 12 months
1.30.b. The paper towel dispenser protrudes into the walkway and is not detectable to blind persons using a cane. AR7 12 months
1.30.c. The side grab bar at the designated accessible toilet is inaccessible because it is obstructed by the toilet paper dispenser. TR6 12 months
1.30.d. The toilet seat cover dispenser is inaccessible because it is mounted too high behind the toilet. CT3 12 months
1.30.e. The bench is inaccessible because it is 16 inches deep and it does not provide clear floor space alongside to allow a transfer. LR2 12 months
1.31. South side unidentified locker room:    
1.31.a. No accessible coat hook has been provided. TR3 12 months
1.31.b. The side grab bar at the designated accessible toilet is inaccessible because it is obstructed by the toilet paper dispenser. TR6 12 months
1.31.c. The toilet seat cover dispenser is inaccessible because it is mounted too high behind the toilet in the dressing room. CT3 12 months
1.31.d. The designated accessible toilet is inaccessible because the rear grab bar is obstructed by the toilet seat cover dispenser. TR15 12 months
1.31.e. The paper towel dispenser protrudes into the walkway and is not detectable to blind persons using a cane. AR7 12 months
1.31.f. The bench is inaccessible because it is 16 inches deep and 36 inches long and does not provide clear floor space alongside to allow a transfer. LR2 12 months
1.32. North side unidentified locker room:    
1.32.a. No accessible coat hook has been provided. TR3 12 months
1.32.b. The side grab bar at the designated accessible toilet is inaccessible because it is obstructed by the toilet paper dispenser. TR6 12 months
1.32.c. The toilet seat cover dispenser is inaccessible because it is mounted too high behind the toilet. CT3 12 months
1.32.d. The designated accessible toilet is inaccessible because the rear grab bar is obstructed by the toilet seat cover dispenser. TR15 12 months
1.32.e. The bench is inaccessible because it is 16 inches deep and 36 inches long and does not provide clear floor space alongside to allow a transfer. LR2 12 months
1.32.f. The paper towel dispenser protrudes into the walkway and is not detectable to blind persons using a cane. AR7 12 months
1.33. Umpires’ locker room:    
1.33.a. No accessible coat hook has been provided. TR3 12 months
1.33.b. The side grab bar at the designated accessible toilet is inaccessible because it is obstructed by the toilet paper dispenser. TR6 12 months
1.33.c. The toilet seat cover dispenser is inaccessible because it is mounted too high behind the toilet. CT3 12 months
1.33.d. The designated accessible toilet is inaccessible because the rear grab bar is obstructed by the toilet seat cover dispenser and the paper towel dispenser. TR15 12 months
1.33.e. The bench is inaccessible because it is 16 inches deep and 36 inches long and does not provide clear floor space alongside to allow a transfer. LR2 12 months
1.34. Single user toilet room - administrative offices:    
1.34.a. The toilet is inaccessible because the small wooden table near the toilet blocks the clear floor space. TR24 12 months
1.34.b. The side grab bar at the toilet is inaccessible because it is obstructed by the toilet paper dispenser. TR6 12 months
1.34.c. The rear grab bar at the toilet is inaccessible because it is obstructed by the seat cover dispenser. TR15 12 months
1.34.d. The toilet seat cover dispenser is inaccessible because it is mounted too high behind the toilet. CT3 12 months
1.35. Visitor’s Locker Room:    
1.35.a. No accessible coat hook has been provided. TR3 12 months
1.35.b. The side grab bar at the designated accessible toilet is inaccessible because it is obstructed by the toilet paper dispenser. TR6 12 months
1.35.c. The toilet seat cover dispenser is inaccessible because it is mounted too high behind the toilet. CT3 12 months
1.35.d. The rear grab bar at the toilet is inaccessible because it is obstructed by the seat cover dispenser. TR15 12 months
1.35.e. The bench is inaccessible because it is 16 inches deep and 36 inches long and does not provide clear floor space alongside to allow a transfer. LR2 12 months
1.36. Single user toilet room - Visitors Dugout, 1st base side:    
1.36.a. The toilet is inaccessible because its centerline is 21 inches from the side wall. TR7 12 months
1.36.b. The side grab bar at the toilet is inaccessible because it is obstructed by the toilet paper dispenser. TR6 12 months
1.36.c. The side grab bar at the toilet is inaccessible because it is mounted 4 1/2 inches from the wall. TR20 12 months
1.36.d. The toilet paper dispenser is inaccessible because it is mounted greater than 48 inches high. TR6 12 months
1.36.e. The rear grab bar at the toilet is inaccessible because it is obstructed by the seat cover dispenser and the paper towel dispenser. TR15 12 months
1.36.f. The toilet seat cover dispenser is inaccessible because it is mounted too high behind the toilet. CT3 12 months
1.37. Men’s toilet room with stalls - lower level, 1st base side:    
1.37.a. The door is inaccessible because it requires 25 pounds of force to open. D3 12 months
1.37.b. No accessible coat hook has been provided. TR3 12 months
1.37.c. The side grab bar at the designated accessible toilet is inaccessible because it is obstructed by the toilet paper dispenser. TR6 12 months
1.37.d. The paper towel dispenser is inaccessible because its mounted 10 inches above the rear grab bar. CT3 12 months
1.37.e. The toilet seat cover dispenser is inaccessible because it is mounted too high behind the toilet. CT3 12 months
1.37.f. The designated accessible toilet is inaccessible because the rear grab bar is obstructed by the toilet seat cover dispenser and the paper towel dispenser. TR15 12 months
1.38. Women’s toilet room with stalls - lower level, 1st base side:    
1.38.a. The door is inaccessible because it requires more than 5 pounds of force to open. D3 12 months
1.38.b. No accessible coat hook has been provided. TR3 12 months
1.38.c. The side grab bar at the designated accessible toilet is inaccessible because it is obstructed by the toilet paper dispenser. TR6 12 months
1.38.d. The toilet seat cover dispenser is inaccessible because it is mounted too high behind the toilet. CT3 12 months
1.38.e. The designated accessible toilet is inaccessible because the rear grab bar is obstructed by the toilet seat cover dispenser and the paper towel dispenser. TR15 12 months
2. Jacksonville Main Library, 303 N. Laura Street    
2.1. Laura Street entrance:    
2.1.a. The automatic door button is inaccessible because it has not been maintained in working order. M1 12 months
2.2. The information counter is inaccessible because it is 38 1/2 inches high. C1 12 months
2.3. The security counter is inaccessible because it is 39 inches high. C1 12 months
2.4. Route through C level: The temporary artwork display protrudes into the walkway and is not detectable to blind persons using a cane. AR7 12 months
2.5. Main Street entrance:    
2.5.a. The exterior automatic door button is inaccessible because the controls require 6 pounds of force to operate. CT2 12 months
2.5.b. The interior automatic door button is inaccessible because the controls require 10 pounds of force to operate. CT2 12 months
2.5.c. The security counter is inaccessible because it is 45 1/2 inches high. C1 12 months
2.6. Interior doors: The doors throughout the facility are inaccessible because they require more than 5 pounds of force to open. D3 12 months
2.7. Toilet rooms: The metal shelves mounted in the toilet rooms throughout the facility protrude into the walkway and are not detectable to blind persons using a cane. AR7 12 months
2.8. Women’s toilet room with stalls - C level near managers office Room 066:    
2.8.a. The lavatory push control is inaccessible because the controls require 7 pounds of force to operate. CT2 12 months
2.9. Men’s toilet room with stalls - C level near managers office Room 066:    
2.9.a. The lavatory faucet control is inaccessible because the controls require 10 pounds of force to operate. CT2 12 months
2.9.b. The urinal is inaccessible because the rim is 24 inches high. TR8 12 months
2.9.c. The rear grab bar is inaccessible because it is obstructed by the hand dryer. TR15 12 months
2.10. Information counter - C level: The security counter is inaccessible because it is 43 1/2 inches high. C1 12 months
2.11. Kitchenette 074: The telephone is inaccessible because it is 56 inches high to the highest operable part. TT1 12 months
2.12. Auditorium - near Main Street:    
2.12.a. The auditorium, containing 391 seats, is inaccessible because there is insufficient wheelchair seating. A total of 6 wheelchair seating areas is required. AA6 12 months
2.12.b. There is no signage informing the public of the availability of an assistive listening system. AA3 12 months
2.12.c. The lift is inaccessible because it requires that a key be obtained from an employee before the lift can be operated. LF2 12 months
2.12.d. The ramp is inaccessible because the handrails do not have 12 inch extensions at the top or bottom, and the diameter of the handrails is 2 1/2 inches. R1 12 months
2.13. Green room - behind stage, serving rooms 045 & 046:    
2.13.a. The lavatory faucet control is inaccessible because the controls require 6 pounds of force to operate. CT2 12 months
2.13.b. The side grab bar at the toilet is inaccessible because it is 24 inches long. TR17 12 months
2.13.c. The telephone in room 045 is inaccessible because it is mounted with the highest controls 56 inches high. CT4 12 months
2.14. Ramp - behind multipurpose room #3: The ramp is inaccessible because it has a slope between 8.7% and 9.5%. R1 12 months
2.15. Women’s employee locker room - C level near conference room:    
2.15.a. The entry door is inaccessible because there is a 1/2 inch high unbeveled threshold. D12 12 months
2.15.b. The lavatory faucet control is inaccessible because the controls require 9 pounds of force to operate. CT2 12 months
2.15.c. The rear grab bar at the toilet is inaccessible because it is 32 inches long. TR14 12 months
2.15.d. The rear grab bar at the toilet is inaccessible because it is obstructed by the soap dispenser. TR15 12 months
2.15.e. There is no accessible locker provided. LR3 12 months
2.15.f. The air dryers protrude into the walkway and are not detectable to blind persons using a cane. AR7 12 months
2.16. Men’s employee locker room - C level near conference room:    
2.16.a. The entry door is inaccessible because there is a 1/2 inch high unbeveled threshold. D12 12 months
2.16.b. The push side of the door, which is accessed through a front approach and which has both a closer and a latch, is inaccessible because it has only 3 1/2 inches of clear space on the latch side. D5 12 months
2.16.c. The lavatory faucet control is inaccessible because the controls require 9 pounds of force to operate. CT2 12 months
2.16.d. The side grab bar is inaccessible because it is mounted with the far end 46 inches from the rear wall. TR17 12 months
2.16.e. The rear grab bar at the toilet is inaccessible because it is 32 inches long. TR14 12 months
2.16.f. The air dryers protrude into the walkway and are not detectable to blind persons using a cane. AR7 12 months
2.17. Drinking fountain - C level outside employee locker rooms:    
2.17.a. The drinking fountain is inaccessible because the controls require 6 pounds of force to operate. DF2 12 months
2.17.b. The wall-mounted drinking fountain is inaccessible because it provides only 26 1/2 inches of clear knee height. DF4 12 months
2.17.c. The higher drinking fountain protrudes into the walkway and is not detectable to blind persons using a cane. AR7 12 months
2.18. Drinking fountain - C level Main Street side, near toilet rooms:    
2.18.a. The drinking fountain is inaccessible because the controls require 9 pounds of force to operate. DF2 12 months
2.18.b. The wall-mounted drinking fountain is inaccessible because it provides only 26 1/2 inches of clear knee height. DF4 12 months
2.18.c. The higher drinking fountain protrudes into the walkway and is not detectable to blind persons using a cane. AR7 12 months
2.19. Women’s toilet room with stalls - C level near Main Street:    
2.19.a. The paper towel dispenser is inaccessible because it is mounted 55 inches high. CT4 12 months
2.19.b. The lavatory is inaccessible because the controls require 10 pounds of force to operate. CT2 12 months
2.19.c. The designated accessible toilet is inaccessible because its centerline is 18 1/2 inches from the side wall. TR7 12 months
2.19.d. The ambulatory stall is inaccessible because it is 34 inches wide, the door is not outward swinging and self-closing, and the toilet is not centered within the stall. TR22 12 months
2.20. Men’s toilet room with stalls - C level near Main Street:    
2.20.a. The lavatory is inaccessible because the controls require 9 pounds of force to operate. CT2 12 months
2.20.b. The designated accessible toilet is inaccessible because its centerline is 18 1/2 inches from the side wall. TR7 12 months
2.21. Single User toilet room - C level near Main Street entry:    
2.21.a. The lavatory is inaccessible because the controls require 10 pounds of force to operate. CT2 12 months
2.21.b. The air dryer protrudes inches into the walkway and is not detectable to blind persons using a cane. AR7 12 months
2.22. Employee service elevator: The elevator is inaccessible because the time from notification that a car is answering a call until the doors of that car start to close is less than 5 seconds. E6 12 months
2.23. Public elevator: The elevator is inaccessible because the time from notification that a car is answering a call until the doors of that car start to close is less than 5 seconds. E6 12 months
2.24. Human resources interview office:    
2.24.a. The counter is inaccessible because it is 43 1/2 inches high. C1 12 months
2.24.b. The first aid kit located on the kitchen counter is inaccessible because it is mounted 55 inches high over an obstruction. CT3 12 months
2.25. Employee mail room: The first aid kit is inaccessible because it is mounted with the controls 65 inches high. CT4 12 months
2.26. Employee exit ramp: The ramp is inaccessible because it has a slope of between 8.6% and 9.5% and the handrails do not have extensions. R4 12 months
2.27. Women’s 1st floor toilet room with stalls:    
2.27.a. The interior side of the door is inaccessible because there is a 1/2 inch high unbeveled threshold. D12 12 months
2.27.b. The paper towel dispenser protrudes into the walkway and is not detectable to blind persons using a cane. AR7 12 months
2.27.c. The lavatory is inaccessible because the controls require 9 pounds of force to operate. CT2 12 months
2.27.d. The grab bar is inaccessible because it is mounted 2 inches from the wall. TR20 12 months
2.28. Men’s 1st floor toilet room with stalls:    
2.28.a. The interior side of the door is inaccessible because there is a 1/2 inch high unbeveled threshold. D12 12 months
2.28.b. The paper towel dispenser protrudes into the walkway and is not detectable to blind persons using a cane. AR7 12 months
2.28.c. The lavatory is inaccessible because the controls require 8 pounds of force to operate. CT2 12 months
2.29. Drinking fountain -near main check out: The drinking fountain is inaccessible because the controls require 7 pounds of force to operate. DF2 12 months
2.30. Single user family toilet room:    
2.30.a. The door is inaccessible because it has a ½ inch high unbeveled threshold. D12 12 months
2.30.b. The rear grab bar at the toilet is inaccessible because it is 32 inches long. TR14 12 months
2.30.c. The toilet is inaccessible because the lavatory obstructs the clear floor space provided. TR24 12 months
2.31. Employee single user toilet rooms - 1st floor: The air dryers protrude into the walkway and are not detectable to blind persons using a cane. AR7 12 months
2.32. Main lobby - 1st floor:    
2.32.a. The check-out area is inaccessible because the counter is 39 inches high. C1 12 months
2.32.b. The information desk is inaccessible because it is 40 inches high. C1 12 months
2.32.c. The card catalog computer table is inaccessible because the keyboard is on a table 41 1/2 inches high. C2 12 months
2.33. Teen room:    
2.33.a. The information counter is inaccessible because it is 42 inches high. C1 12 months
2.33.b. The route is inaccessible because there are only 74 inches of head room provided under the television. AR7 12 months
2.33.c. The print station counter is inaccessible because the table is 42 inches high. C2 12 months
2.34. Women’s toilet room with stalls - 2nd floor near periodical section:    
2.34.a. The door is inaccessible because there is a 1/2 inch high unbeveled threshold. D12 12 months
2.34.b. The grab bars at the designated accessible toilet are inaccessible because they are mounted 2 inches from the wall. TR20 12 months
2.35. Men’s toilet room with stalls - 2nd floor near periodical section:    
2.35.a. The door is inaccessible because there is a 1/2 inch high unbeveled threshold. D12 12 months
2.35.b. The paper towel dispenser protrudes into the walkway and is not detectable to blind persons using a cane. AR7 12 months
2.35.c. The grab bars at the designated accessible toilet are inaccessible because they are mounted 2 inches from the wall. TR20 12 months
2.36. Single user family toilet room - 2nd floor near periodical section:    
2.36.a. The door is inaccessible because there is a 1/2 inch high unbeveled threshold. D12 12 months
2.36.b. The paper towel dispenser is inaccessible because it is mounted with the controls 54 inches high. CT4 12 months
2.36.c. The rear grab bar at the toilet is inaccessible because it is 32 inches long. TR14 12 months
2.37. Drinking fountain - 2nd floor near periodicals: The higher drinking fountain protrudes into the walkway and is not detectable to blind persons using a cane. AR7 12 months
2.38. Children’s theater - 2nd floor:    
2.38.a. The handrail extensions on the ramp to the stage protrude into the walkway and are not detectable to blind persons using a cane. AR7 12 months
2.38.b. The route to the stage is inaccessible because the top of the ramp is obstructed by moveable carts. AR1 12 months
2.38.c. There is no signage informing the public of the availability of an assistive listening system. AA3 12 months
2.39. Girls single user toilet room - 2nd floor children’s library:    
2.39.a. The push side of the door, which is accessed through a front approach and which has both a closer and a latch, is inaccessible because it has insufficient clear space on the latch side. D5 12 months
2.39.b. The door is inaccessible because there is a 1/2 inch high unbeveled threshold. D12 12 months
2.39.c. The air dryer protrudes into the walkway and is not detectable to blind persons using a cane. AR7 12 months
2.40. Boys single user toilet room - 2nd floor children’s library:    
2.40.a. The door is inaccessible because there is a 1/2 inch high unbeveled threshold. D12 12 months
2.40.b. The air dryer protrudes into the walkway and is not detectable to blind persons using a cane. AR7 12 months
2.41. Children’s library - 2nd floor:    
2.41.a. The higher drinking fountain protrudes into the walkway and is not detectable to blind persons using a cane. AR7 12 months
2.41.b. The drinking fountain is inaccessible because the controls require 6 pounds of force to operate. DF2 12 months
2.42. Single user family toilet room - 3rd floor Duval side: The rear grab bar at the toilet is inaccessible because it is 32 inches long. TR14 12 months
2.43. Drinking fountain - 3rd floor Duval side: The higher drinking fountain protrudes into the walkway and is not detectable to blind persons using a cane. AR7 12 months
2.44. Drinking fountain - 3rd floor Monroe side in staff area: The higher drinking fountain protrudes into the walkway and is not detectable to blind persons using a cane. AR7 12 months
2.45. Women’s toilet room with stalls - 3rd floor Monroe side in staff area:    
2.45.a. The air dryers protrude into the walkway and are not detectable to blind persons using a cane. AR7 12 months
2.45.b. The designated accessible toilet is inaccessible because the rear grab bar is obstructed by an air dryer. TR15 12 months
2.46. Men’s toilet room with stalls - 3rd floor Monroe side in staff area:    
2.46.a. The air dryers protrude into the walkway and are not detectable to blind persons using a cane. AR7 12 months
2.46.b. The designated accessible toilet is inaccessible because the rear grab bar is obstructed by an air dryer. TR15 12 months
2.46.c. The urinal is inaccessible because the rim is 25 inches high. TR8 12 months
2.47. Drinking fountain - 4th floor Duval side: The higher drinking fountain protrudes into the walkway and is not detectable to blind persons using a cane. AR7 12 months
2.48. Single user family toilet room - 4th floor Duval side:    
2.49. The rear grab bar at the toilet is inaccessible because it is 32 inches long. TR14 12 months
2.50. The rear grab bar at the toilet is inaccessible because it is obstructed by the soap dispenser. TR15 12 months
2.51. Microfiche - 4th Floor: The table is inaccessible because it provides 24 1/2 inches of clear knee height. DW1 12 months
2.51.a. Employee single user toilet room - 4th floor Duval side: The rear grab bar at the toilet is inaccessible because it is obstructed by the soap dispenser. TR15 12 months
2.52. Drinking fountain - 4th floor employee area Monroe side: The higher drinking fountain protrudes into the walkway and is not detectable to blind persons using a cane. AR7 12 months
2.53. Employee women’s toilet room with stalls - 4th floor Monroe side:    
2.53.a. The paper towel dispenser and air dryer protrude into the walkway and are not detectable to blind persons using a cane. AR7 12 months
2.53.b. The designated accessible toilet is inaccessible because the rear grab bar is obstructed by the air dryer. TR15 12 months
2.54. Employee men’s toilet room with stalls - 4th floor Monroe side:    
2.54.a. The urinal is inaccessible because the rim is 24 inches high. TR8 12 months
2.54.b. The urinal is inaccessible because the route to it is only 26 1/2 inches wide. AR3 12 months
2.54.c. The paper towel dispenser and air dryer protrude into the walkway and are not detectable to blind persons using a cane. AR7 12 months
2.54.d. The designated accessible toilet is inaccessible because the rear grab bar is obstructed by the air dryer. TR15 12 months
3. Kids Kampus, 1410 Gator Bowl Boulevard    
3.1. Picnic Pavilion #1    
3.1.a. The entrance to the pavilion is inaccessible because it is obstructed by a tent pole. AR3 12 months
3.1.b. The picnic tables are inaccessible because none provide the required knee space. DW1 12 months
3.1.c. Drinking fountain between pavilions #2 and #3: The drinking fountain is inaccessible because the controls require more than 5 pounds of force to operate. DF2 12 months
3.2. Picnic Pavilion #3:    
3.2.a. The route is inaccessible because the width of the walkway is 32 1/2 inches wide and there is a 2 1/4 inch change in level between the asphalt walkway and the concrete pad. AR1 12 months
3.2.b. The picnic tables are inaccessible because none provide the required knee space. DW1 12 months
3.3. Tire Run: The route is inaccessible because there is a 1 1/2 inch change in level between the concrete and yellow brick path. AR1 12 months
3.4. Drinking fountain near toilet rooms: The drinking fountain is inaccessible because the controls require more than 5 pounds of force to operate. DF2 12 months
3.5. Drinking fountain near Lake George watering hole: The drinking fountain contains a number of inaccessible features and is not accessible to people using wheelchairs. DF1 12 months
3.6. Women’s toilet room with stalls:    
3.6.a. The paper towel dispenser and the sanitary napkin dispenser protrude into the walkway and are not detectable to blind persons using a cane. AR7 12 months
3.6.b. The toilet paper dispenser in the designated accessible stall is inaccessible because it is mounted more than 9 inches from the front of toilet. TR6 12 months
3.7. Men’s toilet room with stalls: The paper towel dispenser protrudes into the walkway and is not detectable to blind persons using a cane. AR7 12 months
4. Dinsmore Community Center, 7126 Civic Club Road    
4.1. Entrances: The three entrances are inaccessible because there is a 9.3% slope within one door’s maneuvering clearance, the route to another door has a slope of 7.1% with no ramp features, and the building does not have directional signage posted at inaccessible entrances and does not have the International Symbol of Accessibility posted at accessible entrances. D7, D10, R4 12 months
4.2. Baseball fields: The routes to the dugouts are inaccessible because the grass is not firm, stable or slip resistant. AR1 12 months
4.3. Women’s toilet room inside center:    
4.3.a. The toilet room sign is mounted on the door and has no raised or Braille characters. TR11 12 months
4.3.b. The door is inaccessible because it requires 10 pounds of force to open. D3 12 months
4.3.c. The air dryer protrudes into the walkway and is not detectable to blind persons using a cane. AR7 12 months
4.3.d. The designated accessible toilet is inaccessible because its centerline is 21 1/2 inches from the side wall. TR7 12 months
4.3.e. No accessible coat hook has been provided. TR3 12 months
4.3.f. The toilet paper dispenser in the designated accessible stall is inaccessible because it is mounted more than 9 inches from the front of toilet. TR6 12 months
4.4. Men’s toilet room inside center:    
4.4.a. The toilet room sign is mounted on the door and has no raised or Braille characters. TR11 12 months
4.4.b. The door is inaccessible because it requires 11 pounds of force to open. D3 12 months
4.4.c. The air dryer protrudes into the walkway and is not detectable to blind persons using a cane. AR7 12 months
4.4.d. The urinal is inaccessible because the rim is 17 1/2 inches high and the clear floor space is 27 1/2 inches wide. TR8 12 months
4.4.e. The route to the urinal is inaccessible because it is only 27 1/2 inches wide. AR3 12 months
4.4.f. The designated accessible toilet is inaccessible because its centerline is 20 1/2 inches from the side wall. TR7 12 months
4.4.g. No accessible coat hook has been provided. TR3 12 months
4.4.h. The toilet paper dispenser in the designated accessible stall is inaccessible because it is mounted more than 9 inches from the front of toilet TR6 12 months
4.5. Drinking fountains inside center: The higher drinking fountain protrudes into the walkway and is not detectable to blind persons using a cane. AR7 12 months
4.6. Drinking fountains by outdoor toilet rooms: The higher drinking fountain protrudes into the walkway and is not detectable to blind persons using a cane. AR7 12 months
4.7. Single-user women’s toilet room - outdoors by ballfield 2: The air dryer protrudes into the walkway and is not detectable to blind persons using a cane. AR7 12 months
4.8. Single-user men’s toilet room - outdoors by ballfield 2:    
4.8.a. The urinal is inaccessible because the rim is 24 inches high. TR8 12 months
4.8.b. The air dryer protrudes into the walkway and is not detectable to blind persons using a cane. AR7 12 months
5. Sisters Creek Boat Ramp, 8203 Heckscher Drive    
5.1. Parking by boat ramp: The parking lot, with a total of 57 parking spaces, is inaccessible because it only has 2 spaces designated as accessible. This lot requires 1 van accessible space and 2 standard accessible spaces. P1 12 months
5.2. Picnic area near dock: The picnic tables are inaccessible because none provide the required knee space. DW1 12 months
5.3. Metal ramps to boat dock: The three ramps are all inaccessible because they have slopes between 9.5% and 30.2% at the bottom. R4 12 months
5.4. Women’s exterior toilet room with stalls: The air dryer protrudes into the walkway and is not detectable to blind persons using a cane. AR7 12 months
5.5. Men’s exterior toilet room with stalls:    
5.5.a. The lavatory is inaccessible because it has twist-type hardware. LS4 12 months
5.5.b. The designated accessible toilet is inaccessible because its centerline is 18 1/2 inches from the side wall. TR7 12 months
5.5.c. No accessible coat hook has been provided. TR3 12 months
6. Pablo Creek Library, 13295 Beach Boulevard    
6.1. Interior Doors: The doors throughout the facility are inaccessible because they require more than 5 pounds of force to open. D3 12 months
6.2. Drinking fountains: Although designated accessible drinking fountains are provided, there is no drinking fountain provided for people who have difficulty bending or stooping. DF3 12 months
6.3. Men’s toilet room with stalls at front entrance: The designated accessible toilet is inaccessible because the rear grab bar is obstructed by the soap dispenser. TR15 12 months
6.4. Women’s toilet room with stalls at front entrance: Although there are 7 toilet stalls, there is no ambulatory stall provided. TR22 12 months
6.5. Single-user unisex toilet room at front entrance: The toilet room sign is mounted on the door. TR11 12 months
6.6. Teen center room 145: The computers are inaccessible because the keyboards are on a table 39 inches high. C2 12 months
6.7. Main library:    
6.7.a. The magazine displays are inaccessible because they are 65 inches high to the top. CT4 12 months
6.7.b. The book and media drops are inaccessible because they are 49 inches high. CT4 12 months
6.7.c. The catalog computers are inaccessible because the keyboards are on a table 39 1/2 inches high. C2 12 months
6.8. Single-user toilet room in kid’s area: The route into the toilet room is inaccessible because there are only 78 inches of head room provided in the corner by the door. AR7 12 months
6.9. “Ask here” desk: The defibrillator near the desk protrudes into the walkway and is not detectable to blind persons using a cane. AR7 12 months
7. Oceanway Senior Center, 12215 Sago Avenue    
7.1. Route from parking to entrance: The curb ramp is inaccessible because the flared side has a slope of 21%. AR4 12 months
7.2. Kitchen: The sink is inaccessible because it provides no knee clearance. LS1 12 months
7.3. Computer room:    
7.3.a. The computers are inaccessible because the keyboards are on tables that provide 26 1/2 inches of clear knee height. C2 12 months
7.3.b. The tables are inaccessible because they provide 26 1/2 inches of clear knee height. DW1 12 months
7.4. Men’s toilet room with stalls:    
7.4.a. The door is inaccessible because it requires 10 pounds of force to open. D3 12 months
7.4.b. The urinal is inaccessible because the rim is 18 inches high and the clear floor space is 25 1/2 inches wide. TR8 12 months
7.4.c. The route to the urinal is inaccessible because it is only 25 1/2 inches wide. AR3 12 months
7.4.d. No accessible coat hook has been provided. TR3 12 months
7.4.e. The side grab bar at the designated accessible toilet is inaccessible because it is obstructed by the toilet paper dispenser. TR6 12 months
7.4.f. The side grab bar at the designated accessible toilet is inaccessible because it is mounted with the far end 50 inches from the rear wall. TR17 12 months
7.4.g. The grab bars at the designated accessible toilet are inaccessible because they are mounted 32 inches high. TR19 12 months
7.5. Women’s toilet room with stalls:    
7.5.a. The door is inaccessible because it requires 15 pounds of force to open. D3 12 months
7.5.b. No accessible coat hook has been provided. TR3 12 months
7.5.c. The side grab bar at the designated accessible toilet is inaccessible because it is obstructed by the toilet paper dispenser. TR6 12 months
7.5.d. The side grab bar at the designated accessible toilet is inaccessible because it is mounted with the far end 50 inches from the rear wall. TR17 12 months
7.5.e. The grab bars at the designated accessible toilet are inaccessible because they are mounted 32 inches high. TR19 12 months
8. Fire Station #35, 12851 Main Street    
8.1. Entrance: The doorbell is inaccessible because its clear floor space is obstructed by the bench. CT3 12 months
8.2. Single-user toilet room at front entrance: The door is inaccessible because it requires 10 pounds of force to open. D3 12 months
9. Southside Tennis Complex, 1539 Hendricks Avenue    
9.1. Parking: The van accessible parking space is inaccessible because it lacks “Van Accessible” signage. P3 12 months
9.2. Women’s locker room:    
9.2.a. The door is inaccessible because it requires 7 pounds of force to open. D3 12 months
9.2.b. No accessible coat hook has been provided. TR3 12 months
9.2.c. The side grab bar at the designated accessible toilet is inaccessible because it is mounted 12 1/2 inches from the rear wall. TR17 12 months
9.2.d. The designated accessible toilet is inaccessible because the rear grab bar is obstructed by the air dryer. TR15 12 months
9.2.e. The shower contains a number of inaccessible elements and is not accessible to people with disabilities. B2 12 months
9.2.f. No accessible towel hook has been provided. TR3 12 months
9.2.g. The metal shelf protrudes into the walkway and is not detectable to blind persons using a cane. AR7 12 months
9.2.h. The bench is inaccessible because it is 15 1/2 inches deep and 36 inches long. LR1 12 months
9.3. Men’s locker room:    
9.3.a. The door is inaccessible because it requires 9 pounds of force to open. D3 12 months
9.3.b. The urinal is inaccessible because the rim is 18 inches high and the clear floor space is 29 inches wide. TR8 12 months
9.3.c. The designated accessible toilet is inaccessible because its centerline is 19 inches from the side wall. TR7 12 months
9.3.d. No accessible coat hook has been provided. TR3 12 months
9.3.e. The side grab bar at the designated accessible toilet is inaccessible because it is mounted 12 1/2 inches from the rear wall. TR17 12 months
9.3.f. The designated accessible toilet is inaccessible because the rear grab bar is obstructed by the air dryer. TR15 12 months
9.3.g. The routes to the designated accessible toilet stall and to the shower are inaccessible because they have cross slopes of 4.7% and 4%, respectively. AR1 12 months
9.3.h. The shower contains a number of inaccessible elements and is not accessible to people with disabilities. B2 12 months
9.3.i. No accessible towel hook has been provided. TR3 12 months
9.3.j. The metal shelf protrudes into the walkway and is not detectable to blind persons using a cane. AR7 12 months
9.3.k. The bench is inaccessible because it is 16 inches deep and 30 inches long. LR1 12 months
9.4. Exterior drinking fountain: Although a designated accessible drinking fountain is provided, there is no drinking fountain provided for people who have difficulty bending or stooping. DF3 12 months
9.5. Exterior tables:    
9.5.a. The picnic tables are inaccessible because none provide the required knee space. DW1 12 months
9.5.b. The patio tables are inaccessible because they provide 26 inches of clear knee height. DW1 12 months
10. Jacksonville Children’s Commission, 1095 A Philip Randolph Boulevard    
10.1. Entrances: The building does not have directional signage posted at inaccessible entrances and does not have the International Symbol of Accessibility posted at accessible entrances. D10 12 months
10.2. Parking: The designated accessible parking is inaccessible because it is not dispersed among the accessible facility entrances – there is no accessible parking provided in the Brewer Early Learning Center lot. P7 12 months
10.3. Route from parking to main entrance: The sidewalk to the main entrance is inaccessible because it has a slope of up to 7.8% with no ramp features. R4 12 months
10.4. Interior routes: The hallways throughout each of the facilities are inaccessible because the fire extinguishers protrude into the walkway and are not detectable to blind persons using a cane. AR7 12 months
10.5. Interior doors: The doors throughout each of the facilities are inaccessible because they require more than 5 pounds of force to open. D3 12 months
10.6. Women’s toilet room with stalls - 1st floor:    
10.6.a. No accessible mirror has been provided. TR5 12 months
10.6.b. The designated accessible toilet is inaccessible because its centerline is 19 inches from the side wall. TR7 12 months
10.7. Men’s toilet room with stalls - 1st floor: No accessible mirror has been provided. TR5 12 months
10.8. Elevator: The elevator is inaccessible because the emergency system requires voice communication to operate. E7 12 months
10.9. 2nd Floor reception counter: The counter protrudes into the walkway and is not detectable to blind persons using a cane. AR7 12 months
10.10. Women’s toilet room 221:    
10.10.a.  No accessible mirror has been provided. TR14 12 months
10.10.b. The toilet paper dispenser in the designated accessible stall is inaccessible because it is mounted more than 9 inches from the front of the toilet. TR6 12 months
10.11. Men’s toilet room 222:    
10.11.a.  No accessible mirror has been provided. TR5 12 months
10.11.b.  The urinal is inaccessible because the rim is 18 inches high. TR8 12 months
10.11.c.  No accessible coat hook has been provided. TR3 12 months
10.12. Family Services single-user toilet room 135: No accessible mirror has been provided. TR5 12 months
10.13. Drinking fountains by Family Services toilet rooms: The drinking fountain protrudes into the walkway and is not detectable to blind persons using a cane. AR7 12 months
10.14. Conference center - dining/training room 125: The sink is inaccessible because the drain pipes are not insulated or otherwise configured to protect against contact. LS1-5 12 months
10.15. Conference center - men’s toilet room 120: The designated accessible toilet is inaccessible because its centerline is 19 inches from the side wall. TR7 12 months
10.16. Brewer ELC drinking fountain by reception desk: The drinking fountain protrudes into the walkway and is not detectable to blind persons using a cane. AR7 12 months
10.17. Brewer ELC - men’s single-user toilet room 110: The door is inaccessible because it requires 14 pounds of force to open. D3 12 months
10.18. Brewer ELC - women’s single-user toilet room 111:    
10.18.a.  The door is inaccessible because it requires 15 pounds of force to open. D3 12 month
10.18.b. The rear grab bar at the toilet is inaccessible because it is obstructed by the seat cover dispenser. TR15 12 months
10.19. Brewer ELC - women’s toilet room 126: The toilet paper dispenser in the designated accessible stall is inaccessible because it is mounted more than 9 inches from the front of the toilet. TR6 12 months
10.20. Brewer ELC - family toilet room 124A    
10.20.a.  The door is inaccessible because it requires 15 pounds of force to open. D3 12 months
10.20.b.  The bathtub has no seat provided, and there is no vertical bar provided for the shower spray unit. B1 12 months
10.20.c.  The shower controls are inaccessible because the knob hardware requires twisting and grasping. B2 12 months
11. Burnett Park, 3740 Burnett Park Road
11.1. Parking at new ball fields:    
11.1.a. Two of the designated accessible parking spaces are inaccessible because they do not have vertical signage. P3 12 months
11.1.b. The parking reserved for persons with disabilities is inaccessible because the gravel is not firm, stable and slip resistant. P4 12 months

 