Attachment I: Modifications to Newly Constructed Facilities
Please Note: Paragraph 50 of the Settlement Agreement requires that within three months of the effective date of this Agreement, the County will provide signage as necessary to comply with 28 C.F.R. § 35.163(b), after having surveyed all facilities that are the subject of this Agreement for the purpose of identifying those that have multiple entrances not all of which are accessible.
In order to ensure that the following spaces and elements in County facilities, for which construction was commenced after January 26, 1992, are readily accessible to and usable by persons with disabilities, the County will take the following actions:
(1)Men's
(a)The door is inaccessible because the pressure required to open the door is 19 pounds. Provide a door that requires no more than 5 pounds of force to open. Standards §§ 4.1.3(7)(b), 4.13.11(2)(b).
(b)The seat cover dispenser is inaccessible because the controls are mounted 57 inches above the finished floor. Provide a seat cover dispenser with the controls a maximum height above the finished floor of 48 inches for a forward approach or 54 inches for a side approach and that is accompanied by clear floor space of 30 by 48 inches that allows a forward or parallel approach by a person using a wheelchair. Standards §§ 4.1.3(13), 4.27.2, 4.27.3, 4.2.4, 4.2.5, 4.2.6.
(c)The urinal is inaccessible because the flush control is 48 inches above the finished floor. Provide a urinal with an elongated rim mounted 17 inches or less above the finished floor, a clear floor space of at least 30 inches wide and 48 inches deep centered on the urinal, and a flush control height of 44 inches or less above the finished floor. Standards §§ 4.1.3(11), 4.22.5, 4.18.2, 4.18.3, 4.18.4.
(2)Women's
(a)The door is inaccessible because the pressure required to open the door is 18 pounds. Provide a door that requires no more than 5 pounds of force to open. Standards §§ 4.1.3(7)(b), 4.13.11(2)(b).
(1)There is no accessible toilet stall provided. Provide a "standard" accessible toilet stall at least 60 inches wide and at least 59 inches deep (or at least 56 inches deep with a wall-mounted toilet) such that all of the stall's elements, including stall door, stall door hardware, water closet, size and arrangement, toe clearances, grab bars, controls, and dispensers, comply with the Standards. Standards §§ 4.1.3(11), 4.22.4, 4.22.7, 4.13, 4.16, 4.17, 4.26, 4.27, Fig. 30.
(1)The roll-in shower is inaccessible because the controls are not on the back wall, and the fixed shower head is higher than 48 inches. Provide a shower in this room that is exactly 36 inches wide and 36 inches deep with a 48 inch long and 36 inch wide clear floor space alongside the shower opening, and an L-shaped shower seat mounted on the wall opposite the controls and extending the full depth of the stall; OR a shower that is at least 30 inches deep and 60 inches wide with no curb or threshold and with a 36 inch deep and 60 inch wide clear floor space at the shower opening. Ensure that the shower has grab bars, controls, a shower spray unit, and a seat, curb, and enclosure, if provided, that comply fully with the Standards and with Figs. 35, 36, and 37, as applicable. Standards §§ 4.1.3(11), 4.21, Figs. 35, 36, 37.
(1)The stairs are inaccessible because they have open risers. Provide stairs with closed risers, uniform tread width and riser height, a tread depth of at least 11 inches measured from riser to riser, and nosings, treads, and risers that otherwise comply fully with the Standards. Standards §§ 4.1.3(4), 4.9.
(2)The route under the stairs is inaccessible because there are less than 80 inches of head room provided. Provide an accessible route at this location with a minimum of 80 inches of clear head room throughout. If the vertical clearance is reduced to less than 80 inches at any point, provide a barrier. Standards §§ 4.1.3(2), 4.4.2, Fig. 8(c-1).
(1)The shower in the men's and women's units are inaccessible because the stalls are 48 inches wide by 48 inches deep; there are only fixed shower heads, no hand held units or no lower fixed shower heads. Provide showers in these rooms that are exactly 36 inches wide and 36 inches deep with a 48 inch long and 36 inch wide clear floor space alongside the shower opening, and an L-shaped shower seat mounted on the wall opposite the controls and extending the full depth of the stall; OR showers that are at least 30 inches deep and 60 inches wide with no curb or threshold and with a 36 inch deep and 60 inch wide clear floor space at the shower opening. Ensure that the shower has grab bars, controls, a shower spray unit, and a seat, curb, and enclosure, if provided, that comply fully with the Standards and with Figs. 35, 36, and 37, as applicable. Standards §§ 4.1.3(11), 4.21, Figs. 35, 36, 37.
(1)Women's
(a)No accessible mirror has been provided. Provide a mirror with the bottom edge of its reflecting surface no more than 40 inches above the finished floor. Standards §§ 4.1.3(11), 4.22.6, 4.19.6.
(b)The lavatory is inaccessible because the bottom of the apron is 28 inches above the finished floor. Provide a lavatory with the top of its rim or counter 34 inches or less above the finished floor; the bottom edge of the apron at least 29 inches above the finished floor; and knee and toe clearances that comply with Fig. 31. Standards §§ 4.1.3(11), 4.22.6, 4.19.2, Fig. 31.
(c)There is no accessible toilet stall provided. Provide a "standard" accessible toilet stall at least 60 inches wide and at least 59 inches deep (or at least 56 inches deep with a wall-mounted toilet) such that all of the stall's elements, including stall door, stall door hardware, water closet, size and arrangement, toe clearances, grab bars, controls, and dispensers, comply with the Standards. Standards §§ 4.1.3(11), 4.22.4, 4.22.7, 4.13, 4.16, 4.17, 4.26, 4.27, Fig. 30.
(2)Men's
(a)The lavatory is inaccessible because there is no knee or toe clearance. Provide a lavatory with the top of its rim or counter 34 inches or less above the finished floor; the bottom edge of the apron at least 29 inches above the finished floor; and knee and toe clearances that comply with Fig. 31. Standards §§ 4.1.3(11), 4.22.6, 4.19.2, Fig. 31.
(b)There is no accessible toilet stall provided. Provide a "standard" accessible toilet stall at least 60 inches wide and at least 59 inches deep (or at least 56 inches deep with a wall-mounted toilet) such that all of the stall's elements, including stall door, stall door hardware, water closet, size and arrangement, toe clearances, grab bars, controls, and dispensers, comply with the Standards. Standards §§ 4.1.3(11), 4.22.4, 4.22.7, 4.13, 4.16, 4.17, 4.26, 4.27, Fig. 30.
(1)The shower is inaccessible because it measures 48 inches by 48 inches, the seat does not extend the full depth of stall, the seat is not on the opposite wall from the controls, and there is no hand held shower spray unit. Provide a shower in this room that is exactly 36 inches wide and 36 inches deep with a 48 inch long and 36 inch wide clear floor space alongside the shower opening, and an L-shaped shower seat mounted on the wall opposite the controls and extending the full depth of the stall; OR a shower that is at least 30 inches deep and 60 inches wide with no curb or threshold and with a 36 inch deep and 60 inch wide clear floor space at the shower opening. Ensure that the shower has grab bars, controls, a shower spray unit, and a seat, curb, and enclosure, if provided, that comply fully with the Standards and with Figs. 35, 36, and 37, as applicable. Standards §§ 4.1.3(11), 4.21, Figs. 35, 36, 37.
(1)There is no toilet paper dispenser. Provide a toilet paper dispenser that is mounted within reach, with its top at least 1½ inches under the side grab bar, and centered at least 19 inches above the finished floor. Standards §§ 4.1.3(11), 4.22.4, 4.16.6, Fig. 29(b).
(1)The toilet room sign is mounted on the door. Provide a toilet room sign with raised and Braille characters mounted on the wall adjacent to the latch side of the door with the centerline of the sign 60 inches above the finished floor and situated such that a person can approach within 3 inches of the sign without encountering an obstruction or standing within a door swing. Standards §§ 4.1.2(7)(d), 4.30.1, 4.30.4, 4.30.5, 4.30.6.
(2)The door to the toilet room, which is accessed through a front approach and which has both a closer and a latch, is inaccessible because it has only 6 inches of clear floor space on the latch side, push side of the door. On the push side of the door, provide maneuvering clearance at least 48 inches deep and provide a minimum of 12 inches of maneuvering clearance on the latch side of the door, or remove the closer or the latch. Standards §§ 4.1.3(7)(b), 4.13.6, Fig. 25(a).
(3)There is no toilet paper dispenser. Provide a toilet paper dispenser that is mounted within reach, with its top at least 1½ inches under the side grab bar, and centered at least 19 inches above the finished floor. Standards §§ 4.1.3(11), 4.22.4, 4.16.6, Fig. 29(b).
(1)Within 24 months of the effective date of this Agreement, the County shall make the following modifications to Shower #1.
(a)The roll-in shower is inaccessible because the seat is not on the wall adjacent to the controls, the controls are not on the back wall, and the shower unit is not mounted on a vertical bar. Provide a shower in this room that is exactly 36 inches wide and 36 inches deep with a 48 inch long and 36 inch wide clear floor space alongside the shower opening, and an L-shaped shower seat mounted on the wall opposite the controls and extending the full depth of the stall; OR a shower that is at least 30 inches deep and 60 inches wide with no curb or threshold and with a 36 inch deep and 60 inch wide clear floor space at the shower opening. Ensure that the shower has grab bars, controls, a shower spray unit, and a seat, curb, and enclosure, if provided, that comply fully with the Standards and with Figs. 35, 36, and 37, as applicable. Standards §§ 4.1.3(11), 4.21, Figs. 35, 36, 37.
(2)Single User Toilet Rooms
(a)The toilet room signs are not accessible. Provide toilet room signs with raised and Braille characters mounted on the wall adjacent to the latch side of the door with the centerline of the sign 60 inches above the finished floor and situated such that a person can approach within 3 inches of the sign without encountering an obstruction or standing within a door swing. Standards §§ 4.1.2(7)(d), 4.30.1, 4.30.4, 4.30.5, 4.30.6.
(b)There is no toilet paper dispenser. Provide a toilet paper dispenser that is mounted within reach, with its top at least 1½ inches under the side grab bar, and centered at least 19 inches above the finished floor. Standards §§ 4.1.3(11), 4.22.4, 4.16.6, Fig. 29(b).
(c)The side grab bar at the toilet is inaccessible because it is 30 inches long. Provide a side grab bar that is at least 42 inches in overall length, with the far end mounted at least 54 inches from the rear wall and the closer end 12 inches or less from the rear wall. Standards §§ 4.1.3(11), 4.22.4, 4.16.4, Fig. 29(b).
(d)In one toilet room, the rear grab bar is 30 inches long, and the other toilet room has no rear grab bar. Provide a rear grab bar that is at least 36 inches in overall length, with the closer end no more than 6 inches from the side wall; mounted 33 to 36 inches above the finished floor; with a diameter between 1¼ and 1½ inches; with 1½ inches between the grab bar and the wall; and at least 1½ inches between the grab bar and any other object, such as a toilet seat cover dispenser. Standards §§ 4.1.3(11), 4.22.4, 4.16.4, 4.26.2, Fig. 29.
(1)The telephone is inaccessible because the highest operable part is 61 inches above the finished floor. Provide an accessible telephone with a clear floor space of at least 30 inches by 48 inches that allows either a forward or parallel approach by a person using a wheelchair such that bases, enclosures, and fixed seats do not impede approaches to the telephone; with the highest operable part of the telephone mounted no more than 48 inches above the floor for a front approach or no more than 54 inches above the floor for a side approach. Standards §§ 4.1.3(17), 4.31, 4.30.7(2).
(2)The telephone protrudes into the main walkway and would not be detectable to a blind person using a cane. Provide an accessible route at this location such that no objects with their bottom leading edges measuring between 27 inches and 80 inches above the finished floor protrude more than 4 inches into walks, halls, corridors, passageways, or aisles. Free-standing objects mounted on posts or pylons may overhang 12 inches maximum from 27 inches to 80 inches above the ground or finished floor. Standards §§ 4.1.2(3), 4.4.
(1)The telephone is inaccessible because it is not hearing aid compatible. Provide an accessible telephone with a clear floor space of at least 30 inches by 48 inches that allows either a forward or parallel approach by a person using a wheelchair; with the highest operable part of the telephone mounted no more than 48 inches above the floor for a front approach or no more than 54 inches above the floor for a side approach; and that is hearing aid compatible and has a volume control mechanism. Standards §§ 4.1.3(17), 4.31, 4.30.7(2).
(1)The door is inaccessible because the pressure required to open the door is 15 pounds. Provide a door that requires no more than 5 pounds of force to open. Standards §§ 4.1.3(7)(b), 4.13.11(2)(b).
(2)The wall-mounted trash can protrudes into the walkway and would not be detectable to a blind person using a cane. Provide a circulation path at this location such that no objects with their bottom leading edges measuring between 27 inches and 80 inches above the finished floor protrude more than 4 inches into walks, halls, corridors, passageways, or aisles. Free-standing objects mounted on posts or pylons may overhang 12 inches maximum from 27 inches to 80 inches above the ground or finished floor. Providing a cane-detectable barrier is an acceptable solution. Standards §§ 4.1.2(3), 4.4.
(1)The door is inaccessible because the pressure required to open the door is 17 pounds. Provide a door that requires no more than 5 pounds of force to open. Standards §§ 4.1.3(7)(b), 4.13.11(2)(b).
(2)The wall-mounted trash can protrudes into the walkway and would not be detectable to a blind person using a cane. Provide a circulation path at this location such that no objects with their bottom leading edges measuring between 27 inches and 80 inches above the finished floor protrude more than 4 inches into walks, halls, corridors, passageways, or aisles. Free-standing objects mounted on posts or pylons may overhang 12 inches maximum from 27 inches to 80 inches above the ground or finished floor. Providing a cane-detectable barrier is an acceptable solution. Standards §§ 4.1.2(3), 4.4.
(1)Although an accessible drinking fountain is provided, there is no drinking fountain provided for people who have difficulty bending or stooping. Provide a drinking fountain that is accessible to people who have difficulty bending or stooping. This can be accommodated by the use of a "hi-lo" fountain; by providing one fountain accessible to those who use wheelchairs and one fountain at a standard height convenient for those who have difficulty bending; by providing a fountain accessible to people who use wheelchairs and a cup dispenser, or by such other means as would achieve the required accessibility for each group of people. Standards § 4.1.3(10)(a).
(2)The wall-mounted drinking fountain is inaccessible because there is no clear floor space around the fountain. Provide a drinking fountain with clear knee space between the bottom of the apron and the finished floor or ground of at least 27 inches high, 30 inches wide, and 17 to 19 inches deep; and a minimum clear floor space of 30 inches by 48 inches to allow a person in a wheelchair to approach the unit facing forward. Standards §§ 4.1.3(10), 4.15.5(1), Figs. 27(a), (b).
(1)Although an accessible drinking fountain is provided, there is no drinking fountain provided for people who have difficulty bending or stooping. Provide a drinking fountain that is accessible to people who have difficulty bending or stooping. This can be accommodated by the use of a "hi-lo" fountain; by providing one fountain accessible to those who use wheelchairs and one fountain at a standard height convenient for those who have difficulty bending; by providing a fountain accessible to people who use wheelchairs and a cup dispenser, or by such other means as would achieve the required accessibility for each group of people. Standards § 4.1.3(10)(a).
(2)The wall mounted drinking fountaine protrudes into the walkway and would not be detectable to a blind person using a cane. Provide a circulation path at this location such that no objects with their bottom leading edges measuring between 27 inches and 80 inches above the finished floor protrude more than 4 inches into walks, halls, corridors, passageways, or aisles. Free-standing objects mounted on posts or pylons may overhang 12 inches maximum from 27 inches to 80 inches above the ground or finished floor. Providing a cane-detectable barrier is an acceptable solution. Standards §§ 4.1.2(3), 4.4.
(1)Although an audible alarm is provided in this facility, there is no visual alarm appliance in the toilet room. Provide a visual alarm appliance in the toilet room. Standards §§ 4.1.3(14), 4.28.1, 4.28.3.
(2)Shower stall
(a)The shower is inaccessible because the seat does not extend the full depth of the stall. Provide an L-shaped shower seat mounted on the wall opposite the controls and extending the full depth of the stall. Standards §§ 4.1.3(11), 4.21.3, Figs. 35(a), 36.
(b)The shower is inaccessible because no shower spray unit is mounted on a sliding bar for adjustable heights. Provide a shower in this room that has a shower spray unit with a hose at least 60 inches long that can be used both as a fixed shower head and as a hand-held shower. In unmonitored facilities where vandalism is a consideration, a fixed shower head mounted at 48 inches above the shower floor may be used in lieu of a hand-held shower head. Standards §§ 4.1.3(11), 4.21.6, Fig. 37.
(1)Although an audible alarm is provided in this facility, there is no visual alarm appliance in the toilet room. Provide a visual alarm appliance in the toilet room. Standards §§ 4.1.3(14), 4.28.1, 4.28.3.
(2)There is no accessible shower provided. Within 24 months of the effective date of this Agreement, the County shall provide a shower in this room that is exactly 36 inches wide and 36 inches deep with a 48 inch long and 36 inch wide clear floor space alongside the shower opening, and an L-shaped shower seat mounted on the wall opposite the controls and extending the full depth of the stall; OR a shower that is at least 30 inches deep and 60 inches wide with no curb or threshold and with a 36 inch deep and 60 inch wide clear floor space at the shower opening. Ensure that the shower has grab bars, controls, a shower spray unit, and a seat, curb, and enclosure, if provided, that comply fully with the Standards and with Figs. 35, 36, and 37, as applicable. Standards §§ 4.1.3(11), 4.21, Figs. 35, 36, 37.
(1)The door is inaccessible because the pressure required to open the door is 15 pounds. Provide a door that requires no more than 5 pounds of force to open. Standards §§ 4.1.3(7)(b), 4.13.11(2)(b).
(2)The lavatory is inaccessible because the hot water pipes are not insulated or otherwise configured to protect against contact. Provide hot water and drain pipes that are insulated or otherwise configured to protect against contact. Standards §§ 4.1.3(11), 4.22.6, 4.19.4.
(3)The shower is inaccessible because the stall is 40 inches deep by 42 inches wide. Provide a shower in this room that is exactly 36 inches wide and 36 inches deep with a 48 inch long and 36 inch wide clear floor space alongside the shower opening, and an L-shaped shower seat mounted on the wall opposite the controls and extending the full depth of the stall; OR a shower that is at least 30 inches deep and 60 inches wide with no curb or threshold and with a 36 inch deep and 60 inch wide clear floor space at the shower opening. Ensure that the shower has grab bars, controls, a shower spray unit, and a seat, curb, and enclosure, if provided, that comply fully with the Standards and with Figs. 35, 36, and 37, as applicable. Standards §§ 4.1.3(11), 4.21, Figs. 35, 36, 37.
(1)The door is inaccessible because the pressure required to open the door is 15 pounds. Provide a door that requires no more than 5 pounds of force to open. Standards §§ 4.1.3(7)(b), 4.13.11(2)(b).
(2)The lavatory is inaccessible because the hot water pipes are not insulated or otherwise configured to protect against contact. Provide hot water and drain pipes that are insulated or otherwise configured to protect against contact. Standards §§ 4.1.3(11), 4.22.6, 4.19.4.
(3)The toilet paper dispenser is inaccessible because it is mounted more than 36 inches from the rear wall. Provide a toilet paper dispenser that is mounted with its top at least 1½ inches under the side grab bar and 36 inches or less from the rear wall and is centered at least 19 inches above the finished floor. Standards §§ 4.1.3(11), 4.22.4, 4.17.3, Fig. 30(d).
(4)The shower is inaccessible because the stall dimensions are 108 inches deep by 45 inches wide. Provide a shower in this room that is exactly 36 inches wide and 36 inches deep with a 48 inch long and 36 inch wide clear floor space alongside the shower opening, and an L-shaped shower seat mounted on the wall opposite the controls and extending the full depth of the stall; OR a shower that is at least 30 inches deep and 60 inches wide with no curb or threshold and with a 36 inch deep and 60 inch wide clear floor space at the shower opening. Ensure that the shower has grab bars, controls, a shower spray unit, and a seat, curb, and enclosure, if provided, that comply fully with the Standards and with Figs. 35, 36, and 37, as applicable. Standards §§ 4.1.3(11), 4.21, Figs. 35, 36, 37.
(1)The door is inaccessible because the pressure required to open the door is 14 pounds. Provide a door that requires no more than 5 pounds of force to open. Standards §§ 4.1.3(7)(b), 4.13.11(2)(b).
(2)The lavatory is inaccessible because the hot water pipes are not insulated or otherwise configured to protect against contact. Provide hot water and drain pipes that are insulated or otherwise configured to protect against contact. Standards §§ 4.1.3(11), 4.22.6, 4.19.4.
(1)The door is inaccessible because the pressure required to open the door is 17 pounds. Provide a door that requires no more than 5 pounds of force to open. Standards §§ 4.1.3(7)(b), 4.13.11(2)(b).
(2)The lavatory is inaccessible because the hot water pipes are not insulated or otherwise configured to protect against contact. Provide hot water and drain pipes that are insulated or otherwise configured to protect against contact. Standards §§ 4.1.3(11), 4.22.6, 4.19.4.
(1)The bench is 12 inches wide. Provide a 24 inch by 48 inch bench fixed to the wall along the bench's longer dimension. Ensure that the bench has sufficient structural strength and is mounted with its surface between 17 inches and 19 inches above the finished floor. Provide clear floor space alongside the bench to allow a person using a wheelchair to make a parallel transfer onto the bench. Standards §§ 4.1.3(21), 4.35.4, 4.26.3.
(2)No accessible coat hook has been provided. Provide a coat hook at a maximum height above the finished floor of 48 inches for a forward approach or 54 inches for a side approach and that is accompanied by clear floor space of 30 by 48 inches that allows a forward or parallel approach by a person using a wheelchair. Standards §§ 4.1.3(12)(a), 4.25.2, 4.25.3, 4.2.4, 4.2.5, 4.2.6.
(1)The bench is 12 inches wide. Provide a 24 inch by 48 inch bench fixed to the wall along the bench's longer dimension. Ensure that the bench has sufficient structural strength and is mounted with its surface between 17 inches and 19 inches above the finished floor. Provide clear floor space alongside the bench to allow a person using a wheelchair to make a parallel transfer onto the bench. Standards §§ 4.1.3(21), 4.35.4, 4.26.3.
(2)No accessible coat hook has been provided. Provide a coat hook at a maximum height above the finished floor of 48 inches for a forward approach or 54 inches for a side approach and that is accompanied by clear floor space of 30 by 48 inches that allows a forward or parallel approach by a person using a wheelchair. Standards §§ 4.1.3(12)(a), 4.25.2, 4.25.3, 4.2.4, 4.2.5, 4.2.6.
(1)The toilet room sign is not mounted on the latch side of the door. Provide a toilet room sign with raised and Braille characters mounted on the wall adjacent to the latch side of the door with the centerline of the sign 60 inches above the finished floor and situated such that a person can approach within 3 inches of the sign without encountering an obstruction or standing within a door swing. Standards §§ 4.1.2(7)(d), 4.30.1, 4.30.4, 4.30.5, 4.30.6.
(2)The toilet is inaccessible because there is insufficient clear floor space. Provide clear floor space that complies with Fig. 30 at the toilet. Standards §§ 4.1.3(11), 4.22.4, 4.17.3, Fig. 30.
(3)The side grab bar at the toilet is inaccessible because the toilet paper dispenser interferes with its use. Provide a side grab bar that has at least 1½ inches between the grab bar and any other object. Standards §§ 4.1.3(11), 4.22.4, 4.17.6, 4.26.2, Fig. 39.
(1)The toilet room sign is not mounted on the latch side of the door. Provide a toilet room sign with raised and Braille characters mounted on the wall adjacent to the latch side of the door with the centerline of the sign 60 inches above the finished floor and situated such that a person can approach within 3 inches of the sign without encountering an obstruction or standing within a door swing. Standards §§ 4.1.2(7)(d), 4.30.1, 4.30.4, 4.30.5, 4.30.6.
(2)The toilet is inaccessible because there is insufficient clear floor space. Provide clear floor space that complies with Fig. 30 at the toilet. Standards §§ 4.1.3(11), 4.22.4, 4.17.3, Fig. 30.
(3)The side grab bar at the toilet is inaccessible because the toilet paper dispenser interferes with its use. Provide a side grab bar that has at least 1½ inches between the grab bar and any other object. Standards §§ 4.1.3(11), 4.22.4, 4.17.6, 4.26.2, Fig. 39.
(1)The toilet room sign does not have Braille. Provide a toilet room sign with raised and Braille characters mounted on the wall adjacent to the latch side of the door with the centerline of the sign 60 inches above the finished floor and situated such that a person can approach within 3 inches of the sign without encountering an obstruction or standing within a door swing. Standards §§ 4.1.2(7)(d), 4.30.1, 4.30.4, 4.30.5, 4.30.6.
(2)The toilet is inaccessible because there is insufficient clear floor space. Provide clear floor space that complies with Fig. 30 at the toilet. Standards §§ 4.1.3(11), 4.22.4, 4.17.3, Fig. 30.
(3)The side grab bar at the toilet is inaccessible because the toilet paper dispenser interferes with its use. Provide a side grab bar that has at least 1½ inches between the grab bar and any other object. Standards §§ 4.1.3(11), 4.22.4, 4.17.6, 4.26.2, Fig. 39.
(1)The toilet room sign does not have Braille. Provide a toilet room sign with raised and Braille characters mounted on the wall adjacent to the latch side of the door with the centerline of the sign 60 inches above the finished floor and situated such that a person can approach within 3 inches of the sign without encountering an obstruction or standing within a door swing. Standards §§ 4.1.2(7)(d), 4.30.1, 4.30.4, 4.30.5, 4.30.6.
(2)The toilet is inaccessible because there is insufficient clear floor space. Provide clear floor space that complies with Fig. 30 at the toilet. Standards §§ 4.1.3(11), 4.22.4, 4.17.3, Fig. 30.
(3)The side grab bar at the toilet is inaccessible because the toilet paper dispenser interferes with its use. Provide a side grab bar that has at least 1½ inches between the grab bar and any other object. Standards §§ 4.1.3(11), 4.22.4, 4.17.6, 4.26.2, Fig. 39.
(1)The door is inaccessible because the pressure required to open the door is 12 pounds. Provide a door that requires no more than 5 pounds of force to open. Standards §§ 4.1.3(7)(b), 4.13.11(2)(b).
(2)Although an audible alarm is provided in this facility, there is no visual alarm appliance in the toilet room. Provide a visual alarm appliance in the toilet room. Standards §§ 4.1.3(14), 4.28.1, 4.28.3.
(1)The door is inaccessible because the pressure required to open the door is 11 pounds. Provide a door that requires no more than 5 pounds of force to open. Standards §§ 4.1.3(7)(b), 4.13.11(2)(b).
(2)Although an audible alarm is provided in this facility, there is no visual alarm appliance in the toilet room. Provide a visual alarm appliance in the toilet room. Standards §§ 4.1.3(14), 4.28.1, 4.28.3.
(1)No accessible mirror has been provided. Provide a mirror with the bottom edge of its reflecting surface no more than 40 inches above the finished floor. Standards §§ 4.1.3(11), 4.22.6, 4.19.6.
(2)The shower is inaccessible because there is a 1 inch curb at the entrance to the shower. Within 24 months of the effective date of this Agreement, the County shall provide, for shower stalls that are exactly 36 inches wide and 36 inches deep, a curb at the shower entrance that is no higher than ½ inch. For shower stalls that are at least 30 inches deep and 60 inches wide, ensure that there is no curb or threshold at the shower entrance. Standards §§ 4.1.3(11), 4.21.7.
(1)The toilet room sign is not mounted on the latch side of the door 60 inches above the finished floor, and the Braille sign is mounted 114 inches high. Provide a toilet room sign with raised and Braille characters mounted on the wall adjacent to the latch side of the door with the centerline of the sign 60 inches above the finished floor and situated such that a person can approach within 3 inches of the sign without encountering an obstruction or standing within a door swing. Standards §§ 4.1.2(7)(d), 4.30.1, 4.30.4, 4.30.5, 4.30.6.
(2)The toilet is inaccessible because the flush control is on the closed side. Provide a flush control mounted on the "open" side of the toilet's clear floor space; 44 inches or less above the finished floor; and requiring a maximum of 5 pounds of force to operate; or provide an automatic flush device. Standards §§ 4.1.3(11), 4.22.4, 4.16.5, 4.17.2, 4.27.4.
(3)The toilet paper dispenser is inaccessible because it is mounted above the grab bar. Provide a toilet paper dispenser that is mounted with its top at least 1½ inches under the side grab bar and 36 inches or less from the rear wall and is centered at least 19 inches above the finished floor. Standards §§ 4.1.3(11), 4.22.4, 4.17.3, Fig. 30(d).
(1)The toilet room sign is not mounted on the latch side of the door 60 inches above the finished floor, and the Braille sign is mounted 114 inches high. Provide a toilet room sign with raised and Braille characters mounted on the wall adjacent to the latch side of the door with the centerline of the sign 60 inches above the finished floor and situated such that a person can approach within 3 inches of the sign without encountering an obstruction or standing within a door swing. Standards §§ 4.1.2(7)(d), 4.30.1, 4.30.4, 4.30.5, 4.30.6.
(2)The toilet is inaccessible because the flush control is on the closed side. Provide a flush control mounted on the "open" side of the toilet's clear floor space; 44 inches or less above the finished floor; and requiring a maximum of 5 pounds of force to operate; or provide an automatic flush device. Standards §§ 4.1.3(11), 4.22.4, 4.16.5, 4.17.2, 4.27.4.
(3)The toilet paper dispenser is inaccessible because it is mounted above the grab bar. Provide a toilet paper dispenser that is mounted with its top at least 1½ inches under the side grab bar and 36 inches or less from the rear wall and is centered at least 19 inches above the finished floor. Standards §§ 4.1.3(11), 4.22.4, 4.17.3, Fig. 30(d).