Attachment I: Modifications to Newly Constructed Facilities

                       

 

Newly Constructed Facilities:  In order to ensure that the following spaces and elements in County facilities, for which construction was commenced after January 26, 1992, are readily accessible to and usable by persons with disabilities, the County will take the following actions within two years of the effective date of this Agreement:

                       

 

JUSTICE CENTER

 

 130 Homestead Avenue, Hillsboro, Ohio - construction completed in 2003

 

1.         PARKING

 

a.         The designated accessible parking spots do not have signage identifying them as accessible.  Provide all spaces designated as reserved for people with disabilities with vertical signs having the International Symbol of Accessibility located such that they cannot be obstructed by parked vehicles.  Van accessible spaces shall have an additional "Van-Accessible" sign located below the International Symbol of Accessibility.  Standards §§ 4.1.2(5), 4.6, 4.30.7(1).

 

2.         ENTRANCE

 

a.         There is no sign to designate the accessible entrance.  Provide accessible, directional signage with the International Symbol of Accessibility at inaccessible entrances directing users to the accessible entrance, and provide accessible signage with the International Symbol of Accessibility at all permanent accessible entrances.  Standards §§ 4.1.3(8)(d), 4.1.3(16)(b), 4.13, 4.30.

 

3.         MEN'S TOILET ROOM - SHERIFF'S OFFICE AREA

 

a.         The toilet room sign is on the door.  Provide a toilet room sign with the International Symbol of Accessibility and raised and Braille characters.  The sign shall be mounted on the wall adjacent to the latch side of the door with the centerline of the sign at 60 inches above the finished floor and situated such that a person can approach within 3 inches of the sign without encountering an obstruction or standing within a door swing.  Standards §§ 4.1.2(7)(d), 4.30.1, 4.30.4, 4.30.5, 4.30.6, 4.30.7.

 

b.         The lavatory is inaccessible because the hot water pipes are not insulated or otherwise configured to protect against contact.  Provide hot water and drain pipes that are insulated or otherwise configured to protect against contact.  Standards §§ 4.1.3(11), 4.22.6, 4.19.4.

 

4.         WOMEN'S TOILET ROOM - SHERIFF'S OFFICE AREA

 

a.         The toilet room sign is on the door.  Provide a toilet room sign with the International Symbol of Accessibility and raised and Braille characters.  The sign shall be mounted on the wall adjacent to the latch side of the door with the centerline of the sign at 60 inches above the finished floor and situated such that a person can approach within 3 inches of the sign without encountering an obstruction or standing within a door swing.  Standards §§ 4.1.2(7)(d), 4.30.1, 4.30.4, 4.30.5, 4.30.6, 4.30.7.

 

b.         The lavatory is inaccessible because the hot water pipes are not insulated or otherwise configured to protect against contact.  Provide hot water and drain pipes that are insulated or otherwise configured to protect against contact.  Standards §§ 4.1.3(11), 4.22.6, 4.19.4.

 

5.         UNISEX EMPLOYEE TOILET ROOM - 9-1-1 CENTER AREA

 

a.         The lavatory is inaccessible because the hot water pipes are not insulated or otherwise configured to protect against contact.  Provide hot water and drain pipes that are insulated or otherwise configured to protect against contact.  Standards §§ 4.1.3(11), 4.22.6, 4.19.4.

 

b.         No accessible coat hook has been provided.  Provide a coat hook at a maximum height above the finished floor of 48 inches for a forward approach or 54 inches for a side approach and that is accompanied by clear floor space of 30 by 48 inches that allows a forward or parallel approach by a person using a wheelchair.  Standards §§ 4.1.3(12)(a), 4.25.2, 4.25.3, 4.2.4, 4.2.5, 4.2.6.

 

6.         MEN'S TOILET ROOM - MUNICIPAL SECTION AREA

 

a.         The toilet room sign is on the door.  Provide a toilet room sign with the International Symbol of Accessibility and raised and Braille characters.  The sign shall be mounted on the wall adjacent to the latch side of the door with the centerline of the sign at 60 inches above the finished floor and situated such that a person can approach within 3 inches of the sign without encountering an obstruction or standing within a door swing.  Standards §§ 4.1.2(7)(d), 4.30.1, 4.30.4, 4.30.5, 4.30.6, 4.30.7.

 

b.         The lavatory is inaccessible because the hot water pipes are not insulated or otherwise configured to protect against contact.  Provide hot water and drain pipes that are insulated or otherwise configured to protect against contact.  Standards §§ 4.1.3(11), 4.22.6, 4.19.4.

 

c.         No accessible mirror has been provided.  Provide a mirror with the bottom edge of its reflecting surface no more than 40 inches above the finished floor.  Standards §§ 4.1.3(11), 4.22.6, 4.19.6.

 

7.         WOMEN'S TOILET ROOM - MUNICIPAL SECTION AREA

 

a.         The toilet room sign is on the door.  Provide a toilet room sign with the International Symbol of Accessibility and raised and Braille characters.  The sign shall be mounted on the wall adjacent to the latch side of the door with the centerline of the sign at 60 inches above the finished floor and situated such that a person can approach within 3 inches of the sign without encountering an obstruction or standing within a door swing.  Standards §§ 4.1.2(7)(d), 4.30.1, 4.30.4, 4.30.5, 4.30.6, 4.30.7.

 

b.         The lavatory is inaccessible because the hot water pipes are not insulated or otherwise configured to protect against contact.  Provide hot water and drain pipes that are insulated or otherwise configured to protect against contact.  Standards §§ 4.1.3(11), 4.22.6, 4.19.4.

 

8.         COURT ROOM

 

a.         The entrance to the witness stand is inaccessible because it is only 29 ½ inches wide.  Provide an accessible route to the witness stand with a minimum clear width of 36 inches.  Standards §§ 4.1.3(1), 4.3.3.

 

9.         UNISEX TOILET ROOM - EMPLOYEE ADMINISTRATIVE AREA

 

a.         The lavatory is inaccessible because the hot water pipes are not insulated or otherwise configured to protect against contact.  Provide hot water and drain pipes that are insulated or otherwise configured to protect against contact.  Standards §§ 4.1.3(11), 4.22.6, 4.19.4.

 

10.       INTAKE/RELEASE AREA - DETOX CELL

 

a.         The lavatory is inaccessible because the hot water pipes are not insulated or otherwise configured to protect against contact.  Provide hot water and drain pipes that are insulated or otherwise configured to protect against contact.  Standards §§ 4.1.3(11), 4.22.6, 4.19.4.

 

b.         There is no rear grab bar.  Provide a rear grab bar that is at least 36 inches in overall length, with the closer end no more than 6 inches from the side wall; mounted 33 to 36 inches above the finished floor; with a diameter between 1¼ and 1½ inches; with 1½ inches between the grab bar and the wall; and at least 1½ inches between the grab bar and any other object, such as a toilet seat cover dispenser.  Standards §§ 4.1.3(11), 4.22.4, 4.16.4, 4.26.2, Fig. 29.

 

c.         There is no side grab bar.  Provide a side grab bar that is at least 42 inches in overall length, with the far end mounted at least 54 inches from the rear wall and the closer end 12 inches or less from the rear wall; mounted 33 to 36 inches above the finished floor; with a diameter between 1¼ and 1½ inches; with 1½ inches between the grab bar and the wall; and at least 1½ inches between the grab bar and any other object, such as the toilet paper dispenser.  Standards §§ 4.1.3(11), 4.22.4, 4.16.4, 4.26.2, Fig. 29.

 

11.       INTAKE/RELEASE AREA - "CHARGE-A-CALL" TELEPHONE

 

a.         The highest operating part of the telephone is more than 54 above the finished floor.  Provide an accessible telephone with a clear floor space of at least 30 inches by 48 inches that allows either a forward or parallel approach by a person using a wheelchair such that bases, enclosures, and fixed seats do not impede approaches to the telephone; with the highest operable part of the telephone mounted no more than 48 inches above the floor for a front approach or no more than 54 inches above the floor for a side approach; that are hearing aid compatible and have a volume control mechanism; with telephone books, if provided, located between 15 and 48 inches above the finished floor for a front approach or between 9 and 54 inches above the finished floor for a side approach; and with a cord of at least 29 inches long from the telephone to the handset.  Standards §§ 4.1.3(17), 4.31.

 

b.         Although there is a telephone provided, a TTY is not provided.  Provide at least one accessible public TTY with appropriate signage.  Standards §§ 4.1.3(17)(c)(i), 4.30.7(3), 4.31.9.

 

12.       INTAKE/RELEASE AREA - INMATE SHOWER/DRESS-OUT

 

a.         The lavatory is inaccessible because the hot water pipes are not insulated or otherwise configured to protect against contact.  Provide hot water and drain pipes that are insulated or otherwise configured to protect against contact.  Standards §§ 4.1.3(11), 4.22.6, 4.19.4.

 

13.       INTAKE/RELEASE AREA -  INMATE DRESS-OUT TOILET ROOM

 

a.         The toilet room sign is not accessible.  Provide a toilet room sign with the International Symbol of Accessibility and raised and Braille characters.  The sign shall be mounted on the wall adjacent to the latch side of the door with the centerline of the sign at 60 inches above the finished floor and situated such that a person can approach within 3 inches of the sign without encountering an obstruction or standing within a door swing.  Standards §§ 4.1.2(7)(d), 4.30.1, 4.30.4, 4.30.5, 4.30.6, 4.30.7.

 

b.         The lavatory is inaccessible because the hot water pipes are not insulated or otherwise configured to protect against contact.  Provide hot water and drain pipes that are insulated or otherwise configured to protect against contact.  Standards §§ 4.1.3(11), 4.22.6, 4.19.4.

 

c.         The paper towels are inaccessible because the controls are mounted at 56 inches above the finished floor.  Provide a paper towel dispenser with the controls a maximum height above the finished floor of 48 inches for a forward approach or 54 inches for a side approach and that is accompanied by clear floor space of 30 by 48 inches that allows a forward or parallel approach by a person using a wheelchair.  Standards §§ 4.1.3(13), 4.27.2, 4.27.3, 4.2.4, 4.2.5, 4.2.6, Fig. 4.

 

d.         The rear grab bar at the toilet is inaccessible because its overall length is 30 inches.  Provide a rear grab bar that is  as close as possible to 36 inches in overall length, with the closer end no more than 6 inches from the side wall; mounted 33 to 36 inches above the finished floor; with a diameter between 1¼ and 1½ inches; with 1½ inches between the grab bar and the wall; and at least 1½ inches between the grab bar and any other object, such as a toilet seat cover dispenser.  Standards §§ 4.1.3(11), 4.22.4, 4.16.4, 4.26.2, Fig. 29.

 

14.       CELL # 1

 

a.         No accessible mirror has been provided.  Provide a mirror with the bottom edge of its reflecting surface no more than 40 inches above the finished floor.  Standards §§ 4.1.3(11), 4.22.6, 4.19.6.

 

b.         There is no side grab bar.  Provide a side grab bar that is at least 40 inches in overall length, with the far end mounted at least 54 inches from the rear wall and the closer end 12 inches or less from the rear wall; mounted 33 to 36 inches above the finished floor; with a diameter between 1¼ and 1½ inches; with 1½ inches between the grab bar and the wall; and at least 1½ inches between the grab bar and any other object, such as the toilet paper dispenser.  Standards §§ 4.1.3(11), 4.22.4, 4.17.6, 4.26.2, Fig. 30.

 

c.         There is no rear grab bar.  Provide a rear grab bar that is at least 36 inches in overall length, with the closer end no more than 6 inches from the side wall; mounted 33 to 36 inches above the finished floor; with a diameter between 1¼ and 1½ inches; with 1½ inches between the grab bar and the wall; and at least 1½ inches between the grab bar and any other object, such as a toilet seat cover dispenser.  Standards §§ 4.1.3(11), 4.22.4, 4.17.6, 4.26.2, Fig. 30.

 

d.         The toilet is inaccessible because the top of the seat is 20 inches above the finished floor.  Provide a toilet with a seat that measures 17 to 19 inches above the finished floor.  Standards §§ 4.1.3(11), 4.22.4, 4.16.3, 4.17.2, Fig. 30(d).

 

e.         There is no shower seat.  Provide a shower in this room that is exactly 36 inches wide and 36 inches deep with a 48 inch long and 36 inch wide clear floor space alongside the shower opening, and an L-shaped shower seat mounted on the wall opposite the controls and extending the full depth of the stall; OR a shower that is at least 30 inches deep and 60 inches wide with no curb or threshold and with a 36 inch deep and 60 inch wide clear floor space at the shower opening.  Ensure that the shower has grab bars, controls, a shower spray unit, and a seat, curb, and enclosure, if provided, that comply fully with the Standards and with Figs. 35, 36, and 37, as applicable.  Standards §§ 4.1.3(11), 4.21, Figs. 35, 36, 37.

 

15.       AFTER HOURS/VISITATION - PUBLIC AREA

 

a.         The service counter is 43 ½ inches high.  Provide a counter on an accessible route such that a portion of the counter is at least 36 inches wide and no more than 36 inches above the finished floor, or provide an auxiliary counter with a maximum height of 36 inches in close proximity to the main counter, or provide equivalent facilitation.   Equivalent facilitation may be provided in the form of a folding shelf attached to the main counter, an auxiliary table nearby, a clip board made available to the public, or other means.  Standards §§ 4.1.1(2), 7.2(2), 4.1.3(1), 4.3.

 

16.       PUBLIC PAY TELEPHONE - PUBLIC AREA

 

a.         The coin slot is 59 inches above the finished floor and the telephone is inset 11 ½ inches into the wall.  Provide an accessible telephone with a clear floor space of at least 30 inches by 48 inches that allows either a forward or parallel approach by a person using a wheelchair such that bases, enclosures, and fixed seats do not impede approaches to the telephone; with the highest operable part of the telephone mounted no more than 46 inches above the floor for a front approach or no more than 52 inches above the floor for a side approach; that are hearing aid compatible and have a volume control mechanism; with telephone books, if provided, located between 15 and 48 inches above the finished floor for a front approach or between 9 and 54 inches above the finished floor for a side approach; and with a cord of at least 29 inches long from the telephone to the handset.  Standards §§ 4.1.3(17), 4.31.

 

17.       MEN'S PUBLIC AREA TOILET ROOM

 

a.         The toilet room sign is on the door.  Provide a toilet room sign with the International Symbol of Accessibility and raised and Braille characters.  The sign shall be mounted on the wall adjacent to the latch side of the door with the centerline of the sign at 60 inches above the finished floor and situated such that a person can approach within 3 inches of the sign without encountering an obstruction or standing within a door swing.  Standards §§ 4.1.2(7)(d), 4.30.1, 4.30.4, 4.30.5, 4.30.6, 4.30.7.

 

b.         The lavatory is inaccessible because the hot water pipes are not insulated or otherwise configured to protect against contact.  Provide hot water and drain pipes that are insulated or otherwise configured to protect against contact.  Standards §§ 4.1.3(11), 4.22.6, 4.19.4.

 

18.       WOMEN'S PUBLIC AREA TOILET ROOM

 

a.         The toilet room sign is on the door.  Provide a toilet room sign with the International Symbol of Accessibility and raised and Braille characters.  The sign shall be mounted on the wall adjacent to the latch side of the door with the centerline of the sign at 60 inches above the finished floor and situated such that a person can approach within 3 inches of the sign without encountering an obstruction or standing within a door swing.  Standards §§ 4.1.2(7)(d), 4.30.1, 4.30.4, 4.30.5, 4.30.6, 4.30.7.

 

b.         The lavatory is inaccessible because the hot water pipes are not insulated or otherwise configured to protect against contact.  Provide hot water and drain pipes that are insulated or otherwise configured to protect against contact.  Standards §§ 4.1.3(11), 4.22.6, 4.19.4.