ATTACHMENT J: Modifications to Altered Facilities Please Note: Paragraph of the Settlement Agreement requires that within three months of the effective date of this Agreement, the County provide signage as necessary to comply with 28 C.F.R. § 35.163(b), after having surveyed all facilities that are the subject of this Agreement for the purpose of identifying those that have multiple entrances not all of which are accessible. The chart below lists the facilities surveyed by the Department, the access issues identified during the survey, and the actions required to correct the access issues. Required actions are listed using an alphanumeric code. The key to the alphanumeric codes is provided in Attachment M to this Agreement. In order to ensure that the following spaces and elements in the County's facilities in which alterations occurred after January 26, 1992, are readily accessible to and usable by persons with disabilities, the County will take the actions referenced by the alphanumeric code and described in detail in Attachment M to this Settlement Agreement within the time period specified below, which time period will begin to run on the effective date of this Agreement. |
|||
Item # |
Access Issue |
Required Action |
Completion Date |
---|---|---|---|
1 |
Gregg County Courthouse (*Existing unless otherwise indicated) |
||
1.1 |
Accessible Route-Center Street/Sheriff's Entrance |
||
1.1.a |
The building does not have directional signage posted at inaccessible entrances and does not have the International Symbol of Accessibility posted at accessible entrances. |
D16 |
24 months |
1.2 |
Exterior Entrance-Fredonia Street |
||
1.2.a |
The pull side of the door, which is accessed through a front approach, is inaccessible because it has only 3 inches of clear space on the latch side. |
D6 |
24 months |
1.3 |
Ramp-Fredonia Street |
||
1.3.a |
The ramp is inaccessible because it has a slope of up to 9.5%. |
R5 |
24 months |
1.3.b |
The ramp is inaccessible because it does not have edge protection at the drop off sides. |
R1 |
24 months |
1.3.c |
The ramp is inaccessible because it lacks handrails. |
R4 |
24 months |
1.4 |
Elevator-East Annex (*Altered) |
||
1.4.a |
The elevator is inaccessible because the hall call buttons are centered at 50.5 inches above the finished floor. |
E3 |
24 months |
1.4.b |
The elevator is inaccessible because the hall lanterns do not emit an audible or visual signal indicating when a car is answering a call. |
E11 |
24 months |
1.4.c |
The elevator is inaccessible because the time from notification that a car is answering a call until the doors of that car start to close is less than 5 seconds, and the doors do not re-open automatically if obstructed. |
E6 |
24 months |
1.4.d |
The elevator is inaccessible because the car control buttons do not have raised and Braille characters. |
E4 |
24 months |
1.4.e |
The elevator is inaccessible because the emergency system requires voice communication to operate, and it requires tight grasping or pinching to access. |
E8 |
24 months |
1.5 |
Elevator-Courthouse (*Altered) |
||
1.5.a |
The elevator is inaccessible because the time from notification that a car is answering a call until the doors of that car start to close is less than 5 seconds. |
E6 |
24 months |
1.6 |
Elevator-West Annex |
||
1.6.a |
The elevator is inaccessible because the emergency system requires voice communication to operate, it requires tight grasping or pinching to access, and it is not identified by raised symbol and lettering. |
E8 |
24 months |
1.7 |
Women's Single-User Toilet Room; 1st Floor Courthouse |
||
1.7.a |
The door is inaccessible because it requires 9 pounds of force to open. |
D2 |
24 months |
1.7.b |
The light switch is inaccessible because it is mounted 55 inches above the finished floor. |
TR5 |
24 months |
1.7.c |
Although an audible alarm is provided in this facility, there is no visual alarm appliance in the toilet room. |
TR21 |
24 months |
1.7.d |
The paper towel dispenser is inaccessible because it is mounted with the controls 52 inches above the finished floor. |
TR5 |
24 months |
1.8 |
Men's Toilet Room with Stalls; 1st Floor East Annex (*Altered) |
||
1.8.a |
The door is inaccessible because it requires 10 pounds of force to open. |
D2 |
24 months |
1.8.b |
Although an audible alarm is provided in this facility, there is no visual alarm appliance in the toilet room. |
TR21 |
24 months |
1.8.c |
The stall door is inaccessible because there is no hardware on the pull side. |
D1 |
24 months |
1.8.d |
The shelf protrudes into the walkway and is not detectable to blind persons using a cane. |
AR8 |
24 months |
1.9 |
Concession ("Ruthie's"); 1st Floor West Annex |
||
1.9.a |
The counter is inaccessible because it is 44 inches above the finished floor. |
C6 |
24 months |
1.1 |
Voter Registration; 1st Floor |
||
1.10.a |
The door is inaccessible because it requires 9 pounds of force to open. |
D2 |
24 months |
1.10.b |
The counter is inaccessible because it is 43.75 inches above the finished floor. |
C6 |
24 months |
1.11 |
Human Resources Department; 1st Floor |
||
1.11.a |
The door is inaccessible because it requires 13 pounds of force to open. |
D2 |
24 months |
1.11.b |
The counter is inaccessible because it is 47.5 inches above the finished floor. |
C6 |
24 months |
1.12 |
Drinking Fountain; 2nd Floor West Annex |
||
1.12.a |
The drinking fountain is inaccessible because the flow of water is not within 3 inches of the front of the fountain. |
DF7 |
24 months |
1.12.b |
The drinking fountain is inaccessible because the controls require 10 pounds of force to operate. |
DF2 |
24 months |
1.13 |
Men's Toilet Room with Stalls; 2nd Floor West Annex |
||
1.13.a |
The door is inaccessible because it requires 7 pounds of force to open. |
D2 |
24 months |
1.13.b |
Although an audible alarm is provided in this facility, there is no visual alarm appliance in the toilet room. |
TR21 |
24 months |
1.13.c |
The light switch is inaccessible because it is mounted 56 inches above the finished floor. |
TR5 |
24 months |
1.13.d |
No accessible mirror has been provided. |
TR14 |
24 months |
1.13.e |
The stall door is inaccessible because there is no hardware on the pull side. |
D1 |
24 months |
1.13.f |
The grab bars at the designated accessible toilet are inaccessible because they are mounted 37 inches above the finished floor. |
ST12 |
24 months |
1.14 |
Women's Toilet Room with Stalls; 2nd Floor West Annex |
||
1.14.a |
The door is inaccessible because it requires 7 pounds of force to open. |
D2 |
24 months |
1.14.b |
The light switch is inaccessible because it is mounted 55 inches above the finished floor. |
TR5 |
24 months |
1.14.c |
The seat cover dispenser is inaccessible because it is mounted so that it requires a reach of 59 inches above the finished floor. |
TR5 |
24 months |
1.14.d |
The stall door is inaccessible because there is no hardware on the pull side. |
D1 |
24 months |
1.14.e |
The grab bars at the designated accessible toilet are inaccessible because they are mounted 37 inches above the finished floor. |
ST12 |
24 months |
1.15 |
Drinking Fountain; 2nd Floor East Annex Near Men's Toilet Room |
||
1.15.a |
The drinking fountain is inaccessible because the flow of water is 2.5 inches high. |
DF7 |
24 months |
1.15.b |
The wall-mounted drinking fountain is inaccessible because it provides only 26 inches of clear knee space height and 24 inches of clear knee space width. |
DF5 |
24 months |
1.16 |
Women's Toilet Room with Stalls; 2nd Floor East Annex |
||
1.16.a |
The door is inaccessible because it requires 10 pounds of force to open. |
D2 |
24 months |
1.16.b |
Although an audible alarm is provided in this facility, there is no visual alarm appliance in the toilet room. |
TR21 |
24 months |
1.16.c |
The sanitary napkin dispenser is inaccessible because the controls require twisting of the wrist to operate. |
TR3 |
24 months |
1.16.d |
The grab bars at the designated accessible toilet are inaccessible because they are mounted 36.5 inches above the finished floor. |
ST12 |
24 months |
1.17 |
District Attorney-Family Violence; 2nd floor |
||
1.17.a |
The door is inaccessible because it requires 10 pounds of force to open. |
D2 |
24 months |
1.17.b |
The counter is inaccessible because it is 40.25 inches above the finished floor. |
C6 |
24 months |
1.18 |
County Clerk; 2nd Floor |
||
1.18.a |
The door is inaccessible because it requires 11 pounds of force to open. |
D2 |
24 months |
1.18.b |
The counter is inaccessible because it is 38.25 inches above the finished floor. |
C6 |
24 months |
1.19 |
Purchasing Office; 2nd Floor |
||
1.19.a |
The door is inaccessible because it requires 7 pounds of force to open. |
D2 |
24 months |
1.2 |
Law Library; 2nd Floor |
||
1.20.a |
The door is inaccessible because it requires 10 pounds of force to open. |
D2 |
24 months |
1.20.b |
The counter is inaccessible because it is 43 inches above the finished floor. |
C6 |
24 months |
1.21 |
Auto Registration Office; 2nd Floor |
||
1.21.a |
The door is inaccessible because it requires 9 pounds of force to open. |
D2 |
24 months |
1.21.b |
The counter is inaccessible because it is 36.5 inches above the finished floor. |
C6 |
24 months |
1.22 |
Tax Assessor Office; 2nd Floor |
||
1.22.a |
The door is inaccessible because it requires 10 pounds of force to open. |
D2 |
24 months |
1.22.b |
The counter is inaccessible because it is 43.5 inches above the finished floor. |
C6 |
24 months |
1.23 |
Drinking Fountain; 3rd Floor West Annex |
||
1.23.a |
The drinking fountain is inaccessible because the flow of water is within 4 inches from the front of the drinking fountain. |
DF7 |
24 months |
1.24 |
Men's Toilet Room with Stalls; 3rd Floor West Annex |
||
1.24.a |
The door is inaccessible because it requires 10 pounds of force to open. |
D2 |
24 months |
1.24.b |
The light switch is inaccessible because it is mounted 56 inches above the finished floor. |
TR5 |
24 months |
1.24.c |
No accessible mirror has been provided. |
TR14 |
24 months |
1.24.d |
The stall door is inaccessible because there is no hardware on the pull side. |
D1 |
24 months |
1.25 |
Women's Toilet Room with Stalls; 3rd Floor West Annex |
||
1.25.a |
The door is inaccessible because it requires 9 pounds of force to open. |
D2 |
24 months |
1.25.b |
The light switch is inaccessible because it is mounted 56 inches above the finished floor. |
TR5 |
24 months |
1.25.c |
The seat cover dispenser is inaccessible because it is mounted so that it requires a reach of 57 inches above the finished floor. |
TR5 |
24 months |
1.25.d |
The grab bars at the designated accessible toilet are inaccessible because they are mounted 36.5 inches above the finished floor. |
ST12 |
24 months |
1.26 |
Interior Ramp; West Annex to Courthouse |
||
1.26.a |
The ramp is inaccessible because one side lacks a handrail, and the ends of the handrails are not rounded or returned. |
R4 |
24 months |
1.27 |
Men's Toilet Rooms with Stalls; 3rd Floor Courthouse |
||
1.27.a |
The door is inaccessible because it requires 8 pounds of force to open. |
D2 |
24 months |
1.27.b |
Although an audible alarm is provided in this facility, there is no visual alarm appliance in the toilet room. |
TR21 |
24 months |
1.27.c |
The designated accessible toilet is inaccessible because the top of the seat is 18.5 inches above the finished floor. |
ST20 |
24 months |
1.27.d |
The designated accessible toilet is inaccessible because its centerline is 18.5 inches from the side wall. |
ST17 |
24 months |
1.27.e |
The grab bars at the designated accessible toilet are inaccessible because they are mounted 36.5 inches above the finished floor. |
ST12 |
24 months |
1.27.f |
The toilet paper dispenser in the designated accessible stall is inaccessible because it is mounted 37 inches from the rear wall. |
ST19 |
24 months |
1.28 |
Women's Toilet Rooms with Stall's; 3rd Floor Courthouse |
||
1.28.a |
The door is inaccessible because it requires 9 pounds of force to open. |
D2 |
24 months |
1.28.b |
Although an audible alarm is provided in this facility, there is no visual alarm appliance in the toilet room. |
TR21 |
24 months |
1.28.c |
The grab bars at the designated accessible toilet are inaccessible because they are mounted 36.5 inches high. |
ST12 |
24 months |
1.28.d |
The rear grab bar at the designated accessible toilet is inaccessible because it is 35.5 inches long and it is mounted with its closer end 7 inches from the side wall. |
ST4 |
24 months |
1.29 |
Telephones; 3rd Floor East Annex |
||
1.29.a |
The telephone is inaccessible because the counter is 43.5 inches above the finished floor, the clear knee space depth is 16.75 inches deep, the highest operable part is 66.5 inches above the finished floor, and it lacks volume control. |
TT1 |
24 months |
1.3 |
Men's Toilet Room with Stalls; 3rd Floor East Annex |
||
1.30.a |
The door is inaccessible because it requires 7 pounds of force to open. |
D2 |
24 months |
1.30.b |
Although an audible alarm is provided in this facility, there is no visual alarm appliance in the toilet room. |
TR21 |
24 months |
1.30.c |
The lavatory is inaccessible because the bottom of the apron is 28.5 inches above the finished floor. |
TR11 |
24 months |
1.30.d |
The designated accessible toilet is inaccessible because the top of the seat is 16.5 inches above the finished floor. |
ST20 |
24 months |
1.30.e |
The side grab bar at the designated accessible toilet is inaccessible because it is obstructed by the toilet paper dispenser. |
ST8 |
24 months |
1.30.f |
The grab bars at the designated accessible toilet are inaccessible because they are mounted 36.5 inches above the finished floor. |
ST12 |
24 months |
1.30.g |
The stall door is inaccessible because there is no hardware on the pull side. |
D1 |
24 months |
1.31 |
Women's Toilet Room with Stalls; 3rd Floor East Annex |
||
1.31.a |
The door is inaccessible because it requires 8 pounds of force to open. |
D2 |
24 months |
1.31.b |
Although an audible alarm is provided in this facility, there is no visual alarm appliance in the toilet room. |
TR21 |
24 months |
1.31.c |
The designated accessible toilet is inaccessible because its centerline is 18.5 inches from the side wall. |
ST17 |
24 months |
1.31.d |
The side grab bar at the designated accessible toilet is inaccessible because it is obstructed by the toilet paper dispenser. |
ST8 |
24 months |
1.31.e |
The grab bars at the designated accessible toilet are inaccessible because they are mounted 36.75 inches above the finished floor. |
ST12 |
24 months |
1.31.f |
The stall door is inaccessible because there is no hardware on the pull side. |
D1 |
24 months |
1.32 |
County Commissioners Court; 3rd Floor |
||
1.32.a |
The door is inaccessible because it requires 7 pounds of force to open. |
D2 |
24 months |
1.32.b |
There is no accessible route connecting the wheelchair seating areas to the testimony area and the raised dias. |
AA1 |
24 months |
1.32.c |
The courtroom containing 70 seats is inaccessible because no wheelchair seating areas are provided. A total of 4 wheelchair seating areas are required. |
AA6 |
24 months |
1.32.d |
The courtroom is inaccessible to people who are hard ofhearing because, although there are 50 or more fixed seats, there is no assistive listening system provided. This court requires 2 receivers. |
AA4 |
24 months |
1.33 |
County Court at Law 2; 3rd Floor |
||
1.33.a |
Courtroon |
||
1.33.a(1) |
The door is inaccessible because it requires 10 pounds of force to open. |
D2 |
24 months |
1.33.a(2) |
The courtroom containing 64 seats is inaccessible because only 1 wheelchair seating area is provided. A total of 4 wheelchair seating areas are required. |
AA6 |
24 months |
1.33.a(3) |
The witness stand and jury box are inaccessible because they can be accessed only by steps. |
AA8 |
24 months |
1.33.a(4) |
The coat hook(s) is inaccessible because it is mounted 67 inches above the finished floor. |
TR5 |
24 months |
1.33.a(5) |
The route to the jury room is inaccessible because it is only 29 inches wide. |
AR3 |
24 months |
1.33.b |
Men's Single-User Toilet Room-Jury Room |
||
1.33.b(1) |
The toilet room contains a number of inaccessible elements and is not accessible to people with disabilities. |
SU13 |
24 months |
1.33.c |
Women's Single-User Toilet Room-Jury Room |
||
1.33.c(1) |
The toilet room contains a number of inaccessible elements and is not accessible to people with disabilities. |
SU13 |
24 months |
1.34 |
Grand Jury Room; 3rd Floor |
||
1.34.a |
The audience area containing 12 seats is inaccessible because no wheelchair seating areas are provided. A total of 1 wheelchair seating area is required. |
AA6 |
24 months |
1.34.b |
The grand jury box is inaccessible because it can be accessed only by steps. |
AA8 |
24 months |
1.34.c |
There is no signage informing the public of the availability of an assistive listening system. |
AA3 |
24 months |
1.35 |
Gregg County Court Room; 3rd Floor |
||
1.35.a |
Courtroom |
||
1.35.a(1) |
The door is inaccessible because it requires 10 pounds of force to open. |
D2 |
24 months |
1.35.a(2) |
The courtroom containing 58 seats is inaccessible because only 1 wheelchair seating area is provided. A total of 4 wheelchair seating areas are required. |
AA6 |
24 months |
1.35.a(3) |
The judge's bench, witness stand, and jury box are inaccessible because they can be accessed only by steps. |
AA8 |
24 months |
1.35.a(4) |
The coat hook is inaccessible because it is mounted 67 inches above the finished floor. |
TR5 |
24 months |
1.35.b |
Men's Single-User Toilet Room-Jury Room |
||
1.35.b(1) |
The toilet room contains a number of inaccessible elements and is not accessible to people with disabilities. |
SU13 |
24 months |
1.35.b(2) |
Women's Single-User Toilet Room-Jury Room |
||
1.35.b(3) |
The toilet room contains a number of inaccessible elements and is not accessible to people with disabilities. |
SU13 |
24 months |
1.36 |
Criminal-Civil Child Support Office; 3rd Floor |
||
1.36.a |
The counter is inaccessible because it is 43.5 inches above the finished floor. |
C6 |
24 months |
1.36.b |
The computer table is inaccessible because it provides only 24.5 inches of clear knee space height. |
T1 |
24 months |
1.37 |
Criminal-District Attorney's Office; 3rd Floor |
||
1.37.a |
The door is inaccessible because it requires 12 pounds of force to open. |
D2 |
24 months |
1.37.b |
The counter is inaccessible because it is 36.25 inches above the finished floor. |
C6 |
24 months |
1.38 |
District Attorney's Conference Room; 3rd Floor |
||
1.38.a |
The door is inaccessible because it has an opening width of 29.25 inches. |
D25 |
24 months |
1.39 |
District Attorney's Office-Hot Checks Division; 3rd Floor |
||
1.39.a |
The door is inaccessible because it requires 9 pounds of force to open. |
D2 |
24 months |
1.39.b |
The pull side of the door, which is accessed through a front approach, is inaccessible because it lacks adequate clear space on the latch side. |
D6 |
24 months |
1.39.c |
The counter is inaccessible because it is 37 inches above the finished floor. |
C6 |
24 months |
1.4 |
County Auditor's Office; 3rd Floor |
||
1.40.a |
The door is inaccessible because it requires 14 pounds of force to open. |
D2 |
24 months |
1.40.b |
The pull side of the door, which is accessed through a front approach, is inaccessible because it has only 16 inches of clear space on the latch side. |
D6 |
24 months |
1.40.c |
The counter is inaccessible because it is 45 inches above the finished floor. |
C6 |
24 months |
1.41 |
Drinking Fountain-188th District Court; 4th Floor (*Altered) |
||
1.41.a |
The wall-mounted drinking fountain is inaccessible because it provides only 26.5 inches of clear knee space height. |
DF5 |
24 months |
1.42 |
Telephone; 4th Floor West Annex |
24 months |
|
1.42.a |
The telephone is inaccessible because the highest operable part is 56 inches above the finished floor, the cord is 27 inches long, there is no volume control, and the knee space depth is 14 inches deep. |
TT1 |
24 months |
1.43 |
Drinking Fountains; 4th Floor West Annex |
||
1.43.a |
The drinking fountain is inaccessible because the flow of water is 4 inches from the front of the fountain. |
DF7 |
24 months |
1.43.b |
The drinking fountain is inaccessible because the controls require 7 pounds of force to operate. |
DF2 |
24 months |
1.44 |
Men's Toilet Room with Stalls; 4th Floor West Annex |
||
1.44.a |
The door is inaccessible because it requires 9 pounds of force to open. |
D2 |
24 months |
1.44.b |
The light switch is inaccessible because it is 55.5 inches above the finished floor. |
TR5 |
24 months |
1.44.c |
No accessible mirror has been provided. |
TR14 |
24 months |
1.44.d |
The lavatory is inaccessible because the bottom of the apron is 28.75 inches above the finished floor. |
TR11 |
24 months |
1.44.e |
The stall door is inaccessible because there is no hardware on the pull side. |
D1 |
24 months |
1.44.f |
The designated accessible toilet is inaccessible because its centerline is 18.5 inches from the side wall. |
ST17 |
24 months |
1.44.g |
The side grab bars at the designated accessible toilet are inaccessible because they are mounted 37 inches above the finished floor. |
ST12 |
24 months |
1.45 |
Women's Toilet Room with Stalls; 4th Floor West Annex |
||
1.45.a |
The door is inaccessible because it requires 9 pounds of force to open. |
D2 |
24 months |
1.45.b |
The light switch is inaccessible because it is mounted 55 inches above the finished floor. |
TR5 |
24 months |
1.45.c |
No accessible mirror has been provided. |
TR14 |
24 months |
1.45.d |
The lavatory is inaccessible because the bottom of the apron is 28.75 inches above the finished floor. |
TR11 |
24 months |
1.45.e |
The stall door is inaccessible because there is no hardware on the pull side. |
D1 |
24 months |
1.45.f |
The grab bars at the designated accessible toilet are inaccessible because they are mounted 37 inches above the finished floor. |
ST12 |
24 months |
1.46 |
Interior Ramp; Route from West Annex to Courthouse |
||
1.46.a |
The ramp is inaccessible because handrails are not on both sides of the ramp, and the ends of the handrails are not rounded or returned. |
R4 |
24 months |
1.47 |
Men's Toilet Room with Stalls; 4th Floor Courthouse |
||
1.47.a |
The door is inaccessible because it requires 11 pounds of force to open. |
D2 |
24 months |
1.47.b |
Although an audible alarm is provided in this facility, there is no visual alarm appliance in the toilet room. TR21 |
||
1.47.c |
No accessible coat hook has been provided. |
TR1 |
24 months |
1.48 |
Women's Toilet Room with Stalls; 4th Floor Courthouse |
||
1.48.a |
The door is inaccessible because it requires 9 pounds of force to open. |
D2 |
24 months |
1.48.b |
Although an audible alarm is provided in this facility, there is no visual alarm appliance in the toilet room. TR21 |
||
1.48.c |
No accessible coat hook has been provided. |
TR1 |
24 months |
1.49 |
124th District Court; 4th Floor |
||
1.49.a |
Courtroom (*Altered) |
||
1.49.a(1) |
The door is inaccessible because it requires 13 pounds of force to open. |
D2 |
24 months |
1.49.a(2) |
The judge's bench is inaccessible because it can be accessed only by steps. |
AA8 |
24 months |
1.49.a(3) |
There is no signage informing the public of the availability of an assistive listening system. |
AA3 |
24 months |
1.49.b |
Right Conference Room |
||
1.49.b(1) |
The door is inaccessible because it requires 10 pounds of force to open. |
D2 |
24 months |
1.49.c |
Left Conference Room |
||
1.49.c(1) |
The door is inaccessible because it requires 10 pounds of force to open. |
D2 |
24 months |
1.49.d |
Defendant Hall |
||
1.49.d(1) |
The door is inaccessible because it requires 10 pounds of force to open. |
D2 |
24 months |
1.49.e |
Judge's Office |
||
1.49.e(1) |
The door is inaccessible because it requires 10 pounds of force to open. |
D2 |
24 months |
1.49.f |
Juror's Room |
||
1.49.f(1) |
The door is inaccessible because it requires 9 pounds of force to open. |
D2 |
24 months |
1.49.g |
Men's Single-User Toilet Room |
||
1.49.g(1) |
The toilet room contains a number of inaccessible elements and is not accessible to people with disabilities. |
SU13 |
24 months |
1.49.h |
Women's Single-User Toilet Room |
||
1.49.h(1) |
The toilet room contains a number of inaccessible elements and is not accessible to people with disabilities. |
SU13 |
24 months |
1.5 |
188th District Court; 4th Floor (*Altered) |
||
1.50.a |
Courtroom |
||
1.50.a(1) |
The door is inaccessible because it requires 10 pounds of force to open. |
D2 |
24 months |
1.50.a(2) |
The courtroom is inaccessible because companion seats are not provided adjacent to wheelchair locations. |
AA6 |
24 months |
1.50.a(3) |
There is no signage informing the public of the availability of an assistive listening system. |
AA3 |
24 months |
1.50.b |
Right Conference Room |
||
1.50.b(1) |
The door is inaccessible because it requires 10 pounds of force to open. |
D2 |
24 months |
1.50.c |
Left Conference Room |
||
1.50.c(1) |
The door is inaccessible because it requires 10 pounds of force to open. |
D2 |
24 months |
1.50.d |
Juror's Room |
||
1.50.d(1) |
The door is inaccessible because it requires 13 pounds of force to open. |
D2 |
24 months |
1.50.e |
Men's Single-User Toilet Room |
||
1.50.e(1) |
Although an audible alarm is provided in this facility, there is no visual alarm appliance in the toilet room. |
TR21 |
24 months |
1.50.e(2) |
No accessible mirror has been provided. |
TR14 |
24 months |
1.50.f |
Women's Single-User Toilet Room |
||
1.50.f(1) |
Although an audible alarm is provided in this facility, there is no visual alarm appliance in the toilet room. |
TR21 |
24 months |
1.50.f(2) |
No accessible mirror has been provided. |
TR14 |
24 months |
1.51 |
County Court at Law 1; 4th Floor |
||
1.51.a |
Courtroom |
||
1.51.a(1) |
The judge's bench and witness stand are inaccessible because they can be accessed only by steps. |
AA8 |
24 months |
1.51.a(2) |
The courtroom door is inaccessible because it requires 12 pounds of force to open. |
D2 |
24 months |
1.51.a(3) |
The courtroom containing 70 seats is inaccessible because no wheelchair seating areas are provided. A total of 2 wheelchair seating areas is required. |
AA6 |
24 months |
1.51.a(4) |
The jury box has fixed seating preventing a juror using a wheelchair from sitting in the jury box. |
AA9 |
24 months |
1.51.a(5) |
There is no signage informing the public of the availability of an assistive listening system. |
AA3 |
24 months |
1.51.b |
Jury Room; Men's Single-User Toilet Room |
||
1.51.b(1) |
The toilet room contains a number of inaccessible elements and is not accessible to people with disabilities. |
SU13 |
24 months |
1.51.c |
Jury Room; Women's Single-User Toilet Room |
||
1.51.c(1) |
The toilet room contains a number of inaccessible elements and is not accessible to people with disabilities. |
SU13 |
24 months |
1.51.d |
Exterior Entrance and Doors - Conference Room 1 |
||
1.51.d(1) |
The door is inaccessible because it has an opening width of 29 inches. |
D25 |
24 months |
1.51.e |
Conference Room 2 |
||
1.51.e(1) |
The door is inaccessible because it has an opening width of 29 inches. |
D25 |
24 months |
1.52 |
307th District Family Court; 4th Floor |
||
1.52.a |
Courtroom |
||
1.52.a(1) |
The courtroom door is inaccessible because it has an opening width of 28.75 inches. |
D25 |
24 months |
1.52.a(2) |
The courtroom door is inaccessible because it requires 12 pounds of force to open. |
D2 |
24 months |
1.52.a(3) |
The gate to the court well is inaccessible because it has an opening width of 30.5 inches. |
D25 |
24 months |
1.52.a(4) |
The route to the jury box is inaccessible because it is only 26.25 inches wide. |
AR3 |
24 months |
1.52.a(5) |
The witness stand is inaccessible because it can be accessed only by steps. |
AA8 |
24 months |
1.52.a(6) |
The route to the witness stand is inaccessible because it is only 29.5 inches wide. |
AR3 |
24 months |
1.52.a(7) |
The courtroom containing 40 seats is inaccessible because no wheelchair seating areas are provided. A total of 2 wheelchair seating areas is required. |
AA6 |
24 months |
1.52.a(8) |
The courtroom is inaccessible to people who are hard of hearing because there is no assistive listening system provided. This courtroom requires 2 receivers. |
AA5 |
24 months |
1.52.b |
Jury Room |
||
1.52.b(1) |
The door is inaccessible because it requires 15 pounds of force to open. |
D2 |
24 months |
1.52.b(2) |
The pull side of the door, which is accessed through a front approach, is inaccessible because it has inadequate clear space on the latch side. |
D6 |
24 months |
1.52.b(3) |
The push side of the door, which is accessed through a front approach and which has both a closer and a latch, is inaccessible because it has inadequate clear space on the latch side. |
D7 |
24 months |
1.52.c |
Witness Conference Room #1 |
||
1.52.c(1) |
The door is inaccessible because it has an opening width of 29 inches. |
D25 |
24 months |
1.52.c(2) |
The door is inaccessible because it requires 6 pounds of force to open. |
D2 |
24 months |
1.52.c(3) |
The pull side of the door, which is accessed through a front approach, is inaccessible because it has only 3.5 inches of clear space on the latch side and 24.5 inches of clear floor space depth. |
D6 |
24 months |
1.52.d |
Witness Conference Room #2 |
||
1.52.d(1) |
The door is inaccessible because it has an opening width of 29 inches. |
D25 |
24 months |
1.52.d(2) |
The door is inaccessible because it requires 9 pounds of force to open. |
D2 |
24 months |
1.52.e |
Men's Single-User Toilet Room |
||
1.52.e(1) |
The toilet room contains a number of inaccessible elements and is not accessible to people with disabilities. |
SU13 |
24 months |
1.52.f |
Women's Single-User Toilet Room |
||
1.52.f(1) |
The toilet room contains a number of inaccessible elements and is not accessible to people with disabilities. |
SU13 |
24 months |
1.53 |
Justice of the Peace |
||
1.53.a |
Precinct 1; 5th Floor |
||
1.53.a(1) |
The lobby entrance door is inaccessible because it requires 13 pounds of force to open. |
D2 |
24 months |
1.53.a(2) |
The courtroom door is inaccessible because it requires 13 pounds of force to open. |
D2 |
24 months |
1.53.a(3) |
The gate to the court well is inaccessible because it has an opening width of 30.5 inches. |
D25 |
24 months |
1.53.a(4) |
The routes to the jury box, judge's bench, and witness stand is inaccessible because they are only 31 inches wide. |
AR3 |
24 months |
1.53.a(5) |
The judge's bench and witness stand are inaccessible because they can be accessed only by steps. |
AA8 |
24 months |
1.53.a(6) |
The jury box has fixed seating preventing a juror using a wheelchair from sitting in the jury box. |
AA9 |
24 months |
1.53.a(7) |
The courtroom containing 40 seats is inaccessible because no wheelchair seating areas are provided. A total of 2 wheelchair seating areas is required. |
AA6 |
24 months |
1.53.b |
Office |
||
1.53.b(1) |
The counter is inaccessible because it is 42.75 inches above the finished floor. |
C6 |
24 months |
1.53.c |
Jury Room |
||
1.53.c(1) |
The entry door is inaccessible because it has an opening width of 29 inches. |
D25 |
24 months |
1.53.c(2) |
The door is inaccessible because it requires 10 pounds of force to open. |
D2 |
24 months |
1.53.c(3) |
The pull side of the door, which is accessed through a front approach, is inaccessible because it has only 6 inches of clear space on the latch side due to a chair that is fixed to the floor. |
D6 |
24 months |
1.54 |
Sheriff's Office; 5th Floor |
||
1.54.a |
Civil Warrants Office |
||
1.54.a(1) |
The entry door is inaccessible because it has an opening width of 30 inches. |
D25 |
24 months |
1.54.b |
Women's Toilet Room with Stalls |
||
1.54.b(1) |
The toilet room sign is mounted with its centerline at 56 inches above the floor, and has no raised or Braille characters. |
TR17 |
24 months |
1.54.b(2) |
The entry door is inaccessible because it has an opening width of 29 inches. |
D25 |
24 months |
1.54.b(3) |
The door is inaccessible because it requires 20 pounds of force to open. |
D2 |
24 months |
1.54.b(4) |
The light switch is inaccessible because it is mounted 56 inches above the finished floor. |
TR5 |
24 months |
1.54.b(5) |
No accessible mirror has been provided. |
TR14 |
24 months |
1.54.b(6) |
The lavatory is inaccessible because the bottom of the apron is 15 inches above the finished floor. |
TR11 |
24 months |
1.54.b(7) |
The lavatory is inaccessible because it has inadequate clear floor space. |
TR8 |
24 months |
1.54.b(8) |
The designated accessible stall is incorrectly configured as an ambulatory stall, and there is no standard accessible stall provided. |
ST15 |
24 months |
1.54.c |
Men's Toilet Room with Stalls |
||
1.54.c(1) |
The toilet room sign is mounted with its centerline at 56 inches above the floor, and has no raised or Braille characters. |
TR17 |
24 months |
1.54.c(2) |
The entry door is inaccessible because it has an opening width of 29 inches. |
D25 |
24 months |
1.54.c(3) |
The door is inaccessible because it requires 17 pounds of force to open. |
D2 |
24 months |
1.54.c(4) |
The light switch is inaccessible because it is mounted 57 inches above the finished floor. |
TR5 |
24 months |
1.54.c(5) |
No accessible mirror has been provided. |
TR14 |
24 months |
1.54.c(6) |
The lavatory is inaccessible because the bottom of the apron is 15 inches above the finished floor. |
TR11 |
24 months |
1.54.c(7) |
The lavatory is inaccessible because it has inadequate clear floor space. |
TR8 |
24 months |
1.54.c(8) |
The urinal is inaccessible because the rim is 19 inches above the finished floor. |
TR20 |
24 months |
1.54.c(9) |
The designated accessible stall is incorrectly configured as an ambulatory stall, and there is no standard accessible stall provided. |
ST15 |
24 months |
1.54.d |
Drinking Fountain |
||
1.54.d(1) |
The drinking fountain is inaccessible because it has a spout that is 39 inches above the finished floor. |
DF6 |
24 months |
1.54.d(2) |
The drinking fountain is inaccessible because the controls require 8 pounds of force to operate. |
DF2 |
24 months |
1.55 |
Gregg County South Jail; 5th Floor |
||
1.55.a |
Telephone in holding / intake |
||
1.55.a(1) |
The telephone is inaccessible because the cord is 17 inches long. |
TT1 |
24 months |
1.55.a(2) |
The telephone protrudes into the walkway and is not detectable to blind persons using a cane. |
AR8 |
24 months |
1.55.b |
Telephone in booking area |
||
1.55.b(1) |
The telephone is inaccessible because the cord is 17 inches long. |
TT1 |
24 months |
1.55.b(2) |
There is no accessible cell provided. |
PJ1 |
24 months |