Attachment I: Modifications to Newly Constructed Facilities
Please Note: Paragraph 47 of the Settlement Agreement requires that within 24 months of the effective date of this Agreement, the County will provide signage as necessary to comply with 28 C.F.R. § 35.163(b), after having surveyed all facilities that are the subject of this Agreement for the purpose of identifying those that have multiple entrances not all of which are accessible.
In order to ensure that the following spaces and elements in County facilities, for which construction was commenced after January 26, 1992, are readily accessible to and usable by persons with disabilities, the County will take the following actions:
1. Within 60 months of the effective date of this Agreement, the County will complete the following modifications to the Pate Building:
a. Parking
i. Front. Although the front parking lot has 77 parking spaces, an inadequate number are designated as reserved for persons with disabilities. On the shortest accessible route to the accessible entrance, provide one van accessible space and three standard spaces designated as reserved for people with disabilities. Standard accessible spaces shall be a minimum of 96 inches wide and served by access aisles at least 60 inches wide. Van accessible spaces shall be a minimum of 96 inches wide and served by access aisles at least 96 inches wide. All spaces designated as reserved for people with disabilities shall have vertical signs with the International Symbol of Accessibility located such that they cannot be obstructed by parked vehicles. Van accessible spaces shall have an additional "Van-Accessible" sign located below the International Symbol of Accessibility. Standards §§ 4.1.2(5), 4.6, 4.30.7(1).
ii. Rear. The van accessible space designated as reserved for persons with disabilities lacks the appropriate signage. At van accessible spaces, provide a "Van-Accessible" sign located below the International Symbol of Accessibility such that the sign cannot be obstructed by vehicles parked in the space. Standards §§ 4.1.2(5), 4.6.4, 4.30.7(1).
b. Ramp to front entrance. The ramp is inaccessible because there are no 12 inch extensions at the top or bottom of the ramp. Provide handrails that are between 1¼ inches and 1½ inches in diameter with a continuous gripping surface along both sides of the ramp, extending at least 12 inches beyond the top and bottom of the ramp parallel with the ground surface. Ensure that handrails are mounted between 34 inches and 38 inches above the ramp surface and 1½ inches from the wall, with ends rounded or returned smoothly to the floor, wall, or post, and that they do not rotate within their fittings. Standards §§ 4.1.2(1), 4.1.2(2), 4.8.5.
c. First Floor Toilet Rooms with Stalls
i. Men´s Toilet Room
(1) The toilet room sign is not mounted on latch side of door. Provide a toilet room sign with the International Symbol of Accessibility and raised and Braille characters mounted on the wall adjacent to the latch side of the door with the centerline of the sign 60 inches above the finished floor and situated such that a person can approach within 3 inches of the sign without encountering an obstruction or standing within a door swing. Standards §§ 4.1.2(7)(d), 4.30.1, 4.30.4, 4.30.5, 4.30.6, 4.30.7.
(2) No accessible mirror has been provided. Provide a mirror with the bottom edge of its reflecting surface no more than 40 inches above the finished floor. Standards §§ 4.1.3(11), 4.22.6, 4.19.6.
(3) The paper towel dispenser is not accessible because the required clear floor space is not provided. Provide a paper towel dispenser with a maximum height above the finished floor of 48 inches for a forward approach or 54 inches for a side approach and that it is accompanied by clear floor space of 30 by 48 inches that allows a forward or parallel approach by a person using a wheelchair. Standards §§ 4.1.3(13), 4.27.2, 4.27.3, 4.27.4, 4.2.4, 4.2.5, 4.2.6.
(4) The lavatory is inaccessible because it lacks adequate knee and toe clearance. Provide a lavatory with the top of its rim or counter 34 inches or less above the finished floor; the bottom edge of the apron at least 29 inches above the finished floor; and knee and toe clearances that comply with Fig. 31. Standards §§ 4.1.3(11), 4.22.6, 4.19.2, Fig. 31.
(5) The rear grab bar is inaccessible because its closer end is mounted 12 inches from the side wall. Provide a rear grab bar that is at least 36 inches in overall length with the closer end no more than 6 inches from the side wall. Standards §§ 4.1.3(11), 4.22.4, 4.16.4, Fig. 29.
ii. Women´s Toilet Room
(1) No accessible mirror has been provided. Provide a mirror with the bottom edge of its reflecting surface no more than 40 inches above the finished floor. Standards §§ 4.1.3(11), 4.22.6, 4.19.6.
(2) The lavatory is inaccessible because it lacks adequate knee and toe clearance. Provide a lavatory with the top of its rim or counter 34 inches or less above the finished floor; the bottom edge of the apron at least 29 inches above the finished floor; and knee and toe clearances that comply with Fig. 31. Standards §§ 4.1.3(11), 4.22.6, 4.19.2, Fig. 31.
(3) The toilet is inaccessible because its centerline is 19 inches from the side wall. Provide a toilet with its centerline 18 inches from the near side wall. Standards §§ 4.1.3(11), 4.22.4, 4.17.3, Fig. 30.
(4) The side grab bar is inaccessible because the toilet paper dispenser is mounted above the side grab bar. Provide a toilet paper dispenser that is mounted within reach, with its top at least 1½ inches under the side grab bar, and centered at least 19 inches above the finished floor. Standards §§ 4.1.3(11), 4.22.4, 4.16.6, Fig. 29(b).
(5) The rear grab bar is inaccessible because its closer end is mounted 10 inches from the side wall. Provide a rear grab bar that is at least 36 inches in overall length with the closer end no more than 6 inches from the side wall. Standards §§ 4.1.3(11), 4.22.4, 4.16.4, Fig. 29.
d. Finance Department. The top of the counter is 39½ inches above the finished floor. Provide a counter on an accessible route such that a portion of the counter is at least 36 inches wide and no more than 36 inches above the finished floor, or provide an auxiliary counter with a maximum height of 36 inches in close proximity to the main counter, or provide equivalent facilitation. Equivalent facilitation may be provided in the form of a folding shelf attached to the main counter, an auxiliary table nearby, a clip board made available to the public, or other means. Standards §§ 4.1.1(2), 7.2(2), 4.1.3(1), 4.3.
e. Property Appraisal (formerly Juvenile Court)
i. The top of the reception counter is not accessible. Provide a counter on an accessible route such that a portion of the counter is at least 36 inches wide and no more than 36 inches above the finished floor, or provide an auxiliary counter with a maximum height of 36 inches in close proximity to the main counter, or provide equivalent facilitation. Equivalent facilitation may be provided in the form of a folding shelf attached to the main counter, an auxiliary table nearby, a clip board made available to the public, or other means. Standards §§ 4.1.1(2), 7.2(2), 4.1.3(1), 4.3.
ii. The pull side of the door to the Juvenile Courtroom, which is accessed through a front approach, is inaccessible because there is insufficient clear floor space on the latch side of the door. On the pull side of the door, provide maneuvering clearance at least 60 inches deep and provide a minimum of 18 inches (24 inches is preferred) of maneuvering clearance on the latch side of the door. Standards §§ 4.1.3(7)(b), 4.13.6, Fig. 25(a).
f. Second Floor Toilet Rooms with Stalls
i. Men´s Toilet Room
(1) The urinal is inaccessible because the rim is 25 inches above the finished floor and the clear floor space is 26 inches wide. Provide a urinal with an elongated rim mounted 17 inches or less above the finished floor, a clear floor space of at least 30 inches wide and 48 inches deep centered on the urinal, and a flush control height of 44 inches or less above the finished floor. Standards §§ 4.1.3(11), 4.22.5, 4.18.2, 4.18.3, 4.18.4.
(2) The rear grab bar is inaccessible because its closer end is mounted 10 inches from the side wall. Provide a rear grab bar that is at least 36 inches in overall length with the closer end no more than 6 inches from the side wall. Standards §§ 4.1.3(11), 4.22.4, 4.17.6, Fig. 30.
(3) No accessible mirror has been provided. Provide a mirror with the bottom edge of its reflecting surface no more than 40 inches above the finished floor. Standards §§ 4.1.3(11), 4.22.6, 4.19.6.
ii. Women´s Toilet Room
(1) No accessible mirror has been provided. Provide a mirror with the bottom edge of its reflecting surface no more than 40 inches above the finished floor. Standards §§ 4.1.3(11), 4.22.6, 4.19.6.
(2) The lavatory is inaccessible because the clear floor space at the lavatory is less than 30 inches wide by 48 inches deep. Provide a lavatory with clear floor space at least 30 inches wide and 48 inches deep centered on the lavatory. Standards §§ 4.1.3(11), 4.22.6, 4.19.3, Fig. 32.
(3) The rear grab bar is inaccessible because its closer end is mounted 10 inches from the side wall. Provide a rear grab bar that is at least 36 inches in overall length with the closer end no more than 6 inches from the side wall. Standards §§ 4.1.3(11), 4.22.4, 4.17.6, Fig. 30.
g. G.I.S Office. The service counter is inaccessible because the top of the service counter is 40 inches above the finished floor. Provide a counter on an accessible route such that a portion of the counter is at least 36 inches wide and no more than 36 inches above the finished floor, or provide an auxiliary counter with a maximum height of 36 inches in close proximity to the main counter, or provide equivalent facilitation. Equivalent facilitation may be provided in the form of a folding shelf attached to the main counter, an auxiliary table nearby, a clip board made available to the public, or other means. Standards §§ 4.1.1(2), 7.2(2), 4.1.3(1), 4.3.
h. Personnel Office (Human Resource´s Office). The service counter is inaccessible because the top of the service counter is 40 inches above the finished floor. Provide a counter on an accessible route such that a portion of the counter is at least 36 inches wide and no more than 36 inches above the finished floor, or provide an auxiliary counter with a maximum height of 36 inches in close proximity to the main counter, or provide equivalent facilitation. Equivalent facilitation may be provided in the form of a folding shelf attached to the main counter, an auxiliary table nearby, a clip board made available to the public, or other means. Standards §§ 4.1.1(2), 7.2(2), 4.1.3(1), 4.3.
i. Information Technology Office. The door into office space in the Information Technology section is inaccessible because there is a 4½ inch threshold. Provide a door with a threshold no greater than ¼ inch, or between ¼ inch and ½ inch and beveled with a slope no greater than 1:2. Standards §§ 4.1.3(7)(b), 4.13.8, 4.5.2.
j. Third Floor Toilet Rooms with Stalls
i. Men´s Toilet Room
(1) The urinal is inaccessible because its rim is 23 inches above the finished floor and the clear floor space is 26 inches wide. Provide a urinal with an elongated rim mounted 17 inches or less above the finished floor, a clear floor space of at least 30 inches wide and 48 inches deep centered on the urinal, and a flush control height of 44 inches or less above the finished floor. Standards §§ 4.1.3(11), 4.22.5, 4.18.2, 4.18.3, 4.18.4.
(2) No accessible mirror has been provided. Provide a mirror with the bottom edge of its reflecting surface no more than 40 inches above the finished floor. Standards §§ 4.1.3(11), 4.22.6, 4.19.6.
(3) The rear grab bar is inaccessible because its closer end is mounted 10 inches from the side wall. Provide a rear grab bar that is at least 36 inches in overall length with the closer end no more than 6 inches from the side wall. Standards §§ 4.1.3(11), 4.22.4, 4.17.6, Fig. 30.
ii. Women´s Toilet Room
(1) No accessible mirror has been provided. Provide a mirror with the bottom edge of its reflecting surface no more than 40 inches above the finished floor. Standards §§ 4.1.3(11), 4.22.6, 4.19.6.
(2) The rear grab bar is inaccessible because its closer end is mounted 10 inches from the side wall. Provide a rear grab bar that is at least 36 inches in overall length with the closer end no more than 6 inches from the side wall. Standards §§ 4.1.3(11), 4.22.4, 4.17.6, Fig. 30.
k. Finance Purchasing Office. The service counter is inaccessible because the top of the counter is higher than 36 inches above the finished floor. Provide a counter on an accessible route such that a portion of the counter is at least 36 inches wide and no more than 36 inches above the finished floor, or provide an auxiliary counter with a maximum height of 36 inches in close proximity to the main counter, or provide equivalent facilitation. Equivalent facilitation may be provided in the form of a folding shelf attached to the main counter, an auxiliary table nearby, a clip board made available to the public, or other means. Standards §§ 4.1.1(2), 7.2(2), 4.1.3(1), 4.3.
2. Within 60 months of the effective date of this Agreement, the County will complete the following modifications to the Mallory Park:
a. Exterior Accessible Routes. There is no accessible route from the parking area to the toilet rooms/concessions building, bleachers, playground, shuffle board court, basketball court, baseball field, or Recreation Department because the surface of the routes is not stable, firm, and slip resistant. Provide at least one accessible route within the boundary of the site connecting these elements. The accessible route must have a minimum clear width of 36 inches, or a minimum clear width of 42 inches if there is a turn around an obstruction less than 48 inches wide; have passing spaces at least 60 inches by 60 inches at least every 200 feet; have a minimum clear headroom of 80 inches; have a surface that is firm, stable, and slip resistant; have, in the absence of a curb ramp, ramp, elevator, or platform lift, no level changes in excess of ½ inch vertically; and have a running slope of less than 5% (or have been constructed as a fully accessible ramp) and a cross slope of less than 2%. Standards §§ 4.3, 4.5, Fig. 7.
b. Toilet Rooms
i. Women´s Toilet Room with Stalls
(1) The toilet room sign is mounted on the door. Provide a toilet room sign with raised and Braille characters mounted on the wall adjacent to the latch side of the door with the centerline of the sign at 60 inches above the finished floor and situated such that a person can approach within 3 inches of the sign without encountering an obstruction or standing within a door swing. Standards §§ 4.1.2(7)(d), 4.30.1, 4.30.4, 4.30.5, 4.30.6.
(2) No accessible mirror has been provided. Provide a mirror with the bottom edge of its reflecting surface no more than 40 inches above the finished floor. Standards §§ 4.1.3(11), 4.22.6, 4.19.6.
(3) The lavatory is inaccessible because it lacks adequate knee and toe clearance. Provide a lavatory with the top of its rim or counter 34 inches or less above the finished floor; the bottom edge of the apron at least 29 inches above the finished floor; and knee and toe clearances that comply with Fig. 31. Standards §§ 4.1.3(11), 4.22.6, 4.19.2, Fig. 31.
(4) No accessible coat hook has been provided. Provide a coat hook at a maximum height above the finished floor of 48 inches for a forward approach or 54 inches for a side approach and that is accompanied by clear floor space of 30 by 48 inches that allows a forward or parallel approach by a person using a wheelchair. Standards §§ 4.1.3(12)(a), 4.25.2, 4.25.3, 4.2.4, 4.2.5, 4.2.6.
(5) The toilet paper dispenser is inaccessible because it is 39 inches from the back wall and 16 ½ inches above the finished floor. Provide a toilet paper dispenser that is mounted with its top at least 1½ inches under the side grab bar and 36 inches or less from the rear wall and is centered at least 19 inches above the finished floor. Standards §§ 4.1.3(11), 4.22.4, 4.17.3, Fig. 30(d).
ii. Men´s Toilet Room with Stalls
(1) The toilet room sign is mounted on the door. Provide a toilet room sign with raised and Braille characters mounted on the wall adjacent to the latch side of the door with the centerline of the sign at 60 inches above the finished floor and situated such that a person can approach within 3 inches of the sign without encountering an obstruction or standing within a door swing. Standards §§ 4.1.2(7)(d), 4.30.1, 4.30.4, 4.30.5, 4.30.6.
(2) No accessible mirror has been provided. Provide a mirror with the bottom edge of its reflecting surface no more than 40 inches above the finished floor. Standards §§ 4.1.3(11), 4.22.6, 4.19.6.
(3) The lavatory is inaccessible because it lacks adequate knee and toe clearance. Provide a lavatory with the top of its rim or counter 34 inches or less above the finished floor; the bottom edge of the apron at least 29 inches above the finished floor; and knee and toe clearances that comply with Fig. 31. Standards §§ 4.1.3(11), 4.22.6, 4.19.2, Fig. 31.
(4) No accessible coat hook has been provided. Provide a coat hook at a maximum height above the finished floor of 48 inches for a forward approach or 54 inches for a side approach and that is accompanied by clear floor space of 30 by 48 inches that allows a forward or parallel approach by a person using a wheelchair. Standards §§ 4.1.3(12)(a), 4.25.2, 4.25.3, 4.2.4, 4.2.5, 4.2.6.
(5) The toilet flush control is on the closed side. Provide a flush control mounted on the "open" side of the toilet´s clear floor space; 44 inches or less above the finished floor; and requiring a maximum of 5 pounds of force to operate; or provide an automatic flush device. Standards §§ 4.1.3(11), 4.22.4, 4.16.5, 4.17.2, 4.27.4.
c. Drinking Fountains. The drinking fountains protrude into the walkway and would not be detectable to a blind person using a cane. Provide a circulation path at this location such that no objects with their bottom leading edges measuring between 27 inches and 80 inches above the finished floor protrude more than 4 inches into walks, halls, corridors, passageways, or aisles. Free-standing objects mounted on posts or pylons may overhang 12 inches maximum from 27 inches to 80 inches above the ground or finished floor. Providing a cane-detectable barrier is an acceptable solution. Standards §§ 4.1.2(3), 4.4.
3. Except as otherwise specified, within 60 months of the effective date of this agreement, the County will make the following modifications to Selden Park:
a. Parking
i. The parking spaces designated as accessible do not have a firm, stable, and slip-resistant surface; there is no designated van accessible parking; and there are no access aisles. On the shortest accessible route to the accessible entrance, provide one van accessible space and one standard space designated as reserved for people with disabilities. Ensure that standard accessible spaces are a minimum of 96 inches wide and served by access aisles at least 60 inches wide. Ensure that van accessible spaces are a minimum of 96 inches wide and served by access aisles at least 96 inches wide. At all spaces designated as reserved for persons with disabilities, provide vertical signs with the International Symbol of Accessibility located such that they cannot be obstructed by parked vehicles. At van accessible spaces, provide an additional "Van-Accessible" sign located below the International Symbol of Accessibility. Ensure that all spaces and access aisles for persons with disabilities are flat and level, with slopes and cross-slopes not exceeding 2% in all directions, and that their surfaces are firm, stable, and slip-resistant. Standards §§ 4.1.2(5), 4.6, 4.30.7(1).
b. Richard "Bubba" Perry Gymnasium
i. Concession Stand.
(1) The top of the concession counter is 41½ inches above the finished floor. Provide a counter on an accessible route such that a portion of the counter is at least 36 inches wide and no more than 36 inches above the finished floor. Standards §§ 4.1.1(2), 7.2(1), 4.1.3(1), 4.3.
(2) The concession stand counter protrudes into the walkway and would not be detectable to a blind person using a cane. Provide a circulation path at this location such that no objects with their bottom leading edges measuring between 27 inches and 80 inches above the finished floor protrude more than 4 inches into walks, halls, corridors, passageways, or aisles. Free-standing objects mounted on posts or pylons may overhang 12 inches maximum from 27 inches to 80 inches above the ground or finished floor. Providing a cane-detectable barrier is an acceptable solution. Standards §§ 4.1.2(3), 4.4.
ii. Women´s Toilet Room with Stalls
(1) The toilet room sign is not mounted on the latch side of the door. Provide a toilet room sign with raised and Braille characters mounted on the wall adjacent to the latch side of the door with the centerline of the sign 60 inches above the finished floor and situated such that a person can approach within 3 inches of the sign without encountering an obstruction or standing within a door swing. Standards §§ 4.1.2(7)(d), 4.30.1, 4.30.4, 4.30.5, 4.30.6.
(2) The lavatory is inaccessible because the bottom edge of the lavatory apron is mounted 27 inches above the finished floor and the faucet trim requires tight grasping, pinching, or twisting of the wrist. Provide a lavatory with the top of its rim or counter 34 inches or less above the finished floor; the bottom edge of the apron at least 29 inches above the finished floor; knee and toe clearances that comply with Fig. 31 and a faucet that can be operated with 5 pounds of force or less and can be used with one hand and without tight grasping, pinching, or twisting of the wrist (lever-operated, push-type, and electronically controlled mechanisms are examples of acceptable designs). Standards §§ 4.1.3(11), 4.22.6, 4.19.2, 4.19.5, 4.27.4, Fig. 31.
(3) No accessible coat hook has been provided. Provide a coat hook at a maximum height above the finished floor of 48 inches for a forward approach or 54 inches for a side approach and that is accompanied by clear floor space of 30 by 48 inches that allows a forward or parallel approach by a person using a wheelchair. Standards §§ 4.1.3(12)(a), 4.25.2, 4.25.3, 4.2.4, 4.2.5, 4.2.6.
(4) The toilet paper dispenser is inaccessible because it is mounted 38 inches from the rear wall. Provide a toilet paper dispenser that is mounted with its top at least 1½ inches under the side grab bar and 36 inches or less from the rear wall and is centered at least 19 inches above the finished floor. Standards §§ 4.1.3(11), 4.22.4, 4.17.3, Fig. 30(d).
(5) The rear grab bar is inaccessible because its overall length is 34 inches. Provide a rear grab bar that is at least 36 inches in overall length with the closer end no more than 6 inches from the side wall. Standards §§ 4.1.3(11), 4.22.4, 4.17.6, Fig. 30.
iii. Men´s Toilet Room with Stalls
(1) The toilet room sign is not mounted on the latch side of the door. Provide a toilet room sign with raised and Braille characters mounted on the wall adjacent to the latch side of the door with the centerline of the sign 60 inches above the finished floor and situated such that a person can approach within 3 inches of the sign without encountering an obstruction or standing within a door swing. Standards §§ 4.1.2(7)(d), 4.30.1, 4.30.4, 4.30.5, 4.30.6.
(2) No accessible mirror has been provided. Provide a mirror with the bottom edge of its reflecting surface no more than 40 inches above the finished floor. Standards §§ 4.1.3(11), 4.22.6, 4.19.6.
(3) The lavatory is inaccessible because the bottom edge of the lavatory apron is mounted 27 inches above the finished floor and the faucet trim requires tight grasping, pinching, or twisting of the wrist. Provide a lavatory with the top of its rim or counter 34 inches or less above the finished floor; the bottom edge of the apron at least 29 inches above the finished floor; knee and toe clearances that comply with Fig. 31 and a faucet that can be operated with 5 pounds of force or less and can be used with one hand and without tight grasping, pinching, or twisting of the wrist (lever-operated, push-type, and electronically controlled mechanisms are examples of acceptable designs). Standards §§ 4.1.3(11), 4.22.6, 4.19.2, 4.19.5, 4.27.4, Fig. 31.
(4) The urinal is inaccessible because the rim is 24 inches above the finished floor and the flush control is 45 inches above the finished floor. Provide a urinal with an elongated rim mounted 17 inches or less above the finished floor, a clear floor space of at least 30 inches wide and 48 inches deep centered on the urinal, and a flush control height of 44 inches or less above the finished floor. Standards §§ 4.1.3(11), 4.22.5, 4.18.2, 4.18.3, 4.18.4.
(5) The toilet is inaccessible because the flush control is on the closed side. Provide a flush control mounted on the "open" side of the toilet´s clear floor space; 44 inches or less above the finished floor; and requiring a maximum of 5 pounds of force to operate; or provide an automatic flush device. Standards §§ 4.1.3(11), 4.22.4, 4.16.5, 4.17.2, 4.27.4.
(6) The toilet paper dispenser is inaccessible because it is mounted 39 inches from the rear wall. Provide a toilet paper dispenser that is mounted with its top at least 1½ inches under the side grab bar and 36 inches or less from the rear wall and is centered at least 19 inches above the finished floor. Standards §§ 4.1.3(11), 4.22.4, 4.17.3, Fig. 30(d).
iv. Women´s Locker Room - Inside Gym
(1) The toilet room sign is not mounted on the latch side of the door. Provide a toilet room sign with raised and Braille characters mounted on the wall adjacent to the latch side of the door with the centerline of the sign 60 inches above the finished floor and situated such that a person can approach within 3 inches of the sign without encountering an obstruction or standing within a door swing. Standards §§ 4.1.2(7)(d), 4.30.1, 4.30.4, 4.30.5, 4.30.6.
(2) The lavatory is inaccessible because there is insufficient knee and toe clearance and the faucet requires tight grasping, or twisting of the wrist. Provide a lavatory with the top of its rim or counter 34 inches or less above the finished floor; the bottom edge of the apron at least 29 inches above the finished floor; knee and toe clearances that comply with Fig. 31; hot water and drain pipes covered or otherwise configured to protect against contact; clear floor space at least 30 inches wide and 48 inches deep centered on the lavatory; and a faucet that can be operated with 5 pounds of force or less and can be used with one hand and without tight grasping, pinching, or twisting of the wrist (lever-operated, push-type, and electronically controlled mechanisms are examples of acceptable designs). Standards §§ 4.1.3(11), 4.22.6, 4.19.2, 4.19.3, 4.19.4, 4.19.5, 4.27.4, Figs. 31, 32.
(3) No accessible mirror has been provided. Provide a mirror with the bottom edge of its reflecting surface no more than 40 inches above the finished floor. Standards §§ 4.1.3(11), 4.22.6, 4.19.6.
(4) There is no accessible toilet stall provided. Provide a "standard" accessible toilet stall at least 60 inches wide and at least 59 inches deep (or at least 56 inches deep with a wall-mounted toilet) such that all of the stall´s elements, including stall door, stall door hardware, water closet, size and arrangement, toe clearances, grab bars, controls, and dispensers, comply with the Standards. Standards §§ 4.1.3(11), 4.22.4, 4.22.7, 4.13, 4.16, 4.17, 4.26, 4.27, Fig. 30.
(5) The shower in the women´s locker room is inaccessible because the designated accessible shower stall is not configured correctly. Provide a shower in this room that is exactly 36 inches wide and 36 inches deep with a 48 inch long and 36 inch wide clear floor space alongside the shower opening, and an L-shaped shower seat mounted on the wall opposite the controls and extending the full depth of the stall; OR a shower that is at least 30 inches deep and 60 inches wide with no curb or threshold and with a 36 inch deep and 60 inch wide clear floor space at the shower opening. Ensure that the shower has grab bars, controls, a shower spray unit, and a seat, curb, and enclosure, if provided, that comply fully with the Standards and with Figs. 35, 36, and 37, as applicable. Standards §§ 4.1.3(11), 4.21, Figs. 35, 36, 37.
v. Men´s Locker Room - Inside Gym
(1) The toilet room sign is not mounted on the latch side of the door. Provide a toilet room sign with raised and Braille characters mounted on the wall adjacent to the latch side of the door with the centerline of the sign 60 inches above the finished floor and situated such that a person can approach within 3 inches of the sign without encountering an obstruction or standing within a door swing. Standards §§ 4.1.2(7)(d), 4.30.1, 4.30.4, 4.30.5, 4.30.6.
(2) The lavatory is inaccessible because there is insufficient knee and toe clearance and the faucet requires tight grasping, pinching, or twisting of the wrist. Provide a lavatory with the top of its rim or counter 34 inches or less above the finished floor; the bottom edge of the apron at least 29 inches above the finished floor; knee and toe clearances that comply with Fig. 31; hot water and drain pipes covered or otherwise configured to protect against contact; clear floor space at least 30 inches wide and 48 inches deep centered on the lavatory; and a faucet that can be operated with 5 pounds of force or less and can be used with one hand and without tight grasping, pinching, or twisting of the wrist (lever-operated, push-type, and electronically controlled mechanisms are examples of acceptable designs). Standards §§ 4.1.3(11), 4.22.6, 4.19.2, 4.19.3, 4.19.4, 4.19.5, 4.27.4, Figs. 31, 32.
(3) The urinal is inaccessible because the rim is 25 inches above the finished floor and the flush control is 45 inches above the finished floor. Provide a urinal with an elongated rim mounted 17 inches or less above the finished floor, a clear floor space of at least 30 inches wide and 48 inches deep centered on the urinal, and a flush control height of 44 inches or less above the finished floor. Standards §§ 4.1.3(11), 4.22.5, 4.18.2, 4.18.3, 4.18.4.
(4) No accessible toilet stall has been provided. Provide a "standard" accessible toilet stall at least 60 inches wide and at least 59 inches deep (or at least 56 inches deep with a wall-mounted toilet) such that all of the stall´s elements, including stall door, stall door hardware, water closet, size and arrangement, toe clearances, grab bars, controls, and dispensers, comply with the Standards. Standards §§ 4.1.3(11), 4.22.4, 4.22.7, 4.13, 4.16, 4.17, 4.26, 4.27, Fig. 30.
(5) No accessible mirror has been provided. Provide a mirror with the bottom edge of its reflecting surface no more than 40 inches above the finished floor. Standards §§ 4.1.3(11), 4.22.6, 4.19.6.
(6) The shower in the men´s locker room is inaccessible because the designated accessible shower stall is not configured correctly. Provide a shower in this room that is exactly 36 inches wide and 36 inches deep with a 48 inch long and 36 inch wide clear floor space alongside the shower opening, and an L-shaped shower seat mounted on the wall opposite the controls and extending the full depth of the stall; OR a shower that is at least 30 inches deep and 60 inches wide with no curb or threshold and with a 36 inch deep and 60 inch wide clear floor space at the shower opening. Ensure that the shower has grab bars, controls, a shower spray unit, and a seat, curb, and enclosure, if provided, that comply fully with the Standards and with Figs. 35, 36, and 37, as applicable. Standards §§ 4.1.3(11), 4.21, Figs. 35, 36, 37.
c. Bath House and Pool - Within 60 months of the date of this agreement, the County will make the following modifications to the Bath House and Pool at Selden Park. Until these items are addressed, the County will provide an accessible portable toilet, on an accessible route, as a temporary measure:
i. Men´s Locker Room
(1) The lavatory is inaccessible because the hot water pipes are not insulated or otherwise configured to protect against contact and the bottom edge of the apron is 28 inches above the finished floor. Provide a lavatory with the top of its rim or counter 34 inches or less above the finished floor; the bottom edge of the apron at least 29 inches above the finished floor; knee and toe clearances that comply with Fig. 31; hot water and drain pipes covered or otherwise configured to protect against contact; clear floor space at least 30 inches wide and 48 inches deep centered on the lavatory; and a faucet that can be operated with 5 pounds of force or less and can be used with one hand and without tight grasping, pinching, or twisting of the wrist (lever-operated, push-type, and electronically controlled mechanisms are examples of acceptable designs). Standards §§ 4.1.3(11), 4.22.6, 4.19.2, 4.19.3, 4.19.4, 4.19.5, 4.27.4, Figs. 31, 32.
(2) The urinal is inaccessible because the rim is 24 above the finished floor and the flush control is 44 ½ above the finished floor. Provide a urinal with an elongated rim mounted 17 inches or less above the finished floor, a clear floor space of at least 30 inches wide and 48 inches deep centered on the urinal, and a flush control height of 44 inches or less above the finished floor. Standards §§ 4.1.3(11), 4.22.5, 4.18.2, 4.18.3, 4.18.4.
(3) The toilet stall is inaccessible because there is insufficient clear floor space. Provide a toilet stall that is at least 60 inches wide and at least 56 inches deep for a wall-mounted toilet or at least 59 inches deep for a floor-mounted toilet, such that the centerline of the toilet is exactly 18 inches from the near side wall or partition, and there is at least 9 inches of toe clearance above the floor at the front partition if the stall is no more than 60 inches deep. Standards §§ 4.1.3(11), 4.22.4, 4.17, Fig. 30.
(4) The toilet is inaccessible because the top of the seat is 16 inches above the finished floor. Provide a toilet with a seat that is 17 to 19 inches above the finished floor. Standards §§ 4.1.3(11), 4.22.4, 4.16.3, 4.17.2, Fig. 30(d).
(5) The toilet is inaccessible because its centerline is 24 ½ inches from the side wall. Provide a toilet with a centerline that is 18 inches from the near side wall. Standards §§ 4.1.3(11), 4.22.4, 4.17.3, Fig. 30.
(6) Men´s Shower Stall. The shower is inaccessible because it is not configured correctly. Provide a shower in this room that is exactly 36 inches wide and 36 inches deep with a 48 inch long and 36 inch wide clear floor space alongside the shower opening, and an L-shaped shower seat mounted on the wall opposite the controls and extending the full depth of the stall; OR a shower that is at least 30 inches deep and 60 inches wide with no curb or threshold and with a 36 inch deep and 60 inch wide clear floor space at the shower opening. Ensure that the shower has grab bars, controls, a shower spray unit, and a seat, curb, and enclosure, if provided, that comply fully with the Standards and with Figs. 35, 36, and 37, as applicable. Standards §§ 4.1.3(11), 4.21, Figs. 35, 36, 37.
ii. Women´s Locker Room
(1) The toilet stall is inaccessible because there is insufficient clear floor space. Provide a toilet stall that is at least 60 inches wide and at least 56 inches deep for a wall-mounted toilet or at least 59 inches deep for a floor-mounted toilet, such that the centerline of the toilet is exactly 18 inches from the near side wall or partition, and there is at least 9 inches of toe clearance above the floor at the front partition if the stall is no more than 60 inches deep. Standards §§ 4.1.3(11), 4.22.4, 4.17, Fig. 30.
(2) The toilet is inaccessible because the top of the seat is 16 inches above the finished floor. Provide a toilet with a seat that is 17 to 19 inches above the finished floor. Standards §§ 4.1.3(11), 4.22.4, 4.16.3, 4.17.2, Fig. 30(d).
(3) The toilet is inaccessible because its centerline is 24 ½ inches from the side wall. Provide a toilet with a centerline that is 18 inches from the near side wall. Standards §§ 4.1.3(11), 4.22.4, 4.17.3, Fig. 30.
(4) The toilet paper dispenser is inaccessible because it is mounted on the wall opposite the side grab bar. Provide a toilet paper dispenser that is mounted with its top at least 1½ inches under the side grab bar and 36 inches or less from the rear wall and is centered at least 19 inches above the finished floor. Standards §§ 4.1.3(11), 4.22.4, 4.17.3, Fig. 30(d).
(5) Shower Stall. The shower in the women´s locker room is inaccessible because it is not configured correctly. Provide a shower in this room that is exactly 36 inches wide and 36 inches deep with a 48 inch long and 36 inch wide clear floor space alongside the shower opening, and an L-shaped shower seat mounted on the wall opposite the controls and extending the full depth of the stall; OR a shower that is at least 30 inches deep and 60 inches wide with no curb or threshold and with a 36 inch deep and 60 inch wide clear floor space at the shower opening. Ensure that the shower has grab bars, controls, a shower spray unit, and a seat, curb, and enclosure, if provided, that comply fully with the Standards and with Figs. 35, 36, and 37, as applicable. Standards §§ 4.1.3(11), 4.21, Figs. 35, 36, 37.
d. Exterior Accessible Routes (existing). The routes from the parking lot to the old picnic shelter, tennis courts, playground, baseball field, and picnic pavilion, are inaccessible because the surface is not stable, firm, or slip resistant. Provide at least one accessible route within the boundary of the site connecting these elements that, to the maximum extent feasible, coincides with the route for the general public. The accessible route must have a minimum clear width of 36 inches, or a minimum clear width of 42 inches if there is a turn around an obstruction less than 48 inches wide; have passing spaces at least 60 inches by 60 inches at least every 200 feet; have a minimum clear headroom of 80 inches; have a surface that is firm, stable, and slip resistant; have, in the absence of a curb ramp, ramp, elevator, or platform lift, no level changes in excess of ½ inch vertically; and have a running slope of less than 5% (or have been constructed as a fully accessible ramp) and a cross slope of less than 2%. Standards §§ 4.3, 4.5, Fig. 7.
e. Picnic Shelter (existing). The picnic tables are inaccessible because none provides adequate knee. Provide at least one picnic table on an accessible route such that there is knee space at the table at least 27 inches high, 30 inches wide, and 19 inches deep, and such that the height of the top of the table is between 28 inches and 34 inches above the ground. Standards §§ 4.32.3, 4.32.4.
f. Picnic Pavilion (existing). The picnic tables are inaccessible because none provides adequate knee clearance. Provide at least one picnic table on an accessible route such that there is knee space at the table at least 27 inches high, 30 inches wide, and 19 inches deep, and such that the height of the top of the table is between 28 inches and 34 inches above the ground. Standards §§ 4.32.3, 4.32.4.
g. At the toilet rooms located at the picnic pavilion, the County will provide an accessible portable toilet, on an accessible route, as a temporary measure, until the County builds a permanent accessible single user toilet room.
h. Men´s Toilet Room at Picnic Pavilion (existing) - Within 60 months of the date of this agreement, the County will make the following changes to the men´s toilet room at the picnic pavilion in Selden Park:
i. The toilet room sign is mounted on the door and does not have raised or Braille characters. Provide a toilet room sign with raised and Braille characters mounted on the wall adjacent to the latch side of the door with the centerline of the sign at 60 inches above the finished floor and situated such that a person can approach within 3 inches of the sign without encountering an obstruction or standing within a door swing. Standards §§ 4.1.2(7)(d), 4.30.1, 4.30.4, 4.30.5, 4.30.6.
ii. The door is inaccessible because knob hardware is used. Provide a door with hardware that is easy to grasp with one hand and that does not require tight grasping, pinching, or twisting of the wrist to operate. Lever-operated mechanisms, push-type mechanisms, and U-shaped handles are acceptable designs. Standards § 4.13.9.
iii. The toilet room door swings into the required clear floor space at the lavatory. Ensure that no door swings into the required clear floor space at any accessible fixture. Standards § 4.22.2.
iv. The lavatory is inaccessible because the hardware requires tight grasping, pinching, or twisting of the wrist to operate. Provide a lavatory with a faucet that can be operated with 5 pounds of force or less and can be used with one hand and without tight grasping, pinching, or twisting of the wrist (lever-operated, push-type, and electronically controlled mechanisms are examples of acceptable designs). Standards §§ 4.19.5, 4.27.4.
v. The urinal is inaccessible because the rim is mounted 18 inches above the finished floor and the controls are mounted 46 inches above the finished floor. Provide a urinal with an elongated rim mounted 17 inches or less above the finished floor, a clear floor space of at least 30 inches wide and 48 inches deep centered on the urinal, and a flush control height of 44 inches or less above the finished floor. Standards §§ 4.18.2, 4.18.3, 4.18.4.
vi. An accessible toilet paper dispenser has not been provided. Provide a toilet paper dispenser that is mounted with its top at least 1½ inches under the side grab bar and 36 inches or less from the rear wall and is centered at least 19 inches above the finished floor. Standards § 4.17.3, Fig. 30(d).
vii. No rear grab bar is provided at the toilet. Provide a rear grab bar that is at least 36 inches in overall length, with the closer end no more than 6 inches from the side wall; mounted 33 to 36 inches above the finished floor; with a diameter between 1¼ and 1½ inches; with 1½ inches between the grab bar and the wall; and at least 1½ inches between the grab bar and any other object, such as a toilet seat cover dispenser. Standards §§ 4.17.6, 4.26.2, Fig. 30.
viii. The side grab bar at the toilet is inaccessible because its overall length is 36 inches and it is mounted 30 inches above the finished floor. Provide a side grab bar that is at least 40 inches in overall length, with the far end mounted at least 52 inches from the rear wall and the closer end 12 inches or less from the rear wall, and mounted between 33 and 36 inches above the finished floor. Standards § 4.17.6, Figs. 30(a), (d).
i. Women´s Toilet Room at Picnic Pavilion (existing) - Within 60 months of the date of this agreement, the County will make the following changes to the women´s toilet room at the picnic pavilion in Selden Park:
i. The toilet room sign is mounted on the door and does not have raised or Braille characters. Provide a toilet room sign with raised and Braille characters mounted on the wall adjacent to the latch side of the door with the centerline of the sign at 60 inches above the finished floor and situated such that a person can approach within 3 inches of the sign without encountering an obstruction or standing within a door swing. Standards §§ 4.1.2(7)(d), 4.30.1, 4.30.4, 4.30.5, 4.30.6.
ii. No rear grab bar has been provided at the toilet. Provide a rear grab bar that is at least 36 inches in overall length, with the closer end no more than 6 inches from the side wall; mounted 33 to 36 inches above the finished floor; with a diameter between 1¼ and 1½ inches; with 1½ inches between the grab bar and the wall; and at least 1½ inches between the grab bar and any other object, such as a toilet seat cover dispenser. Standards §§ 4.17.6, 4.26.2, Fig. 30.
iii. The toilet is inaccessible because the flush control is on the closed side. Provide a flush control mounted on the "open" side of the toilet´s clear floor space; 44 inches or less above the finished floor; and requiring a maximum of 5 pounds of force to operate; or provide an automatic flush device. Standards §§ 4.16.5, 4.17.2, 4.27.4.
iv. The toilet is inaccessible because the top of the seat is 16 inches above the finished floor. Provide a toilet with a seat that is 17 to 19 inches above the finished floor. Standards §§ 4.16.3, 4.17.2, Fig. 30(d).
v. The side grab bar at the toilet is inaccessible because its overall length is 36 inches. Provide a side grab bar that is at least 40 inches in overall length, with the far end mounted at least 52 inches from the rear wall and the closer end 12 inches or less from the rear wall. Standards § 4.17.6, Figs. 30(a), (d).
vi. The toilet is inaccessible because insufficient clear floor space has been provided. Provide clear floor space that complies with Fig. 30 at the toilet. Standards § 4.17.3, Fig. 30.
vii. No accessible toilet paper dispenser has been provided. Provide a toilet paper dispenser that is mounted with its top at least 1½ inches under the side grab bar and 36 inches or less from the rear wall and is centered at least 19 inches above the finished floor. Standards § 4.17.3, Fig. 30(d).
viii. The lavatory is inaccessible because the hardware requires tight grasping, pinching, or twisting of the wrist to operate. Provide a lavatory with a faucet that can be operated with 5 pounds of force or less and can be used with one hand and without tight grasping, pinching, or twisting of the wrist (lever-operated, push-type, and electronically controlled mechanisms are examples of acceptable designs). Standards §§ 4.19.5, 4.27.4.
4. Within 36 months of the effective date of this agreement, the County will make the following modifications to Ballard Park:
a. No van accessible space has been provided. On the shortest accessible route to the accessible entrance, provide one van accessible space designated as reserved for people with disabilities. Ensure that van accessible spaces are a minimum of 96 inches wide and served by access aisles at least 96 inches wide. At all spaces designated as reserved for persons with disabilities, provide vertical signs with the International Symbol of Accessibility located such that they cannot be obstructed by parked vehicles. At van accessible spaces, provide an additional "Van-Accessible" sign located below the International Symbol of Accessibility. Ensure that all spaces and access aisles for persons with disabilities are flat and level, with slopes and cross-slopes not exceeding 2% in all directions, and that their surfaces are firm, stable, and slip-resistant. Standards §§ 4.1.2(5), 4.6, 4.30.7(1).
b. Employee Single-User Toilet Room in Concession Stand Building
i. The toilet room lacks an accessible sign. Provide a toilet room sign with raised and Braille characters mounted on the wall adjacent to the latch side of the door with the centerline of the sign 60 inches above the finished floor and situated such that a person can approach within 3 inches of the sign without encountering an obstruction or standing within a door swing. Standards §§ 4.1.2(7)(d), 4.30.1, 4.30.4, 4.30.5, 4.30.6.
ii. The toilet is inaccessible because its centerline is 20 ½ inches from the side wall. Provide a toilet with a centerline that is 18 inches from the near side wall. Standards §§ 4.1.3(11), 4.22.4, 4.16.2, Fig. 28.
iii. The toilet paper dispenser is inaccessible because it is mounted 39 inches from the rear wall. Provide a toilet paper dispenser that is mounted within reach, with its top at least 1½ inches under the side grab bar, and centered at least 19 inches above the finished floor. Standards §§ 4.1.3(11), 4.22.4, 4.16.6, Fig. 29(b).
c. Women´s Public Toilet Room with Stalls
i. The toilet room sign is not mounted on the latch side of the door. Provide a toilet room sign with raised and Braille characters mounted on the wall adjacent to the latch side of the door with the centerline of the sign 60 inches above the finished floor and situated such that a person can approach within 3 inches of the sign without encountering an obstruction or standing within a door swing. Standards §§ 4.1.2(7)(d), 4.30.1, 4.30.4, 4.30.5, 4.30.6.
ii. The lavatory is inaccessible because the top of the lavatory is mounted 35 inches above the finished floor, the bottom edge of the apron is mounted 27 inches above the finished floor, and it lacks adequate knee and toe clearance. Provide a lavatory with the top of its rim or counter 34 inches or less above the finished floor; the bottom edge of the apron at least 29 inches above the finished floor; and knee and toe clearances that comply with Fig. 31. Standards §§ 4.1.3(11), 4.22.6, 4.19.2, Fig. 31.
iii. The toilet paper dispenser is inaccessible because it is mounted 38 ½ inches from the rear wall and its top is ½ inch below the side grab bar, impeding the use of the grab bar. Provide a toilet paper dispenser that is mounted within reach, with its top at least 1½ inches under the side grab bar, and centered at least 19 inches above the finished floor. Standards §§ 4.1.3(11), 4.22.4, 4.16.6, Fig. 29(b).
iv. No accessible coat hook has been provided. Provide a coat hook at a maximum height above the finished floor of 48 inches for a forward approach or 54 inches for a side approach and that is accompanied by clear floor space of 30 by 48 inches that allows a forward or parallel approach by a person using a wheelchair. Standards §§ 4.1.3(12)(a), 4.25.2, 4.25.3, 4.2.4, 4.2.5, 4.2.6.
d. Men´s Public Toilet Room with Stalls
i. The toilet room sign is not mounted on the latch side of the door. Provide a toilet room sign with raised and Braille characters mounted on the wall adjacent to the latch side of the door with the centerline of the sign 60 inches above the finished floor and situated such that a person can approach within 3 inches of the sign without encountering an obstruction or standing within a door swing. Standards §§ 4.1.2(7)(d), 4.30.1, 4.30.4, 4.30.5, 4.30.6.
ii. The lavatory is inaccessible because the top of the lavatory is mounted 35½ inches above the finished floor and the bottom edge of its apron is 28 inches above the finished floor. Provide a lavatory with the top of its rim or counter 34 inches or less above the finished floor; the bottom edge of the apron at least 29 inches above the finished floor; and knee and toe clearances that comply with Fig. 31. Standards §§ 4.1.3(11), 4.22.6, 4.19.2, Fig. 31.
iii. No accessible mirror has been provided. Provide a mirror with the bottom edge of its reflecting surface no more than 40 inches above the finished floor. Standards §§ 4.1.3(11), 4.22.6, 4.19.6.
iv. The urinal is inaccessible because the rim is 19 inches above the finished floor. Provide a urinal with an elongated rim mounted 17 inches or less above the finished floor, a clear floor space of at least 30 inches wide and 48 inches deep centered on the urinal, and a flush control height of 44 inches or less above the finished floor. Standards §§ 4.1.3(11), 4.22.5, 4.18.2, 4.18.3, 4.18.4.
v. The toilet is inaccessible because the flush control is on the closed side. The toilet is inaccessible Provide a flush control mounted on the "open" side of the toilet´s clear floor space; 44 inches or less above the finished floor; and requiring a maximum of 5 pounds of force to operate; or provide an automatic flush device. Standards §§ 4.1.3(11), 4.22.4, 4.16.5, 4.17.2, 4.27.4.
vi. The toilet paper dispenser is inaccessible because it is mounted 40 inches from the rear wall, and its top is ½ inch below the side grab bar, interfering with the use of the grab bar. Provide a toilet paper dispenser that is mounted with its top at least 1½ inches under the side grab bar and 36 inches or less from the rear wall and is centered at least 19 inches above the finished floor. Standards §§ 4.1.3(11), 4.22.4, 4.17.3, Fig. 30(d).
vii. No accessible coat hook has been provided. Provide a coat hook at a maximum height above the finished floor of 48 inches for a forward approach or 54 inches for a side approach and that is accompanied by clear floor space of 30 by 48 inches that allows a forward or parallel approach by a person using a wheelchair. Standards §§ 4.1.3(12)(a), 4.25.2, 4.25.3, 4.2.4, 4.2.5, 4.2.6.
e. The drinking fountain protrudes into the walkway and would not be detectable to a blind person using a cane. Provide a circulation path at this location such that no objects with their bottom leading edges measuring between 27 inches and 80 inches above the finished floor protrude more than 4 inches into walks, halls, corridors, passageways, or aisles. Free-standing objects mounted on posts or pylons may overhang 12 inches maximum from 27 inches to 80 inches above the ground or finished floor. Providing a cane-detectable barrier is an acceptable solution. Standards §§ 4.1.2(3), 4.4.
f. Accessible Routes
i. Ballard Tennis Court. No accessible route has been provided from the parking lot to the tennis court. Provide at least one accessible route within the boundary of the site connecting these elements that, to the maximum extent feasible, coincides with the route for the general public. The accessible route must have a minimum clear width of 36 inches, or a minimum clear width of 42 inches if there is a turn around an obstruction less than 48 inches wide; have passing spaces at least 60 inches by 60 inches at least every 200 feet; have a minimum clear headroom of 80 inches; have a surface that is firm, stable, and slip resistant; have, in the absence of a curb ramp, ramp, elevator, or platform lift, no level changes in excess of ½ inch vertically; and have a running slope of less than 5% (or have been constructed as a fully accessible ramp) and a cross slope of less than 2%. Standards §§ 4.1.3(1), 4.3, 4.5, Fig. 7.
ii. Ball Fields, Bleachers, and Dugout. The route from the parking lot to the ball fields, bleachers, and dugouts are inaccessible because the surface, which consists of grass and a dirt road, is not firm, stable, and slip resistant. Provide at least one accessible route within the boundary of the site connecting these elements that, to the maximum extent feasible, coincides with the route for the general public. The accessible route must have a minimum clear width of 36 inches, or a minimum clear width of 42 inches if there is a turn around an obstruction less than 48 inches wide; have passing spaces at least 60 inches by 60 inches at least every 200 feet; have a minimum clear headroom of 80 inches; have a surface that is firm, stable, and slip resistant; have, in the absence of a curb ramp, ramp, elevator, or platform lift, no level changes in excess of ½ inch vertically; and have a running slope of less than 5% (or have been constructed as a fully accessible ramp) and a cross slope of less than 2%. Standards §§ 4.1.3(1), 4.3, 4.5, Fig. 7.
g. Community Room Building (existing)
i. Parking. Accessible parking has not been provided for the community room building. On the shortest accessible route to the accessible entrance, provide one van accessible space designated as reserved for people with disabilities. Ensure that van accessible spaces are a minimum of 96 inches wide and served by access aisles at least 96 inches wide. At all spaces designated as reserved for persons with disabilities, provide vertical signs with the International Symbol of Accessibility located such that they cannot be obstructed by parked vehicles. At van accessible spaces, provide an additional "Van-Accessible" sign located below the International Symbol of Accessibility. Ensure that all spaces and access aisles for persons with disabilities are flat and level, with slopes and cross-slopes not exceeding 2% in all directions, and that their surfaces are firm, stable, and slip-resistant. Standards §§ 4.1.2(5), 4.6, 4.30.7(1).
ii. Entrance. The entry door into the community room is inaccessible because there is a 1½ inch change in level at the threshold to the door. Provide an accessible door with a threshold that is no greater than ¼ inch, or is no greater than ½ inch and is beveled with a slope no greater than 1:2. Standards §§ 4.13.8, 4.5.2.
iii. Women´s and Men´s Toilet Rooms (Both Exterior and Interior). All of the toilet rooms for the community building contain a number of inaccessible elements and are not accessible to people with disabilities. Provide accessible toilet rooms such that all of the rooms´ elements, including signage, door, door hardware, clear floor space, water closet, stall size and arrangement, stall door, urinal (if provided), grab bars, lavatory, mirror, controls, and dispensers, comply with the Standards. Standards §§ 4.13, 4.16, 4.17, 4.18, 4.19, 4.26, 4.27, 4.30, Fig. 30.
5. Within 12 months of the effective date of this agreement, the County will complete the following modifications to Fire Station #7:
a. Parking. The parking reserved for persons with disabilities is inaccessible because the access aisle is less than 96 inches wide. Provide a van accessible parking space that is a minimum of 96 inches wide and served by access aisles at least 96 inches wide. Standards §§ 4.1.2(5), 4.6.3. and Fig. 9.
b. Women´s Single User Toilet Room and Shower
i. The toilet room sign is not mounted on the latch side of the door. Provide a toilet room sign with raised and Braille characters mounted on the wall adjacent to the latch side of the door with the centerline of the sign 60 inches above the finished floor and situated such that a person can approach within 3 inches of the sign without encountering an obstruction or standing within a door swing. Standards §§ 4.1.2(7)(d), 4.30.1, 4.30.4, 4.30.5, 4.30.6.
ii. The door is inaccessible because the force required to open the door is 12 pounds. Provide a door that requires no more than 5 pounds of force to open. Standards §§ 4.1.3(7)(b), 4.13.11(2)(b).
iii. No accessible coat hook has been provided. Provide a coat hook at a maximum height above the finished floor of 48 inches for a forward approach or 54 inches for a side approach and that is accompanied by clear floor space of 30 by 48 inches that allows a forward or parallel approach by a person using a wheelchair. Standards §§ 4.1.3(12)(a), 4.25.2, 4.25.3, 4.2.4, 4.2.5, 4.2.6.
iv. The lavatory is inaccessible because the bottom of its apron is 28 inches above the finished floor. Provide a lavatory with the top of its rim or counter 34 inches or less above the finished floor; the bottom edge of the apron at least 29 inches above the finished floor; and knee and toe clearances that comply with Fig. 31. Standards §§ 4.1.3(11), 4.22.6, 4.19.2, Fig. 31.
v. The shower is inaccessible because it is 36 inches deep by 35 inches wide; the grab bar is mounted on the rear and side wall at 43 inches above the finished floor, there is no clear floor space with a 12 inch overhang on the seat side to allow a transfer from a wheelchair; and the controls are 48½ inches above the finished floor. Provide a shower in this room that is exactly 36 inches wide and 36 inches deep with a 48 inch long and 36 inch wide clear floor space alongside the shower opening, and an L-shaped shower seat mounted on the wall opposite the controls and extending the full depth of the stall; OR a shower that is at least 30 inches deep and 60 inches wide with no curb or threshold and with a 36 inch deep and 60 inch wide clear floor space at the shower opening. Ensure that the shower has grab bars, controls, a shower spray unit, and a seat, curb, and enclosure, if provided, that comply fully with the Standards and with Figs. 35, 36, and 37, as applicable. Standards §§ 4.1.3(11), 4.21, Figs. 35, 36, 37.
c. Men´s Toilet Room with Stalls and Shower
i. The toilet room sign is not mounted on the latch side of the door. Provide a toilet room sign with raised and Braille characters mounted on the wall adjacent to the latch side of the door with the centerline of the sign 60 inches above the finished floor and situated such that a person can approach within 3 inches of the sign without encountering an obstruction or standing within a door swing. Standards §§ 4.1.2(7)(d), 4.30.1, 4.30.4, 4.30.5, 4.30.6.
ii. The door is inaccessible because the force required to open the door is 12 pounds. Provide a door that requires no more than 5 pounds of force to open. Standards §§ 4.1.3(7)(b), 4.13.11(2)(b).
iii. No accessible mirror has been provided. Provide a mirror with the bottom edge of its reflecting surface no more than 40 inches above the finished floor. Standards §§ 4.1.3(11), 4.22.6, 4.19.6.
iv. The urinal is inaccessible because the rim is mounted 24 ½ inches above the finished floor and the controls are mounted 45 inches above the finished floor. Provide a urinal with an elongated rim mounted 17 inches or less above the finished floor, a clear floor space of at least 30 inches wide and 48 inches deep centered on the urinal, and a flush control height of 44 inches or less above the finished floor. Standards §§ 4.1.3(11), 4.22.5, 4.18.2, 4.18.3, 4.18.4.
v. The lavatory is inaccessible because the bottom of the apron is 28 inches above the finished floor. Provide a lavatory with the top of its rim or counter 34 inches or less above the finished floor; the bottom edge of the apron at least 29 inches above the finished floor; and knee and toe clearances that comply with Fig. 31. Standards §§ 4.1.3(11), 4.22.6, 4.19.2, Fig. 31.
vi. No accessible coat hook has been provided. Provide a coat hook at a maximum height above the finished floor of 48 inches for a forward approach or 54 inches for a side approach and that is accompanied by clear floor space of 30 by 48 inches that allows a forward or parallel approach by a person using a wheelchair. Standards §§ 4.1.3(12)(a), 4.25.2, 4.25.3, 4.2.4, 4.2.5, 4.2.6.
vii. The side grab bar at the toilet is inaccessible because its closer end is mounted 15 inches from the rear wall. Provide a side grab bar that is at least 40 inches in overall length, with the far end mounted at least 52 inches from the rear wall and the closer end 12 inches or less from the rear wall; mounted 33 to 36 inches above the finished floor; with a diameter between 1¼ and 1½ inches; with 1½ inches between the grab bar and the wall; and at least 1½ inches between the grab bar and any object beside or below it and at least 18 inches between the grab bar and any object above it. Standards §§ 4.1.3(11), 4.22.4, 4.17.6, 4.26.2, Figs. 30(a), (d), 39.
viii. The rear grab bar at the toilet is inaccessible because its closer end is mounted 12 inches from the side wall. Provide a rear grab bar that is at least 36 inches in overall length, with the closer end no more than 6 inches from the side wall; mounted 33 to 36 inches above the finished floor; with a diameter between 1¼ and 1½ inches; with 1½ inches between the grab bar and the wall; and at least 1½ inches between the grab bar and any object beside or below it and at least 18 inches between the grab bar and any object above it. Standards §§ 4.1.3(11), 4.22.4, 4.17.6, 4.26.2, Figs. 30, 39.
ix. The shower in is inaccessible because the stall dimensions are 36 inches deep by 39 inches wide; no grab bars have been provided; there is no clear floor space with a 12 inch overhang on the seat side to allow a transfer from a wheelchair; and the controls are mounted 49 inches above the finished floor. Provide a shower in this room that is exactly 36 inches wide and 36 inches deep with a 48 inch long and 36 inch wide clear floor space alongside the shower opening, and an L-shaped shower seat mounted on the wall opposite the controls and extending the full depth of the stall; OR a shower that is at least 30 inches deep and 60 inches wide with no curb or threshold and with a 36 inch deep and 60 inch wide clear floor space at the shower opening. Ensure that the shower has grab bars, controls, a shower spray unit, and a seat, curb, and enclosure, if provided, that comply fully with the Standards and with Figs. 35, 36, and 37, as applicable. Standards §§ 4.1.3(11), 4.21, Figs. 35, 36, 37.
6. Within 12 months of the effective date of this Agreement, the County will complete the following modifications to Fire Station #8:
a. Men´s Locker Room
i. The lavatory is inaccessible because the bottom of the apron is 26 inches above the finished floor. Provide a lavatory with the top of its rim or counter 34 inches or less above the finished floor; the bottom edge of the apron at least 29 inches above the finished floor; and knee and toe clearances that comply with Fig. 31. Standards §§ 4.1.3(11), 4.22.6, 4.19.2, Fig. 31.
ii. The urinal is inaccessible because the flush control is mounted 46 inches above the finished floor. Provide a urinal with an elongated rim mounted 17 inches or less above the finished floor, a clear floor space of at least 30 inches wide and 48 inches deep centered on the urinal, and a flush control height of 44 inches or less above the finished floor. Standards §§ 4.1.3(11), 4.22.5, 4.18.2, 4.18.3, 4.18.4.
iii. The shower is inaccessible because there is no clear floor space with a 12 inch overhang on the seat side to allow a transfer from a wheelchair. Provide a shower in this room that is exactly 36 inches wide and 36 inches deep with a 48 inch long and 36 inch wide clear floor space alongside the shower opening, and an L-shaped shower seat mounted on the wall opposite the controls and extending the full depth of the stall; OR a shower that is at least 30 inches deep and 60 inches wide with no curb or threshold and with a 36 inch deep and 60 inch wide clear floor space at the shower opening. Ensure that the shower has grab bars, controls, a shower spray unit, and a seat, curb, and enclosure, if provided, that comply fully with the Standards and with Figs. 35, 36, and 37, as applicable. Standards §§ 4.1.3(11), 4.21, Figs. 35, 36, 37.
b. Women´s Locker Room
i. No accessible mirror has been provided. Provide a mirror with the bottom edge of its reflecting surface no more than 40 inches above the finished floor. Standards §§ 4.1.3(11), 4.22.6, 4.19.6.
ii. The lavatory is inaccessible because the bottom of the apron is 26 inches above the finished floor. Provide a lavatory with the top of its rim or counter 34 inches or less above the finished floor; the bottom edge of the apron at least 29 inches above the finished floor; and knee and toe clearances that comply with Fig. 31. Standards §§ 4.1.3(11), 4.22.6, 4.19.2, Fig. 31.
iii. The rear grab bar at the toilet is inaccessible because its overall length is 30 inches. Provide a rear grab bar that is at least 36 inches in overall length with the closer end no more than 6 inches from the side wall. Standards §§ 4.1.3(11), 4.22.4, 4.17.6, Fig. 30.
iv. The shower in is inaccessible because it is 39 inches wide by 39 inches deep, and it does not have sufficient clear floor space which provides a 12 inch overhang on the seat side to allow for a transfer from a wheelchair. Provide a shower in this room that is exactly 36 inches wide and 36 inches deep with a 48 inch long and 36 inch wide clear floor space alongside the shower opening, and an L-shaped shower seat mounted on the wall opposite the controls and extending the full depth of the stall; OR a shower that is at least 30 inches deep and 60 inches wide with no curb or threshold and with a 36 inch deep and 60 inch wide clear floor space at the shower opening. Ensure that the shower has grab bars, controls, a shower spray unit, and a seat, curb, and enclosure, if provided, that comply fully with the Standards and with Figs. 35, 36, and 37, as applicable. Standards §§ 4.1.3(11), 4.21, Figs. 35, 36, 37.
7. Within 36 months of the effective date of this agreement, the County will make the following modifications to the Public Safety Building:
a. Parking. None of the parking reserved for persons with disabilities has van accessible signage. At van accessible spaces, provide a "Van-Accessible" sign located below the International Symbol of Accessibility such that the sign cannot be obstructed by vehicles parked in the space. Standards §§ 4.1.2(5), 4.6.4, 4.30.7(1).
b. Counters
i. The front counter in the lobby is inaccessible because the top is 42½ inches high above the finished floor. Provide a counter on an accessible route such that a portion of the counter is at least 36 inches wide and no more than 36 inches above the finished floor, or provide an auxiliary counter with a maximum height of 36 inches in close proximity to the main counter, or provide equivalent facilitation. Equivalent facilitation may be provided in the form of a folding shelf attached to the main counter, an auxiliary table nearby, a clip board made available to the public, or other means. Standards §§ 4.1.1(2), 7.2(2), 4.1.3(1), 4.3.
ii. The records counter is inaccessible because the top is 42 inches high above the finished floor. Provide a counter on an accessible route such that a portion of the counter is at least 36 inches wide and no more than 36 inches above the finished floor, or provide an auxiliary counter with a maximum height of 36 inches in close proximity to the main counter, or provide equivalent facilitation. Equivalent facilitation may be provided in the form of a folding shelf attached to the main counter, an auxiliary table nearby, a clip board made available to the public, or other means. Standards §§ 4.1.1(2), 7.2(2), 4.1.3(1), 4.3.
c. Women´s Single User Toilet Room (First Floor)
i. The rear grab bar at the toilet is inaccessible because its overall length is 30 inches. Provide a rear grab bar that is at least 36 inches in overall length with the closer end no more than 6 inches from the side wall. Standards §§ 4.1.3(11), 4.22.4, 4.16.4, Fig. 29.
d. Men´s Single User Toilet Room (First Floor)
i. The side grab bar at the toilet is inaccessible because it is mounted 32 ½ inches above the finished floor. Provide grab bars that are mounted between 33 and 36 inches above the finished floor. Standards §§ 4.1.3(11), 4.22.4, 4.16.4, Fig. 29.
ii. The rear grab bar at the toilet is inaccessible because its overall length is 24 inches. Provide a rear grab bar that is at least 36 inches in overall length with the closer end no more than 6 inches from the side wall. Standards §§ 4.1.3(11), 4.22.4, 4.16.4, Fig. 29.
iii. No accessible mirror has been provided. Provide a mirror with the bottom edge of its reflecting surface no more than 40 inches above the finished floor. Standards §§ 4.1.3(11), 4.22.6, 4.19.6.
e. Women´s Locker Room
i. The entrance door from the hallway is inaccessible because the force required to open the door is 11 pounds. Provide a door that requires no more than 5 pounds of force to open. Standards §§ 4.1.3(7)(b), 4.13.11(2)(b).
ii. The entrance door from the locker room into the gym is inaccessible because the force required to open the door is 10 pounds. Provide a door that requires no more than 5 pounds of force to open. Standards §§ 4.1.3(7)(b), 4.13.11(2)(b).
iii. No accessible mirror has been provided. Provide a mirror with the bottom edge of its reflecting surface no more than 40 inches above the finished floor. Standards §§ 4.1.3(11), 4.22.6, 4.19.6.
iv. Showers. There is no designated accessible shower in the women´s locker room. Provide a shower in this room that is exactly 36 inches wide and 36 inches deep with a 48 inch long and 36 inch wide clear floor space alongside the shower opening, and an L-shaped shower seat mounted on the wall opposite the controls and extending the full depth of the stall; OR a shower that is at least 30 inches deep and 60 inches wide with no curb or threshold and with a 36 inch deep and 60 inch wide clear floor space at the shower opening. Ensure that the shower has grab bars, controls, a shower spray unit, and a seat, curb, and enclosure, if provided, that comply fully with the Standards and with Figs. 35, 36, and 37, as applicable. Standards §§ 4.1.3(11), 4.21, Figs. 35, 36, 37.
v. Toilet. The toilet is inaccessible because its centerline is 20 inches from the side wall. Provide a toilet with a centerline that is 18 inches from the near side wall. Standards §§ 4.1.3(11), 4.22.4, 4.17.3, Fig. 30.
vi. No accessible coat hook has been provided. Provide a coat hook at a maximum height above the finished floor of 48 inches for a forward approach or 54 inches for a side approach and that is accompanied by clear floor space of 30 by 48 inches that allows a forward or parallel approach by a person using a wheelchair. Standards §§ 4.1.3(12)(a), 4.25.2, 4.25.3, 4.2.4, 4.2.5, 4.2.6.
vii. The benches in the women´s locker room are not 24 inches wide, and they are not fixed to the wall. Provide a 24 inch by 48 inch bench fixed to the wall along the bench´s longer dimension. Ensure that the bench has sufficient structural strength and is mounted with its surface between 17 inches and 19 inches above the finished floor. Provide clear floor space alongside the bench to allow a person using a wheelchair to make a parallel transfer onto the bench. Standards §§ 4.1.3(21), 4.35.4, 4.26.3.
f. The route throughout the workout room is inaccessible because there is insufficient clearance between the gym equipment. Provide at least one accessible route within the boundary of the site connecting these elements that, to the maximum extent feasible, coincides with the route for the general public. The accessible route must have a minimum clear width of 36 inches, or a minimum clear width of 42 inches if there is a turn around an obstruction less than 48 inches wide; have passing spaces at least 60 inches by 60 inches at least every 200 feet; have a minimum clear headroom of 80 inches; have a surface that is firm, stable, and slip resistant; have, in the absence of a curb ramp, ramp, elevator, or platform lift, no level changes in excess of ½ inch vertically; and have a running slope of less than 5% (or have been constructed as a fully accessible ramp) and a cross slope of less than 2%. Standards §§ 4.1.3(1), 4.3, 4.5, Fig. 7.
g. Men´s Locker Room
i. The entrance door into the locker room from the hallway is inaccessible because the force required to open the door is 14 pounds. Provide a door that requires no more than 5 pounds of force to open. Standards §§ 4.1.3(7)(b), 4.13.11(2)(b).
ii. The entrance door into the locker room from the gym is inaccessible because the force required to open the door is 11 pounds. Provide a door that requires no more than 5 pounds of force to open. Standards §§ 4.1.3(7)(b), 4.13.11(2)(b).
iii. Toilet. The toilet is inaccessible because its centerline is 21 inches from the side wall. Provide a toilet with a centerline that is 18 inches from the near side wall. Standards §§ 4.1.3(11), 4.22.4, 4.17.3, Fig. 30.
iv. The lavatory is inaccessible because the counter is located 35 inches above the finished floor. Provide a lavatory with the top of its rim or counter 34 inches or less above the finished floor; the bottom edge of the apron at least 29 inches above the finished floor; and knee and toe clearances that comply with Fig. 31. Standards §§ 4.1.3(11), 4.22.6, 4.19.2, Fig. 31.
v. No accessible mirror has been provided. Provide a mirror with the bottom edge of its reflecting surface no more than 40 inches above the finished floor. Standards §§ 4.1.3(11), 4.22.6, 4.19.6.
vi. Shower. No designated accessible shower has been provided in the men´s locker room. Provide a shower in this room that is exactly 36 inches wide and 36 inches deep with a 48 inch long and 36 inch wide clear floor space alongside the shower opening, and an L-shaped shower seat mounted on the wall opposite the controls and extending the full depth of the stall; OR a shower that is at least 30 inches deep and 60 inches wide with no curb or threshold and with a 36 inch deep and 60 inch wide clear floor space at the shower opening. Ensure that the shower has grab bars, controls, a shower spray unit, and a seat, curb, and enclosure, if provided, that comply fully with the Standards and with Figs. 35, 36, and 37, as applicable. Standards §§ 4.1.3(11), 4.21, Figs. 35, 36, 37.
vii. The benches in the men´s locker room are not accessible because they are not 24 inches wide and are not fixed to the wall. Provide a 24 inch by 48 inch bench fixed to the wall along the bench´s longer dimension. Ensure that the bench has sufficient structural strength and is mounted with its surface between 17 inches and 19 inches above the finished floor. Provide clear floor space alongside the bench to allow a person using a wheelchair to make a parallel transfer onto the bench. Standards §§ 4.1.3(21), 4.35.4, 4.26.3.
h. Booking Area
i. Women´s Single-User Toilet Room (117)
(1) The side grab bar at the toilet is inaccessible because its closer end is mounted 21 inches from the rear wall. Provide a side grab bar that is at least 40 inches in overall length, with the far end mounted at least 52 inches from the rear wall and the closer end 12 inches or less from the rear wall; mounted 33 to 36 inches above the finished floor; with a diameter between 1¼ and 1½ inches; with 1½ inches between the grab bar and the wall; and at least 1½ inches between the grab bar and any other object, such as the toilet paper dispenser. Standards §§ 4.1.3(11), 4.22.4, 4.16.4, 4.26.2, Fig. 29.
(2) No accessible mirror has been provided. Provide a mirror with the bottom edge of its reflecting surface no more than 40 inches above the finished floor. Standards §§ 4.1.3(11), 4.22.6, 4.19.6.
ii. Men´s Single-User Toilet Room (118). The rear grab bar at the toilet is inaccessible because its overall length is 30 inches. Provide a rear grab bar that is at least 36 inches in overall length with the closer end no more than 6 inches from the side wall. Standards §§ 4.1.3(11), 4.22.4, 4.16.4, Fig. 29.
i. Men´s Toilet Room with Stalls - Room 209
i. The men´s toilet room on the second floor is inaccessible because the force required to open the door is 14 pounds. Provide a door that requires no more than 5 pounds of force to open. Standards §§ 4.1.3(7)(b), 4.13.11(2)(b).
ii. The urinal is inaccessible because there is insufficient clear floor space at the urinal and the controls are located 45 inches above the finished floor. Provide a urinal with an elongated rim mounted 17 inches or less above the finished floor, a clear floor space of at least 30 inches wide and 48 inches deep centered on the urinal, and a flush control height of 44 inches or less above the finished floor. Standards §§ 4.1.3(11), 4.22.5, 4.18.2, 4.18.3, 4.18.4.
j. Women´s Toilet Room with Stalls - Room 210. The door to the women´s toilet room on the second floor is inaccessible because the force required to open the door is 16 pounds. Provide a door that requires no more than 5 pounds of force to open. Standards §§ 4.1.3(7)(b), 4.13.11(2)(b).
k. Women´s Single User Toilet Room - Room 242
i. The door to the women´s single user toilet room on the second floor is inaccessible because the force required to open the door is 15 pounds. Provide a door that requires no more than 5 pounds of force to open. Standards §§ 4.1.3(7)(b), 4.13.11(2)(b).
ii. The toilet is inaccessible because its centerline is 15½ inches from the side wall. Provide a toilet with its centerline 18 inches from the near side wall. Standards §§ 4.1.3(11), 4.22.4, 4.17.3, Fig. 30.
iii. The lavatory is inaccessible because the bottom of the apron is 27 inches above the finished floor. Provide a lavatory with the top of its rim or counter 34 inches or less above the finished floor; the bottom edge of the apron at least 29 inches above the finished floor; and knee and toe clearances that comply with Fig. 31. Standards §§ 4.1.3(11), 4.22.6, 4.19.2, Fig. 31.
8. Within 24 months of the effective date of this agreement, the County will make the following modifications to North Glynn Complex Field House Recreation Center:
a. Men´s Toilet Room with Stalls - Near Field 3
i. The toilet room sign is not mounted on the latch side of the door. Provide a toilet room sign with raised and Braille characters mounted on the wall adjacent to the latch side of the door with the centerline of the sign 60 inches above the finished floor and situated such that a person can approach within 3 inches of the sign without encountering an obstruction or standing within a door swing. Standards §§ 4.1.2(7)(d), 4.30.1, 4.30.4, 4.30.5, 4.30.6.
ii. The toilet room door is inaccessible because the force required to open the door is 15 pounds. Provide a door that requires no more than 5 pounds of force to open. Standards §§ 4.1.3(7)(b), 4.13.11(2)(b).
iii. The lavatory is inaccessible because there is insufficient knee space provided beneath the lavatory and the top of the counter is 35 inches above the finished floor. Provide a lavatory with the top of its rim or counter 34 inches or less above the finished floor; the bottom edge of the apron at least 29 inches above the finished floor; and knee and toe clearances that comply with Fig. 31. Standards §§ 4.1.3(11), 4.22.6, 4.19.2, Fig. 31.
iv. The rear grab bar at the toilet is inaccessible because its overall length is 24 inches. Provide a rear grab bar that is at least 36 inches in overall length with the closer end no more than 6 inches from the side wall. Standards §§ 4.1.3(11), 4.22.4, 4.16.4, Fig. 29.
v. No accessible coat hook has been provided. Provide a coat hook at a maximum height above the finished floor of 48 inches for a forward approach or 54 inches for a side approach and that is accompanied by clear floor space of 30 by 48 inches that allows a forward or parallel approach by a person using a wheelchair. Standards §§ 4.1.3(12)(a), 4.25.2, 4.25.3, 4.2.4, 4.2.5, 4.2.6.
b. Women´s Toilet Room - Near Field 3
i. The toilet room sign is inaccessible because it is not mounted on the latch side of the door. Provide a toilet room sign with raised and Braille characters mounted on the wall adjacent to the latch side of the door with the centerline of the sign 60 inches above the finished floor and situated such that a person can approach within 3 inches of the sign without encountering an obstruction or standing within a door swing. Standards §§ 4.1.2(7)(d), 4.30.1, 4.30.4, 4.30.5, 4.30.6.
ii. The lavatory is inaccessible because there is insufficient knee space provided beneath the lavatory and the top of the counter is 35 inches above the finished floor. Provide a lavatory with the top of its rim or counter 34 inches or less above the finished floor; the bottom edge of the apron at least 29 inches above the finished floor; and knee and toe clearances that comply with Fig. 31. Standards §§ 4.1.3(11), 4.22.6, 4.19.2, Fig. 31.
iii. No accessible coat hook has been provided. Provide a coat hook at a maximum height above the finished floor of 48 inches for a forward approach or 54 inches for a side approach and that is accompanied by clear floor space of 30 by 48 inches that allows a forward or parallel approach by a person using a wheelchair. Standards §§ 4.1.3(12)(a), 4.25.2, 4.25.3, 4.2.4, 4.2.5, 4.2.6.
iv. The rear grab bar at the toilet is inaccessible because its overall length is 24 inches. Provide a rear grab bar that is at least 36 inches in overall length with the closer end no more than 6 inches from the side wall. Standards §§ 4.1.3(11), 4.22.4, 4.16.4, Fig. 29.
c. Soccer Field
i. Women´s Toilet Room
(1) The toilet room sign is not mounted on the latch side of the door. Provide a toilet room sign with raised and Braille characters mounted on the wall adjacent to the latch side of the door with the centerline of the sign 60 inches above the finished floor and situated such that a person can approach within 3 inches of the sign without encountering an obstruction or standing within a door swing. Standards §§ 4.1.2(7)(d), 4.30.1, 4.30.4, 4.30.5, 4.30.6.
(2) The lavatory is inaccessible because the bottom of the apron is 27 ½ inches above the finished floor and the counter is 34½ inches above the finished floor. Provide a lavatory with the top of its rim or counter 34 inches or less above the finished floor; the bottom edge of the apron at least 29 inches above the finished floor; and knee and toe clearances that comply with Fig. 31. Standards §§ 4.1.3(11), 4.22.6, 4.19.2, Fig. 31.
(3) The toilet is inaccessible because the flush control is on the closed side. Provide a flush control mounted on the "open" side of the toilet´s clear floor space; 44 inches or less above the finished floor; and requiring a maximum of 5 pounds of force to operate; or provide an automatic flush device. Standards §§ 4.1.3(11), 4.22.4, 4.16.5, 4.17.2, 4.27.4.
ii. Men´s Toilet Room
(1) The toilet room sign is not mounted on the latch side of the door. Provide a toilet room sign with raised and Braille characters mounted on the wall adjacent to the latch side of the door with the centerline of the sign 60 inches above the finished floor and situated such that a person can approach within 3 inches of the sign without encountering an obstruction or standing within a door swing. Standards §§ 4.1.2(7)(d), 4.30.1, 4.30.4, 4.30.5, 4.30.6.
(2) The lavatory is inaccessible because it has insufficient knee space height and depth. Provide a lavatory with the top of its rim or counter 34 inches or less above the finished floor; the bottom edge of the apron at least 29 inches above the finished floor; and knee and toe clearances that comply with Fig. 31. Standards §§ 4.1.3(11), 4.22.6, 4.19.2, Fig. 31.
(3) The urinal is inaccessible because the rim is mounted 24 inches above the finished floor and the controls are 45 inches above the finished floor. Provide a urinal with an elongated rim mounted 17 inches or less above the finished floor, a clear floor space of at least 30 inches wide and 48 inches deep centered on the urinal, and a flush control height of 44 inches or less above the finished floor. Standards §§ 4.1.3(11), 4.22.5, 4.18.2, 4.18.3, 4.18.4.
(4) The toilet is inaccessible because the flush control is on the closed side. Provide a flush control mounted on the "open" side of the toilet´s clear floor space; 44 inches or less above the finished floor; and requiring a maximum of 5 pounds of force to operate; or provide an automatic flush device. Standards §§ 4.1.3(11), 4.22.4, 4.16.5, 4.17.2, 4.27.4.
iii. Drinking Fountain. The drinking fountain protrudes into the walkway and would not be detectable to a blind person using a cane. Provide a circulation path at this location such that no objects with their bottom leading edges measuring between 27 inches and 80 inches above the finished floor protrude more than 4 inches into walks, halls, corridors, passageways, or aisles. Free-standing objects mounted on posts or pylons may overhang 12 inches maximum from 27 inches to 80 inches above the ground or finished floor. Providing a cane-detectable barrier is an acceptable solution. Standards §§ 4.1.2(3), 4.4.
iv. Employee Toilet Room - Single User (Inside Concession Area)
(1) No accessible toilet room sign has been provided. Provide a toilet room sign with raised and Braille characters mounted on the wall adjacent to the latch side of the door with the centerline of the sign 60 inches above the finished floor and situated such that a person can approach within 3 inches of the sign without encountering an obstruction or standing within a door swing. Standards §§ 4.1.2(7)(d), 4.30.1, 4.30.4, 4.30.5, 4.30.6.
(2) No accessible mirror has been provided. Provide a mirror with the bottom edge of its reflecting surface no more than 40 inches above the finished floor. Standards §§ 4.1.3(11), 4.22.6, 4.19.6.
(3) No accessible coat hook has been provided. Provide a coat hook at a maximum height above the finished floor of 48 inches for a forward approach or 54 inches for a side approach and that is accompanied by clear floor space of 30 by 48 inches that allows a forward or parallel approach by a person using a wheelchair. Standards §§ 4.1.3(12)(a), 4.25.2, 4.25.3, 4.2.4, 4.2.5, 4.2.6.
(4) The toilet paper dispenser is inaccessible because it is mounted 38 inches from the rear wall. Provide a toilet paper dispenser that is mounted with its top at least 1½ inches under the side grab bar and 36 inches or less from the rear wall and is centered at least 19 inches above the finished floor. Standards §§ 4.1.3(11), 4.22.4, 4.17.3, Fig. 30(d).
d. Parking. Although the parking lot has a total of 578 parking spaces, there are no van accessible spaces provided and the accessible parking signs are not positioned in front of the designated accessible spaces. On the shortest accessible route to the accessible entrance, provide 2 van accessible spaces and 10 standard spaces designated as reserved for people with disabilities. Ensure that standard accessible spaces are a minimum of 96 inches wide and served by access aisles at least 60 inches wide. Ensure that van accessible spaces are a minimum of 96 inches wide and served by access aisles at least 96 inches wide. At all spaces designated as reserved for persons with disabilities, provide vertical signs with the International Symbol of Accessibility located such that they cannot be obstructed by parked vehicles. At van accessible spaces, provide an additional "Van-Accessible" sign located below the International Symbol of Accessibility. Ensure that all spaces and access aisles for persons with disabilities are flat and level, with slopes and cross-slopes not exceeding 2% in all directions, and that their surfaces are firm, stable, and slip-resistant. Standards §§ 4.1.2(5), 4.6, 4.30.7(1).
e. Parking. The parking reserved for persons with disabilities is inaccessible because the access aisle is less than 96 inches wide. Provide designated van accessible parking spaces that are a minimum of 96 inches wide and served by access aisles at least 96 inches wide. Standards §§ 4.1.2(5)(b), 4.6.3, Fig.9.