ATTACHMENT J: Modifications to Altered Facilities
Please Note: Paragraph 45 of the Settlement Agreement requires that within three months of the effective date of this Agreement, the City provide signage as necessary to comply with 28 C.F.R. § 35.163(b), after having surveyed all facilities that are the subject of this Agreement for the purpose of identifying those that have multiple entrances not all of which are accessible.
In order to ensure that the following spaces and elements in City facilities, in which alterations occurred after January 26, 1992, are readily accessible to and usable by persons with disabilities, the City will take the actions referenced by the alphanumeric code and described in detail in Attachment M to this Settlement Agreement.
|
|||
Item # |
Access Issue |
Required Action |
Completion Date |
---|---|---|---|
1. |
The County will correct the following items at the Senior Activity Center, located at 623 Broad Street: |
|
|
1.1 |
Parking |
|
|
1.1a |
The parking lot is inaccessible because the parking spaces reserved for persons with disabilities do not have access aisles. |
P1 |
18 months |
1.1b |
The parking spaces reserved for persons with disabilities are inaccessible because they lack appropriate vertical signage. |
P6 |
18 months |
1.2 |
Offices and Counters – 1st Floor |
|
|
1.2a |
The Secretary's Counter is inaccessible because its top surface is 42 ½ inches above the finished floor. |
C6 |
18 months |
1.2b |
The Reception Desk at the rear entrance is inaccessible because its top surface is 42 inches above the finished floor. |
C6 |
18 months |
1.2c |
The Board Room Door is inaccessible because it requires 10 pounds of force to open. |
D2 |
18 months |
1.3 |
Auditorium |
|
|
1.3a |
The door is inaccessible because it requires 9 pounds of force to open. |
D2 |
18 months |
1.3b |
The auditorium is inaccessible to people who are hard of hearing because it has no assistive listening system. |
AA5
|
18 months |
1.4 |
Women's Toilet Rooms – with stalls, 1st floor |
|
|
1.4a |
In the toilet room near the front entrance, the door is inaccessible because it requires 9 pounds of force to open. |
D2 |
18 months
|
1.4b |
In the toilet room near the rear parking lot, the door is inaccessible because it requires 8 pounds of force to open. |
D2 |
18 months
|
1.5 |
Men's Toilet Rooms – with stalls, 1st floor |
|
|
1.5a |
Near Front Entrance |
|
|
1.5a.i |
The door is inaccessible because it requires 8 pounds of force to open. |
D2 |
18 months |
1.5a.ii |
The urinal is inaccessible because the rim is 18 ½ inches above the finished floor. |
TR20 |
18 months |
1-5a-iii |
The toilet is inaccessible because its centerline is 19 inches from the side wall. |
SU15 |
18 months |
1.5a.iv |
The toilet is inaccessible because the flush control is on the closed side. |
SU1 |
18 months |
1.5b |
Near Rear Parking Lot |
|
|
1.5b.i |
The door is inaccessible because it requires 9 pounds of force to open. |
D2 |
18 months |
1.5b.ii |
The push side of the door, which is accessed through a front approach and which has both a closer and a latch, is inaccessible because it has only 10 ½ inches of clear space on the latch side. |
D7 |
18 months |
1.5b.iii |
The toilet is inaccessible because the flush control is on the closed side. |
SU1 |
18 months |
1.6 |
Drinking Fountains |
|
|
1.6a |
The drinking fountains throughout the facility protrude into the walkway and are not detectable to blind persons using a cane. |
AR8 |
18 months |
1.7 |
Offices and Rooms – 2nd Floor |
|
|
1.7a |
Alaco Room |
|
|
1.7a.i |
The door is inaccessible because it requires 10 pounds of force to open. |
D2 |
18 months |
1.7a.ii |
The room is inaccessible to people who are hard of hearing because no assistive listening system has been provided. |
AA5
|
18 months |
1.7b |
Lee Anne Room |
|
|
1.7b.i |
The room is inaccessible to people who are hard of hearing because there is no assistive listening system provided. |
AA5
|
18 months |
1.8 |
Rooftop Patio |
|
|
1.8a |
There is no access to the rooftop patio for people with mobility disabilities because there is a 7 inch step at the threshold to the door. |
AR9 |
18 months |
1.9 |
Women's Toilet Rooms – Single Users, 2nd Floor |
|
|
1.9a |
Toilet Room Near the Tea Room |
|
|
1.9a.i |
The signage provided is inaccessible because it is mounted so that its centerline is 62 ½ inches above the finished floor. |
TR17 |
18 months |
1.9a.ii |
The door is inaccessible because it requires 14 pounds of force to open. |
D2 |
18 months |
1.9a.iii |
The lavatory is inaccessible because the hot water pipes are not insulated or otherwise configured to protect against contact. |
TR12
|
18 months |
1.9a.iv |
The toilet is inaccessible because the top of the seat is 15 3/4 inches above the finished floor. |
SU18 |
18 months |
1.9a.v |
The toilet is inaccessible because its centerline is 19 ½ inches from the side wall. |
SU15 |
18 months |
1.9a.vi |
The toilet is inaccessible because the flush control is on the closed side. |
SU1 |
18 months |
1.9b |
Toilet Room Near the Bridge Room |
|
|
1.9b.i | The door is inaccessible because it has an opening width of only 28 inches. |
D25 | 18 months |
1.9b.ii |
No accessible mirror has been provided. |
TR14 |
18 months |
1.9b.iii |
The lavatory is inaccessible because the hot water pipes are not insulated or otherwise configured to protect against contact. |
TR12
|
18 months
|
1.9b.iv |
The toilet is inaccessible because the top of the seat is 15 ½ inches above the finished floor. |
SU18 |
18 months |
1.9b.v |
The toilet is inaccessible because its centerline is 19 inches from the side wall. |
SU15 |
18 months |
1.9b.vi |
The toilet is inaccessible because the flush control is on the closed side. |
SU1 |
18 months |
1.9b.vii |
No accessible coat hook has been provided. |
TR1 |
18 months |
1.9b.viii |
There are no grab bars provided. |
ST11 |
18 months |
1.9c |
Toilet Room at North End (near the elevator) |
|
|
1-9c-I |
The door is inaccessible because it requires 10 pounds of force to open. |
D2 |
18 months |
1.9c.ii |
The soap dispenser is inaccessible because it is mounted with the controls 49 ½ inches above the finished floor. |
TR5 |
18 months |
1.9c.iii |
The lavatory is inaccessible because the hot water pipes are not insulated or otherwise configured to protect against contact. |
TR12 |
18 months |
1.9c.iv |
The toilet is inaccessible because the top of the seat is 15 ½ inches above the finished floor. |
ST20 |
18 months |
1.9c.v |
The toilet is inaccessible because its centerline is 19 inches from the side wall. |
ST17 |
18 months |
1.9c.vi |
The toilet is inaccessible because the flush control is on the closed side. |
ST2 |
18 months |
1.10 |
Men's Toilet Rooms – Single Users, 2nd Floor |
|
|
1.10a |
Toilet Room Near the Tea Room |
|
|
1.10a.i |
The door is inaccessible because it requires 7 pounds of force to open. |
D2 |
18 months |
1.10a.ii |
The lavatory is inaccessible because the hot water pipes are not insulated or otherwise configured to protect against contact. |
TR12 |
18 months |
1.10a.iii |
The soap dispenser is inaccessible because it is mounted with the controls 51 ½ inches above the finished floor. |
TR5 |
18 months |
1.10a.iv |
The toilet is inaccessible because the top of the seat is 15 inches above the finished floor. |
ST20 |
18 months |
1.10a.v |
The toilet is inaccessible because its centerline is 19 inches from the side wall. |
ST17 |
18 months |
1.10b |
Toilet Room Near the Bridge Room |
|
|
1.10b.i |
The door is inaccessible because it requires 8 pounds of force to open. |
D2 |
18 months |
1.10b.ii |
The door is inaccessible because it has an opening width of only 29 inches. |
D25 |
18 months |
1.10b.iii |
The lavatory is inaccessible because the hot water pipes are not insulated or otherwise configured to protect against contact. |
TR12
|
18 months
|
1.10b.iv |
The urinal is inaccessible because the rim is 22 ½ inches above the finished floor, and the flush control is 49 inches above the finished floor. |
TR20 |
18 months |
1.10b.v |
The toilet is inaccessible because it lacks sufficient clear floor space and grab bars. |
SU10 SU14 |
18 months |
1.10b.vii |
No accessible coat hook has been provided. |
TR1 |
18 months |
1.10c |
North End Near the Elevator |
|
|
1.10c.i |
The soap dispenser is inaccessible because it is mounted with the controls 51 ½ inches above the finished floor. |
TR5 |
18 months |
1.10c.ii |
The lavatory is inaccessible because the hot water pipes are not insulated or otherwise configured to protect against contact. |
TR12
|
18 months |
1-10c-iii |
The toilet is inaccessible because the top of the seat is 15 ½ inches above the finished floor. |
ST20 |
18 months |
1-10c-iv |
The toilet is inaccessible because its centerline is 19 inches from the side wall. |
ST17 |
18 months
|