ATTACHMENT K: Program Access in Existing Facilities Please Note: Paragraph 44 of the Agreement requires that within three months of the effective date of this Agreement, the City will provide signage as necessary to comply with 28 C.F.R. § 35.163(b), after having surveyed all facilities that are the subject of this Agreement for the purpose of identifying those that have multiple entrances not all of which are accessible. The technical requirements and, where appropriate, the scoping requirements of the Standards are used as a guide for determining whether a program or activity held in an existing facility is "readily accessible to and usable by" persons with disabilities and for determining what changes are necessary to make this program or activity accessible if it continues to be provided in the existing facility in question. See 28 C.F.R. §§ 35.150(b)(1), 35.151. Actions are to be completed before the end of the time specified in the Completion Date column. The chart below lists the facilities surveyed and gives an alphanumeric code for the required remedial action. The key to these codes is found in Attachment M to this agreement. In order to ensure that the programs, services, and activities housed in the CityÕs facilities are accessible to persons with disabilities, when viewed in their entirety, the City will take the actions referenced by the alphanumeric code and described in detail in Attachment M to this Settlement Agreement within the time period specified below, which time period begins to run on the effective date of the Agreement. |
|||
item # |
Access Issue |
Required Action |
Completion Date |
---|---|---|---|
1. |
Convention Center (Harborside) - 1375 Monroe Street |
||
1.1. |
Parking (Altered): The designated accessible parking spaces located near the side entrance are inaccessible because they have slopes of up to 6.5%. |
P7 |
24 months |
1.2. |
Exterior Route to Rear Entrance |
||
1.2.a. |
The curb ramp is inaccessible because it has a slope of 11.5% with a cross slope of 5.8%, and the flared sides have slopes of 12.4% and 18.9%. |
AR5 |
24 months |
1.2.b. |
The ramp to the entrance is inaccessible because it has a slope of up to 12.5%, the intermediate landing has a slope of 6.5%, the top landing has a slope of 4.9%, the handrails lack extensions, and the handrail ends are not rounded or returned. |
R3 |
24 months |
1.3. |
Ramp to Side Entrance: The ramp is inaccessible because it slopes up to 12.3%, the top landing has a slope of 4.5%, and the middle landing has a slope of 4.1%. |
R3 |
24 months |
1.4. |
Front Entrance Passenger Loading Zone near Ticket Booth: The curb ramp is inaccessible because it has a slope of 15.9% with a cross slope of 5.3%, and the flared sides have slopes of 14.2% and 23.3%. |
AR5 |
24 months |
1.5. |
Main Entrance Ramp at Front near Ticket Booth: The ramp is inaccessible because it has a slope of up to 12.4% with a cross slope of up to 4.4%, at the junction of the sloped surface and the top landing, there is an abrupt change in level of between 1 and ½ inch, the handrails have no extensions, and there are no handrails provided on the bottom leg of the ramp. |
R3 |
24 months |
1.6. |
Entrance |
||
1.6.a. |
The building does not have directional signage posted at inaccessible entrances and does not have the International Symbol of Accessibility posted at accessible entrances. |
D16 |
24 months |
1.6.b. |
The exterior ticket counter is inaccessible because it is 41½ inches above the finished floor. |
C6 |
24 months |
1.7. |
Interior Doors: The doors throughout the facility are inaccessible because they require more than 5 pounds of force to open. |
D2 |
24 months |
1.8. |
Elevators near Administrative Offices |
||
1.8.a. |
The hoistway signs are inaccessible because they are centered at 58¾ inches. |
E12 |
24 months |
1.8.b. |
The elevator is inaccessible because the emergency system requires voice communication to operate, it requires tight grasping or pinching to access, and it is not identified by a raised symbol and lettering. |
E8 |
24 months |
1.9. |
Meeting Rooms: There is no signage informing the public of the availability of an assistive listening system. |
AA3 |
24 months |
1.10. |
Drinking Fountains near Administrative Offices: The lower drinking fountain is inaccessible because the water flow is 6½ inches from front of the fountain, and the control requires 7 pounds of pressure to operate. |
DF1 |
24 months |
1.11. |
Single User Toilet Rooms near Administrative Offices |
|
|
1.11.a. |
The toilet room signs are inaccessible because they are centered at 55 inches above the finished floor. |
TR17 |
24 months |
1.11.b. |
No accessible mirror is provided in either room. |
TR14 |
24 months |
1.11.c. |
Each toilet is inaccessible because it is 19½ inches above the finished floor. |
SU14 |
24 months |
1.11.d. |
Each toilet is inaccessible because there is no rear grab bar provided. |
SU2 |
24 months |
1.11.e. |
The side grab bar at each toilet is inaccessible because it is 25½ inches long. |
SU6 |
24 months |
1.12. |
MenÕs Toilet Room with Stalls near Rooms C1 & C2 (Altered) |
||
1.12.a. |
The urinal is inaccessible because the rim is 20 inches above the finished floor and the flush control is 48¾ inches above the finished floor. |
TR20 |
24 months |
1.12.b. |
The designated accessible toilet stall is inaccessible because it is 55 inches deep with a floor mounted toilet. |
ST16 |
24 months |
1.12.c. |
The designated accessible toilet is inaccessible because the top of the seat is 20 inches above the finished floor. |
ST20 |
24 months |
1.12.d. |
No accessible coat hook has been provided. |
TR1 |
24 months |
1.13. |
WomenÕs Toilet Room with Stalls near Rooms C1 & C2 (Altered) |
||
1.13.a. |
The baby changing station is inaccessible because it is mounted with handle 56½ inches above the finished floor. |
TR5 |
24 months |
1.13.b. |
The designated accessible toilet is inaccessible because the top of the seat is 20 inches above the finished floor. |
ST20 |
24 months |
1.13.c. |
The toilet paper dispenser in the designated accessible stall is inaccessible because it is mounted 51½ inches from the rear wall. |
ST19 |
24 months |
1.14. |
Drinking Fountains outside WomenÕs Toilet Room: The drinking fountains are inaccessible because the spouts are 10 inches from the front of the fountain and there is no fountain provided for people who have difficulty bending or stooping. |
DF1 |
24 months |
1.15. |
2nd Floor Drinking Fountains near D-1: The lower drinking fountain is inaccessible because the water flow is 6½ inches from front of fountain and the control requires 8 pounds of pressure to operate. |
DF1 |
24 months |
1.16. |
2nd Floor Meeting Rooms: The thermostats are inaccessible because they are mounted with the controls 60 inches above the finished floor. |
TR5 |
24 months |
1.17. |
Designated Accessible Dressing Room near D2 Meeting Room |
||
1.17.a. |
No accessible coat hook is provided. |
TR1 |
24 months |
1.17.b. |
The toilet is inaccessible because its centerline is 22½ inches from the side wall. |
SU15 |
24 months |
1.17.c. |
The toilet is inaccessible because the flush control is on the closed side. |
SU1 |
24 months |
1.17.d. |
The side grab bar is inaccessible because it is mounted with the far end 49 inches from rear wall. |
SU6 |
24 months |
2. |
City Hall - 2200 Second Street |
||
2.1. |
Ramp from Parking to SE Entrance: The ramp is inaccessible because it has a slope of up to 10.3%, the bottom landing has a slope of 4.1%, the landing at the rampÕs change of direction has a slope of 3.1% and is less than 60 inches long, and the handrails do not have extensions at the top and bottom and are not rounded or returned. |
R3 |
24 months |
2.2. |
Council Chambers Single-User Unisex Toilet Room (Altered) |
||
2.2.a. |
The toilet room sign is mounted on the door. |
TR17 |
24 months |
2.2.b. |
Although an audible alarm is provided in this facility, there is no visual alarm appliance in the toilet room. |
TR21 |
24 months |
2.2.c. |
The soap dispenser is inaccessible because it is mounted 49 inches above the finished floor with a forward reach required. |
TR5 |
24 months |
2.3. |
Council Chambers: The ramp to the dais is inaccessible because it slopes up to 9.2%, there is a handrail on only one side, the handrail is 30 inches above the finished floor at the top of the ramp, and there are no handrail extensions. |
R5 |
24 months |
2.4. |
Lobby |
||
2.4.a. |
The counter and the suggestion box in the lobby and the ashtrays by the lobby elevators all protrude into the walkway and are not detectable to blind persons using a cane. |
AR8 |
24 months |
2.4.b. |
The drinking fountain is inaccessible because the spout is 43 inches above the finished floor, the water flow is 4½ inches from the front of the fountain, the control requires more than 5 pounds of pressure to operate and is located on top, and there are only 19 inches of clear knee height. |
DF1 |
24 months |
2.5. |
Lobby WomenÕs Toilet Room with Stalls |
||
2.5.a. |
The door is inaccessible because it requires 6 pounds of force to open. |
D2 |
24 months |
2.5.b. |
The designated accessible toilet is inaccessible because the flush control is on the closed side. |
ST2 |
24 months |
2.5.c. |
No accessible coat hook is provided. |
TR1 |
24 months |
2.5.d. |
The toilet paper dispenser in the designated accessible toilet stall is inaccessible because it is mounted 17 inches above the finished floor and 44 inches from the rear wall. |
ST19 |
24 months |
2.5.e. |
The sanitary napkin dispenser is inaccessible because the controls require pinching, grasping, or twisting of the wrist to operate. |
TR3 |
24 months |
2.5.f. |
The side grab bar at the designated accessible toilet is inaccessible because it is obstructed by the soap dispenser. |
ST9 |
24 months |
2.6. |
Lobby MenÕs Toilet Room with Stalls |
||
2.6.a. |
The door is inaccessible because it requires 8 pounds of force to open. |
D2 |
24 months |
2.6.b. |
The lavatory is inaccessible because the hot water pipes are not insulated or otherwise configured to protect against contact. |
TR12 |
24 months |
2.6.c. |
The designated accessible toilet is inaccessible because the flush control is on the closed side. |
ST2 |
24 months |
2.6.d. |
No accessible coat hook is provided. |
TR1 |
24 months |
2.6.e. |
The toilet paper dispenser in the designated accessible stall is inaccessible because it is mounted 18 inches above the finished floor and 43 inches from the rear wall. |
ST19 |
24 months |
2.6.f. |
The side grab bar at the designated accessible toilet is inaccessible because it is obstructed by the soap dispenser. |
ST9 |
24 months |
2.7. |
Elevator |
||
2.7.a. |
The elevator is inaccessible because the hall call buttons are mounted 40 inches above the finished floor. |
E3 |
24 months |
2.7.b. |
The elevator is inaccessible because the emergency system requires voice communication to operate. |
E8 |
24 months |
2.8. |
Public Works - 2nd Floor |
||
2.8.a. |
The receptionist desk in the vestibule area is inaccessible because it is 41 inches above the finished floor. |
C6 |
24 months |
2.8.b. |
The dry erase board in Conference Room A protrudes into the walkway and is not detectable to blind persons using a cane. |
AR8 |
24 months |
2.8.c. |
The television in Conference Room B creates an overhead hazard with only 66 inches of head room provided. |
AR7 |
24 months |
2.9. |
MenÕs and WomenÕs Toilet Rooms - 2nd Floor: The menÕs and womenÕs toilet rooms contain a number of inaccessible elements and are not accessible to people with disabilities. |
TR22 |
24 months |
2.10. |
3rd Floor Lobby |
|
|
2.10.a. |
The AED next to the drinking fountain protrudes into the walkway and is not detectable to blind persons using a cane. |
AR8 |
24 months |
2.10.b. |
Although a designated accessible drinking fountain is provided, there is no drinking fountain provided for people who have difficulty bending or stooping. |
DF3 |
24 months |
2.11. |
WomenÕs Toilet Room with Stalls - 3rd Floor |
||
2.11.a. |
The door is inaccessible because it requires 10 pounds of force to open. |
D2 |
24 months |
2.11.b. |
No accessible coat hook is provided. |
TR1 |
24 months |
2.11.c. |
The toilet paper dispenser in the designated accessible stall is inaccessible because it is mounted 14¾ inches above the finished floor and 42 inches from the rear wall. |
ST19 |
24 months |
2.11.d. |
The designated accessible toilet is inaccessible because the flush control is on the closed side. |
ST2 |
24 months |
2.11.e. |
The rear grab bar at the designated accessible toilet is inaccessible because it is 24 inches long. |
ST4 |
24 months |
2.12. |
MenÕs Toilet Room with Stalls - 3rd Floor |
||
2.12.a. |
The door is inaccessible because it requires 10 pounds of force to open. |
D2 |
24 months |
2.12.b. |
The urinal is inaccessible because the flush control is 46¼ inches above the finished floor. |
TR20 |
24 months |
2.12.c. |
No accessible coat hook is provided. |
TR1 |
24 months |
2.12.d. |
The toilet paper dispenser in the designated accessible stall is inaccessible because it is mounted 15½ inches above the finished floor and 44 inches from the rear wall. |
ST19 |
24 months |
2.12.e. |
The rear grab bar at the designated accessible toilet is inaccessible because it is 24 inches long. |
ST4 |
24 months |
2.13. |
Drinking Fountain - 4th Floor: The drinking fountain has a number of inaccessible elements and is not accessible to people with disabilities. |
DF1 |
24 months |
2.14. |
Conference Room - 4th Floor |
||
2.14.a. |
The route into the room is inaccessible because it narrows to 30½ inches wide between the door and the edge of the table. |
AR3 |
24 months |
2.14.b. |
The room is inaccessible to people with hearing disabilities because there is no assistive listening system provided. |
AA5 |
24 months |
2.15. |
MenÕs and WomenÕs Toilet Rooms - 4th Floor: The menÕs and womenÕs toilet rooms contain a number of inaccessible elements and are not accessible to people with disabilities. |
TR22 |
24 months |
3. |
Main Street Garage - 2286 Main Street |
||
3.1. |
Elevator |
||
3.1.a. |
The elevator is inaccessible because the doors do not automatically reopen without contact if obstructed at a height of between 5 and 29 inches above the finished floor. |
E6 |
24 months |
3.1.b. |
The elevator is inaccessible because the car position indicators do not emit an audible signal as the car passes or stops at a floor. |
E5 |
24 months |
3.1.c. |
The elevator is inaccessible because the emergency system requires voice communication to operate. |
E8 |
24 months |
3.1.d. |
The elevator is inaccessible because the hall lanterns do not signal once for up and twice for down. |
E11 |
24 months |
4. |
Fort Myers Police Station - 2210 Peck Street |
||
4.1. |
Parking: The access aisle between the two accessible parking spaces is inaccessible because it is obstructed by the wheel stop. |
AR1 |
24 months |
4.2. |
Route to Front Entrance: The brick walk just in front of the front entrance is inaccessible because it has a slope of 6.5% with no ramp features. |
AR1 |
24 months |
4.3. |
Lobby: The door leading from the lobby is inaccessible because it requires 7 pounds of force to open. |
D2 |
24 months |
4.4. |
MenÕs Toilet Room with Stalls - Lobby |
||
4.4.a. |
The toilet room sign is mounted on the door. |
TR18 |
24 months |
4.4.b. |
The door is inaccessible because it requires 9 pounds of force to open. |
D2 |
24 months |
4.4.c. |
The door is inaccessible because there is a ½ inch high unbeveled threshold. |
D23 |
24 months |
4.4.d. |
The seat cover dispenser is inaccessible because it is mounted 54 inches above the finished floor behind the toilet. |
TR4 |
24 months |
4.4.e. |
The lavatory is inaccessible because the hot water pipes are not insulated or otherwise configured to protect against contact. |
TR12 |
24 months |
4.4.f. |
The toilet paper dispenser in the designated accessible stall is inaccessible because it is mounted 43 inches from the rear wall. |
ST19 |
24 months |
4.5. |
WomenÕs Toilet Room with Stalls - Lobby |
||
4.5.a. |
The toilet room sign is mounted on the door. |
TR18 |
24 months |
4.5.b. |
The door is inaccessible because it requires 7½ pounds of force to open. |
D2 |
24 months |
4.5.c. |
The door is inaccessible because there is a ½ inch high unbeveled threshold. |
D23 |
24 months |
4.5.d. |
No accessible mirror has been provided. |
TR14 |
24 months |
4.5.e. |
The seat cover dispenser is inaccessible because it is mounted 51 inches above the finished floor behind the toilet. |
TR5 |
24 months |
4.5.f. |
The lavatory is inaccessible because the hot water pipes are not insulated or otherwise configured to protect against contact. |
TR12 |
24 months |
4.5.g. |
The toilet paper dispenser in the designated accessible stall is inaccessible because it is mounted 41 inches from the rear wall. |
ST19 |
24 months |
4.6. |
Drinking Fountains - Lobby |
||
4.6.a. |
The drinking fountain is inaccessible because it has a spout that is 37½ inches above the finished floor. |
DF6 |
24 months |
4.6.b. |
Although a designated accessible drinking fountain is provided, there is no drinking fountain provided for people who have difficulty bending or stooping. |
DF3 |
24 months |
4.7. |
TTYÕs: Although there are telephones provided for use by detainees and inmates, a TTY is not provided. |
PJ6 |
24 months |
4.8. |
AED and First Aid Boxes: The AED box on the first floor and the first aid boxes on the first and second floors protrude into the walkway and are not detectable to blind persons using a cane. |
AR8 |
24 months |
4.9. |
Community Affairs: The door is inaccessible because it requires 8 pounds of force to open. |
D2 |
24 months |
4.10. |
Holding Cells: The holding cells are all inaccessible because there are no grab bars at the toilets and the doors are 26 inches wide. |
PJ1 |
24 months |
4.11. |
Elevators: The emergency communications are inaccessible because the system does not work without voice communication - police station dispatch answers and will check, but dispatch is not trained on silent call. |
E8 |
24 months |
5. |
City of Palms Parking Garage - 2116 Bay Street |
||
5.1. |
Accessible Routes |
||
5.1.a. |
The curb ramp to the parking office on the entrance side is inaccessible because it slopes up to 12.5% with a cross slope of 4.7%. |
AR5 |
24 months |
5.1.b. |
The curb ramp to the parking office on the exit side is inaccessible because it slopes up to 10.6% with a cross slope of 5.1%. |
AR5 |
24 months |
5.1.c. |
The door into the Arts League is inaccessible because there is a slope of 3.9% within the doorÕs required maneuvering clearance. |
D13 |
24 months |
5.1.d. |
The elevator is inaccessible because hall lanterns that emit an audible and visual signal indicating when a car is answering a call are not provided. |
E11 |
24 months |
6. |
Constitution Hall Sidewalks - 1700 Monroe Street |
||
6.1. |
Accessible Routes |
||
6.1.a. |
The Monroe Street sidewalk is inaccessible because it has a cross slope of up to 4.2%. |
AR1 |
24 months |
6.1.b. |
The curb ramps are inaccessible because the ramp at the corner of Main Street and Monroe Street has a slope of 10.2%, the flared sides have slopes of 20.8% and 25.8%, and the gutter slope is 12.7%; the built-up curb ramp on Monroe at the passenger loading zone has a slope of 23.9%; one curb ramp at the corner of Second Street and Monroe Street has a slope of 12.2% with a gutter slope of 15.8%, and the other has a slope of 10.1%; and the curb ramp at the corner of Monroe Street and M.L. King Street has a slope of 12.0%. |
AR5 |
24 months |
7. |
Burroughs Home - 2505 First Street |
||
7.1. |
Entrances |
||
7.1.a. |
The building does not have directional signage posted at inaccessible entrances and does not have the International Symbol of Accessibility posted at accessible entrances. |
D16 |
24 months |
7.1.b. |
The designated accessible entrance door is inaccessible because it has an opening width of 30 inches. |
D25 |
24 months |
7.1.c. |
The door is inaccessible because there is a slope of 26.3% within the doorÕs required maneuvering clearance. |
D13 |
24 months |
7.1.d. |
The designated accessible entrance is inaccessible because the door hardware cannot be used with one hand and requires tight grasping, pinching and twisting of the wrist to operate. |
D1 |
24 months |
7.1.e. |
The entrance ramp is inaccessible because the handrails lack extensions at the top and bottom. |
R2 |
24 months |
7.2. |
Interior: There is no access to upper and lower levels of the facility for people with mobility impairments. |
AR9 |
24 months |
7.3. |
Office |
||
7.3.a. |
The entrance ramp is inaccessible because it has a slope of 9.1%, the top landing is 35½ inches deep, the bottom the bottom landing is 44½ inches deep, there is only one handrail, and the handrail does not have extensions. |
R5 |
24 months |
7.3.b. |
The entrance door is inaccessible because the threshold is 1½ inches high. |
D23 |
24 months |
7.3.c. |
The entrance door is inaccessible because it has knob hardware. |
D1 |
24 months |
7.4. |
WomenÕs Toilet Room near Office |
||
7.4.a. |
The toilet room sign is mounted on the door and has no raised or Braille characters. |
TR18 |
24 months |
7.4.b. |
The door is inaccessible because the threshold is ¾ inches high. |
D23 |
24 months |
7.4.c. |
The toilet room is inaccessible because there is insufficient turning space provided within the room. |
TR19 |
24 months |
7.4.d. |
The lavatory is inaccessible because the hot water pipes are not insulated or otherwise configured to protect against contact. |
TR12 |
24 months |
7.4.e. |
The designated accessible toilet stall is inaccessible because it is 49¾ inches wide. |
ST16 |
24 months |
7.4.f. |
The designated accessible toilet is inaccessible because its centerline is 19½ inches from the side wall. |
ST17 |
24 months |
7.4.g. |
No accessible coat hook is provided. |
TR1 |
24 months |
7.4.h. |
The side grab bar at the toilet is inaccessible because it is mounted with the far end 50½ inches from the rear wall. |
SU6 |
24 months |
7.4.i. |
The rear grab bar in the designated accessible stall is inaccessible because the space between the grab bar and the wall is 1¾ inches. |
SU2 |
24 months |
7.4.j. |
The designated accessible stall is inaccessible because the stall door is 30¼ inches wide. |
D25 |
24 months |
7.5. |
MenÕs Toilet Room near Office |
||
7.5.a. |
The route to the toilet room is inaccessible because it is only 30½ inches wide where the additional concrete does not match up on the same level with the main sidewalk. |
AR3 |
24 months |
7.5.b. |
The toilet room sign is mounted on the door and has no raised or Braille characters. |
TR17 |
24 months |
7.5.c. |
The toilet room is inaccessible because there is insufficient turning space provided within the room. |
TR19 |
24 months |
7.5.d. |
The lavatory is inaccessible because the hot water pipes are not insulated or otherwise configured to protect against contact. |
TR12 |
24 months |
7.5.e. |
The urinal is inaccessible because the rim is 19 inches above the finished floor and the flush control is 45 inches above the finished floor. |
TR20 |
24 months |
7.5.f. |
The designated accessible toilet stall is inaccessible because it is insufficiently wide. |
ST16 |
24 months |
7.5.g. |
No accessible coat hook is provided. |
TR1 |
24 months |
7.5.h. |
The toilet paper dispenser in the designated accessible stall is inaccessible because it is mounted 39½ inches from the rear wall. |
ST19 |
24 months |
7.5.i. |
The side grab bar at the toilet is inaccessible because it is mounted with the far end 47 inches from the rear wall. |
SU6 |
24 months |
7.5.j. |
The rear grab bar at the toilet in the designated accessible stall is inaccessible because it is 24 inches long. |
ST3 |
24 months |
8. |
City Parking Lot - Fowler and First Street |
||
8.1. |
Parking: The unstriped parking lot is inaccessible because there are no spaces designated as accessible for people with disabilities. |
P3 |
24 months |
9. |
Dr. Ella Piper Center - 1771 Evans Avenue |
||
9.1. |
Parking: The parking lot is inaccessible because it has no space designated as van accessible. This lot requires 1 van accessible space. |
P3 |
24 months |
9.2. |
Drinking Fountain in Main Hall |
||
9.2.a. |
The drinking fountain is inaccessible because it has a spout that is 39 inches above the finished floor. |
DF6 |
24 months |
9.2.b. |
The wall-mounted drinking fountain is inaccessible because it provides only 22½ inches of clear knee height. |
DF5 |
24 months |
9.3. |
Single User Main Hall WomenÕs Toilet Room |
||
9.3.a. |
Although an audible alarm is provided in this facility, there is no visual alarm appliance in the toilet room. |
TR21 |
24 months |
9.3.b. |
No accessible mirror has been provided. |
TR14 |
24 months |
9.3.c. |
The seat cover dispenser is inaccessible because it is mounted 54 inches above the finished floor with a forward reach required. |
TR5 |
24 months |
9.3.d. |
The side grab bar at the toilet is inaccessible because it is mounted with the far end 47½ inches from the rear wall. |
SU6 |
24 months |
9.4. |
Single User Main Hall MenÕs Toilet Room |
||
9.4.a. |
Although an audible alarm is provided in this facility, there is no visual alarm appliance in the toilet room. |
TR21 |
24 months |
9.4.b. |
The seat cover dispenser is inaccessible because it is mounted 52½ inches above the finished floor with a forward reach required. |
TR5 |
24 months |
9.4.c. |
The toilet is inaccessible because the flush control is on the closed side. |
SU1 |
24 months |
9.4.d. |
The side grab bar at the toilet is inaccessible because it is mounted with the far end 47½ inches from the rear wall. |
SU6 |
24 months |
9.4.e. |
The rear grab bar at the toilet is inaccessible because it is obstructed by the seat cover dispenser. |
SU4 |
24 months |
10. |
Shady Oaks Community Center - 3280 Marion Street |
||
10.1. |
Entrance: The door is inaccessible because there is a ¾ inch high threshold. |
D23 |
24 months |
10.2. |
Lobby: The counter protrudes into the walkway and is not detectable to blind persons using a cane. |
AR8 |
24 months |
10.3. |
Offices: The doors to the offices are inaccessible because knob hardware is used. |
D1 |
24 months |
10.4. |
Drinking Fountains |
||
10.4.a. |
The drinking fountain by the womenÕs toilet room protrudes into the walkway and is not detectable to blind persons using a cane. |
AR8 |
24 months |
10.4.b. |
The drinking fountain by the menÕs toilet room is inaccessible because it provides only 25 inches of clear knee height. |
DF5 |
24 months |
10.4.c. |
Although a designated accessible drinking fountain is provided, there is no drinking fountain provided for people who have difficulty bending or stooping. |
DF3 |
24 months |
10.5. |
MenÕs Toilet Room with Stalls |
||
10.5.a. |
The toilet room sign is inaccessible because the sign is mounted on the door, and there are no raised or Braille characters. |
TR18 |
24 months |
10.5.b. |
The door is inaccessible because it requires 11 pounds of force to open. |
D2 |
24 months |
10.5.c. |
The pull side of the door, which is accessed from the latch side, is inaccessible because it has only 43½ inches of clear depth. |
D10 |
24 months |
10.5.d. |
No accessible mirror has been provided. |
TR14 |
24 months |
10.5.e. |
Although an audible alarm is provided in this facility, there is no visual alarm appliance in the toilet room. |
TR21 |
24 months |
10.5.f. |
The soap dispenser is inaccessible because it is mounted 48½ inches above the finished floor behind the lavatory. |
TR5 |
24 months |
10.5.g. |
The lavatory is inaccessible because the hot water pipes are not insulated or otherwise configured to protect against contact. |
TR12 |
24 months |
10.5.h. |
The designated accessible toilet stall is inaccessible because it is less than 60 inches wide. |
ST16 |
24 months |
10.5.i. |
The toilet is inaccessible because the flush control is on the closed side. |
SU1 |
24 months |
10.5.j. |
The toilet paper dispenser in the designated accessible stall is inaccessible because it is mounted 38 inches from the rear wall. |
ST19 |
24 months |
10.5.k. |
The side grab bar at the designated accessible toilet is inaccessible because it is obstructed by the toilet paper dispenser. |
ST8 |
24 months |
10.5.l. |
The grab bar at the designated accessible toilet is inaccessible because it is mounted more than 1½ inches from the wall. |
ST13 |
24 months |
10.5.m. |
There is no rear grab bar provided at the designated accessible toilet. |
ST3 |
24 months |
10.6. |
WomenÕs Toilet Room with Stalls: The womenÕs toilet room contains a number of inaccessible elements and is not accessible to people with disabilities. |
TR22 |
24 months |
11. |
City of Fort Myers Yacht Basin - 1300 Lee Street |
||
11.1. |
MenÕs Toilet Room with Stalls by Sales Office |
||
11.1.a. |
The pull side of the door, which is accessed through a front approach, is inaccessible because it has 1 inch of clear space on the latch side. |
D6 |
24 months |
11.1.b. |
The soap dispenser mounted on the stall door protrudes into the walkway and is not detectable to blind persons using a cane. |
AR8 |
24 months |
11.1.c. |
The lavatory in the designated accessible stall protrudes into the walkway and is not detectable to blind persons using a cane. |
AR8 |
24 months |
11.1.d. |
The urinal is inaccessible because the rim is 20 inches above the finished floor and the clear floor space is 27 inches wide. |
TR20 |
24 months |
11.1.e. |
The toilet is inaccessible because the top of the seat is 19½ inches above the finished floor. |
ST20 |
24 months |
11.1.f. |
No accessible coat hook has been provided. |
TR1 |
24 months |
11.1.g. |
The toilet paper dispenser in the designated accessible stall is inaccessible because it is mounted 42 inches from the rear wall. |
ST19 |
24 months |
11.1.h. |
The side grab bar at the toilet is inaccessible because it is 36 inches long. |
ST7 |
24 months |
11.1.i. |
The side grab bar at the designated accessible toilet is inaccessible because it is obstructed by the toilet paper dispenser. |
ST8 |
24 months |
11.1.j. |
There is no rear grab bar provided at the designated accessible toilet. |
ST3 |
24 months |
11.2. |
WomenÕs Toilet Room with Stalls by Sales Office |
||
11.2.a. |
The pull side of the door, which is accessed through a front approach, is inaccessible because it has 1 inch of clear space on the latch side. |
D6 |
24 months |
11.2.b. |
The door is inaccessible because the threshold is ½ inch high and is not beveled. |
D23 |
24 months |
11.2.c. |
No accessible mirror has been provided. |
TR14 |
24 months |
11.2.d. |
The toilet is inaccessible because the top of the seat is 19½ inches above the finished floor. |
SU18 |
24 months |
11.2.e. |
No accessible coat hook has been provided. |
TR1 |
24 months |
11.2.f. |
The side grab bar at the toilet is inaccessible because it is mounted with the far end 50½ inches from the rear wall. |
ST7 |
24 months |
11.2.g. |
The grab bar at the designated accessible toilet is inaccessible because it is mounted 32 inches above the finished floor. |
ST12 |
24 months |
11.2.h. |
There is no rear grab bar provided at the designated accessible toilet. |
ST3 |
24 months |
11.3. |
Drinking Fountain by WomenÕs Toilet Room |
||
11.3.a. |
The drinking fountain is inaccessible because it has a spout that is 37 inches above the finished floor. |
DF6 |
24 months |
11.3.b. |
Although a designated accessible drinking fountain is provided, there is no drinking fountain provided for people who have difficulty bending or stooping. |
DF3 |
24 months |
11.4. |
Telephones Near Toilet Rooms |
||
11.4.a. |
The telephone is inaccessible because it lacks signage depicting a handset with radiating sound waves. |
T1 |
24 months |
11.4.b. |
The telephone protrudes into the walkway and is not detectable to blind persons using a cane. |
AR8 |
24 months |
11.5. |
MenÕs Locker Rooms |
||
11.5.a. |
The toilet room sign is mounted on the door and has no raised or Braille characters. |
TR18 |
24 months |
11.5.b. |
The pull side of the door, which is accessed through a front approach, is inaccessible because it has only 16½ inches of clear space on the latch side. |
D6 |
24 months |
11.5.c. |
The route into the room is inaccessible because a plastic locker narrows the path to 30 inches wide. |
AR3 |
24 months |
11.5.d. |
The lavatory is inaccessible because the hot water pipes are not insulated or otherwise configured to protect against contact. |
TR12 |
24 months |
11.5.e. |
No accessible mirror has been provided. |
TR14 |
24 months |
11.5.f. |
There is no accessible toilet stall provided. |
ST15 |
24 months |
11.5.g. |
The roll in shower is inaccessible because the opening is on the narrow side, the curb is 2 inches high, the controls are on the wall opposite the transfer seat, and the shower spray unit cannot be handheld. |
B8 |
24 months |
11.6. |
WomenÕs Locker Rooms |
||
11.6.a. |
The toilet room sign is mounted on the door and has no raised or Braille characters. |
TR18 |
24 months |
11.6.b. |
The pull side of the door, which is accessed through a front approach, is inaccessible because it has only 16 inches of clear space on the latch side. |
D6 |
24 months |
11.6.c. |
The route into the room is inaccessible because a plastic locker narrows the path to 31 inches wide. |
AR3 |
24 months |
11.6.d. |
The lavatory is inaccessible because the hot water pipes are not insulated or otherwise configured to protect against contact. |
TR12 |
24 months |
11.6.e. |
There is no accessible toilet stall provided. |
ST15 |
24 months |
11.6.f. |
There is no accessible shower provided. |
B8 |
24 months |
11.7. |
Yacht Dockmaster Office |
||
11.7.a. |
The pull side of the door, which is accessed through a front approach, is inaccessible because it has 13 inches of clear space on the latch side. |
D6 |
24 months |
11.7.b. |
The red counter protrudes into the walkway and is not detectable to blind persons using a cane. |
AR8 |
24 months |
11.8. |
Ramp to Toilet Rooms, Laundry, Sales Office: The ramp is inaccessible because it has no accessible handrails. |
R3 |
24 months |
11.9. |
Rear Ramp to Store, Dockmaster Office: The ramp is inaccessible because the bottom landing is not level, and there is a handrails on only one side. |
R3 |
24 months |
12. |
Imaginarium - 2000 Cranford Street |
||
12.1. |
Parking (Altered) |
||
12.1.a. |
The parking lot is inaccessible because all of the designated accessible spaces and access aisles have slopes of between 3.4% and 5.2%. |
P7 |
24 months |
12.1.b. |
The passenger loading zone is inaccessible because there is a change in level at least ½ inch high at the bottom of the ramp. |
AR1 |
24 months |
12.2. |
WomenÕs Toilet Room 109 with Stalls (Altered) |
||
12.2.a. |
The door is inaccessible because it requires 12 pounds of force to open. |
D2 |
24 months |
12.2.b. |
No accessible mirror has been provided. |
TR14 |
24 months |
12.2.c. |
The paper towel dispenser protrudes into the walkway and is not detectable to blind persons using a cane. |
AR8 |
24 months |
12.2.d. |
The lavatory is inaccessible because the hot pipes are not insulated or otherwise configured to protect against contact. |
TR12 |
24 months |
12.2.e. |
Although there are 6 stalls, there is no ambulatory stall provided. |
ST1 |
24 months |
12.2.f. |
The designated accessible toilet is inaccessible because the flush control is on the closed side. |
ST2 |
24 months |
12.2.g. |
No accessible coat hook has been provided. |
TR1 |
24 months |
12.2.h. |
The side grab bar at the designated accessible toilet is inaccessible because it is obstructed by the toilet paper dispenser. |
ST8 |
24 months |
12.2.i. |
The designated accessible toilet is inaccessible because the rear grab bar is obstructed by the toilet seat cover dispenser. |
ST5 |
24 months |
12.2.j. |
The baby changing station is inaccessible because it is mounted with the handle 57 inches above the finished floor. |
TR5 |
24 months |
12.3. |
MenÕs Toilet Room 110 with Stalls (Altered) |
||
12.3.a. |
The door is inaccessible because it requires 13 pounds of force to open. |
D2 |
24 months |
12.3.b. |
No accessible mirror has been provided. |
TR14 |
24 months |
12.3.c. |
The paper towel dispenser protrudes into the walkway and is not detectable to blind persons using a cane. |
AR8 |
24 months |
12.3.d. |
The lavatory is inaccessible because the hot pipes are not insulated or otherwise configured to protect against contact. |
TR12 |
24 months |
12.3.e. |
The designated accessible toilet is inaccessible because the flush control is on the closed side. |
ST2 |
24 months |
12.3.f. |
No accessible coat hook has been provided. |
TR1 |
24 months |
12.3.g. |
The toilet paper dispenser in the designated accessible stall is inaccessible because it is mounted 38½ inches from the rear wall. |
ST19 |
24 months |
12.3.h. |
The side grab bar at the designated accessible toilet is inaccessible because it is obstructed by the toilet paper dispenser. |
ST8 |
24 months |
12.3.i. |
The designated accessible toilet is inaccessible because the rear grab bar is obstructed by the toilet seat cover dispenser. |
ST5 |
24 months |
12.3.j. |
The baby changing station is inaccessible because it is mounted with the handle 57½ inches above the finished floor. |
TR5 |
24 months |
12.3.k. |
The baby changing station protrudes into the walkway and is not detectable to blind persons using a cane. |
AR8 |
24 months |
12.4. |
Drinking Fountains between Toilet Rooms and Sting Ray Tank (Altered): The fountains protrude into the walkway and are not detectable to blind persons using a cane. |
AR8 |
24 months |
12.5. |
Gift Shop (Altered) |
||
12.5.a. |
The store has an accessible counter, but the counter is covered with display items. |
C5 |
24 months |
12.5.b. |
The counter protrudes into the walkway and is not detectable to blind persons using a cane. |
AR8 |
24 months |
12.6. |
Adams Center (Altered) |
||
12.6.a. |
The doors are inaccessible because they require 8 pounds of force to open. |
D2 |
24 months |
12.6.b. |
The shelf on the bottom half of the door protrudes into the walkway and is not detectable to blind persons using a cane. |
AR8 |
24 months |
12.7. |
Exhibit Hall |
||
12.7.a. |
The audio or audio-visual programs are not accessible to people who are deaf or hard of hearing. |
AA10 |
24 months |
12.7.b. |
The entry of the Hockey Experience is inaccessible because there is a 1 inch high step up. |
AR2 |
24 months |
12.7.c. |
The entry of the Baseball Experience is inaccessible because there is a 1½ inch high step up . |
AR2 |
24 months |
12.7.d. |
The Discovery drawers are inaccessible because the handles require pinching to open. |
TR3 |
24 months |
12.7.e. |
The doors from the main lobby to the Animal Lab are inaccessible because they require 14 pounds of force to open. |
D2 |
24 months |
12.7.f. |
The reading stands in the Animal Lab protrude into the walkway and are not detectable to blind persons using a cane. |
AR8 |
24 months |
12.8. |
Picnic Areas: The picnic tables are inaccessible because none provide the required knee space. |
PD6 |
24 months |
12.9. |
Florida Fossil Quarry |
24 months |
|
12.9.a. |
The sandbox is inaccessible because the sides are 28½ inches above the finished floor. |
AR1 |
24 months |
12.9.b. |
The paper towel dispenser protrudes into the walkway and is not detectable to blind persons using a cane. |
AR8 |
24 months |
12.10. |
Elevators Off Main Lobby: The elevator is inaccessible because the emergency system requires voice communication to operate, and it requires tight grasping or pinching to access. |
E8 |
24 months |
12.11. |
Exterior Drinking Fountain by Unisex Toilet Room: Although a designated accessible drinking fountain is provided, there is no drinking fountain provided for people who have difficulty bending or stooping. |
DF3 |
24 months |
12.12. |
Exterior Unisex Toilet Room by Auditorium and Lagoon: The toilet room contains a number of inaccessible elements and is not accessible to people with disabilities. |
SU13 |
24 months |
12.13. |
Theater in the Tank (Altered) |
||
12.13.a. |
The ramp to the small stage is inaccessible because it has a slope of approximately 33.3%, no handrails, and no edge protection. |
R5 |
24 months |
12.13.b. |
The fire extinguisher protrudes into the walkway and is not detectable to blind persons using a cane. |
AR8 |
24 months |
12.14. |
Ramp to Open Air Pavilion under Water Tower (Altered): The ramp is inaccessible because the handrails lack extensions and there is insufficient edge protection. |
R3 |
24 months |
13. |
Golfview Pool and Community Center - 1803 Golfview Avenue |
||
13.1. |
Parking: The designated accessible parking space is inaccessible because it has a cross slope of 3.3% and the access aisle has a slope of 3.4% and a cross slope of up to 5.2%. |
P7 |
24 months |
13.2. |
Pool Counter: The AED protrudes into the walkway and is not detectable to blind persons using a cane. |
AR8 |
24 months |
13.3. |
WomenÕs Locker Room (Altered) |
||
13.3.a. |
No accessible mirror has been provided. |
TR14 |
24 months |
13.3.b. |
The paper towel dispenser protrudes into the walkway and is not detectable to blind persons using a cane. |
AR8 |
24 months |
13.3.c. |
The toilet is inaccessible because it is obstructed by the toilet tank. |
ST5 |
24 months |
13.3.d. |
The designated accessible roll-in shower is inaccessible because the transfer seat is built in and does not fold, the seat is not mounted adjacent to the controls, the grab bars are too short, there is no hand-held shower head, and the fixed shower head is 75 inches above the finished floor. |
B8 |
24 months |
13.3.e. |
No accessible towel hook has been provided. |
TR1 |
24 months |
13.3.f. |
The bench is inaccessible because it is 9¼ inches wide and not attached to the wall. |
LR1 |
24 months |
13.4. |
MenÕs Locker Room (Altered) |
||
13.4.a. |
The paper towel dispenser protrudes into the walkway and is not detectable to blind persons using a cane. |
AR8 |
24 months |
13.4.b. |
The urinal is inaccessible because the rim is 18½ inches above the finished floor and the flush control is 47 inches above the finished floor. |
TR20 |
24 months |
13.4.c. |
The toilet is inaccessible because the top of the seat is 19¾ inches above the finished floor. |
ST20 |
24 months |
13.4.d. |
The designated accessible roll-in shower is inaccessible because the transfer seat is built in and does not fold, the seat is not mounted adjacent to the controls, the grab bars are too short, there is no hand-held shower head, and the fixed shower head is 75 inches above the finished floor. |
B8 |
24 months |
13.4.e. |
No accessible towel hook has been provided. |
TR1 |
24 months |
13.4.f. |
The bench is inaccessible because it is 9¼ inches wide and not attached to the wall. |
LR1 |
24 months |
13.5. |
Exterior Drinking Fountain by Locker Rooms |
||
13.5.a. |
The fountain protrudes into the walkway and is not detectable to blind persons using a cane. |
AR8 |
24 months |
13.5.b. |
Although a designated accessible drinking fountain is provided, there is no drinking fountain provided for people who have difficulty bending or stooping. |
DF3 |
24 months |
13.6. |
Picnic Area: The picnic tables are inaccessible because none provide the required knee space. |
PD6 |
24 months |
14. |
Fort Myers Country Club - 3583 McGregor Boulevard |
||
14.1. |
Parking: The parking lot, with a total of 185 parking spaces, is inaccessible because there is only one designated accessible space provided and the access aisle contains a small crater. This lot requires 1 van accessible space and 5 standard accessible spaces, or 6 universal design accessible spaces. |
P3 |
24 months |
14.2. |
Toilet Rooms at Hole #4: The toilet rooms contain a number of inaccessible elements and are not accessible to people with disabilities. |
ST14 |
24 months |
14.3. |
Golf Ball Wash at Hole #4: The route to the ball wash is inaccessible because the mulch is not stable, firm, and slip resistant. |
AR1 |
24 months |
14.4. |
Drinking Fountain at Hole #4 |
||
14.4.a. |
The drinking fountain is inaccessible because the control requires 8 pounds of force to operate. |
DF2 |
24 months |
14.4.b. |
Although a designated accessible drinking fountain is provided, there is no drinking fountain provided for people who have difficulty bending or stooping. |
DF3 |
24 months |
14.5. |
WomenÕs Toilet Room at Hole #7 |
||
14.5.a. |
The pull side of the door, which is accessed through a front approach, is inaccessible because it has only 16½ inches of clear space on the latch side. |
D6 |
24 months |
14.5.b. |
The designated accessible stall is inaccessible because the flush control is on the closed side. |
ST2 |
24 months |
14.5.c. |
The side grab bar at the toilet is inaccessible because it is mounted 13½ inches from the rear wall. |
ST7 |
24 months |
14.6. |
MenÕs Toilet Room at Hole #7 |
||
14.6.a. |
The urinal is inaccessible because the rim is 24 inches above the finished floor and the flush control is 50½ inches above the finished floor. |
TR20 |
24 months |
14.6.b. |
The designated accessible toilet is inaccessible because its centerline is 19 inches from the side wall. |
ST17 |
24 months |
14.6.c. |
The designated accessible stall is inaccessible because the flush control is on the closed side. |
ST2 |
24 months |
14.6.d. |
The side grab bar at the toilet is inaccessible because it is mounted 13½ inches from the rear wall. |
ST7 |
24 months |
14.6.e. |
The rear grab bar at the toilet is inaccessible because it is mounted 7¾ inches from the side wall. |
ST4 |
24 months |
14.6.f. |
The toilet is inaccessible because the rear grab bar is obstructed by the soap dispenser. |
ST5 |
24 months |
14.7. |
Hole #7 |
||
14.7.a. |
The ramp up to the toilet rooms is inaccessible because it has no handrails. |
R4 |
24 months |
14.7.b. |
The fire extinguisher in the toilet room lobby protrudes into the walkway and is not detectable to blind persons using a cane. |
AR8 |
24 months |
14.7.c. |
The picnic tables are inaccessible because none provide the required knee space. |
PD6 |
24 months |
14.7.d. |
Although a designated accessible drinking fountain is provided, there is no drinking fountain provided for people who have difficulty bending or stooping. |
DF3 |
24 months |
14.8. |
Golf Carts: Although there are golf carts for public use at this facility, none are accessible to persons who use wheelchairs. |
G1 |
24 months |
14.9. |
Pro Shop |
||
14.9.a. |
The ramp from the golf course to the entrance is inaccessible because the top landing has a slope of 5.7% and is only 43 inches long, and the handrails lack extensions. |
R3 |
24 months |
14.9.b. |
The designated accessible entrance is inaccessible because there is a slope of 5.7% within the doorÕs required maneuvering clearance. |
D13 |
24 months |
14.9.c. |
The building does not have directional signage posted at inaccessible entrances and does not have the International Symbol of Accessibility posted at accessible entrances. |
D16 |
24 months |
14.9.d. |
The counter protrudes into the walkway and is not detectable to blind persons using a cane. |
AR8 |
24 months |
14.9.e. |
The counter is inaccessible because it is 41½ inches above the finished floor. |
C5 |
24 months |
14.9.f. |
The dressing room is accessible because there is insufficient turning space, the sign is posted on the door, and no accessible bench is provided. |
LR2 |
24 months |
14.10. |
Pro Shop Single User Toilet Room |
||
14.10.a. |
The pull side of the door, which is accessed through a front approach, is inaccessible because it is obstructed by the lavatory. |
D6 |
24 months |
14.10.b. |
Although an audible alarm is provided in this facility, there is no visual alarm appliance in the toilet room. |
TR21 |
24 months |
14.10.c. |
No accessible mirror has been provided. |
TR14 |
24 months |
14.10.d. |
The toilet is inaccessible because there are no grab bars provided. |
SU10 |
24 months |
14.11. |
Edison Restaurant |
||
14.11.a. |
The parking lot, with a total of 72 parking spaces is inaccessible because the designated accessible spaces and access aisles have slopes between 2.4% and 5.2%. |
P7 |
24 months |
14.11.b. |
The ramp from the parking lot is inaccessible because it has a slope of up to 9.5%, the landings are not level, and the bottom handrails lack extensions. |
R3 |
24 months |
14.11.c. |
The route to the fountain in front of the restaurant is inaccessible because it contains steps. |
AR1 |
24 months |
14.11.d. |
The ramp to the entrance is inaccessible because the bottom landing is only 36 inches long and has a slope of 3.8%, and the handrails lack extensions and are mounted between 2 and 5 inches from the wall. |
R3 |
24 months |
14.11.e. |
The building does not have directional signage posted at inaccessible entrances and does not have the International Symbol of Accessibility posted at accessible entrances. |
D16 |
24 months |
14.11.f. |
The door to the porch seating area is inaccessible because it has an opening width of 30¾ inches. |
D25 |
24 months |
14.11.g. |
The lift at the rear of the restaurant is inaccessible because the controls on the door and call stations require tight grasping and twisting of the wrist to operate, and the access ramp has a slope of 18.6%. |
LF2 |
24 months |
14.11.h. |
The elevator is inaccessible because there is no hoistway signage on at least one door jamb. |
E12 |
24 months |
14.11.i. |
There is no signage directing persons with disabilities from inaccessible toilet rooms in the basement and on the 2nd floor to accessible toilet rooms. |
TR16 |
24 months |
14.11.j. |
The 2nd floor is inaccessible because there is insufficient head room provided along the window dormers. |
AR7 |
24 months |
14.11.k. |
Although a designated accessible drinking fountain is provided on the 2nd floor, there is no drinking fountain provided for people who have difficulty bending or stooping. |
DF3 |
24 months |
14.11.l. |
The white box in the basement hallway between the toilet room and elevator protrudes into the walkway and is not detectable to blind persons using a cane. |
AR8 |
24 months |
14.11.m.
|
The basement drinking fountain is inaccessible because it has a spout that is 40½ inches above the finished floor. |
DF6 |
24 months |
14.11.n. |
The basement drinking fountain protrudes into the walkway and is not detectable to blind persons using a cane. |
AR8 |
24 months |
14.12. |
Edison Restaurant Main Floor WomenÕs Toilet Room (Altered) |
||
14.12.a. |
The toilet room sign is inaccessible because it is mounted 51½ inches above the finished floor. |
TR17 |
24 months |
14.12.b. |
The door is inaccessible because it requires 8 pounds of force to open. |
D2 |
24 months |
14.12.c. |
The pull side of the door, which is accessed through a front approach, is inaccessible because it has 11 inches of clear space on the latch side. |
D6 |
24 months |
14.12.d. |
No accessible mirror has been provided. |
TR14 |
24 months |
14.12.e. |
The air dryer and paper towel dispenser protrude into the walkway and are not detectable to blind persons using a cane. |
AR8 |
24 months |
14.12.f. |
The soap dispenser is inaccessible because it is mounted with the controls 50 inches above the finished floor with a forward reach required. |
TR5 |
24 months |
14.12.g. |
The side grab bar at the designated accessible toilet is inaccessible because it is obstructed by the toilet paper dispenser. |
ST8 |
24 months |
14.12.h. |
There is no rear grab bar provided at the designated accessible toilet. |
ST3 |
24 months |
14.13. |
Edison Restaurant Main Floor MenÕs Toilet Room (Altered) |
||
14.13.a. |
The toilet room sign is inaccessible because it is mounted 51½ inches above the finished floor. |
TR17 |
24 months |
14.13.b. |
The door is inaccessible because it requires 9 pounds of force to open. |
D2 |
24 months |
14.13.c. |
The pull side of the door, which is accessed through a front approach, is inaccessible because it has insufficient clear space on the latch side. |
D6 |
24 months |
14.13.d. |
The soap dispenser is inaccessible because it is mounted with the controls 51 inches above the finished floor with a forward reach required. |
TR5 |
24 months |
14.13.e. |
The paper towel dispenser is inaccessible because it is mounted with the controls 52 inches above the finished floor with a forward reach required. |
TR5 |
24 months |
14.13.f. |
The designated accessible toilet is inaccessible because the flush control is on the closed side. |
ST2 |
24 months |
14.13.g. |
The side grab bar at the designated accessible toilet is inaccessible because it is obstructed by the toilet paper dispenser. |
ST8 |
24 months |
14.13.h. |
The side grab bar at the designated accessible toilet is inaccessible because it is 36 inches long. |
ST7 |
24 months |
14.13.i. |
There is no rear grab bar provided at the designated accessible toilet. |
ST3 |
24 months |
14.14. |
Edison Restaurant 2nd Floor Unisex Toilet Room |
||
14.14.a. |
The toilet room sign is mounted on the door and has no raised or Braille characters. |
TR17 |
24 months |
14.14.b. |
The pull side of the door, which is accessed through a front approach, is inaccessible because it has only 9 inches of clear space on the latch side. |
D6 |
24 months |
14.14.c. |
The toilet is inaccessible because the flush control is on the closed side. |
SU1 |
24 months |
14.14.d. |
The side grab bar is inaccessible because it is obstructed by a toilet paper dispenser. |
SU7 |
24 months |
14.14.e. |
The toilet is inaccessible because there is no rear grab bar provided. |
SU2 |
24 months |
15. |
Stars Sports Complex - 2980 Edison Avenue |
||
15.1. |
WomenÕs Toilet Room near Concession Stand |
||
15.1.a. |
The toilet room sign is mounted on the door. |
TR17 |
24 months |
15.1.b. |
The door is inaccessible because there is a ¾ inch high threshold. |
D23 |
24 months |
15.1.c. |
The paper towel dispenser is inaccessible because it is mounted with the controls 55 inches above the finished floor. |
TR5 |
24 months |
15.1.d. |
The designated accessible toilet is inaccessible because the top of the seat is 19½ inches above the finished floor. |
ST20 |
24 months |
15.1.e. |
The designated accessible toilet is inaccessible because its centerline is 19 inches from the side wall. |
ST17 |
24 months |
15.1.f. |
No accessible coat hook has been provided. |
TR1 |
24 months |
15.1.g. |
The side grab bar at the designated accessible toilet is inaccessible because it is 24 inches long. |
ST7 |
24 months |
15.1.h. |
The side grab bar at the designated accessible toilet is inaccessible because it is mounted 32 inches above the finished floor. |
ST12 |
24 months |
15.1.i. |
There is no rear grab bar provided at the designated accessible toilet. |
ST3 |
24 months |
15.2. |
MenÕs Toilet Room near Concession Stand |
||
15.2.a. |
The toilet room sign is mounted on the door. |
TR17 |
24 months |
15.2.b. |
The door is inaccessible because there is a ¾ inch high threshold. |
D23 |
24 months |
15.2.c. |
The lavatory is inaccessible because it has twist-type hardware. |
TR10 |
24 months |
15.2.d. |
The urinal is inaccessible because the rim is 18 inches above the finished floor and the flush control is 45½ inches above the finished floor. |
TR20 |
24 months |
15.2.e. |
The toilet room door swings into the required clear floor space at the urinal. |
TR6 |
24 months |
15.2.f. |
The designated accessible toilet is inaccessible because its centerline is 19¾ inches from the side wall. |
ST17 |
24 months |
15.2.g. |
The designated accessible toilet is inaccessible because the flush control is on the closed side. |
ST2 |
24 months |
15.2.h. |
No accessible coat hook has been provided. |
TR1 |
24 months |
15.2.i. |
The side grab bar at the designated accessible toilet is inaccessible because it is 24 inches long. |
ST7 |
24 months |
15.2.j. |
The side grab bar at the designated accessible toilet is inaccessible because it is mounted 32 inches above the finished floor. |
ST12 |
24 months |
15.2.k. |
There is no rear grab bar provided at the designated accessible toilet. |
ST3 |
24 months |
15.3. |
Drinking Fountain near Concession Stand |
||
15.3.a. |
The drinking fountain is inaccessible because the water flow is less than 4 inches high, the control requires more than 5 pounds of force to operate, and the control is mounted on the top of the fixture. |
DF1 |
24 months |
15.3.b. |
The drinking fountain protrudes into the walkway and is not detectable to blind persons using a cane. |
AR8 |
24 months |
15.4. |
Lobby: The wooden counter protrudes into the walkway and is not detectable to blind persons using a cane. |
AR8 |
24 months |
15.5. |
Gym: The doors are inaccessible because they require 12 pounds of force to open. |
D2 |
24 months |
15.6. |
Studio A |
||
15.6.a. |
The doors are inaccessible because they require 10 pounds of force to open. |
D2 |
24 months |
15.6.b. |
The doors are inaccessible because the door hardware requires pinching in order to operate. |
D1 |
24 months |
15.6.c. |
The womenÕs locker room has a number of inaccessible elements and is not accessible to people with disabilities. |
LR4 |
24 months |
15.7. |
Studio B |
||
15.7.a. |
The doors are inaccessible because the door hardware requires pinching in order to operate. |
D1 |
24 months |
15.7.b. |
The menÕs locker room has a number of inaccessible elements and is not accessible to people with disabilities. |
LR4 |
24 months |
15.8. |
WomenÕs Locker Room |
||
15.8.a. |
The toilet room sign is mounted on the door and has no raised or Braille characters. |
TR17 |
24 months |
15.8.b. |
The doors are inaccessible because they require 10 pounds of force to open. |
D2 |
24 months |
15.8.c. |
No accessible mirror has been provided. |
TR14 |
24 months |
15.8.d. |
The paper towel dispenser protrudes into the walkway and is not detectable to blind persons using a cane. |
AR8 |
24 months |
15.8.e. |
No accessible coat hook has been provided. |
TR1 |
24 months |
15.8.f. |
The side grab bar at the designated accessible toilet is inaccessible because it is obstructed by the toilet paper dispenser. |
ST8 |
24 months |
15.8.g. |
The designated accessible toilet is inaccessible because the rear grab bar is obstructed by the flush valve. |
ST5 |
24 months |
15.8.h. |
The shower is inaccessible because the shower spray unit cannot be hand held and the shower head is mounted 54½ inches above the finished floor. |
B11 |
24 months |
15.8.i. |
The bench is inaccessible because it is 9½ inches deep, it is 20¼ inches above the finished floor, and it is not attached to the wall. |
LR1 |
24 months |
15.9. |
MenÕs Locker Room |
||
15.9.a. |
The toilet room sign is mounted on the door and has no raised or Braille characters. |
TR17 |
24 months |
15.9.b. |
The doors are inaccessible because they require 8 pounds of force to open. |
D2 |
24 months |
15.9.c. |
The pull side of the interior door, which is accessed through a front approach, is inaccessible because it has only 15 inches of maneuvering space on the latch side. |
D6 |
24 months |
15.9.d. |
No accessible mirror has been provided. |
TR14 |
24 months |
15.9.e. |
The paper towel dispenser protrudes into the walkway and is not detectable to blind persons using a cane. |
AR8 |
24 months |
15.9.f. |
The side grab bar at the designated accessible toilet is inaccessible because it is obstructed by the toilet paper dispenser. |
ST8 |
24 months |
15.9.g. |
The designated accessible shower stall is inaccessible because its dimensions are 37½ by 41 inches. |
B8 |
24 months |
15.9.h. |
The bench is inaccessible because it is 9½ inches deep and 20¼ inches above the finished floor, and it is not attached to the wall. |
LR1 |
24 months |
15.10. |
Pool: The picnic tables by the pool are inaccessible because none provide the required knee space. |
PD6 |
24 months |
15.11. |
Drinking Fountains near Pool |
||
15.11.a. |
The drinking fountain is inaccessible because the spout is 38½ inches above the finished floor and the control is mounted on top of the unit. |
DF1 |
24 months |
15.11.b. |
The higher fountain protrudes into the walkway and is not detectable to blind persons using a cane. |
AR8 |
24 months |
16. |
Water Treatment Plant - 2761 Jacksonville Street |
||
16.1. |
Parking: The designated accessible parking space and access aisle are inaccessible because they have slopes of between 2.5% and 3.1%. |
P3 |
24 months |
16.2. |
Entrance Ramp: The ramp is inaccessible because it has a slope of up to 9.2%, the handrails are 33 inches above the finished floor, the handrails do not have extensions at the top or the bottom, and the handrails are not rounded or returned. |
R3 |
24 months |
16.3. |
Entrance |
||
16.3.a. |
The door is inaccessible because each leaf is 30½ inches wide. |
D24 |
24 months |
16.3.b. |
The door is inaccessible because there is a 1¼ inch high threshold. |
D23 |
24 months |
16.4. |
Drinking Fountain: The wall-mounted drinking fountain is inaccessible because it provides only 22½ inches of clear knee height. |
DF5 |
24 months |
16.5. |
MenÕs Single User Toilet Room |
||
16.5.a. |
The toilet room sign is mounted on the door. |
TR17 |
24 months |
16.5.b. |
The door is inaccessible because it requires more than 5 pounds of force to open. |
D2 |
24 months |
16.5.c. |
Although an audible alarm is provided in this facility, there is no visual alarm appliance in the toilet room. |
TR21 |
24 months |
16.5.d. |
No accessible mirror has been provided. |
TR14 |
24 months |
16.5.e. |
The lavatory is inaccessible because the bottom edge of the apron is 27¼ inches above the finished floor. |
TR11 |
24 months |
16.5.f. |
The lavatory is inaccessible because the hot water pipes are not insulated or otherwise configured to protect against contact. |
TR12 |
24 months |
16.5.g. |
The side grab bar at the designated accessible toilet is inaccessible because it is mounted with the far end 51 inches from the rear wall. |
ST7 |
24 months |
16.5.h. |
The designated accessible toilet is inaccessible because the rear grab bar is obstructed by the flush valve. |
ST5 |
24 months |
16.6. |
WomenÕs Single User Toilet Room |
||
16.6.a. |
The toilet room sign is mounted on the door. |
TR17 |
24 months |
16.6.b. |
The door is inaccessible because it requires more than 5 pounds of force to open. |
D2 |
24 months |
16.6.c. |
Although an audible alarm is provided in this facility, there is no visual alarm appliance in the toilet room. |
TR21 |
24 months |
16.6.d. |
No accessible mirror has been provided. |
TR14 |
24 months |
16.6.e. |
No accessible coat hook has been provided. |
TR1 |
24 months |
16.6.f. |
The lavatory is inaccessible because the bottom edge of the apron is 26¾ inches above the finished floor. |
TR11 |
24 months |
16.6.g. |
The lavatory is inaccessible because the hot water pipes are not insulated or otherwise configured to protect against contact. |
TR12 |
24 months |
16.6.h. |
The designated accessible toilet is inaccessible because its centerline is 24¼ inches from the side wall. |
ST17 |
24 months |
16.6.i. |
The designated accessible toilet is inaccessible because the top of the seat is 19½ inches above the finished floor. |
ST20 |
24 months |
16.6.j. |
The toilet paper dispenser in the designated accessible stall is inaccessible because it is mounted 42 inches from the rear wall. |
ST19 |
24 months |
16.6.k. |
The side grab bar at the designated accessible toilet is inaccessible because it is mounted with the far end 50 inches from the rear wall. |
ST7 |
24 months |
16.6.l. |
The designated accessible toilet is inaccessible because the rear grab bar is obstructed by the flush valve. |
ST5 |
24 months |
16.7. |
Tour Route |
||
16.7.a. |
The tour route is inaccessible because there are grates with openings ⅞ inches wide and parallel to the dominant direction of travel. |
AR6 |
24 months |
16.7.b. |
The wall-mounted box by the telephone protrudes into the walkway and is not detectable to blind persons using a cane. |
AR8 |
24 months |
16.7.c. |
In the hallway leading to the last room on the tour (where the water is sent into the city), the stainless steel cabinet protrudes into the walkway and is not detectable to blind persons using a cane. |
AR8 |
24 months |
17. |
City of Fort Myers Cemetery - 3200 Michigan Avenue |
||
17.1. |
Parking: The designated accessible parking space and access aisle are inaccessible because they have slopes of 3.8% and 4%. |
P3 |
24 months |
17.2. |
Office |
||
17.2.a. |
The entrance door is inaccessible because there is a ¾ inch high threshold. |
D23 |
24 months |
17.2.b. |
The entrance door is inaccessible because knob hardware is used. |
D1 |
24 months |
17.3. |
Office Unisex Single User Toilet Room |
||
17.3.a. |
The toilet room sign is not mounted on the latch side of the door. |
TR17 |
24 months |
17.3.b. |
The door to the toilet room is inaccessible because knob hardware is used. |
D1 |
24 months |
17.3.c. |
No accessible mirror has been provided. |
TR14 |
24 months |
17.3.d. |
The toilet room is inaccessible because there is insufficient turning space provided within the room. |
TR19 |
24 months |
17.3.e. |
The paper towel dispenser protrudes into the walkway and is not detectable to blind persons using a cane. |
AR8 |
24 months |
17.3.f. |
The lavatory is inaccessible because the top of the counter is 35¼ inches above the finished floor. |
TR11 |
24 months |
17.3.g. |
The urinal is inaccessible because the rim is 22 inches above the finished floor. |
TR20 |
24 months |
17.3.h. |
The toilet is inaccessible because the clear floor space is obstructed by the additional side grab bar. |
SU16 |
6 Month |
17.3.i. |
The toilet is inaccessible because there is no rear grab bar provided. |
SU2 |
24 months |
17.4. |
Maintenance Shed (New Construction) |
||
17.4.a. |
The ramp to the entrance is inaccessible because it has a slope of up to 10.2%. |
R5 |
24 months |
17.4.b. |
Maintenance Shed Unisex Single User Toilet Room |
||
17.4.b.1)
|
The toilet room sign is inaccessible because it has a centerline of 64 inches. |
TR17 |
24 months |
17.4.b.2)
|
No accessible mirror has been provided. |
TR14 |
24 months |
17.4.b.3)
|
The paper towel dispenser protrudes into the walkway and is not detectable to blind persons using a cane. |
AR8 |
24 months |
17.4.b.4)
|
The toilet is inaccessible because the top of the seat is 15½ inches above the finished floor. |
SU18 |
24 months |
17.4.b.5)
|
The toilet paper dispenser is inaccessible because it is mounted 17 inches above the finished floor. |
SU17 |
24 months |
18. |
Fort Myers Historical Museum - 2300 Peck Street |
||
18.1. |
Interior Exhibit Area |
||
18.1.a. |
The audio or audio-visual programs are not accessible to people who are deaf or hard of hearing. |
AA10 |
24 months |
18.1.b. |
The machine gun display protrudes into the walkway and is not detectable to blind persons using a cane. |
AR8 |
24 months |
18.1.c. |
The ramp to the display cases on the right side of the exhibit area after the machine gun display is inaccessible because it slopes up to 12.3% and does not have handrails. |
R5 |
24 months |
18.1.d. |
The ramp in front of the menÕs and womenÕs toilet rooms is inaccessible because it has a slope of 12.4%, there is only one handrail, which is 2¼ inches wide and between 40 and 46 inches above the finished floor, and there is no bottom landing. |
R5 |
24 months |
18.1.e. |
The ramp to the fire truck display is inaccessible because there are no handrails, it has a slope of 12.3% on the bottom concrete section, and there is a 1 inch high lip at the bottom. |
R5 |
24 months |
18.1.f. |
The first emergency exit is inaccessible because the door hardware is mounted 50½ inches above the finished floor. |
D1 |
24 months |
18.1.g. |
The exterior ramp leading to the emergency exit is inaccessible because there is no level landing at the door, and there are no handrails. |
R5 |
24 months |
18.1.h. |
The second emergency exit is inaccessible because there are 2 steps located on the exterior side of the door. |
AR1 |
24 months |
18.1.i. |
The cannon display protrudes into the walkway and is not detectable to blind persons using a cane. |
AR8 |
24 months |
18.1.j. |
The ramp with the black display case at the top landing is inaccessible because it lacks handrails. |
R2 |
24 months |
18.1.k. |
The ramp leading to the museum exit is inaccessible because it lacks handrails on one side. |
R5 |
24 months |
18.1.l. |
The rounded end of the handrail on the ramp leading to the museum exit protrudes into the walkway and is not detectable to blind persons using a cane. |
AR8 |
24 months |
18.2. |
MenÕs Toilet Room |
||
18.2.a. |
The toilet room sign is mounted on the door and has no raised or Braille characters. |
TR18 |
24 months |
18.2.b. |
The door is inaccessible because it requires 7 pounds of force to open. |
D2 |
24 months |
18.2.c. |
No accessible mirror has been provided. |
TR14 |
24 months |
18.2.d. |
The lavatory is inaccessible because the bottom edge of the apron is 27½ inches above the finished floor. |
TR11 |
24 months |
18.2.e. |
The urinal is inaccessible because the rim is 25 inches above the finished floor and the flush control is 48½ inches above the finished floor. |
TR20 |
24 months |
18.2.f. |
The designated accessible stall is inaccessible because the door is 28½ inches wide. |
D25 |
24 months |
18.2.g. |
The designated accessible toilet is inaccessible because its centerline is 27¾ inches from the side wall. |
ST17 |
24 months |
18.2.h. |
No accessible coat hook has been provided. |
TR1 |
24 months |
18.2.i. |
There are no accessible grab bars provided at the designated accessible toilet. |
ST11 |
24 months |
18.3. |
WomenÕs Toilet Room |
||
18.3.a. |
The toilet room sign is mounted on the door and has no raised or Braille characters. |
TR18 |
24 months |
18.3.b. |
The door is inaccessible because it requires 12 pounds of force to open. |
D2 |
24 months |
18.3.c. |
No accessible mirror has been provided. |
TR14 |
24 months |
18.3.d. |
The lavatory is inaccessible because the bottom edge of the apron is 27 inches above the finished floor. |
TR11 |
24 months |
18.3.e. |
The lavatory faucet is inaccessible because it requires 10 pounds of force to operate. |
TR10 |
24 months |
18.3.f. |
The designated accessible stall is inaccessible because the door is 27 inches wide. |
D25 |
24 months |
18.3.g. |
The designated accessible toilet is inaccessible because its centerline is 30 inches from the side wall. |
ST17 |
24 months |
18.3.h. |
The designated accessible toilet is inaccessible because the flush control is on the closed side. |
ST2 |
24 months |
18.3.i. |
No accessible coat hook has been provided. |
TR1 |
24 months |
18.3.j. |
There are no accessible grab bars provided at the designated accessible toilet. |
ST11 |
24 months |
18.4. |
Fort Myers Museum Replica House (Cracker House) |
||
18.4.a. |
The curb ramp leading to the entrance ramp is inaccessible because it has a slope of 10.7%. |
AR5 |
24 months |
18.4.b. |
The entrance ramp is inaccessible because the first landing is not level, and the landings are not long enough. |
R3 |
24 months |
18.5. |
Train: The routes into the train are inaccessible because they have steps. |
AR1 |
24 months |
19. |
Edison and Ford Winter Estates - 2350 McGregor Boulevard |
||
19.1. |
Parking: The parking lot, with a total of 261 parking spaces, is inaccessible because it only has 5 spaces designated as accessible, one of the designated accessible spaces is missing vertical signage, and another has a cross slope of 3.8%. This lot requires 1 van accessible space and 6 standard accessible spaces. |
P3 |
24 months |
19.2. |
Audio Tour Access: The audio or audio-visual programs are not accessible to people who are deaf or hard of hearing. |
AA10 |
24 months |
19.3. |
Maintenance Building: The route from the parking lot is inaccessible because there is a ½ inch high change in the level onto the sidewalk. |
AR1 |
24 months |
19.4. |
WomenÕs Toilet Room with Stalls |
||
19.4.a. |
The air dryer protrudes into the walkway and is not detectable to blind persons using a cane. |
AR8 |
24 months |
19.4.b. |
The side grab bar at the designated accessible toilet is inaccessible because it is obstructed by the toilet paper dispenser. |
ST8 |
24 months |
19.4.c. |
The ambulatory stall is inaccessible because the toilet is 16 inches above the finished floor, the toilet is not centered within the stall, and the side grab bar is obstructed by the toilet paper dispenser. |
ST1 |
24 months |
19.5. |
MenÕs Toilet Room |
||
19.5.a. |
No accessible mirror has been provided. |
TR14 |
24 months |
19.5.b. |
The air dryer protrudes into the walkway and is not detectable to blind persons using a cane. |
AR8 |
24 months |
19.5.c. |
The lavatory is inaccessible because the bottom edge of the apron is 27 inches above the finished floor. |
TR11 |
24 months |
19.5.d. |
The designated accessible toilet is inaccessible because its centerline is 19¼ inches from the side wall. |
ST17 |
24 months |
19.5.e. |
The side grab bar at the designated accessible toilet is inaccessible because it is obstructed by the toilet paper dispenser. |
ST8 |
24 months |
19.6. |
Information Booth Counter: The counter protrudes into the walkway and is not detectable to blind persons using a cane. |
AR8 |
24 months |
19.7. |
Entrances |
||
19.7.a. |
The door at the designated accessible entrance for the Ticket Office, Gift Shop, and Museum is inaccessible because there is a slope of 6.2% within the doorÕs required maneuvering clearance. |
D13 |
24 months |
19.7.b. |
The door at the designated accessible entrance for the Ticket Office, Gift Shop, and Museum is inaccessible because there is a ¾ inch high threshold. |
D23 |
24 months |
19.7.c. |
The door at the designated accessible Tour Entrance is inaccessible because there is a slope of 3.7% within the doorÕs required maneuvering clearance. |
D13 |
24 months |
19.8. |
Exterior Information Station: The station is inaccessible because the route to it is not firm, stable, and slip resistant. |
AR1 |
24 months |
19.9. |
Ford Cottage Shop |
||
19.9.a. |
The entrance ramp is inaccessible because it has no bottom landing. |
R5 |
24 months |
19.9.b. |
The entrance is inaccessible because the short ramp at the door has a slope of 25.8%. |
AR1 |
24 months |
19.9.c. |
The door is inaccessible because there is a 1 inch high threshold. |
D23 |
24 months |
19.9.d. |
The cash register counter is inaccessible because it is 41 inches above the finished floor. |
C5 |
24 months |
19.9.e. |
The "raised room" is inaccessible because it has a 6 inch high step and the door clearance is 27¼ inches wide. |
AR2 |
24 months |
19.9.f. |
The round display table in the main area protrudes into the walkway and is not detectable to blind persons using a cane. |
AR8 |
24 months |
19.9.g. |
The audio or audio-visual programs are not accessible to people who are deaf or hard of hearing. |
AA10 |
24 months |
19.10. |
The Mangoes - Ford House (under Renovation) |
||
19.10.a. |
The entrance ramp is inaccessible because they lack extensions beyond the ramp surface at the bottom landing. |
R2 |
24 months |
19.10.b. |
The entrances are inaccessible because the thresholds are ¾ inch high, one doorway has a 5½ inch high step, and another doorway has a 6 inch high step. |
D17 |
24 months |
19.10.c. |
The doors in the house are inaccessible because they have opening widths between 28 and 30 inches. |
D25 |
24 months |
19.11. |
WomenÕs Toilet Room between Ford and Edison Houses (Altered) |
||
19.11.a. |
The toilet room sign is inaccessible because it is mounted 51 inches above the finished floor. |
TR17 |
24 months |
19.11.b. |
No accessible mirror has been provided. |
TR14 |
24 months |
19.11.c. |
The air dryer protrudes into the walkway and is not detectable to blind persons using a cane. |
AR8 |
24 months |
19.11.d. |
The lavatory is inaccessible because the hot water pipes are not insulated or otherwise configured to protect against contact. |
TR12 |
24 months |
19.11.e. |
The designated accessible toilet is inaccessible because the top of the seat is 19½ inches above the finished floor. |
ST20 |
24 months |
19.11.f. |
The designated accessible toilet is inaccessible because its centerline is 22½ inches from the side wall. |
ST17 |
24 months |
19.11.g. |
The designated accessible toilet is inaccessible because the flush control is on the closed side. |
ST2 |
24 months |
19.11.h. |
No accessible coat hook has been provided. |
TR1 |
24 months |
19.11.i. |
The side grab bar at the designated accessible toilet is inaccessible because it is obstructed by the toilet paper dispenser. |
ST8 |
24 months |
19.11.j. |
The side grab bar at the designated accessible toilet is inaccessible because it is only 36 inches long. |
ST7 |
24 months |
19.11.k. |
There is no rear grab bar provided at the designated accessible toilet. |
ST3 |
24 months |
19.12. |
MenÕs Toilet Room between Ford and Edison Houses (Altered) |
||
19.12.a. |
The toilet room sign is mounted 51 inches above the finished floor. |
TR17 |
24 months |
19.12.b. |
No accessible mirror has been provided. |
TR14 |
24 months |
19.12.c. |
The air dryer protrudes into the walkway and is not detectable to blind persons using a cane. |
AR8 |
24 months |
19.12.d. |
The lavatory is inaccessible because the hot water pipes are not insulated or otherwise configured to protect against contact. |
TR12 |
24 months |
19.12.e. |
No accessible coat hook has been provided. |
TR1 |
24 months |
19.12.f. |
The side grab bar at the designated accessible toilet is inaccessible because it is obstructed by the toilet paper dispenser. |
ST8 |
24 months |
19.12.g. |
The side grab bar at the designated accessible toilet is inaccessible because it is only 36 inches long. |
ST7 |
24 months |
19.12.h. |
There is no rear grab bar provided at the designated accessible toilet. |
ST3 |
24 months |
19.13. |
Edison Guest House: The guest house is inaccessible because the entrances contain steps. |
AR1 |
24 months |
19.14. |
Edison Main House |
||
19.14.a. |
In the back of the house, the Orchid Lane and Friendship Walk information stand is inaccessible because the route is not firm, stable, and slip resistant. |
AR1 |
24 months |
19.14.b. |
The route on the porch is inaccessible because insufficient head room is provided on the underside of the open stairs and under the fire hose rack. |
AR7 |
24 months |
19.14.c. |
The pool deck and pool guardrail protrude into the walkway and are not detectable to blind persons using a cane. |
AR8 |
24 months |
19.15. |
Edison CaretakerÕs House |
||
19.15.a. |
The entrance ramp is inaccessible because it has no bottom landing. |
R3 |
24 months |
19.15.b. |
The audio or audio-visual programs are not accessible to people who are deaf or head of hearing. |
AA10 |
24 months |
19.15.c. |
The interior and exterior doors are inaccessible because the thresholds are ¾ inch high or more. |
D23 |
24 months |
19.16. |
Edison Botanic Research Laboratory |
||
19.16.a. |
The building does not have directional signage posted at inaccessible entrances and does not have the International Symbol of Accessibility posted at accessible entrances. |
D16 |
24 months |
19.16.b. |
The entrance ramp is inaccessible because it has a slope of up to 9% on the main ramp and 11.6% on the top portable ramp, the portable ramp obstructs the top landing, the bottom landing has a slope of 9.6%, no edge protection is provided, and the handrails lacks extensions at the bottom. |
R3 |
24 months |
19.16.c. |
The door is inaccessible because there is a slope of 11.6% within the doorÕs required maneuvering clearance. |
D13 |
24 months |
19.17. |
Banyan CafŽ |
||
19.17.a. |
The paved sidewalk from the lab to the cafŽ is inaccessible because it has gaps in the pavement, it is 28 inches wide along long portions, and it has a cross slope of up to 6.5%. |
AR1 |
24 months |
19.17.b. |
The picnic tables on the rear lot are inaccessible because they are not on an accessible route and they do not provide accessible clearances. |
PD6 |
24 months |
19.17.c. |
The counter is inaccessible because it is 43¼ inches above the finished floor. |
C5 |
24 months |