ATTACHMENT L: Programs Housed in Others' Facilities Please Note: Paragraph 57 of the Agreement requires that within three months of the effective date of this Agreement, the County will provide signage as necessary to comply with 28 C.F.R. § 35.163(b), after having surveyed all facilities that are the subject of this Agreement for the purpose of identifying those that have multiple entrances not all of which are accessible. The chart below lists the facilities surveyed by the Department, the access issues identified during the survey, and the actions required to correct the access issues. Required actions are listed using an alphanumeric code. The key to the alphanumeric codes is provided in Attachment M to this Agreement. In order to ensure that the County's programs, services, and activities that are operated at facilities owned or controlled by other entities as listed below are, when viewed in their entirety, readily accessible to and usable by persons with mobility disabilities, the County will ensure that the actions listed below have been accomplished within the time period specified below, which time period begins to run on the effective date of the Agreement. Alternatively, within 90 days of the effective date of this Agreement, the County will submit for review by the Department a plan for providing access for persons with disabilities to the programs, services, and activities housed in the facility. |
|||
Item # |
Access Issue |
Required Action |
Completion Date |
---|---|---|---|
1. |
Magistrate Office, located at Arch Street, Connellsville | ||
1.1. |
Route from Parking to Facility Entrance: The route is inaccessible because it has a running slope of 6.8% with no ramp features. |
R5, AR1 |
12 months |
1.2. |
Reception Counter: The counter is inaccessible because it is 44½ inches high, and the clip board provided does not fit through the reception window. |
C6 |
12 months |
1.3. |
Lobby Single User Toilet Room | ||
1.3.a. |
The toilet room sign is inaccessible because it is not centered 60 inches above the finished floor. |
TR18 |
12 months |
1.3.b. |
The toilet is inaccessible because the flush control is on the closed side. |
SU1 |
12 months |
1.3.c. |
The toilet is inaccessible because the side grab bar is mounted with the far end 51 inches from the rear wall. |
SU6 |
12 months |
1.3.d. |
The toilet is inaccessible because the rear grab bar is mounted 7½ inches from the side wall. |
SU3 |
12 months |
1.4. |
Lobby Drinking Fountain | ||
1.4.a. |
The drinking fountain is inaccessible because it has a spout that is 37½ inches high. |
DF6 |
12 months |
1.4.b. |
The drinking fountain is inaccessible because the flow of water is 3 inches high. |
DF7 |
12 months |
1.4.c. |
The drinking fountain protrudes into the walkway and is not detectable to blind persons using a cane. |
AR8 |
12 months |
1.5. |
Courtroom | ||
1.6. |
The signage identifying the courtroom is mounted with its centerline 64 inches high. |
D26 |
12 months |
1.7. |
There is no accessible route to the witness stand due to steps. |
AA8 |
12 months |
1.8. |
Defendants' Single User Toilet Room: The toilet room contains a number of inaccessible elements and is not accessible to persons with disabilities. |
SU13 |
12 months |
2. |
Magistrate Office, located at 114 Main Street, Belle Vernon | ||
2.1. |
Parking Lot: The parking lot, with a total of approximately 12 parking spaces, has no parking spaces designated as reserved for persons with disabilities, and the gravel is not firm, stable, and slip resistant. This lot requires 1 van accessible space. |
P3 |
18 months |
2.2. |
Curb Ramp from Parking Lot to Entrance: The curb ramp is inaccessible because its primary slope is 15.7%, and one side flare slopes 13.4%. |
AR5 |
18 months |
2.3. |
Ramp from Sidewalk to Main Entrance: The running slope of the ramp ranges from 15.8% to 20%; the cross slope is 3.8% in some portions; there is inadequate edge protection; there is a handrail on only one side; and the handrail lacks extensions at the bottom. |
R5 |
18 months |
2.4. |
Magistrate's Office Interior Entrance | ||
2.4.a. |
The door is inaccessible because there is a 1 inch high threshold. |
D23 |
18 months |
2.4.b. |
The door is inaccessible because knob hardware is used. |
D1 |
18 months |
2.5. |
Lobby/Reception: No accessible coat rack has been provided. |
TR1 |
18 months |
2.6. |
Single User Toilet Room off Lobby/Reception | ||
2.6.a. |
The toilet room sign is mounted on the door and does not include raised and Braille characters. |
TR18 |
18 months |
2.6.b. |
The entrance door is inaccessible because it has knob hardware. |
D1 |
18 months |
2.6.c. |
The lavatory is inaccessible because the rim or counter is 38 inches high to the top. |
TR11 |
18 months |
2.6.d. |
The lavatory is inaccessible because the hot water and drain pipes are not insulated or otherwise configured to protect against contact. |
TR12 |
18 months |
2.6.e. |
The toilet is inaccessible because the centerline is 28 inches from the side wall. |
SU15 |
18 months |
2.6.f. |
The toilet is inaccessible because the side grab bar is 36 inches long, the farther end of the grab bar is 50 inches from the rear wall, the closer end of the grab bar is 14 inches from the rear wall, and the grab bar is mounted 38½ inches high. |
SU5 |
18 months |
2.6.g. |
The toilet is inaccessible because no rear grab bar is provided. |
SU2 |
18 months |
2.7. |
Hallway off Lobby/Reception | ||
2.7.a. |
The door from the lobby to the hallway is inaccessible because knob hardware is used. |
D1 |
18 months |
2.7.b. |
The door from the lobby to the hallway is inaccessible because the threshold is between 1 and 1½ inches high. |
D23 |
18 months |
2.8. |
Courtroom | ||
2.8.a. |
The entrance door to the courtroom is inaccessible because knob hardware is used. |
D1 |
18 months |
2.8.b. |
The witness stand is inaccessible because there is a 6½ inch high step into it. |
AA8 |
18 months |
2.9. |
Conference Room: The entrance door is inaccessible because knob hardware is used. |
D1 |
18 months |
2.10. |
Defendant Area: The entrance door is inaccessible because knob hardware is used. |
D1 |
18 months |
2.11. |
Holding Cell Toilet Room: The entrance door is inaccessible because knob hardware is used. |
D1 |
18 months |
2.12. |
Rear Defendant Entrance | ||
2.12.a. |
The rear entry door is inaccessible because there is a threshold approximately 5 inches high. |
D23 |
18 months |
2.12.b. |
The interior hallway ramp is inaccessible because it has a running slope of up to 25.4% and a cross slope of up to 2.5%; there is no level landing at the bottom of the ramp; the handrails are mounted 30½ inches high; and the handrails lack 12 inch extensions and are not rounded or returned. |
R5 |
18 months |
2.12.c. |
The door between the courtroom and the ramped hallway is inaccessible because it has a 1¼ inch high threshold. |
D23 |
18 months |
3. |
Magistrate Office, located at 113C Thorton Road, Brownsville | ||
3.1. |
Parking: The parking lot, with a total of 19 parking spaces, is inaccessible because it does not have a van accessible parking space, the designated accessible parking space does not have an access aisle, the vertical sign provided can be obstructed by a parked vehicle, and the running slope of the space is 5.5% and the cross slope is 3.1%. This lot requires 1 van accessible space. |
P3 |
18 months |
3.2. |
Exterior Accessible Route: The underside of the stairway is an overhead hazard because there are less than 80 inches of head room provided with no cane detectable barrier. |
AR7 |
18 months |
3.3. |
Main Entrance | ||
3.3.a. |
The route from the designated accessible parking space to the entrance is inaccessible because it has a cross slope of 4.3%. |
AR1 |
18 months |
3.3.b. |
The main entrance door is inaccessible because the threshold is 1¼ inch high. |
D23 |
18 months |
3.4. |
Entrance to Detention Area | ||
3.4.a. |
The push side of the door, which is accessed through a front approach and which has both a closer and a latch, is inaccessible because it has 10½ inches of maneuvering clearance on the latch side. |
D7 |
18 months |
3.4.b. |
The entrance door is inaccessible because knob hardware is used. |
D1 |
18 months |
3.5. |
Lobby Single User Toilet Room | ||
3.5.a. |
The toilet room sign is mounted with its centerline 52 inches high. |
TR18 |
18 months |
3.5.b. |
The lavatory is inaccessible because the clear knee width is 16 inches due to the placement of metal support bars. |
TR8, TR11 |
18 months |
3.5.c. |
The toilet is inaccessible because the side grab bar is mounted with the far end 52 inches from the rear wall. |
SU6 |
18 months |
3.6. |
Lobby Drinking Fountain: Although an accessible drinking fountain is provided, there is no drinking fountain provided for people who have difficulty bending or stooping. |
DF3 |
18 months |
3.7. |
Lobby Counter | ||
3.7.a. |
The counter is inaccessible because it is 41¼ inches high. |
C6 |
18 months |
3.7.b. |
The counter protrudes into the walkway and is not detectable to blind persons using a cane. |
AR8 |
18 months |
3.8. |
Courtrooms: The courtrooms are inaccessible to persons with hearing disabilities because there are no assistive listening systems provided. |
AA5 |
18 months |
3.9. |
Ramp from Detention Area to Courtroom: The ramp has a running slope of up to 27.1%; the landing at the top of the ramp is 44 inches deep; the landing at the bottom of the ramp is 34 inches wide; there is a handrail on only one side; and the handrail lacks extensions at the top and bottom and is not rounded or returned. |
R5 |
18 months |
3.10. |
Detention Room: The entrance door is inaccessible because knob hardware is used. |
D1 |
18 months |
3.11. |
Conference Room (Marked "Private"): The push side of the entrance door, which is accessed from the latch side of the door, is inaccessible because it has only 37½ inches of clear maneuvering width. |
D11 |
18 months |
3.12. |
Detention Single User Toilet Room | ||
3.12.a. |
The toilet room sign is mounted with its centerline 58 inches high. |
TR18 |
18 months |
3.12.b. |
The pull side of the entrance door, which is accessed from the latch side of the door, is inaccessible because it has only 13 inches of clear space on the latch side. |
D10 |
18 months |
3.12.c. |
The lavatory is inaccessible because the clear knee width is obstructed by the metal support bars. |
TR8 |
18 months |
3.12.d. |
The toilet paper dispenser is inaccessible because it is mounted 38 inches from the rear wall. |
SU17 |
18 months |
4. |
Magistrate Office, located at 521 Johnston Avenue, Uniontown | ||
4.1. |
Parking: The parking lot, with a total of approximately 18 parking spaces, is inaccessible because it has no parking spaces designated as reserved for persons with disabilities. |
P3 |
12 months |
4.2. |
Main Entrance: The main entrance is inaccessible because the threshold is 1 inch high. |
D23 |
12 months |
4.3. |
Defendants' Entrance: The entrance door is inaccessible because the threshold is 1½ inches high. |
D23 |
12 months |
4.4. |
Lobby Single User Toilet Room | ||
4.4.a. |
The toilet room sign is mounted on the door. |
TR18 |
12 months |
4.4.b. |
The door is inaccessible because it requires 6 pounds of force to open. |
D2 |
12 months |
4.4.c. |
The toilet paper dispenser is inaccessible because it is mounted 38 inches from the rear wall. |
SU17 |
12 months |
4.4.d. |
The toilet is inaccessible because the flush control is on the closed side. |
SU1 |
12 months |
4.4.e. |
The toilet is inaccessible because the side grab bar is mounted 13 inches from the rear wall. |
SU6 |
12 months |
4.5. |
Lobby Drinking Fountain | ||
4.5.a. |
The wall-mounted drinking fountain is inaccessible because the clear knee height is 25 inches high. |
DF5 |
12 months |
4.5.b. |
Although a designated accessible drinking fountain is provided, there is no drinking fountain provided for people who have difficulty bending or stooping. |
DF3 |
12 months |
4.6. |
Magistrate Front Office: The reception counter is inaccessible because it is 41¾ inches high. |
C6 |
12 months |
4.7. |
Defendants' Area: The entrance door is inaccessible because knob hardware is used. |
D1 |
12 months |
4.8. |
Conference Room | ||
4.8.a. |
The entrance door is inaccessible because knob hardware is used. |
D1 |
12 months |
4.8.b. |
The conference table is inaccessible because the clear knee height is 24 inches high. |
T1 |
12 months |
4.9. |
Holding Cell: The entrance door is inaccessible because knob hardware is used. |
D1 |
12 months |
4.10. |
Defendants' Single User Toilet Room | ||
4.10.a. |
The door is inaccessible because the clear opening width is 30 inches. |
D25 |
12 months |
4.10.b. |
The toilet room is inaccessible because there is insufficient turning space provided within the room. |
TR19 |
12 months |
4.10.c. |
The lavatory is inaccessible because there is no knee space provided. |
TR11 |
12 months |
4.10.d. |
The toilet is inaccessible because the top of the seat is 16 inches high. |
SU18 |
12 months |
4.10.e. |
The toilet is inaccessible because the centerline is 14 inches from the near side wall. |
SU15 |
12 months |
4.10.f. |
The toilet is inaccessible because the flush control is on the closed side. |
SU1 |
12 months |
4.10.g. |
The toilet is inaccessible because no grab bars are provided. |
SU10 |
12 months |
5. |
Magistrate Office located at 870 McClellandtown Road, Suite 5, McClellandtown | ||
5.1. |
Parking: The parking lot, with a total of 37 spaces, is inaccessible because it has no van accessible space, neither of the 2 designated accessible spaces have access aisles, and the signage is mounted too low. This lot requires 1 van accessible space and 1 standard accessible space. |
P3 |
18 months |
5.2. |
Route to Main Entrance from Parking: The route is inaccessible because there is an abrupt ½ inch vertical change in level between the sidewalk and the parking lot. |
AR1 |
18 months |
5.3. |
Main Entrance | ||
5.3.a. |
The door is inaccessible because the threshold is ¾ inches high and is not beveled. |
D23 |
18 months |
5.3.b. |
The door is inaccessible because knob hardware is used. |
D1 |
18 months |
5.4. |
Lobby Drinking Fountain | ||
5.4.a. |
The drinking fountain protrudes into the walkway and is not detectable to blind persons using a cane. |
AR8 |
18 months |
5.4.b. |
Although an accessible drinking fountain is provided, there is no drinking fountain provided for people who have difficulty bending or stooping. |
DF3 |
18 months |
5.5. |
Lobby Single User Toilet Room | ||
5.5.a. |
The toilet room sign is mounted with its centerline 61 inches high. |
TR18 |
18 months |
5.5.b. |
The pull side of the toilet room door, which is accessed through a front approach, is inaccessible because it has 15 inches of clear maneuvering width on the latch side. |
D6 |
18 months |
5.5.c. |
The lavatory is inaccessible because the clear floor space is obstructed by a chair and shelves. |
TR8 |
18 months |
5.5.d. |
The toilet is inaccessible because the side grab bar is mounted 36¾ inches high with the far end 48 inches from the rear wall. |
SU5 |
18 months |
5.5.e. |
The rear grab bar at the toilet is inaccessible because it is mounted 12 inches from the side wall. |
SU3 |
18 months |
5.6. |
Lobby/Reception | ||
5.6.a. |
The counter in the lobby protrudes into the walkway and is not detectable to blind persons using a cane. |
AR8 |
18 months |
5.6.b. |
The door from the lobby to the hallway is inaccessible because knob hardware is used. |
D1 |
18 months |
5.6.c. |
The pull side of the door from the lobby to the hallway, which is accessed through a front approach, is inaccessible because it has 7½ inches of maneuvering clearance on the latch side. |
D6 |
18 months |
5.7. |
Holding cell: The cell is inaccessible because the clear opening width of the entrance door is 31 inches. |
D25, PJ1 |
18 months |
5.8. |
Detention Area Single User Toilet Room | ||
5.8.a. |
There is insufficient turning space within the toilet room due to the placement of the portable paper shredder. |
TR19 |
18 months |
5.8.b. |
The lavatory is inaccessible because the hot water and drain pipes are not insulated or otherwise configured to protect against contact. |
TR12 |
18 months |
5.8.c. |
The toilet is inaccessible because the side grab bar is mounted with its far end 48 inches from the rear wall. |
SU6 |
18 months |
5.8.d. |
The toilet is inaccessible because the grab bars are mounted between 36½ and 36¾ inches high. |
SU11 |
18 months |
5.9. |
Courtroom: The courtrooms are inaccessible to persons with hearing disabilities because there is no assistive listening system provided. |
AA5 |
18 months |
6. |
Magistrate Office, located at 2318 Moyer Road, Connellsville | ||
6.1. |
Parking: The parking lot, with a total of 12 parking spaces, is inaccessible because it has no parking spaces designated as reserved for persons with disabilities. This lot requires 1 van accessible space. |
P3 |
12 months |
6.2. |
Main Entrance | ||
6.2.a. |
The entrance is inaccessible because the landing has a running slope of 11.9% within the door's required maneuvering clearance. |
D13 |
12 months |
6.2.b. |
The entrance ramp is inaccessible because it slopes 11.9% and it has no handrails. |
R5 |
12 months |
6.2.c. |
The entrance door is inaccessible because the threshold is 1 inch high. |
D23 |
12 months |
6.2.d. |
The entrance door is inaccessible because knob hardware is used. |
D1 |
12 months |
6.2.e. |
The pull side of the entrance door, which is accessed through a front approach, is inaccessible because it has 10 inches of clear space on the latch side. |
D6 |
12 months |
6.2.f. |
The push side of the entrance door, which is accessed through a front approach and which has both a closer and a latch, is inaccessible because it has only 9 inches of clear space on the latch side. |
D7 |
12 months |
6.3. |
Lobby Counter: The counter is inaccessible because it is 45 inches high. |
C6 |
12 months |
6.4. |
Lobby Single User Toilet Room | ||
6.4.a. |
The toilet room sign is mounted on the door and has no raised or Braille characters. |
TR18 |
12 months |
6.4.b. |
The door is inaccessible because knob hardware is used. |
D1 |
12 months |
6.4.c. |
The lavatory is inaccessible because the hot water and drain pipes are not insulated or otherwise configured to protect against contact. |
TR12 |
12 months |
6.4.d. |
The toilet is inaccessible because the centerline is 20 inches from the side wall. |
SU15 |
12 months |
6.4.e. |
The toilet is inaccessible because the flush control is on the closed side. |
SU1 |
12 months |
6.4.f. |
The side grab bar is inaccessible because it is 32 inches long and it is mounted with the closer end 13½ inches from the rear wall. |
SU6 |
12 months |
6.4.g. |
The rear grab bar is inaccessible because it is 24 inches long and it is mounted with the closer end 8 inches from the side wall. |
SU3 |
12 months |
6.4.h. |
The grab bars are inaccessible because they have a diameter of 1 inch. |
SU9 |
12 months |
6.5. |
Courtroom: The courtroom entrance door is inaccessible because knob hardware is used. |
D1 |
12 months |
7. |
Magistrate Office, located at 1020 Franklin Drive, Suite 1, Smock | ||
7.1. |
Parking: The van accessible parking is inaccessible because it because it lacks the appropriate vertical signage. |
P6 |
18 months |
7.2. |
Lobby Counter: The counter protrudes into the walkway and is not detectable to blind persons using a cane. |
AR8 |
18 months |
7.3. |
Lobby Single User Toilet Room | ||
7.3.a. |
The toilet room sign is mounted with its centerline 64 inches high. |
TR18 |
18 months |
7.3.b. |
The pull side of the entrance door, which is accessed through a front approach, is inaccessible because it has 10½ inches of maneuvering clearance on the latch side. |
D6 |
18 months |
7.3.c. |
No accessible mirror is provided. |
TR14 |
18 months |
7.3.d. |
The lavatory is inaccessible because the counter is 35½ inches high to the top. |
TR11 |
18 months |
7.3.e. |
The lavatory is inaccessible because the hot water and drain pipes are not insulated or otherwise configured to protect against contact. |
TR12 |
18 months |
7.3.f. |
The toilet is inaccessible because the side grab bar is mounted with the far end 49 inches from the rear wall. |
SU6 |
18 months |
7.3.g. |
The toilet is inaccessible because the rear grab bar is 30 inches long. |
SU3 |
18 months |
7.4. |
Courtroom | ||
7.4.a. |
The witness stand is inaccessible because the route to the witness stand has an 8 inch high step and the route narrows to 27 inches wide. |
AA8, AR1 |
18 months |
7.4.b. |
The table provided for attorneys and clients is inaccessible because it has clear knee space 25 inches high. |
T1 |
18 months |
7.4.c. |
The courtroom is inaccessible to persons with hearing disabilities because there is no assistive listening system provided. |
AA5 |
18 months |
7.5. |
Conference Room: The door is inaccessible because knob hardware is used. |
D1 |
18 months |
7.6. |
Detention Area Single User Toilet Room | ||
7.6.a. |
The lavatory is inaccessible because it is 35¾ inches high to the top, the hot water and drain pipes are not covered or otherwise configured to protect against contact, and it has knob hardware. |
TR9 |
18 months |
7.6.b. |
The toilet is inaccessible because the top of the seat is 15½ inches high. |
SU18 |
18 months |
7.6.c. |
The toilet is inaccessible because the centerline is 19 inches from the side wall. |
SU15 |
18 months |
7.6.d. |
The toilet is inaccessible because no grab bars are provided. |
SU10 |
18 months |
7.7. |
Exterior Defendants' Door: The door is inaccessible because it has a step 3¾ inches high. |
AR1, D22, R5 |
18 months |
8. |
Magistrate Office, located at 362 South Mount Vernon, Uniontown | ||
8.1. |
Parking: The van accessible parking space is inaccessible because the sign is mounted too low. |
P6 |
12 months |
8.2. |
Entrance Ramp: The ramp is inaccessible because there is a 1½ inch step onto the bottom of the ramp, there is a handrail on only one side, and there is an insufficient extension at the bottom of the handrail. |
R5 |
12 months |
8.3. |
Lobby Drinking Fountain: Although an accessible drinking fountain is provided, there is no drinking fountain provided for people who have difficulty bending or stooping. |
DF3 |
12 months |
8.4. |
Counter at Reception Window: The counter protrudes into the walkway and is not detectable to blind persons using a cane. |
AR8 |
12 months |
8.5. |
Lobby Single User Toilet Room | ||
8.5.a. |
The sign is mounted on the door with its centerline 64 inches high. |
TR18 |
12 months |
8.5.b. |
The toilet room is inaccessible because the route to the entrance is 30½ inches wide between the door frame and the chair. |
AR3 |
12 months |
8.5.c. |
The lavatory is inaccessible because the hot water and drain pipes are not insulated or otherwise configured to protect against contact. |
TR12 |
12 months |
8.5.d. |
The toilet is inaccessible because the centerline is 19 inches from the side wall. |
SU15 |
12 months |
8.5.e. |
The toilet is inaccessible because the flush control is on the closed side. |
SU1 |
12 months |
8.5.f. |
The side grab bar at the toilet is inaccessible because it is mounted with the far side 44 inches from the rear wall. |
SU6 |
12 months |
8.6. |
Courtroom | ||
8.6.a. |
The witness stand is inaccessible because the route to it is 30 inches wide and there is a 4 inch high step. |
AA8, AR1 |
12 months |
8.6.b. |
The courtroom is inaccessible to persons with hearing disabilities because there is no assistive listening system provided. |
AA5 |
12 months |
8.7. |
Conference Room | ||
8.8. |
The pull side of the door, which is accessed through a latch approach, is inaccessible because it has 5 inches of clear space on the latch side. |
D10 |
12 months |
8.9. |
The push side of the door, which is accessed through a hinge approach, is inaccessible because it has only 37 inches of clear depth. |
D9 |
12 months |