ATTACHMENT I: Modifications to Newly Constructed Facilities
Please Note: Paragraph 43 of the Settlement Agreement requires that within three months of the effective date of this Agreement, the City provide signage as necessary to comply with 28 C.F.R. § 35.163(b), after having surveyed all facilities that are the subject of this Agreement for the purpose of identifying those that have multiple entrances not all of which are accessible. The chart below lists the facilities surveyed by the Department, the access issues identified during the survey, and the actions required to correct the access issues. Required actions are listed using an alphanumeric code. The key to the alphanumeric codes is provided in Attachment M to this Agreement. In order to ensure that the following spaces and elements in City facilities, for which construction was commenced after January 26, 1992, are readily accessible to and usable by persons with disabilities, the City will take the actions referenced by the alphanumeric code and described in detail in Attachment M to this Settlement Agreement within the time periods specified below, which time periods will begin to run on the effective date of this Agreement. |
|||
Item # |
Access Issue |
Required Action |
Completion Date |
---|---|---|---|
1. |
Metro Transit Garage: 23rd Street North | ||
1.1. |
Parking. The parking reserved for persons with disabilities is inaccessible because the signs are mounted too low and can be obstructed by vehicles parked in the spaces. |
P6 |
12 months |
1.2. |
Route to Entrance. One of the curb ramps from the parking lot is inaccessible because it has a slope of 9.9%. |
AR5 |
12 months |
1.3. |
Front Counter | ||
1.3.a. |
The counter is inaccessible because its top surface is 43 inches above the finished floor. |
C6 |
12 months |
1.3.b. |
The counter top protrudes into the walkway and is not detectable to blind persons using a cane. |
AR8 |
12 months |
1.4. |
Men´s Toilet Room with Stalls | ||
1.4.a. |
The toilet room sign is mounted 56 inches above the finished floor. |
TR18 |
12 months |
1.4.b. |
The door is inaccessible because it requires 11 pounds of force to open. |
D2 |
12 months |
1.4.c. |
The toilet paper dispenser in the designated accessible stall is inaccessible because it is mounted 41 inches from the rear wall. |
ST19 |
12 months |
1.4.d. |
The lower urinal is inaccessible because the clear floor space is less than 30 inches wide. |
TR20 |
12 months |
1.5. |
Women´s Toilet Room with Stalls | ||
1.5.a. |
The toilet room sign is mounted with its centerline 56 inches above the finished floor. |
TR18 |
12 months |
1.5.b. |
The door is inaccessible because it requires 10 pounds of force to open. |
D2 |
12 months |
1.5.c. |
The toilet paper dispenser in the designated accessible stall is inaccessible because it is mounted 42 inches from the rear wall. |
ST19 |
12 months |
1.5.d. |
The shelf mounted in the stall protrudes into the walkway and is not detectable to blind persons using a cane. |
AR8 |
12 months |
1.6. |
Drinking Fountain. Although a designated accessible drinking fountain is provided, no drinking fountain has been provided for persons who have difficulty bending or stooping. |
DF3 |
12 months |
2. |
Northport Library: 2714 Broadway | ||
2.1. |
Women´s Single User Toilet Room | ||
2.1.a. |
The door is inaccessible because it requires 10 pounds of force to open. |
D2 |
12 months |
2.1.b. |
No accessible mirror has been provided. |
TR14 |
12 months |
2.1.c. |
The toilet is inaccessible because the top of the seat is 16 inches above the finished floor. |
SU18 |
12 months |
2.1.d. |
The toilet is inaccessible because its centerline is 20 inches from the side wall. |
SU15 |
12 months |
2.1.e. |
The side grab bar at the toilet is inaccessible because it is obstructed by the vertical grab bar. |
SU8 |
12 months |
2.1.f. |
The hazardous waste disposal protrudes into the walkway and is not detectable to blind persons using a cane. |
AR8 |
12 months |
2.2. |
Men´s Single User Toilet Room | ||
2.2.a. |
The door is inaccessible because it requires 12 pounds of force to open. |
D2 |
12 months |
2.2.b. |
No accessible mirror has been provided. |
TR14 |
12 months |
2.2.c. |
The toilet is inaccessible because the top of the seat is 16½ inches above the finished floor. |
SU18 |
12 months |
2.2.d. |
The toilet is inaccessible because its centerline is 15 inches from the side wall. |
SU15 |
12 months |
2.2.e. |
The toilet paper dispenser is inaccessible because it is mounted 40 inches from the rear wall. |
SU17 |
12 months |
2.2.f. |
The side grab bar at the toilet is inaccessible because it is obstructed by the toilet paper dispenser, the vertical grab bar, and the hazardous waste disposal. |
SU7 |
12 months |
2.2.g. |
The toilet is inaccessible because the flush control is on the closed side. |
SU1 |
12 months |
2.2.h. |
The hazardous waste disposal protrudes into the walkway and is not detectable to blind persons using a cane. |
AR8 |
12 months |
3. |
Public Safety Building: 4630 15th Avenue North | ||
3.1. |
Interior Route. The "Elevator" sign protrudes into the walkway and is not detectable to blind persons using a cane. |
AR8 |
12 months |
3.2. |
Emergency Management Counter. The counter top protrudes into the walkway and is not detectable to blind persons using a cane. |
AR8 |
12 months |
3.3. |
Women´s First Floor Toilet Room with Stalls | ||
3.3.a. |
No accessible mirror has been provided. |
TR14 |
12 months |
3.3.b. |
The paper towel dispenser is inaccessible because it is mounted with the controls 55 inches above the finished floor. |
TR5 |
12 months |
3.3.c. |
The hazardous waste disposal protrudes into the walkway and is not detectable to blind persons using a cane. |
AR8 |
12 months |
3.4. |
Men´s First Floor Toilet Room with Stalls | ||
3.4.a. |
The paper towel dispenser is inaccessible because it is mounted with the controls 55 inches above the finished floor. |
TR5 |
12 months |
3.4.b. |
The hazardous waste disposal protrudes into the walkway and is not detectable to blind persons using a cane. |
AR8 |
12 months |
3.5. |
First Floor Drinking Fountain. Although a designated accessible drinking fountain is provided, no drinking fountain has been provided for persons who have difficulty bending or stooping. |
DF3 |
12 months |
3.6. |
Women´s Second Floor Toilet Room with Stalls. The paper towel dispenser is inaccessible because it is mounted with the controls 55 inches above the finished floor. |
TR5 |
12 months |
3.7. |
Men´s Second Floor Toilet Room with Stalls. The paper towel dispenser is inaccessible because it is mounted with the controls 55 inches above the finished floor. |
TR5 |
12 months |
3.8. |
Second Floor Drinking Fountain. Although a designated accessible drinking fountain is provided, no drinking fountain has been provided for persons who have difficulty bending or stooping. |
DF3 |
12 months |
3.9. |
Fire House #6 | ||
3.9.a. |
Although a designated accessible drinking fountain is provided, no drinking fountain has been provided for persons who have difficulty bending or stooping. |
DF3 |
12 months |
3.9.b. |
In both single user toilet/shower rooms in the living area, no accessible mirror has been provided. The remedial action is required for each of the single user toilet rooms. |
TR14 |
12 months |
3.9.c. |
In the single user toilet room in the bay, no accessible mirror has been provided. |
TR14 |
12 months |
3.9.d. |
In the single user toilet room in the bay, the door swings into clear floor space of the lavatory. |
TR6 |
12 months |
4. |
Newman Outdoor Field: 1515 15th Avenue North | ||
4.1. |
Entrances. The building does not have directional signage posted at inaccessible entrances and does not have the International Symbol of Accessibility posted at accessible entrances. |
D16 |
30 months |
4.2. |
Seating. The stadium containing 4690 seats is inaccessible because wheelchair seating areas are not an integral part of the fixed seating plan. It is required that the wheelchair seating is integrated among the fixed seating. |
AA6 |
30 months |
4.3. |
Seating. The stadium, containing 4690 seats, is inaccessible because a fixed companion seat is not provided next to each wheelchair seating area. A total of 47 wheelchair seating areas is required. |
AA7 |
30 months |
4.4. |
Drinking Fountains. Although accessible drinking fountains are provided for use by persons who use wheelchairs, no drinking fountains provided for individuals who have difficulty bending or stooping. |
DF3 |
30 months |
4.5. |
Lower Level Men´s Single User Toilet Room | ||
4.5.a. |
The door is inaccessible because it requires 15 pounds of force to open. |
D2 |
30 months |
4.5.b. |
The toilet room door swings into the required clear floor space at the lavatory. |
TR6 |
30 months |
4.5.c. |
The lavatory is inaccessible because the hot water pipes are not insulated or otherwise configured to protect against contact. |
TR12 |
30 months |
4.6. |
Lower Level Women´s Single User Toilet Room | ||
4.6.a. |
The door is inaccessible because it requires 16 pounds of force to open. |
D2 |
30 months |
4.6.b. |
The lavatory is inaccessible because the hot water pipes are not insulated or otherwise configured to protect against contact. |
TR12 |
30 months |
4.7. |
Elevator Near Main Lobby | ||
4.7.a. |
The elevator is inaccessible because the hall lanterns signal once only to indicate when a car is answering a call and do not provide an audible indication of whether the elevator is traveling up or down. |
E11 |
30 months |
4.7.b. |
The elevator is inaccessible because the emergency system requires voice communication to operate, and it requires tight grasping or pinching to access. |
E8 |
30 months |
4.8. |
Umpire´s Single User Toilet Room | ||
4.8.a. |
The door is inaccessible because it requires more than 5 pounds of force to open. |
D2 |
30 months |
4.8.b. |
No accessible locker has been provided. |
LR3 |
30 months |
4.8.c. |
The lavatory is inaccessible because the hot water pipes are not insulated or otherwise configured to protect against contact. |
TR12 |
30 months |
4.8.d. |
The urinal is inaccessible because its rim is 24 inches above the finished floor and the flush control is 47½ inches above the finished floor. |
TR20 |
30 months |
4.8.e. |
The side grab bar at the toilet is inaccessible because it is mounted with the far end 48½ inches from the rear wall. |
SU6 |
30 months |
4.8.f. |
The transfer shower is inaccessible because has no seat or grab bars and the shower spray unit cannot be handheld. |
B8 |
30 months |
4.9. |
Visitor´s Locker Room | ||
4.9.a. |
The entry door is inaccessible because it requires more than 5 pounds of force to open. |
D2 |
30 months |
4.9.b. |
The lavatories in the main locker room and in the private locker room are inaccessible because the hot water pipes are not insulated or otherwise configured to protect against contact. Remedial action is required in each location. |
TR12 |
30 months |
4.9.c. |
The urinal in the private locker room is inaccessible because the rim is 24½ inches above the finished floor and the flush control is 48 inches above the finished floor. |
TR20 |
30 months |
4.9.d. |
The side grab bar at the designated accessible toilet in the main locker room is inaccessible because it is mounted with the far end 42½ inches from the rear wall. |
ST7 |
30 months |
4.9.e. |
There is no accessible shower provided in the main locker room or in the private locker room. |
B8 |
30 months |
4.9.f. |
No accessible locker has been provided in the main locker room or in the private locker room. Remedial action is required in each locker room. |
LR3 |
30 months |
4.10. |
Team Locker Room | ||
4.10.a. |
The lavatories in the main locker room and in the private locker room are inaccessible because the hot water pipes are not insulated or otherwise configured to protect against contact. Remedial action is required in each location. |
TR12 |
30 months |
4.10.b. |
The designated accessible toilet in the main locker room is inaccessible because its centerline is 21 inches from the side wall. |
ST17 |
30 months |
4.10.c. |
The side grab bar at the designated accessible toilet in the main locker room is inaccessible because it is obstructed by the toilet paper dispenser. |
ST8 |
30 months |
4.10.d. |
No accessible shower has been provided in the main locker room or in the private locker room. Remedial action is required in each location. |
B8 |
30 months |
4.10.e. |
No accessible locker has been provided in the main locker room or in the private locker room. Remedial action is required in each location. |
LR3 |
30 months |
4.11. |
Dugouts. No accessible route is provided to either dugout because the routes all contain stairs. An accessible route to each dugout is required. |
AR1 |
30 months |
4.12. |
Women´s East Side Toilet Room with Stalls on Main Concourse 2nd Level | ||
4.12.a. |
The door is inaccessible because it requires 8 pounds of force to open. |
D2 |
30 months |
4.12.b. |
The lavatory is inaccessible because the hot water pipes are not insulated or otherwise configured to protect against contact. |
TR12 |
30 months |
4.13. |
Men´s East Side Toilet Room with Stalls on Main Concourse 2nd Level | ||
4.13.a. |
The door is inaccessible because it requires 19 pounds of force to open. |
D2 |
30 months |
4.13.b. |
The lavatory is inaccessible because the hot water pipes are not insulated or otherwise configured to protect against contact. |
TR12 |
30 months |
4.14. |
Women´s West Side Toilet Room with Stalls on Main Concourse 2nd Level | ||
4.14.a. |
The door is inaccessible because it requires 10 pounds of force to open. |
D2 |
30 months |
4.14.b. |
The lavatory is inaccessible because the hot water pipes are not insulated or otherwise configured to protect against contact. |
TR12 |
30 months |
4.14.c. |
The ambulatory stall is inaccessible because the toilet´s centerline is 20 inches from one side wall. |
ST1 |
30 months |
4.15. |
Men´s West Side Toilet Room with Stalls on Main Concourse 2nd Level | ||
4.15.a. |
The door is inaccessible because it requires 15 pounds of force to open. |
D2 |
30 months |
4.15.b. |
The lavatory is inaccessible because the hot water pipes are not insulated or otherwise configured to protect against contact. |
TR12 |
30 months |
4.16. |
Unisex Single User Toilet Room on Main Concourse East Side 2nd Level | ||
4.16.a. |
The toilet room sign is mounted on the door. |
TR18 |
30 months |
4.16.b. |
The paper towel dispenser protrudes into the walkway and is not detectable to blind persons using a cane. |
AR8 |
30 months |
4.16.c. |
The lavatory is inaccessible because the hot water pipes are not insulated or otherwise configured to protect against contact. |
TR12 |
30 months |
4.16.d. |
The toilet is inaccessible because the flush control is on the closed side. |
SU1 |
30 months |
4.16.e. |
The side grab bar at the toilet is inaccessible because it is mounted with the far end 52 inches from the rear wall. |
SU6 |
30 months |
4.16.f. |
The rear grab bar at the toilet is inaccessible because it is 24 inches long. |
SU3 |
30 months |
4.17. |
Unisex Single User Toilet Room on Main Concourse West Side 2nd Level | ||
4.17.a. |
The toilet room sign is mounted on the door. |
TR18 |
30 months |
4.17.b. |
The paper towel dispenser protrudes into the walkway and is not detectable to blind persons using a cane. |
AR8 |
30 months |
4.17.c. |
The lavatory is inaccessible because the hot water pipes are not insulated or otherwise configured to protect against contact. |
TR12 |
30 months |
4.17.d. |
The side grab bar at the toilet is inaccessible because it is mounted with the far end 51 inches from the rear wall. |
SU6 |
30 months |
4.17.e. |
The rear grab bar at the toilet is inaccessible because it is 24 inches long. |
SU3 |
30 months |
4.18. |
Women´s Toilet Room with Stalls on 3rd Level | ||
4.18.a. |
The door is inaccessible because it requires 15 pounds of force to open. |
D2 |
30 months |
4.18.b. |
The lavatory is inaccessible because the hot water pipes are not insulated or otherwise configured to protect against contact. |
TR12 |
30 months |
4.18.c. |
The paper towel dispenser protrudes into the walkway and is not detectable to blind persons using a cane. |
AR8 |
30 months |
4.18.d. |
The side grab bar at the designated accessible toilet is inaccessible because it is obstructed by the toilet paper dispenser and trash receptacle. |
ST8 |
30 months |
4.19. |
Men´s Toilet Room with Stalls on 3rd Level | ||
4.19.a. |
The toilet room sign is mounted on the door. |
TR18 |
30 months |
4.19.b. |
The door is inaccessible because it requires 15 pounds of force to open. |
D2 |
30 months |
4.19.c. |
The paper towel dispenser protrudes into the walkway and is not detectable to blind persons using a cane. |
AR8 |
30 months |
4.19.d. |
The lavatory is inaccessible because the hot water pipes are not insulated or otherwise configured to protect against contact. |
TR12 |
30 months |
4.19.e. |
The side grab bar at the designated accessible toilet is inaccessible because it is obstructed by the toilet paper dispenser. |
ST8 |
30 months |
5. |
Fargo Moorhead Convention and Visitor´s Bureau: 2001 44th Street | ||
5.1. |
Parking. The parking lot, with a total of 76 parking spaces, is inaccessible because there is no van accessible space and access aisles are not provided for the standard accessible spaces. This lot requires 1 van accessible space and 3 standard accessible spaces. |
P3 |
18 months |
5.2. |
Men´s Lobby Toilet Room with Stalls | ||
5.2.a. |
The designated accessible toilet is inaccessible because the rear grab bar is obstructed by the seat cover dispenser. |
ST5 |
18 months |
5.2.b. |
The lavatory is inaccessible because the bottom of its apron is 28½ inches above the finished floor. |
TR11 |
18 months |
5.2.c. |
The lavatory is inaccessible because the hot water pipes are not insulated or otherwise configured to protect against contact. |
TR12 |
18 months |
5.2.d. |
The urinal is inaccessible because the rim is 18½ inches above the finished floor. |
TR20 |
18 months |
5.2.e. |
The designated accessible toilet is inaccessible because the top of the seat is 19¾ inches above the finished floor. |
ST20 |
18 months |
5.3. |
Women´s Lobby Toilet Room with Stalls | ||
5.3.a. |
The designated accessible toilet is inaccessible because the rear grab bar is obstructed by the seat cover dispenser. |
ST5 |
18 months |
5.3.b. |
The lavatory is inaccessible because the bottom of the apron is 28½ inches above the finished floor. |
TR11 |
18 months |
5.3.c. |
The lavatory is inaccessible because the hot water pipes are not insulated or otherwise configured to protect against contact. |
TR12 |
18 months |
5.3.d. |
The designated accessible toilet is inaccessible because the top of the seat is 19¾ inches above the finished floor. |
ST20 |
18 months |
5.3.e. |
The designated accessible toilet is inaccessible because its centerline is 17 inches from the side wall. |
ST17 |
18 months |
5.3.f. |
The designated accessible toilet is inaccessible because the flush control is on the closed side. |
ST2 |
18 months |
5.4. |
Lobby Drinking Fountain. Although a designated accessible drinking fountain is provided for persons who use wheelchairs, no drinking fountain has been provided for persons who have difficulty bending or stooping. |
DF3 |
18 months |
5.5. |
Lobby Visitor Telephone | ||
5.5.a. |
The telephone is inaccessible because it is mounted over a counter with its highest operable part 57 inches above the finished floor. |
TR4 |
18 months |
5.5.b. |
The telephone is inaccessible because it is not hearing aid compatible and it does not have volume control. |
TT1 |
18 months |
5.6. |
Route to Picnic Pavilion. The route is inaccessible because the grass and concrete blocks are not stable, firm, and slip resistant. |
AR1 |
18 months |