ATTACHMENT K: Program Access in Existing FacilitiesPlease Note: Paragraph 90 of the Agreement requires that within three months of the effective date of this Agreement, the County will provide signage as necessary to comply with 28 C.F.R. § 35.163(b), after having surveyed all facilities that are the subject of this Agreement for the purpose of identifying those that have multiple entrances not all of which are accessible. The technical requirements and, where appropriate, the scoping requirements of the Standards are used as a guide for determining whether a program or activity held in an existing facility is “readily accessible to and usable by” persons with disabilities and for determining what changes are necessary to make this program or activity accessible if it continues to be provided in the existing facility in question. See 28 C.F.R. §§ 35.150(b)(1), 35.151. The chart below lists the facilities surveyed by the Department, the access issues identified during the survey, and the actions required to correct the access issues. Required actions are listed using an alphanumeric code. The key to the alphanumeric codes is provided in Attachment M to this Agreement. In order to ensure that the programs, services, and activities housed in the County’s facilities are accessible to persons with disabilities, when viewed in their entirety, the County will take the actions referenced by the alphanumeric code and described in detail in Attachment M to this Settlement Agreement within the time period specified below, which time period begins to run on the effective date of the Agreement. |
||
|
Req’d Action |
Completion Date |
---|---|---|
1. Sherwood Regional Library 2501 Sherwood Hall Lane Alexandria, VA 22306 |
|
|
1-1 Accessible Route to Front Entrance |
|
|
1-1. a The route from the parking to the entrance is inaccessible because the curb ramp on the library side of the driveway has a right flared side with a cross slope of 2.8% and a left flared side with a cross slope of 3.3%. |
AR5 |
6 months |
1-1. b The outside book return repository is mounted with the operating mechanism 56 inches above the finished floor. |
TR5 |
6 months |
1-2 First Floor/Ground Level |
|
|
1-2. a Main Library Area |
|
|
1-2. a (1) The computer print station table in the main room is inaccessible because it has a knee clearance of 26 inches. |
T1 |
6 months |
1-2. a (2) The catalogue computer station table in the main room is inaccessible because it has a knee clearance of 25 inches high. |
C3 |
6 months |
1-2. a (3) The square library tables in the main room are inaccessible because they have a knee clearance of 24.75 inches high. |
T1 |
6 months |
1-2. b Designated Accessible Women’s Toilet Room with Stalls |
|
|
1-2. b (1) The toilet room sign is inaccessible because it is mounted on the door. |
TR17 |
6 months |
1-2. b (2) Although an audible alarm is provided in this facility, there is no visual alarm appliance in the toilet room. |
TR21 |
6 months |
1-2. b (3) The toilet is inaccessible because the top of the seat is 16.25 inches above the finished floor. |
ST20 |
6 months |
1-2. b (4) The toilet is inaccessible because its centerline is 17 inches from the side wall. |
ST17 |
6 months |
1-2. b (5) The toilet paper dispenser is inaccessible because it is located 14 inches above the side grab bar. |
ST19 |
6 months |
1-2. b (6) The side grab bar is inaccessible because the closer end is 13 inches from the rear wall. |
ST7 |
6 months |
1-2. c Designated Accessible Men’s Toilet Room with Stalls |
|
|
1-2. c (1) The toilet room sign is inaccessible because it is mounted on the door. |
ST17 |
6 months |
1-2. c (2) The door to the toilet room is inaccessible because the pressure required to open the door is 6 pounds. |
D2 |
6 months |
1-2. c (3) Although an audible alarm is provided in this facility, there is no visual alarm appliance in the toilet room. |
TR21 |
6 months |
1-2. c (4) The urinal is inaccessible because the rim is 18 inches above the finished floor, the clear floor space in front of it is 29 inches wide, and the flush control is 51 inches above the finished floor. |
TR20 |
6 months |
1-2. c (5) The toilet is inaccessible because the top of the seat is 16.25 inches above the finished floor. |
ST20 |
6 months |
1-2. c (6) The toilet is inaccessible because its centerline is 17 inches from the side wall. |
ST17 |
6 months |
1-2. c (7) The toilet paper dispenser is inaccessible because it is located 10.5 inches above the side grab bar. |
ST19 |
6 months |
1-2. d Drinking Fountains near Toilet Rooms |
|
|
1-2. d (1) The higher drinking fountain protrudes into the walkway and would not be detectable to a blind person using a cane. |
AR8 |
6 months |
1-2. d (2) The lower drinking fountain is inaccessible because the knee clearance is 26.25 inches above the finished floor. |
DF5 |
6 months |
1-2. e Carrel 1 Study Room |
|
|
1-2. e (1) The signage for Carrel 1 Study Room is inaccessible because it is mounted on the door and there are no raised characters or Braille. |
D26 |
6 months |
1-2. e (2) The door is inaccessible because it has knob hardware and an opening width of 29 inches. |
D18 |
6 months |
1-2. e (3) The door is inaccessible because the maneuvering clearance on the pull side of the door, which is accessed through a front approach, is blocked by the presence of a built-in desk. |
D6 |
6 months |
1-2. e (4) The fixed study table is inaccessible because it provides 24.5 inches of knee space height. |
T1 |
6 months |
1-2. f Group Study Room |
|
|
1-2. f (1) The door is inaccessible because it has knob hardware. |
D1 |
6 months |
1-2. f (2) The fixed table is inaccessible because it is 24.5 inches of knee space height. |
T1 |
6 months |
1-2. g Local Informational Display |
|
|
1-2. g (1) The top shelf of the local information display is 45.75 inches above the finished floor with a reach over an obstruction of 21.5 inches. |
TR4 |
6 months |
1-2. h Public Pay Telephone near Group Study Room |
|
|
1-2. h (1) The telephone is inaccessible because the clear floor space is blocked by a chair. |
TT1 |
6 months |
1-2. i Kitchenette adjacent to Meeting Room |
|
|
1-2. i (1) The counter in the kitchenette adjacent to the meeting room is inaccessible because it is 36.5 inches above the finished floor. |
C8 |
6 months |
1-2. j Microforms Room |
|
|
1-2. j (1) The microfiche desk is inaccessible because the table is 24 inches of knee space height and there is no toe clearance under the table. |
T1 |
6 months |
1-3 Second Floor Men’s and Women’s Toilet Rooms with Stalls |
|
|
1-3. a The toilet room signage at each toilet room is mounted on the door. |
TR17 |
6 months |
1-3. b There is no signage directing people with disabilities to the accessible toilet rooms. |
TR16 |
6 months |
1-4 Second Floor Drinking Fountain near Toilet Rooms |
|
|
1-4. a Although a drinking fountain is provided, the drinking fountain is not accessible because the water flow height is less than 4 inches high. |
DF1 |
6 months |
1-5 Second Floor Offices |
|
|
1-5. a Many office doors on the second floor are inaccessible because they have knob hardware. |
D1 |
6 months |
1-6 Conference Room #2 |
|
|
1-6. a The signage provided for Conference Room #2 is inaccessible because the signage does not have raised characters or Braille. |
D26 |
6 months |
1-7 Tech Lab |
|
|
1-7. a The computer tables in the Tech Lab are inaccessible because they have a 25.75 inch knee clearance height. |
C3 |
6 months |
1-7. b The ceiling-mounted projector protrudes into the walkway and would not be detectable to a blind person using a cane. |
AR8 |
6 months |
1-8 Print Station |
|
|
1-8. a The door to the print station is inaccessible because it has an opening width of only 29 inches. |
D25 |
6 months |
1-8. b The print station computer is inaccessible because there is no knee space under the counter. |
C3 |
6 months |
2. Lincolnia Senior Center 4710 North Chambliss Street Alexandria, VA 22312 |
|
|
2-1 Accessible Route |
|
|
2-1. a The route from parking to the side entrance is inaccessible because the curb ramp adjacent to the van accessible space next to the building has a slope of 13.2%, the left flared side of the curb ramp has a slope of 11.0%, and the right flared side of the curb ramp has a slope of 11.9%. |
AR5 |
6 months |
2-1. b The front entrance ramp is inaccessible because the handrails do not have 12-inch extensions at the bottom landing and the intermediate landing at the change of direction is smaller than 60 inches by 60 inches. |
R3 |
6 months |
2-2 Lounge Area |
|
|
2-2. a The door to the lounge is inaccessible because the pressure required to open the door is 8 pounds. |
D2 |
6 months |
2-3 Men’s Toilet Room with Stalls |
|
|
2-3. a The toilet room signage is inaccessible because it lacks raised characters and Braille. |
TR17 |
6 months |
2-3. b The door is inaccessible because the pressure required to open the door is 6 pounds. |
D2 |
6 months |
2-3. c No accessible mirror has been provided. |
TR14 |
6 months |
2-3. d The toilet is inaccessible because its centerline is 20.5 inches from the side wall. |
ST17 |
6 months |
2-3. e No accessible coat hook has been provided. |
TR1 |
6 months |
2-3. f No toilet paper dispenser has been provided on the adjacent wall. |
ST19 |
6 months |
2-3. g The side grab bar is inaccessible because it is mounted 1.75 inches from the wall with the far end 48 inches from the rear wall. |
ST6 |
6 months |
2-3. h The designated accessible toilet is inaccessible because no rear grab bar has been provided. |
ST3 |
6 months |
2-4 Women’s Toilet Room with Stalls |
|
|
2-4. a The toilet room signage is inaccessible because a drinking fountain prevents people from approaching the sign within 3 inches and it lacks raised characters and Braille. |
TR17 |
6 months |
2-4. b The door is inaccessible because the pressure required to open the door is 7 pounds. |
D2 |
6 months |
2-4. c The pull side of the door to the women’s toilet room, which is accessed through a front approach, is inaccessible because it has only 16 inches of clear maneuvering space on the latch side of the door. |
D6 |
6 months |
2-4. d The seat cover dispenser is inaccessible because it is mounted with the operating mechanism 57.5 inches above the finished floor. |
TR5 |
6 months |
2-4. e The toilet is inaccessible because its centerline is 19 inches from the side wall. |
ST17 |
6 months |
2-4. f No accessible coat hook has been provided. |
TR1 |
6 months |
2-4. g The side grab bar is inaccessible because it is mounted with the far end 49 inches from the rear wall, 29 inches above the finished floor, it is obstructed by the window ledge, and it is mounted 1 3/4 inches from the wall. |
ST6 |
6 months |
2-4. h The designated accessible toilet is inaccessible because no rear grab bar is provided. |
ST3 |
6 months |
2-5 Drinking Fountain between Toilet Rooms |
|
|
2-5. a Although an accessible drinking fountain is provided, there is no drinking fountain provided for people who have difficulty bending or stooping. |
DF3 |
6 months |
2-5. b The drinking fountain protrudes into the walkway and would not be detectable to a blind person using a cane. |
AR8 |
6 months |
2-6 Library/Computer Room |
|
|
2-6. a The door is inaccessible because the pressure required to open the door is 10 pounds. |
D2 |
6 months |
2-6. b The push side of the door, which is accessed through a front approach and which has both a closer and a latch, is inaccessible because it has only 1 inch of clear maneuvering space on the latch side of the door. |
D7 |
6 months |
2-6. c The computer tables in the library/computer room are inaccessible because the knee clearance is 24 1/8 inches high. |
C3 |
6 months |
2-7 Arts and Crafts Room |
|
|
2-7. a The pull side of the door, which is accessed through a front approach, is inaccessible because it has only 17 inches of maneuvering clearance on the latch side of the door. |
D6 |
6 months |
2-7. b The push side of the door, which is accessed through a front approach and which has both a closer and a latch, is inaccessible because it has only 1 inch of maneuvering clearance on the latch side of the door. |
D7 |
6 months |
2-7. c The door is inaccessible because the pressure required to open the door is 10 pounds. |
D2 |
6 months |
2-7. d The tables are inaccessible because the knee clearance is 25.5 inches high. |
T1 |
6 months |
2-8 Pool Room |
|
|
2-8. a The door is inaccessible because the pressure required to open the door is 9 pounds. |
D2 |
6 months |
3. Martha Washington Library 6614 Fort Hunt Road Alexandria, VA 22307 |
|
|
3-1 Parking |
|
|
3-1. a The parking reserved for persons with disabilities is inaccessible because the van accessible space slopes 4.8%, the adjoining access aisle slopes 5.8% with a cross slope of 3.7%, and the other designated spaces and access aisles have more than a 2% slope. |
P7 |
6 months |
3-2 Accessible Route |
|
|
3-2. a The route from the top of the hill to the entrance is inaccessible because the slope is 8.8%. |
AR1 |
6 months |
3-3 Exterior Entrance |
|
|
3-3. a The public pay telephone located outside the entrance is inaccessible because the highest operable part is 55 inches from the finished floor. |
TT1 |
6 months |
3-3. b The outside book return repository is inaccessible because the operating mechanism is mounted too high. |
TR5 |
6 months |
3-4 Vestibule |
|
|
3-4. a The high drinking fountain located in the entry vestibule protrudes into the walkway and would not be detectable to a blind person using a cane. |
AR8 |
6 months |
3-4. b The defibrillator located at the entrance to the meeting room protrudes into the walkway and would not be detectable to a blind person using a cane. |
AR8 |
6 months |
3-5 Single-User Toilet Room in Entry Vestibule |
|
|
3-5. a The toilet room sign is inaccessible because it is mounted on the door and lacks raised characters and Braille. |
TR17 |
6 months |
3-5. b The wall-mounted hand sanitizer protrudes into the walkway and would not be detectable to a blind person using a cane. |
AR8 |
6 months |
3-5. c The toilet flush control is inaccessible because it is located on the closed side. |
SU1 |
6 months |
3-5. d The side grab bar is inaccessible because it is mounted with the far end 46 inches from the rear wall. |
SU5 |
6 months |
3-6 Library Area |
|
|
3-6. a The magazine rack is inaccessible because the top shelf is 68 inches above the finished floor. |
LB1 |
6 months |
3-6. b The tables are inaccessible because the knee clearance is 25.75 inches high to the bottom of the table. |
LB4 |
6 months |
4. Mount Vernon Recreation Center 2017 Belle View Boulevard Alexandria, VA 22307 |
|
|
4-1 Drinking Fountains Near Lobby |
|
|
4-1. a The low wall-mounted drinking fountain is inaccessible because the knee clearance is 26 inches high. |
DF3 |
6 months |
4-1. b The high drinking fountain protrudes into the walkway and would not be detectable to a blind person using a cane. |
AR8 |
6 months |
4-2 Drinking Fountain Near Ice Rink |
|
|
4-2. a The drinking fountain is inaccessible because the spout is 40 inches above the finished floor. |
DF6 |
6 months |
4-2. b The drinking fountain protrudes into the walkway and would not be detectable to a blind person using a cane. |
AR8 |
6 months |
4-3 Public Pay Telephones |
|
|
4-3. a The two telephones in the lobby are inaccessible because they do not have volume control. |
TT1 |
6 months |
4-4 Family Accessible Changing Room |
|
|
4-4. a No accessible mirror has been provided. |
TR14 |
6 months |
4-4. b The lavatory is inaccessible because the hot water pipes are not insulated or otherwise configured to protect against contact. |
TR12 |
6 months |
4-4. c The toilet paper dispenser is inaccessible because it is located above the side grab bar. |
ST19 |
6 months |
4-4. d The side grab bar for the toilet is inaccessible because it is mounted with the far end 42 inches from the rear wall. |
ST7 |
6 months |
4-4. e The rear grab bar for the toilet is inaccessible because it is mounted with the closer end 7 inches from the side wall. |
ST4 |
6 months |
4-4. f The shower is inaccessible because the dimensions are 37 by 46.5 inches, the seat does not extend the full depth of the stall, and the shower unit may not be used as both hand-held and fixed. |
B8 |
6 months |
4-4. g The lockers are inaccessible because they require twisting of the wrist. |
TR3 |
6 months |
4-4. h The top tier lockers are inaccessible because the controls are mounted at 68 inches above the finished floor. |
TR5 |
6 months |
4-5 Club Room 2 |
|
|
4-5. a The door to Club Room 2 is inaccessible because the pressure required to open the door is 8 pounds. |
D2 |
6 months |
4-5. b The signage provided is inaccessible because it is mounted on the door. |
D26 |
6 months |
4-6 Toilet Rooms Near Ice Rink |
|
|
4-6. a The signage for the women’s toilet room with stalls near the ice rink indicates that it is accessible, but it is not. |
TR16 |
6 months |
4-6. b The signage provided for the women’s toilet room is inaccessible because it is mounted above the door. |
TR17 |
6 months |
4-6. c The men’s toilet room was not surveyed. Same requirements apply. |
|
|
4-7 Team Locker Rooms |
|
|
4-7. a The signage provided for each team locker room is inaccessible because it is mounted above the door. |
TR17 |
6 months |
4-7. b Locker Rooms 1 and 2 are not accessible. |
LR4 |
6 months |
4-7. c Locker Rooms 3 and 4 are inaccessible because there are no fixed benches in either room. |
LR1 |
6 months |
4-8 Ice Rink |
|
|
4-8. a The ice rink is inaccessible because there is no accessible seating with a view of the rink. |
AA6 |
6 months |
4-8. b The defibrillator near the skate rental counter protrudes into the walkway and would not be detectable to a blind person using a cane. |
AR8 |
6 months |
4-9 Women’s Locker Room |
|
|
4-9. a The signage is inaccessible because it does not have the International Symbol of Accessability, is posted on the hinge side of the door and has a centerline of 61.5 inches above the finished floor. |
TR17 |
6 months |
4-9. b The pull side of the door, which is accessed through a front approach, is inaccessible because it has only 10 inches of space on the latch side of the door. |
D6 |
6 months |
4-9. c The baby changing table is inaccessible because the operating mechanism is 59 inches above the finished floor when in the closed position. |
TR5 |
6 months |
4-9. d The fan, soap dispenser, air dryers, and hanger rods protrude into the walkway and would not be detectable to a blind person using a cane. |
AR8 |
6 months |
4-9. e The lavatory is inaccessible because the hot water pipes are not insulated or otherwise configured to protect against contact. |
TR12 |
6 months |
4-9. f There is no accessible stall provided. |
ST15 |
6 months |
4-9. g The designated accessible shower within the gang shower is inaccessible because the grab bar is not continuous and on three walls. |
B8 |
6 months |
4-9. h The benches are not accessible because they are not attached to the wall. |
LR1 |
6 months |
4-9. i The lockers are inaccessible because they require twisting of the wrist. |
TR2 |
6 months |
4-9. j The top tier lockers with the International Symbol of Accessibility are inaccessible because the operating mechanisms are too high. |
TR5 |
6 months |
4-10 Men’s Locker Room |
|
|
4-10. a The signage is not accessible because it does not have the International Symbol of Accessability, is posted on the hinge side of the door and has a centerline of 61.5 inches above the finished floor. |
TR17 |
6 months |
4-10. b The men’s locker room was not surveyed. |
LR4 |
6 months |
5. Gum Springs Glen Child Care 7839 Richmond Highway Alexandria, VA 22306 |
|
|
5-1 Parking |
|
|
5-1. a Although the parking lot has a total of 21 parking spaces, there is no van accessible parking space and the parking currently reserved for people with disabilities has slopes up to 4.4%. |
P3 |
6 months |
5-2 Accessible Route |
|
|
5-2. a The route from the parking lot to the entrance is inaccessible because the curb ramp has a running slope of 8.7%, and the left flared side has a slope of 10.5%. |
AR5 |
6 months |
5-3 Exterior Entrance |
|
|
5-3. a The exterior entrance door is inaccessible because there is a slope of 3.2% at the entry way within the door’s required maneuvering clearance. |
D13 |
6 months |
5-4 Signage |
|
|
5-4. a Many signs throughout the building are inaccessible because they are mounted at 62.5 inches from the finished floor and are not always located on the latch side of the door. |
D26 |
6 months |
5-5 Lobby |
|
|
5-5. a The counter in the lobby is inaccessible because it is 42 inches above the finished floor. |
C6 |
6 months |
5-5. b The defibrillator protrudes into the walkway and would not be detectable to a blind person using a cane. |
AR8 |
6 months |
5-6 Drinking Fountains Near Lobby Reception Area |
|
|
5-6. a The lower fountain is inaccessible because the water flow height is less than 4 inches high, the controls require 10 pounds of force to operate, and the knee space height is 25.5 inches above the finished floor. |
DF1 |
6 months |
5-7 Women’s Toilet Room with Stalls Near Lobby Reception Area |
|
|
5-7. a No accessible mirror has been provided. |
TR14 |
6 months |
5-7. b The toilet is inaccessible because there is insufficient clear floor space as a waste basket and shelf encroach on it. |
ST18 |
6 months |
5-7. c The seat cover dispenser is inaccessible because it is mounted with the operating mechanism 51.5 inches above the finished floor with a reach over an obstruction. |
TR5 |
6 months |
5-7. d Men’s Toilet Room with Stalls Near Lobby Reception Area |
|
|
5-7. d (1) No accessible mirror has been provided. |
TR14 |
6 months |
5-7. d (2) The lavatory is inaccessible because there is a waste basket under the lavatory interfering with the toe clearance. |
TR8 |
6 months |
5-7. d (3) The seat cover dispenser is inaccessible because it is mounted with the operating mechanism 51.5 inches above the finished floor with a reach over an obstruction. |
TR5 |
6 months |
5-7. d (4) The side grab bar is inaccessible because it is obstructed by the toilet paper dispenser. |
ST9 |
6 months |
5-8 Additional Offices |
|
|
5-8. a The Little Scholars Room |
|
|
5-8. a (1) The door is inaccessible because the pressure required to open the door is 11 pounds. |
D2 |
6 months |
5-8. b Play Room |
|
|
5-8. b (1) Outdoor Drinking Fountain Near Play Area Door |
|
|
5-8. b (1)(a) The outdoor wall-mounted drinking fountain next to the door is inaccessible because the clear floor space is blocked by mats. |
DF5 |
6 months |
5-8. c Rainbow Room |
|
|
5-8. c (1) The door to the Rainbow Room is inaccessible because the pressure required to open the door is 11 pounds. |
D2 |
6 months |
5-9 Women’s Single User Toilet Room near Training Room (Altered Element) |
|
|
5-9. a No accessible mirror has been provided. |
TR14 |
6 months |
5-9. b The seat cover dispenser is inaccessible because the operating mechanism is 50 inches above the finished floor over an obstruction. |
TR5 |
6 months |
5-9. c The toilet paper dispenser is inaccessible because it is mounted more than 36 inches from the rear wall. |
SU17 |
6 months |
5-9. d The side grab bar is inaccessible because it is obstructed by the toilet paper dispenser and it is mounted with the far end 45 inches from the rear wall. |
SU5 |
6 months |
5-9. e The rear grab bar is inaccessible because it is 35 inches from the side wall. |
SU3 |
6 months |
5-10 Men’s Single User Toilet Room near Training Room (Altered Element) |
|
|
5-10. a No accessible mirror has been provided. |
TR14 |
6 months |
5-10. b The seat cover dispenser is inaccessible because the operating mechanism is 50 inches above the finished floor over an obstruction. |
TR5 |
6 months |
5-10. c The side grab bar is inaccessible because it is mounted with the far end 45 inches from the rear wall. |
SU6 |
6 months |
5-10. d The rear grab bar is inaccessible because it is 35 inches from the side wall. |
SU3 |
6 months |
5-11 Additional Rooms (Altered Elements) |
|
|
5-11. a The defibrillator in the hallway protrudes into the walkway and would not be detectable to a blind person using a cane. |
AR8 |
6 months |
5-11. b Computer Room |
|
|
5-11. b (1) The overhead TV monitor in the computer room protrudes into the walkway and would not be detectable to a blind person using a cane. |
AR8 |
6 months |
5-11. c Training Room |
|
|
5-11. c (1) The door is inaccessible because the pressure required to open the door is 8 pounds. |
D2 |
6 months
|
5-11. d Conference Room |
|
|
5-11. d (1) The TV bracket in the Conference Room protrudes into the walkway and would not be detectable to a blind person using a cane. |
AR8 |
6 months |
5-11. e The Busy Bees |
|
|
5-11. e (1) The toilet is inaccessible because there is insufficient clear floor space as the toilet is blocked by a waste can. |
SU16 |
6 months |
5-11. f The Little Engineers |
|
|
5-11. f (1) The door is inaccessible because the pressure required to open the door is 11 pounds. |
D2 |
6 months |
6. Mount Vernon Center for Community Mental Health 8119 Holland Road Alexandria, VA 22306 |
|
|
6-1 Lobby |
|
|
6-1. a The lobby counter protrudes into the walkway and would not be detectable to a blind person using a cane. |
AR8 |
6 months |
6-2 Men’s Toilet Room with Stalls near the Regional ACT Program |
|
|
6-2. a The signage for the toilet room is inaccessible because it is mounted on the door and lacks raised characters and Braille. |
TR17 |
6 months |
6-2. b The urinal rim is inaccessible because it is 18 inches above the finished floor. |
TR20 |
6 months |
6-2. c The side grab bar is inaccessible because it is 24 inches long, the far end is 41 inches from the rear wall, the closer end is 17 inches from the rear wall, it is mounted 30 inches above the finished floor, and it is obstructed by the toilet paper dispenser. |
ST6 |
6 months |
6-3 Women’s Single User Toilet Room Near Room 66 |
|
|
6-3. a The signage for the toilet room is inaccessible because it is mounted on the door, lacks raised characters and Braille and does not have the International Symbol of Accessibility. |
TR17 |
6 months |
6-3. b No accessible coat hook has been provided. |
TR1 |
6 months |
6-3. c The side grab bar is inaccessible because it is 36 inches in length and the far end is 36 inches from the rear wall. |
SU6 |
6 months |
6-4 Drinking Fountain Near Room 66 |
|
|
6-4. a The drinking fountain protrudes into the walkway and would not be detectable to a blind person using a cane. |
AR8 |
6 months |
6-4. b Although a low drinking fountain is provided, there is no drinking fountain provided for people who have difficulty bending or stooping. |
DF3 |
6 months |
6-5 Men’s Toilet Room with Stalls Near Room 117 |
|
|
6-5. a The signage for the toilet room is inaccessible because it is mounted on the door and lacks raised characters and Braille. |
TR17 |
6 months |
6-5. b The seat cover dispenser is inaccessible because it is mounted with the operating mechanism 57.5 inches above the finished floor. |
TR5 |
6 months |
6-5. c The lavatory is inaccessible because it is 35 inches above the finished floor to the top of the rim, and the hot water pipes are not insulated or otherwise configured to protect against contact. |
TR9 |
6 months |
6-5. d The urinal is inaccessible because the urinal centerline is 12 inches from the partition wall and flush control is at 48 inches. |
TR20 |
6 months |
6-5. e The toilet is inaccessible because there is insufficient clear floor space and the flush control is on the closed side. |
ST18, ST2 |
6 months |
6-5. f No accessible coat hook has been provided. |
TR1 |
6 months |
6-5. g The side grab bar is inaccessible because the closer end is 13 inches from the rear wall. |
ST7 |
6 months |
6-5. h The rear grab bar is inaccessible because the closer end is 7.5 inches from the side wall. |
ST4 |
6 months |
6-6 Women’s Toilet Room with Stalls near Room 117 |
|
|
6-6. a The signage for the toilet room is inaccessible because it is mounted on the door and it does not have raised characters or Braille. |
TR17 |
6 months |
6-6. b The lavatory rim is inaccessible because it is 35.5 inches above the finished floor to the top of the rim. |
TR11 |
6 months |
6-6. c The side grab bar is inaccessible because it is 24 inches in length, the far end 49 inches from the rear wall and the closer end 25 inches from the rear wall. |
ST7 |
6 months |
6-6. d The rear grab bar is inaccessible because it is 7.5 inches from the closer end to the side wall. |
ST4 |
6 months |
6-7 Single User Toilet Room by Room 19 |
|
|
6-7. a The signage for the toilet room is inaccessible because it is mounted on the door and lacks raised characters and Braille. |
TR17 |
6 months |
6-7. b No accessible mirror has been provided. |
TR14 |
6 months |
6-7. c The lavatory is inaccessible because the hot water pipes are not insulated or otherwise configured to protect against contact. |
TR12 |
6 months |
6-7. d The toilet is inaccessible because its centerline is 15.5 inches from the side wall. |
SU15 |
6 months |
6-7. e The toilet flush control is inaccessible because it is located on the closed side. |
SU1 |
6 months |
6-7. f The side grab bar is inaccessible because the closer end is 13.5 inches from the rear wall, and it is obstructed by the seat cover dispenser. |
SU5 |
6 months |
6-7. g The rear grab bar is inaccessible because it is obstructed by the tank top and the air freshener. |
SU4 |
6 months |
6-8 Drinking Fountain near Room 19 |
|
|
6-8. a Although a low drinking fountain is provided, there is no drinking fountain provided for people who have difficulty bending or stooping. |
DF3 |
6 months |
7. Franconia Governmental Center (excluding Police Department) 6121 Franconia Road Alexandria, VA 22310 |
|
|
7-1 Parking |
|
|
7-1. a The parking reserved for persons with disabilities is inaccessible because the parking spaces and access aisles slope up to 4.6%. |
P7 |
6 months |
7-2 Accessible Route |
|
|
7-2. a The route from the accessible parking to the main entrance is inaccessible because the cross slope of the route on the right side of the main entrance is 9% at the accessible parking, the cross slope of the route on the left side of the main entrance is 7.9% at the accessible parking, and the gutter slopes 19.6% on the right side of the main entrance. |
AR1 |
6 months |
7-3 Lee District Supervisor Room-Room 107 |
|
|
7-3. a The door is inaccessible because the pressure required to open the door is 14 pounds. |
D2 |
6 months |
7-3. b The door to the meeting room within the Lee District Supervisor’s Office is inaccessible because it has knob hardware. |
D1 |
6 months |
7-3. c The front counter protrudes 6.75 inches into the walkway and would not be detectable to a blind person using a cane. |
AR1 |
6 months |
7-4 Lobby |
|
|
7-4. a The brochure rack is mounted 50 inches above the finished floor over chairs, which are an obstruction. |
TR4 |
6 months |
7-5 Men’s Toilet Room with Stalls |
|
|
7-5. a The toilet room sign is inaccessible because it is mounted on the door. |
TR17 |
6 months |
7-5. b The door is inaccessible because the pressure required to open the door is 11 pounds. |
D2 |
6 months |
7-5. c Although an audible alarm is provided in this facility, there is no visual alarm appliance in the toilet room. |
TR21 |
6 months |
7-5. d The lavatory is inaccessible because it has twist-type faucets. |
TR10 |
6 months |
7-5. e No accessible coat hook has been provided. |
TR1 |
6 months |
7-6 Women’s Toilet Room with Stalls |
|
|
7-6. a The toilet room sign is inaccessible because it is mounted on the door. |
TR17 |
6 months |
7-6. b The door is inaccessible because the pressure required to open the door is 12 pounds. |
D2 |
6 months |
7-6. c Although an audible alarm is provided in this facility, there is no visual alarm appliance in the toilet room. |
TR21 |
6 months |
7-6. d The lavatory is inaccessible because it has twist-type faucets. |
TR10 |
6 months |
7-6. e No accessible coat hook has been provided. |
TR1 |
6 months |
7-7 Community Room |
|
|
7-7. a The doors to the community room (A, B, and C) are inaccessible because the pressure required to open door A is 11 pounds, the pressure required to open door B is 10 pounds, and the pressure required to open door C is 8 pounds. |
D2 |
6 months |
8. Franconia Governmental Center (Police Department) 6121 Franconia Road Alexandria, VA 22310 |
|
|
8-1 Police Area |
|
|
8-1. a All interior doors throughout the facility are inaccessible because the doors have knob hardware. |
D1 |
6 months |
8-1. b The signage provided throughout the facility is inaccessible. |
D26 |
6 months |
8-2 Police Area Hallway |
|
|
8-2. a Commander-Room 173 |
|
|
8-2. a (1) The door is inaccessible because the pressure required to open the door is greater than 5 pounds. |
D2 |
6 months |
8-2. b Conference Room-Room 172 |
|
|
8-2. b (1) The door is inaccessible because the pressure required to open the door is greater than 5 pounds. |
D2 |
6 months |
8-2. c Drinking Fountain next to the Single User Toilet Room in the Hallway |
|
|
8-2. c (1) The drinking fountain is inaccessible because the spout is 41.5 inches above the finished floor, and there is inadequate clear floor space and knee clearance. |
DF1 |
6 months |
8-2. d Women’s Single User Toilet Room in Office Hallway Behind Reception Area |
|
|
8-2. d (1) There is no signage directing people with disabilities to the accessible toilet room. |
TR16 |
6 months |
8-2. d (2) The single user toilet room contains a number of inaccessible elements and is not accessible to people with disabilities. |
SU13 |
6 months |
8-2. e Men’s Single User Toilet Room in Office Hallway Behind Reception Area |
|
|
8-2. e (1) There is no signage directing people with disabilities to the accessible toilet room. |
TR16 |
6 months |
8-2. e (2) The single user toilet room contains a number of inaccessible elements and is not accessible to people with disabilities. |
SU13 |
6 months |
8-2. f Squad Supervisor’s Office-Room 158 |
|
|
8-2. f (1) The door is inaccessible because the pressure required to open the door is 9 pounds. |
D2 |
6 months |
8-2. g The display case in the hallway protrudes into the walkway and would not be detectable to a blind person using a cane. |
AR8 |
6 months |
8-2. h The Processing/Secure Weapons Room-Room 154 |
|
|
8-2. h (1) The door is inaccessible because the pressure required to open the door is 9 pounds. |
D2 |
6 months |
8-2. i The Shelter-in-Place/Roll Call Room-Room 149 |
|
|
8-2. i (1) The door is inaccessible because the pressure required to open the door is 9 pounds. |
D2 |
6 months |
9. Hollin Hall Center 1500 Shenandoah Road Alexandria, VA 22308 |
|
|
(Surveyed for Polling purposes only) |
|
|
9-1 Accessible Route |
|
|
9-1. a The route from the parking to the entrance of the facility is inaccessible because the curb ramp at the front entrance has a right flare with a slope of 20.4% and a left flare with a slope of 15.3%. |
AR5 |
6 months |
9-2 Exterior Entrance |
|
|
9-2. a The exterior entrance to the facility is inaccessible because the area at the door’s automatic push button has a slope of 9.6%. |
TR2 |
6 months |
9-3 Exercise/Dance Room-Room112 (polling place) |
|
|
9-3. a The signage provided is inaccessible because it is located above the door. |
D26 |
6 months |
9-4 Ceramics Room-Room 109 (polling place) |
|
|
9-4. a The signage provided is inaccessible because it is located above the door. |
D26 |
6 months |
9-5 Toilet Rooms |
|
|
9-5. a The toilet rooms were not surveyed. |
ST14 |
6 months |
10. Pinecrest Golf Course 6600 Little River Turnpike Alexandria, VA 22312 |
|
|
10-1 Parking |
|
|
10-1. a Although the parking lot has a total of 101 parking spaces, an inadequate number are designated as reserved for people with disabilities. |
P3 |
6 months |
10-2 Accessible Route to Entrance |
|
|
10-2. a The route from the designated accessible parking spaces to the entrance of the facility is inaccessible because the route has a slope of up to 8.8% and a cross slope of up to 11.1%. |
AR1 |
6 months |
10-3 Pro Shop/Clubhouse |
|
|
10-3. a The counter for paying fees and café food is inaccessible because it is 42 inches above the finished floor. |
C5 |
6 months |
10-3. b The drinking fountain protrudes into the walkway and would not be detectable to a blind person using a cane. |
AR8 |
6 months |
10-4 Ramp to Indoor Practice Area |
|
|
10-4. a The ramp is inaccessible because the handrails are mounted 29.5 inches above the ramp surface, there are no extensions on the handrails, and the space between the wall and the handrail is 2 inches. |
R4 |
6 months |
10-5 Women’s Toilet Room with Stalls |
|
|
10-5. a The toilet room signage is inaccessible because it is mounted on the door and the centerline is 54.5 inches above the finished floor. |
TR17 |
6 months |
10-5. b The door is inaccessible because the pressure required to open the door is more than 5 pounds. |
D2 |
6 months |
10-5. c No accessible mirror has been provided. |
TR14 |
6 months |
10-5. d The paper towel dispenser is inaccessible because the controls are 61.5 inches above the finished floor. |
TR5 |
6 months |
10-5. e The lavatory is inaccessible because the hot water pipes are not insulated or otherwise configured to protect against contact. |
TR12 |
6 months |
10-5. f The toilet is inaccessible because the top of the seat is 20 inches above the finished floor, the centerline is 21 inches from the side wall, and the toilet flush control is located on the closed side. |
ST20, ST17, ST2 |
6 months |
10-5. g The air dryer and the paper towel dispenser protrude into the walkway and would not be detectable to a blind person using a cane. |
AR8 |
6 months |
10-5. h No accessible coat hook has been provided. |
TR1 |
6 months |
10-5. i The sanitary napkin dispenser is inaccessible because the controls require tight grasping and twisting of the wrist. |
TR3 |
6 months |
10-5. j The pull side of the door to the toilet room, which is accessed through a front approach, is inaccessible because it has no pull side clearance. |
D6 |
6 months |
10-6 Men’s Toilet Room with Stalls |
|
|
10-6. a The toilet room signage is inaccessible because it is mounted on the door and the sign centerline is 54.5 inches above the finished floor. |
TR17 |
6 months |
10-6. b The door is inaccessible because the pressure required to open the door is more than 5 pounds. |
D2 |
6 months |
10-6. c The lavatory is inaccessible because the hot water pipes are not insulated or otherwise configured to protect against contact. |
TR12 |
6 months |
10-6. d The toilet is inaccessible because the top of the seat is 20 inches above the finished floor and the flush control is located on the closed side. |
ST20, ST2 |
6 months |
10-6. e No accessible coat hook has been provided. |
TR1 |
6 months |
10-6. f The toilet paper dispenser is inaccessible because it is mounted 43 inches from the rear wall. |
ST19 |
6 months |
10-6. g The pull side of the door to the toilet room, which is accessed through a front approach, is inaccessible because it has no pull side clearance. |
D6 |
6 months |
10-7 Door from Pro Shop to Outdoor Patio Area |
|
|
10-7. a The door is inaccessible because there is a 1-inch change in level at the threshold to the door. |
D23 |
6 months |
10-8 Driving Cages |
|
|
10-8. a The route to the driving cages from the front entry door is inaccessible because it is less than 36 inches wide. |
AR3 |
6 months |
10-9 Putting Area |
|
|
10-9. a The route from the front entry door to the putting area is inaccessible because the route is not stable, firm and level. |
AR1 |
6 months |
11. Fred Packer Center 4030 Hummer Road Annandale, VA 22003 |
|
|
(Surveyed for Polling purposes only) |
|
|
11-1 Parking |
|
|
11-1. a The parking lot is inaccessible because the pavement markings are faded and the designated accessible spaces and access aisles slope 3.6% to 6%. |
P3 |
6 months |
11-1. b The route from the parking to the entrance is inaccessible because the running slope of the right curb ramp is 9.6%. |
AR5 |
6 months |
11-2 Accessible Route |
|
|
11-2. a The route from the parking to the entrance is inaccessible because the route has a cross slope up to 4.8% near the left curb ramp and a running slope up to 6.5% near the building, but has not been constructed as a fully accessible ramp. |
AR1 |
6 months |
11-3 Exterior Entrance |
|
|
11-3. a The exterior front entrance is inaccessible because it has an opening width of 26 inches. |
D25 |
6 months |
11-3. b The interior entrance door is inaccessible because the pressure required to open the door is 18 pounds. |
D2 |
6 months |
12. Audrey Moore Recreation Center 8100 Braddock Road Annandale, VA 22003 |
|
|
12-1 Parking |
|
|
12-1. a Although the parking lot has a total of 332 parking spaces, the parking is inaccessible because the pavement markings associated with the van spaces are not clear, not all of the designated van accessible spaces have vertical signage with the International Symbol of Accessibility, the designated van parking spaces have slopes and cross slopes that range from 3.4% to 4.5%, the slope and cross slope of the access aisles associated with some of the van spaces ranges from 3.1% to 4.8%, and none of the additional 10 designated standard accessible parking spaces has access aisles. |
P3 |
6 months |
12-2 Route to Entrance from Parking |
|
|
12-2. a The route from the designated accessible parking spaces to the entrance of the facility is inaccessible because the route has a cross slope of up to 9.4%. |
AR1 |
6 months |
12-2. b The route from the designated accessible parking to the entrance of the facility is inaccessible because the curb ramp slopes 9.4% and one of the flared sides of the curb ramp slopes 11.7%. |
AR5 |
6 months |
12-3 Exterior Entrance |
|
|
12-3. a The exterior entrance is inaccessible because it has an opening width of 31 inches. |
D25 |
6 months |
12-4 Lobby of First Floor |
|
|
12-4. a Club Room #1 |
|
|
12-4. a (1) The signage provided is inaccessible because it is mounted on the door and does not have raised letters and Braille. |
D26 |
6 months |
12-4. b Women’s Toilet Room with Stalls (1st Floor) |
|
|
12-4. b (1) The toilet room signage is inaccessible because it is mounted with the centerline 61 inches above the finished floor. |
TR17 |
6 months |
12-4. b (2) The door is inaccessible because the pressure required to open the door is 15 pounds. |
D2 |
6 months |
12-4. b (3) The pull side of the door, which is accessed from the latch side of the door, is inaccessible because it has a path of travel only 46 inches wide for a side approach |
D10 |
6 months |
12-4. b (4) No accessible mirror has been provided. |
TR14 |
6 months |
12-4. b (5) The lavatory is inaccessible because the hot water pipes are not insulated or otherwise configured to protect against contact, and the counter top height is 35 inches above the finished floor. |
TR9 |
6 months |
12-4. b (6) No accessible coat hook has been provided in the alternate stall. |
TR1 |
6 months |
12-4. b (7) There is no accessible stall provided. |
ST15 |
6 months |
12-4. c Men’s Toilet Room with Stalls (1st Floor) |
|
|
12-4. c (1) The toilet room signage is inaccessible because it is mounted with the centerline 62 inches above the finished floor. |
TR17 |
6 months |
12-4. c (2) The door is inaccessible because the pressure required to open the door is 15 pounds. |
D2 |
6 months |
12-4. c (3) The pull side of the door, which is accessed from the latch side of the door, is inaccessible because it has a path of travel only 46 inches wide for a side approach. |
D10 |
6 months |
12-4. c (4) The lavatory is inaccessible because the hot water pipes are not insulated or otherwise configured to protect against contact, and the counter top height is 35 inches above the finished floor. |
TR9 |
6 months |
12-4. c (5) No accessible coat hook has been provided in the alternate stall. |
TR1 |
6 months |
12-4. c (6) There is no accessible stall provided. |
ST15 |
6 months |
12-4. d Senior Center |
|
|
12-4. d (1) The door is inaccessible because the pressure required to open the door is 15 pounds. |
D2 |
6 months |
12-4. d (2) The coat rack outside the entry door protrudes into the walkway and would not be detectable to a blind person using a cane. |
AR8 |
6 months |
12-5 Elevator |
|
|
12-5. a The elevator contains a number of inaccessible elements and is not accessible to people with disabilities. |
E7 |
84 months |
12-6 Second Floor Women’s Locker Room |
|
|
12-6. a The signage provided is inaccessible because it is not mounted on the latch side of the door with its centerline at 60 inches above the finished floor. |
D26 |
6 months |
12-6. b The door is inaccessible because the pressure required to open the door is 17 pounds. |
D2 |
6 months |
12-6. c The grab bars in the shower are inaccessible because they are mounted at 36.5 inches above the finished floor. |
B9 |
6 months |
12-6. d The shower is inaccessible because the shower entrance slopes 19.2% and the depth of the shower narrows to 25 inches. |
B8 |
6 months |
12-6. e There is no accessible locker provided. |
LR3 |
6 months |
12-7 Second Floor Men’s Locker Room |
|
|
12-7. a (1) This locker room was not surveyed due to heavy usage during this site visit. Provide a locker room that fully complies with the Standards and ensure accessibility, particularly referring to the items noted in the Women’s Locker Room. |
LR4 |
6 months |
12-8 Second Floor “Family Accessible Changing” Room |
|
|
12-8. a The shower in the family changing room is inaccessible because there is no handheld shower head and the shower controls are in the center of the control wall instead of near the outside entrance to the shower. |
B8, B11 |
6 months |
12-9 Lower Floor (bottom of building) |
|
|
12-9. a There is no vertical access for people in wheelchairs to the bottom floor of the building where the racquet ball courts are located. |
AR9 |
84 months |
12-9. b The stairs are inaccessible because the handrails are mounted at 30 inches high above the stair nosings, the handrail clearance from the side wall exceeds 1.5 inches, there is no sloped handrail extension beyond the first nosing, and no 12-inch horizontal extension at the bottom landing. |
AR10 |
84 months |
12-9. c There is no accessible locker provided in the corridor. |
LR3 |
84 months |
13. Wakefield Park 8100 Braddock Road Annandale, VA 22003 |
|
|
13-1 Parking Lot 1 (39 spaces) |
|
|
13-1. a The parking reserved for people with disabilities is inaccessible because the cross slope of the van accessible space is too steep. |
P7 |
6 months |
13-2 Parking Lot 2 (188 spaces) |
|
|
13-2. a Although the parking lot has a total of 188 spaces, an inadequate number are designated as reserved for people with disabilities. |
P3 |
6 months |
13-2. b The parking reserved for people with disabilities is inaccessible because the slopes and cross slopes of several of the parking spaces and access aisles are greater than 2%. |
P7 |
6 months |
13-3 Accessible Route |
|
|
13-3. a The route from the larger parking lot to the bathhouse and ballfields is inaccessible because two of the three curb ramps have slopes exceeding 8.33%, and all three curb ramps have flared sides with slopes exceeding 10%. |
AR5 |
6 months |
13-4 Bathhouse Men’s and Women’s Toilet Rooms with Stalls |
|
|
13-4. a The toilet room signage for both toilet rooms is inaccessible because the signs are mounted on the doors. |
TR17 |
6 months |
13-4. b There is no accessible stall provided in the men’s and women’s toilet rooms. |
ST15 |
6 months |
13-4. c The light switch in each toilet room is mounted too high above the finished floor. |
TR5 |
6 months |
13-4. d In each toilet room, the hand dryer protrudes into the walkway and would not be detectable to a blind person using a cane. |
AR8 |
6 months |
13-4. e In each toilet room, no accessible mirror has been provided. |
TR14 |
6 months |
13-4. f In each toilet room, the lavatory is inaccessible because the hot water pipes are not insulated or otherwise configured to protect against contact and the bottom edge of the apron is less than 29 inches above the finished floor. |
TR9 |
6 months |
13-4. g In each toilet room, the liquid soap dispenser is mounted with the controls 50 inches above the finished floor and requires a forward approach. |
TR5 |
6 months |
13-4. h In the men’s toilet room, the urinal is inaccessible because the rim is higher than 17 inches above the finished floor. |
TR20 |
6 months |
13-4. i In each toilet room, the bench is inaccessible because it is less than 24 inches wide and is not fixed. |
LR1 |
6 months |
13-5 Public Pay Telephones outside Bathhouse |
|
|
13-5. a The two telephones outside the bathhouse are inaccessible because the highest operable part of each telephone is mounted 55 inches above the finished floor and there is no signage provided. |
TT1 |
6 months |
13-6 Drinking Fountain next to Men’s Toilet Room in the Bathhouse |
|
|
13-6. a The drinking fountain is inaccessible because it requires 6 pounds of force to operate, the knee depth space is 10 inches and it does not allow a front approach, the drinking fountain protrudes into the walkway and would not be detectable to a blind person using a cane, and there is no drinking fountain provided for people who have difficulty bending or stooping. |
DF1, DF5 |
6 months |
13-7 Accessible Route from the Parking Lot to Ballfields #1, 2 and 4 |
|
|
13-7. a The route from the parking lot is inaccessible because the route to Ballfield #2 has a 1 inch lip and a 3-inch gap along the way, a tree protrudes into the route, in one area the route slopes up to 7.4% with a cross slope of 5.4%, in an area closer to this field, the route slopes up to 10.5% with a cross slope of 6.2%, and there is a lip 1.25 inches at the end of the route to field #2. The path to Ballfield #3 slopes 8.7%, and there is no accessible route to the other fields. |
AR1 |
6 months |
13-8 Accessible Route from the Parking Lot to the Playground |
|
|
13-8. a The route from the parking lot to the playground is inaccessible because the route is not stable, firm and slip resistant after the entry gate, and there is no access to the benches. |
AR1 |
6 months |
13-9 Ballfields 7 and 8 |
|
|
13-9. a Drinking Fountain |
|
|
13-9. b Although a drinking fountain is provided, it is not operable and there is no drinking fountain provided for people who have difficulty bending or stooping. |
DF3, M1 |
6 months |
13-10 Picnic Tables |
|
|
13-10. a (1) The picnic tables are inaccessible because none provides the required knee space. |
PD6 |
6 months |
13-11 Parking Lot Near Tennis Courts |
|
|
13-11. a No accessible parking is provided. |
P3 |
6 months |
13-11. b There is no curb ramp from the pedestrian parking to the route leading to the tennis courts. |
AR5 |
6 months |
13-12 Parking for and Accessible Route to Basketball Courts and Soccer Field |
|
|
13-12. a The route from the parking lot to the basketball courts and soccer field is inaccessible because there is no accessible parking spaces or curb ramp, and the route to the soccer field slopes up to 8.8%. |
AR1 |
6 months |
13-13 Parking Near Skate Park |
|
|
13-13. a No accessible parking is provided. |
P3 |
6 months |
13-13. b The route is inaccessible because the curb ramp has an edge with a 1.5 inch lip and has a 6.7% cross slope. |
AR5 |
6 months |
13-14 Drinking Fountain in the Skate Park |
|
|
13-14. a The drinking fountain is inaccessible because the knee space is 26 inches high to the bottom of the apron, and it is not operable. |
DF5, M1 |
6 months |
14. Chapel Government Center 4414 Holburn Avenue Annandale, VA 22003 |
|
|
14-1 Parking |
|
|
14-1. a Although the parking lot has a total of 104 parking spaces, an inadequate number are designated as reserved for people with disabilities. |
P3 |
6 months |
14-1. b The van parking reserved for persons with disabilities lacks appropriate signage. |
P6 |
6 months |
14-1. c The parking reserved for persons with disabilities on the street near the front entrance is not located on the shortest accessible route to the accessible facility entrance. |
P5 |
6 months |
14-2 Accessible Route to Main Entrance |
|
|
14-2. a The route from the parking to the main entrance of the facility is inaccessible because the curb ramp near the building main entrance has a running slope of 9.2%. |
AR5 |
6 months |
14-3 Main Corridor |
|
|
14-3. a Many signs throughout the facility are inaccessible because they do not have Braille or raised characters. |
D26 |
6 months |
14-3. b The defibrillator and the fire extinguisher protrude into the walkway and would not be detectable to a blind person using a cane. |
AR8 |
6 months |
14-4 Loading Dock Corridor |
|
|
14-4. a Men’s Toilet Room with Stalls |
|
|
14-4. a (1) The toilet room signage is inaccessible because it is mounted on the door. |
TR17 |
6 months |
14-4. a (2) The door is inaccessible because the pressure required to open the door is 15 pounds. |
D2 |
6 months |
14-4. a (3) The light switch is mounted 55 inches above the finished floor. |
TR5 |
6 months |
14-4. a (4) The route into the toilet room is inaccessible because of the privacy wall. |
TR15 |
6 months |
14-4. a (5) The paper towel dispenser is mounted with the controls 58 inches above the finished floor. |
TR5 |
6 months |
14-4. a (6) The lavatory is inaccessible because the hot water pipes are not insulated or otherwise configured to protect against contact, and the clear floor space is not centered on the lavatory. |
TR9 |
6 months |
14-4. a (7) The urinal is inaccessible because the rim is mounted 19.5 inches above the finished floor. |
TR20 |
6 months |
14-4. a (8) No accessible coat hook has been provided. |
TR1 |
6 months |
14-4. a (9) The rear grab bar is inaccessible because it is 25 inches in length and obstructed by the toilet pipes. |
ST3 |
6 months |
14-4. b Women’s Toilet Room with Stalls |
|
|
14-4. b (1) The toilet room signage is inaccessible because it is mounted on the door. |
TR17 |
6 months |
14-4. b (2) The door is inaccessible because the pressure required to open the door is 14 pounds. |
D2 |
6 months |
14-4. b (3) The light switch is mounted 55 inches above the finished floor. |
TR5 |
6 months |
14-4. b (4) The route to the toilet room is inaccessible because of the privacy wall. |
TR15 |
6 months |
14-4. b (5) The paper towel dispenser is mounted with the controls 58 inches above the finished floor. |
TR5 |
6 months |
14-4. b (6) The sanitary napkin dispenser is inaccessible because it is mounted with the controls 60 inches above the finished floor and requires tight grasping and twisting of the wrist to operate. |
TR2 |
6 months |
14-4. b (7) The lavatory is inaccessible because the hot water pipes are not insulated or otherwise configured to protect against contact, and the clear floor space is not centered on the lavatory. |
TR9 |
6 months |
14-4. b (8) No accessible coat hook has been provided. |
TR1 |
6 months |
14-4. b (9) The rear grab bar is obstructed by the toilet pipes. |
ST5 |
6 months |
14-5 Men’s and Women’s Single User Toilet Rooms |
|
|
14-5. a The single user toilet rooms contain a number of inaccessible elements, including an entry door to each room that is 24 inches wide, which makes them not accessible to people with disabilities. |
SU13 |
6 months |
15. Woodburn Mental Health Center 3340 Woodburn Road Annandale, VA 22003 |
|
|
15-1 Parking Near Trailer |
|
|
15-1. a The parking reserved for persons with disabilities in the trailer parking area is inaccessible because the slope of the accessible space is 6.3%, the slope of the access aisle is 4.3%, and the cross slope of the access aisle is 3.1%. |
P7 |
60 months |
15-2 Parking Near Main Entrance |
|
|
15-2. a The parking reserved for persons with disabilities is inaccessible because the wheel stops protrude into one of the parking spaces. |
M1 |
6 months |
15-3 Emergency Room Parking |
|
|
15-3. a The parking reserved for persons with disabilities in the emergency room parking area is inaccessible because the parking spaces and access aisle have slopes greater than 2%. |
P7 |
60 months |
15-4 Men’s Toilet Room with Stalls near Emergency Services |
|
|
15-4. a The door is inaccessible because the pressure required to open the door is 15 pounds. |
D2 |
6 months |
15-4. b No accessible mirror has been provided. |
TR14 |
6 months |
15-4. c The lavatory is inaccessible because the bottom edge of the apron is 28 inches above the finished floor. |
TR11 |
60 months |
15-4. d The urinal is inaccessible because it does not have an elongated rim and there is inadequate clear floor space at the urinal. |
TR20 |
60 months |
15-4. e The toilet is inaccessible because its centerline is 20.5 inches from the side wall. |
ST17 |
60 months |
15-4. f No accessible coat hook has been provided. |
TR1 |
6 months |
15-5 Women’s Toilet Room with Stalls near Emergency Services |
|
|
15-5. a The door is inaccessible because the pressure required to open the door is 18 pounds. |
D2 |
6 months |
15-5. b No accessible mirror has been provided. |
TR14 |
6 months |
15-5. c The lavatory is inaccessible because the bottom edge of the apron is 28 inches above the finished floor. |
TR11 |
60 months |
15-5. d No accessible coat hook has been provided. |
TR1 |
6 months |
15-6 Offices |
|
|
15-6. a The offices are inaccessible because they have knob hardware. |
D1 |
60 months |
15-7 Drinking Fountain in the Main Lobby near the Unisex Toilet Room |
|
|
15-7. a The drinking fountain in the main lobby is inaccessible because it requires 7 pounds of force to operate. |
DF2 |
60 months |
15-8 Elevator Located Near Out-Patient Services |
|
|
15-8. a The elevator is inaccessible because the hall call buttons, the hall lanterns, the hoistway signage, the car floor plan, the car controls, and the car position indicators are not accessible to people with disabilities. |
E7 |
60 months |
15-9 Accessible Route to Basement |
|
|
15-9. a Ramp |
|
|
15-9. a (1) The ramp is inaccessible because the slope of the ramp ranges from 9.3% to 10%, and the mid-way landing is 60 inches by 59 inches, and is blocked by a trash receptacle. |
R3 |
60 months |
15-10 Basement (Medications Clinic Floor) |
|
|
15-10. a Drinking Fountain |
|
|
15-10. a (1) The drinking fountain is inaccessible because it has a spout 42 inches above the finished floor and only 19.5 inches of clear knee space. |
DF6, DF5 |
60 months |
15-10. b Men’s and Women’s Toilet Rooms with Stalls |
|
|
15-10. b (1) There is no signage directing people with disabilities to the accessible toilet rooms. |
TR16 |
6 months |
15-10. c Single-User Toilet Room |
|
|
15-10. c (1) The toilet room signage is inaccessible because it is mounted above and on the door and does not have raised characters and Braille. |
TR17 |
6 months |
15-10. c (2) The door is inaccessible because it has an opening width of only 29.5 inches, the pressure required to open the door is 23 pounds, it does not have sufficient maneuvering clearance, it has knob hardware, and its threshold is not beveled. |
D18 |
60 months |
15-10. c (3) No accessible mirror has been provided. |
TR14 |
6 months |
15-10. c (4) The toilet seat cover dispenser is mounted 63 inches above the finished floor over the toilet. |
TR4 |
6 months |
15-10. c (5) The paper towel dispenser is mounted 53 inches above the finished floor over the toilet. |
TR4 |
6 months |
15-10. c (6) The lavatory is inaccessible because the bottom edge of the apron is 28 inches above the finished floor, the hot water and drain pipes are not insulated or otherwise configured to protect against contact, the clear floor space is not centered on the lavatory, and the toilet room door swings into the lavatory’s required clear floor space. |
TR9, TR6 |
60 months |
15-10. c (7) The toilet is inaccessible because the toilet centerline is more than 18 inches from the side wall, the toilet flush control is on the closed side, and no compliant grab bars are provided. |
SU14, SU10 |
60 months |
15-11 Basement Medical Clinic Group-Room 1C |
|
|
15-11. a Ramp |
|
|
15-11. a (1) The ramp is inaccessible because it has a slope of 11% and no handrails. |
R5 |
60 months |
15-11. a (2) The door near the end of the ramp is inaccessible because it has knob hardware. |
D1 |
60 months |
15-12 Upper Level (Level 2) |
|
|
15-12. a Men’s and Women’s Toilet Room with Stalls |
|
|
15-12. a (1) The toilet room signage for each toilet room is inaccessible because the sign is mounted on the door. |
TR17 |
6 months |
15-12. a (2) There is no signage directing people with disabilities to the accessible toilet rooms. |
TR16 |
6 months |
15-12. b Clinicians’ Offices |
|
|
15-12. b (1) The signage provided is inaccessible because the room number is not mounted on the latch side of the door with Braille and raised characters. |
D26 |
6 months |
15-13 Lobby Level |
|
|
15-13. a Hallway Doors |
|
|
15-13. a (1) The double leaf door is inaccessible because it has an opening width of 28.5 inches per leaf. |
D25 |
60 months |
15-13. b Single User Toilet Room in Main Lobby |
|
|
15-13. b (1) The toilet room is inaccessible because the sign is mounted on the door. |
TR17 |
6 months |
15-13. b (2) The door is inaccessible because the pressure required to open the door is 15 pounds. |
D2 |
6 months |
15-13. b (3) No accessible coat hook has been provided. |
TR1 |
6 months |
15-13. b (4) The lavatory hot water and drain pipes are not insulated or otherwise configured to protect against contact. |
TR12 |
6 months |
15-13. b (5) The rear grab bar is inaccessible because it is 31 inches long. |
SU2 |
60 months |
15-14 Accessible Route from Parking to Trailer |
|
|
15-14. a Ramp |
|
|
15-14. a (1) The ramp is inaccessible because it slopes up to 10.1%. |
R3 |
60 months |
15-14. b Single User Toilet Room in Trailer |
|
|
15-14. b (1) The toilet seat cover dispenser is inaccessible because it is mounted 56 inches above the finished floor above the toilet. |
TR4 |
6 months |
15-14. b (2) The toilet paper dispenser is inaccessible because it is mounted 40 inches from the rear wall. |
SU17 |
6 months |
15-14. b (3) The side grab bar is inaccessible because it is 40 inches in length and mounted with the closer end 14 inches from the rear wall. |
SU6 |
60 months |
15-14. b (4) The rear grab bar is inaccessible because it is 33 inches in length. |
SU3 |
60 months |
16. Pohick Regional Library 6450 Sydenstricker Road Burke, VA 22015 |
|
|
16-1 Parking |
|
|
16-1. a The parking reserved for persons with disabilities is inaccessible because the slopes and cross slopes of some of the parking spaces and access aisles exceed 2%, and the pavement markings are not clear. |
P7 |
6 months |
16-2 Public Pay Telephone near Entrance Vestibule |
|
|
16-2. a The telephone in the library is inaccessible because a magazine rack is within the clear floor space of the telephone. |
TT1 |
6 months |
16-3 Library Area |
|
|
16-3. a The book stacks are inaccessible because the space between stacks is only 35 inches in width. |
LB5 |
6 months |
16-4 Quiet Study Room |
|
|
16-4. a The door is inaccessible because the pressure required to open the door is 10 pounds. |
D2 |
6 months |
16-5 Women’s Toilet Room with Stalls |
|
|
16-5. a The toilet room signage is inaccessible because is not mounted at a height and in a location that people who are blind or have low vision can use. |
TR17 |
6 months |
16-5. b No accessible coat hook has been provided. |
TR1 |
6 months |
16-5. c The toilet is inaccessible because the flush control is on the closed side. |
ST2 |
6 months |
16-5. d The rear grab bar is inaccessible because it is obstructed by the flush control. |
ST5 |
6 months |
16-5. e No accessible mirror has been provided. |
TR14 |
6 months |
16-5. f The lavatory is inaccessible because the bottom edge of the apron is less than 29 inches above the finished floor. |
TR11 |
6 months |
16-6 Men’s Toilet Room with Stalls |
|
|
16-6. a The toilet room signage is inaccessible because it is not mounted at a height and in a location that people who are blind or have low vision can use. |
TR17 |
6 months |
16-6. b The toilet paper dispenser is inaccessible because it is mounted 42 inches from the rear wall. |
ST19 |
6 months |
16-6. c No accessible coat hook has been provided. |
TR1 |
6 months |
16-6. d The rear grab bar is inaccessible because it is obstructed by the flush control. |
ST5 |
6 months |
17. Centreville Library 14200 St. Germaine Drive Centreville, VA 20121 |
|
|
17-1 Parking |
|
|
17-1. a The parking reserved for persons with disabilities is inaccessible because several of the designated spaces have cross slopes of 3.2% to 4.5%. |
P7 |
6 months |
17-2 Accessible Route to Main Entrance |
|
|
17-2. a The route from the parking lot to the sidewalk is inaccessible because the curb ramp has a slope of 12.7%. |
AR5 |
6 months |
17-2. b The route from the parking lot to the main entrance is inaccessible because the sidewalk has a slope of up to 5.8%. |
AR1 |
6 months |
17-3 Lobby |
|
|
17-3. a The computer table with the sign that reads “reserve internet here” is inaccessible because it has inadequate knee/toe space under the table due to the trash receptacle. |
C3 |
6 months |
17-4 Meeting Rooms #1 and #2 |
|
|
17-4. a The push side of the door to Meeting Room 1, which is accessed from the latch side of the door, is inaccessible because it has only 11 inches of space on the latch side of the door. |
D11 |
6 months |
17-4. b Within both meeting rooms, no accessible coat hook or rack has been provided. |
TR1 |
6 months |
17-4. c The brochures on the wall by Meeting Room #2 are inaccessible because they are obstructed by cardboard boxes on the floor. |
TR4 |
6 months |
17-5 Public Pay Telephone near Toilet Rooms |
|
|
17-5. a The telephone near the toilet rooms is inaccessible because the highest operable part is mounted at 55.5 inches above the finished floor and the signage identifying the location of the telephone is in the wrong location. |
TT1 |
6 months |
17-6 Hallway near Telephone and Women’s Toilet Room |
|
|
17-6. a The defibrillator near the telephone and women’s toilet room protrudes into the walkway and would not be detectable to a blind person using a cane. |
AR8 |
6 months |
17-7 Drinking Fountain near Toilet Rooms |
|
|
17-7. a The drinking fountain protrudes into the walkway and would not be detectable to a blind person using a cane. |
AR8 |
6 months |
17-7. b The drinking fountain is inaccessible because the water flow height is 2.5 inches and there is no drinking fountain provided for people who have difficulty bending or stooping. |
DF1 |
6 months |
17-8 Men’s Toilet Room with Stalls |
|
|
17-8. a The toilet room signage is inaccessible because it is mounted 62 inches above the finished floor and does not have Braille. |
TR17 |
6 months |
17-8. b The toilet is inaccessible because the flush control is on the closed side. |
ST2 |
6 months |
17-8. c No accessible coat hook has been provided. |
TR1 |
6 months |
17-8. d The toilet paper dispenser is inaccessible because it is mounted 39 inches from the rear wall. |
ST19 |
6 months |
17-8. e The baby changing station protrudes into the walkway and would not be detectable to a blind person using a cane. |
AR8 |
6 months |
17-9 Women’s Toilet Room with Stalls |
|
|
17-9. a The toilet room signage is inaccessible because it is mounted 62 inches above the finished floor. |
TR17 |
6 months |
17-9. b No accessible coat hook has been provided. |
TR1 |
6 months |
17-9. c The toilet paper dispenser is inaccessible because it is mounted 39 inches from the rear wall. |
ST19 |
6 months |
17-9. d The baby changing station protrudes into the walkway and would not be detectable to a blind person using a cane. |
AR8 |
6 months |
17-9. e The sanitary napkin dispenser is inaccessible because it requires tight grasping and twisting of the wrist to operate. |
TR3 |
6 months |
17-9. f The toilet room is inaccessible because the door swings into the required clear floor space at the lavatory and sanitary napkin dispenser. |
TR6 |
6 months |
18. Joseph Willard Health Center 3750 Old Lee Highway Fairfax, VA 22030 |
|
|
18-1 Parking |
|
|
18-1. a The parking reserved for persons with disabilities is inaccessible because the cross slope of the van access aisle in front of the entry door is 4.1%. |
P7 |
6 months |
18-2 Accessible Route |
|
|
18-2. a The ramp leading to the front entry is inaccessible because it has handrails on only one side, and has a slope of 8.5% and a cross slope of 3.3%. |
R5 |
6 months |
18-2. b The building does not have directional signage posted at inaccessible entrances and does not have the International Symbol of Accessibility posted at accessible entrances. |
D16 |
6 months |
18-3 Front Entrance Vestibule |
|
|
18-3. a The Lab Corp. box in the vestibule protrudes into the walkway and would not be detectable to a blind person using a cane. |
AR8 |
6 months |
18-4 Single Segment Ramp in the Reception Area |
|
|
18-4. a The ramp is inaccessible because the cross slope exceeds 2%, it has inadequate edge protection, the handrails are not graspable, and there are no handrail extensions. |
R5 |
6 months |
18-5 Public Pay Telephone near Ramp |
|
|
18-5. a The telephone near the ramp in the reception area protrudes into the walkway and would not be detectable to a blind person using a cane. |
AR8 |
6 months |
18-6 Corridor A |
|
|
18-6. a The doors throughout Corridor A are inaccessible because they have knob hardware. |
D1 |
6 months |
18-6. b The signage provided in Corridor A is inaccessible because it is not located on the latch side of the door with raised characters and Braille. |
D26 |
6 months |
18-6. c Although the facility contains an emergency alarm system, the alarm system is inaccessible because visual alarms are not provided in the exam rooms. |
AL1 |
6 months |
18-6. d The pull side of the doors to the exam rooms, which are accessed through a front approach, are inaccessible because they do not have adequate maneuvering space from inside the exam rooms. |
D6 |
6 months |
18-7 Drinking Fountain on Route to Corridor B |
|
|
18-7. a The drinking fountain is inaccessible because the control requires more than 5 pounds of force to operate. |
DF2 |
6 months |
18-7. b The wall-mounted drinking fountain is inaccessible because it has inadequate knee space height, inadequate knee space depth, and does not allow a front approach. |
DF5 |
6 months |
18-8 Corridor B |
|
|
18-8. a The doors throughout Corridor B are inaccessible because they have knob hardware. |
D1 |
6 months |
18-8. b The signage provided in Corridor B is inaccessible because it is not located on the latch side of the door with raised characters and Braille. |
D26 |
6 months |
18-8. c The pull side of the doors to the exam rooms, which are accessed through a front approach, are inaccessible because they do not have adequate maneuvering space from inside the exam rooms. |
D6 |
6 months |
18-9 Women’s Single-User Toilet Room |
|
|
18-9. a The toilet room signage is inaccessible because it mounted on the door, the centerline of the sign is 64 inches above the finished floor, and the sign lacks raised characters and Braille. |
TR17 |
6 months |
18-9. b The door is inaccessible because the pressure required to open the door is greater than 5 pounds. |
D2 |
6 months |
18-9. c No accessible mirror has been provided. |
TR14 |
6 months |
18-9. d The seat cover dispenser is inaccessible because it is mounted with the controls 54.5 inches above the finished floor. |
TR5 |
6 months |
18-9. e The soap dispenser is inaccessible because it is mounted 49 inches above the finished floor over an obstruction with a depth of 26.75 inches. |
TR4 |
6 months |
18-9. f The air dryer protrudes into the walkway and would not be detectable to a blind person using a cane. |
AR8 |
6 months |
18-9. g The toilet paper dispenser is inaccessible because it is mounted 40.75 inches from the rear wall. |
SU17 |
6 months |
18-9. h The side grab bar is inaccessible because it is mounted with the far end 46.5 inches from the rear wall. |
SU6 |
6 months |
18-9. i The rear grab bar is inaccessible because it is 30 inches in length, and mounted so that objects interfere with its use. |
SU2 |
6 months |
18-9. j The lavatory hot water and drain pipes are not insulated or otherwise configured to protect against contact. |
TR12 |
6 months |
18-10 Men’s Single-User Toilet Room |
|
|
18-10. a The toilet room signage is inaccessible because it mounted on the door, the centerline of the sign is 64 inches above the finished floor, and the sign lacks raised characters and Braille. |
TR17 |
6 months |
18-10. b The door is inaccessible because the pressure required to open the door is greater than 5 pounds. |
D2 |
6 months |
18-10. c No accessible mirror has been provided. |
TR14 |
6 months |
18-10. d The seat cover dispenser is inaccessible because it is mounted with the controls 55 inches above the finished floor. |
TR5 |
6 months |
18-10. e The soap dispenser is inaccessible because it is mounted 51.5 inches above the finished floor over an obstruction with a depth of 26.5 inches. |
TR4 |
6 months |
18-10. f The air dryer protrudes into the walkway and would not be detectable to a blind person using a cane. |
AR8 |
6 months |
18-10. g The toilet paper dispenser is inaccessible because it is mounted 42 inches from the rear wall. |
SU17 |
6 months |
18-10. h The side grab bar is inaccessible because it is mounted with the far end 47 inches from the rear wall. |
SU6 |
6 months |
18-10. i The rear grab bar is inaccessible because it is 24 inches in length, and mounted so that objects interfere with its use. |
SU2 |
6 months |
18-10. j The lavatory hot water and drain pipes are not insulated or otherwise configured to protect against contact. |
TR12 |
6 months |
18-11 Third Corridor with Dental Clinics to the Left of the Reception Area |
|
|
18-11. a The doors in the corridor are inaccessible because they have knob hardware. |
D1 |
6 months |
18-11. b The signage provided in the corridor is inaccessible because the signs are mounted on each door and do not have raised characters and Braille. |
D26 |
6 months |
18-11. c Although the facility contains an emergency alarm system, the alarm system is inaccessible because the alarm system is inaccessible because visual alarms are not provided in the exam rooms. |
AL1 |
6 months |
18-11. d The pull side of the doors to the exam rooms, which are accessed through a front approach, are inaccessible because they do not have adequate maneuvering space from inside the exam rooms. |
D6 |
6 months |
18-12 Single-User Toilet Room |
|
|
18-12. a The toilet room sign is inaccessible because it is mounted on the door, the centerline of the sign is not 60 inches above the finished floor, and it lacks raised characters and Braille. |
TR17 |
6 months |
18-12. b The door is inaccessible because the pressure required to open the door is greater than 5 pounds. |
D2 |
6 months |
18-12. c The door is inaccessible because it has knob hardware. |
D1 |
6 months |
18-12. d The pull side of the door, which is accessed through a front approach, is inaccessible because it does not have adequate maneuvering clearance on the pull side of the door because of a trash can. |
D6 |
6 months |
18-12. e The push side of the door, which is accessed through a front approach and which has both a closer and a latch, is inaccessible because it does not have adequate maneuvering clearance on the latch side of the door. |
D7 |
6 months |
18-12. f The toilet is inaccessible because it has insufficient clear floor space. |
SU16 |
6 months |
18-12. g No accessible mirror has been provided. |
TR14 |
6 months |
18-12. h The towel dispenser is inaccessible because it is mounted 46.5 inches above the finished floor over an obstruction of 14.5 inches. |
TR4 |
6 months |
18-12. i The side grab bar is inaccessible because it is obstructed by the trash can. |
SU8 |
6 months |
18-12. j The rear grab bar is inaccessible because it is 30 inches in length. |
SU2 |
6 months |
18-13 Hallway to Speech and Hearing/Daytime Development |
|
|
18-13. a The overhead pipe and the fire extinguisher protrude into the walkway and would not be detectable to a blind person using a cane. |
AR8 |
6 months |
18-13. b Drinking Fountain |
|
|
18-13. b (1) The drinking fountain protrudes into the walkway and would not be detectable to a blind person using a cane. |
AR8 |
6 months |
18-13. b (2) The drinking fountain is inaccessible because the controls require more than 5 pounds of force to operate, and there is no drinking fountain provided for people who have difficulty bending or stooping. |
DF1 |
6 months |
18-14 Men’s and Women’s Toilet Rooms with Stalls Serving the Speech and Hearing Clinic |
|
|
18-14. a There is no signage directing people with disabilities to the accessible toilet rooms. |
TR16 |
6 months |
18-14. b The toilet rooms contain a number of inaccessible elements and are not accessible to people with disabilities. |
ST14 |
6 months |
18-15 Drinking Fountains past the Speech and Hearing/Daytime Development Hallway |
|
|
18-15. a The drinking fountain is inaccessible because the controls require more than 5 pounds of force to operate and there is no drinking fountain provided for people who have difficulty bending or stooping. |
DF1 |
6 months |
18-16 Elevator |
|
|
18-16. a The elevator is inaccessible because the call buttons are centered at 48 inches above the finished floor and the visual signals on the call buttons do not indicate a call registered or answered. |
E3 |
60 months |
18-16. b The elevator is inaccessible because there is no audible and visual hall arrival signal, the hall lantern fixtures are broken, and the hall lantern signals are not visible from the area of the hall call buttons. |
E11 |
60 months |
18-16. c The elevator is inaccessible because hoistway signage is not provided on both jambs. |
E12 |
60 months |
18-16. d The elevator is inaccessible because the floor plan does not conform to Figure 22. |
E2 |
60 months |
18-16. e The elevator is inaccessible because the car control buttons do not have Braille and raised letters, and there is no raised star to indicate the main entry floor. |
E4 |
60 months |
18-16. f The elevator is inaccessible because the emergency controls are at 20 inches above the finished floor. |
E9 |
60 months |
18-16. g The elevator is inaccessible because the car position indicators do not illuminate or ring. |
E5 |
60 months |
18-16. h The elevator is inaccessible because, although emergency communications are provided, the system does not have raised symbol and lettering, and does not operate without tight grasping or twisting. |
E8 |
60 months |
18-17 WIC Office in the Back of the Building on the Lower Level |
|
|
18-17. a The hand sanitizer dispenser is mounted with the controls higher than 54 inches above the finished floor. |
TR5 |
6 months |
18-18 Hallway |
|
|
18-18. a Drinking Fountain near WIC Office |
|
|
18-18. a (1) The drinking fountain is inaccessible because the water height is less than 4 inches, the controls require more than 5 pounds of force to operate, the wall-mounted unit does not have 27 inches of knee space height, and there are no provisions for those who have difficulty bending. |
DF1 |
6 months |
18-19 Exit with Stairs at the Rear of the Building |
|
|
18-19. a The building does not have directional signage posted at inaccessible entrances and does not have the International Symbol of Accessibility posted at accessible entrances. |
TR17 |
6 months |
18-20 Center Clinic Exterior Entrance to the Infant and Toddler Connection Area |
|
|
18-20. a Passenger Loading Zone |
|
|
18-20. a (1) The passenger loading zone is inaccessible because there is no access aisle provided adjacent and parallel to the vehicle pull-up space. |
P4 |
6 months |
18-20. a (2) There is no accessible parking serving this area. |
P3 |
6 months |
18-20. b Curb Ramp Leading to Entrance |
|
|
18-20. b (1) The route from the passenger loading zone to the entrance of the facility is inaccessible because the slope of the curb ramp is 9.3%. |
AR5 |
6 months |
18-21 Parent Support Rooms |
|
|
18-21. a The doors to the parent support rooms are inaccessible because they have knob hardware. |
D1 |
6 months |
19. Little River Glen Senior Center 4001 Barker Court Fairfax, VA 22032 |
|
|
19-1 Front Parking Lot |
|
|
19-1. a The parking reserved for persons with disabilities is inaccessible because the van access aisle near the grass median has a cross slope of more than 2%. |
P7 |
6 months |
19-2 Rear Entrance and Route to Senior Center |
|
|
19-2. a Outdoor Telephone/Intercom |
|
|
19-2. a (1) The outdoor telephone/intercom system is not accessible to people who are deaf or hard of hearing. |
TT2 |
6 months |
19-3 Accessible Route to Front Entrance to Senior Center |
|
|
19-3. a The passenger loading zone is inaccessible because the vertical clearance is less than 114 inches. |
P4 |
6 months |
19-4 Front Entrance to Senior Center |
|
|
19-4. a Public Pay Telephone in Front of Entrance Vestibule |
|
|
19-4. a (1) The telephone in front of the entrance vestibule is inaccessible because the highest operable part is 55.5 inches above the finished floor and there is insufficient clear floor space for either a forward or side approach. |
TT1 |
6 months |
19-5 Men’s and Women’s Toilet Room with Stalls |
|
|
19-5. a Each toilet room sign is inaccessible because the signage is mounted on the door and there is no International Symbol of Accessibility. |
TR17 |
6 months |
19-5. b The doors to each toilet room are inaccessible because the pressure required to open the door is more than 5 pounds. |
D2 |
6 months |
19-5. c In each toilet room, no accessible coat hook has been provided. |
TR1 |
6 months |
19-5. d In each toilet room, the lavatory is inaccessible because the hot water pipes are not insulated or otherwise configured to protect against contact. |
TR12 |
6 months |
19-5. e In each toilet room, the triangular shelf/table protrudes into the walkway and would not be detectable to a blind person using a cane. |
AR8 |
6 months |
19-6 Rooms |
|
|
19-6. a The signage provided is inaccessible because it is mounted on the door. |
D26 |
6 months |
20. Jennings Judicial Center aka County of Fairfax Courthouse 4110 Chain Bridge Road Fairfax, VA 22030 (The renovation and expansion area was under construction during the Department’s site visit and was not surveyed.) |
|
|
20-1 Designated Accessible Parking Lot |
|
|
20-1. a Although the parking lot has a total of 16 parking spaces, none is designated as van-accessible. |
P3 |
6 months |
20-1. b The parking reserved for persons with disabilities is inaccessible because several spaces and access aisle slope 3.2%. |
P7 |
6 months |
20-2 Accessible Route to Jennings Judicial Center Entrance |
|
|
20-2. a The route from the accessible parking lot to the Jennings Judicial Center entrance is inaccessible because the route is temporarily over the road which does not have a stable, firm and slip-resistant surface. |
AR1 |
6 months |
20-2. b The route from the accessible parking lot to the Jennings Judicial Center entrance is inaccessible because a curb ramp along the route has a 16.2% slope, and a flared side with a slope of 16%. |
AR5 |
6 months |
20-3 Ground Floor/Entry Level |
|
|
20-3. a The drinking fountain en route to the cafeteria protrudes into the walkway and would not be detectable to a blind person using a cane. |
AR8 |
6 months |
20-4 Elevator |
|
|
20-4. a The elevator is inaccessible because the door for the emergency communication feature requires pinching to operate. |
E8 |
6 months |
20-4. b The clearance between the car platform sill and the edge of the hoistway landing exceeds 1.25 inches, and the car does not auto level within 0.5 inches. |
E10 |
6 months |
20-5 First Floor |
|
|
20-5. a Office of the Sheriff |
|
|
20-5. a (1) The counter in the sheriff’s office is inaccessible because it is mounted 42 inches above the finished floor. |
C6 |
6 months |
20-5. b General District Court |
|
|
20-5. b (1) The public pay telephone across from the Traffic Division protrudes into the walkway and would not be detectable to a blind person using a cane. |
AR8 |
6 months |
20-6 Third Floor |
|
|
20-6. a Civil Case Management Office |
|
|
20-6. a (1) The counter in the civil case management office is inaccessible because it is mounted 42 inches above the finished floor. |
C6 |
6 months |
20-6. a (2) The signage for Office 354 is inaccessible because it is mounted above the door and lacks Braille and raised characters. |
D26 |
6 months |
20-6. b Law Library |
|
|
20-6. b (1) The push side of the door to the Law Library, which is accessed through a front approach and which has both a closer and a latch, is inaccessible because the pillars of the electronic gate system obstruct the door’s maneuvering clearance. |
D7 |
6 months |
20-6. b (2) The check-out counter is inaccessible because it is mounted 38.75 inches above the finished floor. |
LB2 |
6 months |
20-6. b (3) The tables in the library are inaccessible because they have 25.75 inches of knee clearance to the bottom edge of the table. |
LB4 |
6 months |
20-6. b (4) Some card catalogs are inaccessible because there is less than 36 inches of clear width between the units. |
LB1 |
6 months |
20-6. c Drinking Fountain near the Law Library |
|
|
20-6. c (1) The low drinking fountain near the law library protrudes into the walkway and would not be detectable to a blind person using a cane. |
AR8 |
6 months |
20-6. d Men’s and Women’s Toilet Rooms with Stalls |
|
|
20-6. d (1) The toilet room signage at each toilet room is inaccessible because it is not mounted on the latch side of the door with raised characters and Braille. |
TR17 |
6 months |
20-6. e Land Records Division |
|
|
20-6. e (1) Research and Copy Center Area |
|
|
20-6. e (1)(a) The computer in the research and copy center area is inaccessible because it has a knee clearance height of 25.25 inches to the keyboard. |
C3 |
6 months |
20-6. f Public Services Division |
|
|
20-6. f (1) The push side of the door, which is accessed through a front approach and which has both a closer and a latch, is inaccessible because it has less than 12 inches of maneuvering clearance. |
D7 |
6 months |
20-6. f (2) The signage for Room 328 is inaccessible because it is not mounted on the latch side of the door with raised characters and Braille. |
D26 |
6 months |
20-7 Fourth Floor |
|
|
20-7. a Courtroom 4C, Room 451 |
|
|
20-7. a (1) The courtroom is inaccessible to persons with hearing disabilities because there is no assistive listening system or signage indicating its availability for persons who are hard of hearing. |
AA5 |
6 months |
20-7. a (2) The attorney table in the courtroom is inaccessible because the knee clearance is 25 inches above the finished floor. |
T1 |
6 months |
20-7. a (3) The witness stand is inaccessible because there are two steps in front of the witness stand. |
AA8 |
6 months |
20-7. b Jury Room Unisex Toilet Room |
|
|
20-7. b (1) The toilet room signage lacks the International Symbol of Accessibility. |
TR17 |
6 months |
20-7. b (2) The lavatory hot water and drain pipes are not insulated or otherwise configured to protect against contact. |
TR12 |
6 months |
20-7. b (3) The seat cover dispenser is inaccessible because it is mounted with the controls 67 inches above the finished floor. |
TR5 |
6 months |
20-7. b (4) The paper towel dispenser is inaccessible because it is mounted with the controls 59 inches above the finished floor. |
TR5 |
6 months |
20-7. b (5) The towel dispenser and the lavatory protrude into the walkway and would not be detectable to a blind person using a cane. |
AR8 |
6 months |
20-7. b (6) The lavatory is inaccessible because the hardware requires twisting of the wrist to operate. |
TR10 |
6 months |
20-7. c Drinking Fountain |
|
|
20-7. c (1) The drinking fountain is inaccessible because the knee depth is 10 inches. |
DF5 |
6 months |
20-7. d Accessible Men’s and Women’s Toilet Rooms with Stalls (at the end of the Fourth Floor) |
|
|
20-7. d (1) Each toilet room is inaccessible because the signage has no International Symbol of Accessibility. |
TR17 |
6 months |
20-7. d (2) The paper towel dispenser in the women’s toilet room is inaccessible because it protrudes into the walkway and would not be detectable to blind persons using a cane. |
AR8 |
6 months |
20-7. d (3) The toilet paper dispenser in the designated accessible stall in both toilet rooms is inaccessible because it is located above the grab bar. |
ST19 |
6 months |
20-7. d (4) The rear grab bar in the men’s designated accessible toilet room is inaccessible because it is mounted too far from the side wall. |
ST4 |
6 months |
20-8 Fifth Floor |
|
|
20-8. a Courtroom 5E |
|
|
20-8. a (1) There is no signage informing the public of the availability of an assistive listening system. |
AA3 |
6 months |
20-8. a (2) The attorney table in the courtroom is inaccessible because the knee clearance is 25 inches high. |
T1 |
6 months |
20-8. a (3) The courtroom is inaccessible because only 2 wheelchair seating areas are provided. |
AA6 |
6 months |
20-8. b Jury Room Single-User Toilet Room serving Courtroom 5E |
|
|
20-8. b (1) The single user toilet room is inaccessible because there is no signage. |
TR17 |
6 months |
20-8. b (2) The lavatory is inaccessible because it has twist-type hardware. |
TR10 |
6 months |
20-8. b (3) The side grab bar at the toilet is inaccessible because it is mounted 13 inches from the rear wall. |
SU6 |
6 months |
20-8. c Judicial Chambers - Circuit Court |
|
|
20-8. c (1) The doors to Hearing Room A and B are inaccessible because they have knob hardware. |
D1 |
6 months |
20-8. c (2) The push side of the door to each Hearing Room, which is accessed through a front approach and which has both a closer and a latch, is inaccessible because there is less than 12 inches of maneuvering clearance due to the location of furniture. |
D7 |
6 months |
20-8. c (3) The signage provided for Hearing Rooms A and B is inaccessible because it lacks Braille and raised characters and is not located on the latch side of the door. |
D26 |
6 months |
20-8. c (4) The tables in Hearing Rooms A and B are inaccessible because the knee clearance is approximately 25 inches high. |
T1 |
6 months |
20-8. c (5) There is no signage informing the public of the availability of an assistive listening system. |
AA3 |
6 months |
21. GC Herrity Building 12055 Government Center Parkway Fairfax, VA 22035 |
|
|
21-1 Parking Garage West |
|
|
21-1. a There is no van-accessible parking because the vertical clearance in the garage is less than 98 inches. |
P9 |
6 months |
21-1. b Although the parking lot has a total of 924 parking spaces, an inadequate number are designated as reserved for people with disabilities. |
P3 |
6 months |
21-1. c The signage designating parking as reserved for persons with disabilities is inaccessible because it is too low and is obstructed by parked vehicles. |
P6 |
6 months |
21-2 Accessible Route to Building’s West Entrance |
|
|
21-2. a Ramp |
|
|
21-2. a (1) The parking garage ramp leading to the building entrance is inaccessible because the handrails lack 12 inch extensions at the top and bottom of the sloped ramp surface, and the primary slope of the ramp is 10.1%. |
R5 |
6 months |
21-2. b Public Pay Telephone |
|
|
21-2. b (1) The telephone protrudes into the walkway and would not be detectable to a blind person using a cane. |
AR8 |
6 months |
21-2. b (2) There is no signage indicating the location of the nearest TTY. |
TT2 |
6 months |
21-3 Parking Garage East |
|
|
21-3. a Accessible Route to Building’s East Entrance |
|
|
21-3. a (1) The route from the parking garage to the main entrance is inaccessible because it lacks a curb ramp. |
AR5 |
6 months |
21-4 East On-Street Parking |
|
|
21-4. a The curb ramp provided is inaccessible because it has a slope of 9.8%. |
AR5 |
6 months |
21-5 Accessible Route to Main Entrance from East On-Street Parking |
|
|
21-5. a North Ramp on East Side of Building |
|
|
21-5. a (1) The ramp is inaccessible because the landing at the bottom of the ramp has a 9.6% slope and the 12 inch handrail extensions are not mounted at a level landing. |
R5 |
6 months |
21-6 First Floor |
|
|
21-6. a Elie’s Deli |
|
|
21-6. a (1) The water cups are inaccessible because the cups are on a counter 42 inches above the finished floor with a reach over an obstruction of 18 inches. |
TR4 |
6 months |
21-6. a (2) The tableware area is inaccessible because the dispensing devices are 56 inches above the finished floor. |
PD8 |
6 months |
21-6. a (3) The food service counter is inaccessible because the counter is 50 inches above the finished floor with the food located at a depth of 18 inches. |
TR4 |
6 months |
21-6. a (4) The drink cooler is inaccessible because the dispensing device is 59 inches above the finished floor with an obstruction depth of 18 inches. |
TR4 |
6 months |
21-6. a (5) The yogurt cup dispenser is inaccessible because the dispensing device is 66 inches above the finished floor with an obstruction depth of 18 inches. |
TR4 |
6 months |
21-6. a (6) The coffee condiments are inaccessible because the dispensing devices are 52 inches above the finished floor with a reach over an obstruction. |
TR4 |
6 months |
21-6. a (7) The soup dispenser is inaccessible because the dispensing device is 52 inches above the finished floor with an obstruction depth of 23 inches. |
TR4 |
6 months |
21-6. a (8) The salad bar is inaccessible because it requires a 33-inch reach depth. |
TR4 |
6 months |
21-6. a (9) The coffee dispenser is inaccessible because the dispensing device is 56 inches above the finished floor with a reach over depth of 29 inches. |
TR4 |
6 months |
21-6. b Drinking Fountain near Women’s Toilet Room |
|
|
21-6. b (1) The low drinking fountain protrudes into the walkway and would not be detectable to a blind person using a cane. |
AR8 |
6 months |
21-6. c Public Pay Telephone near Women’s Toilet Room |
|
|
21-6. c (1) There is no signage indicating the location of the nearest TTY. |
TT2 |
6 months |
21-6. d First Floor Women’s Toilet Room with Stalls |
|
|
21-6. d (1) The door is inaccessible because the pressure required to open the door is 16 pounds and it sticks within the door frame. |
D2 |
6 months |
21-6. d (2) The push side of the door, which is accessed through a front approach and which has both a closer and a latch, is inaccessible because it has less than 12 inches of maneuvering clearance. |
D7 |
6 months |
21-6. d (3) The counter protrudes into the walkway and would not be detectable to a blind person using a cane. |
AR8 |
6 months |
21-6. d (4) The seat cover dispenser is inaccessible because it is mounted with the controls 55 inches above the finished floor. |
TR5 |
6 months |
21-6. d (5) No accessible coat hook has been provided. |
TR1 |
6 months |
21-6. d (6) The sanitary napkin dispenser is inaccessible because it requires tight grasping and twisting of the wrist to operate. |
TR3 |
6 months |
21-6. d (7) Although an audible alarm is provided in this facility, there is no visual alarm appliance in the toilet room. |
TR21 |
6 months |
21-6. d (8) The designated accessible stall is incorrectly configured as an ambulatory stall, and there is no standard accessible stall provided. |
ST15 |
6 months |
21-6. e First Floor Men’s Toilet Room with Stalls |
|
|
21-6. e (1) The door is inaccessible because the pressure required to open the door is 14 pounds and the door sticks within the frame. |
D2 |
6 months |
21-6. e (2) The seat cover dispenser is inaccessible because it is mounted with the controls 57 inches above the finished floor. |
TR5 |
6 months |
21-6. e (3) No accessible coat hook has been provided. |
TR1 |
6 months |
21-6. e (4) The toilet paper dispenser is inaccessible because it is mounted 43 inches from the rear wall. |
ST19 |
6 months |
21-6. e (5) The coat rack protrudes into the walkway and would not be detectable to a blind person using a cane. |
AR8 |
6 months |
21-6. e (6) Although an audible alarm is provided in this facility, there is no visual alarm appliance in the toilet room. |
TR21 |
6 months |
21-6. e (7) The designated accessible stall is incorrectly configured as an ambulatory stall, and there is no standard accessible stall provided. |
ST15 |
6 months |
21-7 Main Lobby Elevators (6 cabs) |
|
|
21-7. a The elevator is inaccessible because the emergency controls are mounted at 23 inches above the elevator floor. |
E9 |
6 months |
21-7. b The elevator is inaccessible because, although emergency communications are provided, the system does not work without voice communication. |
E8 |
6 months |
21-8 Second Floor |
|
|
21-8. a Permit Applications - Room 230 |
|
|
21-8. a (1) The door is inaccessible because the pressure required to open the door is 8 pounds. |
D2 |
6 months |
21-8. a (2) The door to the Tech Area is inaccessible because the pressure required to open the door is 7 pounds. |
D2 |
6 months |
21-8. b Site Permits - Rooms 203-207 |
|
|
21-8. b (1) The door is inaccessible because the pressure required to open the door is 7 pounds. |
D2 |
6 months |
21-8. c Zoning Permits - Room 256 |
|
|
21-8. c (1) The door is inaccessible because the pressure required to open the door is 7 pounds. |
D2 |
6 months |
21-8. c (2) The red ticket dispenser and the display stand protrude into the walkway and would not be detectable to a blind person using a cane. |
AR8 |
6 months |
21-8. d Zoning Permits - Room 250 |
|
|
21-8. d (1) The red ticket dispenser is inaccessible because the controls are mounted at 56 inches above the finished floor. |
TR5 |
6 months |
21-8. d (2) The red ticket dispenser protrudes into the walkway and would not be detectable to a blind person using a cane. |
AR8 |
6 months |
21-8. e Public Pay Telephones in Permit Application Office |
|
|
21-8. e (1) All telephones in the permit application office are inaccessible because the highest operable part is 56 inches above the finished floor over a counter with an 18-inch depth. |
TT1 |
6 months |
21-8. e (2) Although there are 3 public telephones provided in this location, a TTY is not provided. |
TT2 |
6 months |
21-8. f Second Floor Women’s Toilet Room with Stalls |
|
|
21-8. f (1) The toilet room signage is inaccessible because it lacks the International Symbol of Accessibility. |
TR17 |
6 months |
21-8. f (2) The door is inaccessible because the pressure required to open the door is 8 pounds. |
D2 |
6 months |
21-8. f (3) The seat cover dispenser is inaccessible because the controls are mounted too high. |
TR5 |
6 months |
21-8. f (4) No accessible coat hook has been provided. |
TR1 |
6 months |
21-8. f (5) Although an audible alarm is provided in this facility, there is no visual alarm appliance in the toilet room. |
TR21 |
6 months |
21-8. g Second Floor Men’s Toilet Room with Stalls |
|
|
21-8. g (1) The toilet room signage is inaccessible because it lacks the International Symbol of Accessibility. |
TR17 |
6 months |
21-8. g (2) The door is inaccessible because the pressure required to open the door is 9 pounds. |
D2 |
6 months |
21-8. g (3) The seat cover dispenser is inaccessible because it is mounted too high. |
TR5 |
6 months |
21-8. g (4) The toilet paper dispenser is inaccessible because it is mounted 39 inches from the rear wall and against the grab bar. |
ST19 |
6 months |
21-8. g (5) No accessible coat hook has been provided. |
TR1 |
6 months |
21-8. g (6) The shelf protrudes into the walkway and would not be detectable to a blind person using a cane. |
AR8 |
6 months |
21-8. g (7) Although an audible alarm is provided in this facility, there is no visual alarm appliance in the toilet room. |
TR21 |
6 months |
21-9 Third Floor |
|
|
21-9. a Building Plan Review - Room 324 |
|
|
21-9. a (1) The public pay telephone is inaccessible because it is blocked by a moveable chair and container. |
TT1 |
6 months |
21-9. a (2) Although there is a public telephone, there is no signage or provisions for TTY users. |
TT2 |
6 months |
21-9. b Inspection Requests and Records - Room 307 |
|
|
21-9. b (1) The computer table is inaccessible because the knee clearance is 25.5 inches high. |
C3 |
6 months |
21-9. c Third Floor Women’s Toilet Room with Stalls |
|
|
21-9. c (1) The toilet paper dispenser is inaccessible because it is mounted 41 inches from the rear wall. |
ST19 |
6 months |
21-10 Fourth Floor |
|
|
21-10. a Planning and Development Division - Room 406 |
|
|
21-10. a (1) The door is inaccessible because the pressure required to open the door is 16 pounds. |
D2 |
6 months |
21-10. b Conference Room - Room 406D |
|
|
21-10. b (1) The door is inaccessible because the pressure required to open the door is 14 pounds. |
D2 |
6 months |
21-10. c Fourth Floor Women’s Toilet Room with Stalls |
|
|
21-10. c (1) The door is inaccessible because the pressure required to open the door is 8 pounds. |
D2 |
6 months |
21-10. c (2) The toilet paper dispenser is inaccessible because it is mounted above the side grab bar and 40 inches from the rear wall. |
ST19 |
6 months |
21-10. d Fourth Floor Men’s Toilet Room with Stalls |
|
|
21-10. d (1) The door is inaccessible because the pressure required to open the door is 8 pounds. |
D2 |
6 months |
21-10. d (2) The toilet paper dispenser is inaccessible because it is mounted 41 inches from the rear wall. |
ST19 |
6 months |
21-11 Fifth Floor |
|
|
21-11. a Research Library - Room 503 |
|
|
21-11. a (1) The door is inaccessible because the pressure required to open the door is 8 pounds. |
D2 |
6 months |
21-11. a (2) Some counters in the library are 42 inches above the finished floor. |
C6 |
6 months |
21-11. b Conference Room - Room 517 |
|
|
21-11. b (1) The counter/table in the conference room is inaccessible because it is 43 inches above the finished floor. |
T1 |
6 months |
21-11. c Fifth Floor Men’s Toilet Room |
|
|
21-11. c (1) The toilet paper dispenser is inaccessible because it is mounted 46 inches from the rear wall. |
ST19 |
6 months |
21-11. d Fifth Floor Women’s Toilet Room |
|
|
21-11. d (1) The designated accessible stall is incorrectly configured as an ambulatory stall, and there is no standard accessible stall provided. |
ST15 |
6 months |
21-12 Sixth Floor |
|
|
21-12. a Sixth Floor Women’s Toilet Room with Stalls |
|
|
21-12. a (1) The side grab bar is obstructed by the toilet paper dispenser. |
ST8 |
6 months |
21-12. b Sixth Floor Men’s Toilet Room with Stalls |
|
|
21-12. b (1) The shelf protrudes into the walkway and would not be detectable to a blind person using a cane. |
AR8 |
6 months |
21-13 Seventh Floor |
|
|
21-13. a Department of Planning and Zoning - Room 730 |
|
|
21-13. a (1) The counter protrudes into the walkway and would not be detectable to a blind person using a cane. |
AR8 |
6 months |
21-13. b Seventh Floor Women’s Toilet Room with Stalls |
|
|
21-13. b (1) The side grab bar is obstructed by the toilet paper dispenser. |
ST8 |
6 months |
21-13. c Seventh Floor Men’s Toilet Room with Stalls |
|
|
21-13. c (1) The shelf protrudes into the walkway and would not be detectable to a blind person using a cane. |
AR8 |
6 months |
21-14 Eighth Floor |
|
|
21-14. a Hallway |
|
|
21-14. a (1) The defibrillator and both units of the drinking fountain protrude into the walkway and would not be detectable to a blind person using a cane. |
AR8 |
6 months |
21-14. b Eighth Floor Women’s Toilet Room with Stalls |
|
|
21-14. b (1) The door is inaccessible because the pressure required to open the door is 12 pounds. |
D2 |
6 months |
21-14. b (2) Although an audible alarm is provided in this facility, there is no visual alarm appliance in the toilet room. |
TR21 |
6 months |
21-14. b (3) The seat cover dispenser is inaccessible because it is mounted with the controls 56 inches above the finished floor. |
TR5 |
6 months |
21-14. b (4) The lavatory is inaccessible because the bottom edge of the apron is 28.5 inches above the finished floor. |
TR11 |
6 months |
21-14. b (5) The lavatory is inaccessible because the hot water pipes are not insulated or otherwise configured to protect against contact. |
TR12 |
6 months |
21-14. b (6) The toilet paper dispenser is inaccessible because it is mounted 43 inches from the rear wall. |
ST19 |
6 months |
21-14. b (7) The side grab bar is inaccessible because it is obstructed by the toilet paper dispenser. |
ST8 |
6 months |
21-14. b (8) The designated accessible stall is incorrectly configured as an ambulatory stall, and there is no standard accessible stall provided. |
ST15 |
6 months |
21-14. c Eighth Floor Men’s Toilet Room with Stalls |
|
|
21-14. c (1) The door is inaccessible because the pressure required to open the door is 16 pounds. |
D2 |
6 months |
21-14. c (2) Although an audible alarm is provided in this facility, there is no visual alarm appliance in the toilet room. |
TR21 |
6 months |
21-14. c (3) The seat cover dispenser is inaccessible because it is mounted with the controls 57 inches above the finished floor. |
TR5 |
6 months |
21-14. c (4) The lavatory is inaccessible because the bottom edge of the apron is 28.5 inches above the finished floor. |
TR11 |
6 months |
21-14. c (5) The lavatory is inaccessible because the hot water pipes are not insulated or otherwise configured to protect against contact. |
TR12 |
6 months |
21-14. c (6) The toilet paper dispenser is inaccessible because it is mounted 41 inches from the rear wall. |
ST19 |
6 months |
21-14. c (7) The side grab bar is inaccessible because it is obstructed by the toilet paper dispenser. |
ST8 |
6 months |
21-14. c (8) The shelf by the toilet room door protrudes into the walkway and would not be detectable to a blind person using a cane. |
AR8 |
6 months |
21-14. c (9) The designated accessible stall is incorrectly configured as an ambulatory stall, and there is no standard accessible stall provided. |
ST15 |
6 months |
21-15 Ninth Floor |
|
|
21-15. a Hallway |
|
|
21-15. a (1) The defibrillator outside of the Planning Division - Room 927 protrudes into the walkway and would not be detectable to a blind person using a cane. |
AR8 |
6 months |
21-15. b Northern Virginia Soil and Water - Room 905 |
|
|
21-15. b (1) The door is inaccessible because the pressure required to open the door is 9 pounds. |
D2 |
6 months |
21-15. b (2) The counter protrudes into the walkway and would not be detectable to a blind person using a cane. |
AR8 |
6 months |
21-15. c Park Authority - Room 941 |
|
|
21-15. c (1) The door is inaccessible because the pressure required to open the door is 7 pounds. |
D2 |
6 months |
21-15. d Ninth Floor Drinking Fountains |
|
|
21-15. d (1) Both units of the drinking fountain protrude into the walkway and would not be detectable to a blind person using a cane. |
AR8 |
6 months |
21-15. e Ninth Floor Women’s Toilet Room with Stalls |
|
|
21-15. e (1) The door is inaccessible because the pressure required to open the door is 11 pounds. |
D2 |
6 months |
21-15. e (2) Although an audible alarm is provided in this facility, there is no visual alarm appliance in the toilet room. |
T21 |
6 months |
21-15. e (3) The designated accessible stall is incorrectly configured as an ambulatory stall, and there is no standard accessible stall provided. |
ST15 |
6 months |
21-15. e (4) The seat cover dispenser is inaccessible because it is mounted with the controls 59 inches above the finished floor. |
TR5 |
6 months |
21-15. e (5) The lavatory is inaccessible because the bottom edge of the apron is 28.5 inches above the finished floor. |
TR11 |
6 months |
21-15. e (6) The lavatory is inaccessible because the hot water pipes are not insulated or otherwise configured to protect against contact. |
TR12 |
6 months |
21-15. e (7) The sanitary napkin dispenser is inaccessible because it requires tight grasping and twisting of the wrist to operate. |
TR3 |
6 months |
21-15. f Ninth Floor Men’s Toilet Room with Stalls |
|
|
21-15. f (1) The door to men’s toilet room is inaccessible because the pressure required to open the door is 14 pounds. |
D2 |
6 months |
21-15. f (2) The designated accessible stall is incorrectly configured as an ambulatory stall, and there is no standard accessible stall provided. |
ST15 |
6 months |
21-15. f (3) Although an audible alarm is provided in this facility, there is no visual alarm appliance in the toilet room. |
TR21 |
6 months |
21-15. f (4) The seat cover dispenser is inaccessible because it is mounted with the controls 56 inches above the finished floor. |
TR5 |
6 months |
21-15. f (5) The lavatory is inaccessible because the hot water pipes are not insulated or otherwise configured to protect against contact. |
TR12 |
6 months |
21-16 Tenth Floor |
|
|
21-16. a Hallway |
|
|
21-16. a (1) The defibrillator outside the Department of Transportation Planning Division -Room 1034 protrudes into the walkway and would not be detectable to a blind person using a cane. |
AR8 |
6 months |
21-16. a (2) The high and low units of the drinking fountain protrude into the walkway and would not be detectable to a blind person using a cane. |
AR8 |
6 months |
21-16. b Tenth Floor Women’s Toilet Room with Stalls |
|
|
21-16. b (1) Although an audible alarm is provided in this facility, there is no visual alarm appliance in the toilet room. |
TR21 |
6 months |
21-16. b (2) The seat cover dispenser is inaccessible because it is mounted with the controls 59 inches above the finished floor. |
TR5 |
6 months |
21-16. b (3) The sanitary napkin dispenser is inaccessible because it requires tight grasping and twisting of the wrist to operate. |
TR3 |
6 months |
21-16. b (4) The lavatory is inaccessible because the hot water pipes are not insulated or otherwise configured to protect against contact. |
TR12 |
6 months |
21-16. b (5) The lavatory is inaccessible because the bottom edge of the apron is 28.5 inches above the finished floor. |
TR11 |
6 months |
21-16. b (6) The designated accessible stall is incorrectly configured as an ambulatory stall, and there is no standard accessible stall provided. |
ST15 |
6 months |
21-16. c Tenth Floor Men’s Toilet Room with Stalls |
|
|
21-16. c (1) The door is inaccessible because the pressure required to open the door is 8 pounds. |
D2 |
6 months |
21-16. c (2) Although an audible alarm is provided in this facility, there is no visual alarm appliance in the toilet room. |
TR21 |
6 months |
21-16. c (3) The seat cover dispenser is inaccessible because it is mounted with the controls 59 inches above the finished floor. |
TR5 |
6 months |
21-16. c (4) The lavatory is inaccessible because the hot water pipes are not insulated or otherwise configured to protect against contact. |
TR12 |
6 months |
21-16. c (5) The designated accessible stall is incorrectly configured as an ambulatory stall, and there is no standard accessible stall provided. |
ST15 |
6 months |
22. GC Pennino Building 12011 Government Center Parkway Fairfax, VA 22035 |
|
|
22-1 Parking Garage |
|
|
22-1. a The signage designating parking as reserved for persons with disabilities is too low and is obstructed by parked vehicles. |
P6 |
6 months |
22-1. b The van accessible parking space is inaccessible because only 90 inches of vertical clearance is provided. |
P9 |
60 months |
22-2 Accessible Route from Parking Garage to Building Entrance |
|
|
22-2. a Ramp from Level 2 of the Parking Garage to Building Entrance |
|
|
22-2. a (1) The ramp is inaccessible because both handrails lack 12 inch extensions at the bottom landing and the west handrail is mounted 2 inches from the wall. |
R4 |
6 months |
22-2. a (2) The east handrail protrudes into the walkway and would not be detectable to a blind person using a cane. |
AR8 |
6 months |
22-2. b The ramp from the parking garage to the building entrance is inaccessible because the slope ranges up to 8.9%, and there are no level landings along the route. |
R3 |
6 months |
22-3 Parking Lot in Front of the Building on the East Side |
|
|
22-3. a The parking reserved for persons with disabilities is inaccessible because the van access aisle is 60 inches wide. |
P8 |
6 months |
22-3. b The parking reserved for persons with disabilities is inaccessible because the spaces have slopes ranging from 3.1% to 5.1% and cross slopes up to 3.9%. |
P7 |
60 months |
22-4 Ground Floor Lobby |
|
|
22-4. a Main Reception Area |
|
|
22-4. a (1) The counter protrudes into the walkway and would not be detectable to a blind person using a cane. |
AR8 |
6 months |
22-4. b Bank of Elevators (6 cabs) |
|
|
22-4. b (1) Elevator Car #1 is inaccessible because, although emergency communications are provided, the system does not work without voice communication. |
E8 |
6 months |
22-5 Second Floor |
|
|
22-5. a Department of Family Services - Room 232 |
|
|
22-5. a (1) The door is inaccessible because the pressure required to open the door is 12 pounds. |
D2 |
6 months |
22-5. a (2) The brochure rack is inaccessible because it is mounted too high above the finished floor over an obstruction. |
TR4 |
6 months |
22-6 Third Floor |
|
|
22-6. a Mental Retardation Services - Room 310 |
|
|
22-6. a (1) The counter protrudes into the walkway and would not be detectable to a blind person using a cane. |
AR8 |
6 months |
22-6. b Meeting Room - Room 332A |
|
|
22-6. b (1) The push side of the door, which is accessed from the latch side of the door, is inaccessible because it has only 9 inches of maneuvering space on the latch side of the door. |
D11 |
6 months |
22-6. c Hallway |
|
|
22-6. c (1) The defibrillator protrudes into the walkway and would not be detectable to a blind person using a cane. |
AR8 |
6 months |
22-7 Fifth Floor |
|
|
22-7. a Department of Family Services - Room 500 |
|
|
22-7. a (1) The counter protrudes into the walkway and would not be detectable to a blind person using a cane. |
AR8 |
6 months |
22-7. b Hallway |
|
|
22-7. b (1) The defibrillator protrudes into the walkway and would not be detectable to a blind person using a cane. |
AR8 |
6 months |
22-8 Seventh Floor |
|
|
22-8. a The defibrillator near the men’s toilet room protrudes into the walkway and would not be detectable to a blind person using a cane. |
AR8 |
6 months |
22-8. b Men’s Toilet Room with Stalls |
|
|
22-8. b (1) The door is inaccessible because the pressure required to open the door is 8 pounds. |
D2 |
6 months |
22-8. b (2) The pull side of the door, which is accessed from the latch side of the door, is inaccessible because it has only 3 inches of clear maneuvering space on the latch side of the door. |
D10 |
6 months |
22-8. b (3) Although an audible alarm is provided in this facility, there is no visual alarm appliance in the toilet room. |
TR21 |
6 months |
22-8. b (4) The seat cover dispenser is inaccessible because it is mounted with the controls 57 inches above the finished floor. |
TR5 |
6 months |
22-8. b (5) No accessible coat hook has been provided in the standard accessible stall. |
TR1 |
6 months |
22-8. b (6) The toilet paper dispenser is inaccessible because it is mounted 38 inches from the rear wall. |
ST19 |
6 months |
22-8. c Women’s Toilet Room with Stalls |
|
|
22-8. c (1) The door is inaccessible because the pressure required to open the door is 7 pounds. |
D2 |
6 months |
22-8. c (2) Although an audible alarm is provided in this facility, there is no visual alarm appliance in the toilet room. |
TR21 |
6 months |
22-8. c (3) The seat cover dispenser is inaccessible because it is mounted with the controls 57 inches above the finished floor. |
TR5 |
6 months |
22-8. c (4) The lavatory is inaccessible because the hot water pipes are not insulated or otherwise configured to protect against contact. |
TR12 |
6 months |
22-8. c (5) No accessible coat hook has been provided in the standard accessible stall. |
TR1 |
6 months |
22-8. c (6) The toilet paper dispenser in the standard accessible stall is inaccessible because it is mounted 38 inches from the rear wall. |
ST19 |
6 months |
22-8. c (7) The partitions in the ambulatory stall are 37 inches wide. |
ST1 |
6 months |
22-8. c (8) No accessible coat hook has been provided in the ambulatory stall. |
TR1 |
6 months |
22-9 Eighth Floor |
|
|
22-9. a Fairfax-Falls Church Community Services Board Room - Room 836 |
|
|
22-9. a (1) The counter protrudes into the walkway and would not be detectable to a blind person using a cane. |
AR8 |
6 months |
22-10 Ninth Floor |
|
|
22-10. a School Age Child Care Room - Room 936 |
|
|
22-10. a (1) The counter protrudes into the walkway and would not be detectable to a blind person using a cane. |
AR8 |
6 months |
22-10. b Hallway |
|
|
22-10. b (1) The defibrillator near the men’s toilet room and vending machines protrudes into the walkway and would not be detectable to a blind person using a cane. |
AR8 |
6 months |
22-11 Tenth Floor |
|
|
22-11. a Community Recreation Services Reception Area |
|
|
22-11. a (1) The counter protrudes into the walkway and would not be detectable to a blind person using a cane. |
AR8 |
6 months |
23. Courthouse, JDR Courts 4000 Chain Bridge Road Fairfax, VA 22030 |
|
|
23-1 Public Parking at the Rear of the Building |
|
|
23-1. a The van accessible parking reserved for persons with disabilities lacks the appropriate signage. |
P6 |
6 months |
23-2 Accessible Route from Rear Parking to Entrance |
|
|
23-2. a Ramp |
|
|
23-2. a (1) The ramp is inaccessible because it slopes up to 9.2%, handrails are not on both sides of the ramp, and the yellow plastic container in the bottom landing reduces landing space. |
R3 |
6 months |
23-3 Signage |
|
|
23-3. a Throughout the building the permanent room number signage is inaccessible because it is not mounted on the latch side of the door. |
D26 |
6 months |
|
|
|
23-4 JRD Courts Holding Area/Cell |
|
|
23-4. a Drinking Fountain |
|
|
23-4. a (1) The wall-mounted drinking fountain is inaccessible because it is has 26 inches knee space height. |
DF5 |
6 months |
23-4. a (2) Although a drinking fountain is provided, there is no drinking fountain provided for people who have difficulty bending or stooping. |
DF3 |
6 months |
23-4. b Men’s Single-User Toilet Room in Juvenile Holding |
|
|
23-4. b (1) The toilet room signage is inaccessible because it is not mounted on the latch side of the door at 60 inches to the centerline of the sign, does not have the International Symbol of Accessibility, and lacks Braille and raised characters. |
TR17 |
6 months |
23-4. b (2) The door is inaccessible because the hardware is not usable with one hand. |
D1 |
6 months |
23-4. b (3) The lavatory hot water and drain pipes are not insulated or otherwise configured to protect against contact. |
TR12 |
6 months |
23-4. b (4) The toilet is inaccessible because the toilet centerline is 19.5 inches from the side wall. |
SU15 |
6 months |
23-4. b (5) The toilet is inaccessible because the flush control is mounted on the closed side. |
SU1 |
6 months |
23-4. b (6) The toilet is inaccessible because no grab bars are provided. |
SU10 |
6 months |
23-4. c Women’s Single-User Toilet Room in Juvenile Holding |
|
|
23-4. c (1) The toilet room signage is inaccessible because it is not mounted on the latch side of the door at 60 inches to the centerline of the sign, does not have the International Symbol of Accessibility, and lacks Braille and raised characters. |
TR17 |
6 months |
23-4. c (2) The toilet is inaccessible because the centerline is 19.5 inches from the side wall. |
SU15 |
6 months |
23-4. c (3) The toilet is inaccessible because no grab bars are provided. |
SU10 |
6 months |
23-4. c (4) The lavatory hot water and drain pipes are not insulated or otherwise configured to protect against contact. |
TR12 |
6 months |
23-4. c (5) The sanitary napkin dispenser is inaccessible because it requires tight grasping and twisting of the wrist to operate. |
TR3 |
6 months |
23-5 Sally Port |
|
|
23-5. a The Sally Port is inaccessible because it has a 7-inch curb with no curb ramp. |
AR1 |
6 months |
23-6 Courtroom G |
|
|
23-6. a The door is inaccessible because the pressure required to open the door is 15 pounds. |
D2 |
6 months |
23-6. b The attorney table in the courtroom is inaccessible because the knee clearance is 25 inches high. |
T1 |
6 months |
23-7 Courtroom F |
|
|
23-7. a The door is inaccessible because the pressure required to open the door is 15 pounds. |
D2 |
6 months |
23-7. b The attorney table in the courtroom is inaccessible because the knee clearance is 25 inches high. |
T1 |
6 months |
23-8 Courtroom C |
|
|
23-8. a The door is inaccessible because the pressure required to open the door is 16 pounds. |
D2 |
6 months |
23-8. b The attorney table in the courtroom is inaccessible because the knee clearance is 25 inches high. |
T1 |
6 months |
23-9 Courtroom 7 (Historical) |
|
|
23-9. a The door is inaccessible because it has an opening width of only 30 inches. |
D25 |
6 months |
23-10 Courtroom 2 |
|
|
23-10. a The attorney table in the courtroom is inaccessible because the knee clearance is 25 inches high. |
T1 |
6 months |
23-11 Domestic Relations Services - Room 2500 |
|
|
23-11. a The door is inaccessible because it has an opening width of only 26 inches. |
D25 |
6 months |
23-12 Hallway |
|
|
23-12. a The drinking fountain near Room 2702 protrudes into the walkway and would not be detectable to a blind person using a cane. |
AR8 |
6 months |
23-13 First Floor |
|
|
23-13. a Women’s Toilet Room with Stalls near Courtroom |
|
|
23-13. a (1) The toilet room signage is inaccessible because it is mounted on the door. |
TR17 |
6 months |
23-13. a (2) The door is inaccessible because the pressure required to open the door is 11 pounds. |
D2 |
6 months |
23-13. a (3) The seat cover dispenser is inaccessible because it is mounted with the controls 61 inches above the finished floor. |
TR5 |
6 months |
23-13. a (4) The lavatory is inaccessible because the clear floor space at the lavatory is 26 inches wide and narrowed by objects. |
TR8 |
6 months |
23-13. a (5) The toilet flush control is inaccessible because it is mounted on the closed side. |
ST2 |
6 months |
23-13. a (6) No accessible coat hook has been provided. |
TR1 |
6 months |
23-13. a (7) The toilet paper dispenser is inaccessible because it is mounted 4 inches above the side grab bar and it interferes with the use of the grab bar. |
ST19 |
6 months |
23-13. a (8) The toilet is inaccessible because the stall door operating mechanism requires tight grasping and twisting of the wrist to operate. |
TR3 |
6 months |
23-13. a (9) The sanitary napkin dispenser is inaccessible because it requires tight grasping and twisting of the wrist to operate. |
TR3 |
6 months |
23-13. a (10) The sanitary napkin dispenser protrudes into the walkway and would not be detectable to a blind person using a cane. |
AR8 |
6 months |
23-13. b First Floor Men’s Toilet Room with Stalls near Courtroom |
|
|
23-13. b (1) The toilet room signage is inaccessible because it is mounted on the door. |
TR17 |
6 months |
23-13. b (2) The door is inaccessible because the pressure required to open the door is 10 pounds. |
D2 |
6 months |
23-13. b (3) The lavatory is inaccessible because the clear floor space at the lavatory is 26 inches wide and narrowed by objects. |
TR8 |
6 months |
23-13. b (4) No accessible coat hook has been provided. |
TR1 |
6 months |
23-13. b (5) The toilet paper dispenser is inaccessible because it is mounted 3 inches above the side grab bar and it interferes with the use of the grab bar. |
ST19 |
6 months |
23-13. b (6) The toilet is inaccessible because the stall door operating mechanism requires tight grasping and twisting of the wrist to operate. |
TR3 |
6 months |
23-14 First Floor Courtroom A |
|
|
23-14. a The door is inaccessible because the pressure required to open the door is 15 pounds. |
D2 |
6 months |
23-14. b The door is inaccessible because it has knob hardware. |
D1 |
6 months |
23-14. c The attorney table in the courtroom is inaccessible because the knee clearance is 25 inches high. |
T1 |
6 months |
24. GC Government Center 12000 Government Center Parkway Fairfax, VA 22035 |
|
|
24-1 Parking Lot |
|
|
24-1. a Although the parking lot has a total of 1830 parking spaces with 4 van accessible spaces and 22 standard spaces, an inadequate number are designated as reserved for people with disabilities. |
P3 |
6 months |
24-2 Parking Lot - North Side Lot 21 |
|
|
24-2. a The parking reserved for persons with disabilities is inaccessible because the cross slopes for the parking spaces and access aisle range up to 4.1%. |
P7 |
60 months |
24-3 Accessible Route - North Side Lot 21 to Main Entrance |
|
|
24-3. a The route from the north side accessible parking leading to the main entrance is inaccessible because the slope of the sidewalk is 5.4 % and the cross slope is 3.2%. |
AR1 |
60 months |
24-3. b The ramp on the route from the north side parking lot sidewalk to the main entrance is inaccessible because is has a slope of 9.3%. |
R5 |
60 months |
24-3. c The alternate route to the building entrance through the parking lot is inaccessible because the curb ramp has a slope of 11.1% with a right side flare of 13.3%. |
AR5 |
60 months |
24-4 Parking Lot - South Side Lot 24 |
|
|
24-4. a The parking reserved for persons with disabilities is inaccessible because the cross slopes for the parking spaces and access aisle range from 3.2% to 6.1%. |
P7 |
60 months |
24-5 Accessible Route from South Side Lot 24 to Entrance |
|
|
24-5. a The ramp on the route from the south side parking lot sidewalk to the main entrance is inaccessible because it has a slope of 9.3%. |
R5 |
60 months |
24-5. b The alternate route through the parking lot from the south side parking lot to the entrance is inaccessible because the curb ramp has a slope of 10.0% with a left side flare of 13.1%. |
AR5 |
60 months |
24-6 First Floor of Government Center - Lobby Area |
|
|
24-6. a Internal House Telephone near Information Counter |
|
|
24-6. a (1) The telephone near the information counter is inaccessible because the phone location lacks accessible signage. |
TT1 |
6 months |
24-7 First Floor Employee Fitness and Wellness Center (Suite 114) |
|
|
24-7. a Counter |
|
|
24-7. a (1) The counter protrudes into the walkway and would not be detectable to a blind person using a cane. |
AR8 |
6 months |
24-7. b First Floor Women’s Locker Room |
|
|
24-7. b (1) The entrance door to the women’s locker room is inaccessible because the pressure required to open the door is 7 pounds. |
D2 |
6 months |
24-7. b (2) The seat cover dispenser in the women’s locker rooms is inaccessible because it is mounted 61 inches above the finished floor. |
TR5 |
6 months |
24-7. b (3) The toilet is inaccessible because the top of the seat is 16.5 inches above the finished floor. |
ST20 |
6 months |
24-7. b (4) No accessible coat hook has been provided. |
TR1 |
6 months |
24-7. b (5) The lavatory is inaccessible because the hot water pipes are not insulated or otherwise configured to protect against contact. |
TR12 |
6 months |
24-7. b (6) The hand dryers, red shelf, and sanitary napkin dispenser protrude into the walkway and would not be detectable to a blind person using a cane. |
AR8 |
6 months |
24-7. b (7) The transfer shower stall is inaccessible because the seat is mounted 16 inches above the finished floor and there is inadequate clear floor space along the shower opening. |
B8 |
6 months |
24-7. b (8) There is no accessible signage provided to identify the dressing room on the latch side of the door. |
D26 |
6 months |
24-7. b (9) The bench in the dressing room is inaccessible because it is not fixed to a wall. |
LR1 |
6 months |
24-7. c First Floor Men’s Locker Room |
|
|
24-7. c (1) The entrance door to the men’s locker room is inaccessible because the pressure required to open the door is 8 pounds. |
D2 |
6 months |
24-7. c (2) The seat cover dispenser in the men’s locker rooms is inaccessible because it is mounted 60 inches above the finished floor. |
TR5 |
6 months |
24-7. c (3) The lavatory is inaccessible because the hot water pipes are not insulated or otherwise configured to protect against contact. |
TR12 |
6 months |
24-7. c (4) The toilet is inaccessible because the top of the seat is 20.5 inches above the finished floor. |
ST20 |
6 months |
24-7. c (5) No accessible coat hook has been provided. |
TR1 |
6 months |
24-7. c (6) The rear grab bar at the toilet is inaccessible because the closer end distance is 7.5 inches from the side wall. |
ST4 |
6 months |
24-7. c (7) The transfer shower stall is inaccessible because the seat is broken. |
B10 |
6 months |
24-7. c (8) The dressing room door is inaccessible because the pressure required to open the door is 8 pounds. |
D2 |
6 months |
24-7. c (9) The pull side of the door to the dressing room, which is accessed through a front approach, is inaccessible because a scale obstructs the clear maneuvering space. |
D6 |
6 months |
24-7. c (10) There is no accessible signage provided to identify the dressing room on the latch side of the door. |
|
|
24-7. d Library |
|
|
24-7. d (1) The computer that provides internet access to the public is not accessible. |
C3 |
6 months |
24-7. e Public Pay Telephones |
|
|
24-7. e (1) Although there are several telephones provided, no TTY is provided. |
TT2 |
6 months |
24-7. f Department of Cable Communication Office - Room 127 |
|
|
24-7. f (1) The interior entrance door is inaccessible because the pressure required to open the door is 7 pounds. |
D2 |
6 months |
24-7. g North End Men’s and Women’s Toilet Rooms with Stalls - M-137 and W-137 |
|
|
24-7. g (1) These toilet rooms located on the 1st floor are not accessible and there is no signage directing people with disabilities to the accessible toilet rooms on the 1st floor. |
TR16 |
6 months |
24-7. h Drinking Fountain Located near Toilet Rooms M-137 and W-137 |
|
|
24-7. h (1) The drinking fountain is inaccessible because the spout is 43 inches above the finished floor and the clear floor space is 28 inches wide. |
DF1 |
6 months |
24-7. i Drinking Fountain Located near Toilet Rooms M-147 and W-147 |
|
|
24-7. i (1) The drinking fountain is inaccessible because its spout is 43 inches above the finished floor and the clear floor space is 28 inches wide. |
DF1 |
6 months |
24-7. j Drinking Fountain Located near Toilet Room M-122 |
|
|
24-7. j (1) The drinking fountain is inaccessible because its spout is 42 inches above the finished floor. |
DF1 |
6 months |
24-7. k Women’s Toilet Room with Stalls W-147 |
|
|
24-7. k (1) The toilet room signage is mounted on the door and is not accessible. |
TR17 |
6 months |
24-7. k (2) Although an audible alarm is provided in this facility, there is no visual alarm appliance in the toilet room. |
TR21 |
6 months |
24-7. k (3) The lavatory is inaccessible because the hot water pipes are not insulated or otherwise configured to protect against contact. |
TR12 |
6 months |
24-7. k (4) The toilet paper dispenser is inaccessible because it is mounted more than 36 inches from the rear wall. |
ST19 |
6 months |
24-7. k (5) The seat cover dispenser is inaccessible because it is mounted with the controls 58 inches above the finished floor. |
TR5 |
6 months |
24-7. k (6) No accessible coat hook has been provided. |
TR1 |
6 months |
24-7. k (7) Although there are 8 stalls, there is no ambulatory stall provided. |
ST1 |
6 months |
24-7. l Men’s Toilet Room with Stalls M-147 |
|
|
24-7. l (1) The toilet room signage is mounted on the door and is not accessible. |
TR17 |
6 months |
24-7. l (2) The lavatory is inaccessible because the hot water pipes are not insulated or otherwise configured to protect against contact. |
TR12 |
6 months |
24-7. l (3) The toilet is inaccessible because the flush control is on the closed side. |
ST2 |
6 months |
24-7. l (4) The seat cover dispenser is inaccessible because it is mounted with the controls 56 inches above the finished floor. |
TR5 |
6 months |
24-7. l (5) No accessible coat hook has been provided. |
TR1 |
6 months |
24-7. m Publication Office - Room 156 |
|
|
24-7. m (1) The door to the publications office is inaccessible because the pressure required to open the door is 9 pounds. |
D2 |
6 months |
24-7. n Single-User Toilet Room near Toilet Room 147 and Storage Room 147 |
|
|
24-7. n (1) The door to the single user toilet room is inaccessible because the pressure required to open the door is 15 pounds. |
D2 |
6 months |
24-7. n (2) Although an audible alarm is provided in this facility, there is no visual alarm appliance in the toilet room. |
TR21 |
6 months |
24-7. n (3) The toilet is inaccessible because the flush control is on the closed side and the toilet seat is 20.5 inches above the finished floor. |
ST2, ST20 |
6 months |
24-7. n (4) No accessible coat hook has been provided. |
TR1 |
6 months |
24-7. n (5) The lavatory hot water and drain pipes are not insulated or otherwise configured to protect against contact. |
TR12 |
6 months |
24-7. o Men’s and Women’s Toilet Rooms with Stalls M-160 and W-160 |
|
|
24-7. o (1) The toilet room signage for each room is mounted on the door. |
TR17 |
6 months |
24-7. o (2) These toilet rooms on the 1st floor are inaccessible and there is no signage directing people with disabilities to the accessible toilet rooms on the 1st floor. |
TR16 |
6 months |
24-8 Second Floor of Government Center |
|
|
24-8. a Men’s and Women’s Toilet Rooms with Stalls - M-260 & W-262 |
|
|
24-8. a (1) The toilet room signage for each room is mounted on the door. |
TR17 |
6 months |
24-8. a (2) There is no signage directing people with disabilities to the accessible toilet rooms. |
TR16 |
6 months |
24-8. b Drinking Fountain near Men’s Toilet Room M-260 |
|
|
24-8. b (1) The drinking fountain protrudes into the walkway and would not be detectable to a blind person using a cane. |
AR8 |
6 months |
24-8. b (2) The drinking fountain is not accessible and there is no signage directing people with disabilities to the accessible drinking fountains. |
DF1 |
6 months |
24-8. c Credit Union Office - Room 266 |
|
|
24-8. c (1) The interior entrance door is inaccessible because the pressure required to open the door is 10 pounds. |
D2 |
6 months |
24-8. d Women’s Toilet Room with Stalls W-247 |
|
|
24-8. d (1) The toilet room signage is inaccessible because it is mounted on the hinge side of the door. |
TR17 |
6 months |
24-8. d (2) The door is inaccessible because the pressure required to open the door is 10 pounds. |
D2 |
6 months |
24-8. d (3) Although there are 7 toilet stalls, there are no ambulatory stalls provided. |
ST1 |
6 months |
24-8. d (4) The lavatory is inaccessible because the hot water pipes are not insulated or otherwise configured to protect against contact. |
TR12 |
6 months |
24-8. d (5) The toilet paper dispenser is inaccessible because it is mounted more than 36 inches from the rear wall. |
ST19 |
6 months |
24-8. d (6) Although an audible alarm is provided in this facility, there is no visual alarm appliance in the toilet room. |
TR21 |
6 months |
24-8. d (7) The seat cover dispenser is inaccessible because it is mounted with the controls 55 inches above the finished floor. |
TR5 |
6 months |
24-8. d (8) No accessible coat hook has been provided. |
TR1 |
6 months |
24-8. e Men’s Toilet Room with Stalls M-247 |
|
|
24-8. e (1) The toilet room signage is inaccessible because it is mounted on the hinge side of the door. |
TR17 |
6 months |
24-8. e (2) The door is inaccessible because the pressure required to open the door is 11 pounds. |
D2 |
6 months |
24-8. e (3) The lavatory is inaccessible because the hot water pipes are not insulated or otherwise configured to protect against contact. |
TR12 |
6 months |
24-8. e (4) The toilet is inaccessible because the flush control is on the closed side. |
ST2 |
6 months |
24-8. e (5) Although an audible alarm is provided in this facility, there is no visual alarm appliance in the toilet room. |
TR21 |
6 months |
24-8. e (6) The seat cover dispenser is inaccessible because it is mounted with the controls 57 inches above the finished floor. |
TR5 |
6 months |
24-8. e (7) No accessible coat hook has been provided. |
TR1 |
6 months |
24-8. f Drinking Fountain near Toilet Room W-247 |
|
|
24-8. f (1) The wall-mounted drinking fountain is inaccessible because the clear floor width at the fountain is 29.5 inches. |
DF5 |
6 months |
24-8. f (2) Although a drinking fountain is provided, there is no drinking fountain provided for people who have difficulty bending or stooping |
DF3 |
6 months |
24-8. g Board Auditorium Suites 152 and 252 (Can be entered from 1st or 2nd floor) |
|
|
24-8. g (1) There is no signage informing the public of the availability of an assistive listening system. |
AA3 |
6 months |
24-8. g (2) The Board Auditorium is inaccessible to people with hearing impairments because although an audio amplification system is provided in combination with fixed seating, there is no assistive listening system. |
AA4 |
6 months |
24-8. h Conference Center |
|
|
24-8. h (1) The public pay telephone located in the conference center is inaccessible because the clear floor space objected by a trash can. |
TT1 |
6 months |
24-8. h (2) The door signage for the conference center is not accessible. |
D26 |
6 months |
24-8. h (2)(a) The entrance door to Room 2 is inaccessible because the pressure required to open the door is 10 pounds. |
D2 |
6 months |
24-8. h (2)(b) The entrance door to Room 3 is inaccessible because the pressure required to open the door is 12 pounds. |
D2 |
6 months |
24-8. h (2)(c) The entrance door to Room 8 is inaccessible because the pressure required to open the door is 8 pounds. |
D2 |
6 months |
24-8. h (3) Conference Room Toilet Rooms M-232 and W-232 |
|
|
24-8. h (3)(a) The signage provided for each toilet room is inaccessible because it is mounted on the door. |
TR17 |
6 months |
24-8. h (3)(b) These toilet rooms are not accessible and there is no signage directing people with disabilities to the other accessible toilet rooms on the 2nd floor. |
TR16 |
6 months |
24-9 Third Floor of the Government Center |
|
|
24-9. a Office of Equity Programs - Room 339 |
|
|
24-9. a (1) The door is inaccessible because the pressure required to open the door is 8 pounds. |
D2 |
6 months |
24-9. b Men’s and Women’s Toilet Rooms with Stalls M-337 & W-337 |
|
|
24-9. b (1) The signage provided for each toilet room is inaccessible because it is mounted on the door. |
TR17 |
6 months |
24-9. b (2) These toilet rooms contain a number of inaccessible elements are not accessible to people with disabilities. |
ST14 |
6 months |
24-9. c Office of Elections - Room 323 |
|
|
24-9. c (1) The door is inaccessible because the pressure required to open the door is 8 pounds. |
D2 |
6 months |
24-9. d Human Rights Commission - Room 318 |
|
|
24-9. d (1) The door is inaccessible because the pressure required to open the door is more than 5 pounds. |
D2 |
6 months |
24-9. d (2) The counter is inaccessible because it is more than 36 inches above the finished floor. |
C6 |
6 months |
24-9. e Chairman of the Board - Room 530 |
|
|
24-9. e (1) The door is inaccessible because the pressure required to open the door is 11 pounds. |
D2 |
6 months |
24-9. e (2) The counter is inaccessible because it is more than 36 inches above the finished floor. |
C6 |
6 months |
25. Burke Lake Park 7315 Ox Road Fairfax Station, VA 22039 |
|
|
25-1 Marina |
|
|
25-1. a Parking Lot Close to the Lake |
|
|
25-1. a (1) Although the parking lot has a total of 127 parking spaces, the pavement markings for the designated accessible spaces are not clearly visible. |
P3 |
6 months |
25-1. b Parking Spaces Next to the Lake |
|
|
25-1. b (1) There is no designated van accessible parking space. |
P3 |
6 months |
25-1. b (2) The parking reserved for persons with disabilities is inaccessible because the slope of the access aisle for one space is 3.2% and the slope of the other access aisle is 6.7%. |
P7 |
6 months |
25-1. c Bait Shop |
|
|
25-1. c (1) The counter is inaccessible because it is 42 inches above the finished floor. |
C5 |
6 months |
25-1. d Men’s Toilet Room with Stalls near Marina |
|
|
25-1. d (1) The toilet room signage is inaccessible because it is not mounted on the wall adjacent to the latch side of the door with the centerline of the sign 60 inches above the finished floor. |
TR17 |
6 months |
25-1. d (2) The door is inaccessible because there is a 1 inch threshold. |
D23 |
6 months |
25-1. d (3) The door is inaccessible because the ground area within the required maneuvering clearance for the door is not level. |
D13 |
6 months |
25-1. d (4) The lavatory is inaccessible because the hot water pipes are not insulated or otherwise configured to protect against contact. |
TR12 |
6 months |
25-1. d (5) The urinal is inaccessible because the rim height is 24 inches above the finished floor and the flush control height is 60 inches above the finished floor. |
TR20 |
6 months |
25-1. d (6) No accessible coat hook has been provided. |
TR1 |
6 months |
25-1. d (7) The toilet paper dispenser is inaccessible because it is mounted 51 inches from the rear wall. |
ST19 |
6 months |
25-1. e Women’s Toilet Room with Stalls near Marina |
|
|
25-1. e (1) The route to the women’s toilet room is inaccessible because it is narrowed by bushes. |
AR1 |
6 months |
25-1. e (2) The door is inaccessible because the ground area within the required maneuvering clearance for the door is not level. |
D13 |
6 months |
25-1. e (3) The toilet room signage is inaccessible because the sign is mounted on the door. |
TR17 |
6 months |
25-1. e (4) The lavatory is inaccessible because the hot water pipes are not insulated or otherwise configured to protect against contact. |
TR12 |
6 months |
25-1. e (5) No accessible coat hook has been provided. |
TR1 |
6 months |
25-1. e (6) The toilet paper dispenser is inaccessible because it is mounted 51 inches from the rear wall. |
ST19 |
6 months |
25-2 Ice Cream Parlor |
|
|
25-2. a Parking Lot (for Ice Cream Parlor and Mini Golf) |
|
|
25-2. a (1) The parking reserved for persons with disabilities is inaccessible because the designated van accessible parking space is 93.5 inches wide. |
P8 |
6 months |
25-2. b Exterior Front Entrance |
|
|
25-2. b (1) The exterior front entrance is inaccessible because the door hardware is mounted 49.5 inches above the finished floor. |
D18 |
6 months |
25-2. c Men’s Toilet Room with Stalls |
|
|
25-2. c (1) The toilet room signage is inaccessible because it is mounted on the door. |
TR17 |
6 months |
25-2. c (2) The toilet room doors that are accessed from inside the ice cream parlor are inaccessible because they have an opening width of only 29 inches, and the pressure required to open the doors is greater than 5 pounds. |
D18 |
6 months |
25-2. c (3) The air dryer is inaccessible because it is mounted with the controls 55.5 inches above the finished floor. |
TR5 |
6 months |
25-2. c (4) The urinal is inaccessible because the rim is mounted 19.5 inches above the finished floor and there is not 30 inches of clear floor space in front of the urinal. |
TR20 |
6 months |
25-2. c (5) No accessible mirror has been provided. |
TR14 |
6 months |
25-2. c (6) The designated accessible stall is inaccessible because it is 47 inches wide and 70 inches deep. |
ST16 |
6 months |
25-2. c (7) There is no rear grab bar provided in the designated accessible stall. |
ST3 |
6 months |
25-2. c (8) The designated accessible toilet is inaccessible because the top of the seat is 19.25 inches above the finished floor. |
ST20 |
6 months |
25-2. d Women’s Toilet Room with Stalls |
|
|
25-2. d (1) The toilet room signage for the inside and outside entrances is mounted on the door. |
TR17 |
6 months |
25-2. d (2) The toilet room door that is accessed from inside the ice cream parlor is inaccessible because it has an opening width of only 29 inches and the pressure required to open the door is 12 pounds. |
D18 |
6 months |
25-2. d (3) No accessible mirror has been provided. |
TR14 |
6 months |
25-2. d (4) The air dryer is mounted with the controls 55 inches above the finished floor. |
TR5 |
6 months |
25-2. d (5) The air dryer protrudes into the walkway and would not be detectable to a blind person using a cane. |
AR8 |
6 months |
25-2. d (6) The designated accessible stall is inaccessible because it is 47 inches wide and 70 inches deep. |
ST16 |
6 months |
25-2. d (7) No accessible coat hook has been provided. |
TR1 |
6 months |
25-2. d (8) The toilet paper dispenser in the designated accessible stall is inaccessible because it is mounted 38 inches from the rear wall. |
ST19 |
6 months
|
25-2. d (9) There is no rear grab bar provided in the designated accessible stall. |
ST3 |
6 months |
25-2. e Exterior Entrance/Exit to Back Porch/Patio |
|
|
25-2. e (1) The door to the back porch of the ice cream parlor is inaccessible because the door hardware is mounted 49.5 inches above the finished floor. |
D18 |
6 months |
25-2. e (2) The ramp adjoining the back porch is inaccessible because the two level landings measure 54 inches by 60 inches, the top rail is not graspable, there is no edge protection, and the handrails on both sides do not have 12 inch extensions. |
R3 |
6 months |
25-2. f Picnic Tables on Patio |
|
|
25-2. f (1) The picnic tables are inaccessible because none provide the required knee space. |
PD6 |
6 months |
25-3 Trail, Carousel, and Playground |
|
|
25-3. a Accessible Route |
|
|
25-3. b Train Exterior Ticket Window Counter |
|
|
25-3. b (1) The train ticket counter is inaccessible because it is 42 inches above the finished floor. |
C5 |
6 months |
25-3. c Playground Entrance |
|
|
25-3. c (1) The route into the playground and to the benches next to the playground is inaccessible because the route does not have a surface that is firm, stable, and slip resistant. |
AR1 |
6 months |
25-4 Ramp to Birthday Party Deck/Shelter near Mini-Golf (New) |
|
|
25-4. a The wooden route to the deck/shelter is inaccessible because there is a 1 inch lip at the beginning of the wooden route leading to the deck. |
AR1 |
6 months |
25-5 Miniature Golf (New) |
|
|
25-5. a Mini-Golf Rental Shed |
|
|
25-5. a (1) The ramp along the side building leading to the front counter is inaccessible because does not have handrails or edge protection. |
R5 |
6 months |
25-6 Amphitheater |
|
|
25-6. a Parking Lot (Shared with other amenities) |
|
|
25-6. a (1) The designated parking reserved for persons with disabilities is inaccessible because the accessible parking spaces closest to the amphitheater have access aisle cross slopes ranging from 4.3% to 5.4%. |
P7 |
6 months |
25-7 Camp Grounds |
|
|
25-7. a Parking for Camp Store |
|
|
25-7. a (1) Although the parking lot has several parking spaces, there are none marked as reserved for people with disabilities. |
P3 |
6 months |
25-7. b Camp Store |
|
|
25-7. b (1) Exterior Accessible Route |
|
|
25-7. b (1)(a) The ramp to the camp store is inaccessible because it has only one handrail, the extension is not parallel with the bottom landing, and the ramp has no edge protection. |
R3 |
6 months |
25-7. b (2) Exterior Public Pay Telephone |
|
|
25-7. b (2)(a) The telephone located on the ramp leading to the camp store is inaccessible because the clear floor space is not level and the cord is 28 inches long. |
TT1 |
6 months |
25-7. b (2)(b) The telephone protrudes into the walkway and would not be detectable to a blind person using a cane. |
AR8 |
6 months |
25-7. b (3) Exterior Entrance to Camp Store |
|
|
25-7. b (3)(a) The door to the camp store is inaccessible because there is a .75 inch change in level at the threshold to the door. |
D23 |
6 months |
25-7. b (3)(b) The door to the camp store is inaccessible because knob hardware is used. |
D1 |
6 months |
25-7. b (4) Camp Store Lobby |
|
|
25-7. b (4)(a) The counter in the lobby of the camp store is inaccessible because it is 41.5 inches above the finished floor. |
C5 |
6 months |
25-8 Women’s Shower Room |
|
|
25-8. a (1) The toilet room signage is inaccessible because it is mounted on the door and lacks the International Symbol of Accessibility, raised characters, and Braille. |
TR17 |
6 months |
25-8. a (2) The push side of the door, which is accessed through a front or side approach and which has both a closer and a latch, is inaccessible because a trash can obstructs the clear maneuvering space. |
D7, D11 |
6 months |
25-8. a (3) The lavatory is inaccessible because the hot water pipes are not insulated or otherwise configured to protect against contact. |
TR12 |
6 months |
25-8. a (4) No accessible coat hook has been provided. |
TR1 |
6 months |
25-8. a (5) There is no accessible stall provided. |
ST15 |
6 months |
25-8. a (6) The transfer shower is inaccessible because it measures 47 inches by 37 inches, the grab bars are 37 inches above the finished floor, the shower controls are 49 inches above the finished floor, the seat is not opposite the controls, the shower head is 58 inches above the finished floor, and the hose is 55 inches long. |
B8 |
6 months |
25-8. a (7) The bench is inaccessible because it measures 11.25 inches wide, 21 inches above the finished floor, and is not fixed. |
LR1 |
6 months |
25-8. b Men’s Shower Room |
|
|
25-8. b (1) The toilet room signage is inaccessible because it is mounted on the door and lacks the International Symbol of Accessibility, raised characters, and Braille. |
TR17 |
6 months |
25-8. b (2) The triangular shelf in the corner protrudes into the walkway and would not be detectable to a blind person using a cane. |
AR8 |
6 months |
25-8. b (3) The urinal is inaccessible because there is insufficient clear floor space on the right side of the urinal. |
TR20 |
6 months |
25-8. b (4) The lavatory is inaccessible because the hot water pipes are not insulated or otherwise configured to protect against contact. |
TR12 |
6 months |
25-8. b (5) No accessible coat hook has been provided. |
TR1 |
6 months |
25-8. b (6) There is no accessible stall provided. |
ST15 |
6 months |
25-8. b (7) The transfer shower is inaccessible because it measures 47 inches by 37 inches, the grab bars are 37.25 inches above the finished floor, the shower controls are 49 inches above the finished floor, the seat is not opposite the controls, the shower head is 58 inches above the finished floor, and the hose is 55 inches long. |
B8 |
6 months |
25-8. b (8) The bench is inaccessible because it is 11.25 inches wide and 21 inches above the finished floor. |
LR1 |
6 months |
25-8. c Camp Site |
|
|
25-8. c (1) Accessible Route |
|
|
25-8. c (1)(a) The route to the picnic table and grill at the designated accessible campsite is inaccessible because it is not stable, firm, and slip-resistant. |
AR1 |
6 months |
25-8. c (2) The picnic table in the designated accessible camp site does not have accessible features. |
PD6 |
6 months |
25-9 Golf Course |
|
|
25-9. a Accessible Route to Clubhouse, Driving Range, and Golf Course |
|
|
25-9. a (1) The route from the parking lot to the golf course is inaccessible because the curb ramp has a lip of .75 inches, a slope of 10.6%, and one of the flared sides of a curb ramp slopes 15.8%. |
AR5 |
6 months |
25-9. a (2) The route to the driving range is inaccessible because of low hanging tree branches that result in minimum clear headroom of less than 80 inches. |
AR1 |
6 months |
25-9. b Clubhouse |
|
|
25-9. b (1) Exterior Entrance |
|
|
25-9. b (1)(a) Both the front and rear doors of the Clubhouse are inaccessible because there are moveable objects in the required door maneuvering clearances at both entrances. |
D18 |
84 months |
25-9. b (1)(b) The rear entrance door is inaccessible because there is a 1.25 inch high threshold. |
D22 |
84 months |
25-9. b (2) Lobby |
|
|
25-9. b (2)(a) The golf counter and food counter are inaccessible because they are too high. |
C4 |
84 months |
25-9. b (3) Men’s and Women’s Toilet Rooms with Stalls |
|
|
25-9. b (3)(a) The toilet room signage for both toilet rooms is mounted on the door. |
TR17 |
84 months |
25-9. b (3)(b) The men’s and women’s toilet rooms contain a number of inaccessible elements and are not accessible to people with disabilities. |
ST14 |
84 months |
25-9. b (4) Lobby |
|
|
25-9. b (4)(a) The suggestion box near the toilet rooms protrudes into the walkway and would not be detectable to a blind person using a cane. |
AR8 |
84 months |
25-9. c Exterior Public Pay Telephone near Front Entrance |
|
|
25-9. c (1) The exterior public pay telephone is inaccessible because the clear floor space is blocked by an object and the highest operable part is not reachable using a front or side approach. |
TT1 |
6 months
|
25-10 Altered Areas |
|
|
25-10. a Information Center |
|
|
25-10. a (1) Parking Lot |
|
|
25-10. a (1)(a) Although the parking lot has a total of 10 parking spaces, there is no designated van accessible parking space and the existing access aisle is 33 inches wide and has a slope of 5.5%, and the signage is partially obstructed by shrubs |
P3 |
6 months |
25-10. a (2) Accessible Route to Entrance |
|
|
25-10. a (2)(a) The route from the parking lot to the entrance of the facility is inaccessible because the curb ramp has a slope of 10.1%, with one flared side with a slope of 12.7%. |
AR5 |
6 months |
25-10. a (2)(b) The route from the parking lot to the entrance of the facility is inaccessible because the route slopes up to 7.8%, but has not been constructed as a fully accessible ramp, there is a 1-inch change in level along the route, and there is a 2-inch gap in the sidewalk approaching the entrance door. |
AR1 |
6 months |
25-10. a (3) Public Pay Telephone near Entrance |
|
|
25-10. a (3)(a) The telephone is inaccessible because there is insufficient clear floor space. |
TT1 |
84 months |
25-10. a (3)(b) The walkway is inaccessible because the telephone protrudes into the walkway and would not be detectable to a blind person using a cane. |
AR8 |
84 months |
25-10. a (4) Brochure Rack near Entrance |
|
|
25-10. a (4)(a) The brochure rack is inaccessible because it is located above a bench which is an obstruction. |
TR4 |
6 months |
25-10. b Picnic Shelters A and B |
|
|
25-10. b (1) Parking Lot |
|
|
25-10. b (1)(a) Although the parking lot has a total of 102 parking spaces, an inadequate number of spaces are designated as reserved for people with disabilities, and the cross slope of one of the parking spaces and one access aisle exceed 2%. |
P3 |
84 months |
25-10. b (2) Route to Toilet Rooms near Picnic Shelter |
|
|
25-10. b (2)(a) The route to the toilets is inaccessible because the route is not stable, firm and slip resistant. |
AR1 |
84 months |
25-10. b (3) Toilets Rooms near Picnic Shelter (Existing) |
|
|
25-10. b (3)(a) The toilet rooms contain a number of inaccessible elements and are not accessible to people with disabilities. |
ST14 |
84 months |
25-10. c Picnic Shelter C |
|
|
25-10. c (1) Although the parking lot for Picnic Shelter C has a total of 102 parking spaces, an inadequate number of spaces are designated as reserved for people with disabilities and not all of the cross slopes of the parking spaces and access aisles are 2% or less. |
P3 |
84 months |
25-10. c (2) The walkway is inaccessible because the drinking fountain near Picnic Shelter C protrudes into the walkway and would not be detectable to a blind person using a cane. |
AR8 |
84 months |
25-10. d Parking for the Accessible Fishing Pier |
|
|
25-10. d (1) The parking is inaccessible because no van accessible parking space has been provided, some of the parking reserved for persons with disabilities lacks appropriate signage, and the surface is not firm, stable, and slip-resistant. |
P3 |
6 months |
26. Providence Recreation Center 7525 Marc Drive Falls Church, VA 22042 |
|
|
26-1 Parking |
|
|
26-1. a The parking reserved for persons with disabilities is inaccessible because the slopes in the accessible parking spaces and access aisles are greater than 2%. |
P7 |
6 months |
26-2 Accessible Route to Entrance |
|
|
26-2. a The route from the parking lot to the entrance of the facility is inaccessible because the three curb ramps leading from the parking spaces have left flared sides with slopes of 11.4%. |
AR5 |
6 months |
26-3 Second Floor (Entry Level) |
|
|
26-3. a Lobby |
|
|
26-3. a (1) The reception counter is inaccessible because the auxiliary counter is 18 inches wide. |
C6 |
6 months |
26-4 Elevator |
|
|
26-4. a The elevator contains a number of inaccessible elements and is not accessible to people with disabilities. |
E7 |
6 months |
26-5 Drinking Fountain in Second Floor Lobby |
|
|
26-5. a The wall-mounted drinking fountain is inaccessible because the knee clearance height is 24 inches |
DF5 |
6 months |
26-5. b Although a drinking fountain is provided, there is no drinking fountain provided for people who have difficulty bending or stooping. |
DF3 |
6 months |
26-6 Men’s and Women’s Toilet Rooms with Stalls on Second Floor |
|
|
26-6. a The toilet room signage at each toilet room is mounted on the door. |
TR17 |
6 months |
26-6. b There is no signage directing people with disabilities to the accessible toilet rooms. |
TR16 |
6 months |
26-6. c The designated accessible stall is incorrectly configured as an ambulatory stall, and there is no standard accessible stall provided. |
ST15 |
6 months |
26-7 Club Room #2 on Second Floor |
|
|
26-7. a The sinks in this room are inaccessible because they are mounted with the counter/rim 36.5 inches above the finished floor. |
S2 |
6 months |
26-8 First Floor |
|
|
26-8. a Drinking Fountain near Stairs |
|
|
26-8. a (1) The drinking fountain is inaccessible because the knee space width is 27 inches, the knee space height is less than 27 inches, there is no access for people who have trouble bending/stooping, and the water height is less than 4 inches. |
DF1 |
6 months |
26-8. b Racquetball Court #3 |
|
|
26-8. b (1) The door to the racquetball court is inaccessible because it has an opening width of only 27 inches and has knob hardware. |
D18 |
6 months |
26-8. c Men’s Locker Room |
|
|
26-8. c (1) The locker room signage is inaccessible because it lacks the International Symbol of Accessibility. |
TR17 |
6 months |
26-8. c (2) The door is inaccessible because the pressure required to open the door is 14 pounds. |
D2 |
6 months |
26-8. c (3) The air dryer protrudes into the walkway and would not be detectable to a blind person using a cane. |
AR8 |
6 months |
26-8. c (4) The toilet paper dispenser is inaccessible because it is mounted above the side grab bar. |
ST19 |
6 months |
26-8. c (5) There is no accessible locker provided. |
LR3 |
6 months |
26-8. d Women’s Locker Room |
|
|
26-8. d (1) The locker room signage is inaccessible because it lacks the International Symbol of Accessibility. |
TR17 |
6 months |
26-8. d (2) The door is inaccessible because the pressure required to open the door is 12 pounds. |
D2 |
6 months |
26-8. d (3) The air dryer protrudes into the walkway and would not be detectable to a blind person using a cane. |
AR8 |
6 months |
26-8. d (4) The toilet paper dispenser is inaccessible because it is mounted above the side grab bar. |
ST19 |
6 months |
26-8. d (5) There is no accessible locker provided. |
LR3 |
6 months |
26-8. e Drinking Fountain in Corridor |
|
|
26-8. e (1) Although a drinking fountain is provided, there is no drinking fountain provided for people who have difficulty bending or stooping. |
DF3 |
6 months |
26-8. f Corridor to Pool and First Aid Room |
|
|
26-8. f (1) The door to the hallway is inaccessible because the pressure required to open the door is 8 pounds. |
D2 |
6 months |
26-8. f (2) The door to the first aid office is inaccessible because the pressure required to open the door is 14 pounds. |
D2 |
6 months |
26-8. g Family Changing Room |
|
|
26-8. g (1) No accessible coat hook has been provided. |
TR1 |
6 months |
26-8. g (2) The air dryer protrudes into the walkway and would not be detectable to a blind person using a cane. |
AR8 |
6 months |
26-8. g (3) The air dryer is inaccessible because it is mounted with the controls 60 inches above the finished floor. |
TR5 |
6 months |
26-8. g (4) The lavatory is not accessible because the clear floor space is not wide enough because of the location of a trash can. |
TR8 |
6 months |
26-8. g (5) The toilet is not accessible because the centerline is 16 inches from the side wall, and there is insufficient clear floor space. |
SU14 |
6 months |
26-8. g (6) The toilet paper dispenser is inaccessible because it is mounted over the side grab bar. |
ST17 |
6 months |
26-8. g (7) The side grab bars are not accessible because they are mounted 3 inches from the wall, and 32.5 inches above the floor. |
SU5 |
6 months |
26-8. g (8) The toilet is not accessible because there is no rear grab bar provided. |
SU2 |
6 months |
26-8. g (9) The shower is inaccessible because the two grab bars mounted at different heights, and one on the back wall is mounted at 37 inches above the finished floor. |
B9 |
6 months |
26-8. g (10) The shower is inaccessible because the controls are mounted at 49 inches above the finished floor and require twisting of the wrist to operate. |
TR2 |
6 months |
26-8. g (11) The shower is inaccessible because no shower spray unit is provided and the shower head is higher than 48 inches above the finished floor. |
B11 |
6 months
|
26-8. h Pool and Spa Area |
|
|
26-8. h (1) The high drinking fountain protrudes into the walkway and would not be detectable to a blind person using a cane. |
AR8 |
6 months |
26-9 Dance Room |
|
|
26-9. a The entrance door is inaccessible because there is a 1 inch threshold. |
D23 |
6 months |
26-10 Patio |
|
|
26-10. a The picnic tables are inaccessible because none provide the required knee space. |
PD6 |
6 months |
27. Willston Instructional Facility 6131 Willston Drive Falls Church, VA 22044 |
|
|
(Surveyed for Polling purposes only) |
|
|
27-1 Parking |
|
|
27-1. a The no parking/standing sign protrudes into the walkway and would not be detectable to a blind person using a cane. |
AR8 |
6 months |
28. Tysons-Pimmit Regional Library 7584 Leesburg Pike Falls Church, VA 22043 |
|
|
28-1 Parking |
|
|
28-1. a The parking reserved for persons with disabilities is inaccessible because the designated standard spaces in the side lot have slopes and cross slopes that exceed 2%. |
P7 |
6 months |
28-2 Accessible Route |
|
|
28-2. a The route from the side parking area to the main entrance is inaccessible because the curb ramp has a slope of 10.6%. |
AR1 |
6 months |
28-3 Exterior Entrance |
|
|
28-3. a The outside book return repository is mounted with the control height 55 inches above the finished floor. |
TR5 |
6 months |
28-4 Library |
|
|
28-4. a The designated accessible computer desk with Zoom Text is inaccessible because the height of the knee space is 24 inches and there is no knee depth. |
C3 |
6 months |
28-5 Drinking Fountain by Toilet Rooms |
|
|
28-5. a The wall-mounted drinking fountain at is inaccessible because the bottom of the apron is 25.5 inches above the finished floor. |
DF5 |
6 months |
28-5. b The high unit of the drinking fountain protrudes into the walkway and would not be detectable to a blind person using a cane. |
AR8 |
6 months |
28-6 Men’s Toilet Room with Stalls |
|
|
28-6. a The toilet room signage is inaccessible because it is mounted on the door. |
TR17 |
6 months |
28-6. b The door is inaccessible because the pressure required to open the door is 10 pounds. |
D2 |
6 months |
28-6. c The push side of the door, which is accessed through a front approach and which has both a closer and a latch, is inaccessible because it has only 6 inches of maneuvering space on the latch side of the door. |
D7 |
6 months |
28-6. d The towel dispenser protrudes into the walkway and would not be detectable to a blind person using a cane. |
AR8 |
6 months |
28-6. e The paper towel dispenser is inaccessible because it is mounted with the controls 55 inches above the finished floor. |
TR5 |
6 months |
28-6. f The lavatory is inaccessible because the hot water pipes are not insulated or otherwise configured to protect against contact and there is inadequate knee clearance. |
TR9 |
6 months |
28-6. g The urinal is inaccessible because the rim is mounted 21 inches above the finished floor. |
TR20 |
6 months |
28-6. h The toilet is inaccessible because the stall door operating mechanism requires tight grasping and twisting of the wrist to operate. |
TR3 |
6 months |
28-6. i The toilet paper dispenser is inaccessible because it is mounted above the grab bar. |
ST19 |
6 months |
28-7 Women’s Toilet Room with Stalls |
|
|
28-7. a The toilet room signage is inaccessible because it is mounted on the door. |
TR17 |
6 months |
28-7. b The door is inaccessible because the pressure required to open the door is 9 pounds. |
D2 |
6 months |
28-7. c The push side of the door, which is accessed through a front approach and which has both a closer and a latch, is inaccessible because it has only 8 inches of maneuvering space on the latch side of the door. |
D7 |
6 months |
28-7. d The paper towel dispenser is inaccessible because it is mounted with the controls 55 inches above the finished floor. |
TR5 |
6 months |
28-7. e The sanitary napkin dispenser is inaccessible because it requires tight grasping and twisting of the wrist to operate. |
TR3 |
6 months |
28-7. f The lavatory is inaccessible because the hot water pipes are not insulated or otherwise configured to protect against contact and there is inadequate knee clearance. |
TR9 |
6 months |
28-7. g The toilet is inaccessible because the stall door operating mechanism requires tight grasping and twisting of the wrist to operate. |
TR3 |
6 months |
28-7. h No accessible coat hook has been provided. |
TR1 |
6 months |
28-7. i The toilet paper dispenser is inaccessible because it is mounted above the grab bar. |
ST19 |
6 months |
28-8 Conference Room #3 |
|
|
28-8. a The door is inaccessible because the pressure required to open the door is 18 pounds. |
D2 |
6 months |
28-9 Book Sale Room |
|
|
28-9. a The pull side of the door, which is accessed through a front approach, is inaccessible because it has insufficient maneuvering clearance due to the presence of the table. |
D6 |
6 months |
29. Lee District Recreation Center 6601 Telegraph Road Franconia, VA 22310 |
|
|
29-1 Parking Lot Serving the Carousel, Train, and Picnic Areas |
|
|
29-1. a The van accessible parking reserved for persons with disabilities lacks the appropriate signage. |
P6 |
6 months |
29-2 Accessible Routes Serving the Carousel, Train, and Picnic Areas |
|
|
29-2. a The route to the carousel is inaccessible because some sections are not stable, firm and slip-resistant. |
AR1 |
6 months |
29-2. b The routes to the train, picnic tables, grills, and portable toilet are inaccessible because the routes are not stable, firm and slip-resistant. |
AR1 |
6 months |
29-3 Picnic Areas |
|
|
29-3. a The picnic tables are inaccessible because none have the required knee space. |
PD6 |
6 months |
29-3. b The toilet paper in the portable toilet room is inaccessible because it is mounted above the grab bar |
SU17 |
6 months |
29-4 Amphitheater |
|
|
29-4. a Accessible Seating Platform |
|
|
29-4. a (1) The entrance to the accessible seating platform is inaccessible because there is a 2.5 inch change in level at the threshold. |
D23 |
6 months |
29-5 Parking Lot Serving the Tennis Courts, Volleyball, Basketball Courts, and Playground |
|
|
29-5. a Although the parking lot has a total of 44 parking spaces, there are no spaces designated as reserved for people with disabilities. |
P3 |
6 months |
29-6 Playground |
|
|
29-6. a The playground is inaccessible because there is a 2-inch change in level at its entrance and there is no accessible route to an accessible piece of play equipment. |
AR1, PG1 |
6 months |
29-7 Parking Lots Serving the Recreation Center |
|
|
29-7. a Although the parking lot has a total of 153 parking spaces, there are no designated van accessible parking spaces. |
P3 |
6 months |
29-7. b The parking is inaccessible because five of the ten designated accessible spaces do not have access aisles and the access aisles provided for five of the spaces are 50 inches wide. |
P1 |
6 months |
29-8 Route from Parking Lot to Main Entrance of the Building |
|
|
29-8. a The route from the parking lot to the main entrance is inaccessible because the cross slope of the sidewalk ranges up to 8.1%. |
AR1 |
6 months |
29-9 Building Lobby |
|
|
29-9. a The defibrillator protrudes into the walkway and would not be detectable to a blind person using a cane. |
AR8 |
6 months |
29-10 Doors |
|
|
29-10. a The interior doors throughout the facility are inaccessible because the pressure required to open the doors is greater than 5 pounds. |
D2 |
6 months |
29-11 Women’s Toilet Room with Stalls |
|
|
29-11. a The toilet room signage is inaccessible because it lacks the International Symbol of Accessibility. |
TR17 |
6 months |
29-11. b No accessible mirror has been provided. |
TR14 |
6 months |
29-11. c The seat cover dispenser is inaccessible because it is mounted with the controls 59 inches above the finished floor. |
TR5 |
6 months |
29-11. d The paper towel dispenser is inaccessible because it requires tight grasping and twisting of the wrist to operate. |
TR3 |
6 months |
29-11. e The paper towel dispenser protrudes into the walkway and would not be detectable to a blind person using a cane. |
AR8 |
6 months |
29-11. f The lavatory is inaccessible because the hot water pipes are not insulated or otherwise configured to protect against contact. |
TR12 |
6 months |
29-11. g The designated accessible toilet is inaccessible because there is insufficient clear floor space. |
ST18 |
6 months |
29-11. h The toilet is inaccessible because its centerline is 19 inches from the wall with the metal partition. |
ST17 |
6 months |
29-11. i No accessible coat hook has been provided. |
TR1 |
6 months |
29-11. j The toilet paper dispenser is inaccessible because it is mounted above the grab bar, it is more than 36 inches from the rear wall, and it interferes with use of the side grab bar. |
ST19 |
6 months |
29-11. k The side grab bar is inaccessible because it is mounted with the far end less than 52 inches from the rear wall. |
ST6 |
6 months |
29-11. l The rear grab bar is inaccessible because it is 21 inches long. |
ST4 |
6 months |
29-12 Men’s Toilet Room with Stalls |
|
|
29-12. a The toilet room signage is inaccessible because it lacks the International Symbol of Accessibility. |
TR17 |
6 months |
29-12. b No accessible mirror has been provided. |
TR14 |
6 months |
29-12. c The seat cover dispenser is inaccessible because it is mounted with the controls 63 inches above the finished floor. |
TR5 |
6 months |
29-12. d The paper towel dispenser is inaccessible because it requires tight grasping and twisting of the wrist to operate. |
TR3 |
6 months |
29-12. e The paper towel dispenser protrudes into the walkway and would not be detectable to a blind person using a cane. |
AR8 |
6 months |
29-12. f The lavatory is inaccessible because the hot water pipes are not insulated or otherwise configured to protect against contact. |
TR12 |
6 months |
29-12. g The urinal is inaccessible because the rim is mounted 19 inches above the finished floor. |
TR20 |
6 months |
29-12. h The toilet is inaccessible because its centerline is 19 inches from the wall with the metal partition. |
ST17 |
6 months |
29-12. i No accessible coat hook has been provided. |
TR1 |
6 months |
29-12. j The side grab bar is inaccessible because it is mounted with the far end less than 52 inches from the rear wall. |
ST6 |
6 months |
29-12. k The toilet is inaccessible because the rear grab bar at the designated accessible toilet is 21 inches long. |
ST4 |
6 months |
29-13 Elevator |
|
|
29-13. a The elevator is inaccessible because audible and visual arrival signals are not provided, the hall lantern fixtures are not centered at 72 inches, and the signals are not visible from the area of the hall call buttons. |
E11 |
6 months |
29-13. b The elevator is inaccessible because the car position indicators are broken. |
E5 |
6 months |
29-13. c The elevator is inaccessible because, although emergency communications are provided, the handset cord is less than 29 inches long and the system does not work without voice communication. |
E8 |
6 months |
29-14 Women’s Locker Room |
|
|
29-14. a The locker room signage is inaccessible because it lacks the International Symbol of Accessibility and signage is not mounted on the latch side of the door. |
TR17 |
6 months |
29-14. b The air dryers and mirror shelf protrude into the walkway and would not be detectable to a blind person using a cane. |
AR8 |
6 months |
29-14. c The lavatory is inaccessible because it has clear floor space that measures 36 inches deep. |
TR8 |
6 months |
29-14. d Although there are 7 stalls, there is no ambulatory stall provided. |
ST1 |
6 months |
29-14. e The toilet stall is inaccessible because it does not have clear floor space measuring 60 inches by 56 inches. |
ST16 |
6 months |
29-14. f The toilet is inaccessible because its centerline is 16 inches from the side wall. |
ST17 |
6 months |
29-14. g The side grab bar is inaccessible because it is mounted less than 52 inches from the rear wall. |
ST7 |
6 months |
29-14. h The rear grab bar is inaccessible because it is less than 36 inches long and the closer end is more than 6 inches from the side wall. |
ST4 |
6 months |
29-14. i The toilet paper dispenser is inaccessible because it is mounted 47 inches from the rear wall. |
ST19 |
6 months |
29-14. j The gang shower is inaccessible because no shower spray unit is provided and the shower head is higher than 48 inches above the finished floor. |
B11 |
6 months |
29-14. k The designated accessible dressing area is inaccessible because there is no signage indicating it is accessible, the bench lacks clear floor space on its side to allow a parallel transfer, and there is no mirror. |
LR2 |
6 months |
29-14. l There is no accessible locker provided. |
LR3 |
6 months |
29-15 Men’s Locker Room |
|
|
29-15. a The locker room signage is inaccessible because it lacks the International Symbol of Accessibility and is not mounted on the latch side of the door. |
TR17 |
6 months |
29-15. b The air dryers protrude into the walkway and would not be detectable to a blind person using a cane. |
AR8 |
6 months |
29-15. c The lavatory is inaccessible because it has clear floor space that is 36 inches deep. |
TR8 |
6 months |
29-15. d Although there are 7 stalls, there is no ambulatory stall provided. |
ST1 |
6 months |
29-15. e The toilet stall is inaccessible because it does not have clear floor space measuring 60 inches by 56 inches. |
ST16 |
6 months |
29-15. f The toilet is inaccessible because its centerline is 16 inches from the side wall. |
ST17 |
6 months |
29-15. g The side grab bar is inaccessible because it is mounted less than 52 inches from the rear wall. |
ST7 |
6 months |
29-15. h The rear grab bar is inaccessible because it is less than 36 inches long and the closer end is more than 6 inches from the side wall. |
ST4 |
6 months |
29-15. i The toilet paper dispenser is inaccessible because it is mounted 47 inches from the rear wall. |
ST19 |
6 months |
29-15. j The gang shower is inaccessible because no shower spray unit is provided and the shower head is higher than 48 inches above the finished floor. |
B11 |
6 months |
29-15. k The designated accessible dressing area is inaccessible because there is no signage indicating it is accessible, the bench lacks clear floor space on its side to allow a parallel transfer, and there is no mirror. |
LR2 |
6 months |
29-15. l There is no accessible locker provided. |
LR3 |
6 months |
29-16 Family Changing Room |
|
|
29-16. a The toilet room signage is inaccessible because it is mounted with the centerline 68 inches above the finished floor. |
TR17 |
6 months |
29-16. b The baby changing table is mounted with the controls 58 inches above the finished floor and the table surface is 38 inches above the finished floor when in the open position. |
TR5 |
6 months |
29-16. c The shower is inaccessible because it measures 38 inches by 43 inches. |
B8 |
6 months |
29-16. d The lavatory is inaccessible because the hot water pipes are not insulated or otherwise configured to protect against contact. |
TR12 |
6 months |
29-16. e The paper towel dispenser is inaccessible because it requires tight grasping and twisting of the wrist to operate. |
TR3 |
6 months |
29-16. f The toilet is inaccessible because its centerline is 20 inches from the side wall. |
SU15 |
6 months |
29-16. g The side grab bar is inaccessible because it is 36 inches long, the closer end is mounted 13 inches from the rear wall, the distance from the far end to the rear wall is 49 inches, and there is 2 inches of space between the grab bar and the wall. |
ST6 |
6 months |
29-16. h There is no accessible locker provided. |
LR3 |
6 months |
29-17 Racquetball Courts |
|
|
29-17. a The door to the racquetball court is inaccessible because it has an opening width of 22 inches and a 1 inch threshold. |
D25 |
6 months |
30. Frying Pan Farm 2739 West Ox Road Herndon, VA 20170 |
|
|
30-1 Visitor Center (New Construction) |
|
|
30-1. a Parking |
|
|
30-1. a (1) Although the parking lot has a total of 92 parking spaces, an inadequate number are designated as reserved for people with disabilities. |
P3 |
6 months |
30-1. a (2) The van accessible parking reserved for persons with disabilities lacks the appropriate signage. |
P6 |
6 months |
30-1. b Exterior Front Entrance |
|
|
30-1. b (1) The building does not have directional signage posted at inaccessible entrances and does not have the International Symbol of Accessibility posted at accessible entrances. |
D16 |
6 months |
30-1. b (2) The exterior front entrance door is inaccessible because there is a 1.5 inch change in level at the threshold to the door. |
D22 |
6 months |
30-1. b (3) The second door in a series is inaccessible because the pressure required to open the door is 9 pounds. |
D2 |
6 months |
30-1. c Auditorium |
|
|
30-1. c (1) There is no accessible route connecting the wheelchair seating areas and the stage or balcony. |
AA1 |
6 months |
30-1. c (2) There is no signage informing the public of the availability of an assistive listening system. |
AA3 |
6 months |
30-1. d Exterior Rear Entrance |
|
|
30-1. d (1) The exterior rear entrance is inaccessible because it has a 6-inch change in level at the threshold to the door, and there is no signage directing people with disabilities to an accessible entrance. |
D23, D16 |
6 months |
30-1. e Route from Rear Entrance to Classrooms |
|
|
30-1. e (1) The fire extinguisher mounted at the top of the steps protrudes into the walkway and would not be detectable to a blind person using a cane. |
AR8 |
6 months |
30-1. f Single-User Toilet Room next to Classroom |
|
|
30-1. f (1) The toilet room contains a number of inaccessible elements and is not accessible to people with disabilities. |
SU13 |
6 months |
30-1. g Drinking Fountain near Front Entrance |
|
|
30-1. g (1) The single drinking fountain protrudes into the walkway and would not be detectable to a blind person using a cane, and there is no drinking fountain for people who have difficulty bending or stooping. |
AR8, DF3 |
6 months |
30-1. h Women’s Toilet Room with Stalls near Front Entrance |
|
|
30-1. h (1) The toilet room signage is inaccessible because it is mounted on the door and lacks the International Symbol of Accessibility, raised and Braille characters mounted on the wall adjacent to the latch side of the door with the centerline of the sign 60 inches above the finished floor. |
TR17 |
6 months |
30-1. h (2) The door to the toilet room is inaccessible because the pressure required to open the door is 17 pounds. |
D2 |
6 months |
30-1. h (3) No accessible mirror has been provided. |
TR14 |
6 months |
30-1. h (4) The lavatory is inaccessible because the top of the counter is 35.5 inches above the finished floor, and the hot water pipes are not insulated or otherwise configured to protect against contact. |
TR9 |
6 months |
30-1. h (5) The designated accessible toilet stall is inaccessible because it is 47 inches wide. |
ST16 |
6 months |
30-1. h (6) The toilet flush control is inaccessible because it is on the closed side. |
ST2 |
6 months |
30-1. h (7) The toilet paper dispenser is inaccessible because it is mounted 39.5 inches from the rear wall. |
ST19 |
6 months |
30-1. h (8) The side and rear grab bars at the designated accessible toilet are mounted 38.5 inches above the finished floor. |
ST12 |
6 months |
30-1. h (9) Although an audible alarm is provided in this facility, there is no visual alarm appliance in the toilet room. |
TR21 |
6 months |
30-1. i Men’s Toilet Room with Stalls Near Front Entrance |
|
|
30-1. i (1) The toilet room signage is inaccessible because it is mounted on the door and lacks the International Symbol of Accessibility, raised and Braille characters mounted on the wall adjacent to the latch side of the door with the centerline of the sign 60 inches above the finished floor. |
TR17 |
6 months |
30-1. i (2) The door to the toilet room is inaccessible because the pressure required to open the door is 17 pounds. |
D2 |
6 months |
30-1. i (3) No accessible mirror has been provided. |
TR14 |
6 months |
30-1. i (4) The lavatory is inaccessible because it the top of the counter is 35 inches above the finished floor, and the hot water pipes are not insulated or otherwise configured to protect against contact. |
TR9 |
6 months |
30-1. i (5) The urinal is inaccessible because the rim is 24 inches above the finished floor and the flush control is 52 inches above the finished floor. |
TR20 |
6 months |
30-1. i (6) The designated accessible toilet stall is inaccessible because it is 47 inches wide. |
ST16 |
6 months |
30-1. i (7) The toilet flush control is inaccessible because it is on the closed side. |
ST2 |
6 months |
30-1. i (8) The side and rear grab bars are inaccessible because they are mounted 38 inches above the finished floor. |
ST12 |
6 months |
30-1. i (9) Although an audible alarm is provided in this facility, there is no visual alarm appliance in the toilet room. |
TR21 |
6 months |
30-2 Activity Center |
|
|
30-2. a Parking |
|
|
30-2. a (1) Although the parking lot has a total of 250 parking spaces, the parking designated for people with disabilities is inaccessible because only two spaces are designated as reserved for people with disabilities; the pavement markings are not clear; the surface is not stable, firm and slip resistant; and the designated accessible spaces are not dispersed and on the shortest accessible route. |
P3 |
6 months |
30-2. b Accessible Route to Entrance |
|
|
30-2. b (1) The route from the designated accessible parking spaces to the entrance of the facility is not accessible because the route is not stable, firm, and slip resistant. |
AR1 |
6 months |
30-2. c Performance Ring and Spectator Area |
|
|
30-2. c (1) The spectator area is inaccessible because there is no accessible route to the wheelchair seating next to the bleachers and the ground at the wheelchair seating area is not firm, stable, and slip-resistant. |
AA7 |
6 months |
30-2. c (2) The announcer’s booth is inaccessible because there are two steps to the entrance. |
AR2 |
6 months |
30-2. d Men’s Toilet Room with Stalls |
|
|
30-2. d (1) The toilet room signage is inaccessible because it is not mounted on the latch side of the door at 60 inches from the centerline of the sign to the finished floor with raised characters and Braille, and lacks the International Symbol of Accessibility. |
TR17 |
6 months |
30-2. d (2) The lavatory is inaccessible because the hot water pipes are not insulated or otherwise configured to protect against contact. |
TR12 |
6 months |
30-2. d (3) The designated accessible stall is incorrectly configured as an ambulatory stall, and there is no standard accessible stall provided. |
ST15 |
6 months |
30-2. e Women’s Toilet Room with Stalls |
|
|
30-2. e (1) The toilet room signage is inaccessible because it is not mounted on the latch side of the door at 60 inches from the centerline of the sign to the finished floor with raised characters and Braille, and lacks the International Symbol of Accessibility. |
TR17 |
6 months |
30-2. e (2) The lavatory is inaccessible because the hot water pipes are not insulated or otherwise configured to protect against contact. |
TR12 |
6 months |
30-2. e (3) The designated accessible stall is incorrectly configured as an ambulatory stall, and there is no standard accessible stall provided. |
ST15 |
6 months |
30-2. f Office |
|
|
30-2. f (1) The office counter is inaccessible because it is 38 inches above the finished floor. |
C6 |
6 months |
30-2. g Drinking Fountain near Office |
|
|
30-2. g (1) The wall-mounted drinking fountain is inaccessible because the knee space between the apron bottom and the finished floor is 25 inches. |
DF5 |
6 months |
30-2. g (2) Although a drinking fountain is provided, there is no drinking fountain provided for people who have difficulty bending or stooping. |
DF3 |
6 months |
30-2. h 4-H Building |
|
|
30-2. h (1) The route to the entrance is inaccessible because it is not stable, firm and slip-resistant. |
AR1 |
6 months |
30-2. i Reviewing Stands (Shaded Viewing Platforms) near Lower Performance Ring |
|
|
30-2. i (1) The reviewing stands are inaccessible because the route to them is not stable, firm and slip-resistant and there are steps to the entrance. |
AR1 |
6 months |
30-2. j Country Store |
|
|
30-2. j (1) The porch is inaccessible because there is a 4.5 inch step leading up to the porch. |
AR1 |
6 months |
30-2. j (2) The store entrance is inaccessible because there is a 3-inch change in level at the threshold to the door. |
D23 |
6 months |
30-2. j (3) The door to the entrance is inaccessible because it has knob hardware. |
D1 |
6 months |
30-2. j (4) The counter in the country store is inaccessible because it is 38 inches above the finished floor |
C5 |
6 months |
30-2. k Toilet Rooms with Stalls near Playground |
|
|
30-2. k (1) The toilet rooms contain a number of inaccessible elements and are not accessible to people with disabilities. |
ST14 |
6 months |
30-3 School House |
|
|
30-3. a Front Entrance/Rear Entrance |
|
|
30-3. a (1) The building does not have directional signage posted at inaccessible entrances and does not have the International Symbol of Accessibility posted at accessible entrances. |
D16 |
6 months |
30-3. a (2) The front entrance is inaccessible because it has a door opening width of 29.5 inches, and there is a 1 inch change in level at the threshold to the door. |
D18 |
6 months |
30-3. a (3) The back entrance is inaccessible because of stairs. |
D23 |
6 months |
30-3. b Interior Route |
|
|
30-3. b (1) The doors in the School House are inaccessible because they have knob hardware. |
D1 |
6 months |
30-3. b (2) There is no access to the main level of the facility for people with mobility impairments as there are 7 steps inside of the front entrance. |
AR9 |
6 months |
30-3. c Main Level |
|
|
30-3. c (1) The wall-mounted drinking fountain is inaccessible because the knee space between the apron bottom and the finished floor is 19 inches. |
DF5 |
6 months |
30-3. c (2) Although a drinking fountain is provided, there is no drinking fountain provided for people who have difficulty bending or stooping. |
DF3 |
6 months |
30-3. c (3) Men’s and Women’s Single-User Toilet Rooms |
|
|
30-3. c (3)(a) The door to the each single user toilet room is inaccessible because it has an opening width of only 27 inches and knob hardware. |
D18 |
6 months |
30-3. c (3)(b) These single user toilet rooms contains a number of inaccessible elements and are not accessible to people with disabilities. |
SU13 |
6 months |
30-4 Kidwell Farm Buildings |
|
|
30-4. a Parking |
|
|
30-4. a (1) The parking reserved for persons with disabilities is inaccessible because the surface is not firm, stable, and slip-resistant. |
P7 |
6 months |
30-4. b Accessible Route |
|
|
30-4. b (1) The route from the parking lot to the buildings is inaccessible because the surface is not firm, stable, and slip-resistant. |
AR1 |
6 months |
30-4. c Historical Kidwell Farm House |
|
|
30-4. c (1) Accessible Route |
|
|
30-4. c (1)(a) The ramp to the rear entrance is inaccessible because it slopes up to 12.8%, and the ramp does not have handrails on both sides that comply with the Standards. |
R3 |
6 months |
30-4. c (2) Exterior Rear Entrance |
|
|
30-4. c (2)(a) The building does not have directional signage posted at inaccessible entrances and does not have the International Symbol of Accessibility posted at accessible entrances. |
D16 |
6 months |
30-4. c (2)(b) The rear entrance to the Kidwell Farm House is inaccessible because there is a 1.5 inch change in level at the threshold to the door. |
D23 |
6 months |
30-4. c (2)(c) The rear entrance to the Kidwell Farm House is inaccessible because it has knob hardware. |
D1 |
6 months |
30-4. c (3) Interior Route |
|
|
30-4. c (3)(a) The doors inside the Kidwell Farm House are inaccessible because they have an opening width of only 28 inches. |
D25 |
6 months |
30-4. d Dairy |
|
|
30-4. d (1) The entrance to the dairy is inaccessible because there is a 1.5 inch change in level at the threshold to the door. |
D23 |
6 months |
30-4. e Tractor Wagons |
|
|
30-4. e (1) None of the tractor wagons are usable by people with mobility disabilities. Ensure program access by providing at least one tractor wagon that is on an accessible route and can be accessed by people who use wheelchairs. |
28 C.F.R. § 35.130 |
6 months |
31. Lorton Library 9520 Richmond Highway Lorton, VA 22079 |
|
|
31-1 Parking |
|
|
31-1. a The van-accessible signage designating parking as reserved for persons with disabilities is obstructed by a bush. |
P6 |
6 months |
31-2 Accessible Route |
|
|
31-2. a The route from the parking lot to the entrance of the facility is inaccessible because two of the parking spaces do not have wheel stops and cars can encroach on the width of the route. |
AR3 |
6 months |
31-3 Women’s Toilet Room with Stalls near Entrance |
|
|
31-3. a The toilet room signage is inaccessible because it is mounted on the door. |
TR17 |
6 months |
31-3. b Although an audible alarm is provided in this facility, there is no visual alarm appliance in the toilet room. |
TR21 |
6 months |
31-3. c No accessible coat hook has been provided. |
TR1 |
6 months |
31-3. d The toilet paper dispenser is inaccessible because it is mounted 37 inches from the rear wall and interferes with the use of the side grab bar. |
ST19 |
6 months |
31-3. e The door to the toilet stall is inaccessible because the latching mechanism requires tight grasping and twisting of the wrist. |
D1 |
6 months |
31-4 Men’s Toilet Room with Stalls |
|
|
31-4. a The toilet room signage is inaccessible because it is mounted on the door. |
TR17 |
6 months |
31-4. b Although an audible alarm is provided in this facility, there is no visual alarm appliance in the toilet room. |
TR21 |
6 months |
31-4. c The door to the toilet room is inaccessible because the pressure required to open the door is 8 pounds. |
D2 |
6 months |
31-4. d The toilet is inaccessible because the flush control is on the closed side. |
ST2 |
6 months |
31-4. e No accessible coat hook has been provided. |
TR1 |
6 months |
31-4. f The urinal is inaccessible because the rim is 25 inches above the finished floor and the flush control is 53 inches above the finished floor. |
TR20 |
6 months |
31-4. g The door to the toilet stall is inaccessible because the latching mechanism requires tight grasping and twisting of the wrist. |
D1 |
6 months |
32. Spring Hill Recreation Center 1239 Spring Hill Road McLean, VA 22102 |
|
|
32-1 Public Pay Telephone |
|
|
32-1. a The telephone is inaccessible because the counter height is 38 inches, the highest operable part is 59 inches above the floor, and the cord is less than 29 inches long. |
TT1 |
6 months |
32-1. b The telephone protrudes into the walkway and would not be detectable to a blind person using a cane. |
AR8 |
6 months |
32-2 Women’s Toilet Room with Stalls |
|
|
32-2. a The toilet room signage is inaccessible because it is not mounted on the latch side of the door. |
TR17 |
6 months |
32-2. b The door is inaccessible because the pressure required to open the door is 10 pounds. |
D2 |
6 months |
32-2. c Although an audible alarm is provided in this facility, there is no visual alarm appliance in the toilet room. |
TR21 |
6 months |
32-2. d No accessible mirror has been provided. |
TR14 |
6 months |
32-2. e The soap dispenser is inaccessible because it is mounted with the controls 53 inches above the finished floor. |
TR5 |
6 months |
32-2. f The lavatory is inaccessible because the hot water pipes are not insulated or otherwise configured to protect against contact. |
TR12 |
6 months |
32-2. g No accessible coat hook has been provided. |
TR14 |
6 months |
32-2. h The rear grab bar at the designated accessible toilet is obstructed by the automatic flush control. |
ST5 |
6 months |
32-3 Men’s Toilet Room with Stalls |
|
|
32-3. a The toilet room signage is inaccessible because it is not mounted on the latch side of the door. |
TR5 |
6 months |
32-3. b The door is inaccessible because the pressure required to open the door is 7 pounds. |
D2 |
6 months |
32-3. c Although an audible alarm is provided in this facility, there is no visual alarm appliance in the toilet room. |
TR21 |
6 months |
32-3. d The soap dispenser is inaccessible because it is mounted with the controls 53 inches above the finished floor. |
TR5 |
6 months |
32-3. e The lavatory is inaccessible because the hot water pipes are not insulated or otherwise configured to protect against contact. |
TR12 |
6 months |
32-3. f The side and rear grab bars at the designated accessible toilet is inaccessible because they are mounted 37 inches above the finished floor. |
ST12 |
6 months |
32-4 Elevator |
|
|
32-4. a The elevator is inaccessible because the hall call buttons are centered at 39.5 inches above the finished floor. |
E3 |
6 months |
32-4. b The elevator is inaccessible because hoistway signage is provided only on one door jamb. |
E12 |
6 months |
32-4. c The elevator is inaccessible because, although emergency communications are provided, the system does not work without voice communication. |
E8 |
6 months |
32-5 Second Floor Rooms |
|
|
32-5. a The door to the weight room is inaccessible because the pressure required to open the door is 10 pounds. |
D2 |
6 months |
32-5. b The door to the community room is inaccessible because the pressure required to open the door is 10 pounds. |
D2 |
6 months |
32-5. c Both racquetball courts are inaccessible because they have knob hardware. |
D1 |
6 months |
32-6 Unisex Locker Room next to the Pool |
|
|
32-6. a Although an audible alarm is provided in this facility, there is no visual alarm appliance in the locker room. |
TR21 |
6 months |
32-6. b The rear grab bar at the designated accessible toilet is inaccessible because it is 30 inches long. |
ST4 |
6 months |
32-6. c The rear grab bar is inaccessible because it is mounted 37 inches above the finished floor. |
ST12 |
6 months |
32-6. d The roll-in shower is inaccessible because the grab bar is not U-shaped or extending three walls of the shower, and no shower spray unit is provided and the shower head is higher than 48 inches above the finished floor. |
B8 |
6 months |
32-6. e The bench is inaccessible because it is mounted with its surface 20 inches above the finished floor. |
LR1 |
6 months |
33. Dolly Madison Library 1244 Oakridge Avenue McLean, VA 22101 |
|
|
33-1 Parking |
|
|
33-1. a The designated van-accessible space closest to the entrance is inaccessible because the access aisle is 75 inches wide, and the slope and cross slope of the parking space and access aisle exceeds 2%. |
P3 |
6 months |
33-1. b The parking reserved for persons with disabilities is inaccessible because many of the designated accessible spaces and access aisle have slopes and cross slopes that exceed 2%. |
P7 |
6 months |
33-2 Accessible Route |
|
|
33-2. a The curb ramp closest to the meeting room is inaccessible because it has a primary slope of 8.6% and the right flared side slopes 25.4%. |
AR5 |
6 months
|
33-2. b The curb ramp in front of the front entrance is inaccessible because it has a primary slope of 10.1%, a cross slope of 3.8%, the right flared side slopes 24.2%, and the left flared side slopes 11.5%. |
AR5 |
6 months |
33-3 Vestibule inside Front Entrance |
|
|
33-3. a The public pay telephone is inaccessible because the clear floor space is blocked by a cart, the counter height is 41 inches, and the highest operable part is 62 inches above the finished floor. |
TT1 |
6 months |
33-3. b The pamphlet rack is inaccessible because many of the publications are out of reach range. |
LB1 |
6 months |
33-4 Lobby |
|
|
33-4. a The low drinking fountain near the front entrance is inaccessible because the water height is less than 4 inches. |
DF1 |
6 months |
33-4. b Single-User Toilet Room Next to Check-Out Desk |
|
|
33-4. b (1) The toilet room signage is inaccessible because it is mounted on the door. |
TR17 |
6 months |
33-4. b (2) The door is inaccessible because the pressure required to open the door is 6 pounds. |
D2 |
6 months |
33-4. b (3) Although an audible alarm is provided in this facility, there is no visual alarm appliance in the toilet room. |
TR21 |
6 months |
33-4. b (4) No accessible coat hook has been provided. |
TR1 |
6 months |
33-4. b (5) No accessible mirror has been provided. |
TR14 |
6 months |
33-4. b (6) The lavatory hot water and drain pipes are not insulated or otherwise configured to protect against contact. |
TR12 |
6 months |
33-4. b (7) The side grab bar at the toilet is inaccessible because it is mounted with the closer end 13 inches from the rear wall. |
SU6 |
6 months |
33-4. b (8) The rear grab bar is inaccessible because it is mounted with the far end less than 48 inches from the side wall. |
SU2 |
6 months |
33-4. c Library Counters |
|
|
33-4. c (1) The book return counter is inaccessible because it is 38.75 inches above the finished floor. |
LB2 |
6 months |
33-4. c (2) The check-out counter is inaccessible because it is 38.5 inches above the finished floor. |
LB2 |
6 months |
33-5 Exterior Ramp to Meeting Room Entrance |
|
|
33-5. a The ramp is inaccessible because the cross slope of Leg A (at the top of the ramp, next to the parking) is 3.9%, Leg A does not have a level landing at the top, there is inadequate edge protection, and the handrails are not smooth. |
R3 |
6 months |
33-6 Lower Level |
|
|
33-6. a Meeting Room |
|
|
33-6. a (1) The door is inaccessible because the pressure required to open the door is 10 pounds. |
D2 |
6 months |
33-6. a (2) There is no assistive listening system available. |
AA5 |
6 months |
33-6. b Women’s Toilet Room with Stalls near Meeting Room |
|
|
33-6. b (1) The toilet room signage is inaccessible because it is mounted on the door. |
TR17 |
6 months |
33-6. b (2) The door is inaccessible because the pressure required to open the door is 10 pounds. |
D2 |
6 months |
33-6. b (3) Although an audible alarm is provided in this facility, there is no visual alarm appliance in the toilet room. |
TR21 |
6 months |
33-6. b (4) The lavatory is inaccessible because the hot water pipes are not insulated or otherwise configured to protect against contact. |
TR12 |
6 months |
33-6. b (5) The sanitary napkin dispenser protrudes into the walkway and would not be detectable to a blind person using a cane. |
AR8 |
6 months |
33-6. b (6) The sanitary napkin dispenser is inaccessible because it requires tight grasping and twisting of the wrist to operate. |
TR3 |
6 months |
33-6. b (7) The baby changing table is inaccessible because it is mounted with the controls 56.5 inches above the finished floor. |
TR5 |
6 months |
33-6. b (8) No accessible coat hook has been provided. |
TR1 |
6 months |
33-6. b (9) The toilet paper dispenser is inaccessible because it is mounted on the rear wall. |
ST19 |
6 months |
33-6. b (10) The side grab bar at the designated accessible toilet is inaccessible because it is mounted with the far end 50.5 inches from the rear wall. |
ST7 |
6 months |
33-6. b (11) The rear grab bar is inaccessible because it is mounted with the closer end 8.5 inches from the side wall. |
ST4 |
6 months |
33-6. b (12) The toilet is inaccessible because the top of the seat is more than 19 inches above the finished floor. |
ST20 |
6 months |
33-6. c Men’s Toilet Room with Stalls near Meeting Room |
|
|
33-6. c (1) The toilet room signage is inaccessible because it is mounted on the door. |
TR17 |
6 months |
33-6. c (2) The door is inaccessible because the pressure required to open the door is 10 pounds. |
D2 |
6 months |
33-6. c (3) Although an audible alarm is provided in this facility, there is no visual alarm appliance in the toilet room. |
TR21 |
6 months |
33-6. c (4) The lavatory is inaccessible because the hot water pipes are not insulated or otherwise configured to protect against contact. |
TR12 |
6 months |
33-6. c (5) The toilet is inaccessible because the top of the seat is 20 inches above the finished floor. |
ST20 |
6 months |
33-6. c (6) The toilet is inaccessible because its centerline is 17 inches from the side wall. |
ST17 |
6 months |
33-6. c (7) No accessible coat hook has been provided. |
TR1 |
6 months |
33-6. c (8) The toilet paper dispenser is inaccessible because it is mounted on the rear wall. |
ST19 |
6 months |
33-6. c (9) The side grab bar at the designated accessible toilet is inaccessible because it is mounted with the far end 50.5 inches from the rear wall. |
ST7 |
6 months |
33-6. c (10) The rear grab bar is inaccessible because it is mounted with the closer end 7 inches from the side wall. |
ST4 |
6 months |
33-6. d Hallway |
|
|
33-6. d (1) The coat rack near the women’s toilet room protrudes into the walkway and would not be detectable to a blind person using a cane. |
AR8 |
6 months |
33-6. d (2) The low wall-mounted drinking fountain on the lower level next to the toilet room is inaccessible because the knee space height between the bottom of the apron and the finished floor is 25.75 inches. |
DF5 |
6 months |
34. McLean Government Center 1437 Balls Hill Road McLean, VA 22101 |
|
|
34-1 Parking |
|
|
34-1. a The parking reserved for persons with disabilities is inaccessible because the designated accessible parking spaces and access aisles have slopes and cross slopes greater than 2%. |
P7 |
6 months |
34-1. b The standard accessible parking space on the side of the building closest to the curb is inaccessible because it is 92 inches wide. |
P3 |
6 months |
34-2 Accessible Routes to Front Entrance |
|
|
34-2. a The route from the front parking lot to the entrance of the facility is inaccessible because the slope of the primary curb ramp is 10.1%, the slope of the left flared side is 17.6%, and the slope of the right flared side is 19.1%. |
AR5 |
6 months |
34-2. b The route from the side parking lot to the entrance of the facility is inaccessible because the surface of the route has a cross slope of 5.6%. |
AR1 |
6 months |
34-2. c The route from the side parking lot to the entrance of the facility is inaccessible because the lip on the curb ramp slopes 18.9%. |
AR5 |
6 months |
34-2. d The ramp to the front entrance is inaccessible because there is no level landing at the bottom, no level landing at the top, and the handrails are mounted 33 inches above the ramp surface, and 3 inches from the wall. |
R5 |
6 months |
34-3 Lobby |
|
|
34-3. a The police counter is inaccessible because it is 42 inches above the finished floor. |
C6 |
6 months |
34-3. b The defibrillator on the wall opposite from the police counter protrudes into the walkway and would not be detectable to a blind person using a cane. |
AR8 |
6 months |
34-4 Interview Rooms 1 and 2 |
|
|
34-4. a The doors to the interview rooms are inaccessible because they have knob hardware. |
D1 |
6 months |
34-5 Supervisor’s Office for Dransville District |
|
|
34-5. a The push side of the door to the supervisor’s office, which is accessed through a front approach and which has both a closer and a latch, is inaccessible because it has inadequate space on the latch side of the door due to the location of furniture and a magazine rack. |
D7 |
6 months |
34-6 Visitors Center and Chamber of Commerce |
|
|
34-6. a The door to the visitor’s center and chamber of commerce is inaccessible because the pressure required to open the door is 6 pounds. |
D2 |
6 months |
34-6. b The pull side of the door, which is accessed through a front approach, is inaccessible because it has only 11.5 inches of maneuvering space on the latch side of the door. |
D6 |
6 months |
34-7 Community Room |
|
|
34-7. a The pull side of the door, which is accessed through a front approach, is inaccessible because it has only 12 inches of maneuvering space on the latch side of the door. |
D6 |
6 months
|
34-8 Drinking Fountain in Hallway near Toilet Rooms and Lobby |
|
|
34-8. a The high drinking fountain protrudes into the walkway and would not be detectable to a blind person using a cane. |
AR8 |
6 months |
34-9 Women’s Toilet Room with Stalls |
|
|
34-9. a The toilet room signage is inaccessible because it lacks the International Symbol of Accessibility. |
TR17 |
6 months |
34-9. b The door is inaccessible because the pressure required to open the door is 10 pounds. |
D2 |
6 months |
34-9. c The push side of the door, which is accessed through a front approach and which has both a closer and a latch, is inaccessible because it has only 4.75 inches of maneuvering space on the latch side of the door. |
D7 |
6 months |
34-9. d Although an audible alarm is provided in this facility, there is no visual alarm appliance in the toilet room. |
TR21 |
6 months |
34-9. e No accessible coat hook has been provided. |
TR1 |
6 months |
34-9. f The side grab bar at the designated accessible toilet is inaccessible because it is mounted with the far end 50 inches from the rear wall. |
ST7 |
6 months |
34-10 Men’s Toilet Room with Stalls |
|
|
34-10. a The toilet room signage is inaccessible because it is not mounted on the latch side of the door and lacks the International Symbol of Accessibility. |
TR17 |
6 months |
34-10. b The door is inaccessible because the pressure required to open the door is 10 pounds. |
D2 |
6 months |
34-10. c The push side of the door, which is accessed through a front approach and which has both a closer and a latch, is inaccessible because it has only 3.75 inches of maneuvering space on the latch side of the door. |
D7 |
6 months |
34-10. d Although an audible alarm is provided in this facility, there is no visual alarm appliance in the toilet room. |
TR21 |
6 months |
34-10. e No accessible coat hook has been provided. |
TR1 |
6 months |
34-10. f The side grab bar at the designated accessible toilet is inaccessible because it is mounted with the far end 51 inches from the rear wall. |
ST7 |
6 months |
35. Oak Marr Recreation Center 3200 Jermantown Road Oakton, VA 22124 |
|
|
35-1 Parking |
|
|
35-1. a The parking reserved for people with disabilities is inaccessible because four of the designated spaces and access aisles have slopes and cross slopes of 3%. |
P7 |
6 months |
35-2 Second Floor Lobby Counter |
|
|
35-2. a The lower counter protrudes into the walkway and is not detectable to blind persons using a cane. |
AR8 |
6 months |
35-3 Drinking Fountain between Toilet Rooms |
|
|
35-3. a Although an accessible drinking fountain is provided, there is no drinking fountain provided for people who have difficulty bending or stooping. |
DF3 |
6 months |
35-4 Women’s Toilet Room with Stalls |
|
|
35-4. a (1) The route to the paper towels is inaccessible because it is obstructed by the wall and it is only 24 inches wide. |
AR3 |
6 months |
35-4. a (2) The lavatory is inaccessible because the hot water pipes are not insulated or otherwise configured to protect against contact. |
TR12 |
6 months |
35-4. a (3) The designated accessible stall is not accessible because it is 53 inches wide. |
ST16 |
6 months |
35-4. a (4) No accessible coat hook has been provided. |
TR1 |
6 months |
35-4. a (5) The side grab bar at the designated accessible toilet is inaccessible because its farthest end is 51 inches from the rear wall. |
ST6 |
6 months |
35-4. b Men’s Toilet Room with Stalls |
|
|
35-4. b (1) The lavatory is inaccessible because the rim or counter is 26 inches to the bottom. |
TR11 |
6 months |
35-4. b (2) The lavatory is inaccessible because the hot water pipes are not insulated or otherwise configured to protect against contact. |
TR12 |
6 months |
35-4. b (3) The urinal is inaccessible because the rim is 24 inches above the finished floor. |
TR20 |
6 months |
35-4. b (4) The designated accessible stall is not accessible because it is 53 inches wide. |
ST16 |
6 months |
35-4. b (5) The designated accessible toilet is inaccessible because its centerline is 19 inches from the side wall. |
ST17 |
6 months |
35-4. b (6) No accessible coat hook has been provided. |
TR1 |
6 months |
35-5 Elevator |
|
|
35-5. a The elevator is inaccessible because the hoistway signage does not have raised and Braille characters. |
E12 |
6 months |
35-5. b The elevator is inaccessible because the car control buttons do not have raised and Braille characters, and the call button for the main entry floor is not designated by a raised star. |
E4 |
6 months |
35-5. c The elevator is inaccessible because the emergency system requires voice communication to operate. |
E8 |
6 months |
35-6 First Floor (Lower Level) |
|
|
35-6. a Women’s Locker Room near Pool |
|
|
35-6. a (1) No accessible mirror has been provided. |
TR14 |
6 months |
35-6. a (2) The lavatory is inaccessible because the hot water pipes are not insulated or otherwise configured to protect against contact. |
TR12 |
6 months |
35-6. a (3) Although there are seven stalls, there is no ambulatory stall provided. |
ST1 |
6 months |
35-6. a (4) The designated accessible stall is not accessible because it is 54 inches wide. |
ST16 |
6 months |
35-6. a (5) The designated accessible toilet is inaccessible because its centerline is 23 inches from the side wall. |
ST17 |
6 months |
35-6. a (6) No accessible coat hook has been provided. |
TR1 |
6 months |
35-6. a (7) The side grab bar at the designated accessible toilet is inaccessible because its farthest end is 51 inches from the rear wall. |
ST6 |
6 months |
35-6. a (8) The rear grab bar at the designated accessible toilet is inaccessible because it is mounted more than 6 inches from the side wall. |
ST3 |
6 months |
35-6. a (9) Roll-In Shower Stall |
|
|
35-6. a (9)(a) The designated accessible roll-in shower stall is inaccessible because the seat does not fold, the grab bars are not U-shaped, the shower controls are mounted at 52 inches above the finished floor, and the shower unit head is 70 inches above the finished floor, not mounted on a vertical bar and useable as handheld. |
B8 |
6 months |
35-6. a (10) Locker Area |
|
|
35-6. a (10)(a) The bench in the dressing room is inaccessible because it is 20 inches wide and 21 inches above the finished floor. |
LR1 |
6 months |
35-6. a (10)(b) The benches at the lockers are inaccessible because they are not attached to the wall. |
LR1 |
6 months |
35-6. a (10)(c) There is no accessible locker provided. |
LR3 |
6 months |
35-6. a (10)(d) The shelves protrude into the walkway and are not detectable to blind persons using a cane. |
AR8 |
6 months |
35-6. a (10)(e) The diaper changing table protrudes into the walkway and is not detectable to blind persons using a cane and it is inaccessible because it is mounted with the operating mechanism at 60 inches above the finished floor. |
AR8 TR5 |
6 months |
35-6. b Men’s Locker Room near Pool |
|
|
35-6. b (1) No accessible mirror has been provided. |
TR14 |
6 months |
35-6. b (2) The lavatory is inaccessible because the hot water pipes are not insulated or otherwise configured to protect against contact. |
TR12 |
6 months |
35-6. b (3) No accessible coat hook has been provided. |
TR1 |
6 months |
35-6. b (4) The designated accessible stall is not accessible because it is 54 inches wide. |
ST16 |
6 months |
35-6. b (5) The side grab bar at the designated accessible toilet is inaccessible because its farthest end is less than 52 inches from the rear wall. |
ST6 |
6 months |
35-6. b (6) Roll-In Shower Stall |
|
|
35-6. b (6)(a) The designated accessible roll-in shower stall is inaccessible because the seat does not fold, the grab bars are not U-shaped, the controls are not useable with one hand, and the shower unit head is not mounted on a vertical bar and useable as handheld. |
B8 |
6 months |
35-6. b (7) Locker Area |
|
|
35-6. b (7)(a) The bench in the dressing room is inaccessible because it is 20 inches wide and 21 inches above the finished floor. |
LR1 |
6 months |
35-6. b (7)(b) The benches at the lockers are inaccessible because they are not attached to the wall. |
LR1 |
6 months |
35-6. b (7)(c) There is no accessible locker provided. |
LR3 |
6 months |
35-6. b (7)(d) The shelves protrude into the walkway and are not detectable to blind persons using a cane. |
AR8 |
6 months |
35-7 Family Single User Changing Room |
|
|
35-7. a The air dryer protrudes into the walkway and is not detectable to blind persons using a cane. |
AR8 |
6 months |
35-7. b The side grab bar at the designated accessible toilet is inaccessible because it is mounted with its farthest end less than 52 inches from the rear wall and is less than 42 inches in length. |
SU5 |
6 months |
35-7. c The toilet is inaccessible because there is no rear grab bar provided |
SU2 |
6 months |
35-7. d Shower Stall |
|
|
35-7. d (1) The designated accessible shower stall is inaccessible because the seat does not fold, the grab bars are not U-shaped, the controls require twisting of the wrist and are too high, and the shower unit head is not mounted on a vertical bar and useable as handheld. |
B8 |
6 months |
35-7. d (2) There is no accessible locker provided. |
LR3 |
6 months |
35-7. d (3) The bench is inaccessible because it is 20 inches wide and 21 inches above the finished floor. |
LR1 |
6 months |
35-8 Pool Area |
|
|
35-8. a Jacuzzi |
|
|
35-8. a (1) The jacuzzi is not accessible because there are three steps leading up to it. |
AR2 |
6 months |
35-9 Racquetball Courts (2) |
|
|
35-9. a Door to Court on Right |
|
|
35-9. a (1) The door to the court is inaccessible because the door hardware requires tight grasping, pinching or twisting of the wrist to operate |
D1 |
6 months |
35-9. b Door to Court on Left |
|
|
35-9. b (1) The door to the court is inaccessible because the door hardware requires tight grasping, pinching or twisting of the wrist to operate |
D1 |
6 months |
35-9. b (2) The door to the court is inaccessible because there is a threshold higher than .5 inch and it is not beveled. |
D23 |
6 months |
35-10 Drinking Fountain near Racquetball Court |
|
|
35-10. a Although an accessible drinking fountain is provided, there is no drinking fountain provided for people who have difficulty bending or stooping. |
DF3 |
6 months |
35-10. b The built-in drinking fountain is inaccessible because there is a 1 inch change in level immediately outside the required clear floor space. |
AR2 |
6 months |
35-11 Oak Marr Mini-Golf Course (New) |
|
|
35-11. a Check-in Booth |
|
|
35-11. a (1) The counter is inaccessible because it is 39 inches above the finished floor. |
C6 |
6 months |
35-12 Oak Marr Golf Complex (New) |
|
|
35-12. a Parking |
|
|
35-12. a (1) Although the parking lot has a total of 206 parking spaces, an inadequate number are designated as reserved for people with disabilities and the pavement markings are not clear. |
P3 |
6 months |
35-12. b Accessible Route |
|
|
35-12. b (1) The route from the parking lot to the golf center entrance is inaccessible because the cross slope of the sidewalk in front of the designated accessible parking area slopes up to 6.4% (because of the location of the curb ramp). |
AR1 |
6 months |
35-12. c Drinking Fountain by Toilet Rooms |
|
|
35-12. c (1) The wall-mounted drinking fountain is inaccessible because the knee clearance height is 26 inches. |
DF5 |
6 months |
35-12. d Toilet Rooms by Front Entrance |
|
|
35-12. d (1) Women’s Room with Stalls |
|
|
35-12. d (1)(a) The toilet room sign is inaccessible because it is mounted on the door with a centerline of 57 inches above the finished floor. |
TR18 |
6 months |
35-12. d (1)(b) The toilet room door is inaccessible because the pressure required to open the door is 8 pounds. |
D2 |
6 months |
35-12. d (1)(c) Although an audible alarm is provided in this facility, there is no visual alarm appliance in the toilet room. |
TR21 |
6 months |
35-12. d (2) Men’s Room with Stalls |
|
|
35-12. d (2)(a) The toilet room sign is inaccessible because it is mounted on the door with a centerline of 57 inches above the finished floor. |
TR18 |
6 months |
35-12. d (2)(b) Although an audible alarm is provided in this facility, there is no visual alarm appliance in the toilet room. |
TR21 |
6 months |
35-12. d (2)(c) The lavatory is inaccessible because the hot water pipes are not insulated or otherwise configured to protect against contact. |
TR12 |
6 months |
35-12. d (2)(d) The toilet is inaccessible because its centerline measures 19 inches from the side wall. |
ST17 |
6 months |
35-12. e Public Pay Telephone Near Rear Entrance |
|
|
35-12. e (1) The telephone is inaccessible because the highest operable part is 55 inches above the finished floor. |
TT1 |
6 months |
35-12. f Golf Driving Range |
|
|
35-12. f (1) The tables by the rear entrance are inaccessible because none provide the required knee space. |
PD6 |
6 months |
35-12. f (2) The driving range in inaccessible because there is no accessible route to the upper deck. |
AR1, AR6, FFX1 |
6 months |
35-12. g Accessible Route From Driving Range to Golf School |
|
|
35-12. g (1) The ramp to the golf school trailer is inaccessible because it has large, square wooden handrails. |
R4 |
6 months |
35-12. h Exterior Entrance to Golf School |
|
|
35-12. h (1) The entrance door is inaccessible because there is a 2-inch change in level at the threshold to the door. |
D22 |
12 months |
36. Lake Fairfax Park 1400 Lake Fairfax Drive Reston, VA 20190 |
|
|
36-1 Parking near Administration Office, Marina, and Water Park |
|
|
36-1. a The parking designated for people with disabilities is inaccessible because there is no designated van accessible parking. |
P3 |
6 months |
36-1. b The parking reserved for people with disabilities is inaccessible because two of the designated accessible parking spaces slope up to 4.5%. |
P7 |
6 months |
36-2 Administration Office, Marina, Water Park, Picnic Pavilion, Toilet Rooms, and Carousel |
|
|
36-2. a Route to Carousel |
|
|
36-2. a (1) The route to the carousel is inaccessible because it is not stable, firm, and slip resistant, and there is a 5-inch change in level. |
AR1 |
6 months |
36-2. b Men’s and Women’s Toilet Rooms with Stalls (behind Office) |
|
|
36-2. b (1) The men’s and women’s toilet rooms contain a number of inaccessible elements and are not accessible to people with disabilities. |
TR22 |
6 months |
36-2. c Drinking Fountain near Toilet Rooms |
|
|
36-2. c (1) Although a designated accessible drinking fountain is provided, there is no drinking fountain provided for people who have difficulty bending or stooping. |
DF3 |
6 months |
36-2. d Route to Trail Head and Marina |
|
|
36-2. d (1) Ramp to Marina |
|
|
36-2. d (1)(a) The ramp is inaccessible because the handrails do not run the full length of the ramp, and do not extend 12 inches in length at the top and bottom. |
R3 |
6 months |
36-2. e Administration Office |
|
|
36-2. e (1) The door to the administration office is inaccessible because knob hardware is used and there is a 1-inch high threshold. |
D1, D23 |
6 months |
36-3 Water Park Admission Booth (New) |
|
|
36-3. a (1) The admission booth counter is inaccessible because it is 36.5 inches above the finished floor. |
C5 |
6 months |
36-4 Men’s Locker Room (New) |
|
|
36-4. a There is no signage for the men’s locker room. |
TR17 |
6 months |
36-4. b The locker room is inaccessible if there is no visual alarm. |
AL1 |
6 months |
36-4. c The lavatory is inaccessible because the hot water pipes are not fully insulated or otherwise configured to protect against contact and the bottom edge of the apron is 25.75 inches above the finished floor. |
TR12, TR11 |
6 months |
36-4. d No accessible coat hook has been provided. |
TR1 |
6 months |
36-4. e The toilet paper dispenser in the designated standard accessible stall is inaccessible because it is mounted above the grab bar. |
ST19 |
6 months |
36-4. f The ambulatory stall is inaccessible because there are no grab bars provided and the coat hook is 66 inches above the finished floor. |
ST1 TR1 |
6 months |
36-4. g Shower Stall |
|
|
36-4. g (1) The shower stall is inaccessible because the diversion control is at 52 inches above the finished floor, the shower head is not on a vertical bar and adjustable, and the shower hose is not 60 inches long. |
B8 |
6 months |
36-4. h No accessible mirror has been provided. |
TR14 |
6 months |
36-5 Women’s Locker Room (New) |
|
|
36-5. a There is no signage for the women’s locker room. |
TR17 |
6 months |
36-5. b The door to the women’s locker room is inaccessible because there is a .5 inch threshold that is not beveled. |
D23 |
6 months |
36-5. c The locker room is inaccessible if there is no visual alarm. |
AL1 |
6 months |
36-5. d The lavatory is inaccessible because the hot water pipes are not fully insulated or otherwise configured to protect against contact |
TR12 |
6 months |
36-5. e No accessible coat hook has been provided. |
TR1 |
6 months |
36-5. f The toilet paper dispenser in the designated accessible stall is inaccessible because it is mounted above the grab bar. |
ST19 |
6 months |
36-5. g The ambulatory stall is inaccessible because there are no grab bars provided and the coat hook is 66 inches above the finished floor. |
ST1 TR1 |
6 months |
36-5. h The coat hooks on the route to shower are inaccessible because they are too high. |
TR1 |
6 months |
36-5. i Shower Stall |
|
|
36-5. i (1) The shower stall is inaccessible because the diversion control is at 52 inches above the finished floor, the controls are not located within 27 inches of the side wall near the seat, the shower head is not on a vertical bar and adjustable, and the shower hose is not 60 inches long. |
B8 |
6 months |
36-5. j No accessible mirror has been provided. |
TR14 |
6 months |
36-6 Unisex Changing Room (New) |
|
|
36-6. a The signage provided is inaccessible because the centerline is 64 inches above the finished floor and it does not have raised and Braille characters. |
TR17 |
6 months |
36-6. b The family locker room is inaccessible if there is no visual alarm. |
AL1 |
6 months |
36-6. c The side grab bar at the toilet is inaccessible because it is obstructed by the sanitary napkin disposal |
SU8 |
6 months |
36-6. d The toilet paper dispenser is inaccessible because it is mounted above the grab bar. |
SU17 |
6 months |
36-7 Route from Unisex Changing Room to Pool Area (New) |
|
|
36-7. a The lockers on the route to the pool are not accessible. |
LR3 |
6 months |
36-8 Toilet Rooms with Stalls adjacent to Picnic Area B |
|
|
36-8. a The route to the toilet rooms is inaccessible because it is not stable, firm and slip resistant. |
AR1 |
84 months |
36-8. b The men’s and women’s toilet rooms contain a number of inaccessible elements and are not accessible to people with disabilities. |
TR22 |
84 months |
36-9 Campgrounds A and C |
|
|
36-9. a Bathhouses including Toilet Rooms with Stalls |
|
|
36-9. a (1) The route to the toilet rooms is inaccessible because it is not stable, firm and slip resistant. |
AR1 |
84 months |
36-9. a (2) The men’s and women’s toilet rooms contain a number of inaccessible elements and are not accessible to people with disabilities. |
TR22 |
84 months |
36-10 Amphitheater |
|
|
36-10. a The route to the amphitheater rooms is inaccessible because it is not stable, firm and slip resistant. |
AR1 |
6 months |
36-11 Parking Lot for Athletic Field |
|
|
36-11. a The parking lot, with a total of 160 spaces, is inaccessible because it only has 4 spaces designated as accessible, none of which are van accessible. |
P3 |
6 months |
36-12 Route from Parking to Port-a-John and Athletic Fields |
|
|
36-12. a The route to the portable toilets and athletic fields is inaccessible because it is not stable, firm and slip resistant. |
AR1 |
6 months |
36-13 Picnic Area B Playground |
|
|
36-13. a Parking, Route and Playground Play Area |
|
|
36-13. a (1) All areas are inaccessible because dirt, gravel and mulch are not stable, firm and slip resistant. |
AR1 |
6 months |
36-14 Portable Toilets |
|
|
36-14. a The portable toilets are inaccessible because the door threshold is more than .5 inch and not beveled, and the side grab bar is too short. |
D23, SU6 |
6 months |
37. North County Government Center 12000 Bowman Towne Center Reston, VA 20190 |
|
|
37-1 Building Signage |
|
|
37-1. a The permanent accessible signage throughout the building is inaccessible because it is not mounted on the latch side of the door. |
D26 |
6 months |
37-2 Public Telephone |
|
|
37-2. a The telephone is inaccessible because it is 55 inches to the highest operable part. |
TT1 |
6 months |
37-3 Main Office |
|
|
37-3. a The door to the main office is inaccessible because it requires 15 pounds of force to open. |
D2 |
6 months |
37-4 Conference Room |
|
|
37-4. a The door to the conference room is inaccessible because the door hardware requires tight grasping, pinching, or twisting of the wrist. |
D1 |
6 months |
37-5 Community Room |
|
|
37-5. a The door to the community room is inaccessible because it requires 14 pounds of force to open. |
D2 |
6 months |
37-5. b The door to the community room is inaccessible because the door hardware requires tight grasping, pinching, or twisting of the wrist to operate. |
D1 |
6 months |
37-6 Women’s Toilet Room with Stalls |
|
|
37-6. a The door to the women’s toilet room is inaccessible because it requires 18 pounds of force to open. |
D2 |
6 months |
37-6. b The designated accessible stall toilet is inaccessible because its centerline is 20 inches from the side wall. |
ST17 |
6 months |
37-6. c No accessible coat hook has been provided. |
TR1 |
6 months |
37-7 Men’s Toilet Room with Stalls |
|
|
37-7. a The door to the men’s toilet room is inaccessible because it requires 15 pounds of force to open |
D2 |
6 months |
37-7. b No accessible coat hook has been provided. |
TR1 |
6 months |
38. Reston Regional Library 11925 Bowman Towne Drive Reston, VA 20190 |
|
|
38-1 Route to Entrance |
|
|
38-1. a The route from the designated accessible parking to the entrance is inaccessible because it has a slope of up to 6.1% and has not been constructed as a fully accessible route. |
AR1 R4 |
6 months |
38-2 Women’s Toilet Room with Stalls near Lobby |
|
|
38-2. a The signage provided is inaccessible because it is mounted on the door. |
TR17 |
6 months |
38-2. b The stall door is inaccessible because the operating mechanism requires tight grasping, pinching, and twisting of the wrist to operate. |
D1 |
6 months |
38-2. c The designated accessible toilet is inaccessible because the flush control is on the closed side. |
ST2 |
6 months |
38-2. d The toilet stall door swings into the required clear floor space at the lavatory. |
TR6 |
6 months |
38-2. e The toilet paper dispenser in the designated accessible stall is inaccessible because it is mounted above the grab bar. |
ST19 |
6 months |
38-2. f No accessible coat hook has been provided. |
TR1 |
6 months |
38-3 Men’s Toilet Room with Stalls near Lobby |
|
|
38-3. a The signage provided is inaccessible because it is mounted on the door. |
TR17 |
6 months |
38-3. b The paper towel dispenser is inaccessible because it is mounted with the controls at 55 inches above the finished floor. |
TR5 |
6 months |
38-3. c The lavatory is inaccessible because it has twist-type hardware. |
TR10 |
6 months |
38-3. d The urinal is inaccessible because the rim is 21 inches above the finished floor, the clear floor space is 25 inches wide, and the flush control is 50 inches above the finished floor. |
TR20 |
6 months |
38-3. e The toilet paper dispenser in the designated accessible stall is inaccessible because it is mounted above the grab bar. |
ST19 |
6 months |
38-3. f No accessible coat hook has been provided. |
TR1 |
6 months |
38-4 Multi-purpose Room #2 |
|
|
38-4. a An assistive listening system is not provided. |
AA5 |
6 months |
38-4. b The signage provided is inaccessible because it does not have raised and Braille characters. |
D26 |
6 months |
38-5 Multi-purpose Room #1 |
|
|
38-5. a The signage provided is inaccessible because it does not have raised and Braille characters. |
D26 |
6 months |
38-5. b An assistive listening system is not provided. |
AA5 |
6 months |
38-6 Telephones (2) near Toilet Rooms |
|
|
38-6. a The lower unit telephone is inaccessible because the knee clearance is 21 inches above the finished floor. |
TT1 |
6 months |
39. Lake Accotink Park 7500 Accotink Park Road Springfield, VA 22150 |
|
|
39-1 Park Office/Visitor’s Center |
|
|
39-1. a Parking Lot |
|
|
39-1. a (1) The parking reserved for persons with disabilities is inaccessible because the van accessible parking space has a slope of 3.4% and a cross slope of 4%, the access aisle for the van accessible parking space has a slope of 3.9% and a cross slope of 4.3%. |
P7 |
6 months |
39-1. b Exterior Entrance |
|
|
39-1. b (1) The push side of the door to the entrance, which is accessed through a front approach and which has both a closer and a latch, is inaccessible because it has only 7 inches of maneuvering clearance on the latch side of the door. |
D7 |
6 months |
39-1. c Lobby Area |
|
|
39-1. c (1) The lobby area is inaccessible because the route between the display case and counter narrows to 34 inches. |
AR2 |
6 months |
39-1. d Women’s Toilet Room with Stalls |
|
|
39-1. d (1) The toilet room signage is inaccessible because it is mounted on the door at 58 inches above the finished floor to the centerline. |
TR17 |
6 months |
39-1. d (2) The door to the toilet room is inaccessible because the pressure required to open the door is 8 pounds. |
D2 |
6 months
|
39-1. d (3) The toilet is inaccessible because the top of the seat is 15.5 inches above the finished floor. |
ST20 |
6 months |
39-1. d (4) The side grab bar is inaccessible because the grab bar is mounted 36.5 inches above the finished floor and the far end is mounted 48 inches from the rear wall. |
ST6 |
6 months |
39-1. e Men’s Toilet Room with Stalls |
|
|
39-1. e (1) The toilet room signage is inaccessible because it is mounted on the door. |
TR17 |
6 months |
39-1. e (2) The door to the toilet room is inaccessible because the pressure required to open the door is 8 pounds. |
D2 |
6 months |
39-1. e (3) The lavatory has 27.5 inches of clear floor space width. |
TR8 |
6 months |
39-1. e (4) The side grab bar is inaccessible because the grab bar is mounted 36.5 inches above the finished floor, the far end is mounted 48 inches from the rear wall, and the magazines interfere with use of the grab bar. |
ST6 |
6 months |
39-1. e (5) The toilet flush control is inaccessible because it is on the closed side. |
ST2 |
6 months |
39-2 Parking Lot near Train Trestle |
|
|
39-2. a The parking reserved for persons with disabilities is inaccessible because it lacks appropriate signage. |
P6 |
6 months |
39-2. b The parking lot is inaccessible because the access aisle is too narrow. |
P1 |
6 months |
39-2. c Although the parking lot has a total of 194 parking spaces, an inadequate number are designated as reserved for people with disabilities and the pavement markings are not clear near the accessible fishing pier. |
P3 |
6 months |
39-3 Picnic Table near Route to Accessible Fishing Pier |
|
|
39-3. a The picnic table near the route from the accessible parking to the fishing pier is inaccessible because the path to it is not stable, firm, and slip resistant. |
AR1 |
6 months |
39-4 Accessible Fishing Pier |
|
|
39-4. a The fishing pier is inaccessible because it does not have adequate edge protection. |
R1 |
6 months |
39-5 Parking Lot next to Marina |
|
|
39-5. a The designated accessible space next to the camp office lacks appropriate signage. |
P6 |
6 months |
39-5. b The designated accessible space next to the camp office is inaccessible because it has a slope of 2.7% and a cross slope of 2.3%, and its access aisles are not level. |
P7 |
6 months |
39-6 Accessible Route to Camp Office |
|
|
39-6. a The route from the parking lot to the camp office is inaccessible because the route in front of the entrance slopes 6.3%. |
AR1 |
6 months |
39-7 Entrance to Camp Office |
|
|
39-7. a The entrance to the camp office is inaccessible because there is a 6 inch change in level at the threshold to the door. |
D23 |
6 months |
39-7. b The entrance to the camp office is inaccessible because it has knob hardware. |
D1 |
6 months |
39-7. c The building does not have directional signage posted at inaccessible entrances and does not have the International Symbol of Accessibility posted at accessible entrances. |
D16 |
6 months |
39-8 Parking Area for Snack Bar |
|
|
39-8. a The curb ramp serving the designated accessible parking spaces across from the snack bar is inaccessible because it has a primary slope of 12.5%. |
AR5 |
6 months |
39-8. b The designated accessible parking space next to the curb is inaccessible because it is 87 inches wide. |
P8 |
6 months |
39-9 Accessible Route to Small Picnic Shelter |
|
|
39-9. a The route from the parking lot to the small picnic shelter is inaccessible because the vehicles parked in the parking spaces closest to the shelter overhang into the route and encroach on the width of the route so it is less than 36 inches wide. |
AR1 |
6 months |
39-9. b The route from the parking lot to the small picnic shelter is inaccessible because the route slopes up to 8.3%. |
AR1 |
6 months |
39-10 Accessible Route to Snack Bar |
|
|
39-10. a The route to the snack bar is inaccessible because the route slopes up to 6%. |
AR1 |
6 months |
39-11 Snack Bar Area |
|
|
39-11. a Drinking Fountain |
|
|
39-11. a (1) There is no accessible drinking fountain because it requires 15 pounds of force to operate, there is 25.5 inches of knee space between the bottom of the apron and the ground, and there is no drinking fountain provided for people who have difficulty bending or stooping. |
DF1 |
6 months |
39-11. b Public Pay Telephone near Snack Bar |
|
|
39-11. b (1) The telephone protrudes into the walkway and would not be detectable to a blind person using a cane. |
AR8 |
6 months |
39-12 Ramp in Front of the Snack Bar |
|
|
39-12. a The ramp is inaccessible because the top landing slopes up to 4.3%, the bottom landing has a cross slope of 2.8%, the ramp lacks handrail extensions on one side and the distance from the inside railing to the wall is 2.25 inches. |
R5 |
6 months |
39-13 Single User Toilet Room at Ticket Booth Building |
|
|
39-13. a The lavatory rim is 35.5 inches above the finished floor. |
TR11 |
6 months |
39-13. b The soap dispenser is inaccessible because it is mounted 51 inches above the finished floor over an obstruction. |
TR4 |
6 months |
39-13. c The operating mechanism for the door is inaccessible because the lock mechanism requires twisting. |
D1 |
6 months |
39-14 Drinking Fountain on Side of the Ticket Booth Building |
|
|
39-14. a The drinking fountain protrudes into the walkway and would not be detectable to a blind person using a cane. |
AR8 |
6 months |
39-14. b The drinking fountain is inaccessible because it requires 9pounds of force to operate. |
DF2 |
6 months |
39-14. c Although a low drinking fountain is provided, there is no drinking fountain provided for people who have difficulty bending or stooping. |
DF3 |
6 months |
39-15 Accessible Route to Playground Area |
|
|
39-15. a The route to the playground area is inaccessible because it is not stable, firm and slip resistant. |
AR1 |
6 months |
39-16 Accessible Route to Picnic Area |
|
|
39-16. a The route to the picnic area is inaccessible because it is located on the slope of a hill. |
AR1 |
6 months |
39-17 Large Picnic Shelter Overlooking the Lake |
|
|
39-17. a There is no accessible route to the large picnic shelter. |
AR1 |
84 months |
39-17. b Women’s Toilet Room with Stalls adjoined to the Large Picnic Shelter |
|
|
39-17. b (1) The toilet room contains a number of inaccessible elements and is not accessible to people with disabilities. |
ST14 |
84 months |
39-17. c Men’s Toilet Room with Stalls adjoined to the Large Picnic Shelter |
|
|
39-17. c (1) The toilet room contains a number of inaccessible elements and is not accessible to people with disabilities. |
ST14 |
84 months |
39-18 Accessible Route from the Parking Lot to Large Picnic Shelter using Stairs |
|
|
39-18. a The stairs are inaccessible because handrails are not provided on the stairs near the toilet area. |
AR10 |
84 months |
39-19 (New Construction) |
|
|
39-19. a Parking next to McLaren-Sargent Shelter |
|
|
39-19. a (1) There is no van accessible parking space reserved for persons with disabilities in the small parking lot adjacent to the shelter. |
P3 |
6 months |
39-19. a (2) The parking reserved for persons with disabilities is inaccessible because the cross slope of the parking space closest to the shelter is 3.7% and the cross slope of the shared access aisle is 5.4%. |
P7 |
6 months |
39-19. a (3) The designated accessible parking space farthest from the McLaren-Sargent Shelter is inaccessible because it is 88 inches wide. |
P8 |
6 months |
39-19. b Lower Main Parking Lot |
|
|
39-19. b (1) The access aisle is inaccessible because a wheel stop blocks the access aisle. |
P8 |
6 months |
39-19. c McLaren-Sargent Shelter |
|
|
39-19. c (1) Drinking Fountain |
|
|
39-19. c (1)(a) The drinking fountain is inaccessible because it requires 6 pounds of force to operate. |
DF2 |
6 months |
39-19. c (1)(b) Although a lower drinking fountain is provided, there is no drinking fountain provided for people who have difficulty bending or stooping. |
DF3 |
6 months |
39-19. c (1)(c) The drinking fountain protrudes into the walkway and would not be detectable to a blind person using a cane. |
AR8 |
6 months |
39-19. d Accessible Routes to Amenities from Shelter |
|
|
39-19. d (1) The route from the shelter to the volleyball and basketball courts is inaccessible because it slopes up to 6.5% in one area, has a cross slope of up to 5.8% in one area, is blocked by a large stone, and is not stable, firm, and slip-resistant. |
AR1 |
6 months |
39-19. d (2) The route from the shelter to the soccer field, bleachers, and picnic table is inaccessible because it is not stable, firm, and slip-resistant. |
AR1 |
6 months |
40. South Run Recreation Center 7550 Reservation Dr. Springfield, VA 22153 |
|
|
40-1 Front Parking Lot |
|
|
40-1. a The parking lot, with a total of 167 parking spaces, is inaccessible because only 5 of the designated accessible parking spaces reserved for persons with disabilities have access aisles, and the slopes of those parking spaces and access aisles exceed 2%. |
P3 |
6 months |
40-1. b The parking lot is inaccessible because the designated temporary accessible spaces do not have access aisles. |
P1 |
6 months |
40-2 Accessible Route from Van Spaces to Front Entrance |
|
|
40-2. a The route from the designated van-accessible parking spaces to the front entrance of the facility is inaccessible because the curb ramp on the parking lot side has a primary slope of 12.1% and a 11.6% slope at the gutter. |
AR5 |
6 months |
40-2. b The route on the walkway to the front entrance of the facility is inaccessible because the slope in front of the entry doors is 6.4%. |
AR1 |
6 months |
40-3 Multi-purpose Room #2 |
|
|
40-3. a The door is inaccessible because the pressure required to open the door is 10 pounds. |
D2 |
6 months |
40-4 Classroom |
|
|
40-4. a The door to the classroom located at the end of the hall is inaccessible because the pressure required to open the door is 11 pounds. |
D2 |
6 months |
40-5 Pool Balcony |
|
|
40-5. a The door is inaccessible because the pressure required to open the door is 6 pounds. |
D2 |
6 months |
40-5. b The pool balcony is inaccessible because the clear floor space from the top of the bleachers to the window is 43.5 inches. |
AA6 |
6 months |
40-6 Drinking Fountain on Upper Level Near Classroom |
|
|
40-6. a The drinking fountain is inaccessible because the controls require 7 pounds of force to operate and there is no drinking fountain provided for people who have difficulty bending or stooping. |
DF1 |
6 months |
40-6. b The drinking fountain protrudes into the walkway and would not be detectable to a blind person using a cane. |
AR8 |
6 months |
40-7 Men’s Toilet Room with Stalls on Upper Level |
|
|
40-7. a The toilet room signage is inaccessible because it is mounted on the door and lacks the International Symbol of Accessibility. |
TR17 |
6 months |
40-7. b The door is inaccessible because the pressure required to open the door is 8 pounds. |
D2 |
6 months |
40-7. c No accessible mirror has been provided. |
TR14 |
6 months |
40-7. d The lavatory is inaccessible because the hot water pipes are not insulated or otherwise configured to protect against contact, and the lavatory apron is 28 inches above the finished floor to the bottom edge. |
TR9 |
6 months |
40-7. e The urinal is inaccessible because there is 27 inches of clear floor space width. |
TR20 |
6 months |
40-7. f No accessible coat hook has been provided. |
TR1 |
6 months |
40-7. g The toilet paper dispenser is inaccessible because it is mounted above the side grab bar. |
ST19 |
6 months |
40-7. h The side grab bar at the designated accessible toilet is inaccessible because it is mounted with the closer end 13.5 inches from the rear wall. |
ST7 |
6 months |
40-7. i The rear grab bar is inaccessible because it is mounted with the closer end 7.5 inches from the side wall and it is mounted 31.5 inches above the finished floor. |
ST3 |
6 months |
40-8 Women’s Toilet Room with Stalls on Upper Level |
|
6 months |
40-8. a The toilet room signage is inaccessible because it is mounted on the door and lacks the International Symbol of Accessibility. |
TR17 |
6 months |
40-8. b The door to the toilet room is inaccessible because the pressure required to open the door is 8 pounds. |
D2 |
6 months |
40-8. c The push side of the door, which is accessed through a front approach and which has both a closer and a latch, is inaccessible because it has only 4 inches of maneuvering clearance on the latch side of the door. |
D7 |
6 months |
40-8. d No accessible mirror has been provided. |
TR14 |
6 months |
40-8. e The lavatory is inaccessible because the hot water pipes are not insulated or otherwise configured to protect against contact, and the lavatory apron is 27.5 inches above the finished floor to the bottom edge. |
TR9 |
|
40-8. f The toilet is inaccessible because its centerline is 16 inches from the side wall. |
ST17 |
6 months |
40-8. g No accessible coat hook has been provided. |
TR1 |
6 months |
40-8. h The toilet paper dispenser is inaccessible because it is mounted above the side grab bar. |
ST19 |
6 months |
40-8. i The side grab bar at the designated accessible toilet is mounted with the closer end 13.5 inches from the rear wall. |
ST7 |
6 months |
40-9 Elevator |
|
|
40-9. a The elevator is inaccessible because the hoistway signage does not have Braille or raised letters. |
E12 |
6 months |
40-9. b The elevator is inaccessible because the door reopening device requires contact with the obstruction, the doors stay open for 2 seconds after reopening, and the time from notification that a car is answering a call until the doors start to close is 2 seconds. |
E6 |
6 months |
40-9. c The elevator is inaccessible because the car controls lack Braille. |
E4 |
6 months |
40-9. d The elevator is inaccessible because, although emergency communications are provided, the emergency communication system is not identified by raised symbols and lettering, the door does not operate without tight grasping or pinching, and the system does not work without voice communication. |
E8 |
6 months |
40-10 Drinking Fountain on Lower Level |
|
|
40-10. a The drinking fountain protrudes into the walkway and would not be detectable to a blind person using a cane. |
AR8 |
6 months |
40-11 Men’s Locker Room on Lower Level |
|
|
40-11. a The locker room signage is inaccessible because it is mounted on the door and lacks the International Symbol of Accessibility. |
TR17 |
6 months |
40-11. b There is no accessible locker provided. |
LR3 |
6 months |
40-11. c The air dryers protrude into the walkway and would not be detectable to a blind person using a cane. |
AR8 |
6 months |
40-11. d The air dryers are inaccessible because they are mounted with the controls 60 inches above the finished floor. |
TR5 |
6 months |
40-11. e The paper towel dispenser is inaccessible because it is mounted with the controls 62 inches above the finished floor. |
TR5 |
6 months |
40-11. f The lavatory is inaccessible because the hot water pipes are not insulated or otherwise configured to protect against contact, and the lavatory apron is 25.5 inches above the finished floor to the bottom edge. |
TR9 |
6 months |
40-11. g The toilet is inaccessible because the top of the seat is 19.75 inches above the finished floor. |
ST20 |
6 months |
40-11. h No accessible coat hook has been provided. |
TR1 |
6 months |
40-11. i The toilet paper dispenser is inaccessible because it is mounted above the side grab bar. |
ST19 |
6 months |
40-11. j The side grab bar at the designated accessible toilet is mounted with the closer end 13.5 inches from the rear wall. |
ST7 |
6 months |
40-11. k The rear grab bar provided at the designated accessible toilet is inaccessible because it is 32 inches long, mounted with the closer end 8 inches from the side wall, and is mounted 31 inches above the finished floor. |
ST3 |
6 months |
40-11. l The roll-in shower is inaccessible because the seat is mounted 22 inches from the finished floor and the grab bar does not extend to three walls of the shower. |
B8 |
6 months |
40-11. m The shower is inaccessible because the controls are mounted at 55 inches above the finished floor and are not within 27 inches of the centerline of the wall. |
TR5 |
6 months |
40-11. n The shower is inaccessible because no shower spray unit is provided and the shower head is higher than 48 inches above the finished floor. |
B11 |
6 months |
40-11. o The bench is inaccessible because it is 17 inches wide, lacks the clear floor space to facilitate a parallel transfer, and is not mounted with its surface between 17 inches and 19 inches above the finished floor. |
LR1 |
6 months |
40-12 Women’s Locker Room on Lower Level |
|
|
40-12. a The locker room signage is inaccessible because it is mounted on the door and lacks the International Symbol of Accessibility. |
TR17 |
6 months |
40-12. b The door is inaccessible because the pressure required to open the door is 10 pounds. |
D2 |
6 months |
40-12. c The air dryers protrude into the walkway and would not be detectable to a blind person using a cane. |
AR8 |
6 months |
40-12. d The paper towel dispenser is inaccessible because it is mounted with the controls 62 inches above the finished floor. |
TR5 |
6 months |
40-12. e The lavatory is inaccessible because the hot water pipes are not insulated or otherwise configured to protect against contact, and the lavatory apron is 26.5 inches above the finished floor to the bottom edge. |
TR9 |
6 months |
40-12. f No accessible coat hook has been provided. |
TR1 |
6 months |
40-12. g The toilet paper dispenser is inaccessible because it is mounted above the grab bar and is more than 36 inches from the rear wall. |
ST19 |
6 months |
40-12. h The side grab bar at the designated accessible toilet is inaccessible because it is mounted with the closer end 13.5 inches from the rear wall. |
ST7 |
6 months |
40-12. i The rear grab bar is inaccessible because it is mounted 31 inches above the finished floor. |
ST3 |
6 months |
40-12. j The transfer shower is inaccessible because the dimensions are 64.5 inches by 48 inches, and the seat is mounted 22.5 inches above the finished floor and is not on the wall opposite of the shower controls, the controls are mounted at 56 inches above the finished floor and are not within 27 inches of the centerline of the wall, the soap dispenser is too high, and there is no bracket to allow the shower head to be used as a fixed shower head. |
B8 |
6 months |
40-12. k The bench is inaccessible because it is 17.25 inches wide and 20.25 inches long. |
LR1 |
6 months |
40-13 Family Changing Room - Entrance Through Pool Office on Lower Level |
|
|
40-13. a The room signage is inaccessible because it is mounted on the door. |
TR17 |
6 months |
40-13. b The door to the pool office is inaccessible because the pressure required to open the door is 15 pounds. |
D2 |
6 months |
40-13. c The pull side of the door, which is accessed through a front approach, is inaccessible because it has only 8 inches of clear maneuvering space due to the presence of metal lockers. |
D6 |
6 months |
40-13. d No accessible mirror has been provided. |
TR14 |
6 months |
40-13. e The soap dispenser next to the lavatory is inaccessible because it is mounted 48 inches above the finished floor over an obstruction. |
TR4 |
6 months |
40-13. f The air dryers are inaccessible because they are mounted with the controls 58 inches above the finished floor. |
TR5 |
6 months |
40-13. g The air dryer protrudes into the walkway and would not be detectable to a blind person using a cane. |
AR8 |
6 months |
40-13. h The baby changing table is inaccessible because it is mounted with the controls 62.5 inches above the finished floor reaching over an obstruction. |
TR4 |
6 months |
40-13. i The lavatory is inaccessible because the apron is 27 inches above the finished floor to the bottom edge and the hot water pipes are not insulated or otherwise configured to protect against contact. |
TR9 |
6 months |
40-13. j The side grab bar at the designated accessible toilet is inaccessible because it is mounted with the closer end 13.5 inches from the rear wall. |
ST7 |
6 months |
40-13. k The rear grab bar is inaccessible because it is 24 inches long and the distance to the closer end from the side wall is 7.5 inches. |
ST4 |
6 months
|
40-13. l The toilet is inaccessible because the top of the seat is 19.5 inches above the finished floor. |
ST20 |
6 months |
40-13. m The bench is inaccessible because it is mounted 19.75 inches above the finished floor. |
LR1 |
6 months |
40-13. n The roll-in shower is inaccessible because the seat is mounted 22 inches above the floor, it does not extend the full length of the wall, it is 13.5 inches away from the rear wall, and the grab bar behind the shower seat obstructs the use of the seat. |
B10, B8 |
6 months |
40-13. o The shower is inaccessible because no shower spray unit is provided and the shower head is higher than 48 inches above the finished floor. |
B11 |
6 months |
40-13. p The soap dispenser in the shower is inaccessible because the controls are mounted too high. |
TR5 |
6 months |
40-13. q There is no accessible locker provided. |
LR3 |
6 months |
40-14 Accessible Route from Building Front to Playgrounds, Basketball Court, and Tennis Court |
|
|
40-14. a The wall-mounted drinking fountain at the corner of the building is inaccessible because it is obstructed by a bench and trash receptacle. |
DF5 |
6 months |
40-15 Field House |
|
|
40-15. a The defibrillator protrudes into the walkway and would not be detectable to a blind person using a cane. |
AR8 |
6 months |
40-15. b Women’s Toilet Room with Stalls |
|
|
40-15. b (1) The toilet room signage is inaccessible because it is mounted on the door and lacks the International Symbol of Accessibility, Braille, and raised characters. |
TR17 |
6 months |
40-15. b (2) The door is inaccessible because the pressure required to open the door is 12 pounds. |
D2 |
6 months |
40-15. b (3) The lavatory is inaccessible because it the apron is 26 inches above the finished floor to the bottom edge, and the hot water pipes are not insulated or otherwise configured to protect against contact. |
TR9 |
6 months |
40-15. b (4) No accessible coat hook has been provided. |
TR1 |
6 months |
40-15. b (5) The side grab bar at the designated accessible toilet is inaccessible because it is mounted with the closer end 13.5 inches from the rear wall. |
ST7 |
6 months |
40-15. b (6) The rear grab bar is inaccessible because it is mounted 31 inches above the floor and its closer end is 7.5 inches from the side wall. |
ST3 |
6 months |
40-15. c Men’s Toilet Room with Stalls |
|
|
40-15. c (1) The toilet room signage is inaccessible because it is mounted on the door and lacks the International Symbol of Accessibility, Braille, and raised characters. |
TR17 |
6 months |
40-15. c (2) The door is inaccessible because the pressure required to open the door is 11 pounds. |
D2 |
6 months |
40-15. c (3) The lavatory is inaccessible because the apron is 27 inches above the finished floor to the bottom edge, and the hot water pipes are not insulated or otherwise configured to protect against contact. |
TR9 |
6 months |
40-15. c (4) The lavatory is inaccessible because the hot water pipes are not insulated or otherwise configured to protect against contact. |
TR12 |
6 months |
40-15. c (5) The urinal is inaccessible because the rim is 25 inches above the floor and the flush control is 48 inches above the floor. |
TR20 |
6 months |
40-15. c (6) No accessible coat hook has been provided. |
TR1 |
6 months |
40-15. c (7) The toilet is inaccessible because the flush control is on the closed side. |
ST2 |
6 months |
40-15. c (8) The side grab bar at the designated accessible toilet is inaccessible because it is mounted with the closer end 13.5 inches from the rear wall. |
ST7 |
6 months |
40-15. d Drinking Fountains near Toilet Rooms |
|
|
40-15. d (1) The low drinking fountain is inaccessible because it requires 9 pounds of force to operate, and the knee space height between the bottom of the apron and the finished floor is 25.5 inches. |
DF1 |
6 months |
40-15. d (2) The high drinking fountain unit protrudes into the walkway and would not be detectable to a blind person using a cane. |
AR8 |
6 months |
40-15. e Public Pay Telephone in Field House |
|
|
40-15. e (1) The telephone is inaccessible because the highest operable part is 55.5 inches from the floor. |
TT1 |
6 months |
40-15. e (2) The telephone protrudes into the walkway and would not be detectable to a blind person using a cane. |
AR8 |
6 months |
40-16 Field House Parking Lot Serving Sports Fields |
|
|
40-16. a The parking lot is inaccessible because the access aisles are too narrow and none of the parking spaces are designated as van-accessible. |
P3 |
6 months |
40-17 Accessible Route to Dog Park and other Amenities |
|
|
40-17. a The route to the portable toilets is inaccessible because the route is not firm, stable and slip-resistant near the portable toilets. |
AR1 |
6 months |
41. Nottoway Park 9537 Courthouse Road Vienna, VA 22181 |
|
|
41-1 Parking near Accessible Garden Plots |
|
|
41-1. a The parking reserved for persons with disabilities is inaccessible because the spaces and pavement markings are covered with gravel. |
P7 |
6 months |
41-2 Parking near Soccer Field |
|
|
41-2. a The parking reserved for persons with disabilities is inaccessible because the slopes of the van accessible parking spaces and access aisles exceed 2%. |
P7 |
6 months |
41-2. b The standard accessible parking space on the right is inaccessible because it is 93 inches wide. |
P3 |
6 months |
41-3 Accessible Route from Soccer Field Parking to Playing Fields |
|
|
41-3. a The route from the soccer field parking to the fields is inaccessible because the curb ramp on the left when facing the fields has a slope of 13.2%, a left flare with a slope of 21.8%, and a right flare with a slope of 13.2%; the middle curb ramp has a 14.1% slope, a left flare with a slope of 11.4%, and a right flare with a slope of 16.9%; and the right curb ramp has a right flare with a slope of 10.6%. |
AR5 |
6 months |
41-3. b The route from the soccer field parking to the fields is inaccessible because the surface is not stable, firm, and slip-resistant. |
AR1 |
6 months |
41-4 Picnic/Playground Areas |
|
|
41-4. a The picnic table with an extension on one end is inaccessible because it has knee space height that is 26 inches above the finished floor. |
PD6 |
6 months |
41-5 Accessible Route from Hunter House Parking Lot to Tennis Courts and other Playing Areas |
|
|
41-5. a The route from the side of the parking lot by the Farmer’s Market to the tennis courts is inaccessible because there is no curb ramp or way for someone who uses a wheelchair to get on or off the sidewalk. |
AR5 |
6 months |
41-5. b The stairs between the tennis courts are inaccessible because the handrails are not continuous. |
AR10 |
6 months |
41-6 Drinking Fountains in the Park |
|
|
41-6. a Fountain Outside Toilet Room Facility |
|
|
41-6. a (1) The drinking fountain is inaccessible because the spout is 42 inches above the finished floor, requires 9 pounds of force to operate, and there is only 12.5 inches of knee depth space. |
DF1 |
6 months |
41-6. b Fountain near Basketball Court |
|
|
41-6. b (1) The drinking fountain is inaccessible because it requires 6 pounds of force to operate and there is no drinking fountain provided for people who have difficulty bending or stooping. |
DF1 |
6 months |
41-6. c Drinking Fountain near Tennis Court |
|
|
41-6. c (1) The drinking fountain is inaccessible because it requires more than 5 pounds of force to operate, the water flow is 4 inches from the front of the fountain, and there is no drinking fountain provided for people who have difficulty bending or stooping. |
DF1 |
6 months |
41-6. c (2) The drinking fountain protrudes into the walkway and would not be detectable to a blind person using a cane. |
AR8 |
6 months |
41-7 Public Pay Phone next to Toilet Room Facility |
|
|
41-7. a The telephone is inaccessible because the highest operable part is mounted 56.5 inches above the floor. |
TT1 |
6 months |
41-8 Women’s Toilet Room with Stalls in the Facility in the Middle of the Park (Near Shelter, Playground and Ballfields) |
|
|
41-8. a The toilet room signage is not accessible because it is not mounted on the latch side of the door close to the door at 60 inches above the finished floor. |
TR17 |
6 months |
41-8. b No accessible mirror has been provided. |
TR14 |
6 months |
41-8. c The towel dispenser is inaccessible because it is mounted 56 inches above the finished floor with a reach over an obstruction of 14 inches. |
TR4 |
6 months |
41-8. d The lavatory is inaccessible because the rim is 35.25 inches above the finished floor to the top. |
TR11 |
6 months |
41-8. e The lavatory is inaccessible because the hot water pipes are not insulated or otherwise configured to protect against contact. |
TR12 |
6 months |
41-8. f The designated accessible stall is incorrectly configured as an ambulatory stall, and there is no standard accessible stall provided. |
ST15 |
6 months |
41-9 Men’s Toilet Room with Stalls in the Facility in the Middle of the Park |
|
|
41-9. a The toilet room signage is not accessible because it is not mounted on the latch side of the door close to the door at 60 inches above the finished floor. |
TR17 |
6 months |
41-9. b No accessible mirror has been provided. |
TR14 |
6 months |
41-9. c The towel dispenser is inaccessible because it is mounted 56 inches above the finished floor with a reach over an obstruction of 14 inches. |
ST19 |
6 months |
41-9. d The lavatory is inaccessible because the hot water pipes are not insulated or otherwise configured to protect against contact. |
TR12 |
6 months |
41-9. e The urinal is inaccessible because it does not have an elongated rim and the rim is 25.5 inches above the finished floor. |
TR20 |
6 months |
41-9. f The designated accessible stall is incorrectly configured as an ambulatory stall, and there is no standard accessible stall provided. |
ST15 |
6 months |