ATTACHMENT J: Modifications to Altered Facilities
Please Note: Paragraph 90 of the Settlement Agreement
requires that within three months of the effective date of this Agreement,
the County provide signage as necessary to comply with 28 C.F.R. § 35.163(b),
after having surveyed all facilities that are the subject of this Agreement
for the purpose of identifying those that have multiple entrances not all of
which are accessible.
The chart below lists the facilities surveyed by the Department,
the access issues identified during the survey, and the actions required to
correct the access issues. Required actions are listed using an alphanumeric
code. The key to the alphanumeric codes is provided in Attachment M to this
Agreement.
In order to ensure that the following spaces and elements
in County facilities, in which alterations occurred after January 26, 1992,
are readily accessible to and usable by persons with disabilities, the County
will take the actions referenced by the alphanumeric code and described in
detail in Attachment M to this Settlement Agreement within the time period
specified below, which time period will begin to run on the effective date of
this Agreement.
|
Access Issue
|
Required Action
|
Completion Date
|
1. Domestic
Violence Shelter (location not to be disclosed)
| | |
1.1 Parking
|
| |
1.1a The
signage designating parking as reserved for persons with disabilities is
inaccessible because it is too low and lacks the appropriate signage.
|
P6
|
36 months
|
1.1b The
parking reserved for persons with disabilities is inaccessible because the
access aisle slopes 4% and the space for the vehicle has a cross slope of
8.9%.
|
P7
|
36 months
|
1.2 Accessible
Route
|
| |
1.2a The ramp
is inaccessible because the bottom leg has a slope of up to 8.8%, the top leg
has a slope of up to 10.4%, there are no handrail extensions, no edge
protection at the top of the ramp leg, and no level landing at the entrance
to the building.
|
R5
|
36 months
|
1.3 Entrance
|
| |
1.3a The
entrance at the top of the ramp is inaccessible because there is a 2 inch
change in level at the threshold to the door.
|
D22
|
36 months
|
1.4 Kitchen
|
| |
1.4a The
counter tops are inaccessible because they are 36 inches above the finished
floor.
|
C8
|
36 months
|
1.4b The
telephone in the kitchen is inaccessible because it is mounted 61 inches
above the finished floor over an obstruction.
|
TR4
|
36 months
|
1.4c The
microwave in the kitchen is inaccessible because its operating mechanism is
mounted at 60 inches above the finished floor.
|
TR4
|
36 months
|
1.4d The sink
is inaccessible because the clear floor space for the sink is not centered.
|
S2
|
36 months
|
1.4e The
doorway between the kitchen and the hallway is inaccessible because it has an
opening width of only 31.5 inches.
|
D25
|
36 months
|
1.5 Bathroom
|
| |
1.5a The
bathroom door is inaccessible because knob hardware is used.
|
D1
|
36 months
|
1.5b Toilet
|
| |
1.5b(1) The
rear grab bar at the toilet is inaccessible because it is 24 inches long.
|
SU3
|
36 months
|
2. Mondloch
House 1 (#2047)
3516 Lockheed Boulevard
Alexandria, VA 22306
| | |
2.1 Front
Parking Lot
| | |
2.1a The van
accessible parking reserved for persons with disabilities in the front
parking lot lacks the appropriate signage.
|
P6
|
6 months
|
2.1b The
route from the designated accessible parking space in the front lot to the
rear entrance is inaccessible because the slope of the curb ramp at the
sidewalk is 13.2% and the slope of the flared side is 23.4%.
|
AR5
|
6 months
|
2.1c The
route from the front parking lot to the rear entrance is inaccessible because
the accessible route is narrowed by cars overhanging the sidewalk and other
movable objects.
|
AR3
|
6 months
|
2.2 Front
Entrance
| | |
2.2a The
building does not have accessible directional signage posted at inaccessible
entrances with characters proportional to the reading distance.
|
D16
|
6 months
|
2.3 Rear Parking
Lot
| | |
2.3a The
parking reserved for persons with disabilities lacks appropriate signage.
|
P6
|
6 months
|
2.3b The
parking reserved for persons with disabilities is inaccessible because the
access aisle is 46 inches wide.
|
P8
|
6 months
|
2.3c The
route from the designated accessible parking space in the rear parking lot to
the rear entrance is inaccessible because the slope of the curb ramp at the
sidewalk is 13.2% and the slope of the right flared side is 22.4%.
|
AR5
|
6 months
|
2.4 Exterior
Rear Entrance
| | |
2.4a The rear
entrance is locked after 7 p.m.
|
D14
|
6 months
|
2.4b The rear
entrance is inaccessible because it has knob hardware on the pull side.
|
D1
|
6 months
|
2.5 Internal
Accessible Route
| | |
2.5a The
doors throughout the facility are inaccessible because knob hardware is used.
|
D1
|
6 months
|
2.5b The
signage throughout the facility is inaccessible.
|
D26
|
6 months
|
2.6 Drinking
Fountain
| | |
2.6a The
drinking fountain in the hallway has a spout that is approximately 40 inches
above the finished floor.
|
DF6
|
6 months
|
2.6b Although
a drinking fountain is provided, there is no drinking fountain provided for
people who have difficulty bending or stooping.
|
DF3
|
6 months
|
2.7 Public
Pay Telephone
| | |
2.7a The pay
telephone in the hallway alcove is inaccessible because the highest operable
part is 57 inches above the finished floor.
|
TT1
|
6 months
|
2.8 Dining
Area
| | |
2.8a The door
from the rear hallway is inaccessible because the pressure required to open
the door is 10 pounds.
|
D2
|
6 months
|
2.9 Reception
Area
| | |
2.9a The
walkway is inaccessible because the reception area counter protrudes into the
walkway and would not be detectable to a blind person using a cane.
|
AR8
|
6 months
|
2.10 Designated
Accessible Sleeping Room (#10)
| | |
2.10a The
sleeping room door is inaccessible because knob hardware is used.
|
D1
|
6 months
|
2.10b The
signage provided is inaccessible because it has no International Symbol of
Accessibility, no Braille or raised characters, and the sign is on the door.
|
D26
|
6 months
|
2.11 Single
User Toilet Room
| | |
2.11a The
toilet room sign is located on the door, has no International Symbol of
Accessibility, and has no raised or Braille characters.
|
TR17
|
6 months
|
2.11b The
door to the single user toilet room is inaccessible because the pressure
required to open the door is 6 pounds.
|
D2
|
6 months
|
2.11c The
push side of the door to the single user toilet room, which is accessed
through a front approach, is inaccessible because it has only 3.5 inches of
maneuvering clearance on the latch side of the door.
|
D7
|
6 months
|
2.11d Although
an audible alarm is provided in this facility, there is no visual alarm
appliance in the toilet room.
|
TR21
|
6 months
|
2.11e The
lavatory is inaccessible because the rim height is 36 inches above the
finished floor, the hot water pipes are not insulated or otherwise configured
to protect against contact, and the support bars are mounted with less than
30 inches between them.
|
TR9
|
6 months
|
2.11f The
grab bars at the toilet are inaccessible because the side grab bar is not 42
inches in length and there is no rear grab bar.
|
SU10
|
6 months
|
2.11g The
toilet is inaccessible because the flush control is on the closed side and
the top of the seat is missing.
|
SU14
|
6 months
|
2.11h Roll-in
Shower Stall
| | |
(a) The
roll-in shower is inaccessible because the shower control requires twisting
of the wrist and is mounted at 22 inches above the floor, no shower spray
unit is provided, the shower head is higher than 48 inches above the finished
floor, and the grab bar is not continuous.
|
B8
|
6 months
|
3. Mount
Vernon Governmental Center
2511 Parkers Lane
Alexandria, VA 22306
| | |
3.1 Parking
| | |
3.1a Although
the parking lot has a total of 138 parking spaces, an inadequate number are
designated as reserved for people with disabilities.
|
P3
|
6 months
|
3.2 Accessible
Route
| | |
3.2a Curb ramp
serving the designated van accessible parking space
| | |
3.2a(1) The
route from the designated van-accessible space to the entrance is
inaccessible because the primary slope of the curb ramp is 8.8%, and the
slope of the right flared side is 11%.
|
AR5
|
6 months
|
3.2b Curb ramp
serving the standard accessible parking space
| | |
3.2b(1) The
route from the standard accessible parking space to the entrance is
inaccessible because the primary slope of the curb ramp is 11.5%, the cross
slope is 2.7%, the slope of the right flared side is 10.2%, and the slope of
the left flared side is 10.6%.
|
AR5
|
6 months
|
3.3 Main
Lobby
| | |
3.3a The
police counter is inaccessible because the height is 51.5 inches.
|
C6
|
6 months
|
3.4 Magistrate
Office-Room 169
| | |
3.4a The door
to Room 169 is inaccessible because the pressure required to open the door is
10 pounds.
|
D2
|
6 months
|
3.4b The lower
counter in the magistrate's office is inaccessible because it is 32.5 inches
wide.
|
C6
|
6 months
|
3.4c The
telephone located near the counter is inaccessible because it is mounted with
its controls located 49 inches above the finished floor and its use requires
a front approach.
|
TT1
|
6 months
|
3.4d The
walkway is inaccessible because the telephone protrudes into the walkway and
would not be detectable to a blind person using a cane.
|
AR8
|
6 months
|
3.5 Community
Room #3-Room 121
| | |
3.5a The door
to each of the three community rooms are inaccessible because the pressure
required to open each door is seven pounds.
|
D2
|
6 months
|
3.5b The
walkway is inaccessible because the height of the bottom of the suspended TV
monitor is 71 inches from the finished floor; it protrudes into the walkway
and would not be detectable to a blind person using a cane.
|
AR8
|
6 months
|
3.6 Drinking
Fountain near Community Rooms
| | |
3.6a The
wall-mounted lower unit drinking fountain is inaccessible because the knee
clearance height is 26 inches above the finished floor.
|
DF5
|
6 months
|
3.7 Women's
Toilet Room with Stalls near Community Rooms
| | |
3.7a The paper
towel dispenser is inaccessible because the controls are mounted at 51.25
inches above the finished floor and are obstructed by a trash receptacle.
|
TR4
|
6 months
|
3.8 Men's
Toilet Room with Stalls near Community Rooms
| | |
3.8a The
toilet room door is inaccessible because the pressure required to open the
door is 10 pounds.
|
D2
|
6 months
|
3.8b The paper
towel dispenser is inaccessible because the controls are mounted at 52.5
inches above the finished floor and are obstructed by the lavatory.
|
TR4
|
6 months
|
3.8c The
toilet is inaccessible because its centerline measures 19 inches from the
side wall.
|
ST17
|
6 months
|
3.8d The
walkway is inaccessible because the air dryer protrudes into the walkway and
would not be detectable to a blind person using a cane.
|
AR8
|
6 months
|
3.9 Room
173-Cell
| | |
3.9a The door
to Room 173 is inaccessible because it has an opening width of only 27.5
inches.
|
D25
|
6 months
|
3.10 Room
162-Women's Locker Room
| | |
3.10a The toilet
room sign does not have the International Symbol of Accessibility.
|
TR17
|
6 months
|
3.10b There is
no accessible toilet stall provided.
|
ST15
|
6 months
|
3.10c There is
no accessible locker provided.
|
LR3
|
6 months
|
3.10d The
benches in the women's locker room are not accessible because of inadequate
depth.
|
LR1
|
6 months
|
3.10e The shower
in the women's locker room is inaccessible.
|
B8
|
6 months
|
3.11 Room
158-Men's Locker Room
| | |
3.11a The toilet
room sign next to the entry door does not have the International Symbol of
Accessbility.
|
TR17
|
6 months
|
3.11b There is
no accessible toilet stall provided.
|
ST15
|
6 months
|
3.11c The urinal
is inaccessible because the rim height is above 17 inches.
|
TR20
|
6 months
|
3.11d There is
no accessible locker provided.
|
LR3
|
6 months
|
3.11e The benches
in the men's locker room are not accessible because of inadequate depth.
|
LR1
|
6 months
|
3.11f The
shower in the men's locker room is inaccessible.
|
B8
|
6 months
|
3.11g No
accessible clothes hook has been provided.
|
TR1
|
6 months
|
3.12 Drinking
Fountain located near the Exercise Room and Lunch Room
| | |
3.12a The
drinking fountain has a spout that is 41 inches above the finished floor.
|
DF6
|
6 months
|
3.12b The
walkway is inaccessible because the drinking fountain protrudes into the
walkway and would not be detectable to a blind person using a cane.
|
AR8
|
6 months
|
3.13 Room
196-Captain's Suite
| | |
3.13a The
service counter in Room 196 is inaccessible because it is more than 36 inches
above the finished floor.
|
C6
|
6 months
|
3.14 District
Supervisor's Office
| | |
3.14a The
service counter in the supervisor's office is inaccessible because it is
43.75 inches above the finished floor.
|
C6
|
6 months
|
3.14b The route
near the television monitor and control pad in the conference room is
inaccessible because there are only 70 inches of head room provided.
|
AR7
|
6 months
|
3.14c The
television in the conference room has controls thar are inaccessible because
the controls are mounted at 65.5 inches above the finished floor.
|
TR5
|
6 months
|
3.15 Emergency
Call Station located in the Parking Lot
| | |
3.15a The route
from the side parking lot to the call station is inaccessible because there
is no curb ramp leading to it.
|
AR5
|
6 months
|
4. Gum
Springs Community Center
8100 Fordson Road
Alexandria, VA 22306
| | |
4.1 Parking
| | |
4.1a One of
the signs on the right side of the building designating parking as reserved
for persons with disabilities is too low.
|
P6
|
6 months
|
4.2 Interior
Accessible Route
| | |
4.2a The
walkway is inaccessible because the defibrillator protrudes into the walkway
and would not be detectable to a blind person using a cane.
|
AR8
|
6 months
|
4.3 Gym-Room
120
| | |
4.3a The
signage provided is inaccessible because the centerline is at a height of
62.25 inches above the finished floor and there are no raised characters and
Braille.
|
D26
|
6 months
|
4.3b Women's
Single User Toilet Room
| | |
4.3b(1) The
toilet room sign has a centerline of 63.5 inches above the finished floor and
is not mounted on the latch side of the door.
|
TR17
|
6 months
|
4.3b(2) No
accessible mirror has been provided.
|
TR14
|
6 months
|
4.3b(3) The
lavatory is inaccessible because the hot water pipes are not insulated or
otherwise configured to protect against contact.
|
TR12
|
6 months
|
4.3b(4) The
toilet is inaccessible because the top of the seat is 20 inches above the
finished floor.
|
SU18
|
6 months
|
4.3c Men's
Single User Toilet Room
| | |
4.3c(1) The
toilet room sign has a centerline of 63.5 inches above the finished floor and
is not mounted on the latch side of the door.
|
TR17
|
6 months
|
4.3c(2) No
accessible mirror has been provided.
|
TR14
|
6 months
|
4.3c(3) The
lavatory is inaccessible because the hot water pipes are not insulated or
otherwise configured to protect against contact.
|
TR12
|
6 months
|
4.3c(4) The
toilet is inaccessible because the top of the seat is 19.5 inches above the
finished floor.
|
SU18
|
6 months
|
4.3c(5) The
toilet is inaccessible because its centerline measures 19.25 inches from the
side wall.
|
SU15
|
6 months
|
4.3d Drinking
Fountain
| | |
4.3d(1) The
drinking fountain has a spout that is 41 inches above the finished floor.
|
DF6
|
6 months
|
4.4 Telephone
near Vending Room
| | |
4.4a The
walkway is inaccessible because the telephone protrudes into the walkway and
would not be accessible to blind persons using a cane.
|
AR8
|
6 months
|
4.5 Game
Room- Room 125B
| | |
4.5a The door
is inaccessible because the pressure required to open the door is 6 pounds.
|
D2
|
6 months
|
4.6 Drinking
Fountain near Fitness Room- (Room 124)
| | |
4.6a The
drinking fountain has a spout that is 42 inches above the finished floor.
|
DF6
|
6 months
|
4.6b The
walkway is inaccessible because the drinking fountain protrudes into the
walkway and would not be detectable to a blind person using a cane.
|
AR8
| |
4.7 Men's
Toilet Room with Stalls near Fitness Room
| | |
4.7a The
toilet room sign is mounted on the door.
|
TR17
|
6 months
|
4.7b The light
switch is inaccessible because the controls are mounted at 58 inches above
the finished floor.
|
TR5
|
6 months
|
4.7c The
lavatory is inaccessible because counter top is 34.75 inches above the
finished floor and the apron bottom is 28 inches above the finished floor.
|
TR11
|
6 months
|
4.7d The
urinal is inaccessible because the flush control is 45.5 inches above the
finished floor.
|
TR20
|
6 months
|
4.7e The
toilet is inaccessible because its centerline measures 16.5 inches from the
side wall.
|
ST17
|
6 months
|
4.8 Women's
Toilet Room with Stalls near Fitness Room
| | |
4.8a The
toilet room sign is mounted on the door.
|
TR17
|
6 months
|
4.8b The light
switch is inaccessible because the controls are mounted at 58 inches above
the finished floor.
|
TR5
|
6 months
|
4.8c The
lavatory is inaccessible because counter top is 34.75 inches above the
finished floor and the apron bottom is 28 inches above the finished floor.
|
TR11
|
6 months
|
4.9 Computer
Club-Room 129
| | |
4.9a The
signage provided is inaccessible because it has no raised characters or
Braille.
|
D26
|
6 months
|
4.10 Senior
Center-Room 131
| | |
4.10a The single
user toilet room contains a number of inaccessible elements and is not
accessible to people with disabilities.
|
SU13
|
6 months
|
4.11 Drinking
Fountain near Classroom A
| | |
4.11a Although
an accessible drinking fountain is provided, there is no drinking fountain
provided for people who have difficulty bending or stooping.
|
DF3
|
6 months
|
4.12 Cafeteria-Room
135
| | |
4.12a The
signage provided is inaccessible because it has no raised characters or
Braille.
|
D26
|
6 months
|
4.13 Exterior
Rear Accessible Route to Playing Fields
| | |
4.13a The ramp
is inaccessible because the cross slope is 3.4% on the top segment, 4.3% on
the middle segment,and 3.3% on the bottom segment, and the ramp has no
handrails or edge protection.
|
R3
|
6 months
|
4.13b The route
from the rear doors of the building to the baseball field is inaccessible
because the route is not stable, firm and slip resistant near the ballfield.
|
AR1
|
6 months
|
4.14 Gum
Springs Head Start Program
| | |
4.14a The
intercom is inaccessible because the highest operable part (the button) is
56.75 inches above the finished floor.
|
TR5
|
6 months
|
4.15 Administrative
Office East-Room 101
| | |
4.15a The
service counter is inaccessible because it is 42.5 inches above the finished
floor.
|
C6
|
6 months
|
4.16 Room 103
| | |
4.16a The
signage provided is inaccessible because it is not mounted on the latch side
of the door.
|
D26
|
6 months
|
4.17 Single
User Toilet Room near Administrative Offices
| | |
4.17a The toilet
room sign has a centerline of 62 inches above the finished floor.
|
TR17
|
6 months
|
4.17b The seat
cover dispenser is inaccessible because the controls are mounted at 60 inches
above the finished floor.
|
TR5
|
6 months
|
4.17c The
lavatory is inaccessible because the bottom edge of the lavatory apron is
27.5 inches above the finished floor and the hot water pipes are not
insulated or otherwise configured to protect against contact.
|
TR11
TR12
|
6 months
|
4.17d The
toilet is inaccessible because there is insufficient clear floor space.
|
SU16
|
6 months
|
4.17e The
sanitary napkin dispenser is inaccessible because the operating mechanism
requires tight grasping and twisting of the wrist.
|
TR3
|
6 months
|
5. George Mason
Regional Library
7001 Little River Turnpike
Annandale, Virginia 22003
| | |
5.1 Parking
| | |
5.1a Although
the parking lot has a total of 170 parking spaces, the pavement markings are
not clear, the four designated accessible spaces and access aisles in front
of the building have slopes ranging from 3.0 % to 4.7% and cross slopes range
from 2.4% to 6.2%, and the four designated spaces on the side of the building
are not on the shortest route to the accessible entrance.
|
P3
|
6 months
|
5.2
Accessible Route
| | |
5.2a The route
from the side of the building turns at right angles as it leads to the front
entrance and it is inaccessible because at that point, a curb ramp intrudes
with a cross slope of 4.7%.
|
AR1
|
6 months
|
5.3 Library
| | |
5.3a The door
to the quiet area is inaccessible because the pressure required to open the
door is 19 pounds.
|
D2
|
6 months
|
5.4 Women's
Toilet Room with Stalls
| | |
5.4a The
toilet room sign has no International Symbol of Accessibility, is not mounted
on the latch side of the door at 60 inches from the finished floor, and does
not have raised characters and Braille.
|
TR17
|
6 months
|
5.4b The door
is inaccessible because the pressure required to open the door is 15 pounds.
|
D2
|
6 months
|
5.4c Although
an audible alarm is provided in this facility, there may be no visual alarm
appliance in the toilet room.
|
TR21
|
6 months
|
5.4d The seat
cover dispenser is inaccessible because the controls are mounted at 70 inches
above the finished floor.
|
TR5
|
6 months
|
5.4e The
toilet is inaccessible because its centerline measures 20 inches from the
side wall.
|
ST17
|
6 months
|
5.4f The
toilet is inaccessible because the flush control is on the closed side.
|
ST2
|
6 months
|
5.4g No
accessible coat hook has been provided.
|
TR1
|
6 months
|
5.4h The
toilet paper dispenser is inaccessible because it is mounted above the grab
bar and interferes with its use, and the toilet paper dispenser distance to
the rear wall is 37 inches.
|
ST19
|
6 months
|
5.5 Men's
Toilet Room with Stalls
| | |
5.5a The
toilet room sign has no International Symbol of Accessibility, is not mounted
on the latch side of the door at 60 inches from the finished floor, and does
not have raised characters and Braille.
|
TR17
|
6 months
|
5.5b The door
is inaccessible because the pressure required to open the door is 11 pounds.
|
D2
|
6 months
|
5.5c Although
an audible alarm is provided in this facility, there may be no visual alarm
appliance in the toilet room.
|
TR21
|
6 months
|
5.5d The seat
cover dispenser is inaccessible because the controls are mounted at 51 inches
above the finished floor and the toilet room stall door swings into the
dispenser's required clear floor space.
|
TR5
|
6 months
|
5.5e The
urinal is inaccessible because the flush control is 45 inches above the
finished floor.
|
TR20
|
6 months
|
5.5f The
toilet is inaccessible because its centerline measures 19 inches from the
side wall.
|
ST17
|
6 months
|
5.5g No
accessible coat hook has been provided.
|
TR1
|
6 months
|
5.5h The
toilet paper dispenser is inaccessible because it is mounted above the grab
bar and interferes with its use.
|
ST19
|
6 months
|
5.6
Drinking Fountain in Lobby
| | |
5.6a The
walkway is inaccessible because the high drinking fountain unit protrudes
into the walkway and would not be detectable to a blind person using a cane.
|
AR8
|
6 months
|
5.6b The lower
drinking fountain has a spout that is 37 inches above the finished floor.
|
DF6
|
6 months
|
6. Mason
Governmental Center
6507 Columbia Pike
Annandale, VA 22003
| | |
6.1 Parking
| | |
6.1a The
parking reserved for persons with disabilities is inaccessible because the
slopes and cross slopes of the designated spaces and access aisles range from
3.6% to 5.5%.
|
P7
|
6 months
|
6.1b The curb
ramp is inaccessible because parked cars can obstruct it.
|
AR5
|
6 months
|
6.2 Passenger
Loading Zone
| | |
6.2a The route
from the parking lot to the entrance is inaccessible because the primary
slope of the curb ramp is 9.6%, one flared side has a slope of 23.3%, and the
other flared side has a slope of 11.5%.
|
AR5
|
6 months
|
6.3 Lobby
| | |
6.3a Although
a public telephone to contact the police desk is provided, there is no
provisions for deaf patrons (a TTY is not provided).
|
TT2
|
6 months
|
6.4 Supervisor's
Office
| | |
6.4a The door
to the supervisor's office is inaccessible because the pressure required to
open the door is 10 pounds.
|
D2
|
6 months
|
6.5 Telephone
across from the Toilet Rooms
| | |
6.5a The
telephone is inaccessible because the knee space is blocked by an object.
|
TT1
|
6 months
|
6.6 Men's
Toilet Room with Stalls
| | |
6.6a The
toilet room sign is mounted at 58 inches above the finished floor.
|
TR17
|
6 months
|
6.6b The door
to the toilet room is inaccessible because the pressure required to open the
door is 11 pounds.
|
D2
|
6 months
|
6.6c No
accessible mirror has been provided.
|
TR14
|
6 months
|
6.6d The paper
towel dispenser is mounted above an obstruction.
|
TR4
|
6 months
|
6.6e The
lavatory is inaccessible because the pipes are not insulated or otherwise
configured to protect against contact.
|
TR12
|
6 months
|
6.6f The
toilet paper dispenser is inaccessible because it is mounted 38 inches from
the rear wall.
|
ST19
|
6 months
|
6.6g The side
grab bar is inaccessible because it is mounted with the closer end 13 inches
from the rear wall.
|
ST7
|
6 months
|
6.6h The rear
grab bar is inaccessible because it is mounted with the closer end 13 inches
from the rear wall.
|
ST4
|
6 months
|
6.7 Women's
Toilet Room with Stalls
| | |
6.7a The door
to the toilet room is inaccessible because the pressure required to open the
door is 14 pounds.
|
D2
|
6 months
|
6.7b No
accessible mirror has been provided.
|
TR14
|
6 months
|
6.7c The
toilet is inaccessible because the centerline is 19 inches from the side
wall.
|
ST17
|
6 months
|
6.7d No
accessible coat hook has been provided.
|
TR1
|
6 months
|
6.7e The
toilet paper dispenser is inaccessible because it is mounted 37.5 inches from
the rear wall.
|
ST19
|
6 months
|
6.7f The rear
grab bar is inaccessible because it is mounted with the closer end 13 inches
from the side wall.
|
ST4
|
6 months
|
6.8 Police
Department Area
| | |
6.8a Room 100
| | |
6.8a(1) The
signage provided is inaccessible because it is mounted 66 inches above the
finished floor to the centerline.
|
D26
|
6 months
|
6.8b Lobby
| | |
6.8b(1) The
counter outside the interview rooms is inaccessible because it is 42 inches
above the finished floor.
|
C6
|
6 months
|
6.8c Holding
Cell
| | |
6.8c(1) The
toilet is inaccessible because there no grab bars are provided.
|
SU10
|
6 months
|
6.8c(2) The
toilet is inaccessible because there is insufficient clear floor space and
its centerline is 19 inches from the side wall.
|
SU14
|
6 months
|
6.8c(3) The
lavatory is inaccessible because the bottom edge of the apron is 27.5 inches
above the finished floor.
|
TR11
|
6 months
|
6.8d Men's and
Women's Locker Rooms
| | |
6.8d(1) The
signage provided for each locker room is inaccessible.
|
D26
|
6 months
|
6.8d(2) No
accessible mirror has been provided.
|
TR14
|
6 months
|
6.8d(3) The
soap dispenser in each locker room is inaccessible because it is mounted 43
inches above the finished floor over an obstruction.
|
TR4
|
6 months
|
6.8d(4) The
lavatory is inaccessible in each locker room because the pipes are not
insulated or otherwise configured to protect against contact, and the faucet
hardware requires twisting of the wrist to operate.
|
TR12,
TR10
|
6 months
|
6.8d(5) There
is no accessible stall provided in each locker room.
|
ST15
|
6 months
|
6.8d(6) The
transfer shower in each locker room is inaccessible because the seat is not
mounted on the wall opposite the controls, the controls are not within 18
inches of the centerline on the open side, the grab bars are mounted at 32
inches above the finished floor, and the distance between the grab bars and
the wall is 3 inches.
|
B8, B9
|
6 months
|
6.8d(7) There
is no accessible locker provided in either locker room.
|
LR3
|
6 months
|
6.8d(8) The
benches in each locker room are not accessible because they are less than 24
inches wide.
|
LR1
|
6 months
|
6.8d(9) The
drinking fountain within each locker room has a spout that is 47.25 inches
above the finished floor.
|
DF1
|
6 months
|
6.8d(10) In
the men's locker room the urinal is inaccessible because the rim of the
urinal is 20.5 inches above the finished floor.
|
TR20
|
6 months
|
6.9 Hall
Door by Room 121
| | |
6.9a The door
by Room 121 is inaccessible because the pressure required to open the door is
15 pounds.
|
D2
|
6 months
|
6.10 Hall Door
by Room 123
| | |
6.10a The door
by Room 123 is inaccessible because the pressure required to open the door is
14 pounds.
|
D2
|
6 months
|
6.11 Drinking
Fountain in Alcove
| | |
6.11a The
drinking fountain is inaccessible because the clear floor space is 28 inches
wide, the knee clearance is 20 inches high, and the spout is more than 36
inches above the finished floor.
|
DF1
|
6 months
|
6.12 Ramp to
Police Area Front Desk
| | |
6.12a The ramp
is inaccessible because the handrails are 32 inches wide and the clear floor
space at the top of the ramp is blocked by objects.
|
R5
|
6 months
|
7. Kings
Park Regional Library
9000 Burke Lake Road
Burke, VA 22105
| | |
7.1 Exterior
Book Drop
| | |
7.1a The book
drop is inaccessible because the highest operable part is 56.5 inches above
the finished floor.
|
TR5
|
6 months
|
7.2 Library
| | |
7.2a The
tables in the library are inaccessible because they provide 26 inches of knee
space height.
|
T1
|
6 months
|
7.3 Meeting
Room
| | |
7.3a The door
is accessible because the pressure required to open the door is 7 pounds.
|
D2
|
6 months
|
7.4 Quiet
Study Room
| | |
7.4a The door
is inaccessible because the pressure required to open the door is 10 pounds.
|
D2
|
6 months
|
7.4b The pull
side of the door, which is accessed through a front approach, is inaccessible
because it has less than 18 inches of clearance on the latch side of the
door.
|
D6
|
6 months
|
7.5 Drinking
Fountain near Toilet Rooms
| | |
7.5a The
walkway is inaccessible because the higher drinking fountain protrudes into
the walkway and would not be detectable to a blind person using a cane.
|
AR8
|
6 months
|
7.6 Men's
and Women's Toilet Rooms
| | |
7.6a The door
to each toilet room is inaccessible because the pressure required to open the
doors is 10 pounds.
|
D2
|
6 months
|
7.6b The
lavatory in the women's toilet room is inaccessible because the hot water
pipes are not insulated or otherwise configured to protect against contact.
|
TR12
|
6 months
|
8. Adult
Detention Center
10520 Judicial Drive
Fairfax, VA 22030
| | |
8.1 Parking
and Accessible Route
| | |
8.1a This
area was under construction during the time of the Department's site visit.
|
P3
|
6 months
|
8.2 Entrance
Lobby
| | |
8.2a Drinking
Fountain
| | |
8.2a(1) Although
a lower drinking fountain is provided, there is no drinking fountain provided
for people who have difficulty bending or stooping.
|
DF3
|
6 months
|
8.2a(2) The
drinking fountain protrudes into the walkway and would not be detectable to a
blind person using a cane.
|
AR8
|
6 months
|
8.3 Elevator
| | |
8.3a The
elevator is inaccessible because, although emergency communications are
provided, it does not work without voice communication.
|
E8
|
6 months
|
8.4 West Building
Secured Areas (New Construction)
| | |
8.4a Day Room
Single User Toilet Rooms
| | |
8.4a(1) The
toilet rooms are inaccessible because they have knob hardware.
|
D1
|
6 months
|
8.4a(2) No
accessible mirrors have been provided.
|
TR14
|
6 months
|
8.4a(3) The
lavatories are inaccessible because the bottom edge of the lavatory aprons
are 27.5 inches above the finished floor.
|
TR11
|
6 months
|
8.4a(4) The
rear grab bars are inaccessible because they are 32 inches in length.
|
SU3
|
6 months
|
8.4b Housing
Units
| | |
8.4b(1) An
inadequate number of housing units (cells) are accessible.
|
PJ4
|
6 months
|
8.4b(2) Designated
Accessible Cells
| | |
(a) No
accessible coat hook has been provided.
|
TR1
|
6 months
|
(b) No
accessible mirror has been provided.
|
TR14
|
6 months
|
(c) The
rear grab bar is inaccessible because it is less than 36 inches in length,
the space between the grab bar and the wall is more than 1.5 inches, and it
is not configured to comply with the Standards.
|
SU2
|
6 months
|
(d) The
side grab bar is inaccessible because it is more than 1.5 inches from the
side wall, the effective use area is approximately 32 inches in length, and
it is not configured to comply with the Standards.
|
SU5
|
6 months
|
(e) The
lavatory is inaccessible because the vertical section of the rear grab bar
impinges on the clear floor space.
|
TR8
|
6 months
|
8.5 Men's
Visitation Area
| | |
8.5a The
non-contact visitation area contains a number of inaccessible elements and is
not accessible to people with disabilities.
|
PJ7
|
6 months
|
8.6 Exterior
Entrance at Judicial Drive (marked Sheriff) (Existing)
| | |
8.6a The
second door in a series is inaccessible because the pressure required to open
the door is more than 5 pounds.
|
D2
|
6 months
|
8.7 Lobby at
Judicial Drive Entrance
| | |
8.7a Drinking
Fountain
| | |
8.7a(1) The
drinking fountain is inaccessible because it requires more than 5 pounds of
force to operate and its spout is 40 inches above the finished floor.
|
DF1
|
6 months
|
8.7a(2) The
drinking fountain protrudes into the walkway and would not be detectable to a
blind person using a cane.
|
AR8
|
6 months
|
8.7a(3) Although
a lower fountain is provided, there is no drinking fountain provided for
people who have difficulty bending or stooping.
|
DF3
|
6 months
|
8.7b Women's
Toilet Room with Stalls
| | |
8.7b(1) The
toilet room signage is inaccessible because it is mounted on the door.
|
TR17
|
6 months
|
8.7b(2) The
door is inaccessible because it has knob hardware.
|
D1
|
6 months
|
8.7b(3) No
accessible mirror has been provided.
|
TR14
|
6 months
|
8.7b(4) The
toilet stall is inaccessible because the clear floor space measures 53 inches
wide and 59 inches deep.
|
ST16
|
6 months
|
8.7b(5) The
toilet is inaccessible because the centerline is 20.5 inches from the side
wall.
|
ST17
|
6 months
|
8.7b(6) The
toilet paper dispenser is inaccessible because it is mounted 38.5 inches from
the rear wall and above the grab bar.
|
ST19
|
6 months
|
8.7b(7) The
side grab bar is inaccessible because it is mounted with the far end 46.5
inches from the rear wall.
|
ST7
|
6 months
|
8.7b(8) No
accessible coat hook has been provided.
|
TR1
|
6 months
|
8.7b(9) The
lavatory is inaccessible because the hot water pipes are not insulated or
otherwise configured to protect against contact.
|
TR12
|
6 months
|
8.7b(10) The
walkway is inaccessible because the paper towel dispenser protrudes into the
walkway and would not be detectable to a blind person using a cane.
|
AR8
|
6 months
|
8.7c Men's
Toilet Room with Stalls
| | |
8.7c(1) The
toilet room signage is inaccessible because it is mounted on the door.
|
TR17
|
6 months
|
8.7c(2) The
door is inaccessible because it has knob hardware.
|
D1
|
6 months
|
8.7c(3) No
accessible mirror has been provided.
|
TR14
|
6 months
|
8.7c(4) The
urinal is inaccessible because the rim is 25 inches above the finished floor,
the clear floor space is 29 inches wide, and the flush control is 53.5 inches
above the finished floor.
|
TR20
|
6 months
|
8.7c(5) The
toilet is inaccessible because the centerline is 15 inches from the side
wall.
|
ST17
|
6 months
|
8.7c(6) The
toilet paper dispenser is inaccessible because it is mounted 41 inches from
the rear wall and above the grab bar.
|
ST19
|
6 months
|
8.7c(7) The
side grab bar is inaccessible because it is mounted with the far end 47.5
inches from the rear wall.
|
ST7
|
6 months
|
8.7c(8) The
lavatory is inaccessible because the hot water pipes are not insulated or
otherwise configured to protect against contact.
|
TR12
|
6 months
|
8.8 Lobby of
Alternative Incarceration Branch
| | |
8.8a Single
User Women's Toilet Room
| | |
8.8a(1) The
toilet room signage is inaccessible because there is no International Symbol
of Accessibility and it is mounted on the door with no Braille and raised
characters.
|
TR17
|
6 months
|
8.8a(2) The
door is inaccessible because the pressure required to open the door is more
than 5 pounds.
|
D2
|
6 months
|
8.8a(3) Although
an audible alarm is provided in this facility, there is no visual alarm
appliance in the toilet room.
|
TR21
|
6 months
|
8.8a(4) The
toilet is inaccessible because the centerline is 23 inches from the side
wall.
|
SU15
|
6 months
|
8.8a(5) The
toilet paper dispenser is inaccessible because it is mounted above the grab
bar.
|
SU17
|
6 months
|
8.8b Single
User Men's Toilet Room
| | |
8.8b(1) The
toilet room signage is inaccessible because there is no International Symbol
of Accessibility and it is mounted on the door with no Braille and raised
characters.
|
TR17
|
6 months
|
8.8b(2) The
door is inaccessible because the pressure required to open the door is more
than 5 pounds.
|
D2
|
6 months
|
8.8b(3) Although
an audible alarm is provided in this facility, there is no visual alarm
appliance in the toilet room.
|
TR21
|
6 months
|
8.8b(4) The
toilet paper dispenser is inaccessible because it is mounted above the grab
bar.
|
SU17
|
6 months
|
8.9 Intake
Area
| | |
8.9a Single
User Men's Toilet Room
| | |
8.9a(1) The
toilet room signage is inaccessible because it lacks the International Symbol
of Accessibility.
|
TR17
|
6 months
|
8.9a(2) No
accessible mirror has been provided.
|
TR14
|
6 months
|
8.9a(3) The
lavatory is inaccessible because the hot water pipes are not insulated or
otherwise configured to protect against contact, the bottom edge of the apron
is 26 inches above the finished floor, and the knee and toe clearances do not
comply with Figure 31 of the Standards.
|
TR9
|
6 months
|
8.9a(4) The
rear grab bar is inaccessible because it is 30 inches in length.
|
SU3
|
6 months
|
8.9a(5) The
toilet flush control is inaccessible because it is mounted on the closed
side.
|
SU1
|
6 months
|
8.9b Single
User Women's Toilet Room
| | |
8.9b(1) The
toilet room signage is inaccessible because it lacks the International Symbol
of Accessibility.
|
TR17
|
6 months
|
8.9b(2) The
door to the toilet room is inaccessible because the front approach clearance
on the pull side includes stairs.
|
D6
|
6 months
|
8.9b(3) No
accessible mirror has been provided.
|
TR14
|
6 months
|
8.9b(4) The
lavatory is inaccessible because the hot water pipes are not insulated or
otherwise configured to protect against contact, the bottom edge of the apron
is 26 inches above the finished floor, and the knee and toe clearances do not
comply with Figure 31 of the Standards.
|
TR9
|
6 months
|
8.9b(5) The
rear grab bar is inaccessible because it is 30 inches in length.
|
SU3
|
6 months
|
8.10 Holding/Intake
Area
| | |
8.10a Transfer
Shower
| | |
8.10a(1) The
shower is inaccessible because it does not have a 48 inch long and 36 inch
wide clear floor space alongside the shower opening and does not have a seat
that extends the full length of the stall, a shower spray unit is not
provided and the shower head is higher than 48 inches above the finished
floor, and the shower controls are higher than 48 inches above the finished
floor.
|
B8,
B11
|
6 months
|
8.11 Diagnostic
and Treatment Holding Area (Existing)
| | |
8.11a The
lavatory is inaccessible because the hot water and drain pipes are not
insulated or otherwise configured to protect against contact.
|
TR12
|
6 months
|
8.11b The
lavatory is inaccessible because it does not have knee and toe clearances that
comply with Figure 31.
|
TR11
|
6 months
|
8.11c The
toilet is not accessible because the centerline is not 18 inches from the
side wall.
|
SU15
|
6 months
|
8.11d The side
grab bar is inaccessible because it is mounted with the closer end more than
12 inches from the rear wall.
|
SU6
|
6 months
|
8.11e There is
no rear grab bar provided.
|
SU2
|
6 months
|
8.11f
The toilet is inaccessible because the mattress blocks the clear floor space
at the toilet.
|
SU16
|
6 months
|
8.12 Women's
Area - Visitation and Holding Area (Existing)
| | |
8.12a Single
User Toilet Room
| | |
8.12a(1) The
toilet room signage is inaccessible because it lacks the International Symbol
of Accessibility.
|
TR17
|
6 months
|
8.12a(2) The
lavatory is inaccessible because the hot water and drain pipes are not
insulated or otherwise configured to protect against contact.
|
TR12
|
6 months
|
8.12a(3) The
lavatory is inaccessible because the knee and toe clearance does not comply
with Figure 31.
|
TR11
|
6 months
|
8.12a(4) The
toilet is inaccessible because the top of the toilet seat is 16 inches above
the finished floor.
|
SU18
|
6 months
|
8.12b Visitation
Room
| | |
8.12b(1) The
door is inaccessible because it has a clear opening width of 29 inches.
|
D25
|
6 months
|
8.12b(2) The
door is inaccessible because it has knob hardware.
|
D1
|
6 months
|
8.12c No
Contact Visitation Area
| | |
8.12c(1) The
visitation area contains a number of inaccessible elements and is not
accessible to people with disabilities.
|
PJ7
|
6 months
|
8.12d Roll-in
Shower
| | |
8.12d(1) The
shower is inaccessible because no shower spray unit is provided and the
shower head is higher than 48 inches above the finished floor.
|
B11
|
6 months
|
8.12d(2) The
shower is inaccessible because there is a curb at the entrance to the shower
that is more than .5 inch.
|
B7
|
6 months
|
8.12e Housing
Area
| | |
8.12e(1) The
door is inaccessible because it has a clear opening width of only 27.5
inches.
|
D25
|
6 months
|
8.12e(2) The
housing area contains a number of inaccessible elements and is not accessible
to people with disabilities.
|
PJ1,
PJ4
|
6 months
|
9. Juvenile
Detention Center
10650 Page Avenue
Fairfax, VA 22030
| | |
9.1 Accessible
Route (New)
| | |
9.1a The
route from the parking lot to the entrance of the facility has a slope
greater than 5%, but has not been constructed as a ramp.
|
AR1
|
6 months
|
9.2 Lobby
(New)
| | |
9.2a The
public pay telephone is inaccessible because a chair obstructs the clear
floor space.
|
TT1
|
6 months
|
9.2b The
magazine display is inaccessible because it is blocked by the couch and out
of reach range for a person in a wheelchair.
|
L1
|
6 months
|
9.2c Men's
Single User Toilet Room
| | |
9.2c(1) The
toilet room signage is inaccessible because it lacks raised characters and
Braille.
|
TR17
|
6 months
|
9.2c(2) No
accessible mirror has been provided.
|
TR14
|
6 months
|
9.2c(3) The
lavatory is inaccessible because the hot water pipes are not insulated or
otherwise configured to protect against contact.
|
TR12
|
6 months
|
9.2c(4) The
seat cover dispenser is inaccessible because the controls are mounted at 55
inches above the finished floor over the toilet.
|
TR4
|
6 months
|
9.2c(5) The
rear grab bar is inaccessible because the flush valve riser interferes with
its use.
|
SU4
|
6 months
|
9.2d Women's
Single User Toilet Room
| | |
9.2d(1) The
toilet room signage is inaccessible because it lacks raised characters and
Braille.
|
TR17
|
6 months
|
9.2d(2) No
accessible mirror has been provided.
|
TR14
|
6 months
|
9.2d(3) The
lavatory is inaccessible because the hot water pipes are not insulated or
otherwise configured to protect against contact.
|
TR12
|
6 months
|
9.2d(4) The
seat cover dispenser is inaccessible because the controls are mounted at 55
inches above the finished floor over the toilet.
|
TR4
|
6 months
|
9.2d(5) The
rear grab bar is inaccessible because the flush valve riser interferes with
its use.
|
SU4
|
6 months
|
9.2d(6) The
paper towel dispenser is inaccessible because the controls are mounted over
the toilet.
|
TR4
|
6 months
|
9.2d(7) The
air dryer is inaccessible because the controls are mounted at 52 inches above
the finished floor over an obstruction.
|
TR4
|
6 months
|
9.2e Drinking
Fountain
| | |
9.2e(1) The
walkway is inaccessible because the higher drinking fountain protrudes into
the walkway and would not be detectable to a blind person using a cane.
|
AR8
|
6 months
|
9.3 Accessible
Route Connecting the East and West Side of the Building (Existing)
| | |
9.3a The
ramp on the route is inaccessible because the handrails are mounted 33 inches
above the ramp surface and there are no handrail extensions.
|
R4
|
6 months
|
9.4 Intake
Area (Existing)
| | |
9.4a Single
User Toilet Room
| | |
9.4a(1) No
accessible mirror has been provided.
|
TR14
|
6 months
|
9.4a(2) The
lavatory is inaccessible because the bottom edge of the apron is 27 inches
above the finished floor and it does not comply with Figure 31.
|
TR11
|
6 months
|
9.4a(3) The
toilet is inaccessible because the centerline is 20 inches from the side
wall.
|
ST17
|
6 months
|
9.4a(4) The
rear grab bar is inaccessible because it is 24.5 inches in length.
|
SU3
|
6 months
|
9.4b Intake
Cell
| | |
9.4b(1) There
is no accessible cell provided.
|
PJ1,
PJ4
|
6 months
|
9.4c Receiving/Holding
Single User Shower Stall
| | |
9.4c(1) The
roll-in shower is inaccessible because it measures 34 inches by 63 inches.
|
B8
|
6 months
|
9.4d Dining
Area
| | |
9.4d(1) The
door is inaccessible because it has knob hardware.
|
D1
|
6 months
|
9.4e Gymnasium
| | |
9.4e(1) The
door is inaccessible because it has knob hardware.
|
D1
|
6 months
|
9.4f Recreation
Yard
| | |
9.4f(1) The
door is inaccessible because it has knob hardware.
|
D1
|
6 months
|
9.5 School
Area (New)
| | |
9.5a First
School Area Single User Toilet Room
| | |
9.5a(1) The
door is inaccessible because the pressure required to open the door is more
than 5 pounds.
|
D2
|
6 months
|
9.5a(2) No
accessible mirror has been provided.
|
TR14
|
6 months
|
9.5a(3) The
lavatory is inaccessible because the bottom edge of the apron is 28.5 inches
above the finished floor.
|
TR11
|
6 months
|
9.5b Second
School Area Single User Toilet Room
| | |
9.5b(1) The
door is inaccessible because the pressure required to open the door is more
than 5 pounds.
|
D2
|
6 months
|
9.5b(2) No
accessible mirror has been provided.
|
TR14
|
6 months
|
9.5b(3) The
lavatory is inaccessible because the bottom edge of the apron is 28.5 inches
above the finished floor.
|
TR11
|
6 months
|
9.6 Housing
Unit East 11 (New)
| | |
9.6a The
mirrors throughout the facility are inaccessible because the reflecting
surface edge is higher than 40 inches from the finished floor.
|
TR14
|
6 months
|
9.6b Drinking
Fountain
| | |
9.6b(1) The
walkway is inaccessible because the drinking fountain protrudes into the
walkway and would not be detectable to a blind person using a cane.
|
AR8
|
6 months
|
9.6c Accessible
Route to Single User Toilet Room
| | |
9.6c(1) The
stainless steel shelf outside the single user toilet room protrudes into the
walkway and would not be detectable to a blind person using a cane.
|
AR8
|
6 months
|
9.6c(2) The
stainless steel shelf outside the single user toilet room renders the signage
provided inaccessible because a person may not approach within 3 inches of
the sign without encountering a protruding object.
|
D26
|
6 months
|
9.6d Single
User Toilet Room
| | |
9.6d(1) No
accessible mirror has been provided.
|
TR14
|
6 months
|
9.6d(2) The
lavatory is inaccessible because the hot water pipes are not insulated or
otherwise configured to protect against contact.
|
TR12
|
6 months
|
9.6e Shower
Rooms with Transfer Shower Stalls throughout the Facility
| | |
9.6e(1) The
lavatory is inaccessible because the hot water pipes are not insulated or
otherwise configured to protect against contact.
|
TR12
|
6 months
|
9.6e(2) The
shower stall is inaccessible because it is 38 inches wide by 37 inches deep,
the seat does not extend the full depth of the stall, and the short and long
sections of the grab bar is reversed.
|
B8
|
6 months
|
9.6f Designated
Accessible Cells throughout the Facility
| | |
9.6f(1) The
designated accessible cells are not accessible because no accessible mirror
has been provided, the top of the toilet seat is not between 17 and 19 inches
above the finished floor, grab bars are not provided, and the desk/table is
not accessible to people who use wheelchairs.
|
PJ1,
PJ4
|
6 months
|
10. James
Lee Community Center
2855-A Annandale Road
Falls Church, VA 22042
| | |
10.1 Parking
| | |
10.1a Front
Parking Lot
| | |
10.1a(1) The
route from the second and third designated parking spaces next to the
building to the front entrance is inaccessible because the front of the
vehicles parked in the second space will encroach on the width of the
accessible route.
|
AR1
|
6 months
|
10.1b Parking
next to Play Area
| | |
10.1b(1) The
van accessible parking reserved for persons with disabilities lacks the
appropriate signage.
|
P6
|
6 months
|
10.2 Exterior
Front Entrance
| | |
10.2a The
building does not have directional signage posted at inaccessible entrances
and does not have the International Symbol of Accessibility posted at
accessible entrances.
|
D16
|
6 months
|
10.3 First
Floor
| | |
10.3a Drinking
Fountain between Men's and Women's Toilet Rooms
| | |
10.3a(1) The
walkway is inaccessible because the higher drinking fountain in the main
corridor protrudes into the walkway and would not be detectable to a blind
person using a cane.
|
AR8
|
6 months
|
10.3b Men's
Toilet Room with Stalls near Lobby
| | |
10.3b(1) The
toilet paper dispenser is inaccessible because it is mounted 42 inches from
the rear wall.
|
ST19
|
6 months
|
10.3b(2) The
push side of the door to the toilet room, which is accessed from the hinge
side of the door, is inaccessible because it has insufficient maneuvering
space due to the placement of the drinking fountains.
|
D9
|
6 months
|
10.3c Women's
Toilet Room with Stalls near Lobby
| | |
10.3c(1) The
toilet paper dispenser is inaccessible because it is mounted 38.5 inches from
the rear wall.
|
ST19
|
6 months
|
10.3c(2) The
push side of the door to the toilet room, which is accessed from the hinge
side of the door, is inaccessible because it has insufficient maneuvering
space due to the placement of the drinking fountains.
|
D9
|
6 months
|
10.3d Women's
Locker Room
| | |
10.3d(1) The
signage is inaccessible because it lacks the International Symbol of Accessibility.
|
TR17
|
6 months
|
10.3d(2) The
toilet is inaccessible because the flush control is on the closed side.
|
ST2
|
6 months
|
10.3d(3) The
toilet paper dispenser is inaccessible because it is mounted 39 inches from
the rear wall.
|
ST19
|
6 months
|
10.3d(4) The
bench is inaccessible because it is too narrow and it is free-standing.
|
LR1
|
6 months
|
10.3d(5) There
is no accessible locker provided.
|
LR3
|
6 months
|
10.3d(6) The
shower is inaccessible because no shower spray unit is provided.
|
B11
|
6 months
|
10.3e Men's
Locker Room
| | |
10.3e(1) The
signage is inaccessible because it lacks the International Symbol of
Accessibility.
|
TR17
|
6 months
|
10.3e(2) The
toilet paper dispenser is inaccessible because it is mounted 44 inches from
the rear wall.
|
ST19
|
6 months
|
10.3e(3) The
bench is inaccessible because it is too narrow and it is free-standing.
|
LR1
|
6 months
|
10.3e(4) There
is no accessible locker provided.
|
LR3
|
6 months
|
10.3e(5) The
shower is inaccessible because no shower spray unit is provided.
|
B11
|
6 months
|
10.3f Gym/Multipurpose
Room - Room 155
| | |
10.3f(1) White
Drinking Fountain
| | |
(a) The
drinking fountain is inaccessible because the water height is less than 4
inches, the controls are not operable without twisting of the wrist, and it
requires more than 5 lbf to operate.
|
DF1
|
6 months
|
10.3f(2) Stainless
Steel Drinking Fountain
| | |
(a) The
walkway is inaccessible because the drinking fountain protrudes into the
walkway and would not be detectable to a blind person using a cane.
|
AR8
|
6 months
|
(b) The
drinking fountain is inaccessible because the controls require 8 lbf to
operate.
|
DF2
|
6 months
|
10.3g Hallway
(Labeled "Caring Hall")
| | |
10.3g(1) Drinking
Fountain near Room 141
| | |
(a) The
walkway is inaccessible because the drinking fountain protrudes into the
walkway and would not be detectable to a blind person using a cane.
|
AR8
|
6 months
|
10.3g(2) Men's
Toilet Room near Day Care Classrooms
| | |
(a) The
toilet paper dispenser is inaccessible because it is mounted 43 inches from
the rear wall.
|
ST19
|
6 months
|
(b) The
toilet is inaccessible because the centerline is 19.5 inches from the side
wall.
|
ST17
|
6 months
|
(c) No
accessible shower/dressing area coat hook has been provided.
|
TR1
|
6 months
|
(d) The
shower is inaccessible because no shower spray unit is provided.
|
B11
|
6 months
|
10.3g(3) Women's
Toilet Room near Day Care Class Rooms
| | |
(a) The
toilet paper dispenser is inaccessible because it is mounted 45.5 inches from
the rear wall.
|
ST19
|
6 months
|
(b) The
shower is inaccessible because no shower spray unit is provided.
|
B11
|
6 months
|
10.3h Drinking
Fountain near Computer Clubhouse (Room 150)
| | |
10.3h(1) The
walkway is inaccessible because the drinking fountain protrudes into the
walkway and would not be detectable to a blind person using a cane.
|
AR8
|
6 months
|
10.3i Platform
Lift to Second Floor
| | |
10.3i(1) The
lift between the first and second floors is inaccessible because the door to
the area is kept locked, the area near the door is used for storage, and the
same key used to open the door is required to operate the lift.
|
LF2
|
6 months
|
10.4 Second
Floor
| | |
10.4a Community
Theater
| | |
10.4a(1) The
theater containing 224 seats is inaccessible because no wheelchair accessible
seats or companion seats are provided.
|
AA6
|
60months
|
10.4a(2) The
theater lacks fixed aisle seating without armrests.
|
AA2
|
60 months
|
10.4a(3) The
theater is inaccessible to people with hearing impairments because although
there are 224 fixed seats, there are only 3 assistive listening devices.
|
AA5
|
60 months
|
10.4a(4) The
path of travel between the front row of seats and the stage is inaccessible
because it narrows to 16 inches in width near the stage stairs.
|
AR3
|
60 months
|
10.4a(5) There
is no accessible route along the side aisles to the stage because the route
slope is greater than 1:12.
|
AA1
|
60 months
|
10.4a(6) The
lift at the stage is inaccessible because it is obstructed by objects near
its entrance.
|
LF2
|
60 months
|
10.5 Exterior
Amenities
| | |
10.5a Picnic
Area
| | |
10.5a(1) The
picnic tables are inaccessible because none provide the required knee space.
|
PD6
|
6 months
|
10.5b Outdoor
Men's and Women's Toilet Rooms with Stalls
| | |
10.5b(1) The
mens' and women's toilet rooms are inaccessible because a grill obstructs the
entrance to both toilet rooms.
|
AR3
|
6 months
|
10.5b(2) The
toilet room signage to each toilet room is inaccessible because it lacks the
International Symbol of Accessibility.
|
TR17
|
6 months
|
10.5b(3) The
toilet paper dispenser in each toilet room is inaccessible because it is
mounted 42 inches from the rear wall.
|
ST19
|
6 months
|
10.5b(4) The
walkway is inaccessible because the air dryer in each toilet room protrudes
into the walkway and would not be detectable to a blind person using a cane.
|
AR8
|
6 months
|
10.5c Accessible
Route to Ballfields
| | |
10.5c(1) No
accessible route to the ballfields and bleachers is provided.
|
AR1
|
6 months
|
11. Pimmit
Hills Senior Center
7510 Aisle Avenue
Falls Church, VA 22043
| | |
11.1 Parking
- Side Lot
| | |
11.1a The
parking reserved for persons with disabilities is inaccessible because it is
not located on the shortest accessible route to the facility entrance, the
parking spaces and access aisle are not level, there is no designated van
accessible space, and the signage is too low.
|
P3
|
6 months
|
11.2 Parking
- Front Lot
| | |
11.2a The
parking lot is inaccessible because one of the designated accessible parking
spaces lacks an access aisle, and the van accessible parking reserved for
persons with disabilities lacks the appropriate signage.
|
P3
|
6 months
|
11.3 Exterior
Entrance
| | |
11.3a The
door is inaccessible because thumb latch hardware is used.
|
D1
|
6 months
|
11.4 Small
Room near Room 185
| | |
11.4a The
paper towel dispenser is inaccessible because it is obstructed by the table.
|
TR4
|
6 months
|
11.4b The
drinking fountain is not accessible because there is no low fountain.
|
DF3
|
6 months
|
11.4c The
kitchen area sink is inaccessible because it lacks adequate knee clearance.
|
S2
|
6 months
|
11.5 Men's
Toilet Room with Stalls across from Senior Center-Room 185
| | |
11.5a The
door is inaccessible because the pressure required to open the door is 13
pounds.
|
D2
|
6 months
|
11.5b The
lavatory is inaccessible because the height to the bottom edge of the apron
is 28 inches and the pipes are not insulated or otherwise configured to
protect against contact.
|
TR9
|
6 months
|
11.5c The
toilet paper dispenser in the designated accessible stall is inaccessible
because it is mounted 42 inches from the rear wall.
|
ST19
|
6 months
|
11.6 Women's
Toilet Room with Stalls across from Senior Center-Room 185
| | |
11.6a The
door is inaccessible because the pressure required to open the door is 9
pounds.
|
D2
|
6 months
|
11.6b The
pull side of the door, which is accessed through a front approach, is
inaccessible because it has only 7 inches of maneuvering space on the latch
side of the door.
|
D6
|
6 months
|
11.6c The
walkway is inaccessible because the paper towel dispenser protrudes into the
walkway and would not be detectable to a blind person using a cane.
|
AR8
|
6 months
|
11.6d The
lavatory is inaccessible because the height to the bottom edge of the apron
is 28 inches and the pipes are not insulated or otherwise configured to
protect against contact.
|
TR9
|
6 months
|
11.6e The
toilet paper dispenser in the designated accessible stall is inaccessible
because it is mounted 45 inches from the rear wall.
|
ST19
|
6 months
|
12. Bailey's
Community Center
5920 Summers Lane
Falls Church, VA 22041
| | |
12.1 Accessible
Route
| | |
12.1a The
route from the parking lot to the entrance of the facility is inaccessible
because the curb ramp by the designated accessible standard parking space has
a slope of 10.1%; and, the curb ramp by the designated van accessible space
has a slope of 11.9% and flared sides with a slope of 16.7%.
|
AR5
|
6 months
|
12.2 Public
Pay Telephone in Lobby
| | |
12.2a The
walkway is inaccessible because the public pay telephone protrudes into the
walkway and would not be detectable to a blind person using a cane.
|
AR8
|
6 months
|
12.3 Men's
Locker Room- Room 111
| | |
12.3a The
signage is inaccessible because the International Symbol of Accessibility is
mounted on the door.
|
TR17
|
6 months
|
12.3b The
door is inaccessible because the pressure required to open the door is 13
pounds.
|
D2
|
6 months
|
12.3c The
pull side of the door, which is accessed from the hinge side of the door, is
inaccessible because it has only 2 inches of maneuvering space on the latch
side of the door.
|
D8
|
6 months
|
12.3d The
urinal is inaccessible because the flush control is 47 inches above the
finished floor.
|
TR20
|
6 months
|
12.3e No
accessible coat hook has been provided.
|
TR1
|
6 months
|
12.3f The
toilet paper dispenser in the designated accessible stall is inaccessible
because it is mounted 42 inches from the rear wall.
|
ST19
|
6 months
|
12.3g The
transfer shower is inaccessible because the seat does not extend the full
depth of the stall.
|
B10
|
6 months
|
12.3h The
bench is not accessible because it is not wide enough.
|
LR1
|
6 months
|
12.4 Women's
Locker Room-Room 115
| | |
12.4a The
signage is inaccessible because the International Symbol of Accessibility is
mounted on the door.
|
TR17
|
6 months
|
12.4b The
door is inaccessible because the pressure required to open the door is 13
pounds.
|
D2
|
6 months
|
12.4c The
sanitary napkin dispenser is inaccessible because it requires tight grasping
and twisting of the wrist to operate.
|
TR3
|
6 months
|
12.4d No
accessible coat hook has been provided.
|
TR1
|
6 months
|
12.4e The
flush control is inaccessible because it is mounted on the closed side.
|
ST2
|
6 months
|
12.4f The
transfer shower is inaccessible because the seat does not extend the full
depth of the stall.
|
B10
|
6 months
|
12.4g The
bench is inaccessible because it is not wide enough and does not have enough
clear floor space alongside to facilitate a parallel transfer.
|
LR1
|
6 months
|
12.5 Gym
| | |
12.5a The
walkway is inaccessible because the basketball hoop crank located on the wall
protrudes into the walkway and would not be detectable to a blind person
using a cane.
|
AR8
|
6 months
|
12.6 Drinking
Fountain outside Gym by Vending Machines
| | |
12.6a The
drinking fountain is inaccessible because the water flow is 4.5 inches from
the front of the fountain.
|
DF1
|
6 months
|
12.6b The
walkway is inaccessible because the high drinking fountain protrudes into the
walkway and would not be detectable to a blind person using a cane.
|
AR8
|
6 months
|
12.7 Computer
Classroom-Room 106
| | |
12.7a The
computer tables are inaccessible because the knee clearance between the table
legs is 22.5 inches wide.
|
C3
|
6 months
|
12.8 Men's
Single User Toilet Room near Computer Room
| | |
12.8a The
signage is inaccessible because the sign is mounted on the door.
|
TR17
|
6 months
|
12.8b The
door is inaccessible because the pressure required to open the door is 15
pounds.
|
D2
|
6 months
|
12.8c The
toilet is inaccessible because the centerline is 20 inches from the side
wall.
|
SU15
|
6 months
|
12.8d The
toilet paper dispenser is inaccessible because it is mounted 42 inches from
the rear wall.
|
SU17
|
6 months
|
12.9 Women's
Single User Toilet Room near Computer Room
| | |
12.9a The
signage is inaccessible because it is mounted on the door.
|
TR17
|
6 months
|
12.9b The
door is inaccessible because the pressure required to open the door is 17
pounds.
|
D2
|
6 months
|
12.10 Auditorium
#3- Room 105
| | |
12.10a The
auditorium is inaccessible to people with hearing disabilities because it
does not have an assistive listening system.
|
AA5
|
6 months
|
12.10b The
exit from the auditorium is inaccessible because it is blocked by furniture.
|
AR3
|
6 months
|
12.11 Accessible
Route to Outdoor Basketball Court
| | |
12.11a The
route from the parking area adjacent to the Head Start building to the
basketball court is inaccessible because the curb ramps have slopes of 10.3%
and 11%.
|
AR5
|
6 months
|
12.12 Accessible
Route to Tennis Courts
| | |
12.12a The
route to the tennis courts is inaccessible because the surface is not stable,
firm, and slip-resistant.
|
AR1
|
6 months
|
12.13 Accessible
Route to Baseball Field
| | |
12.13a The
route to the baseball field is inaccessible because there is no curb ramp.
|
AR5
|
6 months
|
13. Reston
Community Center - Lake Anne
1609 A Washington Plaza
Reston, VA 20190
| | |
13.1 Route to
Entrance
| | |
13.1a The
route to the entrance is inaccessible because there is a 1-inch vertical
change between the parking lot and the sidewalk.
|
AR1
|
6 months
|
13.2 Public
Pay Telephone inside Entrance
| | |
13.2a The
telephone is inaccessible because the clear floor space is blocked by the
trash receptacle.
|
TT1
|
6 months
|
13.3 Drinking
Fountain between the Counter and the Toilet Rooms
| | |
13.3a The
walkway is inaccessible because the drinking fountain protrudes into the
walkway and would not be detectable to a blind person using a cane.
|
AR8
|
6 months
|
13.4 Kitchen
| | |
13.4a The
clear floor space located in the kitchen at the lavatory is blocked by the
trash receptacles.
|
TR8
|
6 months
|
13.4b The
lavatory is inaccessible because it has hot water and drain pipes that are
not insulated or otherwise configured to protect against contact.
|
TR12
|
6 months
|
13.5 Internal
Route through Building
| | |
13.5a Some
of the signage provided throughout the building is inaccessible because it is
mounted on the hinge side of the door.
|
D26
|
6 months
|
13.6 Art
Studio
| | |
13.6a The
first aid kit located next to the paper towel dispenser is inaccessible
because it is mounted too high above the finished floor.
|
TR5
|
6 months
|
13.6b The
studio sink is inaccessible because it lacks adequate knee clearance.
|
TR11
|
6 months
|
13.7 Women's
Toilet Room with Stalls at the Rear of the Facility on the Main Level
| | |
13.7a The
signage is inaccessible because it is mounted on the door with the centerline
57 inches above the finished floor.
|
TR17
|
6 months
|
13.7b The
door is inaccessible because the pressure required to open the door is 10
pounds.
|
D2
|
6 months
|
13.7c The
lavatory is inaccessible because the pipes are not insulated or otherwise
configured to protect against contact.
|
TR12
|
6 months
|
13.7d Although
an audible alarm is provided in this facility, there is no visual alarm
appliance in the toilet room.
|
TR21
|
6 months
|
13.7e The
toilet is inaccessible because the centerline is 18.5 inches from the side
wall.
|
ST17
|
6 months
|
13.8 Men's
Toilet Room with Stalls at the Rear of the Facility on the Main Level
| | |
13.8a The
signage is inaccessible because it is mounted on the door and the centerline
is not 60 inches above the finished floor.
|
TR17
|
6 months
|
13.8b The
door is inaccessible because the pressure required to open the door is more
than 5 pounds.
|
D2
|
6 months
|
13.8c Although
an audible alarm is provided in this facility, there is no visual alarm
appliance in the toilet room.
|
TR21
|
6 months
|
13.8d The
toilet is inaccessible because the centerline is 18.5 inches from the side
wall.
|
ST17
|
6 months
|
14. Patrick
Henry Library
101 Maple Avenue East
Vienna, VA 22180
| | |
14.1 Parking
| | |
14.1a The
parking reserved for persons with disabilities is inaccessible because the
spaces and access aisles have slopes and cross slopes exceeding 2%.
|
P7
|
6 months
|
14.2 Accessible
Route from Parking Lot to Entrance
| | |
14.2a The
curb ramp next to the building near the front entry is inaccessible because
it has a slope of 11.8% and a cross slope of 3.7%, one of its flared sides
has a slope exceeding 10%, and there is a gap and lip at the bottom of the
curb ramp measuring .75 inches high.
|
AR5
|
6 months
|
14.3 Ramp to
Meeting Room Entrance
| | |
14.3a The
ramp is inaccessible because the landing at the bottom is not level (the
slope is 4.9% and the cross slope is 6.9%), and there is inadequate edge protection.
|
R3
|
6 months
|
14.4 Public
Pay Telephone near Main Entrance
| | |
14.4a The
telephone is inaccessible because its clear floor space slopes 9.3%, the
highest operable part is 63.25 inches above the finished floor, and the phone
does not have volume control.
|
TT1
|
6 months
|
14.5 Book
Deposit at Main Entrance
| | |
14.5a The
book deposit is inaccessible because the clear floor space is not level.
|
TR5
|
6 months
|
14.6 Exterior
Front Entrance Foyer
| | |
14.6a The
walkway is inaccessible because the fire extinguisher in the front foyer
protrudes into the walkway and would not be detectable to a blind person
using a cane.
|
AR8
|
6 months
|
14.7 Magazine
Rack
| | |
14.7a The
magazine rack is inaccessible because its top shelf is 62 inches above the
finished floor.
|
LB1
|
6 months
|
14.8 Women's
Toilet Room with Stalls in Front Foyer
| | |
14.8a The
signage is not accessible because the signage is mounted on the door and its
centerline is 48 inches above the finished floor.
|
TR17
|
6 months
|
14.8b The
door is inaccessible because the pressure required to open the door is 10
pounds
|
D2
|
6 months
|
14.8c The
sanitary napkin dispenser is inaccessible because it requires tight grasping
and twisting of the wrist to operate.
|
TR3
|
6 months
|
14.8d The
toilet is inaccessible because the door swings into the required clear floor
space.
|
ST18
|
6 months
|
14.8e No
accessible coat hook has been provided.
|
TR1
|
6 months
|
14.8f The
rear grab bar is inaccessible because it is mounted with the closer end 12.5
inches from the side wall.
|
ST4
|
6 months
|
14.9 Men's
Toilet Room with Stalls in Front Foyer
| | |
14.9a The
signage is inaccessible because the signage is mounted on the door and its
centerline is 48 inches above the finished floor.
|
TR17
|
6 months
|
14.9b The
door is inaccessible because the pressure required to open the door is 8
pounds.
|
D2
|
6 months
|
14.9c The
toilet is inaccessible because the door swings into the required clear floor
space.
|
ST18
|
6 months
|
14.9d No
accessible coat hook has been provided.
|
TR1
|
6 months
|
14.9e The
side grab bar is inaccessible because it is mounted with the closer end 13
inches from the rear wall.
|
ST7
|
6 months
|
14.9f The
rear grab bar is inaccessible because it is mounted with the closer end 12.5
inches from the side wall.
|
ST4
|
6 months
|
14.10 Drinking Fountain near Toilet Rooms
| | |
14.10a The
walkway is inaccessible because the drinking fountain to the right side of
the men's toilet room protrudes into the walkway and would not be detectable
to a blind person using a cane.
|
AR8
|
6 months
|