Attachment H
Existing Facilities
Please Note: Paragraph 31 of the Settlement Agreement requires that within three months of the effective date of this Agreement, the City provide signage as necessary to comply with 28 C.F.R. § 35.163(b), after having surveyed all facilities that are the subject of this Agreement for the purpose of identifying those that have multiple entrances of which not all are accessible.
1. The technical requirements and, where appropriate, the scoping requirements of the Standards are used as a guide for determining whether a program or activity held in an existing facility is “readily accessible to and usable by” persons with disabilities and for determining what changes are necessary to make this program or activity accessible if it continues to be provided in the existing facility in question. See 28 C.F.R. §§ 35.150(b)(1), 35.151.
2. In order to ensure that each of the County’s programs, services, and activities operating at a facility that is the subject of this Agreement, when viewed in its entirety, are readily accessible to and usable by persons with mobility impairments, the County will take the following actions:
3. Within 9 months of the effective date of this Agreement, the City will complete the following modifications to the Amtrak Train Station, located at 400 West Chapel Hill Street:
a. Although there are 30 parking spaces, there is no van accessible space designated as reserved for persons with disabilities. On the shortest accessible route to the accessible entrance, provide one van accessible space and one standard space designated as reserved for people with disabilities. Van accessible spaces shall be a minimum of 96 inches wide and served by access aisles at least 96 inches wide. All spaces designated as reserved for people with disabilities shall have vertical signs with the International Symbol of Accessibility located such that they cannot be obstructed by parked vehicles. Van accessible spaces shall have an additional “Van-Accessible” sign located below the International Symbol of Accessibility. Standards §§ 4.1.2(5), 4.6, 4.30.7(1).
b. The service counters are inaccessible because they are not accessible to persons in wheelchairs. Provide a counter on an accessible route such that a portion of the counter is at least 36 inches wide and no more than 36 inches above the finished floor, or provide an auxiliary counter with a maximum height of 36 inches in close proximity to the main counter, or provide equivalent facilitation. Equivalent facilitation may be provided in the form of a folding shelf attached to the main counter, an auxiliary table nearby, a clip board made available to the public, or other means. Standards §§ 7.2(2), 4.3.
c. The public telephone is inaccessible because the highest operable part is 56 inches above the finished floor, it has inadequate clear floor space, and it lacks accessible signage. Provide an accessible telephone with a clear floor space of at least 30 inches by 48 inches that allows either a forward or parallel approach by a person using a wheelchair such that bases, enclosures, and fixed seats do not impede approaches to the telephone; with the highest operable part of the telephone mounted no more than 48 inches above the floor for a front approach or no more than 54 inches above the floor for a side approach; that is hearing aid compatible and has a volume control mechanism; with telephone books, if provided, located between 15 and 48 inches above the finished floor for a front approach or between 9 and 54 inches above the finished floor for a side approach; with a cord of at least 29 inches long from the telephone to the handset; and with signage that complies with the Standards. Standards §§ 4.31, 4.30.7(2).
d. Ramps
i. The two single segment ramps are inaccessible because the handrails on the ramp to the front and the ramp to the rear entrances do not comply. Provide handrails that are between 1¼ inches and 1½ inches in diameter with a continuous gripping surface along both sides of each ramp, extending at least 12 inches beyond the top and bottom of each ramp parallel with the ground surface. Ensure that handrails are mounted between 34 inches and 38 inches above each ramp surface, with ends rounded or returned smoothly to the floor, wall, or post, and that they do not rotate within their fittings. Standards § 4.8.5.
e. Toilet Room
i. Men’s Single User Toilet Room
(1) The sign to the toilet room is inaccessible because it is mounted on the door. Provide a toilet room sign with raised and Braille characters. The sign shall be mounted on the wall adjacent to the latch side of the door with the centerline of the sign at 60 inches above the finished floor and situated such that a person can approach within 3 inches of the sign without encountering an obstruction or standing within a door swing. Standards §§ 4.1.2(7)(d), 4.30.1, 4.30.4, 4.30.5, 4.30.6.
(2) The lavatory pipes are not covered or insulated to protect against contact. Provide hot water and drain pipes that are insulated or otherwise configured to protect against contact. Standards § 4.19.4.
(3) The distance of the side grab bar’s farthest end to the rear wall is 52 inches. Provide a side grab bar that is at least 42 inches in overall length, with the far end mounted at least 54 inches from the rear wall and the closer end 12 inches or less from the rear wall. Standards § 4.16.4, Fig. 29(b).
ii. Women’s Single User Toilet Room
(1) The sign to the toilet room is mounted on the door. The sign shall be mounted on the wall adjacent to the latch side of the door with the centerline of the sign at 60 inches above the finished floor and situated such that a person can approach within 3 inches of the sign without encountering an obstruction or standing within a door swing. Standards §§ 4.1.2(7)(d), 4.30.1, 4.30.4, 4.30.5, 4.30.6.
(2) The distance of the side grab bar’s farthest end to the rear wall is 52 inches. Provide a side grab bar that is at least 42 inches in overall length, with the far end mounted at least 54 inches from the rear wall and the closer end 12 inches or less from the rear wall. Standards § 4.16.4, Fig. 29(b).
4. Within 12 months of the effective date of this Agreement, the City will complete the following modifications to the Armory, located at 501 Foster Street:
a. The signage provided through the building is inaccessible. Provide permanent room signage with upper case, sans serif or simple serif type letters and numerals, meeting the requirements of the Standards for character height, raised characters, finish and contrast, accompanied by Grade 2 Braille; mounted on the wall adjacent to the latch side of the door or on the nearest adjacent wall at a height of 60 inches above the finished floor to the centerline of the sign; and located so that a person may approach within 3 inches of the signage without encountering protruding objects or standing within the swing of a door. Standards §§ 4.30.1, 4.30.4, 4.30.5, 4.30.6.
b. Access among levels The route from the first floor to the other floor levels in the building is inaccessible because of steps. Provide at least one accessible route within the boundary of the site connecting these elements that, to the maximum extent feasible, coincides with the route for the general public. The accessible route must have a minimum clear width of 36 inches, or a minimum clear width of 42 inches if there is a turn around an obstruction less than 48 inches wide; have passing spaces at least 60 inches by 60 inches at least every 200 feet; have a minimum clear headroom of 80 inches; have a surface that is firm, stable, and slip resistant; have, in the absence of a curb ramp, ramp, elevator, or platform lift, no level changes in excess of ½ inch vertically; and have a running slope of less than 1:20 (5%) (or have been constructed as a fully accessible ramp) and a cross slope of less than 1:50 (2%). Standards §§ 4.3, 4.5, Fig. 7.
c. The ramp to the front entrance is inaccessible because the handrails are mounted too low and lack extensions. Provide handrails that are between 1¼ inches and 1½ inches in diameter such that the inside handrail is continuous and both handrails have a continuous gripping surface along both sides of the ramp extending at least 12 inches beyond the top and bottom of the ramp parallel with the ground surface; the handrails do not rotate within their fittings; and both handrails are mounted between 34 inches and 38 inches above the ramp surface, with ends rounded or returned smoothly to the floor, wall, or post. Standards § 4.8.5.
d. The counter top at the coat check counter is inaccessible because it is 40 inches above the finished floor. Provide a counter on an accessible route such that a portion of the counter is at least 36 inches wide and no more than 36 inches above the finished floor, or provide an auxiliary counter with a maximum height of 36 inches in close proximity to the main counter, or provide equivalent facilitation. Equivalent facilitation may be provided in the form of a folding shelf attached to the main counter, an auxiliary table nearby, a clip board made available to the public, or other means. Standards §§ 7.2(2), 4.3.
e. Assembly Areas
i. First Floor
(1) There is no accessible route connecting the wheelchair seating areas and the stage. Provide an accessible route connecting the wheelchair seating locations to all spaces used by performers. Standards §§ 4.3, 4.33.5.
(2) The assembly area is inaccessible to people who are deaf or hard of hearing because there is no assistive listening system provided. Provide a permanently installed assistive listening system (ALS) or a portable ALS with an adequate number of electrical outlets or other supplementary wiring necessary to support a portable assistive listening system. Also provide a minimum of 2 receivers for use by the general public and signage indicating their availability. Standards §§ 4.30, 4.33.
ii. Second Floor
(1) The route from the first floor of the armory to the second floor is inaccessible because it is only connected by stairs. Provide at least one accessible route within the boundary of the site connecting these elements that, to the maximum extent feasible, coincides with the route for the general public. The accessible route must have a minimum clear width of 36 inches, or a minimum clear width of 42 inches if there is a turn around an obstruction less than 48 inches wide; have passing spaces at least 60 inches by 60 inches at least every 200 feet; have a minimum clear headroom of 80 inches; have a surface that is firm, stable, and slip resistant; have, in the absence of a curb ramp, ramp, elevator, or platform lift, no level changes in excess of ½ inch vertically; and have a running slope of less than 1:20 (5%) (or have been constructed as a fully accessible ramp) and a cross slope of less than 1:50 (2%). Standards §§ 4.3, 4.5, Fig. 7.
f. Men’s and Women’s Toilet Rooms with Stalls
i. There is no accessible route to the toilet rooms due to steps. Provide an accessible route to the toilet rooms with required minimum width, passing space, head room, surface textures, slopes, and changes in level. Standards §§ 4.3.1, 4.3.2, 4.3.3, 4.3.4, 4.3.5, 4.3.6, 4.3.7, 4.3.8.
ii. The men’s and the women’s toilet rooms contain a number of inaccessible elements and are not accessible to people with disabilities. Provide an accessible toilet room for each gender or provide one unisex toilet room such that all of the room’s elements, including signage, door, door hardware, clear floor space, water closet, stall size and arrangement, stall door, urinal (if provided), grab bars, lavatory, mirror, controls, and dispensers, comply with the Standards. Standards §§ 4.13, 4.16, 4.17, 4.18, 4.19, 4.26, 4.27, 4.30, Fig. 30.
g. Telephone The public telephone in the lobby area is inaccessible because the highest operable part is 60 inches above the finished floor and there is no signage. Provide an accessible telephone with a clear floor space of at least 30 inches by 48 inches that allows either a forward or parallel approach by a person using a wheelchair such that bases, enclosures, and fixed seats do not impede approaches to the telephone; with the highest operable part of the telephone mounted no more than 48 inches above the floor for a front approach or no more than 54 inches above the floor for a side approach; that is hearing aid compatible and has a volume control mechanism; with telephone books, if provided, located between 15 and 48 inches above the finished floor for a front approach or between 9 and 54 inches above the finished floor for a side approach; with a cord of at least 29 inches long from the telephone to the handset; and with signage that complies with the Standards. Standards §§ 4.31, 4.30.7(2).
h. Drinking Fountain Although an accessible drinking fountain is provided, there is no drinking fountain provided for people who have difficulty bending or stooping. Provide a drinking fountain that is accessible to people who have difficulty bending or stooping. This can be accommodated by the use of a “hi-lo” fountain; by providing one fountain accessible to those who use wheelchairs and one fountain at a standard height convenient for those who have difficulty bending; by providing a fountain accessible to people who use wheelchairs and a cup dispenser, or by such other means as would achieve the required accessibility for each group of people. Standards § 4.1.3(10)(a).
5. Within 12 months of the effective date of this Agreement, the City will complete the following modifications to the Arts Council, located at 1200 Morris Street:
a. Parking
i. The parking reserved for persons with disabilities is inaccessible because the parking spaces and access aisles are not level. Provide designated accessible parking spaces and access aisles that are flat and level, with slopes and cross-slopes not exceeding 1:50 in all directions, with surfaces that are firm, stable, and slip-resistant. Standards §§ 4.3.6, 4.5.1, 4.6.3.
b. Entrances
i. Front Entrance
(1) The front entrance is inaccessible because there is a 1⁄2 inch rise at the concrete landing within the door’s required maneuvering clearance. Provide a door so that the floor or ground area within the required clearances is level and clear. Standards § 4.13.6, Fig. 25.
(2) The ramp near the front entrance door is inaccessible because it has a slope of 9.1%; handrails on only one side; and the handrail lacks extensions. Provide a ramp that is at least 36 inches wide with a slope not exceeding 1:12 and a cross slope not exceeding 1:50; with level landings at least as wide as the ramp and 60 inches long at the top and bottom of the ramp; and with edge protection at least 2 inches high at the drop off sides. Provide handrails that are between 1¼ inches and 1½ inches in diameter with a continuous gripping surface along both sides of the ramp, extending at least 12 inches beyond the top and bottom of the ramp parallel with the ground surface. Ensure that handrails are mounted between 34 inches and 38 inches above the ramp surface, with ends rounded or returned smoothly to the floor, wall, or post, and that they do not rotate within their fittings. Ensure that the ramp and approaches are designed so that water will not accumulate on walking surfaces. Standards §§ 4.3.8, 4.8.
ii. Morgan Street Entrance The ramp is inaccessible because it has a slope of 8% and has no handrails. Provide a ramp that is at least 36 inches wide with a slope not exceeding 1:12 and a cross slope not exceeding 1:50; with level landings at least as wide as the ramp and 60 inches long at the top and bottom of the ramp; and with edge protection at least 2 inches high at the drop off sides. Provide handrails that are between 1¼ inches and 1½ inches in diameter with a continuous gripping surface along both sides of the ramp, extending at least 12 inches beyond the top and bottom of the ramp parallel with the ground surface. Ensure that handrails are mounted between 34 inches and 38 inches above the ramp surface, with ends rounded or returned smoothly to the floor, wall, or post, and that they do not rotate within their fittings. Ensure that the ramp and approaches are designed so that water will not accumulate on walking surfaces. Standards §§ 4.3.8, 4.8.
c. Central Carolina Bank Visual Arts Gallery The double doors to the gallery are inaccessible because each leaf’s opening clearance is only 31 inches wide. Provide a door at this location that has at least one active leaf with a clear opening at least 32 inches wide when measured from the face of the door to the middle edge of the other door when one door is opened 90 degrees and that has hardware usable with one hand and without tight grasping, pinching, or twisting of the wrist OR provide an automatic door opener that opens both doors simultaneously. Where no automatic opener is provided, door hardware may be lever-operated, push-type, or a U-shaped handle. Unless an automatic door operator is provided, there must be clear and level maneuvering clearances at the pull side and the push side of the active leaf as indicated in Fig. 25. The doors’ threshold must be ½ inch or less in height and beveled with a slope of no greater than 1:2. If a door closer is provided, it must be set so that the sweep period of the active leaf will, from an open position of 70 degrees, take 3 seconds to move to a point 3 inches from the latch, measured to the leading edge of the door. The active leaf must not take more than 5 pounds of force to open or close. Standards § 4.13, Figs. 24, 25.
d. Rollins Dance Studio
i. There is no accessible permanent room sign posted for this room. Provide a permanent room sign with upper case, sans serif or simple serif type letters and numerals, meeting the requirements of the Standards for character height, raised characters, finish and contrast, accompanied by Grade 2 Braille; mounted on the wall adjacent to the latch side of the door or on the nearest adjacent wall at a height of 60 inches above the finished floor to the centerline of the sign; and located so that a person may approach within 3 inches of the signage without encountering protruding objects or standing within the swing of a door. Standards §§ 4.30.1, 4.30.4, 4.30.5, 4.30.6.
ii. The entrance to the room is inaccessible because it has a 3 inch high threshold at the doorway. Provide a door with a threshold no greater than ¼ inch, or between ¼ inch and ½ inch and beveled with a slope no greater than 1:2. Standards §§ 4.13.8, 4.5.2.
e. Wachovia Dance Studio
i. There is no accessible permanent room sign provided. Provide permanent room signage with upper case, sans serif or simple serif type letters and numerals, meeting the requirements of the Standards for character height, raised characters, finish and contrast, accompanied by Grade 2 Braille; mounted on the wall adjacent to the latch side of the door or on the nearest adjacent wall at a height of 60 inches above the finished floor to the centerline of the sign; and located so that a person may approach within 3 inches of the signage without encountering protruding objects or standing within the swing of a door. Standards §§ 4.30.1, 4.30.4, 4.30.5, 4.30.6.
ii. The entrance to the room is inaccessible because there is a 2 3/4 inch high threshold at the doorway. Provide a door with a threshold no greater than ¼ inch, or between ¼ inch and ½ inch and beveled with a slope no greater than 1:2. Standards §§ 4.13.8, 4.5.2.
f. Routes throughout the facility
i. The ramp to the IBM Rehearsal Hall, Room 008, is inaccessible because a handrail is only provided on one side; lacks handrail extensions; and the ends are not rounded or returned smoothly to the floor. Provide a ramp that is at least 36 inches wide with a slope not exceeding 1:12 and a cross slope not exceeding 1:50; with level landings at least as wide as the ramp and 60 inches long at the top and bottom of the ramp; and with edge protection at least 2 inches high at the drop off sides. Provide handrails that are between 1¼ inches and 1½ inches in diameter with a continuous gripping surface along both sides of the ramp, extending at least 12 inches beyond the top and bottom of the ramp parallel with the ground surface. Ensure that handrails are mounted between 34 inches and 38 inches above the ramp surface, with ends rounded or returned smoothly to the floor, wall, or post, and that they do not rotate within their fittings. Ensure that the ramp and approaches are designed so that water will not accumulate on walking surfaces. Standards §§ 4.3.8, 4.8.
ii. The landing at the doorway is inaccessible because there is a slope greater than 1:12 within the door’s required maneuvering clearance. Provide a door so that the floor or ground area within the required clearances is level and clear. Standards § 4.13.6, Fig. 25.
iii. The ramp near the Little Theater on the ground floor is inaccessible because it lacks handrails. Provide handrails that are between 1¼ inches and 1½ inches in diameter with a continuous smooth gripping surface along both sides of the ramp, extending at least 12 inches beyond the top and bottom of the ramp parallel with the ground surface. Ensure that handrails are mounted between 34 inches and 38 inches above the ramp surface, with ends rounded or returned smoothly to the floor, wall, or post, and that they do not rotate within their fittings. Standards § 4.8.5.
g. Elevator
i. The elevator hall lanterns do not provide both audible and visual signals. Provide hall lanterns at each hoistway entrance that emit a visible and audible signal indicating which car is answering a call. Ensure that audible signals sound once for the up direction and twice for the down direction or have verbal annunciators that say “up” or “down;” and that visible signals are mounted so that their centerline is at least 72 inches above the lobby floor, they are at least 2½ inches in the smallest dimension, and they are visible from the vicinity of the hall call button. Lanterns located in cars, visible from the vicinity of hall call buttons, and conforming to the above requirements, are acceptable. Standards § 4.10.4, Fig. 20.
ii. Although emergency communications are provided, via a dial up telephone, voice communication is required because the dial up telephone requires two hands to operate. Provide a two-way communication system such that it does not require voice communication, the highest operable part is a maximum of 48 inches above the finished floor of the car, and it is identified by a raised symbol and lettering located adjacent to the device. If the system uses a handset, ensure that the length of the cord from the panel to the handset is at least 29 inches. If the system is located in a closed compartment, ensure that the compartment door hardware operates without tight grasping, pinching or twisting of the wrist. Standards § 4.10.14.
h. Drinking Fountains
i. 1st Floor, near women’s toilet room The drinking fountain does not have elements within accessible ranges for persons who are bending or stooping. For each accessible drinking fountain, provide a drinking fountain that is accessible to people who have difficulty bending or stooping. This can be accommodated by the use of a “hi-lo” fountain; by providing one fountain accessible to those who use wheelchairs and one fountain at a standard height convenient for those who have difficulty bending; by providing a fountain accessible to people who use wheelchairs and a cup dispenser; or by such other means as would achieve the required accessibility for each group of people. Standards §§ 4.15, 4.27.4, Fig. 27.
ii. 2nd Floor, near Room 205 The drinking fountain does not have elements within accessible ranges for persons who are bending or stooping. For each accessible drinking fountain, provide a drinking fountain that is accessible to people who have difficulty bending or stooping. This can be accommodated by the use of a “hi-lo” fountain; by providing one fountain accessible to those who use wheelchairs and one fountain at a standard height convenient for those who have difficulty bending; by providing a fountain accessible to people who use wheelchairs and a cup dispenser; or by such other means as would achieve the required accessibility for each group of people. Standards §§ 4.15, 4.27.4, Fig. 27.
i. Toilet Rooms
i. Men’s Toilet Room with Stalls - Ground Floor near IBM Rehearsal Hall
(1) The toilet room sign is mounted on the door. Provide a toilet room sign with the International Symbol of Accessibility and raised and Braille characters. The sign shall be mounted on the wall adjacent to the latch side of the door with the centerline of the sign at 60 inches above the finished floor and situated such that a person can approach within 3 inches of the sign without encountering an obstruction or standing within a door swing. Standards §§ 4.1.2(7)(d), 4.30.1, 4.30.4, 4.30.5, 4.30.6, 4.30.7.
(2) The top of the toilet seat in the designated accessible stall is 16 inches above the finished floor. Provide a toilet with a seat that measures 17 to 19 inches above the finished floor. Standards §§ 4.16.3, 4.17.2, Fig. 30(d).
(3) The side grab bar at the toilet in the designated accessible stall is mounted 28 inches above the finished floor. Provide a grab bar that is mounted between 33 and 36 inches above the finished floor. Standards § 4.17.6, Fig. 30.
(4) The toilet paper dispenser in the designated accessible stall is mounted above the grab bar, impeding upon the usability of the bar. Provide a toilet paper dispenser that is mounted with its top at least 1½ inches under the side grab bar and 36 inches or less from the rear wall and is centered at least 19 inches above the finished floor. Standards § 4.17.3, Fig. 30(d).
(5) There is no rear grab bar provided at the toilet in the designated accessible stall. Provide a rear grab bar that is at least 36 inches in overall length, with the closer end no more than 6 inches from the side wall; mounted 33 to 36 inches above the finished floor; with a diameter between 1¼ and 1½ inches; with 1½ inches between the grab bar and the wall; and at least 1½ inches between the grab bar and any other object, such as a toilet seat cover dispenser. Standards §§ 4.17.6, 4.26.2, Fig. 30.
(6) Although an audible alarm is provided in this facility, there is no visual alarm appliance in the toilet room. Provide a visual alarm appliance in the toilet room. Standards §§ 4.28.1, 4.28.3.
ii. Women’s Toilet Room with Stalls - Ground Floor near IBM Rehearsal Hall
(1) The toilet room sign is mounted on the door. Provide a toilet room sign with the International Symbol of Accessibility and raised and Braille characters. The sign shall be mounted on the wall adjacent to the latch side of the door with the centerline of the sign at 60 inches above the finished floor and situated such that a person can approach within 3 inches of the sign without encountering an obstruction or standing within a door swing. Standards §§ 4.1.2(7)(d), 4.30.1, 4.30.4, 4.30.5, 4.30.6, 4.30.7.
(2) The wall-mounted drinking fountain outside the toilet room is inaccessible because it is encroaching upon the maneuvering clearance required at the doorway. Provide a drinking fountain with clear knee space between the bottom of the apron and the finished floor or ground of at least 27 inches high, 30 inches wide, and 17 to 19 inches deep; and a minimum clear floor space of 30 inches by 48 inches to allow a person in a wheelchair to approach the unit facing forward. Standards § 4.15.5(1), Figs. 27(a), (b).
(3) The top of the toilet seat in the designated accessible stall is 16 inches above the finished floor. Provide a toilet with a seat that measures 17 to 19 inches above the finished floor. Standards §§ 4.16.3, 4.17.2, Fig. 30(d).
(4) The toilet flush control in the designated accessible stall is on the closed side. Provide a flush control mounted on the “open” side of the toilet’s clear floor space; 44 inches or less above the finished floor; and requiring a maximum of 5 pounds of force to operate; or provide an automatic flush device. Standards §§ 4.16.5, 4.17.2, 4.27.4.
(5) The side grab bar at the toilet in the designated accessible stall is mounted 28 inches above the finished floor. Provide grab bars that are mounted between 33 and 36 inches above the finished floor. Standards § 4.17.6, Fig. 30.
(6) The toilet paper dispenser in the designated accessible stall is inaccessible because it is mounted above the grab bar, impeding upon the usability of the bar. Provide a toilet paper dispenser that is mounted with its top at least 1½ inches under the side grab bar and 36 inches or less from the rear wall and is centered at least 19 inches above the finished floor. Standards § 4.17.3, Fig. 30(d).
(7) There is no rear grab bar provided at the toilet in the designated accessible stall. Provide a rear grab bar that is at least 36 inches in overall length, with the closer end no more than 6 inches from the side wall; mounted 33 to 36 inches above the finished floor; with a diameter between 1¼ and 1½ inches; with 1½ inches between the grab bar and the wall; and at least 1½ inches between the grab bar and any other object, such as a toilet seat cover dispenser. Standards §§ 4.17.6, 4.26.2, Fig. 30.
(8) No accessible coat hook is provided. Provide a coat hook at a maximum height above the finished floor of 48 inches for a forward approach or 54 inches for a side approach and that is accompanied by clear floor space of 30 by 48 inches that allows a forward or parallel approach by a person using a wheelchair. Standards §§ 4.25.2, 4.25.3, 4.2.4, 4.2.5, 4.2.6.
(9) Although an audible alarm is provided in this facility, there is no visual alarm appliance in the toilet room. Provide a visual alarm appliance in the toilet room. Standards §§ 4.28.1, 4.28.3.
iii. Men’s Toilet Room with Stalls- 1st Floor
(1) The toilet room sign is mounted on the door. Provide a toilet room sign with the International Symbol of Accessibility and raised and Braille characters. The sign shall be mounted on the wall adjacent to the latch side of the door with the centerline of the sign at 60 inches above the finished floor and situated such that a person can approach within 3 inches of the sign without encountering an obstruction or standing within a door swing. Standards §§ 4.1.2(7)(d), 4.30.1, 4.30.4, 4.30.5, 4.30.6, 4.30.7.
(2) There is no accessible stall provided. Provide a “standard” accessible toilet stall at least 60 inches wide and at least 59 inches deep (or at least 56 inches deep with a wall-mounted toilet) such that all of the stall’s elements, including stall door, stall door hardware, water closet, size and arrangement, toe clearances, grab bars, controls, and dispensers, comply with the Standards. Standards §§ 4.13, 4.16, 4.17, 4.26, 4.27, Fig. 30.
(3) Although an audible alarm is provided in this facility, there is no visual alarm appliance provided in the toilet room. Provide a visual alarm appliance in the toilet room. Standards §§ 4.28.1, 4.28.3.
iv. Women’s Toilet Room with Stalls - 1st Floor
(1) The toilet room sign is mounted on the door. Provide a toilet room sign with the International Symbol of Accessibility and raised and Braille characters. The sign shall be mounted on the wall adjacent to the latch side of the door with the centerline of the sign at 60 inches above the finished floor and situated such that a person can approach within 3 inches of the sign without encountering an obstruction or standing within a door swing. Standards §§ 4.1.2(7)(d), 4.30.1, 4.30.4, 4.30.5, 4.30.6, 4.30.7.
(2) The top rim of the lavatory is 36 inches above the finished floor. Provide a lavatory with the top of its rim or counter 34 inches or less above the finished floor; the bottom edge of the apron at least 29 inches above the finished floor; and knee and toe clearances that comply with Fig. 31. Standards § 4.19.2, Fig. 31.
(3) The toilet paper dispenser in the designated accessible stall is mounted above the side grab bar impeding with the usability of the bar. Provide a toilet paper dispenser that is mounted with its top at least 1½ inches under the side grab bar and 36 inches or less from the rear wall and is centered at least 19 inches above the finished floor. Standards § 4.17.3, Fig. 30(d).
(4) There is no rear grab bar provided at the toilet in the designated accessible stall. Provide a rear grab bar that is at least 36 inches in overall length, with the closer end no more than 6 inches from the side wall; mounted 33 to 36 inches above the finished floor; with a diameter between 1¼ and 1½ inches; with 1½ inches between the grab bar and the wall; and at least 1½ inches between the grab bar and any other object, such as a toilet seat cover dispenser. Standards §§ 4.17.6, 4.26.2, Fig. 30.
(5) Although an audible alarm is provided in this facility, there is no visual alarm appliance provided in the toilet room. Provide a visual alarm appliance in the toilet room. Standards §§ 4.28.1, 4.28.3.
v. Men’s Toilet Room with Stalls - 2nd Floor, Near the People Security Insurance Theater
(1) The toilet room sign is mounted on the door. Provide a toilet room sign with the International Symbol of Accessibility and raised and Braille characters. The sign shall be mounted on the wall adjacent to the latch side of the door with the centerline of the sign at 60 inches above the finished floor and situated such that a person can approach within 3 inches of the sign without encountering an obstruction or standing within a door swing. Standards §§ 4.1.2(7)(d), 4.30.1, 4.30.4, 4.30.5, 4.30.6, 4.30.7.
(2) There is no accessible stall provided. Provide a “standard” accessible toilet stall at least 60 inches wide and at least 59 inches deep (or at least 56 inches deep with a wall-mounted toilet) such that all of the stall’s elements, including stall door, stall door hardware, water closet, size and arrangement, toe clearances, grab bars, controls, and dispensers, comply with the Standards. Standards §§ 4.13, 4.16, 4.17, 4.26, 4.27, Fig. 30.
(3) Although an audible alarm is provided in this facility, there is no visual alarm appliance in the toilet room. Provide a visual alarm appliance in the toilet room. Standards §§ 4.28.1, 4.28.3.
vi. Women’s Toilet Room- 2nd Floor, Near People Security Insurance Theater
(1) The toilet room sign is mounted on the door. Provide a toilet room sign with the International Symbol of Accessibility and raised and Braille characters. The sign shall be mounted on the wall adjacent to the latch side of the door with the centerline of the sign at 60 inches above the finished floor and situated such that a person can approach within 3 inches of the sign without encountering an obstruction or standing within a door swing. Standards §§ 4.1.2(7)(d), 4.30.1, 4.30.4, 4.30.5, 4.30.6, 4.30.7.
(2) There is no accessible stall provided. Provide a “standard” accessible toilet stall at least 60 inches wide and at least 59 inches deep (or at least 56 inches deep with a wall-mounted toilet) such that all of the stall’s elements, including stall door, stall door hardware, water closet, size and arrangement, toe clearances, grab bars, controls, and dispensers, comply with the Standards. Standards §§ 4.13, 4.16, 4.17, 4.26, 4.27, Fig. 30.
(3) Although an audible alarm is provided in this facility, there is no visual alarm appliance in the toilet room. Provide a visual alarm appliance in the toilet room. Standards §§ 4.28.1, 4.28.3.
j. Dressing Rooms
i. Boy’s Toilet Room with Stalls - Near the Little Theater There is no signage directing people with disabilities to the accessible toilet rooms. Provide accessible directional signage with the International Symbol of Accessibility at inaccessible toilet rooms indicating the location of the nearest accessible toilet room, and provide accessible signage with the International Symbol of Accessibility at all accessible toilet rooms. Standards §§ 4.1.2(7)(d), 4.1.6(3)(e)(iii), 4.30.1, 4.30.2, 4.30.3, 4.30.5, 4.30.7.
ii. Girl’s Toilet Room with Stalls - Near the Little Theater There is no signage directing people with disabilities to the accessible toilet rooms. Provide accessible directional signage with the International Symbol of Accessibility at inaccessible toilet rooms indicating the location of the nearest accessible toilet room, and provide accessible signage with the International Symbol of Accessibility at all accessible toilet rooms. Standards §§ 4.1.2(7)(d), 4.1.6(3)(e)(iii), 4.30.1, 4.30.2, 4.30.3, 4.30.5, 4.30.7.
iii. Single-User Men’s Dressing/ Toilet Room - Lower Level, Young People’s Theater
(1) No accessible sign is provided. Provide a toilet room sign with the International Symbol of Accessibility and raised and Braille characters. The sign shall be mounted on the wall adjacent to the latch side of the door with the centerline of the sign at 60 inches above the finished floor and situated such that a person can approach within 3 inches of the sign without encountering an obstruction or standing within a door swing. Standards §§ 4.1.2(7)(d), 4.30.1, 4.30.4, 4.30.5, 4.30.6, 4.30.7.
(2) No accessible mirror has been provided. Provide a mirror with the bottom edge of its reflecting surface no more than 40 inches above the finished floor. Standards § 4.19.6.
(3) The door has twist style hardware. Provide a door with hardware usable with one hand and without tight grasping, pinching, or twisting of the wrist. Lever-operated, push-type, and U-shaped handles are acceptable designs. Standards § 4.13.9.
(4) The bottom edge of the dressing table is lower than 27 inches. Provide a table that has clear floor space that is 30 inches wide and 48 inches deep, knee clearance at least 27 inches high, 30 inches wide, and 19 inches deep, and a writing surface between 28 and 34 inches above the finished floor. Standards §§ 4.2.4.1, 4.32.
(5) The shower stall is 36 ½ inches by 35 inches; has twist style hardware; lacks a hand held shower unit; and the shower head is not adjustable. Provide a shower in this room that is exactly 36 inches wide and 36 inches deep with a 48 inch long and 36 inch wide clear floor space alongside the shower opening, and an L-shaped shower seat mounted on the wall opposite the controls and extending the full depth of the stall; OR a shower that is at least 30 inches deep and 60 inches wide with no curb or threshold and with a 36 inch deep and 60 inch wide clear floor space at the shower opening. Ensure that the shower has grab bars, controls, a shower spray unit, and a seat, curb, and enclosure, if provided, that comply fully with the Standards and with Figs. 35, 36, and 37, as applicable. Standards § 4.21, Figs. 35, 36, 37.
(6) The lavatory is inaccessible because its counter top is 36 ½ inches above the floor and lacks knee space clearance. Provide a lavatory with the top of its rim or counter 34 inches or less above the finished floor; the bottom edge of the apron at least 29 inches above the finished floor; knee and toe clearances that comply with Fig. 31; hot water and drain pipes covered or otherwise configured to protect against contact; clear floor space at least 30 inches wide and 48 inches deep centered on the lavatory; and a faucet that can be operated with 5 pounds of force or less and can be used with one hand and without tight grasping, pinching, or twisting of the wrist (lever-operated, push-type, and electronically controlled mechanisms are examples of acceptable designs). Standards §§ 4.19.2, 4.19.3, 4.19.4, 4.19.5, 4.27.4, Figs. 31, 32.
(7) The toilet is totally inaccessible. Provide a toilet with a centerline that is 18 inches from the near side wall; a seat that is between17 and 19 inches above the finished floor; clear floor space at the toilet that complies with Fig. 28; and a flush control mounted on the “open” side of the toilet’s clear floor space. Standards §§ 4.16.2, 4.16.3, 4.16.5, Figs. 28, 29, 32.
(8) The coat hook is not accessible. Provide a coat hook at a maximum height above the finished floor of 48 inches for a forward approach or 54 inches for a side approach and that is accompanied by clear floor space of 30 by 48 inches that allows a forward or parallel approach by a person using a wheelchair. Standards §§ 4.25.2, 4.25.3, 4.2.4, 4.2.5, 4.2.6.
(9) Although an audible alarm is provided in this facility, there is no visual alarm appliance in the toilet room. Provide a visual alarm appliance in the toilet room. Standards §§ 4.28.1, 4.28.3.
iv. Single -User, Women’s Dressing/ Toilet Room - Lower Level, Young People’s Theater
(1) No accessible signage is provided. Provide a toilet room sign with the International Symbol of Accessibility and raised and Braille characters. The sign shall be mounted on the wall adjacent to the latch side of the door with the centerline of the sign at 60 inches above the finished floor and situated such that a person can approach within 3 inches of the sign without encountering an obstruction or standing within a door swing. Standards §§ 4.1.2(7)(d), 4.30.1, 4.30.4, 4.30.5, 4.30.6, 4.30.7.
(2) The door has twist style hardware. Provide a door with hardware usable with one hand and without tight grasping, pinching, or twisting of the wrist. Lever-operated, push-type, and U-shaped handles are acceptable designs. Standards § 4.13.9.
(3) The bottom edge of the dressing table is lower than 27 inches. Provide a table that has clear floor space that is 30 inches wide and 48 inches deep, knee clearance at least 27 inches high, 30 inches wide, and 19 inches deep, and a writing surface between 28 and 34 inches above the finished floor. Standards §§ 4.2.4.1, 4.32.
(4) The shower stall is 36 ½ inches by 35 inches; has twist style hardware; lacks a hand held shower unit; and the shower head is not adjustable. Provide a shower in this room that is exactly 36 inches wide and 36 inches deep with a 48 inch long and 36 inch wide clear floor space alongside the shower opening, and an L-shaped shower seat mounted on the wall opposite the controls and extending the full depth of the stall; OR a shower that is at least 30 inches deep and 60 inches wide with no curb or threshold and with a 36 inch deep and 60 inch wide clear floor space at the shower opening. Ensure that the shower has grab bars, controls, a shower spray unit, and a seat, curb, and enclosure, if provided, that comply fully with the Standards and with Figs. 35, 36, and 37, as applicable. Standards § 4.21, Figs. 35, 36, 37.
(5) The lavatory is inaccessible because its counter top is 36 ½ inches high above the floor and lacks knee space clearance. Provide a lavatory with the top of its rim or counter 34 inches or less above the finished floor; the bottom edge of the apron at least 29 inches above the finished floor; knee and toe clearances that comply with Fig. 31; hot water and drain pipes covered or otherwise configured to protect against contact; clear floor space at least 30 inches wide and 48 inches deep centered on the lavatory; and a faucet that can be operated with 5 pounds of force or less and can be used with one hand and without tight grasping, pinching, or twisting of the wrist (lever-operated, push-type, and electronically controlled mechanisms are examples of acceptable designs). Standards §§ 4.19.2, 4.19.3, 4.19.4, 4.19.5, 4.27.4, Figs. 31, 32.
(6) The toilet is totally inaccessible. Provide a toilet with a centerline that is 18 inches from the near side wall; a seat that is between17 and 19 inches above the finished floor; clear floor space at the toilet that complies with Fig. 28; and a flush control mounted on the “open” side of the toilet’s clear floor space. Standards §§ 4.16.2, 4.16.3, 4.16.5, Figs. 28, 29, 32.
(7) The coat hook is not accessible. Provide a coat hook at a maximum height above the finished floor of 48 inches for a forward approach or 54 inches for a side approach and that is accompanied by clear floor space of 30 by 48 inches that allows a forward or parallel approach by a person using a wheelchair. Standards §§ 4.25.2, 4.25.3, 4.2.4, 4.2.5, 4.2.6.
(8) Although an audible alarm is provided in this facility, there is no visual alarm appliance in the toilet room. Provide a visual alarm appliance in the toilet room. Standards §§ 4.28.1, 4.28.3.
6. Within 9 months of the effective date of this Agreement, the City will complete the following modifications to Athletic Park, located at 400 Morris Street:
a. The parking lot contains spaces for up to 50 cars. None of the designated accessible standard spaces contains an access aisle. No designated accessible van parking spaces are provided. And none of the designated accessible standard parking spaces contains the correct signage, pavement markings, or is level. On the shortest accessible route to the accessible entrance, provide one van accessible space and one standard space designated as reserved for people with disabilities. Ensure that standard accessible spaces are a minimum of 96 inches wide and served by access aisles at least 60 inches wide. Ensure that van accessible spaces are a minimum of 96 inches wide and served by access aisles at least 96 inches wide. At all spaces designated as reserved for persons with disabilities, provide vertical signs with the International Symbol of Accessibility located such that they cannot be obstructed by parked vehicles. At van accessible spaces, provide an additional “Van-Accessible” sign located below the International Symbol of Accessibility. Ensure that all spaces and access aisles for persons with disabilities are flat and level, with slopes and cross-slopes not exceeding 1:50 in all directions, and that their surfaces are firm, stable, and slip-resistant. Standards §§ 4.1.2(5), 4.6, 4.30.7(1).
b. Routes to Seating Area
i. From the Parking Lot to Accessible Seating Area
(1) The route is inaccessible because the surface is not level in some portions of the path of travel making it difficult for people with physical disabilities to maneuver. Provide at least one accessible route within the boundary of the site connecting these elements that, to the maximum extent feasible, coincides with the route for the general public. The accessible route must have a minimum clear width of 36 inches, or a minimum clear width of 42 inches if there is a turn around an obstruction less than 48 inches wide; have passing spaces at least 60 inches by 60 inches at least every 200 feet; have a minimum clear headroom of 80 inches; have a surface that is firm, stable, and slip resistant; have, in the absence of a curb ramp, ramp, elevator, or platform lift, no level changes in excess of ½ inch vertically; and have a running slope of less than 1:20 (5%) (or have been constructed as a fully accessible ramp) and a cross slope of less than 1:50 (2%). Standards §§ 4.3, 4.5, Fig. 7.
(2) The curb cut is inaccessible because it lacks detectable warnings. Provide a curb ramp that is at least 36 inches wide, has a maximum slope of 1:12, is located so that it cannot be obstructed by parked vehicles, and has a stable, firm, and slip-resistant surface with a detectable warning extending the full width and depth of the ramp. If the curb ramp is located where pedestrians must walk across it, provide either flared sides (with a maximum slope of 1:10) or handrails or guardrails to protect against cross traffic. Standards § 4.3.8, 4.7, Fig. 12.
ii. From the Lower Level to the Accessible Seating Area The ramp lacks accessible handrails, and the slope is more than 1:20. Provide handrails that are between 1¼ inches and 1½ inches in diameter with a continuous gripping surface along both sides of the ramp, extending at least 12 inches beyond the top and bottom of the ramp parallel with the ground surface. Ensure that handrails are mounted between 34 inches and 38 inches above the ramp surface, with ends rounded or returned smoothly to the floor, wall, or post, and that they do not rotate within their fittings. Standards § 4.8.5.
iii. Toilet Rooms
(1) Men’s Toilet Room with Stalls - Ground Level Exterior
a. The toilet room lacks accessible signage. Provide a toilet room sign with the International Symbol of Accessibility and raised and Braille characters. The sign shall be mounted on the wall adjacent to the latch side of the door with the centerline of the sign at 60 inches above the finished floor and situated such that a person can approach within 3 inches of the sign without encountering an obstruction or standing within a door swing. Standards §§ 4.1.2(7)(d), 4.30.1, 4.30.4, 4.30.5, 4.30.6, 4.30.7.
b. No accessible mirror has been provided. Provide a mirror with the bottom edge of its reflecting surface no more than 40 inches above the finished floor. Standards § 4.19.6.
c. The light switch is mounted at 57 inches above the finished floor. Provide a light switch at a maximum height above the finished floor of 48 inches for a forward approach or 54 inches for a side approach and that is accompanied by clear floor space of 30 by 48 inches that allows a forward or parallel approach by a person using a wheelchair. Standards §§ 4.27.2, 4.27.3, 4.2.4, 4.2.5, 4.2.6.
d. The lavatory’s hot water pipes are not insulated or otherwise configured to protect against contact. Provide hot water and drain pipes that are insulated or otherwise configured to protect against contact. Standards § 4.19.4.
e. The lavatory has a twist style faucet. Provide a lavatory with a faucet that can be operated with 5 pounds of force or less and can be used with one hand and without tight grasping, pinching, or twisting of the wrist (lever-operated, push-type, and electronically controlled mechanisms are examples of acceptable designs). Standards §§ 4.19.5, 4.27.4.
f. There is no accessible stall provided for persons with disabilities. Provide a “standard” accessible toilet stall at least 60 inches wide and at least 59 inches deep (or at least 56 inches deep with a wall-mounted toilet) such that all of the stall’s elements, including stall door, stall door hardware, water closet, size and arrangement, toe clearances, grab bars, controls, and dispensers, comply with the Standards. Standards §§ 4.13, 4.16, 4.17, 4.26, 4.27, Fig. 30.
g. Although there are four urinals provided, none are lowered so that the rim is mounted no higher than 17 inches above the finished floor. Provide a urinal with an elongated rim mounted 17 inches or less above the finished floor, a clear floor space of at least 30 inches wide and 48 inches deep centered on the urinal, and a flush control height of 44 inches or less above the finished floor. Standards §§ 4.18.2, 4.18.3, 4.18.4.
(2) Women’s Toilet Room with Stalls - Ground Level Exterior
a. The toilet room lacks accessible signage. Provide a toilet room sign with the International Symbol of Accessibility and raised and Braille characters. The sign shall be mounted on the wall adjacent to the latch side of the door with the centerline of the sign at 60 inches above the finished floor and situated such that a person can approach within 3 inches of the sign without encountering an obstruction or standing within a door swing. Standards §§ 4.1.2(7)(d), 4.30.1, 4.30.4, 4.30.5, 4.30.6, 4.30.7.
b. The lavatory is inaccessible because the table impedes the lavatory’s clear floor space. Provide a lavatory with clear floor space at least 30 inches wide and 48 inches deep centered on the lavatory. Standards § 4.19.3, Fig. 32.
c. The light switch is mounted at 57 inches above the finished floor. Provide a light switch at a maximum height above the finished floor of 48 inches for a forward approach or 54 inches for a side approach and that is accompanied by clear floor space of 30 by 48 inches that allows a forward or parallel approach by a person using a wheelchair. Standards §§ 4.27.2, 4.27.3, 4.2.4, 4.2.5, 4.2.6.
d. The lavatory has a twist style faucet. Provide a lavatory with a faucet that can be operated with 5 pounds of force or less and can be used with one hand and without tight grasping, pinching, or twisting of the wrist (lever-operated, push-type, and electronically controlled mechanisms are examples of acceptable designs). Standards §§ 4.19.5, 4.27.4.
e. There is no accessible stall provided for persons with disabilities. Provide a “standard” accessible toilet stall at least 60 inches wide and at least 59 inches deep (or at least 56 inches deep with a wall-mounted toilet) such that all of the stall’s elements, including stall door, stall door hardware, water closet, size and arrangement, toe clearances, grab bars, controls, and dispensers, comply with the Standards. Standards §§ 4.13, 4.16, 4.17, 4.26, 4.27, Fig. 30.
iv. Drinking Fountain
(1) At the time of the site visit, the water fountain was not functioning. The City shall confirm that the water fountain meets the following standards. Provide a drinking fountain with a spout height no higher than 36 inches, measured from the finished floor or ground surface to the spout outlet; and a spout located at the front of the unit that directs the water flow in a trajectory that is nearly parallel to the front of the unit and is positioned so the flow of water is within 3 inches of the front edge of the fountain and at least 4 inches high. Ensure that fountain controls are operable with one hand, require 5 lbf or less to operate without tight grasping, pinching, or twisting of the wrist; and are front mounted or side mounted near the front edge. Standards §§ 4.15, 4.27.4, Fig. 27.
(2) Provide a drinking fountain with clear knee space between the bottom of the apron and the finished floor or ground of at least 27 inches high, 30 inches wide, and 17 to 19 inches deep; and a minimum clear floor space of 30 inches by 48 inches to allow a person in a wheelchair to approach the unit facing forward. Standards § 4.15.5(1), Figs. 27(a), (b).
(3) Although an accessible drinking fountain is provided, there is no drinking fountain provided for people who have difficulty bending or stooping. For each accessible drinking fountain, provide a drinking fountain that is accessible to people who have difficulty bending or stooping. This can be accommodated by the use of a “hi-lo” fountain; by providing one fountain accessible to those who use wheelchairs and one fountain at a standard height convenient for those who have difficulty bending; by providing a fountain accessible to people who use wheelchairs and a cup dispenser, or by such other means as would achieve the required accessibility for each group of people. Standards § 4.1.3(10)(a).
7. Within 12 months of the effective date of this Agreement, the City will complete the following modifications to the Beechwood Cemetery Office, located at 3300 Fayetteville Street:
a. Entrance
i. The ramp to the entrance is inaccessible because the degree of slope exceeds 1:12. Provide a ramp that is at least 36 inches wide with a slope not exceeding 1:12 and a cross slope not exceeding 1:50; with level landings at least as wide as the ramp and 60 inches long at the top and bottom of the ramp; and with edge protection at least 2 inches high at the drop off sides. Provide handrails that are between 11⁄4 inches and 11⁄2 inches in diameter with a continuous gripping surface along both sides of the ramp, extending at least 12 inches beyond the top and bottom of the ramp parallel with the ground surface. Ensure that handrails are mounted between 34 inches and 38 inches above the ramp surface, with ends rounded or returned smoothly to the floor, wall, or post, and that they do not rotate within their fittings. Ensure that the ramp and approaches are designed so that water will not accumulate on walking surfaces. Standards §§ 4.3.8, 4.8.
ii. The landing at the doorway is inaccessible because the door swings out into the required maneuvering clearance. Provide a door so that the floor or ground area within the required clearances is level and clear. Standards § 4.13.6, Fig. 25.
b. The height of the threshold at the entrance door exceeds 1/4 inch. Provide a door with a threshold no greater than ¼ inch, or between ¼ inch and ½ inch and beveled with a slope no greater than 1:2. Standards §§ 4.13.8, 4.5.2.
c. The unisex, single-user toilet room is inaccessible to persons with disabilities. Provide an accessible toilet room such that all of the room’s elements, including signage, door, door hardware, clear floor space, water closet, urinal (if provided), grab bars, lavatory, mirror, controls, and dispensers, comply with the Standards. Standards §§ 4.13, 4.16, 4.18, 4.19, 4.26, 4.27, 4.30, Figs. 28, 29.
8. Within 12 months of the effective date of this Agreement, the City will complete the following modifications to the I.R. Holmes Recreation Center, located at 2000 S. Alston Avenue:
a. Although there are 158 parking spaces, there is no van-accessible space and only four standard spaces designated as reserved for persons with disabilities. On the shortest accessible route to the accessible entrance, provide one van accessible space and one additional standard spaces designated as reserved for people with disabilities. Standard accessible spaces shall be a minimum of 96 inches wide and served by access aisles at least 60 inches wide. Van accessible spaces shall be a minimum of 96 inches wide and served by access aisles at least 96 inches wide. All spaces designated as reserved for people with disabilities shall have vertical signs with the International Symbol of Accessibility located such that they cannot be obstructed by parked vehicles. Van accessible spaces shall have an additional “Van-Accessible” sign located below the International Symbol of Accessibility. Standards §§ 4.1.2(5), 4.6, 4.30.7(1).
b. The route from the parking lot to the sidewalk is inaccessible because the curb cuts do not provide a smooth transition from street to sidewalk. Provide a curb ramp that is at least 36 inches wide, has a maximum slope of 1:12, is located so that it cannot be obstructed by parked vehicles, and has a stable, firm, and slip-resistant surface with a detectable warning extending the full width and depth of the ramp. If the curb ramp is located where pedestrians must walk across it, provide either flared sides (with a maximum slope of 1:10) or handrails or guardrails to protect against cross traffic. Standards § 4.3.8, 4.7, Fig. 12.
c. Toilet Rooms
i. Men’s Toilet Room with Stalls - Lower Level
(1) The toilet room lacks an accessible sign. Provide a toilet room sign with the International Symbol of Accessibility and raised and Braille characters. The sign shall be mounted on the wall adjacent to the latch side of the door with the centerline of the sign at 60 inches above the finished floor and situated such that a person can approach within 3 inches of the sign without encountering an obstruction or standing within a door swing. Standards §§ 4.1.2(7)(d), 4.30.1, 4.30.4, 4.30.5, 4.30.6, 4.30.7.
(2) The door, which is accessed through a front approach, has a maneuvering clearance on the latch/pull side of 8½ inches. On the pull side of the door, provide maneuvering clearance at least 60 inches deep and provide a minimum of 18 inches (24 inches is preferred) of maneuvering clearance on the latch side of the door. Standards § 4.13.6, Fig. 25(a).
(3) Although an audible alarm is provided in this facility, there is no visual alarm appliance in the toilet room. Provide a visual alarm appliance in the toilet room. Standards §§ 4.28.1, 4.28.3.
(4) The rim height of the lower urinal designated for persons with disabilities is 19 inches above the finished floor. Provide a urinal with an elongated rim mounted 17 inches or less above the finished floor, a clear floor space of at least 30 inches wide and 48 inches deep centered on the urinal, and a flush control height of 44 inches or less above the finished floor. Standards §§ 4.18.2, 4.18.3, 4.18.4.
(5) Lavatory
a. The top of the rim of the lavatory is 36 inches above the finished floor. Provide a lavatory with the top of its rim or counter 34 inches or less above the finished floor; the bottom edge of the apron at least 29 inches above the finished floor; and knee and toe clearances that comply with Fig. 31. Standards § 4.19.2, Fig. 31.
b. The lavatory hardware requires tight grasping, twisting or turning of the wrist to operate. Provide a lavatory with a faucet that can be operated with 5 pounds of force or less and can be used with one hand and without tight grasping, pinching, or twisting of the wrist (lever-operated, push-type, and electronically controlled mechanisms are examples of acceptable designs). Standards §§ 4.19.5, 4.27.4.
c. The lavatory’s water pipes are not covered or insulated to protect against contact. Provide hot water and drain pipes that are insulated or otherwise configured to protect against contact. Standards § 4.19.4.
(6) There is no accessible standard stall provided for persons with disabilities. Provide a “standard” accessible toilet stall at least 60 inches wide and at least 59 inches deep (or at least 56 inches deep with a wall-mounted toilet) such that all of the stall’s elements, including stall door, stall door hardware, water closet, size and arrangement, toe clearances, grab bars, controls, and dispensers, comply with the Standards. Standards §§ 4.13, 4.16, 4.17, 4.26, 4.27, Fig. 30.
ii. Women’s Toilet Room with Stalls - Lower Level
(1) The toilet room lacks an accessible sign. Provide a toilet room sign with the International Symbol of Accessibility and raised and Braille characters. The sign shall be mounted on the wall adjacent to the latch side of the door with the centerline of the sign at 60 inches above the finished floor and situated such that a person can approach within 3 inches of the sign without encountering an obstruction or standing within a door swing. Standards §§ 4.1.2(7)(d), 4.30.1, 4.30.4, 4.30.5, 4.30.6, 4.30.7.
(2) The paper towel dispenser is not within required reach ranges for a person using a wheelchair. Provide a paper towel dispenser with the controls a maximum height above the finished floor of 48 inches for a forward approach or 54 inches for a side approach and that is accompanied by clear floor space of 30 by 48 inches that allows a forward or parallel approach by a person using a wheelchair. Standards §§ 4.27.2, 4.27.3, 4.2.4, 4.2.5, 4.2.6.
(3) Lavatory
a. The top of the rim of the lavatory is 35½ inches above the finished floor. Provide a lavatory with the top of its rim or counter 34 inches or less above the finished floor; the bottom edge of the apron at least 29 inches above the finished floor; and knee and toe clearances that comply with Fig. 31. Standards § 4.19.2, Fig. 31.
b. The lavatory hardware requires tight grasping, twisting or turning of the wrist to operate. Provide a lavatory with a faucet that can be operated with 5 pounds of force or less and can be used with one hand and without tight grasping, pinching, or twisting of the wrist (lever-operated, push-type, and electronically controlled mechanisms are examples of acceptable designs). Standards §§ 4.19.5, 4.27.4.
c. The lavatory’s water pipes are not covered or insulated to protect against contact. Provide hot water and drain pipes that are insulated or otherwise configured to protect against contact. Standards § 4.19.4.
(4) There is no accessible standard stall provided for persons with disabilities. Provide a “standard” accessible toilet stall at least 60 inches wide and at least 59 inches deep (or at least 56 inches deep with a wall-mounted toilet) such that all of the stall’s elements, including stall door, stall door hardware, water closet, size and arrangement, toe clearances, grab bars, controls, and dispensers, comply with the Standards. Standards §§ 4.13, 4.16, 4.17, 4.26, 4.27, Fig. 30.
iii. Men’s Toilet Room with Stalls - Upper Level
(1) The toilet room lacks an accessible sign. Provide a toilet room sign with the International Symbol of Accessibility and raised and Braille characters. The sign shall be mounted on the wall adjacent to the latch side of the door with the centerline of the sign at 60 inches above the finished floor and situated such that a person can approach within 3 inches of the sign without encountering an obstruction or standing within a door swing. Standards §§ 4.1.2(7)(d), 4.30.1, 4.30.4, 4.30.5, 4.30.6, 4.30.7.
(2) The door, which is accessed through a front approach, has a maneuvering clearance on the latch/pull side that is less than 18 inches. On the pull side of the door, provide maneuvering clearance at least 60 inches deep and provide a minimum of 18 inches (24 inches is preferred) of maneuvering clearance on the latch side of the door. Standards § 4.13.6, Fig. 25(a).
(3) Although an audible alarm is provided in this facility, there is no visual alarm appliance in the toilet room. Provide a visual alarm appliance in the toilet room. Standards §§ 4.28.1, 4.28.3.
(4) The paper towel dispenser is not within required reach ranges for a person using a wheelchair. Provide a paper towel dispenser with the controls a maximum height above the finished floor of 48 inches for a forward approach or 54 inches for a side approach and that is accompanied by clear floor space of 30 by 48 inches that allows a forward or parallel approach by a person using a wheelchair. Standards §§ 4.27.2, 4.27.3, 4.2.4, 4.2.5, 4.2.6.
(5) Lavatory
a. The bottom edge of the lavatory apron is 28 inches above the finished floor. Provide a lavatory with the top of its rim or counter 34 inches or less above the finished floor; the bottom edge of the apron at least 29 inches above the finished floor; and knee and toe clearances that comply with Fig. 31. Standards § 4.19.2, Fig. 31.
b. The lavatory hardware requires tight grasping, twisting or turning of the wrist to operate. Provide a lavatory with a faucet that can be operated with 5 pounds of force or less and can be used with one hand and without tight grasping, pinching, or twisting of the wrist (lever-operated, push-type, and electronically controlled mechanisms are examples of acceptable designs). Standards §§ 4.19.5, 4.27.4.
c. The lavatory’s water pipes are not covered or insulated to protect against contact. Provide hot water and drain pipes that are insulated or otherwise configured to protect against contact. Standards § 4.19.4.
(6) Although one stall is loosely configured as an alternate stall, there is no standard accessible stall designed for wheelchair users provided. Provide a “standard” accessible toilet stall at least 60 inches wide and at least 59 inches deep (or at least 56 inches deep with a wall-mounted toilet) such that all of the stall’s elements, including stall door, stall door hardware, water closet, size and arrangement, toe clearances, grab bars, controls, and dispensers, comply with the Standards. Standards §§ 4.13, 4.16, 4.17, 4.26, 4.27, Fig. 30.
iv. Women’s Toilet Room with Stalls - Upper Level
(1) The toilet room lacks an accessible sign. Provide a toilet room sign with the International Symbol of Accessibility and raised and Braille characters. The sign shall be mounted on the wall adjacent to the latch side of the door with the centerline of the sign at 60 inches above the finished floor and situated such that a person can approach within 3 inches of the sign without encountering an obstruction or standing within a door swing. Standards §§ 4.1.2(7)(d), 4.30.1, 4.30.4, 4.30.5, 4.30.6, 4.30.7.
(2) The door, which is accessed through a front approach, has a maneuvering clearance on the latch/pull side of 8 inches. On the pull side of the door, provide maneuvering clearance at least 60 inches deep and provide a minimum of 18 inches (24 inches is preferred) of maneuvering clearance on the latch side of the door. Standards § 4.13.6, Fig. 25(a).
(3) Although an audible alarm is provided in this facility, there is no visual alarm appliance in the toilet room. Provide a visual alarm appliance in the toilet room. Standards §§ 4.28.1, 4.28.3.
(4) The paper towel dispenser is not within required reach ranges for a person using a wheelchair. Provide a paper towel dispenser with the controls a maximum height above the finished floor of 48 inches for a forward approach or 54 inches for a side approach and that is accompanied by clear floor space of 30 by 48 inches that allows a forward or parallel approach by a person using a wheelchair. Standards §§ 4.27.2, 4.27.3, 4.2.4, 4.2.5, 4.2.6.
(5) Lavatory
a. The bottom edge of the lavatory apron is 27½ inches above the finished floor. Provide a lavatory with the top of its rim or counter 34 inches or less above the finished floor; the bottom edge of the apron at least 29 inches above the finished floor; and knee and toe clearances that comply with Fig. 31. Standards § 4.19.2, Fig. 31.
b. The lavatory hardware requires tight grasping, twisting or turning of the wrist to operate. Provide a lavatory with a faucet that can be operated with 5 pounds of force or less and can be used with one hand and without tight grasping, pinching, or twisting of the wrist (lever-operated, push-type, and electronically controlled mechanisms are examples of acceptable designs). Standards §§ 4.19.5, 4.27.4.
a. The lavatory’s water pipes are not covered or insulated to protect against contact. Provide hot water and drain pipes that are insulated or otherwise configured to protect against contact. Standards § 4.19.4.
(6) Although one stall is loosely configured as an alternate stall, there is no standard accessible stall designated for people who use wheelchairs. Provide a “standard” accessible toilet stall at least 60 inches wide and at least 59 inches deep (or at least 56 inches deep with a wall-mounted toilet) such that all of the stall’s elements, including stall door, stall door hardware, water closet, size and arrangement, toe clearances, grab bars, controls, and dispensers, comply with the Standards. Standards §§ 4.13, 4.16, 4.17, 4.26, 4.27, Fig. 30.
d. Showers
i. Men’s The shower stall is inaccessible because it measures 41 inches deep by 36 inches wide; lacks a transfer seat; and does not have a shower head that can be used as both a fix shower head and a hand held and is not mounted on a vertical bar or adjustable. Provide a shower in this room that is exactly 36 inches wide and 36 inches deep with a 48 inch long and 36 inch wide clear floor space alongside the shower opening, and an L-shaped shower seat mounted on the wall opposite the controls and extending the full depth of the stall; OR a shower that is at least 30 inches deep and 60 inches wide with no curb or threshold and with a 36 inch deep and 60 inch wide clear floor space at the shower opening. Ensure that the shower has grab bars, controls, a shower spray unit, and a seat, curb, and enclosure, if provided, that comply fully with the Standards and with Figs. 35, 36, and 37, as applicable. Standards § 4.21, Figs. 35, 36, 37.
ii. Women’s The shower stall is inaccessible because it measures 41 inches deep by 36 inches wide; lacks a transfer seat; and does not have a shower head that can be used as both a fix shower head and a hand held and is not mounted on a vertical bar or adjustable. Provide a shower in this room that is exactly 36 inches wide and 36 inches deep with a 48 inch long and 36 inch wide clear floor space alongside the shower opening, and an L-shaped shower seat mounted on the wall opposite the controls and extending the full depth of the stall; OR a shower that is at least 30 inches deep and 60 inches wide with no curb or threshold and with a 36 inch deep and 60 inch wide clear floor space at the shower opening. Ensure that the shower has grab bars, controls, a shower spray unit, and a seat, curb, and enclosure, if provided, that comply fully with the Standards and with Figs. 35, 36, and 37, as applicable. Standards § 4.21, Figs. 35, 36, 37.
9. Within 12 months of the effective date of this Agreement, the City will complete the following modifications to Lake Michie, located at 2303 Bahama Road, Bahama, NC.
a. Boathouse
i. Parking The van accessible parking space reserved for persons with disabilities lacks the appropriate signage. At van accessible spaces, provide a “Van-Accessible” sign located below the International Symbol of Accessibility such that the sign cannot be obstructed by vehicles parked in the space. Standards §§ 4.6.4, 4.30.7(1).
ii. Entrance
(1) There is no signage at the entrance directing people with disabilities to the accessible entrance. Provide accessible directional signage with the International Symbol of Accessibility at inaccessible entrances directing users to the accessible entrance, and provide accessible signage with the International Symbol of Accessibility at all permanent accessible entrances. Standards §§ 4.1.3(8)(d), 4.13, 4.30.
(2) Each of the five entrance doors has an opening width of only 29 inches and a 1 ½ inch change in the level at the threshold. Provide three designated accessible entrances with a clear opening of 32 inches with the door open 90 degrees, measured between the face of the door and the opposite stop. Standards § 4.13.5, Fig. 24. Provide an accessible door with a threshold that is no greater than ¼ inch, or is no greater than ½ inch and is beveled with a slope no greater than 1:2. Standards §§ 4.13.8, 4.5.2.
iii. Interior Doors Each door throughout the facility has an opening width of 29 inches. Provide each door with a clear opening of 32 inches with the door open 90 degrees, measured between the face of the door and the opposite stop. Standards § 4.13.5, Fig. 24.
iv. Drinking Fountain The drinking fountain does not have elements within accessible ranges for persons using wheelchairs. Provide at least one drinking fountain with a spout height no higher than 36 inches, measured from the finished floor or ground surface to the spout outlet; and a spout located at the front of the unit that directs the water flow in a trajectory that is nearly parallel to the front of the unit and is positioned so the flow of water is within 3 inches of the front edge of the fountain and at least 4 inches high. Ensure that fountain controls are operable with one hand, require 5 lbf or less to operate without tight grasping, pinching, or twisting of the wrist; and are front mounted or side mounted near the front edge. For each accessible drinking fountain, provide a drinking fountain that is accessible to people who have difficulty bending or stooping. This can be accommodated by the use of a “hi-lo” fountain; by providing one fountain accessible to those who use wheelchairs and one fountain at a standard height convenient for those who have difficulty bending; by providing a fountain accessible to people who use wheelchairs and a cup dispenser; or by such other means as would achieve the required accessibility for each group of people. Standards §§ 4.15, 4.27.4, Fig. 27.
v. Toilet Rooms The men’s and women’s toilet rooms contain a number of inaccessible elements and are not accessible to people with disabilities. Provide one accessible toilet room for each gender or one accessible unisex toilet room such that all of the room’s elements, including signage, door, door hardware, clear floor space, water closet, stall size and arrangement, stall door, urinal (if provided), grab bars, lavatory, mirror, controls, and dispensers, comply with the Standards. Standards §§ 4.13, 4.16, 4.17, 4.18, 4.19, 4.26, 4.27, 4.30, Fig. 30.
b. Little River Fishing Facility
i. Parking
(1) Although the parking lot has a total of 11 parking spaces, it lacks a van accessible space designated as reserved for persons with disabilities. On the shortest accessible route to the accessible entrance, provide one van accessible space a minimum of 96 inches wide, served by access aisles at least 96 inches wide, with vertical signs with the International Symbol of Accessibility located such that they cannot be obstructed by parked vehicles, and with an additional “Van-Accessible” sign located below the International Symbol of Accessibility. Standards §§ 4.1.2(5)(b), 4.6, 4.30.7(1).
(2) The parking space currently designated as reserved for persons with disabilities has an excessive slope of 8.7%. Provide designated accessible parking spaces and access aisles that are flat and level, with slopes and cross-slopes not exceeding 1:50 (2%) in all directions, with surfaces that are firm, stable, and slip-resistant. Standards §§ 4.3.6, 4.5.1, 4.6.3.
(3) The parking lot is inaccessible because there are no access aisles. At each standard accessible space, provide an access aisle at least 60 inches wide. At each van accessible space, provide an access aisles at least 96 inches wide. Ensure that all access aisles are flat and level, with slopes and cross-slopes not exceeding 1:50 in all directions, and that their surfaces are firm, stable, and slip-resistant. Standards §§ 4.1.2(5), 4.6.3, Fig. 9.
ii. Entrance
(1) The route to the front of the building has a slope of 7.8% and a cross slope of 2.7%. Provide at least one accessible route within the boundary of the site connecting these elements that, to the maximum extent feasible, coincides with the route for the general public. The accessible route must have a minimum clear width of 36 inches, or a minimum clear width of 42 inches if there is a turn around an obstruction less than 48 inches wide; have passing spaces at least 60 inches by 60 inches at least every 200 feet; have a minimum clear headroom of 80 inches; have a surface that is firm, stable, and slip resistant; have, in the absence of a curb ramp, ramp, elevator, or platform lift, no level changes in excess of ½ inch vertically; and have a running slope of less than 1:20 (5%) (or have been constructed as a fully accessible ramp) and a cross slope of less than 1:50 (2%). Standards §§ 4.3, 4.5, Fig. 7.
(2) The front entrance has a 3/4 inch change in level at the threshold to the door. Provide an accessible door with a threshold that is no greater than ¼ inch, or is no greater than ½ inch and is beveled with a slope no greater than 1:2. Standards §§ 4.13.8, 4.5.2.
iii. Picnic Area The route along the foot bridge to the picnic area has a step at the end of the bridge where it meets the walkway. Provide at least one accessible route within the boundary of the site connecting these elements that, to the maximum extent feasible, coincides with the route for the general public. The accessible route must have a minimum clear width of 36 inches, or a minimum clear width of 42 inches if there is a turn around an obstruction less than 48 inches wide; have passing spaces at least 60 inches by 60 inches at least every 200 feet; have a minimum clear headroom of 80 inches; have a surface that is firm, stable, and slip resistant; have, in the absence of a curb ramp, ramp, elevator, or platform lift, no level changes in excess of ½ inch vertically; and have a running slope of less than 1:20 (5%) (or have been constructed as a fully accessible ramp) and a cross slope of less than 1:50 (2%). Standards §§ 4.3, 4.5, Fig. 7.
iv. Drinking Fountains
(1) The drinking fountain located on the route to the front of the building protrudes into the path of travel; has a lead edge that is greater than 27 inches above the finished floor; protrudes more than 4 inches into the hallway; and is not cane detectible. Provide a drinking fountain at this location such that its bottom leading edges measure no more than 27 inches above the finished floor or protrude no more than 4 inches into the walkway. Standards § 4.4.
(2) At the fountain located on the side of the building, there is no drinking fountain provided for people who have difficulty bending or stooping. For each accessible drinking fountain, provide a drinking fountain that is accessible to people who have difficulty bending or stooping. This can be accommodated by the use of a “hi-lo” fountain; by providing one fountain accessible to those who use wheelchairs and one fountain at a standard height convenient for those who have difficulty bending; by providing a fountain accessible to people who use wheelchairs and a cup dispenser, or by such other means as would achieve the required accessibility for each group of people. Standards § 4.1.3(10)(a).
v. Toilet Rooms
(1) Men’s Toilet Room-with Stalls
a. The toilet room sign is inaccessible because it is mounted on the door. Provide a toilet room sign with raised and Braille characters. The sign shall be mounted on the wall adjacent to the latch side of the door with the centerline of the sign at 60 inches above the finished floor and situated such that a person can approach within 3 inches of the sign without encountering an obstruction or standing within a door swing. Standards §§ 4.1.2(7)(d), 4.30.1, 4.30.4, 4.30.5, 4.30.6.
b. The lavatory’s hot water pipes are not insulated or otherwise configured to protect against contact. Provide hot water and drain pipes that are insulated or otherwise configured to protect against contact. Standards § 4.19.4.
c. The soap dispenser controls are mounted at 51 ½ inches above the finished floor and over an obstruction. Provide a soap dispenser such that the controls comply with Fig. 5 for a forward reach or with Fig. 6 for a side reach and such that it is accompanied by clear floor space of 30 by 48 inches that allows a forward or parallel approach, respectively, by a person using a wheelchair. Standards §§ 4.27.2, 4.27.3, 4.2.4, 4.2.5, 4.2.6.
d. The paper towel dispenser controls are mounted at 58 inches above the finished floor. Provide a paper towel dispenser with the controls a maximum height above the finished floor of 48 inches for a forward approach or 54 inches for a side approach and that is accompanied by clear floor space of 30 by 48 inches that allows a forward or parallel approach by a person using a wheelchair. Standards §§ 4.27.2, 4.27.3, 4.2.4, 4.2.5, 4.2.6.
e. There is no accessible standard stall provided for persons with disabilities. Provide a “standard” accessible toilet stall at least 60 inches wide and at least 59 inches deep (or at least 56 inches deep with a wall-mounted toilet) such that all of the stall’s elements, including stall door, stall door hardware, water closet, size and arrangement, toe clearances, grab bars, controls, and dispensers, comply with the Standards. Standards §§ 4.13, 4.16, 4.17, 4.26, 4.27, Fig. 30.
f. The rim of the urinal is mounted 24 inches above the finished floor. Provide a urinal with an elongated rim mounted 17 inches or less above the finished floor, a clear floor space of at least 30 inches wide and 48 inches deep centered on the urinal, and a flush control height of 44 inches or less above the finished floor. Standards §§ 4.18.2, 4.18.3, 4.18.4.
(2) Women’s Toilet Room-with Stalls
a. The toilet room sign is inaccessible because it is mounted on the door. Provide a toilet room sign with raised and Braille characters. The sign shall be mounted on the wall adjacent to the latch side of the door with the centerline of the sign at 60 inches above the finished floor and situated such that a person can approach within 3 inches of the sign without encountering an obstruction or standing within a door swing. Standards §§ 4.1.2(7)(d), 4.30.1, 4.30.4, 4.30.5, 4.30.6.
b. The lavatory’s hot water pipes are not insulated or otherwise configured to protect against contact. Provide hot water and drain pipes that are insulated or otherwise configured to protect against contact. Standards § 4.19.4.
c. The soap dispenser controls are mounted at 51 inches above the finished floor over an obstruction. Provide a soap dispenser such that the controls comply with Fig. 5 for a forward reach or with Fig. 6 for a side reach and such that it is accompanied by clear floor space of 30 by 48 inches that allows a forward or parallel approach, respectively, by a person using a wheelchair. Standards §§ 4.27.2, 4.27.3, 4.2.4, 4.2.5, 4.2.6.
d. The paper towel dispenser controls are mounted at 58 inches above the finished floor. Provide a paper towel dispenser with the controls a maximum height above the finished floor of 48 inches for a forward approach or 54 inches for a side approach and that is accompanied by clear floor space of 30 by 48 inches that allows a forward or parallel approach by a person using a wheelchair. Standards §§ 4.27.2, 4.27.3, 4.2.4, 4.2.5, 4.2.6.
e. There is no accessible standard stall provided for persons with disabilities. Provide a “standard” accessible toilet stall at least 60 inches wide and at least 59 inches deep (or at least 56 inches deep with a wall-mounted toilet) such that all of the stall’s elements, including stall door, stall door hardware, water closet, size and arrangement, toe clearances, grab bars, controls, and dispensers, comply with the Standards. Standards §§ 4.13, 4.16, 4.17, 4.26, 4.27, Fig. 30.
c. Spruce Pine Lodge
i. The Lodge is inaccessible in all aspects, including parking, accessible routes, ramps, entrances, and toilet rooms. Provide parking, accessible routes, ramps, entrances, toilet rooms, and other elements in the Lodge that comply with the Standards. Standards §§ 4.1, 4.3, 4.6, 4.8, 4.14, 4.15, 4.22, 4.30, and 4.31.
10. Within 6 months of the effective date of this Agreement, the City will complete the following modifications to Police Headquarters, located at 505 Chapel Hill Street:
a. Parking Although the parking lot has a total of 236 parking spaces, no van accessible space designated as reserved for people with disabilities is provided. On the shortest accessible route to the accessible entrance, provide at least one van accessible space reserved for people with disabilities. Van accessible spaces shall be a minimum of 96 inches wide and served by access aisles at least 96 inches wide. All spaces designated as reserved for people with disabilities shall have vertical signs with the International Symbol of Accessibility located such that they cannot be obstructed by parked vehicles. Van accessible spaces shall have an additional “Van-Accessible” sign located below the International Symbol of Accessibility. Standards §§ 4.1.2(5), 4.6, 4.30.7(1).
b. The ramp at the front entrance door is inaccessible because the handrail ends are not rounded. Provide handrails that are between 1¼ inches and 1½ inches in diameter with a continuous gripping surface along both sides of the ramp, extending at least 12 inches beyond the top and bottom of the ramp parallel with the ground surface. Ensure that handrails are mounted between 34 inches and 38 inches above the ramp surface, with ends rounded or returned smoothly to the floor, wall, or post, and that they do not rotate within their fittings. Standards § 4.8.5.
c. Toilet Rooms
i. Men’s Toilet Room with Stalls - 1st Floor
(1) The toilet room lacks an accessible sign. Provide a toilet room sign with the International Symbol of Accessibility and raised and Braille characters. The sign shall be mounted on the wall adjacent to the latch side of the door with the centerline of the sign at 60 inches above the finished floor and situated such that a person can approach within 3 inches of the sign without encountering an obstruction or standing within a door swing. Standards §§ 4.1.2(7)(d), 4.30.1, 4.30.4, 4.30.5, 4.30.6, 4.30.7.
(2) The lavatory’s hot water pipes are not insulated or otherwise configured to protect against contact. Provide hot water and drain pipes that are insulated or otherwise configured to protect against contact. Standards § 4.19.4.
(3) There is no rear grab bar provided at the toilet in the designated accessible stall. Provide a rear grab bar that is at least 36 inches in overall length, with the closer end no more than 6 inches from the side wall; mounted 33 to 36 inches above the finished floor; with a diameter between 1¼ and 1½ inches; with 1½ inches between the grab bar and the wall; and at least 1½ inches between the grab bar and any other object, such as a toilet seat cover dispenser. Standards §§ 4.17.6, 4.26.2, Fig. 30.
(4) No accessible coat hook has been provided. Provide a coat hook at a maximum height above the finished floor of 48 inches for a forward approach or 54 inches for a side approach and that is accompanied by clear floor space of 30 by 48 inches that allows a forward or parallel approach by a person using a wheelchair. Standards §§ 4.25.2, 4.25.3, 4.2.4, 4.2.5, 4.2.6.
(5) Although an audible alarm is provided in this facility, there is no visual alarm appliance provided in the toilet room. Provide a visual alarm appliance in the toilet room. Standards §§ 4.28.1, 4.28.3.
ii. Women’s Room with Stalls - 1st Floor
(1) The toilet room lacks an accessible sign. Provide a toilet room sign with the International Symbol of Accessibility and raised and Braille characters. The sign shall be mounted on the wall adjacent to the latch side of the door with the centerline of the sign at 60 inches above the finished floor and situated such that a person can approach within 3 inches of the sign without encountering an obstruction or standing within a door swing. Standards §§ 4.1.2(7)(d), 4.30.1, 4.30.4, 4.30.5, 4.30.6, 4.30.7.
(2) The lavatory’s hot water pipes are not insulated or otherwise configured to protect against contact. Provide hot water and drain pipes that are insulated or otherwise configured to protect against contact. Standards § 4.19.4.
(3) The sanitary napkin dispenser controls are mounted at 57 inches above the finished floor. Provide a sanitary napkin dispenser with the controls a maximum height above the finished floor of 48 inches for a forward approach or 54 inches for a side approach and that is accompanied by clear floor space of 30 by 48 inches that allows a forward or parallel approach by a person using a wheelchair. Standards §§ 4.27.2, 4.27.3, 4.2.4, 4.2.5, 4.2.6.
(4) The toilet centerline in the designated accessible stall measures 12 ½ inches from the side wall. Provide a toilet with a centerline that measures 18 inches from the near side wall. Standards § 4.17.3, Fig. 30.
(5) The top of the toilet seat in the designated accessible stall is 16 inches above the finished floor. Provide a toilet with a seat that measures 17 to 19 inches above the finished floor. Standards §§ 4.16.3, 4.17.2, Fig. 30(d).
(6) The toilet flush control in the designated accessible stall is on the closed side. Provide a flush control mounted on the “open” side of the toilet’s clear floor space; 44 inches or less above the finished floor; and requiring a maximum of 5 pounds of force to operate; or provide an automatic flush device. Standards §§ 4.16.5, 4.17.2, 4.27.4.
(7) There is no rear grab bar provided at the toilet in the designated accessible stall. Provide a rear grab bar that is at least 36 inches in overall length, with the closer end no more than 6 inches from the side wall; mounted 33 to 36 inches above the finished floor; with a diameter between 1¼ and 1½ inches; with 1½ inches between the grab bar and the wall; and at least 1½ inches between the grab bar and any other object, such as a toilet seat cover dispenser. Standards §§ 4.17.6, 4.26.2, Fig. 30.
(8) No accessible coat hook has been provided. Provide a coat hook at a maximum height above the finished floor of 48 inches for a forward approach or 54 inches for a side approach and that is accompanied by clear floor space of 30 by 48 inches that allows a forward or parallel approach by a person using a wheelchair. Standards §§ 4.25.2, 4.25.3, 4.2.4, 4.2.5, 4.2.6.
(9) Although an audible alarm is provided in this facility, there is no visual alarm appliance provided in the toilet room. Provide a visual alarm appliance in the toilet room. Standards §§ 4.28.1, 4.28.3.
11. Within 6 months of the effective date of this Agreement, the City will complete the following modifications to Valley Springs Park, located at 3805 Valley Springs Road:
a. The parking lot contains spaces for up to 50 cars. No designated van accessible parking space is provided, and the access aisle is not the required size for a van. Ensure that van accessible spaces are a minimum of 96 inches wide and served by access aisles at least 96 inches wide. At all spaces designated as reserved for persons with disabilities, provide vertical signs with the International Symbol of Accessibility located such that they cannot be obstructed by parked vehicles. At van accessible spaces, provide an additional “Van-Accessible” sign located below the International Symbol of Accessibility. Ensure that all spaces and access aisles for persons with disabilities are flat and level, with slopes and cross-slopes not exceeding 1:50 in all directions, and that their surfaces are firm, stable, and slip-resistant. Standards §§ 4.1.2(5), 4.6, 4.30.7(1).
b. The baseball field lacks wheelchair seating at the bleachers. Provide 4 wheelchair seating areas, each with a minimum clear ground or floor space of 66 inches wide by 48 inches deep for forward or rear access, or 66 inches wide by 60 inches deep for side access. Ensure that the ground or floor at all wheelchair locations is level, firm, stable, and slip resistant; that wheelchair seating areas are an integral part of the fixed seating plan and are located so as to provide people with physical disabilities a choice of admission prices and lines of sight comparable to those available for members of the general public; that wheelchair seating areas adjoin an accessible route that also serves as a means of egress in case of emergency; and that at least one fixed companion seat is provided next to each wheelchair seating area. Standards §§ 4.1.3(19)(a), 4.5, 4.33.
c. The service counter at the concession stand is more than 36 inches from the finished floor. Provide a counter on an accessible route such that a portion of the counter is at least 36 inches wide and no more than 36 inches above the finished floor. Standards §§ 7.2(1), 4.3.
d. Toilet Rooms
i. Men’s Toilet Room with Stalls
(1) The lavatory’s hot water pipes are not insulated or otherwise configured to protect against contact. Provide hot water and drain pipes that are insulated or otherwise configured to protect against contact. Standards § 4.19.4.
(2) There is no accessible standard stall provided for persons with disabilities. Provide a “standard” accessible toilet stall at least 60 inches wide and at least 59 inches deep (or at least 56 inches deep with a wall-mounted toilet) such that all of the stall’s elements, including stall door, stall door hardware, water closet, size and arrangement, toe clearances, grab bars, controls, and dispensers, comply with the Standards. Standards §§ 4.13, 4.16, 4.17, 4.26, 4.27, Fig. 30.
ii. Women’s Room with Stalls
(1) The lavatory’s hot water pipes are not insulated or otherwise configured to protect against contact. Provide hot water and drain pipes that are insulated or otherwise configured to protect against contact. Standards § 4.19.4.
(2) There is no accessible standard stall provided for persons with disabilities. Provide a “standard” accessible toilet stall at least 60 inches wide and at least 59 inches deep (or at least 56 inches deep with a wall-mounted toilet) such that all of the stall’s elements, including stall door, stall door hardware, water closet, size and arrangement, toe clearances, grab bars, controls, and dispensers, comply with the Standards. Standards §§ 4.13, 4.16, 4.17, 4.26, 4.27, Fig. 30.
e. Drinking Fountain The drinking fountain does not have elements within accessible ranges for persons using wheelchairs. Provide at least one drinking fountain with a spout height no higher than 36 inches, measured from the finished floor or ground surface to the spout outlet; and a spout located at the front of the unit that directs the water flow in a trajectory that is nearly parallel to the front of the unit and is positioned so the flow of water is within 3 inches of the front edge of the fountain and at least 4 inches high. Ensure that fountain controls are operable with one hand, require 5 lbf or less to operate without tight grasping, pinching, or twisting of the wrist; and are front mounted or side mounted near the front edge. For each accessible drinking fountain, provide a drinking fountain that is accessible to people who have difficulty bending or stooping. This can be accommodated by the use of a “hi-lo” fountain; by providing one fountain accessible to those who use wheelchairs and one fountain at a standard height convenient for those who have difficulty bending; by providing a fountain accessible to people who use wheelchairs and a cup dispenser; or by such other means as would achieve the required accessibility for each group of people. Standards §§ 4.15, 4.27.4, Fig. 27.
12. Within 6 months of the effective date of this Agreement, the City will complete the following modifications to the W.D. Hill Recreation Center, located at 1308 Fayetteville Street:
a. Parking Lots
i. Lot #1 - Although there are 28 parking spaces, there is no van-accessible parking space provided, and the standard spaces designated as reserved for persons with disabilities lack access aisles. On the shortest accessible route to the accessible entrance, provide one van accessible space designated as reserved for people with disabilities. Ensure that standard spaces are a minimum of 96 inches wide and served by access aisles at least 60 inches wide. Ensure that van accessible spaces are a minimum of 96 inches wide and served by access aisles at least 96 inches wide. At all spaces designated as reserved for persons with disabilities, provide vertical signs with the International Symbol of Accessibility located such that they cannot be obstructed by parked vehicles. At van accessible spaces, provide an additional “Van-Accessible” sign located below the International Symbol of Accessibility. Ensure that all spaces and access aisles for persons with disabilities are flat and level, with slopes and cross-slopes not exceeding 1:50 in all directions, and that their surfaces are firm, stable, and slip-resistant. Standards §§ 4.1.2(5), 4.6, 4.30.7(1).
ii. Lot #2 - Although the parking lot has 57 spaces, there is no van accessible space provided as designated for persons with disabilities. On the shortest accessible route to the accessible entrance, provide one van accessible space designated as reserved for people with disabilities. Ensure that van accessible spaces are a minimum of 96 inches wide and served by access aisles at least 96 inches wide. At all spaces designated as reserved for persons with disabilities, provide vertical signs with the International Symbol of Accessibility located such that they cannot be obstructed by parked vehicles. At van accessible spaces, provide an additional “Van-Accessible” sign located below the International Symbol of Accessibility. Ensure that all spaces and access aisles for persons with disabilities are flat and level, with slopes and cross-slopes not exceeding 1:50 in all directions, and that their surfaces are firm, stable, and slip-resistant. Standards §§ 4.1.2(5), 4.6, 4.30.7(1).
b. The route from the front entrance door to the end of the main corridor is inaccessible because the drinking fountain on the corridor is a protruding object. Provide an accessible route at this location such that no objects with their bottom leading edges measuring between 27 inches and 80 inches above the finished floor protrude more than 4 inches into walks, halls, corridors, passageways, or aisles. Free-standing objects mounted on posts or pylons may overhang 12 inches maximum from 27 inches to 80 inches above the ground or finished floor. Standards § 4.4.
c. The entrance doors to the computer lab and the ceramic studio are inaccessible because knob hardware is used. Provide a door with hardware that is easy to grasp with one hand and that does not require tight grasping, pinching, or twisting of the wrist to operate. Lever-operated mechanisms, push-type mechanisms, and U-shaped handles are acceptable designs. Standards § 4.13.9.
d. The route into the building is not level, and the curb cut at the parking lot lacks detectable warnings. Provide at least one accessible route within the boundary of the site connecting these elements that, to the maximum extent feasible, coincides with the route for the general public. The accessible route must have a minimum clear width of 36 inches, or a minimum clear width of 42 inches if there is a turn around an obstruction less than 48 inches wide; have passing spaces at least 60 inches by 60 inches at least every 200 feet; have a minimum clear headroom of 80 inches; have a surface that is firm, stable, and slip resistant; have, in the absence of a curb ramp, ramp, elevator, or platform lift, no level changes in excess of ½ inch vertically; have detectable warnings at the curb cut; and have a running slope of less than 1:20 (5%) (or have been constructed as a fully accessible ramp) and a cross slope of less than 1:50 (2%). Standards §§ 4.3, 4.5, Fig. 7.
e. The building is inaccessible because the door to the Dance Studio has a one inch step up to a raised floor. Provide accessible directional signage with the International Symbol of Accessibility at inaccessible entrances directing users to the accessible entrance, and provide accessible signage with the International Symbol of Accessibility at all permanent accessible entrances. Standards §§ 4.1.3(8)(d), 4.13, 4.30.
f. Toilet Rooms
i. Men’s Toilet Room with Stalls
(1) The toilet room lacks an accessible sign. Provide a toilet room sign with the International Symbol of Accessibility and raised and Braille characters. The sign shall be mounted on the wall adjacent to the latch side of the door with the centerline of the sign at 60 inches above the finished floor and situated such that a person can approach within 3 inches of the sign without encountering an obstruction or standing within a door swing. Standards §§ 4.1.2(7)(d), 4.30.1, 4.30.4, 4.30.5, 4.30.6, 4.30.7.
(2) There is no signage directing people with disabilities to the accessible toilet rooms. Provide accessible directional signage with the International Symbol of Accessibility at inaccessible toilet rooms indicating the location of the nearest accessible toilet room, and provide accessible signage with the International Symbol of Accessibility at all accessible toilet rooms. Standards §§ 4.1.2(7)(d), 4.1.6(3)(e)(iii), 4.30.1, 4.30.2, 4.30.3, 4.30.5, 4.30.7.
(3) Although an audible alarm is provided in this facility, there is no visual alarm appliance in the toilet room. Provide a visual alarm appliance in the toilet room. Standards §§ 4.28.1, 4.28.3.
(4) Lavatory
a. The bottom edge of the lavatory apron is 28 inches above the finished floor. Provide a lavatory with the top of its rim or counter 34 inches or less above the finished floor; the bottom edge of the apron at least 29 inches above the finished floor; and knee and toe clearances that comply with Fig. 31. Standards § 4.19.2, Fig. 31.
b. The lavatory’s hot water pipes are not covered or insulated to protect against contact. Provide hot water and drain pipes that are insulated or otherwise configured to protect against contact. Standards § 4.19.4.
(5) The rim height of the urinal is 24 inches above the finished floor. Provide a urinal with an elongated rim mounted 17 inches or less above the finished floor, a clear floor space of at least 30 inches wide and 48 inches deep centered on the urinal, and a flush control height of 44 inches or less above the finished floor. Standards §§ 4.18.2, 4.18.3, 4.18.4.
(6) Although one stall is loosely configured as an alternate stall, there is no standard accessible stall for wheelchair users provided. Provide a “standard” accessible toilet stall at least 60 inches wide and at least 59 inches deep (or at least 56 inches deep with a wall-mounted toilet) such that all of the stall’s elements, including stall door, stall door hardware, water closet, size and arrangement, toe clearances, grab bars, controls, and dispensers, comply with the Standards. Standards §§ 4.13, 4.16, 4.17, 4.26, 4.27, Fig. 30.
ii. Women’s Toilet Room with Stalls
(1) The toilet room lacks an accessible sign. Provide a toilet room sign with the International Symbol of Accessibility and raised and Braille characters. The sign shall be mounted on the wall adjacent to the latch side of the door with the centerline of the sign at 60 inches above the finished floor and situated such that a person can approach within 3 inches of the sign without encountering an obstruction or standing within a door swing. Standards §§ 4.1.2(7)(d), 4.30.1, 4.30.4, 4.30.5, 4.30.6, 4.30.7.
(2) Although an audible alarm is provided in this facility, there is no visual alarm appliance in the toilet room. Provide a visual alarm appliance in the toilet room. Standards §§ 4.28.1, 4.28.3.
(3) Lavatory
a. The bottom edge of the lavatory apron is 27 inches above the finished floor. Provide a lavatory with the top of its rim or counter 34 inches or less above the finished floor; the bottom edge of the apron at least 29 inches above the finished floor; and knee and toe clearances that comply with Fig. 31. Standards § 4.19.2, Fig. 31.
b. The lavatory’s hot water pipes are not covered or insulated to protect against contact. Provide hot water and drain pipes that are insulated or otherwise configured to protect against contact. Standards § 4.19.4.
(4) Although one stall is loosely configured as an alternate stall, there is no standard accessible stall for wheelchair users provided. Provide a “standard” accessible toilet stall at least 60 inches wide and at least 59 inches deep (or at least 56 inches deep with a wall-mounted toilet) such that all of the stall’s elements, including stall door, stall door hardware, water closet, size and arrangement, toe clearances, grab bars, controls, and dispensers, comply with the Standards. Standards §§ 4.13, 4.16, 4.17, 4.26, 4.27, Fig. 30.
13. Within 6 months of the effective date of this Agreement, the City will complete the following modifications to the West Point Mill, located at 5000 North Roxboro Road:
a. Entrance
i. The route to the entrance ramp has a slope of 10% and a cross slope of 2.4%. Provide at least one accessible route within the boundary of the site connecting these elements that, to the maximum extent feasible, coincides with the route for the general public. The accessible route must have a minimum clear width of 36 inches, or a minimum clear width of 42 inches if there is a turn around an obstruction less than 48 inches wide; have passing spaces at least 60 inches by 60 inches at least every 200 feet; have a minimum clear headroom of 80 inches; have a surface that is firm, stable, and slip resistant; have, in the absence of a curb ramp, ramp, elevator, or platform lift, no level changes in excess of ½ inch vertically; and have a running slope of less than 1:20 (5%) (or have been constructed as a fully accessible ramp) and a cross slope of less than 1:50 (2%). Standards §§ 4.3, 4.5, Fig. 7.
ii. The ramp to the front entrance has a cross slope that exceeds 1:50 (2%), lacks edge protection and handrails. Provide a ramp that is at least 36 inches wide and has a slope not exceeding 1:12 and a cross slope not exceeding 1:50. Provide level landings at the top and bottom of the ramp that are at least as wide as the ramp and at least 60 inches long. If the ramp changes direction, provide a level landing measuring at least 60 inches by 60 inches at the change in direction. On both sides of the ramp, provide handrails between 1¼ inches and 1½ inches in diameter with a continuous gripping surface. Ensure that the handrails extend at least 12 inches beyond the top and bottom of the ramp parallel with the ground surface, that they are mounted between 34 inches and 38 inches above the ramp surface, that they will not rotate within their fittings, and that they have ends that are rounded or return smoothly to floor, wall, or post. Provide edge protection that is at least 2 inches high at the ramp’s drop off sides. Ensure that the ramp and its level landing at the top and bottom are designed and maintained so that water does not accumulate on walking surfaces. Standards §§ 4.3.8, 4.8.
iii. The entrance is inaccessible because there is no level landing within the door’s required maneuvering clearance. Provide a door so that the floor or ground area within the required clearances is level and clear. Standards § 4.13.6, Fig. 25.
iv. There is a 1 inch change in level at the threshold to the entrance door. Provide an accessible door with a threshold that is no greater than ¼ inch, or is no greater than ½ inch and is beveled with a slope no greater than 1:2. Standards §§ 4.13.8, 4.5.2.
b. Drinking Fountain Although an accessible drinking fountain is provided, there is no drinking fountain provided for people who have difficulty bending or stooping. For each accessible drinking fountain, provide a drinking fountain that is accessible to people who have difficulty bending or stooping. This can be accommodated by the use of a “hi-lo” fountain; by providing one fountain accessible to those who use wheelchairs and one fountain at a standard height convenient for those who have difficulty bending; by providing a fountain accessible to people who use wheelchairs and a cup dispenser, or by such other means as would achieve the required accessibility for each group of people. Standards § 4.1.3(10)(a).
14. Within 9 months of the effective date of this Agreement, the City will complete the following modifications to the Edison Johnson Recreation Center, located at 600 West Murray Avenue:
a. The signage provided throughout the facility is inaccessible. Provide permanent room signage with upper case, sans serif or simple serif type letters and numerals, meeting the requirements of the Standards for character height, raised characters, finish and contrast, accompanied by Grade 2 Braille; mounted on the wall adjacent to the latch side of the door or on the nearest adjacent wall at a height of 60 inches above the finished floor to the centerline of the sign; and located so that a person may approach within 3 inches of the signage without encountering protruding objects or standing within the swing of a door. Standards §§ 4.1.2(7), 4.30.1, 4.30.4, 4.30.5, 4.30.6.
b. Front Entrance The building has five entrances, three of which are accessible; however, there is no signage designating the entrances as accessible or not. Provide accessible directional signage with the International Symbol of Accessibility at inaccessible entrances directing users to the accessible entrance, and provide accessible signage with the International Symbol of Accessibility at all permanent accessible entrances. Standards §§ 4.1.3(8)(d), 4.1.3(16)(b), 4.13, 4.30.
c. Meeting Room No accessible coat hook has been provided. Provide a coat hook at a maximum height above the finished floor of 48 inches for a forward approach or 54 inches for a side approach and that is accompanied by clear floor space of 30 by 48 inches that allows a forward or parallel approach by a person using a wheelchair. Standards §§ 4.25.2, 4.25.3, 4.2.4, 4.2.5, 4.2.6.
d. Telephone The telephone in the front lobby area is inaccessible because its clear floor space is obstructed by newspaper stands and it lacks signage. Provide an accessible telephone with a clear floor space of at least 30 inches by 48 inches that allows either a forward or parallel approach by a person using a wheelchair such that bases, enclosures, and fixed seats do not impede approaches to the telephone; with the highest operable part of the telephone mounted no more than 48 inches above the floor for a front approach or no more than 54 inches above the floor for a side approach; that is hearing aid compatible and has a volume control mechanism; with telephone books, if provided, located between 15 and 48 inches above the finished floor for a front approach or between 9 and 54 inches above the finished floor for a side approach; with a cord of at least 29 inches long from the telephone to the handset; and with signage that complies with the Standards. Standards §§ 4.31, 4.30.7(2).
e. Toilet Rooms
i. Front Lobby Area, Men’s Room with Stalls
(1) The toilet room sign is inaccessible because it is mounted on the door. Provide a toilet room sign with the International Symbol of Accessibility and raised and Braille characters. The sign shall be mounted on the wall adjacent to the latch side of the door with the centerline of the sign at 60 inches above the finished floor and situated such that a person can approach within 3 inches of the sign without encountering an obstruction or standing within a door swing. Standards §§ 4.1.2(7)(d), 4.30.1, 4.30.4, 4.30.5, 4.30.6, 4.30.7.
(2) The lavatory is inaccessible because the hot water pipes are not insulated or otherwise configured to protect against contact. Provide hot water and drain pipes that are insulated or otherwise configured to protect against contact. Standards § 4.19.4.
(3) The lavatory is inaccessible because it has twist style faucets. Provide a lavatory with a faucet that can be operated with 5 pounds of force or less and can be used with one hand and without tight grasping, pinching, or twisting of the wrist (lever-operated, push-type, and electronically controlled mechanisms are examples of acceptable designs). Standards §§ 4.19.5, 4.27.4.
(4) There is no accessible standard stall provided for persons with disabilities. Provide a “standard” accessible toilet stall at least 60 inches wide and at least 59 inches deep (or at least 56 inches deep with a wall-mounted toilet) such that all of the stall’s elements, including stall door, stall door hardware, water closet, size and arrangement, toe clearances, grab bars, controls, and dispensers, comply with the Standards. Standards §§ 4.13, 4.16, 4.17, 4.26, 4.27, Fig. 30.
(5) The urinal is inaccessible because the rim and flush control are too high. Provide a urinal with an elongated rim mounted 17 inches or less above the finished floor, a clear floor space of at least 30 inches wide and 48 inches deep centered on the urinal, and a flush control height of 44 inches or less above the finished floor. Standards §§ 4.18.2, 4.18.3, 4.18.4.
ii. Front Lobby Area, Women’s Room with Stalls
(1) The toilet room sign is inaccessible because it is mounted on the door. Provide a toilet room sign with the International Symbol of Accessibility and raised and Braille characters. The sign shall be mounted on the wall adjacent to the latch side of the door with the centerline of the sign at 60 inches above the finished floor and situated such that a person can approach within 3 inches of the sign without encountering an obstruction or standing within a door swing. Standards §§ 4.1.2(7)(d), 4.30.1, 4.30.4, 4.30.5, 4.30.6, 4.30.7.
(2) The lavatory is inaccessible because the hot water pipes are not insulated or otherwise configured to protect against contact. Provide hot water and drain pipes that are insulated or otherwise configured to protect against contact. Standards § 4.19.4.
(3) The lavatory is inaccessible because it has twist style faucets. Provide a lavatory with a faucet that can be operated with 5 pounds of force or less and can be used with one hand and without tight grasping, pinching, or twisting of the wrist (lever-operated, push-type, and electronically controlled mechanisms are examples of acceptable designs). Standards §§ 4.19.5, 4.27.4.
(4) There is no accessible standard stall provided for persons with disabilities. Provide a “standard” accessible toilet stall at least 60 inches wide and at least 59 inches deep (or at least 56 inches deep with a wall-mounted toilet) such that all of the stall’s elements, including stall door, stall door hardware, water closet, size and arrangement, toe clearances, grab bars, controls, and dispensers, comply with the Standards. Standards §§ 4.13, 4.16, 4.17, 4.26, 4.27, Fig. 30.
iii. Near Gym; Men’s Single User Room
(1) The toilet room sign is inaccessible. Provide a toilet room sign with the International Symbol of Accessibility and raised and Braille characters. The sign shall be mounted on the wall adjacent to the latch side of the door with the centerline of the sign at 60 inches above the finished floor and situated such that a person can approach within 3 inches of the sign without encountering an obstruction or standing within a door swing. Standards §§ 4.1.2(7)(d), 4.30.1, 4.30.4, 4.30.5, 4.30.6, 4.30.7.
(2) The lavatory is inaccessible because the hot water pipes are not insulated or otherwise configured to protect against contact. Provide hot water and drain pipes that are insulated or otherwise configured to protect against contact. Standards § 4.19.4.
(3) The lavatory is inaccessible because it has twist style faucets. Provide a lavatory with a faucet that can be operated with 5 pounds of force or less and can be used with one hand and without tight grasping, pinching, or twisting of the wrist (lever-operated, push-type, and electronically controlled mechanisms are examples of acceptable designs). Standards §§ 4.19.5, 4.27.4.
(4) The toilet is inaccessible because it lacks elements required for accessibility. Provide a toilet with a centerline that is 18 inches from the near side wall; a seat that is between17 and 19 inches above the finished floor; clear floor space at the toilet that complies with Fig. 28; and a flush control mounted on the “open” side of the toilet’s clear floor space. Standards §§ 4.16.2, 4.16.3, 4.16.5, Figs. 28, 29.
(5) There is no rear grab bar provided. Provide a rear grab bar that is at least 36 inches in overall length, with the closer end no more than 6 inches from the side wall, and a side grab bar that is at least 40 inches in overall length, with the far end mounted at least 52 inches from the rear wall and the closer end 12 inches or less from the rear wall. Ensure that the grab bars are mounted 33 to 36 inches above the finished floor; with a diameter between 1¼ and 1½ inches; with 1½ inches between the grab bars and the wall; and at least 1½ inches between the grab bars and any other object, such as a toilet paper dispenser or a toilet seat cover dispenser. Standards §§ 4.16.4, 4.26.2, Fig. 29.
iv. Near Gym; Women’s Single User Room
(1) The toilet room sign is inaccessible. Provide a toilet room sign with the International Symbol of Accessibility and raised and Braille characters. The sign shall be mounted on the wall adjacent to the latch side of the door with the centerline of the sign at 60 inches above the finished floor and situated such that a person can approach within 3 inches of the sign without encountering an obstruction or standing within a door swing. Standards §§ 4.30.1, 4.30.4, 4.30.5, 4.30.6, 4.30.7.
(2) The lavatory is inaccessible because the hot water pipes are not insulated or otherwise configured to protect against contact. Provide hot water and drain pipes that are insulated or otherwise configured to protect against contact. Standards § 4.19.4.
(3) The lavatory is inaccessible because it has twist style faucets. Provide a lavatory with a faucet that can be operated with 5 pounds of force or less and can be used with one hand and without tight grasping, pinching, or twisting of the wrist (lever-operated, push-type, and electronically controlled mechanisms are examples of acceptable designs). Standards §§ 4.19.5, 4.27.4.
(4) The toilet is inaccessible because it lacks elements required for accessibility. Provide a toilet with a centerline that is 18 inches from the near side wall; a seat that is between17 and 19 inches above the finished floor; clear floor space at the toilet that complies with Fig. 28; and a flush control mounted on the “open” side of the toilet’s clear floor space. Standards §§ 4.16.2, 4.16.3, 4.16.5, Figs. 28, 29.
(5) There is no rear grab bar provided. Provide a rear grab bar that is at least 36 inches in overall length, with the closer end no more than 6 inches from the side wall, and a side grab bar that is at least 40 inches in overall length, with the far end mounted at least 52 inches from the rear wall and the closer end 12 inches or less from the rear wall. Ensure that the grab bars are mounted 33 to 36 inches above the finished floor; with a diameter between 1¼ and 1½ inches; with 1½ inches between the grab bars and the wall; and at least 1½ inches between the grab bars and any other object, such as a toilet paper dispenser or a toilet seat cover dispenser. Standards §§ 4.16.4, 4.26.2, Fig. 29.
15. Within 12 months of the effective date of this Agreement, the City will complete the following modifications to the Church Street Parking Deck, located at 109 S. Mangum Street:
a. Although the parking deck has a total of 408 parking spaces, an inadequate number are designated as reserved for people with disabilities, and no van accessible space is designated as reserved for persons with disabilities. On the shortest accessible route to the accessible entrance, provide at least two van accessible spaces and a total of seven standard spaces designated as reserved for people with disabilities. Standard accessible spaces shall be a minimum of 96 inches wide and served by access aisles at least 60 inches wide. Van accessible spaces shall be a minimum of 96 inches wide and served by access aisles at least 96 inches wide. All spaces designated as reserved for people with disabilities shall have vertical signs with the International Symbol of Accessibility located such that they cannot be obstructed by parked vehicles. Van accessible spaces shall have an additional “Van-Accessible” sign located below the International Symbol of Accessibility. Standards §§ 4.1.2(5), 4.6, 4.30.7(1).
|