Attachment F
Newly Constructed Facilities
1. Within 12 months of the effective date of this Agreement, the City will complete the following modifications to the GSA Facilities Building, located at 2011 Fay Street:
a. Counters
i. The reception counter in the lobby is inaccessible because the top is 42½ inches above the finished floor. Provide a counter on an accessible route such that a portion of the counter is at least 36 inches wide and no more than 36 inches above the finished floor. Standards §§ 4.1.1(2), 7.2(1), 4.1.3(1), 4.3.
ii. The service counter on the first floor is inaccessible because the top is 42 inches above the finished floor. Provide a counter on an accessible route such that a portion of the counter is at least 36 inches wide and no more than 36 inches above the finished floor. Standards §§ 4.1.1(2), 7.2(1), 4.1.3(1), 4.3.
b. Toilet Rooms
i. Area Signage The signage posted on the wall in the vestibule does not meet the ADA requirements. There is no signage directing people with disabilities to the accessible toilet rooms. Provide accessible directional signage with the International Symbol of Accessibility at inaccessible toilet rooms indicating the location of the nearest accessible toilet room, and provide accessible signage with the International Symbol of Accessibility at all accessible toilet rooms. Standards §§ 4.1.2(7)(d), 4.1.6(3)(e)(iii), 4.30.1, 4.30.2, 4.30.3, 4.30.5, 4.30.7.
ii. Men’s Room with Stalls
(1) The lavatory is inaccessible because the top rim is 36 inches above the finished floor. Provide a lavatory with the top of its rim or counter 34 inches or less above the finished floor; the bottom edge of the apron at least 29 inches above the finished floor; and knee and toe clearances that comply with Fig. 31. Standards §§ 4.1.3(11), 4.22.6, 4.19.2, Fig. 31.
(2) The toilet paper dispenser is inaccessible because it is mounted 38½ inches from the rear wall. Provide a toilet paper dispenser that is mounted with its top at least 1½ inches under the side grab bar and 36 inches or less from the rear wall and is centered at least 19 inches above the finished floor. Standards §§ 4.1.3(11), 4.22.4, 4.17.3, Fig. 30(d).
(3) No accessible coat hook has been provided. Provide a coat hook at a maximum height above the finished floor of 48 inches for a forward approach or 54 inches for a side approach and that is accompanied by clear floor space of 30 by 48 inches that allows a forward or parallel approach by a person using a wheelchair. Standards §§ 4.1.3(12)(a), 4.25.2, 4.25.3, 4.2.4, 4.2.5, 4.2.6.
iii. Women’s Room with Stalls
(1) The lavatory is inaccessible because the top rim is 36 inches above the finished floor. Provide a lavatory with the top of its rim or counter 34 inches or less above the finished floor; the bottom edge of the apron at least 29 inches above the finished floor; and knee and toe clearances that comply with Fig. 31. Standards §§ 4.1.3(11), 4.22.6, 4.19.2, Fig. 31.
(2) No accessible coat hook has been provided. Provide a coat hook at a maximum height above the finished floor of 48 inches for a forward approach or 54 inches for a side approach and that is accompanied by clear floor space of 30 by 48 inches that allows a forward or parallel approach by a person using a wheelchair. Standards §§ 4.1.3(12)(a), 4.25.2, 4.25.3, 4.2.4, 4.2.5, 4.2.6.
iv. Unisex Room There is signage designating this toilet room as accessible; however, it is not. Provide accessible directional signage with the International Symbol of Accessibility at inaccessible toilet rooms indicating the location of the nearest accessible toilet room, and provide accessible signage with the International Symbol of Accessibility at all accessible toilet rooms. Standards §§ 4.1.2(7)(d), 4.1.6(3)(e)(iii), 4.30.1, 4.30.2, 4.30.3, 4.30.5, 4.30.7.
2. Within 12 months of the effective date of this Agreement, the City will complete the following modifications to the Parks and Recreation Office, located at 400 Cleveland Street:
a. Entrance
i. Routes
(1) The route from the accessible parking to the front entrance of the building is inaccessible because it has an excessive slope of 5.6%. Provide at least one accessible route within the boundary of the site connecting these elements that, to the maximum extent feasible, coincides with the route for the general public. The accessible route must have a minimum clear width of 36 inches, or a minimum clear width of 42 inches if there is a turn around an obstruction less than 48 inches wide; have passing spaces at least 60 inches by 60 inches at least every 200 feet; have a minimum clear headroom of 80 inches; have a surface that is firm, stable, and slip resistant; have, in the absence of a curb ramp, ramp, elevator, or platform lift, no level changes in excess of ½ inch vertically; and have a running slope of less than 1:20 (5%) (or have been constructed as a fully accessible ramp) and a cross slope of less than 1:50 (2%). Standards §§ 4.1.3(1), 4.3, 4.5, Fig. 7.
(2) The signage designating parking as reserved for persons with disabilities is too low. At each space designated as reserved for persons with disabilities, provide a vertical sign with the International Symbol of Accessibility located such that it cannot be obstructed by vehicles parked in the space. Standards §§ 4.1.2(5), 4.6.4, 4.30.7(1).
(3) The route from the sidewalk to the front entrance is inaccessible because it has an excessive slope of 5.9%. Provide at least one accessible route within the boundary of the site connecting these elements that, to the maximum extent feasible, coincides with the route for the general public. The accessible route must have a minimum clear width of 36 inches, or a minimum clear width of 42 inches if there is a turn around an obstruction less than 48 inches wide; have passing spaces at least 60 inches by 60 inches at least every 200 feet; have a minimum clear headroom of 80 inches; have a surface that is firm, stable, and slip resistant; have, in the absence of a curb ramp, ramp, elevator, or platform lift, no level changes in excess of ½ inch vertically; and have a running slope of less than 1:20 (5%) (or have been constructed as a fully accessible ramp) and a cross slope of less than 1:50 (2%). Standards §§ 4.1.3(1), 4.3, 4.5, Fig. 7.
ii. Signage The front entrance with steps lacks signage directing people with disabilities to accessible entrance. Provide accessible directional signage with the International Symbol of Accessibility at inaccessible entrances directing users to the accessible entrance, and provide accessible signage with the International Symbol of Accessibility at all permanent accessible entrances. Standards §§ 4.1.3(8)(d), 4.1.3(16)(b), 4.13, 4.30.
b. Elevator The elevator is inaccessible because the hall call buttons are centered at 53 inches above the finished floor. Provide hall (lobby) call buttons with visual signals indicating when each call is registered and when each call is answered. Ensure that the call buttons are centered at 42 inches above the finished floor, a minimum of ¾ inch in the smallest dimension, with the button designating the up direction on top; that the call buttons are raised or flush; and that objects mounted beneath hall call buttons do not project into the elevator lobby more than 4 inches. Standards §§ 4.1.3(5), 4.10.3, Fig. 20.
c. Drinking Fountain
i. The drinking fountain has a spout that is 43 inches above the finished floor. Provide a fountain that has a spout height no higher than 36 inches, measured from the finished floor or ground surface to the spout outlet, and that otherwise complies with the Standards. Standards §§ 4.1.3(10), 4.15, 4.27.4, Fig. 27.
ii. The wall-mounted drinking fountain is inaccessible because there is no knee clearance. Provide a drinking fountain with clear knee space between the bottom of the apron and the finished floor or ground of at least 27 inches high, 30 inches wide, and 17 to 19 inches deep; and a minimum clear floor space of 30 inches by 48 inches to allow a person in a wheelchair to approach the unit facing forward. Standards §§ 4.1.3(10), 4.15.5(1), Figs. 27(a), (b).
d. Toilet Rooms
i. 1st Floor, Men’s Single User Room
(1) The paper towel dispenser is inaccessible because the controls are mounted at 60 inches above the finished floor. Provide a paper towel dispenser with the controls a maximum height above the finished floor of 48 inches for a forward approach or 54 inches for a side approach and that is accompanied by clear floor space of 30 by 48 inches that allows a forward or parallel approach by a person using a wheelchair. Standards §§ 4.1.3(13), 4.27.2, 4.27.3, 4.2.4, 4.2.5, 4.2.6.
(2) The toilet is inaccessible because the flush control is on the closed side. Provide a flush control mounted on the “open” side of the toilet’s clear floor space; 44 inches or less above the finished floor; and requiring a maximum of 5 pounds of force to operate; or provide an automatic flush device. Standards §§ 4.1.3(11), 4.22.4, 4.16.5, 4.27.4.
(3) The rear grab bar at the toilet is inaccessible because the flush control impedes with the usability of the bar. Provide a rear grab bar that has at least 1½ inches between the grab bar and any other object, such as a toilet seat cover dispenser. Standards §§ 4.1.3(11), 4.22.4, 4.16.4, 4.26.2, Fig. 39.
(4) The toilet paper dispenser is inaccessible because it is mounted 46 inches form the rear wall. Provide a toilet paper dispenser that is mounted within reach, with its top at least 1½ inches under the side grab bar, and centered at least 19 inches above the finished floor. Standards §§ 4.1.3(11), 4.22.4, 4.16.6, Fig. 29(b).
(5) Although an audible alarm is provided in this facility, there is no visual alarm appliance in the toilet room. Provide a visual alarm appliance in the toilet room. Standards §§ 4.1.3(14), 4.28.1, 4.28.3.
ii. 1st Floor, Women’s Single User Room
(1) There is no signage directing people with disabilities to the accessible toilet room. Provide accessible directional signage with the International Symbol of Accessibility at inaccessible toilet rooms indicating the location of the nearest accessible toilet room, and provide accessible signage with the International Symbol of Accessibility at all accessible toilet rooms. Standards §§ 4.1.2(7)(d), 4.1.6(3)(e)(iii), 4.30.1, 4.30.2, 4.30.3, 4.30.5, 4.30.7.
(2) The entrance door, which is accessed through a front approach, is inaccessible because it has insufficient pull side clearance. On the pull side of the door, provide maneuvering clearance at least 60 inches deep and provide a minimum of 18 inches (24 inches is preferred) of maneuvering clearance on the latch side of the door. Standards §§ 4.1.3(7)(b), 4.13.6, Fig. 25(a).
(3) The paper towel dispenser is inaccessible because the controls are mounted at 60 inches above the finished floor. Provide a paper towel dispenser with the controls a maximum height above the finished floor of 48 inches for a forward approach or 54 inches for a side approach and that is accompanied by clear floor space of 30 by 48 inches that allows a forward or parallel approach by a person using a wheelchair. Standards §§ 4.1.3(13), 4.27.2, 4.27.3, 4.2.4, 4.2.5, 4.2.6.
(4) The toilet is inaccessible because the flush control is on the closed side. Provide a flush control mounted on the “open” side of the toilet’s clear floor space; 44 inches or less above the finished floor; and requiring a maximum of 5 pounds of force to operate; or provide an automatic flush device. Standards §§ 4.1.3(11), 4.22.4, 4.16.5, 4.27.4.
(5) The rear grab bar at the toilet is inaccessible because the flush control impedes with the usability of the bar. Provide a rear grab bar that has at least 1½ inches between the grab bar and any other object, such as a toilet seat cover dispenser. Standards §§ 4.1.3(11), 4.22.4, 4.16.4, 4.26.2, Fig. 39.
(6) The toilet paper dispenser is inaccessible because it is mounted 46 inches from the rear wall. Provide a toilet paper dispenser that is mounted within reach, with its top at least 1½ inches under the side grab bar, and centered at least 19 inches above the finished floor. Standards §§ 4.1.3(11), 4.22.4, 4.16.6, Fig. 29(b).
(7) Although an audible alarm is provided in this facility, there is no visual alarm appliance in the toilet room. Provide a visual alarm appliance in the toilet room. Standards §§ 4.1.3(14), 4.28.1, 4.28.3.
3. Within 12 months of the effective date of this Agreement, the City will complete the following modifications to the Durham Bulls Athletic Park and Stadium, located at 411 Blackwell Street:
a. Facility signage The signage provided throughout the facility is inaccessible. Provide permanent room signage with upper case, sans serif or simple serif type letters and numerals, meeting the requirements of the Standards for character height, raised characters, finish and contrast, accompanied by Grade 2 Braille; mounted on the wall adjacent to the latch side of the door or on the nearest adjacent wall at a height of 60 inches above the finished floor to the centerline of the sign; and located so that a person may approach within 3 inches of the signage without encountering protruding objects or standing within the swing of a door. Standards §§ 4.1.2(7), 4.30.1, 4.30.4, 4.30.5, 4.30.6.
b. Parking
i. Side of Stadium Although the parking lot has a total of 5 accessible parking spaces, none is van accessible. On the shortest accessible route to the accessible entrance, provide 1 van accessible space a minimum of 96 inches wide, served by access aisles at least 96 inches wide, with vertical signs with the International Symbol of Accessibility located such that they cannot be obstructed by parked vehicles, and with an additional “Van-Accessible” sign located below the International Symbol of Accessibility. Standards §§ 4.1.2(5)(b), 4.6, 4.30.7(1).
ii. Gate C Although the parking lot has a total of up to 50 parking spaces, none is van accessible. On the shortest accessible route to the accessible entrance, provide 1 van accessible space a minimum of 96 inches wide, served by access aisles at least 96 inches wide, with vertical signs with the International Symbol of Accessibility located such that they cannot be obstructed by parked vehicles, and with an additional “Van-Accessible” sign located below the International Symbol of Accessibility. Standards §§ 4.1.2(5)(b), 4.6, 4.30.7(1).
c. Entrances The route from the street to the accessible entrance and ticket booths is inaccessible because the curb cut lacks detectable warnings. Provide a curb ramp that is at least 36 inches wide, has a maximum slope of 1:12, is located so that it cannot be obstructed by parked vehicles, and has a stable, firm, and slip-resistant surface with a detectable warning extending the full width and depth of the ramp. If the curb ramp is located where pedestrians must walk across it, provide either flared sides (with a maximum slope of 1:10) or handrails or guardrails to protect against cross traffic. Standards §§ 4.1.2(1), 4.1.2(2), 4.3.8, 4.7, Fig. 12.
d. Exterior Ticket Counter near Front Entrance None of the retail counters are accessible because they lack the appropriate dimensions. There are no accessible counters. Provide counters dispersed throughout the facility on accessible routes such that each counter has a portion at least 36 inches wide and no more than 36 inches above the finished floor. Standards §§ 4.1.1(2), 7.2(2), 4.1.3(1), 4.3.
e. Elevator accessed with key only
i. The elevator is inaccessible because no hall lanterns are provided. Provide hall lanterns at each hoistway entrance that emit a visible and audible signal indicating which car is answering a call. Ensure that audible signals sound once for the up direction and twice for the down direction or have verbal annunciators that say “up” or “down;” and that visible signals are mounted so that their centerline is at least 72 inches above the lobby floor, they are at least 2½ inches in the smallest dimension, and they are visible from the vicinity of the hall call button. Lanterns located in cars, visible from the vicinity of hall call buttons, and conforming to the above requirements, are acceptable. Standards §§ 4.1.3(5), 4.10.4, Fig. 20.
ii. The elevator is inaccessible because, although emergency communications are provided, operation requires voice communication. Provide a two-way communication system such that it does not require voice communication, the highest operable part is a maximum of 48 inches above the finished floor of the car, and it is identified by a raised symbol and lettering located adjacent to the device. If the system uses a handset, ensure that the length of the cord from the panel to the handset is at least 29 inches. If the system is located in a closed compartment, ensure that the compartment door hardware operates without tight grasping, pinching or twisting of the wrist. Standards §§ 4.1.3(5), 4.10.14.
f. Access to Seating Areas
i. The ramp from the ground level to the first level accessible seating area is inaccessible because the handrails are mounted 33 inches high and lack handrail extensions. Provide handrails that are between 1¼ inches and 1½ inches in diameter with a continuous gripping surface along both sides of the ramp, extending at least 12 inches beyond the top and bottom of the ramp parallel with the ground surface. Ensure that handrails are mounted between 34 inches and 38 inches above the ramp surface, with ends rounded or returned smoothly to the floor, wall, or post, and that they do not rotate within their fittings. Standards §§ 4.1.2(1), 4.1.2(2), 4.8.5.
ii. There are no accessible exterior skybox seating areas for persons with disabilities. Provide 2 wheelchair seating areas, each with a minimum clear ground or floor space of 66 inches wide by 48 inches deep for forward or rear access, or 66 inches wide by 60 inches deep for side access. Ensure that the ground or floor at all wheelchair locations is level, firm, stable, and slip resistant; that wheelchair seating areas are an integral part of the fixed seating plan and are located so as to provide people with physical disabilities a choice of lines of sight comparable to those available for members of the general public; that wheelchair seating areas adjoin an accessible route that also serves as a means of egress in case of emergency; and that at least one fixed companion seat is provided next to each wheelchair seating area. Standards §§ 4.1.3(19)(a), 4.5, 4.33.
iii. The service counter at the Home Run Grill is inaccessible because the countertop is higher than 36 inches. Provide a counter on an accessible route such that a portion of the counter is at least 36 inches wide and no more than 36 inches above the finished floor. Standards §§ 4.1.1(2), 7.2(1), 4.1.3(1), 4.3.
iv. The condiment counter on the first level is a protruding object with more than a 12 inch overhang. Provide an accessible route at this location such that no objects with their bottom leading edges measuring between 27 inches and 80 inches above the finished floor protrude more than 4 inches into walks, halls, corridors, passageways, or aisles. Free-standing objects mounted on posts or pylons may overhang 12 inches maximum from 27 inches to 80 inches above the ground or finished floor. Standards §§ 4.1.2(3), 4.4.
g. Toilet Rooms with Stalls
i. 1st Level, Men’s Room set #1, (near elevator)
(1) The lavatory is inaccessible because the hot water pipes are not insulated or otherwise configured to protect against contact. Provide hot water and drain pipes that are insulated or otherwise configured to protect against contact. Standards §§ 4.1.3(11), 4.22.6, 4.19.4.
(2) The paper towel dispenser is inaccessible because the controls are mounted at 58 inches above the finished floor. Provide a paper towel dispenser with the controls a maximum height above the finished floor of 48 inches for a forward approach or 54 inches for a side approach and that is accompanied by clear floor space of 30 by 48 inches that allows a forward or parallel approach by a person using a wheelchair. Standards §§ 4.1.3(13), 4.27.2, 4.27.3, 4.2.4, 4.2.5, 4.2.6.
(3) No accessible mirror has been provided. Provide a mirror with the bottom edge of its reflecting surface no more than 40 inches above the finished floor. Standards §§ 4.1.3(11), 4.22.6, 4.19.6.
(4) No accessible coat hook has been provided. Provide a coat hook at a maximum height above the finished floor of 48 inches for a forward approach or 54 inches for a side approach and that is accompanied by clear floor space of 30 by 48 inches that allows a forward or parallel approach by a person using a wheelchair. Standards §§ 4.1.3(12)(a), 4.25.2, 4.25.3, 4.2.4, 4.2.5, 4.2.6.
(5) The toilet paper dispenser is inaccessible because it is mounted above the side grab bar and interferes with the usability of the bar. Provide a toilet paper dispenser that is mounted within reach, with its top at least 1½ inches under the side grab bar, and centered at least 19 inches above the finished floor. Standards §§ 4.1.3(11), 4.22.4, 4.16.6, Fig. 29(b).
ii. 1st Level, Women’s Room set #1, (near elevator)
(1) The lavatory is inaccessible because the hot water pipes are not insulated or otherwise configured to protect against contact. Provide hot water and drain pipes that are insulated or otherwise configured to protect against contact. Standards §§ 4.1.3(11), 4.22.6, 4.19.4.
(2) The paper towel dispenser is inaccessible because the controls are mounted at 58 inches above the finished floor. Provide a paper towel dispenser with the controls a maximum height above the finished floor of 48 inches for a forward approach or 54 inches for a side approach and that is accompanied by clear floor space of 30 by 48 inches that allows a forward or parallel approach by a person using a wheelchair. Standards §§ 4.1.3(13), 4.27.2, 4.27.3, 4.2.4, 4.2.5, 4.2.6.
(3) No accessible mirror has been provided. Provide a mirror with the bottom edge of its reflecting surface no more than 40 inches above the finished floor. Standards §§ 4.1.3(11), 4.22.6, 4.19.6.
(4) No accessible coat hook has been provided. Provide a coat hook at a maximum height above the finished floor of 48 inches for a forward approach or 54 inches for a side approach and that is accompanied by clear floor space of 30 by 48 inches that allows a forward or parallel approach by a person using a wheelchair. Standards §§ 4.1.3(12)(a), 4.25.2, 4.25.3, 4.2.4, 4.2.5, 4.2.6.
(5) The toilet paper dispenser is inaccessible because it is mounted above the side grab bar and interferes with the usability of the bar. Provide a toilet paper dispenser that is mounted within reach, with its top at least 1½ inches under the side grab bar, and centered at least 19 inches above the finished floor. Standards §§ 4.1.3(11), 4.22.4, 4.16.6, Fig. 29(b).
iii. 1st Level, Men’s Room set #2
(1) The lavatory is inaccessible because the hot water pipes are not insulated or otherwise configured to protect against contact. Provide hot water and drain pipes that are insulated or otherwise configured to protect against contact. Standards §§ 4.1.3(11), 4.22.6, 4.19.4.
(2) The paper towel dispenser is inaccessible because the controls are mounted at 58 inches above the finished floor. Provide a paper towel dispenser with the controls a maximum height above the finished floor of 48 inches for a forward approach or 54 inches for a side approach and that is accompanied by clear floor space of 30 by 48 inches that allows a forward or parallel approach by a person using a wheelchair. Standards §§ 4.1.3(13), 4.27.2, 4.27.3, 4.2.4, 4.2.5, 4.2.6.
(3) The side grab bar at the toilet in the designated accessible stall is inaccessible because a wall-mounted ashtray impedes its usability. Provide a side grab bar that has at least 18 inches of clear space vertically between the grab bar and any other object. Standards §§ 4.1.3(11), 4.22.4, 4.17.6, 4.26.2, Fig. 39.
(4) No accessible coat hook has been provided. Provide a coat hook at a maximum height above the finished floor of 48 inches for a forward approach or 54 inches for a side approach and that is accompanied by clear floor space of 30 by 48 inches that allows a forward or parallel approach by a person using a wheelchair. Standards §§ 4.1.3(12)(a), 4.25.2, 4.25.3, 4.2.4, 4.2.5, 4.2.6.
iv. 1st Level, Women’s Room set #2
(1) The lavatory is inaccessible because the hot water pipes are not insulated or otherwise configured to protect against contact. Provide hot water and drain pipes that are insulated or otherwise configured to protect against contact. Standards §§ 4.1.3(11), 4.22.6, 4.19.4.
(2) The paper towel dispenser is inaccessible because the controls are mounted at 58 inches above the finished floor. Provide a paper towel dispenser with the controls a maximum height above the finished floor of 48 inches for a forward approach or 54 inches for a side approach and that is accompanied by clear floor space of 30 by 48 inches that allows a forward or parallel approach by a person using a wheelchair. Standards §§ 4.1.3(13), 4.27.2, 4.27.3, 4.2.4, 4.2.5, 4.2.6.
(3) The side grab bar at the toilet in the designated accessible stall is inaccessible because a wall-mounted ashtray impedes its usability. Provide a side grab bar that has at least 18 inches of clear space vertically between the grab bar and any other object. Standards §§ 4.1.3(11), 4.22.4, 4.17.6, 4.26.2, Fig. 39.
(4) No accessible coat hook has been provided. Provide a coat hook at a maximum height above the finished floor of 48 inches for a forward approach or 54 inches for a side approach and that is accompanied by clear floor space of 30 by 48 inches that allows a forward or parallel approach by a person using a wheelchair. Standards §§ 4.1.3(12)(a), 4.25.2, 4.25.3, 4.2.4, 4.2.5, 4.2.6.
v. 2nd Level, Men’s Room near players’ and managers’ rooms
(1) The lavatory is inaccessible because the hot water pipes are not insulated or otherwise configured to protect against contact. Provide hot water and drain pipes that are insulated or otherwise configured to protect against contact. Standards §§ 4.1.3(11), 4.22.6, 4.19.4.
(2) The paper towel dispenser is inaccessible because the controls are mounted at 58 inches above the finished floor. Provide a paper towel dispenser with the controls a maximum height above the finished floor of 48 inches for a forward approach or 54 inches for a side approach and that is accompanied by clear floor space of 30 by 48 inches that allows a forward or parallel approach by a person using a wheelchair. Standards §§ 4.1.3(13), 4.27.2, 4.27.3, 4.2.4, 4.2.5, 4.2.6.
(3) No accessible mirror has been provided. Provide a mirror with the bottom edge of its reflecting surface no more than 40 inches above the finished floor. Standards §§ 4.1.3(11), 4.22.6, 4.19.6.
(4) No accessible coat hook has been provided. Provide a coat hook at a maximum height above the finished floor of 48 inches for a forward approach or 54 inches for a side approach and that is accompanied by clear floor space of 30 by 48 inches that allows a forward or parallel approach by a person using a wheelchair. Standards §§ 4.1.3(12)(a), 4.25.2, 4.25.3, 4.2.4, 4.2.5, 4.2.6.
vi. 2nd Level, Women’s Room near players’ and managers’ rooms
(1) The lavatory is inaccessible because the hot water pipes are not insulated or otherwise configured to protect against contact. Provide hot water and drain pipes that are insulated or otherwise configured to protect against contact. Standards §§ 4.1.3(11), 4.22.6, 4.19.4.
(2) The paper towel dispenser is inaccessible because the controls are mounted at 58 inches above the finished floor. Provide a paper towel dispenser with the controls a maximum height above the finished floor of 48 inches for a forward approach or 54 inches for a side approach and that is accompanied by clear floor space of 30 by 48 inches that allows a forward or parallel approach by a person using a wheelchair. Standards §§ 4.1.3(13), 4.27.2, 4.27.3, 4.2.4, 4.2.5, 4.2.6.
(3) No accessible mirror has been provided. Provide a mirror with the bottom edge of its reflecting surface no more than 40 inches above the finished floor. Standards §§ 4.1.3(11), 4.22.6, 4.19.6.
(4) No accessible coat hook has been provided. Provide a coat hook at a maximum height above the finished floor of 48 inches for a forward approach or 54 inches for a side approach and that is accompanied by clear floor space of 30 by 48 inches that allows a forward or parallel approach by a person using a wheelchair. Standards §§ 4.1.3(12)(a), 4.25.2, 4.25.3, 4.2.4, 4.2.5, 4.2.6.
vii. 3rd Level, Men’s Room near Gate C
(1) The paper towel dispenser is inaccessible because the controls are mounted at 58 inches above the finished floor. Provide a paper towel dispenser with the controls a maximum height above the finished floor of 48 inches for a forward approach or 54 inches for a side approach and that is accompanied by clear floor space of 30 by 48 inches that allows a forward or parallel approach by a person using a wheelchair. Standards §§ 4.1.3(13), 4.27.2, 4.27.3, 4.2.4, 4.2.5, 4.2.6.
(2) The side grab bar at the toilet in the designated accessible stall is inaccessible because a wall-mounted ashtray impedes its usability. Provide a side grab bar that has at least 18 inches of clear space vertically between the grab bar and any other object, such as the toilet paper dispenser. Standards §§ 4.1.3(11), 4.22.4, 4.17.6, 4.26.2, Fig. 39.
viii. 3rd Level, Women’s Room near Gate C
(1) The paper towel dispenser is inaccessible because the controls are mounted at 58 inches above the finished floor. Provide a paper towel dispenser with the controls a maximum height above the finished floor of 48 inches for a forward approach or 54 inches for a side approach and that is accompanied by clear floor space of 30 by 48 inches that allows a forward or parallel approach by a person using a wheelchair. Standards §§ 4.1.3(13), 4.27.2, 4.27.3, 4.2.4, 4.2.5, 4.2.6.
(2) The toilet is inaccessible because the flush control is on the closed side. Provide a flush control mounted on the “open” side of the toilet’s clear floor space; 44 inches or less above the finished floor; and requiring a maximum of 5 pounds of force to operate; or provide an automatic flush device. Standards §§ 4.1.3(11), 4.22.4, 4.16.5, 4.17.2, 4.27.4.
(3) The side grab bar at the toilet is inaccessible because a wall-mounted ashtray impedes its usability. Provide a side grab bar that has at least 18 inches of clear space vertically between the grab bar and any other object, such as the toilet paper dispenser. Standards §§ 4.1.3(11), 4.22.4, 4.17.6, 4.26.2, Fig. 39.
ix. Skybox Level, Men’s Room
(1) The lavatory is inaccessible because the hot water pipes are not insulated or otherwise configured to protect against contact. Provide hot water and drain pipes that are insulated or otherwise configured to protect against contact. Standards §§ 4.1.3(11), 4.22.6, 4.19.4.
(2) The paper towel dispenser is inaccessible because the controls are mounted at 58 inches above the finished floor. Provide a paper towel dispenser with the controls a maximum height above the finished floor of 48 inches for a forward approach or 54 inches for a side approach and that is accompanied by clear floor space of 30 by 48 inches that allows a forward or parallel approach by a person using a wheelchair. Standards §§ 4.1.3(13), 4.27.2, 4.27.3, 4.2.4, 4.2.5, 4.2.6.
(3) No accessible coat hook has been provided. Provide a coat hook at a maximum height above the finished floor of 48 inches for a forward approach or 54 inches for a side approach and that is accompanied by clear floor space of 30 by 48 inches that allows a forward or parallel approach by a person using a wheelchair. Standards §§ 4.1.3(12)(a), 4.25.2, 4.25.3, 4.2.4, 4.2.5, 4.2.6.
x. Skybox Level, Women’s Room
(1) The lavatory is inaccessible because the hot water pipes are not insulated or otherwise configured to protect against contact. Provide hot water and drain pipes that are insulated or otherwise configured to protect against contact. Standards §§ 4.1.3(11), 4.22.6, 4.19.4.
(2) The paper towel dispenser is inaccessible because the controls are mounted at 58 inches above the finished floor. Provide a paper towel dispenser with the controls a maximum height above the finished floor of 48 inches for a forward approach or 54 inches for a side approach and that is accompanied by clear floor space of 30 by 48 inches that allows a forward or parallel approach by a person using a wheelchair. Standards §§ 4.1.3(13), 4.27.2, 4.27.3, 4.2.4, 4.2.5, 4.2.6.
(3) No accessible coat hook has been provided. Provide a coat hook at a maximum height above the finished floor of 48 inches for a forward approach or 54 inches for a side approach and that is accompanied by clear floor space of 30 by 48 inches that allows a forward or parallel approach by a person using a wheelchair. Standards §§ 4.1.3(12)(a), 4.25.2, 4.25.3, 4.2.4, 4.2.5, 4.2.6.
(4) Although there are 8 stalls, there is no ambulatory stall provided. Provide at least one stall that is exactly 36 inches wide with an outward swinging, self-closing door and parallel grab bars complying with Fig 30(d). Standards §§ 4.1.3(11), 4.22.4, Fig. 30(d).
h. Single User Toilet Room - Manager's / Coach's Room
i. The lavatory is inaccessible because the hot water pipes are not insulated or otherwise configured to protect against contact. Provide hot water and drain pipes that are insulated or otherwise configured to protect against contact. Standards §§ 4.1.3(11), 4.22.6, 4.19.4.
ii. The paper towel dispenser is inaccessible because the controls are mounted at 58 inches above the finished floor. Provide a paper towel dispenser with the controls a maximum height above the finished floor of 48 inches for a forward approach or 54 inches for a side approach and that is accompanied by clear floor space of 30 by 48 inches that allows a forward or parallel approach by a person using a wheelchair. Standards §§ 4.1.3(13), 4.27.2, 4.27.3, 4.2.4, 4.2.5, 4.2.6.
iii. No accessible coat hook has been provided. Provide a coat hook at a maximum height above the finished floor of 48 inches for a forward approach or 54 inches for a side approach and that is accompanied by clear floor space of 30 by 48 inches that allows a forward or parallel approach by a person using a wheelchair. Standards §§ 4.1.3(12)(a), 4.25.2, 4.25.3, 4.2.4, 4.2.5, 4.2.6.
iv. No accessible mirror has been provided. Provide a mirror with the bottom edge of its reflecting surface no more than 40 inches above the finished floor. Standards §§ 4.1.3(11), 4.22.6, 4.19.6.
v. There is no signage provided for the toilet room. Provide permanent room signage with upper case, sans serif or simple serif type letters and numerals, meeting the requirements of the Standards for character height, raised characters, finish and contrast, accompanied by Grade 2 Braille; mounted on the wall adjacent to the latch side of the door or on the nearest adjacent wall at a height of 60 inches above the finished floor to the centerline of the sign; and located so that a person may approach within 3 inches of the signage without encountering protruding objects or standing within the swing of a door. Standards §§ 4.1.2(7), 4.30.1, 4.30.4, 4.30.5, 4.30.6.
i. Players’ Locker Room
i. The entrance door is inaccessible because it has an opening width of only 30 inches. Provide a door with a clear opening of 32 inches with the door open 90 degrees, measured between the face of the door and the opposite stop. Standards §§ 4.1.3(7)(b), 4.13.5, Fig. 24.
ii. The roll-in shower is inaccessible due to multiple problems. Provide a shower in this room that is exactly 36 inches wide and 36 inches deep with a 48 inch long and 36 inch wide clear floor space alongside the shower opening, and an L-shaped shower seat mounted on the wall opposite the controls and extending the full depth of the stall; OR a shower that is at least 30 inches deep and 60 inches wide with no curb or threshold and with a 36 inch deep and 60 inch wide clear floor space at the shower opening. Ensure that the shower has grab bars, controls, a shower spray unit, and a seat, curb, and enclosure, if provided, that comply fully with the Standards and with Figs. 35, 36, and 37, as applicable. Standards §§ 4.1.3(11), 4.21, Figs. 35, 36, 37.
j. Employee Recreation Room The ramp leading to the employee recreation room on the lower level is inaccessible because of multiple problems with the handrails. Provide handrails that are between 1¼ inches and 1½ inches in diameter with a continuous gripping surface along both sides of the ramp, extending at least 12 inches beyond the top and bottom of the ramp parallel with the ground surface. Ensure that handrails are mounted between 34 inches and 38 inches above the ramp surface, with ends rounded or returned smoothly to the floor, wall, or post, and that they do not rotate within their fittings. Standards §§ 4.1.2(1), 4.1.2(2), 4.8.5.
4. Within 12 months of the effective date of this Agreement, the City will complete the following modifications to the Lyon Park Recreational Center, located at 1313 Halley Street:
a. Parking Although the parking lot has a total of 42 parking spaces, the van accessible parking space is in a gated area that is kept locked. On the shortest accessible route to the accessible entrance, provide 1 van accessible space designated as reserved for persons with disabilities. Ensure that van accessible spaces are a minimum of 96 inches wide and served by access aisles at least 96 inches wide. At all spaces designated as reserved for persons with disabilities, provide vertical signs with the International Symbol of Accessibility located such that they cannot be obstructed by parked vehicles. At van accessible spaces, provide an additional “Van-Accessible” sign located below the International Symbol of Accessibility. Ensure that all spaces and access aisles for persons with disabilities are flat and level, with slopes and cross-slopes not exceeding 1:50 in all directions, and that their surfaces are firm, stable, and slip-resistant. Standards §§ 4.1.2(5), 4.6, 4.30.7(1).
b. Entrances
i. The building has two accessible and two inaccessible entrances; however, they lack the appropriate signage. The accessible entrances are located at the front and side of the building and the inaccessible entrances are located at the rear of the building. Provide accessible directional signage with the International Symbol of Accessibility at inaccessible entrances directing users to the accessible entrance, and provide accessible signage with the International Symbol of Accessibility at all permanent accessible entrances. Standards §§ 4.1.3(8)(d), 4.1.3(16)(b), 4.13, 4.30.
ii. The route is inaccessible because the drinking fountain is a protruding object. Provide an accessible route at this location such that no objects with their bottom leading edges measuring between 27 inches and 80 inches above the finished floor protrude more than 4 inches into walks, halls, corridors, passageways, or aisles. Free-standing objects mounted on posts or pylons may overhang 12 inches maximum from 27 inches to 80 inches above the ground or finished floor. Standards §§ 4.1.2(3), 4.4.
iii. Front Entrance The ramp is inaccessible because the handrail is 42 inches high, it is on one side of the ramp only, and there are no extensions. Provide handrails that are between 1¼ inches and 1½ inches in diameter such that the inside handrail is continuous and both handrails have a continuous smooth gripping surface along both sides of the ramp extending at least 12 inches beyond the top and bottom of the ramp parallel with the ground surface; the handrails do not rotate within their fittings; and both handrails are mounted between 34 inches and 38 inches above the ramp surface, with ends rounded or returned smoothly to the floor, wall, or post. Standards §§ 4.1.2(1), 4.1.2(2), 4.3.8, 4.8.5.
c. Lobby Service Counter The counter is inaccessible because it is 44 inches high. Provide a counter on an accessible route such that a portion of the counter is at least 36 inches wide and no more than 36 inches above the finished floor. Standards §§ 4.1.1(2), 7.2(1), 4.1.3(1), 4.3.
d. Auditorium The auditorium is inaccessible to people with hearing impairments because there is a public address system, but no assistive listening system. Provide a permanently installed assistive listening system (ALS) or a portable ALS with an adequate number of electrical outlets or other supplementary wiring necessary to support a portable assistive listening system. Also provide two receivers for use by the general public and signage indicating their availability. Standards §§ 4.1.3(19)(b), 4.30, 4.33.
e. Toilet Rooms
i. 1st Floor, Men’s Room with Stalls The toilet room sign is inaccessible because the centerline is 65 inches above the finished floor. Provide a toilet room sign with the International Symbol of Accessibility and raised and Braille characters. The sign shall be mounted on the wall adjacent to the latch side of the door with the centerline of the sign at 60 inches above the finished floor and situated such that a person can approach within 3 inches of the sign without encountering an obstruction or standing within a door swing. Standards §§ 4.1.2(7)(d), 4.30.1, 4.30.4, 4.30.5, 4.30.6, 4.30.7.
ii. 1st Floor, Women’s Room with Stalls
(1) The toilet room sign is inaccessible because the centerline is 65 inches above the finished floor. Provide a toilet room sign with the International Symbol of Accessibility and raised and Braille characters. The sign shall be mounted on the wall adjacent to the latch side of the door with the centerline of the sign at 60 inches above the finished floor and situated such that a person can approach within 3 inches of the sign without encountering an obstruction or standing within a door swing. Standards §§ 4.1.2(7)(d), 4.30.1, 4.30.4, 4.30.5, 4.30.6, 4.30.7.
(2) The alternate style stall has a left side and a rear grab bar instead of parallel side grab bars. Provide a right side grab bar that is at least 42 inches in overall length, with the far end mounted at least 54 inches from the rear wall and the closer end 12 inches or less from the rear wall; mounted 33 to 36 inches above the finished floor; with a diameter between 1¼ and 1½ inches; with 1½ inches between the grab bar and the wall; and at least 1½ inches between the grab bar and any other object, such as the toilet paper dispenser. Standards §§ 4.1.3(11), 4.22.4, 4.17.6, 4.26.2, Figs. 30(a), (d).
iii. 1st Floor, Cafeteria Side, Men’s Room with Stalls This toilet room has signage identifying it as accessible; however, it is inaccessible. Provide accessible directional signage with the International Symbol of Accessibility at inaccessible toilet rooms indicating the location of the nearest accessible toilet room, and provide accessible signage with the International Symbol of Accessibility at all accessible toilet rooms. The sign shall be mounted on the wall adjacent to the latch side of the door with the centerline of the sign at 60 inches above the finished floor and situated such that a person can approach within 3 inches of the sign without encountering an obstruction or standing within a door swing. Standards §§ 4.1.2(7)(d), 4.1.6(3)(e)(iii), 4.30.1, 4.30.2, 4.30.3, 4.30.3, 4.30.5, 4.30.6, 4.30.7.
iv. 1st Floor, Cafeteria Side, Women’s Room with Stalls This toilet room has signage identifying it as accessible; however, it is inaccessible. Provide accessible directional signage with the International Symbol of Accessibility at inaccessible toilet rooms indicating the location of the nearest accessible toilet room, and provide accessible signage with the International Symbol of Accessibility at all accessible toilet rooms. The sign shall be mounted on the wall adjacent to the latch side of the door with the centerline of the sign at 60 inches above the finished floor and situated such that a person can approach within 3 inches of the sign without encountering an obstruction or standing within a door swing. Standards §§ 4.1.2(7)(d), 4.1.6(3)(e)(iii), 4.30.1, 4.30.2, 4.30.3, 4.30.3, 4.30.5, 4.30.6, 4.30.7.
v. 2nd Floor, Rear near Park, Men’s Single User Room
(1) The toilet room sign is inaccessible because it is centered 65 inches above the finished floor. Provide a toilet room sign with the International Symbol of Accessibility and raised and Braille characters. The sign shall be mounted on the wall adjacent to the latch side of the door with the centerline of the sign at 60 inches above the finished floor and situated such that a person can approach within 3 inches of the sign without encountering an obstruction or standing within a door swing. Standards §§ 4.1.2(7)(d), 4.30.1, 4.30.4, 4.30.5, 4.30.6, 4.30.7.
(2) The door, which is accessed through a front approach and which has both a closer and a latch, is inaccessible because it has insufficient push side clearance. On the push side of the door, provide maneuvering clearance at least 48 inches deep and provide a minimum of 12 inches of maneuvering clearance on the latch side of the door, or remove the closer or the latch. Standards §§ 4.1.3(7)(b), 4.13.6, Fig. 25(a).
(3) No accessible mirror has been provided. Provide a mirror with the bottom edge of its reflecting surface no more than 40 inches above the finished floor. Standards §§ 4.1.3(11), 4.22.6, 4.19.6.
(4) The rear grab bar at the toilet is inaccessible because it is 24 inches long. Provide a rear grab bar that is at least 36 inches in overall length with the closer end no more than 6 inches from the side wall. Standards §§ 4.1.3(11), 4.22.4, 4.16.4, Fig. 29.
vi. 2nd Floor, Rear near Park, Women’s Single User Room
(1) The toilet room sign is inaccessible because it is centered 65 inches above the finished floor. Provide a toilet room sign with the International Symbol of Accessibility and raised and Braille characters. The sign shall be mounted on the wall adjacent to the latch side of the door with the centerline of the sign at 60 inches above the finished floor and situated such that a person can approach within 3 inches of the sign without encountering an obstruction or standing within a door swing. Standards §§ 4.1.2(7)(d), 4.30.1, 4.30.4, 4.30.5, 4.30.6, 4.30.7.
(2) The door, which is accessed through a front approach and which has both a closer and a latch, is inaccessible because it has insufficient push side clearance. On the push side of the door, provide maneuvering clearance at least 48 inches deep and provide a minimum of 12 inches of maneuvering clearance on the latch side of the door, or remove the closer or the latch. Standards §§ 4.1.3(7)(b), 4.13.6, Fig. 25(a).
(3) No accessible mirror has been provided. Provide a mirror with the bottom edge of its reflecting surface no more than 40 inches above the finished floor. Standards §§ 4.1.3(11), 4.22.6, 4.19.6.
(4) The toilet is inaccessible because the flush control is on the closed side. Provide a flush control mounted on the “open” side of the toilet’s clear floor space; 44 inches or less above the finished floor; and requiring a maximum of 5 pounds of force to operate; or provide an automatic flush device. Standards §§ 4.1.3(11), 4.22.4, 4.16.5, 4.27.4.
(5) The rear grab bar at the toilet is inaccessible because it is 24 inches long. Provide a rear grab bar that is at least 36 inches in overall length with the closer end no more than 6 inches from the side wall. Standards §§ 4.1.3(11), 4.22.4, 4.16.4, Fig. 29.
vii. Clinic, Unisex Toilet Room
(1) The toilet room sign is inaccessible because it is centered at 65 inches above the finished floor. Provide a toilet room sign with the International Symbol of Accessibility and raised and Braille characters. The sign shall be mounted on the wall adjacent to the latch side of the door with the centerline of the sign at 60 inches above the finished floor and situated such that a person can approach within 3 inches of the sign without encountering an obstruction or standing within a door swing. Standards §§ 4.1.2(7)(d), 4.30.1, 4.30.4, 4.30.5, 4.30.6, 4.30.7.
(2) The rear grab bar at the toilet is inaccessible because the flush control, which is directly in front of the bar, impedes on the usability of the bar. Provide a rear grab bar that has at least 1½ inches between the grab bar and any other object. Standards §§ 4.1.3(11), 4.22.4, 4.16.4, 4.26.2, Fig. 39.
(3) The toilet paper dispenser is inaccessible because it is mounted above the side grab bar. Provide a toilet paper dispenser that is mounted within reach, with its top at least 1½ inches under the side grab bar, and centered at least 19 inches above the finished floor. Standards §§ 4.1.3(11), 4.22.4, 4.16.6, Fig. 29(b).
viii. Head Start Room, Unisex Toilet Room The toilet room sign is inaccessible because it is centered at 65 inches above the finished floor. Provide a toilet room sign with the International Symbol of Accessibility and raised and Braille characters. The sign shall be mounted on the wall adjacent to the latch side of the door with the centerline of the sign at 60 inches above the finished floor and situated such that a person can approach within 3 inches of the sign without encountering an obstruction or standing within a door swing. Standards §§ 4.1.2(7)(d), 4.30.1, 4.30.4, 4.30.5, 4.30.6, 4.30.7.
f. Routes within the Facility
i. From the Center to the Playground
(1) The route from the center to the playground is inaccessible because the ramp portion of the route rises more than 30 inches without an intermediate, level landing. Provide a ramp that is at least 36 inches wide with a slope not exceeding 1:12 and a cross slope not exceeding 1:50; with level landings at least as wide as the ramp and 60 inches long at the top and bottom of the ramp and for each 30 inches of rise; with level landings measuring at least 60 inches by 60 inches when the ramp changes direction; and edge protection that is at least 2 inches high at the drop off sides. Provide handrails that are between 1¼ inches and 1½ inches in diameter such that the inside handrail is continuous and both handrails have a continuous gripping surface along both sides of the ramp extending at least 12 inches beyond the top and bottom of the ramp parallel with the ground surface; the handrails do not rotate within their fittings; and both handrails are mounted between 34 inches and 38 inches above the ramp surface, with ends rounded or returned smoothly to the floor, wall, or post. Ensure that the ramp and approaches are designed so that water will not accumulate on walking surfaces. Standards §§ 4.1.2(1), 4.1.2(2), 4.3.8, 4.8.
(2) The walkway from the center to the playground is inaccessible because the ramped portion lacks handrails. Provide a ramp that is at least 36 inches wide and has a slope not exceeding 1:12 and a cross slope not exceeding 1:50. Provide level landings at the top and bottom of the ramp that are at least as wide as the ramp and at least 60 inches long. If the ramp changes direction, provide a level landing measuring at least 60 inches by 60 inches at the change in direction. On both sides of the ramp, provide handrails between 1¼ inches and 1½ inches in diameter with a continuous gripping surface. Ensure that the handrails extend at least 12 inches beyond the top and bottom of the ramp parallel with the ground surface, that they are mounted between 34 inches and 38 inches above the ramp surface, that they will not rotate within their fittings, and that they have ends that are rounded or return smoothly to floor, wall, or post. Provide edge protection that is at least 2 inches high at the ramp’s drop off sides. Ensure that the ramp and its level landing at the top and bottom are designed and maintained so that water does not accumulate on walking surfaces. Standards §§ 4.1.2(1), 4.1.2(2), 4.3.8, 4.8.
(3) The entrance to the playground equipment area is inaccessible because the accessible route is interrupted by an inaccessible surface. Provide at least one accessible route within the boundary of the site connecting these elements that, to the maximum extent feasible, coincides with the route for the general public. The accessible route must have a minimum clear width of 36 inches, or a minimum clear width of 42 inches if there is a turn around an obstruction less than 48 inches wide; have passing spaces at least 60 inches by 60 inches at least every 200 feet; have a minimum clear headroom of 80 inches; have a surface that is firm, stable, and slip resistant; have, in the absence of a curb ramp, ramp, elevator, or platform lift, no level changes in excess of ½ inch vertically; and have a running slope of less than 1:20 (5%) (or have been constructed as a fully accessible ramp) and a cross slope of less than 1:50 (2%). Standards §§ 4.1.3(1), 4.3, 4.5, Fig. 7.
ii. From the Rear of the Center The route from the rear of the center is inaccessible because a portion of the sloped apron at the walkway exceeds the maximum allowable slope of 1:12. Provide at least one accessible route within the boundary of the site connecting these elements that, to the maximum extent feasible, coincides with the route for the general public. The accessible route must have a minimum clear width of 36 inches, or a minimum clear width of 42 inches if there is a turn around an obstruction less than 48 inches wide; have passing spaces at least 60 inches by 60 inches at least every 200 feet; have a minimum clear headroom of 80 inches; have a surface that is firm, stable, and slip resistant; have, in the absence of a curb ramp, ramp, elevator, or platform lift, no level changes in excess of ½ inch vertically; and have a running slope of less than 1:20 (5%) (or have been constructed as a fully accessible ramp) and a cross slope of less than 1:50 (2%). Standards §§ 4.1.3(1), 4.3, 4.5, Fig. 7.
5. Within 12 months of the effective date of this Agreement, the City will complete the following modifications to the Edison Johnson Aquatic Center, located at 600 W. Murray Avenue:
a. Entrance
i. The curb cut at the parking lot serving the front entrance is inaccessible because it lacks detectable warnings. Provide a curb ramp that is at least 36 inches wide, has a maximum slope of 1:12, is located so that it cannot be obstructed by parked vehicles, and has a stable, firm, and slip-resistant surface with a detectable warning extending the full width and depth of the ramp. If the curb ramp is located where pedestrians must walk across it, provide either flared sides (with a maximum slope of 1:10) or handrails or guardrails to protect against cross traffic. Standards §§ 4.1.2(1), 4.1.2(2), 4.3.8, 4.7, Fig. 12.
ii. The building is inaccessible because fewer than 50% of its entrances are accessible. Provide two accessible entrances to the building and provide signage at all inaccessible entrances directing users to the accessible entrance(s). Standards §§ 4.1.3(8), 4.13, 4.30.
iii. The building is inaccessible because there is no signage identifying accessible entrances. Provide accessible directional signage with the International Symbol of Accessibility at inaccessible entrances directing users to the accessible entrance, and provide accessible signage with the International Symbol of Accessibility at all permanent accessible entrances. Standards §§ 4.1.3(8)(d), 4.1.3(16)(b), 4.13, 4.30.
b. Drinking Fountains Although two accessible drinking fountains are provided, there is no drinking fountain provided for people who have difficulty bending or stooping. For each accessible drinking fountain, provide a drinking fountain that is accessible to people who have difficulty bending or stooping. This can be accommodated by the use of a “hi-lo” fountain; by providing one fountain accessible to those who use wheelchairs and one fountain at a standard height convenient for those who have difficulty bending; by providing a fountain accessible to people who use wheelchairs and a cup dispenser, or by such other means as would achieve the required accessibility for each group of people. Standards § 4.1.3(10)(a).
c. Locker / Dressing Rooms
i. Men’s Toilet Room with Stalls
(1) The toilet room sign is inaccessible because it is mounted on the door. Provide a toilet room sign with raised and Braille characters. The sign shall be mounted on the wall adjacent to the latch side of the door with the centerline of the sign at 60 inches above the finished floor and situated such that a person can approach within 3 inches of the sign without encountering an obstruction or standing within a door swing. Standards §§ 4.1.2(7)(d), 4.30.1, 4.30.4, 4.30.5, 4.30.6.
(2) The lavatory is inaccessible because the hot water pipes are not insulated or otherwise configured to protect against contact. Provide hot water and drain pipes that are insulated or otherwise configured to protect against contact. Standards §§ 4.1.3(11), 4.22.6, 4.19.4.
(3) The side grab bar at the toilet in the designated accessible stall is inaccessible because the far end is mounted 47 inches from the rear wall and it is mounted 40 inches above the finished floor. Provide a side grab bar that is at least 42 inches in overall length, with the far end mounted at least 54 inches from the rear wall and the closer end 12 inches or less from the rear wall; mounted 33 to 36 inches above the finished floor; with a diameter between 1¼ and 1½ inches; with 1½ inches between the grab bar and the wall; and at least 1½ inches between the grab bar and any other object, such as the toilet paper dispenser. Standards §§ 4.1.3(11), 4.22.4, 4.17.6, 4.26.2, Figs. 30(a), (d).
(4) The toilet paper dispenser is inaccessible because it is mounted above the grab bar. Provide a toilet paper dispenser that is mounted with its top at least 1½ inches under the side grab bar and 36 inches or less from the rear wall and is centered at least 19 inches above the finished floor. Standards §§ 4.1.3(11), 4.22.4, 4.17.3, Fig. 30(d).
(5) The transfer shower is inaccessible because it measures 34 inches by 40 inches and it has the seat on the wall adjacent to the controls. Provide a shower in this room that is exactly 36 inches wide and 36 inches deep with a 48 inch long and 36 inch wide clear floor space alongside the shower opening, and an L-shaped shower seat mounted on the wall opposite the controls and extending the full depth of the stall; OR a shower that is at least 30 inches deep and 60 inches wide with no curb or threshold and with a 36 inch deep and 60 inch wide clear floor space at the shower opening. Ensure that the shower has grab bars, controls, a shower spray unit, and a seat, curb, and enclosure, if provided, that comply fully with the Standards and with Figs. 35, 36, and 37, as applicable. Standards §§ 4.1.3(11), 4.21, Figs. 35, 36, 37.
(6) The shower controls are inaccessible because they are mounted at 49 inches above the finished floor. Provide a shower with the controls a maximum height above the finished floor of 48 inches for a forward approach or 54 inches for a side approach and that is accompanied by clear floor space of 30 by 48 inches that allows a forward or parallel approach by a person using a wheelchair. Standards §§ 4.1.3(13), 4.27.2, 4.27.3, 4.2.4, 4.2.5, 4.2.6, Fig. 4.
(7) No accessible coat hook has been provided. Provide a coat hook at a maximum height above the finished floor of 48 inches for a forward approach or 54 inches for a side approach and that is accompanied by clear floor space of 30 by 48 inches that allows a forward or parallel approach by a person using a wheelchair. Standards §§ 4.1.3(12)(a), 4.25.2, 4.25.3, 4.2.4, 4.2.5, 4.2.6.
ii. Women’s Toilet Room with Stalls
(1) The toilet room sign is inaccessible because it is mounted on the door. Provide a toilet room sign with raised and Braille characters. The sign shall be mounted on the wall adjacent to the latch side of the door with the centerline of the sign at 60 inches above the finished floor and situated such that a person can approach within 3 inches of the sign without encountering an obstruction or standing within a door swing. Standards §§ 4.1.2(7)(d), 4.30.1, 4.30.4, 4.30.5, 4.30.6.
(2) The lavatory is inaccessible because the hot water pipes are not insulated or otherwise configured to protect against contact. Provide hot water and drain pipes that are insulated or otherwise configured to protect against contact. Standards §§ 4.1.3(11), 4.22.6, 4.19.4.
(3) The side grab bar at the toilet is inaccessible because the far end is mounted 47 inches from the rear wall and it is mounted 40 inches above the finished floor. Provide a side grab bar that is at least 42 inches in overall length, with the far end mounted at least 54 inches from the rear wall and the closer end 12 inches or less from the rear wall; mounted 33 to 36 inches above the finished floor; with a diameter between 1¼ and 1½ inches; with 1½ inches between the grab bar and the wall; and at least 1½ inches between the grab bar and any other object, such as the toilet paper dispenser. Standards §§ 4.1.3(11), 4.22.4, 4.17.6, 4.26.2, Figs. 30(a), (d).
(4) The toilet paper dispenser is inaccessible because it is mounted above the side grab bar. Provide a toilet paper dispenser that is mounted with its top at least 1½ inches under the side grab bar and 36 inches or less from the rear wall and is centered at least 19 inches above the finished floor. Standards §§ 4.1.3(11), 4.22.4, 4.17.3, Fig. 30(d).
(5) Although there are six stalls, there is no ambulatory stall provided. Provide at least one stall that is exactly 36 inches wide with an outward swinging, self-closing door and parallel grab bars complying with Fig 30(d). Standards §§ 4.1.3(11), 4.22.4, Fig. 30(d).
(6) The transfer shower is inaccessible because it measures 34 inches by 40 inches and it has the seat on the wall adjacent to the controls. Provide a shower in this room that is exactly 36 inches wide and 36 inches deep with a 48 inch long and 36 inch wide clear floor space alongside the shower opening, and an L-shaped shower seat mounted on the wall opposite the controls and extending the full depth of the stall; OR a shower that is at least 30 inches deep and 60 inches wide with no curb or threshold and with a 36 inch deep and 60 inch wide clear floor space at the shower opening. Ensure that the shower has grab bars, controls, a shower spray unit, and a seat, curb, and enclosure, if provided, that comply fully with the Standards and with Figs. 35, 36, and 37, as applicable. Standards §§ 4.1.3(11), 4.21, Figs. 35, 36, 37.
(7) The shower controls are inaccessible because they are mounted at 49 inches above the finished floor. Provide a shower with the controls a maximum height above the finished floor of 48 inches for a forward approach or 54 inches for a side approach and that is accompanied by clear floor space of 30 by 48 inches that allows a forward or parallel approach by a person using a wheelchair. Standards §§ 4.1.3(13), 4.27.2, 4.27.3, 4.2.4, 4.2.5, 4.2.6, Fig. 4.
(8) No accessible coat hook has been provided. Provide a coat hook at a maximum height above the finished floor of 48 inches for a forward approach or 54 inches for a side approach and that is accompanied by clear floor space of 30 by 48 inches that allows a forward or parallel approach by a person using a wheelchair. Standards §§ 4.1.3(12)(a), 4.25.2, 4.25.3, 4.2.4, 4.2.5, 4.2.6.
iii. Unisex Toilet Room
(1) The toilet room sign is inaccessible because it is mounted on the door at 65 inches above the floor to its centerline. Provide a toilet room sign with raised and Braille characters. The sign shall be mounted on the wall adjacent to the latch side of the door with the centerline of the sign at 60 inches above the finished floor and situated such that a person can approach within 3 inches of the sign without encountering an obstruction or standing within a door swing. Standards §§ 4.1.2(7)(d), 4.30.1, 4.30.4, 4.30.5, 4.30.6.
(2) The lavatory is inaccessible because the top of the rim is 36 inches above the finished floor. Provide a lavatory with the top of its rim or counter 34 inches or less above the finished floor; the bottom edge of the apron at least 29 inches above the finished floor; and knee and toe clearances that comply with Fig. 31. Standards §§ 4.1.3(11), 4.22.6, 4.19.2, Fig. 31.
(3) The toilet is inaccessible because its centerline measures 20 inches from the side wall. Provide a toilet with a centerline that measures 18 inches from the near side wall. Standards §§ 4.1.3(11), 4.22.4, 4.17.3, Fig. 30.
(4) The toilet is inaccessible because the flush control is on the closed side. Provide a flush control mounted on the “open” side of the toilet’s clear floor space; 44 inches or less above the finished floor; and requiring a maximum of 5 pounds of force to operate; or provide an automatic flush device. Standards §§ 4.1.3(11), 4.22.4, 4.16.5, 4.17.2, 4.27.4.
(5) The toilet paper dispenser is inaccessible because it is mounted above the side grab bar and interferes with the bar’s usability. Provide a toilet paper dispenser that is mounted within reach, with its top at least 1½ inches under the side grab bar, and centered at least 19 inches above the finished floor. Standards §§ 4.1.3(11), 4.22.4, 4.16.6, Fig. 29(b).
(6) The transfer shower is inaccessible because it measures 37 inches by 39½ inches and the grab bar is not continuous. Provide a shower in this room that is exactly 36 inches wide and 36 inches deep with a 48 inch long and 36 inch wide clear floor space alongside the shower opening, and an L-shaped shower seat mounted on the wall opposite the controls and extending the full depth of the stall; OR a shower that is at least 30 inches deep and 60 inches wide with no curb or threshold and with a 36 inch deep and 60 inch wide clear floor space at the shower opening. Ensure that the shower has grab bars, controls, a shower spray unit, and a seat, curb, and enclosure, if provided, that comply fully with the Standards and with Figs. 35, 36, and 37, as applicable. Standards §§ 4.1.3(11), 4.21, Figs. 35, 36, 37.
6. Within 12 months of the effective date of this Agreement, the City will complete the following modifications to the Solid Waste Operations Facility, located at 1833 Camden Avenue:
a. Parking Although the parking lot has a total of 76 parking spaces, 1 designated accessible van space and 1 designated accessible standard space are designated as reserved for people with disabilities. On the shortest accessible route to the accessible entrance, provide two additional standard spaces designated as reserved for people with disabilities. Standard accessible spaces shall be a minimum of 96 inches wide and served by access aisles at least 60 inches wide. Van accessible spaces shall be a minimum of 96 inches wide and served by access aisles at least 96 inches wide. All spaces designated as reserved for people with disabilities shall have vertical signs with the International Symbol of Accessibility located such that they cannot be obstructed by parked vehicles. Van accessible spaces shall have an additional “Van-Accessible” sign located below the International Symbol of Accessibility. Standards §§ 4.1.2(5), 4.6, 4.30.7(1).
b. Entrance
i. The route from the parking lot to the front entrance is inaccessible because the curb cut lacks detectable warnings. Provide a curb ramp that is at least 36 inches wide, has a maximum slope of 1:12, is located so that it cannot be obstructed by parked vehicles, and has a stable, firm, and slip-resistant surface with a detectable warning extending the full width and depth of the ramp. If the curb ramp is located where pedestrians must walk across it, provide either flared sides (with a maximum slope of 1:10) or handrails or guardrails to protect against cross traffic. Standards §§ 4.1.2(1), 4.1.2(2), 4.3.8, 4.7, Fig. 12.
ii. The route from the parking lot to the front entrance is inaccessible because it has an excessive slope of 2.5%. Provide at least one accessible route within the boundary of the site connecting these elements that, to the maximum extent feasible, coincides with the route for the general public. The accessible route must have a minimum clear width of 36 inches, or a minimum clear width of 42 inches if there is a turn around an obstruction less than 48 inches wide; have passing spaces at least 60 inches by 60 inches at least every 200 feet; have a minimum clear headroom of 80 inches; have a surface that is firm, stable, and slip resistant; have, in the absence of a curb ramp, ramp, elevator, or platform lift, no level changes in excess of ½ inch vertically; and have a running slope of less than 1:20 (5%) (or have been constructed as a fully accessible ramp) and a cross slope of less than 1:50 (2%). Standards §§ 4.1.3(1), 4.3, 4.5, Fig. 7.
iii. The building is inaccessible because fewer than 50% of its entrances are accessible. Provide three accessible entrances to the building and provide signage at all inaccessible entrances directing users to the accessible entrance(s). Standards §§ 4.1.3(8), 4.13, 4.30.
iv. The designated accessible entrance is inaccessible because it lacks a level approach within the door’s required maneuvering clearance. Provide a door so that the floor or ground area within the required clearances is level and clear. Standards §§ 4.1.3(7)(a), 4.13.6, Fig. 25.
c. Employee Break Room, Lower Level The ramp is inaccessible because the handrails lack extensions. Provide handrails that are between 1¼ inches and 1½ inches in diameter with a continuous gripping surface along both sides of the ramp, extending at least 12 inches beyond the top and bottom of the ramp parallel with the ground surface. Ensure that handrails are mounted between 34 inches and 38 inches above the ramp surface, with ends rounded or returned smoothly to the floor, wall, or post, and that they do not rotate within their fittings. Standards §§ 4.1.2(1), 4.1.2(2), 4.8.5.
d. Auditorium The auditorium is inaccessible to people with hearing impairments because although there are 50 or more fixed seats, there is no assistive listening system provided. Provide a permanently installed assistive listening system serving the fixed seating. Ensure that the seating served by the system is located within a 50 foot viewing distance of the stage or playing area and has a complete view of the stage or playing area. Provide two receivers for use by the general public and signage indicating their availability. Standards §§ 4.1.3(19)(b), 4.30, 4.33.
e. Drinking Fountain
i. The wall-mounted drinking fountain on the first floor is inaccessible because a recycling receptacle impedes on the clear floor space of the fountain. Provide a drinking fountain with clear knee space between the bottom of the apron and the finished floor or ground of at least 27 inches high, 30 inches wide, and 17 to 19 inches deep; and a minimum clear floor space of 30 inches by 48 inches to allow a person in a wheelchair to approach the unit facing forward. Standards §§ 4.1.3(10), 4.15.5(1), Figs. 27(a), (b).
ii. The route is inaccessible because the drinking fountain is a protruding object. Provide an accessible route at this location such that no objects with their bottom leading edges measuring between 27 inches and 80 inches above the finished floor protrude more than 4 inches into walks, halls, corridors, passageways, or aisles. Free-standing objects mounted on posts or pylons may overhang 12 inches maximum from 27 inches to 80 inches above the ground or finished floor. Standards §§ 4.1.2(3), 4.4.
f. Toilet Rooms
i. Employee Lounge, Men’s Single User Room The rear grab bar at the toilet is inaccessible because it is 24 inches long. Provide a rear grab bar that is at least 36 inches in overall length with the closer end no more than 6 inches from the side wall. Standards §§ 4.1.3(11), 4.22.4, 4.16.4, Fig. 29.
ii. Employee Lounge, Women’ Single User Room
(1) The route to the toilet room is inaccessible because recycling and trash receptacles impede on the clear floor space at the door. Provide an accessible route to the toilet room with required minimum width, passing space, head room, surface textures, slopes, and changes in level. Standards §§ 4.1.3(11), 4.22.1, 4.3.1, 4.3.2, 4.3.3, 4.3.4, 4.3.5, 4.3.6, 4.3.7, 4.3.8.
(2) The rear grab bar at the toilet is inaccessible because it is 24 inches long. Provide a rear grab bar that is at least 36 inches in overall length with the closer end no more than 6 inches from the side wall. Standards §§ 4.1.3(11), 4.22.4, 4.16.4, Fig. 29.
(3) The sanitary napkin dispenser is inaccessible because the controls are mounted at 55 inches above the finished floor. Provide a sanitary napkin dispenser with the controls a maximum height above the finished floor of 48 inches for a forward approach or 54 inches for a side approach and that is accompanied by clear floor space of 30 by 48 inches that allows a forward or parallel approach by a person using a wheelchair. Standards §§ 4.1.3(13), 4.27.2, 4.27.3, 4.2.4, 4.2.5, 4.2.6.
(4) The toilet is inaccessible because the flush control is on the closed side. Provide a flush control mounted on the “open” side of the toilet’s clear floor space; 44 inches or less above the finished floor; and requiring a maximum of 5 pounds of force to operate; or provide an automatic flush device. Standards §§ 4.1.3(11), 4.22.4, 4.16.5, 4.27.4.
iii. Women’s Toilet Room with Stalls The toilet in the designated accessible stall is inaccessible because the flush control is on the closed side. Provide a flush control mounted on the “open” side of the toilet’s clear floor space; 44 inches or less above the finished floor; and requiring a maximum of 5 pounds of force to operate; or provide an automatic flush device. Standards §§ 4.1.3(11), 4.22.4, 4.16.5, 4.17.2, 4.27.4.
|