Attachment G: Program Access Modifications at Emergency Shelters

 

 

1.         Horseshoe Lake Volunteer Fire Department, located at164 Highland Drive.

 

a.         Parking.  Although the parking lot has a total of 9 parking spaces, there is no van accessible space, there is no access aisle, and sign designating the parking space as accessible is mounted to low.  On the shortest accessible route to the accessible entrance, provide at least 1 van accessible space designated as reserved for people with disabilities.  Ensure that van accessible spaces are a minimum of 96 inches wide and served by access aisles at least 96 inches wide.  At all spaces designated as reserved for persons with disabilities, provide vertical signs with the International Symbol of Accessibility located such that they cannot be obstructed by parked vehicles.  At van accessible spaces, provide an additional "Van-Accessible" sign located below the International Symbol of Accessibility.  Ensure that all spaces and access aisles for persons with disabilities are flat and level, with slopes and cross-slopes not exceeding 1:50 in all directions, and that their surfaces are firm, stable, and slip-resistant.  Standards §§ 4.1.2(5), 4.6, 4.30.7(1).

 

b.         Entrance

 

i.          The entrance door is inaccessible because there is a 2¼ inch threshold, due to the drain.  Provide a door with a threshold no greater than ¼ inch, or between ¼ inch and ½ inch and beveled with a slope no greater than 1:2.  Standards §§ 4.13.8, 4.5.2.

 

ii.         The entrance door is inaccessible because knob hardware is used.  Provide a door with hardware that is easy to grasp with one hand and that does not require tight grasping, pinching, or twisting of the wrist to operate.  Lever-operated mechanisms, push-type mechanisms, and U-shaped handles are acceptable designs.  Standards § 4.13.9.

 

c.         Council Room.  The council room door is inaccessible because knob hardware is used.  Provide a door with hardware that is easy to grasp with one hand and that does not require tight grasping, pinching, or twisting of the wrist to operate.  Lever-operated mechanisms, push-type mechanisms, and U-shaped handles are acceptable designs.  Standards § 4.13.9.

 

d.         Kitchen.  The kitchen door is inaccessible because knob hardware is used.  Provide a door with hardware that is easy to grasp with one hand and that does not require tight grasping, pinching, or twisting of the wrist to operate.  Lever-operated mechanisms, push-type mechanisms, and U-shaped handles are acceptable designs.  Standards § 4.13.9.

 

e.         Single User Toilet Rooms.  The toilet rooms contain a number of inaccessible elements and are not accessible to people with disabilities.  Provide an accessible toilet room such that all of the room's elements, including signage, door, door hardware, clear floor space, water closet, urinal (if provided), grab bars, lavatory, mirror, controls, and dispensers, comply with the Standards.  Standards §§ 4.13, 4.16, 4.18, 4.19, 4.26, 4.27, 4.30, Figs. 28, 29.

 

f.          Men's Shower.  The shower in the men's shower room contains a number of inaccessible elements and is not accessible to people with disabilities.  Provide a shower in this room that is exactly 36 inches wide and 36 inches deep with a 48 inch long and 36 inch wide clear floor space alongside the shower opening, and an L-shaped shower seat mounted on the wall opposite the controls and extending the full depth of the stall; OR a shower that is at least 30 inches deep and 60 inches wide with no curb or threshold and with a 36 inch deep and 60 inch wide clear floor space at the shower opening.  Ensure that the shower has grab bars, controls, a shower spray unit, and a seat, curb, and enclosure, if provided, that comply fully with the Standards and with Figs. 35, 36, and 37, as applicable.  Standards § 4.21, Figs. 35, 36, 37.

 

2.         Earl City Hall Annex

 

a.         Main Route

 

i.          The route from the parking are to the building is inaccessible because the cross slope of the surface is 3.9%.  Provide at least one accessible route within the boundary of the site connecting these elements that, to the maximum extent feasible, coincides with the route for the general public.  The accessible route must have a minimum clear width of 36 inches, or a minimum clear width of 42 inches if there is a turn around an obstruction less than 48 inches wide; have passing spaces at least 60 inches by 60 inches at least every 200 feet; have a minimum clear headroom of 80 inches; have a surface that is firm, stable, and slip resistant; have, in the absence of a curb ramp, ramp, elevator, or platform lift, no level changes in excess of ½ inch vertically; and have a running slope of less than 1:20 (5%) (or have been constructed as a fully accessible ramp) and a cross slope of less than 1:50 (2%).  Standards §§ 4.3, 4.5, Fig. 7.

 

ii.         The route from the parking area to the building is inaccessible because the slope of the ramp up to the sidewalk is 28.8%, there are no handrails, and there is a 1 inch lip at the bottom.  Provide a ramp that is at least 36 inches wide with a slope not exceeding 1:12 and a cross slope not exceeding 1:50; with level landings at least as wide as the ramp and 60 inches long at the top and bottom of the ramp; and with edge protection at least 2 inches high at the drop off sides.  Provide handrails that are between 1¼ inches and 1½ inches in diameter with a continuous gripping surface along both sides of the ramp, extending at least 12 inches beyond the top and bottom of the ramp parallel with the ground surface.  Ensure that handrails are mounted between 34 inches and 38 inches above the ramp surface and 1½ inches from the wall, with ends rounded or returned smoothly to the floor, wall, or post, and that they do not rotate within their fittings.  Ensure that the ramp and approaches are designed so that water will not accumulate on walking surfaces.  Standards §§ 4.3.8, 4.8.

 

b.         Exterior Entrance.  The exterior entrance is inaccessible because it has a 1 inch threshold and knob hardware.  Provide a designated accessible entrance that has a minimum clear opening width of 32 inches with the door open 90 degrees, measured between the face of the door and the opposite stop; that has either an automatic door operator or clear and level maneuvering clearance that complies fully with Fig. 25; and that has a threshold not exceeding ½ inch in height and beveled with a slope no greater than 1:2.  Ensure that all hardware and operating devices have shapes that are easy to grasp with one hand and do not require tight grasping, pinching or twisting of the wrist to operate; and that they are mounted no higher than 48 inches above the finished floor.  Standards § 4.13, Figs. 24, 25.

 

c.         Single User Toilet Rooms.  The toilet rooms contain a number of inaccessible elements and are not accessible to people with disabilities.  Provide an accessible toilet room such that all of the room's elements, including signage, door, door hardware, clear floor space, water closet, urinal (if provided), grab bars, lavatory, mirror, controls, and dispensers, comply with the Standards.  Standards §§ 4.13, 4.16, 4.18, 4.19, 4.26, 4.27, 4.30, Figs. 28, 29.

 

3.         Marion Fire Department #2

 

a.         Parking.  The parking lot is inaccessible because there are no markings, no van accessible space, and no access aisles.  On the shortest accessible route to the accessible entrance, provide at least 1 van accessible space a minimum of 96 inches wide, served by an access aisle at least 96 inches wide, with a vertical sign with the International Symbol of Accessibility located such that it cannot be obstructed by parked vehicles, and with an additional "Van-Accessible" sign located below the International Symbol of Accessibility.  Standards §§ 4.1.2(5)(b), 4.6, 4.30.7(1).

 

b.         Exterior Entrance.  The exterior entrance door is inaccessible because there is a slope of 5.9% within the door's required maneuvering clearance.  Provide a door so that the floor or ground area within the required clearances is level and clear.  Standards § 4.13.6, Fig. 25.

 

c.         Single User Toilet Rooms.  The toilet rooms contain a number of inaccessible elements and are not accessible to people with disabilities.  Provide an accessible toilet room such that all of the room's elements, including signage, door, door hardware, clear floor space, water closet, urinal (if provided), grab bars, lavatory, mirror, controls, and dispensers, comply with the Standards.  Standards §§ 4.13, 4.16, 4.18, 4.19, 4.26, 4.27, 4.30, Figs. 28, 29.

 

d.         Drinking Fountain.  Although a drinking fountain is provided, there is no lower drinking fountain for use of people with disabilities.  Provide at least one drinking fountain with a spout height no higher than 36 inches, measured from the finished floor or ground surface to the spout outlet; and a spout located at the front of the unit that directs the water flow in a trajectory that is nearly parallel to the front of the unit and is positioned so the flow of water is within 3 inches of the front edge of the fountain and at least 4 inches high.  Ensure that fountain controls are operable with one hand, require 5 lbf or less to operate without tight grasping, pinching, or twisting of the wrist; and are front mounted or side mounted near the front edge.  Additionally, provide a drinking fountain that is accessible to people who have difficulty bending or stooping.  This can be accommodated by the use of a "hi-lo" fountain; by providing one fountain accessible to those who use wheelchairs and one fountain at a standard height convenient for those who have difficulty bending; by providing a fountain accessible to people who use wheelchairs and a cup dispenser; or by such other means as would achieve the required accessibility for each group of people.  Standards §§ 4.15, 4.27.4, Fig. 27.