ATTACHMENT I: Modifications to Newly Constructed Facilities

The chart below lists the facilities surveyed by the Department, the access issues identified during the survey, and the actions required to correct the access issues.Required actions are listed using an alphanumeric code. The key to the alphanumeric codes is provided in Attachment M to this Agreement.

In order to ensure that the following spaces and elements in County facilities for which construction was commenced after January 26, 1992, are readily accessible to and usable by persons with disabilities, the County will take the actions referenced by the alphanumeric code and described in detail in Attachment M to this Settlement Agreement within the time periods specified below, which time periods will begin to run on the effective date of this Agreement.

Item #

Access Issue

Required Action

Completion Date

1.

Adult Detention Facility, located at 502 South Lierman Avenue, Urbana

1.1.

Employee Parking Lot: The parking lot is inaccessible because it has no van accessible parking space.

P5

32 months

1.2.

Visitor Parking Lot:

1.2.1.

The parking lot is inaccessible because it has no van accessible parking space.

P5

32 months

1.2.2.

The north designated accessible parking space is inaccessible because it has a cross slope of 2.5%.

P4

32 months

1.3.

Route from Employee Parking to Employee Entrance: The route from the employee parking lot to the employee entrance is inaccessible because there is a 1.25 inch change in level at the entrance door.

AR1

32 months

1.4.

Route from Visitor Parking to Visitor Entrance:

1.4.1.

The route is inaccessible because is has a cross-slope of 4.5% near the designated accessible parking.

AR1

32 months

1.4.2.

The curb ramp is inaccessible because it has a cross-slope of 4.8%.

AR4

32 months

1.5.

Men's Single-User Toilet Room in Lobby:

1.5.1.

The signage provided is inaccessible because it is not mounted on the wall adjacent to the latch side of the door and does not have raised and Braille characters.

D15

32 months

1.5.2.

The door is inaccessible because it requires 15 pounds of force to open.

D3

32 months

1.5.3.

No accessible mirror has been provided.

TR5

32 months

1.5.4.

The paper towel dispenser is inaccessible because it is mounted with the controls 60 inches high.

CT4

32 months

1.5.5.

The baby changing table is inaccessible because it is 36 inches high when opened.

DW1

32 months

1.5.6.

The urinal is inaccessible because the rim is 18.5 inches high.

TR8

32 months

1.5.7.

The lavatory is inaccessible because the water supply and drain pipes are not insulated or otherwise configured to protect against contact.

LS2

32 months

1.6.

Women's Single-User Toilet Room in Lobby:

1.6.1.

The toilet room is inaccessible because the sign has no raised or Braille characters and is not mounted on the wall adjacent to the latch side of the door.

D15

32 months

1.6.2.

The door is inaccessible because it requires 15 pounds of force to open.

D3

32 months

1.6.3.

No accessible mirror has been provided.

TR5

32 months

1.6.4.

The paper towel dispenser is inaccessible because it is mounted with the controls 55 inches high.

CT4

32 months

1.6.5.

The SNAP dispenser is inaccessible because the controls require twisting of the wrist to operate.

CT2

32 months

1.6.6.

The baby changing table is inaccessible because it is 44 inches high when opened.

DW1

32 months

1.6.7.

The lavatory is inaccessible because the water supply and drain pipes are not insulated or otherwise configured to protect against contact.

LS2

32 months

1.6.8.

The toilet is inaccessible because the side grab bar is obstructed by the baby changing table.

TR15

32 months

1.6.9.
1.7.

Drinking Fountain in Medical Unit:

1.7.1.

The drinking fountain is inaccessible because it provides no toe clearance.

DF4

32 months

1.7.2.

Although a designated accessible drinking fountain is provided, there is no drinking fountain provided for people who have difficulty bending or stooping.

DF3

32 months

1.8.

Designated Accessible Cell in Disciplinary Segregation (Cell 1A26): There is no accessible cell provided.

PJ1

32 months

1.9.

Shower in Disciplinary Segregation: There is no accessible shower provided.

B2

32 months

2.

Juvenile Detention Center, located at 400 Art Bartell Drive, Urbana

2.1.

Parking:

2.1.1.

The parking lot is inaccessible because it has no van accessible parking space.

P5

32 months

2.1.2.

The designated accessible parking spaces are inaccessible because they have slopes of up to 3%.

P4

32 months

2.2.

Women's Single-User Toilet Room in Lobby:

2.2.1.

The door is inaccessible because it requires 11 pounds of force to open.

D3

32 months

2.2.2.

No accessible mirror has been provided.

TR5

32 months

2.2.3.

The toilet is inaccessible because the rear grab bar is obstructed by the soap dispenser.

TR15

32 months

2.3.

Men's Single-User Toilet Room in Lobby:

2.3.1.

The toilet room is inaccessible because the sign is mounted 44 inches high.

D15

32 months

2.3.2.

The door is inaccessible because it requires 11 pounds of force to open.

D3

32 months

2.3.3.

No accessible mirror has been provided.

TR5

32 months

2.3.4.

The toilet is inaccessible because the rear grab bar is obstructed by the soap dispenser.

TR15

32 months

2.4.

Learning Center Classroom #1, Room 159:

2.4.1.

The signage provided is inaccessible because it is mounted 66 inches high.

D15

32 months

2.4.2.

The door is inaccessible because it requires 16 pounds of force to open.

D3

32 months

2.4.3.

The door is inaccessible because the knob hardware requires tight grasping, pinching, or twisting of the wrist to operate.

D2

32 months

2.5.

Learning Center Classroom #2, Room 162:

2.5.1.

The signage provided is inaccessible because it is mounted 53 inches high.

D15

32 months

2.5.2.

The door is inaccessible because it requires 14 pounds of force to open.

D3

32 months

2.5.3.

The door is inaccessible because the knob hardware requires tight grasping, pinching, or twisting of the wrist to operate.

D2

32 months

2.6.

Learning Center Classroom #3, Room 163:

2.6.1.

The door is inaccessible because it requires 15 pounds of force to open.

D3

32 months

2.6.2.

The door is inaccessible because the knob hardware requires tight grasping, pinching, or twisting of the wrist to operate.

D2

32 months

2.7.

Cell Block 175, Unit F: The toilet room contains a number of inaccessible elements and is not accessible to people with disabilities.

TR1

32 months

3.

Champaign County Nursing Home, located at 500 Art Bartell Road, Champaign

3.1.

Visitor Parking: The parking lot is inaccessible because it has no van accessible parking space.

P5

6 months

3.2.

Employee Parking: The parking lot, with a total of 143 parking spaces only has 3 designated accessible spaces provided.This lot requires 1 van accessible space and 4 standard accessible spaces.

P1

6 months

3.3.

Route from Employee Parking to Employee Entrance: The route from the employee parking lot to the employee entrance is inaccessible because it has a cross-slope of up to 3.2%.

AR1

32 months

3.4.

Employee Entrance:

3.4.1.

The pull side of the door is inaccessible because it has only 12 inches of clear space on the latch side.

D5

32 months

3.4.2.

The door is inaccessible because there is a slope of 2.5% within the required maneuvering clearance.

D7

32 months

3.4.3.

The route to the card reader is inaccessible because it does not have 30 x 48 inches of clear floor space.

AR3

6 months

3.5.

Adult Day Care Entrance: The automatic door actuator is inaccessible because it lacks adequate clear floor space.

AR10

6 months

3.6.

Men's Toilet Room with Stalls (Room 539):

3.6.1.

The door is inaccessible because it requires 11 pounds of force to open.

D3

3 months

3.6.2.

The coat hook is inaccessible because it is mounted 59 inches high.

TR3

3 months

3.7.

Drinking Fountains in Lobby: The drinking fountain is inaccessible because it provides only 26.25 inches of knee clearance.

DF4

6 months

3.8.

Drinking Fountains between Toilet Rooms 538 & 539: This area is inaccessible because the high drinking fountain protrudes into the walkway and is not detectable to blind persons using a cane.

AR7

6 months

3.9.

Women's Toilet Room with Stalls (Room 538):

3.9.1.

The door is inaccessible because it requires 13 pounds of force to open.

D3

3 months

3.9.2.

The SNAP dispenser is inaccessible because the controls require twisting of the wrist to operate.

CT2

3 months

3.9.3.

The coat hook is inaccessible because it is mounted 60 inches high.

TR3

3 months

3.10.

Women's Toilet Room with Stalls in Adult Daycare (Room 163):

3.10.1.

The door is inaccessible because it requires 16 pounds of force to open.

D3

3 months

3.10.2.

The coat hook is inaccessible because it is mounted 61 inches high.

TR3

3 months

3.10.3.

The toilet is inaccessible because the arm rest obstructs the toilet.

TR24

6 months

3.11.

Men's Toilet Room with Stalls in Adult Daycare (Room 164):

3.11.1.

The door is inaccessible because it requires 16 pounds of force to open.

D3

3 months

3.11.2.

The coat hook is inaccessible because it is mounted 61 inches high.

TR3

3 months

3.11.3.

The toilet is inaccessible because the arm rest obstructs the toilet.

TR24

6 months

3.12.

Unisex Single-User Toilet Room in Medical Administration (Room 158):

3.12.1.

No accessible coat hook has been provided.

TR3

3 months

3.12.2.

The toilet is inaccessible because the centerline is 20 inches from the side wall.

TR7

3 months

3.12.3.

This area is inaccessible because the paper towel dispenser protrudes into the walkway and is not detectable to blind persons using a cane.

AR7

3 months

3.13.

Bathing Room (Room 145):

3.13.1.

The toilet is inaccessible because the side grab bar is mounted with the far end 48 inches from the rear wall.

TR17

6 months

3.14.

Single-User Toilet Room (Room 302, Typical One-Room Sleeping Room):

3.14.1.

The facility is inaccessible because, although the facility contains a fire alarm system, there are no visible alarms provided in the toilet room.

AL1

6 months

3.14.2.

The paper towel dispenser is inaccessible because it is mounted out of reach range.

CT3

6 months

3.14.3.

The lavatory is inaccessible because the bottom of the lavatory apron is 28.25 inches high and the knee space is obstructed by a trash can.

LS3

3 months

3.14.4.

The toilet is inaccessible because the arm rest obstructs the toilet.

TR24

6 months

3.14.5.

The toilet is inaccessible because the side grab bar is mounted with the far end 49 inches from the rear wall.

TR17

6 months

3.15.

Single-User Toilet Room (Room 314, Typical Two-Room Sleeping Room):

3.15.1.

The paper towel dispenser is inaccessible because it is mounted out of reach range.

CT3

3 months

3.15.2.

The toilet is inaccessible because the arm rest obstructs the toilet.

TR24

6 months

3.15.3.

The toilet is inaccessible because the centerline is 19 inches from the side wall.

TR7

6 months

3.16.

Bathing Room (Room 335):

3.16.1.

The paper towel dispenser is inaccessible because it is mounted out of reach range.

CT3

3 months

3.16.2.

The lavatory is inaccessible because the bottom of the lavatory apron is 28.5 inches high.

LS3

6 months

3.16.3.

The toilet is inaccessible because there are no grab bars provided.

TR18

6 months

3.16.4.

The toilet is inaccessible because the pull down grab bars obstruct the toilet.

TR24

6 months

3.16.5.

The toilet is inaccessible because the flush control is on the closed side.

TR4

6 months

3.17.

Bathing Room (Room 346): The toilet is inaccessible because the side grab bar is mounted with the far end 44 inches from the rear wall.

TR17

6 months

3.18.

Bathing Room (Room 436):

3.18.1.

The paper towel dispenser is inaccessible because it is mounted out of reach range.

CT3

3 months

3.18.2.

The lavatory is inaccessible because the bottom of the lavatory apron is 28.5 inches high.

LS3

6 months

3.18.3.

The toilet is inaccessible because there are no grab bars provided.

TR18

6 months

3.18.4.

The toilet is inaccessible because the pull down grab bars obstruct the toilet.

TR24

6 months

3.19.

Employee Single-User Toilet Room (Room 441):

3.19.1.

This area is inaccessible because the paper towel dispenser protrudes into the walkway and is not detectable to blind persons using a cane.

AR7

6 months

3.19.2.

The toilet is inaccessible because there are no grab bars provided.

TR18

6 months

3.20.

Lounge (Room 173): The pull side of the door is inaccessible because it has only 5 inches of clear space on the latch side.

D5

6 months

3.21.

Men's Single-User Toilet Room (Room 539):

3.21.1.

The door is inaccessible because it requires 11 pounds of force to open.

D3

3 months

3.21.2.

The coat hook is inaccessible because it is mounted 59 inches high.

TR3

3 months

4.

Champaign County Highway Department Highway Fleet Maintenance, located at 1605 East Main Street, Champaign

4.1.

Visitor Parking:

4.1.1.

The parking lot is inaccessible because it has no van accessible parking space.

P5

6 months

4.1.2.

The access aisle for the designated accessible parking space furthest from the entrance is inaccessible because it has a slope of 2.3%.

P4

6 months

4.2.

Employee Parking:

4.2.1.

The parking lot is inaccessible because it has no van accessible parking space.

P5

6 months

4.2.2.

The access aisle for the designated accessible parking space is inaccessible because it has a slope of 2.8%.

P4

6 months

4.3.

Entrance to the Meeting Room Wing: The door is inaccessible because it requires 12 pounds of force to open.

D3

3 months

4.4.

Highway Department Meeting Room: The doors to the meeting rooms are inaccessible because they require 12-12.5 pounds of force to open.

D3

3 months

4.5.

Engineering and Administration Office:

4.5.1.

The entrance door is inaccessible because it requires 13 pounds of force to open.

D3

3 months

4.5.2.

The door from the reception area to the offices is inaccessible because it requires 13 pounds of force to open.

D3

3 months

4.5.3.

The microfiche machine is inaccessible because there is only 24.5 inches of knee space provided.

C2

3 months

4.6.

Women's Single-User Toilet Room in the Engineering and Administration Office: The toilet is inaccessible because the centerline is 18.75 inches from the side wall.

TR7

6 months

4.7.

Men's Locker Room near Break Room:

4.7.1.

The bench is inaccessible because it is 9.5 inches deep and it provides no back support.

LR2

3 months

4.7.2.

There is no accessible locker provided.

LR3

3 months

4.7.3.

The door to the toilet room area is inaccessible because it requires 8 pounds of force to open.

D3

3 months

4.7.4.

The toilet is inaccessible because the centerline is 20 inches from the side wall.

TR7

32 months

4.7.5.

The coat hook is inaccessible because it is mounted 53 inches high.

TR3

3 months

4.7.6.

The shower is inaccessible because the controls are mounted too low and interfere with the use of the grab bar.

B2

32 months

4.8.

Women's Locker Room near Break Room:

4.8.1.

The door is inaccessible because it requires 13 pounds of force to open.

D3

3 months

4.8.2.

This area is inaccessible because the paper towel dispenser protrudes into the walkway and is not detectable to blind persons using a cane.

AR7

3 months

4.8.3.

The toilet is inaccessible because the centerline is 21 inches from the side wall.

TR7

32 months

4.8.4.

The coat hook is inaccessible because it is mounted 53 inches high.

TR3

3 months