ATTACHMENT K: Program Access in Existing FacilitiesPlease Note: Paragraph 42 of the Agreement requires that within three months of the effective date of this Agreement, the City will provide signage as necessary to comply with 28 C.F.R. § 35.163(b), after having surveyed all facilities that are the subject of this Agreement for the purpose of identifying those that have multiple entrances not all of which are accessible. The technical requirements and, where appropriate, the scoping requirements of the Standards are used as a guide for determining whether a program or activity held in an existing facility is “readily accessible to and usable by” persons with disabilities and for determining what changes are necessary to make this program or activity accessible if it continues to be provided in the existing facility in question. See 28 C.F.R. §§ 35.150(b)(1), 35.151. In order to ensure that each of the City’s programs, services, and activities operating at a facility that is the subject of this Agreement, when viewed in its entirety, is readily accessible to and usable by persons with mobility impairments, the City will take the actions referenced by the alphanumeric code and described in detail in Attachment M to this Settlement Agreement. Actions are to be completed before the end of the time specified in the Completion Date column. |
|||
Item # |
Access Issue
|
Required Action |
Completion Date |
---|---|---|---|
1 |
CITY HALL SOUTH, located at 55 Trinity Avenue |
||
1.1 |
Interior Signage. Much of the signage provided is inaccessible because it does not have raised or Braille characters. |
D26 |
24 months |
1.2 |
Interior Doors. Many of the interior doors are inaccessible because they require more than 5 pounds of force to open. |
D2 |
12 months |
1.3 |
Assistive Listening Systems. There are a number of conference rooms, council chambers, committee rooms, etc., but there are no assistive listening systems provided. |
AA5 |
30 months |
1.4 |
Women’s Toilet Rooms with Stalls: Ground Floor |
||
1.4.a |
The toilet room sign lacks the International Symbol of Accessibility and does not have raised or Braille characters. |
TR17 |
24 months |
1.4.b |
The seat cover dispenser is inaccessible because it is mounted 64 inches high. |
TR5 |
12 months |
1.4.c |
The paper towel dispenser protrudes into the walkway and is not detectable to blind persons using a cane. |
AR8 |
12 months |
1.4.d |
The lavatory is inaccessible because the rim or counter is 27 inches high to the bottom. |
TR11 |
24 months |
1.4.e |
The lavatory is inaccessible because the hot water pipes are not insulated or otherwise configured to protect against contact. |
TR12 |
24 months |
1.4.f |
The designated accessible stall is incorrectly configured as an ambulatory stall, and there is no standard accessible stall provided. |
ST15 |
30 months |
1.5 |
Men’s Toilet Rooms with Stalls: Ground Floor |
||
1.5.a |
The toilet room sign lacks the International Symbol of Accessibility and does not have raised or Braille characters. |
TR17 |
24 months |
1.5.b |
The seat cover dispenser is inaccessible because it is mounted 60 inches high. |
TR5 |
12 months |
1.5.c |
The paper towel dispenser protrudes into the walkway and is not detectable to blind persons using a cane. |
AR8 |
12 months |
1.5.d |
The lavatory is inaccessible because the rim or counter is 27¼ inches high to the bottom. |
TR11 |
24 months |
1.5.e |
The designated accessible stall is incorrectly configured as an ambulatory stall, and there is no standard accessible stall provided. |
ST15 |
30 months |
1.6 |
Drinking Fountains: Ground Floor. The drinking fountain is inaccessible because it requires 11 pounds of force to operate. |
DF2 |
12 months |
1.7 |
Ramp To Stage: 1st Floor. The ramp is inaccessible because the handrails do not have extensions at the top and bottom, they are mounted 2 inches from the wall, and the ends are not rounded or returned. |
R4 |
30 months |
1.8 |
Department of Finance. The counter is inaccessible because it is 40½ inches high. |
C6 |
24 months |
1.9 |
Contract Compliance Room 1700. The pull side of the door, which is accessed through a front approach, has 8½ inches of clearance on the latch side. |
D6 |
30 months |
1.10 |
Water Department Reception. The Water Department Reception counter protrudes into the walkway and is not detectable to blind persons using a cane. |
AR8 |
30 months |
1.11 |
Unisex Single-User Toilet Room 1st Floor: By Room 1450 |
||
1.11.a |
The toilet room door swings into the required clear floor space at the lavatory. |
TR6 |
30 months |
1.11.b |
No accessible mirror has been provided. |
TR14 |
12 months |
1.11.c |
The seat cover dispenser is inaccessible because it is mounted with the controls 58 inches high. |
TR5 |
12 months |
1.11.d |
The paper towel dispenser protrudes into the walkway and is not detectable to blind persons using a cane. |
AR8 |
12 months |
1.11.e |
The lavatory is inaccessible because the rim or counter is 26¾ inches high to the bottom. |
TR11 |
24 months |
1.11.f |
The lavatory is inaccessible because the hot water pipes are not insulated or otherwise configured to protect against contact. |
TR12 |
24 months |
1.11.g |
The toilet is inaccessible because the centerline is 22 inches from the side wall. |
SU15 |
30 months |
1.11.h |
The toilet is inaccessible because the flush control is on the closed side. |
SU1 |
30 months |
1.11.i |
The side grab bar at the toilet is inaccessible because it is obstructed by the toilet paper dispenser. |
SU7 |
12 months |
1.11.j |
The toilet is inaccessible because both rear grab bars are 24 inches long; one grab bar is approximately 47 inches high and is mounted with the near end more than 6 inches from the side wall; and the other grab bar is obstructed by the flush valve and the higher grab bar and is mounted ¾ inches from the wall where it is bent around the pipe. |
SU2 |
30 months |
1.12 |
Unisex Single-User Toilet Room 1st Floor: By Room 1750 |
||
1.12.a |
The toilet room door swings into the required clear floor space at the lavatory. |
TR6 |
24 months |
1.12.b |
No accessible mirror has been provided. |
TR14 |
12 months |
1.12.c |
The paper towel dispenser protrudes into the walkway and is not detectable to blind persons using a cane. |
AR8 |
12 months |
1.12.d |
The lavatory is inaccessible because the rim or counter is 25½ inches high to the bottom. |
TR11 |
24 months |
1.12.e |
The side grab bar at the toilet is inaccessible because it is obstructed by the toilet paper dispenser. |
SU7 |
12 months |
1.12.f |
The toilet is inaccessible because both rear grab bars are 24 inches long; one grab bar is approximately 47 inches high; and the other grab bar is obstructed by the flush valve and the higher grab bar and is mounted ¾ inches from the wall where it is bent around the pipe |
SU2 |
30 months |
1.13 |
Drinking Fountains 1st Floor: West Side By Room 1450. The drinking fountain is inaccessible because the height of the water flow is 1 inch, and the controls require 9 pounds of force to operate. |
DF1 |
12 months |
1.14 |
Drinking Fountains 1st Floor: East Side By Room 1750. The drinking fountain is inaccessible because the controls require 9 pounds of force to operate. |
DF2 |
12 months |
1.15 |
1st Floor: Procurement Room 1790. The counter is inaccessible because it is 43½ inches high. |
C6 |
24 months |
1.16 |
1st Floor: Constituent Services Room 1920 |
||
1.16.a |
The counter is inaccessible because it is 43 inches high. |
C6 |
24 months |
1.16.b |
The counter protrudes into the walkway and is not detectable to blind persons using a cane. |
AR8 |
24 months |
1.17 |
1st Floor: Conference Room 1900. The pull side of the door, which is accessed through a front approach, has only 8 inches of clear space on the latch side. |
D6 |
24 months |
1.18 |
Elevators: Cab 2. The elevator is inaccessible because the hoistway signage does not have Braille. |
E12 |
24 months |
1.19 |
2nd Floor: Council Chambers |
||
1.19.a |
The Council Chamber, containing 230 fixed seats, is inaccessible because no wheelchair seating areas are provided. A total of 4 wheelchair seating areas is required. |
AA6 |
30 months |
1.19.b |
The ramp to the council platform is inaccessible because it has a slope of 12.2% near the top, a landing 38 inches by 42 inches at the change in direction, and the handrails are 31 inches high and mounted 2½ inches from the wall. |
R3 |
30 months |
1.20 |
Accessible Route 2nd Floor: From Elevators to Conference Room #1. The defibrillator protrudes into the walkway and would not be detectable to a blind person using a cane. |
AR8 |
12 months |
1.21 |
Women’s and Men’s Toilet Room with Stalls: 2nd Floor East and West Side. The toilet rooms lack accessible directional signage with the International Symbol of Accessibility indicating the location of the nearest accessible toilet room. |
TR16 |
12 months |
1.22 |
3rd Floor: HVAC Division Room 3700 |
||
1.22.a |
The pull side of the door, which is accessed through a front approach, has 14½ inches of clear space on the latch side. |
D6 |
24 months |
1.22.b |
The counter is inaccessible because it is 43 inches high. |
C6 |
24 months |
1.22.c |
The counter protrudes into the walkway and is not detectable to blind persons using a cane. |
AR8 |
24 months |
1.23 |
3rd Floor: Helen Smith, Arborist |
||
1.23.a |
The counter is inaccessible because it is 43 inches high. |
C6 |
24 months |
1.23.b |
The counter protrudes into the walkway and is not detectable to blind persons using a cane. |
AR8 |
24 months |
1.24 |
3rd Floor: Main Electrical. The counter protrudes into the walkway and is not detectable to blind persons using a cane. |
AR8 |
24 months |
1.25 |
3rd Floor: Bureau of Buildings Room 3900. The computer desks are inaccessible because they do not have sufficient knee space. |
C3 |
24 months |
1.26 |
3rd Floor: Bureau of Planning Room 3350. The courtesy phone is inaccessible because it is mounted 60 inches high. |
TR5 |
12 months |
1.27 |
3rd Floor: Housing Code Enforcement Room 3450 |
||
1.27.a |
The counter is inaccessible because it is 42½ inches high. |
C6 |
24 months |
1.27.b |
The counter protrudes into the walkway and is not detectable to blind persons using a cane. |
AR8 |
24 months |
1.28 |
Unisex Single-User Toilet Room 3rd Floor Near Room 3800. The toilet room lacks accessible directional signage with the International Symbol of Accessibility indicating the location of the nearest accessible toilet room. |
TR16 |
12 months |
1.29 |
Unisex Single-User Toilet Room 3rd Floor Near Room 3450. The toilet room lacks accessible directional signage with the International Symbol of Accessibility indicating the location of the nearest accessible toilet room. |
TR16 |
12 months |
1.30 |
Drinking Fountain 4th Floor: Near Room 4700. The drinking fountain is inaccessible because the controls require 9 pounds of force to operate. |
DF2 |
24 months |
1.31 |
Unisex Single-User Toilet Room 4th Floor Near Room 4800. The toilet room lacks accessible directional signage with the International Symbol of Accessibility indicating the location of the nearest accessible toilet room. |
TR16 |
12 months |
1.32 |
4th Floor: Public Works Department (Under Construction). The counter is inaccessible because it is 44 inches high. |
C6 |
24 months |
1.33 |
4th Floor: Sanitary Services Room 4800. The counter protrudes into the walkway and is not detectable to blind persons using a cane. |
AR8 |
24 months |
1.34 |
4th Floor: Traffic and Transportation Room 4900. The counter is inaccessible because it is 42 inches high. |
C6 |
24 months |
1.35 |
Drinking Fountains 4th Floor: Near Room 4400. The drinking fountain is inaccessible because the controls require 20 pounds of force to operate. |
DF2 |
12 months |
1.36 |
Women’s Toilet Room With Stalls 4th Floor Near Room 4400. The toilet room lacks accessible directional signage with the International Symbol of Accessibility indicating the location of the nearest accessible toilet room. |
TR16 |
12 months |
1.37 |
Men’s Toilet Room With Stalls 4th Floor Near Room 4400. The toilet room lacks accessible directional signage with the International Symbol of Accessibility indicating the location of the nearest accessible toilet room. |
TR16 |
12 months |
2 |
ATLANTA CITY HALL TOWER, located at 68 Mitchell St., NW |
||
2.1 |
Entrances. The accessible entrances are locked at all times, and a call button is provided. |
D14 |
24 months |
2.2 |
Interior Doors. Many of the interior doors throughout the facility are inaccessible because they require more than 5 pounds of force to open. |
D2 |
24 months |
2.3 |
Interior Signage. The signage provided throughout the facility is inaccessible because it lacks raised and Braille characters. |
D26 |
24 months |
2.4 |
Interior Routes. The AED’s throughout the facility protrude into the walkway and are not detectable to blind persons using a cane. |
AR8 |
12 months |
2.5 |
Elevators 2 and 3 |
||
2.5.a |
The elevators are inaccessible because the hall lanterns provide no audible arrival signal on some floors. |
E11 |
24 months |
2.5.b |
The elevator is inaccessible because the hall call buttons are mounted 38½ inches high on some floors. |
E3 |
24 months |
2.5.c |
The elevator is inaccessible because the hoistway signage is mounted 47 inches high. |
E12 |
24 months |
2.5.d |
The elevator is inaccessible because the emergency communications system is not identified by raised lettering, the door requires tight grasping to open, and the handset cord is less than 29 inches long. |
E8 |
24 months |
2.6 |
Exterior Route: From Corner of Mitchell & Washington to Entrance Ramp. The route is inaccessible because it has uneven and broken pavement, and it slopes between 6.4% and 8.1% without having any ramp features. |
AR1 |
30 months |
2.7 |
Exterior Ramp: To City Hall Tower Washington St. Entrance. The ramp is inaccessible because it slopes 9.1% at the bottom and 10.9% at the top, there is no edge protection at the drop off sides, and the handrails lack 12 inch long extensions at the bottom. |
R5 |
30 months |
2.8 |
Drinking Fountains 2nd Floor |
||
2.8.a |
Both drinking fountains are inaccessible because the flow of water is less than 4 inches high. |
DF7 |
12months |
2.8.b |
The drinking fountains protrude into the walkway and are not detectable to blind persons using a cane. |
AR8 |
12 months |
2.9 |
Women’s Toilet Room With Stalls 3rd Floor |
||
2.9.a |
The seat cover dispenser is inaccessible because it is mounted 62 inches above the finished floor. |
TR5 |
12 months |
2.9.b |
The lavatory is inaccessible because the rim or counter is 26½ inches high to the bottom. |
TR11 |
24 months |
2.9.c |
The side grab bar at the designated accessible toilet is inaccessible because it is obstructed by the toilet paper dispenser. |
ST8 |
12 months |
2.9.d |
The side grab bar at the designated accessible toilet is inaccessible because it is mounted 2 inches from the side wall and with the far end 45 inches from the rear wall. |
ST6 |
12 months |
2.9.e |
The rear grab bar at the toilet is inaccessible because it is 33 inches long, it is obstructed by the flush valve, and it is mounted a varying distance from the rear wall. |
ST3 |
30 months |
2.10 |
Men’s Toilet Room With Stalls 3rd Floor |
||
2.10.a |
The seat cover dispenser is inaccessible because it is mounted 62 inches above the finished floor. |
TR5 |
12 months |
2.10.b |
The lavatory is inaccessible because the rim or counter is 26½ inches high to the bottom. |
TR11 |
24 months |
2.10.c |
The urinal is inaccessible because its rim is 22 inches above the finished floor. |
TR20 |
24 months |
2.10.d |
The designated accessible toilet is inaccessible because the flush control is on the closed side. |
ST2 |
30 months |
2.10.e |
The side grab bar at the designated accessible toilet is inaccessible because it is obstructed by the toilet paper dispenser. |
ST8 |
12 months |
2.10.f |
The side grab bar at the designated accessible toilet is inaccessible because it is 35 inches long and is mounted a varying distance from the side wall with the far end 38½ inches from the rear wall. |
ST6 |
24 months |
2.10.g |
The rear grab bar at the toilet is inaccessible because it is 33 inches long, is obstructed by the flush valve, and is mounted a varying distance from the rear wall. |
ST3 |
24 months |
2.11 |
3rd Floor: HR Policy and Planning Room 3200. The door is inaccessible because it has knob hardware. |
D1 |
24 months |
2.12 |
3rd Floor: Auditorium Room 3100. The auditorium is inaccessible because it has no assistive listening system provided. |
AA5 |
24 months |
2.13 |
Drinking Fountain 4th Floor |
||
2.13.a |
The drinking fountain is inaccessible because the controls require 8 pounds of force to operate. |
DF2 |
12 months |
2.13.b |
The drinking fountain protrudes into the walkway and is not detectable to blind persons using a cane. |
AR8 |
12 months |
2.14 |
Men’s Single-User Toilet Room 4th Floor Near Snack Bar Area. The toilet room lacks accessible directional signage with the International Symbol of Accessibility indicating the location of the nearest accessible toilet room. |
T16 |
12 months |
2.15 |
Women’s Single-User Toilet Room 4th Floor Near Snack Bar Area. The toilet room lacks accessible directional signage with the International Symbol of Accessibility indicating the location of the nearest accessible toilet room. |
TR16 |
12 months |
2.16 |
5th Floor: Law Department Suite 5100 |
||
2.16.a |
The exit sign protrudes into the walkway and is not detectable to blind persons using a cane. |
AR8 |
24 months |
2.16.b |
The drinking fountain is inaccessible because the control requires 6 pounds of force to operate. |
DF2 |
12 months |
2.16.c |
The drinking fountain protrudes into the walkway and is not detectable to blind persons using a cane. |
AR8 |
12 months |
2.17 |
Inaccessible 5th Floor Toilet Rooms. The toilet rooms lack accessible directional signage with the International Symbol of Accessibility indicating the location of the nearest accessible toilet room. |
TR16 |
24 months |
2.18 |
Drinking Fountain 5th Floor Atrium: East. The drinking fountain is inaccessible because the water flow is less than 4 inches high. |
DF7 |
12 months |
2.19 |
6th Floor: Accounts Payable Suite 6100 |
||
2.19.a |
The exit sign protrudes into the walkway and is not detectable to blind persons using a cane. |
AR8 |
24 months |
2.19.b |
The counter protrudes into the walkway and is not detectable to blind persons using a cane. |
AR8 |
24 months |
2.19.c |
The route to room 6190 is inaccessible because it narrows to 28½ inches wide. |
AR3 |
24 months |
3 |
CYCLORAMA & CIVIL WAR MUSEUM, located at 800-C Cherokee Ave, SE |
||
3.1 |
Parking. In the parking lot, with a total of 316 parking spaces, all of the rear tier of designated accessible parking spaces have “Van-Accessible” signage, although 5 of the spaces do not have van accessible access aisles, and the 4 van accessible parking spaces nearest to the zoo entrance have no vertical signage. This lot requires 1 van accessible space and 7 standard accessible spaces. |
P3 |
30 months |
3.2 |
Accessible Route. The route leading to the exterior entrance is inaccessible because the running slope is 8.7% and the route has no ramp features. |
AR1 |
30 months |
3.3 |
1st Floor Auditorium |
||
3.3.a |
The door is inaccessible because it requires 10 pounds of force to open. |
D2 |
12 months |
3.3.b |
The auditorium, with 187 fixed seats, is inaccessible because a fixed companion seat is not provided for all wheelchair seating locations. |
AA6 |
30 months |
3.3.c |
The ramp on the route connecting the wheelchair seating areas and the stage is inaccessible because it has a handrail on only one side, the existing handrail has no extensions at the top or bottom, and the ramp lacks edge protection. |
R5 |
30 months |
3.3.d |
The auditorium is inaccessible because it lacks fixed aisle seating without armrests. |
AA2 |
30 months |
3.3.e |
There is no signage informing the public of the availability of an assistive listening system. |
AA3 |
30 months |
3.4 |
Women’s Toilet Room with Stalls 1st Floor |
||
3.4.a |
The lavatory is inaccessible because the hot water pipes are not insulated or otherwise configured to protect against contact. |
TR12 |
24 months |
3.4.b |
The designated accessible stall is incorrectly configured as an ambulatory stall, and there is no standard accessible stall provided. |
ST15 |
30 months |
3.5 |
Men’s Toilet Room With Stalls 1st Floor |
||
3.5.a |
The lavatory is inaccessible because the hot water pipes are not insulated or otherwise configured to protect against contact. |
TR12 |
24 months |
3.5.b |
The lavatory is inaccessible because it has twist-type hardware. |
TR10 |
24 months |
3.5.c |
The lower urinal is inaccessible because the rim is 19 inches high. |
TR20 |
24 months |
3.5.d |
The designated accessible stall is incorrectly configured as an ambulatory stall, and there is no standard accessible stall provided. |
ST15 |
30 months |
3.6 |
Elevator. The elevator is inaccessible because the car control buttons do not have Braille or raised characters to the left of the buttons and the main entry floor is not designated by a raised star. |
E4 |
30 months |
3.7 |
Interior Accessible Route: 1st Floor. The area under the escalators is inaccessible because there are less than 80 inches of head room provided. |
AR7 |
24 months |
3.8 |
Ramp: From Auditorium to Cyclorama. The ramp is inaccessible because the handrails are mounted 32½ inches high. |
R4 |
24 months |
3.9 |
Cyclorama. The Cyclorama is inaccessible because there are no fixed companion seats next to the wheelchair locations. |
AA6 |
30 months |
4 |
ATLANTA POLICE DEPARTMENT ZONE 2, located at 3120 Maple Drive |
||
4.1 |
Parking. The parking lot, with a total of 43 parking spaces, is inaccessible because it only has no spaces designated as accessible. This lot requires 1 van accessible space and 1 standard accessible space. |
P3 |
24 months |
4.2 |
Accessible Route: From Parking Lot to Exterior Entrance. The route is inaccessible because a barrel and sign placed in the walkway obstruct the route and because the surface has a change in level in excess of ½ inch vertically. |
AR1 |
30 months |
4.3 |
Front Desk Counter. The counter protrudes into the walkway and is not detectable to blind persons using a cane. |
AR8 |
24 months |
4.4 |
Men’s Toilet Room With Stalls |
||
4.4.a |
The toilet room sign is mounted on the door and has no raised or Braille characters. |
TR18 |
12 months |
4.4.b |
The door is inaccessible because it requires 15 pounds of force to open. |
D2 |
12 months |
4.4.c |
The pull side of the door to the toilet room, which is accessed through a front approach, is inaccessible because the maneuvering space is obstructed by a table. |
D6 |
12 months |
4.4.d |
There is no accessible toilet stall provided. |
ST15 |
30 months |
4.5 |
Women’s Single-User Toilet Room |
||
4.5.a |
The toilet room sign is mounted on the door and has no raised or Braille characters. |
TR18 |
12 months |
4.5.b |
The pull side of the door to the toilet room, which is accessed through a front approach, is inaccessible because the maneuvering space is blocked by a chair. |
D6 |
12 months |
4.5.c |
The push side of the door to the women’s toilet room, which is accessed through a front approach and which has both a closer and a latch, is inaccessible because it has only 9 inches of clearance on the latch side. |
D7 |
30 months |
4.5.d |
There is insufficient turning space within the toilet room. |
TR19 |
30 months |
4.5.e |
The toilet is inaccessible because the centerline is 19 inches from the side wall. |
SU15 |
30 months |
4.5.f |
The toilet is inaccessible because the flush control is on the closed side. |
SU1 |
30 months |
4.5.g |
The overall length of the side grab bar is 30 inches and the distance from the farther end to the rear wall is 33½ inches. |
SU6 |
24 months |
4.5.h |
The overall length of rear grab bar is 24 inches, and the distance from the closer end to the side wall is 6½ inches. |
SU3 |
24 months |
5 |
ATLANTA POLICE DEPARTMENT ZONE 6, located at 2025 Hosea Williams Drive, SE |
||
5.1 |
Accessible Route: Ramp. The ramp on the route to the main entrance is inaccessible because it slopes up to 12.1%, the cross-slope is greater than 2.0%, the bottom landing is not level, and the handrails are 33 inches high and lack extensions. |
R5 |
30 months |
5.2 |
Exterior Entrance and Doors. The building does not have directional signage posted at inaccessible entrances and does not have the International Symbol of Accessibility posted at accessible entrances. |
D16 |
12 months |
5.3 |
Men’s Single-User Toilet Room |
||
5.3.a |
The toilet room sign is mounted on the door and has no raised and Braille characters. |
TR18 |
24 months |
5.3.b |
The door swings into the clear floor space of the lavatory. |
TR6 |
30 months |
5.3.c |
Although an audible alarm is provided in this facility, there is no visual alarm appliance in the toilet room. |
TR21 |
30 months |
5.3.d |
No accessible mirror has been provided. |
TR14 |
12 months |
5.3.e |
The lavatory is inaccessible because the rim or counter is 27 inches high to the bottom. |
TR11 |
24 months |
5.3.f |
The lavatory is inaccessible because the hot water pipes are not insulated or otherwise configured to protect against contact. |
TR12 |
24 months |
5.3.g |
The toilet is inaccessible because the flush control is mounted on the closed side. |
SU1 |
30 months |
5.3.h |
There is no accessible toilet paper dispenser provided. |
SU17 |
12 months |
5.3.i |
The rear grab bar at the toilet is inaccessible because it is mounted 7 inches from the side wall. |
SU3 |
12 months |
5.4 |
Women’s Single-User Toilet Room |
||
5.4.a |
The toilet room sign is mounted on the door and has no raised and Braille characters. |
TR18 |
24 months |
5.4.b |
The second door leading to the toilet room is blocked by a ladder and prevented from opening to a 90 degree angle. |
D25 |
12 months |
5.4.c |
Although an audible alarm is provided in this facility, there is no visual alarm appliance in the toilet room. |
TR21 |
30 months |
5.4.d |
No accessible mirror has been provided. |
TR14 |
12 months |
5.4.e |
The lavatory is inaccessible because the rim or counter is 27¼ inches high to the bottom. |
TR11 |
24 months |
5.4.f |
The lavatory is inaccessible because the hot water pipes are not insulated or otherwise configured to protect against contact. |
TR12 |
24 months |
5.4.g |
The toilet is inaccessible because the top of the seat is 16 inches high. |
SU18 |
30 months |
5.4.h |
The toilet is inaccessible because there is insufficient clear floor space due to the lavatory post. |
SU16 |
30 months |
5.4.i |
The toilet is inaccessible because the centerline is 16 inches from the wall. |
SU15 |
30 months |
5.4.j |
The toilet is inaccessible because the flush control is mounted on the closed side. |
SU1 |
30 months |
6 |
BOISFEUILLET JONES ATLANTA CIVIC CENTER, located at 395 Piedmont Ave, NE |
||
6.1 |
Parking. All of the lots, which have a total of 882 parking spaces, have a total of 24 designated accessible parking spaces, many of which have slopes and cross-slopes exceeding 2% or are lacking vertical signage; there is no “Van-Accessible” signage; and several of the designated accessible spaces are in the Piedmont lot, which has no access aisles and no accessible route to an accessible entrance. This lot requires 3 van accessible spaces and 15 standard accessible spaces. |
P3 |
30 months |
6.2 |
Accessible Route: From Parking To Entrance |
||
6.2.a |
On the routes from both sides of the parking lot to the entrance, the slope of most of the curb cuts is greater than 8.33%, and some of the flared sides slope greater than 10%. |
AR5 |
30 months |
6.2.b |
On the route from the left side of the parking lot to the entrance, the slope between the planters is 5.2% with no ramp features; on the route from the right side of the parking lot to the entrance, the slope between the planters is 8% and the slope on the island is 7.8% with no ramp features; and on the routes from both sides, there is broken asphalt creating level changes exceeding ½ inch. |
AR1 |
30 months |
6.2.c |
The route from the right side of the parking to the entrance is inaccessible because the underside of the stairs provides less than 80 inches of head room. |
AR7 |
24 months |
6.3 |
Main Entrance - East - Passenger Loading Zone. The slope of the primary curb cut is 13.6%, and the slope of the flared sides is 22% and 25%. |
AR5 |
30 months |
6.4 |
Exterior Entrances. The building does not have directional signage posted at inaccessible entrances and does not have the International Symbol of Accessibility posted at accessible entrances. |
D16 |
12 months |
6.5 |
Public Elevators |
||
6.5.a |
The elevator is inaccessible because the call buttons are centered at 49 inches above the finished floor and are recessed. |
E3 |
30 months |
6.5.b |
The elevator is inaccessible because hall lanterns are not provided. |
E11 |
30 months |
6.5.c |
The elevator is inaccessible because it lacks signage at hoistway entrances. |
E12 |
30 months |
6.5.d |
The elevator is inaccessible because it does not emit an audible signal as the car passes or stops at a floor. |
E5 |
30 months |
6.6 |
Assembly Area: Piedmont Room A & B |
||
6.6.a |
The Piedmont room is inaccessible to people with hearing disabilities because there is no assistive listening system provided. |
AA5 |
30 months |
6.6.b |
There is no accessible route connecting the wheelchair seating areas and the portable stage. |
AA1 |
30 months |
6.7 |
Staff Toilet Rooms By Piedmont Meeting Room. Although these are staff-only toilet rooms, they are used by the public, and there is no signage directing people with disabilities to the accessible public toilet rooms. |
TR16 |
24 months |
6.8 |
Accessible Route: From East Entrance to Orchestra Level. The doors on the route from the east entrance to the orchestra level are inaccessible because they have an opening width of only 29 inches. |
D25 |
30 months |
6.9 |
Women’s Toilet Room With Stalls: Orchestra Level |
||
6.9.a |
The toilet room sign is mounted above the door and has no raised or Braille characters. |
TR18 |
24 months |
6.9.b |
There is no side grab bar provided at the designated accessible toilet. |
ST6 |
24 months |
6.9.c |
The rear grab bar at the designated accessible toilet is inaccessible because it is obstructed by the toilet flush valve. |
ST5 |
24 months |
6.9.d |
Although there are 14 stalls, there is no ambulatory stall provided. |
ST1 |
30 months |
6.10 |
Men’s Toilet Room With Stalls: Orchestra Level |
||
6.10.a |
The toilet room sign is mounted above the door and has no raised or Braille characters. |
TR18 |
24 months |
6.10.b |
The urinals are inaccessible because they are mounted with their rims 20½ inches above the finished floor. |
TR20 |
30 months |
6.10.c |
The rear grab bar at the designated accessible toilet is inaccessible because it is obstructed by the toilet flush valve. |
ST5 |
24 months |
6.10.d |
Although there are 6 stalls, there is no ambulatory stall provided. |
ST1 |
30 months |
6.11 |
Drinking Fountains: Orchestra Level |
||
6.11.a |
The drinking fountain is inaccessible because the control requires 10 pounds of force to operate. |
DF2 |
12 months |
6.11.b |
The drinking fountain protrudes into the walkway and is not detectable to blind persons using a cane. |
AR8 |
12 months |
6.12 |
Accessible Route To Orchestra Level Seats. The route leading to the Orchestral Level seats is inaccessible because the slope of one leg is 10.1%, the slope of the landing between the legs is 3.5%, and handrails are not provided. |
R3 |
30 months |
6.13 |
Auditorium |
||
6.13.a |
The seating is inaccessible because the wheelchair locations do not have fixed companion seats. |
AA6 |
30 months |
6.13.b |
There is no accessible route connecting the wheelchair seating areas and the stage. |
AA1 |
30 months |
6.14 |
Plaza Box Office Ticket Window. The counter at the ticket window is 42 inches above the finished floor and a clipboard is unable to fit through the opening. |
C6 |
24 months |
6.15 |
Drinking Fountain: Plaza Level |
||
6.15.a |
The drinking fountain is inaccessible because the control requires 12 pounds of force to operate. |
DF2 |
12 months |
6.15.b |
The drinking fountain protrudes into the walkway and is not detectable to blind persons using a cane. |
AR8 |
12 months |
6.16 |
Women’s Toilet Room With Stalls: Plaza Level |
||
6.16.a |
The toilet room sign is mounted above the door and has no raised or Braille characters. |
TR18 |
24 months |
6.16.b |
The seat cover dispenser is mounted 56½ inches above the finished floor. |
TR5 |
12 months |
6.16.c |
Left Standard Toilet Stall |
||
6.16.c.1
|
The toilet is inaccessible because the centerline is 24 inches from the side partition. |
ST17 |
30 months |
6.16.c.2
|
The toilet is inaccessible because the side grab bar is obstructed by the toilet seat cover dispenser. |
ST9 |
12 months |
6.16.c.3
|
The toilet is inaccessible because the rear grab bar is mounted 13 inches from the side wall. |
ST4 |
12 months |
6.16.d |
Right Standard Toilet Stall |
||
6.16.d.1
|
The toilet is inaccessible because the stall is 57½ inches wide. |
ST16 |
30 months |
6.16.d.2
|
The toilet is inaccessible because the side grab bar is obstructed by the toilet seat cover dispenser. |
ST9 |
12 months |
6.17 |
Accessible Route: Plaza Level |
||
6.17.a |
The route from the front entrance is inaccessible because there are only 55 inches of head room provided under the stairs. |
AR7 |
24 months |
6.17.b |
The defibrillator protrudes into the walkway and is not detectable to blind persons using a cane. |
AR8 |
12 months |
6.18 |
Men’s Toilet Room With Stalls: Loge Level |
||
6.18.a |
The toilet room sign is mounted above the door and has no raised or Braille characters. |
TR18 |
24 months |
6.18.b |
The urinals are inaccessible because their rims are 20 inches high. |
TR20 |
30 months |
6.18.c |
Although there are 6 stalls, there is no ambulatory stall provided. |
ST1 |
30 months |
6.18.d |
The designated accessible toilet is inaccessible because the stall is 56½ inches deep with a floor-mounted toilet. |
ST16 |
30 months |
6.18.e |
The designated accessible toilet is inaccessible because its centerline is 16 inches from the side wall. |
ST17 |
30 months |
6.18.f |
There is no accessible coat hook provided. |
TR1 |
12 months |
6.18.g |
The designated accessible toilet is inaccessible because the rear grab bar is obstructed by the flush valve. |
ST5 |
30 months |
6.19 |
Women’s Toilet Room With Stalls: Loge Level |
||
6.19.a |
The toilet room sign is mounted above the door and has no raised or Braille characters. |
TR18 |
24 months |
6.19.b |
The designated accessible toilet is inaccessible because its centerline is 16 inches from the side wall. |
ST17 |
30 months |
6.19.c |
Although there are 13 stalls, there is no ambulatory stall provided. |
ST1 |
30 months |
6.19.d |
The designated accessible toilet is inaccessible because the flush control is on the closed side. |
ST2 |
30 months |
6.19.e |
The designated accessible toilet is inaccessible because the rear grab bar is obstructed by the flush valve. |
ST5 |
30 months |
6.20 |
Drinking Fountain: Loge Level |
||
6.20.a |
The drinking fountain is inaccessible because the control requires 7 pounds of force to operate. |
DF2 |
12 months |
6.20.b |
The drinking fountain protrudes into the walkway and is not detectable to blind persons using a cane. |
AR8 |
12 months |
6.21 |
Auditorium: Loge Level |
||
6.21.a |
Each leaf of the double entry doors is inaccessible because it has an opening width of 29½ inches and requires 12 pounds of force to open. |
D5 |
30 months |
6.21.b |
The seating is inaccessible because the slope of the wheelchair locations is 4.4%, the cross-slope is 7.5%, and the wheelchair seating areas lack fixed companion seating. |
AA6 |
30 months |
6.22 |
Auditorium: Balcony Level |
||
6.22.a |
A pipe protrudes into the walkway on the route to the balcony seating that is not detectable to blind persons using a cane. |
AR8 |
30 months |
6.22.b |
Each leaf of the double doors to the Balcony Level seating is inaccessible because it has an opening width of only 30 inches and requires 11 pounds of force to open. |
D5 |
30 months |
6.23 |
Accessible Dressing Room No. 8 |
||
6.23.a |
Although an audible alarm is provided in this facility, there is no visual alarm appliance in the toilet room. |
TR21 |
30 months |
6.23.b |
The shower stall is inaccessible because the clear floor space outside the stall is inadequate, the transfer seat does not extend the full depth of the stall, and a grab bar is not provided on the back wall. |
B8 |
30 months |
6.24 |
Drinking Fountain: Back Stage Area. The drinking fountain protrudes into the walkway and is not detectable to blind persons using a cane. |
AR8 |
12 months |
6.25 |
Elevator: Backstage Freight |
||
6.25.a |
The elevator is inaccessible because the hall call buttons are centered 51 inches high and they have a diameter less than ¾ inches. |
E3 |
30 months |
6.25.b |
The elevator is inaccessible because it lacks hall lanterns. |
E11 |
30 months |
6.25.c |
The elevator is inaccessible because it lacks hoistway signage. |
E12 |
30 months |
6.25.d |
The elevator is inaccessible because it lacks a door protective and reopening device. |
E6 |
30 months |
6.25.e |
The elevator is inaccessible because the car control buttons are less than ¾ inches in dimension and lack Braille and raised characters, the highest button is 61½ inches above the car floor, car position indicators are not provided, and the main entry floor call button is not designated by a raised star. |
E4 |
30 months |
6.25.f |
The elevator is inaccessible because, although emergency communications are provided, the door to the emergency communications requires tight pinching to open. |
E8 |
30 months |
6.26 |
Accessible Route: Main Lobby Exhibition Hall. The route through the main lobby is inaccessible because the underside of the stairs provides less than 80 inches of head room. |
AR7 |
30 months |
6.27 |
Exhibition Hall Main Lobby Box Office (Temporary With Exhibit). The lobby box office counter is inaccessible because it is 46 inches high. |
C6 |
12 months |
6.28 |
Men’s Toilet Room with Stalls: Exhibition Hall |
||
6.28.a |
The toilet room sign is less than 60 inches high and has no raised or Braille characters. |
TR18 |
24 months |
6.28.b |
Although an audible alarm is provided in this facility, there is no visual alarm appliance in the toilet room. |
TR21 |
30 months |
6.28.c |
The paper towel dispenser is inaccessible because the controls are mounted 59 inches high. |
TR5 |
12 months |
6.28.d |
The urinals are inaccessible because their rims are 20 inches high. |
TR20 |
30 months |
6.28.e |
There is no accessible toilet stall provided. |
ST15 |
30 months |
6.28.f |
The ambulatory stall has partitions 37 inches apart, and the toilet paper dispenser is mounted above one side grab bar. |
ST1 |
30 months |
6.29 |
Women’s Toilet Room with Stalls: Exhibition Hall |
||
6.29.a |
The toilet room sign is less than 60 inches high and has no raised or Braille characters. |
TR18 |
24 months |
6.29.b |
Although an audible alarm is provided in this facility, there is no visual alarm appliance in the toilet room. |
TR21 |
30 months |
6.29.c |
No accessible mirror has been provided. |
TR14 |
12 months |
6.29.d |
The paper towel dispenser is inaccessible because the controls are mounted 60 inches high. |
TR5 |
12 months |
6.29.e |
The lavatory is inaccessible because the rim or counter is 27 inches high to the bottom. |
TR11 |
24 months |
6.29.f |
There is no accessible toilet stall provided. |
ST15 |
30 months |
6.29.g |
The ambulatory stall has partitions 38 inches apart, and the toilet paper dispenser is mounted above one side grab bar. |
ST1 |
30 months |
6.30 |
Drinking Fountain: Exhibition Hall by Toilet Rooms |
||
6.30.a |
The drinking fountain is inaccessible because the control requires 12 pounds of force to operate. |
DF2 |
12 months |
6.30.b |
Although a designated accessible drinking fountain is provided, there is no drinking fountain provided for people who have difficulty bending or stooping. |
DF3 |
30 months |
6.31 |
Public Elevator: Exhibition Hall |
||
6.31.a |
The elevator is inaccessible because the hall call buttons are recessed. |
E3 |
30 months |
6.31.b |
The elevator is inaccessible because the doors fail to reopen without contact when obstructed. |
E6 |
30 months |
6.31.c |
The elevator is inaccessible because the car control buttons are recessed, raised characters are not provided, and the call button for the main entry floor is not designated by a raised star. |
E4 |
30 months |
6.32 |
Accessible Route: Exhibition Hall 1st Floor. The route is inaccessible because adequate head room is not provided in the exit area under the stairs. |
AR7 |
30 months |
6.33 |
Exhibition Hall 2nd Floor Meeting Room |
||
6.33.a |
The door is inaccessible because it requires 9 pounds of force to open and the hardware is mounted 53 inches above the floor and requires twisting to operate. |
D1 D18 |
24 months |
6.33.b |
The meeting room is inaccessible to people with hearing disabilities because no assistive listening system is provided. |
AA5 |
30 months |
6.34 |
Drinking Fountain: Exhibition Hall 2nd Floor Meeting Room. Although a designated accessible drinking fountain is provided, there is no drinking fountain provided for people who have difficulty bending or stooping. |
DF3 |
30 months |
6.35 |
Women’s Toilet Room Single-User: Exhibition Hall 2nd Floor Meeting Room |
||
6.35.a |
The toilet room sign is mounted on the door and does not have raised or Braille characters. |
TR18 |
24 months |
6.35.b |
Although an audible alarm is provided in this facility, there is no visual alarm appliance in the toilet room. |
TR21 |
30 months |
6.35.c |
The toilet is inaccessible because its centerline is 19½ inches from the side wall. |
SU15 |
30 months |
6.36 |
Men’s Toilet Room Single-User: Exhibition Hall 2nd Floor Meeting Room |
||
6.36.a |
The toilet room sign is mounted on the door and does not have raised or Braille characters. |
TR18 |
24 months |
6.36.b |
Although an audible alarm is provided in this facility, there is no visual alarm appliance in the toilet room. |
TR21 |
30 months |
6.36.c |
The paper towel dispenser is inaccessible because the controls are mounted at 56 inches high. |
TR5 |
12 months |
6.36.d |
The toilet is inaccessible because there is insufficient clear floor space due to the placement of the lavatory. |
SU16 |
30 months |
6.36.e |
The toilet is inaccessible because its centerline is 19 inches from the side wall. |
SU15 |
30 months |
6.36.f |
The toilet is inaccessible because the flush control is on the closed side. |
SU1 |
30 months |
6.36.g |
The rear grab bar at the toilet is inaccessible because its overall length is 24 inches. |
SU3 |
24 months |
7 |
CANDLER PARK GOLF COURSE, located at 585 Candler Park Dr, NE |
||
7.1 |
Parking Lot. Although the parking lot has a total of 5 parking spaces, there are no accessible parking spaces provided. This lot requires 1 van accessible space. |
P3 |
24 months |
7.2 |
Club House Main Entrance |
||
7.2.a |
The Club House is inaccessible because there is a 4 inch step on the route leading to the main entrance. |
AR1 |
30 months |
7.2.b |
The main entrance door is inaccessible because it has an opening width of only 28 inches per leaf. |
D25 |
30 months |
7.2.c |
The main entrance door is inaccessible because it has a 1½ inch high threshold. |
D23 |
24 months |
7.3 |
Counter. The counter in the clubhouse is inaccessible because it is 39½ inches high. |
C6 |
24 months |
7.4 |
Men’s & Women’s Toilet Rooms with Stalls. The men’s and women’s toilet rooms contain a number of inaccessible elements and are not accessible to people with disabilities. |
ST14 |
30 months |
7.5 |
Drinking Fountain. The drinking fountain is inaccessible because the spout is 43 inches high. |
DF6 |
12 months |
8 |
OAKLAND RECREATION CENTER, located at 1305 Oakland Rd, SW |
||
8.1 |
Parking Lot. The parking reserved for persons with disabilities is inaccessible because it lacks appropriate vertical signage. |
P6 |
24 months |
8.2 |
Women’s Toilet Room With Stalls: 1st Floor |
||
8.2.a |
The door is inaccessible because it requires 7 pounds of force to open. |
D2 |
12 months |
8.2.b |
No accessible mirror has been provided. |
TR14 |
12 months |
8.2.c |
The air dryer protrudes into the walkway and is not detectable to blind persons using a cane. |
AR8 |
12 months |
8.2.d |
The lavatory is inaccessible because it has no knee or toe clearance. |
TR11 |
24 months |
8.2.e |
There is no standard accessible stall provided. |
ST15 |
30 months |
8.3 |
Men’s Toilet Room With Stalls: 1st Floor |
||
8.3.a |
The door is inaccessible because it requires 8 pounds of force to open. |
D2 |
12 months |
8.3.b |
No accessible mirror has been provided. |
TR14 |
12 months |
8.3.c |
The urinal is inaccessible because its rim is 23 inches high. |
TR20 |
24 months |
8.3.d |
The air dryer protrudes into the walkway and is not detectable to blind persons using a cane. |
AR8 |
12 months |
8.3.e |
The lavatory is inaccessible because it has no knee or toe clearance. |
TR11 |
24 months |
8.3.f |
There is no standard accessible stall provided. |
ST15 |
30 months |
8.4 |
Drinking Fountain. The drinking fountain protrudes into the walkway and is not detectable to blind persons using a cane. |
AR8 |
12 months |
9 |
ADAMS PARK & RECREATION CENTER, located on Delowe Dr, SW |
||
9.1 |
Parking Lot. The parking lot, with a total of 6 parking spaces, has no van accessible parking space, and the existing designated accessible parking space has no access aisle and no vertical signage. This lot requires 1 van accessible space. |
P3 |
24 months |
9.2 |
Accessible Route: From Parking Lot To Main Entrance. The route is inaccessible because the curb ramp is steeper than 8.33%, and although it does not have handrails or guardrails to protect against cross traffic, it also does not have flared sides. |
AR5 |
30 months |
9.3 |
Exterior Entrances. The building does not have directional signage posted at inaccessible entrances and does not have the International Symbol of Accessibility posted at accessible entrances. |
D16 |
12 months |
9.4 |
Interior Doors. The interior doors are inaccessible because knob hardware is used. |
D1 |
24 months |
9.5 |
Access Among Levels. There is no access to upper and lower levels of the facility for people with mobility impairments. |
AR9 |
30 months |
9.6 |
Drinking Fountain |
||
9.6.a |
Although an accessible drinking fountain is provided, there is no drinking fountain provided for people who have difficulty bending or stooping. |
DF3 |
30 months |
9.6.b |
The drinking fountain protrudes into the walkway and is not detectable to blind persons using a cane. |
AR8 |
12 months |
9.7 |
Women’s Toilet Room With Stalls: 1st Level |
||
9.7.a |
The toilet room sign is mounted on the door and has no raised or Braille characters. |
TR18 |
24 months |
9.7.b |
The door is inaccessible because it requires 7 pounds of force to open. |
D2 |
12 months |
9.7.c |
The lavatory is inaccessible because the hot water pipes are not insulated or otherwise configured to protect against contact. |
TR12 |
24 months |
9.7.d |
The designated accessible toilet is inaccessible because its centerline is 16½ inches from the side wall. |
ST17 |
30 months |
9.7.e |
The designated accessible toilet is inaccessible because the side grab bar is obstructed by the toilet paper dispenser. |
ST8 |
12 months |
9.7.f |
The grab bars at the designated accessible toilet are inaccessible because they are mounted 30½ inches above the finished floor. |
ST12 |
12 months |
9.7.g |
The grab bars at the designated accessible toilet are inaccessible because the space between the grab bars and the wall is 2¾ inches. |
ST13 |
12 months |
9.7.h |
The rear grab bar at the designated accessible toilet is inaccessible because it is 24 inches long. |
ST4 |
24 months |
9.8 |
Men’s Toilet Room With Stalls: 1st Level |
||
9.8.a |
The toilet room sign is mounted on the door and has no raised or Braille characters. |
TR18 |
24 months |
9.8.b |
The door is inaccessible because it requires 8 pounds of force to open. |
D2 |
12 months |
9.8.c |
No accessible mirror has been provided. |
TR14 |
12 months |
9.8.d |
The lavatory is inaccessible because the hot water pipes are not insulated or otherwise configured to protect against contact. |
TR12 |
24 months |
9.8.e |
The urinal is inaccessible because the rim is more than 17 inches high. |
TR20 |
24 months |
9.8.f |
The designated accessible toilet is inaccessible because its centerline is 20½ inches from the side wall. |
ST17 |
30 months |
9.8.g |
The designated accessible toilet is inaccessible because the side grab bar is obstructed by the toilet paper dispenser. |
ST8 |
12 months |
9.8.h |
The grab bars at the designated accessible toilet are inaccessible because the space between the grab bars and the wall is 2¾ inches. |
ST13 |
24 months |
9.8.i |
The rear grab bar at the toilet is inaccessible because its overall length is 24 inches and it is mounted with the closer end 12 inches from the side wall. |
ST4 |
24 months |
9.9 |
Spectator Area 1st Floor. The door is inaccessible because it requires 12 pounds of force to open. |
D2 |
12 months |
9.10 |
Stairs. The stairs to the basketball court are inaccessible because there are less than 80 inches of head room provided. |
AR7 |
30 months |
9.11 |
Accessible Route: To Tennis Courts. There is no accessible route to the tennis courts. |
AR1 |
30 months |
10 |
MCGHEE TENNIS CENTER, located at 820 Beecher Ct, SW |
||
10.1 |
Parking Lot. The parking lot, with a total of 36 parking spaces, has no van accessible parking space, and has no vertical signage designating accessible parking spaces. This lot requires 1 van accessible space and 1 standard accessible space. |
P3 |
24 months |
10.2 |
Accessible Route: From Parking Lot to Main Entrance. The route is inaccessible because the slope of the curb cut is 12.2%, and the flared sides are too steep. |
AR5 |
30 months |
10.3 |
Main Entrance. The building does not have directional signage posted at inaccessible entrances and does not have the International Symbol of Accessibility posted at accessible entrances. |
D16 |
12 months |
10.4 |
Interior Doors. The doors are inaccessible because knob hardware is used. |
D1 |
24 months |
10.5 |
Women’s Locker Room: Near Lobby |
||
10.5.a |
The sign is mounted on the door and lacks raised and Braille characters. |
TR18 |
24 months |
10.5.b |
The door is inaccessible because it requires 11 pounds of force to open. |
D2 |
12 months |
10.5.c |
The lavatory is inaccessible because there is no knee space provided. |
TR11 |
24 months |
10.5.d |
The designated accessible toilet stall is incorrectly configured as an ambulatory stall, and there is no standard accessible stall provided. |
ST15 |
30 months |
10.5.e |
The designated accessible shower has a number of inaccessible elements and is not accessible to people with disabilities. |
B8 |
30 months |
10.5.f |
The air dryer is inaccessible because the controls are mounted 69 inches above the finished floor. |
TR5 |
12 months |
10.5.g |
The bench is inaccessible because it is 9½ inches wide and is not fixed to a wall. |
LR1 |
30 months |
10.5.h |
The lockers are inaccessible because they require tight grasping to open. |
LR3 |
30 months |
10.6 |
Men’s Locker Room: Near Lobby |
||
10.6.a |
The sign is mounted on the door and lacks raised and Braille characters. |
TR18 |
24 months |
10.6.b |
The door is inaccessible because it requires 11 pounds of force to open. |
D2 |
12 months |
10.6.c |
The lavatory is inaccessible because there is no knee space provided. |
TR11 |
24 months |
10.6.d |
The urinals are inaccessible because their rims are 25 inches high. |
TR20 |
24 months |
10.6.e |
The designated accessible toilet stall is incorrectly configured as an ambulatory stall, and there is no standard accessible stall provided. |
ST15 |
30 months |
10.6.f |
The paper towel dispenser is inaccessible because the controls are mounted more than 54 inches high. |
TR5 |
12 months |
10.6.g |
There is no accessible shower provided. |
B8 |
30 months |
10.6.h |
The air dryer is inaccessible because the controls are mounted 77 inches above the finished floor. |
TR5 |
12 months |
10.6.i |
The bench is inaccessible because it is 9½ inches wide and is not fixed to a wall. |
LR1 |
30 months |
10.6.j |
The lockers are inaccessible because they require tight grasping to open. |
LR3 |
30 months |
10.7 |
Welcome Desk: Lobby Area. The welcome desk is inaccessible because the counter is 44 inches high. |
C6 |
12 months |
10.8 |
Accessible Route: From Side Exit to Tennis Court #7. The ramp leading to the tennis court has a 1 inch change in level at the top, has a slope of 10.3% near the bottom, and lacks handrails. |
AR1 |
30 months |
11 |
GRANT PARK RECREATION CENTER, located at 537 Park Ave, SE |
||
11.1 |
Parking Lot |
||
11.1.a |
The parking lot, with a total of 30 parking spaces, has only one designated accessible parking space, which has no access aisle and no vertical signage. This lot requires 1 van accessible space and 1 standard accessible space. |
P3 |
24 months |
11.1.b |
The curb ramp leading to the basketball and tennis courts is inaccessible because it slopes 15%, the cross-slope is 3.2%, there is a ½ change in level at the bottom of the curb ramp, and the flared sides are too steep. |
AR5 |
30 months |
11.1.c |
The curb ramp leading to the main entrance under the stairs is inaccessible because it slopes 13.9%, the flared sides are too steep, and there is a ¾ inch change in level at the top of the curb ramp. |
AR5 |
30 months |
11.2 |
Exterior Accessible Route. The route from the parking lot to the basketball and tennis courts is inaccessible because the running slope is 6% with no ramp features, the cross-slope is 5.5%, and there is a 2½ inch change in level at the entrance of the tennis court. |
AR1 |
30 months |
11.3 |
Main Entrance. The front entrance is inaccessible because the threshold is 4 inches high. |
D23 |
24 months |
11.4 |
Interior Accessible Route. There is no access to the 2nd floor of the facility for people with mobility impairments. |
AR9 |
30 months |
11.5 |
Dance Room: 1st Floor. The dance room is inaccessible because the door has knob hardware. |
D1 |
24 months |
11.6 |
Side Entrance by Game Room |
||
11.6.a |
The route to the side entrance by the game room is inaccessible because there is a 3¼ change in level leading to the entrance. |
AR1 |
24 months |
11.6.b |
The door is inaccessible because there is a 1 inch high threshold. |
D23 |
24 months |
11.7 |
Classroom: 1st Floor. The classroom is inaccessible because the door has knob hardware. |
D1 |
24 months |
11.8 |
Women’s Toilet Room With Stalls: 1st Floor |
||
11.8.a |
The toilet room sign is not mounted on the latch side of the door and lacks raised and Braille characters. |
TR18 |
24 months |
11.8.b |
The door to the toilet room is inaccessible because it has an opening width of only 29 inches. |
D25 |
30 months |
11.8.c |
The door is inaccessible because it requires 8 pounds of force to open. |
D2 |
12 months |
11.8.d |
The pull side of the door to the toilet room, which is accessed through a front approach, is inaccessible because the clearance on the latch side of the door is only 6 inches wide. |
D6 |
30 months |
11.8.e |
No accessible mirror has been provided. |
TR14 |
12 months |
11.8.f |
The lavatory is inaccessible because the rim or counter is 27 inches high to the bottom. |
TR11 |
24 months |
11.8.g |
The lavatory is inaccessible because the hot water pipes are not insulated or otherwise configured to protect against contact. |
TR12 |
24 months |
11.8.h |
The lavatory is inaccessible because the faucet requires tight grasping or twisting of the wrist to operate. |
TR10 |
24 months |
11.8.i |
There is no accessible toilet stall provided. |
ST15 |
30 months |
11.9 |
Men’s Toilet Room With Stalls: 1st Floor |
||
11.9.a |
The toilet room sign is not mounted on the latch side of the door and lacks raised and Braille characters. |
TR18 |
24 months |
11.9.b |
The door to the toilet room is inaccessible because it has an opening width of only 29 inches. |
D25 |
30 months |
11.9.c |
The door is inaccessible because it requires 8 pounds of force to open. |
D2 |
12 months |
11.9.d |
The pull side of the door to the women’s toilet room, which is accessed through a front approach, is inaccessible because the clearance on the latch side of the door is only 4½ inches wide. |
D6 |
30 months |
11.9.e |
No accessible mirror has been provided. |
TR14 |
12 months |
11.9.f |
The lavatory is inaccessible because the rim or counter is 27 inches high to the bottom. |
TR11 |
24 months |
11.9.g |
The lavatory is inaccessible because the hot water pipes are not insulated or otherwise configured to protect against contact. |
TR12 |
24 months |
11.9.h |
The lavatory is inaccessible because the faucet requires tight grasping or twisting of the wrist to operate. |
TR10 |
24 months |
11.9.i |
The urinals are inaccessible because the rims are 23 inches high. |
TR20 |
24 months |
11.9.j |
The designated accessible stall is incorrectly configured as an ambulatory stall, and there is no standard accessible stall provided. |
ST15 |
30 months |
11.10 |
Drinking Fountain: 1st Floor. The drinking fountain is inaccessible because its spout is 45 inches high. |
DF6 |
24 months |
11.11 |
Stairs: Leading to Gymnasium (Two Sets of Stairs) |
||
11.11.a
|
The stairs have a number of inaccessible features and are not accessible to people with disabilities. |
AR10 |
30 months |
11.11.b
|
The route by the stairs is inaccessible because a cane detectable barrier is not provided under the stairs. |
AR7 |
24 months |
11.12 |
Gymnasium. The gymnasium, containing approximately 480 seats, is inaccessible because it has bleacher style fixed seating and wheelchair seating areas are not provided. A total of 6 wheelchair seating areas is required. |
AA6 |
30 months |
11.13 |
Women’s Gym Locker Room: Ground Level |
||
11.13.a
|
The sign is not mounted on the latch side of the door and does not have raised or Braille characters. |
TR20 |
24 months |
11.13.b |
The locker room is inaccessible because the opening width of both entrance doors is 29 inches, and the outer door requires 6 pounds of force to open and has a 2 inch high threshold. |
D18 |
30 months |
11.13.c
|
No accessible mirror has been provided. |
TR14 |
12 months |
11.13.d
|
The paper towel dispenser is inaccessible because the controls are mounted 56 inches high. |
TR5 |
12 months |
11.13.e |
The lavatory is inaccessible because the bottom of the apron is 27½ inches high, the hot water pipes are not insulated or otherwise configured to protect against contact, and the faucet requires tight grasping or twisting of the wrist to operate. |
TR9 |
30 months |
11.13.f
|
There is no accessible toilet stall provided. |
ST15 |
30 months |
11.13.g
|
There is no accessible shower provided. |
B8 |
30 months |
11.13.h
|
No accessible towel hook has been provided. |
TR1 |
12 months |
11.13.i
|
The towel hooks protrude into the walkway and would not be detectable to a blind person using a cane |
AR8 |
12 months |
11.13.j
|
There is no accessible locker provided. |
LR3 |
30 months |
11.14 |
Men’s Gym Locker Room: Ground Level |
||
11.14.a
|
The sign is not mounted on the latch side of the door and does not have raised or Braille characters. |
TR20 |
24 months |
11.14.b
|
The locker room is inaccessible because the opening width of both entrance doors is 29½ inches. |
D25 |
30 months |
11.14.c
|
The outer door to the locker is inaccessible because there is a 2 inch high threshold. |
D23 |
24 months |
11.14.d
|
The soap dispenser is inaccessible because the controls are mounted 56 inches high. |
TR5 |
12 months |
11.14.e |
The lavatory is inaccessible because the bottom of the apron is 27½ inches high, the hot water pipes are not insulated or otherwise configured to protect against contact, and the faucet requires tight grasping or twisting of the wrist to operate. |
TR9 |
30 months |
11.14.f
|
The urinals are inaccessible because they are mounted with the rims 26 inches high. |
TR20 |
24 months |
11.14.g
|
There is no accessible toilet stall provided. |
ST15 |
30 months |
11.14.h
|
There is no accessible shower provided. |
B8 |
30 months |
11.14.i
|
There is no accessible locker provided. |
LR3 |
30 months |
11.15 |
Drinking Fountain: Gymnasium Area. The drinking fountain is inaccessible because its spout is 43 inches high. |
DF6 |
24 months |
12 |
GRANT PARK SWIMMING POOL, located at 25 Park Ave, SE |
||
12.1 |
Parking Lot. The parking lot, with a total of approximately 20 parking spaces, has no parking spaces provided for people with disabilities. This lot requires 1 van accessible parking space. |
P3 |
24 months |
12.2 |
Accessible Route: From Parking Lot to Rear Entrance. The route is inaccessible because there is a ½ inch unbeveled change in level at the gate. |
AR1 |
24 months |
12.3 |
Men’s Locker Room |
||
12.3.a |
The locker room sign is mounted more than 60 inches high and has no raised or Braille characters. |
TR18 |
24 months |
12.3.b |
The door to the locker room is inaccessible because there is a 3¾ inch high threshold. |
D23 |
24 months |
12.3.c |
No accessible mirror has been provided. |
TR14 |
12 months |
12.3.d |
The lavatory is inaccessible because the faucet requires tight grasping or twisting of the wrist to operate. |
TR10 |
24 months |
12.3.e |
The designated accessible toilet stall is incorrectly configured as an ambulatory stall, and there is no standard accessible stall provided. |
ST15 |
30 months |
12.3.f |
There is no accessible shower provided. |
B8 |
30 months |
12.3.g |
The benches are less than 24 inches wide and are not attached to the wall. |
LR1 |
30 months |
12.4 |
Women’s Locker Room |
||
12.4.a |
The locker room sign is not mounted in the proper position and has no raised or Braille characters. |
TR18 |
24 months |
12.4.b |
The door to the locker room is inaccessible because the threshold is more than ½ inch high. |
D23 |
24 months |
12.4.c |
No accessible mirror has been provided. |
TR14 |
12 months |
12.4.d |
The sanitary napkin dispenser is inaccessible because the controls are mounted 57 inches high. |
TR5 |
12 months |
12.4.e |
The lavatory is inaccessible because the bottom edge of the apron is 24½ inches high, and the faucet requires twisting to operate. |
TR9 |
24 months |
12.4.f |
The designated accessible toilet stall is incorrectly configured as an ambulatory stall, and there is no standard accessible stall provided. |
ST15 |
30 months |
12.4.g |
There is no accessible shower provided. |
B8 |
30 months |
12.4.h |
The benches are less than 24 inches wide and are not attached to the wall. |
LR1 |
30 months |
12.5 |
Picnic Tables. The picnic tables at the pool area are inaccessible because none provide adequate knee space. |
PD6 |
30 months |
12.6 |
Accessible Route: To Pools |
||
12.6.a |
The route from the lockers and picnic area to the pools is inaccessible because it slopes 6.6% and has no ramp features. |
R3 |
30 months |
12.6.b |
The stairs to the diving pool are inaccessible because they lack handrails |
AR10 |
24 months |
13 |
BROWNWOOD RECREATION CENTER, located at 602 Brownwood Ave, SE |
||
13.1 |
Parking Lot. The parking lot, with a total of 15 parking spaces, has no van accessible parking space provided. This lot requires 1 van accessible parking space. |
P3 |
24 months |
13.2 |
Exterior Accessible Route. There is no accessible route provided from the parking lot to the tennis, basketball, or volleyball courts. |
AR1 |
30 months |
13.3 |
Main Entrance. The door is inaccessible because there is a 1½ inch high threshold. |
D23 |
24 months |
13.4 |
Interior Room Signage. Although room signage is provided, many of the signs are not mounted on the latch sides of the doors. |
D26 |
24 months |
13.5 |
Alarms. Although the facility contains an emergency alarm system, the alarm system is inaccessible because visual alarms are not provided in all required locations. |
AL1 |
30 months |
13.6 |
Main Recreation Room |
||
13.6.a |
The kitchen counter protrudes into the walkway and is not detectable to blind persons using a cane. |
AR8 |
24 months |
13.6.b |
The fire extinguisher protrudes into the walkway and is not detectable to blind persons using a cane. |
AR8 |
12 months |
13.6.c |
No accessible coat hook has been provided. |
TR1 |
12 months |
13.6.d |
The pool sticks are inaccessible because they are mounted 55½ inches high. |
TR5 |
12 months |
13.7 |
Picnic Tables in Pavilion. The picnic tables are inaccessible because none provide the required knee space. |
PD6 |
30 months |
13.8 |
Ramp: Behind Recreation Center. The ramp is inaccessible because it slopes more than 8.33%, and the handrails are 41 inches high and lack extensions at the bottom. |
R5 |
30 months |
13.9 |
Computer Room. The pull side of the door, which can be accessed from the latch side of the door, is inaccessible because it has only 7 inches of clear width on the latch side. |
D10 |
30 months |
13.10 |
Drinking Fountain: Near Toilet Rooms |
||
13.10.a |
Although an accessible drinking fountain is provided, there is no drinking fountain provided for people who have difficulty bending or stooping. |
DF3 |
30 months |
13.10.b
|
The drinking fountain protrudes into the walkway and is not detectable to blind persons using a cane. |
AR8 |
12 months |
13.11 |
Women’s Toilet Room With Stalls |
||
13.11.a
|
The door is inaccessible because it requires 11 pounds of force to open. |
D2 |
12 months |
13.11.b
|
Although an audible alarm is provided in this facility, there is no visual alarm appliance in the toilet room. |
TR21 |
30 months |
13.11.c |
The paper towel dispenser is inaccessible because the controls are mounted 50 inches high over an obstruction. |
TR4 |
12 months |
13.11.d
|
The air dryer protrudes into the walkway and is not detectable to blind persons using a cane. |
AR8 |
12 months |
13.11.e
|
The soap dispenser is inaccessible because it requires 13 pounds of force to operate. |
TR3 |
12 months |
13.11.f |
The designated accessible stall is incorrectly configured as an ambulatory stall, and there is no standard accessible stall provided. |
ST15 |
30 months |
13.12 |
Men’s Toilet Room With Stalls |
||
13.12.a
|
The door is inaccessible because it requires 10 pounds of force to open. |
D2 |
12 months |
13.12.b
|
Although an audible alarm is provided in this facility, there is no visual alarm appliance in the toilet room. |
TR21 |
30 months |
13.12.c
|
The soap dispenser is inaccessible because the controls are mounted 56 inches high over an obstruction. |
TR4 |
12 months |
13.12.d
|
The urinal is inaccessible because the rim is 24 inches high and the flush control is 49½ inches high. |
TR20 |
30 months |
13.12.e
|
The air dryer protrudes into the walkway and is not detectable to blind persons using a cane. |
AR8 |
12 months |
13.12.f |
The designated accessible stall is incorrectly configured as an ambulatory stall, and there is no standard accessible stall provided. |
ST15 |
30 months |
13.12.g
|
There is no accessible locker provided. |
LR3 |
30 months |
13.13 |
Assembly Area: Weight Training Room. The weight lifting equipment at the entrance door protrudes into the walkway and is not detectable to blind persons using a cane. |
AR8 |
12 months |
14 |
BESSIE BRANHAM RECREATION CENTER, located at 2051 Brownwood Avenue, SE |
||
14.1 |
Parking Lot. The parking lot, with a total of 25 parking spaces, has no van accessible parking space, and the designated accessible parking spaces are not level. This lot requires 1 van accessible parking space. |
P3 |
30 months |
14.2 |
Accessible Route: From Parking Lot To Main Entrance. The route is inaccessible because the flared sides on the curb cut are too steep. |
AR5 |
30 months |
14.3 |
Arts and Crafts Room. The door is inaccessible because it requires 10 pounds of force to open. |
D2 |
12 months |
14.4 |
Community Room. The door is inaccessible because it requires 10 pounds of force to open. |
D2 |
12 months |
14.5 |
Men’s and Women’s Toilet Rooms: Old Section. The toilet rooms have a number of inaccessible features and are not accessible to people with disabilities. |
ST14 |
30 months |
15 |
BITSY GRANT CENTER, located at 2125 Northside Dr., NW |
||
15.1 |
Accessible Route: to Clubhouse Entrance. The route from the parking area to the clubhouse is inaccessible because the curb ramp has flared sides that slope up to 23.1%. |
AR5 |
30 months |
15.2 |
Pro’s Office: Clubhouse. The door to the Pro’s office is inaccessible because it has an opening width of 29 inches. |
D25 |
30 months |
15.3 |
Ramp: to Clubhouse Exterior Viewing Deck. The ramp is inaccessible because it lacks edge protection and handrails. |
R5 |
30 months |
15.4 |
Exterior Entrance and Doors: Clubhouse |
||
15.4.a |
The building does not have directional signage posted at inaccessible entrances and does not have the International Symbol of Accessibility posted at accessible entrances. |
D16 |
12 months |
15.4.b |
The double-leaf clubhouse entrance door is inaccessible because each leaf is 27½ inches wide. |
D24 |
30 months |
15.5 |
Interior Clubhouse Signage. There is no signage directing people with disabilities to the accessible toilet room and shower. |
TR16 |
24 months |
15.6 |
Unisex Single-User Toilet Room and Shower: Clubhouse |
||
15.6.a |
The door is inaccessible because it requires 10 pounds of force to open. |
D2 |
12 months |
15.6.b |
The light switch is inaccessible because it is mounted 57 inches high. |
TR5 |
12 months |
15.6.c |
The toilet is inaccessible because the flush control is on the closed side. |
SU1 |
24 months |
15.6.d |
The rear grab bar at the toilet is inaccessible because it is 30 inches long. |
SU3 |
24 months |
15.6.e |
The shower is inaccessible because the clear floor space outside the shower is 36 inches wide, the spray unit hose is 57 inches long, and there is a 1½ inch high curb at the entrance of the stall. |
B8 |
30 months |
15.7 |
Clubhouse Lower Level. There is no access to the lower level of the facility for people with mobility impairments. |
AR9 |
30 months |
15.8 |
Exterior Drinking Fountain: By Hard Tennis Courts. The drinking fountain protrudes into the walkway and is not detectable to blind persons using a cane. |
AR8 |
24 months |
15.9 |
Exterior Accessible Routes: To Tennis Courts |
||
15.9.a |
The route to the clay courts is inaccessible because there is a 1 inch change in level on the sidewalk. |
AR1 |
24 months |
15.9.b |
The route to the clay courts is inaccessible because the built-up curb ramp at the courts slopes 13.5%. |
AR5 |
30 months |
15.9.c |
The route to the hard courts is inaccessible because the built-up curb ramps slope 17.8% at the first set of courts and 20.5% at the second set of courts. |
AR5 |
30 months |
15.10 |
Parking: By Hard Tennis Courts. The parking lot, with a total of 104 parking spaces, has two spaces designated as reserved for people with disabilities. This lot requires 1 van accessible space and 4 standard accessible spaces. |
P3 |
30 months |
16 |
COLLIER PARK AND RECREATION CENTER, located at 3691 Collier Drive, NW |
||
16.1 |
Parking Lot. The parking lot, with a total of 38 parking spaces, has two designated accessible spaces with no access aisles, and no vertical signage, and one of the designated accessible spaces is not level. This lot requires 1 van accessible space and 1 standard accessible space. |
P3 |
30 months |
16.2 |
Accessible Route: From Parking Lot to Entrance. The route is inaccessible because the slope near the entrance is 10.5%. |
AR1 |
30 months |
16.3 |
Men’s Toilet Room With Stalls |
||
16.3.a |
The door is inaccessible because it requires 12 pounds of force to open. |
D2 |
12 months |
16.3.b |
The lavatory is inaccessible because the hot water pipes are not insulated or otherwise configured to protect against contact. |
TR12 |
24 months |
16.3.c |
The lavatory is inaccessible because it has twist-type faucets. |
TR10 |
24 months |
16.3.d |
The urinal is inaccessible because the rim is 23 inches high and the flush is 51 inches high. |
TR20 |
30 months |
16.3.e |
The designated accessible stall is incorrectly configured as an ambulatory stall, and there is no standard accessible stall provided. |
ST15 |
30 months |
16.4 |
Women’s Toilet Room With Stalls |
||
16.4.a |
The door is inaccessible because it requires 14 pounds of force to open. |
D2 |
12 months |
16.4.b |
The air dryer protrudes into the walkway and is not detectable to blind persons using a cane. |
AR8 |
12 months |
16.4.c |
The designated accessible stall is incorrectly configured as an ambulatory stall, and there is no standard accessible stall provided. |
ST15 |
30 months |
16.5 |
Recreation Room. The door is inaccessible because it requires 10 pounds of force to open. |
D2 |
12 months |
16.6 |
Exterior Accessible Route |
||
16.6.a |
The route from the parking lot to the sidewalk is inaccessible because the slope of the curb ramp is 9.1%, the slope of the flared sides is 24%, and there is a 2 inch change in level at the bottom of the curb ramp. |
AR5 |
30 months |
16.6.b |
The sidewalk to the play area is inaccessible because the slope is between 6.1% and 7.4%, and there are no ramp features. |
R3 |
30 months |
16.6.c |
The play area is inaccessible because the play equipment is blocked by wooden and rubber barriers, and there is no stable, firm, and slip resistant route. |
AR1 |
30 months |
16.6.d |
The Life Trail and the routes to the volleyball court and the ball fields are inaccessible because the sidewalks slope up to 14.5%. |
AR1 |
30 months |
16.7 |
Exterior Drinking Fountains. The drinking fountains are operated by foot pedals and are not accessible to people with disabilities. |
DF2 |
30 months |
17 |
ZABAN RECREATION CENTER, located at 241 Daniel Avenue, SE |
||
17.1 |
Parking Lot. The parking lot, with a total of 65 parking spaces, has no designated accessible parking spaces. This lot requires 1 van accessible space and 2 standard accessible spaces. |
P3 |
30 months |
17.2 |
Exterior Accessible Routes |
||
17.2.a |
The routes throughout the park, including the route from the parking lot to the recreation center, are inaccessible because they are covered in gravel and wood chips. |
AR1 |
30 months |
17.2.b |
The sidewalk to the main entrance is inaccessible because the running slope is 10.9% and the cross-slope is 4.3%. |
AR1 |
30 months |
17.3 |
Recreation Center Main Entrance. The exterior ramp is inaccessible because it does not have accessible handrails. |
R4 |
30 months |
17.4 |
Drinking Fountain: Near Toilet Rooms. Although an accessible drinking fountain is provided, there is no drinking fountain provided for people who have difficulty bending or stooping |
DF3 |
30 months |
17.5 |
Men’s Toilet Room With Stalls |
||
17.5.a |
The door is inaccessible because it requires 12 pounds of force to open. |
D2 |
30 months |
17.5.b |
The toilet room is inaccessible because there is insufficient turning space provided within the room. |
TR19 |
30 months |
17.5.c |
The urinal is inaccessible because the width of the clear floor space is only 28 inches. |
TR20 |
30 months |
17.5.d |
The toilet stall is incorrectly configured as an ambulatory stall, and there is no standard accessible stall provided. |
ST15 |
30 months |
17.6 |
Women’s Toilet Room With Stalls |
30 months |
|
17.6.a |
The door is inaccessible because it requires 12 pounds of force to open. |
D2 |
30 months |
17.6.b |
The toilet room is inaccessible because there is insufficient turning space provided within the room. |
TR19 |
30 months |
17.6.c |
The lavatory is inaccessible because the hot water pipes are not insulated or otherwise configured to protect against contact. |
TR12 |
30 months |
17.6.d |
The toilet stall is incorrectly configured as an ambulatory stall, and there is no standard accessible stall provided. |
ST15 |
30 months |
17.7 |
Interior Ramp: Down to Exercise/Storage Room The ramp is inaccessible because the inside handrail is not continuous and the ramp is covered in stored furniture and other items. |
R3 |
30 months |
18 |
ATLANTA POLICE ZONE 3, located at 880 Cherokee Avenue |
||
18.1 |
Accessible Route: Curb Ramp to Main Exterior Door. The route is inaccessible because the short ramp has a 2 inch step at the bottom and a ¾ inch step at the top. |
AR1 |
30 months |
18.2 |
Main Entrance. The pull side of the main entrance door, which is accessed through a front approach, is inaccessible because it has only 3 inches of maneuvering space on the latch side. |
D6 |
30 months |
18.3 |
Unisex Single-User Toilet Room: Main Lobby |
||
18.3.a |
The door is inaccessible because it requires 20 pounds of force to open. |
D2 |
12 months |
18.3.b |
The toilet room is inaccessible because the door has knob hardware. |
D1 |
24 months |
18.3.c |
The toilet is inaccessible because the centerline is 16 inches from the side wall. |
SU15 |
30 months |
18.4 |
2nd Floor. There is no access to the upper level of the facility for people with mobility impairments. |
AR9 |
30 months |
18.5 |
Drinking Fountain: Lower Level. Although an accessible drinking fountain is provided, there is no drinking fountain provided for people who have difficulty bending or stooping |
DF3 |
30 months |
18.6 |
Women’s Toilet Room With Stalls: Lower Level |
||
18.6.a |
The toilet room sign is mounted on the door and has no raised or Braille characters. |
TR18 |
24 months |
18.6.b |
The door is inaccessible because it requires 6 pounds of force to open. |
D2 |
12 months |
18.6.c |
The pull side of the door to the toilet room, which is accessed through a front approach, is inaccessible because it has only 17 inches of maneuvering space on the latch side. |
D6 |
30 months |
18.6.d |
The toilet room door swings into the required clear floor space at the lavatory. |
TR6 |
30 months |
18.6.e |
Although an audible alarm is provided in this facility, there is no visual alarm appliance in the toilet room. |
TR21 |
30 months |
18.6.f |
The designated accessible toilet is inaccessible because the stall is 45 inches wide. |
ST16 |
30 months |
18.6.g |
The designated accessible toilet is inaccessible because its centerline is 14 inches from the side wall. |
ST17 |
30 months |
18.6.h |
The designated accessible toilet is inaccessible because the flush control is on the closed side. |
ST2 |
30 months |
18.6.i |
No accessible coat hook has been provided. |
TR1 |
12 months |
18.7 |
Men’s Toilet Room With Stalls: Lower Level |
||
18.7.a |
The toilet room sign is mounted on the door and has no raised or Braille characters. |
TR18 |
24 months |
18.7.b |
The door is inaccessible because it requires 6 pounds of force to open. |
D2 |
12 months |
18.7.c |
Although an audible alarm is provided in this facility, there is no visual alarm appliance in the toilet room. |
TR21 |
30 months |
18.7.d |
The urinal is inaccessible because the rim is 23 inches high and the flush is 51 inches high. |
TR20 |
30 months |
18.7.e |
The designated accessible stall is incorrectly configured as an ambulatory stall, and there is no standard accessible stall provided. |
ST15 |
30 months |
19 |
ATLANTA POLICE ZONE 4, located at 1125 Cascade Circle |
||
19.1 |
Exterior Accessible Route: From Street Parking to Entrance. The route is inaccessible because the it slopes between 5.6% and 7.1% and has no ramp features. |
R3 |
30 months |
19.2 |
Interior Accessible Route: From Main Lobby to Toilet Rooms. The office doors are inaccessible because knob hardware is used. |
D1 |
24 months |
19.3 |
Men’s Toilet Room With Stalls |
||
19.3.a |
The toilet room sign is mounted on the door and lacks raised and Braille characters. |
TR18 |
24 months |
19.3.b |
The door is inaccessible because it requires 9 pounds of force to open. |
D2 |
12 months |
19.3.c |
The pull side of the door, which is accessed through a front approach, is inaccessible because it has only 2½ inches of maneuvering space on the latch side. |
D6 |
30 months |
19.3.d |
The toilet room door swings into the required clear floor space at the lavatory. |
TR6 |
30 months |
19.3.e |
Although an audible alarm is provided in this facility, there is no visual alarm appliance in the toilet room. |
TR21 |
30 months |
19.3.f |
No accessible mirror has been provided. |
TR14 |
12 months |
19.3.g |
The toilet room is inaccessible because there is insufficient turning space provided within the room. |
TR19 |
30 months |
19.3.h |
The soap dispenser is inaccessible because it is mounted with the controls 55 inches high over the lavatory. |
TR4 |
12 months |
19.3.i |
The lavatory is inaccessible because the rim or counter is 35½ inches high to the top. |
TR11 |
24 months |
19.3.j |
The lavatory is inaccessible because the hot water pipes are not insulated or otherwise configured to protect against contact. |
TR12 |
24 months |
19.3.k |
The urinal is inaccessible because the rim is 24 inches high and the flush control is 48 inches high. |
TR20 |
30 months |
19.3.l |
The designated accessible stall is incorrectly configured as an ambulatory stall, and there is no standard accessible stall provided. |
ST15 |
30 months |
19.4 |
Women’s Toilet Room With Stalls |
||
19.4.a |
The toilet room sign is mounted on the door and lacks raised and Braille characters. |
TR18 |
24 months |
19.4.b |
The door is inaccessible because it requires 9 pounds of force to open. |
D2 |
12 months |
19.4.c |
The pull side of the door, which is accessed through a front approach, is inaccessible because it has only 7 inches of maneuvering space on the latch side. |
D6 |
30 months |
19.4.d |
The toilet room door swings into the required clear floor space at the lavatory. |
TR6 |
30 months |
19.4.e |
Although an audible alarm is provided in this facility, there is no visual alarm appliance in the toilet room. |
TR21 |
30 months |
19.4.f |
No accessible mirror has been provided. |
TR14 |
12 months |
19.4.g |
The toilet room is inaccessible because there is insufficient turning space provided within the room. |
TR19 |
30 months |
19.4.h |
The seat cover dispenser is inaccessible because it is mounted with the controls 58 inches high. |
TR5 |
12 months |
19.4.i |
The lavatory is inaccessible because the hot water pipes are not insulated or otherwise configured to protect against contact. |
TR12 |
24 months |
19.4.j |
The urinal is inaccessible because the rim is 24 inches high and the flush control is 48 inches high. |
TR20 |
30 months |
19.4.k |
The designated accessible stall is incorrectly configured as an ambulatory stall, and there is no standard accessible stall provided. |
ST15 |
30 months |
20 |
ATLANTA FIRE STATION 15, located at 170 10th Street, NE |
||
20.1 |
Unisex Single-User Toilet Room |
||
20.1.a |
The toilet room sign is mounted on the door and has no raised or Braille characters. |
TR18 |
24 months |
20.1.b |
The door is inaccessible because it requires 10 pounds of force to open. |
D2 |
12 months |
20.1.c |
Although an audible alarm is provided in this facility, there is no visual alarm appliance in the toilet room. |
TR21 |
30 months |
20.1.d |
The lavatory is inaccessible because the hot water and drain pipes are not insulated or otherwise configured to protect against contact. |
TR12 |
24 months |
20.1.e |
The toilet is inaccessible because the top of the seat is 16 inches high. |
SU18 |
30 months |
20.1.f |
The toilet is inaccessible because the centerline is 27 inches from the side wall. |
SU15 |
30 months |
20.1.g |
The toilet is inaccessible because the rear grab bar is 24 inches long and it is mounted 14½ inches from the side wall. |
SU3 |
24 months |
21 |
ATLANTA FIRE STATION 17, located at 1489 Ralph David Abernathy Boulevard, SW |
||
21.1 |
Parking Lot. The parking lot, with a total of 4 parking spaces, has no designated accessible parking space. This lot requires 1 van accessible space. |
P3 |
24 months |
21.2 |
Accessible Route: From Street to Main Entrance. The route is inaccessible because the slope of the walkway is 13%. |
AR1 |
30 months |
21.3 |
Unisex Single-User Toilet Room: 1st Floor |
||
21.3.a |
The toilet room sign is mounted on the door and has no raised or Braille characters. |
TR18 |
24 months |
21.3.b |
Although an audible alarm is provided in this facility, there is no visual alarm appliance in the toilet room. |
TR21 |
30 months |
21.3.c |
The lavatory is inaccessible because the rim or counter is 26 inches high to the bottom. |
TR11 |
24 months |
21.3.d |
The lavatory is inaccessible because the hot water and drain pipes are not insulated or otherwise configured to protect against contact. |
TR12 |
24 months |
21.3.e |
The toilet is inaccessible because the flush control is on the closed side. |
SU1 |
24 months |
21.3.f |
The toilet is inaccessible because the side grab bar is mounted with the far end 50½ inches from the rear wall. |
SU6 |
12 months |
22 |
ATLANTA FIRE STATION 35, located at 2150 East Non-Licensed Vehicle Road |
||
22.1 |
Parking Lot. The parking lot, with 25 total parking spaces, is inaccessible because it has no space designated as van accessible. This lot requires 1 van accessible space. |
P3 |
24 months |
22.2 |
Exterior Accessible Route: From Parking Lot to Entrance |
||
22.2.a |
The route is inaccessible because the width of the walkway narrows to 21 inches at the pipes and to 22½ inches at the barbeque grill. |
AR3 |
30 months |
22.2.b |
The shelf of the barbeque grill protrudes into the walkway and is not detectable to blind persons using a cane. |
AR8 |
12 months |
22.3 |
Interior Accessible Route: To Blood Pressure Screening Room 127. The route from the entrance to room 127 is inaccessible because it narrows to 22 inches wide at the sofa. |
AR3 |
12 months |
22.4 |
Blood Pressure Screening Room: 127 |
||
22.4.a |
The signage provided has no raised or Braille characters. |
D26 |
24 months |
22.4.b |
The route inside the room is inaccessible because it is only 30 inches wide between the chair and the open door. |
AR3 |
12 months |
22.5 |
Unisex Toilet Room With Stalls: 124 |
||
22.5.a |
The toilet room sign has no raised or Braille characters. |
TR18 |
24 months |
22.5.b |
The door is inaccessible because it requires 7 pounds of force to open. |
D2 |
12 months |
22.5.c |
The urinal is inaccessible because the rim is 18 inches high and the flush control is 46 inches high. |
TR20 |
30 months |
22.5.d |
No accessible coat hook has been provided. |
TR1 |
12 months |
22.5.e |
The designated accessible toilet is inaccessible because the rear grab bar is mounted 7 inches from the near side wall. |
SU3 |
12 months |
23 |
DUNBAR NEIGHBORHOOD FACILITY, located at 477 Windsor Street, SW |
||
23.1 |
Parking Lot. The parking lot, with a total of 106 parking spaces, has only 4 designated accessible parking spaces, the designated accessible parking spaces have no vertical signage and no access aisles, and one of the designated accessible spaces has a cross slope of 3.4%. This lot requires 1 van accessible space and 4 standard accessible spaces. |
P3 |
30 months |
23.2 |
Accessible Route: 2nd Floor. The defibrillator protrudes into the walkway and is not detectable to blind persons using a cane. |
AR8 |
12 months |
23.3 |
Drinking Fountains: 2nd Floor |
||
23.3.a |
The drinking fountain is inaccessible because the control requires 15 pounds of force to operate. |
DF2 |
12 months |
23.3.b |
The drinking fountain protrudes into the walkway and is not detectable to blind persons using a cane. |
AR8 |
12 months |
23.4 |
Women’s Toilet Room With Stalls: 2nd Floor |
||
23.4.a |
The toilet room sign is mounted above the door and has no raised or Braille characters. |
TR18 |
24 months |
23.4.b |
The door is inaccessible because it requires 10 pounds of force to open. |
D2 |
12 months |
23.4.c |
The pull side of the door, which is accessed through a front approach, is inaccessible because it has only 12 inches of clear space on the latch side. |
D6 |
30 months |
23.4.d |
No accessible mirror has been provided. |
TR14 |
12 months |
23.4.e |
The air dryer protrudes into the walkway and is not detectable to blind persons using a cane. |
AR8 |
12 months |
23.4.f |
The designated accessible stall is incorrectly configured as an ambulatory stall, and there is no standard accessible stall provided. |
ST15 |
30 months |
23.5 |
Men’s Toilet Room With Stalls: 2nd Floor |
||
23.5.a |
The toilet room sign is mounted above the door and has no raised or Braille characters. |
TR18 |
24 months |
23.5.b |
The door is inaccessible because it requires 11 pounds of force to open. |
D2 |
12 months |
23.5.c |
No accessible mirror has been provided. |
TR14 |
12 months |
23.5.d |
The air dryer protrudes into the walkway and is not detectable to blind persons using a cane. |
AR8 |
12 months |
23.5.e |
The urinals are inaccessible because the rims are 21 inches high. |
TR20 |
24 months |
23.5.f |
The designated accessible stall is incorrectly configured as an ambulatory stall, and there is no standard accessible stall provided. |
ST15 |
30 months |
23.6 |
Elevator. The elevator is inaccessible because, although emergency communications are provided, the system does not work without voice communication. |
E8 |
30 months |
23.7 |
Offices and Rooms. The doors are inaccessible because they require more than 5 pounds of force to open. |
D2 |
12 months |
24 |
JOHN C. BIRDINE NEIGHBORHOOD FACILITY, located at 215 Lakewood Way, SW |
||
24.1 |
Parking Lot. The parking lot, with a total of 81 parking spaces, has no van accessible parking space, has no vertical signage designating spaces as accessible, and has designated accessible spaces and access aisles that slope between 5.2% and 7.7%. This lot requires 1 van accessible space and 3 standard accessible spaces. |
P3 |
30 months |
24.2 |
Exterior Accessible Route: From Parking Lot to Main Entrance |
||
24.2.a |
The route is inaccessible because the cross-slope of the walkway is 6.4%. |
AR1 |
30 months |
24.2.b |
The route is inaccessible because the slope of the curb ramp is 17.6%, and the flared sides are too steep. |
AR5 |
30 months |
24.3 |
Main Lobby: Counter. The reception counter in the 1st floor lobby is inaccessible because it is 42½ high. |
C6 |
24 months |
24.4 |
Women’s Toilet Room With Stalls: 1st Floor West Side |
||
24.4.a |
The toilet room sign is mounted on the door and has no raised or Braille characters and no International Symbol of Accessibility. |
TR17 |
24 months |
24.4.b |
The door is inaccessible because it requires 17 pounds of force to open. |
D2 |
12 months |
24.4.c |
No accessible mirror has been provided. |
TR14 |
12 months |
24.4.d |
The air dryer protrudes into the walkway and is not detectable to blind persons using a cane. |
AR8 |
12 months |
24.4.e |
The designated accessible stall is incorrectly configured as an ambulatory stall, and there is no standard accessible stall provided. |
ST15 |
30 months |
24.5 |
Men’s Toilet Room With Stalls: 1st Floor West Side |
||
24.5.a |
The toilet room sign is mounted on the door and has no raised or Braille characters and no International Symbol of Accessibility. |
TR17 |
24 months |
24.5.b |
The door is inaccessible because it requires 14 pounds of force to open. |
D2 |
12 months |
24.5.c |
No accessible mirror has been provided. |
TR14 |
12 months |
24.5.d |
The air dryer protrudes into the walkway and is not detectable to blind persons using a cane. |
AR8 |
12 months |
24.5.e |
The urinal is inaccessible because the rim is 23 inches high. |
TR20 |
24 months |
24.5.f |
The designated accessible stall is incorrectly configured as an ambulatory stall, and there is no standard accessible stall provided. |
ST15 |
30 months |
24.6 |
Drinking Fountains: 1st Floor West Side. The higher drinking fountain protrudes into the walkway and is not detectable to blind persons using a cane. |
AR8 |
12 months |
24.7 |
Women’s and Men’s Toilet Rooms with Stalls: 1st Floor East Side. The toilet rooms lack accessible directional signage with the International Symbol of Accessibility indicating the location of the nearest accessible toilet room. |
TR16 |
24 months |
24.8 |
Interior Accessible Route: 1st Floor East Side. The defibrillator protrudes into the walkway and is not detectable to blind persons using a cane. |
AR8 |
12 months |
24.9 |
Library. The library is inaccessible because the automatic door opener requires 14 pounds of force to operate. |
TR3 |
12 months |
24.10 |
Women’s and Men’s Toilet Rooms with Stalls: 2nd Floor West Side: The toilet rooms lack accessible directional signage with the International Symbol of Accessibility indicating the location of the nearest accessible toilet room. |
TR16 |
24 months |
24.11 |
Drinking Fountains: 2nd Floor West Side. The higher drinking fountain protrudes into the walkway and is not detectable to blind persons using a cane. |
AR8 |
12 months |
24.12 |
East Wing Counter. The counter is inaccessible because it is 40 inches high. |
C6 |
24 months |
25 |
MADDOX PARK, located at 1145 North Avenue, NW |
||
25.1 |
Parking Lot. The parking lot, with a total of 12 parking spaces, has no designated accessible parking spaces. This lot requires 1 van accessible space. |
P3 |
24 months |
25.2 |
Exterior Accessible Routes |
||
25.2.a |
There is no accessible route to the tennis court because there is no curb ramp from the road. |
AR5 |
30 months |
25.2.b |
The route to the pavilion is inaccessible because it has numerous stairs. |
AR1 |
30 months |
25.3 |
Picnic Tables. There are no accessible picnic tables provided. |
PD6 |
30 months |
25.4 |
Locker Rooms. The men’s and women’s locker rooms contain a number of inaccessible elements and are not accessible to people with disabilities. |
LR4 |
30 months |
26 |
CHASTAIN ARTS CENTER, located at 135 W. Wieuca Road, NW |
||
26.1 |
Parking. The parking lot, with a total of 28 parking spaces, is inaccessible because the designated accessible spaces have no access aisles and no vertical signage. This lot requires 1 van accessible space and 1 standard accessible space. |
P3 |
24 months |
26.2 |
Ramp to Entry |
||
26.2.a |
The ramp is inaccessible because it has a lip at the top and the bottom 1 inch high. |
AR1 |
30 months |
26.2.b |
The ramp is inaccessible because it has insufficient landing at the bottom and at the change in direction, it slopes between 10.5% and 11.1%, it does not have adequate edge protection, and the handrails lack extensions. |
R3 |
30 months |
26.3 |
Curb Ramp. The curb ramp is inaccessible because it has a slope of 9.6%. |
AR5 |
24 months |
26.4 |
Entrances. The building does not have directional signage posted at inaccessible entrances and does not have the International Symbol of Accessibility posted at accessible entrances. |
D16 |
24 months |
26.5 |
Front Entrance |
||
26.5.a |
The route from the entry ramp to the front door is inaccessible because it slopes 9.4% and has no handrails. |
AR1 |
24 months |
26.5.b |
The route to the front door is inaccessible because the ramp’s front edge has a 1 inch high step up onto it. |
AR1 |
24 months |
26.5.c |
The front door is inaccessible because there is a slope of 10.8% within the door’s required maneuvering clearance. |
D13 |
24 months |
26.6 |
Children’s Studio Entrance. The ramp to the entrance is inaccessible because it slopes up to 16.8%, it does not have adequate edge protection, and the handrail is mounted 2 inches from the wall. |
R3 |
24 months |
26.7 |
Men’s Single-User Toilet Room: Near Children’s Studio |
||
26.7.a |
No accessible mirror has been provided. |
TR14 |
12 months |
26.7.b |
The lavatory is inaccessible because the hot water pipes are not fully insulated or otherwise configured to protect against contact. |
TR12 |
24 months |
26.7.c |
The toilet is inaccessible because its centerline is 19½ inches from the side wall. |
SU15 |
30 months |
26.7.d |
The side grab bar at the toilet is inaccessible because it is mounted 15 inches from the rear wall. |
SU6 |
12 months |
26.8 |
Women’s Single-User Toilet Room: Near Children’s Studio |
||
26.8.a |
No accessible mirror has been provided. |
TR14 |
12 months |
26.8.b |
The lavatory is inaccessible because the hot water pipes are not fully insulated or otherwise configured to protect against contact. |
TR12 |
24 months |
26.8.c |
The side grab bar at the toilet is inaccessible because it is mounted 15 inches from the rear wall. |
SU6 |
12 months |
26.9 |
Drinking Fountain: Main Entry. The drinking fountain is inaccessible because the spout is 41½ inches high, the water flow is 3 inches high, the water flows 4 inches from the front of the fountain, and the controls require 9 pounds of force to operate. |
DF1 |
30 months |
26.10 |
Interior Doors. Many of the doors are inaccessible because knob hardware is used. |
D1 |
24 months |
26.11 |
Interior Accessible Route. The suggestion box in the classroom hallway protrudes into the walkway and is not detectable to blind persons using a cane. |
AR8 |
12 months |
26.12 |
Inaccessible Toilet Rooms. There is no signage directing people with disabilities to the accessible toilet rooms. |
TR16 |
30 months |
26.13 |
Pottery Studio: Main Building |
||
26.13.a
|
No accessible coat hook has been provided. |
TR1 |
12 months |
26.13.b
|
The fire extinguisher protrudes into the walkway and is not detectable to blind persons using a cane. |
AR8 |
12 months |
26.14 |
City Gallery: Main Entrance. The door is inaccessible because there is a 1½ inch high threshold. |
D23 |
24 months |
26.15 |
City Gallery: Painting Studio. The door is inaccessible because there is a 1½ inch high threshold. |
D23 |
24 months |
26.16 |
City Gallery: Studio I and II. The doors are inaccessible because knob hardware is used. |
D1 |
24 months |
26.17 |
City Gallery: Toilet Rooms. The toilet rooms contain a number of inaccessible elements and are not accessible to people with disabilities, and there is no signage directing people with disabilities to the accessible toilet rooms. |
TR16 |
30 months |
26.18 |
City Gallery: Drinking Fountain. |
||
26.18.a
|
The drinking fountain protrudes into the walkway and is not detectable to blind persons using a cane. |
AR8 |
12 months |
26.18.b |
Although an accessible drinking fountain is provided, there is no drinking fountain provided for people who have difficulty bending or stooping. |
DF3 |
30 months |