ATTACHMENT J: Modifications to Altered Facilities

Please Note:  Paragraph 42 of the Settlement Agreement requires that within three months of the effective date of this Agreement, the City provide signage as necessary to comply with 28 C.F.R. § 35.163(b), after having surveyed all facilities that are the subject of this Agreement for the purpose of identifying those that have multiple entrances not all of which are accessible.

In order to ensure that the following spaces and elements in City facilities in which alterations occurred after January 26, 1992, are readily accessible to and usable by persons with disabilities, the City will take the actions referenced by the alphanumeric code and described in detail in Attachment M to this Settlement Agreement.  Actions are to be completed before the end of the time specified in the Completion Date column.

Item #

Access Issue

Required Action

Completion Date

1 

ATLANTA WORKFORCE DEVELOPMENT AGENCY, located at 818 Pollard Boulevard

   

1.1

Parking.  The parking lot is inaccessible because the  designated standard accessible spaces are between 89 and 92 inches wide, they have no access aisles, they have no vertical signage, and the van accessible space has no “Van Accessible” sign.

P3

30 months

1.2

Exterior Accessible Route.  The curb ramp from the parking lot to the entrance is inaccessible because it has a slope of 16%.

AR5

30 months

1.3

Interior Signage.  Much of the permanent room signage inside the facility is mounted above the doors and does not have Braille or raised lettering.

D26

30 months

1.4

Drinking Fountains: Main Entrance.  Although accessible drinking fountains are provided, there is no drinking fountain provided for people who have difficulty bending or stooping.

DF3

24 months

1.5

Men’s Toilet Room With Stalls First Floor: Near Main Entrance

   

1.5.a 

The room is inaccessible because the toilet room sign is mounted on the door and has no raised letters and no International Symbol of Accessibility.

TR17

24 months

1.5.b 

No accessible mirror has been provided.

TR14

12 months

1.5.c 

The paper towel dispenser protrudes into the walkway and is not detectable to blind persons using a cane.

AR8

12 months

1.5.d 

The urinal is inaccessible because the rims are 23 inches high.

TR20

30 months

1.5.e 

The designated accessible toilet is inaccessible because the centerline is 16½ inches from the side wall.

ST17

30 months

1.5.f

No accessible coat hook has been provided in the wide stall.

TR1

12 months

1.5.g 

The designated accessible toilet is inaccessible because the side grab bar is obstructed by the toilet paper dispenser and is mounted 37 inches high.

ST8

ST12

12 months

1.6

Women’s Toilet Room With Stalls: First Floor Near Main Entrance

   

1.6.a 

The room is inaccessible because the room sign is mounted on the door and has no raised letters and no International Symbol of Accessibility.

TR17

24 months

1.6.b 

The seat cover dispenser is inaccessible because it is mounted 62 inches high.

TR5

12 months

1.6.c 

The soap dispenser is inaccessible because it is mounted with the controls 55 inches high.

TR5

12 months

1.6.d 

The designated accessible toilet is inaccessible because the centerline is 16 inches from the side wall.

ST17

30 months

1.6.e 

The designated accessible toilet is inaccessible because the flush control is on the closed side.

ST2

30 months

1.6.f

No accessible coat hook has been provided in the wide stall.

TR1

12 months

1.6.g 

The designated accessible toilet is inaccessible because the side grab bar is obstructed by the toilet paper dispenser.

ST8

12 months

1.6.h 

Although there are 7 toilet stalls, there is no ambulatory stall provided.

ST1

30 months

1.7

Literacy Services.  The counter is more than 36 inches high.

C6

30 months

1.8

Sullivan Hall Auditorium

   

1.8.a 

The auditorium is inaccessible to people with hearing disabilities because, although there are 500 fixed seats, there is no permanently installed assistive listening system provided.  This auditorium requires 20 receivers. 

AA4

30 months

1.8.b 

The seating is inaccessible because there is no fixed companion seating adjacent to wheelchair seating locations.

AA6

30 months

1.9

Elevators

   

1.9.a 

The elevator is inaccessible because it has no audible hall arrival signal.

E11

30 months

1.9.b 

The elevator is inaccessible because there is hoistway signage on only one side, and it has no Braille.

E12

30 months

1.9.c 

The elevator is inaccessible because the clearance between the car platform sill and the edge of the hoistway landing is 1½ inches.

E10

30 months

1.9.d 

The elevator is inaccessible because the car control buttons have no Braille or raised characters, and the main entry floor is not designated by a raised star.

E4

30 months

1.9.e 

The elevator is inaccessible because the emergency communications are not identified by raised lettering, and the door requires pinching to open.

E8

30 months

1.10

Conference Room 240.  There is no assistive listening system available.  This room requires 2 receivers. 

AA5

30 months

1.11

Platform Lift: Near Taxicab Services.  The lift cannot be operated without the user first obtaining a key.

LF1

24 months

1.12

Taxi Bureau.  The room is inaccessible because the double doors are each 27 inches wide, require 7 pounds of force to open, and have thumb latch hardware.

D4

30 months

1.13

Men’s Toilet Room: Near Classrooms

   

1.13.a 

The room is inaccessible because the room sign is painted on the door and has no Braille or raised lettering.

TR18

24 months

1.13.b 

There is no signage directing people with disabilities to the accessible toilet rooms.

TR16

24 months

1.14

Drinking Fountain: Near Classrooms.  The drinking fountain is inaccessible because it has a spout 41 inches high and the water trajectory is 1 inch high.

DF1

24 months

1.15

Administrative Office: Room 217.  The door is inaccessible because it requires 8 pounds of force to open.

D2

24 months

1.16

Interior Accessible Route: Second Floor Near Administrative Office.  The fire extinguisher and the hanging plants in the hallway protrude into the walkway and are not detectable to blind persons using a cane.

AR8

12 months

1.17

Men’s Toilet Room: Second Floor Near Elevators

   

1.17.a 

The room is inaccessible because the room sign is mounted on the door and has no raised letters and no International Symbol of Accessibility.

TR17

24 months

1.17.b 

The paper towel dispenser protrudes into the walkway and is not detectable to blind persons using a cane.

AR8

12 months

1.17.c 

The urinals are inaccessible because the rims are 23 inches high.

TR20

30 months

1.17.d 

No accessible coat hook has been provided.

TR1

12 months

1.17.e 

The designated accessible toilet is inaccessible because the side grab bar is obstructed by the toilet paper dispenser.

ST8

12 months

1.17.f

The designated accessible toilet is inaccessible because the grab bars are mounted 1¾ inches from the wall.

ST13

12 months

1.18

Women’s Toilet Room: Second Floor Near Elevators

   

1.18.a 

The room is inaccessible because the room sign is mounted on the door and has no raised letters and no International Symbol of Accessibility.

TR17

24 months

1.18.b 

The soap dispenser is inaccessible because it is mounted with the controls 55 inches high behind the lavatory.

TR4

12 months

1.18.c 

The designated accessible toilet is inaccessible because the centerline is 18½ inches from the side wall.

ST17

30 months

1.18.d 

The designated accessible toilet is inaccessible because the flush control is on the closed side.

ST2

30 months

1.18.e 

No accessible coat hook has been provided.

TR1

12 months

1.18.f

The designated accessible toilet is inaccessible because the side grab bar is obstructed by the toilet paper dispenser.

ST8

12 months

1.18.g 

The designated accessible toilet is inaccessible because the grab bars are mounted 36½ inches high.

ST12

12 months

1.18.h 

The designated accessible toilet is inaccessible because the grab bars are mounted 1¾ inches from the wall.

ST13

12 months

1.18.i

Although there are 7 stalls, there is no ambulatory stall provided.

ST1

30 months

1.19

Men’s Toilet Room: Third Floor Near Elevators

   

1.19.a 

The room is inaccessible because the room sign has no raised or Braille characters and no International Symbol of Accessibility.

TR17

24 months

1.19.b 

The door is inaccessible because it requires more than 5 pounds to open.

D2

12 months

1.19.c 

No accessible mirror has been provided.

TR14

12 months

1.19.d 

The soap dispenser is inaccessible because it is mounted with the controls 48 inches behind the lavatory.

TR4

12 months

1.19.e 

The towel dispenser protrudes into the walkway and is not detectable to blind persons using a cane.

AR8

12 months

1.19.f

The urinals are inaccessible because the rims are 23 inches high.

TR20

30 months

1.19.g 

No accessible coat hook has been provided.

TR1

12 months

1.19.h 

There are no grab bars provided at the toilet.

ST11

30 months

1.20

Women’s Toilet Room: Third Floor Near Elevators

   

1.20.a 

The room is inaccessible because the room sign has no raised or Braille characters and no International Symbol of Accessibility.

TR17

24 months

1.20.b 

The door is inaccessible because it requires more than 5 pounds to open.

D2

12 months

1.20.c 

The soap dispenser is inaccessible because it is mounted with the controls 49 inches behind the lavatory.

TR4

12 months

1.20.d 

The towel dispenser protrudes into the walkway and is not detectable to blind persons using a cane.

AR8

12 months

1.20.e 

The designated accessible toilet is inaccessible because the flush control is on the closed side.

ST2

30 months

1.20.f

The designated accessible toilet is inaccessible because the side grab bar is obstructed by the toilet paper dispenser.

ST8

12 months

1.20.g 

The designated accessible toilet is inaccessible because the grab bars are mounted 1¾ inches from the wall.

ST13

12 months

1.20.h 

The designated accessible toilet is inaccessible because the grab bars are mounted 37 inches high.

ST12

12 months

1.20.i

Although there are 7 stalls, there is no ambulatory stall provided.

ST1

30 months

1.21

Georgia Center for Children: Third Floor Single User Toilet Room

   

1.21.a 

The lavatory is inaccessible because the rim or counter is 27½  inches high to the bottom.

TR11

30 months

1.21.b 

The toilet is inaccessible because the far end of the side grab bar is 45 inches from the rear wall, the rear grab bar is 24 inches long, and both grab bars are mounted 1¾ inches from the wall.

SU5

24 months

2 

COAN PARK RECREATION CENTER, located at 1530 Woodbine Ave, SE

   

2.1

Parking: Near Playground.  The parking lot, with a total of 28 parking spaces, is inaccessible because none of the spaces is accessible.  This lot requires 1 van accessible space.

P3

30 months

2.2

Exterior Accessible Route: Parking Lot To Recreation Center.  The route to the entrance is inaccessible because the curb ramp from the parking area has a slope of 10.8%, a cross-slope of 3.3% and very steep side flares.

AR5

30 months

2.3

Gymnasium.  The gymnasium is inaccessible because the entry doors have a 1½ inch high threshold.

D22

24 months

2.4

Drinking Fountain: Near Toilet Rooms.  The drinking fountain is inaccessible because the spout is 37 inches above the finished floor.

DF6

24 months

2.5

Toilet Rooms with Stalls.  The men’s and women’s toilet rooms contain a number of inaccessible elements and are not accessible to people with disabilities.

ST14

30 months

2.6

Computer Room

   

2.6.a 

The door is inaccessible because it has an opening width of only 29½ inches.

D25

30 months

2.6.b 

The computers are inaccessible because the keyboards are on tables 26½ inches high.

C3

30 months

2.7

Parking: Pavilion.  The parking is inaccessible because the signage designating parking as reserved for persons with disabilities is too low.

P6

12 months

2.8

Accessible Exterior Route: Parking Lot to Pavilion

   

2.8.a 

The route to the pavilion is inaccessible because the curb ramp from the parking area has a slope of 13.7%.

AR5

30 months

2.8.b 

The route to the pavilion is inaccessible because the ramp does not have adequate edge protection on the bottom portion, and the handrails are mounted 3½ inches from the wall.

R5

30 months

3 

POLICE OFFICE OF PROFESSIONAL STANDARDS, located at 950 Lowery Boulevard

   

3.1

Parking.  The parking is inaccessible because the space marked as van accessible has a 60 inch wide access aisle.

P3

24 months

3.2

Exterior Accessible Route: Parking to Entrance.  The route is inaccessible because the ramp has a slope of 9.3%, there is no handrail extension at the top on one side, and the handrail is mounted 5½ inches from the wall.

R5

30 months

3.3

Entrance.  The entrance is inaccessible because it requires 10 pounds of force to open.

D2

12 months

3.4

Women’s Toilet Room Single-User: Lobby Area

   

3.4.a 

The room is inaccessible because the room sign is mounted 56 inches high and has no Braille.

TR18

24 months

3.4.b 

The door is inaccessible because it requires 7 pounds of force to open.

D2

12 months

3.4.c 

The room is inaccessible because the door has a ½ inch high unbeveled threshold.

D22

24 months

3.4.d 

No accessible mirror has been provided.

TR14

12 months

3.4.e 

The toilet is inaccessible because the side grab bar is mounted with its far end 48 inches from the rear wall.

SU6

12 months

3.4.f

The toilet is inaccessible because the rear grab bar is only 30 inches long and is obstructed by the seat cover dispenser.

SU2

24 months

3.5

Men’s Toilet Room Single-User: Lobby Area

   

3.5.a 

The room is inaccessible because the room sign is mounted 56 inches high and has no Braille.

TR18

24 months

3.5.b 

The room is inaccessible because the door has a ½ inch high unbeveled threshold.

D22

24 months

3.5.c 

The toilet is inaccessible because the side grab bar is mounted with its far end 48 inches from the rear wall.

SU6

12 months

3.6

Interview Room #2.  The pull side of the door, which is accessed from the hinge side of the door, has inadequate maneuvering space

D8

30 months

3.7

Men’s Single-User Toilet Room: Office Area

   

3.7.a 

The room is inaccessible because the room sign is mounted 56 inches high and has no Braille.

TR18

24 months

3.7.b 

The room is inaccessible because the door has an unbeveled threshold greater than ¼ inch.

D22

24 months

3.7.c 

No accessible mirror has been provided.

TR14

12 months

3.7.d 

The toilet is inaccessible because the side grab bar is mounted with its far end 48 inches from the rear wall.

SU6

12 months

3.8

Women’s Single-User Toilet Room: Office Area

   

3.8.a 

The room is inaccessible because the room sign is mounted 56 inches high and has no Braille.

TR18

24 months

3.8.b 

The room is inaccessible because the door has an unbeveled threshold greater than ¼ inch.

D22

24 months

3.8.c 

No accessible mirror has been provided.

TR14

12 months

3.8.d 

The toilet is inaccessible because the centerline is 19 inches from the side wall.

SU15

30 months

3.8.e 

The toilet is inaccessible because the flush control is on the closed side.

SU1

30 months

3.8.f

The toilet is inaccessible because the side grab bar is mounted with its far end 48 inches from the rear wall.

SU6

12 months

4 

ANDERSON PARK RECREATION CENTER, located at 120 Anderson Ave, NW

   

4.1

Parking

   

4.1.a 

Although the parking lot has a total of 29 parking spaces, there is no van accessible space provided, and neither designated accessible space has vertical signage.

P3

30 months

4.1.b 

The built-up curb ramp impermissibly extends into the required accessible parking space’s access aisle.

AR4

30 months

4.2

Main Entrance.  The entrance is inaccessible because the door has hardware that requires tight pinching to open.

D1

24 months

4.3

Drinking Fountain:  Lobby

   

4.3.a 

The drinking fountain protrudes into the walkway and is not detectable to blind persons using a cane.

AR8

12 months

4.3.b 

Although a designated accessible drinking fountain is provided, there is no drinking fountain provided for people who have difficulty bending or stooping.

DF3

30 months

4.4

Men’s Toilet Room with Stalls: Lobby

   

4.4.a 

The room is inaccessible because the room sign is mounted on the hinge side of the door.

TR18

12 months

4.4.b 

No accessible mirror has been provided.

TR14

12 months

4.4.c 

The soap dispenser is inaccessible because it is mounted with the controls 55 inches high over the lavatories.

TR4

12 months

4.4.d 

The urinals are inaccessible because they are mounted with their rims 24 inches high and their flush controls 50 inches high.

TR20

30 months

4.4.e 

The toilet is inaccessible because the stall is 42 inches wide.

ST16

30 months

4.4.f

The toilet is inaccessible because the centerline is 20½ inches from one side wall and 21½ inches from the other.

ST17

30 months

4.4.g 

No accessible coat hook has been provided.

TR1

12 months

4.5

Women’s Toilet Room with Stalls: Lobby

   

4.5.a 

No accessible mirror has been provided.

TR14

12 months

4.5.b 

The air dryer protrudes into the walkway and is not detectable to blind persons using a cane.

AR8

12 months

4.5.c 

The toilet is inaccessible because the stall is 46 inches wide

ST16

30 months

4.5.d 

No accessible coat hook has been provided.

TR1

12 months

4.6

Gymnasium Floor.  The gymnasium is inaccessible because the route onto the floor of the gymnasium contains stairs.

AR2

30 months

4.7

Locker Rooms.  The men’s and women’s locker rooms contain a number of inaccessible elements.

ST14

LR1

LR2

LR3

B8

30 months

5 

A. D. WILLIAMS PARK, located at 1154 James P. Brawley Parkway, NW

   

5.1

Parking.  Although the parking lot has a total of 19 parking spaces, there is no van accessible space provided, and one of the designated accessible space’s access aisles has a cross slope of 4.7%.

P3

36 months

5.2

Exterior Accessible Route: Parking to Entrance

   

5.2.a 

The route to the entrance is inaccessible because the curb ramp leading from the parking lot has a slope of 12.2%.

AR5

30 months

5.2.b 

The ramp to the entrance is inaccessible because it has a cross-slope of 3.9% in one area, it has handrails on only one side, the handrail lacks extensions at the top and bottom and the ends are not rounded or returned.

R5

30 months

5.3

Exterior Accessible Route: To Playground.  The route to the playground is inaccessible because it is covered in mulch and is not firm, stable, and slip resistant.

AR1

30 months

5.4

Entrances.  The building does not have directional signage posted at inaccessible entrances and does not have the International Symbol of Accessibility posted at accessible entrances.

D16

24 months

5.5

Men’s Toilet Room with Stalls

   

5.5.a 

The room is inaccessible because the room sign does not have raised or Braille characters.

TR18

24 months

5.5.b 

The toilet room is inaccessible because the route into the room narrows to 20 inches at the vent unit.

AR3

24 months

5.5.c 

Although an audible alarm is provided in this facility, there is no visual alarm appliance in the toilet room.

TR21

30 months

5.5.d 

No accessible mirror has been provided.

TR14

12 months

5.5.e 

The lavatory is inaccessible because the rim or counter is 28 inches high to the top.

TR11

24 months

5.5.f

The lavatory is inaccessible because the hot water pipes are not insulated or otherwise configured to protect against contact.

TR12

24 months

5.5.g 

The lavatory is inaccessible because it has twist-type hardware.

TR10

24 months

5.5.h 

The urinal is inaccessible because the rim is 24 inches high.

TR20

30 months

5.5.i

The designated accessible toilet is inaccessible because its centerline is 16 inches from the side wall.

ST17

30 months

5.5.j

The designated accessible toilet is inaccessible because the flush control is on the closed side.

ST2

30 months

5.5.k 

The toilet paper dispenser in the designated accessible stall is inaccessible because it is mounted 43 inches from the rear wall.

ST19

12 months

5.5.l

The toilet is inaccessible because the side grab bar is 32 inches long, with the near end 23 inches from the rear wall, it is mounted 2 inches from the side wall, and it is obstructed by the cleaning products and toilet paper rolls placed on it.

ST6

24 months

5.5.m

The rear grab bar at the designated accessible toilet is inaccessible because  it is mounted 4 inches from the rear wall.

ST13

12 months

5.5.n 

The toilet is inaccessible because the rear grab bar is obstructed by the toilet pipe and by the toilet paper rolls placed on it.

ST5

30 months

5.6

Women’s Toilet Room with Stalls

   

5.6.a 

The room is inaccessible because the room sign is not mounted on the latch side of the door and does not have raised or Braille characters.

TR18

24 months

5.6.b 

The toilet room is inaccessible because the route into the room narrows to 18 inches at the vent unit.

AR3

24 months

5.6.c 

Although an audible alarm is provided in this facility, there is no visual alarm appliance in the toilet room.

TR21

30 months

5.6.d 

No accessible mirror has been provided.

TR14

12 months

5.6.e 

The lavatory is inaccessible because the rim or counter is 28 inches high to the top.

TR11

24 months

5.6.f

The lavatory is inaccessible because the hot water pipes are not insulated or otherwise configured to protect against contact.

TR12

24 months

5.6.g 

The lavatory is inaccessible because it has twist-type hardware.

TR10

24 months

5.6.h 

There is no accessible stall provided.

ST15

30 months

6 

GATEWAY HOMELESS SERVICES CENTER, located at 275 Pryor St, SW

   

6.1

Exterior Accessible Route: Bus Stop to Entrance.  The route to the entrance is inaccessible because there is no curb ramp to allow access from the street onto the sidewalk.

AR5

30 months

6.2

Men’s Toilet Room with Stalls: First Floor

   

6.2.a 

The room is inaccessible because the room sign is mounted 55 inches high to the center.

TR18

12 months

6.2.b 

The toilet paper dispenser is inaccessible because it is mounted 40 inches from the rear wall.

ST19

12 months

6.3

Drinking Fountains.  The high drinking fountain protrudes into the walkway and is not detectable to blind persons using a cane.

AR8

12 months

6.4

Men’s Shower:  First Floor.  The shower is inaccessible because it has grab bars on only 2 walls.

B8

30 months

6.5

Women’s Single-User Toilet Room

   

6.5.a 

The room is inaccessible because the room sign is mounted 55 inches high to the center.

TR18

12 months

6.5.b 

No accessible coat hook has been provided.

TR1

12 months

6.6

Intake Counter.  The counter is inaccessible because it is 42½ inches high.

C6

30 months

6.7

Men’s Toilet Room with Stalls: First Floor North Wing

   

6.7.a 

The room is inaccessible because the sign is mounted 56½ inches high to the center.

TR18

12 months

6.7.b 

The door is inaccessible because it requires 14 pounds of force to open.

D2

12 months

6.8

Women’s Toilet Room with Stalls: First Floor North Wing

   

6.8.a 

The room is inaccessible because the sign is mounted 56½ inches high to the center.

TR18

12 months

6.8.b 

The door is inaccessible because it requires 14 pounds of force to open.

D2

12 months

6.9

Drinking Fountains: First Floor North.  The lower drinking fountain is inaccessible because it has 26 inches of knee height.

DF5

24 months

6.10

Elevators: First Floor East Bank

   

6.10.a 

The elevator is inaccessible because the hall lanterns do not signal once for up and twice for down.

E11

30 months

6.10.b 

The elevator is inaccessible because the hoistway signage is mounted 61½ inches high.

E12

30 months

6.11

Women’s and Children’s Center: First Floor.  The counter is inaccessible because it is 42½ inches high.

C6

30 months

6.12

Bedroom #150: First Floor.  The door is inaccessible because knob hardware is used.

D1

24 months

6.13

Bedroom #149: First Floor.  The door is inaccessible because knob hardware is used.

D1

24 months

6.14

Women’s Shower Room: First Floor

   

6.14.a 

The room is inaccessible because the sign is mounted 57 inches high to the center.

TR18

12 months

6.14.b 

No accessible coat hook is provided in the designated accessible toilet stall.

TR1

12 months

6.14.c 

The shower is inaccessible because it has grab bars on only 2 walls.

B8

30 months

6.15

Men’s Dormitory Reception: Second Floor.  The counter is inaccessible because it is 42½ inches high.

C6

30 months

6.16

Unisex Locker Room: Second Floor Men’s Dorm Eastside

   

6.16.a 

The room is inaccessible because the sign is mounted 57 inches high to the center.

TR18

12 months

6.16.b 

The lockers are inaccessible because the hardware requires tight grasping to operate.

LR3

30 months

6.16.c 

The designated accessible toilet is inaccessible because its centerline is 17 inches from the side wall.

ST17

30 months

6.16.d 

The shower is inaccessible because it has grab bars on only 2 walls.

B8

30 months

6.17

Sleeping Pods.  None of the tables provides the required knee space to accommodate a person in a wheelchair.

PD3

30 months

6.18

Unisex Locker Room: Second Floor Men’s Dorm Westside

   

6.18.a 

The room is inaccessible because the sign is mounted 54 inches high to the center.

TR18

12 months

6.18.b 

The shower is inaccessible because it has grab bars on only 2 walls.

B8

30 months

6.19

Clinic Room 202A: Second Floor

   

6.19.a 

The door is inaccessible because it requires 10 pounds of force to open.

D2

12 months

6.19.b 

There is no signage directing people with disabilities to the accessible toilet rooms.

TR16

24 months

6.20

Unisex Single-User Toilet Room/Shower: Third Floor Men’s Dorm

   

6.20.a 

The room is inaccessible because the sign is mounted 55 inches high to the center.

TR18

12 months

6.20.b 

The shower is inaccessible because it has grab bars on only 2 walls.

B8

30 months

6.21

Unisex Single-User Toilet Room/Shower: Fourth Floor Men’s Dorm

   

6.21.a 

The room is inaccessible because the sign is mounted 57 inches high to the center.

TR18

12 months

6.21.b 

The toilet paper dispenser is inaccessible because it is mounted 40 inches from the rear wall.

SU17

12 months

6.21.c 

The shower is inaccessible because it has grab bars on only 2 walls.

B8

30 months

7 

ATLANTA FIRE STATION 31, located at 2406 Fairburn Road, SW

   

7.1

Main Entrance.  The entrance is inaccessible because it does not have level maneuvering clearance, there is only 8 inches of clearance on the latch side, pull side, the threshold is 1¼ inches high, and there is knob hardware.

D17

30 months

7.2

Accessible Route: Public Entrance through Truck Bay to Toilet Rooms

   

7.2.a 

The route is inaccessible because it is less than 36 inches wide.

AR3

24 months

7.2.b 

There is equipment on the truck that protrudes into the walkway and is not detectable to blind persons using a cane.

AR8

12 months

7.3

Unisex Single-User Toilet Room.  The toilet room contains a number of inaccessible elements and is not accessible to people with disabilities.

SU13

30 months

8 

GEORGIA HILL NEIGHBORHOOD FACILITY, located at 250 Georgia Avenue, SE

   

8.1

Parking Lot. The parking lot, with a total of 89 parking spaces, is inaccessible because it only has 3 spaces designated as accessible, there is no van accessible space, there are no access aisles, and the signs are mounted too low.  This lot requires 1 van accessible space and 3 standard accessible spaces.

P3

30 months

8.2

Exterior Accessible Route: Parking to Main Entrance

   

8.2.a 

The route is inaccessible because the curb ramp from the parking area onto the sidewalk has a slope of 16% and side flares that slope 33.7% and 46.1%.

AR5

30 months

8.2.b 

The route is inaccessible because the walk leading to the entrance has a cross slope of 3.7% and a slope between 5.6% and 6.5% and has no ramp features.

R5

30 months

8.3

Interior Signage.  The signage provided throughout the facility is mounted above the door or on the door and does not have raised or Braille characters.

D26

30 months

8.4

Alarms.  Although the facility contains an emergency alarm system, the alarm system is inaccessible because visual alarms are not provided in all hallways, corridors or toilet rooms.

AL1

30 months

8.5

Interior Accessible Route: First Floor Hallway.  The fire extinguisher protrudes into the walkway and is not detectable to blind persons using a cane.

AR8

12 months

8.6

Welcome Desk: First Floor

   

8.6.a 

The counter is inaccessible because it is 43 inches high.

C6

30 months

8.6.b 

The counter protrudes into the walkway and is not detectable to blind persons using a cane.

AR8

12 months

8.7

Women’s Toilet Room with Stalls: First Floor

   

8.7.a 

The door is inaccessible because it requires 6 pounds of force to open.

D2

12 months

8.7.b 

No accessible mirror has been provided.

TR14

12 months

8.7.c 

The air dryer protrudes into the walkway and is not detectable to blind persons using a cane.

AR8

12 months

8.7.d 

The designated accessible stall is incorrectly configured as an ambulatory stall, and there is no standard accessible stall provided.

ST1

30 months

8.8

Men’s Toilet Room with Stalls: First Floor

   

8.8.a 

The door is inaccessible because it requires 6 pounds of force to open.

D2

12 months

8.8.b 

The light switch is inaccessible because it is mounted 68 inches high. 

TR5

12 months

8.8.c 

No accessible mirror has been provided.

TR14

12 months

8.8.d 

The air dryer protrudes into the walkway and is not detectable to blind persons using a cane.

AR8

12 months

8.8.e 

The urinals are inaccessible because they are 22 inches high to the rim and 45¾ inches high to the flush control.

TR20

30 months

8.8.f

The designated accessible stall is incorrectly configured as an ambulatory stall, and there is no standard accessible stall provided.

ST1

30 months

8.9

Day Care: First Floor.  The door is inaccessible because it requires 9 pounds of force to open.

D2

12 months

8.10

Boys Toilet Rooms with Stalls: First Floor Day Care

   

8.10.a 

The door is inaccessible because it has an opening width of only 27 inches.

D25

30 months

8.10.b 

The toilet room contains a number of inaccessible elements and is not accessible to people with disabilities.

ST14

30 months

8.11

Girls Toilet Rooms with Stalls: First Floor Day Care

   

8.11.a 

The door is inaccessible because it has an opening width of only 27 inches.

D25

30 months

8.11.b 

The toilet room contains a number of inaccessible elements and is not accessible to people with disabilities.

ST14

30 months

8.12

Library: First Floor

   

8.12.a 

The tables are inaccessible because they are 24½ inches high to the bottom.

L4

24 months

8.12.b 

The check-out area is inaccessible because the counter is 39 inches high.

L2

30 months

8.12.c 

The book stacks are inaccessible because the space between stacks is only 32 inches wide.

L5

24 months

8.13

Elevators

   

8.13.a 

The elevator is inaccessible because the hall call buttons do not have visual signals indicating when calls are registered or answered.

E3

30 months

8.13.b 

The elevator is inaccessible because the emergency communications are not identified by raised or Braille symbols, and the system does not work without voice communication.

E8

30 months

8.14

Women’s Toilet Room with Stalls: Second Floor

   

8.14.a 

The door is inaccessible because it requires 7 pounds of force to open.

D2

12 months

8.14.b 

The light switch is inaccessible because it is mounted 70½ inches high.

TR5

12 months

8.14.c 

No accessible mirror has been provided.

TR14

12 months

8.14.d 

The paper towel dispenser is inaccessible because it is mounted with the controls 59 inches high.

TR5

12 months

8.14.e 

The designated accessible stall is incorrectly configured as an ambulatory stall, and there is no standard accessible stall provided.

ST15

30 months

8.15

Men’s Toilet Room with Stalls: Second Floor

   

8.15.a 

The door is inaccessible because it requires 10 pounds of force to open.

D2

12 months

8.15.b 

The light switch is inaccessible because it is mounted 69½ inches high.

TR5

12 months

8.15.c 

No accessible mirror has been provided.

TR14

12 months

8.15.d 

The urinals are inaccessible because the rims are 22 inches high and the flush controls are 45 inches high.

TR20

30 months

8.15.e 

The designated accessible stall is incorrectly configured as an ambulatory stall, and there is no standard accessible stall provided.

ST15

12 months

8.16

Women’s Toilet Room with Stalls: Third Floor

   

8.16.a 

The door is inaccessible because it requires 13 pounds of force to open.

D2

12 months

8.16.b 

The light switch is inaccessible because it is mounted 74 inches high.

TR5

12 months

8.16.c 

No accessible mirror has been provided.

TR14

12 months

8.16.d 

The paper towel dispenser is inaccessible because it is mounted with the controls 59 inches high.

TR5

12 months

8.16.e 

The designated accessible stall is incorrectly configured as an ambulatory stall, and there is no standard accessible stall provided.

ST15

30 months

8.17

Men’s Toilet Room with Stalls: Third Floor

   

8.17.a 

The door is inaccessible because it requires 14 pounds of force to open.

D2

12 months

8.17.b 

The light switch is inaccessible because it is mounted 69½ inches high.

TR5

12 months

8.18

No accessible mirror has been provided.

TR14

12 months

8.18.a 

The urinals are inaccessible because the rims are 24 inches high and the flush controls are 45½ inches high.

TR20

30 months

8.18.b 

The designated accessible stall is incorrectly configured as an ambulatory stall, and there is no standard accessible stall provided.

ST15

30 months

9 

M. L. K. NATATORIUM, located at 70 Boulevard Street, NE

   

9.1

Entrances.  The building does not have directional signage posted at inaccessible entrances and does not have the International Symbol of Accessibility posted at accessible entrances.

D16

24 months

9.2

Accessible Route:  To Pool Bleachers.  The route to the bleachers at the pool is inaccessible because it contains a 1 inch high step

AR2

24 months

9.3

Elevators

   

9.3.a 

The elevator is inaccessible because the hall call buttons are centered 41 inches high.

E3

30 months

9.3.b 

The elevator is inaccessible because hoistway signage is not provided on both door jambs.

E12

30 months

9.3.c 

The elevator is inaccessible because the doors do not reopen automatically when obstructed.

E6

30 months

9.4

Women’s Locker Room

   

9.4.a 

The door is inaccessible because it requires 13 pounds of force to open.

D2

12 months

9.4.b 

The air dryers protrude into the walkway and are not detectable to blind persons using a cane.

AR8

12 months

9.4.c 

The designated accessible toilet is inaccessible because the top of the seat is 20 inches high.

ST20

30 months

9.4.d 

The designated accessible toilet is inaccessible because the centerline is 22¼ inches from the side wall.

ST17

30 months

9.4.e 

The designated accessible toilet is inaccessible because the flush control is on the closed side.

ST2

30 months

9.4.f

No accessible coat hook has been provided.

TR1

12 months

9.4.g 

The designated accessible toilet is inaccessible because there are no grab bars.

ST11

12 months

9.4.h 

There is no accessible shower provided.

B8

30 months

9.4.i

No accessible towel hook has been provided.

TR1

12 months

9.5

Men’s Locker Room

   

9.5.a 

The door is inaccessible because it requires 12 pounds of force to open.

D2

12 months

9.5.b 

The air dryers protrude into the walkway and are not detectable to blind persons using a cane.

AR8

12 months

9.5.c 

The urinals are inaccessible because they are mounted with the rims 19 inches high and the flush controls 46 inches high.

TR20

30 months

9.5.d 

There is no accessible toilet stall provided.

ST15

30 months

9.5.e 

There is no accessible shower provided.

B8

30 months

9.5.f

No accessible towel hook has been provided.

TR1

12 months

9.6

Drinking Fountain: Lower Level.  Although a designated accessible drinking fountain is provided, there is no drinking fountain provided for people who have difficulty bending or stooping.

DF3

30 months

9.7

Exterior Accessible Route: Public Access to Future Entrance.  Although the route slopes 6.3% and must therefore be constructed as a ramp, there are handrails on only one side and there is a cross slope of 9.9%.

R3

30 months

10 

BASS RECREATION CENTER, located at 326 Moreland Avenue, NE

   

10.1

Parking Lot: Upper Level

   

10.1.a 

The parking lot is inaccessible because there are no access aisles provided.

P1

24 months

10.1.b 

The parking lot is inaccessible because there is no van accessible space provided.

P3

24 months

10.2

Ramp: Main Entrance.  The ramp is inaccessible because the lower section slopes 9.2%, the handrails lack extensions, the handrail ends are not rounded or returned, and the handrails do not have a diameter of 1¼ to 1½ inches.

R5

30 months

10.3

Main Entrance.  The building does not have directional signage posted at inaccessible entrances and does not have the International Symbol of Accessibility posted at accessible entrances.

D16

12 months

10.4

Multi-Purpose Room.  No accessible coat hook has been provided.

TR1

12 months

10.5

Drinking Fountain: Main Floor

   

10.5.a 

Although a designated accessible drinking fountain is provided, there is no drinking fountain provided for people who have difficulty bending or stooping.

DF3

30 months

10.5.b 

The drinking fountain protrudes into the walkway and is not detectable to blind persons using a cane.

AR8

12 months

10.6

Women’s Toilet Room with Stalls: Main Floor

   

10.6.a 

The door is inaccessible because it requires 9 pounds of force to open.

D2

12 months

10.6.b 

Although an audible alarm is provided in this facility, there is no visual alarm appliance in the toilet room. 

TR21

30 months

10.6.c 

No accessible mirror has been provided.

TR14

12 months

10.6.d 

The designated accessible toilet is inaccessible because there is insufficient clear floor space.

ST18

30 months

10.6.e 

The designated accessible toilet is inaccessible because the centerline is 19 inches from the side wall.

ST17

30 months

10.6.f

No accessible coat hook has been provided.

TR1

12 months

10.6.g 

The designated accessible toilet is inaccessible because the side grab bar is obstructed by the toilet paper dispenser.

ST8

12 months

10.6.h 

There is no rear grab bar provided at the designated accessible toilet.

ST3

30 months

10.7

Men’s Toilet Room with Stalls: Main Floor

   

10.7.a 

The door is inaccessible because it requires 10 pounds of force to open.

D2

12 months

10.7.b 

Although an audible alarm is provided in this facility, there is no visual alarm appliance in the toilet room. 

TR21

30 months

10.7.c 

No accessible mirror has been provided.

TR14

12 months

10.7.d 

The urinal is inaccessible because the rim is 18 inches high.

TR20

30 months

10.7.e 

The designated accessible stall is incorrectly configured as an ambulatory stall, and there is no standard accessible stall provided.

ST15

30 months

11 

CHASTAIN PARK AMPHITHEATER, located at 4469 Stella Drive, NW

   

11.1

Parking Lot

   

11.1.a 

There is no van accessible parking space provided.

P3

24 months

11.1.b 

The parking is inaccessible because the spaces reserved for persons with disabilities are 88 inches wide, and the access aisles are 56 inches wide.

P8

24 months

11.1.c 

The curb ramp from parking to the entrance is inaccessible because it slopes 12% and has a cross slope of 6.1%

AR5

30months

11.2

Concession Counter: Near Seating.  The counter protrudes into the walkway and is not detectable to blind persons using a cane.

AR8

12 months

11.3

Starbucks and Whole Foods Counter

   

11.3.a 

The route to the Starbucks and Whole Foods counter is inaccessible because it  contains many steps.

AR1

30 months

11.3.b 

The retail counter is inaccessible because it is 44 inches high.

C5

30 months

11.4

Winery Area and Sun Room Bar.  The routes to the Winery area and Sun Room bar are inaccessible because they  contain steps and gravel.

AR1

30 months

11.5

Drinking Fountains: Near Toilet Rooms.  The higher drinking fountain protrudes into the walkway and is not detectable to blind persons using a cane.

AR8

12 months

11.6

Men’s Toilet Room with Stalls: Near Entrance

   

11.6.a 

The room is inaccessible because the sign is not mounted in an accessible location and does not have raised or Braille characters.

TR17

24 months

11.6.b 

The toilet room contains a number of inaccessible elements and is currently being renovated.

ST14

30 months

11.7

Women’s Toilet Room with Stalls: Near Entrance

   

11.7.a 

The room is inaccessible because the sign is not mounted in an accessible location and does not have raised or Braille characters.

TR17

24 months

11.7.b 

The paper towel dispensers are inaccessible because they are mounted with the controls 60½ inches high.

TR5

12 months

11.7.c 

No accessible coat hook has been provided in the pink designated accessible stall.

TR1

12 months

11.7.d 

The side grab bar in the pink designated accessible stall is obstructed by the toilet paper dispenser.

ST8

12 months

11.7.e 

The toilet centerline in the grey designated accessible stall is 17 inches from the side wall.

ST17

30 months

11.7.f

The side grab bar in the grey designated accessible stall is 38 inches high.

ST12

12 months

11.7.g 

Although there are 26 stalls, there is no ambulatory stall provided.

ST1

30 months

11.8

Amphitheater

   

11.8.a 

The amphitheater, containing 6839 seats, is inaccessible because it does not have sufficient accessible seats and does not have fixed companion seats next to each wheelchair location.  A total of 69 wheelchair seating areas is required.

AA6

30 months

11.8.b 

The amphitheater is inaccessible to people with hearing disabilities because, although there are more than 50 fixed seats, there is no assistive listening system provided.  This amphitheater requires 274 receivers.

AA4

30 months

11.8.c 

The amphitheater is inaccessible because there is no accessible route connecting the wheelchair seating areas and the stage.

AA1

30 months

11.8.d 

The newly constructed concession stand has no accessible features.

C5

12 months

12 

PITTMAN POOL/RECREATION CENTER, located at 4950 Garibaldi Street, SE

   

12.1

Parking Lot.  The parking lot, with a total of 29 parking spaces, is inaccessible because it only has 1 space designated as accessible.  This lot requires 1 van accessible space and 1 standard accessible space.

P3

30 months

12.2

Main Entrance

   

12.2.a 

The curb ramp at the main entrance drop off area is inaccessible because it has a slope of 14.1% and a cross slope of 7.9%.

AR5

30 months

12.2.b 

The entrance is inaccessible because the threshold is 2¼ inches high.

D22

24 months

12.3

Arts and Crafts.  The door is inaccessible because it requires 7 pounds of force to open.

D2

12 months

12.4

Drinking Fountain: Multi-Purpose Room.  Although an accessible drinking fountain is provided, there is no drinking fountain provided for people who have difficulty bending or stooping.

DF3

30 months

12.5

Women’s Toilet Room with Stalls: Upper Level

   

12.5.a 

The door is inaccessible because it requires 8 pounds of force to open.

D2

12 months

12.5.b 

The lavatory is inaccessible because the hot water pipes are not insulated or otherwise configured to protect against contact.

TR12

24 months

12.5.c 

The air dryer protrudes into the walkway and is not detectable to blind persons using a cane.

AR8

12 months

12.6

Men’s Toilet Room with Stalls: Upper Level

   

12.6.a 

The door is inaccessible because it requires 14 pounds of force to open.

D2

12 months

12.6.b 

The lavatory is inaccessible because the hot water pipes are not insulated or otherwise configured to protect against contact.

TR12

24 months

12.6.c 

The air dryer protrudes into the walkway and is not detectable to blind persons using a cane.

AR8

12 months

12.7

Elevator

   

12.7.a 

The elevator is inaccessible because the hall call buttons are mounted 39 inches high.

E3

30 months

12.7.b 

The elevator is inaccessible because the emergency system requires voice communication.

E8

30 months

12.8

Ramp: Lower Level From Exit to Pool Deck.  The ramp is inaccessible because the lower portion slopes 10%, the upper portion slopes 13.8%, there is a handrail on only one side, the handrail is 29 inches high, it lacks extensions, and it does have ends that are rounded or returned.

R5

30 months

12.9

Gymnasium.  The gymnasium is inaccessible because the threshold at the door is 2½ inches high.

D22

24 months

12.10

Men’s Locker Room: Lower Level

   

12.10.a 

The door is inaccessible because it requires 8 pounds of force to open.

D2

12 months

12.10.b 

The designated accessible stall is incorrectly configured as an ambulatory stall, and there is no standard accessible stall provided.

ST15

30 months

12.10.c 

The air dryer protrudes into the walkway and is not detectable to blind persons using a cane.

AR8

12 months

12.10.d 

The shower is inaccessible because it is incorrect dimensions, there are grab bars on only 2 walls, and the shower spray unit is fixed at more than 48 inches high.

B8

30 months

12.10.e 

The benches are inaccessible because they are too narrow and are not attached at the wall.

LR1

30 months

12.11

Women’s Locker Room: Lower Level

   

12.11.a 

The door is inaccessible because it requires 10 pounds of force to open.

D2

12 months

12.11.b 

The designated accessible stall is incorrectly configured as an ambulatory stall, and there is no standard accessible stall provided.

ST15

30 months

12.11.c 

The air dryer protrudes into the walkway and is not detectable to blind persons using a cane.

AR8

12 months

12.11.d 

The shower is inaccessible because it is 48 inches deep and 47 inches wide, there are grab bars on only 2 walls, and the shower spray unit cannot be fixed.

B8

30 months

12.11.e 

The benches are inaccessible because they are too narrow and are not attached at the wall.

LR1

30 months

13 

PEACHTREE HILLS RECREATION CENTER, located at 308 Peachtree Hills Road, NE

   

13.1

Route: Parking Lot to Main Entrance

   

13.1.a 

The route is inaccessible because the curb ramp has a slope of 9.3% and a cross slope of 4.7%.

AR5

30 months

13.1.b 

The route is inaccessible because the walk to the entrance slopes 7.8%, with a cross slope of 4.8%, and it has no ramp features

R3

30 months

13.2

Entrances.  The building does not have directional signage posted at inaccessible entrances and does not have the International Symbol of Accessibility posted at accessible entrances.

D16

24 months

13.3

Men’s Toilet Room with Stalls: First Floor

   

13.3.a 

The room is inaccessible because the sign is mounted on the hinge side of the door.

TR18

12 months

13.3.b 

The door is inaccessible because it requires 12 pounds of force to open.

D2

12 months

13.3.c 

The air dryer protrudes into the walkway and is not detectable to blind persons using a cane.

AR8

12 months

13.3.d 

The lavatory is inaccessible because the hot water pipes are not insulated or otherwise configured to protect against contact.

TR12

24 months

13.3.e 

The lavatory is inaccessible because it has twist hardware.

TR10

24 months

13.3.f

The urinal is inaccessible because the rim is 18 inches high.

TR20

30 months

13.3.g 

The designated accessible toilet is inaccessible because the flush control is on the closed side.

ST2

30 months

13.3.h 

The toilet paper dispenser is inaccessible because it is mounted 42 inches from the rear wall.

ST19

12 months

13.4

Women’s Toilet Room with Stalls: First Floor

   

13.4.a 

The door is inaccessible because it requires 11 pounds of force to open.

D2

12 months

13.4.b 

The air dryer protrudes into the walkway and is not detectable to blind persons using a cane.

AR8

12 months

13.4.c 

The soap dispenser is inaccessible because it is mounted with the controls 55 inches high

TR5

12 months

13.4.d 

The lavatory is inaccessible because the hot water pipes are not insulated or otherwise configured to protect against contact.

TR12

24 months

13.4.e 

The toilet paper dispenser is inaccessible because it is mounted 44 inches from the rear wall.

ST19

12 months

13.5

Main Lobby.  The underside of the stairs creates an overhead hazard for people with vision disabilities.

AR7

30 months

14 

CENTRAL PARK RECREATION CENTER, located at 400 Merritt Avenue, NE

   

14.1

Central Park Recreation Center is currently under renovation.  Ensure that the facility is fully accessible in accordance with the Standards when renovations are complete.  28 C.F.R. § 35.151.

   

 