ATTACHMENT J: Modifications to Altered FacilitiesPlease Note: Paragraph 42 of the Settlement Agreement requires that within three months of the effective date of this Agreement, the City provide signage as necessary to comply with 28 C.F.R. § 35.163(b), after having surveyed all facilities that are the subject of this Agreement for the purpose of identifying those that have multiple entrances not all of which are accessible. In order to ensure that the following spaces and elements in City facilities in which alterations occurred after January 26, 1992, are readily accessible to and usable by persons with disabilities, the City will take the actions referenced by the alphanumeric code and described in detail in Attachment M to this Settlement Agreement. Actions are to be completed before the end of the time specified in the Completion Date column. |
|||
Item # |
Access Issue |
Required Action |
Completion Date |
---|---|---|---|
1 |
ATLANTA WORKFORCE DEVELOPMENT AGENCY, located at 818 Pollard Boulevard |
||
1.1 |
Parking. The parking lot is inaccessible because the designated standard accessible spaces are between 89 and 92 inches wide, they have no access aisles, they have no vertical signage, and the van accessible space has no “Van Accessible” sign. |
P3 |
30 months |
1.2 |
Exterior Accessible Route. The curb ramp from the parking lot to the entrance is inaccessible because it has a slope of 16%. |
AR5 |
30 months |
1.3 |
Interior Signage. Much of the permanent room signage inside the facility is mounted above the doors and does not have Braille or raised lettering. |
D26 |
30 months |
1.4 |
Drinking Fountains: Main Entrance. Although accessible drinking fountains are provided, there is no drinking fountain provided for people who have difficulty bending or stooping. |
DF3 |
24 months |
1.5 |
Men’s Toilet Room With Stalls First Floor: Near Main Entrance |
||
1.5.a |
The room is inaccessible because the toilet room sign is mounted on the door and has no raised letters and no International Symbol of Accessibility. |
TR17 |
24 months |
1.5.b |
No accessible mirror has been provided. |
TR14 |
12 months |
1.5.c |
The paper towel dispenser protrudes into the walkway and is not detectable to blind persons using a cane. |
AR8 |
12 months |
1.5.d |
The urinal is inaccessible because the rims are 23 inches high. |
TR20 |
30 months |
1.5.e |
The designated accessible toilet is inaccessible because the centerline is 16½ inches from the side wall. |
ST17 |
30 months |
1.5.f |
No accessible coat hook has been provided in the wide stall. |
TR1 |
12 months |
1.5.g |
The designated accessible toilet is inaccessible because the side grab bar is obstructed by the toilet paper dispenser and is mounted 37 inches high. |
ST8 ST12 |
12 months |
1.6 |
Women’s Toilet Room With Stalls: First Floor Near Main Entrance |
||
1.6.a |
The room is inaccessible because the room sign is mounted on the door and has no raised letters and no International Symbol of Accessibility. |
TR17 |
24 months |
1.6.b |
The seat cover dispenser is inaccessible because it is mounted 62 inches high. |
TR5 |
12 months |
1.6.c |
The soap dispenser is inaccessible because it is mounted with the controls 55 inches high. |
TR5 |
12 months |
1.6.d |
The designated accessible toilet is inaccessible because the centerline is 16 inches from the side wall. |
ST17 |
30 months |
1.6.e |
The designated accessible toilet is inaccessible because the flush control is on the closed side. |
ST2 |
30 months |
1.6.f |
No accessible coat hook has been provided in the wide stall. |
TR1 |
12 months |
1.6.g |
The designated accessible toilet is inaccessible because the side grab bar is obstructed by the toilet paper dispenser. |
ST8 |
12 months |
1.6.h |
Although there are 7 toilet stalls, there is no ambulatory stall provided. |
ST1 |
30 months |
1.7 |
Literacy Services. The counter is more than 36 inches high. |
C6 |
30 months |
1.8 |
Sullivan Hall Auditorium |
||
1.8.a |
The auditorium is inaccessible to people with hearing disabilities because, although there are 500 fixed seats, there is no permanently installed assistive listening system provided. This auditorium requires 20 receivers. |
AA4 |
30 months |
1.8.b |
The seating is inaccessible because there is no fixed companion seating adjacent to wheelchair seating locations. |
AA6 |
30 months |
1.9 |
Elevators |
||
1.9.a |
The elevator is inaccessible because it has no audible hall arrival signal. |
E11 |
30 months |
1.9.b |
The elevator is inaccessible because there is hoistway signage on only one side, and it has no Braille. |
E12 |
30 months |
1.9.c |
The elevator is inaccessible because the clearance between the car platform sill and the edge of the hoistway landing is 1½ inches. |
E10 |
30 months |
1.9.d |
The elevator is inaccessible because the car control buttons have no Braille or raised characters, and the main entry floor is not designated by a raised star. |
E4 |
30 months |
1.9.e |
The elevator is inaccessible because the emergency communications are not identified by raised lettering, and the door requires pinching to open. |
E8 |
30 months |
1.10 |
Conference Room 240. There is no assistive listening system available. This room requires 2 receivers. |
AA5 |
30 months |
1.11 |
Platform Lift: Near Taxicab Services. The lift cannot be operated without the user first obtaining a key. |
LF1 |
24 months |
1.12 |
Taxi Bureau. The room is inaccessible because the double doors are each 27 inches wide, require 7 pounds of force to open, and have thumb latch hardware. |
D4 |
30 months |
1.13 |
Men’s Toilet Room: Near Classrooms |
||
1.13.a |
The room is inaccessible because the room sign is painted on the door and has no Braille or raised lettering. |
TR18 |
24 months |
1.13.b |
There is no signage directing people with disabilities to the accessible toilet rooms. |
TR16 |
24 months |
1.14 |
Drinking Fountain: Near Classrooms. The drinking fountain is inaccessible because it has a spout 41 inches high and the water trajectory is 1 inch high. |
DF1 |
24 months |
1.15 |
Administrative Office: Room 217. The door is inaccessible because it requires 8 pounds of force to open. |
D2 |
24 months |
1.16 |
Interior Accessible Route: Second Floor Near Administrative Office. The fire extinguisher and the hanging plants in the hallway protrude into the walkway and are not detectable to blind persons using a cane. |
AR8 |
12 months |
1.17 |
Men’s Toilet Room: Second Floor Near Elevators |
||
1.17.a |
The room is inaccessible because the room sign is mounted on the door and has no raised letters and no International Symbol of Accessibility. |
TR17 |
24 months |
1.17.b |
The paper towel dispenser protrudes into the walkway and is not detectable to blind persons using a cane. |
AR8 |
12 months |
1.17.c |
The urinals are inaccessible because the rims are 23 inches high. |
TR20 |
30 months |
1.17.d |
No accessible coat hook has been provided. |
TR1 |
12 months |
1.17.e |
The designated accessible toilet is inaccessible because the side grab bar is obstructed by the toilet paper dispenser. |
ST8 |
12 months |
1.17.f |
The designated accessible toilet is inaccessible because the grab bars are mounted 1¾ inches from the wall. |
ST13 |
12 months |
1.18 |
Women’s Toilet Room: Second Floor Near Elevators |
||
1.18.a |
The room is inaccessible because the room sign is mounted on the door and has no raised letters and no International Symbol of Accessibility. |
TR17 |
24 months |
1.18.b |
The soap dispenser is inaccessible because it is mounted with the controls 55 inches high behind the lavatory. |
TR4 |
12 months |
1.18.c |
The designated accessible toilet is inaccessible because the centerline is 18½ inches from the side wall. |
ST17 |
30 months |
1.18.d |
The designated accessible toilet is inaccessible because the flush control is on the closed side. |
ST2 |
30 months |
1.18.e |
No accessible coat hook has been provided. |
TR1 |
12 months |
1.18.f |
The designated accessible toilet is inaccessible because the side grab bar is obstructed by the toilet paper dispenser. |
ST8 |
12 months |
1.18.g |
The designated accessible toilet is inaccessible because the grab bars are mounted 36½ inches high. |
ST12 |
12 months |
1.18.h |
The designated accessible toilet is inaccessible because the grab bars are mounted 1¾ inches from the wall. |
ST13 |
12 months |
1.18.i |
Although there are 7 stalls, there is no ambulatory stall provided. |
ST1 |
30 months |
1.19 |
Men’s Toilet Room: Third Floor Near Elevators |
||
1.19.a |
The room is inaccessible because the room sign has no raised or Braille characters and no International Symbol of Accessibility. |
TR17 |
24 months |
1.19.b |
The door is inaccessible because it requires more than 5 pounds to open. |
D2 |
12 months |
1.19.c |
No accessible mirror has been provided. |
TR14 |
12 months |
1.19.d |
The soap dispenser is inaccessible because it is mounted with the controls 48 inches behind the lavatory. |
TR4 |
12 months |
1.19.e |
The towel dispenser protrudes into the walkway and is not detectable to blind persons using a cane. |
AR8 |
12 months |
1.19.f |
The urinals are inaccessible because the rims are 23 inches high. |
TR20 |
30 months |
1.19.g |
No accessible coat hook has been provided. |
TR1 |
12 months |
1.19.h |
There are no grab bars provided at the toilet. |
ST11 |
30 months |
1.20 |
Women’s Toilet Room: Third Floor Near Elevators |
||
1.20.a |
The room is inaccessible because the room sign has no raised or Braille characters and no International Symbol of Accessibility. |
TR17 |
24 months |
1.20.b |
The door is inaccessible because it requires more than 5 pounds to open. |
D2 |
12 months |
1.20.c |
The soap dispenser is inaccessible because it is mounted with the controls 49 inches behind the lavatory. |
TR4 |
12 months |
1.20.d |
The towel dispenser protrudes into the walkway and is not detectable to blind persons using a cane. |
AR8 |
12 months |
1.20.e |
The designated accessible toilet is inaccessible because the flush control is on the closed side. |
ST2 |
30 months |
1.20.f |
The designated accessible toilet is inaccessible because the side grab bar is obstructed by the toilet paper dispenser. |
ST8 |
12 months |
1.20.g |
The designated accessible toilet is inaccessible because the grab bars are mounted 1¾ inches from the wall. |
ST13 |
12 months |
1.20.h |
The designated accessible toilet is inaccessible because the grab bars are mounted 37 inches high. |
ST12 |
12 months |
1.20.i |
Although there are 7 stalls, there is no ambulatory stall provided. |
ST1 |
30 months |
1.21 |
Georgia Center for Children: Third Floor Single User Toilet Room |
||
1.21.a |
The lavatory is inaccessible because the rim or counter is 27½ inches high to the bottom. |
TR11 |
30 months |
1.21.b |
The toilet is inaccessible because the far end of the side grab bar is 45 inches from the rear wall, the rear grab bar is 24 inches long, and both grab bars are mounted 1¾ inches from the wall. |
SU5 |
24 months |
2 |
COAN PARK RECREATION CENTER, located at 1530 Woodbine Ave, SE |
||
2.1 |
Parking: Near Playground. The parking lot, with a total of 28 parking spaces, is inaccessible because none of the spaces is accessible. This lot requires 1 van accessible space. |
P3 |
30 months |
2.2 |
Exterior Accessible Route: Parking Lot To Recreation Center. The route to the entrance is inaccessible because the curb ramp from the parking area has a slope of 10.8%, a cross-slope of 3.3% and very steep side flares. |
AR5 |
30 months |
2.3 |
Gymnasium. The gymnasium is inaccessible because the entry doors have a 1½ inch high threshold. |
D22 |
24 months |
2.4 |
Drinking Fountain: Near Toilet Rooms. The drinking fountain is inaccessible because the spout is 37 inches above the finished floor. |
DF6 |
24 months |
2.5 |
Toilet Rooms with Stalls. The men’s and women’s toilet rooms contain a number of inaccessible elements and are not accessible to people with disabilities. |
ST14 |
30 months |
2.6 |
Computer Room |
||
2.6.a |
The door is inaccessible because it has an opening width of only 29½ inches. |
D25 |
30 months |
2.6.b |
The computers are inaccessible because the keyboards are on tables 26½ inches high. |
C3 |
30 months |
2.7 |
Parking: Pavilion. The parking is inaccessible because the signage designating parking as reserved for persons with disabilities is too low. |
P6 |
12 months |
2.8 |
Accessible Exterior Route: Parking Lot to Pavilion |
||
2.8.a |
The route to the pavilion is inaccessible because the curb ramp from the parking area has a slope of 13.7%. |
AR5 |
30 months |
2.8.b |
The route to the pavilion is inaccessible because the ramp does not have adequate edge protection on the bottom portion, and the handrails are mounted 3½ inches from the wall. |
R5 |
30 months |
3 |
POLICE OFFICE OF PROFESSIONAL STANDARDS, located at 950 Lowery Boulevard |
||
3.1 |
Parking. The parking is inaccessible because the space marked as van accessible has a 60 inch wide access aisle. |
P3 |
24 months |
3.2 |
Exterior Accessible Route: Parking to Entrance. The route is inaccessible because the ramp has a slope of 9.3%, there is no handrail extension at the top on one side, and the handrail is mounted 5½ inches from the wall. |
R5 |
30 months |
3.3 |
Entrance. The entrance is inaccessible because it requires 10 pounds of force to open. |
D2 |
12 months |
3.4 |
Women’s Toilet Room Single-User: Lobby Area |
||
3.4.a |
The room is inaccessible because the room sign is mounted 56 inches high and has no Braille. |
TR18 |
24 months |
3.4.b |
The door is inaccessible because it requires 7 pounds of force to open. |
D2 |
12 months |
3.4.c |
The room is inaccessible because the door has a ½ inch high unbeveled threshold. |
D22 |
24 months |
3.4.d |
No accessible mirror has been provided. |
TR14 |
12 months |
3.4.e |
The toilet is inaccessible because the side grab bar is mounted with its far end 48 inches from the rear wall. |
SU6 |
12 months |
3.4.f |
The toilet is inaccessible because the rear grab bar is only 30 inches long and is obstructed by the seat cover dispenser. |
SU2 |
24 months |
3.5 |
Men’s Toilet Room Single-User: Lobby Area |
||
3.5.a |
The room is inaccessible because the room sign is mounted 56 inches high and has no Braille. |
TR18 |
24 months |
3.5.b |
The room is inaccessible because the door has a ½ inch high unbeveled threshold. |
D22 |
24 months |
3.5.c |
The toilet is inaccessible because the side grab bar is mounted with its far end 48 inches from the rear wall. |
SU6 |
12 months |
3.6 |
Interview Room #2. The pull side of the door, which is accessed from the hinge side of the door, has inadequate maneuvering space |
D8 |
30 months |
3.7 |
Men’s Single-User Toilet Room: Office Area |
||
3.7.a |
The room is inaccessible because the room sign is mounted 56 inches high and has no Braille. |
TR18 |
24 months |
3.7.b |
The room is inaccessible because the door has an unbeveled threshold greater than ¼ inch. |
D22 |
24 months |
3.7.c |
No accessible mirror has been provided. |
TR14 |
12 months |
3.7.d |
The toilet is inaccessible because the side grab bar is mounted with its far end 48 inches from the rear wall. |
SU6 |
12 months |
3.8 |
Women’s Single-User Toilet Room: Office Area |
||
3.8.a |
The room is inaccessible because the room sign is mounted 56 inches high and has no Braille. |
TR18 |
24 months |
3.8.b |
The room is inaccessible because the door has an unbeveled threshold greater than ¼ inch. |
D22 |
24 months |
3.8.c |
No accessible mirror has been provided. |
TR14 |
12 months |
3.8.d |
The toilet is inaccessible because the centerline is 19 inches from the side wall. |
SU15 |
30 months |
3.8.e |
The toilet is inaccessible because the flush control is on the closed side. |
SU1 |
30 months |
3.8.f |
The toilet is inaccessible because the side grab bar is mounted with its far end 48 inches from the rear wall. |
SU6 |
12 months |
4 |
ANDERSON PARK RECREATION CENTER, located at 120 Anderson Ave, NW |
||
4.1 |
Parking |
||
4.1.a |
Although the parking lot has a total of 29 parking spaces, there is no van accessible space provided, and neither designated accessible space has vertical signage. |
P3 |
30 months |
4.1.b |
The built-up curb ramp impermissibly extends into the required accessible parking space’s access aisle. |
AR4 |
30 months |
4.2 |
Main Entrance. The entrance is inaccessible because the door has hardware that requires tight pinching to open. |
D1 |
24 months |
4.3 |
Drinking Fountain: Lobby |
||
4.3.a |
The drinking fountain protrudes into the walkway and is not detectable to blind persons using a cane. |
AR8 |
12 months |
4.3.b |
Although a designated accessible drinking fountain is provided, there is no drinking fountain provided for people who have difficulty bending or stooping. |
DF3 |
30 months |
4.4 |
Men’s Toilet Room with Stalls: Lobby |
||
4.4.a |
The room is inaccessible because the room sign is mounted on the hinge side of the door. |
TR18 |
12 months |
4.4.b |
No accessible mirror has been provided. |
TR14 |
12 months |
4.4.c |
The soap dispenser is inaccessible because it is mounted with the controls 55 inches high over the lavatories. |
TR4 |
12 months |
4.4.d |
The urinals are inaccessible because they are mounted with their rims 24 inches high and their flush controls 50 inches high. |
TR20 |
30 months |
4.4.e |
The toilet is inaccessible because the stall is 42 inches wide. |
ST16 |
30 months |
4.4.f |
The toilet is inaccessible because the centerline is 20½ inches from one side wall and 21½ inches from the other. |
ST17 |
30 months |
4.4.g |
No accessible coat hook has been provided. |
TR1 |
12 months |
4.5 |
Women’s Toilet Room with Stalls: Lobby |
||
4.5.a |
No accessible mirror has been provided. |
TR14 |
12 months |
4.5.b |
The air dryer protrudes into the walkway and is not detectable to blind persons using a cane. |
AR8 |
12 months |
4.5.c |
The toilet is inaccessible because the stall is 46 inches wide |
ST16 |
30 months |
4.5.d |
No accessible coat hook has been provided. |
TR1 |
12 months |
4.6 |
Gymnasium Floor. The gymnasium is inaccessible because the route onto the floor of the gymnasium contains stairs. |
AR2 |
30 months |
4.7 |
Locker Rooms. The men’s and women’s locker rooms contain a number of inaccessible elements. |
ST14 LR1 LR2 LR3 B8 |
30 months |
5 |
A. D. WILLIAMS PARK, located at 1154 James P. Brawley Parkway, NW |
||
5.1 |
Parking. Although the parking lot has a total of 19 parking spaces, there is no van accessible space provided, and one of the designated accessible space’s access aisles has a cross slope of 4.7%. |
P3 |
36 months |
5.2 |
Exterior Accessible Route: Parking to Entrance |
||
5.2.a |
The route to the entrance is inaccessible because the curb ramp leading from the parking lot has a slope of 12.2%. |
AR5 |
30 months |
5.2.b |
The ramp to the entrance is inaccessible because it has a cross-slope of 3.9% in one area, it has handrails on only one side, the handrail lacks extensions at the top and bottom and the ends are not rounded or returned. |
R5 |
30 months |
5.3 |
Exterior Accessible Route: To Playground. The route to the playground is inaccessible because it is covered in mulch and is not firm, stable, and slip resistant. |
AR1 |
30 months |
5.4 |
Entrances. The building does not have directional signage posted at inaccessible entrances and does not have the International Symbol of Accessibility posted at accessible entrances. |
D16 |
24 months |
5.5 |
Men’s Toilet Room with Stalls |
||
5.5.a |
The room is inaccessible because the room sign does not have raised or Braille characters. |
TR18 |
24 months |
5.5.b |
The toilet room is inaccessible because the route into the room narrows to 20 inches at the vent unit. |
AR3 |
24 months |
5.5.c |
Although an audible alarm is provided in this facility, there is no visual alarm appliance in the toilet room. |
TR21 |
30 months |
5.5.d |
No accessible mirror has been provided. |
TR14 |
12 months |
5.5.e |
The lavatory is inaccessible because the rim or counter is 28 inches high to the top. |
TR11 |
24 months |
5.5.f |
The lavatory is inaccessible because the hot water pipes are not insulated or otherwise configured to protect against contact. |
TR12 |
24 months |
5.5.g |
The lavatory is inaccessible because it has twist-type hardware. |
TR10 |
24 months |
5.5.h |
The urinal is inaccessible because the rim is 24 inches high. |
TR20 |
30 months |
5.5.i |
The designated accessible toilet is inaccessible because its centerline is 16 inches from the side wall. |
ST17 |
30 months |
5.5.j |
The designated accessible toilet is inaccessible because the flush control is on the closed side. |
ST2 |
30 months |
5.5.k |
The toilet paper dispenser in the designated accessible stall is inaccessible because it is mounted 43 inches from the rear wall. |
ST19 |
12 months |
5.5.l |
The toilet is inaccessible because the side grab bar is 32 inches long, with the near end 23 inches from the rear wall, it is mounted 2 inches from the side wall, and it is obstructed by the cleaning products and toilet paper rolls placed on it. |
ST6 |
24 months |
5.5.m |
The rear grab bar at the designated accessible toilet is inaccessible because it is mounted 4 inches from the rear wall. |
ST13 |
12 months |
5.5.n |
The toilet is inaccessible because the rear grab bar is obstructed by the toilet pipe and by the toilet paper rolls placed on it. |
ST5 |
30 months |
5.6 |
Women’s Toilet Room with Stalls |
||
5.6.a |
The room is inaccessible because the room sign is not mounted on the latch side of the door and does not have raised or Braille characters. |
TR18 |
24 months |
5.6.b |
The toilet room is inaccessible because the route into the room narrows to 18 inches at the vent unit. |
AR3 |
24 months |
5.6.c |
Although an audible alarm is provided in this facility, there is no visual alarm appliance in the toilet room. |
TR21 |
30 months |
5.6.d |
No accessible mirror has been provided. |
TR14 |
12 months |
5.6.e |
The lavatory is inaccessible because the rim or counter is 28 inches high to the top. |
TR11 |
24 months |
5.6.f |
The lavatory is inaccessible because the hot water pipes are not insulated or otherwise configured to protect against contact. |
TR12 |
24 months |
5.6.g |
The lavatory is inaccessible because it has twist-type hardware. |
TR10 |
24 months |
5.6.h |
There is no accessible stall provided. |
ST15 |
30 months |
6 |
GATEWAY HOMELESS SERVICES CENTER, located at 275 Pryor St, SW |
||
6.1 |
Exterior Accessible Route: Bus Stop to Entrance. The route to the entrance is inaccessible because there is no curb ramp to allow access from the street onto the sidewalk. |
AR5 |
30 months |
6.2 |
Men’s Toilet Room with Stalls: First Floor |
||
6.2.a |
The room is inaccessible because the room sign is mounted 55 inches high to the center. |
TR18 |
12 months |
6.2.b |
The toilet paper dispenser is inaccessible because it is mounted 40 inches from the rear wall. |
ST19 |
12 months |
6.3 |
Drinking Fountains. The high drinking fountain protrudes into the walkway and is not detectable to blind persons using a cane. |
AR8 |
12 months |
6.4 |
Men’s Shower: First Floor. The shower is inaccessible because it has grab bars on only 2 walls. |
B8 |
30 months |
6.5 |
Women’s Single-User Toilet Room |
||
6.5.a |
The room is inaccessible because the room sign is mounted 55 inches high to the center. |
TR18 |
12 months |
6.5.b |
No accessible coat hook has been provided. |
TR1 |
12 months |
6.6 |
Intake Counter. The counter is inaccessible because it is 42½ inches high. |
C6 |
30 months |
6.7 |
Men’s Toilet Room with Stalls: First Floor North Wing |
||
6.7.a |
The room is inaccessible because the sign is mounted 56½ inches high to the center. |
TR18 |
12 months |
6.7.b |
The door is inaccessible because it requires 14 pounds of force to open. |
D2 |
12 months |
6.8 |
Women’s Toilet Room with Stalls: First Floor North Wing |
||
6.8.a |
The room is inaccessible because the sign is mounted 56½ inches high to the center. |
TR18 |
12 months |
6.8.b |
The door is inaccessible because it requires 14 pounds of force to open. |
D2 |
12 months |
6.9 |
Drinking Fountains: First Floor North. The lower drinking fountain is inaccessible because it has 26 inches of knee height. |
DF5 |
24 months |
6.10 |
Elevators: First Floor East Bank |
||
6.10.a |
The elevator is inaccessible because the hall lanterns do not signal once for up and twice for down. |
E11 |
30 months |
6.10.b |
The elevator is inaccessible because the hoistway signage is mounted 61½ inches high. |
E12 |
30 months |
6.11 |
Women’s and Children’s Center: First Floor. The counter is inaccessible because it is 42½ inches high. |
C6 |
30 months |
6.12 |
Bedroom #150: First Floor. The door is inaccessible because knob hardware is used. |
D1 |
24 months |
6.13 |
Bedroom #149: First Floor. The door is inaccessible because knob hardware is used. |
D1 |
24 months |
6.14 |
Women’s Shower Room: First Floor |
||
6.14.a |
The room is inaccessible because the sign is mounted 57 inches high to the center. |
TR18 |
12 months |
6.14.b |
No accessible coat hook is provided in the designated accessible toilet stall. |
TR1 |
12 months |
6.14.c |
The shower is inaccessible because it has grab bars on only 2 walls. |
B8 |
30 months |
6.15 |
Men’s Dormitory Reception: Second Floor. The counter is inaccessible because it is 42½ inches high. |
C6 |
30 months |
6.16 |
Unisex Locker Room: Second Floor Men’s Dorm Eastside |
||
6.16.a |
The room is inaccessible because the sign is mounted 57 inches high to the center. |
TR18 |
12 months |
6.16.b |
The lockers are inaccessible because the hardware requires tight grasping to operate. |
LR3 |
30 months |
6.16.c |
The designated accessible toilet is inaccessible because its centerline is 17 inches from the side wall. |
ST17 |
30 months |
6.16.d |
The shower is inaccessible because it has grab bars on only 2 walls. |
B8 |
30 months |
6.17 |
Sleeping Pods. None of the tables provides the required knee space to accommodate a person in a wheelchair. |
PD3 |
30 months |
6.18 |
Unisex Locker Room: Second Floor Men’s Dorm Westside |
||
6.18.a |
The room is inaccessible because the sign is mounted 54 inches high to the center. |
TR18 |
12 months |
6.18.b |
The shower is inaccessible because it has grab bars on only 2 walls. |
B8 |
30 months |
6.19 |
Clinic Room 202A: Second Floor |
||
6.19.a |
The door is inaccessible because it requires 10 pounds of force to open. |
D2 |
12 months |
6.19.b |
There is no signage directing people with disabilities to the accessible toilet rooms. |
TR16 |
24 months |
6.20 |
Unisex Single-User Toilet Room/Shower: Third Floor Men’s Dorm |
||
6.20.a |
The room is inaccessible because the sign is mounted 55 inches high to the center. |
TR18 |
12 months |
6.20.b |
The shower is inaccessible because it has grab bars on only 2 walls. |
B8 |
30 months |
6.21 |
Unisex Single-User Toilet Room/Shower: Fourth Floor Men’s Dorm |
||
6.21.a |
The room is inaccessible because the sign is mounted 57 inches high to the center. |
TR18 |
12 months |
6.21.b |
The toilet paper dispenser is inaccessible because it is mounted 40 inches from the rear wall. |
SU17 |
12 months |
6.21.c |
The shower is inaccessible because it has grab bars on only 2 walls. |
B8 |
30 months |
7 |
ATLANTA FIRE STATION 31, located at 2406 Fairburn Road, SW |
||
7.1 |
Main Entrance. The entrance is inaccessible because it does not have level maneuvering clearance, there is only 8 inches of clearance on the latch side, pull side, the threshold is 1¼ inches high, and there is knob hardware. |
D17 |
30 months |
7.2 |
Accessible Route: Public Entrance through Truck Bay to Toilet Rooms |
||
7.2.a |
The route is inaccessible because it is less than 36 inches wide. |
AR3 |
24 months |
7.2.b |
There is equipment on the truck that protrudes into the walkway and is not detectable to blind persons using a cane. |
AR8 |
12 months |
7.3 |
Unisex Single-User Toilet Room. The toilet room contains a number of inaccessible elements and is not accessible to people with disabilities. |
SU13 |
30 months |
8 |
GEORGIA HILL NEIGHBORHOOD FACILITY, located at 250 Georgia Avenue, SE |
||
8.1 |
Parking Lot. The parking lot, with a total of 89 parking spaces, is inaccessible because it only has 3 spaces designated as accessible, there is no van accessible space, there are no access aisles, and the signs are mounted too low. This lot requires 1 van accessible space and 3 standard accessible spaces. |
P3 |
30 months |
8.2 |
Exterior Accessible Route: Parking to Main Entrance |
||
8.2.a |
The route is inaccessible because the curb ramp from the parking area onto the sidewalk has a slope of 16% and side flares that slope 33.7% and 46.1%. |
AR5 |
30 months |
8.2.b |
The route is inaccessible because the walk leading to the entrance has a cross slope of 3.7% and a slope between 5.6% and 6.5% and has no ramp features. |
R5 |
30 months |
8.3 |
Interior Signage. The signage provided throughout the facility is mounted above the door or on the door and does not have raised or Braille characters. |
D26 |
30 months |
8.4 |
Alarms. Although the facility contains an emergency alarm system, the alarm system is inaccessible because visual alarms are not provided in all hallways, corridors or toilet rooms. |
AL1 |
30 months |
8.5 |
Interior Accessible Route: First Floor Hallway. The fire extinguisher protrudes into the walkway and is not detectable to blind persons using a cane. |
AR8 |
12 months |
8.6 |
Welcome Desk: First Floor |
||
8.6.a |
The counter is inaccessible because it is 43 inches high. |
C6 |
30 months |
8.6.b |
The counter protrudes into the walkway and is not detectable to blind persons using a cane. |
AR8 |
12 months |
8.7 |
Women’s Toilet Room with Stalls: First Floor |
||
8.7.a |
The door is inaccessible because it requires 6 pounds of force to open. |
D2 |
12 months |
8.7.b |
No accessible mirror has been provided. |
TR14 |
12 months |
8.7.c |
The air dryer protrudes into the walkway and is not detectable to blind persons using a cane. |
AR8 |
12 months |
8.7.d |
The designated accessible stall is incorrectly configured as an ambulatory stall, and there is no standard accessible stall provided. |
ST1 |
30 months |
8.8 |
Men’s Toilet Room with Stalls: First Floor |
||
8.8.a |
The door is inaccessible because it requires 6 pounds of force to open. |
D2 |
12 months |
8.8.b |
The light switch is inaccessible because it is mounted 68 inches high. |
TR5 |
12 months |
8.8.c |
No accessible mirror has been provided. |
TR14 |
12 months |
8.8.d |
The air dryer protrudes into the walkway and is not detectable to blind persons using a cane. |
AR8 |
12 months |
8.8.e |
The urinals are inaccessible because they are 22 inches high to the rim and 45¾ inches high to the flush control. |
TR20 |
30 months |
8.8.f |
The designated accessible stall is incorrectly configured as an ambulatory stall, and there is no standard accessible stall provided. |
ST1 |
30 months |
8.9 |
Day Care: First Floor. The door is inaccessible because it requires 9 pounds of force to open. |
D2 |
12 months |
8.10 |
Boys Toilet Rooms with Stalls: First Floor Day Care |
||
8.10.a |
The door is inaccessible because it has an opening width of only 27 inches. |
D25 |
30 months |
8.10.b |
The toilet room contains a number of inaccessible elements and is not accessible to people with disabilities. |
ST14 |
30 months |
8.11 |
Girls Toilet Rooms with Stalls: First Floor Day Care |
||
8.11.a |
The door is inaccessible because it has an opening width of only 27 inches. |
D25 |
30 months |
8.11.b |
The toilet room contains a number of inaccessible elements and is not accessible to people with disabilities. |
ST14 |
30 months |
8.12 |
Library: First Floor |
||
8.12.a |
The tables are inaccessible because they are 24½ inches high to the bottom. |
L4 |
24 months |
8.12.b |
The check-out area is inaccessible because the counter is 39 inches high. |
L2 |
30 months |
8.12.c |
The book stacks are inaccessible because the space between stacks is only 32 inches wide. |
L5 |
24 months |
8.13 |
Elevators |
||
8.13.a |
The elevator is inaccessible because the hall call buttons do not have visual signals indicating when calls are registered or answered. |
E3 |
30 months |
8.13.b |
The elevator is inaccessible because the emergency communications are not identified by raised or Braille symbols, and the system does not work without voice communication. |
E8 |
30 months |
8.14 |
Women’s Toilet Room with Stalls: Second Floor |
||
8.14.a |
The door is inaccessible because it requires 7 pounds of force to open. |
D2 |
12 months |
8.14.b |
The light switch is inaccessible because it is mounted 70½ inches high. |
TR5 |
12 months |
8.14.c |
No accessible mirror has been provided. |
TR14 |
12 months |
8.14.d |
The paper towel dispenser is inaccessible because it is mounted with the controls 59 inches high. |
TR5 |
12 months |
8.14.e |
The designated accessible stall is incorrectly configured as an ambulatory stall, and there is no standard accessible stall provided. |
ST15 |
30 months |
8.15 |
Men’s Toilet Room with Stalls: Second Floor |
||
8.15.a |
The door is inaccessible because it requires 10 pounds of force to open. |
D2 |
12 months |
8.15.b |
The light switch is inaccessible because it is mounted 69½ inches high. |
TR5 |
12 months |
8.15.c |
No accessible mirror has been provided. |
TR14 |
12 months |
8.15.d |
The urinals are inaccessible because the rims are 22 inches high and the flush controls are 45 inches high. |
TR20 |
30 months |
8.15.e |
The designated accessible stall is incorrectly configured as an ambulatory stall, and there is no standard accessible stall provided. |
ST15 |
12 months |
8.16 |
Women’s Toilet Room with Stalls: Third Floor |
||
8.16.a |
The door is inaccessible because it requires 13 pounds of force to open. |
D2 |
12 months |
8.16.b |
The light switch is inaccessible because it is mounted 74 inches high. |
TR5 |
12 months |
8.16.c |
No accessible mirror has been provided. |
TR14 |
12 months |
8.16.d |
The paper towel dispenser is inaccessible because it is mounted with the controls 59 inches high. |
TR5 |
12 months |
8.16.e |
The designated accessible stall is incorrectly configured as an ambulatory stall, and there is no standard accessible stall provided. |
ST15 |
30 months |
8.17 |
Men’s Toilet Room with Stalls: Third Floor |
||
8.17.a |
The door is inaccessible because it requires 14 pounds of force to open. |
D2 |
12 months |
8.17.b |
The light switch is inaccessible because it is mounted 69½ inches high. |
TR5 |
12 months |
8.18 |
No accessible mirror has been provided. |
TR14 |
12 months |
8.18.a |
The urinals are inaccessible because the rims are 24 inches high and the flush controls are 45½ inches high. |
TR20 |
30 months |
8.18.b |
The designated accessible stall is incorrectly configured as an ambulatory stall, and there is no standard accessible stall provided. |
ST15 |
30 months |
9 |
M. L. K. NATATORIUM, located at 70 Boulevard Street, NE |
||
9.1 |
Entrances. The building does not have directional signage posted at inaccessible entrances and does not have the International Symbol of Accessibility posted at accessible entrances. |
D16 |
24 months |
9.2 |
Accessible Route: To Pool Bleachers. The route to the bleachers at the pool is inaccessible because it contains a 1 inch high step |
AR2 |
24 months |
9.3 |
Elevators |
||
9.3.a |
The elevator is inaccessible because the hall call buttons are centered 41 inches high. |
E3 |
30 months |
9.3.b |
The elevator is inaccessible because hoistway signage is not provided on both door jambs. |
E12 |
30 months |
9.3.c |
The elevator is inaccessible because the doors do not reopen automatically when obstructed. |
E6 |
30 months |
9.4 |
Women’s Locker Room |
||
9.4.a |
The door is inaccessible because it requires 13 pounds of force to open. |
D2 |
12 months |
9.4.b |
The air dryers protrude into the walkway and are not detectable to blind persons using a cane. |
AR8 |
12 months |
9.4.c |
The designated accessible toilet is inaccessible because the top of the seat is 20 inches high. |
ST20 |
30 months |
9.4.d |
The designated accessible toilet is inaccessible because the centerline is 22¼ inches from the side wall. |
ST17 |
30 months |
9.4.e |
The designated accessible toilet is inaccessible because the flush control is on the closed side. |
ST2 |
30 months |
9.4.f |
No accessible coat hook has been provided. |
TR1 |
12 months |
9.4.g |
The designated accessible toilet is inaccessible because there are no grab bars. |
ST11 |
12 months |
9.4.h |
There is no accessible shower provided. |
B8 |
30 months |
9.4.i |
No accessible towel hook has been provided. |
TR1 |
12 months |
9.5 |
Men’s Locker Room |
||
9.5.a |
The door is inaccessible because it requires 12 pounds of force to open. |
D2 |
12 months |
9.5.b |
The air dryers protrude into the walkway and are not detectable to blind persons using a cane. |
AR8 |
12 months |
9.5.c |
The urinals are inaccessible because they are mounted with the rims 19 inches high and the flush controls 46 inches high. |
TR20 |
30 months |
9.5.d |
There is no accessible toilet stall provided. |
ST15 |
30 months |
9.5.e |
There is no accessible shower provided. |
B8 |
30 months |
9.5.f |
No accessible towel hook has been provided. |
TR1 |
12 months |
9.6 |
Drinking Fountain: Lower Level. Although a designated accessible drinking fountain is provided, there is no drinking fountain provided for people who have difficulty bending or stooping. |
DF3 |
30 months |
9.7 |
Exterior Accessible Route: Public Access to Future Entrance. Although the route slopes 6.3% and must therefore be constructed as a ramp, there are handrails on only one side and there is a cross slope of 9.9%. |
R3 |
30 months |
10 |
BASS RECREATION CENTER, located at 326 Moreland Avenue, NE |
||
10.1 |
Parking Lot: Upper Level |
||
10.1.a |
The parking lot is inaccessible because there are no access aisles provided. |
P1 |
24 months |
10.1.b |
The parking lot is inaccessible because there is no van accessible space provided. |
P3 |
24 months |
10.2 |
Ramp: Main Entrance. The ramp is inaccessible because the lower section slopes 9.2%, the handrails lack extensions, the handrail ends are not rounded or returned, and the handrails do not have a diameter of 1¼ to 1½ inches. |
R5 |
30 months |
10.3 |
Main Entrance. The building does not have directional signage posted at inaccessible entrances and does not have the International Symbol of Accessibility posted at accessible entrances. |
D16 |
12 months |
10.4 |
Multi-Purpose Room. No accessible coat hook has been provided. |
TR1 |
12 months |
10.5 |
Drinking Fountain: Main Floor |
||
10.5.a |
Although a designated accessible drinking fountain is provided, there is no drinking fountain provided for people who have difficulty bending or stooping. |
DF3 |
30 months |
10.5.b |
The drinking fountain protrudes into the walkway and is not detectable to blind persons using a cane. |
AR8 |
12 months |
10.6 |
Women’s Toilet Room with Stalls: Main Floor |
||
10.6.a |
The door is inaccessible because it requires 9 pounds of force to open. |
D2 |
12 months |
10.6.b |
Although an audible alarm is provided in this facility, there is no visual alarm appliance in the toilet room. |
TR21 |
30 months |
10.6.c |
No accessible mirror has been provided. |
TR14 |
12 months |
10.6.d |
The designated accessible toilet is inaccessible because there is insufficient clear floor space. |
ST18 |
30 months |
10.6.e |
The designated accessible toilet is inaccessible because the centerline is 19 inches from the side wall. |
ST17 |
30 months |
10.6.f |
No accessible coat hook has been provided. |
TR1 |
12 months |
10.6.g |
The designated accessible toilet is inaccessible because the side grab bar is obstructed by the toilet paper dispenser. |
ST8 |
12 months |
10.6.h |
There is no rear grab bar provided at the designated accessible toilet. |
ST3 |
30 months |
10.7 |
Men’s Toilet Room with Stalls: Main Floor |
||
10.7.a |
The door is inaccessible because it requires 10 pounds of force to open. |
D2 |
12 months |
10.7.b |
Although an audible alarm is provided in this facility, there is no visual alarm appliance in the toilet room. |
TR21 |
30 months |
10.7.c |
No accessible mirror has been provided. |
TR14 |
12 months |
10.7.d |
The urinal is inaccessible because the rim is 18 inches high. |
TR20 |
30 months |
10.7.e |
The designated accessible stall is incorrectly configured as an ambulatory stall, and there is no standard accessible stall provided. |
ST15 |
30 months |
11 |
CHASTAIN PARK AMPHITHEATER, located at 4469 Stella Drive, NW |
||
11.1 |
Parking Lot |
||
11.1.a |
There is no van accessible parking space provided. |
P3 |
24 months |
11.1.b |
The parking is inaccessible because the spaces reserved for persons with disabilities are 88 inches wide, and the access aisles are 56 inches wide. |
P8 |
24 months |
11.1.c |
The curb ramp from parking to the entrance is inaccessible because it slopes 12% and has a cross slope of 6.1% |
AR5 |
30months |
11.2 |
Concession Counter: Near Seating. The counter protrudes into the walkway and is not detectable to blind persons using a cane. |
AR8 |
12 months |
11.3 |
Starbucks and Whole Foods Counter |
||
11.3.a |
The route to the Starbucks and Whole Foods counter is inaccessible because it contains many steps. |
AR1 |
30 months |
11.3.b |
The retail counter is inaccessible because it is 44 inches high. |
C5 |
30 months |
11.4 |
Winery Area and Sun Room Bar. The routes to the Winery area and Sun Room bar are inaccessible because they contain steps and gravel. |
AR1 |
30 months |
11.5 |
Drinking Fountains: Near Toilet Rooms. The higher drinking fountain protrudes into the walkway and is not detectable to blind persons using a cane. |
AR8 |
12 months |
11.6 |
Men’s Toilet Room with Stalls: Near Entrance |
||
11.6.a |
The room is inaccessible because the sign is not mounted in an accessible location and does not have raised or Braille characters. |
TR17 |
24 months |
11.6.b |
The toilet room contains a number of inaccessible elements and is currently being renovated. |
ST14 |
30 months |
11.7 |
Women’s Toilet Room with Stalls: Near Entrance |
||
11.7.a |
The room is inaccessible because the sign is not mounted in an accessible location and does not have raised or Braille characters. |
TR17 |
24 months |
11.7.b |
The paper towel dispensers are inaccessible because they are mounted with the controls 60½ inches high. |
TR5 |
12 months |
11.7.c |
No accessible coat hook has been provided in the pink designated accessible stall. |
TR1 |
12 months |
11.7.d |
The side grab bar in the pink designated accessible stall is obstructed by the toilet paper dispenser. |
ST8 |
12 months |
11.7.e |
The toilet centerline in the grey designated accessible stall is 17 inches from the side wall. |
ST17 |
30 months |
11.7.f |
The side grab bar in the grey designated accessible stall is 38 inches high. |
ST12 |
12 months |
11.7.g |
Although there are 26 stalls, there is no ambulatory stall provided. |
ST1 |
30 months |
11.8 |
Amphitheater |
||
11.8.a |
The amphitheater, containing 6839 seats, is inaccessible because it does not have sufficient accessible seats and does not have fixed companion seats next to each wheelchair location. A total of 69 wheelchair seating areas is required. |
AA6 |
30 months |
11.8.b |
The amphitheater is inaccessible to people with hearing disabilities because, although there are more than 50 fixed seats, there is no assistive listening system provided. This amphitheater requires 274 receivers. |
AA4 |
30 months |
11.8.c |
The amphitheater is inaccessible because there is no accessible route connecting the wheelchair seating areas and the stage. |
AA1 |
30 months |
11.8.d |
The newly constructed concession stand has no accessible features. |
C5 |
12 months |
12 |
PITTMAN POOL/RECREATION CENTER, located at 4950 Garibaldi Street, SE |
||
12.1 |
Parking Lot. The parking lot, with a total of 29 parking spaces, is inaccessible because it only has 1 space designated as accessible. This lot requires 1 van accessible space and 1 standard accessible space. |
P3 |
30 months |
12.2 |
Main Entrance |
||
12.2.a |
The curb ramp at the main entrance drop off area is inaccessible because it has a slope of 14.1% and a cross slope of 7.9%. |
AR5 |
30 months |
12.2.b |
The entrance is inaccessible because the threshold is 2¼ inches high. |
D22 |
24 months |
12.3 |
Arts and Crafts. The door is inaccessible because it requires 7 pounds of force to open. |
D2 |
12 months |
12.4 |
Drinking Fountain: Multi-Purpose Room. Although an accessible drinking fountain is provided, there is no drinking fountain provided for people who have difficulty bending or stooping. |
DF3 |
30 months |
12.5 |
Women’s Toilet Room with Stalls: Upper Level |
||
12.5.a |
The door is inaccessible because it requires 8 pounds of force to open. |
D2 |
12 months |
12.5.b |
The lavatory is inaccessible because the hot water pipes are not insulated or otherwise configured to protect against contact. |
TR12 |
24 months |
12.5.c |
The air dryer protrudes into the walkway and is not detectable to blind persons using a cane. |
AR8 |
12 months |
12.6 |
Men’s Toilet Room with Stalls: Upper Level |
||
12.6.a |
The door is inaccessible because it requires 14 pounds of force to open. |
D2 |
12 months |
12.6.b |
The lavatory is inaccessible because the hot water pipes are not insulated or otherwise configured to protect against contact. |
TR12 |
24 months |
12.6.c |
The air dryer protrudes into the walkway and is not detectable to blind persons using a cane. |
AR8 |
12 months |
12.7 |
Elevator |
||
12.7.a |
The elevator is inaccessible because the hall call buttons are mounted 39 inches high. |
E3 |
30 months |
12.7.b |
The elevator is inaccessible because the emergency system requires voice communication. |
E8 |
30 months |
12.8 |
Ramp: Lower Level From Exit to Pool Deck. The ramp is inaccessible because the lower portion slopes 10%, the upper portion slopes 13.8%, there is a handrail on only one side, the handrail is 29 inches high, it lacks extensions, and it does have ends that are rounded or returned. |
R5 |
30 months |
12.9 |
Gymnasium. The gymnasium is inaccessible because the threshold at the door is 2½ inches high. |
D22 |
24 months |
12.10 |
Men’s Locker Room: Lower Level |
||
12.10.a |
The door is inaccessible because it requires 8 pounds of force to open. |
D2 |
12 months |
12.10.b |
The designated accessible stall is incorrectly configured as an ambulatory stall, and there is no standard accessible stall provided. |
ST15 |
30 months |
12.10.c |
The air dryer protrudes into the walkway and is not detectable to blind persons using a cane. |
AR8 |
12 months |
12.10.d |
The shower is inaccessible because it is incorrect dimensions, there are grab bars on only 2 walls, and the shower spray unit is fixed at more than 48 inches high. |
B8 |
30 months |
12.10.e |
The benches are inaccessible because they are too narrow and are not attached at the wall. |
LR1 |
30 months |
12.11 |
Women’s Locker Room: Lower Level |
||
12.11.a |
The door is inaccessible because it requires 10 pounds of force to open. |
D2 |
12 months |
12.11.b |
The designated accessible stall is incorrectly configured as an ambulatory stall, and there is no standard accessible stall provided. |
ST15 |
30 months |
12.11.c |
The air dryer protrudes into the walkway and is not detectable to blind persons using a cane. |
AR8 |
12 months |
12.11.d |
The shower is inaccessible because it is 48 inches deep and 47 inches wide, there are grab bars on only 2 walls, and the shower spray unit cannot be fixed. |
B8 |
30 months |
12.11.e |
The benches are inaccessible because they are too narrow and are not attached at the wall. |
LR1 |
30 months |
13 |
PEACHTREE HILLS RECREATION CENTER, located at 308 Peachtree Hills Road, NE |
||
13.1 |
Route: Parking Lot to Main Entrance |
||
13.1.a |
The route is inaccessible because the curb ramp has a slope of 9.3% and a cross slope of 4.7%. |
AR5 |
30 months |
13.1.b |
The route is inaccessible because the walk to the entrance slopes 7.8%, with a cross slope of 4.8%, and it has no ramp features |
R3 |
30 months |
13.2 |
Entrances. The building does not have directional signage posted at inaccessible entrances and does not have the International Symbol of Accessibility posted at accessible entrances. |
D16 |
24 months |
13.3 |
Men’s Toilet Room with Stalls: First Floor |
||
13.3.a |
The room is inaccessible because the sign is mounted on the hinge side of the door. |
TR18 |
12 months |
13.3.b |
The door is inaccessible because it requires 12 pounds of force to open. |
D2 |
12 months |
13.3.c |
The air dryer protrudes into the walkway and is not detectable to blind persons using a cane. |
AR8 |
12 months |
13.3.d |
The lavatory is inaccessible because the hot water pipes are not insulated or otherwise configured to protect against contact. |
TR12 |
24 months |
13.3.e |
The lavatory is inaccessible because it has twist hardware. |
TR10 |
24 months |
13.3.f |
The urinal is inaccessible because the rim is 18 inches high. |
TR20 |
30 months |
13.3.g |
The designated accessible toilet is inaccessible because the flush control is on the closed side. |
ST2 |
30 months |
13.3.h |
The toilet paper dispenser is inaccessible because it is mounted 42 inches from the rear wall. |
ST19 |
12 months |
13.4 |
Women’s Toilet Room with Stalls: First Floor |
||
13.4.a |
The door is inaccessible because it requires 11 pounds of force to open. |
D2 |
12 months |
13.4.b |
The air dryer protrudes into the walkway and is not detectable to blind persons using a cane. |
AR8 |
12 months |
13.4.c |
The soap dispenser is inaccessible because it is mounted with the controls 55 inches high |
TR5 |
12 months |
13.4.d |
The lavatory is inaccessible because the hot water pipes are not insulated or otherwise configured to protect against contact. |
TR12 |
24 months |
13.4.e |
The toilet paper dispenser is inaccessible because it is mounted 44 inches from the rear wall. |
ST19 |
12 months |
13.5 |
Main Lobby. The underside of the stairs creates an overhead hazard for people with vision disabilities. |
AR7 |
30 months |
14 |
CENTRAL PARK RECREATION CENTER, located at 400 Merritt Avenue, NE |
||
14.1 |
Central Park Recreation Center is currently under renovation. Ensure that the facility is fully accessible in accordance with the Standards when renovations are complete. 28 C.F.R. § 35.151. |