ATTACHMENT J: Modifications to Altered Facilities  

Please Note: Paragraph 45 of the Settlement Agreement requires that within three months of the effective date of this Agreement, the City will provide signage as necessary to comply with 28 C.F.R. ¤ 35.163(b), after having surveyed all facilities that are the subject of this Agreement for the purpose of identifying those that have multiple entrances not all of which are accessible.

The chart below lists the facilities surveyed by the Department, the access issues identified during the survey, and the actions required to correct the access issues. Required actions are listed using an alphanumeric code. The key to the alphanumeric codes is provided in Attachment M to this Agreement.

In order to ensure that the following spaces and elements in the CityÕs facilities in which alterations occurred after January 26, 1992, are readily accessible to and usable by persons with disabilities, the City will take the actions referenced by the alphanumeric code and described in detail in Attachment M to this Settlement Agreement within the time period specified below, which time period will begin to run on the effective date of this Agreement.

Item # Access Issue Required Action Completion Date
1. Swope Memorial Golf Course, located in Swope Park at 6900 Swope Memorial Drive    
1.1. Parking: The parking lot, with a total of 140 parking spaces, is inaccessible because there are only 3 designated accessible parking spaces, there is no space designated as van accessible, the signs are mounted too low, and the spaces and access aisles have slopes of up to 5%. This lot requires 1 van accessible space and 4 standard accessible spaces. P3 24 months
1.2. Entrance: The pull side of the door, which is accessed through a front approach, is inaccessible because it has only 13 inches of clear space on the latch side due to the placement of the plant pot. D6 24 months
1.3. Club House MenÕs Toilet Room with Stalls    
1.3.a. The toilet room sign is mounted 53 inches high to the center of the sign. TR18 24 months
1.3.b. The door is inaccessible because it requires more than 5 pounds of force to open. D2 24 months
1.3.c. The paper towel dispensers protrude into the walkway and are not detectable to blind persons using a cane. AR8 24 months
1.3.d. The designated accessible toilet is inaccessible because the side grab bar is mounted with the far end 47 inches from the rear wall. ST7 24 months
1.4. Club House WomenÕs Toilet Room with Stalls    
1.4.a. The toilet room sign is mounted 53 inches high to the center of the sign. TR18 24 months
1.4.b. The door is inaccessible because it requires more than 5 pounds of force to open. D2 24 months
1.4.c. The designated accessible toilet is inaccessible because the side grab bar is mounted with the far end 47 inches from the rear wall. ST7 24 months
1.5. Club House MenÕs Locker Room    
1.5.a. There is no accessible locker provided. LR3 24 months
1.5.b. The bench is inaccessible because it is 11 inches deep and 16 inches high, it is not attached at the wall, and it does not provide clear floor space alongside to allow a transfer. LR1 24 months
1.5.c. The transfer shower is inaccessible because the seat is 22 inches high, the shower hose is 58 inches long, and the curb is 1 inch high. B8 24 months
1.6. Club House WomenÕs Locker Room    
1.6.a. There is no accessible locker provided. LR3 24 months
1.6.b. The bench is inaccessible because it is 11 inches deep and 16 inches high, it is not attached at the wall, and it does not provide clear floor space alongside to allow a transfer. LR1 24 months
1.6.c. The transfer shower is inaccessible because the seat is 22 inches high, the shower hose is 58 inches long, and the curb is 1 inch high. B8 24 months
1.7. Club House Lobby Computer Desk: The computer is inaccessible because the keyboard is on a table that provides only 26 inches of clear knee height. C3 24 months
1.8. Club House Kitchen    
1.8.a. The entrance is inaccessible because it is only 32 inches wide for a depth of more than 24 inches. AR3 24 months
1.8.b. The sink is inaccessible because there is no knee space provided. S2 24 months
1.9. Club House Drinking Fountain: Although a designated accessible drinking fountain is provided, there is no drinking fountain provided for people who have difficulty bending or stooping. DF3 24 months
2. Swope Park, located at East Meyer Boulevard and Swope Parkway    
2.1. Bandstand Drinking Fountain: The drinking fountain protrudes into the walkway and is not detectable to blind persons using a cane. AR8 30 months
2.2. Lewis Road Parking for Shelter 6    
2.2.a. The parking lot, with a total of 137 parking spaces, is inaccessible because it only has 3 spaces designated as accessible. This lot requires 1 van accessible space and 4 standard accessible spaces. P3 30 months
2.2.b. The curb ramp is inaccessible because it has a slope of 12.6% and the flared sides have slopes of 21.9% and 25.6%. AR5 30 months
2.3. Drinking Fountain Between Shelter 6 Toilet Rooms    
2.3.a. The drinking fountain protrudes into the walkway and is not detectable to blind persons using a cane. AR8 30 months
2.3.b. Although a designated accessible drinking fountain is provided, there is no drinking fountain provided for people who have difficulty bending or stooping. DF3 30 months
2.4. Shelter 6 MenÕs Toilet Room with Stalls    
2.4.a. There is no accessible toilet room sign provided. TR18 30 months
2.4.b. The air dryer protrudes into the walkway and is not detectable to blind persons using a cane. AR8 30 months
2.4.c. The urinal is inaccessible because the rim is 18½ inches high. TR20 30 months
2.5. Shelter 6 WomenÕs Toilet Room with Stalls: The air dryer protrudes into the walkway and is not detectable to blind persons using a cane. AR8 30 months
2.6. Game Street Curb Ramp to Skate Park: The curb ramp is inaccessible because it has a slope of 9.9%. AR5 30 months
2.7. Skate Park Drinking Fountain: The drinking fountain is inaccessible because it provides only 20½ inches of clear knee height. DF5 30 months
2.8. Shelter 3    
2.8.a. The parking lot, with a total of approximately 20 parking spaces, is inaccessible because there is no accessible space provided. This lot requires 1 van accessible space. P3 30 months
2.8.b. The routes to the playgrounds and drinking fountain are inaccessible because the grass is not firm, stable, and slip resistant. AR1 30 months
2.9. Shelter 7: The parking lot, with a total of 24 parking spaces, is inaccessible because there is no accessible space provided. This lot requires 1 van accessible space. P3 30 months
2.10. Baseball Diamonds 1, 2, 3: The routes to the bleachers are inaccessible because the grass is not firm, stable, and slip resistant. AR1 30 months
2.11. Shelter 2    
2.11.a. The parking lot, with a total of approximately 20 parking spaces, is inaccessible because there is no accessible space provided. This lot requires 1 van accessible space. P3 30 months
2.11.b. The routes to the playground, pavilion, and drinking fountain are inaccessible because the grass is not firm, stable, and slip resistant. AR1 30 months
2.11.c. Although a designated accessible drinking fountain is provided, there is no drinking fountain provided for people who have difficulty bending or stooping. DF3 30 months
2.12. Shelter 4: The routes to the pavilion and drinking fountain are inaccessible because the grass is not firm, stable, and slip resistant. AR1 30 months
2.13. Shelter 9: The route to the pavilion is inaccessible because the grass is not firm, stable, and slip resistant. AR1 30 months
2.14. Disc Golf Course: The parking lot, with a total of approximately 22 parking spaces, is inaccessible because there is no accessible space provided. This lot requires 1 van accessible space. P3 30 months
2.15. Shelter 8 Toilet Rooms    
2.15.a. The drinking fountain protrudes into the walkway and is not detectable to blind persons using a cane. AR8 30 months
2.15.b. Although a designated accessible drinking fountain is provided, there is no drinking fountain provided for people who have difficulty bending or stooping. DF3 30 months
2.15.c. The air dryers protrude into the walkway and are not detectable to blind persons using a cane. AR8 30 months
2.15.d. The toilets are inaccessible because the side grab bars are obstructed by the toilet paper dispensers. ST8 30 months
2.15.e. The toilet seat cover dispensers are inaccessible because they are mounted more than 56 inches high behind the toilet. TR4 30 months
2.15.f. Shelter 5: The route to the playground is inaccessible because the grass is not firm, stable, and slip resistant. AR1 30 months
3. Terry R. Dopson Administration Building , located at 4600 East 63rd Street    
3.1. Parking    
3.1.a. The parking lot, with a total of 233 parking spaces, is inaccessible because there are only 6 spaces designated as accessible, and three of these spaces have slopes between 2.3% and 3.4%. This lot requires 1 van accessible space and 6 standard accessible spaces. P3 24 months
3.1.b. The curb ramp between parking spaces in the side lot is inaccessible because it has a slope of 10.5% AR5 24 months
3.1.c. The curb ramps leading toward each other in the rear lot are inaccessible because they have slopes of 9.3% and 10.4%. AR5 24 months
3.2. Parks Board Room    
3.2.a. The door is inaccessible because it requires 7 pounds of force to open. D2 24 months
3.2.b. The room is inaccessible to people with hearing disabilities because there is no assistive listening system provided. AA5 24 months
3.3. Lobby Elevator: The elevator is inaccessible because the hall lanterns do not emit a visual signal indicating when a car is answering a call. E11 24 months
3.4. Basement Vending Machines: The snack vending machine is inaccessible because its controls are 57 inches high. TR5 24 months
3.5. Lobby WomenÕs Toilet Room with Stalls    
3.5.a. The door is inaccessible because it requires 7 pounds of force to open. D2 24 months
3.5.b. The feminine products dispenser protrudes into the walkway and is not detectable to blind persons using a cane. AR8 24 months
3.5.c. The designated accessible toilet is inaccessible because the side grab bar is mounted with the far end 51 inches from the rear wall. ST7 24 months
3.5.d. The designated accessible toilet is inaccessible because the rear grab bar is mounted 7½ inches from the side wall. ST4 24 months
3.5.e. The designated accessible toilet is inaccessible because the flush control is on the closed side. ST2 24 months
3.5.f. The seat cover dispenser is inaccessible because it is mounted with the controls 56 inches high. TR5 24 months
3.6. Lobby MenÕs Toilet Room with Stalls    
3.6.a. The door is inaccessible because it requires 7½ pounds of force to open. D2 24 months
3.6.b. The designated accessible toilet is inaccessible because the side grab bar is mounted with the far end 50½ inches from the rear wall. ST7 24 months
3.6.c. The designated accessible toilet is inaccessible because the rear grab bar is mounted 7½ inches from the side wall. ST4 24 months
3.6.d. The designated accessible toilet is inaccessible because the flush control is on the closed side. ST2 24 months
3.6.e. The designated accessible toilet is inaccessible because the top of the seat is 19½ inches high. ST20 24 months
3.6.f. The seat cover dispenser is inaccessible because it is mounted with the controls 56 inches high. TR5 24 months
3.6.g. The urinal is inaccessible because the rim is 18 inches high. TR20 24 months
3.7. WomenÕs Toilet Room with Stalls behind Board Room    
3.7.a. The door is inaccessible because it requires 12 pounds of force to open. D2 24 months
3.7.b. The feminine products dispenser protrudes into the walkway and is not detectable to blind persons using a cane. AR8 24 months
3.7.c. The designated accessible toilet is inaccessible because its centerline is 20 inches from the side wall. ST17 24 months
3.7.d. The designated accessible toilet is inaccessible because the side grab bar is mounted with the far end 50½ inches from the rear wall. ST7 24 months
3.7.e. The designated accessible toilet is inaccessible because the rear grab bar is mounted 7½ inches from the side wall. ST4 24 months
3.7.f. The designated accessible toilet is inaccessible because the rear grab bar is obstructed by the seat cover dispenser. ST5 24 months
3.8. Basement WomenÕs Toilet Room with Stalls    
3.8.a. The toilet room sign is mounted on the door and has no International Symbol of Accessibility. TR17 24 months
3.8.b. The door is inaccessible because it requires more than 5 pounds of force to open. D2 24 months
3.8.c. The lavatory is inaccessible because the bottom of the apron is 27½ inches high. TR11 24 months
3.8.d. The lavatory is inaccessible because the hot water pipes are not insulated or otherwise configured to protect against contact. TR12 24 months
3.8.e. The designated accessible toilet is inaccessible because the side grab bar is mounted with the far end 50½ inches from the rear wall. ST7 24 months
3.8.f. The designated accessible toilet is inaccessible because the rear grab bar is mounted 7½ inches from the side wall. ST4 24 months
3.9. Basement MenÕs Toilet Room with Stalls    
3.9.a. The toilet room sign is mounted on the hinge side of the door. TR18 24 months
3.9.b. The toilet room contains a number of inaccessible elements and is not accessible to people with disabilities and there is no signage directing people to the nearest accessible toilet room. TR16 24 months
3.10. 2nd Floor Unisex Toilet Room    
3.10.a. The toilet room sign is mounted on the door. TR17 24 months
3.10.b. The toilet is inaccessible because the flush control is on the closed side. SU1 24 months
3.10.c. The toilet is inaccessible because the side grab bar is mounted with the far end 50½ inches from the rear wall. SU6 24 months
3.10.d. The toilet is inaccessible because the rear grab bar is mounted 7½ inches from the side wall. SU3 24 months
3.10.e. The feminine products dispenser protrudes into the walkway and is not detectable to blind persons using a cane. AR8 24 months
3.10.f. The toilet is inaccessible because the rear grab bar is obstructed by the seat cover dispenser. SU4 24 months
4. City Hall, located at 414 East 12th Street    
4.1. Entrances    
4.1.a. The west side pedestrian entrance on Oak Street is inaccessible because the vestibule is not sufficiently deep. D3 36 months
4.1.b. The west side pedestrian entrance on Oak Street is inaccessible because the security door has an opening width of 29 inches. D25 36 months
4.1.c. The Main entrance is inaccessible because it has an opening width of 30 inches. D25 36 months
4.1.d. The exterior handrail outside the main entrance protrudes into the walkway and is not detectable to blind persons using a cane. AR8 36 months
4.2. Main Elevators: The elevator is inaccessible because the hall lanterns signal once for both up and down. E11 36 months
4.3. Interior Signage: The signage provided throughout the facility is inaccessible because it is mounted too low. D26 36 months
4.4. Drinking Fountains    
4.4.a. The drinking fountains throughout the facility are inaccessible because the spouts are 42 inches high, the water flow is less than 4 inches high, and the controls require twisting to operate. DF1 36 months
4.4.b. The drinking fountains throughout the facility protrude into the walkway and are not detectable to blind persons using a cane. AR8 36 months
4.5. Elevator Lobbies throughout the Building    
4.5.a. The televisions in the lobbies display notices that are not accessible to people who are blind or have low vision. M2 36 months
4.5.b. The televisions in the lobbies encroach on the required head room. AR7 36 months
4.5.c. The U.S. Mail slots are inaccessible because they are 59 inches high. TR5 36 months
4.6. Lower Level: The route from the entrance to the elevators is inaccessible because the security door has an opening width of 30 inches. D25 36 months
4.7. Lower Level WomenÕs Toilet Room with Stalls    
4.7.a. The door is inaccessible because it has an opening width of 30 inches. D25 36 months
4.7.b. No accessible mirror has been provided. TR14 36 months
4.7.c. The lavatory is inaccessible because the hot water pipes are not insulated or otherwise configured to protect against contact. TR12 36 months
4.7.d. No accessible coat hook has been provided. TR1 36 months
4.7.e. The grab bars provided at the designated accessible toilet have a number of inaccessible features and obstruct the toiletÕs clear floor space. ST11, ST18 36 months
4.7.f. Although there are 8 toilet stalls, there is no ambulatory stall provided. ST1 36 months
4.8. Lower Level MenÕs Toilet Room with Stalls    
4.8.a. The door is inaccessible because it has an opening width of 30 inches. D25 36 months
4.8.b. No accessible mirror has been provided. TR14 36 months
4.8.c. The lavatory is inaccessible because the hot water pipes are not insulated or otherwise configured to protect against contact. TR12 36 months
4.8.d. The designated accessible toilet is inaccessible because the top of the seat is 20 inches high. ST20 36 months
4.8.e. The designated accessible toilet is inaccessible because the flush control is on the closed side. ST2 36 months
4.8.f. The grab bars provided at the designated accessible toilet have a number of inaccessible features and obstruct the toiletÕs clear floor space. ST11, ST18 36 months
4.8.g. Although there are 6 toilet stalls, there is no ambulatory stall provided. ST1 36 months
4.9. Credit Union: The door is inaccessible because it has an opening width of 30 inches. D25 36 months
4.10. Finance Office    
4.10.a. The hand sanitizer is inaccessible because it is mounted with the controls 58 inches high. TR5 36 months
4.10.b. The payment, assessment, and tax counters are inaccessible because they are 42 inches high. C6 36 months
4.11. Revenue Division: The door is inaccessible because it has an opening width of 25 inches. D25 36 months
4.12. Business License Office    
4.12.a. The door is inaccessible because it has an opening width of 26 inches. D25 36 months
4.12.b. The door is inaccessible because it requires 10 pounds of force to open. D2 36 months
4.13. 4th Floor Human Relations WomenÕs Toilet Room with Stalls    
4.13.a. The door is inaccessible because it requires 12 pounds of force to open. D2 36 months
4.13.b. The designated accessible toilet is inaccessible because the side grab bar is mounted 12½ inches from the rear wall. ST7 36 months
4.13.c. The designated accessible toilet is inaccessible because the rear grab bar is mounted 6½ inches from the side wall. ST4 36 months
4.14. 4th Floor Human Relations MenÕs Toilet Room with Stalls    
4.14.a. The door is inaccessible because it requires 10 pounds of force to open. D2 36 months
4.14.b. The door is inaccessible because knob hardware is used on the pull side. D1 36 months
4.14.c. The route to the lavatory is inaccessible because it is less than 32 inches wide. AR3 36 months
4.14.d. The designated accessible toilet is inaccessible because its centerline is 19½ inches from the side wall. ST17 36 months
4.14.e. The designated accessible toilet is inaccessible because the rear grab bar is mounted 6½ inches from the side wall. ST4 36 months
4.15. Human Relations Conference Room 404: The door is inaccessible because it has an opening width of 30½ inches. D25 36 months
4.16. Neighborhood Community Service    
4.16.a. The door is inaccessible because it has an opening width of 31 inches. D25 36 months
4.16.b. The door is inaccessible because it requires 10 pounds of force to open. D2 36 months
4.17. Conference Room 403: The door is inaccessible because it requires 13 pounds of force to open. D2 36 months
4.18. City Planning Office    
4.18.a. The door is inaccessible because it has an opening width of 28 inches. D25 36 months
4.18.b. The ramp inside the entry door is inaccessible because it has no handrails. R4 36 months
4.18.c. The counters protrude into the walkway and are not detectable to blind persons using a cane. AR8 36 months
4.19. 5th Floor WomenÕs Toilet Room with Stalls: The door is inaccessible because it requires 8 pounds of force to open. D2 36 months
4.20. 5th Floor MenÕs Toilet Room with Stalls    
4.20.a. The sign is mounted on the hinge side of the door. TR17 36 months
4.20.b. No accessible mirror has been provided. TR14 36 months
4.20.c. The paper towel dispenser protrudes into the walkway and is not detectable to blind persons using a cane. AR8 36 months
4.20.d. The lavatory is inaccessible because the hot water pipes are not insulated or otherwise configured to protect against contact. TR12 36 months
4.21. Public Works 503 West    
4.21.a. The door is inaccessible because there is a slope of 7.4% within the doorÕs required maneuvering clearance. D13 36 months
4.21.b. The door is inaccessible because it requires 10 pounds of force to open. D2 36 months
4.22. Records Management 602: The double doors are inaccessible because each leaf is 28 inches wide. D24 36 months
4.23. The Forum    
4.23.a. The door is inaccessible because it has an opening width of 29 inches. D25 36 months
4.23.b. There is no accessible route onto the stage. AR2 36 months
4.23.c. The Forum, containing 78 seats, is inaccessible because companion seats are not provided adjacent to wheelchair seating locations. A total of 4 wheelchair seating areas is required. AA6 36 months
4.23.d. The ramp leading to the Forum is inaccessible because it has a slope of up to 9.7%. R5 36 months
4.23.e. The Forum is inaccessible to people with hearing disabilities because, although there are 78 fixed seats, there is no assistive listening system provided. This room requires 4 receivers. AA4 36 months
4.24. 6th Floor Toilet Rooms: The toilet rooms do not have accessible features, and there is no signage directing people with disabilities to the accessible toilet rooms. TR16 36 months
4.25. 7th Floor Toilet Rooms: The toilet rooms do not have accessible features, and there is no signage directing people with disabilities to the accessible toilet rooms. TR16 36 months
4.26. Cafeteria 803    
4.26.a. The paper towel dispensers are inaccessible because they are mounted with the controls 56 inches high. TR5 36 months
4.26.b. The sink is inaccessible because there is no knee space provided. S2 36 months
4.26.c. The chips and candy vending machines are inaccessible because some of the controls are 58 inches high. TR5 36 months
4.27. 8th Floor MenÕs Toilet Room with Stalls    
4.27.a. The door is inaccessible because it has an opening width of 28½ inches. D25 36 months
4.27.b. The pull side of the door, which is accessed from the latch side of the door, is inaccessible because it has insufficient clear space on the latch side. D10 36 months
4.27.c. The lavatory is inaccessible because the hot water pipes are not insulated or otherwise configured to protect against contact. TR12 36 months
4.27.d. The designated accessible toilet stall door is inaccessible because it has an opening width of 30½ inches. D25 36 months
4.27.e. The designated accessible toilet stall is inaccessible because it is 57 inches long. ST16 36 months
4.28. 8th Floor WomenÕs Toilet Room with Stalls    
4.28.a. The door is inaccessible because it has an opening width of 28½ inches. D25 36 months
4.28.b. The pull side of the door, which is accessed from the latch side of the door, is inaccessible because it has insufficient clear space on the latch side. D10 36 months
4.28.c. The light switch is inaccessible because it is mounted 54½ inches high. TR5 36 months
4.28.d. No accessible mirror has been provided. TR14 36 months
4.28.e. The wooden shelf protrudes into the walkway and is not detectable to blind persons using a cane. AR8 36 months
4.28.f. The lavatory is inaccessible because the hot water pipes are not insulated or otherwise configured to protect against contact. TR12 36 months
4.28.g. The designated accessible stall is incorrectly configured as an ambulatory stall, and there is no standard accessible stall provided. ST15 36 months
4.29. City Council Dining Room 804    
4.29.a. The telephone is inaccessible because it is mounted with the controls up to 56 inches high. TR5 36 months
4.29.b. The door is inaccessible because it has an opening width of 27 inches. D25 36 months
4.30. 9th Floor Toilet Rooms: The toilet room contains a number of inaccessible elements and is not accessible to people with disabilities. ST14 36 months
4.31. 10th Floor Toilet Rooms: The toilet room contains a number of inaccessible elements and is not accessible to people with disabilities. ST14 36 months
4.32. Committee Room 1003    
4.32.a. The door is inaccessible because it has an opening width of 26½ inches. D25 36 months
4.32.b. There is no signage informing the public of the availability of an assistive listening system. AA3 36 months
4.33. 11th Floor Toilet Rooms: The toilet room contains a number of inaccessible elements and is not accessible to people with disabilities. ST14 36 months
4.34. Room 1102: The double doors are inaccessible because each leaf is 30 inches wide. D24 36 months
4.35. Room 1103    
4.35.a. The counter is inaccessible because it is 43 inches high. C6 36 months
4.35.b. The counter protrudes into the walkway and is not detectable to blind persons using a cane. AR8 36 months
4.36. 11th Floor Employee Break Room    
4.36.a. The route between the copier and the counter into the break room is inaccessible because it is only 29 inches wide. AR3 36 months
4.36.b. The sink is inaccessible because there is no knee space provided. S2 36 months
4.37. Room 1104: The door is inaccessible because it has an opening width of 30 inches. D25 36 months
4.38. 12th Floor WomenÕs Toilet Room with Stalls    
4.38.a. The door is inaccessible because it has an opening width of 29 inches. D25 36 months
4.38.b. The door is inaccessible because it requires 12 pounds of force to open. D2 36 months
4.38.c. Although an audible alarm is provided in this facility, there is no visual alarm appliance in the toilet room. TR21 36 months
4.38.d. The paper towel dispenser protrudes into the walkway and is not detectable to blind persons using a cane. AR8 36 months
4.38.e. The designated accessible stall is incorrectly configured as an ambulatory stall, and there is no standard accessible stall provided. ST15 36 months
4.39. 12th Floor MenÕs Toilet Room with Stalls    
4.39.a. The door is inaccessible because it has an opening width of 29 inches. D25 36 months
4.39.b. The door is inaccessible because it requires 16 pounds of force to open. D2 36 months
4.39.c. The light switch is inaccessible because it is mounted 55 inches high. TR5 36 months
4.39.d. Although an audible alarm is provided in this facility, there is no visual alarm appliance in the toilet room. TR21 36 months
4.39.e. The paper towel dispenser protrudes into the walkway and is not detectable to blind persons using a cane. AR8 36 months
4.39.f. The designated accessible stall is incorrectly configured as an ambulatory stall, and there is no standard accessible stall provided. ST15 36 months
4.40. Room 1201    
4.40.a. The door is inaccessible because it has an opening width of 31 inches. D25 36 months
4.40.b. The door is inaccessible because it requires more than 5 pounds of force to open. D2 36 months
4.40.c. The door is inaccessible because knob hardware is used. D1 36 months
4.40.d. The pull side of the door, which is accessed through a front approach, is inaccessible because it has only 3 inches of clear space on the latch side. D6 36 months
4.40.e. The route into the room is inaccessible because it is only 25 inches wide past the first desk. AR3 36 months
4.41. Room 1203: The mail slots in the compensation area protrude into the walkway and are not detectable to blind persons using a cane. AR8 36 months
4.42. Room 1205    
4.42.a. The double doors are inaccessible because each leaf is 29½ inches wide. D24 36 months
4.42.b. The door is inaccessible because it requires 8 pounds of force to open. D2 36 months
4.42.c. The pull side of the door, which is accessed from the latch side of the door, is inaccessible because it has only 42 inches of clear depth. D10 36 months
4.42.d. The counter protrudes into the walkway and is not detectable to blind persons using a cane. AR8 36 months
4.43. 13th Floor Toilet Rooms: The toilet room contains a number of inaccessible elements and is not accessible to people with disabilities. ST14 36 months
4.44. Room 1303    
4.44.a. The double doors are inaccessible because each leaf is 29½ inches wide. D24 36 months
4.44.b. The counter protrudes into the walkway and is not detectable to blind persons using a cane. AR8 36 months
4.44.c. The sink in the break room is inaccessible because there is no knee space provided. S2 36 months
4.45. 14th Floor Toilet Rooms: The toilet room contains a number of inaccessible elements and is not accessible to people with disabilities. ST14 36 months
4.46. Room 1401    
4.46.a. The door is inaccessible because it has an opening width of 31 inches. D25 36 months
4.46.b. The door is inaccessible because it requires 11 pounds of force to open. D2 36 months
4.46.c. The door is inaccessible because knob hardware is used. D1 36 months
4.46.d. The push side of the door, which is accessed through a front approach and which has both a closer and a latch, is inaccessible because it has only 3 inches of clear space on the latch side. D7 36 months
4.47. Room 1402: The double doors are inaccessible because each leaf is 29½ inches wide. D24 36 months
4.48. Room 1405    
4.48.a. The double doors are inaccessible because each leaf is 29½ inches wide. D24 36 months
4.48.b. The counter is inaccessible because it is 40 inches high. C6 36 months
4.48.c. The counter protrudes into the walkway and is not detectable to blind persons using a cane. AR8 36 months
4.49. Room 1407    
4.49.a. The double doors are inaccessible because each leaf is 29½ inches wide. D24 36 months
4.49.b. The door is inaccessible because it requires 11 pounds of force to open. D2 36 months
4.50. Room 1408    
4.50.a. The door is inaccessible because it has an opening width of 31 inches. D25 36 months
4.50.b. The door is inaccessible because it requires 8 pounds of force to open. D2 36 months
4.50.c. The door is inaccessible because knob hardware is used. D1 36 months
4.50.d. The pull side of the door, which is accessed through a front approach, is inaccessible because it has only 3½ inches of clear space on the latch side. D6 36 months
4.50.e. The push side of the door, which is accessed through a front approach and which has both a closer and a latch, is inaccessible because it has only 3 inches of clear space on the latch side. D7 36 months
4.51. 15th Floor Toilet Rooms: The toilet room contains a number of inaccessible elements and is not accessible to people with disabilities. ST14 36 months
4.52. Room 1501: The door is inaccessible because it has an opening width of 31 inches. D25 36 months
4.53. Room 1502    
4.53.a. The double doors are inaccessible because each leaf is 29½ inches wide. D24 36 months
4.53.b. The door is inaccessible because it requires 12 pounds of force to open. D2 36 months
4.54. Room 1503: The sink in the break room is inaccessible because there is no knee space provided. S2 36 months
4.55. Room 1504: The double doors are inaccessible because each leaf is 29½ inches wide. D24 36 months
4.56. 16th Floor Toilet Rooms: The toilet room contains a number of inaccessible elements and is not accessible to people with disabilities. ST14 36 months
4.57. Room 1601    
4.57.a. The door is inaccessible because it has an opening width of 31 inches. D25 36 months
4.57.b. The door is inaccessible because it requires 11 pounds of force to open. D2 36 months
4.57.c. The door is inaccessible because knob hardware is used. D1 36 months
4.57.d. The pull side of the door, which is accessed through a front approach, is inaccessible because it has only 3½ inches of clear space on the latch side. D6 36 months
4.57.e. The push side of the door, which is accessed through a front approach and which has both a closer and a latch, is inaccessible because it has only 3½ inches of clear space on the latch side. D7 36 months
4.57.f. The conference room door is inaccessible because it requires 7½ pounds of force to open. D2 36 months
4.57.g. The conference room door is inaccessible because knob hardware is used. D1 36 months
4.58. Room 1602    
4.58.a. The double doors are inaccessible because each leaf is 29½ inches wide. D24 36 months
4.58.b. The counter is inaccessible because it is 43 inches high. C6 36 months
4.58.c. The counter protrudes into the walkway and is not detectable to blind persons using a cane. AR8 36 months
4.59. Room 1603    
4.59.a. The counter is inaccessible because it is 44 inches high. C6 36 months
4.59.b. The counter protrudes into the walkway and is not detectable to blind persons using a cane. AR8 36 months
4.59.c. The door to the drafting area is inaccessible because the threshold is not stable, firm, and slip resistant. AR2 36 months
4.60. Room 1604: The double doors are inaccessible because each leaf is 29½ inches wide. D24 36 months
4.61. Room 1605    
4.61.a. The double doors are inaccessible because each leaf is 29½ inches wide. D24 36 months
4.61.b. The counter protrudes into the walkway and is not detectable to blind persons using a cane. AR8 36 months
4.61.c. The route past the counter is inaccessible because it is only 29½ inches wide. AR3 36 months
4.62. 17th Floor WomenÕs Toilet Room with Stalls    
4.62.a. The door is inaccessible because it has an opening width of 30½ inches. D25 36 months
4.62.b. The designated accessible toilet is inaccessible because its centerline is 19½ inches from the side wall. ST17 36 months
4.63. 17th Floor MenÕs Toilet Room with Stalls    
4.63.a. The door is inaccessible because it has an opening width of 30½ inches. D25 36 months
4.63.b. The paper towel dispenser protrudes into the walkway and is not detectable to blind persons using a cane. AR8 36 months
4.64. Room 1702    
4.64.a. The double doors are inaccessible because each leaf is 29½ inches wide. D24 36 months
4.64.b. The door is inaccessible because it requires 10 pounds of force to open. D2 36 months
4.64.c. The sink in the break room is inaccessible because there is no knee space provided. S2 36 months
4.65. Room 1703    
4.65.a. The counter is inaccessible because it is 42 inches high. C6 36 months
4.65.b. The counter protrudes into the walkway and is not detectable to blind persons using a cane. AR8 36 months
4.65.c. The sink in the break room is inaccessible because there is no knee space provided. S2 36 months
4.66. Room 1704    
4.66.a. The double doors are inaccessible because each leaf is 29½ inches wide. D24 36 months
4.66.b. The door is inaccessible because it requires 13 pounds of force to open. D2 36 months
4.67. Room 1801: The door is inaccessible because it has an opening width of 31 inches. D25 36 months
4.68. Room 1802    
4.68.a. The double doors are inaccessible because each leaf is 29½ inches wide. D24 36 months
4.68.b. The door is inaccessible because it requires 14 pounds of force to open. D2 36 months
4.68.c. The counter protrudes into the walkway and is not detectable to blind persons using a cane. AR8 36 months
4.69. Room 1804    
4.69.a. The double doors are inaccessible because each leaf is 29½ inches wide. D24 36 months
4.69.b. The door is inaccessible because it requires 15 pounds of force to open. D2 36 months
4.70. 18th Floor WomenÕs Toilet Room with Stalls: The door is inaccessible because it requires 12 pounds of force to open. D2 36 months
4.71. 18th Floor MenÕs Toilet Room with Stalls    
4.71.a. The door is inaccessible because it requires 12 pounds of force to open. D2 36 months
4.71.b. The paper towel dispenser protrudes into the walkway and is not detectable to blind persons using a cane. AR8 36 months
4.72. 19th Floor Toilet Rooms: The toilet room contains a number of inaccessible elements and is not accessible to people with disabilities. ST14 36 months
4.73. Room 1901    
4.73.a. The door is inaccessible because it has an opening width of 31 inches. D25 36 months
4.73.b. The door is inaccessible because it requires 10 pounds of force to open. D2 36 months
4.73.c. The door is inaccessible because knob hardware is used. D1 36 months
4.73.d. The pull side of the door, which is accessed through a front approach, is inaccessible because it has only 4 inches of clear space on the latch side. D6 36 months
4.73.e. The push side of the door, which is accessed through a front approach and which has both a closer and a latch, is inaccessible because it has only 2½ inches of clear space on the latch side. D7 36 months
4.74. Room 1902: The door is inaccessible because it has an opening width of 29½ inches. D25 36 months
4.75. Room 1903    
4.75.a. The counter is inaccessible because it is 43 inches high. C6 36 months
4.75.b. The counter protrudes into the walkway and is not detectable to blind persons using a cane. AR8 36 months
4.76. Room 1905    
4.76.a. The door is inaccessible because it has an opening width of 31 inches. D25 36 months
4.76.b. The door is inaccessible because it requires 11 pounds of force to open. D2 36 months
4.76.c. The door is inaccessible because knob hardware is used. D1 36 months
4.76.d. The pull side of the door, which is accessed through a front approach, is inaccessible because it has only 4 inches of clear space on the latch side. D6 36 months
4.76.e. The push side of the door, which is accessed through a front approach and which has both a closer and a latch, is inaccessible because it has only 3½ inches of clear space on the latch side. D7 36 months
4.77. 20th Floor Toilet Rooms: The toilet room contains a number of inaccessible elements and is not accessible to people with disabilities. ST14 36 months
4.78. Room 2001    
4.78.a. The door is inaccessible because it has an opening width of 31 inches. D25 36 months
4.78.b. The door is inaccessible because it requires 11 pounds of force to open. D2 36 months
4.78.c. The door is inaccessible because knob hardware is used. D1 36 months
4.78.d. The pull side of the door, which is accessed from the hinge side of the door, is inaccessible because it has only 4 inches of clear space on the latch side. D8 36 months
4.78.e. The push side of the door, which is accessed through a front approach and which has both a closer and a latch, is inaccessible because it has only 3 inches of clear space on the latch side. D7 36 months
4.79. Room 2002    
4.79.a. The double doors are inaccessible because each leaf is 30 inches wide. D24 36 months
4.79.b. The door is inaccessible because it requires 14 pounds of force to open. D2 36 months
4.80. Room 2003    
4.80.a. The double doors are inaccessible because each leaf is 30 inches wide. D24 36 months
4.80.b. The counter is inaccessible because it is 43 inches high. C6 36 months
4.81. Room 2004: The door is inaccessible because it has an opening width of 29½ inches. D25 36 months
4.82. 20th Floor Break Room: The sink is inaccessible because there is no knee space provided. S2 36 months
4.83. 21st Floor Toilet Rooms: The toilet room contains a number of inaccessible elements and is not accessible to people with disabilities. ST14 36 months
4.84. Room 2101    
4.84.a. The door is inaccessible because it has an opening width of 31 inches. D25 36 months
4.84.b. The door is inaccessible because it requires 14 pounds of force to open. D2 36 months
4.84.c. The door is inaccessible because knob hardware is used. D1 36 months
4.84.d. The pull side of the door, which is accessed through a front approach, is inaccessible because it has only 3½ inches of clear space on the latch side. D6 36 months
4.84.e. The push side of the door, which is accessed through a front approach and which has both a closer and a latch, is inaccessible because it has only 3 inches of clear space on the latch side. D7 36 months
4.84.f. The counter is inaccessible because it is 43 inches high. C6 36 months
4.84.g. The counter protrudes into the walkway and is not detectable to blind persons using a cane. AR8 36 months
4.85. Room 2103    
4.85.a. The counter is inaccessible because it is 43 inches high. C6 36 months
4.85.b. The counter protrudes into the walkway and is not detectable to blind persons using a cane. AR8 36 months
4.86. 21st Floor Break Room: The sink is inaccessible because there is no knee space provided. S2 36 months
4.87. 22nd Floor Lobby Security Desk: The counter protrudes into the walkway and is not detectable to blind persons using a cane. AR8 36 months
4.88. 22nd Floor WomenÕs Toilet Room with Stalls    
4.88.a. The door is inaccessible because it requires 13 pounds of force to open. D2 36 months
4.88.b. The designated accessible toilet is inaccessible because its centerline is 19¾ inches from the side wall. ST17 36 months
4.88.c. The toilet paper dispenser in the designated accessible stall is inaccessible because it is mounted 39 inches from the rear wall. ST19 36 months
4.88.d. The designated accessible toilet is inaccessible because the side grab bar is mounted 13 inches from the rear wall. ST7 36 months
4.89. 22nd Floor MenÕs Toilet Room with Stalls    
4.89.a. The door is inaccessible because it requires 12 pounds of force to open. D2 36 months
4.89.b. The designated accessible toilet is inaccessible because the top of the seat is 20 inches high. ST20 36 months
4.89.c. The toilet paper dispenser in the designated accessible stall is inaccessible because it is mounted 39 inches from the rear wall. ST19 36 months
4.89.d. The designated accessible toilet is inaccessible because the rear grab bar is mounted 6¾ inches from the side wall. ST4 36 months
4.90. 22nd Floor Suite: The door is inaccessible because it requires 10½ pounds of force to open. D2 36 months
4.91. Room 2202    
4.91.a. The double doors are inaccessible because each leaf is 29½ inches wide. D24 36 months
4.91.b. The door is inaccessible because it requires 15 pounds of force to open. D2 36 months
4.92. Room 2203: The counter is inaccessible because it is 45 inches high. C6 36 months
4.93. 22nd Floor Break Room: The sink is inaccessible because there is no knee space provided. S2 36 months
4.94. Room 2204    
4.94.a. The double doors are inaccessible because each leaf is 29½ inches wide. D24 36 months
4.94.b. The door is inaccessible because it requires 12 pounds of force to open. D2 36 months
4.95. Room 2301    
4.95.a. The door is inaccessible because it requires 14 pounds of force to open. D2 36 months
4.95.b. The door is inaccessible because knob hardware is used. D1 36 months
4.95.c. The pull side of the door, which is accessed through a front approach, is inaccessible because it has only 4 inches of clear space on the latch side. D6 36 months
4.95.d. The push side of the door, which is accessed through a front approach and which has both a closer and a latch, is inaccessible because it has only 3 inches of clear space on the latch side. D7 36 months
4.95.e. The counter is inaccessible because it is 44 inches high. C6 36 months
4.95.f. The counters protrude into the walkway and are not detectable to blind persons using a cane. AR8 36 months
4.96. Room 2302    
4.96.a. The door is inaccessible because it requires 11 pounds of force to open. D2 36 months
4.96.b. The door is inaccessible because knob hardware is used. D1 36 months
4.97. 23rd Floor Toilet Rooms: The toilet room contains a number of inaccessible elements and is not accessible to people with disabilities. ST14 36 months
4.98. Room 2303    
4.98.a. The door is inaccessible because it requires 13 pounds of force to open. D2 36 months
4.98.b. The counter is inaccessible because it is 39 inches high. C6 36 months
4.99. 24th Floor Toilet Rooms: The toilet rooms do not have accessible features, and there is no signage directing people with disabilities to the accessible toilet rooms. TR16 36 months
4.100. Room 2505 City ClerkÕs Office    
4.100.a.  The double doors are inaccessible because each leaf is 27 inches wide. D24 36 months
4.100.b.  The door is inaccessible because it requires 9 pounds of force to open. D2 36 months
4.100.c.  The counters are inaccessible because they are more than 36 inches high. C6 36 months
4.100.d.  The lobby counter protrudes into the walkway and is not detectable to blind persons using a cane. AR8 36 months
4.101. 25th Floor MenÕs Toilet Room with Stalls    
4.101.a.  The door is inaccessible because it has an opening width of 29 inches. D25 36 months
4.101.b. The designated accessible stall is incorrectly configured as an ambulatory stall, and there is no standard accessible stall provided. ST15 36 months
4.102. 25th Floor WomenÕs Toilet Room with Stalls    
4.102.a.  The door is inaccessible because it has an opening width of 29 inches. D25 36 months
4.102.b. Although an audible alarm is provided in this facility, there is no visual alarm appliance in the toilet room. TR21 36 months
4.102.c. The designated accessible stall is incorrectly configured as an ambulatory stall, and there is no standard accessible stall provided. ST15 36 months
4.103. 26th Floor Lobby    
4.103.a. The wall-mounted ashtray protrudes into the walkway and is not detectable to blind persons using a cane. AR8 36 months
4.103.b.  The route is inaccessible because it is only 29½ inches wide past the table. AR3 36 months
4.104. 26th Floor WomenÕs Toilet Room with Stalls    
4.104.a.  The door is inaccessible because it has an opening width of 30 inches. D25 36 months
4.104.b.  No accessible coat hook has been provided. TR1 36 months
4.104.c. The paper towel and feminine products dispensers protrude into the walkway and are not detectable to blind persons using a cane. AR8 36 months
4.104.d.  The designated accessible toilet is inaccessible because its centerline is 19 inches from the side wall. ST17 36 months
4.104.e.  The designated accessible toilet is inaccessible because the flush control is on the closed side. ST2 36 months
4.104.f.  The designated accessible toilet stall is inaccessible because it is 55 inches long. ST16 36 months
4.104.g. The designated accessible toilet is inaccessible because the side grab bar is mounted with the far end 52 inches from the rear wall. ST7 36 months
4.105. 26th Floor Council Chamber    
4.105.a.  The double doors are inaccessible because each leaf is 30½ inches wide. D24 36 months
4.105.b. The chamber is inaccessible to people with hearing disabilities because, although there are 168 fixed seats, there is no assistive listening system provided. This room requires 7 receivers. AA4 36 months
4.106. 26th Floor Single User Family Toilet Room    
4.106.a.  The toilet room sign is mounted on the hinge side of the door. TR17 36 months
4.106.b.  The door is inaccessible because it has an opening width of 30 inches. D25 36 months
4.106.c.  The door is inaccessible because knob hardware is used. D1 36 months
4.106.d. Although an audible alarm is provided in this facility, there is no visual alarm appliance in the toilet room. TR21 36 months
4.106.e.  The toilet is inaccessible because the top of the seat is 20 inches high. SU18 36 months
4.106.f. The toilet is inaccessible because the side grab bar is mounted with the far end less than 54 inches from the rear wall. SU6 36 months
4.107. 27th Floor Toilet Rooms: The toilet room contains a number of inaccessible elements and is not accessible to people with disabilities. ST14 36 months
4.108. 28th Floor Toilet Rooms: The toilet room contains a number of inaccessible elements and is not accessible to people with disabilities. ST14 36 months
5. Fire Station #29, located at 1414 East 63rd Street    
5.1. Single-User Family Toilet Room: The toilet room sign is mounted 64 inches high. TR18 6 months
6. Golden Oaks Park, located at Northeast 46th Street and North Antioch Road    
6.1. The route to the sprayground is inaccessible because the grass is not firm, stable, and slip resistant. AR1 18 months
7. Robert J. Mohart Center, located at 3200 Wayne Avenue    
7.1. Multi-Purpose Room    
7.1.a. The double doors are inaccessible because each leaf is 28 inches wide. D24 30 months
7.1.b. The doors are inaccessible because they require 15 pounds of force to open. D2 30 months
7.2. Kitchen    
7.2.a. The door is inaccessible because it requires 12 pounds of force to open. D2 30 months
7.2.b. The fire extinguisher protrudes into the walkway and is not detectable to blind persons using a cane. AR8 30 months
7.2.c. The door from the multipurpose room to the kitchen is inaccessible because it requires 10 pounds of force to open. D2 30 months
7.3. Employee 1st Floor East Side Unisex Single User Toiler Room    
7.3.a. The toilet is inaccessible because the side grab bar is obstructed by the toilet seat cover dispenser. SU8 30 months
7.3.b. The toilet is inaccessible because the rear grab bar is 24 inches long. SU3 30 months
7.4. 1st Floor Public East Side Unisex Single User Toiler Room    
7.4.a. The toilet is inaccessible because its centerline is 19½ inches from the side wall. SU15 30 months
7.4.b. The toilet is inaccessible because the side grab bar is obstructed by the toilet seat cover dispenser. SU8 30 months
7.5. Exterior Lobby Toilet Rooms: There is no signage directing people with disabilities to the accessible toilet rooms. TR16 30 months
7.6. MenÕs West Side Entrance Toilet Room with Stalls    
7.6.a. The soap dispenser, which requires a forward reach, is inaccessible because it is mounted with the controls 52½ inches high. TR5 30 months
7.6.b. The designated accessible toilet is inaccessible because the stall is 55 inches wide. ST16 30 months
7.6.c. The designated accessible toilet is inaccessible because the side grab bar is obstructed by the toilet seat cover dispenser. ST9 30 months
7.7. WomenÕs West Side Entrance Toilet Room with Stalls    
7.7.a. The designated accessible toilet is inaccessible because the side grab bar is obstructed by the toilet seat cover dispenser. ST9 30 months
7.7.b. The designated accessible toilet is inaccessible because the rear grab bar is mounted 10 inches from the side wall. ST4 30 months
7.8. WomenÕs 2nd Floor West Wing Toilet Room with Stalls    
7.8.a. The toilet paper dispenser in the designated accessible stall is inaccessible because it is mounted 17½ inches high. ST19 30 months
7.8.b. The designated accessible toilet is inaccessible because the side grab bar is mounted with the far end 48½ inches from the rear wall. ST7 30 months
7.8.c. The designated accessible toilet is inaccessible because the grab bars are mounted 36¾ inches high. ST12 30 months
7.8.d. The designated accessible toilet is inaccessible because the rear grab bar is mounted 8 inches from the side wall. ST4 30 months
7.8.e. The designated accessible toilet is inaccessible because the side grab bar is obstructed by the toilet seat cover dispenser. ST9 30 months
7.8.f. The shelf protrudes into the walkway and is not detectable to blind persons using a cane. AR8 30 months
7.9. MenÕs 2nd Floor West Wing Toilet Rooms with Stalls    
7.9.a. The pull side of the door, which is accessed through a front approach, is inaccessible because it has only 5½ inches of clear space on the latch side. D6 30 months
7.9.b. The urinal is inaccessible because the clear floors space is 28 inches wide. TR20 30 months
7.9.c. The toilet paper dispenser in the designated accessible stall is inaccessible because it is mounted 18 inches high. ST19 30 months
7.9.d. The designated accessible toilet is inaccessible because the side grab bar is obstructed by the toilet seat cover dispenser. ST9 30 months
7.10. West Side Activity Room    
7.10.a. The door is inaccessible because knob hardware is used. D1 30 months
7.10.b. The door is inaccessible because it has an opening width of 30 inches. D25 30 months
7.11. Chronic Disease Management Class: The door is inaccessible because knob hardware is used. D1 30 months
7.12. Conference Room 205: The door is inaccessible because knob hardware is used. D1 30 months
7.13. Conference Room 201: The door is inaccessible because knob hardware is used. D1 30 months
7.14. 1st Floor Drinking Fountains: Although a designated accessible drinking fountain is provided, there is no drinking fountain provided for people who have difficulty bending or stooping. DF3 30 months
7.15. 2nd Floor Drinking Fountain    
7.15.a. The drinking fountain is inaccessible because it has a spout that is 41 inches high. DF6 30 months
7.15.b. The drinking fountain is inaccessible because the flow of water is less than 4 inches high. DF7 30 months
7.15.c. The wall-mounted drinking fountain is inaccessible because it provides inadequate knee clearance. DF5 30 months
7.16. Ramp from West Side Entrance to Auditorium: The ramp is inaccessible because it has a slope of 9%, it does not have edge protection at the drop off sides, it lacks a handrail on one side, the handrail is 32 inches high, and the handrail lacks extensions. R5 30 months
7.17. Auditorium    
7.17.a. The door to the auditorium vestibule is inaccessible because it has an opening width of 30 inches. D25 30 months
7.17.b. The auditorium is inaccessible to people with hearing disabilities because, although there are more than 50 fixed seats, there is no assistive listening system provided. This auditorium requires 15 receivers. AA4 30 months
7.17.c. The ramps to the stage are inaccessible because they each lack a handrail on one side, and the handrails lack extensions. R2 30 months
7.18. North Main Exterior Entrance: The double doors are inaccessible because each leaf is 30 inches wide. D24 30 months
7.19. 2nd Floor Route from West Wing to East Wing    
7.19.a. The east side door connecting to the west wing is inaccessible because it has an opening width of 25 inches. D25 30 months
7.19.b. The ramp is inaccessible because it has a slope of up to 10% and a cross slope of up to 4.2%. R5 30 months
7.20. 2nd Floor Unisex Single User Toilet Room    
7.20.a. The toilet is inaccessible because the side grab bar is obstructed by the toilet seat cover dispenser. SU8 30 months
7.20.b. The toilet is inaccessible because the rear grab bar is 24 inches long. SU3 30 months
7.21. Plan Room 205: The door is inaccessible because knob hardware is used. D1 30 months
7.22. Assembly Room 226: The room is inaccessible to people with hearing disabilities because there is no assistive listening system provided. AA5 30 months
7.23. Second Floor West Wing Ramp to Auditorium Balcony: The ramp is inaccessible because is has a slope of up to 10.4%. R3 30 months
7.24. Boardroom 101    
7.24.a. The door is inaccessible because knob hardware is used. D1 30 months
7.24.b. The flat screen television protrudes into the walkway and is not detectable to blind persons using a cane. AR8 30 months
7.24.c. The sink in the kitchenette is inaccessible because it lacks adequate knee clearance. S2 30 months
7.25. East Side Wayne Avenue Entrance: The door is inaccessible because it has an opening width of 30 inches. D25 30 months
7.26. Parking    
7.26.a. The designated accessible parking spaces are inaccessible because the signage is mounted too low. P6 30 months
7.26.b. The designated accessible parking spaces are inaccessible because they have cross slopes of up to 3.2%. P7 30 months
8. Conference Center, located at 201 West 14th Street    
8.1. WomenÕs Toilet Room with Stalls 1511    
8.1.a. No accessible coat hook has been provided. TR1 24 months
8.1.b. The designated accessible toilet is inaccessible because the side grab bar is obstructed by the toilet paper dispenser. ST8 24 months
8.1.c. The designated accessible toilet is inaccessible because the side grab bar is mounted with the far end 49 inches from the rear wall. ST7 24 months
8.1.d. The designated accessible toilet is inaccessible because the rear grab bar is obstructed by the flush valve. ST5 24 months
8.1.e. The ambulatory stalls are inaccessible because they are both more than 36 inches wide, the toilets are not centered within the stall, one side grab bar in each stall is obstructed by the toilet paper dispenser, and the side grab bars are all mounted with the far ends 49 inches from the rear wall. ST1 24 months.
8.2. MenÕs Toilet Room with Stalls 1512    
8.2.a. The urinal is inaccessible because the rim is 20 inches high. TR20 24 months
8.2.b. No accessible coat hook has been provided. TR1 24 months
8.2.c. The designated accessible toilet is inaccessible because the side grab bar is obstructed by the toilet paper dispenser. ST8 24 months
8.2.d. The designated accessible toilet is inaccessible because the side grab bar is mounted with the far end 49 inches from the rear wall. ST7 24 months
8.3. MenÕs Toilet Room with Stalls 2511    
8.3.a. The door is inaccessible because it requires 14 pounds of force to open. D2 24 months
8.3.b. The pull side of the door, which is accessed through a front approach, is inaccessible because it has only 5 inches of clear space on the latch side. D6 24 months
8.3.c. The air dryer protrudes into the walkway and is not detectable to blind persons using a cane. AR8 24 months
8.3.d. No accessible coat hook has been provided. TR1 24 months
8.3.e. The designated accessible toilet is inaccessible because the side grab bar is mounted with the far end 49 inches from the rear wall. ST7 24 months
8.3.f. The designated accessible toilet is inaccessible because the side grab bar is obstructed by the toilet paper dispenser. ST8 24 months
8.4. WomenÕs Toilet Room with Stalls 2512    
8.4.a. No accessible coat hook has been provided. TR1 24 months
8.4.b. The designated accessible toilet is inaccessible because the side grab bar is obstructed by the toilet paper dispenser. ST8 24 months
8.4.c. The air dryer protrudes into the walkway and is not detectable to blind persons using a cane. AR8 24 months
8.4.d. The designated accessible toilet is inaccessible because the side grab bar is mounted with the far end 49 inches from the rear wall. ST7 24 months
8.4.e. The designated accessible toilet is inaccessible because the side grab bar is obstructed by the toilet paper dispenser. ST8 24 months
8.4.f. The ambulatory stalls are inaccessible because one side grab bar in each stall is obstructed by the toilet paper dispenser. ST1 24 months.
8.5. WomenÕs Toilet Room with Stalls 2521    
8.5.a. The pull side of the door, which is accessed through a front approach, is inaccessible because it has only 5 inches of clear space on the latch side. D6 24 months
8.5.b. The designated accessible toilet is inaccessible because the side grab bar is obstructed by the toilet paper dispenser and the seat cover dispenser. ST8 24 months
8.5.c. The air dryer and paper towel dispenser protrude into the walkway and are not detectable to blind persons using a cane. AR8 24 months
8.5.d. The ambulatory stalls are inaccessible because the side grab bars in each stall are obstructed by the toilet paper dispenser and/or the seat cover dispenser. ST1 24 months.
8.6. Family Single-User Toilet Room 2522    
8.6.a. The door is inaccessible because it requires 15 pounds of force to open. D2 24 months
8.6.b. The toilet is inaccessible because the side grab bar is obstructed by the toilet paper dispenser. SU7 24 months
8.7. MenÕs Toilet Room with Stalls 2523    
8.7.a. The air dryers protrude into the walkway and are not detectable to blind persons using a cane. AR8 24 months
8.7.b. The designated accessible toilet is inaccessible because the side grab bar is obstructed by the toilet paper dispenser and the seat cover dispenser. ST8 24 months
8.7.c. The ambulatory stalls are inaccessible because the side grab bars are obstructed by the toilet paper dispenser and/or the seat cover dispenser, and one of the stalls is 35 inches wide. ST1 24 months
8.8. MenÕs Toilet Room with Stalls 2585    
8.8.a. No accessible coat hook has been provided. TR1 24 month
8.8.b. The urinal is inaccessible because the rim is 18½ inches high. TR20 24 month
8.8.c. The designated accessible toilet is inaccessible because the side grab bar is obstructed by the toilet paper dispenser. ST8 24 month
8.8.d. The designated accessible toilet is inaccessible because the side grab bar is mounted with the far end 48 inches from the rear wall. ST7 24 month
8.9. WomenÕs Toilet Room with Stalls 2586    
8.9.a. The air dryer protrudes into the walkway and is not detectable to blind persons using a cane. AR8 24 months
8.9.b. No accessible coat hook has been provided. TR1 24 months
8.9.c. The designated accessible toilet is inaccessible because the side grab bar is obstructed by the toilet paper dispenser. ST8 24 months
8.9.d. The designated accessible toilet is inaccessible because the side grab bar is mounted with the far end 49 inches from the rear wall. ST7 24 months
8.9.e. The ambulatory stall is inaccessible because the partitions are 38½ inches apart, one side grab bar is obstructed by the toilet paper dispenser, and the grab bars are mounted with the far ends 48 inches from the rear wall. ST1 24 months
8.10. Drinking Fountain near Room 2586: The drinking fountain is inaccessible because it has a spout that is 37 inches high. DF6 24 months
8.11. Elevator: The elevator is inaccessible because the hall lanterns do not signal once for up, twice for down or have voice. E11 24 months
8.12. Public Telephone: The telephone is inaccessible because it is 64½ inches high to the highest operable part and it lacks volume control signage. TT1 24 months
8.13. Drinking Fountain near Room 3010: The drinking fountain is inaccessible because it has a spout that is 37 inches high. DF6 24 months
8.14. WomenÕs Toilet Room with Stalls 3510    
8.14.a. The designated accessible toilet stall is inaccessible because it is 55½ inches wide. ST16 24 months
8.14.b. No accessible coat hook has been provided. TR1 24 months
8.14.c. The designated accessible toilet is inaccessible because the side grab bar is obstructed by the toilet paper dispenser. ST8 24 months
8.14.d. The designated accessible toilet is inaccessible because the side grab bar is mounted with the far end 48 inches from the rear wall. ST7 24 months
8.14.e. The air dryer protrudes into the walkway and is not detectable to blind persons using a cane. AR8 24 months
8.14.f. The ambulatory stall is inaccessible because the partitions are 38½ inches apart, one side grab bar is obstructed by the toilet paper dispenser, and the grab bars are mounted with the far ends 48 inches from the rear wall. ST1 24 months
8.15. MenÕs Toilet Room with Stalls 3511    
8.15.a. The air dryer protrudes into the walkway and is not detectable to blind persons using a cane. AR8 24 months
8.15.b. No accessible coat hook has been provided. TR1 24 months.
8.15.c. The urinal is inaccessible because the rim is 19 inches high. TR20 24 months
8.15.d. The designated accessible toilet is inaccessible because the top of the seat is 20 inches high. ST20 24 months
8.15.e. The designated accessible toilet is inaccessible because the side grab bar is obstructed by the toilet paper dispenser. ST8 24 months
8.15.f. The designated accessible toilet is inaccessible because the side grab bar is mounted with the far end 49 inches from the rear wall. ST7 24 months
9. Hillcrest Community Center, located at 10401 Hillcrest Road    
9.1. Parking    
9.1.a. The designated accessible parking is inaccessible because the signs are mounted too low. P6 30 months
9.1.b. The designated accessible parking is inaccessible because two of the designated accessible spaces and access aisles have slopes of between 4.1% and 8.7%. P7 30 months
9.2. Gymnasium    
9.2.a. The platform lift is inaccessible because it requires that a key be obtained from an employee before the lift can be operated. LF1 30 months
9.2.b. The platform lift is inaccessible because there is a 2 inch high change in level to enter the lift. LF2 30 months
9.2.c. The gymnasium is inaccessible because the underside of the stairs poses an overhead hazard. AR7 30 months
9.2.d. Although a designated accessible drinking fountain is provided, there is no drinking fountain provided for people who have difficulty bending or stooping. DF3 30 months
9.3. Lobby Vending Machine: The snack machine is inaccessible because the controls are 60½ inches high. TR5 30 months
9.4. Hallway: The fire extinguisher protrudes into the walkway and is not detectable to blind persons using a cane. AR8 30 months
9.5. Game Room Patio: The picnic tables are inaccessible because none provide the required knee space. PD6 30 months
9.6. MenÕs Locker Room    
9.6.a. The designated accessible toilet is inaccessible because its centerline is 19½ inches from the side wall. ST17 30 months
9.6.b. The shower is inaccessible because the shower spray unit hose is 57 inches long and the unit cannot be fixed to the wall. B11 30 months
9.6.c. The bench is inaccessible because it is 18 inches deep and 16 inches high and it does not provide clear floor space alongside to allow a transfer. LR1 30 months
9.7. WomenÕs Locker Room    
9.7.a. The designated accessible toilet is inaccessible because the top of the seat is 19½ inches high. ST20 30 months
9.7.b. The designated accessible toilet is inaccessible because its centerline is 19½ inches from the side wall. ST17 30 months
9.7.c. Although there are 7 toilet stalls, there is no ambulatory stall provided. ST1 30 months
9.7.d. The shower is inaccessible because the shower spray unit hose is 57 inches long and the unit cannot be fixed to the wall. B11 30 months
9.7.e. The bench is inaccessible because it is 18 inches deep and 16 inches high and it does not provide clear floor space alongside to allow a transfer. LR1 30 months
9.8. MenÕs Toilet Room with Stalls: The door is inaccessible because it requires more than 5 pounds of force to open. D2 30 months
9.9. WomenÕs Toilet Room with Stalls    
9.9.a. The door is inaccessible because it requires more than 5 pounds of force to open. D2 30 months
9.9.b. The designated accessible toilet is inaccessible because its centerline is 19½ inches from the side wall. ST17 30 months
9.9.c. The feminine products dispenser is inaccessible because the controls require twisting of the wrist to operate. TR3 30 months
9.10. Gymnasium Unisex Locker Room: The toilet is inaccessible because the side grab bar is mounted with the far end 52 inches from the rear wall. SU6 30 months
10. Kansas City North Community Center, located at 3930 N.E. Antioch Road    
10.1. Front Parking    
10.1.a. The designated accessible parking spaces are inaccessible because 2 of them are not level. P7 30 months
10.1.b. The designated accessible parking is inaccessible because the signs are mounted too low. P6 30 months
10.2. Rear Parking: The built-up curb ramp impermissibly extends into the required parking spaceÕs access aisle and the access aisle has a slope of 7.6%. AR4, P7 30 months
10.3. Lobby Counter: The counter is inaccessible because it is 39 inches high. C6 30 months
10.4. Lift to Gymnasium: The platform lift is inaccessible because it requires that a key be obtained from an employee before the lift can be operated. LF1 30 months
10.5. WomenÕs Toilet Room with Stalls    
10.5.a. The designated accessible toilet stall is inaccessible because it is 48 inches wide. ST16 30 months
10.5.b. The designated accessible toilet is inaccessible because the flush control is on the closed side. ST2 30 months
10.6. MenÕs Toilet Room with Stalls    
10.6.a. The toilet room sign is inaccessible because the centerline of the sign is mounted 52½ inches high. TR18 30 months
10.6.b. The lavatory is inaccessible because the bottom of the apron is 26½ inches high. TR11 30 months
10.6.c. The designated accessible toilet stall is inaccessible because it is 48 inches wide. ST16 30 months
10.6.d. The designated accessible toilet is inaccessible because the flush control is on the closed side. ST2 30 months
10.7. WomenÕs 1st Floor Locker Room    
10.7.a. The lavatory is inaccessible because the hot water pipes are not insulated or otherwise configured to protect against contact. TR12 30 months
10.7.b. The designated accessible toilet is inaccessible because its centerline is 21 inches from the side wall. ST17 30 months
10.7.c. The designated accessible toilet is inaccessible because the flush control is on the closed side. ST2 30 months
10.7.d. No accessible coat hook has been provided. TR1 30 months
10.7.e. The shower is inaccessible because the opening is along the narrow, 30 inch wide, dimension, and there are grab bars only on 2 walls that do not extend the full length of either wall. B8 30 months
10.7.f. The bench is inaccessible because it is 19 inches deep and it does not provide clear floor space alongside to allow a transfer. LR1 30 months
10.8. MenÕs 1st Floor Locker Room    
10.8.a. The lavatory is inaccessible because the hot water pipes are not insulated or otherwise configured to protect against contact. TR12 30 months
10.8.b. The designated accessible toilet is inaccessible because its centerline is 21 inches from the side wall. ST17 30 months
10.8.c. The designated accessible toilet is inaccessible because the flush control is on the closed side. ST2 30 months
10.8.d. The shower is inaccessible because the opening is along the narrow, 30 inch wide, dimension, and there are grab bars only on 2 walls that do not extend the full length of either wall. B8 30 months
10.8.e. The bench is inaccessible because it is 19 inches deep and it does not provide clear floor space alongside to allow a transfer. LR1 30 months
10.9. MenÕs Existing Locker Room next to Basketball Courts    
10.9.a. The locker room is inaccessible because there is insufficient turning space provided within the room. TR19 30 months
10.9.b. The bench is inaccessible because it is 19 inches deep and it does not provide clear floor space alongside to allow a transfer. LR1 30 months
10.9.c. The designated accessible stall is incorrectly configured as an ambulatory stall, and there is no standard accessible stall provided. ST15 30 months
10.9.d. The transfer shower is inaccessible because the controls are mounted on the far wall. B8 30 months
10.10. WomenÕs Existing Locker Room next to Basketball Courts    
10.10.a. The locker room is inaccessible because there is insufficient turning space provided within the room. TR19 30 months
10.10.b. The bench is inaccessible because it is 19 inches deep and it does not provide clear floor space alongside to allow a transfer. LR1 30 months
10.10.c. The designated accessible stall is incorrectly configured as an ambulatory stall, and there is no standard accessible stall provided. ST15 30 months
10.10.d. The transfer shower is inaccessible because the controls are mounted on the far wall. B8 30 months
10.11. Picnic Table by Rear Entrance: The picnic table is inaccessible because it does not provide the required knee space. PD6 30 months
10.12. Drinking Fountains    
10.12.a. Although designated accessible drinking fountains are provided, there is no drinking fountain provided for people who have difficulty bending or stooping. DF3 30 months
10.12.b. Each of the drinking fountains protrudes into the walkway and is not detectable to blind persons using a cane. AR8 30 months
11. Heart of America Golf Course, located in Swope Park at 7501 Blue River Road    
11.1. Parking: The parking lot, with a total of 167 parking spaces, is inaccessible because there are only 3 designated accessible parking spaces, there is no van accessible space, there are no access aisles provided, and the signs are mounted too low. This lot requires 1 van accessible space and 5 standard accessible spaces. P3 30 months
11.2. Entrance: The entrance door is inaccessible because there is a slope of 5% within the doorÕs required maneuvering clearance. D13 30 months
11.3. Payment Counter: The counter is inaccessible because it is 37¾ inches high. C6 30 months
11.4. Snack Bar: The counter is inaccessible because it is 42 inches high. C5 30 months
11.5. Soda Fountain: The soda fountain is inaccessible because it is mounted with the controls 58½ inches high. TR5 30 months
11.6. WomenÕs Locker Room    
11.6.a. The lavatory is inaccessible because the hot water pipes are not insulated or otherwise configured to protect against contact. TR12 30 months
11.6.b. No accessible coat hook has been provided. TR1 30 months
11.6.c. The designated accessible toilet is inaccessible because the rear grab bar is mounted 10 inches from the side wall. ST4 30 months
11.6.d. The designated accessible toilet is inaccessible because the rear grab bar is obstructed by the seat cover dispenser. ST5 30 months
11.6.e. The transfer shower is inaccessible because it is 37½ inches by 44 inches. B8 30 months
11.6.f. The bench is inaccessible because it is 12 inches deep, it does not provide clear floor space alongside to allow a transfer, and it is not attached at a wall. LR1 30 months
11.6.g. There is no accessible locker provided. LR3 30 months
11.7. MenÕs Locker Room    
11.7.a. The paper towel dispenser is inaccessible because it is mounted with the controls 56 inches high. TR5 30 months
11.7.b. The lavatory is inaccessible because the hot water pipes are not insulated or otherwise configured to protect against contact. TR12 30 months
11.7.c. The designated accessible toilet is inaccessible because the flush control is on the closed side. ST2 30 months
11.7.d. No accessible coat hook has been provided. TR1 30 months
11.7.e. The designated accessible toilet is inaccessible because the rear grab bar is mounted 10 inches from the side wall. ST4 30 months
11.7.f. The transfer shower is inaccessible because it is 37½ inches by 44 inches. B8 30 months
11.7.g. The bench is inaccessible because it is 12 inches deep, it is 16 inches high, it does not provide clear floor space alongside to allow a transfer, and it is not attached at a wall. LR1 30 months
11.7.h. There is no accessible locker provided. LR3 30 months

 