ATTACHMENT I: Modifications to Newly Constructed FacilitiesPlease Note: Paragraph 45 of the Settlement Agreement requires that within three months of the effective date of this Agreement, the City will provide signage as necessary to comply with 28 C.F.R. § 35.163(b), after having surveyed all facilities that are the subject of this Agreement for the purpose of identifying those that have multiple entrances not all of which are accessible. The chart below lists the facilities surveyed by the Department, the access issues identified during the survey, and the actions required to correct the access issues. Required actions are listed using an alphanumeric code. The key to the alphanumeric codes is provided in Attachment M to this Agreement. In order to ensure that the following spaces and elements in City facilities for which construction was commenced after January 26, 1992, are readily accessible to and usable by persons with disabilities, the City will take the actions referenced by the alphanumeric code and described in detail in Attachment M to this Settlement Agreement within the time periods specified below, which time periods will begin to run on the effective date of this Agreement. |
|||
Item # | Access Issue | Required Action | Completion Date |
---|---|---|---|
1. | 300 Wyandotte Parking Garage, located at 300 Wyandotte Street | ||
1.1. | Route | ||
1.1.a. | The route through the van access aisle is inaccessible because it is obstructed by a wheel stop. | AR1 | 18 months |
1.1.b. | The door into the building by the designated van accessible parking space is inaccessible because there is a slope of 4.3% within the door´s required maneuvering clearance. | D13 | 18 months |
2. | Auditorium Plaza Garage, located at 1220 Wyandotte Street | ||
2.1. | Parking | ||
2.1.a. | The parking lot, with a total of 975 parking spaces, is inaccessible because it only has 17 spaces designated as accessible. This lot requires 3 van accessible spaces and 17 standard accessible spaces. | P3 | 18 months |
2.1.b. | The designated accessible parking on level P2 is inaccessible because one of the spaces lacks vertical signage. | P6 | 18 months |
2.1.c. | The designated accessible parking is inaccessible because one of the spaces on level P2 is 91 inches wide and another is 88 inches wide, and one of the access aisles narrows to 33 inches wide. | P8 | 18 months |
2.1.d. | The designated accessible parking is inaccessible because one of the spaces on level P2 has a slope of 4.3% and a cross slope of 4.5% and 2 of the access aisles have slopes of 4.5% and 5.8% and cross slopes of 4.7% and 4.4% along one side. | P7 | 18 months |
2.2. | Route: Near 2H, the vent unit hanging from the ceiling protrudes into the walkway and is not detectable to blind persons using a cane. | AR8 | 18 months |
2.3. | Elevator | ||
2.3.a. | The elevator is inaccessible because the hall call buttons are mounted 41 inches high. | E3 | 18 months |
2.3.b. | The elevator is inaccessible because the doors do not automatically reopen without contact if obstructed. | E6 | 18 months |
3. | Health Department, located at 2400 Troost Avenue | ||
3.1. | Visitor Parking Lot | ||
3.1.a. | The designated van accessible parking space is inaccessible because the access aisle is 85 inches wide. | P8 | 30 months |
3.1.b. | The designated van accessible parking space is inaccessible because it has a cross slope of 5%. | P7 | 30 months |
3.2. | Auditorium/Employee Parking Lot | ||
3.2.a. | The parking lot, with a total of 201 parking spaces, is inaccessible because it only has 6 spaces designated as accessible. This lot requires 1 van accessible space and 6 standard accessible spaces. | P3 | 30 months |
3.2.b. | The designated van accessible parking space is inaccessible because it lacks van accessible signage. | P6 | 30 months |
3.2.c. | The parking lot is inaccessible because the designated accessible spaces have slopes and cross slopes between 3.8% and 7.3%. | P7 | 30 months |
3.2.d. | The parking lot is inaccessible because 4 of the designated accessible spaces have no access aisles. | P1 | 30 months |
3.2.e. | The curb ramp is inaccessible because it has a slope of 9.2% and an abrupt 1 inch high drop at the bottom. | AR5 | 30 months |
3.3. | Room 3300: The door is inaccessible because it requires 15 pounds of force to open. | D2 | 30 months |
3.4. | Suite 2300: The counter is inaccessible because it is 42 inches high. | C6 | 30 months |
3.5. | Passenger Elevators | ||
3.5.a. | The elevators are inaccessible because the hall lanterns do not emit an audible signal indicating when a car is answering a call. | E11 | 30 months |
3.5.b. | The elevators are inaccessible because, after reopening due to an obstruction, the doors stay open less than 20 seconds. | E6 | 30 months |
3.5.c. | The elevators are inaccessible because the car position indicators do not emit an audible signal as the car passes or stops at a floor. | E5 | 30 months |
3.5.d. | The elevators are inaccessible because the doors to the emergency controls require tight grasping to open. | E8 | 30 months |
3.6. | Freight Elevator | ||
3.6.a. | The elevator is inaccessible because the hall lanterns sound once whether the elevator is going up or down. | E11 | 30 months |
3.6.b. | The elevator is inaccessible because the door stays open for 3 seconds after notification that the car has arrived, and, after reopening due to an obstruction, the door stays open for 2 seconds. | E6 | 30 months |
3.6.c. | The elevator is inaccessible because the door to the emergency controls requires tight grasping to open. | E8 | 30 months |
3.7. | Drinking Fountain 4 East | ||
3.7.a. | The drinking fountain protrudes into the walkway and is not detectable to blind persons using a cane. | AR8 | 30 months |
3.7.b. | The drinking fountain is inaccessible because it has a spout that is 35 inches high. | DF6 | 30 months |
3.7.c. | Although a designated accessible drinking fountain is provided, there is no drinking fountain provided for people who have difficulty bending or stooping. | DF3 | 30 months |
3.8. | Drinking Fountains: Lobby, 1E, 2nd, 3rd, and 4th Floors: Although designated accessible drinking fountains are provided, there are no drinking fountains provided for people who have difficulty bending or stooping. | DF3 | 30 months |
3.9. | Drinking Fountains 3rd and 4th Floors East: The drinking fountains protrude into the walkway and are not detectable to blind persons using a cane. | AR8 | 30 months |
3.10. | 4th Floor Employee Women´s Single User Toilet Room | ||
3.10.a. | The toilet is inaccessible because the side grab bar is obstructed by the toilet paper dispenser. | SU7 | 30 months |
3.10.b. | The lavatory is inaccessible because there is no knee space provided. | TR11 | 30 months |
3.11. | 4th Floor Employee Men´s Single User Toilet Room | ||
3.11.a. | The toilet is inaccessible because the side grab bar is obstructed by the toilet paper and seat cover dispensers. | SU7 | 30 months |
3.11.b. | The lavatory is inaccessible because there is no knee space provided. | TR11 | 30 months |
3.12. | Public Women´s Toilet Room 4th Floor East: The door is inaccessible because it requires 12 pounds of force to open. | D2 | 30 months |
3.13. | Public Men´s Toilet Room 4th Floor East: The door is inaccessible because it requires 15 pounds of force to open. | D2 | 30 months |
3.14. | Public Women´s Toilet Room 3rd Floor East: The door is inaccessible because it requires 14 pounds of force to open. | D2 | 30 months |
3.15. | Public Men´s Toilet Room 3rd Floor East: The door is inaccessible because it requires 14 pounds of force to open. | D2 | 30 months |
3.16. | Employee Single User Toilet Room 3rd Floor West | ||
3.16.a. | The door is inaccessible because it requires 18 pounds of force to open. | D2 | 30 months |
3.16.b. | No accessible mirror has been provided. | TR14 | 30 months |
3.16.c. | The toilet room is inaccessible because there is insufficient turning space provided within the room. | TR19 | 30 months |
3.16.d. | The lavatory is inaccessible because the hot water pipes are not insulated or otherwise configured to protect against contact. | TR12 | 30 months |
3.16.e. | The toilet is inaccessible because the top of the seat is 16¼ inches high. | SU18 | 30 months |
3.16.f. | The toilet is inaccessible because its centerline is 13½ inches from the side wall. | SU15 | 30 months |
3.16.g. | The toilet is inaccessible because the side grab bar is obstructed by the toilet seat cover dispenser and the toilet paper dispenser. | SU7 | 30 months |
3.16.h. | There is no rear grab bar provided at the toilet. | SU2 | 30 months |
3.17. | Staff Women´s Single User Toilet Room 2nd Floor West | ||
3.17.a. | No accessible mirror has been provided. | TR14 | 30 months |
3.17.b. | The lavatory is inaccessible because the hot water pipes are not insulated or otherwise configured to protect against contact. | TR12 | 30 months |
3.17.c. | The toilet is inaccessible because the flush control is on the closed side. | SU1 | 30 months |
3.17.d. | The toilet is inaccessible because the side grab bar is obstructed by the toilet seat cover dispenser and the toilet paper dispenser. | SU7 | 30 months |
3.17.e. | The toilet is inaccessible because the grab bars are mounted 37 inches high. | SU11 | 30 months |
3.18. | Staff Men´s Single User Toilet Room 2nd Floor West | ||
3.18.a. | The toilet room sign is mounted on the hinge side of the door. | TR18 | 30 months |
3.18.b. | No accessible mirror has been provided. | TR14 | 30 months |
3.18.c. | The toilet room is inaccessible because there is insufficient turning space provided within the room. | TR19 | 30 months |
3.18.d. | The lavatory is inaccessible because the hot water pipes are not insulated or otherwise configured to protect against contact. | TR12 | 30 months |
3.18.e. | The toilet is inaccessible because the side grab bar is obstructed by the toilet paper dispenser. | SU7 | 30 months |
3.18.f. | The toilet is inaccessible because there is no rear grab bar provided. | SU2 | 30 months |
3.19. | STD Clinic Lobby Patients Only Single User Toilet Room | ||
3.19.a. | The toilet room sign has no raised or Braille characters. | TR18 | 30 months |
3.19.b. | No accessible mirror has been provided. | TR14 | 30 months |
3.19.c. | The lavatory is inaccessible because the hot water pipes are not insulated or otherwise configured to protect against contact. | TR12 | 30 months |
3.19.d. | The toilet is inaccessible because the side grab bar is obstructed by the toilet seat cover dispenser and the toilet paper dispenser. | SU7 | 30 months |
3.19.e. | The toilet is inaccessible because the rear grab bar is 24 inches long. | SU3 | 30 months |
3.19.f. | The toilet is inaccessible because the grab bars are mounted 37 inches high. | SU11 | 30 months |
3.20. | Staff Only Women´s Single User Toilet Room 2nd Floor East | ||
3.20.a. | No accessible mirror has been provided. | TR14 | 30 months |
3.20.b. | The lavatory is inaccessible because the hot water pipes are not insulated or otherwise configured to protect against contact. | TR12 | 30 months |
3.20.c. | The toilet is inaccessible because the flush control is on the closed side. | SU1 | 30 months |
3.20.d. | The toilet is inaccessible because its centerline is 19 inches from the side wall. | SU15 | 30 months |
3.20.e. | The toilet is inaccessible because the side grab bar is obstructed by the toilet seat cover dispenser and the toilet paper dispenser. | SU7 | 30 months |
3.20.f. | The toilet is inaccessible because there is no rear grab bar provided. | SU2 | 30 months |
3.21. | Staff Only Men´s Single User Toilet Room 2nd Floor East | ||
3.21.a. | The toilet room sign fell off the wall and was on the floor at the time of our onsite. | TR18 | 30 months |
3.21.b. | No accessible mirror has been provided. | TR14 | 30 months |
3.21.c. | The lavatory is inaccessible because the hot water pipes are not insulated or otherwise configured to protect against contact. | TR12 | 30 months |
3.21.d. | The toilet is inaccessible because the flush control is on the closed side. | SU1 | 30 months |
3.21.e. | The toilet is inaccessible because its centerline is 19 inches from the side wall. | SU15 | 30 months |
3.21.f. | The toilet is inaccessible because the top of the seat is 16½ inches high. | SU18 | 30 months |
3.21.g. | The toilet is inaccessible because there is no rear grab bar provided. | SU2 | 30 months |
3.22. | Health Care Trust Lobby Single User Toilet Room | ||
3.22.a. | No accessible mirror has been provided. | TR14 | 30 months |
3.22.b. | The soap dispenser is inaccessible because it is mounted with the controls 51½ inches high with only a forward reach provided. | TR5 | 30 months |
3.22.c. | The lavatory is inaccessible because its clear floor space is obstructed. | TR8 | 30 months |
3.22.d. | The toilet is inaccessible because the rear grab bar is 24 inches long. | SU3 | 30 months |
3.23. | Children´s Clinic Lobby Single User Toilet Room | ||
3.23.a. | The door is inaccessible because it requires 9 pounds of force to open. | D2 | 30 months |
3.23.b. | No accessible mirror has been provided. | TR14 | 30 months |
3.23.c. | The lavatory is inaccessible because the hot water pipes are not insulated or otherwise configured to protect against contact. | TR12 | 30 months |
3.23.d. | The toilet is inaccessible because the top of the seat is 19½ inches high. | SU18 | 30 months |
3.23.e. | The toilet is inaccessible because the side grab bar is obstructed by the toilet seat cover dispenser and the toilet paper dispenser. | SU7 | 30 months |
3.23.f. | The toilet is inaccessible because the rear grab bar is 24 inches long. | SU3 | 30 months |
3.24. | Women´s Toilet Room with Stalls 2nd Floor East | ||
3.24.a. | The door is inaccessible because it requires 10 pounds of force to open. | D2 | 30 months |
3.24.b. | No accessible mirror has been provided. | TR14 | 30 months |
3.24.c. | The designated accessible toilet is inaccessible because the side grab bar is obstructed by the toilet paper dispenser. | ST8 | 30 months |
3.25. | Men´s Toilet Room with Stalls 2nd Floor East | ||
3.25.a. | The door is inaccessible because it requires 10 pounds of force to open. | D2 | 30 months |
3.25.b. | No accessible mirror has been provided. | TR14 | 30 months |
3.25.c. | The lavatory is inaccessible because the top of the rim is 34½ inches high. | TR11 | 30 months |
3.26. | Health Care Trust Lobby Women´s Toilet Room with Stalls | ||
3.26.a. | The door is inaccessible because it requires 12 pounds of force to open. | D2 | 30 months |
3.26.b. | No accessible mirror has been provided. | TR14 | 30 months |
3.26.c. | The lavatory is inaccessible because the clear floor space is blocked by a moveable object. | TR8 | 30 months |
3.26.d. | The toilet is inaccessible because there is insufficient clear floor space provided. | ST18 | 30 months |
3.26.e. | The toilet is inaccessible because its centerline is 22½ inches from the side wall. | ST17 | 30 months |
3.26.f. | The toilet is inaccessible because the side grab bar is obstructed by the toilet paper dispenser. | ST8 | 30 months |
3.26.g. | The toilet is inaccessible because the side grab bar is mounted 36½ inches high. | ST12 | 30 months |
3.27. | Health Care Trust Lobby Men´s Toilet Room with Stalls | ||
3.27.a. | The door is inaccessible because it requires 14 pounds of force to open. | D2 | 30 months |
3.27.b. | No accessible mirror has been provided. | TR14 | 30 months |
3.27.c. | The lavatory is inaccessible because the top of the rim is 34¾ inches high. | TR11 | 30 months |
3.27.d. | The designated accessible toilet is inaccessible because the rear grab bar is obstructed by the toilet seat cover dispenser. | ST5 | 30 months |
3.28. | Health Care Trust Staff Only Women´s Toilet Room with Stalls | ||
3.28.a. | The door is inaccessible because it requires 12 pounds of force to open. | D2 | 30 months |
3.28.b. | The toilet is inaccessible because the side grab bar is obstructed by the toilet paper dispenser. | ST8 | 30 months |
3.29. | Health Care Trust Staff Only Men´s Toilet Room with Stalls | ||
3.29.a. | The door is inaccessible because it requires 14 pounds of force to open. | D2 | 30 months |
3.29.b. | No accessible mirror has been provided. | TR14 | 30 months |
3.29.c. | The lavatory is inaccessible because the top of the rim is 34½ inches high. | TR11 | 30 months |
3.30. | Route through Lobby: The route is inaccessible because the underside of the stairs creates an overhead hazard. | AR7 | 30 months |
3.31. | Central Registration Women´s Toilet Room with Stalls | ||
3.31.a. | The door is inaccessible because it requires 12 pounds of force to open. | D2 | 30 months |
3.31.b. | The toilet is inaccessible because its centerline is 19½ inches from the side wall. | ST17 | 30 months |
3.32. | Central Registration Men´s Toilet Room with Stalls | ||
3.32.a. | The door is inaccessible because it requires 14 pounds of force to open. | D2 | 30 months |
3.32.b. | The long shelf on the wall protrudes into the walkway and is not detectable to blind persons using a cane. | AR8 | 30 months |
3.33. | Auditorium Women´s Toilet Room: The door is inaccessible because it requires 12 pounds of force to open. | D2 | 30 months |
3.34. | Auditorium Men´s Toilet Room: The door is inaccessible because it requires 14 pounds of force to open. | D2 | 30 months |
3.35. | Women´s Locker Room Lower Level | ||
3.35.a. | The door is inaccessible because it requires 19 pounds of force to open. | D2 | 30 months |
3.35.b. | The toilet is inaccessible because the side grab bar is mounted with the far end 48 inches from the rear wall. | ST7 | 30 months |
3.35.c. | The shower is inaccessible because the clear floor space is 46½ inches wide, the grab bars are mounted 41 inches high, the curb is 2 inches high, and the fixed shower head is mounted more than 48 inches high. | B8 | 30 months |
3.35.d. | The 3 benches are inaccessible because only one is mounted against a wall, only one (a different one) is 48 inches long, and none are 24 inches deep. | LR1 | 30 months |
3.35.e. | The air dryer by the lockers protrudes into the walkway and is not detectable to blind persons using a cane. | AR8 | 30 months |
3.36. | Men´s Locker Room Lower Level | ||
3.36.a. | The door is inaccessible because it requires 15 pounds of force to open. | D2 | 30 months |
3.36.b. | The urinal is inaccessible because the rim is 25 inches high. | TR20 | 30 months |
3.36.c. | The toilet is inaccessible because the flush control is 46 inches high. | ST2 | 30 months |
3.36.d. | The toilet is inaccessible because the side grab bar is mounted with the far end 48 inches from the rear wall. | ST7 | 30 months |
3.36.e. | The shower is inaccessible because the clear floor space is 46 inches wide, the grab bars are mounted 41 inches high, the curb is 2 inches high, and the fixed shower head is mounted more than 48 inches high. | B8 | 30 months |
3.36.f. | The 3 benches are inaccessible because only one is mounted against a wall, and it is less than 48 inches long, and none are 24 inches deep. | LR1 | 30 months |
3.36.g. | The air dryer by the lockers protrudes into the walkway and is not detectable to blind persons using a cane. | AR8 | 30 months |
3.37. | Employee Lunch Room | ||
3.37.a. | The chips and candy vending machine is inaccessible because it is mounted with the controls 57 inches high. | TR5 | 30 months |
3.37.b. | The door is inaccessible because it requires 14 pounds of force to open. | D2 | 30 months |
3.38. | Biery Auditorium | ||
3.38.a. | The door is inaccessible because it requires 17 pounds of force to open. | D2 | 30 months |
3.38.b. | The security counter is inaccessible because it is 43 inches high. | C6 | 30 months |
3.38.c. | There is no signage informing the public of the availability of an assistive listening system. | AA3 | 30 months |
4. | Fire Station #14, located at 8300 N. Brighton Avenue | ||
4.1. | Parking: The designated accessible parking is inaccessible because it lacks “Van Accessible” signage. | P6 | 24 months |
4.2. | Lobby: The Pepsi vending machine is inaccessible because it is mounted with the controls 59½ inches high. | TR5 | 24 months |
4.3. | Elevators: The elevator is inaccessible because the hall call buttons are mounted 41 inches high. | E3 | 24 months |
4.4. | Single User Toilet Room Employee Area by Weight Room | ||
4.4.a. | The paper towel dispenser is inaccessible because it is mounted with the controls 55 inches high with a forward reach required. | TR5 | 24 months |
4.4.b. | The lavatory is inaccessible because the top of the rim is 37½ inches high, and there is no knee clearance provided. | TR11 | 24 months |
4.4.c. | The toilet is inaccessible because the top of the seat is 16 inches high. | SU18 | 24 months |
4.4.d. | The toilet paper dispenser is inaccessible because it is mounted 38½ inches from the rear wall. | SU17 | 24 months |
4.4.e. | The toilet is inaccessible because there are no grab bars provided. | SU10 | 24 months |
4.5. | Employee Single User Toilet and Shower Room | ||
4.5.a. | There is no accessible locker provided. | LR3 | 24 months |
4.5.b. | Although an audible alarm is provided in this facility, there is no visual alarm appliance in the toilet room. | TR21 | 24 months |
4.5.c. | No accessible towel hook has been provided. | TR1 | 24 months |
4.5.d. | The lavatory is inaccessible because the top of the rim is 37½ inches high, and there is no knee clearance provided. | TR11 | 24 months |
4.5.e. | The toilet is inaccessible because its centerline is 19 inches from the side wall. | SU15 | 24 months |
4.5.f. | The toilet is inaccessible because the top of the seat is 16 inches high. | SU18 | 24 months |
4.5.g. | The toilet is inaccessible because there are no grab bars provided. | SU10 | 24 months |
4.5.h. | There is no accessible shower provided. | B8 | 24 months |
4.6. | Second Floor Bunk | ||
4.6.a. | The door is inaccessible because it requires 30 pounds of force to open. | D2 | 24 months |
4.6.b. | The shelf is inaccessible because it is mounted 62¾ inches high. | S1 | 24 months |
4.7. | Bay Area Single User Toilet Room | ||
4.7.a. | The paper towel dispenser is inaccessible because it is mounted with the controls 57 inches high. | TR5 | 24 months |
4.7.b. | The lavatory is inaccessible because the bottom of the apron is 27½ inches high. | TR11 | 24 months |
4.7.c. | The lavatory is inaccessible because the hot water pipes are not insulated or otherwise configured to protect against contact. | TR12 | 24 months |
4.7.d. | The toilet is inaccessible because there are no grab bars provided. | SU10 | 24 months |
4.7.e. | There is no accessible locker provided. | LR3 | 24 months |
5. | Tony Aguirre Community Center, located at 2050 West Pennway Street | ||
5.1. | Parking: The designated accessible parking in the lower lot is inaccessible because the van access aisle is 62 inches wide. | P8 | 30 months |
5.2. | Route from Lower Parking Lot to Entrance | ||
5.2.a. | The curb ramp is inaccessible because it has a slope of 15.3%. | AR5 | 30 months |
5.2.b. | The route from the parking lot is inaccessible because there is a slope of 12.8% near the top of the curb ramp. | AR1 | 30 months |
5.3. | Interior Signage: The room signs throughout the facility are inaccessible because they are mounted with their centerlines 55 to 56 inches high. | TR18 | 30 months |
5.4. | Women´s 1st Floor Locker Room | ||
5.4.a. | The designated accessible toilet is inaccessible because its centerline is 19 inches from the side wall. | ST17 | 30 months |
5.4.b. | The door from the locker room to the pool is inaccessible because it requires 26 pounds of force to open. | D2 | 30 months |
5.4.c. | The bench is inaccessible because it is 12 inches deep and 19½ inches high and it does not provide clear floor space alongside to allow a transfer. | LR1 | 30 months |
5.5. | Ramp from Lobby to Pool: The ramp is inaccessible because it has a slope of up to 9%. | R3 | 30 months |
5.6. | 1st Floor Single User Family Changing Room 111 | ||
5.6.a. | The toilet is inaccessible because the side grab bar is is mounted with the far end 38 inches from the rear wall. | SU6 | 30 months |
5.6.b. | The toilet is inaccessible because there is a bench obstructing the clear floor space. | SU16 | 30 months |
5.6.c. | The bench is inaccessible because it is 16½ inches deep and is not fixed to the wall. | LR1 | 30 months |
5.6.d. | No accessible towel hook has been provided. | TR1 | 30 months |
5.7. | Men´s 1st Floor Locker Room: The door from the locker room to the pool is inaccessible because it requires 23 pounds of force to open. | D2 | 30 months |
5.8. | Ramp from Men´s Locker Room to Pool: The ramp is inaccessible because it lacks a level landing at the top and one handrail lacks an extension on the top. | R5 | 30 months |
5.9. | 2nd Floor Drinking Fountains: The drinking fountains protrude into the walkway and are not detectable to blind persons using a cane. | AR8 | 30 months |
5.10. | 2nd Floor Ramp from Gym to Toilet Room: The ramp is inaccessible because it has a slope between 8.5% and 9.1%. | R5 | 30 months |
5.11. | 2nd Floor Men´s Toilet Room with Stalls | ||
5.11.a. | The door is inaccessible because it requires 20 pounds of force to open. | D2 | 30 months |
5.11.b. | No accessible mirror has been provided. | TR14 | 30 months |
5.11.c. | The lavatory is inaccessible because it has twist-type hardware. | TR10 | 30 months |
5.11.d. | The designated accessible toilet is inaccessible because there is no side grab bar. | ST6 | 30 months |
5.12. | 2nd Floor Ramp from Lobby to Toilet Room: The ramp is inaccessible because it has a slope of 8.8%. | R5 | 30 months |
5.13. | 2nd Floor Women´s Toilet Room with Stalls | ||
5.13.a. | The door is inaccessible because it requires 17 pounds of force to open. | D2 | 30 months |
5.13.b. | No accessible mirror has been provided. | TR14 | 30 months |
6. | Brush Creek Community Center, located at 3801 Emanuel Cleaver II Boulevard | ||
6.1. | Parking | ||
6.1.a. | The designated accessible parking spaces and access aisles are inaccessible because they have slopes and cross slopes between 4.7% and 6.4% and the surface is cracked and broken. | P7 | 30 months |
6.1.b. | The curb ramp is inaccessible because it has a slope of up to 11.8%. | AR5 | 30 months |
6.2. | Drinking Fountains near Locker Room: The wall-mounted drinking fountain is inaccessible because it provides 26 inches of clear knee height. | DF5 | 30 months |
6.3. | Women´s Locker Room | ||
6.3.a. | The designated accessible toilet is inaccessible because the flush control is on the closed side. | ST2 | 30 months |
6.3.b. | The designated accessible toilet is inaccessible because the rear grab bar is mounted 12 inches from the side wall. | ST4 | 30 months |
6.3.c. | The roll-in shower is inaccessible because the shower head cannot be fixed to the wall, there are grab bars on only 2 walls, and the seat is 20½ inches high. | B8 | 30 months |
6.3.d. | The bench is inaccessible because it is 9½ inches deep and it does not provide clear floor space alongside to allow a transfer. | LR1 | 30 months |
6.3.e. | The door to the pool is inaccessible because it requires 26 pounds of force to open. | D2 | 30 months |
6.4. | Men´s Locker Room | ||
6.4.a. | The designated accessible toilet is inaccessible because its centerline is 15½ inches from the side wall. | ST17 | 30 months |
6.4.b. | The designated accessible toilet is inaccessible because the flush control is on the closed side. | ST2 | 30 months |
6.4.c. | The designated accessible toilet is inaccessible because there is no side grab bar. | ST6 | 30 months |
6.4.d. | The designated accessible toilet is inaccessible because the rear grab bar is mounted 12 inches from the side wall. | ST4 | 30 months |
6.4.e. | There is no accessible shower provided. | B8 | 30 months |
6.4.f. | The bench is inaccessible because it is 9½ inches wide. | LR1 | 30 months |
6.4.g. | There is no accessible locker provided. | LR3 | 30 months |
6.5. | Drinking Fountain near Meeting Room: The wall-mounted drinking fountain is inaccessible because it provides 26 inches of clear knee height. | DF5 | 30 months |
6.6. | Women´s Toilet Room with Stalls near Meeting Room | ||
6.6.a. | The designated accessible toilet is inaccessible because the flush control is on the closed side. | ST2 | 30 months |
6.6.b. | The designated accessible toilet is inaccessible because the rear grab bar is mounted 12 inches from the side wall. | ST4 | 30 months |
6.6.c. | The baby changing shelf protrudes into the walkway and is not detectable to blind persons using a cane. | AR8 | 30 months |
6.7. | Men´s Toilet Room with Stalls near Meeting Room | ||
6.7.a. | The designated accessible toilet is inaccessible because the rear grab bar is mounted 12 inches from the side wall. | ST4 | 30 months |
6.7.b. | The baby changing shelf protrudes into the walkway and is not detectable to blind persons using a cane. | AR8 | 30 months |
7. | Shoal Creek Golf, located at Shoal Creek Parkway | ||
7.1. | Parking: The parking lot, with a total of 208 parking spaces is inaccessible because there are only 6 accessible spaces. This lot requires 1 van accessible space and 6 standard accessible spaces. | P3 | 30 months |
7.2. | Bar: The bar counter is inaccessible because it is 42 inches high. | PD2 | 30 months |
7.3. | Women´s Toilet Room with Stalls by Banquet Hall | ||
7.3.a. | The door is inaccessible because it requires 9 pounds of force to open. | D2 | 30 months |
7.3.b. | The toilet paper dispenser in the designated accessible stall is inaccessible because it is mounted 39 inches from the rear wall. | ST19 | 30 months |
7.4. | Men´s Toilet Room with Stalls by Banquet Hall | ||
7.4.a. | The door is inaccessible because it requires 8 pounds of force to open. | D2 | 30 months |
7.4.b. | The toilet paper dispenser in the designated accessible stall is inaccessible because it is mounted 39 inches from the rear wall. | ST19 | 30 months |
7.5. | Women´s Locker Room: The bench is inaccessible because it does not provide clear floor space alongside to allow a transfer. | LR1 | 30 months |
7.6. | Men´s Locker Room | ||
7.6.a. | The door is inaccessible because it requires 13 pounds of force to open. | D2 | 30 months |
7.6.b. | The toilet paper dispenser in the designated accessible stall is inaccessible because it is mounted 39 inches from the rear wall. | ST19 | 30 months |
7.6.c. | The bench is inaccessible because it does not provide clear floor space alongside to allow a transfer. | LR1 | 30 months |
7.7. | Portable Toilets between Holes 6 and 7: The portable toilets contain a number of inaccessible elements and are not accessible to people with disabilities. | SU13 | 30 months |
8. | Safety Street, located at 2401 Campbell Street | ||
8.1. | Route to Main Entrance: The route is inaccessible because it has a slope of 8.7% and cross slope of 4.4%, with no ramp features. | AR1 | 24 months |
8.2. | Entrances: The building does not have directional signage posted at inaccessible entrances and does not have the International Symbol of Accessibility posted at accessible entrances. | D16 | 24 months |
8.3. | Main Entry Drinking Fountains: The drinking fountains protrude into the walkway and are not detectable to blind persons using a cane. | AR8 | 24 months |
8.4. | Side Hall Women´s Toilet Room with Stalls | ||
8.4.a. | The door is inaccessible because it requires 12 pounds of force to open. | D2 | 24 months |
8.4.b. | Although an audible alarm is provided in this facility, there is no visual alarm appliance in the toilet room. | TR21 | 24 months |
8.4.c. | The designated accessible toilet is inaccessible because the flush control is on the closed side. | ST2 | 24 months |
8.4.d. | The toilet is inaccessible because its centerline is 19 inches from the side wall. | ST17 | 24 months |
8.5. | Side Hall Men´s Toilet Room with Stalls | ||
8.5.a. | The door is inaccessible because it requires 11 pounds of force to open. | D2 | 24 months |
8.5.b. | Although an audible alarm is provided in this facility, there is no visual alarm appliance in the toilet room. | TR21 | 24 months |
8.5.c. | The toilet is inaccessible because its centerline is 19 inches from the side wall. | ST17 | 24 months |
9. | 11th and Oak Garage, located at 11th and Oak Streets | ||
9.1. | Parking: The parking garage, with a total of 1,395 parking spaces is inaccessible because it only has 2 van accessible spaces. This lot requires 3 van accessible spaces. | P3 | 12 months |
9.2. | Elevators on 10th Street and 11th Street Sides: The elevators are inaccessible because the buttons for the main entry floor are not designated by a raised star. | E4 | 12 months |
10. | Shoal Creek Patrol Division, located at 6885 NE Pleasant Valley Road | ||
10.1. | Front Parking Lot: The designated accessible parking is inaccessible because the signs are mounted too low and there is no “Van Accessible” signage. | P6 | 30 months |
10.2. | Community Room: The door is inaccessible because it requires 18 pounds of force to open. | D2 | 30 months |
10.3. | 1st Floor Women´s Single User Toilet Room | ||
10.3.a. | The door is inaccessible because it requires 30 pounds of force to open. | D2 | 30 months |
10.3.b. | The toilet is inaccessible because the side grab bar is obstructed by the trash receptacle. | SU8 | 30 months |
10.3.c. | The toilet is inaccessible because the rear grab bar is obstructed by the toilet seat cover dispenser. | SU4 | 30 months |
10.4. | 1st Floor Men´s Single User Toilet Room | ||
10.4.a. | The door is inaccessible because it requires 20 pounds of force to open. | D2 | 30 months |
10.4.b. | The toilet is inaccessible because the rear grab bar is obstructed by the toilet seat cover dispenser. | SU4 | 30 months |
10.5. | 1st Floor Single User Toilet Rooms Near Elevator | ||
10.5.a. | The toilet room signs have no raised or Braille characters. | TR18 | 30 months |
10.5.b. | The doors are inaccessible because they each require 18 to 20 pounds of force to open. | D2 | 30 months |
10.5.c. | The toilets are inaccessible because the rear grab bars are obstructed by the seat cover dispensers. | SU4 | 30 months |
10.5.d. | One of the toilets is inaccessible because the side grab bar is obstructed by the trash receptacle. | SU8 | 30 months |
10.6. | Adult Holding Cells: The toilet/lavatory combination contains a number of inaccessible elements and is not accessible to people with disabilities. | SU13 | 30 months |
10.7. | Single User Toilet Room near Juvenile Cells | ||
10.7.a. | The door is inaccessible because it requires 17 pounds of force to open. | D2 | 30 months |
10.7.b. | The toilet is inaccessible because the top of the seat is 15 inches high. | SU18 | 30 months |
10.8. | Vending Machine in Break Room: The vending machine is inaccessible because its controls are 57 inches high. | TR5 | 30 months |
10.9. | Women´s Lower Level Locker Room | ||
10.9.a. | The door is inaccessible because it requires 18 pounds of force to open. | D2 | 30 months |
10.9.b. | The toilet is inaccessible because its centerline is 20 inches from the side wall. | ST17 | 30 months |
10.9.c. | The toilet is inaccessible because the side grab bar is obstructed by the trash receptacle. | ST9 | 30 months |
10.9.d. | There is no accessible locker provided. | LR3 | 30 months |
10.10. | Men´s Locker Room Lower Level | ||
10.10.a. | The door is inaccessible because it requires 18 pounds of force to open. | D2 | 30 months |
10.10.b. | There is no accessible locker provided. | LR3 | 30 months |
10.10.c. | The toilet seat cover dispenser is inaccessible because it is mounted 50 inches high behind the toilet. | TR4 | 30 months |
10.10.d. | The designated accessible toilet is inaccessible because the rear grab bar is obstructed by the toilet seat cover dispenser. | ST5 | 30 months |
10.11. | Police Academy Side Parking Lot: The side parking lot, with a total of 218 parking spaces is inaccessible because the signs are mounted too low. | P6 | 30 months |
10.12. | Police Academy Auditorium: The doors are inaccessible because they require 15 to 20 pounds of force to open. | D2 | 30 months |
10.13. | Police Academy Main Level Lobby Drinking Fountains: The drinking fountains protrude into the walkway and are not detectable to blind persons using a cane. | AR8 | 30 months |
10.14. | Police Academy Main Level Toilet Rooms: The doors are inaccessible because they require between 17 and 20 pounds of force to open. | D2 | 30 months |
10.15. | Police Academy Administrative Office: The door is inaccessible because it requires 20 pounds of force to open. | D2 | 30 months |
10.16. | Police Academy Elevator Behind Auditorium: The elevator is inaccessible because the hall call buttons are centered 40 inches above the finished floor. | E3 | 30 months |
10.17. | Police Academy Drinking Fountain near F.A.T.S: The drinking fountains protrude into the walkway and are not detectable to blind persons using a cane. | AR8 | 30 months |
10.18. | Police Academy Drinking Fountains in Gym: The drinking fountains protrude into the walkway and are not detectable to blind persons using a cane. | AR8 | 30 months |
10.19. | Police Academy Library: The door is inaccessible because it requires 15 pounds of force to open. | D2 | 30 months |
10.20. | Police Academy Men´s and Women´s Staff and Student Locker Rooms | ||
10.20.a. | The doors are inaccessible because they require 16 to 25 pounds of force to open. | D2 | 30 months |
10.20.b. | The wall telephones protrude into the walkway and are not detectable to blind persons using a cane. | AR8 | 30 months |
10.20.c. | There is no accessible shower provided in any of the locker rooms. | B8 | 30 months |
10.20.d. | The benches are inaccessible because they are either 9½ or 20 inches deep, and some are less than 48 inches wide. | LR1 | 30 months |
10.20.e. | The counter in the women´s student locker room protrudes into the walkway and is not detectable to blind persons using a cane. | AR8 | 30 months |
10.21. | Rifle Range Parking | ||
10.21.a. | The designated accessible parking is inaccessible because the signs are mounted too low. | P6 | 30 months |
10.21.b. | The designated accessible parking is inaccessible because it has a slope of 4.5%. | P7 | 30 months |
10.22. | Rifle Range Lobby Toilet Rooms with Stalls: The doors are inaccessible because they require 10 to 15 pounds of force to open. | D2 | 30 months |
10.23. | Rifle Range Lobby Vending Machine: The vending machine is inaccessible because its controls are 57 inches high. | TR5 | 30 months |
10.24. | Rifle Range Firearms Lockers: The lockers are inaccessible because the controls require tight grasping and twisting of the wrist to operate. | TR3 | 30 months |
11. | Metro Patrol Division, located at 7601 Prospect Street | ||
11.1. | Parking: The parking lot, with a total of 216 parking spaces, is inaccessible because it has only 5 designated accessible parking spaces, and the designated accessible parking space in the rear has no access aisle or vertical sign. This lot requires 1 van accessible space and 6 standard accessible spaces. | P3 | 18 months |
11.2. | Rear Route to Building: There is no curb ramp provided in the rear of the building. | AR5 | 18 months |
11.3. | Lobby: The wall-mounted television protrudes into the walkway and is not detectable to blind persons using a cane. | AR8 | 18 months |
11.4. | Conference Room: The door is inaccessible because it requires 12 pounds of force to open. | D2 | 18 months |
11.5. | Upper Level Family Toilet Room | ||
11.5.a. | The door is inaccessible because it requires 22 pounds of force to open. | D2 | 18 months |
11.5.b. | No accessible coat hook has been provided. | TR1 | 18 months |
11.6. | Lobby Women´s Single User Toilet Room | ||
11.6.a. | The door is inaccessible because it requires 15 pounds of force to open. | D2 | 18 months |
11.6.b. | No accessible coat hook has been provided. | TR1 | 18 months |
11.7. | Lobby Men´s Single User Toilet Room | ||
11.7.a. | The door is inaccessible because it requires 18 pounds of force to open. | D2 | 18 months |
11.7.b. | No accessible coat hook has been provided. | TR1 | 18 months |
11.8. | Women´s Single User Toilet Room behind Lobby: The door is inaccessible because it requires 17 pounds of force to open. | D2 | 18 months |
11.9. | Wall-Mounted Television behind Lobby: The television protrudes into the walkway and is not detectable to blind persons using a cane. | AR8 | 18 months |
11.10. | Property Crimes | ||
11.10.a. | The door is inaccessible because it requires 19 pounds of force to open. | D2 | 18 months |
11.10.b. | The counter is inaccessible because it is 44½ inches high. | C6 | 18 months |
11.11. | Administrative Offices: The counter is inaccessible because it is 43 inches high. | C6 | 18 months |
11.12. | Break Room Counter: The counter is inaccessible because it is 43½ inches high. | C6 | 18 months |
11.13. | Women´s Single User Toilet Room near Break Room | ||
11.13.a. | The door is inaccessible because it requires 22 pounds of force to open. | D2 | 18 months |
11.13.b. | No accessible coat hook has been provided. | TR1 | 18 months |
11.14. | Men´s Single User Toilet Room near Break Room | ||
11.14.a. | The door is inaccessible because it requires 15 pounds of force to open. | D2 | 18 months |
11.14.b. | No accessible coat hook has been provided. | TR1 | 18 months |
11.15. | Lockers: The kitchen and firearm lockers throughout the facility are inaccessible because the controls require twisting of the wrist to operate. | TR3 | 18 months |
11.16. | Lower Level Break Room | ||
11.16.a. | The television protrudes into the walkway and is not detectable to blind persons using a cane. | AR8 | 18 months |
11.16.b. | The vending machine is inaccessible because its controls are 58 inches high. | TR5 | 18 months |
11.17. | Lower Level Telephone: The wall-mounted telephone near the locker rooms protrudes into the walkway and is not detectable to blind persons using a cane. | AR8 | 18 months |
11.18. | Adult Holding Cells: The toilet/lavatory combination contains a number of inaccessible elements and is not accessible to people with disabilities. | SU13 | 18 months |
11.19. | Juvenile Detention Single User Toilet Room: The door is inaccessible because it requires 22 pounds of force to open. | D2 | 18 months |
11.20. | Drinking Fountains in Lower Level Break Room: The drinking fountains protrude into the walkway and are not detectable to blind persons using a cane. | AR8 | 18 months |
11.21. | Women´s Locker Room Lower Level | ||
11.21.a. | The door is inaccessible because it requires 16 pounds of force to open. | D2 | 18 months |
11.21.b. | The wall-mounted telephone protrudes into the walkway and is not detectable to blind persons using a cane. | AR8 | 18 months |
11.21.c. | The roll-in shower is inaccessible because the transfer seat is 16¼ inches high and is not adjacent to the controls. | B10 | 18 months |
11.21.d. | The shower is inaccessible because there are grab bars on only 2 walls. | B8 | 18 months |
11.21.e. | The bench is inaccessible because it is 9½ inches deep and 23¼ inches high. | LR1 | 18 months |
11.21.f. | The designated accessible lockers are inaccessible because the controls are mounted 63 inches high. | TR5 | 18 months |
11.22. | Men´s Locker Room Lower Level | ||
11.22.a. | The door is inaccessible because it requires 12 pounds of force to open. | D2 | 18 months |
11.22.b. | The wall-mounted telephone protrudes into the walkway and is not detectable to blind persons using a cane. | AR8 | 18 months |
11.22.c. | The roll-in shower is inaccessible because the transfer seat is 16¼ inches high and is not adjacent to the controls. | B10 | 18 months |
11.22.d. | The shower is inaccessible because there are grab bars on only 2 walls. | B8 | 18 months |
11.22.e. | The designated accessible lockers are inaccessible because the controls are mounted 63 inches high. | TR5 | 18 months |
12. | KC Live Parking Garage, located at 151 E 13th Street | ||
12.1. | Parking Pay Stations: The pay stations are inaccessible because they are mounted with the highest controls 55 inches high. | TR5 | 12 months |
12.2. | Elevators | ||
12.2.a. | The lobby elevator is inaccessible because there is no hoistway signage provided on the 2nd floor. | E12 | 12 months |
12.2.b. | The lobby elevator is inaccessible because the hall call buttons are mounted 45½ inches high. | E3 | 12 months |
12.2.c. | The lobby elevator is inaccessible because the clearance between the car platform sill and the edge of the hoistway landing is 1½ inches. | E10 | 12 months |
13. | Heart of America Golf Course, located in Swope Park at 7501 Blue River Road | ||
13.1. | Parking: The parking lot, with a total of 167 parking spaces, is inaccessible because there are only 3 designated accessible parking spaces, there is no van accessible space, there are no access aisles provided, and the signs are mounted too low. This lot requires 1 van accessible space and 5 standard accessible spaces. | P3 | 30 months |
13.2. | Entrance: The entrance door is inaccessible because there is a slope of 5% within the door´s required maneuvering clearance. | D13 | 30 months |
13.3. | Payment Counter: The counter is inaccessible because it is 37¾ inches high. | C6 | 30 months |
13.4. | Snack Bar: The counter is inaccessible because it is 42 inches high. | C5 | 30 months |
13.5. | Soda Fountain: The soda fountain is inaccessible because it is mounted with the controls 58½ inches high. | TR5 | 30 months |
13.6. | Women´s Locker Room | ||
13.6.a. | The lavatory is inaccessible because the hot water pipes are not insulated or otherwise configured to protect against contact. | TR12 | 30 months |
13.6.b. | No accessible coat hook has been provided. | TR1 | 30 months |
13.6.c. | The designated accessible toilet is inaccessible because the rear grab bar is mounted 10 inches from the side wall. | ST4 | 30 months |
13.6.d. | The designated accessible toilet is inaccessible because the rear grab bar is obstructed by the seat cover dispenser. | ST5 | 30 months |
13.6.e. | The transfer shower is inaccessible because it is 37½ inches by 44 inches. | B8 | 30 months |
13.6.f. | The bench is inaccessible because it is 12 inches deep, it does not provide clear floor space alongside to allow a transfer, and it is not attached at a wall. | LR1 | 30 months |
13.6.g. | There is no accessible locker provided. | LR3 | 30 months |
13.7. | Men´s Locker Room | ||
13.7.a. | The paper towel dispenser is inaccessible because it is mounted with the controls 56 inches high. | TR5 | 30 months |
13.7.b. | The lavatory is inaccessible because the hot water pipes are not insulated or otherwise configured to protect against contact. | TR12 | 30 months |
13.7.c. | The designated accessible toilet is inaccessible because the flush control is on the closed side. | ST2 | 30 months |
13.7.d. | No accessible coat hook has been provided. | TR1 | 30 months |
13.7.e. | The designated accessible toilet is inaccessible because the rear grab bar is mounted 10 inches from the side wall. | ST4 | 30 months |
13.7.f. | The transfer shower is inaccessible because it is 37½ inches by 44 inches. | B8 | 30 months |
13.7.g. | The bench is inaccessible because it is 12 inches deep, it is 16 inches high, it does not provide clear floor space alongside to allow a transfer, and it is not attached at a wall. | LR1 | 30 months |
13.7.h. | There is no accessible locker provided. | LR3 | 30 months |
14. | Lakeside Nature Center, located in Swope Park at 4701 East Gregory Boulevard | ||
14.1. | Parking: The designated accessible parking is inaccessible because two of the designated accessible parking spaces lack vertical signage, the one existing sign is mounted too low, and there is no “Van Accessible” sign. | P6 | 24 months |
14.2. | Women´s Toilet Room with Stalls: No accessible coat hook has been provided. | TR1 | 24 months |
14.3. | Men´s Toilet Room with Stalls | ||
14.3.a. | The urinal is inaccessible because the flush control is 47 inches high. | TR20 | 24 months |
14.3.b. | No accessible coat hook has been provided. | TR1 | 24 months |
14.3.c. | The toilet paper dispenser in the designated accessible stall is inaccessible because it is mounted 39½ inches from the rear wall. | ST19 | 24 months |
14.4. | Ramp from Lobby to Lower Level: The ramp is inaccessible because it has a slope of up to 11.3% and a cross slope of up to 5.1% and the handrails lack extensions. | R5 | 24 months |
15. | Starlight Theater, located at 4600 Starlight Road | ||
15.1. | West Side Parking Adjacent to Theater | ||
15.1.a. | The parking lot is inaccessible because the designated accessible spaces and access aisles have slopes of up to 5.2 %. | P7 | 36 months |
15.1.b. | The curb ramp is inaccessible because the flared sides have slopes of more than 10%. | AR5 | 36 months |
15.2. | Northeast Zebra Lot Parking: The parking lot is inaccessible because the designated accessible spaces and access aisles have slopes of up to 7.7 %. | P7 | 36 months |
15.3. | North Women´s Toilet Room with Stalls | ||
15.3.a. | The toilet room sign is mounted on the door and has no raised or Braille characters. | TR18 | 36 months |
15.3.b. | The door is inaccessible because it has an opening width of 31 inches. | D25 | 36 months |
15.3.c. | The paper towel dispensers protrude into the walkway and are not detectable to blind persons using a cane. | AR8 | 36 months |
15.3.d. | Although there are 7 toilet stalls, there is no ambulatory stall provided. | ST1 | 36 months |
15.3.e. | The designated accessible toilet is inaccessible because the side grab bar is mounted with its far end 49 inches from the rear wall. | ST7 | 36 months |
15.3.f. | The designated accessible toilet is inaccessible because the rear grab bar is mounted 7 inches from the side wall. | ST4 | 36 months |
15.4. | North Men´s Toilet Room with Stalls | ||
15.4.a. | The toilet room sign is mounted on the door and has no raised or Braille characters. | TR18 | 36 months |
15.4.b. | The light switch is inaccessible because it is mounted 58 inches high. | TR5 | 36 months |
15.4.c. | The paper towel dispenser protrudes into the walkway and is not detectable to blind persons using a cane. | AR8 | 36 months |
15.4.d. | Although there are 7 toilet stalls, there is no ambulatory stall provided. | ST1 | 36 months |
15.4.e. | The designated accessible toilet is inaccessible because its centerline is 23½ inches from the side wall. | ST17 | 36 months |
15.4.f. | The designated accessible toilet is inaccessible because the side grab bar is 30 inches long. | ST7 | 36 months |
15.4.g. | The designated accessible toilet is inaccessible because the side grab bar is mounted 6 inches from the side wall on which it is mounted. | ST13 | 36 months |
15.5. | East Women´s Toilet Room with Stalls | ||
15.5.a. | The sanitary napkin dispenser is inaccessible because the controls require tight grasping and twisting of the wrist to operate. | TR3 | 36 months |
15.5.b. | The lavatory is inaccessible because the knee space is 21½ inches high. | TR11 | 36 months |
15.6. | East Men´s Toilet Room with Stalls: The lavatory is inaccessible because the knee space is 21½ inches high. | TR11 | 36 months |
15.7. | Administrative Office Women´s Toilet Room with Stalls: The door is inaccessible because it requires 15 pounds of force to open. | D2 | 36 months |
15.8. | Administrative Office Men´s Toilet Room with Stalls: The door is inaccessible because it requires 15 pounds of force to open. | D2 | 36 months |
15.9. | Stage Area Men´s Toilet Room with Stalls | ||
15.9.a. | The door is inaccessible because it requires 15 pounds of force to open. | D2 | 36 months |
15.9.b. | The toilet paper dispenser in the designated accessible stall is inaccessible because it is mounted 40 inches from the rear wall. | ST19 | 36 months |
15.10. | Stage Area Women´s Toilet Room with Stalls | ||
15.10.a. | The toilet paper dispenser in the designated accessible stall is inaccessible because it is mounted 38 inches from the rear wall. | ST19 | 36 months |
15.10.b. | The paper towel dispensers and feminine products dispenser protrude into the walkway and are not detectable to blind persons using a cane. | AR8 | 36 months |
15.11. | Counters | ||
15.11.a. | The northwest concession stand counter is inaccessible because it is 46 inches high. | C5 | 36 months |
15.11.b. | The bar and concession stand #4 counter is inaccessible because it is 42 inches high. | C5 | 36 months |
15.11.c. | The bar #3 counter is inaccessible because it is 42 inches high. | C5 | 36 months |
15.11.d. | The administrative office box office counter is inaccessible because it is 42 inches high. | C6 | 36 months |
15.11.e. | The administrative office box office counter protrudes into the walkway and is not detectable to blind persons using a cane. | AR8 | 36 months |
15.12. | Administrative Office Lobby Elevator: The elevator is inaccessible because the emergency system requires voice communication to operate. | E8 | 36 months |
15.13. | Epic Front Office Unisex Single User Toilet Room | ||
15.13.a. | The toilet room sign is mounted on the door. | TR18 | 36 months |
15.13.b. | The door is inaccessible because it requires 11 pounds of force to open. | D2 | 36 months |
15.13.c. | Although an audible alarm is provided in this facility, there is no visual alarm appliance in the toilet room. | TR21 | 36 months |
15.13.d. | The toilet is inaccessible because the flush control is on the closed side. | SU1 | 36 months |
15.13.e. | The toilet is inaccessible because the side grab bar is mounted with the far end 48 inches from the rear wall. | SU6 | 36 months |
15.13.f. | The toilet is inaccessible because the side grab bar is obstructed by the toilet paper dispenser. | SU7 | 36 months |
15.14. | Women´s Dressing Room Toilet Room with Stalls: The door is inaccessible because it requires 16 pounds of force to open. | D2 | 36 months |
15.15. | Star Women´s Single User Toilet Room: The toilet is inaccessible because there are no grab bars provided. | SU10 | 36 months |
15.16. | Men´s Dressing Room Toilet Room with Stalls: The door is inaccessible because it requires 16 pounds of force to open. | D2 | 36 months |
15.17. | Green Room Unisex Single User Toilet Rooms | ||
15.17.a. | The door of the room on the right is inaccessible because it requires 13 pounds of force to open. | D2 | 36 months |
15.17.b. | The toilet room on the left is inaccessible because there are no grab bars provided. | SU10 | 36 months |
15.18. | Chorus Rooms and Director´s Pavilion | ||
15.18.a. | The route to the chorus rooms is inaccessible because it can be accessed only via stairs. | AR2 | 36 months |
15.18.b. | The toilet rooms contain a number of inaccessible elements and are not accessible to people with disabilities. | ST14 | 36 months |
15.19. | Women´s Southwest Toilet Room with Stalls | ||
15.19.a. | The feminine products dispenser is inaccessible because the controls require tight grasping and twisting of the wrist to operate. | TR3 | 36 months |
15.19.b. | The designated accessible toilet is inaccessible because the flush control is on the closed side. | ST2 | 36 months |
15.19.c. | The ambulatory stall is inaccessible because the door is not self closing, the toilet paper dispenser is mounted 43 inches from the rear wall, and only one grab bar is provided. | ST1 | 36 months |
15.20. | Men´s Southwest Toilet Room with Stalls | ||
15.20.a. | The toilet paper dispenser in the designated accessible stall is inaccessible because it is mounted 42 inches from the rear wall. | ST19 | 36 months |
15.20.b. | The ambulatory stall is inaccessible because the door is not self closing and the toilet paper dispenser is mounted 43½ inches from the rear wall. | ST1 | 36 months |
15.21. | Men´s Middle West Toilet Room with Stalls | ||
15.21.a. | The toilet room sign is mounted above the door and has no raised or Braille characters. | TR18 | 36 months |
15.21.b. | The door is inaccessible because there is a 1 inch high threshold. | D22 | 36 months |
15.21.c. | The lavatory is inaccessible because it has twist-type hardware. | TR10 | 36 months |
15.21.d. | The urinal is inaccessible because the flush control is 46 inches high. | TR20 | 36 months |
15.21.e. | No accessible coat hook has been provided. | TR1 | 36 months |
15.21.f. | The designated accessible toilet is inaccessible because the side grab bar is obstructed by the toilet paper dispenser. | ST8 | 36 months |
15.21.g. | Although there are 8 toilet stalls, there is no ambulatory stall provided. | ST1 | 36 months |
15.22. | Women´s Middle West Toilet Room with Stalls | ||
15.22.a. | The toilet room sign is mounted above the door and has no raised or Braille characters. | TR18 | 36 months |
15.22.b. | The door is inaccessible because it requires more than 5 pounds of force to open. | D2 | 36 months |
15.22.c. | The door is inaccessible because knob hardware is used. | D1 | 36 months |
15.22.d. | The lavatory is inaccessible because it has twist-type hardware. | TR10 | 36 months |
15.22.e. | The designated accessible toilet is inaccessible because its centerline is 20 inches from the side wall. | ST17 | 36 months |
15.22.f. | The toilet paper dispenser in the designated accessible stall is inaccessible because it is mounted 38 inches from the rear wall. | ST19 | 36 months |
15.22.g. | The designated accessible toilet is inaccessible because the side grab bar is 36 inches long and is mounted 16 inches from the rear wall. | ST7 | 36 months |
15.22.h. | Although there are 14 toilet stalls, there is no ambulatory stall provided. | ST1 | 36 months |
15.23. | Seating Bowl | ||
15.23.a. | The seating area, containing 7,958 seats, is inaccessible because only 20 wheelchair seating locations are provided on accessible routes and all are located on the Terrace Level in the last row of the theater with no lines of sight provided over standing spectators. The rest of the designated wheelchair seating locations have slopes of up to 10.3% or are on routes that have slopes of up to 19.6% and cross slopes of up to 13.6%. A total of 81 wheelchair seating areas is required. | AA7 | 36 months |
15.23.b. | There is no accessible route connecting the wheelchair seating areas and the stage. | AA1 | 36 months |
15.23.c. | The seating area lacks fixed aisle seating without armrests. | AA2 | 36 months |
16. | Communications Center, located at 1111 Locust Street | ||
16.1. | Entrance | ||
16.1.a. | The route to the entrance is inaccessible because it contains three sets of stairs. | AR1 | 24 months |
16.1.b. | The stair handrails protrude into the walkway and are not detectable to blind persons using a cane. | AR8 | 24 months |
16.2. | Interior Signage: The signage provided is inaccessible because it is mounted above the doors and does not have raised and Braille characters. | D26 | 24 months |
16.3. | Elevators | ||
16.3.a. | The freight elevator is inaccessible because the hall call buttons are mounted 40½ inches high. | E3 | 24 months |
16.3.b. | Both elevators are inaccessible because the emergency controls are grouped at the top of the panel. | E9 | 24 months |
16.4. | Break Room 203 | ||
16.4.a. | The snack vending machines are inaccessible because the controls are more than 54 inches high. | TR5 | 24 months |
16.4.b. | The change machine is inaccessible because it is mounted with the return control 55 inches high. | TR5 | 24 months |
16.5. | Room 320 | ||
16.5.a. | The door is inaccessible because it requires 12 pounds of force to open. | D2 | 24 months |
16.5.b. | The counter is inaccessible because it is 46 inches high. | C6 | 24 months |
16.5.c. | The counter protrudes into the walkway and is not detectable to blind persons using a cane. | AR8 | 24 months |
16.5.d. | The wall-mounted information screen protrudes into the walkway and is not detectable to blind persons using a cane. | AR8 | 24 months |
16.6. | 3rd Floor Drinking Fountain: The drinking fountain is inaccessible because the flow of water is less than 4 inches high. | DF7 | 24 months |
16.7. | 3rd Floor Women´s Toilet Room with Stalls | ||
16.7.a. | The doors are inaccessible because they require 8 and 12 pounds of force to open. | D2 | 24 months |
16.7.b. | The paper towel and feminine products dispensers protrude into the walkway and are not detectable to blind persons using a cane. | AR8 | 24 months |
16.7.c. | The designated accessible toilet is inaccessible because the flush control is on the closed side. | ST2 | 24 months |
16.7.d. | The designated accessible toilet is inaccessible because the rear grab bar is obstructed by the toilet seat cover dispenser. | ST5 | 24 months |
16.7.e. | The toilet seat cover dispenser is inaccessible because it is mounted too high behind the toilet. | TR4 | 24 months |
16.7.f. | No accessible coat hook has been provided. | TR1 | 24 months |
16.8. | 3rd Floor Men´s Toilet Room with Stalls | AR8 | 24 months |
16.8.a. | The paper towel dispensers protrude into the walkway and are not detectable to blind persons using a cane. | AR8 | 24 months |
16.8.b. | The doors are inaccessible because they require 10 and 12 pounds of force to open. | D2 | 24 months |
16.8.c. | No accessible coat hook has been provided. | TR1 | 24 months |
16.9. | 3rd Floor Break Room Kitchen: The sink is inaccessible because there is no knee space provided. | S2 | 24 months |
16.10. | Room 428 | ||
16.10.a. | The counter is inaccessible because it is 46 inches high. | C6 | 24 months |
16.10.b. | The counter protrudes into the walkway and is not detectable to blind persons using a cane. | AR8 | 24 months |
16.11. | Break Room 445: The snack vending machine is inaccessible because the controls are 57½ inches high. | TR5 | 24 months |
16.12. | 4th Floor Drinking Fountain: The wall-mounted drinking fountains are inaccessible because one provides only 25½ inches of clear knee height and the other has a spout that is more than 36 inches high. | DF5 | 24 months |
16.13. | 4th Floor Women´s Toilet Room with Stalls | ||
16.13.a. | The toilet room sign is mounted on the door. | TR18 | 24 months |
16.13.b. | The doors are inaccessible because they require 11 and 8 pounds of force to open. | D2 | 24 months |
16.13.c. | The designated accessible toilet is inaccessible because the flush control is on the closed side. | ST2 | 24 months |
16.13.d. | The designated accessible toilet is inaccessible because the side grab bar is obstructed by the toilet seat cover dispenser. | ST9 | 24 months |
16.13.e. | No accessible coat hook has been provided. | TR1 | 24 months |
16.14. | 4th Floor Men´s Toilet Room with Stalls | ||
16.14.a. | The toilet room sign is mounted on the door. | TR18 | 24 months |
16.14.b. | The doors are inaccessible because they require 11 and 8 pounds of force to open. | D2 | 24 months |
16.14.c. | No accessible coat hook has been provided. | TR1 | 24 months |
16.15. | Training Room 506: The door is inaccessible because it requires 11 pounds of force to open. | D2 | 24 months |
16.16. | 5th Floor CSTAR Room | ||
16.16.a. | The door is inaccessible because it requires 7 pounds of force to open. | D2 | 24 months |
16.16.b. | The fire extinguisher just outside the door protrudes into the walkway and is not detectable to blind persons using a cane. | AR8 | 24 months |
16.17. | 5th Floor Drinking Fountains | DF3 | 24 months |
16.17.a. | Although three designated accessible drinking fountains are provided, there is no drinking fountain provided for people who have difficulty bending or stooping. | DF3 | 24 months |
16.17.b. | The third drinking fountain is inaccessible because it provides only 25½ inches of clear knee height. | DF5 | 24 months |
16.18. | 5th Floor Women´s Toilet Room with Stall 566 | ||
16.18.a. | The toilet room sign is mounted on the door. | TR18 | 24 months |
16.18.b. | The door is inaccessible because it requires 9 pounds of force to open. | D2 | 24 months |
16.18.c. | No accessible coat hook has been provided. | TR1 | 24 months |
16.19. | 5th Floor Men´s Toilet Room with Stall 567 | ||
16.19.a. | The toilet room sign is mounted on the door. | TR18 | 24 months |
16.19.b. | The door is inaccessible because it requires 10 pounds of force to open. | D2 | 24 months |
16.19.c. | The designated accessible toilet is inaccessible because the flush control is on the closed side. | ST2 | 24 months |
16.19.d. | The designated accessible toilet is inaccessible because the side grab bar is obstructed by the toilet seat cover dispenser. | ST9 | 24 months |
16.19.e. | No accessible coat hook has been provided. | TR1 | 24 months |
16.19.f. | The urinal is inaccessible because the clear floor space is 28 inches wide. | TR20 | 24 months |
16.20. | Exercise Room 532 | ||
16.20.a. | The door is inaccessible because it requires 8 pounds of force to open. | D2 | 24 months |
16.20.b. | The paper towels, hand sanitizer, and telephone are inaccessible because they are mounted with the controls 57, 59, and 60 inches high, respectively. | TR5 | 24 months |
16.20.c. | The paper towel dispenser protrudes into the walkway and is not detectable to blind persons using a cane. | AR8 | 24 months |
16.21. | Kitchen Room 534: The sink is inaccessible because it does not provide knee clearance. | S2 | 24 months |
16.22. | Kitchen Room 542: The sink is inaccessible because it does not provide knee clearance. | S2 | 24 months |
16.23. | Break Room 517 | ||
16.23.a. | The sink is inaccessible because it does not provide knee clearance. | S2 | 24 months |
16.23.b. | The vending machine and telephone are inaccessible because they are mounted with the controls 58 and 59 inches high, respectively. | TR5 | 24 months |
16.24. | KCFD Communication Center: The door is inaccessible because it requires 15 pounds of force to open. | D2 | 24 months |
16.25. | Northeast Door Leaving Fire Area: The door is inaccessible because it requires 11 pounds of force to open. | D2 | 24 months |
16.26. | Northeast Door to Police Dispatch: The door is inaccessible because it requires 10 pounds of force to open. | D2 | 24 months |
16.27. | 911 Dispatch: The entrance door and the door out of the 911 hallway are inaccessible because they require 12 and 7 pounds of force to open, respectively. | D2 | 24 months |
16.28. | Women´s Locker Room 547 | ||
16.28.a. | The locker room sign is mounted on the door. | TR18 | 24 months |
16.28.b. | The door is inaccessible because it requires 10 pounds of force to open. | D2 | 24 months |
16.28.c. | The coat rack protrudes into the walkway and is not detectable to blind persons using a cane. | AR8 | 24 months |
16.28.d. | The designated accessible toilet is inaccessible because the side grab bar is obstructed by the toilet seat cover dispenser. | ST9 | 24 months |
16.28.e. | No accessible coat hook has been provided. | TR1 | 24 months |
16.28.f. | The shower is inaccessible because the controls require twisting of the wrist to operate. | TR3 | 24 months |
16.28.g. | The shower is inaccessible because the shower spray unit hose is 57 inches long. | B11 | 24 months |
16.28.h. | The bench is inaccessible because it is 9½ inches deep and is not attached at a wall. | LR1 | 24 months |
16.29. | Men´s Locker Room 543 | ||
16.29.a. | The locker room sign is mounted on the door. | TR18 | 24 months |
16.29.b. | The doors are inaccessible because they each require 8 pounds of force to open. | D2 | 24 months |
16.29.c. | The designated accessible toilet is inaccessible because the flush control is on the closed side. | ST2 | 24 months |
16.29.d. | The designated accessible toilet is inaccessible because the side grab bar is obstructed by the toilet seat cover dispenser. | ST9 | 24 months |
16.29.e. | No accessible coat hook has been provided. | TR1 | 24 months |
16.29.f. | The shower is inaccessible because the controls require twisting of the wrist to operate. | TR3 | 24 months |
16.29.g. | The designated accessible shower is inaccessible because the clear floor space extends only 4 inches beyond the shower wall on which the seat is mounted. | B8 | 24 months |
16.29.h. | The bench is inaccessible because it is 9½ inches deep and is not attached at a wall. | LR1 | 24 months |
16.30. | Women´s Locker Room 523 | ||
16.30.a. | The locker room sign is mounted on the door. | TR18 | 24 months |
16.30.b. | The door is inaccessible because it requires 7 pounds of force to open. | D2 | 24 months |
16.30.c. | The shelf protrudes into the walkway and is not detectable to blind persons using a cane. | AR8 | 24 months |
16.30.d. | The coat rack protrudes into the walkway and is not detectable to blind persons using a cane. | AR8 | 24 months |
16.30.e. | The designated accessible toilet is inaccessible because the flush control is on the closed side. | ST2 | 24 months |
16.30.f. | The designated accessible toilet is inaccessible because the side grab bar is obstructed by the toilet seat cover dispenser. | ST9 | 24 months |
16.30.g. | No accessible coat hook has been provided. | TR1 | 24 months |
16.30.h. | The shower is inaccessible because the controls require twisting of the wrist to operate. | TR3 | 24 months |
16.30.i. | The bench is inaccessible because it is 9½ inches deep and is not attached at a wall. | LR1 | 24 months |
16.31. | Men´s Locker Room 529 | ||
16.31.a. | The locker room sign is mounted on the door. | TR18 | 24 months |
16.31.b. | The doors are inaccessible because they each require between 7 and 9 pounds of force to open. | D2 | 24 months |
16.31.c. | The coat rack protrudes into the walkway and is not detectable to blind persons using a cane. | AR8 | 24 months |
16.31.d. | The designated accessible toilet is inaccessible because the side grab bar is obstructed by the toilet seat cover dispenser. | ST9 | 24 months |
16.31.e. | No accessible coat hook has been provided. | TR1 | 24 months |
16.31.f. | The shower is inaccessible because the controls require twisting of the wrist to operate. | TR3 | 24 months |
16.31.g. | The bench is inaccessible because it is 9½ inches deep and is not attached at a wall. | LR1 | 24 months |
16.32. | Conference Room 573: The door is inaccessible because it requires 6 pounds of force to open. | D2 | 24 months |
17. | Southeast Community Center, located at 4201 East 63rd Street | ||
17.1. | Parking: The parking lot, with a total of 157 parking spaces, is inaccessible because it has no van accessible space. This lot requires 1 van accessible space and 5 standard accessible spaces. | P3 | 24 months |
17.2. | Entrance: The building does not have directional signage posted at inaccessible entrances and does not have the International Symbol of Accessibility posted at accessible entrances. | D16 | 24 months |
17.3. | Interior Doors: The doors throughout the facility are inaccessible because they require more than 5 pounds of force to open. | D2 | 24 months |
17.4. | 1st Floor Drinking Fountain next to Toilet Room: The drinking fountain is inaccessible because the controls require 13 pounds of force to operate. | DF2 | 24 months |
17.5. | 1st Floor Drinking Fountain in Gym | ||
17.5.a. | The drinking fountain is inaccessible because the controls require 16½ pounds of force to operate. | DF2 | 24 months |
17.5.b. | The wall-mounted drinking fountain is inaccessible because it provides only 25½ inches of clear knee height. | DF5 | 24 months |
17.5.c. | The high drinking fountain protrudes into the walkway and is not detectable to blind persons using a cane. | AR8 | 24 months |
17.6. | Game Room: The pull side of the door, which is accessed through a front approach, is inaccessible because it has only 17 inches of clear space on the latch side. | D6 | 24 months |
17.7. | Front Desk Vending Machines: The snack machine is inaccessible because the controls are 57½ inches high. | TR5 | 24 months |
17.8. | Weight Room: The fire extinguisher protrudes into the walkway and is not detectable to blind persons using a cane. | AR8 | 24 months |
17.9. | Lobby Men´s Toilet Room with Stalls: The toilet is inaccessible because the side grab bar is mounted 36½ inches high. | ST12 | 24 months |
17.10. | Lobby Women´s Toilet Room with Stalls | ||
17.10.a. | The feminine products dispenser is inaccessible because the controls require right grasping and twisting of the wrist to operate. | TR3 | 24 months |
17.10.b. | The lavatory is inaccessible because the bottom of the apron is 28¼ inches high. | TR11 | 24 months |
17.11. | Elevator | ||
17.11.a. | The elevator is inaccessible because the hall call buttons are mounted 43½ inches high. | E3 | 24 months |
17.11.b. | The elevator is inaccessible because the hoistway signage is mounted 61 inches high. | E12 | 24 months |
17.11.c. | The elevator is inaccessible because the car control button for the main entry floor is not designated by a raised star. | E4 | 24 months |
17.12. | Women´s Locker Room | ||
17.12.a. | The lavatory is inaccessible because the bottom of the apron is 28 inches high. | TR11 | 24 months |
17.12.b. | The feminine products dispenser protrudes into the walkway and is not detectable to blind persons using a cane. | AR8 | 24 months |
17.12.c. | No accessible towel hook has been provided. | TR1 | 24 months |
17.13. | Men´s Locker Room: The lavatory is inaccessible because the bottom of the apron is 28 inches high. | TR11 | 24 months |
17.14. | Unisex Family Locker Room Near Pool | ||
17.14.a. | The lavatory is inaccessible because the top of the rim is 34½ inches high. | TR11 | 24 months |
17.14.b. | No accessible coat hook has been provided. | TR1 | 24 months |
17.14.c. | The transfer shower is inaccessible because no grab bars are provided. | B9 | 24 months |
17.14.d. | The bench is inaccessible because it is less than 24 inches deep. | LR1 | 24 months |
Project Civic Access | archive.ADA.gov Home Page