ATTACHMENT I: Modifications to Newly Constructed Facilities

Please Note: Paragraph 45 of the Settlement Agreement requires that within three months of the effective date of this Agreement, the City will provide signage as necessary to comply with 28 C.F.R. § 35.163(b), after having surveyed all facilities that are the subject of this Agreement for the purpose of identifying those that have multiple entrances not all of which are accessible. The chart below lists the facilities surveyed by the Department, the access issues identified during the survey, and the actions required to correct the access issues.

Required actions are listed using an alphanumeric code. The key to the alphanumeric codes is provided in Attachment M to this Agreement. In order to ensure that the following spaces and elements in City facilities for which construction was commenced after January 26, 1992, are readily accessible to and usable by persons with disabilities, the City will take the actions referenced by the alphanumeric code and described in detail in Attachment M to this Settlement Agreement within the time periods specified below, which time periods will begin to run on the effective date of this Agreement.

Item # Access Issue Required Action Completion Date
1. 300 Wyandotte Parking Garage, located at 300 Wyandotte Street    
1.1. Route    
1.1.a. The route through the van access aisle is inaccessible because it is obstructed by a wheel stop. AR1 18 months
1.1.b. The door into the building by the designated van accessible parking space is inaccessible because there is a slope of 4.3% within the door´s required maneuvering clearance. D13 18 months
2. Auditorium Plaza Garage, located at 1220 Wyandotte Street    
2.1. Parking    
2.1.a. The parking lot, with a total of 975 parking spaces, is inaccessible because it only has 17 spaces designated as accessible. This lot requires 3 van accessible spaces and 17 standard accessible spaces. P3 18 months
2.1.b. The designated accessible parking on level P2 is inaccessible because one of the spaces lacks vertical signage. P6 18 months
2.1.c. The designated accessible parking is inaccessible because one of the spaces on level P2 is 91 inches wide and another is 88 inches wide, and one of the access aisles narrows to 33 inches wide. P8 18 months
2.1.d. The designated accessible parking is inaccessible because one of the spaces on level P2 has a slope of 4.3% and a cross slope of 4.5% and 2 of the access aisles have slopes of 4.5% and 5.8% and cross slopes of 4.7% and 4.4% along one side. P7 18 months
2.2. Route: Near 2H, the vent unit hanging from the ceiling protrudes into the walkway and is not detectable to blind persons using a cane. AR8 18 months
2.3. Elevator    
2.3.a. The elevator is inaccessible because the hall call buttons are mounted 41 inches high. E3 18 months
2.3.b. The elevator is inaccessible because the doors do not automatically reopen without contact if obstructed. E6 18 months
3. Health Department, located at 2400 Troost Avenue    
3.1. Visitor Parking Lot    
3.1.a. The designated van accessible parking space is inaccessible because the access aisle is 85 inches wide. P8 30 months
3.1.b. The designated van accessible parking space is inaccessible because it has a cross slope of 5%. P7 30 months
3.2. Auditorium/Employee Parking Lot    
3.2.a. The parking lot, with a total of 201 parking spaces, is inaccessible because it only has 6 spaces designated as accessible. This lot requires 1 van accessible space and 6 standard accessible spaces. P3 30 months
3.2.b. The designated van accessible parking space is inaccessible because it lacks van accessible signage. P6 30 months
3.2.c. The parking lot is inaccessible because the designated accessible spaces have slopes and cross slopes between 3.8% and 7.3%. P7 30 months
3.2.d. The parking lot is inaccessible because 4 of the designated accessible spaces have no access aisles. P1 30 months
3.2.e. The curb ramp is inaccessible because it has a slope of 9.2% and an abrupt 1 inch high drop at the bottom. AR5 30 months
3.3. Room 3300: The door is inaccessible because it requires 15 pounds of force to open. D2 30 months
3.4. Suite 2300: The counter is inaccessible because it is 42 inches high. C6 30 months
3.5. Passenger Elevators    
3.5.a. The elevators are inaccessible because the hall lanterns do not emit an audible signal indicating when a car is answering a call. E11 30 months
3.5.b. The elevators are inaccessible because, after reopening due to an obstruction, the doors stay open less than 20 seconds. E6 30 months
3.5.c. The elevators are inaccessible because the car position indicators do not emit an audible signal as the car passes or stops at a floor. E5 30 months
3.5.d. The elevators are inaccessible because the doors to the emergency controls require tight grasping to open. E8 30 months
3.6. Freight Elevator    
3.6.a. The elevator is inaccessible because the hall lanterns sound once whether the elevator is going up or down. E11 30 months
3.6.b. The elevator is inaccessible because the door stays open for 3 seconds after notification that the car has arrived, and, after reopening due to an obstruction, the door stays open for 2 seconds. E6 30 months
3.6.c. The elevator is inaccessible because the door to the emergency controls requires tight grasping to open. E8 30 months
3.7. Drinking Fountain 4 East    
3.7.a. The drinking fountain protrudes into the walkway and is not detectable to blind persons using a cane. AR8 30 months
3.7.b. The drinking fountain is inaccessible because it has a spout that is 35 inches high. DF6 30 months
3.7.c. Although a designated accessible drinking fountain is provided, there is no drinking fountain provided for people who have difficulty bending or stooping. DF3 30 months
3.8. Drinking Fountains: Lobby, 1E, 2nd, 3rd, and 4th Floors: Although designated accessible drinking fountains are provided, there are no drinking fountains provided for people who have difficulty bending or stooping. DF3 30 months
3.9. Drinking Fountains 3rd and 4th Floors East: The drinking fountains protrude into the walkway and are not detectable to blind persons using a cane. AR8 30 months
3.10. 4th Floor Employee Women´s Single User Toilet Room    
3.10.a. The toilet is inaccessible because the side grab bar is obstructed by the toilet paper dispenser. SU7 30 months
3.10.b. The lavatory is inaccessible because there is no knee space provided. TR11 30 months
3.11. 4th Floor Employee Men´s Single User Toilet Room    
3.11.a. The toilet is inaccessible because the side grab bar is obstructed by the toilet paper and seat cover dispensers. SU7 30 months
3.11.b. The lavatory is inaccessible because there is no knee space provided. TR11 30 months
3.12. Public Women´s Toilet Room 4th Floor East: The door is inaccessible because it requires 12 pounds of force to open. D2 30 months
3.13. Public Men´s Toilet Room 4th Floor East: The door is inaccessible because it requires 15 pounds of force to open. D2 30 months
3.14. Public Women´s Toilet Room 3rd Floor East: The door is inaccessible because it requires 14 pounds of force to open. D2 30 months
3.15. Public Men´s Toilet Room 3rd Floor East: The door is inaccessible because it requires 14 pounds of force to open. D2 30 months
3.16. Employee Single User Toilet Room 3rd Floor West    
3.16.a. The door is inaccessible because it requires 18 pounds of force to open. D2 30 months
3.16.b. No accessible mirror has been provided. TR14 30 months
3.16.c. The toilet room is inaccessible because there is insufficient turning space provided within the room. TR19 30 months
3.16.d. The lavatory is inaccessible because the hot water pipes are not insulated or otherwise configured to protect against contact. TR12 30 months
3.16.e. The toilet is inaccessible because the top of the seat is 16¼ inches high. SU18 30 months
3.16.f. The toilet is inaccessible because its centerline is 13½ inches from the side wall. SU15 30 months
3.16.g. The toilet is inaccessible because the side grab bar is obstructed by the toilet seat cover dispenser and the toilet paper dispenser. SU7 30 months
3.16.h. There is no rear grab bar provided at the toilet. SU2 30 months
3.17. Staff Women´s Single User Toilet Room 2nd Floor West    
3.17.a. No accessible mirror has been provided. TR14 30 months
3.17.b. The lavatory is inaccessible because the hot water pipes are not insulated or otherwise configured to protect against contact. TR12 30 months
3.17.c. The toilet is inaccessible because the flush control is on the closed side. SU1 30 months
3.17.d. The toilet is inaccessible because the side grab bar is obstructed by the toilet seat cover dispenser and the toilet paper dispenser. SU7 30 months
3.17.e. The toilet is inaccessible because the grab bars are mounted 37 inches high. SU11 30 months
3.18. Staff Men´s Single User Toilet Room 2nd Floor West    
3.18.a. The toilet room sign is mounted on the hinge side of the door. TR18 30 months
3.18.b. No accessible mirror has been provided. TR14 30 months
3.18.c. The toilet room is inaccessible because there is insufficient turning space provided within the room. TR19 30 months
3.18.d. The lavatory is inaccessible because the hot water pipes are not insulated or otherwise configured to protect against contact. TR12 30 months
3.18.e. The toilet is inaccessible because the side grab bar is obstructed by the toilet paper dispenser. SU7 30 months
3.18.f. The toilet is inaccessible because there is no rear grab bar provided. SU2 30 months
3.19. STD Clinic Lobby Patients Only Single User Toilet Room    
3.19.a. The toilet room sign has no raised or Braille characters. TR18 30 months
3.19.b. No accessible mirror has been provided. TR14 30 months
3.19.c. The lavatory is inaccessible because the hot water pipes are not insulated or otherwise configured to protect against contact. TR12 30 months
3.19.d. The toilet is inaccessible because the side grab bar is obstructed by the toilet seat cover dispenser and the toilet paper dispenser. SU7 30 months
3.19.e. The toilet is inaccessible because the rear grab bar is 24 inches long. SU3 30 months
3.19.f. The toilet is inaccessible because the grab bars are mounted 37 inches high. SU11 30 months
3.20. Staff Only Women´s Single User Toilet Room 2nd Floor East    
3.20.a. No accessible mirror has been provided. TR14 30 months
3.20.b. The lavatory is inaccessible because the hot water pipes are not insulated or otherwise configured to protect against contact. TR12 30 months
3.20.c. The toilet is inaccessible because the flush control is on the closed side. SU1 30 months
3.20.d. The toilet is inaccessible because its centerline is 19 inches from the side wall. SU15 30 months
3.20.e. The toilet is inaccessible because the side grab bar is obstructed by the toilet seat cover dispenser and the toilet paper dispenser. SU7 30 months
3.20.f. The toilet is inaccessible because there is no rear grab bar provided. SU2 30 months
3.21. Staff Only Men´s Single User Toilet Room 2nd Floor East    
3.21.a. The toilet room sign fell off the wall and was on the floor at the time of our onsite. TR18 30 months
3.21.b. No accessible mirror has been provided. TR14 30 months
3.21.c. The lavatory is inaccessible because the hot water pipes are not insulated or otherwise configured to protect against contact. TR12 30 months
3.21.d. The toilet is inaccessible because the flush control is on the closed side. SU1 30 months
3.21.e. The toilet is inaccessible because its centerline is 19 inches from the side wall. SU15 30 months
3.21.f. The toilet is inaccessible because the top of the seat is 16½ inches high. SU18 30 months
3.21.g. The toilet is inaccessible because there is no rear grab bar provided. SU2 30 months
3.22. Health Care Trust Lobby Single User Toilet Room    
3.22.a. No accessible mirror has been provided. TR14 30 months
3.22.b. The soap dispenser is inaccessible because it is mounted with the controls 51½ inches high with only a forward reach provided. TR5 30 months
3.22.c. The lavatory is inaccessible because its clear floor space is obstructed. TR8 30 months
3.22.d. The toilet is inaccessible because the rear grab bar is 24 inches long. SU3 30 months
3.23. Children´s Clinic Lobby Single User Toilet Room    
3.23.a. The door is inaccessible because it requires 9 pounds of force to open. D2 30 months
3.23.b. No accessible mirror has been provided. TR14 30 months
3.23.c. The lavatory is inaccessible because the hot water pipes are not insulated or otherwise configured to protect against contact. TR12 30 months
3.23.d. The toilet is inaccessible because the top of the seat is 19½ inches high. SU18 30 months
3.23.e. The toilet is inaccessible because the side grab bar is obstructed by the toilet seat cover dispenser and the toilet paper dispenser. SU7 30 months
3.23.f. The toilet is inaccessible because the rear grab bar is 24 inches long. SU3 30 months
3.24. Women´s Toilet Room with Stalls 2nd Floor East    
3.24.a. The door is inaccessible because it requires 10 pounds of force to open. D2 30 months
3.24.b. No accessible mirror has been provided. TR14 30 months
3.24.c. The designated accessible toilet is inaccessible because the side grab bar is obstructed by the toilet paper dispenser. ST8 30 months
3.25. Men´s Toilet Room with Stalls 2nd Floor East    
3.25.a. The door is inaccessible because it requires 10 pounds of force to open. D2 30 months
3.25.b. No accessible mirror has been provided. TR14 30 months
3.25.c. The lavatory is inaccessible because the top of the rim is 34½ inches high. TR11 30 months
3.26. Health Care Trust Lobby Women´s Toilet Room with Stalls    
3.26.a. The door is inaccessible because it requires 12 pounds of force to open. D2 30 months
3.26.b. No accessible mirror has been provided. TR14 30 months
3.26.c. The lavatory is inaccessible because the clear floor space is blocked by a moveable object. TR8 30 months
3.26.d. The toilet is inaccessible because there is insufficient clear floor space provided. ST18 30 months
3.26.e. The toilet is inaccessible because its centerline is 22½ inches from the side wall. ST17 30 months
3.26.f. The toilet is inaccessible because the side grab bar is obstructed by the toilet paper dispenser. ST8 30 months
3.26.g. The toilet is inaccessible because the side grab bar is mounted 36½ inches high. ST12 30 months
3.27. Health Care Trust Lobby Men´s Toilet Room with Stalls    
3.27.a. The door is inaccessible because it requires 14 pounds of force to open. D2 30 months
3.27.b. No accessible mirror has been provided. TR14 30 months
3.27.c. The lavatory is inaccessible because the top of the rim is 34¾ inches high. TR11 30 months
3.27.d. The designated accessible toilet is inaccessible because the rear grab bar is obstructed by the toilet seat cover dispenser. ST5 30 months
3.28. Health Care Trust Staff Only Women´s Toilet Room with Stalls    
3.28.a. The door is inaccessible because it requires 12 pounds of force to open. D2 30 months
3.28.b. The toilet is inaccessible because the side grab bar is obstructed by the toilet paper dispenser. ST8 30 months
3.29. Health Care Trust Staff Only Men´s Toilet Room with Stalls    
3.29.a. The door is inaccessible because it requires 14 pounds of force to open. D2 30 months
3.29.b. No accessible mirror has been provided. TR14 30 months
3.29.c. The lavatory is inaccessible because the top of the rim is 34½ inches high. TR11 30 months
3.30. Route through Lobby: The route is inaccessible because the underside of the stairs creates an overhead hazard. AR7 30 months
3.31. Central Registration Women´s Toilet Room with Stalls    
3.31.a. The door is inaccessible because it requires 12 pounds of force to open. D2 30 months
3.31.b. The toilet is inaccessible because its centerline is 19½ inches from the side wall. ST17 30 months
3.32. Central Registration Men´s Toilet Room with Stalls    
3.32.a. The door is inaccessible because it requires 14 pounds of force to open. D2 30 months
3.32.b. The long shelf on the wall protrudes into the walkway and is not detectable to blind persons using a cane. AR8 30 months
3.33. Auditorium Women´s Toilet Room: The door is inaccessible because it requires 12 pounds of force to open. D2 30 months
3.34. Auditorium Men´s Toilet Room: The door is inaccessible because it requires 14 pounds of force to open. D2 30 months
3.35. Women´s Locker Room Lower Level    
3.35.a. The door is inaccessible because it requires 19 pounds of force to open. D2 30 months
3.35.b. The toilet is inaccessible because the side grab bar is mounted with the far end 48 inches from the rear wall. ST7 30 months
3.35.c. The shower is inaccessible because the clear floor space is 46½ inches wide, the grab bars are mounted 41 inches high, the curb is 2 inches high, and the fixed shower head is mounted more than 48 inches high. B8 30 months
3.35.d. The 3 benches are inaccessible because only one is mounted against a wall, only one (a different one) is 48 inches long, and none are 24 inches deep. LR1 30 months
3.35.e. The air dryer by the lockers protrudes into the walkway and is not detectable to blind persons using a cane. AR8 30 months
3.36. Men´s Locker Room Lower Level    
3.36.a. The door is inaccessible because it requires 15 pounds of force to open. D2 30 months
3.36.b. The urinal is inaccessible because the rim is 25 inches high. TR20 30 months
3.36.c. The toilet is inaccessible because the flush control is 46 inches high. ST2 30 months
3.36.d. The toilet is inaccessible because the side grab bar is mounted with the far end 48 inches from the rear wall. ST7 30 months
3.36.e. The shower is inaccessible because the clear floor space is 46 inches wide, the grab bars are mounted 41 inches high, the curb is 2 inches high, and the fixed shower head is mounted more than 48 inches high. B8 30 months
3.36.f. The 3 benches are inaccessible because only one is mounted against a wall, and it is less than 48 inches long, and none are 24 inches deep. LR1 30 months
3.36.g. The air dryer by the lockers protrudes into the walkway and is not detectable to blind persons using a cane. AR8 30 months
3.37. Employee Lunch Room    
3.37.a. The chips and candy vending machine is inaccessible because it is mounted with the controls 57 inches high. TR5 30 months
3.37.b. The door is inaccessible because it requires 14 pounds of force to open. D2 30 months
3.38. Biery Auditorium    
3.38.a. The door is inaccessible because it requires 17 pounds of force to open. D2 30 months
3.38.b. The security counter is inaccessible because it is 43 inches high. C6 30 months
3.38.c. There is no signage informing the public of the availability of an assistive listening system. AA3 30 months
4. Fire Station #14, located at 8300 N. Brighton Avenue    
4.1. Parking: The designated accessible parking is inaccessible because it lacks “Van Accessible” signage. P6 24 months
4.2. Lobby: The Pepsi vending machine is inaccessible because it is mounted with the controls 59½ inches high. TR5 24 months
4.3. Elevators: The elevator is inaccessible because the hall call buttons are mounted 41 inches high. E3 24 months
4.4. Single User Toilet Room Employee Area by Weight Room    
4.4.a. The paper towel dispenser is inaccessible because it is mounted with the controls 55 inches high with a forward reach required. TR5 24 months
4.4.b. The lavatory is inaccessible because the top of the rim is 37½ inches high, and there is no knee clearance provided. TR11 24 months
4.4.c. The toilet is inaccessible because the top of the seat is 16 inches high. SU18 24 months
4.4.d. The toilet paper dispenser is inaccessible because it is mounted 38½ inches from the rear wall. SU17 24 months
4.4.e. The toilet is inaccessible because there are no grab bars provided. SU10 24 months
4.5. Employee Single User Toilet and Shower Room    
4.5.a. There is no accessible locker provided. LR3 24 months
4.5.b. Although an audible alarm is provided in this facility, there is no visual alarm appliance in the toilet room. TR21 24 months
4.5.c. No accessible towel hook has been provided. TR1 24 months
4.5.d. The lavatory is inaccessible because the top of the rim is 37½ inches high, and there is no knee clearance provided. TR11 24 months
4.5.e. The toilet is inaccessible because its centerline is 19 inches from the side wall. SU15 24 months
4.5.f. The toilet is inaccessible because the top of the seat is 16 inches high. SU18 24 months
4.5.g. The toilet is inaccessible because there are no grab bars provided. SU10 24 months
4.5.h. There is no accessible shower provided. B8 24 months
4.6. Second Floor Bunk    
4.6.a. The door is inaccessible because it requires 30 pounds of force to open. D2 24 months
4.6.b. The shelf is inaccessible because it is mounted 62¾ inches high. S1 24 months
4.7. Bay Area Single User Toilet Room    
4.7.a. The paper towel dispenser is inaccessible because it is mounted with the controls 57 inches high. TR5 24 months
4.7.b. The lavatory is inaccessible because the bottom of the apron is 27½ inches high. TR11 24 months
4.7.c. The lavatory is inaccessible because the hot water pipes are not insulated or otherwise configured to protect against contact. TR12 24 months
4.7.d. The toilet is inaccessible because there are no grab bars provided. SU10 24 months
4.7.e. There is no accessible locker provided. LR3 24 months
5. Tony Aguirre Community Center, located at 2050 West Pennway Street    
5.1. Parking: The designated accessible parking in the lower lot is inaccessible because the van access aisle is 62 inches wide. P8 30 months
5.2. Route from Lower Parking Lot to Entrance    
5.2.a. The curb ramp is inaccessible because it has a slope of 15.3%. AR5 30 months
5.2.b. The route from the parking lot is inaccessible because there is a slope of 12.8% near the top of the curb ramp. AR1 30 months
5.3. Interior Signage: The room signs throughout the facility are inaccessible because they are mounted with their centerlines 55 to 56 inches high. TR18 30 months
5.4. Women´s 1st Floor Locker Room    
5.4.a. The designated accessible toilet is inaccessible because its centerline is 19 inches from the side wall. ST17 30 months
5.4.b. The door from the locker room to the pool is inaccessible because it requires 26 pounds of force to open. D2 30 months
5.4.c. The bench is inaccessible because it is 12 inches deep and 19½ inches high and it does not provide clear floor space alongside to allow a transfer. LR1 30 months
5.5. Ramp from Lobby to Pool: The ramp is inaccessible because it has a slope of up to 9%. R3 30 months
5.6. 1st Floor Single User Family Changing Room 111    
5.6.a. The toilet is inaccessible because the side grab bar is is mounted with the far end 38 inches from the rear wall. SU6 30 months
5.6.b. The toilet is inaccessible because there is a bench obstructing the clear floor space. SU16 30 months
5.6.c. The bench is inaccessible because it is 16½ inches deep and is not fixed to the wall. LR1 30 months
5.6.d. No accessible towel hook has been provided. TR1 30 months
5.7. Men´s 1st Floor Locker Room: The door from the locker room to the pool is inaccessible because it requires 23 pounds of force to open. D2 30 months
5.8. Ramp from Men´s Locker Room to Pool: The ramp is inaccessible because it lacks a level landing at the top and one handrail lacks an extension on the top. R5 30 months
5.9. 2nd Floor Drinking Fountains: The drinking fountains protrude into the walkway and are not detectable to blind persons using a cane. AR8 30 months
5.10. 2nd Floor Ramp from Gym to Toilet Room: The ramp is inaccessible because it has a slope between 8.5% and 9.1%. R5 30 months
5.11. 2nd Floor Men´s Toilet Room with Stalls    
5.11.a. The door is inaccessible because it requires 20 pounds of force to open. D2 30 months
5.11.b. No accessible mirror has been provided. TR14 30 months
5.11.c. The lavatory is inaccessible because it has twist-type hardware. TR10 30 months
5.11.d. The designated accessible toilet is inaccessible because there is no side grab bar. ST6 30 months
5.12. 2nd Floor Ramp from Lobby to Toilet Room: The ramp is inaccessible because it has a slope of 8.8%. R5 30 months
5.13. 2nd Floor Women´s Toilet Room with Stalls    
5.13.a. The door is inaccessible because it requires 17 pounds of force to open. D2 30 months
5.13.b. No accessible mirror has been provided. TR14 30 months
6. Brush Creek Community Center, located at 3801 Emanuel Cleaver II Boulevard    
6.1. Parking    
6.1.a. The designated accessible parking spaces and access aisles are inaccessible because they have slopes and cross slopes between 4.7% and 6.4% and the surface is cracked and broken. P7 30 months
6.1.b. The curb ramp is inaccessible because it has a slope of up to 11.8%. AR5 30 months
6.2. Drinking Fountains near Locker Room: The wall-mounted drinking fountain is inaccessible because it provides 26 inches of clear knee height. DF5 30 months
6.3. Women´s Locker Room    
6.3.a. The designated accessible toilet is inaccessible because the flush control is on the closed side. ST2 30 months
6.3.b. The designated accessible toilet is inaccessible because the rear grab bar is mounted 12 inches from the side wall. ST4 30 months
6.3.c. The roll-in shower is inaccessible because the shower head cannot be fixed to the wall, there are grab bars on only 2 walls, and the seat is 20½ inches high. B8 30 months
6.3.d. The bench is inaccessible because it is 9½ inches deep and it does not provide clear floor space alongside to allow a transfer. LR1 30 months
6.3.e. The door to the pool is inaccessible because it requires 26 pounds of force to open. D2 30 months
6.4. Men´s Locker Room    
6.4.a. The designated accessible toilet is inaccessible because its centerline is 15½ inches from the side wall. ST17 30 months
6.4.b. The designated accessible toilet is inaccessible because the flush control is on the closed side. ST2 30 months
6.4.c. The designated accessible toilet is inaccessible because there is no side grab bar. ST6 30 months
6.4.d. The designated accessible toilet is inaccessible because the rear grab bar is mounted 12 inches from the side wall. ST4 30 months
6.4.e. There is no accessible shower provided. B8 30 months
6.4.f. The bench is inaccessible because it is 9½ inches wide. LR1 30 months
6.4.g. There is no accessible locker provided. LR3 30 months
6.5. Drinking Fountain near Meeting Room: The wall-mounted drinking fountain is inaccessible because it provides 26 inches of clear knee height. DF5 30 months
6.6. Women´s Toilet Room with Stalls near Meeting Room    
6.6.a. The designated accessible toilet is inaccessible because the flush control is on the closed side. ST2 30 months
6.6.b. The designated accessible toilet is inaccessible because the rear grab bar is mounted 12 inches from the side wall. ST4 30 months
6.6.c. The baby changing shelf protrudes into the walkway and is not detectable to blind persons using a cane. AR8 30 months
6.7. Men´s Toilet Room with Stalls near Meeting Room    
6.7.a. The designated accessible toilet is inaccessible because the rear grab bar is mounted 12 inches from the side wall. ST4 30 months
6.7.b. The baby changing shelf protrudes into the walkway and is not detectable to blind persons using a cane. AR8 30 months
7. Shoal Creek Golf, located at Shoal Creek Parkway    
7.1. Parking: The parking lot, with a total of 208 parking spaces is inaccessible because there are only 6 accessible spaces. This lot requires 1 van accessible space and 6 standard accessible spaces. P3 30 months
7.2. Bar: The bar counter is inaccessible because it is 42 inches high. PD2 30 months
7.3. Women´s Toilet Room with Stalls by Banquet Hall    
7.3.a. The door is inaccessible because it requires 9 pounds of force to open. D2 30 months
7.3.b. The toilet paper dispenser in the designated accessible stall is inaccessible because it is mounted 39 inches from the rear wall. ST19 30 months
7.4. Men´s Toilet Room with Stalls by Banquet Hall    
7.4.a. The door is inaccessible because it requires 8 pounds of force to open. D2 30 months
7.4.b. The toilet paper dispenser in the designated accessible stall is inaccessible because it is mounted 39 inches from the rear wall. ST19 30 months
7.5. Women´s Locker Room: The bench is inaccessible because it does not provide clear floor space alongside to allow a transfer. LR1 30 months
7.6. Men´s Locker Room    
7.6.a. The door is inaccessible because it requires 13 pounds of force to open. D2 30 months
7.6.b. The toilet paper dispenser in the designated accessible stall is inaccessible because it is mounted 39 inches from the rear wall. ST19 30 months
7.6.c. The bench is inaccessible because it does not provide clear floor space alongside to allow a transfer. LR1 30 months
7.7. Portable Toilets between Holes 6 and 7: The portable toilets contain a number of inaccessible elements and are not accessible to people with disabilities. SU13 30 months
8. Safety Street, located at 2401 Campbell Street    
8.1. Route to Main Entrance: The route is inaccessible because it has a slope of 8.7% and cross slope of 4.4%, with no ramp features. AR1 24 months
8.2. Entrances: The building does not have directional signage posted at inaccessible entrances and does not have the International Symbol of Accessibility posted at accessible entrances. D16 24 months
8.3. Main Entry Drinking Fountains: The drinking fountains protrude into the walkway and are not detectable to blind persons using a cane. AR8 24 months
8.4. Side Hall Women´s Toilet Room with Stalls    
8.4.a. The door is inaccessible because it requires 12 pounds of force to open. D2 24 months
8.4.b. Although an audible alarm is provided in this facility, there is no visual alarm appliance in the toilet room. TR21 24 months
8.4.c. The designated accessible toilet is inaccessible because the flush control is on the closed side. ST2 24 months
8.4.d. The toilet is inaccessible because its centerline is 19 inches from the side wall. ST17 24 months
8.5. Side Hall Men´s Toilet Room with Stalls    
8.5.a. The door is inaccessible because it requires 11 pounds of force to open. D2 24 months
8.5.b. Although an audible alarm is provided in this facility, there is no visual alarm appliance in the toilet room. TR21 24 months
8.5.c. The toilet is inaccessible because its centerline is 19 inches from the side wall. ST17 24 months
9. 11th and Oak Garage, located at 11th and Oak Streets    
9.1. Parking: The parking garage, with a total of 1,395 parking spaces is inaccessible because it only has 2 van accessible spaces. This lot requires 3 van accessible spaces. P3 12 months
9.2. Elevators on 10th Street and 11th Street Sides: The elevators are inaccessible because the buttons for the main entry floor are not designated by a raised star. E4 12 months
10. Shoal Creek Patrol Division, located at 6885 NE Pleasant Valley Road    
10.1. Front Parking Lot: The designated accessible parking is inaccessible because the signs are mounted too low and there is no “Van Accessible” signage. P6 30 months
10.2. Community Room: The door is inaccessible because it requires 18 pounds of force to open. D2 30 months
10.3. 1st Floor Women´s Single User Toilet Room    
10.3.a. The door is inaccessible because it requires 30 pounds of force to open. D2 30 months
10.3.b. The toilet is inaccessible because the side grab bar is obstructed by the trash receptacle. SU8 30 months
10.3.c. The toilet is inaccessible because the rear grab bar is obstructed by the toilet seat cover dispenser. SU4 30 months
10.4. 1st Floor Men´s Single User Toilet Room    
10.4.a. The door is inaccessible because it requires 20 pounds of force to open. D2 30 months
10.4.b. The toilet is inaccessible because the rear grab bar is obstructed by the toilet seat cover dispenser. SU4 30 months
10.5. 1st Floor Single User Toilet Rooms Near Elevator    
10.5.a. The toilet room signs have no raised or Braille characters. TR18 30 months
10.5.b. The doors are inaccessible because they each require 18 to 20 pounds of force to open. D2 30 months
10.5.c. The toilets are inaccessible because the rear grab bars are obstructed by the seat cover dispensers. SU4 30 months
10.5.d. One of the toilets is inaccessible because the side grab bar is obstructed by the trash receptacle. SU8 30 months
10.6. Adult Holding Cells: The toilet/lavatory combination contains a number of inaccessible elements and is not accessible to people with disabilities. SU13 30 months
10.7. Single User Toilet Room near Juvenile Cells    
10.7.a. The door is inaccessible because it requires 17 pounds of force to open. D2 30 months
10.7.b. The toilet is inaccessible because the top of the seat is 15 inches high. SU18 30 months
10.8. Vending Machine in Break Room: The vending machine is inaccessible because its controls are 57 inches high. TR5 30 months
10.9. Women´s Lower Level Locker Room    
10.9.a. The door is inaccessible because it requires 18 pounds of force to open. D2 30 months
10.9.b. The toilet is inaccessible because its centerline is 20 inches from the side wall. ST17 30 months
10.9.c. The toilet is inaccessible because the side grab bar is obstructed by the trash receptacle. ST9 30 months
10.9.d. There is no accessible locker provided. LR3 30 months
10.10. Men´s Locker Room Lower Level    
10.10.a.  The door is inaccessible because it requires 18 pounds of force to open. D2 30 months
10.10.b.  There is no accessible locker provided. LR3 30 months
10.10.c.  The toilet seat cover dispenser is inaccessible because it is mounted 50 inches high behind the toilet. TR4 30 months
10.10.d.  The designated accessible toilet is inaccessible because the rear grab bar is obstructed by the toilet seat cover dispenser. ST5 30 months
10.11. Police Academy Side Parking Lot: The side parking lot, with a total of 218 parking spaces is inaccessible because the signs are mounted too low. P6 30 months
10.12. Police Academy Auditorium: The doors are inaccessible because they require 15 to 20 pounds of force to open. D2 30 months
10.13. Police Academy Main Level Lobby Drinking Fountains: The drinking fountains protrude into the walkway and are not detectable to blind persons using a cane. AR8 30 months
10.14. Police Academy Main Level Toilet Rooms: The doors are inaccessible because they require between 17 and 20 pounds of force to open. D2 30 months
10.15. Police Academy Administrative Office: The door is inaccessible because it requires 20 pounds of force to open. D2 30 months
10.16. Police Academy Elevator Behind Auditorium: The elevator is inaccessible because the hall call buttons are centered 40 inches above the finished floor. E3 30 months
10.17. Police Academy Drinking Fountain near F.A.T.S: The drinking fountains protrude into the walkway and are not detectable to blind persons using a cane. AR8 30 months
10.18. Police Academy Drinking Fountains in Gym: The drinking fountains protrude into the walkway and are not detectable to blind persons using a cane. AR8 30 months
10.19. Police Academy Library: The door is inaccessible because it requires 15 pounds of force to open. D2 30 months
10.20. Police Academy Men´s and Women´s Staff and Student Locker Rooms    
10.20.a.  The doors are inaccessible because they require 16 to 25 pounds of force to open. D2 30 months
10.20.b.  The wall telephones protrude into the walkway and are not detectable to blind persons using a cane. AR8 30 months
10.20.c.  There is no accessible shower provided in any of the locker rooms. B8 30 months
10.20.d. The benches are inaccessible because they are either 9½ or 20 inches deep, and some are less than 48 inches wide. LR1 30 months
10.20.e. The counter in the women´s student locker room protrudes into the walkway and is not detectable to blind persons using a cane. AR8 30 months
10.21. Rifle Range Parking    
10.21.a.  The designated accessible parking is inaccessible because the signs are mounted too low. P6 30 months
10.21.b.  The designated accessible parking is inaccessible because it has a slope of 4.5%. P7 30 months
10.22. Rifle Range Lobby Toilet Rooms with Stalls: The doors are inaccessible because they require 10 to 15 pounds of force to open. D2 30 months
10.23. Rifle Range Lobby Vending Machine: The vending machine is inaccessible because its controls are 57 inches high. TR5 30 months
10.24. Rifle Range Firearms Lockers: The lockers are inaccessible because the controls require tight grasping and twisting of the wrist to operate. TR3 30 months
11. Metro Patrol Division, located at 7601 Prospect Street    
11.1. Parking: The parking lot, with a total of 216 parking spaces, is inaccessible because it has only 5 designated accessible parking spaces, and the designated accessible parking space in the rear has no access aisle or vertical sign. This lot requires 1 van accessible space and 6 standard accessible spaces. P3 18 months
11.2. Rear Route to Building: There is no curb ramp provided in the rear of the building. AR5 18 months
11.3. Lobby: The wall-mounted television protrudes into the walkway and is not detectable to blind persons using a cane. AR8 18 months
11.4. Conference Room: The door is inaccessible because it requires 12 pounds of force to open. D2 18 months
11.5. Upper Level Family Toilet Room    
11.5.a. The door is inaccessible because it requires 22 pounds of force to open. D2 18 months
11.5.b. No accessible coat hook has been provided. TR1 18 months
11.6. Lobby Women´s Single User Toilet Room    
11.6.a. The door is inaccessible because it requires 15 pounds of force to open. D2 18 months
11.6.b. No accessible coat hook has been provided. TR1 18 months
11.7. Lobby Men´s Single User Toilet Room    
11.7.a. The door is inaccessible because it requires 18 pounds of force to open. D2 18 months
11.7.b. No accessible coat hook has been provided. TR1 18 months
11.8. Women´s Single User Toilet Room behind Lobby: The door is inaccessible because it requires 17 pounds of force to open. D2 18 months
11.9. Wall-Mounted Television behind Lobby: The television protrudes into the walkway and is not detectable to blind persons using a cane. AR8 18 months
11.10. Property Crimes    
11.10.a.  The door is inaccessible because it requires 19 pounds of force to open. D2 18 months
11.10.b.  The counter is inaccessible because it is 44½ inches high. C6 18 months
11.11. Administrative Offices: The counter is inaccessible because it is 43 inches high. C6 18 months
11.12. Break Room Counter: The counter is inaccessible because it is 43½ inches high. C6 18 months
11.13. Women´s Single User Toilet Room near Break Room    
11.13.a.  The door is inaccessible because it requires 22 pounds of force to open. D2 18 months
11.13.b.  No accessible coat hook has been provided. TR1 18 months
11.14. Men´s Single User Toilet Room near Break Room    
11.14.a.  The door is inaccessible because it requires 15 pounds of force to open. D2 18 months
11.14.b.  No accessible coat hook has been provided. TR1 18 months
11.15. Lockers: The kitchen and firearm lockers throughout the facility are inaccessible because the controls require twisting of the wrist to operate. TR3 18 months
11.16. Lower Level Break Room    
11.16.a.  The television protrudes into the walkway and is not detectable to blind persons using a cane. AR8 18 months
11.16.b.  The vending machine is inaccessible because its controls are 58 inches high. TR5 18 months
11.17. Lower Level Telephone: The wall-mounted telephone near the locker rooms protrudes into the walkway and is not detectable to blind persons using a cane. AR8 18 months
11.18. Adult Holding Cells: The toilet/lavatory combination contains a number of inaccessible elements and is not accessible to people with disabilities. SU13 18 months
11.19. Juvenile Detention Single User Toilet Room: The door is inaccessible because it requires 22 pounds of force to open. D2 18 months
11.20. Drinking Fountains in Lower Level Break Room: The drinking fountains protrude into the walkway and are not detectable to blind persons using a cane. AR8 18 months
11.21. Women´s Locker Room Lower Level    
11.21.a.  The door is inaccessible because it requires 16 pounds of force to open. D2 18 months
11.21.b.  The wall-mounted telephone protrudes into the walkway and is not detectable to blind persons using a cane. AR8 18 months
11.21.c.  The roll-in shower is inaccessible because the transfer seat is 16¼ inches high and is not adjacent to the controls. B10 18 months
11.21.d.  The shower is inaccessible because there are grab bars on only 2 walls. B8 18 months
11.21.e.  The bench is inaccessible because it is 9½ inches deep and 23¼ inches high. LR1 18 months
11.21.f.  The designated accessible lockers are inaccessible because the controls are mounted 63 inches high. TR5 18 months
11.22. Men´s Locker Room Lower Level    
11.22.a.  The door is inaccessible because it requires 12 pounds of force to open. D2 18 months
11.22.b.  The wall-mounted telephone protrudes into the walkway and is not detectable to blind persons using a cane. AR8 18 months
11.22.c.  The roll-in shower is inaccessible because the transfer seat is 16¼ inches high and is not adjacent to the controls. B10 18 months
11.22.d.  The shower is inaccessible because there are grab bars on only 2 walls. B8 18 months
11.22.e.  The designated accessible lockers are inaccessible because the controls are mounted 63 inches high. TR5 18 months
12. KC Live Parking Garage, located at 151 E 13th Street    
12.1. Parking Pay Stations: The pay stations are inaccessible because they are mounted with the highest controls 55 inches high. TR5 12 months
12.2. Elevators    
12.2.a. The lobby elevator is inaccessible because there is no hoistway signage provided on the 2nd floor. E12 12 months
12.2.b. The lobby elevator is inaccessible because the hall call buttons are mounted 45½ inches high. E3 12 months
12.2.c. The lobby elevator is inaccessible because the clearance between the car platform sill and the edge of the hoistway landing is 1½ inches. E10 12 months
13. Heart of America Golf Course, located in Swope Park at 7501 Blue River Road    
13.1. Parking: The parking lot, with a total of 167 parking spaces, is inaccessible because there are only 3 designated accessible parking spaces, there is no van accessible space, there are no access aisles provided, and the signs are mounted too low. This lot requires 1 van accessible space and 5 standard accessible spaces. P3 30 months
13.2. Entrance: The entrance door is inaccessible because there is a slope of 5% within the door´s required maneuvering clearance. D13 30 months
13.3. Payment Counter: The counter is inaccessible because it is 37¾ inches high. C6 30 months
13.4. Snack Bar: The counter is inaccessible because it is 42 inches high. C5 30 months
13.5. Soda Fountain: The soda fountain is inaccessible because it is mounted with the controls 58½ inches high. TR5 30 months
13.6. Women´s Locker Room    
13.6.a. The lavatory is inaccessible because the hot water pipes are not insulated or otherwise configured to protect against contact. TR12 30 months
13.6.b. No accessible coat hook has been provided. TR1 30 months
13.6.c. The designated accessible toilet is inaccessible because the rear grab bar is mounted 10 inches from the side wall. ST4 30 months
13.6.d. The designated accessible toilet is inaccessible because the rear grab bar is obstructed by the seat cover dispenser. ST5 30 months
13.6.e. The transfer shower is inaccessible because it is 37½ inches by 44 inches. B8 30 months
13.6.f. The bench is inaccessible because it is 12 inches deep, it does not provide clear floor space alongside to allow a transfer, and it is not attached at a wall. LR1 30 months
13.6.g. There is no accessible locker provided. LR3 30 months
13.7. Men´s Locker Room    
13.7.a. The paper towel dispenser is inaccessible because it is mounted with the controls 56 inches high. TR5 30 months
13.7.b. The lavatory is inaccessible because the hot water pipes are not insulated or otherwise configured to protect against contact. TR12 30 months
13.7.c. The designated accessible toilet is inaccessible because the flush control is on the closed side. ST2 30 months
13.7.d. No accessible coat hook has been provided. TR1 30 months
13.7.e. The designated accessible toilet is inaccessible because the rear grab bar is mounted 10 inches from the side wall. ST4 30 months
13.7.f. The transfer shower is inaccessible because it is 37½ inches by 44 inches. B8 30 months
13.7.g. The bench is inaccessible because it is 12 inches deep, it is 16 inches high, it does not provide clear floor space alongside to allow a transfer, and it is not attached at a wall. LR1 30 months
13.7.h. There is no accessible locker provided. LR3 30 months
14. Lakeside Nature Center, located in Swope Park at 4701 East Gregory Boulevard    
14.1. Parking: The designated accessible parking is inaccessible because two of the designated accessible parking spaces lack vertical signage, the one existing sign is mounted too low, and there is no “Van Accessible” sign. P6 24 months
14.2. Women´s Toilet Room with Stalls: No accessible coat hook has been provided. TR1 24 months
14.3. Men´s Toilet Room with Stalls    
14.3.a. The urinal is inaccessible because the flush control is 47 inches high. TR20 24 months
14.3.b. No accessible coat hook has been provided. TR1 24 months
14.3.c. The toilet paper dispenser in the designated accessible stall is inaccessible because it is mounted 39½ inches from the rear wall. ST19 24 months
14.4. Ramp from Lobby to Lower Level: The ramp is inaccessible because it has a slope of up to 11.3% and a cross slope of up to 5.1% and the handrails lack extensions. R5 24 months
15. Starlight Theater, located at 4600 Starlight Road    
15.1. West Side Parking Adjacent to Theater    
15.1.a. The parking lot is inaccessible because the designated accessible spaces and access aisles have slopes of up to 5.2 %. P7 36 months
15.1.b. The curb ramp is inaccessible because the flared sides have slopes of more than 10%. AR5 36 months
15.2. Northeast Zebra Lot Parking: The parking lot is inaccessible because the designated accessible spaces and access aisles have slopes of up to 7.7 %. P7 36 months
15.3. North Women´s Toilet Room with Stalls    
15.3.a. The toilet room sign is mounted on the door and has no raised or Braille characters. TR18 36 months
15.3.b. The door is inaccessible because it has an opening width of 31 inches. D25 36 months
15.3.c. The paper towel dispensers protrude into the walkway and are not detectable to blind persons using a cane. AR8 36 months
15.3.d. Although there are 7 toilet stalls, there is no ambulatory stall provided. ST1 36 months
15.3.e. The designated accessible toilet is inaccessible because the side grab bar is mounted with its far end 49 inches from the rear wall. ST7 36 months
15.3.f. The designated accessible toilet is inaccessible because the rear grab bar is mounted 7 inches from the side wall. ST4 36 months
15.4. North Men´s Toilet Room with Stalls    
15.4.a. The toilet room sign is mounted on the door and has no raised or Braille characters. TR18 36 months
15.4.b. The light switch is inaccessible because it is mounted 58 inches high. TR5 36 months
15.4.c. The paper towel dispenser protrudes into the walkway and is not detectable to blind persons using a cane. AR8 36 months
15.4.d. Although there are 7 toilet stalls, there is no ambulatory stall provided. ST1 36 months
15.4.e. The designated accessible toilet is inaccessible because its centerline is 23½ inches from the side wall. ST17 36 months
15.4.f. The designated accessible toilet is inaccessible because the side grab bar is 30 inches long. ST7 36 months
15.4.g. The designated accessible toilet is inaccessible because the side grab bar is mounted 6 inches from the side wall on which it is mounted. ST13 36 months
15.5. East Women´s Toilet Room with Stalls    
15.5.a. The sanitary napkin dispenser is inaccessible because the controls require tight grasping and twisting of the wrist to operate. TR3 36 months
15.5.b. The lavatory is inaccessible because the knee space is 21½ inches high. TR11 36 months
15.6. East Men´s Toilet Room with Stalls: The lavatory is inaccessible because the knee space is 21½ inches high. TR11 36 months
15.7. Administrative Office Women´s Toilet Room with Stalls: The door is inaccessible because it requires 15 pounds of force to open. D2 36 months
15.8. Administrative Office Men´s Toilet Room with Stalls: The door is inaccessible because it requires 15 pounds of force to open. D2 36 months
15.9. Stage Area Men´s Toilet Room with Stalls    
15.9.a. The door is inaccessible because it requires 15 pounds of force to open. D2 36 months
15.9.b. The toilet paper dispenser in the designated accessible stall is inaccessible because it is mounted 40 inches from the rear wall. ST19 36 months
15.10. Stage Area Women´s Toilet Room with Stalls    
15.10.a. The toilet paper dispenser in the designated accessible stall is inaccessible because it is mounted 38 inches from the rear wall. ST19 36 months
15.10.b. The paper towel dispensers and feminine products dispenser protrude into the walkway and are not detectable to blind persons using a cane. AR8 36 months
15.11. Counters    
15.11.a.  The northwest concession stand counter is inaccessible because it is 46 inches high. C5 36 months
15.11.b.  The bar and concession stand #4 counter is inaccessible because it is 42 inches high. C5 36 months
15.11.c.  The bar #3 counter is inaccessible because it is 42 inches high. C5 36 months
15.11.d.  The administrative office box office counter is inaccessible because it is 42 inches high. C6 36 months
15.11.e. The administrative office box office counter protrudes into the walkway and is not detectable to blind persons using a cane. AR8 36 months
15.12. Administrative Office Lobby Elevator: The elevator is inaccessible because the emergency system requires voice communication to operate. E8 36 months
15.13. Epic Front Office Unisex Single User Toilet Room    
15.13.a.  The toilet room sign is mounted on the door. TR18 36 months
15.13.b.  The door is inaccessible because it requires 11 pounds of force to open. D2 36 months
15.13.c. Although an audible alarm is provided in this facility, there is no visual alarm appliance in the toilet room. TR21 36 months
15.13.d.  The toilet is inaccessible because the flush control is on the closed side. SU1 36 months
15.13.e. The toilet is inaccessible because the side grab bar is mounted with the far end 48 inches from the rear wall. SU6 36 months
15.13.f.  The toilet is inaccessible because the side grab bar is obstructed by the toilet paper dispenser. SU7 36 months
15.14. Women´s Dressing Room Toilet Room with Stalls: The door is inaccessible because it requires 16 pounds of force to open. D2 36 months
15.15. Star Women´s Single User Toilet Room: The toilet is inaccessible because there are no grab bars provided. SU10 36 months
15.16. Men´s Dressing Room Toilet Room with Stalls: The door is inaccessible because it requires 16 pounds of force to open. D2 36 months
15.17. Green Room Unisex Single User Toilet Rooms    
15.17.a.  The door of the room on the right is inaccessible because it requires 13 pounds of force to open. D2 36 months
15.17.b.  The toilet room on the left is inaccessible because there are no grab bars provided. SU10 36 months
15.18. Chorus Rooms and Director´s Pavilion    
15.18.a.  The route to the chorus rooms is inaccessible because it can be accessed only via stairs. AR2 36 months
15.18.b.  The toilet rooms contain a number of inaccessible elements and are not accessible to people with disabilities. ST14 36 months
15.19. Women´s Southwest Toilet Room with Stalls    
15.19.a. The feminine products dispenser is inaccessible because the controls require tight grasping and twisting of the wrist to operate. TR3 36 months
15.19.b.  The designated accessible toilet is inaccessible because the flush control is on the closed side. ST2 36 months
15.19.c. The ambulatory stall is inaccessible because the door is not self closing, the toilet paper dispenser is mounted 43 inches from the rear wall, and only one grab bar is provided. ST1 36 months
15.20. Men´s Southwest Toilet Room with Stalls    
15.20.a. The toilet paper dispenser in the designated accessible stall is inaccessible because it is mounted 42 inches from the rear wall. ST19 36 months
15.20.b. The ambulatory stall is inaccessible because the door is not self closing and the toilet paper dispenser is mounted 43½ inches from the rear wall. ST1 36 months
15.21. Men´s Middle West Toilet Room with Stalls    
15.21.a.  The toilet room sign is mounted above the door and has no raised or Braille characters. TR18 36 months
15.21.b.  The door is inaccessible because there is a 1 inch high threshold. D22 36 months
15.21.c.  The lavatory is inaccessible because it has twist-type hardware. TR10 36 months
15.21.d.  The urinal is inaccessible because the flush control is 46 inches high. TR20 36 months
15.21.e.  No accessible coat hook has been provided. TR1 36 months
15.21.f. The designated accessible toilet is inaccessible because the side grab bar is obstructed by the toilet paper dispenser. ST8 36 months
15.21.g.  Although there are 8 toilet stalls, there is no ambulatory stall provided. ST1 36 months
15.22. Women´s Middle West Toilet Room with Stalls    
15.22.a.  The toilet room sign is mounted above the door and has no raised or Braille characters. TR18 36 months
15.22.b.  The door is inaccessible because it requires more than 5 pounds of force to open. D2 36 months
15.22.c.  The door is inaccessible because knob hardware is used. D1 36 months
15.22.d.  The lavatory is inaccessible because it has twist-type hardware. TR10 36 months
15.22.e.  The designated accessible toilet is inaccessible because its centerline is 20 inches from the side wall. ST17 36 months
15.22.f. The toilet paper dispenser in the designated accessible stall is inaccessible because it is mounted 38 inches from the rear wall. ST19 36 months
15.22.g. The designated accessible toilet is inaccessible because the side grab bar is 36 inches long and is mounted 16 inches from the rear wall. ST7 36 months
15.22.h.  Although there are 14 toilet stalls, there is no ambulatory stall provided. ST1 36 months
15.23. Seating Bowl    
15.23.a. The seating area, containing 7,958 seats, is inaccessible because only 20 wheelchair seating locations are provided on accessible routes and all are located on the Terrace Level in the last row of the theater with no lines of sight provided over standing spectators. The rest of the designated wheelchair seating locations have slopes of up to 10.3% or are on routes that have slopes of up to 19.6% and cross slopes of up to 13.6%. A total of 81 wheelchair seating areas is required. AA7 36 months
15.23.b.  There is no accessible route connecting the wheelchair seating areas and the stage. AA1 36 months
15.23.c.  The seating area lacks fixed aisle seating without armrests. AA2 36 months
16. Communications Center, located at 1111 Locust Street    
16.1. Entrance    
16.1.a. The route to the entrance is inaccessible because it contains three sets of stairs. AR1 24 months
16.1.b. The stair handrails protrude into the walkway and are not detectable to blind persons using a cane. AR8 24 months
16.2. Interior Signage: The signage provided is inaccessible because it is mounted above the doors and does not have raised and Braille characters. D26 24 months
16.3. Elevators    
16.3.a. The freight elevator is inaccessible because the hall call buttons are mounted 40½ inches high. E3 24 months
16.3.b. Both elevators are inaccessible because the emergency controls are grouped at the top of the panel. E9 24 months
16.4. Break Room 203    
16.4.a. The snack vending machines are inaccessible because the controls are more than 54 inches high. TR5 24 months
16.4.b. The change machine is inaccessible because it is mounted with the return control 55 inches high. TR5 24 months
16.5. Room 320    
16.5.a. The door is inaccessible because it requires 12 pounds of force to open. D2 24 months
16.5.b. The counter is inaccessible because it is 46 inches high. C6 24 months
16.5.c. The counter protrudes into the walkway and is not detectable to blind persons using a cane. AR8 24 months
16.5.d. The wall-mounted information screen protrudes into the walkway and is not detectable to blind persons using a cane. AR8 24 months
16.6. 3rd Floor Drinking Fountain: The drinking fountain is inaccessible because the flow of water is less than 4 inches high. DF7 24 months
16.7. 3rd Floor Women´s Toilet Room with Stalls    
16.7.a. The doors are inaccessible because they require 8 and 12 pounds of force to open. D2 24 months
16.7.b. The paper towel and feminine products dispensers protrude into the walkway and are not detectable to blind persons using a cane. AR8 24 months
16.7.c. The designated accessible toilet is inaccessible because the flush control is on the closed side. ST2 24 months
16.7.d. The designated accessible toilet is inaccessible because the rear grab bar is obstructed by the toilet seat cover dispenser. ST5 24 months
16.7.e. The toilet seat cover dispenser is inaccessible because it is mounted too high behind the toilet. TR4 24 months
16.7.f. No accessible coat hook has been provided. TR1 24 months
16.8. 3rd Floor Men´s Toilet Room with Stalls AR8 24 months
16.8.a. The paper towel dispensers protrude into the walkway and are not detectable to blind persons using a cane. AR8 24 months
16.8.b. The doors are inaccessible because they require 10 and 12 pounds of force to open. D2 24 months
16.8.c. No accessible coat hook has been provided. TR1 24 months
16.9. 3rd Floor Break Room Kitchen: The sink is inaccessible because there is no knee space provided. S2 24 months
16.10. Room 428    
16.10.a.  The counter is inaccessible because it is 46 inches high. C6 24 months
16.10.b.  The counter protrudes into the walkway and is not detectable to blind persons using a cane. AR8 24 months
16.11. Break Room 445: The snack vending machine is inaccessible because the controls are 57½ inches high. TR5 24 months
16.12. 4th Floor Drinking Fountain: The wall-mounted drinking fountains are inaccessible because one provides only 25½ inches of clear knee height and the other has a spout that is more than 36 inches high. DF5 24 months
16.13. 4th Floor Women´s Toilet Room with Stalls    
16.13.a.  The toilet room sign is mounted on the door. TR18 24 months
16.13.b.  The doors are inaccessible because they require 11 and 8 pounds of force to open. D2 24 months
16.13.c.  The designated accessible toilet is inaccessible because the flush control is on the closed side. ST2 24 months
16.13.d.  The designated accessible toilet is inaccessible because the side grab bar is obstructed by the toilet seat cover dispenser. ST9 24 months
16.13.e.  No accessible coat hook has been provided. TR1 24 months
16.14. 4th Floor Men´s Toilet Room with Stalls    
16.14.a.  The toilet room sign is mounted on the door. TR18 24 months
16.14.b.  The doors are inaccessible because they require 11 and 8 pounds of force to open. D2 24 months
16.14.c.  No accessible coat hook has been provided. TR1 24 months
16.15. Training Room 506: The door is inaccessible because it requires 11 pounds of force to open. D2 24 months
16.16. 5th Floor CSTAR Room    
16.16.a.  The door is inaccessible because it requires 7 pounds of force to open. D2 24 months
16.16.b.  The fire extinguisher just outside the door protrudes into the walkway and is not detectable to blind persons using a cane. AR8 24 months
16.17. 5th Floor Drinking Fountains DF3 24 months
16.17.a. Although three designated accessible drinking fountains are provided, there is no drinking fountain provided for people who have difficulty bending or stooping. DF3 24 months
16.17.b.  The third drinking fountain is inaccessible because it provides only 25½ inches of clear knee height. DF5 24 months
16.18. 5th Floor Women´s Toilet Room with Stall 566    
16.18.a.  The toilet room sign is mounted on the door. TR18 24 months
16.18.b.  The door is inaccessible because it requires 9 pounds of force to open. D2 24 months
16.18.c.  No accessible coat hook has been provided. TR1 24 months
16.19. 5th Floor Men´s Toilet Room with Stall 567    
16.19.a.  The toilet room sign is mounted on the door. TR18 24 months
16.19.b.  The door is inaccessible because it requires 10 pounds of force to open. D2 24 months
16.19.c.  The designated accessible toilet is inaccessible because the flush control is on the closed side. ST2 24 months
16.19.d. The designated accessible toilet is inaccessible because the side grab bar is obstructed by the toilet seat cover dispenser. ST9 24 months
16.19.e.  No accessible coat hook has been provided. TR1 24 months
16.19.f.  The urinal is inaccessible because the clear floor space is 28 inches wide. TR20 24 months
16.20. Exercise Room 532    
16.20.a.  The door is inaccessible because it requires 8 pounds of force to open. D2 24 months
16.20.b.  The paper towels, hand sanitizer, and telephone are inaccessible because they are mounted with the controls 57, 59, and 60 inches high, respectively. TR5 24 months
16.20.c.  The paper towel dispenser protrudes into the walkway and is not detectable to blind persons using a cane. AR8 24 months
16.21. Kitchen Room 534: The sink is inaccessible because it does not provide knee clearance. S2 24 months
16.22. Kitchen Room 542: The sink is inaccessible because it does not provide knee clearance. S2 24 months
16.23. Break Room 517    
16.23.a.  The sink is inaccessible because it does not provide knee clearance. S2 24 months
16.23.b.  The vending machine and telephone are inaccessible because they are mounted with the controls 58 and 59 inches high, respectively. TR5 24 months
16.24. KCFD Communication Center: The door is inaccessible because it requires 15 pounds of force to open. D2 24 months
16.25. Northeast Door Leaving Fire Area: The door is inaccessible because it requires 11 pounds of force to open. D2 24 months
16.26. Northeast Door to Police Dispatch: The door is inaccessible because it requires 10 pounds of force to open. D2 24 months
16.27. 911 Dispatch: The entrance door and the door out of the 911 hallway are inaccessible because they require 12 and 7 pounds of force to open, respectively. D2 24 months
16.28. Women´s Locker Room 547    
16.28.a.  The locker room sign is mounted on the door. TR18 24 months
16.28.b.  The door is inaccessible because it requires 10 pounds of force to open. D2 24 months
16.28.c.  The coat rack protrudes into the walkway and is not detectable to blind persons using a cane. AR8 24 months
16.28.d. The designated accessible toilet is inaccessible because the side grab bar is obstructed by the toilet seat cover dispenser. ST9 24 months
16.28.e.  No accessible coat hook has been provided. TR1 24 months
16.28.f.  The shower is inaccessible because the controls require twisting of the wrist to operate. TR3 24 months
16.28.g.  The shower is inaccessible because the shower spray unit hose is 57 inches long. B11 24 months
16.28.h.  The bench is inaccessible because it is 9½ inches deep and is not attached at a wall. LR1 24 months
16.29. Men´s Locker Room 543    
16.29.a.  The locker room sign is mounted on the door. TR18 24 months
16.29.b.  The doors are inaccessible because they each require 8 pounds of force to open. D2 24 months
16.29.c.  The designated accessible toilet is inaccessible because the flush control is on the closed side. ST2 24 months
16.29.d. The designated accessible toilet is inaccessible because the side grab bar is obstructed by the toilet seat cover dispenser. ST9 24 months
16.29.e.  No accessible coat hook has been provided. TR1 24 months
16.29.f.  The shower is inaccessible because the controls require twisting of the wrist to operate. TR3 24 months
16.29.g.  The designated accessible shower is inaccessible because the clear floor space extends only 4 inches beyond the shower wall on which the seat is mounted. B8 24 months
16.29.h.  The bench is inaccessible because it is 9½ inches deep and is not attached at a wall. LR1 24 months
16.30. Women´s Locker Room 523    
16.30.a.  The locker room sign is mounted on the door. TR18 24 months
16.30.b.  The door is inaccessible because it requires 7 pounds of force to open. D2 24 months
16.30.c.  The shelf protrudes into the walkway and is not detectable to blind persons using a cane. AR8 24 months
16.30.d.  The coat rack protrudes into the walkway and is not detectable to blind persons using a cane. AR8 24 months
16.30.e.  The designated accessible toilet is inaccessible because the flush control is on the closed side. ST2 24 months
16.30.f. The designated accessible toilet is inaccessible because the side grab bar is obstructed by the toilet seat cover dispenser. ST9 24 months
16.30.g.  No accessible coat hook has been provided. TR1 24 months
16.30.h.  The shower is inaccessible because the controls require twisting of the wrist to operate. TR3 24 months
16.30.i.  The bench is inaccessible because it is 9½ inches deep and is not attached at a wall. LR1 24 months
16.31. Men´s Locker Room 529    
16.31.a.  The locker room sign is mounted on the door. TR18 24 months
16.31.b.  The doors are inaccessible because they each require between 7 and 9 pounds of force to open. D2 24 months
16.31.c.  The coat rack protrudes into the walkway and is not detectable to blind persons using a cane. AR8 24 months
16.31.d. The designated accessible toilet is inaccessible because the side grab bar is obstructed by the toilet seat cover dispenser. ST9 24 months
16.31.e.  No accessible coat hook has been provided. TR1 24 months
16.31.f.  The shower is inaccessible because the controls require twisting of the wrist to operate. TR3 24 months
16.31.g.  The bench is inaccessible because it is 9½ inches deep and is not attached at a wall. LR1 24 months
16.32. Conference Room 573: The door is inaccessible because it requires 6 pounds of force to open. D2 24 months
17. Southeast Community Center, located at 4201 East 63rd Street    
17.1. Parking: The parking lot, with a total of 157 parking spaces, is inaccessible because it has no van accessible space. This lot requires 1 van accessible space and 5 standard accessible spaces. P3 24 months
17.2. Entrance: The building does not have directional signage posted at inaccessible entrances and does not have the International Symbol of Accessibility posted at accessible entrances. D16 24 months
17.3. Interior Doors: The doors throughout the facility are inaccessible because they require more than 5 pounds of force to open. D2 24 months
17.4. 1st Floor Drinking Fountain next to Toilet Room: The drinking fountain is inaccessible because the controls require 13 pounds of force to operate. DF2 24 months
17.5. 1st Floor Drinking Fountain in Gym    
17.5.a. The drinking fountain is inaccessible because the controls require 16½ pounds of force to operate. DF2 24 months
17.5.b. The wall-mounted drinking fountain is inaccessible because it provides only 25½ inches of clear knee height. DF5 24 months
17.5.c. The high drinking fountain protrudes into the walkway and is not detectable to blind persons using a cane. AR8 24 months
17.6. Game Room: The pull side of the door, which is accessed through a front approach, is inaccessible because it has only 17 inches of clear space on the latch side. D6 24 months
17.7. Front Desk Vending Machines: The snack machine is inaccessible because the controls are 57½ inches high. TR5 24 months
17.8. Weight Room: The fire extinguisher protrudes into the walkway and is not detectable to blind persons using a cane. AR8 24 months
17.9. Lobby Men´s Toilet Room with Stalls: The toilet is inaccessible because the side grab bar is mounted 36½ inches high. ST12 24 months
17.10. Lobby Women´s Toilet Room with Stalls    
17.10.a.  The feminine products dispenser is inaccessible because the controls require right grasping and twisting of the wrist to operate. TR3 24 months
17.10.b.  The lavatory is inaccessible because the bottom of the apron is 28¼ inches high. TR11 24 months
17.11. Elevator    
17.11.a.  The elevator is inaccessible because the hall call buttons are mounted 43½ inches high. E3 24 months
17.11.b.  The elevator is inaccessible because the hoistway signage is mounted 61 inches high. E12 24 months
17.11.c. The elevator is inaccessible because the car control button for the main entry floor is not designated by a raised star. E4 24 months
17.12. Women´s Locker Room    
17.12.a.  The lavatory is inaccessible because the bottom of the apron is 28 inches high. TR11 24 months
17.12.b. The feminine products dispenser protrudes into the walkway and is not detectable to blind persons using a cane. AR8 24 months
17.12.c.  No accessible towel hook has been provided. TR1 24 months
17.13. Men´s Locker Room: The lavatory is inaccessible because the bottom of the apron is 28 inches high. TR11 24 months
17.14. Unisex Family Locker Room Near Pool    
17.14.a.  The lavatory is inaccessible because the top of the rim is 34½ inches high. TR11 24 months
17.14.b.  No accessible coat hook has been provided. TR1 24 months
17.14.c.  The transfer shower is inaccessible because no grab bars are provided. B9 24 months
17.14.d.  The bench is inaccessible because it is less than 24 inches deep. LR1 24 months