Attachment I

 

 

Please Note: Paragraph 52 of the Settlement Agreement requires that within three months of the effective date of this Agreement, the County provide signage as necessary to comply with 28 C.F.R. § 35.163(b), after having surveyed all facilities that are the subject of this Agreement for the purpose of identifying those that have multiple entrances not all of which are accessible.

 

Newly Constructed Facilities:  In order to ensure that the spaces and elements in facilities for which construction was commenced after January 26, 1992, are readily accessible to and usable by persons with disabilities, the City will take the actions listed below:

 

A.        Within 12 months of the effective date of this Agreement, the City will complete the following modifications to Johannes Park's Aquatic Center Bathhouse, Walnut and Baird Streets:

 

1.         Toilet Room: Single-User, Unisex (right side)

 

a.         The flush control on toilet is on the closed side.  Provide a flush control mounted on the "open" side of the toilet's clear floor space; 44 inches or less above the finished floor; and requiring a maximum of 5 pounds of force to operate; or provide an automatic flush device.  Standards §§ 4.1.3(11), 4.22.4, 4.16.5, 4.27.4.

 

2.         Men's Locker Room

 

a.         The room signage includes Braille, but the Braille characters indicate only that the room is accessible; they do not indicate that it is a men's toilet room.  Provide a toilet room sign with Braille that identifies the room.  The sign shall be mounted on the wall adjacent to the latch side of the door with the centerline of the sign at 60 inches above the finished floor and situated such that a person can approach within 3 inches of the sign without encountering an obstruction or standing within a door swing.  Standards §§ 4.1.2(7)(d), 4.30.1, 4.30.4, 4.30.5, 4.30.6, 4.30.7.

 

b.         The flush control in the toilet stall for persons with disabilities is on the closed side.  Provide a flush control mounted on the "open" side of the toilet's clear floor space; 44 inches or less above the finished floor; and requiring a maximum of 5 pounds of force to operate; or provide an automatic flush device.  Standards §§ 4.1.3(11), 4.22.4, 4.16.5, 4.17.2, 4.27.4.

 

c.         The lockers require tight grasping and twisting of the wrist to operate.  Provide a locker with mechanical controls, if any, that can be operated with 5 lbf or less and that can be used with one hand and without tight grasping, pinching, or twisting of the wrist (lever-operated, push-type, and electronically controlled mechanisms are examples of acceptable designs).   Standards § 4.27.4.

 

3.         Women's Toilet Room with Stalls

 

a.         The room signage includes Braille, but the Braille characters indicate only that the room is accessible; they do not indicate that it is a women's toilet room.  Provide a toilet room sign with Braille that identifies the room.  The sign shall be mounted on the wall adjacent to the latch side of the door with the centerline of the sign at 60 inches above the finished floor and situated such that a person can approach within 3 inches of the sign without encountering an obstruction or standing within a door swing.  Standards §§ 4.1.2(7)(d), 4.30.1, 4.30.4, 4.30.5, 4.30.6, 4.30.7.

 

b.         The lockers require tight grasping and twisting of the wrist to operate.  Provide a locker with mechanical controls, if any, that can be operated with 5 lbf or less and that can be used with one hand and without tight grasping, pinching, or twisting of the wrist (lever-operated, push-type, and electronically controlled mechanisms are examples of acceptable designs).  Standards § 4.27.4.

 

c.         Although 1 of the 6 stalls is loosely configured to be accessible to ambulatory persons with disabilities, not all of its elements comply with the Standards.   Provide at least one stall that is exactly 36 inches wide with an outward swinging, self-closing door and parallel grab bars complying with Fig 30(d).   Standards §§ 4.1.3(11), 4.22.4, Fig. 30(d).

 

B.         Within 36 months of the effective date of this Agreement, the City will complete the following modifications to St. Philip Park's Warming House, 52 Irene Street:

 

1.         Routes

 

a.         There is no accessible route from the street to the shelter as the current route is over grass and there is no curb-cut.  Provide at least one accessible route within the boundary of the site connecting these elements that, to the maximum extent feasible, coincides with the route for the general public.  The accessible route must have a minimum clear width of 36 inches, or a minimum clear width of 42 inches if there is a turn around an obstruction less than 48 inches wide; have passing spaces at least 60 inches by 60 inches at least every 200 feet; have a minimum clear headroom of 80 inches; have a surface that is firm, stable, and slip resistant; have, in the absence of a curb ramp, ramp, elevator, or platform lift, no level changes in excess of ½ inch vertically; and have a running slope of less than 1:20 (5%) (or have been constructed as a fully accessible ramp) and a cross slope of less than 1:50 (2%).  Standards §§ 4.3, 4.5, Fig. 7.

 

b.         There is no accessible route from the shelter to the play area or to any piece of play equipment as the route is over grass.  Provide at least one accessible route within the boundary of the site connecting these elements that, to the maximum extent feasible, coincides with the route for the general public.  The accessible route must have a minimum clear width of 36 inches, or a minimum clear width of 42 inches if there is a turn around an obstruction less than 48 inches wide; have passing spaces at least 60 inches by 60 inches at least every 200 feet; have a minimum clear headroom of 80 inches; have a surface that is firm, stable, and slip resistant; have, in the absence of a curb ramp, ramp, elevator, or platform lift, no level changes in excess of ½ inch vertically; and have a running slope of less than 1:20 (5%) (or have been constructed as a fully accessible ramp) and a cross slope of less than 1:50 (2%).  Standards §§ 4.3, 4.5, Fig. 7.

 

2.         Shelter

 

a.         The exterior door into the activity room has a threshold of more than ½ inch.  Provide an accessible door with a threshold that is no greater than ¼ inch, or is no greater than ½ inch and is beveled with a slope no greater than 1:2.  Standards §§ 4.1.3(7)(a), 4.13.8, 4.5.2.

 

3.         Men's Toilet Room: Single-User

 

a.         The toilet room sign does not contain the International Symbol of Accessibility or raised or Braille characters and it is not mounted at the required location.  Provide a toilet room sign with the International Symbol of Accessibility and raised and Braille characters.  The sign shall be mounted on the wall adjacent to the latch side of the door with the centerline of the sign at 60 inches above the finished floor and situated such that a person can approach within 3 inches of the sign without encountering an obstruction or standing within a door swing.  Standards §§ 4.1.2(7)(d), 4.30.1, 4.30.4, 4.30.5, 4.30.6. 

 

b.         The lavatory faucet requires twisting of the wrist to operate.  Provide a lavatory with a faucet that can be operated with 5 pounds of force or less and can be used with one hand and without tight grasping, pinching, or twisting of the wrist (lever-operated, push-type, and electronically controlled mechanisms are examples of acceptable designs).  Standards §§ 4.1.3(11), 4.22.6, 4.19.5, 4.27.4.

 

4.         Women's Toilet Room: Single-User

 

a.         The toilet room sign does not contain the International Symbol of Accessibility or raised or Braille characters and it is not mounted at the required location.  Provide a toilet room sign with the International Symbol of Accessibility and raised and Braille characters.  The sign shall be mounted on the wall adjacent to the latch side of the door with the centerline of the sign at 60 inches above the finished floor and situated such that a person can approach within 3 inches of the sign without encountering an obstruction or standing within a door swing.  Standards §§ 4.1.2(7)(d), 4.30.1, 4.30.4, 4.30.5, 4.30.6. 

 

b.         The lavatory faucet requires twisting of the wrist to operate.  Provide a lavatory with a faucet that can be operated with 5 pounds of force or less and can be used with one hand and without tight grasping, pinching, or twisting of the wrist (lever-operated, push-type, and electronically controlled mechanisms are examples of acceptable designs).  Standards §§ 4.1.3(11), 4.22.6, 4.19.5, 4.27.4.

 

c.         The toilet flush control is mounted on the closed side.  Provide a flush control mounted on the "open" side of the toilet's clear floor space; 44 inches or less above the finished floor; and requiring a maximum of 5 pounds of force to operate; or provide an automatic flush device.  Standards §§ 4.1.3(11), 4.22.4, 4.16.5, 4.27.4.

 

C.        Within 9 months of the effective date of this Agreement, the City will complete the following modifications to the Wildlife Sanctuary's Observation Building, 1660 East Shore Drive:

 

1.         The ramp to the main entrance has no appropriate handrails.  Provide handrails that are between 1¼ inches and 1½ inches in diameter with a continuous gripping surface along both sides of the ramp, extending at least 12 inches beyond the top and bottom of the ramp parallel with the ground surface.  Ensure that handrails are mounted between 34 inches and 38 inches above the ramp surface, with ends rounded or returned smoothly to the floor, wall, or post, and that they do not rotate within their fittings.  Ensure that the ramp and approaches are designed so that water will not accumulate on walking surfaces.  Standards §§ 4.1.2(1), 4.1.2(2), 4.3.8, 4.8.

 

2.         The ramp to the rear entrance lacks handrails on one side.  Provide handrails that are between 1¼ inches and 1½ inches in diameter with a continuous gripping surface along both sides of the ramp, extending at least 12 inches beyond the top and bottom of the ramp parallel with the ground surface.  Ensure that handrails are mounted between 34 inches and 38 inches above the ramp surface, with ends rounded or returned smoothly to the floor, wall, or post, and that they do not rotate within their fittings.  Standards §§ 4.1.2(1), 4.1.2(2), 4.3.8, 4.8.5.

 

3.         Women's Toilet Room with Stalls

 

a.         The toilet room sign is mounted on the door.  Provide a toilet room sign with raised and Braille characters.  The sign shall be mounted on the wall adjacent to the latch side of the door with the centerline of the sign at 60 inches above the finished floor and situated such that a person can approach within 3 inches of the sign without encountering an obstruction or standing within a door swing.  Standards §§ 4.1.2(7)(d), 4.30.1, 4.30.4, 4.30.5, 4.30.6. 

 

b.         The pressure required to open the room door is 15 pounds.  Provide a door that requires no more than 5 pounds of force to open.  Standards §§ 4.1.3(7)(b), 4.13.11(2)(b).

 

c.         The paper towel dispenser controls are 56 inches above the finished floor.  Provide paper towel dispenser controls with the controls a maximum height above the finished floor of 48 inches for a forward approach or 54 inches for a side approach and that is accompanied by clear floor space of 30 by 48 inches that allows a forward or parallel approach by a person using a wheelchair.  Standards §§ 4.1.3(13), 4.27.2, 4.27.3, 4.2.4, 4.2.5, 4.2.6, Fig. 4.

 

d.         Due to the placement of a trash can, there is inadequate clear floor space at the lavatory.  Provide and maintain a lavatory with clear floor space at least 30 inches wide and 48 inches deep centered on the lavatory.  Standards §§ 4.1.3(11), 4.22.6, 4.19.3, Fig. 32.

 

e.         The lavatory hardware requires 9 pounds of force to operate.  Provide a lavatory with a faucet that can be operated with 5 pounds of force or less and can be used with one hand and without tight grasping, pinching, or twisting of the wrist (lever-operated, push-type, and electronically controlled mechanisms are examples of acceptable designs).  Standards §§ 4.1.3(11), 4.22.6, 4.19.5, 4.27.4.

 

f.          Toilet Stall for Persons with Disabilities

 

i.          The coat hook is inaccessible.  Provide a coat hook at a maximum height above the finished floor of 48 inches for a forward approach or 54 inches for a side approach and that is accompanied by clear floor space of 30 by 48 inches that allows a forward or parallel approach by a person using a wheelchair.  Standards §§ 4.1.3(12)(a), 4.25.2, 4.25.3, 4.2.4, 4.2.5, 4.2.6.

 

4.         Men's Toilet Room with Stalls

 

a.         The toilet room sign is mounted on the door.  Provide a toilet room sign with raised and Braille characters.  The sign shall be mounted on the wall adjacent to the latch side of the door with the centerline of the sign at 60 inches above the finished floor and situated such that a person can approach within 3 inches of the sign without encountering an obstruction or standing within a door swing.  Standards §§ 4.1.2(7)(d), 4.30.1, 4.30.4, 4.30.5, 4.30.6. 

 

b.         The pressure required to open the door is 15 pounds.  Provide a door that requires no more than 5 pounds of force to open.  Standards §§ 4.1.3(7)(b), 4.13.11(2)(b).

 

c.         The paper towel dispenser controls are 57 inches above the finished floor.  Provide paper towel dispenser controls with the controls a maximum height above the finished floor of 48 inches for a forward approach or 54 inches for a side approach and that is accompanied by clear floor space of 30 by 48 inches that allows a forward or parallel approach by a person using a wheelchair.  Standards §§ 4.1.3(13), 4.27.2, 4.27.3, 4.2.4, 4.2.5, 4.2.6, Fig. 4.

 

d.         The lavatory hardware requires 7 pounds of force to operate.  Provide a lavatory with a faucet that can be operated with 5 pounds of force or less and can be used with one hand and without tight grasping, pinching, or twisting of the wrist (lever-operated, push-type, and electronically controlled mechanisms are examples of acceptable designs).  Standards §§ 4.1.3(11), 4.22.6, 4.19.5, 4.27.4.

 

e.         Toilet Stall for Persons with Disabilities

 

i.          The coat hook is inaccessible.  Provide a coat hook at a maximum height above the finished floor of 48 inches for a forward approach or 54 inches for a side approach and that is accompanied by clear floor space of 30 by 48 inches that allows a forward or parallel approach by a person using a wheelchair.  Standards §§ 4.1.3(12)(a), 4.25.2, 4.25.3, 4.2.4, 4.2.5, 4.2.6.

 

5.         Drinking Fountain                                                        

 

a.         The lower drinking fountain is obstructed by some carpeted steps and lacks adequate clear floor space for a front or side approach.  Provide and maintain a drinking fountain with clear knee space between the bottom of the apron and the finished floor or ground of at least 27 inches high, 30 inches wide, and 17 to 19 inches deep; and a minimum clear floor space of 30 inches by 48 inches to allow a person in a wheelchair to approach the unit facing forward.  Standards § 4.15.5(1), Figs. 27(a), (b).

 

D.        Within 9 months of the effective date of this Agreement, the City will complete the following modifications to the Metro Boat Launch, Bay Beach Road:

 

1.         Parking:  The van accessible parking reserved for persons with disabilities lacks the appropriate signage.  At van accessible spaces, provide a "Van-Accessible" sign located below the International Symbol of Accessibility such that the sign cannot be obstructed by vehicles parked in the space.  Standards §§ 4.1.2(5), 4.6.4, 4.30.7(1).

 

2.         The drinking fountain is not accessible to people who have problems bending or stooping.  For each lower drinking fountain, provide a drinking fountain that is accessible to people who have difficulty bending or stooping.  This can be accommodated by the use of a "hi-lo" fountain; by providing one fountain accessible to those who use wheelchairs and one fountain at a standard height convenient for those who have difficulty bending; by providing a fountain accessible to people who use wheelchairs and a cup dispenser, or by such other means as would achieve the required accessibility for each group of people.  Standards § 4.1.3(10)(a).

 

3.         Men's Toilet Room with Stalls

 

a.         The toilet room sign lacks the International Symbol of Accessibility and raised and Braille characters and it is not mounted in the required location.  Provide a toilet room sign with raised and Braille characters.  The sign shall be mounted on the wall adjacent to the latch side of the door with the centerline of the sign at 60 inches above the finished floor and situated such that a person can approach within 3 inches of the sign without encountering an obstruction or standing within a door swing.  Standards §§ 4.1.2(7)(d), 4.30.1, 4.30.4, 4.30.5, 4.30.6. 

 

b.         The paper towel dispenser controls are 58½ inches above the finished floor.  Provide paper towel dispenser controls with the controls a maximum height above the finished floor of 48 inches for a forward approach or 54 inches for a side approach and that is accompanied by clear floor space of 30 by 48 inches that allows a forward or parallel approach by a person using a wheelchair.  Standards §§ 4.1.3(13), 4.27.2, 4.27.3, 4.2.4, 4.2.5, 4.2.6, Fig. 4.

 

c.         The paper towel dispenser is a protruding object that is not cane-detectable.  Provide an accessible route at this location such that no objects with their bottom leading edges measuring between 27 inches and 80 inches above the finished floor protrude more than 4 inches into walks, halls, corridors, passageways, or aisles.  Free-standing objects mounted on posts or pylons may overhang 12 inches maximum from 27 inches to 80 inches above the ground or finished floor.  Standards §§ 4.1.2(3), 4.4.

 

d.         The lavatory hot water pipes are not insulated or otherwise configured to protect against contact.  Provide hot water and drain pipes that are insulated or otherwise configured to protect against contact.  Standards §§ 4.1.3(11), 4.22.6, 4.19.4.

 

e.         Dressing Rooms

 

i.          The coat hook is inaccessible.  Provide a coat hook at a maximum height above the finished floor of 48 inches for a forward approach or 54 inches for a side approach and that is accompanied by clear floor space of 30 by 48 inches that allows a forward or parallel approach by a person using a wheelchair.  Standards §§ 4.1.3(12)(a), 4.25.2, 4.25.3, 4.2.4, 4.2.5, 4.2.6.

 

ii.          The changing bench is not 24 inches by 42 inches.  Provide a 24 inch by 48 inch bench fixed to the wall along the bench's longer dimension.  Ensure that the bench has sufficient structural strength and is mounted with its surface between 17 inches and 19 inches above the finished floor.  Provide clear floor space alongside the bench to allow a person using a wheelchair to make a parallel transfer onto the bench.  Standards §§ 4.35.4, 4.26.3.

 

f.          Toilet Stall for Persons with Disabilities

 

i.          The toilet paper dispenser is mounted above the side grab bar.  Provide a toilet paper dispenser that is mounted with its top at least 1½ inches under the side grab bar and 36 inches or less from the rear wall and is centered at least 19 inches above the finished floor.  Standards §§ 4.1.3(11), 4.22.4, 4.17.3, Fig. 30(d).

 

ii.          The overall length of the rear grab bar is 33 inches.  Provide a rear grab bar that is at least 36 inches in overall length with the closer end no more than 6 inches from the side wall.  Standards §§ 4.1.3(11), 4.22.4, 4.17.6, Fig. 30. 

 

4.         Women's Toilet Room with Stalls

 

a.         The toilet room sign lacks the International Symbol of Accessibility and raised and Braille characters and it is not mounted in the required location.  Provide a toilet room sign with raised and Braille characters.  The sign shall be mounted on the wall adjacent to the latch side of the door with the centerline of the sign at 60 inches above the finished floor and situated such that a person can approach within 3 inches of the sign without encountering an obstruction or standing within a door swing.  Standards §§ 4.1.2(7)(d), 4.30.1, 4.30.4, 4.30.5, 4.30.6. 

 

b.         The paper towel dispenser controls are 58½ inches above the finished floor.  Provide paper towel dispenser controls with the controls a maximum height above the finished floor of 48 inches for a forward approach or 54 inches for a side approach and that is accompanied by clear floor space of 30 by 48 inches that allows a forward or parallel approach by a person using a wheelchair.  Standards §§ 4.1.3(13), 4.27.2, 4.27.3, 4.2.4, 4.2.5, 4.2.6, Fig. 4.

 

c.         The lavatory hot water pipes are not insulated or otherwise configured to protect against contact.  Provide hot water and drain pipes that are insulated or otherwise configured to protect against contact.  Standards §§ 4.1.3(11), 4.22.6, 4.19.4.

 

d.         Dressing Rooms

 

i.          The coat hook is inaccessible.  Provide a coat hook at a maximum height above the finished floor of 48 inches for a forward approach or 54 inches for a side approach and that is accompanied by clear floor space of 30 by 48 inches that allows a forward or parallel approach by a person using a wheelchair.  Standards §§ 4.1.3(12)(a), 4.25.2, 4.25.3, 4.2.4, 4.2.5, 4.2.6.

 

ii.          The changing bench is not 24 inches by 42 inches.  Provide a 24 inch by 48 inch bench fixed to the wall along the bench's longer dimension.  Ensure that the bench has sufficient structural strength and is mounted with its surface between 17 inches and 19 inches above the finished floor.  Provide clear floor space alongside the bench to allow a person using a wheelchair to make a parallel transfer onto the bench.  Standards §§ 4.35.4, 4.26.3.

 

e.         Toilet Stall for Persons with Disabilities

 

i.          The toilet paper dispenser is mounted above the side grab bar.  Provide a toilet paper dispenser that is mounted with its top at least 1½ inches under the side grab bar and 36 inches or less from the rear wall and is centered at least 19 inches above the finished floor.  Standards §§ 4.1.3(11), 4.22.4, 4.17.3, Fig. 30(d).

 

ii.          The toilet flush control is on the closed side.  Provide a flush control mounted on the "open" side of the toilet's clear floor space; 44 inches or less above the finished floor; and requiring a maximum of 5 pounds of force to operate; or provide an automatic flush device.  Standards §§ 4.1.3(11), 4.22.4, 4.16.5, 4.17.2, 4.27.4.

 

iii.         The overall length of the rear grab bar is 33 inches.  Provide a rear grab bar that is at least 36 inches in overall length with the closer end no more than 6 inches from the side wall.  Standards §§ 4.1.3(11), 4.22.4, 4.17.6, Fig. 30. 

 

E.         Within 6 months of the effective date of this Agreement, the City will complete the following modifications to the Green Bay Transit Facility, 901 University Avenue:

 

1.         Parking:  The van accessible parking reserved for persons with disabilities lacks the appropriate signage and the space and its access aisle are not level.  On the shortest accessible route to the accessible entrance, provide at least 1 van accessible space designated as reserved for people with disabilities.  Ensure that van accessible spaces are a minimum of 96 inches wide and served by access aisles at least 96 inches wide.  At all spaces designated as reserved for persons with disabilities, provide vertical signs with the International Symbol of Accessibility located such that they cannot be obstructed by parked vehicles.  At van accessible spaces, provide an additional "Van-Accessible" sign located below the International Symbol of Accessibility.  Ensure that all spaces and access aisles for persons with disabilities are flat and level, with slopes and cross-slopes not exceeding 1:50 in all directions, and that their surfaces are firm, stable, and slip-resistant.  Standards §§ 4.1.2(5), 4.6, 4.30.7(1).

 

2.         Community Meeting Room

 

a.         Men's East End Toilet Room with Stalls

 

i.          The pressure required to open the door is 10 pounds.  Provide a door that requires no more than 5 pounds of force to open.  Standards §§ 4.1.3(7)(b), 4.13.11(2)(b).

 

ii.          The coat hook is inaccessible.  Provide a coat hook at a maximum height above the finished floor of 48 inches for a forward approach or 54 inches for a side approach and that is accompanied by clear floor space of 30 by 48 inches that allows a forward or parallel approach by a person using a wheelchair.  Standards §§ 4.1.3(12)(a), 4.25.2, 4.25.3, 4.2.4, 4.2.5, 4.2.6.

 

iii.         The paper towel dispenser is a protruding object that is not cane-detectable.  Provide an accessible route at this location such that no objects with their bottom leading edges measuring between 27 inches and 80 inches above the finished floor protrude more than 4 inches into walks, halls, corridors, passageways, or aisles.  Free-standing objects mounted on posts or pylons may overhang 12 inches maximum from 27 inches to 80 inches above the ground or finished floor.  Standards §§ 4.1.2(3), 4.4.

 

b.         Women's East End Toilet Room with Stalls

 

i.          The pressure required to open the door is 10 pounds.  Provide a door that requires no more than 5 pounds of force to open.  Standards §§ 4.1.3(7)(b), 4.13.11(2)(b).

 

ii.          The controls to the feminine products dispenser require grasping to operate.  Provide a sanitary napkin dispenser with mechanical controls, if any, that can be operated with 5 pounds of force or less and that can be used with one hand and without tight grasping, pinching, or twisting of the wrist (lever-operated, push-type, and electronically controlled mechanisms are examples of acceptable designs).  Standards §§ 4.1.3(13), 4.27.4.

 

iii.         The feminine products dispenser and the paper towel dispenser are protruding objects that are not cane-detectable.  Provide an accessible route at this location such that no objects with their bottom leading edges measuring between 27 inches and 80 inches above the finished floor protrude more than 4 inches into walks, halls, corridors, passageways, or aisles.  Free-standing objects mounted on posts or pylons may overhang 12 inches maximum from 27 inches to 80 inches above the ground or finished floor.  Standards §§ 4.1.2(3), 4.4.

 

3.         Transit Waiting Room

 

a.         Men's Toilet Room with Stalls

 

i.          The pressure required to open the door is 12 pounds.  Provide a door that requires no more than 5 pounds of force to open.  Standards §§ 4.1.3(7)(b), 4.13.11(2)(b).

 

ii.          The controls to the paper towel dispenser are 58 inches above the finished floor.  Provide a paper towel dispenser with the controls a maximum height above the finished floor of 48 inches for a forward approach or 54 inches for a side approach and that is accompanied by clear floor space of 30 by 48 inches that allows a forward or parallel approach by a person using a wheelchair.  Standards §§ 4.1.3(13), 4.27.2, 4.27.3, 4.2.4, 4.2.5, 4.2.6, Fig. 4.

 

b.         Women's Toilet Room with Stalls

 

i.          The pressure required to open the door is 14 pounds.  Provide a door that requires no more than 5 pounds of force to open.  Standards §§ 4.1.3(7)(b), 4.13.11(2)(b).

 

c.         Telephones

 

i.          The telephone's coin slot height is 58 inches above the finished floor and there is no volume control.  Provide an accessible telephone with a clear floor space of at least 30 inches by 48 inches that allows either a forward or parallel approach by a person using a wheelchair such that bases, enclosures, and fixed seats do not impede approaches to the telephone; with the highest operable part of the telephone mounted no more than 48 inches above the floor for a front approach or no more than 54 inches above the floor for a side approach; that are hearing aid compatible and have a volume control mechanism; with telephone books, if provided, located between 15 and 48 inches above the finished floor for a front approach or between 9 and 54 inches above the finished floor for a side approach; and with a cord of at least 29 inches long from the telephone to the handset.  Standards §§ 4.1.3(17), 4.31.

 

F.         Within 6 months of the effective date of this Agreement, the City will complete the following modifications to the Community Policing Center, Walnut and Baird Streets:

 

1.         Ramp at Entrance

 

a.         The entrance ramp has no handrails.  Provide handrails that are between 1¼ inches and 1½ inches in diameter with a continuous gripping surface along both sides of the ramp, extending at least 12 inches beyond the top and bottom of the ramp parallel with the ground surface.  Ensure that handrails are mounted between 34 inches and 38 inches above the ramp surface, with ends rounded or returned smoothly to the floor, wall, or post, and that they do not rotate within their fittings.  Standards §§ 4.1.2(1), 4.1.2(2), 4.8.5.

 

b.         There is no signage at the stairs to inform persons with disabilities of the availability or location of the ramp.  Provide accessible directional signage with the International Symbol of Accessibility at the stairs directing users to the ramp, and provide accessible signage with the International Symbol of Accessibility at the ramp.  Standards §§ 4.1.3(8)(d), 4.1.3(16)(b), 4.13, 4.30.

 

2.         Women's Toilet Room: Single-User (Community Room)

 

a.         The toilet room sign lacks the International Symbol of Accessibility and raised and Braille characters.  Provide a toilet room sign with the International Symbol of Accessibility and raised and Braille characters.  The sign shall be mounted on the wall adjacent to the latch side of the door with the centerline of the sign at 60 inches above the finished floor and situated such that a person can approach within 3 inches of the sign without encountering an obstruction or standing within a door swing.  Standards §§ 4.1.2(7)(d), 4.30.1, 4.30.4, 4.30.5, 4.30.6. 

 

b.         The lavatory hardware requires twisting of the wrist to operate.  Provide a lavatory with a faucet that can be operated with 5 pounds of force or less and can be used with one hand and without tight grasping, pinching, or twisting of the wrist (lever-operated, push-type, and electronically controlled mechanisms are examples of acceptable designs).  Standards §§ 4.1.3(11), 4.22.6, 4.19.5, 4.27.4.

 

c.         The lavatory hot water pipes are not insulated or otherwise configured to protect against contact.  Provide hot water and drain pipes that are insulated or otherwise configured to protect against contact.  Standards §§ 4.1.3(11), 4.22.6, 4.19.4.         

 

d.         The toilet flush control is mounted on the closed side.  Provide a flush control mounted on the "open" side of the toilet's clear floor space; 44 inches or less above the finished floor; and requiring a maximum of 5 pounds of force to operate; or provide an automatic flush device.  Standards §§ 4.1.3(11), 4.22.4, 4.16.5, 4.17.2, 4.27.4.

 

3.         Men's Toilet Room: Single-User

 

a.         The toilet room sign lacks the International Symbol of Accessibility and raised and Braille characters.  Provide a toilet room sign with the International Symbol of Accessibility and raised and Braille characters.  The sign shall be mounted on the wall adjacent to the latch side of the door with the centerline of the sign at 60 inches above the finished floor and situated such that a person can approach within 3 inches of the sign without encountering an obstruction or standing within a door swing.  Standards §§ 4.1.2(7)(d), 4.30.1, 4.30.4, 4.30.5, 4.30.6. 

 

b.         The lavatory hardware requires twisting of the wrist to operate.  Provide a lavatory with a faucet that can be operated with 5 pounds of force or less and can be used with one hand and without tight grasping, pinching, or twisting of the wrist (lever-operated, push-type, and electronically controlled mechanisms are examples of acceptable designs).  Standards §§ 4.1.3(11), 4.22.6, 4.19.5, 4.27.4.

 

c.         The lavatory hot water pipes are not insulated or otherwise configured to protect against contact.  Provide hot water and drain pipes that are insulated or otherwise configured to protect against contact.  Standards §§ 4.1.3(11), 4.22.6, 4.19.4.