Attachment G: Modifications to Altered Facilities

 

1.         By July 1, 2006, the City will complete the following modifications to the Public Service Administration Building located at 16489 Orange Way.

 

            a.         Women’s Toilet Room

 

                        i.         The toilet room sign is mounted on the door. Provide a toilet room sign with raised and Braille characters. The sign shall be mounted on the wall adjacent to the latch side of the door with the centerline of the sign at 60 inches above the finished floor and situated such that a person can approach within 3 inches of the sign without encountering an obstruction or standing within a door swing. Standards §§ 4.1.2(7)(d), 4.1.6(1)(b), 4.30.1, 4.30.4, 4.30.5, 4.30.6.

 

                        ii.        The women’s toilet room door is inaccessible because the pressure required to open the door is 7 pounds. Provide a door that requires no more than 5 pounds of force to open. Standards §§ 4.1.3(7)(b), 4.1.6(1)(b), 4.13.11(2)(b).

 

                        iii.       The coat hook in the designated accessible stall is inaccessible. Provide a coat hook at a maximum height above the finished floor of 48 inches for a forward approach or 54 inches for a side approach and that is accompanied by clear floor space of 30 by 48 inches that allows a forward or parallel approach by a person using a wheelchair. Standards §§ 4.1.3(12)(a), 4.1.6(1)(b), 4.25.2, 4.25.3, 4.2.4, 4.2.5, 4.2.6.

 

                        iv.       The toilet paper dispenser in the designated accessible stall is inaccessible because it is mounted 40 inches from the rear wall. Provide a toilet paper dispenser that is mounted with its top at least 1½ inches under the side grab bar and 36 inches or less from the rear wall and is centered at least 19 inches above the finished floor. Standards §§ 4.1.3(11), 4.1.6(1)(b), 4.22.4, 4.17.3, Fig. 30(d).

 

            b.         Men’s Toilet Room

 

                        i.         The toilet room sign is mounted on the door. Provide a toilet room sign with raised and Braille characters. The sign shall be mounted on the wall adjacent to the latch side of the door with the centerline of the sign at 60 inches above the finished floor and situated such that a person can approach within 3 inches of the sign without encountering an obstruction or standing within a door swing. Standards §§ 4.1.2(7)(d), 4.1.6(1)(b), 4.30.1, 4.30.4, 4.30.5, 4.30.6.

 

                        ii.        The men’s toilet room door is inaccessible because the pressure required to open the door is 13 pounds. Provide a door that requires no more than 5 pounds of force to open. Standards §§ 4.1.3(7)(b), 4.1.6(1)(b), 4.13.11(2)(b).

 

                        iii.       The urinal is inaccessible because the flush control is 45 inches above the finished floor. Provide a urinal with an elongated rim mounted 17 inches or less above the finished floor, a clear floor space of at least 30 inches wide and 48 inches deep centered on the urinal, and a flush control height of 44 inches or less above the finished floor. Standards §§ 4.1.3(11), 4.1.6(1)(b), 4.22.5, 4.18.2, 4.18.3, 4.18.4.

 

                        iv.       The coat hook in the designated accessible stall is inaccessible. Provide a coat hook at a maximum height above the finished floor of 48 inches for a forward approach or 54 inches for a side approach and that is accompanied by clear floor space of 30 by 48 inches that allows a forward or parallel approach by a person using a wheelchair. Standards §§ 4.1.3(12)(a), 4.1.6(1)(b), 4.25.2, 4.25.3, 4.2.4, 4.2.5, 4.2.6.

 

                        v.         The toilet paper dispenser is inaccessible because it is mounted 40 inches from the rear wall. Provide a toilet paper dispenser that is mounted with its top at least 1½ inches under the side grab bar and 36 inches or less from the rear wall and is centered at least 19 inches above the finished floor. Standards §§ 4.1.3(11), 4.1.6(1)(b), 4.22.4, 4.17.3, Fig. 30(d).

 

            c.         Women’s Toilet Room

 

                        i.         The shower in the women’s toilet room is inaccessible because the grab bars are mounted in an incorrect location. Provide a shower in this room that is exactly 36 inches wide and 36 inches deep with a 48 inch long and 36 inch wide clear floor space alongside the shower opening, and an L-shaped shower seat mounted on the wall opposite the controls and extending the full depth of the stall; OR a shower that is at least 30 inches deep and 60 inches wide with no curb or threshold and with a 36 inch deep and 60 inch wide clear floor space at the shower opening. Ensure that the shower has grab bars, controls, a shower spray unit, and a seat, curb, and enclosure, if provided, that comply fully with the Standards and with Figs. 35, 36, and 37, as applicable. Standards §§ 4.1.3(11), 4.1.6(1)(b), 4.21, Figs. 35, 36, 37.

 

            d.         Men’s Toilet Room

 

                        i.         The toilet in the designated accessible stall is inaccessible because its centerline measures 19½ inches from the side wall. Provide a toilet with a centerline that measures 18 inches from the near side wall. Standards §§ 4.1.3(11), 4.1.6(1)(b), 4.22.4, 4.17.3, Fig. 30.

 

                        ii.        The shower in men’s toilet room is inaccessible because the grab bars are mounted in an incorrect location. Provide a shower in this room that is exactly 36 inches wide and 36 inches deep with a 48 inch long and 36 inch wide clear floor space alongside the shower opening, and an L-shaped shower seat mounted on the wall opposite the controls and extending the full depth of the stall; OR a shower that is at least 30 inches deep and 60 inches wide with no curb or threshold and with a 36 inch deep and 60 inch wide clear floor space at the shower opening. Ensure that the shower has grab bars, controls, a shower spray unit, and a seat, curb, and enclosure, if provided, that comply fully with the Standards and with Figs. 35, 36, and 37, as applicable. Standards §§ 4.1.3(11), 4.1.6(1)(b), 4.21, Figs. 35, 36, 37.

 

            e.         The service counter at front reception is inaccessible because it is not 36 inches wide. Provide a counter on an accessible route such that a portion of the counter is at least 36 inches wide and no more than 36 inches above the finished floor, or provide an auxiliary counter with a maximum height of 36 inches in close proximity to the main counter, or provide equivalent facilitation. Equivalent facilitation may be provided in the form of a folding shelf attached to the main counter, an auxiliary table nearby, a clip board made available to the public, or other means. Standards §§ 4.1.1(2), 4.1.6(1)(b), 7.2(2), 4.1.3(1), 4.3.

 

2.         By July 1, 2006, the City will complete the following modifications to City Hall located at 8353 Sierra Avenue.

 

            a.         Women’s Toilet Room

 

                        i.         The toilet room sign is mounted on the door and there is no symbol of accessibility. Provide a toilet room sign with the International Symbol of Accessibility and raised and Braille characters. The sign shall be mounted on the wall adjacent to the latch side of the door with the centerline of the sign at 60 inches above the finished floor and situated such that a person can approach within 3 inches of the sign without encountering an obstruction or standing within a door swing. Standards §§ 4.1.2(7)(d), 4.1.6(1)(b), 4.30.1, 4.30.4, 4.30.5, 4.30.6, 4.30.7.

 

                        ii.        The women’s toilet room door is inaccessible because the pressure required to open the door is 8 pounds. Provide a door that requires no more than 5 pounds of force to open. Standards §§ 4.1.3(7)(b), 4.1.6(1)(b), 4.13.11(2)(b).

 

                        iii.       The toilet paper dispenser in the designated accessible stall is inaccessible because it is mounted 42 inches from the rear wall. Provide a toilet paper dispenser that is mounted with its top at least 1½ inches under the side grab bar and 36 inches or less from the rear wall and is centered at least 19 inches above the finished floor. Standards §§ 4.1.3(11), 4.1.6(1)(b), 4.22.4, 4.17.3, Fig. 30(d).

 

            b.         Men’s Toilet Room

 

                        i.         The toilet room sign is mounted on the door and there is no symbol of accessibility. Provide a toilet room sign with the International Symbol of Accessibility and raised and Braille characters. The sign shall be mounted on the wall adjacent to the latch side of the door with the centerline of the sign at 60 inches above the finished floor and situated such that a person can approach within 3 inches of the sign without encountering an obstruction or standing within a door swing. Standards §§ 4.1.2(7)(d), 4.1.6(1)(b), 4.30.1, 4.30.4, 4.30.5, 4.30.6, 4.30.7.

 

                        ii.        The men’s toilet room door is inaccessible because the pressure required to open the door is 9 pounds. Provide a door that requires no more than 5 pounds of force to open. Standards §§ 4.1.3(7)(b), 4.1.6(1)(b), 4.13.11(2)(b)

 

                        iii.       The toilet paper dispenser in the designated accessible stall is inaccessible because it is mounted 44 inches from the rear wall. Provide a toilet paper dispenser that is mounted with its top at least 1½ inches under the side grab bar and 36 inches or less from the rear wall and is centered at least 19 inches above the finished floor. Standards §§ 4.1.3(11), 4.1.6(1)(b), 4.22.4, 4.17.3, Fig. 30(d).

 

            c.         Drinking Fountains

 

                        i.         Although an accessible drinking fountain is provided, there is no drinking fountain provided for people who have difficulty bending or stooping. For each accessible drinking fountain, provide a drinking fountain that is accessible to people who have difficulty bending or stooping. This can be accommodated by the use of a “hi-lo” fountain; by providing one fountain accessible to those who use wheelchairs and one fountain at a standard height convenient for those who have difficulty bending; by providing a fountain accessible to people who use wheelchairs and a cup dispenser, or by such other means as would achieve the required accessibility for each group of people. Standards §§ 4.1.3(10)(a), 4.1.6(1)(b).

 

            d.         Women’s Toilet Room

 

                        i.         The door to the women’s toilet room, which is accessed through a front approach, is inaccessible because it has only 2 inches of clear floor space on the latch side of the pull side of the door. On the pull side of the door, provide maneuvering clearance at least 60 inches deep and provide a minimum of 18 inches (24 inches is preferred) of maneuvering clearance on the latch side of the door. Standards §§ 4.1.3(7)(b), 4.1.6(1)(b), 4.13.6, Fig. 25(a).

 

3.         By July 1, 2007, the City will complete the following modifications to City Hall located at 8353 Sierra Avenue.

 

            a.         Parking

 

                        i.         Although the parking lot has a total of 110 parking spaces, an inadequate number are designated as reserved for people with disabilities. On the shortest accessible route to the accessible entrance, provide one van accessible space and 4 standard spaces designated as reserved for people with disabilities. Standard accessible spaces shall be a minimum of 96 inches wide and served by access aisles at least 60 inches wide. Van accessible spaces shall be a minimum of 96 inches wide and served by access aisles at least 96 inches wide. All spaces designated as reserved for people with disabilities shall have vertical signs with the International Symbol of Accessibility located such that they cannot be obstructed by parked vehicles. Van accessible spaces shall have an additional “Van-Accessible” sign located below the International Symbol of Accessibility. Standards §§ 4.1.2(5), 4.1.6(1)(b), 4.6, 4.30.7(1).

 

                        ii.        The parking reserved for persons with disabilities is inaccessible because one of the accessible parking spaces has an access aisle that is 53 inches wide. Provide designated accessible parking spaces that are a minimum of 96 inches wide and served by access aisles at least 60 inches wide. Provide van accessible spaces that are a minimum of 96 inches wide and served by access aisles at least 96 inches wide. Standards §§ 4.1.2(5), 4.1.6(1)(b), 4.6.3, Fig.9.

 

                        iii.       The signage designating parking as reserved for persons with disabilities is too low. At each space designated as reserved for persons with disabilities, provide a vertical sign with the International Symbol of Accessibility located such that it cannot be obstructed by vehicles parked in the space. Standards §§ 4.1.2(5), 4.1.6(1)(b), 4.6.4, 4.30.7(1).

 

4.         By July 1, 2006, the City will complete the following modifications to the City Hall East Annex, Engineering Department, located at 17001 Upland Avenue.

 

            a.         Men’s Toilet Room

 

                        i.         The men’s toilet room door is inaccessible because the pressure required to open the door is 10 pounds. Provide a door that requires no more than 5 pounds of force to open. Standards §§ 4.1.3(7)(b), 4.1.6(1)(b), 4.13.11(2)(b)

 

            b.         Women’s Toilet Room

 

                        i.         The women’s toilet room door is inaccessible because the pressure required to open the door is 10 pounds. Provide a door that requires no more than 5 pounds of force to open. Standards §§ 4.1.3(7)(b), 4.1.6(1)(b), 4.13.11(2)(b)

 

                        ii.        The toilet paper dispenser in the designated accessible stall is inaccessible because it is mounted 38 inches from the rear wall. Provide a toilet paper dispenser that is mounted with its top at least 1½ inches under the side grab bar and 36 inches or less from the rear wall and is centered at least 19 inches above the finished floor. Standards §§ 4.1.3(11), 4.1.6(1)(b), 4.22.4, 4.17.3, Fig. 30(d).

 

            c.         Men’s Toilet Room

 

                        i.         The toilet in the designated accessible stall is inaccessible because its centerline measures 19 inches from the side wall. Provide a toilet with a centerline that measures 18 inches from the near side wall. Standards §§ 4.1.3(11), 4.1.6(1)(b), 4.22.4, 4.17.3, Fig. 30.

 

                        ii.        The toilet paper dispenser in the designated accessible stall is inaccessible because it is mounted 42 inches from the rear wall. Provide a toilet paper dispenser that is mounted with its top at least 1½ inches under the side grab bar and 36 inches or less from the rear wall and is centered at least 19 inches above the finished floor. Standards §§ 4.1.3(11), 4.1.6(1)(b), 4.22.4, 4.17.3, Fig. 30(d).

 

5.         By July 1, 2006, the City will complete the following modifications to Veteran’s Park West located at 9055 Mango Avenue.

 

            a.         There is no accessible stall designated for persons with disabilities provided in either the men’s or women’s toilet rooms. Provide a “standard” accessible toilet stall at least 60 inches wide and at least 59 inches deep (or at least 56 inches deep with a wall-mounted toilet) such that all of the stall’s elements, including stall door, stall door hardware, water closet, size and arrangement, toe clearances, grab bars, controls, and dispensers, comply with the Standards. Standards §§ 4.1.3(11), 4.1.6(1)(b), 4.22.4, 4.22.7, 4.13, 4.16, 4.17, 4.26, 4.27, Fig. 30.

 

6.         By July 1, 2006, the City will complete the following modifications to the Miller Fitness Center and Park located at 17004 Arrow Boulevard.

 

            a.         The entrances to all racquetball courts are inaccessible because there is a 3 inch threshold. Provide at least one racquetball court with an entrance threshold no greater than ¼ inch, or between ¼ inch and ½ inch and beveled with a slope no greater than 1:2. Standards §§ 4.1.3(7)(b), 4.1.6(1)(b), 4.13.8, 4.5.2.

 

            b.         Women’s Locker Room (8 stalls)

 

                        i.         The women’s toilet room door is inaccessible because the pressure required to open the door is 8 pounds. Provide a door that requires no more than 5 pounds of force to open. Standards §§ 4.1.3(7)(b), 4.1.6(1)(b), 4.13.11(2)(b)

 

            c.         The ramp is inaccessible because there are no handrails. Provide handrails that are between 1¼ inches and 1½ inches in diameter with a continuous gripping surface along both sides of the ramp, extending at least 12 inches beyond the top and bottom of the ramp parallel with the ground surface. Ensure that handrails are mounted between 34 inches and 38 inches above the ramp surface, with ends rounded or returned smoothly to the floor, wall, or post, and that they do not rotate within their fittings. Standards §§ 4.1.2(1), 4.1.2(2), 4.1.6(1)(b), 4.3.8, 4.8.5.

 

            d.         The front counter at the entrance is inaccessible because it is 41 inches above the finished floor. Provide a counter on an accessible route such that a portion of the counter is at least 36 inches wide and no more than 36 inches above the finished floor, or provide an auxiliary counter with a maximum height of 36 inches in close proximity to the main counter, or provide equivalent facilitation. Equivalent facilitation may be provided in the form of a folding shelf attached to the main counter, an auxiliary table nearby, a clip board made available to the public, or other means. Standards §§ 4.1.1(2), 4.1.6(1)(b), 7.2(2), 4.1.3(1), 4.3.

 

7.         By July 1, 2007, the City will complete the following modifications to the Miller Fitness Center and Park located at 17004 Arrow Boulevard.

 

            a.         Women’s Locker Room (8 stalls)

 

                        i.         The mirror is inaccessible. Provide a mirror with the bottom edge of its reflecting surface no more than 40 inches above the finished floor. Standards §§ 4.1.3(11), 4.1.6(1)(b), 4.22.6, 4.19.6.

 

                        ii.        The toilet in the designated accessible stall is inaccessible because its centerline measures 20 inches from the side wall. Provide a toilet with a centerline that measures 18 inches from the near side wall. Standards §§ 4.1.3(11), 4.1.6(1)(b), 4.22.4, 4.17.3, Fig. 30.

 

                        iii.       Although there are 8 stalls, there is no ambulatory stall provided. Provide at least one stall that is exactly 36 inches wide with an outward swinging, self-closing door and parallel grab bars complying with Fig 30(d). Standards §§ 4.1.3(11), 4.1.6(1)(b), 4.22.4, Fig. 30(d).

 

                        iv.       The shower in the women’s locker room is inaccessible because the shower is 48 inches deep by 42 inches wide and the shower seat does not extend the full depth of the stall. Provide a shower in this room that is exactly 36 inches wide and 36 inches deep with a 48 inch long and 36 inch wide clear floor space alongside the shower opening, and an L-shaped shower seat mounted on the wall opposite the controls and extending the full depth of the stall; OR a shower that is at least 30 inches deep and 60 inches wide with no curb or threshold and with a 36 inch deep and 60 inch wide clear floor space at the shower opening. Ensure that the shower has grab bars, controls, a shower spray unit, and a seat, curb, and enclosure, if provided, that comply fully with the Standards and with Figs. 35, 36, and 37, as applicable. Standards §§ 4.1.3(11), 4.1.6(1)(b), 4.21, Figs. 35, 36, 37.

 

            b.         Men’s Locker Room

 

                        i.         The mirror is inaccessible. Provide a mirror with the bottom edge of its reflecting surface no more than 40 inches above the finished floor. Standards §§ 4.1.3(11), 4.1.6(1)(b), 4.22.6, 4.19.6.

 

                        ii.        The toilet in the designated accessible stall is inaccessible because there is insufficient clear floor space. Provide clear floor space that complies with Fig. 30 at the toilet. Standards §§ 4.1.3(11), 4.1.6(1)(b), 4.22.4, 4.17.3, Fig. 30.

 

                        iii.       The side grab bar at the toilet in the designated accessible stall is inaccessible because it is mounted 16 inches from the rear wall. Provide a side grab bar that is at least 40 inches in overall length, with the far end mounted at least 52 inches from the rear wall and the closer end 12 inches or less from the rear wall; mounted 33 to 36 inches above the finished floor; with a diameter between 1¼ and 1½ inches; with 1½ inches between the grab bar and the wall; and at least 1½ inches between the grab bar and any other object, such as the toilet paper dispenser. Standards §§ 4.1.3(11), 4.1.6(1)(b), 4.22.4, 4.17.6, 4.26.2, Figs. 30(a), (d).

 

                        iv.       The shower in the men’s locker room is inaccessible because the shower is 48 inches deep by 41 inches wide and the shower seat does not extend the full depth of the stall. Provide a shower in this room that is exactly 36 inches wide and 36 inches deep with a 48 inch long and 36 inch wide clear floor space alongside the shower opening, and an L-shaped shower seat mounted on the wall opposite the controls and extending the full depth of the stall; OR a shower that is at least 30 inches deep and 60 inches wide with no curb or threshold and with a 36 inch deep and 60 inch wide clear floor space at the shower opening. Ensure that the shower has grab bars, controls, a shower spray unit, and a seat, curb, and enclosure, if provided, that comply fully with the Standards and with Figs. 35, 36, and 37, as applicable. Standards §§ 4.1.3(11), 4.1.6(1)(b), 4.21, Figs. 35, 36, 37.