Appendix E

 

 

Altered Facilities

 

Please Note: Paragraph 21 of the Settlement Agreement requires that within three months of the effective date of this Agreement, the City provide signage as necessary to comply with 28 C.F.R. § 35.163(b), after having surveyed all facilities that are the subject of this Agreement for the purpose of identifying those that have multiple entrances not all of which are accessible.

 

In order to ensure that the following spaces and elements in City facilities, which were altered after January 26, 1992, are readily accessible to and usable by persons with disabilities, the City will take the following actions:

 

A.        Within one month of the effective date of this Agreement, the City will, in writing, notify the Management Company responsible for the Biltmore Hotel (1200 Anastasia Avenue) and request that it do the following:[1]

 

1.         Throughout the facility, visual alarm appliances are absent in most public and common use areas, even though audible alarms are provided.  Provide visual alarm devices in toilet rooms and any other general usage areas (e.g., meeting rooms), hallways, lobbies, and any other area for common use.  Such devices shall be integrated into the facility alarm system and shall meet the requirements of the Standards for lamp type, color, pulse duration, intensity, and flash rate.  Visual alarm appliances shall be placed 80 inches above the highest floor level within the space or 6 inches below the ceiling, whichever is lower.  Visual alarm appliances shall be located such that no place in any room or space, including common corridors or hallways, required to have a visual alarm appliance shall be more than 50 feet from the signal.  In large rooms and spaces exceeding 100 feet across, without obstructions 6 feet above the finished floor, devices may be placed around the perimeter, spaced a maximum of 100 feet apart, in lieu of suspending appliances from the ceiling.  Standards §§ 4.1.3(14), 4.1.6(1)(b), 4.28.3.

 

2.         Lower Lobby (Near the Entrance to the Pool and Spa)

 

a. Telephone (altered element) – The lower telephone has a counter at 26 inches above the finished floor, a handset cord that is 27 inches long, and no volume control.  Provide an accessible telephone with a clear floor space of at least 30 inches by 48 inches that allows either a forward or parallel approach by a person using a wheelchair such that bases, enclosures, and fixed seats do not impede approaches to the telephone; with the highest operable part of the telephone mounted no more than 48 inches above the floor for a front approach or no more than 54 inches above the floor for a side approach; that are hearing aid compatible and have a volume control mechanism; with telephone books, if provided, located between 15 and 48 inches above the finished floor for a front approach or between 9 and 54 inches above the finished floor for a side approach; and with a cord of at least 29 inches long from the telephone to the handset.  Standards §§ 4.1.3(17), 4.1.6(1)(b), 4.31.

 

b. Men's Toilet Room with Stalls (altered)

 

i. The lowest urinal's rim is 19 inches above the finished floor.  Provide a urinal with an elongated rim mounted 17 inches or less above the finished floor, a clear floor space of at least 30 inches wide and 48 inches deep centered on the urinal, and a flush control height of 44 inches or less above the finished floor.  Standards §§ 4.1.3(11), 4.1.6(1)(b), 4.22.5, 4.18.2, 4.18.3, 4.18.4.

 

ii. Although there are several lavatories in the toilet room (one in the toilet stall for persons with disabilities and others for common use), none are accessible because the lavatory inside the toilet stall has a bottom apron edge at 26 ½ inches above the finished floor and the lavatories outside the stall have bottom apron edges of 26 inches above the finished floor. Provide a lavatory with the top of its rim or counter 34 inches or less above the finished floor; the bottom edge of the apron at least 29 inches above the finished floor; and knee and toe clearances that comply with Fig. 31.  Standards §§ 4.1.3(11), 4.1.6(1)(b), 4.22.6, 4.19.2, Fig. 31.

 

iii. Toilet Stall for Persons with Disabilities

 

(a) The toilet centerline is 15 inches from the side wall.  Provide a toilet with a centerline that measures 18 inches from the near side wall.  Standards §§ 4.1.3(11), 4.1.6(1)(b), 4.22.4, 4.17.3, Fig. 30.

 

(b) The side grab bar is 36 inches long and mounted with the farther end 40 inches from the back wall.  Provide a side grab bar that is at least 40 inches in overall length, with the far end mounted at least 52 inches from the rear wall and the closer end 12 inches or less from the rear wall.  Standards §§ 4.1.3(11), 4.1.6(1)(b), 4.22.4, 4.17.6, Figs. 30(a), (d).

 

(c) The flush control is on the closed side of the stall.  Provide a flush control mounted on the "open" side of the toilet's clear floor space; 44 inches or less above the finished floor; and requiring a maximum of 5 pounds of force to operate; or provide an automatic flush device.  Standards §§ 4.1.3(11), 4.1.6(1)(b), 4.22.4, 4.16.5, 4.17.2, 4.27.4.

 

c. Women's Toilet Room with Stalls

 

i. Although there are several lavatories in the toilet room (one in the toilet stall for persons with disabilities and others for common use), none are accessible because the lavatory inside the toilet stall has a bottom apron edge at 26 ½ inches above the finished floor and the lavatories outside the stall have bottom apron edges of 26 inches above the finished floor.  Provide a lavatory with the top of its rim or counter 34 inches or less above the finished floor; the bottom edge of the apron at least 29 inches above the finished floor; and knee and toe clearances that comply with Fig. 31.  Standards §§ 4.1.3(11), 4.1.6(1)(b), 4.22.6, 4.19.2, Fig. 31.

 

ii. Toilet Stall for Persons with Disabilities

 

(a) The toilet centerline is 15 inches from the side wall.  Provide a toilet with a centerline that measures 18 inches from the near side wall.  Standards §§ 4.1.3(11), 4.1.6(1)(b), 4.22.4, 4.17.3, Fig. 30.

 

(b) The side grab bar is 36 inches long and mounted with the closer end 4 inches from the back wall.  Provide a side grab bar that is at least 40 inches in overall length, with the far end mounted at least 52 inches from the rear wall and the closer end 12 inches or less from the rear wall.  Standards §§ 4.1.3(11), 4.1.6(1)(b), 4.22.4, 4.17.6, Figs. 30(a), (d).

 

d. Elevator by the Spa

 

i. Emergency Communication– The emergency communication is not identified by raised symbol and lettering.  Provide a two-way communication system such that it does not require voice communication, the highest operable part is a maximum of 48 inches above the finished floor of the car, and it is identified by a raised symbol and lettering located adjacent to the device.  If the system uses a handset, ensure that the length of the cord from the panel to the handset is at least 29 inches.  If the system is located in a closed compartment, ensure that the compartment door hardware operates without tight grasping, pinching or twisting of the wrist.  Standards §§ 4.1.3(5), 4.1.6(1)(b), 4.10.14.

 

3.         Upper Lobby

 

a. Historic Elevators

 

i. Because the historic elevator cars are not wide enough for all persons who use wheelchairs, provide appropriate directional signage to alternate accessible routes.

 

ii. There is no Braille signage on the hall call buttons.  Provide hall (lobby) call buttons with visual signals indicating when each call is registered and when each call is answered.  Ensure that the call buttons are centered at 42 inches above the finished floor, a minimum of ¾ inch in the smallest dimension, with the button designating the up direction on top; that the call buttons are raised or flush; and that objects mounted beneath hall call buttons do not project into the elevator lobby more than 4 inches.  Standards §§ 4.1.3(5), 4.1.6(1)(b), 4.10.3, Fig. 20.

 

b. Men's Toilet Room with Stalls

 

i. The lavatory is inaccessible because the bottom edge of the apron is 27 ½ inches above the finished floor.  Provide a lavatory with the top of its rim or counter 34 inches or less above the finished floor; the bottom edge of the apron at least 29 inches above the finished floor; and knee and toe clearances that comply with Fig. 31.  Standards §§ 4.1.3(11), 4.1.6(1)(b), 4.22.6, 4.19.2, Fig. 31.

 

ii. Although there are 5 toilet stalls, none of them are designed to be accessible for people with disabilities.  Provide a "standard" accessible toilet stall at least 60 inches wide and at least 59 inches deep (or at least 56 inches deep with a wall-mounted toilet) such that all of the stall's elements, including stall door, stall door hardware, water closet, size and arrangement, toe clearances, grab bars, controls, and dispensers, comply with the Standards.  Standards §§ 4.1.3(11), 4.1.6(1)(b), 4.22.4, 4.22.7, 4.13, 4.16, 4.17, 4.26, 4.27, Fig. 30.

 

iii. The air dryer is a protruding object that is not cane-detectable.  Provide an accessible route at this location such that the bottom leading edges of all elements measuring 27 inches and 80 inches above the finished floor protrude no more than 4 inches into walks, halls, corridors, passageways, or aisles.  Free-standing objects mounted on posts or pylons may overhang 12 inches maximum from 27 inches to 80 inches above the ground or finished floor.  Standards §§ 4.1.2(3), 4.1.6(1)(b), 4.4.

 

c. Women's Toilet Room with Stalls

 

i. Although there are 5 stalls and 1 is designed to be accessible for persons with disabilities, none complies fully with the Standards.  Provide a "standard" accessible toilet stall at least 60 inches wide and at least 59 inches deep (or at least 56 inches deep with a wall-mounted toilet) such that all of the stall's elements, including stall door, stall door hardware, water closet, size and arrangement, toe clearances, grab bars, controls, and dispensers, comply with the Standards.  Standards §§ 4.1.3(11), 4.1.6(1)(b), 4.22.4, 4.22.7, 4.13, 4.16, 4.17, 4.26, 4.27, Fig. 30.

 

4.         Near Catalonia Meeting Room

 

a. The drinking fountain spout is 39 inches above the finished floor.  Provide at least one drinking fountain with a spout height no higher than 36 inches, measured from the finished floor or ground surface to the spout outlet; and a spout located at the front of the unit that directs the water flow in a trajectory that is nearly parallel to the front of the unit and is positioned so the flow of water is within 3 inches of the front edge of the fountain and at least 4 inches high.  Ensure that fountain controls are operable with one hand, require 5 pounds of force or less to operate without tight grasping, pinching, or twisting of the wrist; and are front mounted or side mounted near the front edge.  For each accessible drinking fountain, provide a drinking fountain that is accessible to people who have difficulty bending or stooping.  This can be accommodated by the use of a "hi-lo" fountain; by providing one fountain accessible to those who use wheelchairs and one fountain at a standard height convenient for those who have difficulty bending; by providing a fountain accessible to people who use wheelchairs and a cup dispenser; or by such other means as would achieve the required accessibility for each group of people.  Standards §§ 4.1.3(10), 4.1.6(1)(b), 4.15, 4.27.4, Fig. 27.

 

b. Men's Toilet Room with Stalls

 

i. The toilet room door requires 9 pounds of force to operate.  Provide a door that requires no more than 5 pounds of force to open.  Standards §§ 4.1.3(7)(b), 4.1.6(1)(b), 4.13.11(2)(b).

 

ii. Although 2 toilet stalls are provided and 1 is designed for persons with disabilities, none fully complies with the Standards, because the stall designed for people with disabilities is only 54 inches wide, the toilet centerline is at 20 ½ inches from the side wall, the side grab bar is 45 inches long, and the closer end of the rear grab bar is 7 ½ inches to the side wall.  Provide a "standard" accessible toilet stall at least 60 inches wide and at least 59 inches deep (or at least 56 inches deep with a wall-mounted toilet) such that all of the stall's elements, including stall door, stall door hardware, water closet, size and arrangement, toe clearances, grab bars, controls, and dispensers, comply with the Standards.  Standards §§ 4.1.3(11), 4.1.6(1)(b), 4.22.4, 4.22.7, 4.13, 4.16, 4.17, 4.26, 4.27, Fig. 30.

 

c. Women's Toilet Room with Stalls

 

i. The toilet room door requires 9 pounds of force to operate.  Provide a door that requires no more than 5 pounds of force to open.  Standards §§ 4.1.3(7)(b), 4.1.6(1)(b), 4.13.11(2)(b).

 

ii. Although 2 toilet stalls are provided and 1 is designed for persons with disabilities, none fully complies with the Standards, because in the one designed for people with disabilities the clear floor space is 55 inches wide by 59 inches deep, the toilet centerline is 20 ½ inches from the side wall, and the closer end of the rear grab bar is 8 inches to the side wall.  Provide a "standard" accessible toilet stall at least 60 inches wide and at least 59 inches deep (or at least 56 inches deep with a wall-mounted toilet) such that all of the stall's elements, including stall door, stall door hardware, water closet, size and arrangement, toe clearances, grab bars, controls, and dispensers, comply with the Standards.  Standards §§ 4.1.3(11), 4.1.6(1)(b), 4.22.4, 4.22.7, 4.13, 4.16, 4.17, 4.26, 4.27, Fig. 30.

 

5.         Executive Center (existing)

 

a. The ramp between the Executive Center and the upper lobby level of the main hotel has an excessive slope, an excessive cross slope at the change of direction landing, and handrails are provided only on one side and, where provided, do not extend at the top and the bottom of the ramp.  Provide accessible, directional signage with the International Symbol of Accessibility at the ramp directing users to the accessible entrance, and provide accessible signage with the International Symbol of Accessibility at all permanent accessible entrances.  Standards §§ 4.1.3(8)(d), 4.1.3(16)(b), 4.1.6(1)(b), 4.13, 4.30.

 

6.         Spa

 

a. Men's Locker Room (Toilet Stalls, Showers, and Steam Room)

 

i. The room signage is not accessible.  Provide a toilet room sign with the International Symbol of Accessibility and raised and Braille characters.  The sign shall be mounted on the wall adjacent to the latch side of the door with the centerline of the sign at 60 inches above the finished floor and situated such that a person can approach within 3 inches of the sign without encountering an obstruction or standing within a door swing.  Standards §§ 4.1.2(7)(d), 4.1.6(1)(b), 4.30.1, 4.30.4, 4.30.5, 4.30.6, 4.30.7.

 

ii. The entry room door has only 10 inches of clearance on the push / latch side of the door and requires a forward approach.  On the push side of the door, provide a clear path of travel for a side approach at least 42 inches wide and at least 24 inches of clear maneuvering space adjacent to the latch side of the door.  Standards §§ 4.1.3(7)(b), 4.1.6(1)(b), 4.13.6, Fig. 25(c).

 

iii. The lower urinal rim is 19 inches above the finished floor.  Provide a urinal with an elongated rim mounted 17 inches or less above the finished floor, a clear floor space of at least 30 inches wide and 48 inches deep centered on the urinal, and a flush control height of 44 inches or less above the finished floor.  Standards §§ 4.1.3(11), 4.1.6(1)(b), 4.22.5, 4.18.2, 4.18.3, 4.18.4.

 

iv. The bottom edge of the lavatory apron is 27 ½ inches above the finished floor.  Provide a lavatory with the top of its rim or counter 34 inches or less above the finished floor; the bottom edge of the apron at least 29 inches above the finished floor; and knee and toe clearances that comply with Fig. 31.  Standards §§ 4.1.3(11), 4.1.6(1)(b), 4.22.6, 4.19.2, Fig. 31.

 

v. There is no accessible toilet stall.  Provide a "standard" accessible toilet stall at least 60 inches wide and at least 59 inches deep (or at least 56 inches deep with a wall-mounted toilet) such that all of the stall's elements, including stall door, stall door hardware, water closet, size and arrangement, toe clearances, grab bars, controls, and dispensers, comply with the Standards.  Standards §§ 4.1.3(11), 4.1.6(1)(b), 4.22.4, 4.22.7, 4.13, 4.16, 4.17, 4.26, 4.27, Fig. 30.

 

vi. The grab bar in the shower stall designed for persons with disabilities is not continuous and the transfer seat is 22 1/4 inches above the finished floor.  Provide a shower in this room that is exactly 36 inches wide and 36 inches deep with a 48 inch long and 36 inch wide clear floor space alongside the shower opening, and an L-shaped shower seat mounted on the wall opposite the controls and extending the full depth of the stall; OR a shower that is at least 30 inches deep and 60 inches wide with no curb or threshold and with a 36 inch deep and 60 inch wide clear floor space at the shower opening.  Ensure that the shower has grab bars, controls, a shower spray unit, and a seat, curb, and enclosure, if provided, that comply fully with the Standards and with Figs. 35, 36, and 37, as applicable.  Standards §§ 4.1.3(11), 4.1.6(1)(b), 4.21, Figs. 

 

b. Women's Locker Room (Toilet Stalls, Showers, and Steam Room)

 

i. The door signage does not contain the International Symbol of Accessibility or raised and Braille characters.  Provide a toilet room sign with the International Symbol of Accessibility and raised and Braille characters.  The sign shall be mounted on the wall adjacent to the latch side of the door with the centerline of the sign at 60 inches above the finished floor and situated such that a person can approach within 3 inches of the sign without encountering an obstruction or standing within a door swing.  Standards §§ 4.1.2(7)(d), 4.1.6(1)(b), 4.30.1, 4.30.4, 4.30.5, 4.30.6, 4.30.7.

 

ii. The entry doors require more than 15 pounds of force to operate.  Provide a door that requires no more than 5 pounds of force to open.  Standards §§ 4.1.3(7)(b), 4.1.6(1)(b), 4.13.11(2)(b).

 

iii. The exterior door has only 9 3/4 inches of maneuvering clearance on the pull/ latch side and 9 ½ inches of clearance on the push/ latch side. On the pull side of the door, provide a path of travel at least 48 inches wide for a side approach and at least 24 inches of clear maneuvering space adjacent to the latch side of the door.  Standards §§ 4.1.3(7)(b), 4.1.6(1)(b), 4.13.6, Fig. 25(c).  On the push side of the door, provide a clear path of travel for a side approach at least 42 inches wide and at least 24 inches of clear maneuvering space adjacent to the latch side of the door.  Standards §§ 4.1.3(7)(b), 4.1.6(1)(b), 4.13.6, Fig. 25(c).

 

iv. The interior door has only 8 ½ inches of maneuvering clearance on both the pull and push latch sides.  On the pull side of the door, provide a path of travel at least 48 inches wide for a side approach and at least 24 inches of clear maneuvering space adjacent to the latch side of the door.  Standards §§ 4.1.3(7)(b), 4.1.6(1)(b), 4.13.6, Fig. 25(c).  On the push side of the door, provide a clear path of travel for a side approach at least 42 inches wide and at least 24 inches of clear maneuvering space adjacent to the latch side of the door.  Standards §§ 4.1.3(7)(b), 4.1.6(1)(b), 4.13.6, Fig. 25(c).

 

v. The bottom edge of the lavatory apron is 27 ½ inches above the finished floor.  Provide a lavatory with the top of its rim or counter 34 inches or less above the finished floor; the bottom edge of the apron at least 29 inches above the finished floor; and knee and toe clearances that comply with Fig. 31.  Standards §§ 4.1.3(11), 4.1.6(1)(b), 4.22.6, 4.19.2, Fig. 31.

 

vi. There is no accessible toilet stall.  Provide a "standard" accessible toilet stall at least 60 inches wide and at least 59 inches deep (or at least 56 inches deep with a wall-mounted toilet) such that all of the stall's elements, including stall door, stall door hardware, water closet, size and arrangement, toe clearances, grab bars, controls, and dispensers, comply with the Standards.  Standards §§ 4.1.3(11), 4.1.6(1)(b), 4.22.4, 4.22.7, 4.13, 4.16, 4.17, 4.26, 4.27, Fig. 30.

 

vii. The shower stall designed for people with disabilities is 42 inches deep by 37 inches wide; the grab bar is not continuous; the transfer seat is 22 ½ inches above the room's finished floor or 20 inches above the shower's finished floor; and there is a 2-1/2 inch change in level between the finished floors of the room and the transfer shower.  Provide a shower in this room that is exactly 36 inches wide and 36 inches deep with a 48 inch long and 36 inch wide clear floor space alongside the shower opening, and an L-shaped shower seat mounted on the wall opposite the controls and extending the full depth of the stall; OR a shower that is at least 30 inches deep and 60 inches wide with no curb or threshold and with a 36 inch deep and 60 inch wide clear floor space at the shower opening.  Ensure that the shower has grab bars, controls, a shower spray unit, and a seat, curb, and enclosure, if provided, that comply fully with the Standards and with Figs. 35, 36, and 37, as applicable.  Standards §§ 4.1.3(11), 4.1.6(1)(b), 4.21, Figs. 35, 36, 37.

 

viii. The steam room threshold is 1 inch with no beveling and the fixed seating in the steam room is 20 inches above the finished floor.  Provide a door with a threshold no greater than ¼ inch, or between ¼ inch and ½ inch and beveled with a slope no greater than 1:2.  Standards §§ 4.1.3(7)(b), 4.1.6(1)(b), 4.13.8, 4.5.2.  Provide a 24 inch by 48 inch bench fixed to the wall along the bench's longer dimension.  Ensure that the bench has sufficient structural strength and is mounted with its surface between 17 inches and 19 inches above the finished floor.  Provide clear floor space alongside the bench to allow a person using a wheelchair to make a parallel transfer onto the bench.  Standards §§ 4.1.3(21), 4.1.6(1)(b), 4.35.4, 4.26.3.

 

B.         Within six months of the effective date of this Agreement, the City will complete the following modifications to the Hotel Biltmore Golf and Pro Shop (1210 Anastasia Avenue)

 

1.         Although audible alarms are provided, there are no visual alarm appliances throughout the facility.  Provide visual alarm devices in toilet rooms and any other general usage areas (e.g., meeting rooms), hallways, lobbies, and any other area for common use.  Such devices shall be integrated into the facility alarm system and shall meet the requirements of the Standards for lamp type, color, pulse duration, intensity, and flash rate.  Visual alarm appliances shall be placed 80 inches above the highest floor level within the space or 6 inches below the ceiling, whichever is lower.  Visual alarm appliances shall be located such that no place in any room or space, including common corridors or hallways, required to have a visual alarm appliance shall be more than 50 feet from the signal.  In large rooms and spaces exceeding 100 feet across, without obstructions 6 feet above the finished floor, devices may be placed around the perimeter, spaced a maximum of 100 feet apart, in lieu of suspending appliances from the ceiling.  Standards §§ 4.1.3(14), 4.1.6(1)(b), 4.28.3.

 

2.         Although directional signage is provided to some accessible features, some of the signage has faded and no longer meets the high-contrast requirements.  Provide accessible, directional signage with the International Symbol of Accessibility at inaccessible entrances directing users to the accessible entrance, and provide accessible signage with the International Symbol of Accessibility at all permanent accessible entrances.  Standards §§ 4.1.3(8)(d), 4.1.3(16)(b), 4.1.6(1)(b), 4.13, 4.30.

 

3.         The drinking fountains near the men's locker room and across from the pro shop are not accessible to persons who have difficulty bending or stooping.  For each accessible drinking fountain, provide a drinking fountain that is accessible to people who have difficulty bending or stooping.  This can be accommodated by the use of a "hi-lo" fountain; by providing one fountain accessible to those who use wheelchairs and one fountain at a standard height convenient for those who have difficulty bending; by providing a fountain accessible to people who use wheelchairs and a cup dispenser, or by such other means as would achieve the required accessibility for each group of people.  Standards §§ 4.1.3(10)(a), 4.1.6(1)(b).           

 

4.         Men's Locker Room (Toilet Stalls and Shower Stalls)

 

a. The top of the lavatory rim is 35 ½ inches above the finished floor and the bottom edge of the apron is 28 ½ inches above the finished floor.  Provide a lavatory with the top of its rim or counter 34 inches or less above the finished floor; the bottom edge of the apron at least 29 inches above the finished floor; and knee and toe clearances that comply with Fig. 31.  Standards §§ 4.1.3(11), 4.1.6(1)(b), 4.22.6, 4.19.2, Fig. 31.

 

b. Although 1 of the 2 toilet stalls is designed for ambulatory persons with disabilities, no toilet stall is provided for persons who use wheelchairs.  The "ambulatory" stall does not comply with the Standards because the stall partitions are 38 inches apart and the toilet seat is 19-1/2 inches above the finished floor.  Provide a "standard" accessible toilet stall at least 60 inches wide and at least 59 inches deep (or at least 56 inches deep with a wall-mounted toilet) such that all of the stall's elements, including stall door, stall door hardware, water closet, size and arrangement, toe clearances, grab bars, controls, and dispensers, comply with the Standards.  Standards §§ 4.1.3(11), 4.1.6(1)(b), 4.22.4, 4.22.7, 4.13, 4.16, 4.17, 4.26, 4.27, Fig. 30.

 

c. The clear floor space required at the lower urinal can be encroached upon by the outward-swinging door of the toilet stall designed for ambulatory persons with disabilities.  Ensure that no door swings into the required clear floor space at any accessible fixture.  Standards §§ 4.1.3(11), 4.1.6(1)(b), 4.22.2.

 

d. In the transfer shower stall designed for persons with disabilities, there is no 12 inch maneuvering clearance to the side rear of the transfer seat and the transfer seat does not extend the full depth of the stall.  Provide a shower in this room that is exactly 36 inches wide and 36 inches deep with a 48 inch long and 36 inch wide clear floor space alongside the shower opening, and an L-shaped shower seat mounted on the wall opposite the controls and extending the full depth of the stall; OR a shower that is at least 30 inches deep and 60 inches wide with no curb or threshold and with a 36 inch deep and 60 inch wide clear floor space at the shower opening.  Ensure that the shower has grab bars, controls, a shower spray unit, and a seat, curb, and enclosure, if provided, that comply fully with the Standards and with Figs. 35, 36, and 37, as applicable.  Standards §§ 4.1.3(11), 4.1.6(1)(b), 4.21, Figs. 35, 36, 37. 

 

5.         Women's Locker Room (Toilet Stalls and Shower Stalls)

 

a. The top of the lavatory rim is 36 ½ inches above the finished floor.  Provide a lavatory with the top of its rim or counter 34 inches or less above the finished floor; the bottom edge of the apron at least 29 inches above the finished floor; and knee and toe clearances that comply with Fig. 31.  Standards §§ 4.1.3(11), 4.1.6(1)(b), 4.22.6, 4.19.2, Fig. 31.

 

b. Although 1 of the 2 toilet stalls is designed for ambulatory persons with disabilities, none is provided for persons who use wheelchairs.  Additionally, the "ambulatory" stall's partitions are 38 inches apart.  Provide a "standard" accessible toilet stall at least 60 inches wide and at least 59 inches deep (or at least 56 inches deep with a wall-mounted toilet) such that all of the stall's elements, including stall door, stall door hardware, water closet, size and arrangement, toe clearances, grab bars, controls, and dispensers, comply with the Standards.  Standards §§ 4.1.3(11), 4.1.6(1)(b), 4.22.4, 4.22.7, 4.13, 4.16, 4.17, 4.26, 4.27, Fig. 30.  Provide at least one stall that is exactly 36 inches wide with an outward swinging, self-closing door and parallel grab bars complying with Fig 30(d).  Standards §§ 4.1.3(11), 4.1.6(1)(b), 4.22.4, Fig. 30(d).

 

c. In the transfer shower stall designed for persons with disabilities, there is no 12 inch maneuvering clearance to the side rear of the transfer bench and the bench does not extend the full depth of the stall.  Provide a shower in this room that is exactly 36 inches wide and 36 inches deep with a 48 inch long and 36 inch wide clear floor space alongside the shower opening, and an L-shaped shower seat mounted on the wall opposite the controls and extending the full depth of the stall; OR a shower that is at least 30 inches deep and 60 inches wide with no curb or threshold and with a 36 inch deep and 60 inch wide clear floor space at the shower opening.  Ensure that the shower has grab bars, controls, a shower spray unit, and a seat, curb, and enclosure, if provided, that comply fully with the Standards and with Figs. 35, 36, and 37, as applicable.  Standards §§ 4.1.3(11), 4.1.6(1)(b), 4.21, Figs. 35, 36, 37.  

 

d. There is a 2 inch change in level between the finished floors of the room and the transfer shower.  Provide a door with a threshold no greater than ¼ inch, or between ¼ inch and ½ inch and beveled with a slope no greater than 1:2.  Standards §§ 4.1.3(7)(b), 4.1.6(1)(b), 4.13.8, 4.5.2.

 

C.        Within  six months of the effective date of this Agreement, the City will complete the following modifications to the Biltmore Kerdyk Tennis Center (1150 Anastasia Avenue)

 

1.         There is no wheelchair seating at the fixed picnic tables.  Provide at least one picnic table on an accessible route such that there is knee space at the table at least 27 inches high, 30 inches wide, and 19 inches deep, and such that the height of the top of the table is between 28 inches and 34 inches above the ground.  Standards §§ 4.1.3(18), 4.1.6(1)(b), 4.32.3, 4.32.4.

 

2.         The drinking fountain between the men's and women's toilet rooms is not accessible to persons who have difficulty bending or stooping.  For each accessible drinking fountain, provide a drinking fountain that is accessible to people who have difficulty bending or stooping.  This can be accommodated by the use of a "hi-lo" fountain; by providing one fountain accessible to those who use wheelchairs and one fountain at a standard height convenient for those who have difficulty bending; by providing a fountain accessible to people who use wheelchairs and a cup dispenser, or by such other means as would achieve the required accessibility for each group of people.  Standards §§ 4.1.3(10)(a), 4.1.6(1)(b).

 

3.         The drinking fountain across from the elevator is not accessible to persons who have difficulty bending and stooping.  For each accessible drinking fountain, provide a drinking fountain that is accessible to people who have difficulty bending or stooping.  This can be accommodated by the use of a "hi-lo" fountain; by providing one fountain accessible to those who use wheelchairs and one fountain at a standard height convenient for those who have difficulty bending; by providing a fountain accessible to people who use wheelchairs and a cup dispenser, or by such other means as would achieve the required accessibility for each group of people.  Standards §§ 4.1.3(10)(a), 4.1.6(1)(b).

 

4.         Women's Single User Toilet Room

 

a. The toilet is inaccessible because the toilet centerline is 19 ½ inches from the side wall and the flush is on the closed/narrow side.  Provide a toilet with a centerline that measures 18 inches from the near side wall.  Standards §§ 4.1.3(11), 4.1.6(1)(b), 4.22.4, 4.17.3, Fig. 30.

 

b. The sanitary napkin dispenser is a protruding object that is not cane-detectable, with its bottom leading edge mounted 45 inches above the finished floor protruding 6 ½ inches from the back wall.  Provide an accessible route at this location such that the bottom leading edges of all elements measuring 27 inches and 80 inches above the finished floor protrude no more than 4 inches into walks, halls, corridors, passageways, or aisles.  Free-standing objects mounted on posts or pylons may overhang 12 inches maximum from 27 inches to 80 inches above the ground or finished floor.  Standards §§ 4.1.2(3), 4.1.6(1)(b), 4.4.

 

5.         Elevator (altered)

 

a. The centerline of the emergency controls is 25 inches above the finished floor.  Provide a two-way communication system such that it does not require voice communication, the highest operable part is a maximum of 48 inches above the finished floor of the car, and it is identified by a raised symbol and lettering located adjacent to the device.  If the system uses a handset, ensure that the length of the cord from the panel to the handset is at least 29 inches.  If the system is located in a closed compartment, ensure that the compartment door hardware operates without tight grasping, pinching or twisting of the wrist.  Standards §§ 4.1.3(5), 4.1.6(1)(b), 4.10.14.

 

b. The emergency communication system, as tested, does not work without voice communication.  There was no response to the silent call and a later inquiry revealed that the dispatcher could not identify where the call was coming from.  Provide a two-way communication system such that it does not require voice communication, the highest operable part is a maximum of 48 inches above the finished floor of the car, and it is identified by a raised symbol and lettering located adjacent to the device.  If the system uses a handset, ensure that the length of the cord from the panel to the handset is at least 29 inches.  If the system is located in a closed compartment, ensure that the compartment door hardware operates without tight grasping, pinching or twisting of the wrist.  Standards §§ 4.1.3(5), 4.1.6(1)(b), 4.10.14.

 

D.        Within nine months of the effective date of this Agreement, the City will complete the following modifications to City Hall (405 Biltmore Way)

 

1.         Parking

 

a. None of the six spaces reserved for persons with disabilities is designated as "van accessible."  On the shortest accessible route to the accessible entrance, provide one van accessible space designated as reserved for people with disabilities.  Ensure that van accessible spaces are a minimum of 96 inches wide and served by access aisles at least 96 inches wide.  At all spaces designated as reserved for persons with disabilities, provide vertical signs with the International Symbol of Accessibility located such that they cannot be obstructed by parked vehicles.  At van accessible spaces, provide an additional "Van-Accessible" sign located below the International Symbol of Accessibility.  Ensure that all spaces and access aisles for persons with disabilities are flat and level, with slopes and cross-slopes not exceeding 1:50 in all directions, and that their surfaces are firm, stable, and slip-resistant.  Standards §§ 4.1.2(5), 4.1.6(1)(b), 4.6, 4.30.7(1).

 

b. One of the spaces reserved for persons with disabilities in back of City Hall is missing a vertical sign with the International Symbol of Accessibility.  At all spaces designated as reserved for persons with disabilities, provide vertical signs with the International Symbol of Accessibility located such that they cannot be obstructed by parked vehicles.  At van accessible spaces, provide an additional "Van-Accessible" sign located below the International Symbol of Accessibility.  Standards §§ 4.1.2(5), 4.1.6(1)(b), 4.6.4, 4.30.7(1).

 

c. The space reserved for persons with disabilities facing Coral Way does not have a demarcated access aisle.  At each standard accessible space, provide an access aisle at least 60 inches wide.  At each van accessible space, provide an access aisles at least 96 inches wide.  Ensure that all access aisles are flat and level, with slopes and cross-slopes not exceeding 1:50 in all directions, and that their surfaces are firm, stable, and slip-resistant.  Standards §§ 4.1.2(5), 4.1.6(1)(b), 4.6.3, Fig. 9.

 

2.         Along the route from parking in back of City Hall to the front entrance, the sidewalk is 42 inches wide and does not have an adequate 60 inch by 60 inch passing area every 200 feet.  Provide at least one accessible route within the boundary of the site connecting these elements that, to the maximum extent feasible, coincides with the route for the general public.  The accessible route must have a minimum clear width of 36 inches, or a minimum clear width of 42 inches if there is a turn around an obstruction less than 48 inches wide; have passing spaces at least 60 inches by 60 inches at least every 200 feet; have a minimum clear headroom of 80 inches; have a surface that is firm, stable, and slip resistant; have, in the absence of a curb ramp, ramp, elevator, or platform lift, no level changes in excess of ½ inch vertically; and have a running slope of less than 1:20 (5%) (or have been constructed as a fully accessible ramp) and a cross slope of less than 1:50 (2%).  Standards §§ 4.1.3(1), 4.1.6(1)(b), 4.3, 4.5, Fig. 7.

 

3.         Ramps In Front of City Hall

 

a. The ramps' handrails are only on the outside of the ramps, they are mounted at 32 inches from the ramps' surfaces, and they do not extend at the bottoms of the ramps.  Provide handrails that are between 1¼ inches and 1½ inches in diameter with a continuous gripping surface along both sides of the ramp, extending at least 12 inches beyond the top and bottom of the ramp parallel with the ground surface.  Ensure that handrails are mounted between 34 inches and 38 inches above the ramp surface, with ends rounded or returned smoothly to the floor, wall, or post, and that they do not rotate within their fittings.  Standards §§ 4.1.2(1), 4.1.2(2), 4.1.6(1)(b), 4.3.8, 4.8.5.

 

b. The inaccessible "Employee Only" entrance lacks directional signage to the front entrance.  Provide accessible, directional signage with the International Symbol of Accessibility at inaccessible entrances directing users to the accessible entrance, and provide accessible signage with the International Symbol of Accessibility at all permanent accessible entrances.  Standards §§ 4.1.3(8)(d), 4.1.3(16)(b), 4.1.6(1)(b), 4.13, 4.30.

 

c. At the front entrance, the automatic door opener only controls the right leaf of the double doors, providing only 28 inches of clear opening width.  Provide a designated accessible entrance that has at least one active leaf with a minimum 32 inch clear opening width with the door open 90 degrees, measured between the face of the door and the opposite stop; that has either an automatic door operator or clear and level maneuvering clearance that complies fully with Fig. 25; and that has a threshold not exceeding ½ inch in height and beveled with a slope no greater than 1:2.  Ensure that all hardware and operating devices have shapes that are easy to grasp with one hand and do not require tight grasping, pinching, or twisting of the wrist to operate, and that they are mounted no higher than 48 inches above the finished floor.  Standards § 4.1.3(7)(a), 4.1.6(1)(b), 4.13, Figs. 24, 25.

 

d. The printing on the automatic door opener at the front entrance is faded.  Provide an automatic door opener that is operable working condition such that it is accessible to and usable by persons with disabilities.  Standards § 36.211.

 

4.         Public Offices

 

a. General Reception

 

i. The service counter is 38 inches above the finished floor.  Provide a counter on an accessible route such that a portion of the counter is at least 36 inches wide and no more than 36 inches above the finished floor.  Standards §§ 4.1.1(2), 4.1.6(1)(b), 7.2(1), 4.1.3(1), 4.3.

 

b. City Manager #100

 

i. The door requires 10 pounds of force to operate.  Provide a door that requires no more than 5 pounds of force to open.  Standards §§ 4.1.3(7)(b), 4.1.6(1)(b), 4.13.11(2)(b).

 

ii. The hardware on the inside of the door is knob style.  Provide a door with hardware that is easy to grasp with one hand and that does not require tight grasping, pinching, or twisting of the wrist to operate.  Lever-operated mechanisms, push-type mechanisms, and U-shaped handles are acceptable designs.  Standards §§ 4.1.3(7)(b), 4.1.6(1)(b), 4.13.9.

 

c. City Clerk #101

 

i. The door requires 10 pounds of force to operate.  Provide a door that requires no more than 5 pounds of force to open.  Standards §§ 4.1.3(7)(b), 4.1.6(1)(b), 4.13.11(2)(b).

 

ii. The hardware on the inside of the door is knob style.  Provide a door with hardware that is easy to grasp with one hand and that does not require tight grasping, pinching, or twisting of the wrist to operate.  Lever-operated mechanisms, push-type mechanisms, and U-shaped handles are acceptable designs.  Standards §§ 4.1.3(7)(b), 4.1.6(1)(b), 4.13.9.

 

iii. The service counter is 44 inches above the finished floor.  Provide a counter on an accessible route such that a portion of the counter is at least 36 inches wide and no more than 36 inches above the finished floor.  Standards §§ 4.1.1(2), 4.1.6(1)(b), 7.2(1), 4.1.3(1), 4.3.

 

d. Finance Cashier

 

i. The service counter is 39 ½ inches above the finished floor.  Provide a counter on an accessible route such that a portion of the counter is at least 36 inches wide and no more than 36 inches above the finished floor.  Standards §§ 4.1.1(2), 4.1.6(1)(b), 7.2(1), 4.1.3(1), 4.3.

 

e. Finance Reception

 

i. The service counter is 42 inches above the finished floor.  Provide a counter on an accessible route such that a portion of the counter is at least 36 inches wide and no more than 36 inches above the finished floor.  Standards §§ 4.1.1(2), 4.1.6(1)(b), 7.2(1), 4.1.3(1), 4.3.

 

f. Conference Room (escorted, by appointment only)

 

i. The hardware on the inside of the door is knob style.  Provide a door with hardware that is easy to grasp with one hand and that does not require tight grasping, pinching, or twisting of the wrist to operate.  Lever-operated mechanisms, push-type mechanisms, and U-shaped handles are acceptable designs.  Standards §§ 4.1.3(7)(b), 4.1.6(1)(b), 4.13.9.

 

g. City Attorney, 2nd floor

 

i. The door requires 12 pounds of force to operate.  Provide a door that requires no more than 5 pounds of force to open.  Standards §§ 4.1.3(7)(b), 4.1.6(1)(b), 4.13.11(2)(b).

 

ii. The hardware on the door is knob style.  Provide a door with hardware that is easy to grasp with one hand and that does not require tight grasping, pinching, or twisting of the wrist to operate.  Lever-operated mechanisms, push-type mechanisms, and U-shaped handles are acceptable designs.  Standards §§ 4.1.3(7)(b), 4.1.6(1)(b), 4.13.9.

 

h. City Commission Office

 

i. The hardware on the door is knob style.  Provide a door with hardware that is easy to grasp with one hand and that does not require tight grasping, pinching, or twisting of the wrist to operate.  Lever-operated mechanisms, push-type mechanisms, and U-shaped handles are acceptable designs.  Standards §§ 4.1.3(7)(b), 4.1.6(1)(b), 4.13.9.

 

i. Planning Department, 3rd floor

 

i. The door requires 15 pounds of force to operate.  Provide a door that requires no more than 5 pounds of force to open.  Standards §§ 4.1.3(7)(b), 4.1.6(1)(b), 4.13.11(2)(b).

ii. The hardware on the door is knob style.  Provide a door with hardware that is easy to grasp with one hand and that does not require tight grasping, pinching, or twisting of the wrist to operate.  Lever-operated mechanisms, push-type mechanisms, and U-shaped handles are acceptable designs.  Standards §§ 4.1.3(7)(b), 4.1.6(1)(b), 4.13.9.

 

j. Owner / Building Rep

 

i. The service counter is 44 inches above the finished floor.  Provide a door that requires no more than 5 pounds of force to open.  Standards §§ 4.1.3(7)(b), 4.1.6(1)(b), 4.13.11(2)(b).

 

k. Cashier

 

i. The service counter is 39 inches above the finished floor.  Provide a door that requires no more than 5 pounds of force to open.  Standards §§ 4.1.3(7)(b), 4.1.6(1)(b), 4.13.11(2)(b).

 

l. Microfilm Room

 

i. The hardware on the door is knob style.  Provide a door with hardware that is easy to grasp with one hand and that does not require tight grasping, pinching, or twisting of the wrist to operate.  Lever-operated mechanisms, push-type mechanisms, and U-shaped handles are acceptable designs.  Standards §§ 4.1.3(7)(b), 4.1.6(1)(b), 4.13.9.

 

m. Board of Architects and Inspectors

 

i. The hardware on the door is knob style.  Provide a door with hardware that is easy to grasp with one hand and that does not require tight grasping, pinching, or twisting of the wrist to operate.  Lever-operated mechanisms, push-type mechanisms, and U-shaped handles are acceptable designs.  Standards §§ 4.1.3(7)(b), 4.1.6(1)(b), 4.13.9.

 

ii. The service counter is 44 ½ inches above the finished floor.  Provide a counter on an accessible route such that a portion of the counter is at least 36 inches wide and no more than 36 inches above the finished floor.  Standards §§ 4.1.1(2), 4.1.6(1)(b), 7.2(1), 4.1.3(1), 4.3.

 

n. Brochures and Forms

 

i. The service counter is 41 ½ inches finished floor.  Provide a counter on an accessible route such that a portion of the counter is at least 36 inches wide and no more than 36 inches above the finished floor.  Standards §§ 4.1.1(2), 4.1.6(1)(b), 7.2(1), 4.1.3(1), 4.3.

 

o. Inspector's Office, Mezzanine Level

 

i. The service counter is 44 inches finished floor and the nearby auxiliary table has an apron that is 26 inches above the finished floor.  Provide a counter on an accessible route such that a portion of the counter is at least 36 inches wide and no more than 36 inches above the finished floor.  Standards §§ 4.1.1(2), 4.1.6(1)(b), 7.2(1), 4.1.3(1), 4.3.   Provide a table or counter that has clear floor space that is 30 inches wide and 48 inches deep, knee clearance at least 27 inches high, 30 inches wide, and 19 inches deep, and a writing surface between 28 and 34 inches above the finished floor.  Standards §§ 4.1.3(18), 4.1.6(1)(b), 4.2.4.1, 4.32.

 

5.         Commission Room, 2nd floor

 

a. There is no accessible route to the audience podium (it is up 1 step) and Commission dias (it is up 2 steps).  Provide an accessible route connecting the wheelchair seating to the audience podium.  Standards §§ 4.1.3(19)(a), 4.1.6(1)(b), 4.3, 4.33.5.

 

6.         The elevator doors will reopen if obstructed, however they only remain open for 3 seconds.  Provide doors that open and close automatically with a reopening device that will stop and reopen the car door and hoistway door automatically if the door becomes obstructed by an object or person.  Ensure that the device is capable of completing these operations without requiring contact for obstructions passing through the opening at heights of 5 inches and 29 inches above the finished floor; that door reopening devices remain effective for at least 20 seconds, after which the doors may close; that the minimum time from notification that a car is answering a call until the doors of that car start to close is 5 seconds; and that the minimum time for elevator doors to remain fully open in response to a car call is 3 seconds.  Standards §§ 4.1.3(5), 4.1.6(1)(b), 4.10.6, 4.10.7, 4.10.8, Figs. 20, 21.

 

7.         Men's Toilet Room with Stalls

 

a. The door requires 15 pounds of force to operate.  Provide a door that requires no more than 5 pounds of force to open.  Standards §§ 4.1.3(7)(b), 4.1.6(1)(b), 4.13.11(2)(b).

 

b. Although there are 3 urinals, none are accessible because the lowest rim height is 29 inches high, the flush control is 51 inches high, and the clear floor space is only 32 inches deep.  Provide a urinal with an elongated rim mounted 17 inches or less above the finished floor, a clear floor space of at least 30 inches wide and 48 inches deep centered on the urinal, and a flush control height of 44 inches or less above the finished floor.  Standards §§ 4.1.3(11), 4.1.6(1)(b), 4.22.5, 4.18.2, 4.18.3, 4.18.4.

 

c. Although 1 of the 3 toilet stalls is designed to be accessible to ambulatory persons with disabilities, none is accessible to persons who use wheelchairs.  The "ambulatory" stall has partitions set 35 inches apart and the flush control is 66 inches above the finished floor.  Provide a "standard" accessible toilet stall at least 60 inches wide and at least 59 inches deep (or at least 56 inches deep with a wall-mounted toilet) such that all of the stall's elements, including stall door, stall door hardware, water closet, size and arrangement, toe clearances, grab bars, controls, and dispensers, comply with the Standards.  Standards §§ 4.1.3(11), 4.1.6(1)(b), 4.22.4, 4.22.7, 4.13, 4.16, 4.17, 4.26, 4.27, Fig. 30.

 

8.         Women's Toilet Room with Stalls

 

a. The exterior door requires 15 pounds of force to operate and the interior door requires 25 pounds of force to operate.  Provide a door that requires no more than 5 pounds of force to open.  Standards §§ 4.1.3(7)(b), 4.1.6(1)(b), 4.13.11(2)(b).

 

b. The door hardware is knob style.  Provide a door with hardware that is easy to grasp with one hand and that does not require tight grasping, pinching, or twisting of the wrist to operate.  Lever-operated mechanisms, push-type mechanisms, and U-shaped handles are acceptable designs.  Standards §§ 4.1.3(7)(b), 4.1.6(1)(b), 4.13.9.

 

c. The soap dispenser is mounted at 48 inches high with a forward reach required over a 20 inch obstruction.  Provide a soap dispenser with the controls a maximum height above the finished floor of 48 inches for a forward approach or 54 inches for a side approach and that is accompanied by clear floor space of 30 by 48 inches that allows a forward or parallel approach by a person using a wheelchair.  Standards §§ 4.1.3(13), 4.1.6(1)(b), 4.27.2, 4.27.3, 4.2.4, 4.2.5, 4.2.6, Fig. 4.

 

d. The sanitary napkin dispenser requires tight pinching and wrist twisting to operate.  Provide a sanitary napkin dispenser with mechanical controls, if any, that can be operated with 5 pounds of force or less and that can be used with one hand and without tight grasping, pinching, or twisting of the wrist (lever-operated, push-type, and electronically controlled mechanisms are examples of acceptable designs).  Standards §§ 4.1.3(13), 4.1.6(1)(b), 4.27.4.

 

e. Although 1 of the 3 toilet stalls is designed for ambulatory persons with disabilities, none is provided for persons who use wheelchairs.  The coat hook in the "ambulatory" stall is inaccessible.  Provide a "standard" accessible toilet stall at least 60 inches wide and at least 59 inches deep (or at least 56 inches deep with a wall-mounted toilet) such that all of the stall's elements, including stall door, stall door hardware, water closet, size and arrangement, toe clearances, grab bars, controls, and dispensers, comply with the Standards.  Standards §§ 4.1.3(11), 4.1.6(1)(b), 4.22.4, 4.22.7, 4.13, 4.16, 4.17, 4.26, 4.27, Fig. 30.

 

9.         The spout on the first floor drinking fountain is 41 inches above the finished floor; the water flows 2 inches high and 5 inches from the front of the fountain; there is no access for people who have trouble bending or stooping; and the fountain protrudes 22 inches and is not cane-detectable.  Provide a drinking fountain with a spout height no higher than 36 inches, measured from the finished floor or ground surface to the spout outlet; and a spout located at the front of the unit that directs the water flow in a trajectory that is nearly parallel to the front of the unit and is positioned so the flow of water is within 3 inches of the front edge of the fountain and at least 4 inches high.  Ensure that fountain controls are operable with one hand, require 5pounds of force or less to operate without tight grasping, pinching, or twisting of the wrist; and are front mounted or side mounted near the front edge.  For each accessible drinking fountain, provide a drinking fountain that is accessible to people who have difficulty bending or stooping.  This can be accommodated by the use of a "hi-lo" fountain; by providing one fountain accessible to those who use wheelchairs and one fountain at a standard height convenient for those who have difficulty bending; by providing a fountain accessible to people who use wheelchairs and a cup dispenser; or by such other means as would achieve the required accessibility for each group of people.  Standards §§ 4.1.3(10), 4.1.6(1)(b), 4.15, 4.27.4, Fig. 27.

 

10.       The spout on the second floor drinking fountain is 38 ½ inches high; the water flows 5 inches from the front of the fountain; there is no access for people who have trouble bending or stooping; and the fountain protrudes 22 inches and is not cane-detectable.  Provide at least one drinking fountain with a spout height no higher than 36 inches, measured from the finished floor or ground surface to the spout outlet; and a spout located at the front of the unit that directs the water flow in a trajectory that is nearly parallel to the front of the unit and is positioned so the flow of water is within 3 inches of the front edge of the fountain and at least 4 inches high.  Ensure that fountain controls are operable with one hand, require 5 pounds of force or less to operate without tight grasping, pinching, or twisting of the wrist; and are front mounted or side mounted near the front edge.  For each accessible drinking fountain, provide a drinking fountain that is accessible to people who have difficulty bending or stooping.  This can be accommodated by the use of a "hi-lo" fountain; by providing one fountain accessible to those who use wheelchairs and one fountain at a standard height convenient for those who have difficulty bending; by providing a fountain accessible to people who use wheelchairs and a cup dispenser; or by such other means as would achieve the required accessibility for each group of people.  Standards §§ 4.1.3(10), 4.1.6(1)(b), 4.15, 4.27.4, Fig. 27.

 

E.         The City represents that it intends to renovate the City Hall Annex (285 Aragon Avenue / 2300 Salzedo Street).  Within 6 months of the effective date of this Agreement, the City will submit for the Department's prior approval complete design and construction documentation, including construction drawings, as built drawings, project manuals, addenda, and change orders for the alteration of the City Hall Annex.  The Department will review the documentation for conformity to the ADA Standards for Accessible Design and will note any deficiencies.  Before the facility is occupied, the City will ensure that the alterations carried out in a way that meets the Department's approval.

 

F.         Within 12 months of the effective date of this Agreement, the City will complete the following modifications to the Granada Golf Course (2001 Granada Blvd.)

 

1.         Parking– Although there are 11 parking spaces, none are designed or designated for people with disabilities.  On the shortest accessible route to the accessible entrance, provide one van accessible space a minimum of 96 inches wide, served by access aisles at least 96 inches wide, with vertical signs with the International Symbol of Accessibility located such that they cannot be obstructed by parked vehicles, and with an additional "Van-Accessible" sign located below the International Symbol of Accessibility.  Standards §§ 4.1.2(5)(b), 4.1.6(1)(b), 4.6, 4.30.7(1).

 

2.         Route

 

a. The inaccessible route from the parking lot to the front entrance to the back door of the pro shop does not have directional signage to the accessible route.  Provide accessible, directional signage with the International Symbol of Accessibility at inaccessible entrances directing users to the accessible entrance, and provide accessible signage with the International Symbol of Accessibility at all permanent accessible entrances.  Standards §§ 4.1.3(8)(d), 4.1.3(16)(b), 4.1.6(1)(b), 4.13, 4.30.

 

b. The route to the North Greenway Drive entrance does not have signage indicating it as the accessible route.  Provide accessible, directional signage with the International Symbol of Accessibility at inaccessible entrances directing users to the accessible entrance, and provide accessible signage with the International Symbol of Accessibility at all permanent accessible entrances.  Standards §§ 4.1.3(8)(d), 4.1.3(16)(b), 4.1.6(1)(b), 4.13, 4.30.

 

c. Accessible Entrance at the Back of the Pro Shop

 

i. There is a 3 inch unbeveled threshold at the exterior entrance.  Provide a door with a threshold no greater than ¼ inch, or between ¼ inch and ½ inch and beveled with a slope no greater than 1:2.  Standards §§ 4.1.3(7)(b), 4.1.6(1)(b), 4.13.8, 4.5.2.

 

ii. The entry door hardware requires tight grasping to open and cannot be opened with one hand.  Provide a door with hardware that is easy to grasp with one hand and that does not require tight grasping, pinching, or twisting of the wrist to operate.  Lever-operated mechanisms, push-type mechanisms, and U-shaped handles are acceptable designs.  Standards §§ 4.1.3(7)(b), 4.1.6(1)(b), 4.13.9.

 

3.         Men's Locker Room

 

a. The door signage is mounted above the door.  Provide a sign with raised and Braille characters.  The sign shall be mounted on the wall adjacent to the latch side of the door with the centerline of the sign at 60 inches above the finished floor and situated such that a person can approach within 3 inches of the sign without encountering an obstruction or standing within a door swing.  Standards §§ 4.1.2(7)(d), 4.1.6(1)(b), 4.30.1, 4.30.4, 4.30.5, 4.30.6.

 

b. There are no accessible shower stalls.  Provide a shower in this room that is exactly 36 inches wide and 36 inches deep with a 48 inch long and 36 inch wide clear floor space alongside the shower opening, and an L-shaped shower seat mounted on the wall opposite the controls and extending the full depth of the stall; OR a shower that is at least 30 inches deep and 60 inches wide with no curb or threshold and with a 36 inch deep and 60 inch wide clear floor space at the shower opening.  Ensure that the shower has grab bars, controls, a shower spray unit, and a seat, curb, and enclosure, if provided, that comply fully with the Standards and with Figs. 35, 36, and 37, as applicable.  Standards §§ 4.1.3(11), 4.1.6(1)(b), 4.21, Figs. 35, 36, 37.

 

c. The changing bench is in the middle of the room, not next to a wall.  Provide a 24 inch by 48 inch bench fixed to the wall along the bench's longer dimension.  Ensure that the bench has sufficient structural strength and is mounted with its surface between 17 inches and 19 inches above the finished floor.  Provide clear floor space alongside the bench to allow a person using a wheelchair to make a parallel transfer onto the bench.  Standards §§ 4.1.3(21), 4.1.6(1)(b), 4.35.4, 4.26.3.

 

4.         Men's Toilet Room with Stalls

 

a. The room signage is mounted above the door.  Provide a sign with raised and Braille characters.  The sign shall be mounted on the wall adjacent to the latch side of the door with the centerline of the sign at 60 inches above the finished floor and situated such that a person can approach within 3 inches of the sign without encountering an obstruction or standing within a door swing.  Standards §§ 4.1.2(7)(d), 4.1.6(1)(b), 4.30.1, 4.30.4, 4.30.5, 4.30.6.

 

b. The entry door provides only 30 inches of clear opening width.  Provide a door with a clear opening of 32 inches with the door open 90 degrees, measured between the face of the door and the opposite stop.  Standards §§ 4.1.3(7)(b), 4.1.6(1)(b), 4.13.5, Fig. 24.

 

c. None of the 3 urinals are accessible to persons with disabilities.  Provide a urinal with an elongated rim mounted 17 inches or less above the finished floor, a clear floor space of at least 30 inches wide and 48 inches deep centered on the urinal, and a flush control height of 44 inches or less above the finished floor.  Standards §§ 4.1.3(11), 4.1.6(1)(b), 4.22.5, 4.18.2, 4.18.3, 4.18.4.

 

d. None of the 3 toilet stalls are accessible to persons with disabilities.  Provide a "standard" accessible toilet stall at least 60 inches wide and at least 59 inches deep (or at least 56 inches deep with a wall-mounted toilet) such that all of the stall's elements, including stall door, stall door hardware, water closet, size and arrangement, toe clearances, grab bars, controls, and dispensers, comply with the Standards.  Standards §§ 4.1.3(11), 4.1.6(1)(b), 4.22.4, 4.22.7, 4.13, 4.16, 4.17, 4.26, 4.27, Fig. 30.

 

e. The lavatory rim is 36 inches above the finished floor and the hot water and drain pipes are not insulated or otherwise configured to protect against contact.  Provide a lavatory with the top of its rim or counter 34 inches or less above the finished floor; the bottom edge of the apron at least 29 inches above the finished floor; and knee and toe clearances that comply with Fig. 31.  Standards §§ 4.1.3(11), 4.1.6(1)(b), 4.22.6, 4.19.2, Fig. 31.  Provide hot water and drain pipes that are insulated or otherwise configured to protect against contact.  Standards §§ 4.1.3(11), 4.1.6(1)(b), 4.22.6, 4.19.4.

 

5.         Women's Locker Room

 

a. The door signage does not include the International Symbol of Accessibility.   Provide a toilet room sign with raised and Braille characters.  The sign shall be mounted on the wall adjacent to the latch side of the door with the centerline of the sign at 60 inches above the finished floor and situated such that a person can approach within 3 inches of the sign without encountering an obstruction or standing within a door swing.  Standards §§ 4.1.2(7)(d), 4.1.6(1)(b), 4.30.1, 4.30.4, 4.30.5, 4.30.6.

 

b. No changing bench is provided.  Provide a 24 inch by 48 inch bench fixed to the wall along the bench's longer dimension.  Ensure that the bench has sufficient structural strength and is mounted with its surface between 17 inches and 19 inches above the finished floor.  Provide clear floor space alongside the bench to allow a person using a wheelchair to make a parallel transfer onto the bench.  Standards §§ 4.1.3(21), 4.1.6(1)(b), 4.35.4, 4.26.3.

 

c. There are no accessible shower stalls.  Provide a shower in this room that is exactly 36 inches wide and 36 inches deep with a 48 inch long and 36 inch wide clear floor space alongside the shower opening, and an L-shaped shower seat mounted on the wall opposite the controls and extending the full depth of the stall; OR a shower that is at least 30 inches deep and 60 inches wide with no curb or threshold and with a 36 inch deep and 60 inch wide clear floor space at the shower opening.  Ensure that the shower has grab bars, controls, a shower spray unit, and a seat, curb, and enclosure, if provided, that comply fully with the Standards and with Figs. 35, 36, and 37, as applicable.  Standards §§ 4.1.3(11), 4.1.6(1)(b), 4.21, Figs. 35, 36, 37.

 

6.         Women's Toilet Room with Stalls

 

a. The room signage is mounted on the door and does not contain the International Symbol of Accessibility or raised and Braille characters.  Provide a sign with raised and Braille characters.  The sign shall be mounted on the wall adjacent to the latch side of the door with the centerline of the sign at 60 inches above the finished floor and situated such that a person can approach within 3 inches of the sign without encountering an obstruction or standing within a door swing.  Standards §§ 4.1.2(7)(d), 4.1.6(1)(b), 4.30.1, 4.30.4, 4.30.5, 4.30.6.

 

b. The entry door provides only 27 inches of clear opening width and requires 15 pounds of force to operate.  Provide a door with a clear opening of 32 inches with the door open 90 degrees, measured between the face of the door and the opposite stop.  Standards §§ 4.1.3(7)(b), 4.1.6(1)(b), 4.13.5, Fig. 24.

 

c. Neither of the toilet stalls are designed for persons with disabilities.  Provide a "standard" accessible toilet stall at least 60 inches wide and at least 59 inches deep (or at least 56 inches deep with a wall-mounted toilet) such that all of the stall's elements, including stall door, stall door hardware, water closet, size and arrangement, toe clearances, grab bars, controls, and dispensers, comply with the Standards.  Standards §§ 4.1.3(11), 4.1.6(1)(b), 4.22.4, 4.22.7, 4.13, 4.16, 4.17, 4.26, 4.27, Fig. 30.

 

d. The top of the lavatory rim is 37 inches above the finished floor and the hot water and drain pipes are not insulated or configured to protect against contact.  Provide a lavatory with the top of its rim or counter 34 inches or less above the finished floor; the bottom edge of the apron at least 29 inches above the finished floor; and knee and toe clearances that comply with Fig. 31.  Standards §§ 4.1.3(11), 4.1.6(1)(b), 4.22.6, 4.19.2, Fig. 31.  Provide hot water and drain pipes that are insulated or otherwise configured to protect against contact.  Standards §§ 4.1.3(11), 4.1.6(1)(b), 4.22.6, 4.19.4.

 

7.         The drinking fountain in the Pro Shop is not accessible to people who have trouble bending or stooping.  For each accessible drinking fountain, provide a drinking fountain that is accessible to people who have difficulty bending or stooping.  This can be accommodated by the use of a "hi-lo" fountain; by providing one fountain accessible to those who use wheelchairs and one fountain at a standard height convenient for those who have difficulty bending; by providing a fountain accessible to people who use wheelchairs and a cup dispenser, or by such other means as would achieve the required accessibility for each group of people.  Standards §§ 4.1.3(10)(a), 4.1.6(1)(b).

 

8.         The door to Big Al's Repair Shop requires 15 pounds of force to operate.  Provide a door that requires no more than 5 pounds of force to open.  Standards §§ 4.1.3(7)(b), 4.1.6(1)(b), 4.13.11(2)(b).

 

9.         The door from the Café to the Pro Shop requires 13 pounds of force to operate.  Provide a door that requires no more than 5 pounds of force to open.  Standards      §§ 4.1.3(7)(b), 4.1.6(1)(b), 4.13.11(2)(b).

 

10.       The double doors to the Café have a 3 inch threshold.  Provide a door with a threshold no greater than ¼ inch, or between ¼ inch and ½ inch and beveled with a slope no greater than 1:2.  Standards §§ 4.1.3(7)(b), 4.1.6(1)(b), 4.13.8, 4.5.2.

 

G.        Within 12 months of the effective date of this Agreement, the City will complete the following modifications to the Central Police and Fire (2801 Salzedo Street)

 

1.         The curb cut between the on-street parking and the route to the entrance has a 1 inch vertical rise and no detectable warnings.  Provide a curb ramp located so that it does not project into this element and all aspects of the ramp or curb cut comply with the Standards.  Standards §§ 4.1.2(1), 4.1.2(2), 4.1.6(1)(b), 4.3.8, 4.7.6.

 

2.         The first floor wall-mounted lobby drinking fountain has a spout height of 43 inches above the finished floor; the water height reaches only 2 inches; and there is only 23 inches of knee space above the finished floor and 10 inches of knee depth.  Provide at least one drinking fountain with a spout height no higher than 36 inches, measured from the finished floor or ground surface to the spout outlet; and a spout located at the front of the unit that directs the water flow in a trajectory that is nearly parallel to the front of the unit and is positioned so the flow of water is within 3 inches of the front edge of the fountain and at least 4 inches high.  Ensure that fountain controls are operable with one hand, require 5 pounds of force or less to operate without tight grasping, pinching, or twisting of the wrist; and are front mounted or side mounted near the front edge.  For each accessible drinking fountain, provide a drinking fountain that is accessible to people who have difficulty bending or stooping.  This can be accommodated by the use of a "hi-lo" fountain; by providing one fountain accessible to those who use wheelchairs and one fountain at a standard height convenient for those who have difficulty bending; by providing a fountain accessible to people who use wheelchairs and a cup dispenser; or by such other means as would achieve the required accessibility for each group of people.  Standards §§ 4.1.3(10), 4.1.6(1)(b), 4.15, 4.27.4, Fig. 27.

 

3.         The Records Window Service Counter is 38 inches above the finished floor.  Provide a counter on an accessible route such that a portion of the counter is at least 36 inches wide and no more than 36 inches above the finished floor.  Standards §§ 4.1.1(2), 4.1.6(1)(b), 7.2(1), 4.1.3(1), 4.3.

 

4.         The Parking Department Second Floor Service Counter is 44 inches above the finished floor.  Provide a counter on an accessible route such that a portion of the counter is at least 36 inches wide and no more than 36 inches above the finished floor.  Standards §§ 4.1.1(2), 4.1.6(1)(b), 7.2(1), 4.1.3(1), 4.3.

 

5.         The Employee Relations Service Counter is 43 inches above the finished floor.  Provide a counter on an accessible route such that a portion of the counter is at least 36 inches wide and no more than 36 inches above the finished floor.  Standards §§ 4.1.1(2), 4.1.6(1)(b), 7.2(1), 4.1.3(1), 4.3.

 

6.         Second Floor Men's Toilet Room with Stalls

 

a. The International Symbol of Access is provided on the door, rather than on the wall on the latch side of the door.  Provide a toilet room sign with raised and Braille characters.  The sign shall be mounted on the wall adjacent to the latch side of the door with the centerline of the sign at 60 inches above the finished floor and situated such that a person can approach within 3 inches of the sign without encountering an obstruction or standing within a door swing.  Standards §§ 4.1.2(7)(d), 4.1.6(1)(b), 4.30.1, 4.30.4, 4.30.5, 4.30.6.

 

b. The exterior door's clear opening width is 26 inches and the interior door frame's (door has been removed) clear opening width is 28 inches.  The door requires 15 pounds of force to operate.  Provide a door and the interior door frame with a clear opening of 32 inches with the door open 90 degrees, measured between the face of the door and the opposite stop.  Standards §§ 4.1.3(7)(b), 4.1.6(1)(b), 4.13.5, Fig. 24.  Provide a door that requires no more than 5 pounds of force to open.  Standards §§ 4.1.3(7)(b), 4.1.6(1)(b), 4.13.11(2)(b).

 

c. One of the 2 urinals is lower, but its rim is 23 inches above the finished floor and the flush control is 53 inches above the finished floor.  Additionally, the urinals are in an alcove and the route into the alcove has a clear opening width of only 30 inches.  Provide an accessible route to the urinal with a minimum clear width of 36 inches, except at doors, where the width may decrease to 32 inches.  Standards §§ 4.1.3(1), 4.1.6(1)(b), 4.3.3, 4.13.5.  Provide a urinal with an elongated rim mounted 17 inches or less above the finished floor, a clear floor space of at least 30 inches wide and 48 inches deep centered on the urinal, and a flush control height of 44 inches or less above the finished floor.  Standards §§ 4.1.3(11), 4.1.6(1)(b), 4.22.5, 4.18.2, 4.18.3, 4.18.4.

 

d. The top rim of the lavatory is 35 inches above the finished floor.  Provide a lavatory with the top of its rim or counter 34 inches or less above the finished floor; the bottom edge of the apron at least 29 inches above the finished floor; and knee and toe clearances that comply with Fig. 31.  Standards §§ 4.1.3(11), 4.1.6(1)(b), 4.22.6, 4.19.2, Fig. 31.

 

e. Although 2 toilet stalls are provided, neither is configured to be accessible to persons who use wheelchairs.  One is loosely configured in the "alternate" stall configuration designed for ambulatory persons with disabilities.   Provide a "standard" accessible toilet stall at least 60 inches wide and at least 59 inches deep (or at least 56 inches deep with a wall-mounted toilet) such that all of the stall's elements, including stall door, stall door hardware, water closet, size and arrangement, toe clearances, grab bars, controls, and dispensers, comply with the Standards.  Standards §§ 4.1.3(11), 4.1.6(1)(b), 4.22.4, 4.22.7, 4.13, 4.16, 4.17, 4.26, 4.27, Fig. 30.

 

7.         Second Floor Women's Toilet Room with Stalls

 

a. The door provides only 26 inches of clear opening width.  Provide a door with a clear opening of 32 inches with the door open 90 degrees, measured between the face of the door and the opposite stop.  Standards §§ 4.1.3(7)(b), 4.1.6(1)(b), 4.13.5, Fig. 24.

 

b. The International Symbol of Accessibility is mounted on the door and the permanent room sign is mounted on the adjacent wall, rather than on the wall to the latch side of the door.  Provide a toilet room sign with the International Symbol of Accessibility and raised and Braille characters.  The sign shall be mounted on the wall adjacent to the latch side of the door with the centerline of the sign at 60 inches above the finished floor and situated such that a person can approach within 3 inches of the sign without encountering an obstruction or standing within a door swing.  Standards §§ 4.1.2(7)(d), 4.1.6(1)(b), 4.30.1, 4.30.4, 4.30.5, 4.30.6, 4.30.7.

 

c. The door requires 15 pounds of force to operate.  Provide a door that requires no more than 5 pounds of force to open.  Standards §§ 4.1.3(7)(b), 4.1.6(1)(b), 4.13.11(2)(b).

 

d. The maneuvering clearance on the latch side of the door from the "pull" side is only 9 inches.  On the pull side of the door, provide maneuvering clearance at least 60 inches deep and provide a minimum of 18 inches (24 inches is preferred) of maneuvering clearance on the latch side of the door.  Standards §§ 4.1.3(7)(b), 4.1.6(1)(b), 4.13.6, Fig. 25(a).

 

e. The path of travel into the room is restricted by an entrance arch that is only 28 inches wide.  Provide a pat of travel with a clear opening of 32 inches with the door open 90 degrees, measured between the face of the door and the opposite stop.  Standards §§ 4.1.3(7)(b), 4.1.6(1)(b), 4.13.5, Fig. 24.

 

f. The sanitary napkin dispenser controls are mounted at 58 inches above the finished floor and require the user to twist her hand at the wrist to operate.  Provide a sanitary napkin dispenser with the controls a maximum height above the finished floor of 48 inches for a forward approach or 54 inches for a side approach and that is accompanied by clear floor space of 30 by 48 inches that allows a forward or parallel approach by a person using a wheelchair and that can be operated with 5 pounds of force or less and that can be used with one hand and without tight grasping, pinching, or twisting of the wrist (lever-operated, push-type, and electronically controlled mechanisms are examples of acceptable designs).   Standards §§ 4.1.3(13), 4.1.6(1)(b), 4.27.2, 4.27.3, 4.27.4,  4.2.4, 4.2.5, 4.2.6, Fig. 4.

 

g. The top of the lavatory rim or counter top is 36 inches above the finished floor.  Provide a lavatory with the top of its rim or counter 34 inches or less above the finished floor; the bottom edge of the apron at least 29 inches above the finished floor; and knee and toe clearances that comply with Fig. 31.  Standards §§ 4.1.3(11), 4.1.6(1)(b), 4.22.6, 4.19.2, Fig. 31.

 

h. Although 3 toilet stalls are provided, none is designed or configured to be accessible to persons who use wheelchairs.  One is loosely configured in an "alternate" stall configuration, designed for persons with disabilities who are ambulatory; it measures 42 inches wide by 55 inches deep and does not have an outward swinging, self-closing door.  Also, the coat hook in this stall is inaccessible.  Provide a "standard" accessible toilet stall at least 60 inches wide and at least 59 inches deep (or at least 56 inches deep with a wall-mounted toilet) such that all of the stall's elements, including stall door, stall door hardware, water closet, size and arrangement, toe clearances, grab bars, controls, and dispensers, comply with the Standards.  Standards §§ 4.1.3(11), 4.1.6(1)(b), 4.22.4, 4.22.7, 4.13, 4.16, 4.17, 4.26, 4.27, Fig. 30.

 

8.         The second floor wall-mounted drinking fountain has a spout height of 44 inches above the finished floor; the water flow height reaches only 2 inches; and there is only 24 inches of knee space above the finished floor and 10 inches of knee depth.  Provide at least one drinking fountain with a spout height no higher than 36 inches, measured from the finished floor or ground surface to the spout outlet; and a spout located at the front of the unit that directs the water flow in a trajectory that is nearly parallel to the front of the unit and is positioned so the flow of water is within 3 inches of the front edge of the fountain and at least 4 inches high.  Ensure that fountain controls are operable with one hand, require 5 pounds of force or less to operate without tight grasping, pinching, or twisting of the wrist; and are front mounted or side mounted near the front edge.  For each accessible drinking fountain, provide a drinking fountain that is accessible to people who have difficulty bending or stooping.  This can be accommodated by the use of a "hi-lo" fountain; by providing one fountain accessible to those who use wheelchairs and one fountain at a standard height convenient for those who have difficulty bending; by providing a fountain accessible to people who use wheelchairs and a cup dispenser; or by such other means as would achieve the required accessibility for each group of people.  Standards §§ 4.1.3(10), 4.1.6(1)(b), 4.15, 4.27.4, Fig. 27.

 

9.         Elevators

 

a. The hall lanterns signal once for up and once for down.  Provide hall lanterns at each hoistway entrance that emit a visible and audible signal indicating which car is answering a call.  Ensure that audible signals sound once for the up direction and twice for the down direction or have verbal annunciators that say "up" or "down;" and that visible signals are mounted so that their centerline is at least 72 inches above the lobby floor, they are at least 2½ inches in the smallest dimension, and they are visible from the vicinity of the hall call button.  Lanterns located in cars, visible from the vicinity of hall call buttons, and conforming to the above requirements, are acceptable.  Standards §§ 4.1.3(5), 4.1.6(1)(b), 4.10.4, Fig. 20.

 

b. The door protective and reopening device is set so that after reopening, the doors stay open only 3 seconds.  Provide doors that open and close automatically with a reopening device that will stop and reopen the car door and hoistway door automatically if the door becomes obstructed by an object or person.  Ensure that the device is capable of completing these operations without requiring contact for obstructions passing through the opening at heights of 5 inches and 29 inches above the finished floor; that door reopening devices remain effective for at least 20 seconds, after which the doors may close; that the minimum time from notification that a car is answering a call until the doors of that car start to close is 5 seconds; and that the minimum time for elevator doors to remain fully open in response to a car call is 3 seconds.  Standards §§ 4.1.3(5), 4.1.6(1)(b), 4.10.6, 4.10.7, 4.10.8, Figs. 20, 21.

 

c. The doors start to close only 3 seconds after the door and signal timing device notifies users of the car's arrival.  Provide doors that open and close automatically with a reopening device that will stop and reopen the car door and hoistway door automatically if the door becomes obstructed by an object or person.  Ensure that the device is capable of completing these operations without requiring contact for obstructions passing through the opening at heights of 5 inches and 29 inches above the finished floor; that door reopening devices remain effective for at least 20 seconds, after which the doors may close; that the minimum time from notification that a car is answering a call until the doors of that car start to close is 5 seconds; and that the minimum time for elevator doors to remain fully open in response to a car call is 3 seconds.  Standards §§ 4.1.3(5), 4.1.6(1)(b), 4.10.6, 4.10.7, 4.10.8, Figs. 20, 21.

 

10.       The emergency alarm activation mechanism on the second floor of Fire 1 near the stairs is mounted 62 inches above the finished floor.  Provide an emergency alarm activation mechanism with the controls a maximum height above the finished floor of 48 inches for a forward approach or 54 inches for a side approach and that is accompanied by clear floor space of 30 by 48 inches that allows a forward or parallel approach by a person using a wheelchair.  Standards §§ 4.1.3(13), 4.1.6(1)(b), 4.27.2, 4.27.3, 4.2.4, 4.2.5, 4.2.6, Fig. 4.

 

11.       Jail

 

a. There is no accessible route for arrestees who are brought to the jail in law enforcement vehicles, as there is a 4 inch step into the building from the secured garage.  Provide at least one accessible route within the boundary of the site connecting these elements that, to the maximum extent feasible, coincides with the route for the general public.  The accessible route must have a minimum clear width of 36 inches, or a minimum clear width of 42 inches if there is a turn around an obstruction less than 48 inches wide; have passing spaces at least 60 inches by 60 inches at least every 200 feet; have a minimum clear headroom of 80 inches; have a surface that is firm, stable, and slip resistant; have, in the absence of a curb ramp, ramp, elevator, or platform lift, no level changes in excess of ½ inch vertically; and have a running slope of less than 1:20 (5%) (or have been constructed as a fully accessible ramp) and a cross slope of less than 1:50 (2%).  Standards §§ 4.1.3(1), 4.1.6(1)(b), 4.3, 4.5, Fig. 7.

 

b. The holding cell for female inmates has a lavatory/toilet combination unit where the toilet seat height is 16 inches above the finished floor, 38 inches to the centerline of the toilet, no grab bars, and no clear floor space at the lavatory.   Provide a toilet with a centerline that is 18 inches from the near side wall; a seat that is between17 and 19 inches above the finished floor; clear floor space at the toilet that complies with Fig. 28; and a flush control mounted on the "open" side of the toilet's clear floor space.  Standards §§ 4.1.3(11), 4.1.6(1)(b), 4.22.4, 4.16.2, 4.16.3, 4.16.5, Figs. 28, 29.  Provide a rear grab bar that is at least 36 inches in overall length, with the closer end no more than 6 inches from the side wall, and a side grab bar that is at least 42 inches in overall length, with the far end mounted at least 54 inches from the rear wall and the closer end 12 inches or less from the rear wall.  Ensure that the grab bars are mounted 33 to 36 inches above the finished floor; with a diameter between 1¼ and 1½ inches; with 1½ inches between the grab bars and the wall; and at least 1½ inches between the grab bars and any other object, such as a toilet paper dispenser or a toilet seat cover dispenser.  Standards §§ 4.1.3(11), 4.1.6(1)(b), 4.22.4, 4.16.4, 4.26.2, Fig. 29.  Provide a lavatory with clear floor space at least 30 inches wide and 48 inches deep centered on the lavatory.  Standards §§ 4.1.3(11), 4.1.6(1)(b), 4.22.6, 4.19.3, Fig. 32.

 

c. The holding cells for adult men are not accessible, due to narrow doors.  Provide holding cell doors with a clear opening of 32 inches with the door open 90 degrees, measured between the face of the door and the opposite stop.  Standards §§ 4.1.3(7)(b), 4.1.6(1)(b), 4.13.5, Fig. 24.

 

d. Both of the juvenile holding cells have lavatory/toilet combination units where the toilet seat heights are 16 inches above the finished floor, 38 inches to the centerline of the toilets, no grab bars, and no clear floor space at the lavatories.  Provide a toilet with a centerline that is 18 inches from the near side wall; a seat that is between17 and 19 inches above the finished floor; clear floor space at the toilet that complies with Fig. 28; and a flush control mounted on the "open" side of the toilet's clear floor space.  Standards §§ 4.1.3(11), 4.1.6(1)(b), 4.22.4, 4.16.2, 4.16.3, 4.16.5, Figs. 28, 29.  Provide a rear grab bar that is at least 36 inches in overall length, with the closer end no more than 6 inches from the side wall, and a side grab bar that is at least 42 inches in overall length, with the far end mounted at least 54 inches from the rear wall and the closer end 12 inches or less from the rear wall.  Ensure that the grab bars are mounted 33 to 36 inches above the finished floor; with a diameter between 1¼ and 1½ inches; with 1½ inches between the grab bars and the wall; and at least 1½ inches between the grab bars and any other object, such as a toilet paper dispenser or a toilet seat cover dispenser.  Standards §§ 4.1.3(11), 4.1.6(1)(b), 4.22.4, 4.16.4, 4.26.2, Fig. 29.  Provide a lavatory with clear floor space at least 30 inches wide and 48 inches deep centered on the lavatory.  Standards §§ 4.1.3(11), 4.1.6(1)(b), 4.22.6, 4.19.3, Fig. 32.

 

H.        Within three months of the effective date of this Agreement, the City will complete the following modifications to the Fire Station #2 (525 South Dixie Highway)

 

1.         Although 1 of the fewer-than-25 parking spaces is designated for persons with disabilities, there is no access aisle and no "van-accessible" signage.  On the shortest accessible route to the accessible entrance, provide one van accessible space designated as reserved for people with disabilities.  Ensure that van accessible spaces are a minimum of 96 inches wide and served by access aisles at least 96 inches wide.  At all spaces designated as reserved for persons with disabilities, provide vertical signs with the International Symbol of Accessibility located such that they cannot be obstructed by parked vehicles.  At van accessible spaces, provide an additional "Van-Accessible" sign located below the International Symbol of Accessibility.  Ensure that all spaces and access aisles for persons with disabilities are flat and level, with slopes and cross-slopes not exceeding 1:50 in all directions, and that their surfaces are firm, stable, and slip-resistant.  Standards §§ 4.1.2(5), 4.1.6(1)(b), 4.6, 4.30.7(1).

 

2.         The building entrance is not accessible, as the clear opening width for each leaf of the double hinged doors at the entrance is only 26 inches.  Provide a designated accessible entrance that has at least one active leaf with a minimum 32 inch clear opening width with the door open 90 degrees, measured between the face of the door and the opposite stop; that has either an automatic door operator or clear and level maneuvering clearance that complies fully with Fig. 25; and that has a threshold not exceeding ½ inch in height and beveled with a slope no greater than 1:2.  Ensure that all hardware and operating devices have shapes that are easy to grasp with one hand and do not require tight grasping, pinching, or twisting of the wrist to operate, and that they are mounted no higher than 48 inches above the finished floor.  Standards §§ 4.1.3(7)(a), 4.1.6(1)(b), 4.13, Figs. 24, 25.

 

3.         To access the building after hours, there is a doorbell and intercom, but no provisions are made for persons who cannot speak or hear.  Provide a way for persons who are deaf or who cannot speak to access the building after hours.

 

I.          Within 12 months of the effective date of this Agreement, the City will complete the following modifications to the Coral Gables War Memorial Youth Center (405 University Dr.)

 

1.         Parking

 

a. The parking lot that serves the building is divided into two discrete lots, each served by its own entrance.  On the shortest accessible route to the accessible entrance, provide one van accessible space designated as reserved for people with disabilities in each of these discrete lots.  Ensure that van accessible spaces are a minimum of 96 inches wide and served by access aisles at least 96 inches wide that does not encroach into traffic.  At van accessible spaces, provide an additional "Van-Accessible" sign located below the International Symbol of Accessibility.  Ensure that all spaces and access aisles for persons with disabilities are flat and level, with slopes and cross-slopes not exceeding 1:50 in all directions, and that their surfaces are firm, stable, and slip-resistant.  Standards §§ 4.1.2(5), 4.6, 4.30.7(1).           

 

2.         The handrails on the ramp to the University Street entrance to the Youth Center extend only 7 inches at the bottom of the ramp.  Provide handrails that are between 1¼ inches and 1½ inches in diameter such that the inside handrail is continuous and both handrails have a continuous gripping surface along both sides of the ramp extending at least 12 inches beyond the top and bottom of the ramp parallel with the ground surface; the handrails do not rotate within their fittings; and both handrails are mounted between 34 inches and 38 inches above the ramp surface, with ends rounded or returned smoothly to the floor, wall, or post.  Standards §§ 4.1.2(1), 4.1.2(2), 4.1.6(1)(b), 4.3.8, 4.8.

 

3.         All interior doors throughout the facility require 15 or more pounds of force to operate.  Provide doors that requires no more than 5 pounds of force to open.  Standards §§ 4.1.3(7)(b), 4.1.6(1)(b), 4.13.11(2)(b).

 

4.         Interior Elevators

 

a. The door protective and reopening device is set so that after reopening, the doors stay open only 3 seconds.  Provide doors that open and close automatically with a reopening device that will stop and reopen the car door and hoistway door automatically if the door becomes obstructed by an object or person.  Ensure that the device is capable of completing these operations without requiring contact for obstructions passing through the opening at heights of 5 inches and 29 inches above the finished floor; that door reopening devices remain effective for at least 20 seconds, after which the doors may close; that the minimum time from notification that a car is answering a call until the doors of that car start to close is 5 seconds; and that the minimum time for elevator doors to remain fully open in response to a car call is 3 seconds.  Standards §§ 4.1.3(5), 4.1.6(1)(b), 4.10.6, 4.10.7, 4.10.8, Figs. 20, 21.

 

b. The doors start to close only 3 seconds after the door and signal timing device notifies users of the car's arrival.  Provide doors that open and close automatically with a reopening device that will stop and reopen the car door and hoistway door automatically if the door becomes obstructed by an object or person.  Ensure that the device is capable of completing these operations without requiring contact for obstructions passing through the opening at heights of 5 inches and 29 inches above the finished floor; that door reopening devices remain effective for at least 20 seconds, after which the doors may close; that the minimum time from notification that a car is answering a call until the doors of that car start to close is 5 seconds; and that the minimum time for elevator doors to remain fully open in response to a car call is 3 seconds.  Standards §§ 4.1.3(5), 4.1.6(1)(b), 4.10.6, 4.10.7, 4.10.8, Figs. 20, 21.

 

5.         Exterior Elevators

 

a. The door protective and reopening device is set so that after reopening, the doors stay open only 2 seconds.  Provide doors that open and close automatically with a reopening device that will stop and reopen the car door and hoistway door automatically if the door becomes obstructed by an object or person.  Ensure that the device is capable of completing these operations without requiring contact for obstructions passing through the opening at heights of 5 inches and 29 inches above the finished floor; that door reopening devices remain effective for at least 20 seconds, after which the doors may close; that the minimum time from notification that a car is answering a call until the doors of that car start to close is 5 seconds; and that the minimum time for elevator doors to remain fully open in response to a car call is 3 seconds.  Standards §§ 4.1.3(5), 4.1.6(1)(b), 4.10.6, 4.10.7, 4.10.8, Figs. 20, 21.

 

b. The doors start to close only 2 seconds after the door and signal timing device notifies users of the car's arrival.  Provide doors that open and close automatically with a reopening device that will stop and reopen the car door and hoistway door automatically if the door becomes obstructed by an object or person.  Ensure that the device is capable of completing these operations without requiring contact for obstructions passing through the opening at heights of 5 inches and 29 inches above the finished floor; that door reopening devices remain effective for at least 20 seconds, after which the doors may close; that the minimum time from notification that a car is answering a call until the doors of that car start to close is 5 seconds; and that the minimum time for elevator doors to remain fully open in response to a car call is 3 seconds.  Standards §§ 4.1.3(5), 4.1.6(1)(b), 4.10.6, 4.10.7, 4.10.8, Figs. 20, 21.

 

c. The doors remain fully open only 2 seconds.  Provide doors that open and close automatically with a reopening device that will stop and reopen the car door and hoistway door automatically if the door becomes obstructed by an object or person.  Ensure that the device is capable of completing these operations without requiring contact for obstructions passing through the opening at heights of 5 inches and 29 inches above the finished floor; that door reopening devices remain effective for at least 20 seconds, after which the doors may close; that the minimum time from notification that a car is answering a call until the doors of that car start to close is 5 seconds; and that the minimum time for elevator doors to remain fully open in response to a car call is 3 seconds.  Standards §§ 4.1.3(5), 4.1.6(1)(b), 4.10.6, 4.10.7, 4.10.8, Figs. 20, 21.

 

6.         In Room 105 (Toddler Room), the flush control valve is on the closed side of the single-user toilet room.  Provide a flush control mounted on the "open" side of the toilet's clear floor space; 44 inches or less above the finished floor; and requiring a maximum of 5 pounds of force to operate; or provide an automatic flush device.  Standards §§ 4.1.3(11), 4.1.6(1)(b), 4.22.4, 4.16.5, 4.27.4.

 

7.         In Room 107 (Children's Activity Room), the signage is mounted on the non-latch side of the door and is centered at 73 inches above the finished floor.  Provide permanent room signage with upper case, sans serif or simple serif type letters and numerals, meeting the requirements of the Standards for character height, raised characters, finish and contrast, accompanied by Grade 2 Braille; mounted on the wall adjacent to the latch side of the door or on the nearest adjacent wall at a height of 60 inches above the finished floor to the centerline of the sign; and located so that a person may approach within 3 inches of the signage without encountering protruding objects or standing within the swing of a door.  Standards §§ 4.1.2(7), 4.1.6(1)(b), 4.30.1, 4.30.4, 4.30.5, 4.30.6.

 

8.         Adult Activity Room

 

a. The sink is mounted in a floor cabinet, with no knee or toe clearance.  Provide a sink with clear floor space at least 30 inches wide and 48 inches deep centered on the lavatory.  Standards §§ 4.1.3(11), 4.1.6(1)(b), 4.22.6, 4.19.3, Fig. 32.

 

b. Single User Toilet Room

 

i. The toilet flush control in the single-user toilet room is on the closed side of the room.  Provide a flush control mounted on the "open" side of the toilet's clear floor space; 44 inches or less above the finished floor; and requiring a maximum of 5 pounds of force to operate; or provide an automatic flush device.  Standards §§ 4.1.3(11), 4.1.6(1)(b), 4.22.4, 4.16.5, 4.27.4.

 

ii. The hand dryer is a protruding object that is not cane-detectable and it interferes with the clear floor space required at the lavatory.  Provide an accessible route at this location such that the bottom leading edges of all elements measuring 27 inches and 80 inches above the finished floor protrude no more than 4 inches into walks, halls, corridors, passageways, or aisles.  Free-standing objects mounted on posts or pylons may overhang 12 inches maximum from 27 inches to 80 inches above the ground or finished floor.  Standards §§ 4.1.2(3), 4.1.6(1)(b), 4.4.

 

9.         Teaching Kitchen Classroom

 

a. The sinks are installed in base cabinets with no knee clearance.  Provide a sink with clear floor space at least 30 inches wide and 48 inches deep centered on the lavatory.  Standards §§ 4.1.3(11), 4.1.6(1)(b), 4.22.6, 4.19.3, Fig. 32.

 

b. The microwave and range/oven controls are outside the reach ranges of persons who use wheelchairs.  Provide a microwave and range/oven with the controls a maximum height above the finished floor of 48 inches for a forward approach or 54 inches for a side approach and that is accompanied by clear floor space of 30 by 48 inches that allows a forward or parallel approach by a person using a wheelchair.  Standards §§ 4.1.3(13), 4.1.6(1)(b), 4.27.2, 4.27.3, 4.2.4, 4.2.5, 4.2.6, Fig. 4.

 

10.       Auditorium

 

a. The stage is not accessible to persons with disabilities from the spectator area; the only accessible route onto the stage is via a ramp backstage.  Provide an accessible route connecting the wheelchair seating locations to all spaces used by performers.  Standards §§ 4.1.3(19)(a), 4.1.6(1)(b), 4.3, 4.33.5.

 

b. The ramp between the courtyard and backstage area lacks adequate handrail extensions at the bottom of the ramp.  Provide handrails that are between 1¼ inches and 1½ inches in diameter with a continuous gripping surface along both sides of the ramp, extending at least 12 inches beyond the top and bottom of the ramp parallel with the ground surface.  Ensure that handrails are mounted between 34 inches and 38 inches above the ramp surface, with ends rounded or returned smoothly to the floor, wall, or post, and that they do not rotate within their fittings.  Standards §§ 4.1.2(1), 4.1.2(2), 4.1.6(1)(b), 4.3.8, 4.8.

 

c. No assistive listening system is available (installed or portable).  Provide a permanently installed assistive listening system (ALS) or a portable ALS with an adequate number of electrical outlets or other supplementary wiring necessary to support a portable assistive listening system.  Also provide an appropriate number of receivers for use by the general public and signage indicating their availability.  Standards §§ 4.1.3(19)(b), 4.1.6(1)(b), 4.30, 4.33.

 

d. Room 126 (backstage single user toilet room)

 

i. The lavatory faucets require tight grasping and twisting.  Provide a lavatory with a faucet that can be operated with 5 pounds of force or less and can be used with one hand and without tight grasping, pinching, or twisting of the wrist (lever-operated, push-type, and electronically controlled mechanisms are examples of acceptable designs).  Standards §§ 4.1.3(11), 4.1.6(1)(b), 4.22.6, 4.19.5, 4.27.4.

 

ii. The toilet flush control valve is on the closed side of the toilet room.   Provide a flush control mounted on the "open" side of the toilet's clear floor space; 44 inches or less above the finished floor; and requiring a maximum of 5 pounds of force to operate; or provide an automatic flush device.  Standards §§ 4.1.3(11), 4.1.6(1)(b), 4.22.4, 4.16.5, 4.27.4.

 

iii. The toilet paper dispenser is mounted too low.  Provide a toilet paper dispenser that is mounted within reach, with its top at least 1½ inches under the side grab bar, and centered at least 19 inches above the finished floor.  Standards §§ 4.1.3(11), 4.1.6(1)(b), 4.22.4, 4.16.6, Fig. 29(b).

 

iv. The hand dryer is a protruding object that is not cane-detectable.  Provide an accessible route at this location such that the bottom leading edges of all elements measuring 27 inches and 80 inches above the finished floor protrude no more than 4 inches into walks, halls, corridors, passageways, or aisles.  Free-standing objects mounted on posts or pylons may overhang 12 inches maximum from 27 inches to 80 inches above the ground or finished floor.  Standards §§ 4.1.2(3), 4.1.6(1)(b), 4.4.

 

e. The higher of the 2 drinking fountains outside at the stage is a protruding object that is not cane-detectable.  Provide an accessible route at this location such that the bottom leading edges of all elements measuring 27 inches and 80 inches above the finished floor protrude no more than 4 inches into walks, halls, corridors, passageways, or aisles.  Free-standing objects mounted on posts or pylons may overhang 12 inches maximum from 27 inches to 80 inches above the ground or finished floor.  Standards §§ 4.1.2(3), 4.1.6(1)(b), 4.4.

 

11.       The hand dryer in the employee-only toilet room (Room 101) is a protruding object that is not cane-detectable.  Provide an accessible route at this location such that the bottom leading edges of all elements measuring 27 inches and 80 inches above the finished floor protrude no more than 4 inches into walks, halls, corridors, passageways, or aisles.  Free-standing objects mounted on posts or pylons may overhang 12 inches maximum from 27 inches to 80 inches above the ground or finished floor.  Standards §§ 4.1.2(3), 4.1.6(1)(b), 4.4.

 

12.       Room 102 (girls' locker room).

 

a. The hand dryer inside the toilet stall for persons with disabilities is a protruding object that is not cane-detectable.  Provide an accessible route at this location such that the bottom leading edges of all elements measuring 27 inches and 80 inches above the finished floor protrude no more than 4 inches into walks, halls, corridors, passageways, or aisles.  Free-standing objects mounted on posts or pylons may overhang 12 inches maximum from 27 inches to 80 inches above the ground or finished floor.  Standards §§ 4.1.2(3), 4.1.6(1)(b), 4.4.

 

b. The bench in the transfer shower stall does not appear to extend the full depth of the stall, or the stall is more than 36 inches deep.  Provide an L-shaped shower seat mounted on the wall opposite the controls and extending the full depth of the stall that comply fully with the Standards and with Figs. 35, 36, and 37, as applicable.  Standards §§ 4.1.3(11), 4.1.6(1)(b), 4.21, Figs. 35, 36, 37.

 

13.       Room 103 (women's toilet room with stalls)

 

a. The interior door to the room does not appear to have adequate clear maneuvering clearance on the latch/pull side of the door.  On the pull side of the door, provide maneuvering clearance at least 60 inches deep and provide a minimum of 18 inches (24 inches is preferred) of maneuvering clearance on the latch side of the door.  Standards §§ 4.1.3(7)(b), 4.1.6(1)(b), 4.13.6, Fig. 25(a).

 

14.       Room 104 (men's toilet room with stalls)

 

a. The interior door to the toilet room swings into the clear floor space required at the "Koala Kare" diaper changing station.  Ensure that no door swings into the required clear floor space at any accessible fixture.  Standards §§ 4.1.3(11), 4.1.6(1)(b), 4.22.2.

 

15.       Room 106 (boys' locker room)

 

a. Transfer shower

 

i. The transfer bench is mounted with the deeper side near the entrance, rather than along the back wall; the transfer bench does not appear to extend the full depth of the shower stall; and there is no 12 inch overhang at the transfer bench.  Provide an L-shaped shower seat mounted on the wall opposite the controls and extending the full depth of the stall that comply fully with the Standards and with Figs. 35, 36, and 37, as applicable.  Standards §§ 4.1.3(11), 4.1.6(1)(b), 4.21, Figs. 35, 36, 37.

 

16.       In Room 118 (women's toilet room with stalls), the visual alarm appliance is not situated so that it would provide adequate warning to persons using the toilet stalls.  Provide visual alarm devices in toilet rooms and any other general usage areas (e.g., meeting rooms), hallways, lobbies, and any other area for common use.  Such devices shall be integrated into the facility alarm system and shall meet the requirements of the Standards for lamp type, color, pulse duration, intensity, and flash rate.  Visual alarm appliances shall be placed 80 inches above the highest floor level within the space or 6 inches below the ceiling, whichever is lower.  Visual alarm appliances shall be located such that no place in any room or space, including common corridors or hallways, required to have a visual alarm appliance shall be more than 50 feet from the signal.  In large rooms and spaces exceeding 100 feet across, without obstructions 6 feet above the finished floor, devices may be placed around the perimeter, spaced a maximum of 100 feet apart, in lieu of suspending appliances from the ceiling.  Standards §§ 4.1.3(14), 4.1.6(1)(b), 4.28.3.

 

17.       Room 205 (women's toilet room with stalls)

 

a. There is inadequate clear maneuvering space at the pull/latch side of the entry door.  On the pull side of the door, provide maneuvering clearance at least 60 inches deep and provide a minimum of 18 inches (24 inches is preferred) of maneuvering clearance on the latch side of the door.  Standards §§ 4.1.3(7)(b), 4.1.6(1)(b), 4.13.6, Fig. 25(a).

 

b. Toilet Stall for Persons with Disabilities

 

i. The coat hook is inaccessible.  Provide a coat hook at a maximum height above the finished floor of 48 inches for a forward approach or 54 inches for a side approach and that is accompanied by clear floor space of 30 by 48 inches that allows a forward or parallel approach by a person using a wheelchair.  Standards §§ 4.1.3(12)(a), 4.1.6(1)(b), 4.25.2, 4.25.3, 4.2.4, 4.2.5, 4.2.6.

 

ii. The toilet flush control is on the closed side of the stall.  Provide a flush control mounted on the "open" side of the toilet's clear floor space; 44 inches or less above the finished floor; and requiring a maximum of 5 pounds of force to operate; or provide an automatic flush device.  Standards §§ 4.1.3(11), 4.1.6(1)(b), 4.22.4, 4.16.5, 4.17.2, 4.27.4.

 

iii. The hand dryer is a protruding object that is not cane-detectable.  Provide an accessible route at this location such that the bottom leading edges of all elements measuring 27 inches and 80 inches above the finished floor protrude no more than 4 inches into walks, halls, corridors, passageways, or aisles.  Free-standing objects mounted on posts or pylons may overhang 12 inches maximum from 27 inches to 80 inches above the ground or finished floor.  Standards §§ 4.1.2(3), 4.1.6(1)(b), 4.4.

 

18.       Room 208 (men's toilet room with stalls)

 

a. Toilet Stall for Persons with Disabilities

 

i. The coat hook is inaccessible.  Provide a coat hook at a maximum height above the finished floor of 48 inches for a forward approach or 54 inches for a side approach and that is accompanied by clear floor space of 30 by 48 inches that allows a forward or parallel approach by a person using a wheelchair.  Standards §§ 4.1.3(12)(a), 4.1.6(1)(b), 4.25.2, 4.25.3, 4.2.4, 4.2.5, 4.2.6.

 

ii. The hand dryer in the stall is a protruding object that is not cane-detectable.  Provide an accessible route at this location such that the bottom leading edges of all elements measuring 27 inches and 80 inches above the finished floor protrude no more than 4 inches into walks, halls, corridors, passageways, or aisles.  Free-standing objects mounted on posts or pylons may overhang 12 inches maximum from 27 inches to 80 inches above the ground or finished floor.  Standards §§ 4.1.2(3), 4.1.6(1)(b), 4.4.

 

19.       In Room 209 (employee kitchen), the sink is mounted in a floor cabinet, with no knee or toe clearance.  Provide a sink with the top of its rim or counter 34 inches or less above the finished floor; the bottom edge of the apron at least 29 inches above the finished floor; and knee and toe clearances that comply with Fig. 31.  Standards §§ 4.1.3(11), 4.1.6(1)(b), 4.22.6, 4.19.2, Fig. 31.

 

20.       Room 218 (men's locker room at the fitness center)

 

a. The rim of the urinal is 25 inches above the finished floor and the urinal flush control valve is 47 inches above the finished floor.  Provide a urinal with an elongated rim mounted 17 inches or less above the finished floor, a clear floor space of at least 30 inches wide and 48 inches deep centered on the urinal, and a flush control height of 44 inches or less above the finished floor.  Standards §§ 4.1.3(11), 4.1.6(1)(b), 4.22.5, 4.18.2, 4.18.3, 4.18.4.

 

b. Transfer Shower

 

i. The required 12 inch maneuvering clearance to the rear side of the transfer bench is missing.  Provide a shower in this room that is exactly 36 inches wide and 36 inches deep with a 48 inch long and 36 inch wide clear floor space alongside the shower opening, and an L-shaped shower seat mounted on the wall opposite the controls and extending the full depth of the stall.  Ensure that the shower has grab bars, controls, a shower spray unit, and a seat, curb, and enclosure, if provided, that comply fully with the Standards and with Figs. 35, 36, and 37, as applicable.  Standards §§ 4.1.3(11), 4.1.6(1)(b), 4.21, Figs. 35, 36, 37.

 

ii. The towel hooks at the transfer shower are inaccessible.  Provide a shower hook at a maximum height above the finished floor of 48 inches for a forward approach or 54 inches for a side approach and that is accompanied by clear floor space of 30 by 48 inches that allows a forward or parallel approach by a person using a wheelchair.  Standards §§ 4.1.3(12)(a), 4.1.6(1)(b), 4.25.2, 4.25.3, 4.2.4, 4.2.5, 4.2.6.

 

c. Toilet Stall for Persons with Disabilities.  The side grab bar at the toilet is only 36 inches long.  Provide a side grab bar that is at least 40 inches in overall length, with the far end mounted at least 52 inches from the rear wall and the closer end 12 inches or less from the rear wall.  Standards §§ 4.1.3(11), 4.1.6(1)(b), 4.22.4, 4.17.6, Figs. 30(a), (d).

 

d. The bench near the lockers is not accessible to persons with disabilities and it blocks the route to the transfer shower.  Provide a 24 inch by 48 inch bench fixed to the wall along the bench's longer dimension.  Ensure that the bench has sufficient structural strength and is mounted with its surface between 17 inches and 19 inches above the finished floor.  Provide clear floor space alongside the bench to allow a person using a wheelchair to make a parallel transfer onto the bench.  Standards §§ 4.1.3(21), 4.1.6(1)(b), 4.35.4, 4.26.3.

 

21.       Room 219 (women's locker room at the fitness center)

 

a. Toilet Stall for Persons with Disabilities

 

i. The flush valve in the stall is on the closed side of the stall.  Provide a flush control mounted on the "open" side of the toilet's clear floor space; 44 inches or less above the finished floor; and requiring a maximum of 5 pounds of force to operate; or provide an automatic flush device.  Standards §§ 4.1.3(11), 4.1.6(1)(b), 4.22.4, 4.16.5, 4.17.2, 4.27.4.

 

ii. The side grab bar at the toilet is only 36 inches long.  Provide a side grab bar that is at least 40 inches in overall length, with the far end mounted at least 52 inches from the rear wall and the closer end 12 inches or less from the rear wall.  Standards §§ 4.1.3(11), 4.1.6(1)(b), 4.22.4, 4.17.6, Figs. 30(a), (d).

 

b. The sanitary napkin dispenser is 58 inches above the finished floor and requires pinching and twisting for operation.  Provide a sanitary napkin dispenser with the controls a maximum height above the finished floor of 48 inches for a forward approach or 54 inches for a side approach and that is accompanied by clear floor space of 30 by 48 inches that allows a forward or parallel approach by a person using a wheelchair.  Provide a sanitary napkin dispenser with mechanical controls, if any, that can be operated with 5 lbf or less and that can be used with one hand and without tight grasping, pinching, or twisting of the wrist (lever-operated, push-type, and electronically controlled mechanisms are examples of acceptable designs).  Standards §§ 4.1.3(13), 4.1.6(1)(b), 4.27.2, 4.27.3,  4.27.4., 4.2.4, 4.2.5, 4.2.6, Fig. 4.

 

c. The changing bench is not deep enough for persons with disabilities.  Provide a 24 inch by 48 inch bench fixed to the wall along the bench's longer dimension.  Ensure that the bench has sufficient structural strength and is mounted with its surface between 17 inches and 19 inches above the finished floor.  Provide clear floor space alongside the bench to allow a person using a wheelchair to make a parallel transfer onto the bench.  Standards §§ 4.1.3(21), 4.1.6(1)(b), 4.35.4, 4.26.3.

 

d. There is no 12 inch required overhang at the transfer bench in the shower for persons with disabilities.  Provide an L-shaped shower seat mounted on the wall opposite the controls and extending the full depth of the stall.  Ensure that the shower has grab bars, controls, a shower spray unit, and a seat, curb, and enclosure, if provided, that comply fully with the Standards and with Figs. 35, 36, and 37, as applicable.  Standards §§ 4.1.3(11), 4.1.6(1)(b), 4.21, Figs. 35, 36, 37.

 

22.       The higher of the 2 drinking fountains to the left of the men's locker room entry at the fitness center is a protruding object that is not cane-detectable.  Provide an accessible route at this location such that the bottom leading edges of all elements measuring 27 inches and 80 inches above the finished floor protrude no more than 4 inches into walks, halls, corridors, passageways, or aisles.  Free-standing objects mounted on posts or pylons may overhang 12 inches maximum from 27 inches to 80 inches above the ground or finished floor.  Standards §§ 4.1.2(3), 4.1.6(1)(b), 4.4.

 

23.       Fields

 

a. The basketball court/roller hockey rink has a 9 inch high wall that users have to step over at the entrance.  Provide at least one accessible route within the boundary of the site connecting these elements that, to the maximum extent feasible, coincides with the route for the general public.  The accessible route must have a minimum clear width of 36 inches, or a minimum clear width of 42 inches if there is a turn around an obstruction less than 48 inches wide; have passing spaces at least 60 inches by 60 inches at least every 200 feet; have a minimum clear headroom of 80 inches; have a surface that is firm, stable, and slip resistant; have, in the absence of a curb ramp, ramp, elevator, or platform lift, no level changes in excess of ½ inch vertically; and have a running slope of less than 1:20 (5%) (or have been constructed as a fully accessible ramp) and a cross slope of less than 1:50 (2%).  Standards §§ 4.1.3(1), 4.1.6(1)(b), 4.3, 4.5, Fig. 7.

 

b. The concession counter is 43 inches above the finished floor.  Provide a counter on an accessible route such that a portion of the counter is at least 36 inches wide and no more than 36 inches above the finished floor.  Standards §§ 4.1.1(2), 4.1.6(1)(b), 7.2(1), 4.1.3(1), 4.3.

 

c. The drinking fountain opposite the concession counter is not accessible to persons who have difficulty bending or stooping.  For each accessible drinking fountain, provide a drinking fountain that is accessible to people who have difficulty bending or stooping.  This can be accommodated by the use of a "hi-lo" fountain; by providing one fountain accessible to those who use wheelchairs and one fountain at a standard height convenient for those who have difficulty bending; by providing a fountain accessible to people who use wheelchairs and a cup dispenser, or by such other means as would achieve the required accessibility for each group of people.  Standards §§ 4.1.3(10)(a), 4.1.6(1)(b).

 

d. None of the picnic tables are configured to be accessible to persons who use wheelchairs.  Provide at least one picnic table on an accessible route such that there is knee space at the table at least 27 inches high, 30 inches wide, and 19 inches deep, and such that the height of the top of the table is between 28 inches and 34 inches above the ground.  Standards §§ 4.1.3(18), 4.1.6(1)(b), 4.32.3, 4.32.4.

 

24.       Men's Field Toilet Room with Stalls

 

a. The coat hook in the toilet stall is inaccessible.  Provide a coat hook at a maximum height above the finished floor of 48 inches for a forward approach or 54 inches for a side approach and that is accompanied by clear floor space of 30 by 48 inches that allows a forward or parallel approach by a person using a wheelchair.  Standards §§ 4.1.3(12)(a), 4.1.6(1)(b), 4.25.2, 4.25.3, 4.2.4, 4.2.5, 4.2.6.

 

25.       Women's Field Toilet Room with Stalls

 

a. One of the ramp handrails does not return completely to the wall at the top of the ramp.  Provide handrails that are between 1¼ inches and 1½ inches in diameter with a continuous gripping surface along both sides of the ramp, extending at least 12 inches beyond the top and bottom of the ramp parallel with the ground surface.  Ensure that handrails are mounted between 34 inches and 38 inches above the ramp surface, with ends rounded or returned smoothly to the floor, wall, or post, and that they do not rotate within their fittings.   Standards §§ 4.1.2(1), 4.1.2(2), 4.1.6(1)(b), 4.3.8, 4.8.

 

b. Toilet Stall for Persons with Disabilities.

 

i. The toilet flush valve is on the closed side of the stall.  Provide a flush control mounted on the "open" side of the toilet's clear floor space; 44 inches or less above the finished floor; and requiring a maximum of 5 pounds of force to operate; or provide an automatic flush device.  Standards §§ 4.1.3(11), 4.1.6(1)(b), 4.22.4, 4.16.5, 4.17.2, 4.27.4.

 

ii. The coat hook is inaccessible.  Provide a coat hook at a maximum height above the finished floor of 48 inches for a forward approach or 54 inches for a side approach and that is accompanied by clear floor space of 30 by 48 inches that allows a forward or parallel approach by a person using a wheelchair.  Standards §§ 4.1.3(12)(a), 4.1.6(1)(b), 4.25.2, 4.25.3, 4.2.4, 4.2.5, 4.2.6.

 

iii. The rear grab bar is not long enough.  Provide a rear grab bar that is at least 36 inches in overall length with the closer end no more than 6 inches from the side wall.  Standards §§ 4.1.3(11), 4.1.6(1)(b), 4.22.4, 4.17.6, Fig. 30.

 

26.       The higher drinking fountain at Room 106 is a protruding object that is not cane-detectable.  Provide an accessible route at this location such that the bottom leading edges of all elements measuring 27 inches and 80 inches above the finished floor protrude no more than 4 inches into walks, halls, corridors, passageways, or aisles.  Free-standing objects mounted on posts or pylons may overhang 12 inches maximum from 27 inches to 80 inches above the ground or finished floor.  Standards §§ 4.1.2(3), 4.1.6(1)(b), 4.4.

 

J.          Except for as set forth in paragraph "2"  below, within 12 months of the effective date of this Agreement, the City will complete the following modifications to the Salvadore Park and Tennis Center (1120 Andalusia Avenue)

 

1.         The drinking fountains near the park toilet rooms are in a "hi-lo" configuration, but there is insufficient clear floor space at the lower fountain due to the placement of a cement block stepping stone for children.  Provide a drinking fountain with a clear floor space of at least 30 inches by 48 inches that allows a person in a wheelchair to make a parallel approach to the unit.  Standards §§ 4.1.3(10), 4.1.6(1)(b), 4.15.5(2), 4.2.4, Figs. 27(c), (d).

 

2.         Park Toilet Rooms.  The City represents that it intends to alter significantly the toilet rooms at the Park.  Within 6 months of the effective date of this Agreement, the City will submit for the Department's prior approval complete design and construction documentation, including construction drawings, as built drawings, project manuals, addenda, and change orders for the alteration of these toilet rooms.  The Department will review the documentation for conformity to the ADA Standards for Accessible Design and will note any deficiencies.  Before the facility is re-opened, the City will ensure that the alterations carried out in a way that meets the Department's approval.

 

3.         The drinking fountain near the tennis center women's toilet room is 37 inches above the finished floor to the spout.  There is no accessible alternative for persons who have difficulty bending or stooping.  For each accessible drinking fountain, provide a drinking fountain that is accessible to people who have difficulty bending or stooping.  This can be accommodated by the use of a "hi-lo" fountain; by providing one fountain accessible to those who use wheelchairs and one fountain at a standard height convenient for those who have difficulty bending; by providing a fountain accessible to people who use wheelchairs and a cup dispenser, or by such other means as would achieve the required accessibility for each group of people.  Standards §§ 4.1.3(10)(a), 4.1.6(1)(b).

 

4.         The upper and lower level picnic tables at the tennis center are not accessible to persons who use wheelchairs, as fixed benches prevent access.  Provide at least one picnic table on an accessible route such that there is knee space at the table at least 27 inches high, 30 inches wide, and 19 inches deep, and such that the height of the top of the table is between 28 inches and 34 inches above the ground.  Standards §§ 4.1.3(18), 4.1.6(1)(b), 4.32.3, 4.32.4.

 

5.         Tennis Center Women's Shower and Toilet Room

 

a. Toilet Stall for Persons with Disabilities

 

i. There is inadequate clear floor space at the lavatory inside the stall for persons with disabilities.  Provide clear floor space that complies with Fig. 30 at the toilet.  Standards §§ 4.1.3(11), 4.1.6(1)(b), 4.22.4, 4.17.3, Fig. 30.

 

ii. The toilet paper dispenser is mounted with its closer edge 39 inches from the rear wall.  Provide a toilet paper dispenser that is mounted with its top at least 1½ inches under the side grab bar and 36 inches or less from the rear wall and is centered at least 19 inches above the finished floor.  Standards §§ 4.1.3(11), 4.1.6(1)(b), 4.22.4, 4.17.3, Fig. 30(d).

 

b. The transfer shower stall is 36 ½ inches deep by 37 inches wide, with no 12 inch overhang at the transfer bench and the mounting location of the changing bench may interfere with the use of the transfer shower.  Provide a shower in this room that is exactly 36 inches wide and 36 inches deep with a 48 inch long and 36 inch wide clear floor space alongside the shower opening, and an L-shaped shower seat mounted on the wall opposite the controls and extending the full depth of the stall; OR a shower that is at least 30 inches deep and 60 inches wide with no curb or threshold and with a 36 inch deep and 60 inch wide clear floor space at the shower opening.  Ensure that the shower has grab bars, controls, a shower spray unit, and a seat, curb, and enclosure, if provided, that comply fully with the Standards and with Figs. 35, 36, and 37, as applicable.  Standards §§ 4.1.3(11), 4.1.6(1)(b), 4.21, Figs. 35, 36, 37.

 

6.         Tennis Center Men's Shower and Toilet Room

 

a. The toilet paper dispenser in the stall for persons with disabilities is mounted with its closer edge 39 inches from the rear wall.  Provide a toilet paper dispenser that is mounted with its top at least 1½ inches under the side grab bar and 36 inches or less from the rear wall and is centered at least 19 inches above the finished floor.  Standards §§ 4.1.3(11), 4.1.6(1)(b), 4.22.4, 4.17.3, Fig. 30(d).

 

b. The roll-in shower is not configured to be accessible to persons with disabilities: due to a bump-out in the wall, the width of the stall varies between 55 and 59 inches and the controls, faucets, and shower unit are not on the long, back wall.  Provide a shower in this room that is exactly 36 inches wide and 36 inches deep with a 48 inch long and 36 inch wide clear floor space alongside the shower opening, and an L-shaped shower seat mounted on the wall opposite the controls and extending the full depth of the stall; OR a shower that is at least 30 inches deep and 60 inches wide with no curb or threshold and with a 36 inch deep and 60 inch wide clear floor space at the shower opening.  Ensure that the shower has grab bars, controls, a shower spray unit, and a seat, curb, and enclosure, if provided, that comply fully with the Standards and with Figs. 35, 36, and 37, as applicable.  Standards §§ 4.1.3(11), 4.1.6(1)(b), 4.21, Figs. 35, 36, 37.

 

c. The changing bench is not deep enough for persons with disabilities.  Provide a 24 inch by 48 inch bench fixed to the wall along the bench's longer dimension.  Ensure that the bench has sufficient structural strength and is mounted with its surface between 17 inches and 19 inches above the finished floor.  Provide clear floor space alongside the bench to allow a person using a wheelchair to make a parallel transfer onto the bench.  Standards §§ 4.1.3(21), 4.1.6(1)(b), 4.35.4, 4.26.3.

 

K.        Within three months of the effective date of this Agreement, the City will complete the following modifications to Coral Bay Park (1590 Campamento Avenue)

 

1.         There is no accessible route to any of the picnic tables.  Provide at least one accessible route within the boundary of the site connecting these elements that, to the maximum extent feasible, coincides with the route for the general public.  The accessible route must have a minimum clear width of 36 inches, or a minimum clear width of 42 inches if there is a turn around an obstruction less than 48 inches wide; have passing spaces at least 60 inches by 60 inches at least every 200 feet; have a minimum clear headroom of 80 inches; have a surface that is firm, stable, and slip resistant; have, in the absence of a curb ramp, ramp, elevator, or platform lift, no level changes in excess of ½ inch vertically; and have a running slope of less than 1:20 (5%) (or have been constructed as a fully accessible ramp) and a cross slope of less than 1:50 (2%).  Standards §§ 4.1.3(1), 4.1.6(1)(b), 4.3, 4.5, Fig. 7.

 

2.         The "hi-lo" drinking fountain is a protruding object that is not cane-detectable.  Provide an accessible route at this location such that the bottom leading edges of all elements measuring 27 inches and 80 inches above the finished floor protrude no more than 4 inches into walks, halls, corridors, passageways, or aisles.  Free-standing objects mounted on posts or pylons may overhang 12 inches maximum from 27 inches to 80 inches above the ground or finished floor.  Standards §§ 4.1.2(3), 4.1.6(1)(b), 4.4.

 

L.         Within three months of the effective date of this Agreement, the City will complete the following modifications to Jaycee Park (1230 Hardee Road)

 

1.         There is no accessible picnic table under the shelter.  Provide at least one picnic table on an accessible route such that there is knee space at the table at least 27 inches high, 30 inches wide, and 19 inches deep, and such that the height of the top of the table is between 28 inches and 34 inches above the ground.  Standards §§ 4.1.3(18), 4.1.6(1)(b), 4.32.3, 4.32.4.

 

M.        Within 12 months of the effective date of this Agreement, the City will complete the following modifications to Phillips Park (90 Menores Avenue)

 

1.         The drinking fountain is not accessible to persons who have difficulty bending or stooping and there are no accessible alternatives.  For each accessible drinking fountain, provide a drinking fountain that is accessible to people who have difficulty bending or stooping.  This can be accommodated by the use of a "hi-lo" fountain; by providing one fountain accessible to those who use wheelchairs and one fountain at a standard height convenient for those who have difficulty bending; by providing a fountain accessible to people who use wheelchairs and a cup dispenser, or by such other means as would achieve the required accessibility for each group of people.  Standards §§ 4.1.3(10)(a), 4.1.6(1)(b).

 

2.         Men's Toilet Room with Stalls (new)

 

a. The toilet room lacks signage.  Provide a toilet room sign with raised and Braille characters.  The sign shall be mounted on the wall adjacent to the latch side of the door with the centerline of the sign at 60 inches above the finished floor and situated such that a person can approach within 3 inches of the sign without encountering an obstruction or standing within a door swing.  Standards §§ 4.1.2(7)(d), 4.1.6(1)(b), 4.30.1, 4.30.4, 4.30.5, 4.30.6.

 

b. The urinal has clear floor space of only 28 ½ inches wide.  Provide a urinal with an elongated rim mounted 17 inches or less above the finished floor, a clear floor space of at least 30 inches wide and 48 inches deep centered on the urinal, and a flush control height of 44 inches or less above the finished floor.  Standards §§ 4.1.3(11), 4.1.6(1)(b), 4.22.5, 4.18.2, 4.18.3, 4.18.4.

 

c. Stall for Persons with Disabilities

 

i. The toilet seat height is 20 inches above the finished floor.  Provide a toilet with a seat that measures 17 to 19 inches above the finished floor.  Standards §§ 4.1.3(11), 4.1.6(1)(b), 4.22.4, 4.16.3, 4.17.2, Fig. 30(d).

 

ii. The toilet centerline is 17 inches from the side wall.  Provide a toilet with a centerline that measures 18 inches from the near side wall.  Standards §§ 4.1.3(11), 4.1.6(1)(b), 4.22.4, 4.17.3, Fig. 30.

 

iii. The toilet flush control is on the closed side of the stall.  Provide a flush control mounted on the "open" side of the toilet's clear floor space; 44 inches or less above the finished floor; and requiring a maximum of 5 pounds of force to operate; or provide an automatic flush device.  Standards §§ 4.1.3(11), 4.1.6(1)(b), 4.22.4, 4.16.5, 4.17.2, 4.27.4.

 

iv. The coat hook is inaccessible.  Provide a coat hook at a maximum height above the finished floor of 48 inches for a forward approach or 54 inches for a side approach and that is accompanied by clear floor space of 30 by 48 inches that allows a forward or parallel approach by a person using a wheelchair.  Standards §§ 4.1.3(12)(a), 4.1.6(1)(b), 4.25.2, 4.25.3, 4.2.4, 4.2.5, 4.2.6.

 

v. The distance of the closer end of the side grab bar to the rear wall is 13 inches.  Provide a side grab bar that is at least 40 inches in overall length, with the far end mounted at least 52 inches from the rear wall and the closer end 12 inches or less from the rear wall.  Standards §§ 4.1.3(11), 4.1.6(1)(b), 4.22.4, 4.17.6, Figs. 30(a), (d).

 

3.         Women's Toilet Room with Stalls (new)

 

a. The toilet seat height is 20 inches above the finished floor.  Provide a toilet with a seat that measures 17 to 19 inches above the finished floor.  Standards §§ 4.1.3(11), 4.1.6(1)(b), 4.22.4, 4.16.3, 4.17.2, Fig. 30(d).

 

b. Toilet Stall for Persons with Disabilities

 

i. The toilet seat is 20 inches above the finished floor.  Provide a toilet with a seat that measures 17 to 19 inches above the finished floor.  Standards §§ 4.1.3(11), 4.1.6(1)(b), 4.22.4, 4.16.3, 4.17.2, Fig. 30(d).

 

ii. The toilet centerline is 20 ½ inches from the side wall or partition.  Provide a toilet with a centerline that measures 18 inches from the near side wall.  Standards §§ 4.1.3(11), 4.1.6(1)(b), 4.22.4, 4.17.3, Fig. 30.

 

iii. The flush control is on the closed side of the stall.  Provide a flush control mounted on the "open" side of the toilet's clear floor space; 44 inches or less above the finished floor; and requiring a maximum of 5 pounds of force to operate; or provide an automatic flush device.  Standards §§ 4.1.3(11), 4.1.6(1)(b), 4.22.4, 4.16.5, 4.17.2, 4.27.4.

 

iv. The coat hook is inaccessible.  Provide a coat hook at a maximum height above the finished floor of 48 inches for a forward approach or 54 inches for a side approach and that is accompanied by clear floor space of 30 by 48 inches that allows a forward or parallel approach by a person using a wheelchair.  Standards §§ 4.1.3(12)(a), 4.1.6(1)(b), 4.25.2, 4.25.3, 4.2.4, 4.2.5, 4.2.6.

 

4.         The picnic shelter has a 1 ½ inch threshold.  Provide an accessible shelter with a threshold that is no greater than ¼ inch, or is no greater than ½ inch and is beveled with a slope no greater than 1:2.  Standards §§ 4.1.3(7)(a), 4.1.6(1)(b), 4.13.8, 4.5.2.

 

N.        Within three months of the effective date of this Agreement, the City will complete the following modifications to Pierce Park (101 Oak Avenue)

 

1.         There is no picnic table on an accessible route or configured to be usable by persons who use wheelchairs.  Provide at least one picnic table on an accessible route such that there is knee space at the table at least 27 inches high, 30 inches wide, and 19 inches deep, and such that the height of the top of the table is between 28 inches and 34 inches above the ground.  Standards §§ 4.1.3(18), 4.1.6(1)(b), 4.32.3, 4.32.4.

 

O.        Within three months of the effective date of this Agreement, the City will complete the following modifications to Sunrise Park (25 Sunrise Avenue)

 

1.         There is no transfer platform on an accessible route at any of the playground equipment.  Provide at least one accessible route to the end of the steps at wood playground assembly that, to the maximum extent feasible, coincides with the route for the general public.  The accessible route must have a minimum clear width of 36 inches, or a minimum clear width of 42 inches if there is a turn around an obstruction less than 48 inches wide; have passing spaces at least 60 inches by 60 inches at least every 200 feet; have a minimum clear headroom of 80 inches; have a surface that is firm, stable, and slip resistant; have, in the absence of a curb ramp, ramp, elevator, or platform lift, no level changes in excess of ½ inch vertically; and have a running slope of less than 1:20 (5%) (or have been constructed as a fully accessible ramp) and a cross slope of less than 1:50 (2%).  Standards §§ 4.1.3(1), 4.1.6(1)(b), 4.3, 4.5, Fig. 7.


 

            [1] The City represents that the Biltmore Hotel is on a long-term lease with a management company.   In addition to notifying the management company of these architectural violations, the City's notification will specify that the remediation be completed within one year of the effective date of this Agreement.  The City will simultaneously send a courtesy copy to the Department.