Attachment L: Access to Billings Programs Housed in Others’ Facilities

 

Access to City Programs Housed in Others’ Facilities: In order to ensure that the City’s programs, services, and activities that are the subject of this Agreement and that are operated by the City at facilities owned or controlled by other entities, when viewed in its entirety, are readily accessible to and usable by persons with mobility impairments, the City will implement and report to the Department its written plan regarding how the programs, activities, or services housed in the following facilities will be made accessible to persons with disabilities:

 

1.         GW Building, located at 2720 3rd Avenue North

 

            a.         Public Defender’s Office (Suite 240): The door requires 14 pounds of force to operate. Provide a door that requires no more than 5 pounds of force to open. Standards §§ 4.1.3(7)(b), 4.1.6(1)(b), 4.13.11(2)(b).

 

            b.         Offices - Generally: The office doors have round door knob hardware. Provide doors with hardware that is easy to grasp with one hand and that does not require tight grasping, pinching, or twisting of the wrist to operate. Lever-operated mechanisms, push-type mechanisms, and U-shaped handles are acceptable designs. Standards §§ 4.1.3(7)(b), 4.1.6(1)(b), 4.13.9.

 

            c.         Elevator

 

                        i.         The elevator call buttons are centered at 54 inches above the finished floor. Ensure that the call buttons are centered at 42 inches above the finished floor, a minimum of ¾ inch in the smallest dimension, with the button designating the up direction on top; that the call buttons are raised or flush; and that objects mounted beneath hall call buttons do not project into the elevator lobby more than 4 inches. Standards §§ 4.1.3(5), 4.1.6(1)(b), 4.10.3, Fig. 20.

 

                        ii.        No hoistway signage is provided. Provide signage at hoistway entrances with raised and Braille floor designations on both jambs such that the centerline of the characters is 60 inches above the finished floor and the characters are 2 inches high. Standards §§ 4.1.3(5), 4.1.6(1)(b), 4.10.5, Fig. 20.

 

                        iii.       Car Controls: Braille or raised characters are not provided to the left of the buttons, the main entry floor button is not designated by a star, visual button indicators are not provided, emergency controls are located at the top of the control panel, and the emergency alarm button is 61 inches above the finished floor. Provide car control buttons that are at least ¾ inch in their smallest dimension and are raised or flush and that are designated by Braille and by raised standard alphabet characters for letters, arabic characters for numerals, or standard symbols. Ensure that the call button for the main entry floor is designated by a raised star at the left of the floor designation; that all raised designations for control buttons are placed immediately to the left of the buttons to which they apply; that floor buttons are provided with visual indicators to show when each call is registered and are extinguished when each call is answered; that all floor buttons are no higher than 54 inches above the finished floor for a side approach and no more than 48 inches above the finished floor for a front approach; and that emergency controls, including the emergency alarm and emergency stop, are grouped at the bottom of the panel and have their centerlines no less than 35 inches above the finished floor. Standards §§ 4.1.3(5), 4.1.6(1)(b), 4.10.12, Fig. 23.

 

            d.         The Women’s single user toilet room contains a number of inaccessible elements and is not accessible to people with disabilities. Provide an accessible toilet room such that all of the room’s elements, including signage, door, door hardware, clear floor space, water closet, grab bars, lavatory, mirror, controls, and dispensers, comply with the Standards. Standards §§ 4.13, 4.16, 4.18, 4.19, 4.26, 4.27, 4.30, Figs. 28, 29.

 

            e.         The Men’s single user toilet room contains a number of inaccessible elements and is not accessible to people with disabilities. Provide an accessible toilet room such that all of the room’s elements, including signage, door, door hardware, clear floor space, water closet, urinal (if provided), grab bars, lavatory, mirror, controls, and dispensers, comply with the Standards. Standards §§ 4.13, 4.16, 4.18, 4.19, 4.26, 4.27, 4.30, Figs. 28, 29.