Attachment K: Program Access in Existing Facilities
Pursuant to Paragraph 40 of the Agreement, within three months of the effective date of the Agreement, the City will provide signage as necessary to comply with 28 C.F.R. § 35.163(b), after having surveyed all facilities that are the subject of this Agreement for the purpose of identifying those that have multiple entrances not all of which are accessible.
The technical requirements and, where appropriate, the scoping requirements of the Standards are used as a guide for determining whether a program or activity held in an existing facility is “readily accessible to and usable by” persons with disabilities and for determining what changes are necessary to make this program or activity accessible if it continues to be provided in the existing facility in question. See 28 C.F.R. §§ 35.150(b)(1), 35.151.
In order to ensure that each of the City’s programs, services, and activities operating at a facility that is the subject of this Agreement, when viewed in its entirety, are readily accessible to and usable by persons with mobility impairments, the City will take the following actions:
1. Within 24 months of the effective date of this Agreement, the City shall complete the following modifications to the City Hall:
a. Common Elements
i. The double-leaf entrance doors (exterior and interior) to the City Hall and Police Department are inaccessible because the automatic door openers are mounted on the doors. At each such location, provide automatic door openers that are positioned so that users will not be hit by the swing of the door. Standards § 4.13, Figs. 24, 25.
ii. Raised and Braille characters are not provided at doors to permanent rooms throughout the facility. Wherever permanent room signs are provided, provide accessible signage with raised and Braille characters at permanent rooms and spaces. Each such sign shall be mounted on the wall adjacent to the latch side of the door with the centerline of the sign at 60 inches above the finished floor and situated such that a person can approach within 3 inches of the sign without encountering an obstruction or standing within a door swing. Standards §§ 4.1.3(16)(d), 4.30.1, 4.30.4, 4.30.5, 4.30.6.
iii. Numerous interior doors throughout the facility have knob handles. Within 36 months, at each door used by the public, provide door hardware that is easy to grasp with one hand and that does not require tight grasping, pinching, or twisting of the wrist to operate. Lever-operated mechanisms, push-type mechanisms, and U-shaped handles are acceptable designs. Standards § 4.13.9.
iv. Numerous interior doors throughout the facility are inaccessible because the pressure required to open the doors is greater than 5 pounds. For each door used by the public, ensure that the door requires no more than 5 pounds of force to open. Standards § 4.13.11(2)(b).
v. Numerous service counters, gun lockers, and other elements throughout the facility are protruding objects that are not cane-detectable. Provide an accessible route at each such location such that no objects with their bottom leading edges measuring between 27 inches and 80 inches above the finished floor protrude more than 4 inches into walks, halls, corridors, passageways, or aisles. Free-standing objects mounted on posts or pylons may overhang 12 inches maximum from 27 inches to 80 inches above the ground or finished floor. Standards § 4.4.
vi. Although the facility contains an emergency alarm system, the alarm system is inaccessible because audible alarms are not provided in all meeting rooms where visual alarms are installed. Provide visual alarm devices in toilet rooms and any other general usage areas (e.g., meeting rooms), hallways, lobbies, and any other area for common use. Such devices shall be integrated into the facility alarm system and shall meet the requirements of the Standards for lamp type, color, pulse duration, intensity, and flash rate. Visual alarm appliances shall be placed 80 inches above the highest floor level within the space or 6 inches below the ceiling, whichever is lower. Visual alarm appliances shall be located such that no place in any room or space, including common corridors or hallways, required to have a visual alarm appliance shall be more than 50 feet from the signal. In large rooms and spaces exceeding 100 feet across, without obstructions 6 feet above the finished floor, devices may be placed around the perimeter, spaced a maximum of 100 feet apart, in lieu of suspending appliances from the ceiling. Standards § 4.28.3.
b. City Hall Police and City Court
i. Lift at Interior Entrance to Police Department: The lift located at the entrance to the Police Department is inaccessible because the lift was turned off, the key was difficult to locate, there was no buzzer or signage with lift instructions, and the staff was unaware of proper operation. Provide a lift at this location that facilitates unassisted entry, operation, and exit from the lift. Standards § 4.11.3.
ii. Elevator
(1) The elevator is inaccessible because the main entry floor call button is not designated by raised star. Provide car control buttons that are at least ¾ inch in their smallest dimension and are raised or flush and that are designated by Braille and by raised standard alphabet characters for letters, arabic characters for numerals, or standard symbols. Ensure that the call button for the main entry floor is designated by a raised star at the left of the floor designation; that all raised designations for control buttons are placed immediately to the left of the buttons to which they apply; that floor buttons are provided with visual indicators to show when each call is registered and are extinguished when each call is answered; that all floor buttons are no higher than 54 inches above the finished floor for a side approach and no more than 48 inches above the finished floor for a front approach; and that emergency controls, including the emergency alarm and emergency stop, are grouped at the bottom of the panel and have their centerlines no less than 35 inches above the finished floor. Standards § 4.10.12, Fig. 23.
(2) The elevator is inaccessible because car position does not ring as car passes or stops on floors. Provide visual car position indicators above the car control panel or over the door to show the position of the elevator in the hoistway. Ensure that indicators emit an audible and visual signal as the car passes or stops at a floor served by the elevator, with the corresponding floor designation being illuminated; and that numerals are a minimum of ½ inch high. Standards § 4.10.13.
(3) The elevator is inaccessible because, although emergency communications are provided, the system does not work without voice communication. Provide a two-way communication system such that it does not require voice communication, the highest operable part is a maximum of 48 inches above the finished floor of the car, and it is identified by a raised symbol and lettering located adjacent to the device. If the system uses a handset, ensure that the length of the cord from the panel to the handset is at least 29 inches. If the system is located in a closed compartment, ensure that the compartment door hardware operates without tight grasping, pinching or twisting of the wrist. Standards § 4.10.14.
iii. City Court on Second Floor
(1) The metal detector has an opening width of only 29 inches. Provide an entrance to the court with a clear opening of 32 inches. Standards § 4.13.5, Fig. 24.
(2) There is no assistive listening system installed and there are not portable listening systems available. Provide a permanently installed assistive listening system (ALS) or a portable ALS with an adequate number of electrical outlets or other supplementary wiring necessary to support a portable assistive listening system. Also provide 4% of total seats or a minimum of 2 receivers for use by the general public and signage indicating their availability. Standards §§ 4.30, 4.33.
(3) The jury box is inaccessible because there is an 8 inch step up to the jury box. Install a ramp or platform lift in compliance with the Standards or establish a procedure for providing access to this area. Any procedure shall not require lifting or carrying persons with mobility impairments or require them to traverse unnecessary or extreme distances. Standards §§ 4.33.5, 4.3.8, 4.8, 4.11.
iv. Women’s Toilet Room with Stalls Near City Hall Administrative Offices: In the toilet stall for persons with disabilities, the toilet seat cover dispenser is inaccessible because it is mounted above the back grab bar over the toilet and require a forward reach above the toilet. Provide a seat cover dispenser such that the controls comply with Fig. 5 for a forward reach or with Fig. 6 for a side reach and such that it is accompanied by clear floor space of 30 by 48 inches that allows a forward or parallel approach, respectively, by a person using a wheelchair. Standards §§ 4.1.3(13), 4.27.2, 4.27.3, 4.2.4, 4.2.5, 4.2.6.
v. Men’s Toilet Room with Stalls Near City Hall Administrative Offices: In the toilet stall for persons with disabilities, the toilet seat cover dispenser is inaccessible because the controls are mounted above the back grab bar over the toilet and require a forward reach above the toilet. Provide a seat cover dispenser such that the controls comply with Fig. 5 for a forward reach or with Fig. 6 for a side reach and such that it is accompanied by clear floor space of 30 by 48 inches that allows a forward or parallel approach, respectively, by a person using a wheelchair. Standards §§ 4.1.3(13), 4.27.2, 4.27.3, 4.2.4, 4.2.5, 4.2.6.
vi. Women’s Toilet Room with Stalls Near City Court
(1) The toilet room sign is mounted with the centerline at 54 inches above the finished floor. Provide a toilet room sign with raised and Braille characters. The sign shall be mounted on the wall adjacent to the latch side of the door with the centerline of the sign at 60 inches above the finished floor and situated such that a person can approach within 3 inches of the sign without encountering an obstruction or standing within a door swing. Standards §§ 4.1.2(7)(d), 4.30.1, 4.30.4, 4.30.5, 4.30.6.
(2) In the toilet stall for persons with disabilities, the toilet seat cover dispenser is inaccessible because the controls are mounted above the rear grab bar. Provide a toilet paper seat cover dispenser such that the controls comply with Fig. 5 for a forward reach or with Fig. 6 for a side reach and such that it is accompanied by clear floor space of 30 by 48 inches that allows a forward or parallel approach, respectively, by a person using a wheelchair. Standards §§ 4.27.2, 4.27.3, 4.2.4, 4.2.5, 4.2.6.
(3) The tampon dispenser is inaccessible because it requires grasping, pinching, or wrist-twisting to operate. Provide a tampon dispenser with mechanical controls, if any, that can be operated with 5 lbf or less and that can be used with one hand and without tight grasping, pinching, or twisting of the wrist (lever-operated, push-type, and electronically controlled mechanisms are examples of acceptable designs). Standards § 4.27.4.
vii. Men’s Single User Toilet Room Near City Court
(1) The lavatory counter is a protruding object that is not cane-detectable. Provide an accessible route at this location such that no objects with their bottom leading edges measuring between 27 inches and 80 inches above the finished floor protrude more than 4 inches into walks, halls, corridors, passageways, or aisles. Free-standing objects mounted on posts or pylons may overhang 12 inches maximum from 27 inches to 80 inches above the ground or finished floor. Standards § 4.4.
(2) The toilet is inaccessible because the flush control is on the closed side. Provide a flush control mounted on the “open” side of the toilet’s clear floor space; 44 inches or less above the finished floor; and requiring a maximum of 5 pounds of force to operate; or provide an automatic flush device. Standards §§ 4.16.5, 4.17.2, 4.27.4.
(3) The toilet seat cover is inaccessible because the controls are mounted above the rear grab bar over the toilet and requires a forward reach over the toilet. Provide a toilet seat cover dispenser such that the controls comply with Fig. 5 for a forward reach or with Fig. 6 for a side reach and such that it is accompanied by clear floor space of 30 by 48 inches that allows a forward or parallel approach, respectively, by a person using a wheelchair. Standards §§ 4.27.2, 4.27.3, 4.2.4, 4.2.5, 4.2.6.
viii. Drinking Fountains: The drinking fountain under the 1940 dedication sign is inaccessible because the fountain is not detectable to a blind person using a cane. Provide an accessible route at this location such that no objects with their bottom leading edges measuring between 27 inches and 80 inches above the finished floor protrude more than 4 inches into walks, halls, corridors, passageways, or aisles. Free-standing objects mounted on posts or pylons may overhang 12 inches maximum from 27 inches to 80 inches above the ground or finished floor. Standards § 4.4.
2. Within 24 months of the effective date of this Agreement, the City shall complete the following modifications to the Park 3 Parking Garage:
a. Parking: Some of the parking spaces reserved for persons with disabilities are narrower than 96 inches or their vertical signs are too low, and none of the “van accessible” spaces are served by access aisles that are 96 inches or wider. On the shortest accessible route to the accessible entrance, provide at least 1 van accessible space and 6 standard spaces designated as reserved for people with disabilities. Ensure that standard accessible spaces are a minimum of 96 inches wide and served by access aisles at least 60 inches wide. Ensure that van accessible spaces are a minimum of 96 inches wide and served by access aisles at least 96 inches wide. At all spaces designated as reserved for persons with disabilities, provide vertical signs with the International Symbol of Accessibility located such that they cannot be obstructed by parked vehicles. At van accessible spaces, provide an additional “Van-Accessible” sign located below the International Symbol of Accessibility. Ensure that all spaces and access aisles for persons with disabilities are flat and level, with slopes and cross-slopes not exceeding 1:50 in all directions, and that their surfaces are firm, stable, and slip-resistant. Standards §§ 4.1.2(5), 4.6, 4.30.7(1).
b. The ramp located on level 2 of the Park 3 parking garage is inaccessible because its handrails do not extend past the top and bottom of the ramp. Provide handrails that are between 1¼ inches and 1½ inches in diameter such that the inside handrail is continuous and both handrails have a continuous gripping surface along both sides of the ramp extending at least 12 inches beyond the top and bottom of the ramp parallel with the ground surface; the handrails do not rotate within their fittings; and both handrails are mounted between 34 inches and 38 inches above the ramp surface, with ends rounded or returned smoothly to the floor, wall, or post. Standards § 4.8.5.
c. Entrances: There is no directional signage at accessible and inaccessible entrances. Provide accessible directional signage with the International Symbol of Accessibility at inaccessible entrances directing users to the accessible entrance, and provide accessible signage with the International Symbol of Accessibility at all permanent accessible entrances. Standards §§ 4.1.3(8)(d), 4.13, 4.30.
3. Within six months of the effective date of this Agreement, the City shall submit for the Department’s review and approval, a written plan for providing access for persons with disabilities to the programs currently held at North Park, Hawthorne Park, Pioneer Park, Veteran’s Park, Highland Park and Sprayground, Rose Park, Westwood Park, and Athletic Park/Cobb Stadium. Such plan shall not unnecessarily segregate persons with disabilities.
4. Within 24 months of the effective date of this Agreement, the City shall complete the following modifications to the Park 2 Parking Garage:
a. Parking
i. Although there are parking spaces designated as “van accessible,” the access aisles serving these spaces are less than 96 inches. Provide designated van accessible parking spaces that are a minimum of 96 inches wide and served by access aisles at least 96 inches wide. Standards §§ 4.1.2(5)(b), 4.6.3, Fig.9.
ii. The parking space on level 2 that is designated as “van accessible” is not level. Provide designated accessible parking spaces and access aisles that are flat and level, with slopes and cross-slopes not exceeding 1:50 in all directions, with surfaces that are firm, stable, and slip-resistant. Standards §§ 4.3.6, 4.5.1, 4.6.3.
b. Elevator
i. The elevator is inaccessible because no hoistway signage is provided. Provide signage at hoistway entrances with raised and Braille floor designations on both jambs such that the centerline of the characters is 60 inches above the finished floor and the characters are 2 inches high. Standards § 4.10.5, Fig. 20.
ii. The elevator is inaccessible because Braille is not provided at the call buttons and the main entry floor call button is not designated by a raised star. Provide car control buttons that are at least ¾ inch in their smallest dimension and are raised or flush and that are designated by Braille and by raised standard alphabet characters for letters, arabic characters for numerals, or standard symbols. Ensure that the call button for the main entry floor is designated by a raised star at the left of the floor designation; that all raised designations for control buttons are placed immediately to the left of the buttons to which they apply; that floor buttons are provided with visual indicators to show when each call is registered and are extinguished when each call is answered; that all floor buttons are no higher than 54 inches above the finished floor for a side approach and no more than 48 inches above the finished floor for a front approach; and that emergency controls, including the emergency alarm and emergency stop, are grouped at the bottom of the panel and have their centerlines no less than 35 inches above the finished floor. Standards § 4.10.12, Fig. 23.
5. Within 24 months of the effective date of this Agreement, the City shall complete the following modifications to the City Library:
a. Telephone on First Level of Library: The telephone is inaccessible because the coin slot is 63 inches above the finished floor. Provide an accessible telephone with a clear floor space of at least 30 inches by 48 inches that allows either a forward or parallel approach by a person using a wheelchair such that bases, enclosures, and fixed seats do not impede approaches to the telephone; with the highest operable part of the telephone mounted no more than 48 inches above the floor for a front approach or no more than 54 inches above the floor for a side approach; that is hearing aid compatible and has a volume control mechanism; with telephone books, if provided, located between 15 and 48 inches above the finished floor for a front approach or between 9 and 54 inches above the finished floor for a side approach; with a cord of at least 29 inches long from the telephone to the handset; and with signage that complies with the Standards. Standards §§ 4.31, 4.30.7(2).
b. Meeting Rooms Throughout the Facility: Despite having several meeting and conference rooms, there is no permanently installed or portable assistive listening system provided. Provide a permanently installed assistive listening system (ALS) in each meeting or conference room or a portable ALS with an adequate number of electrical outlets or other supplementary wiring necessary to support a portable assistive listening system. Also provide a minimum of 2 receivers for use by the general public and signage in each meeting or conference room indicating their availability. Standards §§ 4.30, 4.33.
c. Women’s Toilet Room with Stalls; First Level of Library
i. The toilet room sign is mounted on the door, there is no International Symbol of Accessibility, and no raised and Braille characters. Provide a toilet room sign with the International Symbol of Accessibility and raised and Braille characters. The sign shall be mounted on the wall adjacent to the latch side of the door with the centerline of the sign at 60 inches above the finished floor and situated such that a person can approach within 3 inches of the sign without encountering an obstruction or standing within a door swing. Standards §§ 4.1.2(7)(d), 4.30.1, 4.30.4, 4.30.5, 4.30.6, 4.30.7.
ii. The door is inaccessible because the pressure required to open the door is 15 pounds. Provide a door that requires no more than 5 pounds of force to open. Standards § 4.13.11(2)(b).
iii. The door is inaccessible because knob hardware is used and a standard key is required to unlock the door. Provide a door with hardware that is easy to grasp with one hand and that does not require tight grasping, pinching, or twisting of the wrist to operate. Lever-operated mechanisms, push-type mechanisms, and U-shaped handles are acceptable designs. Standards § 4.13.9.
iv. The door to the toilet room, which is accessed through a front approach, is inaccessible because the pull side clearance is less than 18 inches. On the pull side of the door, provide maneuvering clearance at least 60 inches deep and provide a minimum of 18 inches (24 inches is preferred) of maneuvering clearance on the latch side of the door. Standards § 4.13.6, Fig. 25(a).
v. The bottom edge of the lavatory apron is 26 inches above the finished floor. Provide a lavatory with the top of its rim or counter 34 inches or less above the finished floor; the bottom edge of the apron at least 29 inches above the finished floor; and knee and toe clearances that comply with Fig. 31. Standards § 4.19.2, Fig. 31.
vi. The lavatory is inaccessible because the hot water pipes are not insulated or otherwise configured to protect against contact. Provide hot water and drain pipes that are insulated or otherwise configured to protect against contact. Standards § 4.19.4.
vii. The paper towel dispensers are protruding objects and would not be detectable to a blind person using a cane. Provide an accessible route at this location such that no objects with their bottom leading edges measuring between 27 inches and 80 inches above the finished floor protrude more than 4 inches into walks, halls, corridors, passageways, or aisles. Free-standing objects mounted on posts or pylons may overhang 12 inches maximum from 27 inches to 80 inches above the ground or finished floor. Standards § 4.4.
viii. Toilet Stall for Persons with Disabilities: Although 1 toilet stall has some elements intended for use by persons with disabilities, there is no toilet stall that is accessible to persons who use wheelchairs. Provide a “standard” accessible toilet stall at least 60 inches wide and at least 59 inches deep (or at least 56 inches deep with a wall-mounted toilet) such that all of the stall’s elements, including stall door, stall door hardware, water closet, size and arrangement, toe clearances, grab bars, controls, and dispensers, comply with the Standards. Standards §§ 4.13, 4.16, 4.17, 4.26, 4.27, Fig. 30.
d. Men’s Toilet Room with Stalls
i. The toilet room sign is mounted on the door, there is no International Symbol of Accessibility, and no raised and Braille characters. Provide a toilet room sign with the International Symbol of Accessibility and raised and Braille characters. The sign shall be mounted on the wall adjacent to the latch side of the door with the centerline of the sign at 60 inches above the finished floor and situated such that a person can approach within 3 inches of the sign without encountering an obstruction or standing within a door swing. Standards §§ 4.1.2(7)(d), 4.30.1, 4.30.4, 4.30.5, 4.30.6, 4.30.7.
ii. The door is inaccessible because the pressure required to open the door is 10 pounds. Provide a door that requires no more than 5 pounds of force to open. Standards § 4.13.11(2)(b).
iii. The door is inaccessible because knob hardware is used and a standard key is required to unlock the door. Provide a door with hardware that is easy to grasp with one hand and that does not require tight grasping, pinching, or twisting of the wrist to operate. Lever-operated mechanisms, push-type mechanisms, and U-shaped handles are acceptable designs. Standards § 4.13.9.
iv. The bottom edge of the lavatory apron is 26 inches above the finished floor. Provide a lavatory with the top of its rim or counter 34 inches or less above the finished floor; the bottom edge of the apron at least 29 inches above the finished floor; and knee and toe clearances that comply with Fig. 31. Standards § 4.19.2, Fig. 31.
v. The lavatory is inaccessible because the hot water pipes are not insulated or otherwise configured to protect against contact. Provide hot water and drain pipes that are insulated or otherwise configured to protect against contact. Standards § 4.19.4.
vi. Toilet Stall for Persons with Disabilities: Although 1 toilet stall has some elements intended for use by persons with disabilities, there is no toilet stall that is accessible to persons who use wheelchairs. Provide a “standard” accessible toilet stall at least 60 inches wide and at least 59 inches deep (or at least 56 inches deep with a wall-mounted toilet) such that all of the stall’s elements, including stall door, stall door hardware, water closet, size and arrangement, toe clearances, grab bars, controls, and dispensers, comply with the Standards. Standards §§ 4.13, 4.16, 4.17, 4.26, 4.27, Fig. 30.
e. Girls’ Toilet Room
i. There is no signage directing people with disabilities to the accessible toilet rooms. Provide accessible directional signage with the International Symbol of Accessibility at inaccessible toilet rooms indicating the location of the nearest accessible toilet room, and provide accessible signage with the International Symbol of Accessibility at all accessible toilet rooms. Standards §§ 4.1.2(7)(d), 4.1.6(3)(e)(iii), 4.30.1, 4.30.2, 4.30.3, 4.30.5, 4.30.7.
f. Boys’ Toilet Room
i. There is no signage directing people with disabilities to the accessible toilet rooms. Provide accessible directional signage with the International Symbol of Accessibility at inaccessible toilet rooms indicating the location of the nearest accessible toilet room, and provide accessible signage with the International Symbol of Accessibility at all accessible toilet rooms. Standards §§ 4.1.2(7)(d), 4.1.6(3)(e)(iii), 4.30.1, 4.30.2, 4.30.3, 4.30.5, 4.30.7.
g. Elevator 1 (Between 1st and 2nd levels)
i. The elevator is inaccessible because the hall call buttons are centered at 59 inches above the finished floor and there is no visual signal to indicate when a call is registered or answered. Provide hall (lobby) call buttons with visual signals indicating when each call is registered and when each call is answered. Ensure that the call buttons are centered at 42 inches above the finished floor, a minimum of ¾ inch in the smallest dimension, with the button designating the up direction on top; that the call buttons are raised or flush; and that objects mounted beneath hall call buttons do not project into the elevator lobby more than 4 inches. Standards § 4.10.3, Fig. 20.
ii. The elevator is inaccessible because a position indicator does not ring as the car passes or stops on floors. Provide visual car position indicators above the car control panel or over the door to show the position of the elevator in the hoistway. Ensure that indicators emit an audible and visual signal as the car passes or stops at a floor served by the elevator, with the corresponding floor designation being illuminated; and that numerals are a minimum of ½ inch high. Standards § 4.10.13.
iii. The elevator is inaccessible because hoistway signage is not provided. Provide signage at hoistway entrances with raised and Braille floor designations on both jambs such that the centerline of the characters is 60 inches above the finished floor and the characters are 2 inches high. Standards § 4.10.5, Fig. 20.
iv. The car control buttons do not have Braille and visual indicators and the main entry floor call button does not have a raised star. Provide car control buttons that are at least ¾ inch in their smallest dimension and are raised or flush and that are designated by Braille and by raised standard alphabet characters for letters, arabic characters for numerals, or standard symbols. Ensure that the call button for the main entry floor is designated by a raised star at the left of the floor designation; that all raised designations for control buttons are placed immediately to the left of the buttons to which they apply; that floor buttons are provided with visual indicators to show when each call is registered and are extinguished when each call is answered; that all floor buttons are no higher than 54 inches above the finished floor for a side approach and no more than 48 inches above the finished floor for a front approach; and that emergency controls, including the emergency alarm and emergency stop, are grouped at the bottom of the panel and have their centerlines no less than 35 inches above the finished floor. Standards § 4.10.12, Fig. 23.
v. The emergency communications system is not marked by raised symbol or lettering and a silent test call revealed that the operator did not know how to respond appropriately to a silent call, indicating that the system does not work without voice communication. Provide a two-way communication system such that it does not require voice communication, the highest operable part is a maximum of 48 inches above the finished floor of the car, and it is identified by a raised symbol and lettering located adjacent to the device. If the system uses a handset, ensure that the length of the cord from the panel to the handset is at least 29 inches. If the system is located in a closed compartment, ensure that the compartment door hardware operates without tight grasping, pinching or twisting of the wrist. Standards § 4.10.14.
6. Within 24 months of the effective date of this Agreement, the City shall complete the following modifications to Fire Station # 1:
a. Parking: The signage designating parking as reserved for persons with disabilities is too low and the pavement markings lack adequate demarcation. At each space designated as reserved for persons with disabilities, provide a vertical sign with the International Symbol of Accessibility located such that it cannot be obstructed by vehicles parked in the space. Standards §§ 4.6.4, 4.30.7(1).
b. Entrances
i. There is no signage with the International Symbol of Accessibility indicating the accessible entrances or directional signage at inaccessible entrances pointing to the accessible entrances. Provide accessible directional signage with the International Symbol of Accessibility at inaccessible entrances directing users to the accessible entrance, and provide accessible signage with the International Symbol of Accessibility at all permanent accessible entrances. Standards §§ 4.1.3(8)(d), 4.13, 4.30.
c. Women’s Toilet Room with Stalls (Basement)
i. The toilet room sign is mounted on the door, there is no International Symbol of Accessibility, and no raised and Braille characters. Provide a toilet room sign with the International Symbol of Accessibility and raised and Braille characters. The sign shall be mounted on the wall adjacent to the latch side of the door with the centerline of the sign at 60 inches above the finished floor and situated such that a person can approach within 3 inches of the sign without encountering an obstruction or standing within a door swing. Standards §§ 4.1.2(7)(d), 4.30.1, 4.30.4, 4.30.5, 4.30.6, 4.30.7.
ii. The door is inaccessible because the pressure required to open the door is 11 pounds. Provide a door that requires no more than 5 pounds of force to open. Standards § 4.13.11(2)(b).
iii. The lavatory is inaccessible because the hot water pipes are not insulated or otherwise configured to protect against contact. Provide hot water and drain pipes that are insulated or otherwise configured to protect against contact. Standards § 4.19.4.
iv. The paper towel dispenser controls requires tight grasping, pinching or twisting of the wrist to advance the towels for use. Provide a paper towel dispenser with mechanical controls, if any, that can be operated with 5 lbf or less and that can be used with one hand and without tight grasping, pinching, or twisting of the wrist (lever-operated, push-type, and electronically controlled mechanisms are examples of acceptable designs). Standards § 4.27.4.
v. The paper towel dispenser is a protruding object and would not detectable to a blind person using a cane. Provide an accessible route at this location such that no objects with their bottom leading edges measuring between 27 inches and 80 inches above the finished floor protrude more than 4 inches into walks, halls, corridors, passageways, or aisles. Free-standing objects mounted on posts or pylons may overhang 12 inches maximum from 27 inches to 80 inches above the ground or finished floor. Standards § 4.4.
vi. Although 1 toilet stall has some elements intended for use by persons with disabilities, there is no toilet stall that is accessible to persons who use wheelchairs. Within 36 months, provide a “standard” accessible toilet stall at least 60 inches wide and at least 59 inches deep (or at least 56 inches deep with a wall-mounted toilet) such that all of the stall’s elements, including stall door, stall door hardware, water closet, size and arrangement, toe clearances, grab bars, controls, and dispensers, comply with the Standards. Standards §§ 4.13, 4.16, 4.17, 4.26, 4.27, Fig. 30.
d. Men’s Toilet Room with Stalls (Basement)
i. The toilet room sign is mounted on the door, there is no International Symbol of Accessibility, and no raised and Braille characters. Provide a toilet room sign with the International Symbol of Accessibility and raised and Braille characters. The sign shall be mounted on the wall adjacent to the latch side of the door with the centerline of the sign at 60 inches above the finished floor and situated such that a person can approach within 3 inches of the sign without encountering an obstruction or standing within a door swing. Standards §§ 4.1.2(7)(d), 4.30.1, 4.30.4, 4.30.5, 4.30.6, 4.30.7.
ii. The door is inaccessible because the pressure required to open the door is 10 pounds. Provide a door that requires no more than 5 pounds of force to open. Standards § 4.13.11(2)(b).
iii. The lavatory is inaccessible because the hot water pipes are not insulated or otherwise configured to protect against contact. Provide hot water and drain pipes that are insulated or otherwise configured to protect against contact. Standards § 4.19.4.
iv. The paper towel dispenser is a protruding object and would not detectable to a blind person using a cane. Provide an accessible route at this location such that no objects with their bottom leading edges measuring between 27 inches and 80 inches above the finished floor protrude more than 4 inches into walks, halls, corridors, passageways, or aisles. Free-standing objects mounted on posts or pylons may overhang 12 inches maximum from 27 inches to 80 inches above the ground or finished floor. Standards § 4.4.
v. The paper towel dispenser controls requires tight grasping, pinching or twisting of the wrist to advance the towels for use. Provide a paper towel dispenser with mechanical controls, if any, that can be operated with 5 lbf or less and that can be used with one hand and without tight grasping, pinching, or twisting of the wrist (lever-operated, push-type, and electronically controlled mechanisms are examples of acceptable designs). Standards § 4.27.4.
vi. Although 1 toilet stall has some elements intended for use by persons with disabilities, there is no toilet stall that is accessible to persons who use wheelchairs. Within 36 months, provide a “standard” accessible toilet stall at least 60 inches wide and at least 59 inches deep (or at least 56 inches deep with a wall-mounted toilet) such that all of the stall’s elements, including stall door, stall door hardware, water closet, size and arrangement, toe clearances, grab bars, controls, and dispensers, comply with the Standards. Standards §§ 4.13, 4.16, 4.17, 4.26, 4.27, Fig. 30.
e. Women’s Toilet Room near Lobby (Main Level)
i. There is no signage directing people with disabilities to the accessible toilet rooms. Provide accessible directional signage with the International Symbol of Accessibility at inaccessible toilet rooms indicating the location of the nearest accessible toilet room, and provide accessible signage with the International Symbol of Accessibility at all accessible toilet rooms. Standards §§ 4.1.2(7)(d), 4.1.6(3)(e)(iii), 4.30.1, 4.30.2, 4.30.3, 4.30.5, 4.30.7.
f. Men’s Toilet Room near Lobby (Main Level)
i. There is no signage directing people with disabilities to the accessible toilet rooms. Provide accessible directional signage with the International Symbol of Accessibility at inaccessible toilet rooms indicating the location of the nearest accessible toilet room, and provide accessible signage with the International Symbol of Accessibility at all accessible toilet rooms. Standards §§ 4.1.2(7)(d), 4.1.6(3)(e)(iii), 4.30.1, 4.30.2, 4.30.3, 4.30.5, 4.30.7.
g. Elevator
i. The elevator is inaccessible because the hoistway signage lacks raised characters and Braille. Provide signage at hoistway entrances with raised and Braille floor designations on both jambs such that the centerline of the characters is 60 inches above the finished floor and the characters are 2 inches high. Standards § 4.10.5, Fig. 20.
7. Within 24 months of the effective date of this Agreement, the City shall complete the following modifications to the Utility Services Center:
a. Parking: There are no demarcated access aisles serving the parking spaces designated as reserved for persons with disabilities. At each standard accessible space, provide an access aisle at least 60 inches wide. At each van accessible space, provide an access aisles at least 96 inches wide. Ensure that all access aisles are flat and level, with slopes and cross-slopes not exceeding 1:50 in all directions, and that their surfaces are firm, stable, and slip-resistant. Standards §§ 4.1.2(5), 4.6.3, Fig. 9.